Selecting the Right Air Handling Approach for Data Centers Data Center Systems, Inc. info@datacsi.com PROPRIETARY INFORMATION: The information contained in this presentation is the property of Emerson Network Power and is subject to change without notice. Except as specifically authorized in writing by Emerson Network Power, the holder of this presentation shall keep all information contained herein confidential and shall protect same in whole or in part from disclosure and dissemination to all third parties. The Dynamic Data Center Industry Traditional Systems Progressive Systems Perimeter cooling with raised Variety of deployment schemes floor Cool temperatures with tight temperature and humidity control Availability is only concern Increasing temperatures and wide humidity levels accepted Availability and efficiency concerns Questions to Ask What is the target PUE? What are the whitespace specifications? What specific site considerations are there? What is the financial model for the project? What is the load deployment plan? How would a design respond to Value Engineering? Air Handler Technologies Chilled Water Indirect Evaporative • Most often used for traditional operating range of DC conditions • High efficiency economizer use or high water temperatures • High efficiency system without use of outside air • Indoor or outdoor application • Uses elevated DC conditions Direct Evaporative Direct Expansion • Lowest initial & operation costs • Requires use of outside air and wide range of data center conditions • Requires outdoor equipment • High efficiency requires economizer or evap. condensing • Supports modular deployment Air Handler Technology Comparison Chilled Water Indirect Evaporative Direct Evaporative Direct Expansion $ / kW $850 - $1100 $600 - $700 $300-$500 $800 $1000 Mechanical PUE 1.2 – 1.4 1.15 1.05 - 1.1 1.2 – 1.3 Raised Floor YES NO NO NO Outside Air In DC Some Designs NO YES Some Designs Typical Unit Size (kW) 250 – 400 250 – 350 250 – 350 200 - 500 Design RAT (°F) ~90 95-105 95-105 ~90 Typical SAT (°F) 65-70 70-75 65-85 65-70 Humidity 40-60% 40-60% 25-80% 40-60% (Typical Application) Chilled Water Air Handlers Typical Deployments • • Vertical units along perimeter or in gallery discharging into raised floor Horizontal units in gallery or outside the building – may not have raised floor for air distribution Key Positive Aspects of System • • • Can deliver relatively precise data center conditions Can be very efficient with elevated water loop temperatures Indoor units are typically easy to service and commission Areas to be Cautious • • • Significant upfront cost associated with chiller plant Economizer operation often abandoned in a few years Water usage, storage, and treatment Chilled Water Energy Saving Strategies Outside Air Economizing Water Side Economizing Cooling Tower Only • • • • • Often requires outside wall access Requires Temp & Humidity sensors to control indoor moisture Easy to shut off outside air if required Plate frame heat exchanger in series with chiller allows for partial economizing • • Coils design for 75 EWT and 105 EAT Only cooling towers used with heat exchangers between loops Small side stream chiller may be used Chilled Water Air Handler Control Components Return Air Temp Sensors Chilled Water Filter Gauges Supply Air Temp Sensors Fluid Flow Sensors Airflow Measurement Fan Power Meters 8 Indirect Evaporative Air Handlers Typical Deployments • • • Large units deployed outside the data Raised floor is often utilized Full containment system with elevated supply and return temperatures critical for high efficiency Key Positive Aspects of System • • • • High efficiency systems with mechanical PUE < 1.2 Downsized electrical infrastructure Low cost per kW initial cost Low peak power consumption Areas to be Cautious • • • Typical design of 100 to 102 °F RAT has minimal thermal “ride-through” time Makeup air required for positive pressure in the space Water usage, storage, treatment Indirect Evaporative Typical System Components Indirect Evaporative Filters Supply Fan Array Optional Trim Cooling Coil Return Air ~102 °F Heat Exchanger Supply Air ~75 °F Indirect Evaporative Typical System Components Mist Eliminator Scavenger Air Indirect Evaporative Option Condenser Coil Spray Nozzles Scavenger Air Heat Exchanger Recirc Pump Sump Basin Compressor Section Indirect Evaporative Operation Modes: Dry HX Supply Air Temp Control Indirect Evaporative Amb Cooling Mode Dry Bulb (°F) Wet Bulb (°F) (gp m) Clg. PUE Cold Dry 35 30 - 1.08 Wet HX + Trim Cooling Supply Air Vol Control Wet HX Dry HX 50 °F 65 °F Indirect Evaporative Operation Modes: Wet HX Supply Air Temp Control Indirect Evaporative Amb Cooling Mode Dry Bulb (°F) Wet Bulb (°F) (gp m) Clg. PUE Warm Wet 68 57 2.5 1.09 Wet HX + Trim Cooling Supply Air Vol Control Wet HX Dry HX 65 °F 69 °F Indirect Evaporative Operation Modes: Wet + Trim HX Supply Air Temp Control Indirect Evaporative Amb Cooling Mode Dry Bulb (°F) Wet Bulb (°F) (gp m) Clg. PUE Warm Wet + Trim 68 57 2.5 1.16 Wet HX + Trim Cooling Supply Air Vol Control Wet HX Dry HX 69 °F Indirect Evaporative Heat Exchanger Technology Aluminum Plate Polymeric Tubing • • • • DC and Scavenger Air travel in 90° paths separated by aluminum Dry efficiency 60-70% Wet Efficiency 75–85% • • Indirect Evaporative DC air travels through tubes & Scavenger Air flows perpendicularly around tubes Dry efficiency 40-50% Wet Efficiency 75–85% Indirect Evaporative Water Treatment / Scale Prevention Indirect Evaporative Scale is result of dissolved minerals forming solids on surfaces exposed to water Critical to control or mitigate on any evaporative system Provides medium for biological growth Four Critical Methods of Scale Prevention ● Engineered spray system that ensures “overspray” ● Conductivity controller set to desired cycles of concentration ● Control SOO that minimize on/off cycles ● Retain local water quality company to maintain water quality levels Indirect Evaporative Performance Across the US Indirect Evaporative PUE 1.10 PUE 1.11 PUE 1.10 PUE 1.11 PUE 1.12 PUE 1.13 PUE 1.14 PUE 1.14 Indirect Evaporative Operational Control Strategies Indirect Evaporative Unit Control Strategies System Control Strategies • • • • Unit capacity controlled to supply air setpoint Control in real-time at optimum mix of scavenger fan & water usage Makeup air unit controlled by return air humidity levels • • Supply fan speed controlled by plenum pressure Cold aisle dampers controlled by rack sensor readings Coordinate units for standby operation to prevent fighting Supply Pressure Control Unit Capacity Coordination Rack Sensors Supply Air Temp Control Cold Aisle Control Dampers Direct Evaporative Air Handlers Typical Deployments • • • Large units deployed outside the data Slab floor with hot aisle / cold aisle row arrangement Full containment system with elevated supply and return temperatures as design points Key Positive Aspects of System • • • • Very high efficiency systems with mechanical PUE < 1.1 Low kW per unit – downsizes electrical infrastructure Lowest cost per kW initial cost Lowest peak power consumption Areas to be Cautious • • • • Wider temperature and humidity ranges Reduced level of control Water usage and water storage Water treatment Direct Evaporative Typical System Components Outside Air Dampers Return Air Return Air Dampers Bypass Damper Direct Evaporative Supply Fan Isolation Array Damper Supply Air Outside Air Filters Evap Media Evap Media Sump Basin Optional Trim Cooling Coil Direct Evaporative How Evaporative Cooling Works Evaporative Cooling Process • Dry bulb temperature of air is reduced while wet bulb remains the same 86 / 66 • • Ex. (86 °F – 66 °F) x 0.89 = 18 °F • • Ex. (86 °F – 18 °F) = 68 °F / 66 °F 89% Direct Evaporative Direct Evaporative Modes of Operation Zones of Operation Direct Evaporative Pittsburgh, PA Example Typical Design SA Range • 65 – 85 °F Dry Bulb • 25 – 80 % RH Mechanical Cooling Typical Design SA Range • 65 – 85 °F Dry Bulb • 25 – 80 % RH 0 Hours (0.0%) 1,756 Hrs (20.0%) 4,012 Hrs (41.8%) OA Only OA & RA Mix OA & RA + Hum OA w/ Evap Clg 2,749 Hrs (31.4%) 243 Hours (2.8%) Direct Evaporative Operation Cold Ambient Conditions Return Air Damper 87°F 70% Open Bypass Damper 50% Open Direct Evaporative Typical Cold Ambient Supply Temperature Fan Operation 65 °F to 72 °F 60% 67°F 27°F MAT Outside Air Damper Evap Media Pump Top: 50% Open Bottom: 0% Open Supply Air Setpoint Zone On: 1 Stages (of 4) MAT Direct Evaporative Operation Cool Ambient Conditions Return Air Damper 33% Open 89°F Bypass Damper 100% Open Direct Evaporative Fan Operation 60% 67°F 56°F Supply Air Setpoint Zone Outside Air Damper Evap Media Pump Top: 100% Open Bottom: 33% Open Off: 0 Stages (of 4) MAT Direct Evaporative Operation “Just Right” Conditions Return Air Damper 0% Open 92°F Bypass Damper 100% Open Direct Evaporative Fan Operation 60% 70°F 70°F Supply Air Setpoint Zone Outside Air Damper Evap Media Pump Top: 100% Open Bottom: 100% Open Off: 0 Stages (of 4) Direct Evaporative Operation Hot Ambient Conditions Return Air Damper 0% Open 105°F Bypass Damper ~25% Open Direct Evaporative Fan Operation 75% 83°F 95°F Outside Air Damper Evap Media Pump Top: 100% Open Bottom: 100% Open On: 4 Stages (of 4) Supply Air Setpoint Zone Direct Evaporative Operation Hot and Humid Conditions Return Air Damper 0% Open 105°F Bypass Damper 25% Open Direct Evaporative Fan Operation 75% 83°F 115°F Return Air Supply Air Outside Air Outside Air Damper Evap Media Pump Top: 100% Open Bottom: 100% Open On: 4 Stages (of 4) Trim Cooling Coil On: Full Capacity Supply Air Setpoint Zone Direct Evaporative Control Strategies Direct Evaporative Unit Control Strategies System Control Strategies • • • • Unit capacity controlled to supply air setpoint range Power metering on supply fan, pumps, and exhaust fan for energy optimization Fan speed controlled by rack inlet temperature sensors • • Flooded room with hot aisle containment Coordinate units for standby operation to prevent fighting Monitor server fan power consumption to minimize site power consumption Server Fan Power Cons. RA / OA Mod. Dampers Supply Fan Power Mtr SA Temp Sensor RA / OA Temp Sensors Evap Bypass Dampers Direct Expansion Air Handlers Typical Deployments • • Roof mounted units in single or two story buildings Often requires supply and/or return ductwork for air distribution Key Positive Aspects of System • • Easily accommodates modular build outs Evaporative condensing with outside air can result in very efficient systems Areas to be Cautious • • • Low ambient conditions can often cause operation issues Existing building may require roof structure to be improved Comfort units don’t have the optimal refrigeration circuits Direct Expansion Typical Components Exhaust Hood Outside Hood Filters Return Air Dampers Direct Expansion Supply Fan Mixing Dampers Digital Scroll Compressors Cooling Coil Evaporative Condensing Section Direct Expansion Control Strategies Direct Expansion Unit Control Strategies System Control Strategies • • • • Unit capacity controlled to supply air setpoint Unit controlling economizer based on supply temp and enthalpy Fan speed controlled by pressure setpoint in space or supply plenum Enthalpy Based Economizer • • Rack inlet sensors used to verify fan airflow volume Coordinate units for standby operation to prevent fighting Return air pressure monitored for proper space pressure control Lead / Lag or Common Capacity Operation Rack Inlet Sensors Frequently Asked Questions Contact Tifft Gannon directly for clarifications or further information if your question is not answered – tifft.gannon@emerson.com What percentage of trim cooling capacity is designed for evaporative systems? Is there a unit size that is too big and what are the issues at that size? How would someone use both waterside and airside economizing in a chilled water system? What percentage of data center are using supply air temperatures up to 85 °F? Are any of these systems better at handling low load situations? What systems are best for Canadian installations that see temperatures to 40 °F? How many stages of cooling control are there on direct evaporative systems? What happens when my customer predicted return air temperature comes in much lower than what they told me? For Further Information Contact Data Center Systems 952.403.9900 PROPRIETARY INFORMATION: The information contained in this presentation is the property of Emerson Network Power and is subject to change without notice. Except as specifically authorized in writing by Emerson Network Power, the holder of this presentation shall keep all information contained herein confidential and shall protect same in whole or in part from disclosure and dissemination to all third parties.