NEMA Full Voltage Power Devices Section 1 NEMA Rated Full Voltage Contactors CR305, CR385 Auxiliary Contact Kits For Field Installation on Magnetic Contactors NEMA Sizes 0-7 Application Auxiliary contacts can add to the versatility of magnetic contactors by providing additional control circuits to do a variety of jobs without adding to the width of the contactor. Kits make it easy to add contacts to control accessory equipment such as indicating lights. Auxiliary contacts can be added to all across-the-line magnetic contactors. Each auxiliary contact is rated 10 Amperes ac, resistive load, NEMA “A600,” and is suitable for either right or left side mounting. An insulating shield is also provided between each auxiliary contact unit and the contactor. Auxiliary contacts are furnished in the basic block design or as an adder block. Each contact is marked NO or NC on the block and is not convertible. Logic reed contacts suitable for low energy level circuits are also available. These are designed for applications on lowvoltage control circuits (24 Volts and below), such as inputs to computers and programmable starters. Basic Block and Adder Block Product Number Selection Instructions 1. Order by quantity and complete Product Number. Example: Three CR305X300A at $36.00 each, GO-10G. Reference Publications Instructions NEMA Size 0, 1 2 3, 4 5, 6 7-9 0, 1 Logic Reed 2 Logic Reed 3, 4 Logic Reed 5, 6 Logic Reed Publication Number GEH-4758 GEH-4759 GEH-4760 GEH-4761 GEH-5109 GEH-5178 GEH-5185 GEH-5186 GEH-5187 Field-Installed Modifications for Magnetic Contactors (CR305, CR385) – Contents Application Information and Selection Instructions.............1-204 Auxiliary Contact Kits (CR305X, CR385X) ...................................1-205 Modification Kits ....................................................................................1-207 Outlines and Dimensions (CR305, CR385) .................................1-210 Product Number Selection Instructions: See page 1-204 1-204 Control Catalog www.geindustrial.com Rev. 7/13 Prices and data subject to change without notice NEMA Full Voltage Power Devices Section 1 NEMA Rated Full Voltage Contactors CR305X, CR385X Auxiliary Contact Kits Field-Installed Modification Kits For 300-Line Contactors Auxiliary Contact Kits NEMA Size 0,1 0,1 0,1 2 2 2 3, 4 3, 4 3, 4 5, 6 5, 6 5, 6 7 7 7 8-9 8-9 8-9 Contact Configuration Block Design 1NO 1NC 1NO-1NC 1NO 1NC 1NO-1NC 1NO 1NC 1NO-1NC 1NO 1NC 1NO-1NC 1NO 1NC 1NO-1NC 1NO 1NC 1NO-1NC Basic Basic Basic Basic Basic Basic Basic Basic Basic Basic Basic Basic Basic Basic Basic Basic Basic Basic Product Number List Price GO-10G CR305X100A CR305X100B CR305X100C CR305X200A CR305X200B CR305X200C CR305X300A CR305X300B CR305X300C CR305X500A CR305X500B CR305X500C CR385X600A CR385X600B CR385X600C CR385X800A CR385X800B CR385X800C $36.00 $36.00 $48.00 $36.00 $36.00 $48.00 $36.00 $36.00 $48.00 $36.00 $36.00 $48.00 $198.00 $198.00 $396.00 $198.00 $198.00 $396.00 Auxiliary Contact Kits - Adder Blocks NEMA Size 0-9 0-9 Contact Configuration Block Design Product Number List Price GO-10G 1NO 1NC Adder Adder CR305X100D1 CR305X100E1 $36.00 $36.00 Logic Reed Switch Auxiliary Contacts2 NEMA Size Contact Configuration Product Number List Price GO-10G 00, 0, 1 00, 0, 1 00, 0, 1 2 2 2 3, 4 3, 4 3, 4 5, 6 5, 6 5, 6 1NO-0NC 0NO-1NC 1NO-1NC 1NO-0NC 0NO-1NC 1NO-1NC 1NO-0NC 0NO-1NC 1NO-1NC 1NO-0NC 0NO-1NC 1NO-1NC CR305X100RA CR305X100RB CR305X100RC CR305X200RA CR305X200RB CR305X200RC CR305X300RA CR305X300RB CR305X300RC CR305X500RA CR305X500RB CR305X500RC $45.00 $45.00 $72.00 $45.00 $45.00 $72.00 $45.00 $45.00 $72.00 $45.00 $45.00 $72.00 Contact Ratings - Basic Blocks High Fidelity Contact Basic Block 120 VAC maximum .15 A maximum, 8 VA maximum resistive. 30 VDC maximum .15 A maximum, 4.5 VA maximum resistive. Standard Block AC Volts Continuous Current Amperes Inrush Current Amperes DC Volts Continuous Current Amperes 115 6.0 60 125 1.1 230 3.0 30 250 0.5 460 1.5 15 — — 575 1.2 12 — — 1First adder block must be mounted to a basic block. A second adder block can be added to the first adder block on size 2 through size 9 starters. Inrush Current Amperes — — — — Four extra auxiliary contacts (not blocks) is the maximum that can be added to either a NEMA size 0 or 1 starter while five is the maximum extra auxiliary contacts that can be added to NEMA Size 2 through 6 devices. 2CR305X logic reed switch auxiliary contacts may be ordered as a factory-installed modification. Order by description. For factory-installed modification, add $75.00, GO-10G, per circuit to price of starter. Rev. 7/13 Prices and data subject to change without notice www.geindustrial.com Control Catalog 1-205