Brushless Doubly Fed Induction Generator based Wind Turbine Drivetrain under Grid Fault Conditions Udai Shipurkar Master of Science Thesis Supervisor: Dr.ir. H. Polinder Ir. T.D. Strous Electrical Power Processing Department of Electrical Sustainable Energy Faculty of Electrical Engineering, Mathematics and Computer Science Delft University of Technology July 8, 2014 Abstract With growing interest in sustainable forms of energy, the wind industry is growing rapidly. The Doubly Fed Induction Generator is the most popular choice for the drivetrain because it is cost effective. However, it suffers from reliability and maintenance issues due to the slip rings and brushes it requires. The Brushless Doubly Fed Induction Generator (B-DFIG) aims to address these drawbacks. With increased wind power penetration, tripping of wind turbines during grid disturbances is no longer acceptable for the power system. Therefore, it is important to study the performance of such wind turbine drivetrain under low voltage events. This thesis studies the Low Voltage Ride Through (LVRT) characteristics of the B-DFIG for its application in wind turbines. This thesis first looks at the modelling and control of the Brushless Doubly Fed Induction Generator (B-DFIG) to be used in a wind turbine drivetrain. It develops the steady state model using circuit theory to study the steady state characteristics of the machine. The dynamic model is developed to form the basis of the study of the machine during low voltage events. Further, the controller is developed based on vector control. The second part of the thesis looks at the performance of a B-DFIG based wind turbine under symmetric low voltage dips. It compares the performance of this generator with that of the Permanent Magnet Synchronous Machine (PMSM) and Doubly Fed Induction Generator (DFIG) - two of the most prevalent generators used in wind turbine drivetrains today. The thesis also looks at protection methods for these generators. The issue with LVRT performance of the PMSM is the rise in the DC link voltage which is due to the mismatch in power generated by the machine and the power transferred to the grid. It has been found that apart from offering better reliability through the exclusion of slip rings and brushes, the B-DFIG also has an improved LVRT performance when compared with the DFIG. The protection is simpler and can be built into the control algorithm of the machine controller. iii iv Acknowledgements First, I would like to thank Henk Polinder for his help and guidance throughout the duration of this thesis. Discussions with him have always been enlightening and thought provoking. I would also like to thank Tim Strous who has been a great support in carrying out this thesis work. He has always been ready to discuss my questions and doubts and has been very helpful when I was writing this document. I would also like to thank the rest of the B-DFIG team - Nils van der Blij, Einar Vilmarsson and Xuezhou Wang - discussions with whom have helped build my understanding of this machine. Thanks also to my fellow master students of the student room - Foivos, Nikolas, Joost, Didier, Einar, Ralino and JK - who have made these months fun-filled and informative. Thanks also to Didier for permission to use his photograph in the cover and Siddhartha for his help in designing it. v Contents Abstract iii Acknowledgements v Contents vii List of Symbols 1 Introduction 1.1 Background . . . 1.2 Thesis Objective 1.3 Methodology . . 1.4 Contribution . . ix . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1 1 2 2 4 2 B-DFIG Steady State Modelling 2.1 Machine Description . . . . . . . . . . . . . . 2.1.1 Machine Operation . . . . . . . . . . . 2.2 Equivalent Circuit . . . . . . . . . . . . . . . 2.2.1 Development of the Equivalent Circuit 2.2.2 Power Balance Equations . . . . . . . 2.3 Simplified Equivalent Circuit . . . . . . . . . 2.4 The Γ-Equivalent Circuit . . . . . . . . . . . 2.5 Steady State Characteristics . . . . . . . . . . 2.6 Discussion . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5 5 6 7 8 16 17 18 19 21 3 B-DFIG Dynamic Modelling 3.1 The Dynamic Equations of the Machine . . 3.2 Dynamic Model in the Block Diagram Form 3.3 Dynamic Behaviour . . . . . . . . . . . . . 3.4 Discussion . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23 23 27 29 30 4 B-DFIG Control 4.1 Wind Turbine Drivetrain System . . . . . . . . 4.2 Reference Signal Generation . . . . . . . . . . . 4.2.1 Modelling for Optimal Power Extraction 4.2.2 B-DFIG Reference Signal . . . . . . . . 4.3 Active and Reactive Power Control . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31 32 34 34 36 37 vii . . . . . . . . . 37 40 44 45 46 . . . . . . . . . . . 47 47 50 51 52 56 57 60 63 64 66 72 6 Conclusion 6.1 Conclusions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6.2 Future Work . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 73 73 74 Bibliography 75 Appendices 79 A Additional LVRT Performance Simulations 81 B B-DFIG Analytical Parameter Calculation 89 C B-DFIG Simple Case Study Machine 93 D PMSM 3.2MW Case Study Machine 97 E DFIG 3.2MW Case Study Machine 99 4.4 4.5 4.6 4.3.1 Active Power Control . 4.3.2 Reactive Power Control PI Tuning . . . . . . . . . . . . Control Behaviour . . . . . . . Discussion . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5 Performance Under Grid Events 5.1 Grid Code Requirements . . . . . . . . . . . . . . . . . 5.2 Simulation of the LVRT Performance for the PMSM . 5.2.1 LVRT Performance without Protection . . . . . 5.2.2 LVRT Performance with Protection . . . . . . 5.3 Simulation of the LVRT Performance of the DFIG . . 5.3.1 Performance without Protection . . . . . . . . 5.3.2 Performance with Protection . . . . . . . . . . 5.4 Simulation of the LVRT Performance for the B-DFIG 5.4.1 Performance without Protection . . . . . . . . 5.4.2 Performance with Protection . . . . . . . . . . 5.5 Discussion . . . . . . . . . . . . . . . . . . . . . . . . . F B-DFIG 3.2MW Case Study Machine viii . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 103 List of Symbols A bp bc Cp ip ic ir,l ix,d−ref p ipx,q−ref ix,d−ref c icx,q−ref Lp,σ Lc,σ Lp,m Lc,m Lr,lσ Lr,lm Mp,nl Mc,nl Nn Nl pp pc Pp Pc Pp,ag Pc,ag Pp,cu Pc,cu Pr,cu PF e Ppref Qref p R Rp Rc swept area of wind turbine rotor Power Winding air-gap Control Winding air-gap power coecient Power Winding current Control Winding current rotor loop - l current reference Power Winding d-axis current in the ‘x’ reference frame reference Power Winding q-axis current in the ‘x’ reference frame reference Control Winding d-axis current in the ‘x’ reference frame reference Control Winding q-axis current in the ‘x’ reference frame Power Winding leakage inductance Control Winding leakage inductance Power Winding main inductance Control Winding main inductance rotor loop -l leakage inductance rotor loop - l main inductance mutual inductance between Power Winding and rotor loop - l mutual inductance between Control Winding and rotor loop - l number of rotor nests number of loops in each rotor nest Power Winding pole number Control Winding pole number Power Winding real power Control Winding real power Power Winding air-gap power Control Winding air-gap power Power Winding copper loss Control Winding copper loss rotor copper loss machine iron loss reference Power Winding active power reference Power Winding reactive power wind turbine rotor radius Power Winding resistance Control Winding resistance ix Rr,l s sp Sp Sc Tref up uc ūxp ūxc rotor loop - l resistance Control Winding circuit slip rotor circuit slip Power Winding apparent power Control Winding apparent power reference torque Power Winding voltage Control Winding voltage voltage vector of Power Winding in ‘x’ reference frame voltage vector of Control Winding in ‘x’ reference frame reference Control Winding d-axis voltage in the ‘x’ reference frame reference Control Winding q-axis voltage in the ‘x’ reference frame DC link voltage ωp ωc ωm φp,c λ̄xp λ̄xc λ̄xr ρ Power Winding excitation frequency Control Winding excitation frequency rotor mechanical angular velocity phase angle between Power and Control Winding voltages Power Winding flux linkage vector in ‘x’ reference frame Control Winding flux linkage vector in ‘x’ reference frame rotor flux linkage vector in ‘x’ reference frame density of air ux,d−ref c ux,q−ref c udc x Chapter 1 Introduction The Brushless Doubly Fed Induction Machine (B-DFIM) traces its origin to the beginning of the twentieth century. It has recently been explored for use as generators in wind turbines. This chapter serves as an introduction to the work in this thesis. Section 1.1 looks at the historical developments of the B-DFIM. Section 1.2 describes the objectives of this thesis work. Section 1.3 describes the approach taken in this document and Section 1.4 details the contribution made by this thesis. This document deals with the Brushless Doubly Fed Induction Machine used in a wind turbine. Although this machine can operate both as a motor and as a generator, for the wind turbine application its operation is restricted to use as a generator. Therefore, the term Brushless Doubly Fed Induction Generator (B-DFIG) is used interchangeably with Brushless Doubly Fed Induction Machine (B-DFIM). 1.1 Background The development of the Brushless Doubly Fed Induction Machine can be traced back to the early twentieth century. Before the use of power electronics became prevalent for the control of electric machines, the use of two cascade connected slip ring induction machines for speed control was common. In 1907, Hunt [1] proposed a machine that incorporated two machine windings in the stator and a special rotor design. This machine achieved speed control through resistors connected to one of the stator windings, thus doing away with slip rings. The design of the B-DFIM was further developed by Creedy [2] in the early 1920s. Further advancements for the B-DFIM came in 1970 when Broadway et al. [3] proposed a caged rotor (nested loop) design. Modern B-DFIMs still used rotors based on this design. They also developed the equivalent circuit for the machine and analysed the performance in steady state and also noted the operation of the machine in the ’synchronous mode’. Kusko and Somuah [4] studied the operation of the single-frame brushless induction motor with a rectifier-inverter to control speed by slip-power pump back to the line. Till this point all stator designs, including those of Hunt and Creedy, used a single stator winding which produced both fields of different pole numbers. However, Rochelle et al. in 1990 compared the alternatives for stator winding design and concluded that electrically isolated windings were more advantageous [5]. Subsequently all BDFIM’s have used this stator winding design. 1 CHAPTER 1. INTRODUCTION Wallace et al. at Oregan State University developed a dynamic model1 of the machine [6] and used simulation models to investigate the behaviour [7] in the mid-1980s. Li et al. developed a two-axis model suitable for dynamic studies [8] and presented results of dynamic simulations [9]. Further developments in the modelling of the Brushless Doubly Fed Machine took place at Cambridge University. Williamson et al. presented a generalised mathematical model for the machine operating in the synchronous mode [10] [11]. Zhou et al. presented the first field-oriented control algorithm for the machine [12] and followed that with a simplified version [13]. However, these algorithms were heavily dependant on machine parameters. In 2002, Poza et al. presented a vector control algorithm [14] based on the Power Winding flux. There has been little research on the Low Voltage Ride Through (LVRT) performance of the B-DFIG. Shao et al. studied the dynamic behaviour of the machine during symmetrical voltage dips [15]. However, this study was limited as it did not consider the subsequent voltage rise of the grid and it did not propose any methods to improve the performance. In 2011 they proposed a control scheme that gives the B-DFIG the capability to ride through low voltage faults [16] and this was extended for asymmetric low voltage faults [17]. This thesis work has been carried out under the aegis of the Project Windrive - ‘Industrialization of a 3MW Medium-Speed Brushless DFIG Drivetrain for Wind Turbine Applications’ . One aspect of this project, that this thesis attempts to address, is the investigation of the effects of grid events (LVRT) on the electrical systems of the Brushless Doubly Fed Induction Generators, Doubly-Fed Induction Generators and Permanent Magnet Synchronous Generators. The investigation covers the protection of the power electronics during voltage events and the reaction of the generator in these situations. 1.2 Thesis Objective The primary objective of this thesis is the study of the Low Voltage Ride Through (LVRT) characteristics of the Brushless Doubly Fed Induction Generator (B-DFIG) for its application in wind turbines. In order to achieve this goal, the objective has been broken down into a number of subsidiary objectives. These are describes below; 1. Develop a dynamic model for the B-DFIG. 2. Develop a controller based on the use of the B-DFIG as a wind turbine generator. 3. Determine the LVRT performance of the B-DFIG. 4. Compare the LVRT performance of the B-DFIG with those of other prevalent wind turbine generator technologies such as Permanent Magnet Synchronous Machines (PMSM) and Doubly Fed Induction Generators (DFIG). 1.3 Methodology This section describes the approach taken in this thesis. The steps described here also form the layout of this document. 1 Previously published analyses assumed the system to be equivalent to two separate motors with rotors coupled mechanically and electrically. 2 CHAPTER 1. INTRODUCTION Steady State Model The first step taken as part of this thesis is the development of the steady state model of the B-DFIG. This is done by forming phasor equations from the time varying voltage equations of the machine. The machine parameters are derived from the geometry of the machine. Apart from the steady state model forming the basis of the development of the dynamic model, the steady state model becomes a way to check the results of the dynamic model. It also forms a preliminary tool to understand the behaviour expected from the machine. The development of the steady state model has been described in Chapter 2 of this thesis. Dynamic Model The dynamic model of the B-DFIG is developed with a view to study the transient behaviour of the machine. This model is created in the state-space form and implemented as a MATLAB Simulink block model. When the LVRT performance of the machine is to be studied the dynamic model becomes the tool used to study the transition period between two steady states. The development of the dynamic model is described in Chapter 3. Controller for the Machine The B-DFIG operates in the synchronous mode under conditions described in Section 2.1.1. Therefore, for the machine to be used in the intended application (i.e. as a wind turbine generator) it is required to be controlled by the power electronic converter connected to the Control Winding. The control developed is a form of vector control in the stator flux reference frame. The controller developed for use with the B-DFIG as a wind turbine generator is described in Chapter 4. LVRT Performance of the B-DFIG Using the dynamic model and controller developed for the B-DFIG the LVRT performance of the machine under constraints laid down by grid codes is investigated. Methods to improve this performance are also studied. This study is detailed in Chapter 5 of this document. Comparison with other Generators To compare the LVRT performance of the B-DFIG, the LVRT performance of the PMSM and DFIG are simulated. All the three case study generators used are developed for a 3.2MW wind turbine drivetrain. Therefore, they provide a good basis on which a comparison can be made. The dynamic model and controller for all three types of machines have been developed for this thesis, however, only the model and controller for the B-DFIG has been covered in detail. The details of the LVRT performance for the PMSM and DFIG are given in Chapter 5. 3 CHAPTER 1. INTRODUCTION 1.4 Contribution This thesis focuses on the Brushless Doubly Fed Induction Generator. It looks at the modelling, control and performance during low voltage events of a wind turbine based on this machine. Some of the contributions this thesis makes are listed below. This thesis develops the dynamic model and controller for the B-DFIG to be used in a wind turbine. For the control of the machine, a method to generate a reference (Ppref ) signal for optimal operation is developed. This has not been widely covered in literature. It also develops and implements the concept of ‘Cross-Coupling Compensation’. The thesis also compares the LVRT performance of case study B-DFIG, PMSM and DFIG generator based wind turbine drivetrains. 4 Chapter 2 B-DFIG Steady State Modelling Steady state models are an important tool for the study of electrical machines. This chapter explores the development of the steady state model and the steady state characteristics for the Brushless Doubly Fed Induction Machine (B-DFIM). Section 2.1 describes the machine and looks at its operation. Section 2.2 develops the mathematical model of the machine which is used to study the machine in the steady state. Section 2.3 extends this model into a simplified one that helps develop greater insight into the behaviour of the machine. Section 2.4 further used the Γ-transformation to form another simplified model of the machine. Finally, Section 2.5 studies the steady state behaviour of the machine. 2.1 Machine Description The B-DFIM has two sets of 3-phase windings with different pole numbers. One of these windings is termed the ‘Power Winding’ while the other ‘Control Winding’. For machine operation the Power Winding is connected directly to the supply while the Control Winding is connected through a power electronic converter. This is shown in Figure 2.1. B − DF IM Partially Rated P.E. Converter Figure 2.1 Schematic Description of the Brushless Doubly Fed Induction Machine 5 CHAPTER 2. B-DFIG STEADY STATE MODELLING 2.1.1 Machine Operation As can be expected from a machine with two different stator winding configurations the machine can be run in the induction machine mode where either one of the windings are used to run the machine. The machine can also be run as a cascaded induction machine by short circuiting one of the stator windings. However, the most promising operation method of the machine is the synchronous operation. The synchronous mode of operation occurs due to the coupling of the two stator windings (with different pole numbers) through the rotor [10]. In this arrangement, the Power Winding is connected to the supply while the Control Winding is supplied with a voltage of variable frequency as shown in Figure 2.1. In this condition the fundamental airgap fields produced by these windings are given by, bp (θ, t) = B̂p cos(ωp t − pp θ + αp ) bc (θ, t) = B̂c cos(ωc t − pc θ + αc ) (2.1) (2.2) where bp and bc describe the fields produced by the Power Winding and Control Winding respectively with pole pairs pp and pc . ωp and ωc are the excitation frequencies and αp and αc are the phase angles. When the rotor rotates with an angular velocity of ωm the expressions for airgap fields may be written in a reference frame rotating with the rotor as expressed in Equation 2.3 and Equation 2.4. bp (θ0 , t) = B̂p cos((ωp − pp ωm )t − pp θ0 + αp ) bc (θ0 , t) = B̂c cos((ωc − pc ωm )t − pc θ0 + αc ) (2.3) (2.4) The two stator windings will be coupled through the rotor when the frequency and distribution of the currents induced by these two fields in the rotor are equal [10]. For induced frequencies to be equal Equation 2.5 needs to be satisfied. ωp − pp ωm = ωc − pc ωm which gives, ωm = ωp − ωc pp − pc (2.5) (2.6) For the induced currents to have an equal distribution [10], pp 2π 2π = pc + 2qπ Nn Nn (2.7) where Nn are the number of rotor bars. Which gives rise to the condition, pp − pc = qNn (2.8) Nn = pp − pc (2.9) if q=1, this gives, However, as cos(θ) = cos(−θ), Equation 2.4 is equivalent to, bc (θ0 , t) = B̂c cos(−(ωc − pc ωm )t + pc θ0 − αc ) 6 (2.10) CHAPTER 2. B-DFIG STEADY STATE MODELLING Again equating frequencies and phase differences, as in Equation 2.5 and Equation 2.7, gives, ωp − pp ωm = −(ωc − pc ωm ) or, ωm = (2.11) ωp + ωc pp + pc (2.12) For the induced currents to have an equal distribution [10], pp 2π 2π = −pc + 2qπ Nn Nn (2.13) which gives Equation 2.14 if it is assumed that q=1, Nn = pp + pc (2.14) It seems it is better to use Equation 2.14 in selecting the number of rotor bars. This number, however, is still small for practical machine pole numbers. This results in a high rotor leakage inductance [3]. This is combated by using rotor Nest structures. Here, Nn is also taken to be the total number of nests in the rotor structure. When these conditions mentioned above are met, the machine operates in the synchronous mode of operation and performs as a synchronous machine [18]. 2.2 Equivalent Circuit The equivalent circuit for the B-DFIM is shown in Figure 2.2. Here, the equivalent circuit and the voltage equations are shown, these will be derived later in this section. The voltage Rr,1 Rp Lp,σ Up • Lp,m Rc s Lc,σ Uc s • • Lr,1p Rr,2 Lr,2p • Lc,m Lr,1c Lr,2c • • Figure 2.2 Lr,1σ Single Phase Equivalent Circuit. 7 Lr,2σ CHAPTER 2. B-DFIG STEADY STATE MODELLING equations are given by, U p =Rp I p + ωp Lp,σ I p + ωp Lp,m I p + U c Rc = I c + ωp Lc,σ I c + ωp Lc,m I c − s s Nl X l=1 Nl X ωp Mp,nl I 0l (2.15) ωp Mc,nl I 0l (2.16) l=1 Rr,l I + ωp Lr,lσ I r,l + ωp Lr,lm I r,l + ωp Mp,nl I p − ωp Mc,nl I c 0= sp r,l (2.17) where the quantity X represents a complex phasor quantity. All parameters, such as s and sp , are discussed and explained later in the section. 2.2.1 Development of the Equivalent Circuit The remaining part of this section looks at the development of this equivalent circuit. To derive the steady state characteristics of the Brushless Doubly Fed Induction Machine (B-DFIM) a number of assumptions have been made. These are, • The influence of saturation, hysterisis and eddy currents have been neglected. • The rotor is cylindrical, the air gap is uniform and the surfaces of the rotor and stator are smooth neglecting slotting effects. • The phase conductors distributions are perfectly sinusoidal and the currents through the conductors are balanced and sinusoidal. • There is no coupling between the power and control circuit windings. The mutual inductance between the power and control winding is zero. This has been shown in Appendix B. Further, • Each loop is identified by the indices nl where n represents the Nest number and l represents the Loop number. The total number of loops is Nl and the total number of nests is Nn . • The resistance of the stator Power Winding is given by Rp while that of the stator Control Winding is Rc . • The self inductance of the stator Power Winding is Lp while the self inductance of the stator Control Winding is given by Lc . The mutual inductance between phases of the Power Winding is Mp while for the Control Winding this is given by Mc . • The mutual inductance between the stator Power winding and the nl loop is given by M̂p,nl cos(pp ωm t + βnl + pp βp ). Here, βnl is the initial angle between the nl rotor loop and the reference axis while βp is the angle between the stator Power Winding and the reference axis. Similarly, the mutual inductance between the stator Control Winding and the nl loop is given by M̂c,nl cos(pp ωm t + βnl + pc βc ). Again, βc is the angle between the stator control winding and the reference axis. This is detailed in Appendix B and Figure 2.3 shows some of these details. 8 CHAPTER 2. B-DFIG STEADY STATE MODELLING Power Winding Axis Rotor Loop - nl Axis βp βnl a Reference Axis a’ ωm Figure 2.3 Winding Details Given the resistances and inductances of the windings and the mutual inductances between windings, the voltage equations for each winding in the time domain is given by, N up,a N n l X X d = Rp ip,a + (Lp ip,a + Mp ip,b + Mp ip,c + M̂p,nl cos(pp ωm t + βnl )inl ) dt up,b = Rp ip,b + up,c = Rp ip,c + d (Lp ip,b + Mp ip,a + Mp ip,c + dt d (Lp ip,c + Mp ip,b + Mp ip,a + dt l=1 n=1 Nl X Nn X l=1 n=1 Nl X Nn X (2.18) M̂p,nl cos(pp ωm t + βnl )inl ) (2.19) M̂p,nl cos(pp ωm t + βnl )inl ) (2.20) l=1 n=1 Similarly, the voltage equations for the control winding are, N uc,a = Rc ic,a + uc,b = Rc ic,b + uc,c = Rc ic,c + N l X n X d (Lc ic,a + Mc ic,b + Mc ic,c + M̂c,nl cos(pc ωm t + βnl )inl ) dt d (Lc ic,b + Mc ic,a + Mc ic,c + dt d (Lc ic,c + Mc ic,b + Mc ic,a + dt l=1 n=1 Nl X Nn X l=1 n=1 Nl X Nn X (2.21) M̂c,nl cos(pc ωm t + βnl )inl ) (2.22) M̂c,nl cos(pc ωm t + βnl )inl ) (2.23) l=1 n=1 where, up,a , up,b and up,c are the power winding voltage in the three phases. uc,a , uc,b and uc,c are the control winding voltage in the three phases. Similarly, ip,a and ic,a are the currents in the power and control winding in the respective phases. These equations can 9 CHAPTER 2. B-DFIG STEADY STATE MODELLING be written as, N up,a N l X n X dip,a d d M̂p,nl (inl cos(pp ωm t + βnl ) =Rp ip,a + Lp + Mp (ip,b + ip,c ) + dt dt dt l=1 n=1 d + cos(pp ωm t + βnl ) inl ) dt (2.24) N uc,a N l X n X dic,a d d =Rc ic,a + Lc + Mc (ic,b + ic,c ) + M̂c,nl (inl cos(pc ωm t + βnl ) dt dt dt l=1 n=1 d + cos(pc ωm t + βnl ) inl ) dt (2.25) A few aspects of the rotor are now discussed. They help in the next step of the development of the steady state model. It has been seen that the mutual inductance between the stator and rotor depends on the angle between the loop and the reference axis as shown 2π , where Nn is the in Figure 2.3. This value for consecutive rotor nests will differ by Nn number of rotor nests. Assuming that a rotor nest is aligned with the reference axis, the value of the mutual inductance can therefore be written as, 2π ) Nn 2π = M̂c,nl cos(−pc ωm t + pc βc − (n − 1) ) Nn Mp,nl = M̂p,nl cos(pp ωm t − pp βp + (n − 1) (2.26) Mc,nl (2.27) The machine convention used in this derivation is that the Control Winding field is positive when it rotates opposite to the Power Winding field [19]. This causes the difference between the expression for Mc,nl and Mp,nl , i.e. the expression for Mp,nl has a pp ωm t term 2π electrical degrees, while Mc,nl has a −pc ωm t term. Since the rotor loops are displaced by Nn the current will also be displaced by this quantity. The frequency of the currents in these loops is given by Equation 2.3. It can be seen that the magnitude of the currents of the lth loop in all the nests will be equal. The rotor loop currents are given by, 2π ) Nn 2π = Iˆl sin((ωc + pc ωm )t + φnl − (n − 1) ) Nn inl = Iˆl sin((ωp − pp ωm )t + φnl − (n − 1) (2.28) (2.29) where φnl is the phase shift due to the impedence of the loops. Using Equations 2.24, 2.26 and 2.28 the voltage equation can be developed into, up,a Nl X Nn X M̂p,nl Iˆl d dip,a d =Rp ip,a + Lp + Mp (ip,b + ip,c ) + (sin(ωp t − pp βp + φnl ) dt dt 2 dt l=1 n=1 + sin((ωp − 2pp ωm ) + φnl + pp βp − (n − 1) 4π ) Nn (2.30) Here the summation of the second sine term over l = 1 to Nl will be zero due to the 2π (n−1) term. The assumption of balanced currents will also be used and ip,b +ip,c = −ip,a . Nn 10 CHAPTER 2. B-DFIG STEADY STATE MODELLING The Equation 2.30 is therefore simplified to, up,a Nl ωp M̂p,nl Nn Iˆl dip,a X = Rp ip,a + (Lp − Mp ) + cos(ωp t − pp βp + φ0 ) dt 2 (2.31) n=1 A similar analysis on the voltage equation of the stator control winding gives us the following equation, uc,a Nl ωc M̂c,nl Nn Iˆl dic,a X − cos(ωc t − pc βc + φ0 ) = Rc ic,a + (Lc − Mc ) dt 2 (2.32) n=1 Now, the complete voltage equations for the two stator circuits are reproduced below. N up,a = Rp ip,a + (Lp − Mp ) l ωp M̂p,nl Nn Iˆl dip,a X + cos(ωp t − pp βp + φ0 ) dt 2 up,b = Rp ip,b + (Lp − Mp ) dip,b + dt up,c = Rp ip,c + (Lp − Mp ) dip,c + dt uc,a = Rc ic,a + (Lc − Mc ) dic,a − dt uc,b = Rc ic,b + (Lc − Mc ) dic,b − dt uc,c = Rc ic,c + (Lc − Mc ) dic,c − dt n=1 Nl X n=1 Nl X n=1 ωp M̂p,nl Nn Iˆl cos(ωp t − pp βp + φ0 ) 2 (2.34) ωp M̂p,nl Nn Iˆl cos(ωp t − pp βp + φ0 ) 2 (2.35) Nl X ωc M̂c,nl Nn Iˆl n=1 Nl X n=1 Nl X n=1 (2.33) cos(ωc t − pc βc + φ0 ) (2.36) ωc M̂c,nl Nn Iˆl cos(ωc t − pc βc + φ0 ) 2 (2.37) ωc M̂c,nl Nn Iˆl cos(ωc t − pc βc + φ0 ) 2 (2.38) 2 For the rotor, the voltage equation of the nlth loop is given by, 0 =Rr inl + Nl X Nn X l=1 n=1 Mnlnl d d 2π inl + (M̂p,nl cos(pp ωm t − pp βp + (n − 1) )ip,a dt dt Nn 2π 2π − )ip,b Nn 3 2π 4π + M̂p,nl cos(pp ωm t − pp βp + (n − 1) − )ip,c ) Nn 3 d 2π )ic,a + (M̂c,nl cos(−pc ωm t + pc βc − (n − 1) dt Nn 2π 2π + M̂c,nl cos(−pc ωm t + pc βc − (n − 1) − )ic,b Nn 3 4π 2π + M̂c,nl cos(−pc ωm t + pc βc − (n − 1) − )ic,c ) Nn 3 + M̂p,nl cos(pp ωm t − pp βp + (n − 1) 11 (2.39) CHAPTER 2. B-DFIG STEADY STATE MODELLING where Mnlnl is the mutual inductance between the loops. The current in the stator circuits is given by, ip,a = Iˆp sin(ωp t + φp ) 2π = Iˆp sin(ωp t + φp − ) 3 4π ) = Iˆp sin(ωp t + φp − 3 ip,b ip,c (2.40) (2.41) (2.42) and ic,a = Iˆc sin(ωc t + φc ) 2π ) 3 4π ) = Iˆc sin(ωc t + φc + 3 (2.43) ic,b = Iˆc sin(ωc t + φc + (2.44) ic,c (2.45) Here, it can be seen that the phase sequence of the stator control circuit currents is taken to be opposite to that of the stator power circuits. The Equation 2.39 is simplified to, 0 =Rr inl + Nl X Nn X d 3 2π d inl + ( M̂p,nl Iˆp sin((ωp − pp ωm )t + pp βp + φp − (n − 1) ) dt dt 2 Nn Mnlnl l=1 n=1 2π 3 )) − M̂c,nl Iˆc sin((ωc + pc ωm )t − pc βc + φc + (n − 1) 2 Nn (2.46) or, 0 =Rr inl + Nl X Nn X 2π (ωp − pp ωm )Mnlnl Iˆnl cos((ωp − pp ωm )t + φnl − (n − 1) ) Nn l=1 n=1 3 2π + (ωp − pp ωm )M̂p,nl Iˆp cos((ωp − pp ωm )t + pp βp + φp − (n − 1) ) 2 Nn 3 2π − (ωc + pc ωc )M̂c,nl Iˆc cos((ωc + pc ωm )t − pc βc + φc + (n − 1) ) 2 Nn (2.47) This defines the complete set of voltage equations for the machine. They are now transformed into phasor equations from which the equivalent circuit can be derived. The voltage equation of the stator power winding for a single phase reproduced below for surveyability. N up,a l ωp M̂p,nl Nn Iˆl dip,a X = Rp ip,a + (Lp − Mp ) + cos(ωp t + pp βp + φ0 ) dt 2 (2.48) n=1 Nn A transformation for the rotor current such that, Il0 = Il is used. The transform Mp,nl = 3 3 M̂p,nl is also used. Therefore, 2 N up,a = Rp ip,a + (Lp − Mp ) l dip,a X + ωp Mp,nl Iˆl0 cos(ωp t + pp βp + φ0 ) dt n=1 12 (2.49) CHAPTER 2. B-DFIG STEADY STATE MODELLING Taking up,a = Ûp sin(ωp t), Equation 2.49 can be extended to all three phase equations as, Im(Up eωp t ) =Im(Rp Ip eφp eωp t ) + Im(ωp (Lp − Mp )Ip eφp eωp t ) + Nl X Im(ωp Mp,nl In e(pp βp +φnl ) eωp t ) Nl X Im(ωp Mp,nl In e(pp βp +φnl ) eωp t ) Nl X Im(ωp Mp,nl In e(pp βp +φnl ) eωp t ) 0 (2.50) n=1 Im(Up e− 2π 3 eωp t ) =Im(Rp Ip e(φp − + 2π ) 3 eωp t ) + Im(ωp (Lp − Mp )Ip e(φp − 2π ) 3 eωp t ) 0 (2.51) n=1 − 4π ωp t 3 Im(Up e e ) =Im(Rp Ip e(φp − + 4π ) 3 eωp t ) + Im(ωp (Lp − Mp )Ip e(φp − 4π ) 3 eωp t ) 0 (2.52) n=1 Removing the imaginary function and using phasor notation to represent the equations, U p = Rp I p + ωp (Lp − Mp )I p + Nl X ωp Mp,nl I 0l (2.53) l=1 A similar exercise is now done on the voltage equations of the stator control winding circuit. N uc,a = Rc ic,a + (Lc − Mc ) l dic,a X − ωc Mc,nl Iˆl cos(ωc t + pc βc + φ0 ) dt (2.54) n=1 First, the slips for the machine are defined, these are sp and s which are given by, ωp − pp ωm ωc + pc ωm = ωp ωc ωc s= ωp sp = (2.55) (2.56) Also, uc,a = Ûc sin(ωc t + θc ) and, Im(Uc eθc eωc t ) =Im(Rc Ic eφc eωc t ) + Im(ωc (Lc − Mc )Ic eφc eωc t ) + Nl X 0 Im(ωc Mcn In e(pc βc +φnl ) eωc t ) n=1 13 (2.57) CHAPTER 2. B-DFIG STEADY STATE MODELLING which, using Equation 2.56 can be written for all phases as, Im(Uc eθc esωp t ) =Im(Rc Ic eφc esωp t ) + Im(sωp (Lc − Mc )Ic eφc esωp t ) − Im(Uc e(θc − 2π ) 3 Im(sωp Mcn In e(pc βc +φnl ) esωp t ) Nl X Im(sωp Mcn In e(pc βc +φnl ) esωp t ) Nl X Im(sωp Mcn In e(pc βc +φnl ) esωp t ) 0 (θc − 4π ) sωp t 3 e 2π ) 3 esωp t ) + Im(sωp (Lc − Mc )Ic e(φc − 2π ) 3 esωp t ) 0 (2.59) n=1 ) =Im(Rc Ic e(φc − − (2.58) n=1 esωp t ) =Im(Rc Ic e(φc − − Im(Uc e Nl X 4π ) 3 esωp t ) + Im(sωp (Lc − Mc )Ic e(φc − 4π ) 3 esωp t ) 0 (2.60) n=1 Using phasor notation, the equation can be expressed as, N l X Uc Rc = I c + ωp (Lp − Mp )I c − ωp Mp,nl I 0l s s (2.61) l=1 The rotor voltage equations are now reproduced below. 0 =Rr inl + Nl X Nn X (ωp − pp ωm )Mnlnl Iˆnl cos((ωp − pp ωm )t + φnl − (n − 1) l=1 n=1 2π ) Nn 2π + (ωp − pp ωm )Mp,nl Iˆp cos((ωp − pp ωm )t − pp βp + φp − (n − 1) ) Nn 2π − (ωc + pc ωc )Mc,nl Iˆc cos((ωc + pc ωm )t − pc βc + φc + (n − 1) ) Nn (2.62) or, Nl X 0 =Rr inl + (ωp − pp ωm )Mnlnl Iˆl0 cos((ωp − pp ωm )t + φnl ) l=1 2π ) + (ωp − pp ωm )Mp,nl Iˆp cos((ωp − pp ωm )t − pp βp + φp − (n − 1) Nn 2π − (ωc + pc ωc )Mc,nl Iˆc cos((ωc + pc ωm )t − pc βc + φc + (n − 1) ) Nn (2.63) The procedure followed for the stator voltage equations are repeated, and the rotor voltage equation becomes, Nl X Rr,l 0 φnl sp ωp t 0 =Im( Ie e )+ Im(ωp Mnlnl Il0 eφnl esp ωp t ) sp l m=1 2π (−pp βp +φp −(n−1) N ) sp ωp t n + Im(ωp Mp,nl Ip e − Im(sp ωp Mc,nl Ic e e ) 2π ) sp ωp t (−pc βc +φc+(n−1) N n e 14 ) (2.64) CHAPTER 2. B-DFIG STEADY STATE MODELLING which is expressed in the phasor form for each rotor loop as, 0= Rr,l 0 I + ωp Lr,l I 0l + ωp Mp,nl I p − ωp Mc,nl I c sp l (2.65) The voltage equations are now reproduced in the phasor form, with inductances split into the leakage and main part, below, U p =Rp I p + ωp Lp,σ I p + ωp Lp,m I p + U c Rc = I c + ωp Lc,σ I c + ωp Lc,m I c − s s Nl X l=1 Nl X ωp Mp,nl I 0l (2.66) ωp Mp,nl I 0l (2.67) l=1 Rr,l 0= I + ωp Lr,lσ I r,l + ωp Lr,lm I r,l + ωp Mp,nl I p − ωp Mc,nl I c sp r,l (2.68) On the basis of these equations, i.e. Equations 2.66, 2.67 and 2.68 the equivalent circuit for the BDFM shown in Figure 2.2 is formed. It is also important to look at what happens to the equivalent circuit under hypernatural operation of the machine. As per the convention used, the voltage for the stator control circuit would be given by, uc,a =Ûc sin(ωc t + θc ) 4π ) 3 2π =Ûc sin(ωc t + θc − ) 3 (2.69) uc,b =Ûc sin(ωc t + θc − (2.70) uc,c (2.71) As the phase sequence of this is different to that of the power and rotor circuits, it needs to be transformed so as to include it in the equivalent circuit. This is done as follows, uc,a = − Ûc sin(−ωc t − θc ) (2.72) uc,b (2.73) uc,c 4π = − Ûc sin(−ωc t − θc + ) 3 2π = − Ûc sin(−ωc t − θc + ) 3 (2.74) The phase sequence now is identical for all the circuits and the control circuit can now be added to the equivalent circuit. Also, in the convention a negative value for ωc during operation at hyper-natural speeds has been considered. Therefore we have, uc,a =Ûc sin(ωc t + (−θc + π)) 4π ) 3 2π =Ûc sin(ωc t + (−θc + π) + ) 3 (2.75) uc,b =Ûc sin(ωc t + (−θc + π) + (2.76) uc,c (2.77) Therefore, during hyper-natural operation, a phase difference of θc for the stator control circuit voltage must be taken as (−θc + π) in the steady state equivalent circuit. 15 CHAPTER 2. B-DFIG STEADY STATE MODELLING 2.2.2 Power Balance Equations The apparent power input to the machine is given by, Sp = Up Ip∗ (2.78) Sc = Uc Ic∗ (2.79) This gives the expressions for the Active Power input to the machine as, Ip2Rp Ir2Rr Pm Ic2Rc Pp Pp,ag Pc,ag Pc (a) P OW ER W IN DIN G ROT OR CON T ROL W IN DIN G Ip2Rp Ir2Rr Pm Pp Ic2Rc Pp,ag Pc,ag Pc (b) Figure 2.4 Power Flow in Motoring Mode neglecting Iron losses (a) for Sub-Natural Speeds and (b) for Hyper-Natural Speeds. Pp = <(Up Ip∗ ) Pc = <(Uc Ic∗ ) (2.80) (2.81) A part of this power is lost in the form of copper losses in the stator windings. Thus the air-gap power transferred to the rotor may be given by, Pp,ag = Pp − Pp,cu Pc,ag = Pc − Pc,cu (2.82) (2.83) A part of this air-gap power is lost as copper losses and iron losses in the rotor. The remaining power is available as mechanical power to the shaft. This is shown in Equation 2.84. Pm = Pp,ag + Pc,ag − Pr,cu − PF e (2.84) Figure 2.4 gives a schematic representation of this while neglecting the iron losses in the machine. 16 CHAPTER 2. B-DFIG STEADY STATE MODELLING 2.3 Simplified Equivalent Circuit A simplification to this equivalent circuit shown in Figure 2.2 can be made by transforming the stator and rotor circuits onto a single circuit. This can be done by first transforming the control winding circuit onto the rotor circuit. Then transforming this onto the power winding circuit. This has been shown below for a single rotor loop, but can be extended to include multiple rotor loops. The first step is the transformation of the control winding to the rotor. The transformation ratio is given by, Lc,m = a2 (2.85) Lr,c This transform can be seen in Figure 2.5. The transformed parameters are given by, Rp Up Uc0 s • Lp,σ • Figure 2.5 Lr,σ Lr,p Lp,m Rc0 s Rr sp L0c,σ L0c,m First Step in the Simplified Equivalent Circuit Formation. 1 Rc a2 1 = 2 Lc,σ a = Lr,c Rc0 = L0c,σ L0c,m (2.86) (2.87) (2.88) The next step is to transform this circuit onto the power winding circuit. This transformation ratio is given by Lp,m = a02 (2.89) Lr,p The transformed parameters are given by, a02 Rc a2 a02 = a02 L0c,σ = 2 Lc,σ a 02 0 = a Lc,m = a02 Lr,c Rc00 = a02 Rc0 = L00c,σ L00c,m Rr0 L0r,σ (2.90) (2.91) (2.92) 02 = a Rr (2.93) = a02 Lr,σ (2.94) 17 CHAPTER 2. B-DFIG STEADY STATE MODELLING The thus simplified equivalent circuit is shown in Figure 2.6. Rp Rr0 sp Lp,σ Up L0r,σ Rc00 s Uc00 s L0c,m Lp,m Figure 2.6 L00c,σ Simplified Equivalent Circuit. This can be extended to machine with multiple rotor loops to form the equivalent circuit shown in Figure 2.7. Rp Up Lp,σ L0r,2σ 0 Rr,1 sp L0r,1σ L00c,σ L0c,m Lp,m Figure 2.7 2.4 0 Rr,2 sp Rc00 s Uc00 s Simplified Equivalent Circuit. The Γ-Equivalent Circuit The Γ-equivalent is another simplified model. This equivalent circuit can be seen in Figure 2.8. This has been shown for a circuit with a single rotor loop but can be extended to include multiple loops as well. The parameters [20] are given by, where, L0c,m−γ = αL0c,m (2.95) Lp,m−γ = α0 Lp,m Lr,σ−γ = α02 α2 L0r,σ + αL00c,σ + α0 Lp,σ (2.96) L00c,σ + L0c,m L0c,m Lp,σ + Lp,m α0 = Lp,m α= 18 (2.97) (2.98) (2.99) CHAPTER 2. B-DFIG STEADY STATE MODELLING Up L0rσ−γ Rr0 sp Rp Rc00 s Uc s L0cm−γ Lpm−γ Figure 2.8 Γ-Equivalent Circuit. As described by McMahon et al. [18], the equivalent circuit for the inner core of the machine (i.e. the circuit obtained by omiting the magnetising reactances and the stator and rotor resistances) resembles the circuit for a synchronous machine. This has been reproduced in Figure 2.9, ωp L0rσ−γ Uc00 s Up Figure 2.9 Equivalent Circuit for Core. This leads us to believe that the performance of the BDFM must be similar to that of the synchronous machine with a synchronous speed given by, ωm,syn = 2.5 ωp − ωc Nn (2.100) Steady State Characteristics The steady state characteristics are shown in Figure 2.10. The figure follows the convention that power flow into the machine is positive and power flow out of the machine is negative. It can be seen that at speeds below the natural speeds (i.e. sub-natural speeds) the control circuit acts in the motoring mode while the power winding acts in the generating mode. While at speeds above the natural speed (i.e. hyper-natural speeds), the control and power winding circuits, both act in the generating mode. This is also highlighted in Figure 2.4. The machine parameters used for the simulations are based on the case study machine detailed in Appendix C. The Power Winding circuit and the Control Winding circuit are fed by two independent voltage sources. As the power circuit is connected directly to the grid, we assume a constant voltage and frequency for this circuit. For the results shown in this section, the power circuit frequency ωp was taken to be fixed at 2 × π × 50 rad/s. The frequency of the control circuit is fixed as per the Equation 2.12 for the rotor speeds taken in each case. As the control 19 CHAPTER 2. B-DFIG STEADY STATE MODELLING 200 Net Power Power Circuit Power Control Circuit Power 0 Power (kW) −200 −400 −600 −800 −1000 0 5 10 Figure 2.10 15 20 25 Speed of Rotation (rad/s) 30 35 40 45 50 Power-Speed Characteristics of B-DFIG. circuit is fed through a power electronic converter it is possible to control its phase with respect to Up which is taken as the reference vector. Figure 2.11 explores the operation of the machine when ωc = −25% of ωp and the ωp . The phase difference between Uc and the rotational speed is given by, ωm = 0.75 Nn reference Up is varied between −π and +π. The effect of this on the circuit is shown. 450 Power Circuit Power Control Circuit Power Net Power 300 350 200 300 100 0 250 200 −100 150 −200 100 −300 50 −400 0 −100 0 100 Uc angle with Up (degrees) Figure 2.11 Ip Ic Ir 400 Current (kA) Power (MW) 400 Ip angle Ic angle Ir angle 150 Angle of Current with Up (degrees) 500 100 50 0 −50 −100 −150 −100 0 100 Uc angle with Up (degrees) −100 0 100 Uc angle with Up (degrees) ωp with constant magnitude input voltages and Nn variation of phase angle between them. Characteristics for ωm = 0.75 Figure 2.12 explores the operation of the machine when ωc = +25% of ωp and the ωp rotational speed is given by, ωm = 1.25 . The circuit used for these simulations is the Nn equivalent circuit as in Figure 2.2. 20 CHAPTER 2. B-DFIG STEADY STATE MODELLING 450 Power Circuit Power Control Circuit Power Net Power Ip Ic Ir 400 400 350 300 Current (kA) Power (MW) 200 0 −200 250 200 150 100 −400 50 −600 −100 0 0 100 Uc angle with Up (degrees) Figure 2.12 2.6 Ip angle Ic angle Ir angle 150 Angle of Current with Up (degrees) 600 100 50 0 −50 −100 −150 −100 0 100 Uc angle with Up (degrees) −100 0 100 Uc angle with Up (degrees) ωp with constant magnitude input voltages and Nn variation of phase angle between them. Characteristics for ωm = 1.25 Discussion From the characteristics of Section 2.5, a number of observations can be made. First, the power flow for the conditions of sub-natural and hyper-natural speeds of operation can be clearly observed from Figure 2.11 and Figure 2.12. During sub-natural operation, the power flow in the power and control winding are in the opposite direction, while in the hyper-natural mode of operation, the power flow in both the stator circuits flow in the same direction (i.e. if power flows into the stator power winding circuit then power also flows into the stator control winding circuit and vice versa). Second, it can be observed that at two separate operating points, i.e. at φp,c = 0 and φp,c = ±π (where, φp,c is the phase angle difference between Up and Uc ), we have zero power output. It is interesting to note that at these points the values of power winding, control winding and rotor current are different. This fact can be explained by looking at the stator flux wave and rotor position. Figure 2.13 describes the condition for φp,c = ±π. The flux linked with the rotor loop is maximum and hence, the rotor currents are maximum. The torque in this position on both conductors that make up the loop will be opposite and equal, causing the net torque to be zero. Figure 2.14 decribes the condition for φp,c = 0. The flux linked with the rotor loop will be zero and therefore, rotor currents will be minimum. Due to this zero flux linkage, the torque produced will be zero. Third, for the condition φp,c = ±π, we see that a small perturbation in the positive x direction will increase the torque in that direction will reducing the opposing torque, causing the rotor to run-off in the positive x direction. Similarly, a perturbation in the negative x direction will cause a run-off in the negative x direction. This operating point is therefore, unstable. In contrast, the condition given by φp,c = 0 is stable. This will be further studied during the dynamic simulation of the machine. 21 CHAPTER 2. B-DFIG STEADY STATE MODELLING Stator Flux Wave Rotor Loop Stator Flux Wave and Rotor Loop at φp,c = ±π. Figure 2.13 Stator Flux Wave Rotor Loop Figure 2.14 Stator Flux Wave and Rotor Loop at φp,c = 0. 500 Power Circuit Power Control Circuit Power Net Power Stable Region Unstable Region 400 Power (MW) 300 Unstable Region 200 100 0 −100 −200 −300 −400 −150 −100 −50 0 50 100 150 Uc angle with Up (degrees) Figure 2.15 Stable and Unstable Operating Ranges for ωm = 0.75 22 ωp . Nn Chapter 3 B-DFIG Dynamic Modelling To study the behaviour of the machine during grid events, it is necessary to develop a dynamic model of the B-DFIG based wind turbine drivetrain. The development of the dynamic model is discussed in this chapter. Section 3.1 describes the dynamic model using differential equations. Section 3.2 represents the dynamic model graphically sing block diagrams and finally, Section 3.3 describes the response of the developed model. 3.1 The Dynamic Equations of the Machine In this section the dynamic voltage equations of the B-DFIG are developed. First, the convention used in this chapter and the rest of the document is described. As an example, ūxa , gives the voltage vector ū for the a circuit in the x reference frame. Similarly, ux,d a , gives the voltage u for the a circuit in the d-axis of the x reference frame. The vector ūxa can be represented as, x,d u x ūa = ax,q (3.1) ua Now, the voltage equations for the B-DFIG are given by, dλ̄sp dt dλ̄s ūsc = Rc i¯sc + c dt dλ¯r 0 = Rr i¯rr + r dt ūsp = Rp i¯sp + (3.2) where, the flux linkages are given by, λ¯sp = Lp i¯sp + Mpr i¯sr λ¯sc = Lc i¯sc − Mcr i¯sr λ¯rr = Lr i¯rr + Mpr i¯rp − Mcr i¯rc (3.3) (3.4) (3.5) These equations come from the equivalent circuit developed in the previous chapter. Here, the vectors (such as λ̄rr ,īsp etc.) are all in different reference frames. To combine these 23 CHAPTER 3. B-DFIG DYNAMIC MODELLING equations to form the dynamic model of the machine, they are transformed into a common reference frame. First, the transformation of the quantities in the abc domain to the stator reference frame is looked at. This is done through the Clarks’ transform shown below. 1 1 − r 1 − √2 xa √2 xα 3 3 → − −1 xβ = 2 x abc (3.6) xb = Cαβ,abc 0 − 3 2 2 x0 x 1 c 1 1 √ √ √ 2 2 2 For the ease of control of the machine the selection of a reference frame will be made later in this document. Therefore, it is desirable to create a model in an arbitrary reference frame. Figure 3.1 show the positioning of the two stator reference frames and the rotor reference frames related to the pp and pc pole pair distributions. Here, the Power Winding αp βp reference frame is taken to be the overall static reference frame. βp βrc αrp, αrc βrp θm αp, αc π 2pc βc Figure 3.1 B-DFIG Reference Frames with mechanical angles First, the quantities in the Control Winding αc βc reference frame are transformed to the overall static reference frame, i.e. the αp βp . For the operation of the machine it has been shown that Equation 2.11 and Equation 2.14 are to be met. Therefore, a vector x̄ in the αrp βrp and the αrc βrc are related by Equation 3.7. x̄αrc βrc = x̄αrp βrp (3.7) x̄αc βc = Crot (−pc θm )x̄αrc βrc (3.8) Using Figure 3.1, x̄ αp βp = Crot (pp θm )x̄ αrp βrp (3.9) where, cos θ − sin θ Crot (θ) = sin θ cos θ 24 (3.10) CHAPTER 3. B-DFIG DYNAMIC MODELLING Using Equation 3.7 - Equation 3.9 the transformation of a quantity from the Control Winding αc βc reference frame to the Power Winding αp βp reference frame is given by, x̄αp βp = Crot ((pp + pc )θm )x̄αc βc (3.11) Therefore, if an arbitrary reference frame rotating with an angular speed of ωk with respect to the Power Winding static reference frame is chosen, the voltage equation can be written as, ūkp = Rp īkp + Crot (−θk ) d Crot (θk )λ¯kp dt (3.12) ūkc = Rc īkc + Crot (−(θk − (pp + pc )θm )) 0 = Rr īkr + Crot (−(θk − pp θm )) d Crot dt d Crot ((θk − (pp + pc )θm ))λ¯kc dt ((θ − p θ ))λ¯k k p m r (3.13) (3.14) where, dθk = ωk dt dθm = ωm dt (3.15) (3.16) This simplifies to, k 0 −1 ¯k dλ̄p λp + = + ωk 1 0 dt 0 −1 ¯k dλ̄kc λc + ūkc = Rc īkc + (ωk − (pp + pc )ωm ) 1 0 dt 0 −1 ¯k dλ̄kr λp + 0 = Rr īkr + (ωk − pp ωm ) 1 0 dt ūkp Rp īkp The equations of the dynamic model, rewritten in state-space form, are given by, dλkp 0 −1 ¯k k k λp = ūp − Rp īp − ωk 1 0 dt dλkc 0 −1 ¯k k k = ūc − Rc īc − (ωk − (pp + pc )ωm ) λc 1 0 dt dλkr 0 −1 ¯k k = −Rr īr − (ωk − pp ωm ) λr 1 0 dt k k īp λ̄p Lp 0 Mpr īkc = inv 0 Lc −Mcr λ̄kc k Mpr −Mcr Lr īr λ̄kr (3.17) (3.18) (3.19) (3.20) (3.21) (3.22) (3.23) A further look at these equations will be taken when the control for the machine is discussed. To complete the dynamic model, the expression for power is computed. The total electrical power at the terminals of a stator winding is given by, ps = ūTs,abc īs,abc 25 (3.24) CHAPTER 3. B-DFIG DYNAMIC MODELLING using the Clark’s transform defined in Equation 3.6, −1 −1 ps =(Cαβ,abc ūs,αβ )T (Cαβ,abc īs,αβ ) (3.25) s,α ps =us,α s is s =īsT s ūs (3.26) + s,β us,β s is (3.27) The voltage equation of the stator in the stator reference frame is reproduced below, ūss = Rs īss + dλ̄ss dt (3.28) the flux linkage λ̄ss may be considered to be made up of two parts, the leakage flux linkage λ̄ss,σ and the main flux linkage λ̄ss,m . Therefore, the equation may be expressed as, dλ̄ss,σ dλ̄ss,m + dt dt s d ī dīs dīs =Rs īss + Ls,σ s + Ls,m s + Msr r dt dt dt The differential of the currents in the stator reference frame is given by, s,β dθ d is,α dθ 0 −1 is,α −is s s p = s,β p s,β = s,α 1 0 is is dt is dt dt ūss =Rs īss + The voltage equation can therefore be given by, 0 −1 s dθ 0 −1 s dθ s s ī p + Msr ūs =Rs īs + (Ls,σ + Ls,m ) ī p 1 0 s dt 1 0 r dt From this voltage equation the power in the winding may be expressed as, sT s sT 0 −1 s dθ sT 0 −1 s dθ ps =Rs īs īs + (Ls,σ + Ls,m )īs ī p + Msr īs ī p 1 0 s dt 1 0 r dt (3.29) (3.30) (3.31) (3.32) (3.33) It can be seen that the first term represents the resistance loss in the winding, the second and third terms will be equal to zero and the remaining term represents the power converted into mechanical power. The torque is given by, dθ dt Therefore, the electromagnetic torque can be given by, sT 0 −1 s Te =pMsr īs ī 1 0 r pm = Te s,α s,α s,β =pMsr (is,β s ir − is ir ) (3.34) (3.35) (3.36) This expression is extended to form the torque expression for the B-DFIG by taking into account the two stator windings. This is expressed as, s,α s,α s,β s,β s,α s,α s,β Te = pp Mpr (is,β p ir − ip ir ) + pc Mcr (ic ir − ic ir ) (3.37) If the Park’s transform is used, the equation in the stator reference frame may be converted to a rotating reference frame, k,d k,d k,q k,q k,d k,d k,q Te = pp Mpr (ik,q p ir − ip ir ) + pc Mcr (ic ir − ic ir ) 26 (3.38) CHAPTER 3. B-DFIG DYNAMIC MODELLING 3.2 Dynamic Model in the Block Diagram Form From the voltage equations derived in the previous section (Equation 3.20-Equation 3.23 and Equation 3.38) the dynamic model of the B-DFIG in an arbitrary reference frame is presented in block diagram form in Figure 3.2. ūkp − 0 −1 1 0 1 s − X ωk īkr λ̄kp Rp ūkc − 1 s X λ̄kc − 1 s Mux X Figure 3.2 De-Mux + Te + λ̄kr īkr 0 −1 1 0 īkr M ωrk Rr īkp īkc 0 −1 1 0 − pp Mpr ωck Rc . īkp 0 −1 1 0 − 0 −1 1 0 . pc Mcr īkc Dynamic Model of the B-DFIG in the arbitrary reference frame ‘k’ 27 CHAPTER 3. B-DFIG DYNAMIC MODELLING where the matrix M is given by, Lp,σ + Lp,m 0 Mpr 0 Lc,σ + Lc,m −Mcr M = inv Mpr −Mcr Lr,σ + Lr,m (3.39) and, ωck =ωk − (pp + pc )ωm ωrk =ωk − pp ωm 28 (3.40) (3.41) CHAPTER 3. B-DFIG DYNAMIC MODELLING 3.3 Dynamic Behaviour In this section the dynamic behaviour of the B-DFIG is discussed. The operation in the stable state for sub-natural speeds as described in Figure 2.15 is shown. Figure 3.3a shows the torque output of the machine, operating in steady state in the stable region, with a 10% step increase in the load torque at t = 15s with a constant frequency on the control circuit. Figure 3.3b shows the speed response for the condition. When the 5600 15.716 Generator Torque Load Torque 5500 15.714 5400 15.712 Speed (rad/s) Torque (kNm) 5300 5200 5100 5000 15.71 15.708 15.706 4900 15.704 4800 15.702 4700 4600 0 5 10 15 20 25 30 35 40 45 15.7 0 50 5 10 15 20 Time (s) (a) Figure 3.3 25 30 35 40 45 50 Time (s) (b) Step Response in Stable Region with a 10% Step increase in Load Torque (a) Torque Response (b) Speed Response. step change in load torque is applied the machine torque also increases and oscillates around the load torque value. The speed also oscillates, however, the oscillations remains around the stable speed before the change in load. As the Control Winding frequency has been kept constant, the machine acts as a synchronous machine. This is the reason the speed of the machine oscillates around the original speed. The response for the machine in the unstable region is also shown, in Figure 3.4. Figure 3.4a shows the torque output of the machine, operating in steady state in the unstable region, with a 10% step increase in the load torque at t = 15s with a constant frequency on the control circuit. Figure 3.4b shows the speed response for this condition. In this case the machine is unable to take an increase in load torque. The machine torque oscillates around zero and the machine speed reduces. 8000 15.8 Generator Torque Load Torque 6000 15.6 15.4 4000 Speed (rad/s) Torque (kNm) 15.2 2000 0 −2000 15 14.8 14.6 14.4 −4000 14.2 −6000 −8000 0 14 5 10 15 20 25 30 35 40 45 13.8 0 50 Time (s) 10 15 20 25 30 35 40 45 50 Time (s) (a) Figure 3.4 5 (b) Step Response in Stable Region with a 10% Step increase in Load Torque (a) Torque Response (b) Speed Response. These characteristics lead to a number of observations. First, they reinforce the discussion on the stable and unstable regions of operation in the previous chapter. It can be seen 29 CHAPTER 3. B-DFIG DYNAMIC MODELLING that a perturbation in the unstable region causes the rotor to run off as can be seen in the speed characteristics in Figure 3.4b. Second, the characteristics can be seen to be similar to those of a synchronous machine. This has already been seen in the previous chapter, refer Figure 2.9, the equivalent circuit for the B-DFIG can be seen as a synchronous machine. This is confirmed by the response of the B-DFIG dynamic model. 3.4 Discussion This chapter has focussed on the creation of the dynamic model. Section 3.1 has developed the dynamic model equations. This has been done in the arbitrary reference frame such that a suitable choice of reference frame could be made when the control of the machine is investigated. Section 3.2 has developed these equations into a block form which can be implemented in Simulink. Finally, Section 3.3 discussed aspects of the dynamic behaviour of the machine. The results confirmed the observations made in Chapter 2. 30 Chapter 4 B-DFIG Control This chapter aims at the development of the control system for the operation of the B-DFIG. A system level view of the B-DFIG in a wind turbine application is given in Figure 4.1. The control developed in this thesis is based on the vector control method and employs two cascaded current loops. Figure 4.1 System Level B-DFIG Schematic This chapter is organised in the following manner, Section 4.1 develops the wind turbine drivetrain for the study. Section 4.2 develops the method to generate reference signals for optimal power extraction. Section 4.3 looks at the control for Active and Reactive Power. It looks at the rationale behind the choice of the controlled quantity, i.e. Power Winding Active Power Pp in this case, and develops the control scheme for the machine. Section 4.4 looks at the tuning of the PI controllers used. Section 4.5 describes the control behaviour of the machine and Section 4.6 discusses the results. 31 CHAPTER 4. B-DFIG CONTROL 4.1 Wind Turbine Drivetrain System This section looks at the components of the wind turbine drivetrain. This is discussed for the three generator types used in this study - the B-DFIG, the DFIG and the PMSM. Wind Turbine Rotor The wind turbine rotor is responsible for converting the kinetic energy in the wind to rotational energy that is used in the generator. This thesis does not focus in the characteristics of the rotor. However, a simple model that calculates the torque on the rotor based on the wind speed is discussed. The power in the wind airflow is given by [21], 1 Pwind = ρAv 3 2 (4.1) where, ρ is the air density, A is the swept area of the rotor and v is the upwind free wind speed. The power transferred from the wind through the wind turbine rotor to the shaft connected to the gearbox is given by, Pturbine = Cp Pwind (4.2) where Cp is the power coefficient. The wind model is important for two reasons, first, it is used to model the wind as a load for the turbine and second, it is used to generate the reference signal for the control of the machine. The power transferred to the turbine by the wind is given by Equation 4.2. It has been ωm R shown that Cp varies with the tip speed ratio (λt = ) and the pitch angle (θ), where v R is the radius of the wind turbine rotor. Here, the following numerical approximation [22] is used for the estimation of Cp , 1 −C 1 − C3 λi θ − C4 θCx − C5 )e 6 λi λi 1 1 0.035 = − λi λt + 0.08θ θ3 + 1 Cp (λi , θ) =C1 (C2 (4.3) (4.4) The region of pitch control is not considered here. Therefore the pitch angle is assumed to be constant, i.e. θ = 0. The coefficients used are, C1 = 0.5, C2 = 218, C3 = 0.4, C4 = 0, C5 = 10.5 and C6 = 25. The variation of Cp with the tip speed ratio is shown in Figure 4.2. For wind speeds above vrated the pitch of the blades is controlled to maintain constant load torque. The Load Torque can therefore be defined as, 1 v3 ρACp (λt ) if v < vrated ωm Tload = 2 (4.5) 3 v 1 ρACp (λt , θ) rated if v ≥ vrated 2 ωm 32 CHAPTER 4. B-DFIG CONTROL 0.5 0.45 0.4 0.35 Cp 0.3 0.25 0.2 0.15 0.1 0.05 0 0 2 4 6 8 10 12 Tip Speed Ratio Figure 4.2 Variation of Cp with λt Gearbox The gearbox transforms the speed of the rotor into one that can be better utilised by the generator. In this thesis the gearbox has been considered to be lossless. Generator The generator converts the rotational kinetic energy of the wind turbine rotor into electrical energy. Three generators have been considered here - the PMSM, the DFIG and the BDFIG. Figure 4.3 shows the drivetrains for the wind turbine with each of these generators. (a) (b) (c) Figure 4.3 Drivetrain Schematic (a) with B-DFIG (b) with DFIG (c) with PMSM The generators in this study are based on a 3.2MW generator design and are detailed in Appendix D, E and Appendix F. The dynamic model for the B-DFIG is developed in 33 CHAPTER 4. B-DFIG CONTROL Chapter 3 while the equations describing the dynamic behaviour of the PMSM and DFIG machines are in Appendix D and Appendix E respectively. Power Electronic Converter and Controller The power electronic converter for the B-DFIG and DFIG based wind turbine drivetrains are partially rated while the PMSM employs a fully rated converter. The design of the controller for this machine is detailed in this chapter. The control is based on a vector control algorithm and an overview is shown in Figure 4.4. idp Qref p i¯c i¯p ωm Ref. Gen. − id−ref p idc icd−ref PI − − PI ud,ref c + dq Cross-Coupling Compensator Ref. Gen. iq−ref p − q−ref PI + ic − iqp q,ref PI − uc iqc Figure 4.4 B-DFIG Control Scheme The controller for the DFIG is also based on the vector control algorithm, however, it is simpler and does not require cascaded current control loops. A number of studies have described this and it is therefore not detailed in this document. Similarly, the controller for the PMSM is based on vector control, but not detailed here. 4.2 Reference Signal Generation This section deals with the first step of controlling the generator for a wind turbine, the generation of a reference signal. It looks at obtaining this signal such that the generator operates at the optimal operating point. Section 4.2.1 looks at the requirement to extract maximum power from the wind while Section 4.2.2 looks at converting this reference signal into one that can be used to control the machine. 4.2.1 Modelling for Optimal Power Extraction The control of a wind turbine consists of two parts; the mechanical control of the pitch of the rotor blades and the electrical control of the generator. For this thesis only electrical control is considered. The aim of the control scheme is to maximise the power output of the wind turbine. A typical wind turbine characteristic, with the optimal power extraction-speed 34 CHAPTER 4. B-DFIG CONTROL curve and its intersection with the Cp,max for all wind speeds [23] is shown in Figure 4.5. As Popt is the curve with Cp,max it is evident that if the turbine is controlled and kept on this curve, the turbine will generate the maximum energy. This is followed for all speeds below rated. For speeds above rated, rated power Prated is maintained through pitch control. This is described in Equation 4.8. Maximum Power Curve (Popt) Generator Power Rated Power Generator Speed Figure 4.5 Control Strategy for Optimal Power Extraction. The plot shows the generator output power vs. speed curve for different wind speeds. The Popt curve connects all the points of maximum power forming the curve for optimal power extraction. Pref 1 ρAC 3 p,max v = 2 P rated if v < vrated (4.6) if v ≥ vrated This equation can be modified to represent a reference torque by using the expression ωm R v= . This is shown in Equation 4.7. λt 3 1 ρAR Cp,max ω 2 if ω < ω m rated m λ3t,max Tref = 2 (4.7) T if ωm ≥ ωrated rated or, Pref 3 1 ρAR Cp,max ω 3 m λ3t,max = 2 P rated if ωm < ωrated (4.8) if ωm ≥ ωrated where λt,max is the tip speed ratio for Cp,max . This equation is valid till the speed of the generator equals the rated speed ωrated . At this speed the generator is generating rated torque and rated power. Once this speed is crossed, the power output is held constant by varying the pitch angle of the rotor blades [21]. This method of generating the Tref is used in the control of the DFIG and the PMSM[23] [24] [25]. However, for the B-DFIG, control using torque is complex and hence the Power Winding active power is used. The rationale behind this choice is explained in the following sections. 35 CHAPTER 4. B-DFIG CONTROL 4.2.2 B-DFIG Reference Signal Section 4.2.1 discusses the generation of a reference signal for optimal power extraction from wind turbines. This signal is the net torque or power from the machine. Section 4.3.1 discusses the control of the machine, this control is based on the Active Power of the Power Winding alone. Therefore, it is required to generate the control signal (Ppref ) from the rotor speed (ωm ). The steady state characteristics, as defined in Chapter 2, are used to generate a function for the relation between ωm and Ppref . The characteristics depend on two variables, i.e. magnitude of the Control Winding voltage and the phase angle between Control Winding and Power Winding voltages. Therefore, given a value of ωm and P ref there are a number of operating points possible. To select an optimal operating point the efficiency of the machine is used as a selection criteria. The curve of the shaft power with rotor speed, as per Equation 4.8, is shown in Figure 4.6. Solving the system for maximum efficiency, the curve for the Power Winding Power corresponding to each point of the net power curve shown in Figure 4.6 is shown in Figure 4.7. These curves have been drawn for the B-DFIG 3.2MW Case Study Machine detailed in Appendix F. −0.5 Active Power (MW) −1 −1.5 −2 −2.5 −3 −3.5 24 26 28 30 32 34 36 38 Rotor Speed (rad/s) Figure 4.6 Power Curve for optimal power generation in the motor convention Curve fitting on the Power Winding Power curve gives the polynomial equation of the relation between Ppref and ωm . This is given in Equation 4.9. 3 2 Ppref = 1.4185 × ωm − 2071.7218 × ωm + 7406.5342 × ωm − 1.3713 × 105 36 (4.9) CHAPTER 4. B-DFIG CONTROL −0.5 Net Power Power Winding Power Active Power (MW) −1 −1.5 −2 −2.5 −3 −3.5 24 26 28 30 32 34 36 38 Rotor Speed (rad/s) Figure 4.7 4.3 Curve for net Shaft Power and Power Winding Active Power. Active and Reactive Power Control A number of control strategies for the B-DFIG have been proposed in literature. They can be classified into the following categories amongst others, • Scalar Voltage Control [26][27] • Vector Control [28][14][29] [30] • Direct Torque Control [31] [32][33]. The control of the B-DFIG in this thesis is based on vector control (also used for DFIG based systems[34]). This choice has been made because the speed and accuracy of the response of the system with a vector control strategy is adequate for the study taken up in this thesis. 4.3.1 Active Power Control The Power Winding power in the arbitrary reference frame ‘k’ is given by Equation 4.10. k,d k,q k,q Pp = uk,d p ip + up ip (4.10) Here, the voltage equations provided in Chapter 3 Equation 3.17 are reproduced below, uk,d p uk,q p dλk,d p = − + dt dλk,q p k,d = Rp ik,q + ω λ + k p p dt Rp ik,d p ωk λk,q p Using Equation 4.11 and Equation 4.12 and substituting in Equation 4.10 gives, 37 (4.11) (4.12) CHAPTER 4. B-DFIG CONTROL k,d Pp = Rp (ik,d2 + ik,q2 p p ) + ip k,q dλk,d p k,q k,q dλp k,d − ωk ik,d λ + i + ωk ik,q p p p p λp dt dt (4.13) Choosing a reference frame rotating with the Power Winding flux results in Equation 4.14 and Equation 4.15 for the d and q components of Power Winding flux. λPp W,d =|λp | λPp W,q (4.14) =0 (4.15) This reference frame is referred to as the PW reference frame in the rest of this document. The equation for Power Winding power in this reference frame is, Pp = Rp (iPp W,d iPp W,d + iPp W,q iPp W,q ) + iPp W,d d|λp | + ωk iPp W,q |λp | dt (4.16) Here, if the assumption is made that Up is constant and Rp is small enough to be neglected, the flux |λp | will be constant. This gives, Rp (iPp W,d iPp W,d + iPp W,q iPp W,q ) ≈ 0 d|λp | ≈0 dt (4.17) (4.18) Therefore, Pp simplifies to, Pp ≈ ωP W |λp |iPp W,q (4.19) This is the first step in the control of the machine, i.e. the generation of a reference iPp W,q value from the Ppref value. This can be visualised in the control scheme shown in Figure 4.8. Ppref ÷ |λp | × ωP W Figure 4.8 iPp W,q−ref W,q Reference iP Generation p For this machine, only the Control Winding circuit is controllable through the power electronic converter. Therefore, the next step would be to obtain a reference iPc W,q current. Consider the flux equations, PW PW PW λ¯p = Lp i¯p + Mpr i¯r λ¯c PW λ¯r PW = PW Lc i¯c = PW Lr i¯r − + (4.20) PW Mcr i¯r PW Mpr i¯p 38 (4.21) − PW Mcr i¯c (4.22) CHAPTER 4. B-DFIG CONTROL From these equations the relation between the Power Winding and Control Winding currents is given by, 1 P W,d λ − Lc c 1 = λPc W,q − Lc iPc W,d = iPc W,q Mcr Lp P W,d Mcr ip + |λp | Mpr Lc Mpr Lc Mcr Lp P W,q i Mpr Lc p (4.23) (4.24) From Equation 4.24 it is seen that iPc W,q depends on iPp W,q and λPc W,q . λPc W,q is weakly dependant on iPp W,d and iPc W,d through Equation 3.21 reproduced below in the PW reference frame. dλPc W,q = uPc W,q − Rc iPc W,q − (ωP W − (pp + pc )ωm )λPc W,d dt (4.25) This influence of d−axis terms on q−axis quantities and vice versa is termed ‘CrossCoupling’. For accurate control it is required that the d and q axis terms be completely de-coupled such that the control of both parameters is independent of the other. This is done through the addition of a compensation term, calculated using Equation 4.24, shown in Equation 4.26. iPc W,q = f (iPp W,q , |λp |) + 1 P W,q λ Lc c | {z } (4.26) Cross-Coupling Term It is also seen that iPc W,q varies with −iPp W,q . The control scheme for this step is shown in Figure 4.9. ipP W,q−ref− + PI + iqcomp iPp W,q Figure 4.9 iPc W,q−ref W,q Reference iP Generation c where, iqcomp = 1 P W,q λ Lc c (4.27) The power electronic converter can be controlled by the duty ratio for the switches which can be calculated from the reference Control Winding voltage and the DC bus voltage. For the simulations here, the reference voltage uc is used as input to the machine. The dependence of uqc on iqc can be calculated from the Control Winding voltage equation in Equation 4.28. uPc W,q = Rc iPc W,q + (ωP W − (pp + pc )ωm )λPc W,d + 39 dλPc W,q dt (4.28) CHAPTER 4. B-DFIG CONTROL A similar cross-coupling term, due to λPc W,d , as seen in Equation 4.26 is seen in the equation above. This can also be expressed as in Equation 4.29. Lp Mcr P W,d uPc W,q = f (iPc W,q , λPc W,q ) − (ωP W − (pp + pc )ωm )( i + Lc iPc W,d ) Mpr p | {z } (4.29) Cross-Coupling Term The control scheme for this is shown in Figure 4.10. iPc W,q−ref − uPc W,q−ref PI − uqcomp iPc W,q Figure 4.10 W,q Generation Reference uP c where, uqcomp = (ωP W − (pp + pc )ωm )( Lp Mcr P W,d i + Lc iPc W,d ) Mpr p (4.30) The complete control scheme for Active Power control of the B-DFIG is shown in Figure 4.4. The next section will look at the control of Reactive Power for the machine. 4.3.2 Reactive Power Control The Reactive Power of the Power Winding for the B-DFIG in the arbitrary reference frame ‘k’ is given by, k,d k,d k,q Qp = uk,q p ip − up ip (4.31) Substituting Equation 4.11 and Equation 4.12 in Equation 4.31 gives, Qp = ik,d p k,d dλk,q p k,d k,q dλp k,q + ωk ik,d λ − i + ωk ik,q p p p p λp dt dt (4.32) Again, choosing the PW reference frame results in Equation 4.33 and Equation 4.34 for the d and q components of Power Winding flux. λPp W,d =|λp | λPp W,q =0 (4.33) (4.34) Using the assumption that Up is constant and Rp is small enough to be neglected, the flux |λp | will be constant. This gives, d|λp | ≈0 dt (4.35) The expression for Qp can therefore be expressed as, Qp ≈ ωP W |λdp |iPp W,d 40 (4.36) CHAPTER 4. B-DFIG CONTROL Qref p |λp | ωP W Figure 4.11 iPp W,d−ref ÷ × W,d Reference iP Generation p This is the first step in the control of the reactive power of the machine, i.e. the generation of a reference iPp W,d value from the Qref value. This can be visualised in the control scheme p shown in Figure 4.11. From Equation 4.23 it is seen that iPc W,d depends on iPp W,d and λPc W,d . λPc W,d is weakly dependant on iPp W,q and iPc W,q through Equation 3.21 reproduced below in the PW reference frame. dλPc W,d = uPc W,d − Rc iPc W,d + (ωP W − (pp + pc )ωm )λPc W,q (4.37) dt Again there is a dq cross-coupling term which must be compensated for. This compensation term can be calculated using Equation 4.23, as seen in Equation 4.38. iPc W,d = f (iPp W,d , |λp |) − 1 P W,d λ Lc c | {z } (4.38) Cross-Coupling Term This part of the control scheme is shown in Figure 4.12. id,ref p − + iPc W,d−ref PI iPp W,d − idcomp Figure 4.12 W,d Reference iP Generation c where, idcomp = 1 P W,d λ Lc c (4.39) The dependence of uPc W,d on iPc W,d can be calculated from the Control Winding voltage equation. uPc W,d = Rc iPc W,d − (ωP W − (pp + pc )ωm )λPc W,q + dλPc W,d dt (4.40) Again, we see a dq cross-coupling term due to λPc W,q . This can be seen in Equation 4.41. Lp Mcr q uPc W,d = f (iPc W,d , λPc W,d ) − (ωP W − (pp + pc )ωm )( i + Lc iPc W,q ) Mpr P W,p | {z } Cross-Coupling Term 41 (4.41) CHAPTER 4. B-DFIG CONTROL The control scheme for this is shown in Figure 4.13. iPc W,d−ref − PI − udcomp iPc W,d Figure 4.13 uPc W,d−ref Reference udc Generation Here, it is important to discuss current limits. In the control scheme described both P W,ref P W,ref ¯ ip and i¯c must be maintained within the operating limits of the machine for safe operation. This is described by the equations, q (iPp W,d−ref )2 + (iPp W,q−ref )2 ≤ Ip,limit (4.42) q (iPc W,d−ref )2 + (iPc W,q−ref )2 ≤ Ic,limit (4.43) In the event that the reference d − q currents are larger than that allowed by the current limiters. The current d component is given preference over the q component. This is because the d current component is responsible for the creation of the stator flux |λp |. For operation it is important to maintain the flux of the machine and therefore the d component is important to maintain. The complete control scheme is shown in Figure 4.14. 42 abc PW i¯c abc PW λ¯c uc ic abc up |λp | ωp PW Estimator u¯p measurement B-DFIG PW abc ip i¯p ωm PW λ¯p PW × P.E. Controller iPp W,d Qref p 43 ÷ − iPp W,d−ref iPc W,d iPc W,d−ref PI − − PI idcomp iqcomp Ppref |λp | ωp ÷ iPp W,q−ref − PI − udcomp PW i¯c PW dq Cross-Coupling Compensator i¯p ωm iPp W,q iPc W,q × Figure 4.14 uPc W,q uqcomp P W,q−ref + ic − B-DFIG Controller measurement uPc W,d PI − CHAPTER 4. B-DFIG CONTROL u¯c CHAPTER 4. B-DFIG CONTROL 4.4 PI Tuning The PI controller used in this thesis work is described by, K(1 + 1 ) τs (4.44) The controller is designed using the internal mode control method [35] where the pole of the open-loop system is compensated with the zero of the PI controller. Inner Current Loop The open loop transfer function for the inner current control loop, taking cross-coupling compensation into account is given by, ic 1 = uc Rc + sLc G1 = (4.45) The PI parameters are given by [35], K =α1 Lc Lc τ= Rc (4.46) (4.47) where, α1 is the required closed loop bandwidth. The value of α is limited by the equations [35], ωs ≥ 10α ωsw ≥ 5α (4.48) (4.49) where, ωs is the angular sampling frequency of the system and ωsw is the angular switching frequency. α is also related to the rise-time tr as, α= ln9 tr (4.50) Selecting the rise time for the inner loop as 1ms we have, α1 = ln9 = 2197.224 rad/s 0.001 (4.51) (4.52) Outer Current Loop A simplified model for the plant of the outer current control loop is shown in Figure 4.15. This transfer function takes cross-coupling compensation and the inner current control loop into account. The open loop transfer function is, G2 = − Lc Mpr s Mcr Rp + sLp 44 (4.53) CHAPTER 4. B-DFIG CONTROL iref p iref c PI − −Lc Mpr s Mcr Rp + sLp ic Control ip Reference idc Generation Figure 4.15 The PI parameters are given by, K =α2 Lp Lp τ= Rp (4.54) (4.55) where, α2 is the closed loop bandwidth. Here, we choose a rise time tr of 2.5ms and can calculate α2 as, α2 = 4.5 ln9 = 878.89 rad/s 0.0025 (4.56) Control Behaviour This section describes the behaviour of the B-DFIG with the control scheme detailed in the previous sections under the condition of a step change applied to the load torque. A step increase of 10% in load torque is simulated to observe the response of the system. The machine used in the simulations is detailed in Appendix C. The simulated torque response is shown in Figure 4.16a. This figure shows both the Load Torque generated by the wind and the Electrical Torque produced by the B-DFIG. The rotor angular speed under this condition is shown in Figure 4.16b. The Power Winding and Control Winding currents in the PW reference frame are shown in Figure 4.17a and Figure 4.17b respectively. In these simulations Qref has been maintained at a constant p value. −520 26 Load Torque B−DFIG Torque 25.8 −530 Rotational Speed (rad/s) 25.6 Torque (kNm) −540 −550 −560 −570 25.4 25.2 25 24.8 24.6 24.4 −580 24.2 −590 800 900 1000 1100 1200 1300 1400 1500 1600 1700 24 800 1800 Time (s) 900 1000 1100 1200 1300 1400 1500 1600 1700 1800 Time (s) (a) (b) Figure 4.16 Response of the B-DFIG Control Scheme with a 10% Load Torque Step at t=1000s (a) B-DFIG and Load Torque Response (b) Rotational Speed of the B-DFIG 45 CHAPTER 4. B-DFIG CONTROL 1900 −2000 d−axis Current q−axis Current 1700 1600 1500 1400 1300 1200 1100 d−axis Current q−axis Current −3000 Control Winding d−q Current (A) Power Winding d−q Current (A) 1800 −4000 −5000 −6000 −7000 −8000 −9000 −10000 1000 800 900 1000 1100 1200 1300 1400 1500 1600 1700 1800 −11000 800 Time (s) 900 1000 1100 1200 1300 1400 1500 1600 1700 1800 Time (s) (a) (b) Figure 4.17 Response of the B-DFIG Control Scheme with a 10% Load Torque Step at t=1000s (a) Power Winding Currents in the PW Reference Frame (b) Control Winding Currents in the PW Reference Frame It can be seen that the response of the control scheme is acceptable, however, the speed of response is limited by the inertia of the turbine. 4.6 Discussion This chapter has focussed on the development of a control method for the B-DFIG in a wind turbine. The control has been based on the vector control method and is implemented in the Power Winding flux reference frame. Section 4.2 describes the generation of the reference signal to control the machine such that it operates at an optimal operating point. This step is a challenge for a B-DFIG as the control is based on the Power Winding Active Power. Section 4.3 discussed the control methodology for the machine. This includes the concept of ‘Cross-Coupling Compensation’ to decouple the d and q axis control. The d axis is used to control the reactive power supplied to the system while the q axis component controls the active power. The behaviour of the control has been shown in Section 4.5. The response shown is for a step change in wind speed. The response of the B-DFIG in this case is found to be limited by the inertia of the turbine. 46 Chapter 5 Performance Under Grid Events With increased wind energy penetration, wind turbine generators are required to have Fault Ride Through (FRT) or Low Voltage Ride Through (LVRT) capabilities. This chapter looks at this capability of the B-DFIG and compares this with those of other wind turbine generating technologies such as permanent magnet generators and doubly fed induction generators. This comparison is made for case study machines developed for a 3.2MW wind turbine which gives a good basis on which a comparison can be made. Section 5.1 looks at the grid code requirements for LVRT capabilities. It defines the test cases under which these capabilities will be tested. Section 5.2 discusses the LVRT response of the Permanent Magnet Synchronous Machine while Section 5.3 looks at the LVRT response of the Doubly Fed Induction Generator. Section 5.4 describes the performance of the B-DFIG and Section 5.5 compares the response of all three generators. 5.1 Grid Code Requirements The European Network of Transmission System Operators for Electricity (ENTSO-E) represents the electric Transmission System Operators (TSO) in the European Union. The ENTSO-E released its Network Code on Requirement of Generators (NC RfG) [36] [37] in March 2013. The purpose of the NC RfG is to develop a set of coherent requirements to create harmonised solutions and products for the pan-European market. The NC RfG gives the requirements for the Fault Ride Through (FRT) or Low Voltage Ride Through (LVRT) capabilities for generators connected to the grid. These are divided into conditions for connections below 110kV and above 110kV. The objective is to limit the potential loss of generation after a fault on the distribution or transmission system in order to avoid more severe disturbances, i.e. frequency collapse in a synchronous area causing demand tripping and unexpected power flows resulting in overloads both on internal transmission lines and tie lines with neighbouring systems possibly leading to cascading tripping, system splitting, load shedding, major faults, brown outs and even black outs. In the case of a fault on the transmission system level a voltage drop will propagate across large geographical areas around the point of the fault during the period of the fault. The increased levels of distributed generation will need to be tolerant to such faults, especially where the total installed volume of embedded generation possibly affected by a transmission system fault exceeds the maximum designed generation loss. It is also possible that a large generator may have been tripped depending upon the exact fault location. Unless 47 CHAPTER 5. PERFORMANCE UNDER GRID EVENTS this capability is established, the total loss would then be the sum of this large generator plus any lower level distributed generation tripping.[36] 1.0 Urec2 Urec1 Uclear Uret tclear Figure 5.1 trec1 trec2 trec3 Voltage Profile for LVRT capability of generators connected to the grid. The NC RfG specifies a profile that represents the worst voltage variation during a fault and after its clearance. Power Generating Modules are required to stay connected to the grid and continue stable operation for voltages above the worst case conditions. The specification of the profile comprises of a set of parameters for times and voltages as shown in Figure 5.1. The parameters are described in Table 5.1. TSOs specify a voltageVoltage Parameters (pu) Uret 0.05-0.15 Uclear Uret -0.15 Urec1 Uclear Urec2 0.85 Table 5.1 Time Parameters (s) tclear 0.14-0.25 trec1 tclear trec2 trec1 trec3 1.5-3.0 Parameters for generators connected below 110kV as per NC RfG against-time profile for LVRT capabilities based on the parametrised curve in Figure 5.1. Therefore, for the purpose of this study, two voltage profiles cases which are the worst case scenarios within the constraints defined in the NC RfG will be considered. These are shown in Figure 5.2 and Figure 5.3. Case A has been selected as the steep drop and rise of voltage, at t = 0 s and t = 0.25 s respectively, are expected to cause the highest transients current magnitudes in the case of the DFIG and B-DFIG. Here, a 95% symmetric voltage dip is considered. Case B has been selected as can be expected to cause transient currents 48 CHAPTER 5. PERFORMANCE UNDER GRID EVENTS for longer periods of time. It can also be expected to cause larger DC-link Voltage rise for PMSM machines as it involves power mismatch for longer periods. V oltage (pu) 1.0 0.25 Figure 5.2 T ime (s) Voltage profile for Case A of the LVRT response study V oltage (pu) 1.0 0.25 Figure 5.3 T ime (s) 3.0 Voltage profile for Case B of the LVRT response study In the following sections, the LVRT response of the B-DFIG and the two most prevalent generators used in wind turbines, the Permanent Magnet Synchronous Machine (PMSM) and the Doubly Fed Induction Generator (DFIG), will be investigated. In this chapter the response of these generators for the ‘Case A’ voltage profile described in Figure 5.2 is discussed in detail. The response for the ‘Case B’ voltage profile is discussed in Appendix A. 49 CHAPTER 5. PERFORMANCE UNDER GRID EVENTS 5.2 Simulation of the LVRT Performance for the PMSM The schematic layout of the PMSM based wind turbine system is shown in Figure 5.4. Figure 5.4 Schematic of the Permanent Magnet Synchronous Machine (PMSM) as a Wind Turbine The PMSM is completely isolated from the grid through an AC-DC-AC converter. Therefore, disturbances on the grid do not directly affect the machine. However, in the occurance of an LVRT event the ability of the grid side inverter to transfer power to the grid is greatly reduced. This results in the rise of the DC link voltage which is a cause for concern to the DC link capacitors. Section 5.2.1 looks at the performance of the PMSM under an LVRT event. Section 5.2.2 discusses methods for protecting the DC link during such events and shows the response of the system under LVRT conditions. The machine used in these simulation is the PMSM Case Study Machine detailed in Appendix D. The operating point of the generator at the instant of the event is the limit of maximum output i.e. Pout = 3.2MW. As the PMSM is completely isolated from the grid the Reactive Power transferred to the grid is generated at the grid side converter. Therefore, Qout of the generator is taken to be zero. For the power electronic converter, the shape of the DC link voltage depends on the value of Capacitance used. Here, an arbitrary value of 1F has been chosen. 50 CHAPTER 5. PERFORMANCE UNDER GRID EVENTS 5.2.1 LVRT Performance without Protection The response of the PMSM (without any protection circuit or algorithm) to a Low Voltage event is shown in Figure 5.5. 0 32 −50 31 −100 30 −150 29 0.8 0.6 0.4 0.2 0 999 999.2 999.4 999.6 999.8 1000 1000.2 1000.4 1000.6 1000.8 −200 999 1001 999.2 999.4 999.6 999.8 Time (s) 1000.2 1000.4 1000.6 1000.8 28 1001 (b) 50 0.2 d−axis Current q−axis Current 0 d−axis Current q−axis Current 40 30 Grid d−q Currents (kA) −0.2 −0.4 −0.6 −0.8 −1 −1.2 20 10 0 −10 −20 −30 −1.4 −40 −1.6 999 1000 Time (s) (a) Generator d−q Currents (kA) Generator Speed (rad/s) Generator Torque (kNm) Grid Voltage in Grid Reference Frame (pu) 1 999.2 999.4 999.6 999.8 1000 1000.2 1000.4 1000.6 1000.8 −50 999 1001 999.2 999.4 999.6 999.8 Time (s) (c) 1000 Time (s) 1000.2 1000.4 1000.6 1000.8 1001 (d) 1.9 1.8 9 9 7 7 5 5 3 3 1 1 1.6 1.5 1.4 1.3 1.2 1.1 Reactive Power (MVAr) Active Power (MW) DC−link Voltage (pu) 1.7 1 0.9 999 999.2 999.4 999.6 999.8 1000 1000.2 1000.4 1000.6 1000.8 −1 999 1001 999.2 999.4 Time (s) 999.6 999.8 1000 1000.2 1000.4 1000.6 1000.8 −1 1001 Time (s) (e) (f ) Figure 5.5 LVRT Performance of PMSM Without Protection for a 95% Symmetric Voltage Dip at t=1000s (a) Grid Voltage magnitude (b) Torque and Speed (c) Generator Currents in the PW reference frame (d) Grid Currents in the grid reference frame (e) DC link voltage (f ) Active and Reactive Power to the grid The flow of energy through the Power Electronic Converter is described in Figure 5.6. The difference between the input energy and the output energy is stored in the capacitor (causing the voltage rise). This can be described using Equation 5.1. Pin − Pout = udc C dudc dt (5.1) During a Low Voltage event, the grid voltage reduces and if the current output of the grid side converter is kept within the current limits specified, the power delivered to the grid is substantially reduced. This results in a rise in the DC link voltage seen in Figure 5.5e. As 51 CHAPTER 5. PERFORMANCE UNDER GRID EVENTS Pin Pout C Generator-Side Converter Figure 5.6 Grid-Side Converter Power Flow in the Converter for a PMSM the generator is completely isolated from the grid, there is no effect of the Low Voltage event on the generator currents and torque. Therefore, the issue with the LVRT performance of a PMSM does not arise in the machine but the DC link due to a mismatch in power flow capabilities. 5.2.2 LVRT Performance with Protection The previous section highlighted the issue of DC link voltage rise during a low voltage event. A number of methods have been devised to manage the mismatch in power flow which causes this problem. Two such methods, Energy Discharge Circuits [38] and Power Balancing [39] have been simulated and discussed, while others have been described in brief. Energy Discharge Circuit This method prevents the rise of the DC link voltage by using resistive elements to dissipate a part of the power fed to the DC circuit through the generator side converter. A schematic of this is shown in Figure 5.7. This minimises the difference between the power fed into the DC circuit and the power taken out of the DC circuit, thus limiting the rise in DC link voltage. Figure 5.8 shows the performance of the PMSM equipped with a Energy Discharge Circuit in the DC link. Pin Pout Energy Discharge Circuit C R Generator-Side Converter Figure 5.7 Grid-Side Converter Schematic of the Energy Discharge Circuit The results in Figure 5.8 show that with the Energy Discharge Circuit implemented it is possible to control the rise of the DC link voltage. This method however has a number of drawbacks, • It requires additional power electronic switches and large resistor banks capable of carrying large currents. • The excess energy, however small, is dissipated and lost. 52 CHAPTER 5. PERFORMANCE UNDER GRID EVENTS 0 32 −50 31 −100 30 −150 29 0.8 0.6 0.4 0.2 0 999 999.2 999.4 999.6 999.8 1000 1000.2 1000.4 1000.6 1000.8 −200 999 1001 999.2 999.4 999.6 999.8 1000 Time (s) 1000.2 1000.4 1000.6 1000.8 28 1001 Time (s) (a) (b) 20 0.2 d−axis Current q−axis Current 0 d−axis Current q−axis Current 15 −0.2 Grid d−q Currents (kA) Generator d−q Currents (kA) Generator Speed (rad/s) Generator Torque (kNm) Grid Voltage in Grid Reference Frame (pu) 1 −0.4 −0.6 −0.8 −1 −1.2 10 5 0 −5 −10 −1.4 −15 −1.6 999 999.2 999.4 999.6 999.8 1000 1000.2 1000.4 1000.6 1000.8 −20 999 1001 999.2 999.4 999.6 999.8 1000 Time (s) Time (s) (c) 1000.2 1000.4 1000.6 1000.8 1001 (d) 1.02 9 9 7 7 5 5 3 3 1 1 0.99 0.98 0.97 0.96 0.95 999 999.2 999.4 999.6 999.8 1000 1000.2 1000.4 1000.6 1000.8 −1 999 1001 Time (s) 999.2 999.4 999.6 999.8 1000 1000.2 1000.4 1000.6 1000.8 Reactive Power (MVAr) 1 Active Power (MW) DC−link Voltage (pu) 1.01 −1 1001 Time (s) (e) (f ) Braking Resistor Current (A) 2500 2000 1500 1000 500 0 999 999.2 999.4 999.6 999.8 1000 1000.2 1000.4 1000.6 1000.8 1001 Time (s) (g) Figure 5.8 LVRT performance of PMSM with Energy Discharge Circuit for a 95% Symmetric Voltage Dip at t=1000s (a) Grid Voltage magnitude (b) Torque and Speed (c) Generator Currents in the PW reference frame (d) Grid Currents in the grid reference frame (e) DC link voltage (f ) Active and Reactive Power to the grid (g) Energy Discharge Circuit - Resistor Current Power Balancing This method controls the rise of the DC link voltage by minimising the difference between the power transferred to the grid and the power generated by the PMSM. This is done 53 CHAPTER 5. PERFORMANCE UNDER GRID EVENTS by forcing the generator side converter to follow the grid side converter during Low Voltage events. Figure 5.9 shows the performance of the PMSM when the Power Balancing Algorithm is implemented. 0 32 −50 31 −100 30 −150 29 0.8 0.6 0.4 0.2 0 999 999.2 999.4 999.6 999.8 1000 1000.2 1000.4 1000.6 1000.8 −200 999 1001 999.2 999.4 999.6 999.8 Time (s) 1000 1000.2 1000.4 1000.6 1000.8 28 1001 Time (s) (a) (b) 10 0.2 d−axis Current q−axis Current 0 d−axis Current q−axis Current 5 −0.2 Grid d−q Currents (kA) Generator d−q Currents (kA) Generator Speed (rad/s) Generator Torque (kNm) Grid Voltage in Grid Reference Frame (pu) 1 −0.4 −0.6 −0.8 −1 −1.2 0 −5 −10 −1.4 −1.6 999 999.2 999.4 999.6 999.8 1000 1000.2 1000.4 1000.6 1000.8 −15 999 1001 999.2 999.4 999.6 999.8 Time (s) (c) 1000 Time (s) 1000.2 1000.4 1000.6 1000.8 1001 (d) 1.008 1.006 9 9 7 7 5 5 3 3 1 1 1 0.998 0.996 0.994 0.992 Reactive Power (MVAr) 1.002 Active Power (MW) DC−link Voltage (pu) 1.004 0.99 0.988 999 999.2 999.4 999.6 999.8 1000 1000.2 1000.4 1000.6 1000.8 −1 999 1001 Time (s) 999.2 999.4 999.6 999.8 1000 1000.2 1000.4 1000.6 1000.8 −1 1001 Time (s) (e) (f ) Figure 5.9 LVRT performance of PMSM with Power Balancing for a 95% Symmetric Voltage Dip at t=1000s (a) Grid Voltage magnitude (b) Torque and Speed (c) Generator Currents in the PW reference frame (d) Grid Currents in the grid reference frame (e) DC link voltage (f ) Active and Reactive Power to the grid The results in Figure 5.9 show that with the Power Balancing Algorithm implemented it is possible to control the rise of the DC link voltage. This method does not require any additional components and does not dissipate the excess energy, instead it saves this excess in the rotor in the form of kinetic energy. However, it has a number of drawbacks, • It causes sharp torque ripples as can be seen in Figure 5.9b. This may be addressed with a better choice of reference torque (for example, a ramped change in reference in place of a step change) during the Low Voltage event. • As the generated power, and hence the generated torque, reduces during the event it may cause the rotor speed to increase beyond the limits of operation. This may not 54 CHAPTER 5. PERFORMANCE UNDER GRID EVENTS be a major issue when the rotor has a large inertia and the low voltage event occurs for a short period of time. This could also be limited by pitch control. Other Methods There are a number of other methods that have been proposed and used to address the issues arising due to Low Voltage events. Pitching Control seems to be an obvious solution. When a disturbance in the form of a Low Voltage event is sensed on the grid, the pitch of the rotor blades is increased to reduce the torque on the generator. This will reduce the imbalance of power in the DC circuit. However, the speed at which the blades can be pitched is very important to determine the success of this method. Conroy et al. demonstrated that even with a maximum pitching rate of 20◦ per second the DC link voltage rise is not significantly mitigated [40]. Another method is to use Energy Storage Systems to manage and store the energy during Low Voltage events [38]. In this case the excess energy is stored during the voltage event and transferred to the grid after the voltage is restored. Wang et al. simulated the use of Vanadium Redox Flow Battery (VRB) based Energy Storage System for the PMSM [41]. The system could also be used to smoothen the power transferred to the grid apart from improving LVRT response. The drawbacks of this system are its size and cost. 55 CHAPTER 5. PERFORMANCE UNDER GRID EVENTS 5.3 Simulation of the LVRT Performance of the DFIG The schematic layout of the DFIG based wind turbine system is shown in Figure 5.10. Figure 5.10 Schematic of the Doubly Fed Induction Generator (DFIG) as a Wind Turbine Unlike the PMSM, the DFIG is not isolated from the grid. The stator is directly connected to the grid and any disturbance in the form of a Low Voltage event can be expected to have an effect on the stator and rotor currents. Under normal operating conditions the flux space vectors of the rotor and stator rotate with synchronous speed. When the grid voltage drops, the magnitude of the stator flux vector also reduces. The rotor flux vector however retains its magnitude and speed, causing oscillatory stator currents. The voltage dip also induces large oscillating currents in the rotor which could harm the power electronics connected in the circuit. Section 5.3.1 looks at the performance of the DFIG under LVRT without protection while Section 5.3.2 looks at some methods for improving LVRT performance. The machine used in these simulations is the DFIG Case Study Machine detailed in Appendix E. As with the PMSM, the operating point of the DFIG used for the simulations is Pout = 3.2MW. For the reactive power generation, it has been assumed that the complete reactive power transferred to the grid by the machine is through the stator winding. This means that it has been assumed that the power electronic converter does not have any reactive power interaction with the grid. As per the NC RfG discussed in Section 5.1 the outer limits for the reactive power capabilities of the generator are −0.5Pmax and 0.65Pmax . For this study, the condition Qout = −0.5Pmax is used. Considering that the power electronic converter for a DFIG is partially rated (say, 25% of rated power) the capacitance value has been chosen such that the energy stored in it 1 ( CV 2 ) is a quarter of the energy stored in the PMSM capacitor under standard operating 2 conditions. 56 CHAPTER 5. PERFORMANCE UNDER GRID EVENTS 5.3.1 Performance without Protection The response of the DFIG without any means of protection angainst LVRT is shown in Figure 5.11. 1000 0.8 0.6 0.4 500 30 0 0.2 0 999 999.5 1000 1000.5 1001 1001.5 1002 1002.5 −500 999 1003 1000 1001 Time (s) 1003 1004 28 1005 (b) 20 25 d−axis Current q−axis Current 15 d−axis Current q−axis Current 20 Rotor d−q Currents (kA) 10 5 0 −5 −10 −15 15 10 5 0 −5 −10 −20 −15 −25 −30 999 1002 Time (s) (a) Stator d−q Currents (kA) Generator Speed (rad/s) 32 Generator Torque (kNm) Grid Voltage in Grid Reference Frame (pu) 1 1000 1001 1002 1003 1004 −20 999 1005 1000 1001 Time (s) 1002 1003 1004 1005 Time (s) (c) (d) 1.8 15 15 10 10 5 5 0 0 −5 −5 −10 −10 1.7 1.5 1.4 1.3 1.2 Reactive Power (MVAr) Active Power (MW) DC−link Voltage (pu) 1.6 1.1 1 0.9 999 999.5 1000 1000.5 1001 1001.5 1002 1002.5 −15 999 1003 Time (s) 1000 1001 1002 1003 1004 −15 1005 Time (s) (e) (f ) Figure 5.11 LVRT performance of DFIG without protection for a 95% Symmetric Voltage Dip at t=1000s (a) Grid Voltage magnitude (b) Torque and Speed (c) Stator Currents in the Stator Flux reference frame (d) Rotor Currents in the Stator Flux reference frame (e) DC link voltage (f ) Active and Reactive Power to the grid A number of issues with the performance of the machine during a Low Voltage event are seen. First, as with the case of the PMSM, there is a substantial rise in the DC link voltage. This however, may be easily controlled using methods discussed in the Section 5.2.2. Also, the voltage disturbance causes large oscillatory currents in the stator as seen in Figure 5.11c. Such currents, due to the magnetic coupling between the stator and the rotor, also flow in the rotor circuit as shown in Figure 5.11d. This is further highlighted in the plots of stator and rotor phase currents shown in Figure 5.12. The transients occur at both instances of voltage change (i.e. voltage drop when fault in the system occurs and the subsequent rise in voltage when the fault is cleared). These transient currents in the rotor circuit are 57 20 20 15 15 Rotor Phase Currents (kA) Stator Phase Currents (kA) CHAPTER 5. PERFORMANCE UNDER GRID EVENTS 10 5 0 −5 −10 −15 10 5 0 −5 −10 −15 −20 −25 999.5 1000 1000.5 1001 −20 999.5 1001.5 1000 1000.5 Time (s) (a) Figure 5.12 1001 1001.5 Time (s) (b) LVRT performance of DFIG without protection for a 95% Symmetric Voltage Dip at t=1000s (a) Stator Phase Currents (b) Rotor Phase Currents especially dangerous to the power electronics and hence must be contained. It is seen that the maximum current magnitude in the rotor circuit is approximately 2.5 times the current at rated operation. This is when the voltage limits on the power electronic converter is 1.25 times that required for rated operation. One way to control the rotor currents would be by applying a sufficiently large rotor voltage to control them. Figure 5.13 shows the response of the DFIG under the assumption that the voltage rating of the power electronic converter is no longer a constraint. Such a study may be used as a tool to compare the LVRT response of different machines. It can 0 1 0.8 0.6 0.4 −100 −150 −200 30 −250 Generator Speed (rad/s) Generator Torque (kNm) Grid Voltage in Grid Reference Frame (pu) −50 0.2 −300 0 999 999.5 1000 1000.5 1001 1001.5 1002 1002.5 −350 999 1003 999.5 1000 1000.5 Time (s) 1001 1001.5 1002 1002.5 1003 Time (s) (a) (b) 6 −4.86 d−axis Current q−axis Current d−axis Current q−axis Current −4.88 Rotor d−q Currents (kA) Stator d−q Currents (kA) 4 2 0 −2 −4.9 −4.92 −4.94 −4.96 −4.98 −5 −4 −5.02 −6 999 999.5 1000 1000.5 1001 1001.5 1002 1002.5 −5.04 999 1003 Time (s) 999.5 1000 1000.5 1001 1001.5 1002 1002.5 1003 Time (s) (c) (d) Figure 5.13 LVRT performance of DFIG without constraints on Voltage of Converter for a 95% Symmetric Voltage Dip at t=1000s (a) Grid Voltage magnitude (b) Torque and Speed (c) Stator Currents in the Stator Flux reference frame (d) Rotor Currents in the Stator Flux reference frame be seen that the rotor currents are indeed controlled. This is further highlighted in the phase currents shown in Figure 5.14b. The magnitude of the excess rotor voltage required 58 6 6 4 4 Rotor Phase Currents (kA) Stator Phase Currents (kA) CHAPTER 5. PERFORMANCE UNDER GRID EVENTS 2 0 −2 −4 −6 999.5 2 0 −2 −4 1000 1000.5 1001 −6 999.5 1001.5 1000 1000.5 Time (s) 1001 1001.5 Time (s) (a) (b) 2000 Rotor Phase Voltages (V) 1500 1000 500 0 −500 −1000 −1500 −2000 999.5 1000 1000.5 1001 Time (s) (c) Figure 5.14 LVRT performance of DFIG without constraints on Voltage of Converter for a 95% Symmetric Voltage Dip at t=1000s (a) Stator Phase Currents (b) Rotor Phase Currents (c) Rotor Phase Voltages to control the rotor currents during LVRT can be seen in Figure 5.14c. It can be seen that the Volt-Ampere (VA) rating required of the power electronic converter is approximately 9.3 times that required for rated operation. The next section discusses methods to control the issues of rotor transient currents. 59 CHAPTER 5. PERFORMANCE UNDER GRID EVENTS 5.3.2 Performance with Protection A common method that is used to improve the LVRT performance of DFIG based wind turbines is the use of a Crowbar [38]. The performance of a DFIG with crowbar protection has been simulated while other methods have been briefly discussed in the following sections. Crowbar In the event of large rotor currents being generated during a Low Voltage event, it may be necessary to by-pass the power electronic converter for its protection. The crowbar circuit is a set of switches and resistors that short circuit the rotor terminals through the resistors in the case of the Low Voltage event and disconnect the generator side converter. Figure 5.15 and Figure 5.16 show the LVRT response of the DFIG with a crowbar circuit implemented such that the crowbar is triggered in the event that the rotor current exceeds the rated current. The connection of the crowbar circuit serves a number of purposes. First, it bypasses the power electronic converter when large transient rotor currents are present. This protects the converter in the event of a Low Voltage event. Second, the added resistance in the rotor circuit lowers the magnitude of the transient rotor currents. Third, the added resistance Lr in the crowbar circuit reduces the time constant of the rotor circuit (τr = ), Rr + Rcrowbar this means that the currents during the fault will decay faster. There are however a number of issues with the use of the crowbar circuit as well. First, when the crowbar circuit is activated, the DFIG resembles a induction motor with an external rotor resistance. This would mean that the machine would absorb reactive power from the grid which may further exasperate the condition of the grid. Second, the vector control is lost during the action of the crowbar circuit and re-establishing control after the crowbar is released is a challenge. 60 CHAPTER 5. PERFORMANCE UNDER GRID EVENTS 1000 0.8 0.6 0.4 500 30 0 0.2 999.5 1000 1000.5 1001 1001.5 1002 1002.5 −500 999 1003 1000 1001 Time (s) (a) 1004 1005 20 d−axis Current q−axis Current d−axis Current q−axis Current 15 Rotor d−q Currents (kA) 10 Stator d−q Currents (kA) 1003 (b) 15 5 0 −5 −10 −15 −20 −25 999 1002 Time (s) 10 5 0 −5 −10 −15 1000 1001 1002 1003 1004 −20 999 1005 1000 1001 Time (s) 1002 1003 1004 1005 Time (s) (c) (d) 20 20 1.4 15 15 10 10 5 5 0 0 −5 −5 −10 −10 Active Power (MW) 1.5 1.3 1.2 1.1 1 0.9 999 999.5 1000 1000.5 1001 1001.5 1002 1002.5 −15 999 1003 Time (s) 1000 1001 1002 1003 1004 Reactive Power (MVAr) 0 999 DC−link Voltage (pu) Generator Speed (rad/s) Generator Torque (kNm) Grid Voltage in Grid Reference Frame (pu) 1 −15 1005 Time (s) (e) (f ) Figure 5.15 LVRT performance of DFIG with Crowbar protection for a 95% Symmetric Voltage Dip at t=1000s (a) Grid Voltage magnitude (b) Torque and Speed (c) Stator Currents in the Stator Flux reference frame (d) Rotor Currents in the Stator Flux reference frame (e) DC link voltage (f ) Active and Reactive Power to the grid Other Methods A number of methods have been proposed to protect the DFIG during low voltage events. Liang et al. proposed an additional control [43], i.e. injection of additional feed-forward transient compensation terms, for the DFIG with crowbar. This controll scheme results in minimum transient rotor currents and minimum crowbar usage. However, apart from this still requiring the crowbar circuit, it requires additional computation effort [42]. Another solution employs a parallel grid side converter with a series grid side converter to provide robust voltage disturbance ride through [42]. However, this method also requires additional devices. Most proposed methods either require the crowbar circuit or other additional circuits (like the parallel grid side converter). Therefore, an additional circuit is required for the protection of the DFIG. 61 20 20 15 15 Rotor Phase Currents (kA) Stator Phase Currents (kA) CHAPTER 5. PERFORMANCE UNDER GRID EVENTS 10 5 0 −5 −10 −15 −20 999.5 10 5 0 −5 −10 −15 1000 1000.5 1001 −20 999.5 1001.5 1000 1000.5 Time (s) 1001 1001.5 Time (s) (a) (b) 20 Rotor Phase Currents (kA) 15 10 5 0 −5 −10 −15 −20 999.5 1000 1000.5 1001 1001.5 Time (s) (c) Figure 5.16 LVRT performance of DFIG with Crowbar protection for a 95% Symmetric Voltage Dip at t=1000s (a) Stator Phase Currents in the Stator Reference Frame (b) Rotor Currents in the Stator Reference Frame (c) Crowbar Resistance Phase Currents 62 CHAPTER 5. PERFORMANCE UNDER GRID EVENTS 5.4 Simulation of the LVRT Performance for the B-DFIG The schematic layout of a B-DFIG based wind turbine system is shown in Figure 5.17. Figure 5.17 System Level B-DFIG Schematic The B-DFIG suffers from the same issues faced by the DFIG during Low Voltage events. When a low voltage occurs the magnitude of the Power Winding flux reduces, in this event the rotor flux induces transient currents in the Power Winding circuit. This sets up transient currents in the Control Winding circuit through the rotor circuit. Control Winding transient currents occur when the controller is unable to match the induced voltages in this winding caused by the rotor currents. Section 5.4.1 describes the LVRT performance of the B-DFIG without protection while Section 5.4.2 looks at methods to improve this performance. The machine used in these simulations is the B-DFIG 3.2MW Case Study Machine detailed in Appendix F. The operating conditions of the B-DFIG used for the simulations here are identical to that of the DFIG. Therefore, Pout = 3.2MW and Qout = −0.5Pmax . As with the DFIG, this operating point has been chosen as it defines the boundary of operation as defined in the NC RfG. The capacitance value has been selected using the method described for the DFIG. 63 CHAPTER 5. PERFORMANCE UNDER GRID EVENTS 5.4.1 Performance without Protection The response of the B-DFIG without any protection against an Low Voltage event is shown in Figure 5.18. 1000 0.8 0.6 0.4 500 39 0 38 0.2 0 999 999.5 1000 1000.5 1001 1001.5 1002 1002.5 −500 999 1003 999.5 1000 1000.5 Time (s) 1001 1001.5 1002 37 1003 (b) 4 15 d−axis Current q−axis Current Control Winding d−q Currents (kA) d−axis Current q−axis Current 2 0 −2 −4 −6 −8 999 1002.5 Time (s) (a) Power Winding d−q Currents (kA) Generator Speed (rad/s) Generator Torque (kNm) Grid Voltage in Grid Reference Frame (pu) 1 999.5 1000 1000.5 1001 1001.5 1002 1002.5 10 5 0 −5 −10 −15 −20 999 1003 999.5 1000 1000.5 Time (s) 1001 1001.5 1002 1002.5 1003 Time (s) (c) (d) 1.1 1.08 20 20 10 10 0 0 1.04 1.02 1 0.98 −10 −10 Reactive Power (MVAr) Active Power (MW) DC−link Voltage (pu) 1.06 0.96 0.94 0.92 999 −20 999.5 1000 1000.5 1001 1001.5 1002 1002.5 1003 999 Time (s) −20 999.5 1000 1000.5 1001 1001.5 1002 1002.5 1003 Time (s) (e) (f ) Figure 5.18 LVRT performance of B-DFIG without protection for a 95% Symmetric Voltage Dip at t=1000s (a) Grid Voltage magnitude (b) Torque and Speed (c) Power Winding Currents in the PW reference frame (d) Control Winding Currents in the PW reference frame (e) DC link voltage (f ) Active and Reactive Power to the grid Large transient currents are seen in the Power Winding and Control Winding. These are further highlighted in Figure 5.19. These transients occur at both the instant of voltage dip (i.e. when fault occurs) and the subsequent voltage rise (i.e. when the fault is cleared). The mechanism of transient current generation in the B-DFIG is similar to that of the DFIG, however, there is an additional circuit (i.e. the control winding circuit). Therefore, it can be expected that the Control Winding transients for the B-DFIG are lower than that for the rotor in the DFIG. Another reason is the typically larger leakage inductances of the B-DFIG. It is seen that the maximum current magnitude in the Control Winding circuit is approximately 1.5 times the current required for rated operation when the voltage limits 64 CHAPTER 5. PERFORMANCE UNDER GRID EVENTS 15 Control Winding Phase Currents (kA) Power Winding Phase Currents (kA) 6 4 2 0 −2 −4 −6 −8 999.5 1000 1000.5 1001 1001.5 1002 1002.5 10 5 0 −5 −10 −15 999.5 1003 1000 1000.5 1001 Time (s) 1001.5 1002 1002.5 1003 Time (s) (a) (b) Figure 5.19 LVRT performance of B-DFIG without protection for a 95% Symmetric Voltage Dip at t=1000s (a) Power Winding Phase Currents (b) Control Winding Phase Currents on the power electronic converter is 1.25 times the voltage for rated operation. As with the DFIG, the response of the B-DFIG under the assumption that the voltage on the power electronic converter is not a constraint, is shown in Figure 5.20. The magnitude of the Control Winding voltage required to control the currents is seen in Figure 5.20c. It can be seen that the Volt-Ampere (VA) rating required for the converter is approximately 5.85 times that required for rated operation which is lower than that required for the DFIG. The next section discusses methods to control the transient currents in the Control Winding. 15 Control Winding Phase Currents (kA) Power Winding Phase Currents (kA) 6 4 2 0 −2 −4 −6 −8 999.5 1000 1000.5 1001 1001.5 1002 1002.5 10 5 0 −5 −10 −15 999.5 1003 1000 1000.5 1001 Time (s) 1001.5 1002 1002.5 1003 Time (s) (a) (b) 5000 Rotor Phase Voltages (V) 4000 3000 2000 1000 0 −1000 −2000 −3000 −4000 −5000 999.5 999.6 999.7 999.8 999.9 1000 1000.1 1000.2 1000.3 1000.4 1000.5 Time (s) (c) Figure 5.20 LVRT performance of B-DFIG without constraints on Voltage of Converter for a 95% Symmetric Voltage Dip at t=1000s (a) Power Winding Phase Currents (b) Control Winding Phase Currents (c) Control Winding Phase Voltages 65 CHAPTER 5. PERFORMANCE UNDER GRID EVENTS 5.4.2 Performance with Protection The issue of transient currents in the Control Winding circuit, which is dangerous for the power electronic converter, has been highlighted in the previous section. This section looks at some methods to combat this. Crowbar As with the DFIG, a crowbar circuit may be used to by-pass the power electronic converter in the event of large transient rotor currents. Figure 5.21 shows the response of the B-DFIG when crowbar protection is used. 1000 0.8 0.6 0.4 500 39 0 38 0.2 0 999 999.5 1000 1000.5 1001 1001.5 1002 1002.5 −500 999 1003 999.5 1000 1000.5 Time (s) 1001 1001.5 1002 37 1003 (b) 4 15 d−axis Current q−axis Current Control Winding d−q Currents (kA) d−axis Current q−axis Current 2 0 −2 −4 −6 −8 999 1002.5 Time (s) (a) Power Winding d−q Currents (kA) Generator Speed (rad/s) Generator Torque (kNm) Grid Voltage in Grid Reference Frame (pu) 1 999.5 1000 1000.5 1001 1001.5 1002 1002.5 10 5 0 −5 −10 −15 −20 999 1003 999.5 1000 1000.5 Time (s) 1001 1001.5 1002 1002.5 1003 Time (s) (c) (d) 1.05 1.04 20 20 10 10 0 0 1.01 1 0.99 0.98 −10 −10 Reactive Power (MVAr) 1.02 Active Power (MW) DC−link Voltage (pu) 1.03 0.97 0.96 0.95 999 −20 999.5 1000 1000.5 1001 1001.5 1002 1002.5 1003 999 Time (s) −20 999.5 1000 1000.5 1001 1001.5 1002 1002.5 1003 Time (s) (e) (f ) Figure 5.21 LVRT performance of B-DFIG with Crowbar protection for a 95% Symmetric Voltage Dip at t=1000s (a) Grid Voltage magnitude (b) Torque and Speed (c) Stator Currents in the Stator Flux reference frame (d) Rotor Currents in the Stator Flux reference frame (e) DC link voltage (f ) Active and Reactive Power to the grid 66 CHAPTER 5. PERFORMANCE UNDER GRID EVENTS Crowbarless Protection The lower transient currents in the B-DFIG indicate the ability of controlling the Control Winding currents without the use of external circuits such as the crowbar. This is done by appropriately setting reference currents [44]. Transient currents in the control winding are observed for the duration of disturbance in the Power Winding flux. Therefore, one option would be to set these reference currents to zero for the duration of this disturbance. The results with such a control strategy are shown in Figure 5.22 and Figure 5.23. 1000 0.8 0.6 0.4 500 39 0 38 0.2 0 999 999.5 1000 1000.5 1001 1001.5 1002 1002.5 −500 999 1003 999.5 1000 1000.5 Time (s) 1001 1001.5 1002 37 1003 (b) 4 15 d−axis Current q−axis Current Control Winding d−q Currents (kA) d−axis Current q−axis Current 2 0 −2 −4 −6 −8 −10 999 1002.5 Time (s) (a) Power Winding d−q Currents (kA) Generator Speed (rad/s) Generator Torque (kNm) Grid Voltage in Grid Reference Frame (pu) 1 999.5 1000 1000.5 1001 1001.5 1002 1002.5 10 5 0 −5 −10 −15 −20 999 1003 999.5 1000 1000.5 Time (s) 1001 1001.5 1002 1002.5 1003 Time (s) (c) (d) 1.03 Active Power (MW) DC−link Voltage (pu) 1.04 1.02 1.01 1 20 20 0 0 Reactive Power (MVAr) 1.05 0.99 −20 0.98 999 999.5 1000 1000.5 1001 1001.5 1002 1002.5 1003 999 Time (s) −20 999.5 1000 1000.5 1001 1001.5 1002 1002.5 1003 Time (s) (e) (f ) Figure 5.22 LVRT performance of B-DFIG with Crowbarless protection for a 95% Symmetric Voltage Dip at t=1000s (a) Grid Voltage magnitude (b) Torque and Speed (c) Stator Currents in the Stator Flux reference frame (d) Rotor Currents in the Stator Flux reference frame (e) DC link voltage (f ) Active and Reactive Power to the grid 67 CHAPTER 5. PERFORMANCE UNDER GRID EVENTS 15 Control Winding Phase Currents (kA) Power Winding Phase Currents (kA) 6 4 2 0 −2 −4 −6 −8 999.5 1000 1000.5 1001 1001.5 1002 1002.5 10 5 0 −5 −10 −15 999.5 1003 Time (s) 1000 1000.5 1001 1001.5 1002 1002.5 1003 Time (s) (a) (b) Figure 5.23 LVRT performance of B-DFIG with Crowbarless protection for a 95% Symmetric Voltage Dip at t=1000s (a) Power Winding Phase Currents (b) Control Winding Phase Currents It is seen that such a control strategy is successful in controlling the Control Winding currents in a Low Voltage event and also controls torque oscillations in the machine. However, this strategy limits the ability of the machine to generate power immediately after the clearance of the fault (at t = 1000.25 s in this case). This is not healthy for the grid. 68 CHAPTER 5. PERFORMANCE UNDER GRID EVENTS Therefore, it is advantageous to control the machine such that the reference currents are set to zero only for the duration of the Low Voltage event. The response in this case is shown in Figure 5.24 and Figure 5.25. In this case the Control Winding current is limited to approximately 1.1 times the current at rated operation. 1000 0.8 0.6 0.4 500 39 0 38 0.2 0 999 999.5 1000 1000.5 1001 1001.5 1002 1002.5 −500 999 1003 999.5 1000 1000.5 Time (s) 1001 1001.5 1002 37 1003 (b) 4 15 d−axis Current q−axis Current Control Winding d−q Currents (kA) d−axis Current q−axis Current 2 0 −2 −4 −6 −8 −10 999 1002.5 Time (s) (a) Power Winding d−q Currents (kA) Generator Speed (rad/s) Generator Torque (kNm) Grid Voltage in Grid Reference Frame (pu) 1 999.5 1000 1000.5 1001 1001.5 1002 1002.5 10 5 0 −5 −10 −15 −20 999 1003 999.5 1000 1000.5 Time (s) 1001 1001.5 1002 1002.5 1003 Time (s) (c) (d) 1.05 Active Power (MW) DC−link Voltage (pu) 1.03 1.02 1.01 1 10 0 0 −10 Reactive Power (MVAr) 20 1.04 0.99 −20 0.98 999 999.5 1000 1000.5 1001 1001.5 1002 1002.5 1003 999 Time (s) −20 999.5 1000 1000.5 1001 1001.5 1002 1002.5 1003 Time (s) (e) (f ) Figure 5.24 LVRT performance of B-DFIG with Crowbarless protection for a 95% Symmetric Voltage Dip at t=1000s (a) Grid Voltage magnitude (b) Torque and Speed (c) Stator Currents in the Stator Flux reference frame (d) Rotor Currents in the Stator Flux reference frame (e) DC link voltage (f ) Active and Reactive Power to the grid Chapter 4 has discussed the control of the B-DFIG. It is seen in Section 4.3 that the reference signal id−ref and iq−ref are calculated on the basis of the d-axis Power Winding p p flux (see Equation 4.19 and Equation 4.36). Therefore in the case of a Low Voltage event, it is required to maintain the pre-fault reference values until oscillations in the flux are minimised. The control during the Low Voltage event may therefore be expressed as the following, 1. Detect Low Voltage event. 2. Set inner loop reference currents (i.e. id−ref and iq−ref ) to zero. c c 69 CHAPTER 5. PERFORMANCE UNDER GRID EVENTS 15 Control Winding Phase Currents (kA) Power Winding Phase Currents (kA) 6 4 2 0 −2 −4 −6 −8 999.5 1000 1000.5 1001 1001.5 1002 1002.5 10 5 0 −5 −10 −15 999.5 1003 1000 1000.5 1001 Time (s) 1001.5 1002 1002.5 1003 Time (s) (a) (b) Figure 5.25 LVRT performance of B-DFIG with Crowbarless protection for a 95% Symmetric Voltage Dip at t=1000s (a) Power Winding Phase Currents (b) Control Winding Phase Currents 3. Store the pre-fault current reference values and set post-fault reference to these values until flux disturbance is minimised. An advantage of such a control algorithm is the ability to inject reactive current to the grid during Low Voltage events. This is done by setting the id−ref to the rated value and p q−ref ic to zero. This is shown in Figure 5.26. Ipd−rated Qref p Ref. Gen. idp − id−ref p idp idc − PI PI icd−ref − idc − PI PI ud,ref c + dq Cross-Coupling Compensator ωm Ref. Gen. iq−ref p − q−ref PI + ic −q ic i,q p 0 −q ic Figure 5.26 q,ref PI − uc PI B-DFIG Control Scheme with LVRT Protection The performance of the B-DFIG with such a control algorithm is shown in Figure 5.27. Figure 5.28 shows the Power and Control Winding phase currents. 70 CHAPTER 5. PERFORMANCE UNDER GRID EVENTS 750 39 1 0.8 0.6 0.4 0.2 0 999 250 38 0 −250 37 −500 999.5 1000 1000.5 1001 1001.5 1002 1002.5 −750 999 1003 999.5 1000 1000.5 1001 Time (s) 1001.5 1002 36 1003 (b) 4 15 d−axis Current q−axis Current Control Winding d−q Currents (kA) d−axis Current q−axis Current Power Winding d−q Currents (kA) 1002.5 Time (s) (a) 2 0 −2 −4 −6 −8 −10 999 Generator Speed (rad/s) Generator Torque (kNm) Grid Voltage in Grid Reference Frame (pu) 500 999.5 1000 1000.5 1001 1001.5 1002 1002.5 10 5 0 −5 −10 −15 −20 999 1003 999.5 1000 1000.5 1001 Time (s) 1001.5 1002 1002.5 1003 Time (s) (c) (d) 1.03 Active Power (MW) DC−link Voltage (pu) 1.04 1.02 1.01 1 20 20 0 0 Reactive Power (MVAr) 1.05 0.99 −20 0.98 999 999.5 1000 1000.5 1001 1001.5 1002 1002.5 1003 999 −20 999.5 1000 Time (s) 1000.5 1001 1001.5 1002 1002.5 1003 Time (s) (e) (f ) Figure 5.27 LVRT performance of B-DFIG with Crowbarless protection and Reactive Current Injection for a 95% Symmetric Voltage Dip at t=1000s (a) Grid Voltage magnitude (b) Torque and Speed (c) Stator Currents in the Stator Flux reference frame (d) Rotor Currents in the Stator Flux reference frame (e) DC link voltage (f ) Active and Reactive Power to the grid 15 Control Winding Phase Currents (kA) Power Winding Phase Currents (kA) 6 4 2 0 −2 −4 −6 −8 999.5 1000 1000.5 1001 1001.5 1002 1002.5 10 5 0 −5 −10 −15 999.5 1003 Time (s) 1000 1000.5 1001 1001.5 1002 1002.5 1003 Time (s) (a) (b) Figure 5.28 LVRT performance of B-DFIG with Crowbarless protection and Reactive Current Injection for a 95% Symmetric Voltage Dip at t=1000s (a) Power Winding Phase Currents (b) Control Winding Phase Currents 71 CHAPTER 5. PERFORMANCE UNDER GRID EVENTS 5.5 Discussion This chapter has discussed and compared the LVRT performance of the PMSM, the DFIG and the B-DFIG based wind turbines. The PMSM is not affected by a Low Voltage event because of the power electronic converter that isolates the machine from the grid. The issue for such a wind turbine lies in the voltage rise of the DC link due to a mismatch in the power generated and the power transferred to the grid. A number of methods have been discussed to combat this issue which give an adequate protection against the voltage rise. This wind turbine system has the further advantage that it does not suffer from torque disturbances during voltage dips. When the LVRT performance of the DFIG and the B-DFIG are compared, it is seen that the performance of the B-DFIG is better, i.e. it has lower transient current magnitude as well as lower torque disturbances. This is attributed to the higher leakage inductance of the B-DFIG (in this case the leakage inductance of the B-DFIG is an order of magnitude higher than that of the DFIG) as well as an additional Control Winding circuit. A comparison between the DFIG and B-DFIG is shown in Table 5.2. Table 5.2 Comparison of Maximum Current (without protection) for Winding Circuit connected to Power Electronic Converter during a 95% Symmetric Low Voltage Dip Machine PMSM DFIG B-DFIG without Protection Crowbar without Protection Crowbar-less Protection Maximum Current Israted−operation 2.5 × Irrated−operation 2.2 × Irrated−operation 1.5 × Icrated−operation 1.1 × Icrated−operation Requirement of Extra Circuits for Protection – –– Crowbar based Protection + Algorithm based Protection Here a (-) sign in the last column signifies that the machine has a disadvantage for this criteria, i.e. an extra circuit is required for protection, while a (+) sign signifies that the machine has an advantage for this criteria and does not require an extra circuit for protection. When protection is used, both the DFIG and the B-DFIG can handle the currents generated in the winding connected to the power electronic converter. The DFIG does this by bypassing the converter with the help of a crowbar circuit. The B-DFIG, however, can achieve this without the use of an external circuit. The torque oscillations for the BDFIG are also lower than that in the DFIG. From the results obtained it can be concluded that Crowbarless operation of the B-DFIG is possible during Low Voltage events. The advantages of the LVRT performance of the B-DFIG over the DFIG is, • The currents during the low voltage event are lower in the B-DFIG. • The protection for the B-DFIG can be achieved with a control algorithm and does not require an external protection circuit. • The B-DFIG controller retains control of the machine through the low voltage event. For the DFIG the controller is disconnected when the low voltage event is disconnected. 72 Chapter 6 Conclusion 6.1 Conclusions This thesis work has looked at the modelling and control of the Brushless Doubly Fed Induction Generator (B-DFIG). The controller developed for the machine is based on vector control methods and has two current loops. It has been found that using the Power Winding Active Power (Pp ) is a good way to control the output of the machine and a method to generate a reference (Ppref ) signal for optimal operation is developed. This has been done using the steady state characteristics and calculating the point at which the machine has the highest efficiency for a given machine torque. The concept of ‘Cross-Coupling Compensation’ for control has also been developed and implemented. Further this thesis focussed on the performance of the machine under symmetric low voltage events. This performance is compared with that of two other generators - the Permanent Magnet Synchronous Machine (PMSM) and the Doubly Fed Induction Generator (DFIG). The concept of protection for these generators is also looked at. All the three case study generators used are developed for a 3.2MW wind turbine drivetrain. Therefore, they provide a good basis on which a comparison can be made. The dynamic model and controller for all three types of machines have been developed for this thesis, however, only the model and controller for the B-DFIG has been covered in detail. It has been found that for the PMSM based wind turbine, the issue with Low Voltage Ride Through (LVRT) is the rise in the DC link voltage . This is due to the mismatch in power generated by the machine and the power transferred to the grid (which is limited by the reduced voltage at the grid side converter terminals). Methods for controlling this DC voltage rise, such as the use of an energy discharge circuit, have also been investigated. Another method described is Power Balancing, where the power generated by the machine is controlled to match the power transferred to the grid in the event of a low voltage event. This method has been seen to control the issue of DC link voltage rise as well, however, it introduces torque disturbances in the machine. For the DFIG it has been found that voltage dips cause large transient currents in the stator and rotor circuit. The over-currents in the rotor circuit are a cause for concern as they may lead to adverse effects on the power electronic converter connected to the circuit. A possible method to overcome this issue - the use of a Crowbar circuit - has been investigated. The crowbar circuit manages the problem by bypassing the power electronic converter in the event of current rise. Additionally, the crowbar resistors reduce the time 73 CHAPTER 6. CONCLUSION constant of the rotor circuit, allowing for a faster decay of transient currents. In the case of the B-DFIG, it has been found that again transient currents are set up in the power and control windings in the event of a voltage dip. However, the magnitude of these currents is lower when compared to that in a DFIG. This is attributed to the higher leakage inductance of the B-DFIG. A Crowbarless method has also been studied which is successful in controlling the high currents generated in the control winding. This Crowbarless control method also reduces the torque oscillations observed in the B-DFIG for a low voltage event. In conclusion, apart from offering better reliability through the exclusion of slip ring and brushes, the B-DFIG also has an improved LVRT performance when compared with the DFIG. The protection is also simpler and does not require an external circuit, like the crowbar, but can be built into the control algorithm of the machine controller. 6.2 Future Work Over the course of this thesis a number of possible avenues of further investigation have been identified. First, the response of the machine with the controller developed for normal operation as well as under low voltage events need to be practically validated. Second, this study has been conducted on a machine whose design has not been optimised. Although, it is not expected that there would be a large variation in the nature of the results presented, it would be beneficial if this study is extended to such an optimised machine. Third, in this study the complete reactive power interaction is considered from the power winding of the machine. In reality, there is a possibility to use the grid side converter for the transfer of reactive power to and from the grid as well. This aspect and its effect on the machine response should be looked into. Finally, this study has focussed only on symmetric voltage dips. It would be interesting to study the effect of asymmetric dips (such as those caused by single line or double line faults) on the machine. 74 Bibliography [1] L. J. Hunt, “A New Type Of Induction Motor,” Journal of IEE, vol. 38, pp. 648–677, 1907. [2] F. Creedy, “Some Developments in Multi-Speed Cascade Induction Motors,” Journal of IEE, vol. 59, pp. 511–537, 1921. [3] A. R. W. Broadway and L. Burbridge, “Self-cascaded machine : a low-speed motor or high-frequency brushless alternator,” Proceedings of IEE, vol. 117, no. 7, pp. 1277– 1290, 1970. [4] A. Kusko and C. B. Somuah, “Speed Control of a Single-Frame Cascade Induction Motor with Slip-Power Pump Back,” IEEE Transactions on Industry Applications1, vol. IA-14, no. 2, pp. 97–105, 1978. [5] P. Rochelle, R. Spée, and A. K. Wallace, “The Effect of Stator Winding Configuration on the Performance of Brushless Doubly-Fed Machines in Adjustable Speed Drives,” Conference Record of the IEEE Industry Applications Society Annual Meeting, vol. 1, pp. 331–337, 1990. [6] A. Wallace, R. Spée, and H. K. Lauw, “Dynamic Modeling of Brushless Doubly-Fed Machines,” Conference Record of the IEEE Industry Applications Society Annual Meeting, vol. 1, pp. 329–334, 1989. [7] R. Spée, A. K. Wallace, and H. K. Lauw, “Performance Simulation of Brushless DoublyFed Adjustable Speed Drives,” Conference Record of the IEEE Industry Applications Society Annual Meeting1, vol. 1, pp. 738–743, 989. [8] R. Li, A. Wallace, R. Spée, and Y. Wang, “Two-Axis Model Development of CageRotor Brushless Doubly-Fed Machines,” IEEE Transactions on Energy Conversion, vol. 6, no. 3, pp. 453–460, 1991. [9] R. Li, A. Wallace, and R. Spée, “Dynamic Simulation of Brushless Doubly-Fed Machines,” IEEE Transactions on Energy Conversion, vol. 6, no. 3, pp. 445–452, 1991. [10] S. Williamson, A. C. Ferreira, and A. K. Wallace, “Generalised theory of the brushless doubly-fed machine . Part I : Analysis,” IEE Proceedings - Electric Power Applications, vol. 144, no. 2, pp. 111–122, 1997. [11] S. Williamson and A. Ferreira, “Generalised theory of the brushless doubly-fed machine. Part 2: Model verification and performance,” IEE Proceedings - Electric Power Applications, vol. 144, no. 2, p. 123, 1997. 75 BIBLIOGRAPHY [12] D. Zhou and R. Spée, “Synchronous Frame Model and Decoupled Control Development for Doubly-Fed Machines,” IEEE Power Electronics Specialists Conference, vol. 2, pp. 1229–1236, 1994. [13] D. Zhou, R. Spée, G. C. Alexander, and A. K. Wallace, “A Simplified Method for Dynamic Control of Brushless Doubly-Fed Machines,” IEEE International Conference on Industrial Electronics, Control and Instrumentation, vol. 2, pp. 946–951, 1996. [14] J. Poza, E. Oyarbide, and D. Roye, “New vector control algorithm for brushless doublyfed machines,” IEEE 28th Annual Conference of the Industrial Electronics Society. IECON, vol. 2, no. 3, pp. 1138–1143, 2002. [15] S. Shao, E. Abdi, and R. McMahon, “Dynamic Analysis of the Brushless Doubly-Fed Induction Generator during Symmetrical Three-Phase Voltage Dips,” International Conference on Power Electronics and Drive Systems, pp. 464–469, 2009. [16] S. Shao, T. Long, E. Abdi, R. McMahon, and Y. Wu, “Symmetrical Low Voltage Ride-Through of the Brushless Doubly-Fed Induction Generator,” IEEE Industrial Electronics Society Conference, pp. 3209–3214, 2011. [17] T. Long, S. Shao, E. Abdi, R. a. McMahon, and S. Liu, “Asymmetrical Low-Voltage Ride Through of Brushless Doubly Fed Induction Generators for the Wind Power Generation,” IEEE Transactions on Energy Conversion, vol. 28, pp. 502–511, Sept. 2013. [18] R. A. McMahon, P. C. Roberts, X. Wang, and P. J. Tavner, “Performance of BDFM as generator and motor,” IEE Proceedings - Electric Power Applications, vol. 153, no. 2, pp. 289–299, 2006. [19] R. Li, R. Spee, A. Wallace, and G. Alexander, “Synchronous drive performance of brushless doubly-fed motors,” IEEE Transactions on Industry Applications, vol. 30, no. 4, pp. 963–970, 1994. [20] G. R. Slemon, “Circuit Models for Polyphase Induction Machines,” Electric Machines & Power Systems, vol. 8, no. 4-5, pp. 369–379, 1983. [21] J. Manwell, J. McGowan, and A. Rogers, Wind Energy Explained - Theory, Design and Application. Wiley, 2009. [22] J. Slootweg, H. Polinder, and W. Kling, “Dynamic Modelling of a Wind Turbine with Doubly Fed Induction Generator,” Power Engineering Society Summer Meeting, vol. 1, pp. 644–649, 2001. [23] R. Pena, J. Dlare, and G. Asher, “Doubly fed induction generator uising back-to-back PWM converters and its application to variable- speed wind-energy generation,” IEE Proc.-Electr. Power Appl., vol. 143, no. 3, pp. 231–241, 1996. [24] O. Anaya-Lara, N. Jenkins, J. Ekanayake, P. Cartwright, and M. Hughes, Wind Energy Generation - Modelling and Control. Wiley, 2009. 76 BIBLIOGRAPHY [25] L. Holdsworth, X. G. Wu, J. B. Ekanayake, and N. Jenkins, “Comparison of fixed speed and doubly-fed induction wind turbines during power system disturbances,” IEE Proc. -Gener. Transm. Distrib., vol. 150, no. 3, pp. 343–352, 2003. [26] J. Poza, E. Oyarbide, D. Roye, and I. Sarasola, “Stability Analysis of a BDFM under Open-Loop Voltage Control,” Proc. European Conf. Power Electronics and Applications (EPE), pp. 1–10, 2005. [27] I. Sarasola, J. Poza, E. Oyarbide, and M. A. Rodrı́guez, “Stability Analysis of a Brushless Doubly-Fed Machine under Closed Loop Scalar Current Control,” Proc. IEEE Industrial Electronics Society Conf. (IECON), pp. 1527–1532, 2006. [28] D. Zhou, R. Spee, and G. C. Alexander, “Experimental Evaluation of a Rotor Flux Oriented Control Algorithm for Brushless Doubly-Fed Machines,” IEEE Transactions on Power Electronics, vol. 12, no. 1, pp. 72–78, 1997. [29] J. Poza, E. Oyarbide, I. Sarasola, and M. Rodriguez, “Vector control design and experimental evaluation for the brushless doubly fed machine,” IET Electric Power Applications, vol. 3, no. 4, pp. 247–256, 2009. [30] E. Abdi, F. Barati, and R. McMahon, “Stator-Flux-Oriented Vector Control for Brushless Doubly Fed Induction Generator,” IEEE Transactions on Industrial Electronics, vol. 56, pp. 4220–4228, Oct. 2009. [31] W. R. Brassfield, R. Spee, and T. G. Habetler, “Direct Torque Control for Brushless Doubly-Fed Machines,” IEEE Transactions on Industry Applications, vol. 32, no. 5, pp. 1098–1104, 1996. [32] I. Sarasola, J. Poza, M. A. Rodriguez, and G. Abad, “Direct Torque Control for Brushless Doubly Fed Induction Machines,” 2007 IEEE International Electric Machines & Drives Conference, pp. 1496–1501, May 2007. [33] I. Sarasola, J. Poza, M. A. Rodrı́guez, and G. Abad, “Predictive Direct Torque Control for Brushless Doubly Fed Machine with Reduced Torque Ripple at Constant Switching Frequency,” Proc. IEEE Int. Symp. on Industrial Electronics (ISIE), pp. 1074–1079, 2007. [34] A. Tapia, G. Tapia, J. Ostolaza, and J. Saenz, “Modeling and control of a wind turbine driven doubly fed induction generator,” IEEE Transactions on Energy Conversion, vol. 18, pp. 194–204, June 2003. [35] L. Harnefors and H.-P. Nee, “Model-based current control of AC machines using the internal model control method,” IEEE Transactions on Industry Applications, vol. 34, no. 1, pp. 133–141, 1998. [36] ENTSO-E, “Implementation Guideline for Network Code Requirements for Grid Connection Applicable to all Generators.” [37] ENTSO-E, “Network Code For Requirements For Grid Connection Applicable To All Generators - Frequently Asked Questions.” 77 BIBLIOGRAPHY [38] C. Abbey, W. Li, L. Owatta, and G. Joos, “Power Electronic Converter Control Techniques for Improved Low Voltage Ride Through Performance in WTGs,” Power Electronics Specialists Conference, pp. 1–6, 2006. [39] X.-P. Yang, X.-F. Duan, F. Feng, and L.-L. Tian, “Low Voltage Ride-Through of Directly Driven Wind Turbine with Permanent Magnet Synchronous Generator,” 2009 Asia-Pacific Power and Energy Engineering Conference, pp. 1–5, Mar. 2009. [40] J. F. Conroy and R. Watson, “Low-voltage ride-through of a full converter wind turbine with permanent magnet generator,” IET Renew. Power Gener., vol. 1, no. 3, pp. 182– 189, 2007. [41] W. Wang, B. Ge, D. Bi, M. Qin, and W. Liu, “Energy storage based LVRT and stabilizing power control for direct-drive wind power system,” 2010 International Conference on Power System Technology, vol. 3, pp. 1–6, Oct. 2010. [42] M. Ezzat, M. Benbouzid, S. Muyeen, and L. Harnefors, “Low-voltage ride-through techniques for DFIG-based wind turbines: state-of-the-art review and future trends,” IECON 2013 - 39th Annual Conference of the IEEE Industrial Electronics Society, pp. 7681–7686, Nov. 2013. [43] J. Liang, W. Qiao, and R. G. Harley, “Feed-Forward Transient Current Control for Low-Voltage Ride-Through Enhancement of DFIG Wind Turbines,” IEEE Transactions on Energy Conversion, vol. 25, no. 3, pp. 836–843, 2010. [44] T. Long, S. Shao, P. Malliband, E. Abdi, and R. McMahon, “Crowbarless Fault RideThrough of the Brushless Doubly Fed Induction Generator in a Wind Turbine Under Symmetrical Voltage Dips,” IEEE Transactions on Industrial Electronics, vol. 60, no. 7, pp. 2833–2841, 2013. [45] J. L. Willems, “Generalized Clarke Components for Polyphase Networks,” IEEE Transactions on Education, pp. 69–71, 1969. 78 Appendices 79 Appendix A Additional LVRT Performance Simulations Chapter 5 has investigated the performance of the PMSM, DFIG and B-DFIG based machines for the ‘Case A’ Symmetric Voltage Dip. In this section performance of these machines far a symmetric voltage dip as shown in Figure A.1 is discussed. V oltage (pu) 1.0 0.25 Figure A.1 A.1 T ime (s) 3.0 Voltage profile for Case B of the LVRT response study LVRT Performance of the PMSM In this section the performance of the PMSM machine with and without protection as discussed in Chapter 5 is shown. 81 APPENDIX A. ADDITIONAL LVRT PERFORMANCE SIMULATIONS A.1.1 Performance without Protection Figure A.2 shows the performance of the PMSM machine when faced with a 95% symmetric voltage dip as shown in Figure A.1. 0 32 −50 31 −100 30 −150 29 0.8 0.6 0.4 0.2 0 999 1000 1001 1002 1003 1004 −200 999 1005 1000 1001 1002 Time (s) 1004 28 1005 (b) 50 0.2 d−axis Current q−axis Current 0 d−axis Current q−axis Current 40 30 Grid d−q Currents (kA) −0.2 −0.4 −0.6 −0.8 −1 −1.2 20 10 0 −10 −20 −30 −1.4 −40 −1.6 999 1003 Time (s) (a) Generator d−q Currents (kA) Generator Speed (rad/s) Generator Torque (kNm) Grid Voltage in Grid Reference Frame (pu) 1 1000 1001 1002 1003 1004 −50 999 1005 1000 1001 1002 Time (s) Time (s) (c) 1003 1004 1005 (d) 3.5 DC−link Voltage (pu) 3 2.5 2 1.5 1 0.5 999 1000 1001 1002 1003 1004 1005 Time (s) (e) Figure A.2 LVRT performance of PMSM without Protection (a) Grid Voltage magnitude (b) Torque and Speed (c) Generator Currents in the PW reference frame (d) Grid Currents in the grid reference frame (e) DC link voltage A.1.2 Performance with Protection In this section the performance of the PMSM with protection against LVRT is shown. The protection methods used in Chapter 5 are covered. 82 APPENDIX A. ADDITIONAL LVRT PERFORMANCE SIMULATIONS Energy Discharge Circuit The LVRT performance of the PMSM with an Energy Discharge circuit is shown in Figure A.3. 0 32 −50 31 −100 30 −150 29 0.8 0.6 0.4 0.2 0 999 1000 1001 1002 1003 1004 −200 999 1005 1000 1001 Time (s) 1002 1003 1004 28 1005 Time (s) (a) (b) 20 0.2 d−axis Current q−axis Current 0 d−axis Current q−axis Current 15 −0.2 Grid d−q Currents (kA) Generator d−q Currents (kA) Generator Speed (rad/s) Generator Torque (kNm) Grid Voltage in Grid Reference Frame (pu) 1 −0.4 −0.6 −0.8 −1 −1.2 10 5 0 −5 −10 −1.4 −15 −1.6 999 1000 1001 1002 1003 1004 −20 999 1005 1000 1001 Time (s) (c) 1004 1005 1003 1004 1005 2.5 Braking Resistor Current (kA) 1.01 DC−link Voltage (pu) 1003 (d) 1.015 1.005 1 0.995 0.99 0.985 999 1002 Time (s) 1000 1001 1002 1003 1004 2 1.5 1 0.5 0 999 1005 Time (s) 1000 1001 1002 Time (s) (e) (f ) Figure A.3 LVRT performance of PMSM with Energy Discharge Circuit (a) Grid Voltage magnitude (b) Torque and Speed (c) Generator Currents in the PW reference frame (d) Grid Currents in the grid reference frame (e) DC link voltage (f ) Energy Discharge Circuit - Resistor Current Power Balancing Figure A.4 shows the performance of the PMSM when protectied with the Power Balancing Algorithm. 83 APPENDIX A. ADDITIONAL LVRT PERFORMANCE SIMULATIONS 0 32 −50 31 −100 30 −150 29 0.8 0.6 0.4 Generator Speed (rad/s) Generator Torque (kNm) Grid Voltage in Grid Reference Frame (pu) 1 0.2 0 999 1000 1001 1002 1003 1004 −200 999 1005 1000 1001 1002 Time (s) 1003 1004 28 1005 Time (s) (a) (b) 10 d−axis Current q−axis Current d−axis Current q−axis Current 5 Grid d−q Currents (kA) Generator d−q Currents (kA) 0 −0.5 −1 0 −5 −10 −1.5 −15 −2 999 1000 1001 1002 1003 1004 −20 999 1005 1000 1001 1002 Time (s) Time (s) (c) 1003 1004 1005 (d) 1.04 1.03 DC−link Voltage (pu) 1.02 1.01 1 0.99 0.98 0.97 0.96 0.95 999 1000 1001 1002 1003 1004 1005 Time (s) (e) Figure A.4 LVRT performance of PMSM with Power Balancing (a) Grid Voltage magnitude (b) Torque and Speed (c) Generator Currents in the PW reference frame (d) Grid Currents in the grid reference frame (e) DC link voltage A.2 LVRT Performance of the DFIG This section shows the performance of the DFIG for a symmetric voltage drop as shown in Figure A.1. A.2.1 Performance without Protection Figure A.6 shows the performance of the DFIG without protection. 84 APPENDIX A. ADDITIONAL LVRT PERFORMANCE SIMULATIONS 1000 32.5 0.8 0.6 0.4 500 30.5 29.5 0 28.5 0.2 0 999 1000 1001 1002 1003 1004 −500 999 1005 1000 1001 Time (s) 27.5 1005 d−axis Current q−axis Current 15 Rotor d−q Currents (kA) Stator d−q Currents (kA) 1004 20 d−axis Current q−axis Current 10 5 0 −5 −10 −15 −20 10 5 0 −5 −10 −15 1000 1001 1002 1003 1004 −20 999 1005 1000 1001 Time (s) 1002 1003 1004 1005 Time (s) (c) (d) 15 20 10 15 Rotor Phase Currents (kA) Stator Phase Currents (kA) 1003 (b) 15 5 0 −5 −10 −15 −20 999.5 1002 Time (s) (a) −25 999 Generator Speed (rad/s) 31.5 Generator Torque (kNm) Grid Voltage in Grid Reference Frame (pu) 1 10 5 0 −5 −10 −15 1000 1000.5 1001 1001.5 −20 999.5 Time (s) 1000 1000.5 1001 1001.5 Time (s) (e) (f ) Figure A.5 LVRT performance of DFIG without Protection (a) Grid Voltage magnitude (b) Torque and Speed (c) Stator Currents in the Stator Flux Reference Frame (d) Rotor Currents in the Stator Flux Reference Frame (e) Stator Phase Currents (f ) Rotor Phase Currents A.2.2 Performance with Crowbar Protection Figure A.6 shows the performance of the DFIG when a Crowbar circuit as defined in Section 5.3.2 is used. 85 APPENDIX A. ADDITIONAL LVRT PERFORMANCE SIMULATIONS 1000 32.5 0.8 0.6 0.4 500 30.5 29.5 0 28.5 0.2 0 999 1000 1001 1002 1003 1004 −500 999 1005 1000 1001 1002 Time (s) 1003 1004 (b) 15 10 d−axis Current q−axis Current d−axis Current q−axis Current 10 5 Rotor d−q Currents (kA) Stator d−q Currents (kA) 27.5 1005 Time (s) (a) 5 0 −5 0 −5 −10 −10 −15 999 1000 1001 1002 1003 1004 −15 999 1005 1000 1001 1002 Time (s) 1003 1004 1005 Time (s) (c) (d) 15 15 10 10 Rotor Phase Currents (kA) Stator Phase Currents (kA) Generator Speed (rad/s) 31.5 Generator Torque (kNm) Grid Voltage in Grid Reference Frame (pu) 1 5 0 −5 −10 5 0 −5 −10 −15 999.5 1000 1000.5 1001 −15 999.5 1001.5 1000 1000.5 Time (s) 1001 1001.5 Time (s) (e) (f ) 15 Rotor Phase Currents (kA) 10 5 0 −5 −10 −15 999.5 1000 1000.5 1001 1001.5 1002 1002.5 1003 1003.5 1004 1004.5 1005 Time (s) (g) Figure A.6 LVRT performance of DFIG without Protection (a) Grid Voltage magnitude (b) Torque and Speed (c) Stator Currents in the Stator Flux Reference Frame (d) Rotor Currents in the Stator Flux Reference Frame (e) Stator Phase Currents (f ) Rotor Phase Currents (g) Crowbar Phase Currents A.3 LVRT Performance of the B-DFIG This section charts the performance of the B-DFIG with and without protection for voltage dips as shown in Figure A.1 86 APPENDIX A. ADDITIONAL LVRT PERFORMANCE SIMULATIONS A.3.1 Performance without Protection Performance of the B-DFIG without protection is shown in Figure A.7. 750 39 1 0.6 0.4 0.2 250 38 0 −250 37 −500 0 999 1000 1001 1002 1003 1004 −750 999 1005 1000 1001 Time (s) 1002 1003 (b) 5 15 d−axis Current q−axis Current Control Winding d−q Currents (kA) Power Winding d−q Currents (kA) d−axis Current q−axis Current 0 −5 −10 999 1000 1001 1002 1003 1004 10 5 0 −5 −10 −15 −20 999 1005 1000 1001 Time (s) 1002 1003 1004 1005 Time (s) (c) (d) 15 Control Winding Phase Currents (kA) 6 Power Winding Phase Currents (kA) 36 1005 1004 Time (s) (a) 4 2 0 −2 −4 −6 −8 999.5 Generator Speed (rad/s) Generator Torque (kNm) Grid Voltage in Grid Reference Frame (pu) 500 0.8 1000 1000.5 1001 1001.5 1002 1002.5 1003 1003.5 1004 1004.5 10 5 0 −5 −10 −15 999.5 1005 Time (s) 1000 1000.5 1001 1001.5 1002 1002.5 1003 1003.5 1004 1004.5 1005 Time (s) (e) (f ) Figure A.7 LVRT performance of B-DFIG without Protection (a) Grid Voltage magnitude (b) Torque and Speed (c) Power Winding Currents in the PW Reference Frame (d) Control Winding Currents in the PW Reference Frame (e) Stator Phase Currents (f ) Rotor Phase Currents 87 APPENDIX A. ADDITIONAL LVRT PERFORMANCE SIMULATIONS 88 Appendix B B-DFIG Analytical Parameter Calculation This appendix deals with the calculation of some parameters of the Brushless Doubly Fed Machine. B.1 Mutual Inductance - Power and Control Windings The flux linkage between the two windings is, ∞ X ∞ Z X λsaA = 2π φpakp (αm )ZcAkc (αm )rdαm (B.1) kp =1 kc =1 0 where αm is the mechanical angle along the stator, φpakp is the expression for the kp harmonic flux produced by a current in the 0 a0 phase of the Power Winding and ZcAkc is the kc harmonic conductor distribution of the 0 a0 phase of the Control Winding. φpa and ZcA are of the form, lrB̂ pa sin(kpp αm + pp βkpa ) kpp Nsek = sin(kpc αm ) 2r φpak = ZcAk (B.2) Therefore, λsaA = ∞ X ∞ Z X kp =1 kc =1 0 2π ls rNsekp B̂ pa sin(kp pp αm + pp βkp pa ) sin(kc pc αm ) 2kp pp (B.3) This will have a value of zero ∀kp pp 6= kc pc . Therefore, the two stator windings are not mutually coupled except for the case of certain harmonic frequencies depending on the number of poles of each winding. Also, the pole number of the two windings can be chosen such that there is no coupling for these windings for any harmonic number. 89 APPENDIX B. B-DFIG ANALYTICAL PARAMETER CALCULATION Figure B.1 B.2 Rotor Structure with Nn nests of 3 loops each Mutual Inductance between Rotor loops The rotor structure consists of a set of Nn nests each with a set of Nl loops. This is shown in figure B.1. To calculate the mutual inductance between two rotor loops first we define the conductor distribution of the rotor loops. This distribution can be represented in the form of the dirac delta function. This distribution will be further broken down into a set of sinusoidally distributed windings using Fourier Analysis. Figure B.2 gives the distribution of the rotor conductors in space. This is used to calculate the equivalent fourier distribution. Because the conductor distribution of the Figure B.2 Rotor Loops in the Rotor Space 90 APPENDIX B. B-DFIG ANALYTICAL PARAMETER CALCULATION rotor loops is odd, an of the fourier distribution will be zero. The value of bn is given by, Z π 2Nn Nn bn = δ(α − γ) sin(nNn α)dα π 0 Z π 2Nn Nn 1 (B.4) bn = lim sin(nNn α)dα π 0 →0 Z γ+ 1 2Nn bn = lim sin(nNn α)dα →0 π γ Therefore, 2Nn sin(nNn γ) π The conductor distribution is now given as, bn = Zj (α) = ∞ X 2Nn Zc sin(kNn γj ) sin(kNn α) π k=1 (B.5) (B.6) where Zc is the number of rotor conductors per slot. The MMF due to a current flowing through the loop j is given by, Fj (α) = ij Z α+ Nπ n Zj dα α Fj (α) = Fj (α) = ∞ X 2Nn Zc k=1 ∞ X k=1 π sin(kNn γj ) Z α+ Nπ n sin(kNn α)dα α (B.7) 4ij Zc sin(kNn γj ) cos(kNn α) kπ From Ampere’s Law and equation B.7 we get, Bj (α) = ∞ X 2µ0 ij Zc k=1 gkπ sin(kNn γj ) cos(kNn α) (B.8) where g is the effective air-gap length. The flux linkage between the loops j and m (i.e. λjm ) is now given by, λjm = Z 2π ∞ X ∞ X 4µ0 Nn Zcj Zcm ij ls r sin(k N γ ) sin(k N γ ) sin(kj Nn α) sin(km Nn α)dα j n j m n m gkj π 2 0 kj =1 km =1 (B.9) When the two loops are displaced from a common reference point by the mechanical angles βj and βm , λjm can be written as, λjm ∞ X ∞ X 4µ0 Nn Zcj Zcm ij ls r = sin(kj Nn γj ) sin(km Nn γm ) gkj π 2 kj =1 km =1 Z 2π sin(kj Nn α − Nn βj ) sin(km Nn α − Nn βm )dα 0 91 (B.10) APPENDIX B. B-DFIG ANALYTICAL PARAMETER CALCULATION This will have a non-zero value only if kj = km which will be given by, λjm = ∞ X 4µ0 Zcj Zcm ij ls r k=1 gk 2 π sin(kNn γj ) sin(kNn γm ) cos(Nn βj − Nn βm ) (B.11) Therefore, the mutual inductance is given by, Mjm = ∞ X 4µ0 Zcj Zcm ls r k=1 B.3 gk 2 π sin(kNn γj ) sin(kNn γm ) cos(Nn βj − Nn βm ) (B.12) Mutual Inductance between Rotor and Stator The flux due to a current in the rotor loop is given by, φr (α) = ∞ X 2µ0 Zc ir ls r k=1 gkn π sin(kNn γr ) sin(kNn α − βr ) (B.13) where βr is the angle between the rotor loop and an arbitrary frame of reference. The conductor distribution for the stator coils is given by, Zs (α) = ∞ X Nse k=1 2r sin(kpα − pβs ) (B.14) where Nse is the effective number of winding turns and βs is the angle between the stator winding and the arbitrary frame of reference. The flux linkage is given by, λsr Z 2π ∞ X ∞ X µ0 ir ls rNse Zc = sin(kr Nn γr ) sin(kr Nn α − pβr ) sin(ks pα − pβs )dα (B.15) gkr π 0 kr =1 ks =1 which will have a non zero value only when kr Nn = ks p which is given by, λsr = ∞ X µ0 ir ls rNse Zc k=1 where k = (2n − 1) gk 2 sin(kNn γr ) cos(pβr − pβs ) (B.16) Nn where k, nN . Therefore, the mutual inductance is given by, p Msr = ∞ X µ0 ls rNse Zc k=1 gk 2 sin(kNn γr ) cos(pβr − pβs ) 92 (B.17) Appendix C B-DFIG Simple Case Study Machine This appendix gives the overview of the case study machine that has been used in the preliminary development of the machine and its control. It is based on a single loop rotor design for simplicity and neglects all saturation. The electric circuit parameters are derived from the discussion in Appendix B. Table C.1 B-DFIG Design Number of Pole Pairs (PW & CW) Rated Electric Frequency (PW & CW) Rated Generator Speed Stator Outer Radius Stack Length Rotor Inner Radius Air-Gap Length Ratio Length-Diameter Ratio Slot height-Slot width Stator Yoke Width Stator Slot Width Table C.2 Hz rpm m m m mm mm mm 4&6 50 & 20 275 0.83 1.57 0.58 1.5 0.96 2.35 80 29.7 Winding Parameters Power winding pole-pairs Power winding slots/pole/phase Power winding no. of turns per coil Power winding pole-pitch Power winding coil-pitch Control winding pole-pairs Control winding slots/pole/phase Control winding no. of turns per coil Control winding pole-pitch Control winding coil-pitch 93 pp qp np ypp ypc pc qc nc ycp ycc 4 3 1 9 9 6 2 1 6 6 APPENDIX C. B-DFIG SIMPLE CASE STUDY MACHINE 94 APPENDIX C. B-DFIG SIMPLE CASE STUDY MACHINE Table C.3 Electrical Circuit Parameters Power winding resistance Power winding main inductivity (main harmonic) Power winding leakage inductivity Control winding resistance Control winding main inductivity (main harmonic) Control winding leakage inductivity Rotor nest loop-1 resistance Rotor nest loop-1 (pp main harmonic) inductivity Rotor nest loop-1 (pc main harmonic) inductivity Rotor nest leakage inductivity 95 Rp Lpm(p) Lpσ Rc Lcm(c) Lcσ Rr Lrm(p) Lrm(c) Lrσ H mH H mH m mH mH mH 0.0023 0.0116 0.1447 0.0021 0.0052 0.1447 0.0296 0.1 0.0843 0.0068 APPENDIX C. B-DFIG SIMPLE CASE STUDY MACHINE 96 Appendix D PMSM 3.2MW Case Study Machine This appendix describes the details of the PMSM generator. The design of this generator has been based on a number of optimisation variables, including stack length, stator inner radius and stator outer radius, for the REpower 3.2M114 wind turbine. This design and optimisation is not within the scope of this thesis. D.1 Machine Details Table D.1 PMSM Design Number of Pole Pairs Rated Electric Frequency Rated Generator Speed Stator Outer Radius Stack Length Rotor Inner Radius Air-Gap Length Ratio Length-Diameter Ratio Slot height-Slot width Stator Yoke Width Stator Slot Width Table D.2 Stator Stator Stator Stator winding winding winding winding Hz rpm m m m mm mm mm 11 51.02 278.3 0.85 0.63 0.66 2.58 0.37 1.91 52.07 34.71 Winding Parameters slots/pole/phase number of turns per coil pole-pitch coil-pitch 97 q n yp ypc 1 1 3 3 APPENDIX D. PMSM 3.2MW CASE STUDY MACHINE Table D.3 Electrical Circuit Parameters Stator voltage Frequency Stator nominal current Stator resistance Stator main inductivity (main harmonic) Stator leakage inductivity 0 V Hz A m mH mH 205 50 5969.9 0.32518 0.0081 1.9000E-03 −0.8475 Figure D.1 D.2 U snom fe Isnom Rs Lsm Lsσ Geometric Plot of the PMSM Case Study Machine Machine Dynamic Equations in Rotor Flux Reference Frame ūrs = Rs īrs + pωm r,d λr,d s = Ls is + ψr λr,q s = T = 0 −1 r dλ̄rs λ̄s + 1 0 dt Ls ir,q s pψr ir,q s (D.1) (D.2) (D.3) (D.4) 98 Appendix E DFIG 3.2MW Case Study Machine E.1 Machine Details This appendix describes the details of the DFIG generator. The design of this generator has been based on a number of optimisation variables, including stack length, stator inner radius and stator outer radius, for the REpower 3.2M114 wind turbine. This design and optimisation is not within the scope of this thesis. Table E.1 DFIG Design Number of Pole Pairs Rated Electric Frequency Rated Generator Speed Stator Outer Radius Stack Length Rotor Inner Radius Air-Gap Length Ratio Length-Diameter Ratio Slot height-Slot width Stator Yoke Width Stator Slot Width Table E.2 Stator Stator Stator Stator Hz rpm m m m mm mm mm 13 50.30 278.30 0.85 0.97 0.66 2.58 0.57 1.15 46.52 31.01 Winding Parameters slots/pole/phase number of turns per coil pole-pitch coil-pitch 99 q n ysp ysc 1 1 3 3 APPENDIX E. DFIG 3.2MW CASE STUDY MACHINE Table E.3 Electrical Circuit Parameters Stator voltage Stator frequency Stator nominal current Rotor nominal current Stator resistance Stator main inductivity (main harmonic) Stator leakage inductivity Rotor resistance Rotor main inductivity (main harmonic) Rotor leakage inductivity U snom f se Isnom Irnom Rs Lsm Lsσ Rr Lrm Lrσ V Hz A A mH mH m mH mH 333 50 2880.7 3256 0.0011 0.487 0.0495 0.911 0.4859 0.0588 0 −0.8522 Figure E.1 Geometric Plot of the DFIG Case Study Machine 100 APPENDIX E. DFIG 3.2MW CASE STUDY MACHINE E.2 Machine Dynamic Equations in Arbitrary Reference Frame 0 −1 k dλ̄ks = + (pωm + ωk ) λ̄s + 1 0 dt k 0 −1 k dλ̄r ūkr = Rr īkr + ωk λ̄r + 1 0 dt 1 (Lr λ̄ks − Msr λ̄kr ) īks = 2 Ls Lr − Msr 1 īkr = (−Msr λ̄ks + Ls λ̄kr ) 2 Ls Lr − Msr ūks Rs īks k,d k,d k,q T = pMsr (ik,q s ir − is ir ) 101 (E.1) (E.2) (E.3) (E.4) (E.5) APPENDIX E. DFIG 3.2MW CASE STUDY MACHINE 102 Appendix F B-DFIG 3.2MW Case Study Machine This appendix describes the details of the B-DFIG generator, based on a 4-rotor loop rotor design. The design of this generator has been based on a number of optimisation variables, including stack length, stator inner radius and stator outer radius, for the REpower 3.2M114 wind turbine. This design and optimisation is not within the scope of this thesis. Table F.1 B-DFIG Design Number of Pole Pairs (PW & CW) Rated Electric Frequency (PW & CW) Rated Generator Speed Stator Outer Radius Stack Length Rotor Inner Radius Air-Gap Length Ratio Length-Diameter Ratio Slot height-Slot width Stator Yoke Width Stator Slot Width Table F.2 Hz rpm m m m mm mm mm 4&6 50 & 20 275 0.83 1.57 0.58 2.58 0.95 2.35 80 29.7 Winding Parameters Power winding slots/pole/phase Power winding number of turns per coil Power winding pole-pitch Power winding coil-pitch Control winding slots/pole/phase Control winding number of turns per coil Control windig pole-pitch Control winding coil-pitch 103 qp np ypp ypc qc nc ycp ycc 3 1 9 9 2 1 6 6 APPENDIX F. B-DFIG 3.2MW CASE STUDY MACHINE Table F.3 Electrical Circuit Parameters Power winding resistance Power winding main inductivity (main harmonic) Power winding leakage inductivity Control winding resistance Control winding main inductivity (main harmonic) Control winding leakage inductivity Rotor nest loop-1 resistance Rotor nest loop-2 resistance Rotor nest loop-3 resistance Rotor nest loop-4 resistance Rotor nest loop-1 (pp main harmonic) inductivity Rotor nest loop-1 (pc main harmonic) inductivity Rotor nest loop-2 (pp main harmonic) inductivity Rotor nest loop-2 (pc main harmonic) inductivity Rotor nest loop-3 (pp main harmonic) inductivity Rotor nest loop-3 (pc main harmonic) inductivity Rotor nest loop-4 (pp main harmonic) inductivity Rotor nest loop-4 (pc main harmonic) inductivity Rotor nest leakage inductivity Rp Lpm(p) Lpσ Rc Lcm(c) Lcσ Rr1 Rr2 Rr3 Rr4 Lrm(p)1 Lrm(c)1 Lrm(p)2 Lrm(c)2 Lrm(p)3 Lrm(c)3 Lrm(p)4 Lrm(c)4 Lrσ H mH H mH m m m m mH mH mH mH mH mH mH mH mH 0.0023 0.0073 0.1613 0.0021 0.0033 0.1613 0.1168 0.1108 0.1047 0.0986 0.4704 0.2482 0.3733 0.23 0.2397 0.1617 0.08259 0.0581 0.3865 0 −0.83 Figure F.1 Geometric Plot of the B-DFIG 3.2MW Case Study Machine 104 LVRT Performance of Brushless Doubly Fed Induction Machines U. Shipurkar, T. Strous, H. Polinder Abstract—The Brushless Doubly Fed Induction Machine (BDFIM) shows promise for use in wind turbine drivetrains. This paper discusses the performance of this machine under symmetric low voltage dips and compares this with the performance of two other machines - the Permanent Magnet Synchronous Machine (PMSM) and the Doubly-Fed Induction Generator (DFIG). Attention is paid to the controller for the B-DFIM and protection methods for improved Low Voltage Ride Through (LVRT) performance are discussed. Index Terms—Brushless Doubly-Fed Machine (BDFM), DFIG, Cross coupling, LVRT. dλ̄sc dt d λ¯r 0 = Rr i¯rr + r dt where, the flux linkages are given by, ūsc = Rc i¯sc + (1) λ¯sp = Lp i¯sp + Mpr i¯sr λ¯sc = Lc i¯sc − Mcr i¯sr λ¯r = Lr i¯r + Mpr i¯r − Mcr i¯r r r p c (2) (3) (4) These are transformed to a common arbitrary reference frame rotating with an angular velocity ‘ωk ’ with respect to the I. I NTRODUCTION Power Winding stator reference frame. This is given by, ITH growing interest in sustainable forms of energy, k the wind industry is growing rapidly. The DFIG is 0 −1 ¯k dλ̄p k k ūp = Rp īp + ωk λp + (5) a popular choice for the wind turbine drivetrain because it 1 0 dt is cost effective. However, it suffers from reliability and 0 −1 ¯k dλ̄kc maintenance issues due to the slip rings and brushes it ūkc = Rc īkc + (ωk − (pp + pc )ωm ) λc + 1 0 dt requires. The B-DFIM aims at addressing these drawbacks. (6) With increased wind power penetration, it is no longer k 0 −1 ¯k dλ̄r acceptable for wind turbines to trip during grid disturbances. 0 = Rr īkr + (ωk − pp ωm ) (7) λp + 1 0 dt Therefore, the study of the performance of wind turbine drivetains under low voltage events is important. There has The equations that form the dynamic model, rewritten in been little research on the LVRT performance of the B-DFIG. state-space form, are given by, Shao et al. studied the dynamic behaviour of the machine dλkp 0 −1 ¯k during symmetrical voltage dips [1]. However, this study was k k = ūp − Rp īp − ωk λp (8) 1 0 limited as it did not consider the subsequent voltage rise of dt the grid and it did not propose any methods to improve the dλkc 0 −1 ¯k = ūkc − Rc īkc − (ωk − (pp + pc )ωm ) λc performance. In 2011 they proposed a control scheme that 1 0 dt gives the B-DFIG the capability to ride through low voltage (9) faults [2] and this was extended for asymmetric low voltage k dλr 0 −1 ¯k faults [3]. = −Rr īkr − (ωk − pp ωm ) λr (10) 1 0 dt This paper develops a controller for the B-DFIM as part k k īp λ̄p Lp 0 Mpr of a wind turbine drivetrain. This controller is based on īkc = inv 0 Lc −Mcr λ̄kc (11) vector control and consists of cascaded current control loops Mpr −Mcr Lr λ̄kr īkr - one for the power winding current and the inner loop for the control winding current. The paper also investigates the The model is completed with the expression for electrical performance of the B-DFIM under symmetric low voltage power at the terminals of a stator winding. This is given by, events and compares this with the performance of PMSM and DFIG based drivetrains. ps = ūTs,abc īs,abc (12) Section II develops the dynamic model of the B-DFIG. Section III develops the controller for the B-DFIG which using the Clark’s transform, −1 −1 is based on vector control. Section IV discusses the LVRT ps =(Cαβ,abc ūs,αβ )T (Cαβ,abc īs,αβ ) (13) performance of the PMSM, the DFIG and the B-DFIG. s,α s,α s,β s,β ps =us is + us is (14) W II. B-DFIM DYNAMIC M ODEL A. B-DFIM Dynamic Equations The voltage equations for the B-DFIG, in vector form, are given by, ūsp = Rp i¯sp + dλ̄sp dt s =īsT s ūs (15) Using Equation 8, Equation 9 and Equation 15 the power may be expressed as, sT s sT 0 −1 s dθ ps =Rs īs īs + (Ls,σ + Ls,m )īs ī p 1 0 s dt 0 −1 s dθ + Msr īsT ī p (16) s 1 0 r dt It can be seen that the first term represents the resistance loss in the winding, the second term will be equal to zero and the remaining term represents the power converted into mechanical power. The torque is given by, pm = Te dθ dt (17) Therefore, the electromagnetic torque can be given by, sT 0 −1 s Te =pMsr īs ī (18) 1 0 r s,α s,α s,β =pMsr (is,β s ir − is ir ) (19) This expression is extended to form the torque expression for the B-DFIG by including both the stator windings. This is expressed as, s,α s,α s,β s,β s,α s,α s,β Te = pp Mpr (is,β p ir − ip ir ) + pc Mcr (ic ir − ic ir ) (20) From these equations the relation between the Power Winding and Control Winding currents is given by, 1 P W,d λ − Lc c 1 W,q = λP − Lc c W,d iP = c W,q iP c Mcr Lp P W,d Mcr i + |λp | Mpr Lc p Mpr Lc Mcr Lp P W,q i Mpr Lc p (31) (32) W,q W,q From Equation 32 it is seen that iP depends on iP c p P W,q P W,q P W,d P W,d and λc . λc is weakly dependant on ip and ic . This influence of d−axis terms on q−axis quantities and vice versa is termed ‘Cross-Coupling’. For accurate control it is required that the d and q axis terms be completely de-coupled such that the control of both parameters is independent of the other. This is done through the addition of a compensation term, shown in Equation 33. W,q W,q iP = f (iP , |λp |) + c p 1 P W,q λ L c | c {z } (33) Cross-Coupling Term If the Park’s transform is used, the equation in the stator reference frame may be converted to a rotating reference frame, W,q W,q It is also seen that iP varies with −iP . c p The power electronic converter can be controlled by the duty ratio for the switches which can be calculated from the k,d k,d k,q k,q k,d k,d k,q Te = pp Mpr (ik,q p ir − ip ir ) + pc Mcr (ic ir − ic ir ) reference Control Winding voltage and the DC bus voltage. (21) For the simulations here, the reference voltage uc is used as input to the machine. The dependence of uqc on iqc can be calculated from the Control Winding voltage equation in III. B-DFIM C ONTROL Equation 34. A. Active Power Control W,q dλP c W,q P W,q P W,d A reference frame rotating with the Power Winding flux uP = R i + (ω − (p + p )ω )λ + c P W p c m c c c dt is chosen and results in Equation 22 and Equation 23 for the (34) d and q components of Power Winding flux. A similar cross-coupling term, due to λP W,d , as seen in W,d λP =|λp | (22) Equation 33 is seen in the equation above.c This can also be p W,q λP =0 (23) expressed as in Equation 35. p This reference frame is referred to as the PW reference frame in the rest of this document. Here, if the assumption is made that Up is constant and Rp is small enough to be neglected, the flux |λp | will be constant. This gives, W,d P W,d W,q P W,q Rp (iP ip + iP ip )≈0 p p d|λp | ≈0 dt (24) W,q W,q W,q uP = f (iP , λP ) c c c Lp Mcr P W,d W,d i + Lc iP ) + (ωP W − (pp + pc )ωm )( c Mpr p | {z } Cross-Coupling Term (35) (25) The complete control scheme for Active Power control of the B-DFIG is shown in Figure 3. (26) B. Reactive Power Control Therefore, Pp simplifies to, W,q Pp ≈ ωk |λp |iP p Therefore, a reference power winding current signal can be generated from a reference Pp signal using Equation 27. W,q−ref iP p Ppref = ωk |λp | (27) For this machine, only the Control Winding circuit is controllable through the power electronic converter. Therefore, W,q the next step would be to obtain a reference iP current. c Consider the flux equations, PW PW PW λ¯p = Lp i¯p + Mpr i¯r PW PW PW λ¯c = Lc i¯c − Mcr i¯r PW PW PW PW λ¯r = Lr i¯r + Mpr i¯p − Mcr i¯c (28) (29) (30) The Reactive Power of the Power Winding for the B-DFIG in the arbitrary reference frame ‘k’ is given by, k,d k,d k,q Qp = uk,q p ip − up ip (36) Substituting Equation 8 and Equation 9 in Equation 36 gives, Qp = ik,d p dλk,q dλk,d p p k,d k,q + ωk ik,d λ − i p p p dt dt k,q +ωk ik,q p λp (37) Again, the PW reference frame is chosen (Equation 22 and Equation 23) and Up is assumed to be constant and Rp is neglected. The expression for Qp can be expressed as, W,d Qp ≈ ωP W |λdp |iP p (38) The reference power winding current signal can be generated from the reference Qp signal using Equation 39. Qref p ωP W |λp | Rated Power Generator Power W,d−ref iP = p Maximum Power Curve (Popt) (39) W,d W,d From Equation 31 it is seen that iP depends on iP c p P W,d P W,d P W,q P W,q and λc . λc is weakly dependant on ip and ic . Again there is a dq cross-coupling term which must be compensated for. This compensation term can be calculated as seen in Equation 40. 1 P W,d λ L c | c {z } (40) Cross-Coupling Term The dependence of on can be calculated from the Control Winding voltage equation. W,d uP c W,d iP c W,d W,d W,q uP = Rc iP − (ωP W − (pp + pc )ωm )λP c c c + W,d dλP c dt (41) W,q Again, we see a dq cross-coupling term due to λP . This c can be seen in Equation 42. W,d W,d W,d uP = f (iP , λP ) c c c Lp Mcr q W,q − (ωP W − (pp + pc )ωm )( i + Lc iP ) c Mpr P W,p | {z } Cross-Coupling Term The previous two sections discussed the control of the active and reactive power in a B-DFIM. When such a machine is used in a wind turbine drivetrain, the reference power signal is chosen so as to extract the maximum energy from the blades. Therefore, this section describes the generation of such a Ppref signal from the rotational angular velocity of the machine rotor. The aim of the control scheme is to maximise the power output of the wind turbine. A typical wind turbine characteristics with the optimal power extraction-speed curve and its intersection with the Cp,max for all wind speeds [4] is shown in Figure 1. As Popt is the curve with Cp,max it is evident that if the turbine is controlled and kept on this curve, the turbine will generate the maximum energy. This is followed for all speeds below rated. For speeds above rated, rated power Prated is maintained. This is described in Equation 43. Pref = or, Pref = ( The steady state characteristics are used to generate a function for the relation between ωm and Ppref . The characteristics depend on two variables, i.e. magnitude of the Control Winding voltage and the phase angle between Control Winding and Power Winding voltages. Therefore, given a value of ωm and P ref there are a number of operating points possible. To select an optimal operating point the efficiency of the machine is used as a selection criteria. Solving the system for maximum efficiency, the curve for the Power Winding Power corresponding to each point of the net power curve is shown in Figure 2. −0.5 Net Power Power Winding Power (42) C. Reference Signal Generation ( Fig. 1. Control Strategy for Optimal Power Extraction. The plot shows the generator output power vs. speed curve for different wind speeds. The Popt curve connects all the points of maximum power forming the curve for optimal power extraction. −1 Active Power (MW) W,d W,d iP = f (iP , |λp |) − c p Generator Speed −1.5 −2 −2.5 −3 −3.5 24 26 28 30 Prated if v < vrated if v ≥ vrated 3 1 ρAR Cp,max 3 ωm 2 λ3t,max if ωm < ωrated Prated if ωm ≥ ωrated 34 36 38 Fig. 2. Curve for net Shaft Power and Power Winding Active Power based on maximising Efficiency. idp Qref p − Ref. Gen. idc PI ipd−ref id−ref c − − PI ud,ref c + i¯c i¯p ωm dq Cross-Coupling Compensator Ref. Gen. iq−ref p − PI iqp 1 3 2 ρACp,max v 32 Rotor Speed (rad/s) q−ref + ic − PI q,ref − uc iqc (43) Fig. 3. B-DFIG Control Scheme (44) where λt,max is the tip speed ratio for Cp,max . Section III-A discusses the control of the machine, this control is based on the Active Power of the Power Winding alone. Therefore, it is required to generate the control signal (Ppref ) from the rotor speed (ωm ). IV. LVRT P ERFORMANCE The symmetric voltage dip considered here is shown in Figure 4. The details of the machines used in the simulations in the rest of the section are given in the Appendix. A. PMSM Performance The PMSM is completely isolated from the grid through an AC-DC-AC converter. Therefore, disturbances on the grid do 50 d−axis Current q−axis Current 40 1.0 V oltage (pu) Grid d−q Currents (kA) 30 20 10 0 −10 −20 −30 −40 −50 999 999.2 999.4 999.6 999.8 1000 Time (s) 1000.2 1000.4 1000.6 1000.8 1001 1000.2 1000.4 1000.6 1000.8 1001 (d) T ime (s) 0.25 1.9 1.8 Fig. 4. Voltage Profile for LVRT Response Study 0.8 1.5 1.4 1.3 1.2 1 0.9 999 999.2 999.4 999.6 999.8 1000 Time (s) (e) 9 9 7 7 5 5 3 3 1 1 0.6 Reactive Power (MVAr) Grid Voltage in Grid Reference Frame (pu) 1 1.6 1.1 Active Power (MW) not directly affect the machine. However, in the occurrence of an LVRT event, the ability of the grid side converter to transfer power to the grid is greatly reduced. This results in the rise in voltage of the DC link which is a cause for concern for the DC link capacitors. Figure 5 shows the response of the machine when it encounters a 95% symmetric voltage dip as shown in Figure 5a. DC−link Voltage (pu) 1.7 0.4 −1 999 999.2 999.4 999.6 999.8 1000 1000.2 1000.4 1000.6 1000.8 −1 1001 Time (s) 0.2 (f) 0 999 999.2 999.4 999.6 999.8 1000 1000.2 1000.4 1000.6 1000.8 1001 Fig. 5. LVRT Performance of PMSM for a 95% Symmetric Voltage Dip (a) Grid Voltage magnitude (b) Torque and Speed (c) Stator Currents in the Stator Flux reference frame (d) Grid Currents in the Grid Reference Frame (e) DC link voltage (f) Active and Reactive Power to the grid Time (s) 0 32 −50 31 −100 30 −150 29 −200 999 999.2 999.4 999.6 999.8 1000 1000.2 1000.4 1000.6 1000.8 Generator Speed (rad/s) Generator Torque (kNm) (a) events. Other methods include Power Balancing [6] which follows the generator side converter to follow the grid side converter during low voltage events. This reduces the power mismatch during such events and hence reduces the DC link voltage rise. 28 1001 Time (s) B. DFIG Performance (b) Unlike the PMSM, the DFIG is not isolated from the grid. The stator of the machine is connected directly to the grid and any disturbance in the form of a low voltage event can be expected to have an effect on the stator and rotor currents. The response of the DFIG is shown in Figure 6. It is seen that large transient currents are induced in the stator winding. Such transient currents are also induced in the rotor circuit due to the magnetic coupling of the stator and rotor circuits. These induced transient rotor currents are dangerous to the (c) power electronic converter connected to the circuit. Fig. 5. LVRT Performance of PMSM for a 95% Symmetric Voltage Dip A widely used method for the protection of the DFIG under (contd.) low voltage events is the Crowbar circuit [5]. The crowbar Figure 7a and Figure 7b show that there is little effect of circuit is a set of switches and resistors that short circuit the low voltage event on the machine. However, Figure 7d the rotor terminals through the resistors in the case of the low voltage event and by-pass the generator side converter. shows that the DC voltage rise is indeed an issue. A number of methods have been devised to address this The connection of the crowbar circuit serves a number of issue. One such method is the use of Energy Discharge purposes. First, it bypasses the power electronic converter Circuits [5]. This limits the rise of the DC link voltage by when large transient rotor currents are present. This protects using resistive elements to dissipate a part of the power the converter in the event of a Low Voltage event. Second, the fed to the DC circuit through the generator side converter. added resistance in the rotor circuit lowers the magnitude of Another method used is the use of Energy Storage Systems the transient rotor currents. Third, the added resistance in the [5] to manage and store the excess energy during low voltage crowbar circuit reduces the time constant of the rotor circuit 0.2 d−axis Current q−axis Current Generator d−q Currents (kA) 0 −0.2 −0.4 −0.6 −0.8 −1 −1.2 −1.4 −1.6 999 999.2 999.4 999.6 999.8 1000 Time (s) 1000.2 1000.4 1000.6 1000.8 1001 challenge. 1000 500 30 0 −500 999 1000 1001 1002 1003 Generator Speed (rad/s) Generator Torque (kNm) 32 28 1005 1004 C. B-DFIM Performance The B-DFIM suffers from the same issues faced by the DFIG under low voltage events. Figure 7 shows the performance of the B-DFIM under the condition of a 95% symmetric voltage dip. Time (s) (a) Generator Torque (kNm) 20 d−axis Current q−axis Current 15 Stator d−q Currents (kA) 10 5 0 −5 500 39 0 38 Generator Speed (rad/s) 1000 −10 −15 −500 999 −20 999.5 1000 1000.5 −30 999 1001 1001.5 1002 1002.5 37 1003 Time (s) (a) −25 1000 1001 1002 1003 1004 1005 Time (s) (b) 4 Power Winding d−q Currents (kA) d−axis Current q−axis Current 25 d−axis Current q−axis Current 20 Rotor d−q Currents (kA) 15 10 5 2 0 −2 −4 −6 0 −5 −8 999 999.5 1000 1000.5 1000 1001 1002 1003 1004 1002 1002.5 1003 1005 Time (s) 15 d−axis Current q−axis Current Control Winding d−q Currents (kA) (c) 1.8 1.7 1.6 DC−link Voltage (pu) 1001.5 (b) −15 −20 999 1001 Time (s) −10 1.5 1.4 10 5 0 −5 −10 −15 1.3 −20 999 1.2 999.5 1000 1000.5 1001 1001.5 1002 1002.5 1003 1001.5 1002 1002.5 1003 Time (s) (c) 1.1 1 999.5 1000 1000.5 1001 1001.5 1002 1002.5 1003 1.05 Time (s) 15 15 10 10 5 5 0 0 −5 −5 −10 −10 −15 999 1000 1001 1002 1003 1004 DC−link Voltage (pu) 1.04 Reactive Power (MVAr) Active Power (MW) (d) 1.03 1.02 1.01 1 0.99 0.98 999 999.5 1000 1000.5 1001 Time (s) (d) −15 1005 Time (s) 20 20 10 10 0 0 Fig. 6. LVRT Performance of DFIG for a 95% Symmetric Voltage Dip (a) Torque and Speed (b) Stator Currents in the Stator Flux reference frame (c) Rotor Currents in the Stator Flux reference frame (d) DC link voltage (e) Active and Reactive Power to the grid Active Power (MW) (e) −10 −10 −20 Lr Rr +Rcrowbar ), this means that the currents during the (τr = fault will decay faster. There are however a number of issues with the use of the crowbar circuit as well. First, when the crowbar circuit is activated, the DFIG resembles a induction motor with an external rotor resistance. This would mean that the machine would absorb reactive power from the grid which may further exasperate the condition of the grid. Second, the vector control is lost during the action of the crowbar circuit and re-establishing control after the crowbar is released is a 999 Reactive Power (MVAr) 0.9 999 −20 999.5 1000 1000.5 1001 1001.5 1002 1002.5 1003 Time (s) (e) Fig. 7. LVRT Performance of B-DFIM for a 95% Symmetric Voltage Dip (a) Torque and Speed (b) Power Winding Currents in the PW Reference Frame (c) Control Winding Currents in the PW Reference Frame (d) DC link voltage (e) Active and Reactive Power to the grid It can be seen that the magnitude of the transient currents is lower in the B-DFIM than that in the DFIG. This can be attributed to the larger leakage inductance of the B-DFIM. Also, it can be seen that the current induced in the control 15 Control Winding Phase Currents (kA) winding circuit has an additional circuit (power winding rotor - control winding) when compared to the DFIG (stator winding - rotor winding). Although the B-DFIM could also be protected against the effects of a low voltage event by the use of a Crowbar circuit, this machine can be protected without the use of an external circuit and with the use of an addition in the control algorithm. Figure 8 shows the performance of the B-DFIM with Crowbarless protection [7]. 10 5 0 −5 −10 −15 999.5 1000 1000.5 1001 1001.5 1002 1002.5 1003 Time (s) (a) 15 39 0 38 Control Winding Phase Currents (kA) 500 Generator Speed (rad/s) Generator Torque (kNm) 1000 10 5 0 −5 −10 −15 999.5 −500 999 999.5 1000 1000.5 1001 1001.5 1002 1002.5 37 1003 Time (s) Power Winding d−q Currents (kA) d−axis Current q−axis Current 2 −2 −4 −6 −8 1000.5 1001 1001.5 1002 1002.5 1003 Time (s) (b) 15 Control Winding d−q Currents (kA) d−axis Current q−axis Current 10 1002.5 1003 V. C ONCLUSIONS 0 −5 −10 −15 999.5 1000 1000.5 1001 1001.5 1002 1002.5 1003 1001.5 1002 1002.5 1003 Time (s) (c) 1.05 1.04 DC−link Voltage (pu) 1002 5 −20 999 1.03 1.02 1.01 1 0.99 0.98 999 999.5 1000 1000.5 1001 Time (s) (d) 10 0 0 −10 −20 999 Reactive Power (MVAr) 20 Active Power (MW) 1001.5 Time (s) Figure 9 shows the control winding phase currents both, without and with Crowbarless protection. Crowbarless protection is achieved by detecting a low voltage event and setting the reference values of the inner control winding current loops to zero. Section III-A and Section III-B has discussed the calculation of the id−ref and iq−ref reference signal depends on the p p d-axis power winding flux. Therefore, in the case of a low voltage event it is required to maintain pre-fault reference values. 0 1000 1001 Fig. 9. Control Winding Phase Currents (a) Without Protection (b) With Crowbarless Protection 4 999.5 1000.5 (b) (a) −10 999 1000 −20 999.5 1000 1000.5 1001 1001.5 1002 1002.5 1003 Time (s) (e) Fig. 8. LVRT Performance of B-DFIM with Crowbarless Protection for a 95% Symmetric Voltage Dip (a) Torque and Speed (b) Power Winding Currents in the PW Reference Frame (c) Control Winding Currents in the PW Reference Frame (d) DC link voltage (e) Active and Reactive Power to the grid For the PMSM based wind turbine, the issue with Low Voltage Ride Through (LVRT) is the rise in the DC link voltage . This is due to the mismatch in power generated by the machine and the power transferred to the grid. For the DFIG it has been found that voltage dips cause large transient currents in the stator and rotor circuit. The oscillations in the rotor circuit are cause for concern as they may lead to adverse effects on the power electronic converter connected to the circuit. A possible method to overcome this issue is the use of a Crowbar circuit. The crowbar circuit manages the problem by bypassing the power electronic converter in the event of current rise. Additionally, the crowbar resistors reduce the time constant of the rotor circuit, allowing for a faster decay of transient currents. In the case of the B-DFIG, it has been found that again transient currents are set up in the power and control windings in the event of a voltage dip. However, the magnitude of these currents is lower when compared to that in a DFIG. This is attributed to the higher leakage inductance of the B-DFIG. A Crowbarless method has also been discussed which is successful in controlling the high currents generated in the control winding. This Crowbarless control method also reduces the torque oscillations observed in the B-DFIG for a low voltage event. In conclusion, apart from offering better reliability through the exclusion of slip ring and brushes, the B-DFIG also has an improved LVRT performance when compared with the DFIG. The protection does not require an external circuit, like the crowbar, and can be built into the machine controller. R EFERENCES [1] S. Shao, E. Abdi, and R. McMahon, “Dynamic Analysis of the Brushless Doubly-Fed Induction Generator during Symmetrical ThreePhase Voltage Dips,” International Conference on Power Electronics and Drive Systems, pp. 464–469, 2009. [2] S. Shao, T. Long, E. Abdi, R. McMahon, and Y. Wu, “Symmetrical Low Voltage Ride-Through of the Brushless Doubly-Fed Induction Generator,” IEEE Industrial Electronics Society Conference, pp. 3209–3214, 2011. [3] T. Long, S. Shao, E. Abdi, R. a. McMahon, and S. Liu, “Asymmetrical Low-Voltage Ride Through of Brushless Doubly Fed Induction Generators for the Wind Power Generation,” IEEE Transactions on Energy Conversion, vol. 28, no. 3, pp. 502–511, Sep. 2013. [Online]. Available: http://ieeexplore.ieee.org/lpdocs/epic03/wrapper.htm?arnumber=6544266 [4] R. Pena, J. Dlare, and G. Asher, “Doubly fed induction generator uising back-to-back PWM converters and its application to variable- speed wind-energy generation,” IEE Proc.-Electr. Power Appl., vol. 143, no. 3, pp. 231–241, 1996. [5] C. Abbey, W. Li, L. Owatta, and G. Joos, “Power Electronic Converter Control Techniques for Improved Low Voltage Ride Through Performance in WTGs,” Power Electronics Specialists Conference, pp. 1–6, 2006. [6] X.-P. Yang, X.-F. Duan, F. Feng, and L.-L. Tian, “Low Voltage Ride-Through of Directly Driven Wind Turbine with Permanent Magnet Synchronous Generator,” 2009 Asia-Pacific Power and Energy Engineering Conference, pp. 1–5, Mar. 2009. [Online]. Available: http://ieeexplore.ieee.org/lpdocs/epic03/wrapper.htm?arnumber=4918470 [7] T. Long, S. Shao, P. Malliband, E. Abdi, and R. McMahon, “Crowbarless Fault Ride-Through of the Brushless Doubly Fed Induction Generator in a Wind Turbine Under Symmetrical Voltage Dips,” IEEE Transactions on Industrial Electronics, vol. 60, no. 7, pp. 2833–2841, 2013. VI. A PPENDIX TABLE I: PMSM Parameters Stator Resistance Stator Leakage Inductance Stator Main Inductance Rs Ls,σ Ls,m 3.25E-4 1.95E-5 8.105E-5 TABLE II: DFIG Parameters Stator Resistance Stator Leakage Inductance Stator Main Inductance Rotor Resistance Rotor Leakage Inductance Rotor Main Inductance Rs Ls,σ Ls,m Rr Lr,σ Lr,m 0.0011 4.95E-5 4.88E-4 9.11E-4 5.88E-5 4.86E-4 TABLE III: B-DFIM Parameters Power Winding Resistance Power Winding Inductance Control Winding Resistance Control Winding Inductance Rotor Loop - 1 Resistance Rotor Loop - 2 Resistance Rotor Loop - 3 Resistance Rotor Loop - 4 Resistance Rotor Loop - 1 Inductance Rotor Loop - 2 Inductance Rotor Loop - 3 Inductance Rotor Loop - 4 Inductance Rp Lp Rc Lc Rr1 Rr2 Rr3 Rr4 Lr1 Lr2 Lr3 Lr4 0.0023 3.5E-3 0.0021 1.74E-3 1.17E-4 1.11E-4 1.05E-4 0.99E-4 2.35E-4 1.84E-4 1.41E-4 1.02E-4