Siemens Energy, Inc. Power Technology Issue 111 Modeling Metal Oxide Varistors (MOV) in Short Circuit Calculations Krishnat Patil Staff Software Engineer krishnat.patil@siemens.com Carlos Grande-Moran Principal Consultant carlos.grande@siemens.com Introduction The ability to model Metal Oxide Varistor (MOV) protection for series compensated lines in short circuit calculations is now available in PSS®E Version 33.1. This MOV modeling will allow PSS®E users to evaluate the short circuit capability of breakers used in the switching of series compensated lines and series capacitor banks for symmetrical and asymmetrical fault currents. PSS®E fault current calculation activities ASCC, IECS and SCMU model MOV protection. The use of series capacitors as a solution to increase the power transfer capability of existing extra high voltage (EHV) transmission lines has been tried extensively in recent years. The general idea is to reduce the inductive reactance of the line, thereby increasing the electrical length and surge impedance loading of a series compensated transmission line. An important design issue of series capacitors in transmission lines is their overvoltage protection. A widely used protection scheme based on metal (zinc) oxide varistors (MOV) has proven to be very effective and reliable. MOVs present a nonlinear resistance characteristic that is approximated by fundamental frequency nonlinear impedance during short circuit calculations. The series capacitors and MOV protection are modeled together as equivalent branch impedance, Zeq= RCeq –j XCeq, controlled by the branch current I flowing into the MOV-protected series capacitor branch1. A typical MOV-protected series capacitor arrangement is shown in Figure 1. The MOV protection is connected directly in parallel with the series capacitor and performs its function by holding the maximum capacitor voltage within the designed protective level. MOV conduction normally occurs only during faults because the capacitor protective level is usually specified above the maximum voltages expected during overload or swing conditions. In normal operation, all current flows through the series capacitor and none through the MOV protection. 1 Daniel L. Goldsworthy, "A Linearized Model for MOV-protected Series Capacitors," IEEE Transactions on Power Systems, Vol. PWRS-2, No. 4, pp 953-958, November 1987. For additional details refer to PSS®E Program Application Guide Volume I. Power Technology March 2012 C Va Ia V’a Va MOV C Vb Ib V’b Zeqc MOV C Ic Zeq b Vb Vc Vc Zeq a Ia V’a Ib V’b Ic V’c V’c MOV Figure 1 – Three-phase, MOV-protected Series Capacitor Bank An MOV is a nonlinear variable resistance that has very high resistance for low voltages across the varistor, and then above the threshold voltage its resistance decreases rapidly. Figure 2 illustrates a typical VI characteristic of a 120 kV rms rated MOV. Notice that the unit conducts little current up to a voltage of about √3 x 120 = 208 kV and then, as the voltage across it increases further, the current increases very rapidly. 700.0 600.0 Typical Arrester Voltage‐Current (VI) Characteristics Arrester Voltage (kVp) 500.0 400.0 300.0 200.0 100.0 0.0 1E‐05 0.0001 0.001 0.01 0.1 1 10 100 1000 Arrester Current (A) Figure 2 - Typical VI Characteristic for MOV Page 2 10000 100000 1E+06 Power Technology March 2012 Solving a network containing a nonlinear impedance Zeq requires an iterative scheme. An initial value of current entering this equivalent impedance is estimated, based on the system condition, and then the network with the nonlinear impedance is solved using the values corresponding to this estimated current. This procedure is repeated until the estimated line current change between two consecutive iterations is within a desired tolerance. This procedure is described by the equation below where I is the MOVprotected series capacitor branch current, α is an accelerating factor, and k is the iteration number. I k 1 I k α I k 1 I k for α 1.0 The desired tolerance, accelerating factor and maximum number of MOV loop iterations values are provided as PSS®E options. Their default values are as follows: acceleration factor equals 0.3, tolerance equals 0.01 and maximum number of MOV loop iterations equals 20. These default values have been tested to assure convergence when working with many real world cases. PSS®E Data Requirements The series capacitor installation must be explicitly modeled in the PSS®E working case as a branch with an impedance equal to 0.0 – j XC, i.e., the branch resistance must be zero. Also, branch reactance in positive and zero sequence must be the same. The MOV data is entered into the working case zero sequence non-transformer branch data records found in the Sequence Data File. Each zero sequence branch data record has the following format: I, J, ICKT, RLINZ, XLINZ, BCHZ, GI, BI, GJ, BJ, IPR, SCTYP where IPR MOV rated current for a series capacitor branch; entered in kA. IPR must be positive. The default for IPR is 0.0. SCTYP MOV protection mode The three protection modes allowed are: 0 for a normal branch (i.e., not an MOV-protected branch) 1 for MOV Protection enabled 2 for MOV Protection disabled The default value for SCTYP is 0. (For other elements in this data record, please refer to the PSS®E Program Operation Manual.) Page 3 Power Technology March 2012 Figure 3 shows PSS®E branch data editor dialog that can be used to edit the MOV protection mode and MOV-rated current data. Figure 3 – PSS®E Branch Data Editor Dialog Numerical Example A ten-bus test system with two series compensated lines (4010-4011 and 4020-4021) is used in this numerical example. The bus fault currents calculated using activity ASCC for symmetrical, three-phase, and asymmetrical, LG, LLG and LL faults are shown in Table 1. The test system used in this example is effectively grounded (X0/X1<3 and R0/X1<1) and thus asymmetrical short circuit currents involving ground will tend to be bigger than three-phase symmetrical fault currents. The first column in each block set shows the momentary short circuit current at the faulted bus with MOV protection disabled; the second column presents the short circuit results with MOV protection enabled. Note that the magnitude of the momentary short circuit currents is smaller when the MOV protection is enabled, as the effective impedance presented by the MOV-protected series capacitor is larger than the effective impedance when the series capacitor installation has its MOV protection disabled. Faulted Bus 3 Phase Fault (Amps) LG Fault (Amps) LLG Fault (Amps) Disabled Enabled Disabled Enabled Disabled Enabled Disabled Enabled 4000 11660.3 11587.1 14435.5 14353.9 18943.5 18881.2 10098.3 10034 4001 6112.7 5966.9 7953.8 7767.4 11405.8 11202.4 5289.1 5163.2 4002 6041.9 6035.6 6343.6 6335 6677.3 6669.5 5232.4 5224.6 4010 1434.9 772.8 1487.4 796.5 1544.2 807.6 1242.6 692 4011 1486.1 738.1 1515.9 742.6 1546.9 751.3 1287 638.3 4020 1434.9 774.6 1487.4 796.5 1544.2 807.6 1242.6 692 4021 1486.1 738.1 1515.9 742.6 1546.9 751.3 1287 638.3 Table 1 - PSS®E Short Circuit Results with Activity ASCC Page 4 LL Fault (Amps) Power Technology March 2012 The short circuit results can be presented graphically on a slider diagram. The slider shows the series capacitor installations specified with MOV protection by means of a symbol that shows a series capacitor in parallel with its MOV protection. Figures 4 and 5 below display the faulted bus, the momentary threephase short circuit current at bus 4021, as well as the post-fault branch currents and bus voltages resulting from the application of the bolted three-phase fault at bus 4021. Figure 4 shows results with the MOV protection disabled; Figure 5 shows results with the MOV protection enabled. 4002 BUS2 4300 GEN3LV 1 14778.4 12.6 167.1 12731.6 -172.0 334.2 8.0 27487.6 1 4001 BUS1 167.1 -172.0 8.0 167.1 4200 GEN2LV 723.8 27574.7 -132.4 47.6 167.1 41271.7 1 -172.0 10.5 8.0 1 -6.3 238.0, 24.1 6.4, 27.0 33473.4 -47.9 6.1, -1.4 4021 SC2B2 4011 SC1B2 207.1 28.8 207.1 389.0 389.0 93.6 -86.4 207.1 -151.2 1201.3 28.8 -37.5 205.0, 32.1 0.0, 0.0 1486.1, -48.9 (3PH) 225.0, 0.2 4010 SC1B1 4000 GEN1HV 207.1 -151.2 207.1 28.8 4020 SC2B1 207.1 1201.3 1201.3 1201.3 -151.2 142.5 -37.5 142.5 4100 GEN1LV 216.5, 9.7 1298.5 -29.1 25969.9 480.5, -127.5 150.9 25969.9 1 TEST SYSTEM #3 -SSR 217.1, 41.8 WED, FEB 15 2012 12:01 ASCC : Three Phase Fault: Bus 4021, IA (AMPS), VA (VOLTS), (POLAR) -29.1 11.4, 42.7 Figure 4 – Fault Currents for Three-phase Fault at Bus 4021 and MOV Protection Disabled Page 5 Power Technology March 2012 4002 BUS2 4300 GEN3LV 1 14778.3 12.6 169.2 12892.3 -171.8 338.4 8.2 27650.3 4200 GEN2LV 4001 BUS1 169.2 -171.8 8.2 169.2 695.5 26493.5 -131.7 48.3 41343.7 169.2 1 1 6.1, -1.6 238.0, 24.1 6.4, 27.0 1 -6.5 8.2 -171.8 10.6 33882.3 -46.2 4021 SC2B2 4011 SC1B2 170.4 28.5 170.4 389.9 389.9 93.2 -86.8 170.4 -151.5 410.3 28.5 -41.3 203.9, 25.8 0.0, 0.0 738.1, -63.5 (3PH) 225.6, -0.1 4010 SC1B1 4000 GEN1HV 170.4 -151.5 170.4 28.5 170.4 -151.5 4020 SC2B1 410.3 410.3 138.7 -41.3 410.3 138.7 4100 GEN1LV 225.0, 18.1 495.4 -22.5 9908.8 10.7, -62.9 157.5 9908.8 1 TEST SYSTEM #3 -SSR 234.2, 42.8 WED, FEB 15 2012 11:31 ASCC : Three Phase Fault: Bus 4021, IA (AMPS), VA (VOLTS), (POLAR) -22.5 11.9, 43.2 Figure 5 – Fault Currents for Three-phase Fault at Bus 4021 and MOV Protection Enabled Page 6