City of Hamilton Tender for the Construction of the New

advertisement
Julia Furii
Procurement Specialist
City of Hamilton
Corporate Services Department
Procurement Section
Phone: (905) 546-2424, ext.: 3988
Fax:
(905) 546-2327
E-Mail: Julia.furii@hamilton.ca
Date Issued: July 07, 2016
City of Hamilton
REQUEST FOR TENDERS
Contract Number: C13-40-16
Tender for the Construction of the New Bernie Morelli Recreation
Centre in the City of Hamilton
ADDENDUM 5
The following queries and responses, issued by the Procurement Section shall form part of
the Request for Tenders documents for the above, and the revisions and additions noted
herein and any attachments shall read in conjunction with all other documents. This
Addendum shall, however, take precedence over all previously issued Request for Tenders
documents where differences occur.
Addendum 5 contains: 7 pages of Addendum information
26 pages of PDF information
33 pages total
.0
2 pages, Addendum Summary
.1
Questions: 6 pages
.2
Architectural Addendum A- 04, dated July 7, 2016.(Attached) 12 total pages include:
.1 2 pages, Architectural Addendum Summary
.2 7 pages, Glass Guards and Railings Section 08 88 00
.3 3 pages, 3 sketches (ASK-14, ASK-15, ASK-16)
.3
Structural Addendum S-02, dated July 7, 2016.(Attached) 1 total page includes:
.1 1 page, Structural Addendum Summary
.4
Mechanical Addendum M-04, dated July 6, 2016.(Attached) 4 total pages include:
.1 2 pages, Mechanical Addendum Summary
.2 1 page, Re-heat Coil Schedule
.3 1 page, Custom Make Up Air Handling Unit Schedule
.5
Mechanical Addendum M-05, dated July 7, 2016.(Attached) 1 total pages include:
.1 1 pages, Mechanical Addendum Summary
C13-40-16 Addendum 5
Tender for the Construction of the New Bernie Morelli Recreation Centre in the City of Hamilton
Page 1 of 7
.6
Electrical Addendum E-03, dated July 6, 2016.(Attached) 8 total pages include:
.1 1 page, Electrical Addendum Summary
.2 7 pages, Luminaire Schedule
.1 Questions
PREVIOUS QUESTIONS
Response
RFIs received: June 30th, 2016
Question 4.15:
The polyethylene tubing for splash pad is 160 psi
or 1600 psi? Is pipe diameter/size IPS or DIPS?
Butt or socket fused? Pipe lengths in 10’ or 20’ or
40’ sticks, or coils? Most HDPE pipe these days
is the newer and improved 4710 resin, and I’m
not sure 3408 is manufactured in many sizes now
a days.
Response 1(as provided in Addendum 4):
Piping can be rated for 200psi. Pipe
diameter/size is DIPS. Contractor can use set
lengths or coils. Contractor is to follow 3408
resin piping. Contractor to use brass for
compression fitting as well as for other fittings
including but not limited to threaded tees, elbows
and reducing bushing
Response 2:
Piping shall be rated for minimum of 200psi. Pipe
diameter/size is IPS. Piping from headers to
splash pad nozzles shall be assumed as 1-1/2”.
Splash pad contractor shall detail and provide
required pipe sizes for splash pad in shop
drawings. Contractor can use set lengths or coils.
Contractor is to follow 3408 resin piping.
Contractor to use brass for compression fittings
as well as for other fittings including but not
limited to threaded tees, elbows and reducing
bushings.
RFIs received: July 5th, 2016
Question 4.18:
Please provide an exact location of the substrate
board to be adhered over the pool area – such as
from grid line ? - to grid line ?
Response 1:
Ceiling types indicated on A112. Ceiling types
are defined on A001. Vertical surfaces
assemblies are indicated on various sections.
Refer to A310-323
Question 4.19:
The “ through-wall flashing “ is mentioned in
section 076200 but doesn’t state any
material to be used. Please advise?
Response 1:
Refer to Section 04 05 23
Question 4.22:
Section 08 88 00: Glass Guards & Railings: Part
Response 1:
Refer to revised section 08 88 00 included within
C13-40-16 Addendum 5
Tender for the Construction of the New Bernie Morelli Recreation Centre in the City of Hamilton
Page 2 of 7
2 Products: Please specify Manufacturer & model
#’s for Glass Anchors required for Balustrade
glass as detailed on drawing 12/A500.
this addendum.
Question 4.23:
Please specify Manufacturer & models #’s for
glass standoff anchors for handrails as per
details 22/A501 & 23/A501, also please specify
Handrails as per same details.
Response 1:
Refer to revised section 08 88 00 included within
this addendum
Question 4.24:
Please specify channel cap & acceptable
Manufacturers, for laminated glass as per detail
14/A500.
Response 1:
Refer to revised section 08 88 00 included within
this addendum.
NEW QUESTIONS
Response
RFIs received: July 5th, 2016
Question 5.1:
On Drawing E-402 Ground floor lighting in Hall
126 & 125 the fixture shown is a type L1 fixture
that show to be 4feet long. The Lighting
schedule description for the type L1 says it is
supposed to be an 8 foot long fixture?
Response 1:
Light fixtures in Hall 125 &126 are to be type
L1B.
Question 5.2:
Are barriers required in all exterior lighting pole
that have 120V and low voltage wiring for
cameras and AV equipment?
Response 1:
4 rigid conduits shall be provided (One for power
to the light fixture, one for camera heater power,
one 27mm (1”) for security, and one 27mm (1”)
for AV) to the base of the light pole. Within the
pole, the rigid conduits for the power to the light
fixture and camera heater will transition to liquid
tight ACWU90 flex conduit (or approved
equivalent) and run throughout the pole. The flex
conduit and cable for the camera heater will run
to the pre-fabricated location of the security
camera and terminate within the weatherproof
box at the top of the pole. The security and AV
cables are to run in free air.
Refer to Detail 1 on drawing E002 and Detail 9
on drawing E003 for pole base details.
Refer to drawings E206 and E207 for conduit
requirements for AV equipment and security cctv,
respectively. Power for light fixture and camera
C13-40-16 Addendum 5
Tender for the Construction of the New Bernie Morelli Recreation Centre in the City of Hamilton
Page 3 of 7
to be in separate conduit as they are coming from
two different sources.
Question 5.3:
Where is Panel RP-1G located. Drawing E203
states that it is located in the main electrical room
but on the Layout of the main electrical room on
drawing E600 does not show panel RP-1G.
Response 1:
RP-1G is located in Janitor room #182. Refer to
drawing E302.
Question 5.4:
Panels LP-1C and RP-1D are not located on the
ground floor drawings. E203 notes that there are
supposed to be 2 electrical rooms located on the
ground floor, but only one room is shown. Also
the location of the of TX-1A shown on drawing E600 is shown different on drawing E203.
Response 1:
LP-1C and RP-1D are on drawing E203 located
in Storage Room #112 (North of the Gym). TX1A is located in Electrical Room #122; Detail 2
on drawing E600 shows correct location.
RFIs received: July 6th, 2016
Question 5.5:
Drawing M-401. Note on floor plan reference:
150 underground E/A pipe to pool gutter as per
detail ---. Mechanical detail drawings have been
reviewed and there is no detail provided for this
connection/termination. Please advise.
Response 1:
150dia. exhaust air connection to gutter is as per
detail #3 on M702.
Question 5.6:
Section 23 31 13.00 Lists Mechanical contractors
as acceptable sheet metal contractors. We
contacted most of those and are not participating
in the tendering process. Can we use other than
those listed for the sheet metal?
Response 1:
The list of Sheet Metal Contractors will be
deleted. Refer to Addendum M-02.
RFIs received: July 7th, 2016
Question 5.7
There are designations “R 0.5kW/700”. These
look like Radiant Heaters or Wall Fins. I don’t see
any such equipment on the Schedules. Can you
please clarify?
Response 1:
Type R is a wall fin. Enclosure shall be
Engineered Air type WF-2X or equivalent and be
indicated in addendum ADD-M-05.
Question 5.8
Please advise where the refrigeration system air
cooled fluid cooler shall be placed.
Response 1:
Fluid cooler FC-01 shall be in mechanical well as
per M403.
C13-40-16 Addendum 5
Tender for the Construction of the New Bernie Morelli Recreation Centre in the City of Hamilton
Page 4 of 7
Question 5.9
Where and how does the refrigeration air cooled
fluid cooler glycol supply & return piping run from
the ice plant room to the air cooled fluid cooler.
Response 1:
Piping is run on M401, M402 and M403 as
indicated as CDS and CDR form mechanical well
to basement refrigeration room.
Question 5.10
What is the total pipe distance between the
refrigeration system and the air cooled fluid
cooler?
Response 1:
Contractor must measure and estimate this
distance from documents.
Question 5.11
The vibration and noise control does not clearly
identify what is required for our 20,000lb
refrigeration package. What seismic restraints is
required for the refrigeration package.
Response 1:
Contractor to follow mechanical specification
section 23 05 49.00 Seismic Restraint Systems
and structural documents.
Question 5.12
The vibration and noise control does not clearly
identify what is required for the refrigeration fluid
cooler. What seismic restraints is required for the
air cooled fluid cooler.
Response 1:
Contractor to follow mechanical specification
section 23 05 49.00 Seismic Restraint Systems
and structural documents.
Question 5.13
Is 68 DBA for the refrigeration air cooled fluid
cooler acceptable?
Response 1:
Due to the timeliness of the question, we are
unable to provide a full and complete response.
The bidder should base their bid on the contract
documents.
Question 5.14
What seismic category shall this facility be
constructed for?
Response 1:
Contractor to follow mechanical specification
section 23 05 49.00 Seismic Restraint Systems
and structural documents.
Question 5.15
DWG M70 Make-up water level sensor and
pump shut-off water sensor TO BAS. Can you
please if the controls contractor is required to
supply these sensors? If so, are there to be two
separate sensorss or one ultrasonic? What is the
intent? Is BAS to monitor the tank level only?
Response 1:
Make-up water level sensors in surge tanks and
water circulation pump shut-off water sensor shall
be by pool contractor and are hard wired to pump
and makeup water solenoid. They are specified
in pool spec.
Question 5.16
Section 23 09 23
Item 3.22 RECIRCULATION POOL PUMPS
Item 3.22.2 “During a purge cycle, the VFD
speed shall be adjusted to match the filter purge
rate.” Can you please advise if an interface is
Response 1:
Filter backwash is completed manually using
valves.
C13-40-16 Addendum 5
Tender for the Construction of the New Bernie Morelli Recreation Centre in the City of Hamilton
Page 5 of 7
required between the BAS and the pool controller
to obtain the purge information? Would this be
accomplished through contacts or communication
protocol?
Question 5.17
Section 23 09 23
Item 3.24 REFRIGERATION PLANT
“install refrigeration contractor supplied software
to access information”?
Is the controls contractor required to install the
entire refrigeration plant DDC system including
setting up graphics, programming etc?
As per 23 30 30, this scope of work is to be
carried out by the refrigeration contractor, and
BAS is to have ability to connect to the
refrigeration plant control system through a
BACnet interface.
Please elaborate.
Response 1:
BAS must pick up all data and alarm points, show
in graphics and trend all points indicated going to
BAS in Refrigeration Spec. BAS contractor must
coordinate with refrigeration contractor.
Question 5.18
Section 23 09 23
Item 3.25 SPLASH PAD AND REFLECTING
POOL
What protocol is to be used for the interface
between BAS and the Refrigeration Plant
Controls?
Can you elaborate on “install splash pad/pool
contractor supplied software to access
information”? This is a pretty vague statement,
what is involved here?
Response 1:
BAS must pick up all data and alarm points, show
in graphics and trend all points indicated going to
BAS in Splash Pad and Reflecting Pool Spec.
BAS contractor must coordinate with Splash Pad
and Reflecting Pool contractor.
Question 5.19
Section 23 09 23
Item 3.26.7 “Provide LAN connection to the
unitary air conditioning unit”. Item 3.20 states to
ONLY monitor temperature in the AC conditioned
space. Which is to be considered? If LAN
connection is required, please indicate protocol to
be used and confirm it will be available on the AC
unit.
Response 1:
Provide alarms from unitary air conditioning units.
Question 5.20
Section 23 09 23
Item 3.26,8 “Provide a connection to the
sprinkler system remote monitoring device.”
Please elaborate.
Response 1:
Provide and trend status.
C13-40-16 Addendum 5
Tender for the Construction of the New Bernie Morelli Recreation Centre in the City of Hamilton
Page 6 of 7
Question 5.21
Section 23 09 23
Item 3.26.11.1 “Alarms shall not be tied through
BAS. Provide function that can email operator for
refrigerant leak and refrigerant plant failure.”
Please elaborate. Since this is specified in the
BAS section, is it still part of our scope?
Response 1:
BAS shall still collect alarms and graphically
show. A separate dedicated system has been
requested by the City of Hamilton to provide
these alarms directly to operator email. A
secondary system must be implemented.
END OF ADDENDUM 5
Bidders providing a signed Form of Tender have made any necessary inquiries with respect to addenda issued by the City
and have provided for all addenda in their Bid submission.
All Addenda will be posted on the City’s Biddingo.com bid portal at:
biddingo.com/hamilton
Procurement Section, City of Hamilton, Ontario
C13-40-16 Addendum 5
Tender for the Construction of the New Bernie Morelli Recreation Centre in the City of Hamilton
Page 7 of 7
Bernie Morelli Recreation Centre
MacLennan Jaunkalns Miller Architects
Project No. 1429
Architectural Addendum 04
A-04
Page 1
July 7, 2016
ARCHITECTURAL ADDENDUM A-04
1. ARCHITECTURAL SPECIFICATIONS
1. Section 08 88 00 Glass Guards and Railing
a) Add Section 2.2.5 - Handrail, stairs in public areas:
.1 Custom solid wood handrails
.2 Species: White Oak
.3Grade A
.4 Cut: plain sawn
.5 Finish: catalytic clear lacquer
b) Add Section 2.2.6 Standoff System:
.1 CRL ‘Standoff System’ 1-1/2” (38.1mm) diameter brushed 316 stainless steel 2” '
with ‘Flush Mount Cap Assembly’.
.2 Catalogue numbers: S0B1122BS, CAPF112BS, CAP38S.
c) Add Section 2.2.7 Handrail Brackets:
.1 Glass Mounted Handrail Bracket:
.1 CRL Brushed Stainless ‘Coastal Series Glass Mounted Hand Rail Bracket’
brushed 316 stainless steel.
.2 Catalogue number: HR2FGBS.
.2 Wall Mounted Handrail Bracket:
.1 CRL ‘Coastal Series Wall Mounted Hand Rail Bracket’ brushed 316 stainless
steel.
.2 Catalogue number: HR2FWBS.
.3 Post Mounted Handrail Bracket:
.1 CRL ‘Coastal Series Post Mounted Hand Rail Bracket’ brushed 316 stainless
steel.
.2 Catalogue number: HR2FPBS.
d) Add Section 2.2.8 Channel cap:
.1 CRL ‘Crisp Corner Low Profile 11 Gauge Cap Railing’ brushed 304 stainless steel.
.2 Catalogue number: GRLC20BS.
e) Revise subsequent subsection numbers based on new subsection numbers
indicated above.
f) See revised section 08 88 00 Glass Guard and Railing Section attached, Addendum
4, dated, July 7, 2016
2. Section 14 24 23 Hydraulic Passenger Elevators
a) Revise paragraph 2.8.18.3 Handrails on non-access sides:
.1 50mm (2”) flat bar
.1 38mm diameter stainless steel tube
2. ARCHITECTURAL DRAWINGS
Drawing A104– Roof Level Plan
.1) 1/A104 Roof Level
a) Revise location of roof ladder and section reference “3/A316”. Move ladder and
section reference east 4.1M to match location as shown on drawing A103. Drawing
not re-issued.
Drawing A111– Reflected Ceiling Plan Ground
.1) 1/A111 RCP Ground Floor
Bernie Morelli Recreation Centre
MacLennan Jaunkalns Miller Architects
Project No. 1429
Architectural Addendum 04
A-04
Page 2
July 7, 2016
a) Add section detail reference “7/A122” at ceiling access hatches in wood ceiling in
Multipurpose Room 1 RM106. Drawing not re-issued.
b) Add ceiling tag at gym RM120. Refer to ASK-16 attached.
Drawing A112– Reflected Ceiling Plan Second
.1) 1/A111 RCP Second Floor
a) Add section detail reference “7/A122” at ceiling access hatches in wood ceiling in
Hall RM200. Drawing not re-issued.
Drawing A120– Enlarged Ceiling Plans and Ceiling Details
.1) 1/A120 Enlarged Wood Ceiling Plan – Lobby
a) Add removable wd slat access panel and section detail reference “7/A122”. See
ASK-15 attached.
.2) 4/A120 Enlarged Wood Ceiling Plan – Cafeteria / Lounge / Multipurpose
a) Add section detail reference “7/A122” at removable wd. slat panels. Drawings not reissued.
Drawing A122– Ceiling Details
.1) 7/A122 Removable Access Hatch at Wood Ceiling
a) Add section detail for removable panel at wood ceiling. See ASK-14 attached.
Drawing A351– Interior Wall Sections
.1) 3/A351 Int. Wall Section – Universal Changeroom Entry
a) Revise section detail reference “1/A410”.
Delete “1/A410”. Replace with “7/A402” Drawing not re-issued.
.2) 2/A351 Int. Wall Section – at fireplace wall
a) Revise section detail reference “3/A121”.
Delete “3/A121”. Replace with “1A/A121 sim” Drawing not re-issued.
END OF A-04
Bernie Morelli Recreation Centre
City of Hamilton
Section 08 88 00
Page 1
July 7, 2016
Glass Guards and Railings
Section revised and reissued by Addendum No. 04
PART 1 - GENERAL
1.1
.1
Summary
Section includes:
.1
1.2
.1
Administrative Requirements
Conduct a pre-installation meeting in accordance with Section 01 31 19.
.1
1.3
Glass guards, railings and components.
Independent inspection and testing company shall attend the pre-installation
meeting.
Submittals
.1
Submit required submittals in accordance with Section 01 33 00.
.2
Product data sheets:
.1
.3
.4
Shop drawings:
.1
Submit engineered shop drawings.
.2
Submit shop drawings illustrating construction of glass guards and railings, glass
thicknesses, supports, methods of joining, details of field connections and
anchorage, layout showing locations of glass joints, interfacing with other parts of
the Work, fastening and sealing methods.
.3
Submit design calculations to support drawing details. Prepare calculations in a
clear and comprehensive manner so that they can be easily reviewed. Incomplete
or haphazard calculations will be rejected.
Samples:
.1
1.4
Submit manufacturer’s Product data sheets for Products proposed for use in the
work of this section.
Submit samples of glass, stainless steel, anchors, and railings, showing shapes
and finishes, glass edges, and as required.
Closeout Submittals
.1
Submit closeout submittals in accordance with Section 01 77 00.
.2
Operation and maintenance data:
.1
1.5
.1
Submit manufacturer’s maintenance instructions for incorporation into the
operation and maintenance manuals.
Quality Assurance
Qualifications:
Bernie Morelli Recreation Centre
City of Hamilton
Section 08 88 00
Page 2
July 7, 2016
Glass Guards and Railings
Section revised and reissued by Addendum No. 04
.1
.2
Installers / applicators / erectors: Provide the work of this section by a
Subcontractor who has adequate plant, equipment, and skilled workers to perform
the work expeditiously, and is known to have been responsible for satisfactory
installations similar to that specified during a period of at least the immediate past
5 years, who is completely familiar with referenced standards and requirements of
the work of this section, and with approval of Product manufacturers.
Mock-ups:
.1
Provide mock-up of railing installation, including minimum of 2 full size sections of
glass and railings. Locate mock-up where approved by Consultant.
PART 2 – PRODUCTS
2.1
Performance/Design Requirements
.1
Work of this section that functions to resist forces imposed by dead and live loads shall
conform to requirements of jurisdictional authorities and the building code.
.2
Design in accordance CAN/CGSB 12.20-M89. Make adequate provision for differential
thermal and structural movement of component parts of system and fastenings, to prevent
opening of joints, breakage of glass, undue stress on fastenings or other detrimental
effects.
.3
Design glazing to withstand metal railings loads as calculated in accordance with the
building code.
.4
Design of glass guards and railings and shop drawings for glass guards and railings shall
be carried out by a professional engineer licensed to practice engineering in the Place of
the Work experienced in this type of engineering, and in accordance with Section
01 33 00.
2.2
.1
.2
Materials
General:
.1
Unless detailed or specified otherwise, standard Products will be acceptable if
construction details and installation meet intent of the Contract Documents.
.2
Include materials, Products, accessories, and supplementary parts necessary to
complete assembly and installation of the work of this section.
.3
Incorporate only metals that are free from defects which impair strength or
durability, or which are visible. Install only new metals of best quality, and free from
rust or waves and buckles, and that are clean, straight, and with sharply defined
profiles.
Glass:
.1
Tempered to CAN/CGSB 12.1-M90, glazing quality, with clean cut edges, without
wings, convolutions, sharks teeth, serration hackle, flare, bevel and chips.
.1 Fabrication Process: By horizontal (roller-hearth) process with roll-wave
distortion parallel to bottom edge of glass as installed unless otherwise
indicated.
.2
Laminated glass:
Bernie Morelli Recreation Centre
City of Hamilton
Section 08 88 00
Page 3
July 7, 2016
Glass Guards and Railings
Section revised and reissued by Addendum No. 04
.1 Clear glass to requirements of CAN/CGSB 12.1-M90, 1.52 mm (0.060")
minimum thickness, PVB interlayer.
.2 Construction:
.1 Laminate glass with polyvinyl butyral interlayer to comply with interlayer
manufacturer's written recommendations.
.3 Interlayer thickness: Provide thickness not less than 1.52 mm (0.060") and as
needed to comply with requirements.
.4 Interlayer colour:
.1 Clear.
.5 Each glass layer minimum 10 mm thick.
.6 Glass type: annealed or heat strengthened or tempered, as required to suit
design requirements.
.7 Laminated glass products to be fabricated free of foreign substances and air
or glass pockets in autoclave with heat plus pressure.
.3
.3
Exposed edges of panels at vertical joints shall have slight arrises and be polished.
.4
Wherever balustrades finish with exposed glass at end, the face edge and arrises
shall be polished.
Glass clamps:
.1
.4
C.R. Laurence Co., Inc., ‘Z-Series Square Type Radius Surface Glass Clamps’
Heavy duty base shoe: Aluminum extrusions: Alloy 6063-T5 to ANSI H35.1/H35.1M-2013.
.1
C.R. Laurence Co., Inc. Base #B7S, 69 mm (2-3/4") x 103 mm (4-1/8") high
rectangular cross section.
.2
Base cladding finish:
.1 ANSI Type 304 stainless steel.
.1 No. 4 brushed finish.
.3
Fasteners for base shoe:
.1 For concrete: Hilti HSL3 expansion anchors 95 mm (3-3/4"), CRL Part #
EBA334.
.2 For steel: Stainless steel socket head cap screw 1/2-13 x 25 mm (1"), CRL Part
# SHCS12X1.
.5
.6
Handrail, stairs in public areas:
.1
Custom solid wood handrails.
.2
Species: White Oak.
.3
Grade: A.
.4
Cut: plain sawn.
.5
Finish: catalytic clear lacquer.
Standoff system:
Bernie Morelli Recreation Centre
City of Hamilton
Section 08 88 00
Page 4
July 7, 2016
Glass Guards and Railings
Section revised and reissued by Addendum No. 04
.7
.1
CRL ‘Standoff System’ 1-1/2” (38.1mm) diameter brushed 316 stainless steel 2” '
with ‘Flush Mount Cap Assembly’.
.2
Catalogue numbers: S0B1122BS, CAPF112BS, CAP38S.
Handrail brackets:
.1
Glass Mounted Handrail Bracket:
.1 CRL Brushed Stainless ‘Coastal Series Glass Mounted Hand Rail Bracket’
brushed 316 stainless steel.
.2 Catalogue number: HR2FGBS.
.2
Wall Mounted Handrail Bracket:
.1 CRL ‘Coastal Series Wall Mounted Hand Rail Bracket’ brushed 316 stainless
steel.
.2 Catalogue number: HR2FWBS.
.3
Post Mounted Handrail Bracket:
.1 CRL ‘Coastal Series Post Mounted Hand Rail Bracket’ brushed 316 stainless
steel.
.2 Catalogue number: HR2FPBS.
.8
Channel cap:
.1
CRL ‘Crisp Corner Low Profile 11 Gauge Cap Railing’ brushed 304 stainless steel.
.2
Catalogue number: GRLC20BS.
.5.9 Spacers and setting blocks: Neoprene to ASTM C542-05(2011), 70 to 90 Durometer
Shore 'A' hardness, of sizes required, exposed colour as selected by Consultant.
.6.10
Stainless steel:
.1
Material and finish: Type 304, AISI No. 4 finish.
.2
Stainless steel plate: ASTM A167-99(2009).
.3
Stainless steel bar stock: ASTM A276-15(2015).
.4
Stainless steel tubing: ASTM A269.
.7.11
Ferrous metals: Steel, structural shapes, plate, bars: hot-rolled, to meet specified
requirements of CSA G40.21-04, Grade 300W or acceptable alternative.
.8.12
Bolts, screws and fasteners: Non-magnetic, stainless steel, countersunk,
tamperproof.
.9.13
Dry glazed shoe system: Consists of high strength reinforced nylon tapered shims,
L-shaped pressure block, and roll-in gasket.
.1
.10.14
C.R. Laurence Co., Inc. ‘GRS Glass Railing Dry Glaze Taper-Loc System’.
Structural glazing adhesive; meeting the following:
.1
One-part, neutral-cure elastomeric sealant.
.2
ASTM C920-11, Type S, Grade NS, Class 50, Use NT, G and A.
.3
ASTM C1184-05.
Bernie Morelli Recreation Centre
City of Hamilton
Section 08 88 00
Page 5
July 7, 2016
Glass Guards and Railings
Section revised and reissued by Addendum No. 04
.4
SWRI Validation.
.5
Colour: as selected by Consultant from manufacturer’s full colour range.
.11.15
Sealant: One component, 100% silicone base glazing sealant, chemical cure,
conforming to CAN/CGSB 19.13-M87. Colour to later selection by Consultant.
.1
Acceptable manufacturers:
.1 Tremco.
.2 Dow Corning.
.3 Momentive.
.12.16
Dielectric separator: Non-staining alkali resistant, rubber isolation pads or 10 mil
vinyl membrane type, electrolytic isolation factor of 1.0.
2.3
Fabrication
.1
Fabricate glass guards and railings to types indicated or scheduled, and as specified
herein.
.2
Fabricate anchors and devices to be built into or attached to structure which are necessary
for adequate anchorage and attachment of the work of this section.
.3
Fabricate with materials, component sizes, metal gauges, reinforcing, anchors, and
fasteners of adequate strength to withstand intended use, and within allowable design
factors imposed by jurisdictional authorities. Fabricate items from stainless steel unless
otherwise noted.
.4
Ensure that glass guards and railings will remain free of warping, buckling, opening of
joints and seams, distortion, and permanent deformation to expansion and contraction
forces and loads.
.5
Accurately cut, machine and fit joints, corners, copes and mitres so that junctions between
components fit together tightly and in true planes.
.6
Fasten with concealed methods unless otherwise indicated.
.7
Continuous weld, grind welds smooth and flat where exposed to view and polish to match
metal finish.
.8
Allow for differential movements within assemblies and at junctions of assemblies with
surrounding work.
.9
Cleanly and smoothly finish exposed edges of materials including holes.
.10 Cap open ends of sections exposed to view.
.11 Glass to be pre-drilled to accept mechanical fastenings.
2.4
Welding
.1
Do welding work in accordance with CSA W59-15 unless specified otherwise.
.2
Weld structural components in steel, to conform to requirements of CSA W59-15, and by
a fabricator fully certified by the Canadian Welding Bureau to conditions of CSA W47.109(2014) and CSA W55.3-08 (R2013) as applicable.
Bernie Morelli Recreation Centre
City of Hamilton
Section 08 88 00
Page 6
July 7, 2016
Glass Guards and Railings
Section revised and reissued by Addendum No. 04
.3
Exposed welds shall be indiscernible from metals being welded. Fill welds, grind flat, and
polish to match welded metal finish.
.4
Touch up metal structural support finish as specified in metal structural support sections.
PART 3 - EXECUTION
3.1
.1
3.2
Examination
Inspect surfaces into which the work of this section is dependent for any irregularities
detrimental to installation and performance of the work of this section. Confirm conditions
satisfactory before proceeding.
Installation
.1
Erect members and component parts plumb, level and true to building lines, in correct
relation to the work of other sections and established lines, curves and levels indicated.
.2
Securely bolt steel framing to concrete by means of bolts and expansion anchors, shim
and pack to true straight lines and levels.
.3
Securely bolt heavy duty base shoe with anchors, shim to true straight lines and levels.
.4
Install components in accordance with reviewed shop drawings.
.5
Insulate between dissimilar metals or between metal, and masonry or concrete with
bituminous paint to prevent electrolytic action.
.6
Adhere prefinished sheet metal cladding to exposed shoe base sections with
manufacturer’s silicone sealant. Provide end caps where ends of shoe base sections are
exposed to view. Install sheet metal cladding in continuous lengths, longest lengths
possible available from manufacturer. Set to ensure installation is free of gaps and joints
are tightly fitted without gaps.
.7
Glass shall be in lengths shown, cut to shapes and conditions indicated and to provide
vertical joints. Set glass plumb and true to line with no variation in face plane between
sections of glass at joints.
.8
Coordinate railing anchorage with related work of other Subcontractors.
3.3
Installation – Tolerances
.1
Install plumb, level, tight and secured.
.2
Comply with the following maximum tolerances:
3.4
.1
Level and plumb: 3 mm in 3 m (1/8" in 10'-0").
.2
Variation from indicated position: plus/minus 3 mm (1/8").
Field Quality Control
.1
Conduct quality control in accordance with Section 01 45 00.
.2
Manufacturer’s field review to be in accordance with Section 01 45 00.
Bernie Morelli Recreation Centre
City of Hamilton
Section 08 88 00
Page 7
July 7, 2016
Glass Guards and Railings
Section revised and reissued by Addendum No. 04
3.5
.1
Adjusting and Cleaning
Clean and polish glass and metal surfaces after installation is complete. Use only
materials that won't scratch or mar finished surfaces and as approved by material
manufacturers.
END OF SECTION
Bernie Morelli Recreation Centre
Blackwell
Project No. 150046
Structural Addendum S02
SA S02
Page 1
7 July 2016
1. GENERAL
.1
Part 2 STRUCTURAL REVISIONS AND CLARIFICATIONS – 1 page.
.2
Structural Addendum No. S02, dated July 7, 2016, 1 page. Drawings not reissued.
2. STRUCTURAL REVISIONS AND CLARIFICATIONS
.1 Structural Drawings
Drawing S102 – GROUND FLOOR FRAMING PLAN
.1 Revise GD1 note to read “GD1 - 62 concrete on 38 composite metal deck
r/w 152x152 MW 18.7/18.7 WWF”.
Drawing S103 – 2ND FLOOR FRAMING PLAN
.1 Revise 2D2 note to read “2D2 - 62 concrete on 38 composite metal deck
r/w 152x152 MW 18.7/18.7 WWF”.
.2 Revise 2D3 note to read “2D3 - 62 concrete on 38 composite metal deck
r/w 152x152 MW 18.7/18.7 WWF & 4-20M each edge of track on each of
the 4 sides between grids 6-12 & A-F, typ. Refer to sections 2&3/S501 for
further information”.
.3 Revise deck designation for second floor deck south of grid P between
grids 6-8 (approx) to be 2D2.
Bernie Morelli Recreation Centre, Stadium Precinct, Hamilton
Smith + Andersen
Project No. 15331.000.M.000
Mechanical Addendum M-04
M-04
Page 1
July 6, 2016
MECHANICAL ADDENDUM M-04
1. Mechanical Specifications
23 82 19.00 – Fan Coil Units
1. Revise section 2.1.1 as follows;
2.1.1. Fan Coil Units: Daikin, York, Carrier, Engineered Air, Dunham-Bush,
Aeromec or Rittling.
2. Add section 2.2.9 as follows;
2.2.9. Units shall be low noise construction
23 74 13.16 – Roof Mounted Air Conditioning Units
1. Add section 2.4.3 as follows.
2.4.3 Control valve for hot water heating coils shall be provided by this section.
2. Mechanical Schedules
23 06 70.17 – Pool Dehumidification Unit Schedule
1. Revise air handling unit tag from AHU-11 to AHU-01.
23 06 80.29 – Reheat Coil Schedule
1. Revise reheat coil schedule page 5 as per attached.
23 06 70.16 – Roof Top Unit Schedule
1. Revise roof top unit schedule as per attached.
3. Mechanical Drawings
M403 – Second Floor HVAC
1. Revise Fluid cooler tag from CT-01 to FC-01.
2. Add reheat coil tag number as per below sketch.
Bernie Morelli Recreation Centre, Stadium Precinct, Hamilton
Smith + Andersen
Project No. 15331.000.M.000
Mechanical Addendum M-04
3. Add reheat coil tag number as per below sketch.
M601 – Mechanical Room Part Plans
1. Add heating coil tag RHC-B-01.
END OF ADD-M-04
M-04
Page 2
July 6, 2016
Bernie Morelli Recreation Center, Stadium Precinct, Hamilton
15288.000
EQUIPMENT NO.
RHC-02-15
RHC-02-16
RHC-02-17
RHC-B-01
Location
Pool Viewing
Corridor
Meeting Room
Pool Mech Room
Airflow Rate
cfm
L/s
2,862
1,351
278
131
153
72
In
In
ft²
fpm
mm
mm
m²
m/s
Entering Air Temperature (db)
°F
°C
55.0
12.8
55.0
12.8
55.0
12.8
Leaving Air Temperature (db)
°F
°C
71.9
22.2
63.7
17.6
90.0
In H2O
KPa
0.2
0.04
0.2
0.04
0.2
USgpm
L/min
Water
2.62
9.90
°F
°F
°C
°C
ft H2O
kPa
MBH
kW
1,200
566
--
-----
-----
-4.0
-20.0
--
32.2
60.0
15.6
--
0.04
0.2
0.04
--
Number of Coils
Width
Height
Area
Face velocity
-----
-----
-----
Type
Minimum Rows
Fins per inch
Series
AIR SIDE
Air Pressure Drop
FLUID SIDE
Fluid
Fluid Flow Rate
Entering Fluid Temperature
Leaving Fluid Temperature
Fluid Pressure Drop
MINIMUM CAPACITY
Total
Turbulators
Yes/No
REMARKS
Issued for Tender on 2016-06-14
160.0
120.0
71.1
48.9
Water
0.13
0.49
160.0
120.0
--
52.3
No
15.3
71.1
48.9
Water
0.29
1.10
160.0
120.0
--
2.6
No
0.8
71.1
48.9
Water
10.00
37.85
160.0
120.0
--
5.8
1.7
100.0
71.1
48.9
---
--
--
29.3
--
No
No
Electro-Fin coating
Electro-Fin coating
Re-Heat Coil Schedule
--
Page 5 of 5
Bernie Morelli Recreation Center, Stadium Precinct, Hamilton
EQUIPMENT NO.
LOCATION
SERVES
MODEL
RTU-01
RTU-02
RTU-03
RTU-04
MAU-R-01
Mechanical Well
Gymnaisum
Daikin
Mechanical Well
Multipurpose Space
Daikin
Mechanical Well
Changerooms
AAON
South Building
South Building
Daikin
Mechanical Well
Kitchen
AAON
SUPPLY FAN
External Static Pressure
RPM
Motor
cfm
In H2O
L/s
Pa
10,000
1.5
hp
kW
RETURN FAN
External Static Pressure
RPM
Motor
cfm
In H2O
Sound Data
2nd Band
3rd Band
4th Band
5th Band
4,720
373
25,000
1.5
10.0
11,800
373
2,500
2.0
7.46
25
18.64
L/s
Pa
10,000
1.0
4,720
249
25,000
1.0
11,800
249
hp
kW
3
2.24
9
Inlet
Outlet
1,420
75
71
68
65
MBH
MBH
°F
°F
°F
°F
kW
kW
°C
°C
°C
°C
407.6
279.9
79.3
66.5
53.7
53.0
HEATING
Entering Air Temperature (db)
Leaving Air Temperature (db)
Type (gas/elec/glycol)
Entering Glycol Temperature
Leaving Glycol Temperature
Glycol Flow Rate
Glycol Pressure Drop
MBH
°F
°F
kW
°C
°C
°F
°F
USgpm
ft H2O
°C
°C
L/min
kPa
311.0
91
43.0
6.1
71.4
21.9
40% Prop. Glycol
155.0
68.3
115.0
46.1
17.3
65
1.6
5
FILTERS
Pre-Filter
Final Filter
MERV #
MERV #
INCHES
INCHES
lbs/hr
kg/hr
°F
°C
2
12
32.20
35.0
842.3
642.2
77.3
64.7
53.8
53.4
hp
kW
26
4
3,000
1.5
1,416
373
---
---
2.24
--
--
548.1
161
55.4
13.0
75.5
24.2
40% Prop. Glycol
155.0
68.3
115.0
46.1
30.5
115
1.0
3
2
12
145.0
3
87
89
86
79
68
78
80
69
152.0
86.8
88.0
74.0
54.8
54.6
45
25
31.1
23.3
12.7
12.6
192.0
56
-2.2
-19.0
59.5
15.3
40% Prop. Glycol
155.0
68.3
115.0
46.1
10.5
40
9.5
28
8
14
2
12
65.91
95.0
35.0
6
19.24
1,453
72
2.98
82
78
79
74
85
81
84
80
ERV-RTU-03
247
188
25.2
18.2
12.1
11.9
8
14
2,360
373
6,350
2,997
0.8
187
1,760
5
3.73
1,730
84
79
77
76
4
ELECTRICAL
Volts/Phase/Cycle
Maximum Circuit Ampacity
REMARKS
119
82
26.3
19.2
12.1
11.7
95.0
2.24
6.56
N/A
COOLING (total)
Sensible Capacity
Entering Air Temperature (db)
Entering Air Temperature (wb)
Leaving Air Temperature (db)
Leaving Air Temperature (wb)
CONDENSER
Ambient Air Temperature (db)
No. of Compressers
Compressor Motor (total)
3
2,013
81
76
74
73
N/A
70.8
5,000
1.5
649
71
68
63
60
8
14
1,180
497
857
476
Energy Recovery Wheel
HUMIDIFICATION (integral)
15288.000
N/A
142.0
118.0
76.3
64.0
54.7
54.5
42
35
24.6
17.8
12.6
12.5
78.1
23
70.0
21.1
84.3
29.1
40% Prop Glycol
155.0
68.3
115.0
46.1
4.3
16
1.7
5
8
35.0
2
--
95.0
2
53.84
88
92
86
77
N/A
--
95.0
83
84
75
71
------608.0
178
-4.0
-20.0
74.0
23.3
40% Prop Glycol
155.0
68.3
115.0
46.1
67.0
254
6.6
20
8
--
--
35.0
--
7.90
--
2
--
11
600/3/60
70.4
600/3/60
140.6
600/3/60
28
600/3/60
17.9
600/3/60
8
9687 lb
Comes with MHGRH
VFDs & Harmonic Filters
15729 lb
2466 lbs
Custom Unit
120/1/60 circuit for lights
2637 lbs
R/A balanced to 944cfm
Heat Pump Operation
1300 lbs
Issued for ADD-M-04 on 2016-07-06
VFDs & Harmonic Filters
2
--
Custom Make Up Air Handling Unit Schedule
Page 1 of 1
Bernie Morelli Recreation Centre, Stadium Precinct, Hamilton
Smith + Andersen
Project No. 15331.000.M.000
Mechanical Addendum M-05
M-05
Page 1
July 7, 2016
MECHANICAL ADDENDUM M-05
1. Mechanical Specifications
23 82 36.00 – Wall Fin Convectors
1. Add section 2.1.5 as follows;
2.1.5. Enclosures for type R wall fins shall be engineered air type WF-2X or
equivalent, unless specified in trench with grille above as per detail 4 on
M6.02.
END OF ADD-M-05
Bernie Morelli Recreation Center
Hamilton, Ontario
Project No. 15288.000.E.001
ED-03
Page 1
July 6, 2016
Electrical Addendum E-03
ELECTRICAL ADDENDUM E-03
1. Electrical Specifications
1. LUMINAIRE SCHEDULE
1.
Revise light fixture type L1A, as highlighted.
2.
Revise light fixture type L1B, as highlighted.
2. Electrical Drawings
Drawing E002 – Electrical Details (not attached)
.1 Detail 1 – Pole Concrete Base Detail – Type L15B
a) Add note N-13 to read, “Where security and/or AV equipment will be
mounted to the light pole, the rigid PVC conduits for the power to the light
fixture and camera heater will transition to liquid tight ACWU90 flex conduit,
or approved equivalent, and run throughout the light pole, as to provide a
barrier. The flex conduit and cable for the camera heater will run to the prefabricated location of the security camera and terminate within the
weatherproof box at the top of the pole; refer to detail 8/E003. The security
and AV cables are to run in free air.”
Drawing E003 – Electrical Details (not attached)
.1 Detail 9 – Pole Base Detail – Type L13, L13A, L15, AND L15A
a) Add note N-12 to read, “Where security and/or AV equipment will be
mounted to the light pole, the rigid PVC conduits for the power to the light
fixture and camera heater will transition to liquid tight ACWU90 flex conduit,
or approved equivalent, and run throughout the light pole, as to provide a
barrier. The flex conduit and cable for the camera heater will run to the prefabricated location of the security camera and terminate within the
weatherproof box at the top of the pole; refer to detail 8/E003. The security
and AV cables are to run in free air.”
Drawing E203 – Rise Diagrams (not attached)
.1 Detail 1 – Power Riser Diagram
b) Relocate Panel RP-1G from Main Electrical Room to Janitor Room #182.
c) Relocate Panel RP-1F from Ground Floor Elec Room (Near Gym) to Ground
Floor Kitchen.
d) Relocate TX-1A from Ground Floor Elec Room (Near Gym) to Ground Floor
Elec Room (Near Pool).
e) For clarification, revise “Ground Floor Elec Room (Near Gym)” label to
“Ground Floor Elec Room (Storage Room #112).
Drawing E402 – GROUND FLOOR LIGHTING (not attached)
a) Revise light fixture type to L1B in Hall 125 & 126.
END OF ED-03
LUMINAIRE SCHEDULE
Project Name: BERNIE MORELLI RECREATION CENTRE
Project number: 15288.000.E001
TYPE VOLT.
LAMP(S)
DIMENSIONS
DESCRIPTION
MANUFACTURER/ CATALOGUE NUMBER
MINIMUM
PERFORMANCE
REQUIRED
LOCATED
LED
L1
120V
96W LED
(3500K)
95mmW x 102mmH
x2440mm L
(3.7"x4"x96")
Pendant mounted linear flangless stem mounted LED.
Polycarbonate protective LED frosted lens in a rigid extruded
aluminum housing. High performance internal reflector. Black
finish, stem mounted. Coordinate stem drop with architectural
sections. Complete with 0-10V dimming driver.
• Metalumen: Grande RM4D-1L35K-8-M-C
(Black)-L4-1-PA-120
120V
48W LED
(3500K)
95mmW x 102mmH x Pendant cement board mounted linear flangless LED. Rigid
• Metalumen: Grande RM4D Series
1220mmL
extruded aluminum housing c/w frosted acrylic lens. High
(3.7"x4"x48")
(Refer to specification section 26 51 13.00,
performance internal reflector. Black finish, stem mounted.
Coordinate stem drop with architectural sections. Complete with 0- clause 1.6)
10V dimming driver.
L1B
120V
14W LED
(3500K)
95mmW x 102mmH x Recessed linear LED. Polycarbonate protective LED frosted lens
1220mmL
in a rigid extruded aluminum housing. High performance internal
(3.7"x4"x48")
reflector. Black finish. Complete with 0-10V dimming driver.
Reserved
Recessed in drywall flangless LED. Rigid extruded aluminum
housing c/w frosted acrylic lens. High performance internal
reflector. Final finishing to be confirmed by Architect during shop
drawing review.
120V
28W LED
(3500K)
95mmW x 102mmH
x2440mm L
(3.7"x4"x96")
L2
120V
48W LED per
1200mm
(3500K)
95mmW x 102mmHx
length as per
drawings
(3.8"x
4.2"x
length as per
drawings)
L3
120V
14W LED
(3500K)
95mmW x 102mmH x Recessed in soffit linear LED. Rigid extruded aluminum housing c/w
1220mmL
frosted acrylic lens. High performance internal reflector. Black finish.
(3.7"x4"x48")
Minimum CSA listed for damp locations. Suitable for installation in
Gymnasium- wood ceiling
5500 Lumens per
1200mm
Gymnasium- 1st level
(Refer to specification section 26 51 13.00,
clause 1.6)
L1A
L1C
L1D
5500 Lumens per
1200mm
• Metalumen:Grande RM4D Series
• Mark Architectural Lighting: S4LD 4FT
WRD Series
• NEORAY: S23-D-P Series
• Architectural Lighting Works: Lightplane
LP3.5SD Series
1500 Lumens per 1200 Lobby/ Lounge wood ceiling
mm
• Metalumen:Grande RM4D Series
• Mark Architectural Lighting: SL4L Series
• NEORAY: S123-DR Series
1500 Lumens per 1200 Washrooms- above sinks
mm
Wall Mount LED. Polycarbonate protective LED frosted lens in an • Metalumen: Grande RM4DOD Series
aluminum housing, white finish with corrosion resistant finish, stem
(Refer to specification section 26 51 13.00,
mounted. Complete with dimming driver. Suitable for wet
clause 1.6)
locations. Natatorium finish.
5500 Lumens per
1200mm
Pool
• Metalumen: Grande RM4DOD Series
• NEORAY: S123 Series
1500 Lumens per 1200 Soffit
mm
• Metalumen:Grande RM4D Series
• Architectural Lighting Works: LP3.5R
series
• Mark Architectural Lighting: Slot 2 Series
1500 Lumens per 1200 Second level- Stone Wall
mm
accent
insulated ceilings. Suitable for cold weather.
L4
120V
140W LED
(3500K)
95mmWx 102mmH x Wall mounted, recessed in drywall LED. Rigid extruded
12200mmL
aluminum housing c/w frosted acrylic lens. High performance
(3.7"x4"x480")
internal asymmetric reflector. Final finishing to be confirmed by
Architect during shop drawing review.
See drawing E003, detail 7 for more details.
Page 1
7/6/2016
LUMINAIRE SCHEDULE
Project Name: BERNIE MORELLI RECREATION CENTRE
Project number: 15288.000.E001
L5
120V
20W LED per
head (3500K)
40 degree beam
230mm W x 175mm
H x 600mm L
(9"x6.75"x24")
Recessed twin-multi-head LED. Cold rolled steel housing with
solid alumnium adjustable and lockable double gimbals. Gimbal
adjustment does not require the use of tools. Extruded aluminum
heat sinks. Gimbals are adjustable 40 degrees in both directions
along the length of the housing and 35 degrees along width of the
housing. White trim, black gimbal finish, black housing interior.
Final finishing to be confirmed by architect during shop drawing
review.
0-10V driver.
• 3G Lighting- RC2LED series
• Juno Lighting: Multi-Spot LED MSSR302
Series
• RSA: Combolight Gen 3 Recessed Series
• Senso: LETO 1 double Series
• Juno Lighting: MSSR302 Series
2000 Lumens per head Second Floor Hallway- wood
ceiling
L6
120V
LED 3500K
35W
150mmW x 160mmH Recessed TechStyle Ceiling Linear LED Luminaire. Extruded
1220mmL
aluminum housing with white powder coated sheet steel. Frosted
(5.75"x6.25"x48")
acrylic snap-in lens with micro lens. C/w special clips to be
compatible with Hunter Douglas TechStyle Ceiling (imperial).
0-10V driver.
• Gammalux: G-Beam Series
• Williams: LL6 Series
• Mark Architectural Lighting: Slot 5 LED
Series
• Neo-Ray: Define 5 LED Series
• Architectural Lighting Works: Lightplane 5
LP5R Series
• Metalumen: Grande RM6D Series
908 lumens per 300mm Multi-purpose rooms
L6A
120V
LED 3500K
35W
150mmW x 160mmH Recessed TechStyle Ceiling Linear LED Luminaire. Extruded
1220mmL
aluminum housing with white powder coated sheet steel. Frosted
(5.75"x6.25"x48")
acrylic snap-in lens with micro lens. C/w special clips to be
compatible with Hunter Douglas TechStyle Ceiling (imperial).
Suitable for damp locations.
0-10V driver.
• Gammalux: G-Beam Series
• Williams: LL6 Series
• Mark Architectural Lighting: Slot 5 LED
Series
• Neo-Ray: Define 5 LED Series
• Architectural Lighting Works: Lightplane 5
LP5R Series
908 lumens per 300mm Change Rooms
Not Used.
Recessed round LED Open Down light. Self-flanged, spun
0.050" thick aluminum lower reflector with galvanized steel
construction hosuing. Universal mounting bracket, adjusts 5"
vertically from above and below ceiling. Light engine and driver
accessible through aperture. Polygcarbonate lens integral to light
engine with specular Clear finish.
• Gotham: 6" Evo Downlight Series
• Portfolio: LD6A15 6LM Series
•GE Lighting: DI6R Series
•Senso: LETO 13 Series
• Clarus: 6LE-XL2-2000 Series
1400 Lumens
Lobby, Vestibule, Meeting
Rooms, Multipurpose Room,
Lounge, Billiard, Washrooms,
Open office
Recessed round LED Lensed shower down light. Self-flanged,
spun 0.050" thick aluminum lower reflector. Universal mounting
bracket, adjusts 4" vertically from above and below ceiling.
Suitable for Wet locations with covered ceiling. IP66 rated. White
painted flange.
• Gotham: 6" Evo Downlight Series
• Portfolio: LD6A15 6LM Series (specify
LGSKT6IP66 option)
• Clarus: 6LE-XL2-2000 Series (specify
diffuser lens and WL for wet location)
1400 Lumens
Change Rooms Showers
• Gotham: 6" Evo Downlight Series
• Portfolio: LD6A30 6LW Series
• Clarus: 6LE-XL2-3000 Series
3000 Lumens
Second level gym
L7
L8
120V
25W LED
(3500K)
80 CRI
medium beam
160mm aperature x
200mm H
(6-1/4"x7-9/16")
L8A
120V
25W LED
3500K
83 CRI
160mm aperature x
200mm H
(6-1/4"x7-9/16")
L8B
L8C
L8D
120V
LED 3000K
70º beam angle
85 CRI
160mm aperature x
200mm H
(6-1/4"x7-9/16")
Not Used.
Not Used.
Recessed round LED Open Down light. Self-flanged, spun
0.050" thick aluminum lower reflector with galvanized steel
construction hosuing. Universal mounting bracket, adjusts 5"
vertically from above and below ceiling. Light engine and driver
accessible through aperture. Polygcarbonate lens integral to light
engine with specular Clear finish.
Page 2
7/6/2016
LUMINAIRE SCHEDULE
Project Name: BERNIE MORELLI RECREATION CENTRE
Project number: 15288.000.E001
L9
120V
50W LED
(3500K)
610mmWx 100mmD Recessed static troffer with lens. Die formed one piece
x1220mmL
housing. Multi stage phosphate treated for maximum corrosion
(24"x4.5"x48")
resistance and finish coat is high reflectance baked white enamel.
Mechanically designed interlocks eliminate light leaks. Flat steel
door frame features smooth rolled edges and mitered corners c/w
gasketing. Inverted K12 lens (flat part to the bottom)
L10
120V
42W LED
(3500K)
80 CRI
90mmW x 100mmH
x1220mmL
(3-3/8"x3-1/4"x48")
• Lithonia: 2GTL Series
• PACO: PRCL Series
• Metalux: 24GR LED Series
Pendant Mount Lensed LED Striplight (Chain-hung). Die formed • Lithonia: ZL2N Series
• Bartco: BLT210 Series
cold rolled steel channel with numerous KOs for ease of
installation. Channel / wireway secured with sheet metal screw.
White reflector. Medium Diffuse lens. Long-life LED system with
electronic driver.
4700 lumens
Food services
3000 Lumens
Mechanical Rooms, Storage,
Janitor, Elevator machine
Room,
7000 Lumens
Stairs
Exterior- Wall mount
Lights shall be suspended below any mechanical ducts or pipes.
L11
120V
70W LED
(3500K)
80 CRI
80mmW x 80mmH x Pendant (chain hung) or Surface Mount lensed Strip LED.
• Lithonia: ZL1N Series
1220mmL
• Metalux: SWLED Series
Compact-design channel and cover are formed from code-gauge
(3"x3"x48")
cold-rolled steel. High-gloss, baked white enamel finish. Five-stage
iron phosphate pre-treatment ensures superior paint adhesion and
rust resistance. Snap on frosted diffuse lens.
Provide minimum 3m of chains. Exact length of chains to be
adjusted on site.
L12
120V
20W LED
3500K
150mmW x 175mmH Architectural LED Wall Pack. Low-profile, rugged die-cast
x 100mmD
aluminum construction, universal back box, stainless steel
(5-3/4"x6-3/4"x3-5/8") hardware with a sealed and gasketed optical compartment.
Impact resistant tempered glass lens. IESNA full cut-off
compliance. Wet location listed. Suitable for cold
environments.
Final colour finishing to be confirmed by architect during shop
drawing review.
• Lumark: XTOR Series
• Lithonia: OLWX1 LED Series
• WAC Lighting: WP-LED1 Series
•RAB Design: GWL2-LED30 Series
1400 lumens
L13
120V
100W LED per
head 4000K
5 heads
40 degree beam
13-3/8" apperture
various mounting
heights
•Lumenpulse: Lumenbeam Grande Series
•Martini Lighting - LUX 400 LED Series
5077 lumens per head Exterior skating pond/ splash
pad landscape islands
Refer to detail
4/E003 for fixture
configurations
Exterior LED Floodlight. High pressure die-cast aluminum
housing, silicone sealed, clear tempered glass, polyester powder
coat finish, corrosion resistant coating adjustable heads. IP66
Rated. Five heads mounted per pole. Wet location listed.
Suitable for cold environments.
24' round, galvanized steel, non-tapered, base-mounted pole.
Light fixtures to be mounted at different heights and aimed at
different angles. Refer to drawings for more details. Pole head
and finish to be confirmed by architects.
Page 3
7/6/2016
LUMINAIRE SCHEDULE
Project Name: BERNIE MORELLI RECREATION CENTRE
Project number: 15288.000.E001
L13A
120V
100W LED per
head
3500K
13-3/8" apperture
various mounting
heights
Refer to detail
5/E003 for fixture
configurations
L14
L15
208V
100W LED
3500K
1 head
127mm W x 400mm
H x 950mm L (each
head)
6m (20ft) pole
Exterior LED Floodlight. High pressure die-cast aluminum
housing, silicone sealed, clear tempered glass, polyester powder
coat finish, corrosion resistant coating adjustable heads. IP66
Rated. Three heads mounted per pole.
•Lumenpulse: Lumenbeam Grande
•Martini Lighting- LUX 400 LED Series
5077 lumens per head Exterior landscape islands
•Architectural Area Lighting: Kick- K51
medium Scale series
•Philips Gardco P21 Pureform Series
8154 lumens
Splash pad/ skating rink
perimeter
8154 lumens per head
Pedestrian Pathway
15' round, galvanized steel, non-tapered, base-mounted pole.
Light fixtures to be mounted at different heights and aimed at
different angles. Refer to drawings for more details. Pole head
and finish to be confirmed by architects.
Reserved
Aluminum housing with corrosion resistant finish and clear opitcal
molded acrylic lenses. IP 66 rated. Type III distribution.
Integral galvanized steel pole to be 6m high, round tapered, 4"
round at the top of the pole with a 0.13" tapered galvanized steel
shaft, internally dampened to eliminate second mode vibrations.
CSA certified. Powdercoated painted (colour to be selected by
Architect during shop drawing review). Galvanizing standards to
ISO 1461. Wet location listed. Suitable for cold environments.
Speakers (80lbs) to be mounted to pole where indicated on
drawing. Refer to Audiovisual drawings for mounting heights.
L15A
208V
200W LED per
head
3500K
2 heads, 180
degrees apart
127mm W x 400mm
H x 950mm L (each
head)
4.6m (14ft) pole
Aluminum housing with corrosion resistant finish and clear opitcal •Architectural Area Lighting: Kick- K52
medium Scale series
molded acrylic lenses. IP 66 rated. Type III distribution.
•Philips Gardco P21 Pureform Series
Integral galvanized steel pole to be 3.7m high, round tapered, 4"
round at the top of the pole with a 0.13" tapered galvanized steel
shaft, internally dampened to eliminate second mode vibrations.
CSA certified. Powdercoated painted (colour to be selected by
Architect during shop drawing review). Galvanizing standards to
ISO 1461. Wet location listed. Suitable for cold environments.
Page 4
7/6/2016
LUMINAIRE SCHEDULE
Project Name: BERNIE MORELLI RECREATION CENTRE
Project number: 15288.000.E001
L15B
208V
282W LED
4000K
2 head
2 heads, 180
degrees apart
127mm W x 400mm
H x 950mm L (each
head)
6m (20ft) pole
1m concrete base
Aluminum housing with corrosion resistant finish and clear opitcal
molded acrylic lenses. IP 66 rated. Type IV distribution.
Integral galvanized steel pole to be 6m high, round tapered, 4"
round at the top of the pole with a 0.13" tapered galvanized steel
shaft, internally dampened to eliminate second mode vibrations.
CSA certified. Powdercoated painted (colour to be selected by
Architect during shop drawing review). Galvanizing standards to
ISO 1461.
•Architectural Area Lighting: Kick- K52
medium Scale series
•Philips Gardco P21 Pureform Series
11600 lumens per head Parking Lighting
Allow for 27mm conduit and mounting of security CCTV cameras
on pole. Pole to have a wind dampening system to avoid camera
shaking. See note 11.
Wall recessed linear lensed LED. Gasketed, die-cast aluminum, • BetaCalco: Verso Series
resistant to oxidation housing. Powder coated, resistant to UV and • FC Lighting: FCSL240 Series
• Bega: 33 065 Series
oxidation. Clear tempered glass lens. Wet location listed.
L16
120V
8.5W LED
4000K
330mm W x 127mm
Hx
102mm D
L17
120V
33W LED
(3500K)
80 CRI
80mmW x 80mmH x Wall Mounted lensed Strip LED. Compact-design channel and
1220mmL
cover are formed from code-gauge cold-rolled steel. High-gloss,
(3"x3"x48")
baked white enamel finish. Five-stage iron phosphate pretreatment ensures superior paint adhesion and rust resistance.
Snap on clear lens.
L18
120V
30W LED
4000K
80 CRI
593mmW x 456mmL Recessed round LED Lensed Down light. Self-flanged, spun
• Lithonia: ZL1N Series
x 200mmH (23• Metalux: SNLED Series
0.050" thick aluminum lower reflector with galvanized steel
3/8"x18"x7-7/8")
• Visioneerig: LCOM
construction hosuing. Universal mounting bracket, adjusts
vertically from above and below ceiling. Light engine and driver
accessible through aperture. Polygcarbonate lens with clear finish.
Minimum CSA listed for damp locations. Suitable for
installation in insulated ceilings. Suitable for cold weather.
L19
120V
39W LED
3500K
175mmWx 150mmH Low Profile Gasketed surface mounted LED luminaire.
x 1220mmL
Fiberglass housing closed cell gasket. Stainless steel latches.
(6-13/16" x4Frosted acrylic lens. Suitable for damp locations.
1/8"x48")
• Lithonia: FEM
• Metalux: Vaportite 4VT2 Series
• GE Lighting: Albeo ALR1 Series
L20
120v
15W/ft. LED
4000K
75mmW x 70mmH x
length as per
drawings
(2.1"x 2.7"x length as
per drawings)
Wall Graze LED luminaire. Extruded anodized aluminum
housing. Clear polycarbonate lens. Suitable for wet locations.
Provide c/w remote driver, jumper cables and required mounting
accessories.
• Philips eW Graze MX Powercore
872 lumens/ft.
• io Lighting: line 2.0 Series
• Tempo Architectural: C6RX Exterior Series
• Lumenpulse: LOG HO Series
Building Entrance-Exterior
75mmW x 70mmH x
length as per
drawings
(2.1"x 2.7"x length as
per drawings)
Wall Graze LED luminaire. Extruded anodized aluminum
housing. Clear polycarbonate lens. Suitable for dry locations.
• Philips eW Graze MX Powercore
• io Lighting: line 2.0 Series
• Tempo Architectural: C6R Series
• Lumenpulse: LOGi HO Series
Building Entrance- Interior
30x60 beam
angle
L20A
120V
15W/ft. LED
4000K
30x60 beam
angle
Provide c/w remote driver, jumper cables and required mounting
accessories.
Page 5
• Lithonia: ZL1N Series
• Metalux: SNLED Series
• Visioneerig: LCOM
400 lumens
Exterior Bench
3000 Lumens
Elevator Shaft
1700 lumens
Building Entrance-Exterior
3000 lumens
Garbage Room, Pool Storage
872 lumens/ft.
7/6/2016
LUMINAIRE SCHEDULE
Project Name: BERNIE MORELLI RECREATION CENTRE
Project number: 15288.000.E001
L21
120V
22W LED
3500K, 80CRI
4-1/2" Dia aperture,
5-11/16" Trim
5-11/16"" Depth
• Gotham: 4" EVO WW Series
Recessed round LED Wall Wash. Self-flanged, aluminum, 4"
medium reflector. Medium beam distribution with 50 degree cutoff. • GE Lighting: DI4R Wall Wash Series
• Portfolio: LD4A13-4LM111 series
Universal mounting bracket, adjusts 5" vertically from above and
below ceiling. Specular Clear finish.
L22
120V
3.6W/ft. LED
3500K, 80CRI
2-1/4" x 3-5/8" x
length as per
drawings
Recessed 2" Wide Linear flangless LED. Extruded aluminum
(0.075" nominal) housing. Frosted acrylic snap-in lens with micro
lens. Certified to UL standards. Suitable for dry locations.
L22A
120V
3.6W/ft. LED
3500K, 80CRI
2-1/4" x 3-5/8" x
length as per
drawings
Recessed 2" Wide Linear LED. Extruded aluminum (0.075"
nominal) housing. Frosted acrylic snap-in lens with micro lens.
Certified to UL standards. Suitable for dry locations.
1500 lumens
Ground Floor Kitchen
• Axis: Beam2 Series
• Metalumen: Caladonia RML Series
• Mark Architectural Lighting: Slot 2 LED
Series
400 lumens/ft.
Ground Floor Kitchen
• Axis: Beam2 Series
• Metalumen: Caladonia RML Series
• Mark Architectural Lighting: Slot 2 LED
Series
400 lumens/ft.
Customer Service 132
Luminiare is a continuous "L" shaped recessed in drywall. Refer to
drawing E302 and corresponding architectural RCP drawing for
more details.
EMERGENCY LIGHTING
X1
120V LED
Recessed edgelit pictogram exit. White, baked powder coat steel
trim plate. High-output LED. Universal surface mounting- wall,
ceiling, or end mount. Refer to drawings for mounting, number of
faces and direction of arrows. AC only.
• Lumacell: LDE Series
• Emergi-Lite: EDE Series
• Beghelli: Guida RM Series
• Stanpro: REMA Series
Public areas
X2
120V
LED
Architectural Edge-lit Pictogram Exit, slim-profile extruded
aluminum housing, high-output LED. Universal surface mountingwall, ceiling, or end mount. Extruded acrylic panel with pictogram
legend. Refer to drawings for mounting, number of faces and
direction of arrows. AC only.
• Lumacell: LAE Series
• Emergi-Lite: EAE Series
• Beghelli: Ottica RM Series
• Aimlite: RPEL Series
• Stanpro: RMEA Series
Pool, Change rooms, gym
(Second Floor)
X3
120V
LED
Commercial Steel pictogram Exit sign, high output LED. Universal
surface mounting- wall, ceiling, or end mount. Refer to drawings
for mounting, number of faces and direction of arrows. AC only.
c/w wireguard
• Lumacell: LS Series
• Emergi-Lite: ES Series
• Beghelli: Stella RM Series
• Stanpro: RMS Series
• Aimlite: RPST Series
Gym (Ground floor)
X4
120V
LED
Attractive low profile commercial pictogram exit sign, made of
tough thermoplastic. Tamperproof screws. Universal surface
mounting- wall, ceiling, or end mount. Refer to drawings for
mounting, number of faces and direction of arrows. AC only.
• Lumacell: LP Series
• Emergi-Lite: EP Series
• Beghelli: Verde RM Series
• Aimlite: RPPL Series
• Stanpro: RMP Series
Back of house areas
X5
120
LED
Surface mounted cast Vandal Resistant pictogram exit sign, high
output LED, protected by hugh abuse clear polycarbonate c/w fully
gasketed housing and tamper resistant screws. Wet location
listed. Suitable for cold weather application. NEMA 4X rated.
Refer to drawings for mounting, number of faces and direction of
arrows. AC Only.
• Lumacell: LN Series
• Emergi-Lite: EN Series
• Beghelli: Fortezza RM Series
• Stanpro: RMR Series
• Aimlite: RPWP Series
Exterior- mechanical well
OTHER
Page 6
7/6/2016
LUMINAIRE SCHEDULE
Project Name: BERNIE MORELLI RECREATION CENTRE
Project number: 15288.000.E001
Fire Do 120V
not
Enter
LED
Recessed edgelit exit with custom "Fire Do not Enter" wording.
White, baked powder coat steel trim plate. High-output LED.
Wording shall not be visble when not engergized.
• Lumacell: LER2 Series
• Emergi-Lite: Prestige Series
• Beghelli: GuidaSeries
• Stanpro: SLEXO Series
At BMRC/ JTP Link
NOTES:
1. All luminaires need to be consistent on technology and must match reference standard description regardless of catalogue number. Where finishes are not indicated, allow for special finish. Manufacturer/Catalogue number not listed will not be considered.
2. The Electrical Contractor is responsible for the supply and installation of all fixed per unit cost luminaires as part of the base electrical contract. Refer to items 1.4.8. and 2.4.5. in specification 16505 or 26 51 13.00 for more details.
3. LED's are to be latest technology to proved maximum lumens, binned, best colour and longest life at time of purchase. Drivers are to be the latest technology at time of purchase.
4.LED luminaires dimensions listed are the maximum size allowed. Luminaires provided can be smaller than the dimension listed.
5. All luminaires diameter and depth listed are the maximum size allowed. Luminaires provided can be smaller than the dimension listed.
6. All LED luminaires that present signs of failure on site, within the warranty period, must be replaced at no cost to the owner. If temporary luminaires are required to replace any failed LED luminaires, during the waiting time for parts (i.e. drivers, boards, heat sinks, etc.), the
labour cost including installation, temporary luminaire supply, temporary luminaire removal and reinstallation of the LED fixture must be provided at no cost of the owner. Additional electrical costs, associated with higher Wattage temporary luminaires, must be reimbursed with
interest to the owner by the manufacturer.
7. In case of failure of a LED luminaire complete or part there of the luminaire failure, a independent third party testing Laboratory (approved by Smith + Andersen) shall be commissioned by the manufacturer or vendor to perform tests on samples taken from the failed luminaires
installed on corresponding site. All reporting including the test results must be submitted to Smith + Andersen for evaluation and final approval.
8. Any additional time (related to luminaire manufacturing issues) involved by Smith + Andersen will be billed at our hourly rates to the manufacturer or vendor.
9. All LED parts and accessories must be replaceable on site without removal of the luminaire.
10. Equivalents will only be considered at Smith + Andersen discretion prior to tender close. Sample must be supplied with plug and cord for mock-up
11. Poles and bases are to be designed to accommodate wind conditions to avoid damage due to wind-induced vibrations. Shop drawings are to be signed by a structural engineer registered in the local jurisdiction.
12 . Fixtures identified as "CASH ALLOWANCE" shall be purchased by the Electrical Contractor after tender award through the cash allowance carried in the Base Contract. The Electrical Contractor shall carry and include in their base bid price the handling, delivery, storage
and installation of all "CASH ALLOWANCE" fixtures. No additional Contractor markups shall be allowed or accepted to be charged against the cash allowance value. Refer specification 26 51 13.00 for more details.
Page 7
7/6/2016
Download