EXP. 1: Electric Power Measurement AIM The aim of this experiment is to understand the principle of electric power and the method of power measurement. In this experiment, you will learn how to measure power and power factor, and examine the power concept of single- and three-phase load. Finally you need to determine the relations between the voltage and current phasors and the power, and the solution for power-factor improvement. INTRODUCTION The measurement of power in a DC circuit can be carried out by simultaneous measurements of voltage and current by using standard types of dc voltmeters and ammeters. The product of the readings typically gives a sufficiently accurate measure of dc power. If great accuracy is required, corrections for the power used by the instruments should be made. In AC circuits the phase difference between the voltage and current precludes use of the voltmeter-ammeter method unless the load is known to be purely resistive. When this method is applicable, the instrument readings lead directly to average power if the ac voltmeters and ammeters are capable of measuring rms (root mean square) values. The potential difference in volts between two points is equal to the energy per unit charge (in joules/coulomb) which is required to move electric charge between the points. Since the electric current measures the charge per unit time (in coulombs/second), the electric power P is given by the product of the current i and the voltage v ( joules/second = watts), as in Eq. (1). P vi (1) Alternate forms of the basic definition can be obtained by using Ohm's law, which states that the voltage across a pure resistance is proportional to the current through the element. This results in Eq. (2), P i2R v2 R (2) where R is the resistance, i is the current through and v is the voltage across the resistive element. Other commonly used units for electromechanical systems is horsepower (1 hp = 746 W). These fundamental expressions yield the instantaneous power as a function of time. In the DC case where v and i are each constant, the instantaneous power is also constant. In all other cases where v or i or both are time-varying, the instantaneous power is also time-varying. When the voltage and current are periodic with the same fundamental frequency, the instantaneous power is also periodic with twice the fundamental frequency. In this case a much more significant quantity is the average power, since in most cases the electric power is converted to some other physical 3315ENG Efficient Energy System 1/8 form such as heat, mechanical power, or light. The rapid fluctuations of the power are smoothed by the thermal or mechanical inertia of the output system. There are three major power equations relating the three types of power to resistance, reactance, and impedance (all use scalar quantities): Figure 1: The three types of power to resistance, reactance, and impedance. The following terms are used to describe energy flow in a system (and assign each of them a different unit to differentiate between them): Real power (P) or active power: watt [W] Reactive power (Q): volt-ampere reactive [Var] Complex power (S): volt-ampere [VA] Apparent Power (|S|): The absolute value of the complex power S Phase of Current (φ): The angle of difference (in degrees) between voltage and current; Current lagging Voltage (Quadrant I Vector), Current leading voltage (Quadrant IV Vector) In Figure 2, P is the real power, Q is the reactive power (in this case positive), S is the complex power and the length of S is the apparent power. Reactive power does not transfer energy, so it is represented as the imaginary axis of the vector diagram. Real power moves energy, so it is the real axis. 3315ENG Efficient Energy System 2/8 Figure 2: The apparent power is the vector sum of real and reactive power. EQUIPMENT Digital Power Meter: WT210 Load: Light bulbs, varactor (Auto-transformer), single phase motor, three phase motor. LCR meter EXPERIMENT Step 1: Connect the light bulbs to the digital power meter and ask Lab demonstrator to check the circuit connection before start your power measurement. Record all you findings (voltage, current, different types of power, power factor), by conducting the three measurements (one light bulb, the other light bulb, both light bulbs) and compare the results with your calculation results. Step 2: Repeat the measurements with the varactor connected in series with the light bulbs, by choosing 50% and 100% of the varactor value. Step 3: Calculate the values X and R for: one light bulb, the other light bulb, both light bulbs, with and without the varactor in series. Record the values in a table (leave some space on the right side for comparisons). Step 4: Set the varactor to 0 and calculate the capacitor value to achieve a power factor improvement 1 and enter the values into Figure 9. Step 5: Connect the two 1-phase motors to the power meter and repeat the measurements. Step 6: Compare the findings of the motors, to each other, the type plate and to the measurements from Step 2. Describe if the motors are resistive, reactive, complex…. 3315ENG Efficient Energy System 3/8 1. 3-Phase motor power measurements In a 3-phase and 3-wire system, the active power supplied to a 3-phase load may be measured by two single-phase power meter connected as shown in Figure 3. The total power is equal to the sum of the two power meter readings. For balanced loads, if the power factor is less than 100 percent, the instruments will give different readings. Indeed, if the power factor is less than 50 percent, one of the power meters will give a negative reading. In this case, the power of the 3-phase circuit is equal to the difference between the two power meter readings. The two-power meter method gives the active power absorbed whether the load is balanced or unbalanced. The following equations can be used to calculate three phase power and angle. Figure 3: 3-phase power measurement using two single-phase power meter Apparent power supplied to the motor is S 3VI (3) Active power supplied to the motor is P P1 P3 cos P / S (4) Step 7: Conduct power measurements with the three phase motor (Figure 3) and compare the findings with the type plate. How is the motor connected (star or delta)? 2. Power factor and angle The angle of this “power triangle” as shown in Figure 2, graphically indicates the ratio between the amount of dissipated (or consumed) power and the amount of absorbed/returned power. It also happens to be the same angle as that of the circuit's impedance in polar form. When expressed as a fraction, this ratio between true power and apparent power is called the power factor for this circuit. Because true power and apparent power form the adjacent and hypotenuse sides of a right triangle, respectively, the power factor ratio is also equal to the cosine of that phase angle. 3315ENG Efficient Energy System 4/8 The ratio between real power and apparent power in a circuit is called the power factor. It's a practical measurement of the efficiency of a power distribution system. For two systems transmitting the same amount of real power, the system with the lower power factor will have higher circulating currents due to energy that returns to the source from energy storage in the load. These higher currents produce higher losses and reduce overall transmission efficiency. A lower power factor circuit will have a higher apparent power and higher losses for the same amount of real power. The power factor is 1 when the voltage and current are in phase. It is zero when the current leads or lags the voltage by 90 degrees. Power factors are usually stated as "leading" or "lagging" to show the sign of the phase angle, where leading indicates a negative sign. Purely capacitive circuits cause reactive power with the current waveform leading the voltage wave by 90 degrees, while purely inductive circuits cause reactive power with the current waveform lagging the voltage waveform by 90 degrees. The result of this is that capacitive and inductive circuit elements tend to cancel each other out. Example: Power factor improvement. Figure 4 shows an example of power factor improvement. Figure 4: Power factor improvement. The power factor without parallel capacitor can be calculated as follow: 3315ENG Efficient Energy System 5/8 Figure 5: Power factor calculation Parallel capacitor corrects lagging power factor of inductive load, therefore the apparent power can be reduced, as shown in Fig. 9. Figure 6: Power factor correction. Since we know that the (uncorrected) reactive power is 119.998 VAR (inductive), we need to calculate the correct capacitor size to produce the same quantity of (capacitive) reactive power. Since this capacitor will be directly in parallel with the source (of known voltage), we'll use the power formula which starts from voltage and reactance: Figure 7: Calculation of Capacitor. The power factor for the circuit, overall, has been substantially improved. The main current has been decreased from 1.41 amps to 994.7 milliamps, while the power 3315ENG Efficient Energy System 6/8 dissipated at the load resistor remains unchanged at 119.365 watts. The power factor is much closer to being 1: Figure 8: Power factor improvement 3. Recommendation of power factor improvement Reactive power flow on the alternating current transmission system is needed to support the transfer of real power over the network. In alternating current circuits energy is stored temporarily in inductive and capacitive elements, which can result in the periodic reversal of the direction of energy flow. The portion of power flow remaining after being averaged over a complete AC waveform is the real power, which is energy that can be used to do work (for example overcome friction in a motor, or heat an element). On the other hand the portion of power flow that is temporarily stored in the form of electric or magnetic fields, due to inductive and capacitive network elements, and returned to source is known as the reactive power. AC connected devices that store energy in the form of a magnetic field include inductive devices called reactors, which consist of a large coil of wire. When a voltage is initially placed across the coil a magnetic field builds up, and it takes a period of time for the current to reach full value. This causes the current to lag the voltage in phase, and hence these devices are said to absorb reactive power. A capacitor is an AC device that stores energy in the form of an electric field. When current is driven through the capacitor, it takes a period of time for charge to build up to produce the full voltage difference. On an AC network the voltage across a capacitor is always changing – the capacitor will oppose this change causing the voltage to lag behind the current. In other words the current leads the voltage in phase, and hence these devices are said to generate reactive power. Energy stored in capacitive or inductive elements of the network give rise to reactive power flow. Reactive power flow strongly influences the voltage levels across the network. Voltage levels and reactive power flow must be carefully controlled to allow a power system to be operated within acceptable limits. Regarding to your measurement results, if a capacitor and an inductor are placed in parallel, then the currents flowing through the inductor and the capacitor tend to cancel out rather than adding. Conventionally, capacitors are considered to generate 3315ENG Efficient Energy System 7/8 reactive power and inductors to consume it. This is the fundamental mechanism for controlling the power factor in electric power transmission; capacitors (or inductors) are inserted in a circuit to partially cancel reactive power 'consumed' by the load. You need to calculate the capacitor size (C=?) to produce the same quantity of reactive power. Figure 9: Calculation of capacitor value for power factor improvement Reference: [1] P. Schavemaker and L. V. D. Sluis, “Electrical Power System Essentials”, Wiley, 2009 [2] Tony R. Kuphaldt, Lessons In Electric Circuits, Volume II – AC, Sixth Edition, last update July 25, 2007 [3] Electric power - Wikipedia, the free encyclopedia.htm 3315ENG Efficient Energy System 8/8