National Electrical Code References 2002 NEC Cable Requirements UL Grounding Requirements The types of cables permitted by the 2002 NEC are indicated in Table 392.3 (A), Uses Permitted, Wiring Methods.They include: All Quick Tray Wire Mesh CableTrays are UL classified with regard to suitability for use as an Equipment Grounding Conductor (EGC). Compliance with other appropriate NEC cable articles is required.The Cable Tray Institute (CTI) recommends compliance with National Electrical Manufacturers, NEMA, Standards Publications Nos.VE1 and VE2, and with the manufacturer's recommendations. • Power and Control Tray Cable (Type TC) - NEC Article 340 • Power Limited Tray Cable (Type PLTC) - NEC Sections 725-61 and 725-71 • Instrument Tray Cable (Type ITC) - NEC Article 727 • Optical Fiber Cables - Article 770 • Fire Alarm Circuit Conductors - Article 760 • Communication Cables - Article 800 • Mineral Insulated (MI) Cable - Article 333 • Metal Clad (MC) Cable - Article 334 Other cables, particularly those specially approved for installation in cable trays, may also be permitted. Medium voltage (type MV) and single conductor cables in sizes 1/0 and larger are permitted, with some restrictions, in industrial establishments where qualified persons service the installation. All Quick Tray Wire Mesh CableTray systems must be grounded [392.7(A)]. This is true whether or not the tray is being used as an equipment ground.There are many ways to meet this requirement.The most effective method is to treat the tray as if it were an equipment ground, meaning that the whole system is continuously bonded. However, the general requirement only calls for each section to be grounded. In order to be used as an equipment ground, several requirements must be met [392.7(B)]. First, the system must be bonded: where two sections meet, the connection should be solidly connected by an approved means, that is, a bolted connection. Additionally, supervision must ensure that only qualified personnel service the cable tray system [392.3(C)]. Therefore, when using Quick Tray Wire Mesh CableTray as an equipment grounding conductor, maintain continuous grounding by using the tray in conjunction with "nut and bolt" and steel splices as shown below. 18 Data subject to change without notice ☎ 763 422 2211 • FAX 763 422 2600 • www.hoffmanonline.com © 2004 Hoffman Enclosures Inc. National Electrical Code References Additional Options for Grounding • Use a single conductor cable as the common EGC for all the circuits in the cable tray [NEC Section 392-3(b)(1) Exception 2]. • Use individual EGC conductors in each multiconductor cable in the cable tray (NEC Section 250-95). Walking on Cable Trays Walking on cable trays must not be permitted. It violates the new version of NEMA standard VE-2, manufacturers' marking and recommendations, and the intent of the NFPA 70 Electrical Safety in Employee Work Practices.Walking on electrical equipment, conduits, cables or other electrical systems should also be avoided. In addition to the fall hazard, there is the risk of damage to equipment and possible contact with conductors. High Voltage Cables High voltage cables can be installed in Quick Tray Wire Mesh CableTray. NEC permits type MC (Article 334) and type MV (Article 326) in industrial establishments where qualified persons will service the installation. Multiconductor cables rated over 600 volts must be separated from lower voltage cables by a separate cable tray or a solid fixed barrier.Type MC cables can be mixed with lower voltage cables. See NEC 392-6(f). National Electrical Code Uses Permitted Article 392.3A Cable Type Article Armored Cable 320 Communications Raceway 800 Electrical Metallic Tubing 358 Electrical Nonmetallic Tubing 362 Fire Alarm Cables 760 Flexible Metal Conduit 348 Flexible Metal Tubing 360 Instrumentation Tray Cable 727 Liquid-tight Flexible Metal Conduit 350 Liquid-tight Flexible Nonmetallic Conduit 350 Metal-clad Cable 330 Mineral-insulated, Metal-sheathed Cable 332 Multiconductor Service Entrance Cable 338 Multiconductor Underground Feeder and Branch Circuit Cable 340 Multipurpose and Communications Cables 800 Nonmetallic Sheathed Cable 334 Power and Control Tray Cable Power-limited Tray Cablesa 336 – Optical Fiber Cables 770 aSections 725-61 (c) and 721-71 (f). Instrumentation, Signal, and Telecommunications Cables Instrumentation, signal, and telecommunications cabling should be separated from power cabling, both to meet NEC requirements and to avoid noise and electromagnetic pickup from adjacent power cables.This can be accomplished by a separate cable tray system or by a divider within a cable tray.The requirements for cables that have an outer metal armor are less stringent than for plastic jacketed cables.The general rule is to separate communication, control, signal, and instrumentation cabling from power cabling. Power cabling includes 460 volt motor power, 120 volt power, and lighting circuits. Note that 120 volt circuits can generate noise. Generally, a separation of two inches (51mm) is minimum, but the individual circuit and cable are the determining factors in separation requirements. Data subject to change without notice ☎ 763 422 2211 • FAX 763 422 2600 • www.hoffmanonline.com © 2004 Hoffman Enclosures Inc 19