A technical manual from the experts in Business-Critical Continuity™ NetSure™ ITM Site Planning Data and System Drawings – 48V DC UPS Section 6037 (Issue 10, October 21, 2010) Contents 1. Site Planning Data 2. One Line Diagram 3. System Outline Drawings 4. Connection Details Section 6037 Issue 10, October 20, 2010 Emerson Network Power NetSure™ ITM 1 SITE PLANNING DATA 1.1 Technical Specifications NetSure® ITM – Technical Specifications Power Rating (full) – kW Power Rating (N + 1) – kW AC Input Specifications Phase Power Factor Frequency – Hz Input Voltage – Nominal Input Voltage – Range Input Breaker Rating / AIC Rating – A Max Input Current / Module Inrush Current Total Harmonic Distortion DC Output Specifications Voltage System Efficiency Energy Optimization Mode: Intelligent Power Matching Branch Distribution Options Battery Specification Type Arrangement Backup Time Design Life Recharge Time (to 97% of nominal capacity) Physical Data Form Factor Installed Dimensions (H x W x D) – in. (mm) Installed Weight – lb. (kg) Environmental Specifications System Operating Temp. – °F (°C) System Storage Temp. – °F (°C) Relative Humidity Operating Elevation – ft. (m) Audible Noise Heat Rejection at Full Load – BTU/hr. (kW) EMI Safety Certifications Agency Approved Monitoring Capability Standard Optional Page 2 Primary Module 1 70 64 Expansion Module 2 70 70 Expansion Module 3 70 70 Expansion Module 4 70 70 3 0.99 at full load, 0.98 at 50% load 45-65 400 / 480V, 3 wire + ground 304-530 VAC; shall withstand up to 600 VAC input without damage. 150 / 65,000 480V: 115A @ 384V; 92A @ 480V 400V: 138A @ 320V; 110A @ 400V 380V: 145A @ 304V; 116A @ 380V Inrush current does not exceed 150% of the rated input steady state peak value <5% from 50-100% of load Nominal: -48VDC; normal operation: -54.5 VDC (battery float) Range: -42 to -58 VDC 92.5% peak (system level including branch distribution losses) Allows operation at near-peak efficiency down to 5% overall load 22 circuit breakers, 100-200A each; optional: 6 fuses, 2x500A + 4x200A VRLA, Emerson Excellence EB4, 200 Ah 3 strings; eight 6V blocks per string See backup time table at various loads 15 years @ 20 °C ; 10 years @ 25 °C Less than 3 hours for > 35% load; Less than 4 hours > 15% load Rack 83 x 24 x 41 (2100 x 600 x 1040) 3214 (1458) -5 °C to +35 °C; recommended operation with battery: 20 °C to 25 °C air inlet -40 to 158 °F (-40 °C to +70 °C) 0 to 95%, non condensing 6562 (2000) at full power < 60dB 18,096 (5.3) per module FCC class A CE Marked to EN 60 950-1:2006 UL Listed to 60 950-1 + UL 1801; CSA certified Web-based monitoring, alarm reporting via SNMP, and integration with SiteScan via SiteLink-E module Energy Master Remote Supervision Proprietary Information This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited. Emerson Network Power NetSure™ ITM Section 6037 Issue 10, October 20, 2010 1.2 Battery Run Times Battery Back-up Time (minutes) Load 10kW 20kW 30kW 40kW 50kW 64kW 70kW 80kW 90kW 100kW 110kW 120kW 134kW 140kW 150kW 160kW 170kW 180kW 190kW 204kW 210kW 220kW 230kW 240kW 250kW 260kW 274kW 280kW Single module 70kW 130 55 28 17 12 7 3 Two modules 140kW 300 130 90 55 41 24 21 17 14 12 10 8 6 3 Proprietary Information Three modules 210kW 480 210 130 90 70 50 43 34 27 22 19 17 16 14 12 10 9 8 7 4 2 Four modules 280kW 630 300 180 130 100 75 69 55 47 40 34 28 25 22 19 17 15 14 13 11 10 9 9 8 7 6 3 1 Page 3 This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited. Section 6037 Issue 10, October 20, 2010 Emerson Network Power NetSure™ ITM 2 ONE LINE DIAGRAM PRIMARY DC UPS MODULE (1) AC Input A AC Input B (Optional) EXPANSION DC UPS MODULES (2-4) AC Input A AC Input B (Optional) AC Circuit Breakers (Note 3) AC Circuit Breakers (Note 3) Internal COM-link Controller and Communication Controller and Communication Current Transformer Current Transformer PCU Breakers (Note 4) PCU Breakers (Note 4) PCU PCU PCU PCU PCU LVD LVD Battery Shunts Load Shunts Load Breakers or Optional Fuses PCU Battery Fuse Battery Shunts Battery Internal DC-link Battery Fuse Battery Load Shunts Load Breakers or Optional Fuses NOTES 1. DUAL AC INPUT VERSION OPTIONAL. 2. RECOMMENDED INPUT WIRE SIZE 2/0 AWG, 90˚C (194˚F), SEE NEC TABLE 310.16. 3. MAX INPUT CURRENT: 480V: 115A @ 384V; 92A @ 480V 400V: 138A @ 320V; 110A @ 400V 380V: 145A @ 304V; 116A @ 380V 3. SYSTEM AC INPUT BREAKER(S) RATED 150A, 65kAIC. 4. PCU AC INPUT BREAKERS RATED 32A, 5000AIC. TWO (2) PCUs PER BREAKER. Page 4 Proprietary Information This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited. Emerson Network Power NetSure™ ITM Section 6037 Issue 10, October 20, 2010 3 SYSTEM OUTLINE DRAWINGS 3.1 Mechanical Installation and Outline Drawings 3.1.1 Individual Cabinet Mechanical Data DC UPS MODULE WITH BOTTOM FEED DC DISTRIBUTION DC UPS MODULE WITH TOP FEED DC DISTRIBUTION Battery Compartment Battery Compartment CG CG Conduits for AC Inputs 41.34 (1050) 26.38 (670) 41.34 (1050) DC Power System Compartment 26.38 (670) DC Power System Compartment Conduits for AC Inputs 11.81 (300) 11.81 (300) 23.62 (600) Top View 23.62 (600) Top View CENTER OF GRAVITY 84.33 (2142) top cabled Top Cabled Version X = 11.81 (300) Y = 26.38 (670) Z = 36.61 (930) 84.72 (2152) bottom cabled Bottom Cabled Version X = 11.81 (300) Y = 26.38 (670) Z = 40.55 (1030) (Bottom cabled) CG Z Y CG (top cabled) X 40.55 (1030) 36.61 (930) Notes: 1. Dimensions are in inches (millimeters). 2. Weight (fully loaded): 3240 lbs / 1470 kg. 3. Heat Rejection: 18096 BTU/h at full load (per module) 4. May be installed on concrete slab or raised floor. 11.81 (300) . Front View 3.1.2 System Configurations Single Module 70kW (full) 64kW (n+1) Two Modules 140kW (full) 134kW (n+1) Three Modules 210kW (full) 204kW (n+1) Four Modules 280kW (full) 274kW (n+1) System can be expanded either to the left or the right of the Primary Module. Proprietary Information Page 5 This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited. Section 6037 Issue 10, October 20, 2010 Emerson Network Power NetSure™ ITM 3.1.3 Main Components 3.1.3.1 Bottom Cabled Configuration - Circuit Breaker Load Distribution (Standard) AC Input Conduit Feeds PCU Position (left to right) #1/#2, #3/#4, #5/#6, #7/#8, #9/#10, #11/#12 Internal Circuit Breakers (32A) (Each Circuit Breaker Feeds Two PCUs) PCU* Position #2 PCU* Position #1 #3 #4 #5 #6 #7 #8 #9 #10 #11 #12 * PCUs (12 x 5833W) SM-AC (AC Input Monitoring) ACU+ (Controller) AC Input Circuit Breaker(s) (150A, 65kAIC) Battery Fuses (800A) (Battery leads factory connected and routed to Battery Compartment.) LVD Contactor 1 11 12 22 Load Distribution Devices (DC distribution circuit breakers, 22 positions, 100-200A) (Fuse Option Available) Battery Return and Load Return (Battery return leads factory connected and routed to Battery Compartment.) Front View (door removed) Page 6 Proprietary Information This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited. Emerson Network Power NetSure™ ITM Section 6037 Issue 10, October 20, 2010 3.1.3.2 Top Cabled Configuration - Circuit Breaker Load Distribution (Standard) AC Input Conduit Openings Battery Return and Load Return (Battery return leads factory connected and routed to Battery Compartment.) 1 11 Load Distribution Devices (DC distribution circuit breakers, 22 positions, 100-200A) (Fuse Option Available) 12 22 ACU+ (Controller) Feeds PCU Position (left to right) #1/#2, #3/#4, #5/#6, #7/#8, #9/#10, #11/#12 Internal Circuit Breakers (32A) (Each Circuit Breaker Feeds Two PCUs) SM-AC (AC Input Monitoring) AC Input Circuit Breaker(s) (150A, 65kAIC) PCU* Position #2 PCU* Position #1 #3 #4 #5 #6 #7 #8 #9 #10 #11 #12 * PCUs (12 x 5833W) Battery Fuses (800A) (Battery leads factory connected and routed to Battery Compartment.) SUIT ABLE F O R MO UNT ING O N CO NCRET E O R O THER NO N-COMBUST IBLE SURF ACE O NLY. LVD Contactor Front View (door removed) Proprietary Information Page 7 This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited. Section 6037 Issue 10, October 20, 2010 Emerson Network Power NetSure™ ITM 3.1.4 Bottom Cable Entry Notes: 1. Dimensions are in inches (millimeters). 2. Do not block air intake openings. 3. Minimum under floor space for underfloor output cable runs: A = 1f (300mm). 4. Run cables not to block air openings for battery cooling. Battery Compartment Conduits for AC Inputs DC Power System Compartment Hot Aisle Cold Aisle Top PCUs PCUs PCUs PCUs PCUs PCUs Air Flow Battery Compartment BFU Distr. Distr. Note 2 Raised Floor Front Side View 17.72 (450) 35.43 (900) 8.86 (225) 9.84 (250) Support Stand 8.86 (225) 9.84 (250) ½” (12mm) Floor Anchoring Bolts (4 places) Optional Floor Opening for Battery Cooling 19.68 (500) P/N 547822 24” Tall Floor Stand Page 8 A P/N 547823 36” Tall Floor Stand Proprietary Information This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited. Emerson Network Power NetSure™ ITM Section 6037 Issue 10, October 20, 2010 3.1.5 Top Cable Entry Hot Aisle Cold Aisle Battery Compartment Distr. DC Power System Compartment AC Input Conduit Openings Openings for Output Cables Distr. Air Flow Top Battery Compartment PCUs PCUs PCUs PCUs PCUs PCUs BFU Concrete Floor (slab) Side View Cable Tray Note 2 Cable Tray Supports if Mounted on Top of Module Front Cable Run 35.43 (900) Air Exchange (keep clear) Front View ½” (12mm) Floor Anchoring Bolts (4 places) 19.68 (500) Battery Compartment 23.62 (600) Cable Tray Notes: 1. Dimensions are in inches (millimeters). 2. Do not block air intake openings. Top View Proprietary Information Openings for Output Cables Page 9 This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited. Section 6037 Issue 10, October 20, 2010 Emerson Network Power NetSure™ ITM 4 CONNECTON DETAILS 4.1 Bottom Cable Entry Electrical Connection Detail DETAIL B (Circuit Breaker Option) CABINET GROUNDING SUITABLE CABLE LUGS WITH HOLE DIA 3/8" (M10) TYPICAL LUG THOMAS & BETTS TYPE 54136 RECOMMENDED TORQUE 407-434 in-lbs (46-49 Nm). INPUT AC CONDUIT(S) SEE DETAIL ”E” 1” SUITABLE CABLE LUGS WITH HOLE DIA 3/8" (M10) TYPICAL LUG THOMAS & BETTS TYPE 54109 RECOMMENDED TORQUE 407-434 in-lbs (46-49 Nm) CONTROLLER SEE DETAIL ”D” DETAIL C (Circuit Breaker Option) 1" INPUT AC CONNECTION SEE DETAIL ”A” INPUT GROUNDING CONNECTION LUGS 5/16" (M8) TYPICAL LUG THOMAS & BETTS TYPE 54109 RECOMMENDED TORQUE 204-221 in-lbs (23-25 Nm) NEGATIVE BUSBAR SEE DETAIL ”C” (LOAD) POSITIVE BUSBAR SEE DETAIL ”B” (RETURN) SUITABLE CABLE LUGS WITH HOLE DIA 3/8" (M10) TYPICAL LUG THOMAS & BETTS TYPE 54209 RECOMMENDED TORQUE 407-434 in-lbs (46-49 Nm) SIDE PLATES ARE ONLY DELIVERED ON MAIN CABINET. SHALL BE MOVED TO THE LAST EXTENSION CABINET IN A ROW DETAIL A factory wiring 1.7 5" ONE OR TWO AC CIRCUIT BREAKERS, NO LUGS NEEDED. MARK CABLES A-L1, A-L2 AND A-L3 (B-L1, B-L2, B-L3) RECOMMENDED TORQUE 124 in-lbs (14 Nm) DETAIL B (Fuse Option) 1 .75" INPUT AC CABLE ROUTING GND Stud GND Stud L1 L2 L3 L1 L2 L3 AC IN A AC IN B DETAIL D DETAIL E 2" S U IT A B L E C A B L E L U GS W IT H H O L E D IA 1 /2 " ( M 1 2 ) T Y P IC A L L U G T H O M A S & B E T T S T Y P E 5 4 2 8 2 (3 5 0 kcm il) R E C O M M E N D E D T O R Q U E 690-743 in-lbs (78-84 Nm) DETAIL C (Fuse Option) 1.5” ENT USB RJ45 USB RECOMMENDED COUPLING: RACO TYPE 2628 (GRAINGER 3LV08) OR THOMAS BETTS TYPE TK126US COMMUNICATION LINKS BETWEEN CABINETS: 1. RS-485 BUS WIRES (TWISTED YELLOW/WHITE WIRES) SHALL BE CONNECTED TO SM-AC. 2. CAN-BUS WIRES (TWISTED BLACK/WHITE WIRES) SHALL BE INTERCONNECTED. 3. CONTACTOR CONTROL CABLES SHALL BE INTERCONNECTED. NOTE 1. WHEN CONNECTING OUTPUT DISTRIBUTION CABLES – START WHITH INNER ROW FIRST. Page 10 1 .75" ESC S U IT A B L E C A B L E L U GS W IT H H O L E D IA 1 /2 " ( M 1 2 ) T Y P IC A L L U G T H O M A S & B E T T S T Y P E 5 4 2 8 2 (3 5 0 kcm il) R E C O M M E N D E D T O R Q U E 690-743 in-lbs (78-84 Nm) Proprietary Information This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited. Emerson Network Power NetSure™ ITM Section 6037 Issue 10, October 20, 2010 4.2 Top Cable Entry Electrical Connection Detail CABINET GROUNDING SUITABLE CABLE LUGS WITH HOLE DIA 3/8" (M10) TYPICAL LUG THOMAS & BETTS TYPE 54136 RECOMMENDED TORQUE 407-434 in-lbs (46-49 Nm). KNOCKOUTS FOR INPUT AC CONDUIT(S) SIZE 2" OR COUPLING(S) SIZE 2" (NOT INCLUDED) INPUT AC CABLE ROUTING DETAIL B (Circuit Breaker Option) 1” SUITABLE CABLE LUGS WITH HOLE DIA 3/8" (M10) TYPICAL LUG THOMAS & BETTS TYPE 54109 RECOMMENDED TORQUE 407-434 in-lbs (46-49 Nm) POSITIVE BUSBAR SEE DETAIL ”B” (RETURN) INPUT GROUNDING CONNECTION LUGS 5/16" (M8) TYPICAL LUG THOMAS & BETTS TYPE 54109 RECOMMENDED TORQUE 204-221 in-lbs (23-25 Nm) NEGATIVE BUSBAR SEE DETAIL ”C” (LOAD) DETAIL C (Circuit Breaker Option) 1" INPUT AC CONNECTION SEE DETAIL ”A” CONTROLLER SEE DETAIL ”D” SIDE PLATES ARE ONLY DELIVERED ON MAIN CABINET. SHALL BE MOVED TO THE LAST EXTENSION CABINET IN A ROW. SUITABLE CABLE LUGS WITH HOLE DIA 3/8" (M10) TYPICAL LUG THOMAS & BETTS TYPE 54209 RECOMMENDED TORQUE 407-434 in-lbs (46-49 Nm) DETAIL B (Fuse Option) DETAIL A GND Stud factory wiring DETAIL D 1 .75" GND Stud ONE OR TWO AC CIRCUIT BREAKERS, NO LUGS NEEDED. MARK CABLES A-L1, A-L2 AND A-L3 (B-L1, B-L2, B-L3) RECOMMENDED TORQUE 124 in-lbs (14 Nm) 1 .75" AC IN A AC IN B L1 L2 L3 L1 L2 L3 DETAIL E 2" S U IT A B L E C A B L E L U GS W IT H H O L E D IA 1 /2 " ( M 1 2 ) T Y P IC A L L U G T H O M A S & B E T T S T Y P E 5 4 2 8 2 (3 5 0 kcm il) R E C O M M E N D E D T O R Q U E 690-743 in-lbs (78-84 Nm) ENT ESC USB RJ45 USB RECOMMENDED COUPLING: RACO TYPE 2628 (GRAINGER 3LV08) OR THOMAS BETTS TYPE TK126US COMMUNICATION LINKS BETWEEN CABINETS: 1. RS-485 BUS WIRES (TWISTED YELLOW/WHITE WIRES) SHALL BE CONNECTED TO SM-AC. 2. CAN-BUS WIRES (TWISTED BLACK/WHITE WIRES) SHALL BE INTERCONNECTED. 3. CONTACTOR CONTROL CABLES SHALL BE INTERCONNECTED. NOTE 1. WHEN CONNECTING OUTPUT DISTRIBUTION CABLES – START WITH INNER ROW FIRST. Proprietary Information 1 .75" DETAIL C (Fuse Option) 1.5” S U IT A B L E C A B L E L U GS W IT H H O L E D IA 1 /2 " ( M 1 2 ) T Y P IC A L L U G T H O M A S & B E T T S T Y P E 5 4 2 8 2 (3 5 0 kcm il) R E C O M M E N D E D T O R Q U E 690-743 in-lbs (78-84 Nm) Page 11 This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited. Emerson (NYSE: EMR), based in St. Louis, is a global leader in bringing technology and engineering together to provide innovative solutions for customers in industrial, commercial, and consumer markets through its network power, process management, industrial automation, climate technologies, and appliance and tools businesses. For more information, visit: Emerson.com. Emerson Network Power, a business of Emerson (NYSE:EMR), is the global leader in enabling Business-Critical Continuity™ from grid to chip for telecommunication networks, data centers, health care and industrial facilities. Emerson Network Power provides innovative solutions and expertise in areas including AC and DC power, precision cooling, embedded computing and power, integrated racks and enclosures, power switching and controls, infrastructure management, and connectivity. All solutions are supported globally by local Emerson Network Power service technicians. For more information on Emerson Network Power’s full suite of solutions specifically supporting the communications network infrastructure, visit: EmersonNetworkPower.com/EnergySystems. Learn more about the NetSure™ ITM DC UPS from Emerson at: EmersonNetworkPower.com/NetSureITM. . This publication is issued to provide outline information only which (unless agreed by Emerson Network Power Energy Systems, North America, Inc. in writing) may not be used, applied or reproduced for any purpose or form part of any order or contract or be regarded as a representation relating to the products or services concerned. Emerson Network Power Energy Systems, North America, Inc. reserves the right to alter without notice the specification, design or conditions of supply of any product or service. Emerson®, Emerson Network Power™, Business-Critical Continuity™, Efficiency Without Compromise™, Albér®, EnergyMaster™, Liebert®, NetSure®, SiteScan™ and SiteWeb™ are trademarks of Emerson Electric Co. and/or one of its subsidiaries. Emerson Network Power Energy Systems, North America 4350 Weaver Parkway, Warrenville, IL 60555 Toll Free: 800-800-1280 (USA and Canada) Telephone: 440-246-6999 Fax: 440-246-4876 Web: EmersonNetworkPower.com/EnergySystems EnergyNet: Secure.EmersonNetworkPower.com Emerson Network Power. The global leader in enabling Business-Critical Continuity™ . AC Power Connectivity DC Power Code: Section 6037, Issue 10 EmersonNetworkPower.com Embedded Computing Embedded Power Outside Plant Power Switching & Controls Racks & Integrated Cabinets Services Infrastructure Management & Monitoring Precision Cooling Surge Protection