115S I/O Expansion Products

advertisement
115S I/O Expansion Products
I/O for Expanding Applications
Applications
• Flow meter monitoring
• Storage tank monitoring
• Pipeline cathodic protection
• Pump stop-start
• Lighting bank control
• Emergency shower notification
• Weather station reporting
• Bearing condition monitoring
• Modbus Slave I/O
Specifications
Input/Output
Digital Input(1) and
Output(2) (3) (4)
115S-11: up to 16
115S-12: up to 8
115S-13: up to 8
The ELPRO 115S series allows end users to readily accommodate changing
I/O needs as project specifications evolve. The 115S series can be used
with ELPRO transceiver-based I/O, Gateway, Ethernet and Serial products to
expand input and output count or act as Modbus slave I/O to connect other
field devices.
Analog Input
115S-11: 0
115S-12: 4 “floating”/8 commoned (0-20mA/0-10V)
115S-13: 0
Analog Output
115S-11: 0
115S-12: 0
115S-13: 8 sink/source (0-20mA/0-10V)
Connected via RS485 and communicating ELPRO or Modbus protocols,
the 115S series is available in three versions of I/O count and multiple 115S
products may be daisy-chained to accommodate changing application needs.
Pulse Input(3)
115S-11: 4 (first 4 DI only) (max rate 1KHz)
115S-12: 0
115S-13: 0
Pulse Output(3) (5)
115S-11: 8
115S-12: 8
115S-13: 8
Description
Features
• Provides differing I/O count for expanding applications.
• Combine units (daisy-chain) to accommodate additional I/O needs.
• Serial modem expansion I/O for ELPRO transceiver I/O, Gateway and
Ethernet Products.
• Modbus RTU slave I/O expansion capability.
• Serial I/O multiplexer featuring ELPRO change of state WIBNetTM protocol.
Serial Port
RS232
9pin DB9 female connector DCE (Modbus only)
RS485
2 pin terminal block
(max distance 4000’/1.2km - non isolated)
(Modbus and ELPRO protocol)
Data Rate Configurable
1200bps to 115.2Kbps, 7/8 bits, n/e/o Parity, 1/2 stop bits
Note: Specifications subject to change.
1) All digital inputs voltage free contacts.
2) All digital outputs FET (30Vdc/0.2A).
3) Pulse and digital I/O are same connection.
4)Selectable digital inputs and outputs are combined channels. When channel used as
an output, it is not available as an input.
5) All pulse outputs to maximum 100Hz.
Continued on back.
©2011 Cooper Bussmann
www.cooperbussmann.com/wireless
1211
BU-SB11853
Page 1 of 2
Data Sheet # 7922
115S I/O Expansion Products
I/O for Expanding Applications
Specifications
Ordering
LED Indication
To order, select product code from the table.
PWR (Power)
Mains/battery power supply available
OK
Micro processer/PCB operational
TX
Serial port transmitting/communicating
RX
Serial port receiving/communicating
I/O LED Markers
I/O inputs and outputs status
General
Size
5.91” x 7.09” x 1.38” (150 x 180 x 35mm)
Weight
1.1lbs (0.5kg)
Temperature
-40 to +60°C (-40 to 140°F)
Humidity
0-99%RH Non-Condensing
Housing
High temperature polycarbonate
Mounting
DIN rail mounting
Terminal Strip
Removable: up to 2.5mm2 (12 AWG)
Approvals
EMC: FCC Part 15
Safety: UL Class I Div 2, IECEx nA IIC, ATEX Zone 2
Product
Code
Description
115S-11
Serial I/O, ELPRO/Modbus RS485, 16 DIO; 10.8 - 30Vdc Input
115S-12
Serial I/O, ELPRO/Modbus RS485, 8 DIO, 8 AI; 10.8 - 30Vdc Input
115S-13
Serial I/O, ELPRO/Modbus RS485, 8 AO; 10.8 - 30Vdc Input
Accessories
No accessories are required with this product.
Power Supply
Nominal Supply
9-30Vdc
Quiescent Current
12V, 150mA: 24V, 90mA
Loop Supply
Internal DC/DC converter: 24Vdc
115S-12: 270mA
115S-13: 160mA
Note: Specifications subject to change.
The only controlled copy of this Data Sheet is the electronic read-only version located on the Cooper Bussmann Network Drive. All other copies of this document are by definition uncontrolled. This bulletin is intended to clearly present comprehensive product data and provide technical information that will help the end user with design applications. Cooper Bussmann reserves the right, without notice, to change design or construction of any products and to discontinue or limit distribution of