Branch Circuits
Advanced power protection at the service panel
Have you ever wanted complete surge elimination and power conditioning at
the branch circuit level, eliminating the need for additional protection
downstream? We have the solution.
Features:
The SurgeX Branch Circuit product line provides guaranteed surge elimination
and conditioning for audio, video, and mission critical equipment at the
service panel. Available in three configurations, our unique solutions are built
with professional-grade NEMA magnetic shielding steel enclosures that meet
code for use at the service entrance, sub-panels, and in-ceiling plenums.
• Impedance Tolerant® EMI/RFI filtering
• NEMA rated magnetic shielding steel enclosure
• Advanced Series Mode® surge elimination
• SurgeX ICE® (Inrush Current Elimination)
(SX-20NE-RT)
• Remote turn-on (SX-20NE-RT)
• Self-circuit with visual indicator (SX-20NE-RT)
They are engineered with Advanced Series Mode surge elimination and power
conditioning technologies to provide top-of-the-line protection. Superior to
conventional MOV circuitry or MOV-hybrid designs, they completely eliminate
surge energy up to 6,000 Volts without producing harmful side effects such as
ground contamination or common-mode disturbances. Completely
non-sacrificial and never needing reset, they provide the most reliable
protection available.
Our branch circuit line also features both common mode and normal mode
impedance tolerant EMI/RFI filtering, and SurgeX ICE (Inrush Current
Elimination) for a complete power conditioning solution.
Inside the PF-420
Model Number
Description
PF-420
Branch Circuit Surge Eliminator, multi circuit, 20A/120V
SX-20NE-RT
Branch Circuit Surge Eliminator with Remote Control, single circuit, 20A/120V
SX-20NE
Branch Circuit Surge Eliminator, single circuit, 20A/120V
Power Protection + Distribution
Branch Circuits
Technical Specifications
PF-420
SX-20NE-RT
SX-20NE
Load Rating:
20 Amps per circuit @ 120 Volts
(80 Amps total)
20 Amps @ 120 Volts
20 Amps @ 120 Volts
Power Requirement (no load)
15 watts per circuit
15 watts per circuit
15 watts per circuit
Surge Let- Through Voltage
(6000-volt surge)
0 Volts
0 Volts
0 Volts
UL 1449 Adjunct Classification
Test Results
1000 surges, 6000 Volts, 3000 Amps, B3
pulse; Measured suppressed voltage:
170 Volts; no failures.
1000 surges, 6000 Volts, 3000 Amps, B3
pulse; Measured suppressed voltage:
170 Volts; no failures.
1000 surges, 6000 Volts, 3000 Amps, B3
pulse; Measured suppressed voltage:
170 Volts; no failures.
Federal Guidelines
Grade A, Class 1, Mode 1 (CID A-A-55818)
Grade A, Class 1, Mode 1 (CID A-A-55818)
Grade A, Class 1, Mode 1 (CID A-A-55818)
EMI/RFI Filter, Normal Mode
(50-ohm load)
40 dB @ 100 kHz; 50 dB @ 300 kHz;
50 dB @ 3 MHz; 50 dB @ 30 MHz
40 dB @ 100 kHz; 50 dB @ 300 kHz;
50 dB @ 3 MHz; 50 dB @ 30 MHz
40 dB @ 100 kHz; 50 dB @ 300 kHz;
50 dB @ 3 MHz; 50 dB @ 30 MHz
EMI/RFI Filter, Common Mode
(50-ohm load)
18 dB @ 300 kHz; 30 dB @ 1 MHz;
50 dB @ 5 MHz; 50 dB @ 20 MHz
18 dB @ 300 kHz; 30 dB @ 1 MHz;
50 dB @ 5 MHz; 50 dB @ 20 MHz
18 dB @ 300 kHz; 30 dB @ 1 MHz;
50 dB @ 5 MHz; 50 dB @ 20 MHz
Maximum Applied Surge Voltage
6000 Volts*
6000 Volts*
6000 Volts*
Maximum Applied Surge Current
Unlimited, due to current limiting*
Unlimited, due to current limiting*
Unlimited, due to current limiting*
Maximum Applied Surge Energy
Unlimited, due to current limiting*
Unlimited, due to current limiting*
Unlimited, due to current limiting*
Endurance
(C62.41-1991 Category B3 pulses)
1 kV>500,000; 3 kV>10,000; 6 kV>1000
1 kV>500,000; 3 kV>10,000; 6 kV>1000
1 kV>500,000; 3 kV>10,000; 6 kV>1000
Maximum Load Inrush Current
During Power-up
N/A
1000 Joules
N/A
Remote Turn-on Applied
Voltage Range
N/A
5 to 30 Volts DC
N/A
Remote Turn-on Current Draw
N/A
Contact Closure: 3 mA
5 V DC Applied Voltage: 1 mA
12 V DC Applied Voltage: 2.5 mA
24 V DC Applied Voltage: 5 mA
N/A
Auxiliary Relay Contact Rating
N/A
30 Volts at 1 Amp
N/A
LED Output
12 volts DC, maximum 20 mA
(resistor required)
12 volts DC, maximum 20 mA
(resistor required)
12 volts DC, maximum 20 mA
(resistor required)
Dimensions
16.0" H x 12.0" W x 4.0" D
(40.6 x 30.5 x 10.2 cm)
12.0" H x 12.0" W x 4.0" D
(30.5 x 30.5 x 10.2 cm)
10.0" H x 8.0" W x 4.0" D
(25.4 x 20.3 x 10.1 cm)
Weight
30 lbs (13.6 kg)
12 lbs (5.45 kg)
9 lbs (4.0 kg)
Temperature Range
5º to 35º C
5º to 35º C
5º to 35º C
Humidity Range
5% to 95% R.H., non-condensing
5% to 95% R.H., non-condensing
5% to 95% R.H., non-condensing
Agency Listings
ETL and cETL (UL 1449, 2nd edition;
CSA C22.2 No.8-M1986, R2000)
ETL and cETL (UL 1449, 2nd edition;
CSA C22.2 No.8-M1986, R2000)
ETL and cETL (UL 1449, 2nd edition;
CSA C22.2 No.8-M1986, R2000)
*1.2 x 50 µs pulse, industry standard combination wave surge, as per IEEE C62.41
Agency Listings: ETL and cETL (UL 1449, 2nd edition; CSA C22.2 No.8-M1986, R2000)
Specifications subject to change without notice.
© 2013 SurgeX / Electronic Systems Protection, Inc.