Deadbreak Apparatus
Connectors
Cooper Power Systems
Electrical Apparatus
200 A 15 and 25 kV Class
Deadbreak Elbow Connector
550-10
DESCRIPTION
The Cooper Power Systems RTE®
Deadbreak Elbow connector is a
fully-shielded and insulated plug-in
termination for connecting underground
cable to transformers, switching
cabinets and junctions equipped with
deadbreak bushings. The elbow
connector and bushing comprise the
essential components of deadbreak
separable connections.
RTE deadbreak elbows are molded
using high quality peroxide-cured
EPDM insulation. Standard features
include a copperTop connector, tin
plated copper probe, stainless steel
reinforced pulling-eye, and a capacitive test point.
Cable ranges are sized to accept a
wider range of cable diameter for a
given size elbow. The wider cable
ranges increase installation flexibility.
The CopperTop compression
connector is a standard item to
transition from the cable to the probe.
An aluminum crimp barrel is inertiawelded to a copper lug. The aluminum
barrel makes the connector easy to
crimp and the copper lug ensures a
reliable, tight, cool operating connection with the deadbreak probe.
INSTALLATION
Cable stripping and scoring tools,
available from various tool manufacturers, are recommended for use
when installing deadbreak elbows.
After preparing the cable, the elbow
housing is pushed onto the cable.
The probe is threaded into the coppertop connector using the supplied
installation tool. A spring-loaded bail
is also included to assure a safe, reliable connection.
Figure 1.
15/25 kV Deadbreak Elbow Connector.
PRODUCTION TESTS
Tests conducted in accordance with
ANSI/IEEE Standard 386:
■ ac 60 Hz 1 Minute Withstand
–40 kV
■ Minimum Corona Voltage Level
–19 kV
■ Test Point Voltage Test
TABLE 1
Voltage Ratings and Characteristics
Description
Standard Voltage Class
Maximum Rating Phase-to-Phase
Maximum Rating Phase-to-Ground
ac 60 Hz 1 Minute Withstand
dc 15 Minute Withstand
BIL and Full Wave Crest
Minimum Corona Voltage Level
kV
25
26.3
15.2
40
78
125
19
Tests are conducted in accordance
with Cooper Power Systems
requirements:
■ Physical Inspection
■ Periodic Dissection
■ Periodic Fluoroscopic Analysis
TABLE 2
Current Ratings and Characteristics
Description
Continuous
Short Time
Amperes
200 A rms
10,000 A rms symmetrical
for 0.17 s
3,500 A rms symmetrical
for 3.0 s
Current ratings and characteristics are in
accordance with ANSI/IEEE Standard 386.
Voltage ratings and characteristics are in
accordance with ANSI/IEEE Standard 386.
November 1997 • Supersedes 7/97
Printed in U.S.A.
1
1250 A Connecting
Plug
DPC612
1250 A, 24 kV Class
Electrical Apparatus
I550-51
APPLICATION
■
Connects two or more 1250 A bolted tee connectors
for use as a separable cable joint or for connection of
multiple cables to an apparatus bushing.
■
For system voltage (Um) of 24 kV.
■
Continuous current 1250 A (1800 A overload for 8
hours).
■
For indoor and outdoor installation.
FEATURES
■
Provides a fully screened and fully submersible
connection when mated with tee connectors.
■
Copper current carrying parts.
■
Moulded EPDM insulation.
■
Moulded semi-conductive EPDM collar maintains
screen continuity.
■
100% factory tested.
STANDARDS
Figure 1.
DPC612 Connecting Plug.
■
Interfaces meet the requirements of CENELEC HD
506 S1 and ANSI/IEEE 386.
QUALITY
INSTALLATION
■
Threaded connections mate with the clamping screw
of the tee connectors.
■
A 10 mm hex key and torque wrench are required for
installation.
■
Typical arrangements and dimensions are shown on
the following pages.
PACKAGING
■
Complete kit includes installation instructions and
silicone lubricant.
ORDERING INFORMATION
Specify DPC612.
July 1999 • New Issue
Printed in U.S.A.
■
Manufacturing facility is registered to ISO-9001-1994
by third party audit.
■
Routine tests.
■
X-ray audit of random samples.
TABLE A
Electrical Ratings
Catalog Number
Maximum
System Voltage (Um)
Partial Discharge
Extinction (<3 pC) *
Impulse Withstand
AC Withstand *
Continuous Current
Overload (8 hrs.)
Short Circuit
Withstand, 1 sec (rms sym)
* Denotes routine tests on 100% of production.
DPC608
24 kV
20 kV
125 kV
54 kV
1250 A
1800 A
75 kA
1
P.O. Box 1640
Waukesha, WI 53187
www.cooperpower.com
© 1999 Cooper Industries, Inc.
MI
Printed on Recycled Paper
7/99
1250 A Deadbreak
Tee Connector (M16)
DT612
1250 A, 24 kV Class
Electrical Apparatus
I550-50
APPLICATION
■
For connection of polymeric cable to transformers,
switchgear, motors, and other equipment with a
premoulded separable connector.
■
For indoor and outdoor installation.
■
Continuous current 1250 A (1800 A overload for
8 hours).
■
For system voltage (Um) to 24 kV .
■
Conductor size:
■
An optional adapter kit is available for use with
PILC cables.
12 kV 70-630 mm2
24 kV 25-630 mm2
FEATURES
Figure 1.
DT612 Deadbreak Tee Connector.
■
Provides a fully screened and fully submersible
connection when mated with the proper bushing or
plug.
■
Optional capacitive test point allows for an easy
check of the circuit status or installation of a fault
indicator.
■
No minimum phase clearance requirements.
■
Mounting can be vertical, horizontal, or any angle in
between.
■
100% factory tested.
STANDARDS
■
Meets the requirements of CENELEC HD 629.1 S1,
IEC 60502-4, and ANSI/IEEE 386.
QUALITY
■
Manufacturing facility is registered to ISO-9001-1994
by third party audit.
RELATED PRODUCTS
■
DPC612 Connecting Plug
■
Routine tests.
■
DRC600 Receptacle Cap
■
X-ray audit of random samples.
■
DPS600 Standoff Plug
■
DPE600 Earthing Plug
■
DPR600 Reducing Tap Plug
INSTALLATION
■
No special tools, heating, taping, or potting are
required.
■
Connector may be energised immediately after
installation on its mating part.
■
Mates with bushings, plugs, and junction devices
complying with the listed standards.
TABLE A
Electrical Ratings
Maximum
System Voltage (Um)
Partial Discharge
Extinction (<3 pC)*
Impulse Withstand
AC Withstand*
Continuous Current
Overload (8 hrs.)
Short Circuit
Withstand, 1 sec. (rms sym.)
24 kV
20 kV
125 kV
54 kV
1250 A
1800 A
75 kA
*Denotes routine tests on 100% of production.
July 1999 • Supersedes 5/98
Printed in U.S.A.
1
Features and Detailed Description
3. Basic Insulating Plug
4
3
2
1
Moulded epoxy part has a threaded metal insert
to accept the clamping screw.
4. Capacitive Test Point
Capacitive test point provides means to check
circuit status.
5. Rubber Cap
5
12
6
Moulded EPDM semi-conducting rubber cap
protects and earths the test point during normal
operation.
6. Internal Screen
7
11
10
Moulded EPDM semi-conducting rubber screen
controls electrical stress.
7. Capacitive Test Point (Optional)
Provides a means to mount a fault indicator or a
voltage indicator. A moulded semi-conducting
EPDM rubber cap earths the test point when not
in use.
8
9
8. Built-in Stress Relief
The configuration of the external screen and the
cable adapter provides cable stress relief.
9. Cable Adapter
The sized opening maintains a watertight seal on
the cable and provides the initial cable stress
relief.
Figure 2.
1250 A, 24 kV Class DT612 Deadbreak Tee Connector
10. Earthing Eyes
Moulded into the external screen for connection
of one or more earthing wires.
1. Clamping Screw (M16)
Tin-plated copper stud and nut secure the contact to the bushing.
11. External Screen
Moulded semi-conducting EPDM rubber maintains screen continuity and ensures that the
assembly is at earth potential.
2. Insulation
Moulded EPDM insulating rubber is formulated
and mixed in-house to ensure high quality.
2
12. Conductor Contact
Compression connector accepts copper or
aluminum conductors.
I550-50
86 mm
DT612
DEADBREAK
246 mm
82 mm
82 mm
105 mm
275 mm
300 mm
Figure 3.
DT612 Deadbreak Tee Connector.
ORDERING INFORMATION
The ordering formula is DT612-R-C. Substitute for R
and C as follows. Select the range from Table R that fits
the diameter of the core insulation. Select the code from
Table C for the conductor size and type of compression
connector required.
Cable seal adapters are ordered separately.
TABLE C
Conductor Code
TABLE R
Core Insulation Range
Insulation Range
Designation
Ordering Example: For 20 kV cable, 240 mm2 aluminum conductor, 31.0 mm core insulation diameter,
DIN connector, specify DT612-F-240.
Core Insulation Range (mm)
Minimum
Maximum
A
16.3
Stranded Conductor
Size (mm2)
DIN
type
EDF
type
DIN
All Copper
19.3
25
25
E25
C25
35
E35
C35
B
18.3
21.5
35
C
19.9
24.6
50
50
E50
C50
D
23.1
27.1
70
70
E70
C70
29.0
95
95
E95
C95
120
E120
C120
C150
E
24.9
F
27.4
32.5
120
G
31.0
36.1
150
150
E150
H
34.5
39.6
185
185
E185
C185
240
E240
C240
J
37.6
43.2
240
K
41.6
46.7
300
300
E300
C300
L
45.2
49.9
400
400
E400
C400
500
500
E500
C500
E630
C630
630
Optional Test Point
If a test point on the tee body is required, add a “T”
before the insulation range designation.
Example: DT612TF240
P.O. Box 1640
Waukesha, WI 53187
www.cooperpower.com
© 1999 Cooper Industries, Inc.
MI
Printed on Recycled Paper
7/99
3
800 A Deadbreak
Junctions
DJ608
800 A, 24 kV Class
Electrical Apparatus
I550-43
APPLICATION
■
For connection of two, three, or four 800 A premoulded
tee connectors to form a separable cable joint.
■
For indoor or outdoor applications.
■
For use in submerged vaults, surface applications,
and with aerial cables.
■
System voltage to 24 kV.
■
Continuous current 800 A (900 A overload for 8 hours).
■
For de-energised operation.
FEATURES
Figure 1.
DJ608 Deadbreak Junctions.
■
Available in two, three, and four way configurations.
■
Stainless steel mounting brackets are available as an
option.
■
Provides a fully screened and fully submersible
separable connection when mated with the tee
connectors.
■
No minimum phase spacing requirements.
■
100% factory tested.
STANDARDS
■
RELATED PRODUCTS
■
DT608 Tee Connector
■
DRC600 Receptacle Cap
INSTALLATION
■
No special tools, heating, taping, or potting are
required.
■
Can be energised immediately after the mating parts
are secured.
PACKAGING
■
Supplied in single-phase kits.
August 1999 • New Issue
Printed in U.S.A.
Meets the requirements of CENELEC HD 629.1 S1,
IEC 60502-4, and ANSI/IEEE 386.
QUALITY ASSURANCE
■
Manufacturing facility is registered to ISO 9001-1994
by third party audit.
■
Routine Tests.
■
X-Ray audit of random samples.
TABLE A
Electrical Ratings
Maximum
System Voltage (Um)
Partial Discharge
Extinction (<3 pC) *
AC Withstand *
Impulse Withstand
Continuous Current
Overload (8 hrs.)
Short Circuit
Withstand, 1 sec (rms sym)
* Denotes routine tests on 100% of production.
24 kV
20 kV
54 kV
125 kV
800 A
900 A
48 kA
1
Features and Detailed Description
6
1
2
3
4
1. Threaded Contact
Threaded 5/8" aluminum contact. A stud is included
to mate with M16 DT608 tee connectors.
2. Busbar
Internal aluminum current-carrying part for low electrical resistance and high mechanical strength.
3. External Screen
Moulded semi-conductive EPDM rubber mates with
the screen of the connector to maintain screen continuity.
4. Insulation
Moulded EPDM rubber provides the phase-to-earth
insulation and forms the interface with the mating
connectors to maintain dielectric ratings and a
watertight seal.
5. Stainless Steel Mounting Bracket
Optional bracket is corrosion resistant and includes
parking pockets for standoff plugs or earthing
plugs.
6. Shipping Caps
The cap prevents contamination of the interface
during installation.
2
I550-43
102
A
186
132
B
14
107
36
15
Number of
Interfaces
2
3
4
50
C
A
360
585
685
Dimensions (mm)
B
170
270
375
50
C
375
490
630
ORDERING INFORMATION
Number of
Interfaces
2
3
4
Junction
Only
DJ608A2
DJ608A3
DJ608A4
Junction
with Bracket
DJ608A2B
DJ608A3B
DJ608A4B
All kits include junction, silicone lubricant, and installation
instructions
P.O. Box 1640
Waukesha, WI 53187
www.cooperpower.com
© 1999 Cooper Industries, Inc.
MI
Printed on Recycled Paper
8/99
3
800 A Connecting
Plug
DPC608
800 A, 24 kV Class
Electrical Apparatus
I550-41
APPLICATION
■
Connects two or more 800 A bolted tee connectors
for use as a separable cable joint or for connection of
multiple cables to an apparatus bushing.
■
For system voltage (Um) of 24 kV.
■
Continuous current 800 A (900 A overload for 8 hours).
■
For indoor and outdoor installation.
FEATURES
■
Provides a fully screened and fully submersible
connection when mated with tee connectors.
■
Aluminum current carrying parts.
■
Moulded EPDM insulation.
■
Moulded semi-conductive EPDM collar maintains
screen continuity.
■
100% factory tested.
STANDARDS
Figure 1.
DT608 Deadbreak Tee Connector.
■
Interfaces meet the requirements of CENELEC HD
506 S1 and ANSI/IEEE 386.
QUALITY
INSTALLATION
■
Threaded connections mate with the clamping screw
of the tee connectors.
■
Manufacturing facility is registered to ISO-9001-1994
by third party audit.
■
Routine tests.
X-ray audit of random samples.
■
A 10 mm hex key and torque wrench are required for
installation.
■
■
Typical arrangements and dimensions are shown on
the following pages.
TABLE A
Electrical Ratings
PACKAGING
■
Complete kit includes installation instructions and
silicone lubricant.
ORDERING INFORMATION
Specify DPC608.
Catalog Number
Maximum
System Voltage (Um)
Partial Discharge
Extinction (<3 pC)*
AC Withstand*
Impulse Withstand
Continuous Current
Overload (8 hrs max.)
Short Circuit
Withstand, 1 sec. (rms sym.)
DPC608
24 kV
20 kV
54 kV
125 kV
800 A
900 A
48 kA
*Denotes routine tests on 100% of production.
June 1999 • Supersedes 8/96• © 1999 Cooper Industries, Inc.
Printed in U.S.A.
1
P.O. Box 1640
Waukesha, WI 53187
www.cooperpower.com
Printed on Recycled Paper
MI
6/99
800 A Deadbreak
Tee Connector (M16)
DT608
800 A, 24 kV Class
Electrical Apparatus
I550-40
APPLICATION
■
For connection of polymeric cable to transformers,
switchgear, motors, and other equipment with a
premoulded separable connector.
■
For indoor and outdoor installation.
■
Continuous current 800 A (900 A overload for 8 hours).
■
For system voltage (Um) to 24 kV.
■
Conductor size:
12 kV 70-630 mm2
24 kV 25-630 mm2
■ An optional adapter kit is available for use with PILC
cables.
FEATURES
■
Provides a fully screened and fully submersible
connection when mated with the proper bushing or
plug.
■
Optional capacitive test point on moulded connector
allows for an easy check of the circuit status or
installation of a fault indicator.
■
No minimum phase clearance requirements.
■
Mounting can be vertical, horizontal, or any angle in
between.
■
100% factory tested.
STANDARDS
Figure 1.
DT608 Deadbreak Tee Connector.
■
Meets the requirements of CENELEC HD 629.1 S1,
IEC 60502-4, and ANSI/IEEE 386.
QUALITY
■
Manufacturing facility is registered to ISO-9001-1994
by third party audit.
RELATED PRODUCTS
■
Routine tests.
■
DPC608 Connecting Plug
■
X-ray audit of random samples.
■
DRC600 Receptacle Cap
■
DPS600 Standoff Plug
■
DPE600 Earthing Plug
■
DPR600 Reducing Tap Plug
INSTALLATION
■
No special tools, heating, taping, or potting are
required.
■
Connector may be energised immediately after
installation on its mating part.
■
Mates with bushings, plugs, and junction devices
complying with the listed standards.
July 1999 • Supersedes 8/96
Printed in U.S.A.
TABLE A
Electrical Ratings
Maximum
System Voltage (Um)
Partial Discharge
Extinction (<3 pC)*
Impulse Withstand
AC Withstand*
Continuous Current
Overload (8 hrs)
Short Circuit
Withstand, 1 sec. (rms sym.)
24 kV
20 kV
125 kV
54 kV
800 A
900 A
48 kA
*Denotes routine tests on 100% of production.
1
Features and Detailed Description
3. Basic Insulating Plug
4
3
2
1
Moulded epoxy part has a threaded metal insert
to accept the clamping screw.
4. Capacitive Test Point
Capacitive test point provides means to check
circuit status.
5. Rubber Cap
5
12
6
Moulded EPDM semi-conducting rubber cap
protects and earths the test point during normal
operation.
6. Internal Screen
7
11
10
Moulded EPDM semi-conducting rubber screen
controls electrical stress.
7. Capacitive Test Point (Optional)
Provides a means to mount a fault indicator or a
voltage indicator. A moulded semi-conducting
EPDM rubber cap earths the test point when not
in use.
8
9
8. Built-in Stress Relief
The configuration of the external screen and the
cable adapter provides cable stress relief.
9. Cable Adapter
The sized opening maintains a watertight seal on
the cable and provides the initial cable stress
relief.
Figure 2.
800 A, 24 kV Class DT608 Deadbreak Tee Connector
10. Earthing Eyes
Moulded into the external screen for connection
of one or more earthing wires.
1. Clamping Screw (M16)
Tin-plated aluminum stud and nut secure the
contact to the bushing.
11. External Screen
Moulded semi-conducting EPDM rubber
maintains screen continuity and ensures that the
assembly is at earth potential.
2. Insulation
Moulded EPDM insulating rubber is formulated
and mixed in-house to ensure high quality.
2
12. Conductor Contact
Compression connector accepts copper or
aluminum conductors.
I550-40
86 mm
DT608
DEADBREAK
246 mm
82 mm
82 mm
105 mm
275 mm
300 mm
Figure 3.
DT608 Deadbreak Tee Connector.
ORDERING INFORMATION
The ordering formula is DT608-R-C. Substitute for R
and C as follows. Select the range from Table R that fits
the diameter of the core insulation. Select the code from
Table C for the conductor size and type of compression
connector required.
Cable seal adapters are ordered separately.
TABLE C
Conductor Code
TABLE R
Core Insulation Range
Insulation Range
Designation
Ordering Example: For 20 kV cable, 240 mm2 aluminum
conductor, 31.0 mm core insulation diameter, DIN
connector, specify DT608-F-240.
Core Insulation Range (mm)
Minimum
Maximum
A
16.3
Stranded Conductor
Size (mm2)
DIN
type
EDF
type
DIN
All Copper
19.3
25
25
E25
C25
35
E35
C35
B
18.3
21.5
35
C
19.9
24.6
50
50
E50
C50
D
23.1
27.1
70
70
E70
C70
29.0
95
95
E95
C95
120
E120
C120
C150
E
24.9
F
27.4
32.5
120
G
31.0
36.1
150
150
E150
H
34.5
39.6
185
185
E185
C185
240
E240
C240
J
37.6
43.2
240
K
41.6
46.7
300
300
E300
C300
L
45.2
49.9
400
400
E400
C400
500
500
E500
C500
E630
C630
630
Optional Test Point
If a test point on the tee body is required, add a “T”
before the insulation range designation.
Example: DT608TF240
P.O. Box 1640
Waukesha, WI 53187
www.cooperpower.com
© 1999 Cooper Industries, Inc.
MI
Printed on Recycled Paper
7/99
3
630 A Deadbreak
Bolted Tee Connector
Electrical Apparatus
I550-37
DTB624 – 24 kV Applications
APPLICATION
„
„
„
„
„
„
For connection of polymeric cable to transformers,
switchgear, motors and other equipment with a
premoulded separable connector.
For indoor and outdoor installations.
System voltage up to 24 kV.
Continuous current 630 A (900 A overload for 8 hours).
Cable particulars:
–Polymeric cable (XLPE, EPR, etc.)
–Copper or aluminum conductors
–Semiconducting or metallic screens
Conductor size:
12 kV 70-400 mm2
24 kV 25-400 mm2
FEATURES
„
„
„
„
„
Provides a fully screened and fully submersible
separable connection when mated with the proper
bushing or plug.
Built-in capacitive test point allows for an easy check
of the circuit status or installation of a fault indicator.
No minimum phase clearance requirements.
Mounting can be vertical, horizontal, or any angle in
between.
100% factory tested.
STANDARDS
„
Meets the requirements of IEC 60502-4 and
CENELEC HD 629.1 S2.
QUALITY ASSURANCE
Figure 1.
630 A Deadbreak Bolted Tee Connector.
„
„
„
Our manufacturing facility is registered to
ISO 9001-2000 by third party audit.
Required Production Tests
Periodic X-Ray Analysis
RELATED PRODUCTS
PACKAGING
„
„
DRC400 Receptacle Cap
INSTALLATION
„
„
„
No special tools, heating, taping, or potting are required.
Connector may be energised immediately after
installation on its mating part.
Mates with bushings, plugs, and junction devices
complying with the listed standards.
Supplied in a kit with all necessary parts, approximate
weight 3 kg.
TABLE A
Electrical Ratings
DTB624
Maximum System Voltage (Um)
24 kV
Impulse
125 kV
AC Withstand (5 min.)
54 kV
Continuous Current
630 A
Overload (8 hrs. Max.)
900 A
Short Circuit Withstand, 1 sec.
(rms sym)
35 kA
Note: Ratings are based on IEC Standards and do net reflect
maximum capability.
February 2007 • New Issue
Printed in U.S.A.
1
DTB624 - 24 kV Applications
Features and Detailed Description
1. Clamping Screw and Connecting Rod
3
1
Tin-plated copper screw secures the conductor
contact to the bushing.
2. Insulation
Moulded EPDM insulating rubber is formulated and
mixed in-house to ensure high quality.
4
3. Basic Insulating Plug
5
12
6
2
11
7
4. Capacitive Test Point
Capacitive test point provides means to check
circuit status.
5. Rubber Cap
10
8
Moulded epoxy part has a threaded metal insert to
accept the clamping screw.
8
Moulded EPDM conducting rubber cap protects
and earths the test point during normal operation.
6. Internal Screen
Moulded EPDM conducting rubber screen controls
electrical stress.
9
7. Capacitive Test Point (Optional)
Provides a means to mount a fault indicator. A
moulded EPDM conducting rubber cap provides a
watertight seal.
8. Stress Relief
The configuration of the outer screen and the cable
adapter provide cable stress relief.
9. Cable Adapter
The sized opening provides an interference fit to
maintain a watertight seal and provides the initial
cable stress relief.
10. Earthing Eyes
Moulded into the external screen for connection of
an earthing wire.
11. External Screen
Moulded EPDM conducting rubber mates with the
cable screen to maintain screen continuity and
ensure that the assembly is at earth potential.
12. Conductor Contact
Figure 2.
630 A, 24 kV Class DTB624 Deadbreak Tee Connector.
2
Inertia welded bimetallic compression connector
accepts copper or aluminum conductors.
I550-37
179 mm
135 mm
109 mm
341 mm
Figure 3.
DTB624 Deadbreak Tee Connector dimensional information.
KIT CONTENTS
Optional Test Point
The complete kit includes 1 each moulded tee housing,
cable adapter, conductor contact, connecting rod,
clamping screw, silicone lubricant, and installation
instructions.
If a test point on the tee body is required, add a “T” at the
end of the catalog number.
Example: DTB624F240T
NOTE: The insulating plug and rubber cap are supplied
with the mating DTS624 tee connector.
Ordering Example: For 20 kV cable, 240 mm2
aluminum conductor, 31.0 mm core insulation diameter,
DIN connector, specify DTB624F240.
ORDERING INFORMATION
Cable seal adapters are ordered separately.
The complete catalog number for the tee connector is
DTB624RC.
TABLE C
Conductor Code
R is the cable range designation and C is the conductor
contact code. Select the cable range designation from
Table R. Select the conductor contact code from Table C
for the conductor size and type of connector required.
TABLE R
Cable Insulation Range
Insulation Range
Cable Insulation Range Ø (mm)
Designation
Min.
Max.
Stranded Conductor
Size (mm2)
DIN
Type
EDF
Type
DIN
All Copper
25
25
E25
C25
35
35
E35
C35
50
50
E50
C50
70
70
E70
C70
95
95
E95
C95
120
E120
C120
AA
13.5
17.2
120
A
16.3
19.3
150
150
E150
C150
185
E185
C185
B
18.3
21.0
185
C
20.0
24.1
240
240
E240
C240
D
23.1
27.0
300
300
-
C300
400
400
-
C400
E
24.9
28.9
F
27.7
32.6
G
30.9
36.2
H
34.0
39.5
NOTE: Bimetallic connectors can be used with aluminum or
copper conductors.
3
DTB624 - 24 kV Applications
© 2007 Cooper Power Systems, Inc., or its affiliates
1045 Hickory Stret
Pewaukee, WI 53072 USA
www.cooperpower.com
630 A Deadbreak
Bolted Tee Connector
Electrical Apparatus
I550-36
DTS624 – 24 kV Applications
APPLICATION
„
„
„
„
„
„
For connection of polymeric cable to transformers,
switchgear, motors and other equipment with a
premoulded separable connector.
For indoor and outdoor installations.
System voltage up to 24 kV.
Continuous current 630 A (900 A overload for 8 hours).
Cable particulars:
–Polymeric cable (XLPE, EPR, etc.)
–Copper or aluminum conductors
–Semiconducting or metallic screens
Conductor size:
12 kV 70-400 mm2
24 kV 25-400 mm2
FEATURES
„
„
„
„
„
Provides a fully screened and fully submersible
separable connection when mated with the proper
bushing or plug.
Built-in capacitive test point allows for an easy check
of the circuit status or installation of a fault indicator.
No minimum phase clearance requirements.
Mounting can be vertical, horizontal, or any angle in
between.
100% factory tested.
STANDARDS
„
Meets the requirements of IEC 60502-4 and
CENELEC HD 659.1 S2.
QUALITY ASSURANCE
Figure 1.
630 A Deadbreak Bolted Tee Connector.
„
„
„
Our manufacturing facility is registered to
ISO 9001-2000 by third party audit.
Required Production Tests
Periodic X-Ray Analysis
RELATED PRODUCTS
PACKAGING
„
„
DRC400 Receptacle Cap
INSTALLATION
„
„
„
No special tools or heating are required.
Connector may be energised immediately after
installation on its mating part.
Mates with bushings, plugs, and junction devices
complying with the listed standards.
Supplied in a kit with all necessary parts, approximate
weight 3 kg.
TABLE A
Electrical Ratings
DTS624
Maximum System Voltage (Um)
24 kV
Impulse
125 kV
AC Withstand (5 min.)
54 kV
Continuous Current
630 A
Overload (8 hrs. Max.)
900 A
Short Circuit Withstand, 1 sec.
(rms sym)
35 kA
Note: Ratings are based on IEC Standards and do not reflect maximum
capability.
February 2007 • New Issue
Printed in U.S.A.
1
DTS624 - 24 kV Applications
Features and Detailed Description
1. Clamping Screw
1
3
Tin-plated copper screw secures the conductor
contact to the bushing.
2. Insulation
Moulded EPDM insulating rubber is formulated and
mixed in-house to ensure high quality.
4
3. Basic Insulating Plug
5
12
6
11
2
Moulded epoxy part has a threaded metal insert to
accept the clamping screw.
4. Capacitive Test Point
Capacitive test point provides means to check
circuit status.
5. Rubber Cap
7
10
Moulded EPDM conducting rubber cap protects
and earths the test point during normal operation.
6. Internal Screen
9
8
Moulded EPDM conducting rubber screen controls
electrical stress.
7. Capacitive Test Point (Optional)
Provides a means to mount a fault indicator. A
moulded EPDM conducting rubber cap provides a
watertight seal.
8. Stress Relief
The configuration of the outer screen and the cable
adapter provide cable stress relief.
9. Cable Adapter
The sized opening provides an interference fit to
maintain a watertight seal and provides the initial
cable stress relief.
10. Earthing Eyes
Moulded into the external screen for connection of
an earthing wire.
11. External Screen
Moulded EPDM conducting rubber mates with the
cable screen to maintain screen continuity and
ensure that the assembly is at earth potential.
12. Conductor Contact
Figure 2.
630 A, 24 kV Class DTS624 Deadbreak Tee Connector.
2
Inertia welded bimetallic compression connector
accepts copper or aluminum conductors.
I550-36
196 mm
108 mm
341 mm
Figure 3.
DTS624 Deadbreak Tee Connector dimensional information.
KIT CONTENTS
Optional Test Point
The complete kit includes 1 each moulded tee housing,
cable adapter, conductor contact, insulating plug, rubber
cap, clamping screw, silicone lubricant, and installation
instructions.
If a test point on the tee body is required, add a “T” at the
end of the catalog number.
Example: DTS624F240T
Ordering Example: For 20 kV cable, 240 mm2
aluminum conductor, 31.0 mm core insulation diameter,
DIN connector, specify DTS624F240.
ORDERING INFORMATION
The complete catalog number for the tee connector is
DTS624RC.
R is the cable range designation and C is the conductor
contact code. Select the cable range designation from
Table R. Select the conductor contact code from Table C
for the conductor size and type of connector required.
TABLE R
Cable Insulation Range
Insulation Range
Cable Insulation Range Ø (mm)
Designation
Min.
Max.
Cable seal adapters are ordered separately.
TABLE C
Conductor Code
Stranded Conductor
Size (mm2)
DIN
Type
EDF
Type
DIN
All Copper
25
25
E25
C25
35
35
E35
C35
50
50
E50
C50
70
E70
C70
AA
13.5
17.2
70
A
16.3
19.3
95
95
E95
C95
B
18.3
21.0
120
120
E120
C120
150
E150
C150
C
20.0
24.1
150
D
23.1
27.0
185
185
E185
C185
240
E240
C240
E
24.9
28.9
240
F
27.7
32.6
300
300
-
C300
G
30.9
36.2
400
400
-
C400
H
34.0
39.5
NOTE: Bimetallic connectors can be used with aluminum or
copper conductors.
3
DTS624 - 24 kV Applications
© 2007 Cooper Power Systems, Inc., or its affiliates
4
1045 Hickory Stret
Pewaukee, WI 53072 USA
www.cooperpower.com
630 A Apparatus
Bushings
Cooper Power Systems
Electrical Apparatus
DB630 – 24 for 24 kV Applications
DB630 – 36 for 36 kV Applications
I550-35
APPLICATION
■
For oil-insulated (R-temp, hydrocarbon, or silicon)
apparatus, including switchgear, transformers, and
capacitors.
■
System voltage (Um) of 24 kV and 36 kV.
■
Continuous Current 630 A.
■
For indoor and outdoor installations.
■
Mounting in vertical or horizontal position.
STANDARDS
■
Meets the interface requirements of DIN 47636,
EDF C33-051, CENELEC HD 506 S1, and others.
■
Has been tested with mating parts to IEC 60502-4
and CENELEC HD 629.1 51.
QUALITY
■
100% Production Tests
■
Periodic X-Ray Analysis
TABLE A
Electrical Ratings
DB630-24
Maximum
System Voltage (Um)
Impulse Withstand
AC Withstand
Continuous Current
Overload (8 hrs Max.)
Short Circuit Withstand
1 sec. (rms sym.)
DB630-36
24 kV
125 kV
54 kV
630 A
900 A
36 kV
170 kV
81 kV
630 A
900 A
35 kA
35 kA
Figure 1.
DB630 Deadbreak Apparatus Bushing.
RELATED PRODUCTS
■
Mates with the following products of the same voltage
rating:
DT400 Tee
DT436 Tee
DRC400 Receptacle Cap
DRC436 Receptacle Cap
PACKAGING
■
Supplied in a box of three, approximate weight 12 kg.
October 1997 • New Issue • © 1997 Cooper Power Systems, Inc.
Printed in U.S.A.
1
Features and Detailed Description
1. Threaded Contact
➀
M16
M16 thread accepts the clamping screw of the
mating part.
➁
2. Interface
40
The interference fit between the bushing and the
connector prevents the entrance of moisture and
contamination.
133
➂
3. Shipping Cap
➃
330
The cap prevents contamination of the interface
before energization.
4. Internal Screen
10
The screen controls electrical stress. An earthing
plate for connection to the screen is supplied.
Ø87
5. Central Conductor
Ø128
147
The copper conductor has an M16 thread for the
apparatus connection.
6. Moulded Epoxy Resin Body
➅
➄
41
“X”
M16
OIL
LEVEL
Dimensions in mm
Figure 2.
Section View DB630 Bushing.
Voltage (kV)
12
24
36
ORDERING INFORMATION
To order, simply specify:
DB630-24 for 24 kV applications
DB630-36 for 36 kV applications.
Clamping devices and gaskets are ordered separately,
as shown below:
X (mm)
40
50
70
Figure 3.
Minimum oil level.
TABLE B
Clamping Devices and Gaskets
Type of Clamp
DIN 42538
NFC 52-453
Catalog Number
BC-D-400-630
BC-N-400-630
Cooper Power Systems
P.O. Box 1640, Waukesha, WI 53187
www.cooperpower.com
Quality from
Cooper Industries
2
MI
Printed on Recycled Paper
10/97 2M
630 A Connecting
Plug
DPC400 - 24 kV Applications
DPC436 - 36 kV Applications
Electrical Apparatus
I550-31
APPLICATION
■
Connects two or more 630 A bolted tee connectors
for use as a separable cable joint or for connection of
multiple cables to an apparatus bushing.
■
For system voltages (Um) of 24 kV and 36 kV.
■
Continuous current 630 A (900 A overload for 8 hours).
■
For indoor and outdoor installation.
FEATURES
Figure 1.
630 A Connecting Plug.
■
Provides a fully screened and fully submersible
connection when mated with tee connectors.
■
Copper current carrying parts.
■
Moulded EPDM insulation.
■
Moulded semi-conductive EPDM collar maintains
screen continuity.
■
100% factory tested.
STANDARDS
■
INSTALLATION
■
Threaded connections mate with the clamping screw
of the tee connectors.
■
A 10 mm hex key and torque wrench are required for
installation.
■
Typical arrangements and dimensions are shown on
the following pages.
PACKAGING
■
Complete kit includes installation instructions and
silicone lubricant.
ORDERING INFORMATION
For 24 kV applications, specify DPC400.
For 36 kV applications, specify DPC436.
Interfaces meet the requirements of CENELEC HD
506 S1, and other major standards.
QUALITY
■
Manufacturing facility is registered to ISO-9001-1994
by third party audit.
■
Routine Tests.
■
X-Ray Audit of random samples.
TABLE A
Electrical Ratings
Catalog Number
Maximum
System Voltage (Um)
Partial Discharge
Extinction (<3 pC)*
Impulse Withstand
AC Withstand*
Continuous Current
Overload (8 hrs.)
Short Circuit
Withstand, 1 sec (rms sym)
DPC400
DPC436
24 kV
36 kV
20 kV
125 kV
54 kV
630 A
900 A
30 kV
170 kV
81 kV
630 A
900 A
35 kA
35 kA
*Denotes routine tests on 100% of production.
August 1999 • New Issue
Printed in U.S.A.
1
P.O. Box 1640
Waukesha, WI 53187
www.cooperpower.com
© 1999 Cooper Industries, Inc.
MI
Printed on Recycled Paper
8/99
630 A Deadbreak
Bolted Tee Connector
Electrical Apparatus
DT400 - 24 kV Applications
DT436 - 36 kV Applications
I550-30
APPLICATION
For connection of polymeric cable to transformers,
switchgear, motors and other equipment with a
premoulded separable connector.
For indoor and outdoor installations.
System voltage up to 36 kV.
Continuous current 630 A (900 A overload for 8 hours).
Cable particulars:
- Polymeric cable (XLPE, EPR, etc.)
- Copper or aluminum conductors
- Semiconducting or metallic screens
Conductor size: 12 kV 70-400 mm2
24 kV 25-400 mm2
36 kV 25-240 mm2
FEATURES
Figure 1.
630 A Deadbreak Bolted Tee Connector.
RELATED PRODUCTS
DPC400/DPC436 Connecting Plug
DRC400/DRC436 Receptacle Cap
INSTALLATION
No special tools, heating, taping, or potting are
required.
Connector may be energised immediately after
installation on its mating part.
Mates with bushings, plugs, and junction devices
complying with the listed standards.
Provides a fully screened and fully submersible
separable connection when mated with proper bushing
or plug.
Built-in capacitive test point allows for an easy check of
the circuit status or installation of a fault indicator.
No minimum phase clearance requirements.
Mounting can be vertical, horizontal, or any angle in
between.
100% factory tested.
AC withstand
Partial Discharge
STANDARDS
Meets the requirements of Cenelec HD629.1 S2 and
IEC 60502-4.
QUALITY ASSURANCE
Our manufacturing facility is registered to
ISO 9001-2000 by third party audit.
Required Production Tests
Periodic X-Ray Analysis
PACKAGING
Supplied in a kit with all necessary parts, approximate
weight 3 kg.
TABLE A
Electrical Ratings
February 2007 • Supersedes 08/96
DT400
DT436
Maximum
System Voltage (Um)
24 kV
36 kV
Impulse
125 kV
170 kV
AC Withstand (5 min.)
54 kV
81 kV
Continuous Current
630 A
630 A
Overload (8 hrs. Max.)
900 A
900 A
Short Circuit
Withstand, 1 sec (rms sym)
35 kA
35 kA
1
Features and Detailed Description
1. Clamping Screw
4
3
2
Tin-plated copper screw secures the conductor
contact to the bushing.
1
2. Insulation
Moulded EPDM insulating rubber is formulated
and mixed in-house to ensure high quality.
3. Basic Insulating Plug
Moulded epoxy part has a threaded metal insert
to accept the clamping screw.
4. Capacitive Test Point
Capacitive test point provides means to check
circuit status.
5. Rubber Cap
12
5
6
Moulded EPDM conducting rubber cap
protects and earths the test point during normal
operation.
6. Internal Screen
11
7
Moulded EPDM conducting rubber screen
controls electrical stress.
7. Capacitive Test Point (Optional)
Provides a means to mount a fault indicator. A
moulded EPDM conducting rubber cap earths
the test point when not in use.
8. Stress Relief
10
The configuration of the outer screen and the
cable adapter provide cable stress relief.
9. Cable Adapter
The sized opening provides an interference fit to
maintain a watertight seal and provides the initial
cable stress relief.
8
10. Earthing Eyes
9
Moulded into the external screen for connection
of an earthing wire.
11. External Screen
Moulded EPDM conducting rubber mates with
the cable screen to maintain screen continuity
and ensure that the assembly is at earth
potential.
12. Conductor Contact
Inertia welded bimetallic compression connector
accepts copper or aluminum conductors.
Figure 2.
630 A - 24 and 36 kV Class Deadbreak Tee Connector.
2
I550-30
86
257*
75
DT400
24 kV
109
262
80
287
Dimensions in mm
* Add 100 mm to disconnect
Figure 3.
DT400/DT436 Deadbreak Tee Connector dimensional information.
KIT CONTENTS
Optional Test Point
The complete kit includes 1 each moulded tee housing,
cable adapter, conductor contact, insulating plug, rubber
cap, clamping screw, silicone lubricant, and installation
instructions.
If a test point on the tee body is required, add a “T” before
the insulation range designation.
ORDERING INFORMATION
For 24 kV the complete catalog number for the tee
connector is DT400RC.
For 36 kV, the complete catalog number for the tee
connector is DT436RC.
R is the cable range designation and C is the conductor
contact code. Select the cable range designation from
Table R. Select the conductor contact code from Table C
for the conductor size and type of connector required.
Table R
Cable Insulation Range
Insulation Range
Designation
Cable Insulation Range Ø (mm)
Min.
Max.
A
16.3
19.3
B
18.3
21.0
C
20.0
24.1
D
23.1
27.0
E
24.9
28.9
F
27.7
32.6
G
30.9
36.2
H
34.0
39.5
Example: DT400TF240
Ordering Example: For 20 kV cable, 240 mm2 aluminum
conductor, 31.0 mm core insulation diameter, DIN
connector, specify DT400F240.
Cable seal adapters are ordered separately.
TABLE C
Conductor Code
Stranded
Conductor
Size (mm2)
DIN Type
EDF Type
DIN
All Copper
25
25
E25
C25
35
35
E35
C35
50
50
E50
C50
70
70
E70
C70
95
95
E95
C95
120
120
E120
C120
150
150
E150
C150
185
185
E185
C185
240
240
E240
C240
300
300
-
C300
400
400
-
C400
NOTE: Bimetallic connectors can be used with aluminum
or copper conductors.
3
© 2007 Cooper Power Systems, Inc., or its affiliates
1045 Hickory Street
Pewaukee, WI 53072 USA
www.cooperpower.com
400 A Apparatus
Bushings
Cooper Power Systems
Electrical Apparatus
DB400 – 24 for 24 kV Applications
DB400 – 36 for 36 kV Applications
I550-25
APPLICATION
■
For oil-insulated (R-temp, hydrocarbon, or silicon)
apparatus, including switchgear, transformers, and
capacitors.
■
System voltages of 24 kV and 36 kV.
■
Continuous Current 400 A.
■
For indoor and outdoor installations.
■
Mounting in vertical or horizontal position.
STANDARDS
■
Meets the interface requirements of
CENELEC HD 506 S1, DIN 47636, and EDF C33-051
and others.
■
Has been tested with mating parts to IEC 60502-4 and
CENELEC HD 629.1 S1.
QUALITY
■
100% Production Tests
■
Periodic X-Ray Analysis
TABLE A
Electrical Ratings
DB400-24
Maximum
System Voltage (Um)
Impulse Withstand
AC Withstand
Continuous Current
Overload (8 hrs Max.)
Short Circuit Withstand
1 sec. (rms sym.)
DB400-36
24 kV
125 kV
54 kV
400 A
600 A
36 kV
170 kV
81 kV
400 A
600 A
18 kA
18 kA
Figure 1.
DB400 Deadbreak Apparatus Bushing.
RELATED PRODUCTS
■
Mates with the following products of the same voltage
rating:
DE400 Elbow
DE436 Elbow
DT400P Plug-in Tee
DT436P Plug-in Tee
DRC400P Receptacle Cap DRC436P Receptacle Cap
PACKAGING
■
Supplied in a box of three, approximate weight 10 kg.
October 1997 • New Issue • © 1997 Cooper Power Systems, Inc.
Printed in U.S.A.
1
Features and Detailed Description
1. Contact
➀
Plated multi-point contact accepts the pin contact
of the mating connector.
➁
2. Interface
➂
132
The interference fit between the bushing and the
connector prevents the entrance of moisture and
contamination.
3. Shipping Cap
➃
The cap prevents contamination of the interface
before energization.
10
➄
Ø87
330
4. Bail Tabs
Attachment points for the bail of the mating
connector.
Ø128
5. Internal Screen
The screen controls electrical stress. An earthing
plate for connection to the screen is supplied.
➆
147
6. Central Conductor
The copper conductor has an M16 thread for the
apparatus connection.
➅
7. Moulded Epoxy Resin Body
41
M16
Dimensions in mm
Figure 2.
Section View DB400 Bushing
“X”
OIL
LEVEL
ORDERING INFORMATION
To order, simply specify:
DB400-24 for 24 kV applications
DB400-36 for 36 kV applications.
Clamping devices and gaskets are ordered separately,
as shown below:
TABLE B
Clamping Device and Gaskets
Type of Clamp
DIN 42538
NFC 52-453
Voltage (kV)
12
24
36
X (mm)
40
50
70
Figure 3.
Minimum oil level.
Catalog Number
BC-D-400-630
BC-N-400-630
Cooper Power Systems
P.O. Box 1640, Waukesha, WI 53187
www.cooperpower.com
Quality from
Cooper Industries
2
MI
Printed on Recycled Paper
10/97 2M
I550-30
86
257*
75
DT400
24 kV
109
262
80
287
Dimensions in mm
*Add 100 mm to disconnect
Figure 3.
DT400 Deadbreak Tee Connector dimensional information.
Insulation Range
Designation
Cable Insulation Range Ø (mm)
Min.
Max.
Stranded Conductor
Size (mm2)
DIN
Type
EDF
Type
DIN
All Copper
A
16.3
19.3
25
25
E25
C25
B
18.3
21.0
35
35
E35
C35
24.1
50
50
E50
C50
27.0
70
70
E70
C70
C
D
20.0
23.1
E
24.9
28.9
95
95
E95
C95
F
27.7
32.6
120
120
E120
C120
G
30.9
36.2
150
150
E150
C150
39.5
185
185
E185
C185
240
240
E240
C240
300
300
–
C300
400
400
–
C400
H
34.0
3
400 A Deadbreak
Plug-in Tee Connector
Cooper Power Systems
Electrical Apparatus
DT400P – 24 kV Applications
DT436P – 36 kV Applications
I550-21
APPLICATION
■
For connection of polymeric cable to transformers,
switchgear, motors and other equipment with a
premoulded separable connector.
■ For indoor and outdoor installations.
■ System voltage up to 36 kV.
■ Continuous current 400 A (600 A overload for 8 hours).
■ Cable particulars:
–Polymeric cable (XLPE, EPR, etc.)
–Copper or aluminum conductors
–Semiconducting or metallic screens
■ Conductor size:
12 kV 70-400 mm2
24 kV 25-400 mm2
36 kV 25-240 mm2
■ An optional adapter kit is available for use with PILC
cables.
FEATURES
■
Provides a fully screened and fully submersible
separable connection when mated with the proper
bushing or plug.
■ Built-in capacitive test point allows for an easy check
of the circuit status or installation of a fault indicator.
■ No minimum phase clearance requirements.
■ Mounting can be vertical, horizontal, or any angle in
between.
■ 100% factory tested.
STANDARDS
Figure 1.
400 A Deadbreak Plug-in Tee Connector.
■
Will meet the requirements of VDE 0278, IEC 502-4,
EDF HN 52-5-61, BS 7215 and others.
QUALITY ASSURANCE
RELATED PRODUCTS
■
■
■
■
■
■
PACKAGING
DPC400 Connecting Plug
DRC400 Receptacle Cap
DPR400 Reducing Tap Plug
DPS400 Standoff Plug
DPE400 Earthing Plug
INSTALLATION
Our manufacturing facility is registered to
ISO 9001-1994 by third party audit.
■ Required Production Tests
■ Periodic X-Ray Analysis
■
Supplied in a kit with all necessary parts, approximate
weight 3 kg.
■
No special tools, heating, taping, or potting are
required.
■ Connector may be energised immediately after
installation on its mating part.
■ Mates with bushings, plugs, and junction devices
complying with the listed standards.
TABLE A
Electrical Ratings
Maximum
System Voltage (Um)
Impulse
AC Withstand (5 min.)
Continuous Current
Overload (8 hrs Max.)
Short Curcuit
Withstand, 1 sec. (rms sym.)
DT400P
DT436P
24 kV
125 kV
54 kV
400 A
600 A
36 kV
170 kV
81 kV
400 A
600 A
18 kA
18 kA
Note: Ratings are based on IEC Standards and do not reflect
maximum capability.
August 1996 • Supersedes 8/95 • © 1996 Cooper Power Systems, Inc.
Printed in U.S.A.
1
Features and Detailed Description
1. Pin Contact
➁
➀
➂
➃
Tin-plated copper contact screws into the conductor
contact.
2. Insulation
Moulded EPDM insulating rubber is formulated and
mixed in-house to ensure high quality.
3. Basic Insulating Plug
Moulded epoxy part has a threaded metal insert to
accept the pin contact.
➅
4. Capacitive Test Point
12
●
Capacitive test point provides means to check
circuit status. A moulded EPDM conducting rubber
cap provides a watertight seal.
➄
11
●
➆
5. Rubber Cap
Moulded EPDM conducting rubber cap protects
and earths the test point during normal operation.
6. Internal Screen
➇
➉
Moulded EPDM conducting rubber screen controls
electrical stress.
7. Capacitive Test Point (Optional)
➈
Provides a means to mount a fault indicator. A
moulded EPDM conducting rubber cap provides a
watertight seal.
8. Stress Relief
The configuration of the outer screen and the cable
adapter provides cable stress relief.
9. Cable Adapter
Figure 2.
400 A, 36 kV Class DT400P Deadbreak Tee Connector.
The sized opening provides an interference fit to
maintain a watertight seal and provides the initial
cable stress relief.
10. Earthing Eyes
Moulded into the external screen for connection of
an earthing wire.
11. External Screen
Moulded EPDM conducting rubber mates with the
cable screen to maintain screen continuity and
ensure that the assembly is at earth potential.
12. Conductor Contact
Inertia welded bimetallic compression connector
accepts copper or aluminum conductors.
2
I550-21
135
86
257*
75
DT400
24 kV
109
80
262
115
287
Dimensions in mm
*Add 100 mm to disconnect
Figure 3.
DT400P Deadbreak Tee Connector dimensional information.
ORDERING INFORMATION
For 12 kV and 24 kV applications, the ordering formula
is DT400P-R-C. For 36 kV applications, the ordering formula is DT436P-R-C. Substitute for R and C as
described below. Select the range from Table R that
best fits the diameter of the core insulation. Select the
code from Table C for the conductor size and type of
connector required.
A
B
NOTE: Bimetallic connectors can be used with aluminum
or copper conductors.
Cable seal adapters are ordered separately.
TABLE C
Conductor Code
TABLE R
Cable Insulation Range
Insulation Range
Designation
Ordering Example: For 20 kV cable, 240 mm2
aluminum conductor, 31.0 mm core insulation diameter,
DIN connector, specify DT400P-F-240.
Cable Insulation Range Ø (mm)
Min.
Max.
16.3
18.3
Stranded Conductor
Size (mm2)
DIN
Type
EDF
Type
DIN
All Copper
19.3
25
25
E25
C25
21.0
35
35
E35
C35
50
E50
C50
C70
C
20.0
24.1
50
D
23.1
27.0
70
70
E70
28.9
95
95
E95
C95
120
E120
C120
E
24.9
F
27.7
32.6
120
G
30.9
36.2
150
150
E150
C150
H
34.0
39.5
185
185
E185
C185
240
240
E240
C240
Optional Test Point
300
300
–
C300
If a test point on the tee body is required, add a “T”
before the insulation range designation.
Example: DT400PTF240
400
400
–
C400
Cooper Power Systems
Quality from
Cooper Industries
P.O. Box 1640, Waukesha, WI 53187
3
400 A Deadbreak
Elbow Connector
Cooper Power Systems
DE400 – 24 kV Applications
DE436 – 36 kV Applications
Electrical Apparatus
I550-20
APPLICATION
■
For connection of polymeric cable to transformers,
switchgear, motors and other equipment with a
premoulded separable connector.
■ For indoor and outdoor installations.
■ System voltage up to 36 kV.
■ Continuous current 400 A (600 A overload for 8 hours).
■ Cable particulars:
–Polymeric cable (XLPE, EPR, etc.)
–Copper or aluminum conductors
–Semiconducting or metallic screens
■ Conductor size: 12 kV 70-400 mm2
24 kV 25-400 mm2
36 kV 25-240 mm2
■ An optional adapter kit is available for use with PILC
cables.
FEATURES
■
Provides a fully screened and fully submersible
separable connection when mated with the proper
bushing or plug.
■ Built-in capacitive test point allows for an easy check of
the circuit status or installation of a fault indicator.
■ No minimum phase clearance requirements.
■ Mounting can be vertical, horizontal, or any angle in
between.
■ 100% factory tested.
STANDARDS
■
Figure 1.
400 A Deadbreak Elbow Connector.
Will meet the requirements of VDE 0278, IEC 502-4,
EDF HN 52-S-61, BS 7215 and others.
QUALITY ASSURANCE
■
RELATED PRODUCTS
■
■
■
DRC400 Receptacle Cap
DPE400 Earthing Plug
DPS400 Standoff Plug
Our manufacturing facility is registered to
ISO 9001-1994 by third party audit.
■ Required Production Tests
■ Periodic X-Ray Analysis
PACKAGING
■
INSTALLATION
Supplied in a kit with all necessary parts, approximate
weight 2 kg.
■
No special tools, heating, taping, or potting are
required.
■ Connector may be energised immediately after
installation on its mating part.
■ Mates with bushings, plugs, and junction devices
complying with the listed standards.
TABLE A
Electrical Ratings
Maximum
System Voltage (Um)
Impulse
AC Withstand (5 min.)
Continuous Current
Overload (8 hrs Max.)
Short Curcuit
Withstand, 1 sec. (rms sym.)
DE400
DE436
24 kV
125 kV
54 kV
400 A
600 A
36 kV
170 kV
81 kV
400 A
600 A
18 kA
18 kA
Note: Ratings are based on IEC Standards and do not reflect
maximum capability.
August 1996 • Supersedes 8/95 • © 1996 Cooper Power Systems, Inc.
Printed in U.S.A.
1
Features and Detailed Description
1. Pin Contact
➀
➁
➃
➂
Tin-plated copper pin screws into the conductor
contact with the supplied hex key.
2. Internal Screen
Moulded EPDM conducting rubber screen controls
electrical stress.
3. Insulation
Moulded EPDM insulating rubber is formulated and
mixed in-house to ensure high quality.
➄
4. Pulling Eye
➉
Encapsulated stainless steel pulling eye with a
detent to position the bail.
5. Capacitive Test Point
Capacitive test point provides means to check
circuit status. A moulded EPDM conducting rubber
cap provides a watertight seal.
➈
6. Stress Relief
➇
➅
The configuration of the outer screen and the cable
adapter provide cable stress relief.
7. Cable Adapter
The sized opening provides an interference fit to
maintain a watertight seal.
8. Earthing Eye
Moulded into the external screen for connection of
an earthing wire.
➆
9. External Screen
Moulded EPDM conducting rubber mates with the
cable screen to maintain screen continuity and
ensure that the assembly is at earth potential.
Figure 2.
400 A, 36 kV Class DE400 Deadbreak Elbow Connector.
10. Conductor Contact
Inertia welded bimetallic compression connector
accepts copper or aluminum conductors.
11. Stainless Steel Bail (Not Shown)
Secures the connector to its mating bushing or
accessory.
2
I550-20
83
280
100
MAX.
DE400
400 A
24 kV
195*
210*
Ø 69
129
250
275
APPROXIMATELY
78
Dimensions in mm
*Add 100 mm to disconnect
115
MAX.
Figure 3.
DE400 Deadbreak Connector dimensional information.
ORDERING INFORMATION
For 12 kV and 24 kV applications, the ordering formula
is DE400-R-C. For 36 kV applications, the ordering
formula is DE436-R-C. Substitute for R and C as
described below. Select the range from Table R that
best fits the diameter of the core insulation. Select the
code from Table C for the conductor size and type of
connector required.
TABLE R
Cable Insulation Range
Insulation Range
Designation
A
B
C
Ordering Example: For 20 kV cable, 150 mm2 aluminum
conductor, 27.0 mm core insulation diameter DIN-type
connector, specify DE400-E-150.
NOTE: Bimetallic connectors can be used with
aluminum or copper conductors.
Cable seal adapters are ordered separately.
TABLE C
Conductor Code
Cable Insulation Range Ø (mm)
Min.
Max.
16.3
18.3
20.0
Stranded Conductor
Size (mm2)
DIN
Type
EDF
Type
DIN
All Copper
19.3
25
25
E25
C25
21.0
35
35
E35
C35
24.1
50
50
E50
C50
C70
D
23.1
27.0
70
70
E70
E
24.9
28.9
95
95
E95
C95
120
E120
C120
F
27.7
32.6
120
G
30.9
36.2
150
150
E150
C150
H
34.0
39.5
185
185
E185
C185
240
240
E240
C240
300
300
–
C300
400
400
–
C400
Cooper Power Systems
Quality from
Cooper Industries
P.O. Box 1640, Waukesha, WI 53187
3
250 A Apparatus
Bushings
Cooper Power Systems
Electrical Apparatus
DB250
DB250S
DB250L
I550-15
APPLICATION
■
For oil-insulated (R-temp, hydrocarbon, or silicon)
apparatus, including switchgear, transformers, and
capacitors.
■
System voltage up to 24 kV.
■
Continuous Current 250 A.
■
For indoor and outdoor installations.
■
Mounting in vertical or horizontal position.
STANDARDS
■
Meets the interface requirements of
CENELEC HD 506 S1, ANSI/IEEE 386, DIN 47636
EDF C33-051, and others.
■
Has been tested with mating parts to IEC 60502-4 and
CENELEC HD 629.1 S1.
QUALITY
■
100% Production Tests
■
Periodic X-Ray Analysis
TABLE A
Electrical Ratings
Maximum
System Voltage (Um)
Impulse Withstand
AC Withstand
Continuous Current
Overload (8 hrs. Max.)
Short Circuit Withstand
1 sec. (rms sym.)
24 kV
125 kV
54 kV
250 A
300 A
12.5 kA
Figure 1.
DB250 Deadbreak Apparatus Bushing.
RELATED PRODUCTS
■
Mates with the following products:
DE250 Elbow
DS250 Straight
DRC250 Receptacle Cap
PACKAGING
■
Supplied in a box of three, approximate weight 4 kg.
October 1997 • New Issue • © 1997 Cooper Power Systems, Inc.
Printed in U.S.A.
1
Features and Detailed Description
1. Contact
➀
Plated multi-point contact accepts the pin contact
of the mating connector.
➁
➂
2. Interface
The interference fit between the bushing and the
connector prevents the entrance of moisture and
contamination.
86
➃
3. Shipping Cap
8
“A”
➄
Ø76
The cap prevents contamination of the interface
before energization.
4. Bail Tabs
Ø111
Attachment points for the bail of the mating
connector.
“B”
➆
5. Internal Screen
The screen controls electrical stress. An earthing
plate for connection to the screen is supplied.
22
6. Central Conductor
➅
The copper conductor has an M10 thread for the
apparatus connection.
M10
Dimensions in mm
7. Moulded Epoxy Resin Body
Figure 2.
Section View DB250 Bushing.
TABLE B
DIMENSIONS
Bushing Catalog No.
DB250 (standard)
DB250S (short)
DB250L (long)
“A” (mm)
224
189
284
“B” (mm)
108
73
168
ORDERING INFORMATION
To order, simply specify the catalog number with the
required shank length from table B.
Clamping devices and gaskets are ordered separately,
as shown below:
“X”
Voltage (kV)
12
24
OIL
LEVEL
X (mm)
40
50
Figure 3.
Minimum oil level.
TABLE C
Clamping Devices and Gaskets
Type of Clamp
DIN 42538
NFC 52-453
Catalog Number
BC-D-250
BC-N-250
Cooper Power Systems
P.O. Box 1640, Waukesha, WI 53187
www.cooperpower.com
Quality from
Cooper Industries
2
MI
Printed on Recycled Paper
10/97 2M
2
Accessories for
250 A Connectors
Electrical Apparatus
I550-13
Deadend Plug
Standoff Plug
Earthing Plug
July 1999 • Supersedes 5/98
Printed in U.S.A.
DPD250
■
Moulded EPDM rubber part to dead-end a 250 A
connector or junction.
■
Maintains the electrical ratings, and submersibility of
the mating part.
■
Supplied with silicone lubricant and installation
instructions.
■
Bail assembly is ordered separately.
■
For de-energised operation.
■
Interface meets the dimensional requirements of
CENELEC HD 506 S1.
DPS250
■
Moulded EPDM rubber part to support and dead-end
a 250 A connector or junction after removal from the
apparatus bushing.
■
Maintains the electrical ratings and submersibility of
the mating connector.
■
Supplied with silicone lubricant and installation
instructions.
■
Uses the standard bail of the mating connector.
■
For de-energised operation.
■
Interface meets the dimensional requirements of
CENELEC HD 506 S1.
DPE250
■
Moulded EPDM rubber part to support and earth a
250 A connector or junction after removal from the
apparatus bushing.
■
Maintains the electrical ratings and submersibility of
the mating connector.
■
Supplied with silicone lubricant and installation
instructions.
■
Uses the standard bail of the mating connector.
■
For de-energised operation.
■
Interface meets the dimensional requirements of
CENELEC HD 506 S1.
1
Accessories for 250 A Connectors
Receptacle Cap
2
DRC250
■
Mates with 250 A interfaces of CENELEC HD 506 S1
and other major bushing standards.
■
Seals mating bushing to maintain electrical ratings,
external screen, and watertightness.
■
Moulded EPDM insulation with semi-conductive
EPDM external screen.
■
Supplied with silicone lubricant and installation
instructions.
■
Bail assembly is ordered separately.
■
For de-energised operation.
I550-13
Crimp Connectors for 250 A Elbow (DE250)
Conductor
Size (mm2)
DIN
(Bimetallic)
EDF
(Bimetallic)
DIN
(All copper)
16
CDE250U16
CDE250E16
CDE250C16
25
CDE250U25
CDE250E25
CDE250C25
35
CDE250U35
CDE250E35
CDE250C35
50
CDE250U50
CDE250E50
CDE250C50
70
CDE250U70
CDE250E70
CDE250C70
95
CDE250U95
CDE250E95
CDE250C95
120
CDE250U120
-
CDE250C120
Conductor
Size (mm2)
DIN
(Bimetallic)
EDF
(Bimetallic)
DIN
(All copper)
16
CDS250U16
CDS250E16
CDS250C16
25
CDS250U25
CDS250E25
CDS250C25
35
CDS250U35
CDS250E35
CDS250C35
50
CDS250U50
CDS250E50
CDS250C50
70
CDS250U70
CDS250E70
CDS250C70
95
CDS250U95
CDS250E95
CDS250C95
120
CDS250U120
-
CDS250C120
Crimp Connectors for 250 A Straight (DS250)
Pin Contact & Hex Key for 250 A Elbow (DE250)
2638370C01EX - Pin Contact
2639205B01 - Wrench
■
Tin-plated copper pin contact
■
Special hex key applies the proper torque
P.O. Box 1640
Waukesha, WI 53187
www.cooperpower.com
© 1999 Cooper Industries, Inc.
MI
Printed on Recycled Paper
7/99
3
250 A Deadbreak
Straight Connector
DS250
`
250 A, 24 kV Class
Electrical Apparatus
I550-11
APPLICATION
For connection of polymeric cable to transformers,
switchgear, motors and other equipment with a
premoulded separable connector.
For indoor and outdoor installations.
System voltage up to 24 kV.
Continuous current 250 A (300 A overload for 8 hours).
Cable particulars:
- Polymeric cable (XLPE, EPR, etc.)
- Copper or aluminum conductors
- Semiconducting or metallic screens
Conductor size:
16-120 mm2
FEATURES
Provides a fully screened and fully submersible
separable connection when mated with proper bushing
or plug.
Built-in capacitive test point to determine the circuit
status or install a fault indicator.
No minimum phase clearance requirements.
Mounting can be vertical, horizontal, or any angle in
between.
100% factory tested.
AC withstand
Partial Discharge
Figure 1.
DS250 Deadbreak Straight Connector.
STANDARDS
RELATED PRODUCTS
QUALITY ASSURANCE
DPC250 Receptacle Cap
DPD2500 Dead End Plug
DPE250 Earthing Plug
DPS250 Standoff Plug
DJ250 Junctions
INSTALLATION
No special tools, heating, taping, or potting are
required.
Connector may be energised immediately after
installation on its mating part.
Mates with bushings, plugs, and junction devices
complying with the listed standards.
Meets the requirements of Cenelec HD629.1 S2 &
IEC 60502-4.
Our manufacturing facility is registered to
ISO 9001-2000 by third party audit.
Required Production Tests
Periodic X-Ray Analysis
PACKAGING
Supplied in a kit with all necessary parts, approximate
weight 1 kg.
TABLE A
Electrical Ratings
Maximum
System Voltage (Um)
24 kV
Impulse
125 kV
AC Withstand (5 min.)
54 kV
Continuous Current
250 A
Overload (8 hrs. Max.)
Short Circuit
Withstand, 1 sec (rms sym)
February 2007 • Supersedes 08/96
300 A
12.5 kA
1
Features and Detailed Description
1. Conductor Contact
9
Inertia welded bimetallic compression connector
accepts copper or aluminum conductors.
2. Internal Screen
Moulded EPDM conducting rubber screen
controls electrical stress.
1
3. Capacitive Test Point
Capacitive test point provides a means to check
circuit status. A moulded EPDM conducting
rubber cap earths the test point when not in
use.
2
3
8
4. Stress Relief
The configuration of the outer screen and insulation provides cable stress relief.
5. Cable Entrance
The sized opening provides an interference fit to
maintain a watertight seal.
6. External Screen
Moulded EPDM conducting rubber mates with
the cable screen to maintain screen continuity
and ensure that the assembly is at earth
potential.
7. Earthing Eye
4
Moulded into the external screen for connection
of an earthing wire.
7
8. Insulation
6
Moulded EPDM insulating rubber is formulated
and mixed in-house to ensure high quality.
9. Locking Ring Groove
Provision for an optional three-phase locking
ring.
10. Stainless Steel Bail (Not Shown)
Secures the connector to its mating bushing or
accessory.
5
Figure 2.
250 A - 24 kV Class DS250 Deadbreak Straight Connector.
2
I550-11
253*
102
2.5
32
.1
-24
100
DS250
250 A
24 kV
M
.7
70
F
M
19.6
110
-.950 IN
Dimensions in mm
* Add 55 mm to disconnect
Figure 3.
DS250 Deadbreak Connector dimensional information.
KIT CONTENTS
The complete kit includes 1 each moulded straight
housing, conductor contact, stainless steel ball, silicone
lubricant, and installation instructions.
Ordering Example: For 20 kV cable, 50 mm2 aluminum
conductor, 21.0 mm core insulation diameter, unplated
DIN connector, specify DS250F50.
Cable seal adapters are ordered separately.
ORDERING INFORMATION
The complete catalog number for the elbow connector is
DS250RC.
R is the cable range designation and C is the conductor
contact code. Select the cable range designation from
Table R. Select the conductor contact code from Table C
for the conductor size and type of connector required.
Table R
Cable Insulation Range
Insulation Range
Designation
TABLE C
Conductor Code
Cable Insulation Range Ø (mm)
Min.
Max.
Stranded
Conductor
Size (mm2)
DIN Unplated
EDF Type
DIN
All Copper
B
13.5
17.4
16
16
E16
C16
D
16.3
20.8
25
25
E25
C25
F
19.6
24.1
35
35
E35
C35
H
23.1
28.7
50
50
E50
C50
J
27.9
33.5
70
70
E70
C70
95
95
E95
C95
120
120
-
C120
NOTE: Bimetallic connectors can be used with aluminum
or copper conductors.
3
© 2007 Cooper Power Systems, Inc., or its affiliates
1045 Hickory Street
Pewaukee, WI 53072 USA
www.cooperpower.com
250 A Deadbreak
Elbow Connector
Cooper Power Systems
DE250
Electrical Apparatus
I550-10
250 A, 24 kV Class
APPLICATION
■
For connection of polymeric cable to transformers,
switchgear, motors and other equipment with a
premoulded separable connector.
■ For indoor and outdoor installations.
■ System voltage up to 24 kV.
■ Continuous current 250 A (300 A overload for 8 hours).
■ Cable particulars:
– Polymeric cable (XLPE, EPR, etc.)
– Copper or aluminum conductors
– Semiconducting or metallic screens
■ Conductor size 16-120 mm2
FEATURES
■
Provides a fully screened and fully submersible
separable connection when mated with the proper
bushing or plug.
■ Built-in capacitive test point to determine the circuit
status or install a fault indicator.
■ No minimum phase clearance requirements.
■ Mounting can be vertical, horizontal, or any angle in
between.
■ 100% factory tested.
STANDARDS
■
Will meet the requirements of VDE 0278, IEC 502-4,
EDF HN 52-S-61, ANSI/IEEE 386, BS 7215 and others.
QUALITY ASSURANCE
■
Figure 1.
DE250 Deadbreak Elbow Connector.
Our manufacturing facility is registered to
ISO 9001-1994 by third party audit.
■ Required Production Tests
■ Periodic X-Ray Analysis
RELATED PRODUCTS
PACKAGING
■
■
■
■
■
DRC250 Receptacle Cap
DPD250 Dead End Plug
DPS250 Standoff Plug
DPE250 Earthing Plug
DJ2503 3-Way Junction
INSTALLATION
■
No special tools, heating, taping, or potting are
required.
■ Connector may be energised immediately after
installation on its mating part.
■ Mates with bushings, plugs, and junction devices
complying with the listed standards.
■
Supplied in a kit with all necessary parts, approximate
weight 1 kg.
TABLE A
Electrical Ratings
Maximum
System Voltage (Um)
Impulse
AC Withstand (5 min.)
Continuous Current
Overload (8 hrs Max.)
Short Curcuit
Withstand, 1 sec. (rms sym.)
24 kV
125 kV
54 kV
250 A
300 A
12.5 kA
Note: Ratings are based on IEC Standards and do not reflect
maximum capability.
August 1996 • Supersedes 8/95 • © 1996 Cooper Power Systems, Inc.
Printed in U.S.A.
1
Features and Detailed Description
1. Pin Contact
➃
➂
Tin-plated copper pin screws into the conductor
connector with the supplied hex key.
➁
➀
2. Internal Screen
Moulded EPDM conducting rubber screen controls
electrical stress.
3. Insulation
Moulded EPDM insulating rubber is formulated and
mixed in-house to ensure high quality.
4. Pulling Eye
11
●
➉
➂
Encapsulated stainless steel pulling eye with a
detent to position the bail.
5. Capacitive Test Point
Capacitive test point provides means to check
circuit status. A moulded EPDM conducting rubber
cap provides a watertight seal.
➄
➈
➅
➇
6. Stress Relief
The configuration of the outer screen and insulation
provides cable stress relief.
7. Cable Entrance
The sized opening provides an interference fit to
maintain a watertight seal.
8. External Screen
➆
Moulded EPDM conducting rubber mates with the
cable screen to maintain screen continuity and
ensure that the assembly is at earth potential.
9. Earthing Eye
Figure 2.
250 A, 24 kV Class DE250 Deadbreak Elbow Connector.
Moulded into the external screen for connection of
an earthing wire.
10. Conductor Contact
Inertia welded bimetallic compression connector
accepts copper or aluminum conductors.
11. Locking Ring Groove
Provision for an optional three-phase locking ring.
12. Stainless Steel Bail (Not Shown)
Secures the connector to its mating bushing or
accessory.
2
I550-10
192
66
160*
145*
.7 7
MM
IN
90
MAX
DE250
250A
24 kV
4.1
6-2
950
F
0 -.
170
19.
2.5
85
62
32
100
Dimensions in mm
*Add 55 mm to disconnect
Figure 3.
DE250 Deadbreak Elbow Connector dimensional information.
ORDERING INFORMATION
The ordering formula for the DE250 Separable
Connector is DE250-R-C. Substitute for R and C as
described below. Select the range from Table R that
best fits the diameter of the core insulation. Select the
code from Table C for the conductor size and type of
connector required.
Ordering Example: For 20 kV cable, 50 mm2
aluminum conductor, 21.0 mm core insulation diameter,
unplated, DIN connector, specify DE250-F-50
NOTE: Bimetallic connectors can be used with aluminum
or copper conductors.
Cable seal adapters are ordered separately.
TABLE R
Cable Insulation Range
Insulation Range
Designation
Cable Insulation Range Ø (mm)
Min.
Max.
B
13.5
17.4
D
16.3
20.8
F
19.6
24.1
H
23.1
28.7
J
27.9
33.5
TABLE C
Conductor Code
Stranded Conductor
Size (mm2)
DIN
Unplated
DIN
Plated
EDF
Type
DIN
Copper
16
16
P16
E16
C16
25
25
P25
E25
C25
35
35
P35
E35
C35
50
50
P50
E50
C50
70
70
P70
E70
C70
95
95
P95
E95
C95
120
120
P120
–
C120
Cooper Power Systems
Quality from
Cooper Industries
P.O. Box 1640, Waukesha, WI 53187
3
Deadbreak Apparatus
Connectors
Cooper Power Systems
Electrical Apparatus
200 A 15 and 25 kV Class
Deadbreak Straight Connector
550-12
DESCRIPTION
The Cooper Power Systems RTE®
Deadbreak Straight Connector is a
fully-shielded and insulated plug-in
termination for connecting underground
cable to transformers, switching
cabinets and junctions equipped with
deadbreak bushings. The design of
the straight connector allows mounting to be vertical, horizontal, or any
angle in between.
RTE deadbreak straight connectors
are molded using high quality peroxide-cured EPDM insulation. Standard
features include a copperTop pin
connector, bail assembly and a built-in
capacitive test point.
Cable ranges are sized to accept a
wider range of cable diameter for a
given size elbow. The wider cable
ranges increase installation flexibility.
The CopperTop pin compression
connector is a standard item to
transition from the cable to the deadbreak bushing. An aluminum crimp
barrel is inertia-welded to a copper
probe. The aluminum barrel makes
the connector easy to crimp and the
copper probe ensures a reliable, tight,
cool operating connection with the
bushing.
INSTALLATION
Cable stripping and scoring tools,
available from various tool manufacturers, are recommended for use
when installing deadbreak connectors. After preparing the cable, the
compression connector is installed on
the conductor. The molded housing is
then pushed onto the cable.
Figure 1.
15/25 kV Deadbreak Straight Connector.
PRODUCTION TESTS
Tests conducted in accordance with
ANSI/IEEE Standard 386:
■ ac 60 Hz 1 Minute Withstand
–40 kV
■ Minimum Corona Voltage Level
–19 kV
■ Test Point Voltage Test
TABLE 1
Voltage Ratings and Characteristics
Description
Standard Voltage Class
Maximum Rating Phase-to-Phase
Maximum Rating Phase-to-Ground
ac 60 Hz 1 Minute Withstand
dc 15 Minute Withstand
BIL and Full Wave Crest
Minimum Corona Voltage Level
kV
25
26.3
15.2
40
78
125
19
Tests are conducted in accordance
with Cooper Power Systems
requirements:
■ Physical Inspection
■ Periodic Dissection
■ Periodic Fluoroscopic Analysis
TABLE 2
Current Ratings and Characteristics
Description
Continuous
Short Time
Amperes
200 A rms
10,000 A rms symmetrical
for 0.17 s
3,500 A rms symmetrical
for 3.0 s
Current ratings and characteristics are in
accordance with ANSI/IEEE Standard 386.
Voltage ratings and characteristics are in
accordance with ANSI/IEEE Standard 386.
November 1997 • Supersedes 8/97
Printed in U.S.A.
1
200 A 15 and 25 kV Class Deadbreak Straight Connector
SEMI-CONDUCTING SHIELD
Molded Semi-Conducting EPDM shield
meets requirements of IEEE Standard 592
and provides ground shield continuity
between molded connector and cable
shield.
TEST POINT
Capacitive test point with snap-on cap
provides a shielded, hotstick-operable
means to determine circuit condition.
COPPERTOP CONNECTOR
CopperTop pin compression
connector is a field-proven,
bimetallic, friction-welded
design that accepts copper or
aluminum cable conductors.
GROUNDING TAB
Grounding tab is molded into semi-conductive
shield for the attachment of a ground wire to
ensure deadfront construction.
EPDM INSULATION
High quality peroxide cured EPDM
insulation is mixed and formulated inhouse for complete control of
rubber characteristics.
SEMI-CONDUCTING INSERT
Molded EPDM Semi-Conducting
Insert controls electrical stress.
Figure 2.
Straight connector cutaway illustrates design integrity.
1.0"
253 mm
4.0"
102 mm
4.3"
110 mm
N
19.
.7
70
F
MM
4.1
6-2
-. 9 5 0 I
Figure 3.
DS225 Deadbreak Connector dimensional information.
2
DS225
200 A
15.2 kV
3.9"
100 mm
550-12
ORDERING INFORMATION
The standard elbow kit is packaged in
a heavy-duty polyethylene bag, bulk
packed 30 kits to a multi-pak box.
Individual boxed kits are also available by special part number. To order
a 15/25 kV Class Deadbreak Straight
Connector kit, for cable meeting AEIC
CS5 and CS6, follow the easy steps
below.
Each kit contains:
■ Molded Straight Body
■ CopperTop Compression Pin
Connector
■ Bail Assembley
■ Silicone Lubricant
■ Installation Instruction Sheet
STEP 1: Determine the cable’s
diameter over the electrical insulation
as shown in Figure 4 (including
tolerances). Then identify a cable
range from Table 3 that brackets the
minimum and maximum insulation
diameters. Select the CABLE RANGE
CODE from the far right column.
STEP 2: Identify the conductor size
and type in Table 4 and select the
CONDUCTOR CODE from the far
right column.
STEP 3: For a Straight Connector kit
with a capacitive test point order:
DS225
CABLE RANGE
CODE
CONDUCTOR
CODE
T
METAL NEUTRAL
OR SHIELD
OUTER JACKET
DIAMETER OVER
INSULATION
INSULATION
SHIELD
CONDUCTOR
INSULATION
CONDUCTOR
SHIELD
Figure 4.
Illustration showing typical construction of medium voltage underground cable.
TABLE 3
Cable Range
Cable Range
Inches
.531-.685
.642-.819
.772-.949
.909-1.13
1.10-1.32
CABLE RANGE
CODE
Millimeters
13.5-17.4
16.3-20.8
19.6-24.1
23.1-28.7
27.9-33.5
BA
DA
FA
HA
JA
TABLE 4
Conductor Size and Type
Concentric or
Compressed
AWG
mm2
#6
#4
#3
#2
#1
1/0
2/0
3/0
4/0
250*
16
–
–
25
35
50
70
–
95
120
Compact or
Solid
AWG
CONDUCTOR
CODE
mm2
No Connector
For a Straight connector kit without a
compression connector, use “00” for
the conductor code.
For a kit individually packaged in a
corrugated cardboard box, insert an
“X” as the last character in the part
number.
EXAMPLE: Select a connector kit
with a capacitive test point for use on
a #1 compact cable with a nominal
insulation diameter of .760".
00
#4
#3
#2
#1
1/0
2/0
3/0
4/0
250
300
–
–
25
35
50
70
–
95
120
–
01
02
03
04
05
06
07
08
09
10
*Compressed stranding only.
STEP 1: Nominal diameter over the
insulation is 0.760" ± .030".
Minimum Diameter
0.760"–.030" = 0.730"
Maximum Diameter
0.760"+.030" = 0.790"
From Table 3, identify the cable range
.642"–.819" and select the “D”
CABLE RANGE CODE.
STEP 2: The conductor size is a #1
and the type is compact.
From Table 4, under the column
“Compact or Solid” identify #1 and
select the “04” conductor code.
STEP 3: Order catalog number.
DS 225 DA 04 T
3
200 A 15 and 25 kV Class Deadbreak Straight Connector
TABLE 6
Replacement Parts
TABLE 5
Replacement CopperTop Pin Connectors
Description
Conductor Size
Concentric or Compressed
AWG
mm2
Compact or Solid
AWG
mm2
Catalog
Number
2.88 in. x 0.625 in. Connectors
6
2
1
1/0
2/0
4/0
250*
16
25
35
50
70
95
120
4
1
1/0
2/0
3/0
250
300
–
35
50
70
–
120
–
CDS250U16
CDS250U25
CDS250U35
CDS250U50
CDS250U70
CDS250U95
CDS250U120
Bail Assembly
Silicone Grease
.25 oz tube
5.2 oz tube
Test Point Cap
Catalog
Number
2639253B01B
2603393A01
2605670A02M
2625641A51
* Compressed Stranding Only
NOTE: CopperTop compression connector may be used on both aluminum and copper cable conductors.
ACCESSORIES
Figure 5.
Tape Shield Adapter (see catalog section 500-70).
Figure 6.
Drain Wire Adapter (see catalog section 500-75).
Cooper Power Systems
Quality from
Cooper Industries
P.O. Box 1640, Waukesha, WI 53187
www.cooperpower.com
© 1997 Cooper Power Systems, Inc.
RTE® is a registered trademark of Cooper Industries, Inc.
MI
4
Printed on Recycled Paper
10/97 16M
1250 A Deadbreak
Junctions
DJ612
1250 A, 24 kV Class
Electrical Apparatus
I550-53
APPLICATION
■
For connection of two, three, or four 1250 A premoulded
tee connectors to form a separable cable joint.
■
For indoor or outdoor applications.
■
For use in submerged vaults, surface applications,
and with aerial cables.
■
System voltage to 24 kV.
■
Continuous current 1250 A (1800 A overload for
8 hours).
■
For de-energised operation.
FEATURES
Figure 1.
DJ612 Deadbreak Junctions.
■
Available in two, three, and four way configurations.
■
Stainless steel mounting brackets are available as an
option.
■
Provides a fully screened and fully submersible
separable connection when mated with the tee
connectors.
■
No minimum phase spacing requirements.
■
100% factory tested.
STANDARDS
RELATED PRODUCTS
■
DT612 Tee Connector
■
DRC600 Receptacle Cap
■
QUALITY ASSURANCE
■
Manufacturing facility is registered to ISO 9001-1994
by third party audit.
■
Routine Tests.
■
X-Ray audit of random samples.
INSTALLATION
■
No special tools, heating, taping, or potting are
required.
■
Can be energised immediately after the
mating parts are secured.
PACKAGING
■
Supplied in single-phase kits.
August 1999 • New Issue
Printed in U.S.A.
Meets the requirements of CENELEC HD 629.1 S1,
IEC 60502-4, and ANSI/IEEE 386.
TABLE A
Electrical Ratings
Maximum
System Voltage (Um)
Partial Discharge
Extinction (<3 pC) *
AC Withstand *
Impulse Withstand
Continuous Current
Overload (8 hrs.)
Short Circuit
Withstand, 1 sec (rms sym)
* Denotes routine tests on 100% of production.
24 kV
20 kV
54 kV
125 kV
1250 A
1800 A
75 kA
1
Features and Detailed Description
6
1
2
3
4
1. Threaded Contact
Threaded 5/8" copper contact. A stud is included to
mate with M16 DT612 tee connectors.
2. Busbar
Internal copper current-carrying part for low electrical resistance and high mechanical strength.
3. External Screen
Moulded semi-conductive EPDM rubber mates with
the screen of the connector to maintain screen continuity.
4. Insulation
Moulded EPDM rubber provides the phase-to-earth
insulation and forms the interface with the mating
connectors to maintain dielectric ratings and a
watertight seal.
5. Stainless Steel Mounting Bracket
Optional bracket is corrosion resistant and includes
parking pockets for standoff plugs or earthing
plugs.
6. Shipping Caps
The cap prevents contamination of the interface
during installation.
2
I550-53
102
A
186
132
B
14
107
36
15
Number of
Interfaces
2
3
4
50
C
A
360
585
685
Dimensions (mm)
B
170
270
375
50
C
375
490
630
ORDERING INFORMATION
Number of
Interfaces
2
3
4
Junction
Only
DJ612C2
DJ612C3
DJ612C4
Junction
with Bracket
DJ612C2B
DJ612C3B
DJ612C4B
All kits include junction, silicone lubricant, and installation
instructions.
P.O. Box 1640
Waukesha, WI 53187
www.cooperpower.com
© 1999 Cooper Industries, Inc.
MI
Printed on Recycled Paper
8/99
3
200 A 15 and 25 kV Class Deadbreak Elbow Connector
SEMI-CONDUCTING SHIELD
Molded Semi-Conducting EPDM shield meets requirements of
IEEE Standard 592 and provides ground shield continuity
between elbow and cable shield.
PROBE
Field replaceable, tin plated copper
probe ensures reliable electrical
connection.
PULLING EYE
Stainless steel reinforced
pulling eye provides reliable
hotstick operating point. Sturdy
construction exceeds
ANSI/IEEE 386 requirements.
COPPERTOP CONNECTOR
CopperTop compression connector is
a field proven, bimetallic friction
welded design that accepts
copper or aluminum cable
conductors.
SEMI-CONDUCTING INSERT
Molded EPDM Semi-Conducting
Insert controls electrical stress.
TEST POINT
Capacitive test point with snap-on cap
provides a shielded,
hotstick-operable means to determine
circuit condition.
GROUNDING TAB
Grounding tab is molded into semi-conductive
shield for the attachment of a ground wire to
ensure deadfront construction.
EPDM INSULATION
High quality peroxide cured EPDM
insulation is mixed and formulated inhouse for complete control of
rubber characteristics.
Figure 2.
Elbow cutaway illustrates design integrity.
7.6"
192 mm
2.6"
66 mm
6.3"
160 mm
.7 7
MM
IN
4.1
6-2
950
F
0 -.
6.7"
170 mm
19.
5.7"
145 mm
DE225
200A
15.2 kV
3.3"
85 mm
3.5"
90 mm
MAX.
11.5"
62 mm
3.9"
100 mm
Figure 3.
DE225 Deadbreak Elbow Connector dimensional information.
2
550-10
ORDERING INFORMATION
The standard elbow kit is packaged in
a heavy-duty polyethylene bag and
bulk-packed, 20 kits to a multipak
box. Individual boxed kits are also
available by special part number. To
order a 15/25 kV Class Deadbreak
Elbow Kit, for cable meeting AEIC
CS5 and CS6, follow the easy steps
below.
Each kit contains:
■ Elbow Body
■ CopperTop Compression
Connector
■ Copper Probe
■ Probe Installation Tool
■ Spring Bail Assembly
■ Silicone Lubricant
■ Installation Instruction Sheet
STEP 1: Determine the cable’s diameter over the electrical insulation as
shown in Figure 4 (including tolerances). Then identify a cable range
from Table 3 that brackets the minimum and maximum insulation diameters. Select the CABLE RANGE
CODE from the far right column.
STEP 2: Identify the conductor size
and type in Table 4 and select the
CONDUCTOR CODE from the far
right column.
STEP 3: For an elbow kit with a
capacitive test point order:
DE225
CABLE RANGE
CODE
CONDUCTOR
CODE
METAL NEUTRAL
OR SHIELD
OUTER JACKET
CONDUCTOR
INSULATION
CONDUCTOR
SHIELD
Figure 4.
Illustration showing typical construction of medium voltage underground cable.
TABLE 3
Cable Range
Cable Range
Inches
.531-.685
.642-.819
.772-.949
.909-1.13
1.10-1.32
CABLE RANGE
CODE
Millimeters
18.5-17.4
16.3-20.8
19.6-24.1
23.1-28.7
27.9-33.5
BA
DA
FA
HA
JA
TABLE 4
Conductor Size and Type
Concentric or
Compressed
AWG
mm2
#6
#4
#3
#2
#1
1/0
2/0
3/0
4/0
250*
16
–
–
25
35
50
70
–
95
120
Compact or
Solid
AWG
CONDUCTOR
CODE
mm2
No Connector
T
For an elbow kit without a compression connector, use “00” for the
conductor code.
For an elbow kit individually packaged
in a corrugated cardboard box, insert
an “X” as the last character in the
part number.
EXAMPLE: Select an elbow kit with a
capacitive test point for use on a #1
compact cable with a nominal insulation diameter of .760".
DIAMETER OVER
INSULATION
INSULATION
SHIELD
00
#4
#3
#2
#1
1/0
2/0
3/0
4/0
250
300
–
–
25
35
50
70
–
95
120
–
01
02
03
04
05
06
07
08
09
10
*Compressed stranding only.
STEP 1: Nominal diameter over the
insulation is 0.760" ± .030".
Minimum Diameter
0.760"–.030" = 0.730"
Maximum Diameter
0.760"+.030" = 0.790"
From Table 3, identify the cable range
.642"–.819" and select the “D”
CABLE RANGE CODE.
STEP 2: The conductor size is a #1
and the type is compact.
From Table 4, under the column
“Compact or Solid” identify #1 and
select the “04” conductor code.
STEP 3: Order catalog number.
DE 225 DA 04 T
3
200 A 15 and 25 kV Class Deadbreak Elbow Connector
TABLE 6
Replacement Parts
TABLE 5
Replacement CopperTop Connectors
Conductor Size
Concentric or Compressed
AWG
mm2
Description
Compact or Solid
AWG
mm2
Catalog
Number
2.88 in. x 0.625 in. Connectors
6
4
3
2
1
1/0
2/0
3/0
4/0
250*
16
–
–
25
35
50
70
–
96
120
4
3
2
1
1/0
2/0
3/0
4/0
250
300
–
–
25
35
50
70
–
95
120
–
2639043A01B
2639043A02B
2639043A03B
2639043A04B
2639043A05B
2639043A06B
2639043A07B
2639043A08B
2639043A09B
2639043A10B
Deadbreak Probe
Installation Tool
Deadbreak Probe Only
Bail Assembly
Silicone Grease
.25 oz tube
5.2 oz tube
Test Point Cap
Catalog
Number
2639205B01
2638370C01EX
2690322D01
2603393A01
2605670A02M
2625641A51
* Compressed Stranding Only
NOTE: CopperTop compression connector may be used on both aluminum and copper cable conductors.
ACCESSORIES
Figure 5.
Tape Shield Adapter (see catalog section 500-70).
Figure 6.
Drain Wire Adapter (see catalog section 500-75).
Cooper Power Systems
Quality from
Cooper Industries
P.O. Box 1640, Waukesha, WI 53187
www.cooperpower.com
© 1997 Cooper Power Systems, Inc.
RTE® is a registered trademark of Cooper Industries, Inc.