WFG JOB NO.
SHEET NO.
−
ELECTRICAL ABBREVIATIONS
A
M
A
AC
AF
AFC
AFF
AFG
AHU
AIC
ALT
ARCH
AT
ATS
AUTO
AUX
AWG
AMPERES
ALTERNATING CURRENT
AMPERE FRAME (BREAKER RATING)
ABOVE FINISHED COUNTER
ABOVE FINISHED FLOOR
ABOVE FINISHED GRADE
AIR HANDLING UNIT
AMPERE INTERRUPTING CAPACITY
ALTERNATE
ARCHITECT
AMPERES TRIP
AUTOMATIC TRANSFER SWITCH
AUTOMATIC
AUXILIARY
AMERICAN WIRE GAUGE
B
BRKR, BKR
BLDG
MCA
MCB
MCC
MECH
MFR
MH
MIN
MISC
MLO
MOCP
MTD
MTG
MTS
MV
BREAKER
BUILDING
C
C
CB
CATV
CCTV
CONDUIT
CIRCUIT BREAKER
CABLE TELEVISION
CLOSED CIRCUIT TELEVISION
CKT
CIRCUIT
CLG
CEILING
COM, COMM
COMMUNICATIONS
CP
CPT
CT
CU
CONTROL PANEL
CONTROL POWER TRANSFORMER
CURRENT TRANSFORMER
COPPER
NIC
NO
NO., NUM, #
NTS
T
NEUTRAL
NORMALLY CLOSED
OC
OCPD
OFCI
OFOI
OH
OHE/T
D
DIRECT CURRENT
DISC
DISCONNECT
DIST
DIV
DN
DP
DPDT
DPST
DISTRIBUTION
DIVISION
DOWN
DISTRIBUTION PANEL
DOUBLE POLE DOUBLE THROW
DOUBLE POLE SINGLE THROW
DWG
DRAWING
E
EG
EQUIPMENT GROUND
ELEC
ELECTRIC, ELECTRICAL
EM, EMERG
EMERGENCY
ELEV
ELEVATOR
EMT
ENCL
EQ, EQUIP
ELECTRIC METALLIC CONDUIT
ENCLOSURE
EQUIPMENT
EWC
EWH
E, EX, EXIST
ELECTRIC WATER COOLER
ELECTRIC WATER HEATER
EXISTING
P
PA
PB
PDP
PE
PF
PH,
PNL
PRI
PT
PVC
PWR
QTY
F
FA
FAAP
FACP
FAEP
FUSE
FIRE ALARM
FIRE ALARM ANNUNCIATOR PANEL
FIRE ALARM CONTROL PANEL
FIRE ALARM EXTENDER PANEL
FC
FOOT CANDLE
FDR
FL, FLR
FLA
FLEX
FLUOR
FT
FEEDER
FLOOR
FULL LOAD AMPS
FLEXIBLE
FLUORESCENT
FOOT/FEET (')
G
GROUND
GENERATOR
GROUND FAULT INTERRUPTER
H
HORIZONTAL MOUNTING
HAND HOLE
HAND-OFF-AUTOMATIC
HORSEPOWER
HIGH PRESSURE SODIUM
HOUR
HEIGHT
HEATER
HEATING VENTILATION AND AIR CONDITIONING
HERTZ
I
ISOLATED GROUND
INCH/INCHES (")
INCANDESCENT
J
JB, JBOX
JUNCTION BOX
KEY INTERLOCK
1000 CIRCULAR mils
KILOVOLTS (THOUSAND VOLTS)
KILOVOLTS-AMPERES (THOUSAND VOLT-AMPS)
KILOWATTS (THOUSAND WATTS)
KILOWATT-HOURS
L
LA
LAN
LC, LCP
LP
L-L
L-N
L-G
LTG
LV
HAND-OFF-AUTO SELECTOR SWITCH WITH PILOT LIGHT
WYE CONNECTION - SOLID GROUND
MANUAL MOTOR STARTER WITH PILOT LIGHT AS INDICATED.
M
VFD
VARIABLE FREQUENCY DRIVE/VARIABLE FREQUENCY MOTOR CONTROLLER
C
FUSE
TB
TBB
TC
TEL,TELE
TELECOM
TP
TV
TYP
STRESS CONE
EMU
POLE
PUBLIC ADDRESS
PULL BOX
POWER DISTRIBUTION PANEL
PHOTO ELECTRIC
POWER FACTOR
PHASE
PANEL
PRIMARY
POTENTIAL TRANSFORMER
POLYVINYL CHLORIDE
POWER
ELECTRONIC METERING UNIT
LIGHTNING ARRESTOR
LOCAL AREA NETWORK
LIGHTING CONTROL PANEL
LIGHTING PANEL
LINE TO LINE
LINE TO NEUTRAL
LINE TO GROUND
LIGHTING
LOW VOLTAGE (BELOW 50 VOLTS)
LIGHTING CONTROL PANEL, SURFACE MTD. UON.
TELECOMMUNICATIONS DATA OUTLET, FLOOR MTD SERVICE FITTING, SURFACE TYPE
("F" DENOTES FLUSH TYPE, "P" DENOTES POKE THRU TYPE)
LRP
LOW VOLTAGE LIGHTING RELAY PANEL, SURFACE MTD. UON
TELECOMMUNICATIONS COMBINATION VOICE/DATA OUTLET, FLOOR MTD SERVICE FITTING,
SURFACE TYPE ("F" DENOTES FLUSH TYPE, "P" DENOTES POKE THRU TYPE)
MOTOR CONTROL CENTER
TELECOMMUNICATIONS VOICE OUTLET, CEILING MTD SERVICE FITTING,
SURFACE TYPE ("F" DENOTES FLUSH TYPE)
UNINTERRUPTIBLE POWER SUPPLY
TELECOMMUNICATIONS DATA OUTLET, CEILING MTD SERVICE FITTING,
SURFACE TYPE ("F" DENOTES FLUSH TYPE)
UPS
TBB
TELECOMMUNICATIONS BACKBOARD
GAP
GENERATOR ANNUNCIATOR (DERANGEMENT) PANEL
D
D
SINGLE RECEPTACLE, 20A, 125V, 2P, 3W. (SLASH INDICATES MOUNTING ABOVE FINISH COUNTER)
LIGHTING FIXTURE - TYPE AS INDICATED (SUBSCRIPT INDICATES SWITCH CONTROL)
DUPLEX RECEPTACLE, 20A, 125V, 2P, 3W. (SLASH INDICATES MOUNTING ABOVE FINISH COUNTER)
G
GB
CT
XX
WHEN MORE THAN ONE 20A., 1P., 120 VOLT CIRCUIT FEEDS A SURFACE RACEWAY CONNECT
RECEPTACLES TO ALTERNATE CIRCUITS AS FOLLOWS - U.O.N.
A
B
C
A
B
C
GM DISCLAIMER & TYPICAL NOTES
SINGLE POLE SWITCH (SUBSCRIPT INDICATES FIXTURES CONTROLLED)
CEILING MOUNTED QUADRUPLEX ISOLATED GROUND RECEPTACLE, (2)20A, 125V, 2P,
3W, DUPLEX ISOLATED GROUND RECEPTACLES WITH A COMMON FACEPLATE.
3
THREE-WAY SWITCH (S3P-THREE-WAY SWITCH WITH PILOT LIGHT)
RECEPTACLES MOUNTED ABOVE THE CEILING.
4
FOUR - WAY SWITCH
P
SINGLE POLE SWITCH WITH PILOT LIGHT
K
KEY OPERATED SWITCH
FLOOR MOUNTED SINGLE RECEPTACLE, 20A, 125V, 2P, 3W.
22733.000
SUPPLIER DRAWN BY
REFERENCE SYMBOLS
1
E1-1.0
L
D
PI
PASSIVE INFRARED OCCUPANCY SENSOR (WALL/CEILING)
DT
ELTD
CX
PASSIVE INFRARED/ULTRASONIC OCCUPANCY SENSOR (WALL/CEILING)
SWITCHED DUPLEX RECEPTACLE, 20A, 125V, 2P, 3W.
PHOTO CELL
EMERGENCY DUPLEX RECEPTACLE, 20A, 125V, 2P, 3W.
EMERGENCY LIGHTING TRANSFER DEVICE
FLOOR BOX ("X" DENOTES TYPE AS SPECIFIED)
DR
DESKTOP RECEPTACLE (DOUG MOCKETT MODEL # PCS36A/EE-90)
PSD
POWER SUPPLY FOR DOOR(S) WITH ELECTRICAL HARDWARE
FEEDER BUSWAY
RX
REQUEST-FOR-EXIT SENSOR
PLUG-IN BUSWAY
DGP
DATA GATHERING PANEL
DO
DOOR OPERATING EQUIPMENT
ELM
ELECTRIC LOCKING/LATCHING AND MONITORING HARDWARE
AC
ACCESS CONTROL STATION - CARD TYPE
K
ACCESS CONTROL STATION - KEYPAD TYPE
J
JUNCTION BOX - CEILING OR WALL MOUNTED - INDICATED IN POWER, LIGHTING & FIRE
ALARM SYSTEMS PLANS.
SMITHGROUPJJR, INC
500 GRISWOLD SUITE 1700
DETROIT, MI 48226
T 313.983.3600 F 313.983.3636
www.smithgroupjjr.com
MOUNTING HEIGHTS
P
SR-X
WALL SWITCHES
4'-0" AFF
RECEPTACLES
1'-6" AFF
TELECOMMUNICATIONS OUTLETS
1'-6" AFF
TELECOMMUNICATIONS OUTLETS - WALL PHONE
4'-6" AFF
CLOCK OUTLETS
7'-6" AFF
TV OUTLETS
1'-6" AFF
PUSHBUTTONS
4'-0" AFF
DISCONNECT SWITCHES
5'-6" AFF
MOTOR STARTERS
5'-6" AFF
PANELS & CABINETS
6'-0" TO TOP
VOLUME CONTROLS
4'-0" AFF
DIRECT CONNECTION TO EQUIPMENT
NURSE CALL STATIONS
4'-0" AFF
POWER SERVICE FITTING (FLOOR/WALL) MOUNTED FOR CONNECTION TO FURNITURE SYSTEM
AS SPECIFIED.
NURSE CALL DOME LIGHTS
7'-6" AFF
SURFACE RACEWAY ("X" DENOTES TYPE AS SPECIFIED)
INDIVIDUAL CIRCUIT BREAKERS
JUNCTION BOX - FLOOR MOUNTED
J
P
SPECIAL PURPOSE RECEPTACLE. TYPE AS INDICATED ON DRAWINGS.
COORDINATE RECEPTACLE TYPE WITH ACTUAL EQUIPMENT PRIOR TO INSTALLATION.
FBX
J
CCTV SURVEILLANCE CAMERA OUTLET - WALL MTD, UON ('CX' DENOTES TYPE AS SPECIFIED)
DOOR MONITOR SWITCH
AC
DEMO KEY NOTE
DRAWING NUMBER WHERE DRAWN
FLOOR MOUNTED QUADRUPLEX ISOLATED GROUND RECEPTACLE, (2)20A, 125V, 2P,
3W, DUPLEX ISOLATED GROUND RECEPTACLES WITH A COMMON FACEPLATE.
ULTRASONIC OCCUPANCY SENSOR (WALL/CEILING)
CCTV SURVEILLANCE CAMERA OUTLET - CEILING MTD
CCTV
1
DIMMERS
6" ABOVE THE MIRROR
INTERCOM
4'-6" AFF
FIREMAN'S PHONE
4'-6" AFF
4'-0" AFF
GLASS BREAK DETECTOR
FIRE ALARM - PULL STATIONS
CONDUIT TURNED DOWN
CR
CARD READER
HC
DOOR OPERATOR SWITCH
FIRE ALARM DEVICES HORN/SPEAKERS/STROBES
BETWEEN +80" AND 96"AFF
(MOUNTING HEIGHT AT THE BOTTOM OF THE FIRE ALARM DEVICE OR
6" BELOW CEILING WHICH IS LOWER)
MD
MOTION DETECTOR - CEILING MTD
MD
MOTION DETECTOR - WALL MTD
1.
ALL ELEVATIONS ARE TO CENTER LINE OF DEVICE, UNLESS OTHERWISE NOTED.
A
INTERCOMMUNICATION SYSTEM ( AI PHONE)
2.
REFER TO EQUIPMENT ELEVATION DRAWINGS FOR COORDINATION WITH
CASEWORK.
ELECTRIC POWER TRANSFER DEVICE
3.
MOUNT MANUAL MOTOR STARTER ADJACENT TO OR ON UNIT.
4.
REFER TO ARCHITECTURAL A0 SERIES FOR ADDITIONAL MOUNTING HEIGHTS.
PTM
Warren Technical Center Campus
Site ID: 1563
Structure ID: 4235
Level:
4'-0" AFF
GB
GROUND ROD
General Motors Corporation
5'-6" TO TOP
ACCESS CONTROL DEVICES
VANITY LIGHT IN TOILET
Worldwide Facilities Group
4'-0" AFF
CONDUIT TURNED UP
TELEPHONE MANHOLE
FIRM INFO & LOGO
1
E1-1.0
FLOOR MOUNTED QUADRUPLEX RECEPTACLE, (2)20A, 125V, 2P, 3W, DUPLEX
RECEPTACLES WITH A COMMON FACEPLATE.
SECURITY SYSTEM SYMBOLS
CCTV
CONSULTANT A/E
DRAWING NUMBER WHERE DRAWN
FLOOR MOUNTED DUPLEX ISOLATED GROUND RECEPTACLE, 20A, 125V, 2P, 3W.
PI
DT
KEY NOTE
DIMMER SWITCH
OCCUPANCY SENSOR WALL SWITCH
U
FLOOR MOUNTED DUPLEX RECEPTACLE, 20A, 125V, 2P, 3W. PROVIDE CORE
DRILL PACKAGE TO MAINTAIN FIRE RATING OF FLOOR. EXTEND CONDUIT AND
WIRING IN CEILING SPACE OF FLOOR BELOW TO ELECTRICAL CLOSET OR
PANELBOARD.
LOW VOLTAGE SWITCH
OS
U
PERCENT IMPEDANCE
3
SUPPLIER PE/PM
1
DETAIL NUMBER
3
SUPPLIER CHECKED BY
SECTION NUMBER
FLOOR MOUNTED SINGLE ISOLATED GROUND RECEPTACLE, 20A, 125V, 2P, 3W.
DUAL LEVEL SWITCHING - ONE SWITCH CONTROLS OUTER LAMPS AND
ONE SWITCH CONTROLS REMAINING INNER LAMPS.
DM
ELECTRIC HANDHOLE
CERTIFIED BY
SUPPLIER PROJECT NO.
a
DEPT. MGR/SUPR
APPROVAL
R E V I S I O N S
CEILING MOUNTED DUPLEX ISOLATED GROUND RECEPTACLE, 20A, 125V, 2P, 3W.
CEILING MOUNTED QUADRUPLEX RECEPTACLE, (2)20A, 125V, 2P, 3W, DUPLEX RECEPTACLES
WITH A COMMON FACEPLATE.
DOOR CONTACT SWITCH
EHH
PROJECT ARCH/
ENGR APPROVAL
DATE
CEILING MOUNTED DUPLEX RECEPTACLE, 20A, 125V, 2P, 3W.
SINGLE OR DOUBLE, REMOTE EMERGENCY LIGHTING FIXTURE
DC
ELECTRIC MANHOLE
NOT
FOR
CON
STRU
CTIO
N
NO.
LIGHTING FIXTURE TYPE DESIGNATION - "XX" INDICATES SPECIFIC TYPE
DEMOLITION WORK
EMH
TMH
N.
CEILING MOUNTED SINGLE ISOLATED GROUND RECEPTACLE, 20A, 125V, 2P, 3W.
SITE LIGHTING FIXTURE TYPE AS INDICATED
RECEIVER/DRIVER UNIT
CABLE TRAY
MOUNT DEVICES FLUSH WITH CONCEALED CONDUIT, EXCEPT AS NOTED ON THE DRAWINGS
AND IN MECHANICAL AND ELECTRICAL EQUIPMENT ROOMS.
CEILING MOUNTED SINGLE RECEPTACLE, 20A, 125V, 2P, 3W.
EXIT LIGHT - WALL/CEILING MOUNTED - DIRECTIONAL
ARROWS AS INDICATED SHADING INDICATES ILLUMINATED
FACE
R/D
GROUND BUS
M.
LIGHTING TRACK - "X" DENOTES TYPE
CONDUIT CAST IN CONCRETE OR BELOW SLAB
GROUND CABLE, SIZE AS INDICATED
SITE/BUILDING PLAN & NORTH ARROW
QUADRUPLEX ISOLATED GROUND RECEPTACLE, (2)20A, 125V, 2P, 3W,
DUPLEX ISOLATED GROUND RECEPTACLES WITH A COMMON FACEPLATE.
(SLASH INDICATES MOUNTING ABOVE FINISH COUNTER)
HOMERUN TO PANEL WITH CIRCUIT NUMBER(S) AS INDICATED
PB
FURNITURE LAYOUTS ARE FOR REFERENCE ONLY. COORDINATE THE FINAL LOCATION OF
ELECTRICAL DEVICES AND OUTLETS WITH ARCHITECT, OWNER AND FINAL FURNITURE PLANS
PRIOR TO INSTALLATION.
DUPLEX ISOLATED GROUND RECEPTACLE, 20A, 125V, 2P, 3W.
(SLASH INDICATES MOUNTING ABOVE FINISH COUNTER)
SHADING INDICATES FIXTURE [CONNECTED TO LIFE SAFETY BRANCH
(UNSWITCHED)] [W/FLUORESCENT BATTERY/INVERTER UNIT (UNSWITCHED)]
A-1
FB
L.
SINGLE ISOLATED GROUND RECEPTACLE, 20A, 125V, 2P, 3W.
(SLASH INDICATES MOUNTING ABOVE FINISH COUNTER)
SHADING INDICATES FIXTURE [CONNECTED TO CRITICAL BRANCH]
[CONNECTED TO GENERATOR CIRCUIT (SWITCHED)]
[W/FLUORESCENT BATTERY/INVERTER UNIT (SWITCHED)]
ELECTRICAL WIRING SYMBOLS
UNDERGROUND CONDUIT/DUCTBANK
PROVIDE FEEDERS AND BRANCH CIRCUITS WHICH HAVE AN AMPACITY EQUAL TO OR GREATER
THAN THE CIRCUIT OVERCURRENT PROTECTIVE DEVICE RATING, U.O.N.
QUADRUPLEX RECEPTACLE, (2)20A, 125V, 2P, 3W, DUPLEX RECEPTACLES WITH A
COMMON FACEPLATE. (SLASH INDICATES MOUNTING ABOVE FINISH COUNTER)
6-30R
UG
K.
GFI, DUPLEX RECEPTACLE, 20A, 125V, 2P, 3W. (SLASH INDICATES MOUNTING ABOVE FINISH COUNTER)
WALLWASH LIGHT FIXTURE,
PH
CONDUIT RUN CONCEALED IN FINISHED AREAS, EXPOSED IN UNFINISHED
AREAS OR BELOW ACCESS FLOORS
WHERE EXIT SIGNS ARE INDICATED ABOVE DOOR MOUNT AS FOLLOWS, CENTER THE EXIT
SIGN BETWEEN TOP OF DOOR FRAME AND CEILING IF DISTANCE BETWEEN TOP OF DOOR
FRAME AND CEILING IS 24 INCHES OR LESS; OTHERWISE MOUNT BOTTOM OF EXIT SIGN 6
INCHES FROM TOP OF DOOR FRAME, MOUNT OTHER WALL MOUNTED EXIT SIGNS IN THE SAME
AREA AT THE SAME HEIGHT. COORDINATE WITH ARCHITECTURAL DETAILS.
JUNCTION BOX FLOOR OR WALL MOUNTED FOR CONNECTION TO FURNITURE SYSTEM.
WALL MOUNTED LIGHTING FIXTURE- TYPE AS INDICATED
FLUORESCENT LIGHTING FIXTURE - TYPE AS INDICATED
Z
%Z
J.
NOTIFICATION APPLIANCE POWER EXTENDER PANEL
ELECTRICAL POWER SYMBOLS
a
X
TRANSFORMER
WHERE ELECTRICAL DEVICES WITH DIFFERENT MOUNTING HEIGHTS ARE LOCATED IN THE
SAME AREA ALIGN DEVICES VERTICALLY THROUGH THEIR CENTERLINES, UON.
NAC
TELECOMMUNICATIONS DATA OUTLET ABOVE CEILING
ELECTRICAL LIGHTING SYMBOLS
WIRE
WITH
WITHOUT
WATT HOUR METER
WEATHERPROOF
XFMR
I.
VALVE SUPERVISORY (TAMPER) SWITCH, FOR CONNECTION ONLY
GENERATOR
G
VARIABLE FREQUENCY DRIVE/
VARIABLE FREQUENCY MOTOR
CONTROLLER
REMOVE DEVICE
WHERE DIFFERENT RECESSED ELECTRICAL DEVICES WITH THE SAME MOUNTING HEIGHTS
ARE INDICATED SIDE-BY-SIDE, MOUNT THE DEVICES SO THAT THERE IS FOUR INCHES
BETWEEN ADJACENT VERTICAL EDGES OF THE FACEPLATES, UON.
WATER FLOW SWITCH, FOR CONNECTION ONLY
TS
DEPT. MGR/SUPR
APPROVAL
TELECOMMUNICATIONS COMBINATION VOICE/DATA OUTLET, CEILING MTD SERVICE FITTING,
SURFACE TYPE ("F" DENOTES FLUSH TYPE)
SYMBOL INDICATES TO WHICH PANELBOARD INDICATED CIRCUITS IN THE ROOM
ARE TO BE CONNECTED.
RP-XXXX
VOLTS
VOLT-AMPERES
X
H.
WF
FIRE ALARM ANNUNCIATOR PANEL (FLUSH/SURFACE)
LCP
W
W
W/
W/O
WHM
WP
WHERE MULTIPLE SWITCHES, RECEPTACLES, AND OTHER OUTLETS (EXCEPT WALL PHONES)
ARE INDICATED PROVIDE MULTI-GANG BACK BOXES WITH GANG BARRIERS AND A COMMON
FACEPLATE.
MANUAL FIRE ALARM PULL STATION
FAAP
TELECOMMUNICATIONS COMBINATION VOICE/DATA OUTLET, WALL MTD.
(SLASH INDICATES MOUNTING ABOVE FINISH COUNTER)
U
V
VA
VFD
F
FAAP
TELECOMMUNICATIONS VOICE OUTLET, FLOOR MTD SERVICE FITTING, SURFACE TYPE
("F" DENOTES FLUSH TYPE, "P" DENOTES POKE THRU TYPE)
TERMINAL BLOCK
TELEPHONE BACKBOARD
TIME CLOCK
TELEPHONE
TELECOMMUNICATIONS
TAMPERPROOF
TELEVISION
TYPICAL
UNDERGROUND PRIMARY
UNDERGROUND SECONDARY
UNDERGROUND TELEPHONE
UNDERWRITER'S LABORATORY
UNLESS OTHERWISE NOTED
UNINTERRUPTIBLE POWER SUPPLY
G.
HEAT DETECTOR
CONTACTOR
PANELBOARD - (FLUSH/SURFACE)
SCHEDULE
SECONDARY
SQUARE FOOT
SPEAKER
SPECIFICATION(S)
SURGE PROTECTIVE DEVICE
SINGLE POLE DOUBLE THROW
SINGLE POLE SINGLE THROW
STANDARD
SWITCH
SWITCHBOARD
SWITCHGEAR
SYMMETRICAL
UGP
UGS
UGT
UL
UON
UPS
REFER TO ARCH. REFLECTED CEILING PLANS FOR EXACT LOCATION OF CEILING MOUNTED
DEVICES AND LIGHT FIXTURES, UNLESS OTHERWISE INDICATED.
FIRE ALARM REMOTE CONTROL PANEL (FLUSH/SURFACE)
TELECOMMUNICATIONS DATA OUTLET, WALL MTD
(SLASH INDICATES MOUNTING ABOVE FINISH COUNTER, "W" INDICATES WALL PHONE HEIGHT)
DISTRIBUTION PANELBOARD
RELOCATE AS SHOWN
REMOTE CONTROL LIGHTING PANEL
RECEPTACLE
REFRIGERATOR
RADIO FREQUENCY
RIGID STEEL CONDUIT
RATED (RUNNING) LOAD AMPS
ROOM
RECEPTACLE PANELBOARD
UNDERGROUND
F.
FACP
TELECOMMUNICATIONS VOICE OUTLET, WALL MTD
(SLASH INDICATES MOUNTING ABOVE FINISH COUNTER, "W" INDICATES WALL PHONE HEIGHT,
"PY" INDICATES PAY PHONE)
GROUND
OPPOSITE
UG
SMOKE DETECTOR - HVAC DUCT TYPE
LIGHTNING ARRESTOR
S
SCH, SCHED
SEC
SF
SPKR
SPEC(S)
SPD
SPDT
SPST
STD
SW
SWBD
SWGR
SYM
LIMIT VOLTAGE DROP TO 2% FOR FEEDERS AND 3% FOR BRANCH CIRCUITS. INCLUDE
DERATING FACTOR FOR ROOF-MOUNTED CONDUITS.
FACP
TELECOMMUNICATION SYMBOLS
R
R, RE
RCLP
RCPT
REF
RF
RSC
RLA
RM
RP
E.
FA SPEAKER W/STROBE - CEILING MOUNTED
EMERGENCY POWER OFF
AUTOMATIC TRANSFER SWITCH
BUS DUCT PLUG-IN UNIT
OVERHEAD
OVERHEAD ELECTRIC/TELEPHONE
QUANTITY
SMOKE DETECTOR - CEILING OR SURFACE MOUNTED
FA SPEAKER W/STROBE - WALL MOUNTED
PUSHBUTTON STATION
STATIONARY CIRCUIT BREAKER
V
K
K
Kcmil
KV
KVA
KW
KWH
DELTA CONNECTION
KEY INTERLOCKING SYSTEM
T
IG
IN
INCAND
COMBINATION MOTOR STARTER WITH DISCONNECT SWITCH.
PROVIDE SWITCH AND FUSE AMACITY EQUAL TO OR GREATER THAN FEEDER AMPACITY, UON
K
Q
F
H
HH
HOA
HP
HPS
HR
HT
HTR
HVAC
HZ
CURRENT TRANSFORMER
DRAWOUT TYPE, CIRCUIT BREAKER
P
DC
INSTALL ELECTRICAL WORK IN ACCORDANCE WITH THE NATIONAL ELECTRICAL CODE AND
LOCAL BUILDING AND FIRE CODES, IN A NEAT AND WORKMANLIKE MANNER.
FA SPEAKER - CEILING MOUNTED
CONTROL POWER TRANSFORMER
PACKAGE CONTROL UNIT (PROVIDED BY EQUIPMENT SUPPLIER)
ON CENTER
OVERCURRENT PROTECTION DEVICE
OWNER FURNISHED, CONTRACTOR INSTALLED
OWNER FURNISHED, OWNER INSTALLED
D.
FA SPEAKER - WALL MOUNTED
CIRCUIT BREAKER IN NEMA 1 ENCLOSURE (FLUSH/SURFACE)
PC
ATS
PROVIDE FIRE STOPPING FOR CONDUITS AND ELECTRICAL EQUIPMENT FOR FLOOR SLABS,
WALLS AND CEILINGS TO MAINTAIN FIRE RATING.
DISCONNECT SWITCH, FUSED.
PROVIDE SWITCH AND FUSE AMACITY EQUAL TO OR GREATER THAN FEEDER AMPACITY, UON
ELECTRIC INTERLOCK SYSTEM
NOT IN CONTRACT
NORMALLY OPEN
NUMBER
NOT TO SCALE
C.
TRANSFORMER - TYPE AND RATING AS INDICATED
E
NATIONAL ELECTRICAL CODE
NATIONAL ELECTRICAL MANUFACTURERS
ASSOCIATION
PROVIDE A DEDICATED NEUTRAL WIRE FOR EACH BRANCH CIRCUIT.
COORDINATE DEVICE LOCATIONS AND MOUNTING HEIGHTS WITH ARCHITECTURAL DRAWINGS
PRIOR TO ROUGH-IN.
STROBE - CEILING MOUNTED
POTENTIAL TRANSFORMER
CPT
B.
DISCONNECT SWITCH, NON-FUSED
PROVIDE SWITCH AMPACITY EQUAL TO OR GREATER THAN FEEDER AMPACITY, UON
PROJECT ARCH/
ENGR APPROVAL
ISSUED FOR
22MAY13 BIDS
PROVIDE 1#12 + 1#12N + 1#12G FOR 20A BRANCH CIRCUITING, UON; MAXIMUM OF THREE
CIRCUITS PER CONDUIT UON; MINIMUM CONDUIT SIZE OF 3/4" C, UON.
FUSED SWITCH
CB
GENERAL NOTES
A.
STROBE - WALL MOUNTED
O
OPP
G, GND, GRD
GEN
GFI
MINIMUM CIRCUIT AMPACITY
MAIN CIRCUIT BREAKER
MOTOR CONTROL CENTER
MECHANICAL
MANUFACTURER
MANHOLE
MINIMUM
MISCELLANEOUS
MAIN LUGS ONLY
MAXIMUM OVERCURRENT PROTECTION
MOUNTED
MOUNTING
MANUAL TRANSFER SWITCH
MEDIUM VOLTAGE (OVER 600V LESS THAN 35KV)
FIRE ALARM SYMBOLS
MOTOR AND CONNECTION
SWITCH - SINGLE THROW
N
N
NC
NEC
NEMA
ELECTRICAL EQUIPMENT SYMBOLS
DISTRIBUTION AND DIAGRAM SYMBOLS
DATE
MOUNTING HEIGHT NOTES:
ELECTRICAL LEGENDS,
ABBREVIATIONS AND GENERAL
NOTES
WFG PE/PM
WFG JOB NO
N. WEINGARTZ
DRAWN BY
1200912
SHEET NUMBER
Author
SCALE
DATE
22MAY13
FILE PLOT DATE STAMP
E0−001
5/21/2013 12:15:42 PM
WFG JOB NO.
SHEET NO.
−
DATE
PROJECT ARCH/
ENGR APPROVAL
ISSUED FOR
DEPT. MGR/SUPR
APPROVAL
22MAY13 BIDS
DRAWING NOTES
FEEDER & BRANCH CIRCUIT SIZING SCHEDULE GENERAL PURPOSE
CIRCUIT SIZING SCHEDULES NOTES:
(NOTES 1 & 2)
OVERCURRENT
DEVICE RATING
(AMPERES)
MAX.
CIRCUIT
LOAD
(AMPS)
CONDUIT SIZE
1.
3 WIRE
4 WIRE
(3PH & 1N)
3/4"
3/4"
3/4"
10
3/4"
3/4"
3/4"
8
10
3/4"
3/4"
3/4"
45-50
8(6)
10
3/4"
3/4"
3/4"(1")
60
6(4)
10
3/4"(1")
3/4"(1")
1"(1 1/4")
70
6(4)
8
3/4"(1")
3/4"(1")
1"(1 1/4")
80-90
4(2)
8
1"
1"(1 1/4")
1 1/4"
100
3(2)
8
1"(1 1/4")
1 1/4"
1 1/4"
110
2(1)
6
1 1/4"
125
1(1/0)
6
1 1/4"
1 1/2"
1 1/2"(2")
150
1/0
6
1 1/4"
1 1/2"
2"
175
2/0
6
1 1/2"
2"
2"
200
3/0
6
1 1/2"
2"
2"
225
4/0
4
2"
2"
2 1/2"
250
250
4
2"
2 1/2"
2 1/2"
300
350
4
2 1/2"
3"
3"
350
500
3
3"
3"
3 1/2"
400
600
3
3"
4"
4"
450
2-4/0
2-2
2-2"
2-2"
2-2 1/2"
500
2-250
2-2
2-2"
2-2 1/2"
2-2 1/2"
600
2-350
2-1
2-2 1/2"
2-3"
2-3"
700
2-500
2-1/0
2-3"
2-3"
2-3 1/2"
800
2-600
2-1/0
2-3"
2-3"
2-4"
1000
3-400
3-2/0
3-2 1/2"
3-3"
3-3"
1200
4-350
4-3/0
4-2 1/2"
4-3"
4-3"
1600
5-400
5-4/0
5-2 1/2"
5-3"
5-3"
2000
6-400
6-250
6-2 1/2"
6-3"
6-3"
PHASE
& NEUTRAL
E.G.
15-20
12
12
25-30
10
35-40
2 WIRE
1 1/4"(1 1/2")
NOTE
2.
3.
4.
5.
6.
BASED ON THHN/THWN, 90°., 600V., INSULATED, COPPER WIRE APPLIED AT
75°FOR TERMINATIONS RATED AT 60°C/75°C AND 75°C. FOR
TERMINATIONS RATED AT 60°C PROVIDE WIRE AND CONDUIT SIZES
INDICATED IN PARENTHESIS.
BASED ON WIRE OUTSIDE DIAMETERS AND RIGID METALLIC CONDUIT
INSIDE DIAMETERS AS PROVIDED IN THE NEC. DO NOT REDUCE CONDUIT
SIZE FOR NON-RIGID METALLIC APPLICATION. REFER TO NEC FOR
CONDUIT TYPES MORE RESTRICTIVE THAN RIGID METALLIC.
BASED ON MOTOR FULL LOAD AMPERES AS PROVIDED BY THE NEC.
BASED ON MOTOR RUNNING OVERLOAD PROTECTION PROVIDED BY
THERMAL OVERLOAD RELAYS.
MOTOR STARTING TYPE BASED ON 460V., 3 PHASE, FULL VOLTAGE NONREVERSING EXCEPT FOR MOTORS SIZED 75HP OR GREATER WHICH ARE
BASED ON 460V., 3 PHASE, PART WINDING REDUCED VOLTAGE STARTING.
TRANSFORMER CIRCUITS BASED ON 480V TO 208/120V., 3 PHASE, 4
WIRE,DRY TYPE.
1 1/4"(1 1/2")
SITE/BUILDING PLAN & NORTH ARROW
NOT
FOR
CON
STRU
CTIO
N
GM DISCLAIMER & TYPICAL NOTES
MOTOR CIRCUIT SIZING SCHEDULE
480V., THREE PHASE CIRCUIT LENGTH TABLE
BREAKER
AMPACITY
(AMPS)
WIRE SIZE - AWG OR KCMIL
(FOR 460V., 3 PHASE MOTORS) (NOTES 3,4,5)
MAXIMUM LENGTH IN FEET
STARTER
CONDUIT & WIRE
MOTOR HP
SWITCH/FUSE
CIRCUIT
BREAKER
SIZE/TYPE
PHASE
E.G.
CONDUIT
NO.12
NO.10
NO.8
NO.6
NO.4
NO.2
NO.1
1/0
2/0
3/0
4/0
250
350
500
2-3/0
2-4/0
2-250
2-350
2-500
3-300
3-400
4-350
5-400
6-400
6-500
1/2
30/3A.
15A
1
12
12
3/4"
20
16
253
403
642
1019
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
3/4
30/3A.
15A
1
12
12
3/4"
30
24
-
269
428
679
1079
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
1
30/6A.
15A
1
12
12
3/4"
40
32
-
-
321
509
809
1293
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
1 1/2
30/6A.
15A
1
12
12
3/4"
50
40
-
-
-
408
648
1034
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
2
30/6A.
15A
1
12
12
3/4"
60
48
-
-
-
-
540
862
1083
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
3
30/10A.
15A
1
12
12
3/4"
70
56
-
-
-
-
-
739
928
1169
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
5
30/15A.
20A
1
12
12
3/4"
80
64
-
-
-
-
-
646
812
1023
1286
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
7 1/2
30/20A.
30A
1
12
10
3/4"
90
72
-
-
-
-
-
574
722
909
1143
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
10
30/25A.
35A
1
12
10
3/4"
15
30/30A.
50A
2
10
10
3/4"
100
80
-
-
-
-
-
-
650
818
1029
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
20
60/40A.
60A
2
8
10
3/4"
125
100
-
-
-
-
-
-
-
655
823
1043
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
25
60/50A.
75A
2
6
10
1"
150
120
-
-
-
-
-
-
-
546
689
869
1107
-
-
-
-
-
-
-
-
-
-
-
-
-
-
30
60/60A.
100A
3
6
10
1"
175
140
-
-
-
-
-
-
-
-
588
745
949
1110
-
-
-
-
-
-
-
-
-
-
-
-
-
40
100/80A.
125A
3
4
8
1 1/2"
200
160
-
-
-
-
-
-
-
-
-
652
830
971
1360
-
-
-
-
-
-
-
-
-
-
-
-
50
100/100A.
150A
3
3
8
1 1/2"
225
180
-
-
-
-
-
-
-
-
-
-
738
863
1209
1743
-
-
-
-
-
-
-
-
-
-
-
60
200/125A.
175A
4
1
6
1 1/2"
250
200
-
-
-
-
-
-
-
-
-
-
-
777
1088
1569
1043
-
-
-
-
-
-
-
-
-
-
75
200/150A.
200A
4
1/0
6
1 1/2"
300
240
-
-
-
-
-
-
-
-
-
-
-
-
907
1307
869
1107
-
-
-
-
-
-
-
-
-
100
200/200A.
225A
4
2/0
6
2"
350
280
-
-
-
-
-
-
-
-
-
-
-
-
-
1120
745
949
1110
-
-
-
-
-
-
-
-
125
200/200A.
225A
5
3/0
6
2"
400
320
-
-
-
-
-
-
-
-
-
-
-
-
-
980
652
830
971
1360
-
-
-
-
-
-
-
150
400/250A.
300A
5
4/0
4
2 1/2"
450
360
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
738
863
1209
-
-
-
-
-
-
-
200
400/350A.
400A
5
350
4
3"
500
400
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
777
1088
1569
-
-
-
-
-
-
600
480
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
907
1307
1165
-
-
-
-
-
700
560
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
1120
999
1346
-
-
-
-
800
640
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
874
1177
1360
-
-
-
1000
800
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
942
1088
1569
-
-
1200
960
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
907
1307
-
-
1600
1200
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
980
1226
1307
1800
1440
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
1089
1177
2000
1600
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
980
1137
NO.
BREAKER
AMPACITY
(AMPS)
20
30
MAX.
MAX.
CIRCUIT
CIRCUIT
CURRENT
LOAD
(AMPS)
(VOLT-AMPS)
MAXIMUM LENGTH IN FEET
NO.12
NO.10
NO.8
NO.6
NO.4
4
480
220
349
556
882
-
8
960
110
174
278
441
12
1440
73
116
185
16
1920
55
87
139
24
2880
-
58
93
BREAKER
AMPACITY
(AMPS)
MAX.
MAX.
CIRCUIT
CIRCUIT
LOAD
LOAD
(VOLT-AMPS) (VOLT-AMPS)
22733.000
SUPPLIER DRAWN BY
SUPPLIER PE/PM
CONSULTANT A/E
NO.12
NO.10
NO.8
NO.6
NO.4
BREAKER
AMPACITY
(AMPS)
20
MAX.
CIRCUIT
LOAD
(AMPS)
MAX.
CIRCUIT
LOAD
(VOLT-AMPS)
4
(NOTE 6)
277V. SINGLE PHASE CIRCUIT LENGTH TABLE
BREAKER AMPACITY
(AMPS)
MAXIMUM LENGTH IN FEET
NO.12
NO.10
NO.8
NO.6
NO.4
1440
439
698
1113
-
-
20
MAXIMUM LENGTH IN FEET
NO.12
NO.10
200
300
PRIMARY CIRCUIT (480V.)
SWITCH/FUSE OR
CIRCUIT BREAKER
PRIMARY FEEDER
SWITCH/FUSE OR
CIRCUIT BREAKER
SYSTEM/EQUIPMENT
BONDING JUMPER
(GROUND WIRE)
SECONDARY FEEDER
9
30/20A.
20A., 3W.
30/30A.
#8
30A., 4W.
15
30/25A.
25A., 3W.
60/60A.
#8
60A., 4W.
30
60/45A.
45A., 3W.
100/100A.
#8
100A., 4W.
45
100/70A.
70A., 3W.
200/175A.
#4
175A., 4W.
75
200/125A.
125A., 3W.
400/300A.
#2
300A., 4W.
200/175A.
175A., 3W.
400/400A.
#1/0
400A., 4W.
380
605
964
-
-
701
8
1664
190
302
482
765
-
8
2880
220
349
557
883
-
294
467
12
2496
127
202
321
510
810
12
4320
127
233
371
589
935
150
400/225A.
225A., 3W.
600/600A.
#2/0
600A., 4W.
221
350
16
3328
95
151
241
382
607
16
5760
95
175
278
442
701
225
400/350A.
350A., 3W.
800/800A.
#3/0
800A., 4W.
300
600/500A.
500A., 3W.
1200/1000A.
#3/0
1000A., 4W.
30
24
4992
-
101
161
255
405
30
24
8640
-
116
186
294
112 1/2
SMITHGROUPJJR, INC
500 GRISWOLD SUITE 1700
DETROIT, MI 48226
T 313.983.3600 F 313.983.3636
www.smithgroupjjr.com
SECONDARY CIRCUIT (208/120V.)
832
234
FIRM INFO & LOGO
TRANSFORMER CIRCUIT SIZING SCHEDULE - GENERAL PURPOSE TYPE
4
147
20
MAXIMUM LENGTH IN FEET
CERTIFIED BY
SUPPLIER PROJECT NO.
SUPPLIER CHECKED BY
208V. THREE PHASE CIRCUIT LENGTH TABLE
208V. SINGLE PHASE CIRCUIT LENGTH TABLE
DEPT. MGR/SUPR
APPROVAL
R E V I S I O N S
TRANSF. KVA
120V. SINGLE PHASE CIRCUIT LENGTH TABLE
PROJECT ARCH/
ENGR APPROVAL
DATE
Worldwide Facilities Group
General Motors Corporation
468
Warren Technical Center Campus
40
32
3840
-
-
70
110
175
40
32
6656
-
-
121
191
304
40
32
11520
-
-
139
221
351
50
40
4800
-
-
-
88
140
50
40
8320
-
-
-
153
243
50
40
14400
-
-
-
177
281
60
48
5760
-
-
-
-
117
60
48
9984
-
-
-
-
202
60
48
17280
-
-
-
-
234
Site ID: 1563
Structure ID: 4235
Level:
CIRCUIT MAXIMUM DISTANCE TABLES
NOTES:
1.
2.
CIRCUIT MAXIMUM DISTANCE IS BASED ON NEC CHAPTER 9, TABLE 8
CONDUCTOR PROPERTIES FOR COATED COPPER CONDUCTORS AT
75 DEGREES CELSIUS.
MAXIMUM CIRCUIT LOAD FOR DISTANCE IS BASED ON NEC 220-10(b)
ELECTRICAL SCHEDULES,
TABLES AND DRAWING NOTES
WFG PE/PM
WFG JOB NO
N. WEINGARTZ
DRAWN BY
1200912
SHEET NUMBER
Author
SCALE
1 : 1
DATE
22MAY13
FILE PLOT DATE STAMP
E0−002
5/21/2013 12:15:45 PM
WFG JOB NO.
SHEET NO.
−
DATE
PROJECT ARCH/
ENGR APPROVAL
ISSUED FOR
DEPT. MGR/SUPR
APPROVAL
22MAY13 BIDS
TYPE
DESCRIPTION
F2
2'X4' PRISMATIC TROFFER
F3
1' X 12' RECESSED LINEAR FLUORESCENT WITH UNIFORM DIFFUSE FLEXIBLE
TRNASLUCENT WHITE PVC MEMBRANE LENS, 10" DEPTH, FLANGED DOOR FOR
DRYWALL APPLICATION, WHITE FRAME AND INTEGRAL 1% DIMMING BALLAST.
COMBINE THREE 4' FIXTURE MODULES END-TO-END TO CREATE SINGLE 12' FIXTURE.
PROVIDE CUSTOM LENS FRAME TO ALLOW MULTIPLE FIXTURE MODULES TO BUTT
END-TO-END WITHOUT LIGHT LEAKS.
1'X4' CHAIN HUNG INDUSTRIAL
F4
F5
48" LENGTH RECESSED LINEAR FLUORESCENT WITH 2.5" APERTURE, MICROPRISMATIC
LENS, TRIMLESS FLANGE, INTERNAL REFLECTOR, WHITE FINISH AND INTEGRAL
ELECTRONIC BALLAST.
F6
1' X 4' RECESSED LINEAR FLUORESCENT WITH UNIFORM DIFFUSE FLEXIBLE
TRNASLUCENT WHITE PVC MEMBRANE LENS, 10" DEPTH, FLANGED DOOR FOR
DRYWALL APPLICATION, WHITE FRAME AND INTEGRAL DIMMING BALLAST.
SAME AS TYPE F6 BUT WITH STANDARD BALLAST
F6A
L1
L2
L3
L5
RGBW MULTI-CHIP LED MOTORIZED WASH WITH 23° - 58° ZOOM, 540° PAN, 270° TILT, 16
BIT RGBW COLOR MIXING, VARIABLE FAN COOLING, COMPATIBLE WITH DMX512
CONSOLES, 5 PIN DMX IN AND THRU CONNECTIONS, WHITE POWER CORD AND WHITE
HOUSING FINISH.
400W ARC MOTORIZED SPOT WITH 15° - 36° ZOOM, 540° PAN, 260° TILT, 16 BIT CMY
COLOR MIXING, VARIABLE FAN COOLING, ROTATING GOBO WHEEL, MECHANICAL IRIS,
VARIABLE BEAM FOCUS, COMPATIBLE WITH DMX512 CONSOLES, 5 PIN DMX IN AND
THRU CONNECTIONS WHITE POWER CORD AND WHITE HOUSING FINISH.
RGBW MULTI-CHIP LED MOTORIZED WASH WITH 37 X 10W RGBW MULTICHIPS, 8° - 63°
1/2 PEAK BEAM OPTICAL ZOOM, 450° PAN, 300° TILT, 16 BIT RGBW COLOR MIXING,
VARIABLE FAN COOLING, COMPATIBLE WITH DMX512 CONSOLES, 5 PIN DMX IN AND
THRU CONNECTIONS, WHITE POWER CORD AND WHITE HOUSING FINISH.
LINEAR WHITE LED WITH WIDE 110°X110° OPTICS, WHITE FINISH, LOCKABLE
ROTATABLE SURFACE MOUNT, MOUNTING TRACK, 16 BIT DMX DIMMABLE TO 1%, DMX
ADRESSIBLE BY FIXTURE LENGTH, INTEGRAL DRIVER AND END TO END CONNECTORS.
MANUFACTURER
MODEL
MANUFACTURER
(OPTION 1)
LITHONIA
SP8
COOPER (METALUX)
MARK ARCHITECTURAL
LIGHTING
VEIL
LITHONIA
DIM
XAL
EE - LIGHTING FIXTURE SCHEDULE1
MODEL
MANUFACTURER
MODEL
(OPTION 1)
(OPTION 2)
(OPTION 2)
GR8
LIGHTOLIER
XP
LOAD
LAMP
64 VA
(2) 32W T8
105 VA
COOPER (METALUX)
PROGRAMMED
RAPID START
(1) 32W T8 4100K NEMA PREMIUM
CCT IN CROSS
PROGRAMMED
SECTION
START
MOUNTING
120 V
RECESSED
120 V
RECESSED
PROVIDE INTEGRAL 1% DIMMING BALLAST. PROVIDE SHOP DRAWINGS SHOWING
ALL FIXTURE MODULES AND SECTIONS OF CUSTOM LENS FRAME PRIOR TO FINAL
APPROVAL.
120 V
CHAIN HUNG
PROVIDE WIRE GUARD AND CHAIN HANGING KIT, SURFACE MOUNT IN AREAS
WHERE A DROP CEILING IS PROVIDED.
PROVIDE SPECIALFX LIGHTING FADE-NOT POLYSLEEVE NEUTRAL DENSITY
FILTER FOR EACH LAMP. PROVIDE SAMPLES OF 2' T5 FADE-NOT POLY SLEEVES IN
COLOR OPTIONS ROSCO N.15 #3415, ROSCO N.3 #3402, ROSCO N.6 #3403 AND
ROSCOSUN N.9 #3404 FOR ON-SITE MOCKUP. FINAL FADE-NOT POLY SLEEVE
COLOR SPECIFICATION TO BE DETERMINED AFTER ON-SITE MOCKUP.
COORDINATE MOCKUP WITH LIGHTING DESIGNER.
PROVIDE INTEGRAL DIMMING BALLAST
(2) 32W T8
MINIMAL 60
33 VA
(1) 28W T5; 3000K
CCT; 80+ CRI IN
CROSS SECTION
120 V
RECESSED
MARK ARCHITECTURAL
LIGHTING
VEIL
66 VA
120 V
RECESSED
MARK ARCHITECTURAL
VEIL
66 VA
120 V
RECESSED
PHILIPS VARI-LITE
VLX WASH
820 VA
(2) 32W T8 4100K
CCT; 80+ CRI IN
CROSS SECTION
(2) 32W T8 4100K
CCT; 80+ CRI IN
CROSS SECTION
7 X 120W RGBW
MULTICHIP LED
120 V
C-CLAMP
PHILIPS VARI-LITE
VL440 SPOT
792 VA
400W ARC
120 V
ROBE
ROBIN 1200
LEDWASH
680 VA
37 X 10W RGBW
MULTICHIP LED
120 V
COLOR KINETICS
eW COVE MX
PRECISION DIM
50 VA
WHITE LED; MIN
700 LUMEN;
4000K CCT; 80+
CRI; 4 SCDM
MAX
WHITE LED; 20W;
4000K CCT; 80+
CRI; 4 SCDM
MAX
120 V
LUMENCOVE HO
PROGRAMMED
RAPID START
VOLTAGE
64 VA
LUMENPULSE
LIGHTOLIER
BALLAST
L6
MOTORIZED LED TRACK HEAD WITH 11° OPTICS, 4000K WHITE LED MODULE, WHITE
FINISH, DMX DRIVER AND HOOK CLAMP FOR MOUNTING TO THEATRICAL TRUSS.
REMOTE CONTROLLED
LIGHTING LTD
DR8
27 VA
L6A
SAME AS L6 BUT WITH TRACK MOUNT ADAPTER FOR MOUNTING TO FACTORY-CURVED REMOTE CONTROLLED
LIGHTING LTD
2 CIRCUIT DMX DATA ENABLED TRACK. ENTIRE TRACK ASSEMBELY TO HAVE WHITE
FINISH.
DR8
27 VA
WHITE LED; 20W;
4000K CCT; 80+
CRI; 4 SCDM
MAX
120 V
L6B
SAME AS L6 BUT WITH 24° BEAM OPTICS AND TRACK MOUNT ADAPTER FOR MOUNTING REMOTE CONTROLLED
LIGHTING LTD
TO RECESSED 2 CIRCUIT DMX DATA ENABLED TRACK. ENTIRE TRACK ASSEMBELY TO
HAVE WHITE FINISH.
DR8
27 VA
WHITE LED; 20W;
4000K CCT; 80+
CRI; 4 SCDM
MAX
120 V
L6C
SURFACE MOUNTED TRACK
RCL
EURTRAC
40 VA
NONE
120 V
L7
LINEAR WHITE LED WITH MEDIUM 50°X70° OPTICS, WHITE FINISH, LOCKABLE
ROTATABLE SURFACE MOUNT, 16 BIT DMX DIMMABLE TO 1%, DMX ADRESSIBLE BY 1FT
SEGMENTS, INTEGRAL DRIVER AND END TO END CONNECTORS.
COLOR KINETICS
eW COVE MX
PRECISION DIM
LUMENPULSE
LUMENFACADE
INTERIOR
50 VA
120 V
L8
LINEAR WHITE LED WITH 30°X60° OPTICS, WHITE FINISH, LOCKABLE ROTATABLE
SURFACE MOUNT, 16 BIT DMX DIMMABLE TO 1%, DMX ADRESSIBLE BY 1FT SEGMENTS,
INTEGRAL DRIVER AND END TO END CONNECTORS.
COLOR KINETICS
EW FUSE
PRECISION DIM
LUMENPULSE
LUMENFACADE
INTERIOR
50 VA
L9
LINEAR RGB LED WITH MEDIUM 50°X70° OPTICS, WHITE FINISH, LOCKABLE ROTATABLE
SURFACE MOUNT, 16 BIT DMX DIMMABLE TO 1%, DMX ADRESSIBLE BY 1FT SEGMENTS,
INTEGRAL DRIVER AND END TO END CONNECTORS.
COLOR KINETICS
iCOLOR COVE MX
LUMENPULSE
LUMENFACADE
INTERIOR
50 VA
WHITE LED; MIN
700 LUMENS/FT;
4000K CCT;
80+CRI; MAX 4
SDCM
WHITE LED; MIN
700 LUMENS/FT;
4000K CCT;
80+CRI; MAX 4
SDCM
MIN 400
LUMENS/FT RGB
LED ARRAY
L10
LINEAR RGB LED WITH 30°X60° OPTICS, WHITE FINISH, LOCKABLE ROTATABLE
SURFACE MOUNT, 16 BIT DMX DIMMABLE TO 1%, DMX ADRESSIBLE BY 1FT SEGMENTS,
INTEGRAL DRIVER AND END TO END CONNECTORS.
COLOR KINETICS
iCOLOR FUSE
LUMENPULSE
LUMENFACADE
INTERIOR
50 VA
L11
2" APERTURE LED DOWNLIGHT WITH 40° OPTIC, NON-IC MOUNTING TRAY, ALUMINUM
HEAT SINK, 4" APERTURE MATTE WHITE POWDERCOAT PAINTED FLUSH TRIM PLATE
WITH SPACKLE FLANGE FOR TRIMLESS INSTALLATION, 1" REGRESSED DIE CAST BLACK
BAFFLE, SOFT FOCUS LENS AND INTEGRAL DRIVER
SAME AS L11 BUT 4000K LED MODULE, IC HOUSING AND 60° OPTICS
LUCIFER
DL1ZP-LEDX
14 VA
LUCIFER
DL1ZP-LEDX
14 VA
LUCIFER
DL9ZP LEDX
14 VA
L11A
L11B
L12
SAME AS L11 BUT WITH 4000K CCT MODULE, IC HOUSING, 60° OPTICS, AND WET LISTED
TRIM
RECTANGULAR MIRROR WITH IMBEDDED T5 FLUORESCENT LIGHTING
TECH LIGHTING
TL REFLECTION
MIRROR
14 VA
L13
LINEAR LED COVE FIXTURE WITH 60°X110° BEAM ANGLE, LOCKABLE ROTATABLE
SURFACE MOUNT, MOUNTING TRACK, END TO END CONNECTORS, AND INTEGRAL
DRIVER
COLOR KINETICS
eW COVE QLX
MEDIUM BEAM
LUMENPULSE
LUMENCOVE
L14
LINEAR WHITE LED WITH WIDE 110°X110° OPTICS, WHITE FINISH, FIXED SURFACE
MOUNT, MOUNTING TRACK, 16 BIT DMX DIMMABLE TO 1%, DMX ADDRESSIBLE BY 12"
LENGTH, INTEGRAL DRIVER AND END TO END CONNECTORS.
COLOR KINETICS
eW COVE MX
PRECISION DIM
LUMENPULSE
LUMENCOVE HO
L16
3.5" APERTURE LED DOWNLIGHT WITH 10° OPTIC, DIE CAST 1" REGRESSED BEVEL
WITH WHITE PAINTED FLANGE, SOLITE LENS, INTEGRAL 0-10V DIMMING DRIVER
L17
LED TASK LIGHT WITH 18" ADJUSTABLE GOOSENECK, SWITCH LOCATED IN BASE, CAST
WEIGHTED BASE, RUBBER FOOTINGS, POWER CABLE AND 120V RECEPTACLE REMOTE
POWER SUPPLY.
L22
EXTERIOR RGB LED FLOOD FIXTURE WITH IP 66 RATING, WHITE FINISH, ALUMINUM
HOUSING, 86°SPREAD LENS, INTEGRAL DMX DRIVER AND SURFACE MOUNTED TO
POURED CONCRETE FOOTER
USAI
BEVELED 2.0
LITTLIGHT
L-18-LED
COLOR KINETICS
COLOR BLAST
KURT VERSEN
A1137-10-40-27-70D1-WHT
ECOSENSE
LINEAR INT
6 VA
14 VA
KIRLIN
LRR-04002-39-41KSPT-XX
16 VA
27 VA
50 VA
120 V
COMMENTS
PROVIDE ALL NECESSARY ACCESSORIES AND CONNECTORS FOR INTEGRATION
WITH DMX THEATRICAL LIGHTING CONSOLE. PROVIDE 18" WHITE SAFETY CABLE
WITH 5/16" SPRINGHOOK, MOUNTING BRACKET AND C-CLAMP. ALL MOUNTING
HARDWARE AND CABLES TO BE WHITE. DMX CONSOLE PROVIDED BY OTHERS.
C-CLAMP
PROVIDE ALL NECESSARY ACCESSORIES AND CONNECTORS FOR INTEGRATION
WITH DMX THEATRICAL LIGHTING CONSOLE. PROVIDE 18" WHITE SAFETY CABLE
WITH 5/16" SPRINGHOOK, MOUNTING BRACKET AND C-CLAMP. ALL MOUNTING
HARDWARE AND CABLES TO BE WHITE. DMX CONSOLE PROVIDED BY OTHERS.
SURFACE MOUNT PROVIDE ALL NECESSARY ACCESSORIES AND CONNECTORS FOR INTEGRATION
WITH DMX THEATRICAL LIGHTING CONSOLE. PROVIDE 18" WHITE SAFETY CABLE
WITH 5/16" SPRINGHOOK AND MOUNTING BRACKET. ALL MOUNTING HARDWARE
AND CABLES TO BE WHITE. DMX CONSOLE PROVIDED BY OTHERS.
SURFACE
PROVIDE APPROPRIATE QUANTITY OF 1' AND 4' FIXTURES TO FILL ENTIRE
FIXTURE RUN. PROVIDE ALL NECESSARY DATA BOXES, ACCESSORIES AND
CONNECTORS FOR INTEGRATION WITH DMX THEATRICAL LIGHTING CONSOLE.
ALL VISIBLE DATA BOXES, MOUNTING HARDWARE AND CABLES TO BE WHITE.
DMX CONTROL CONSOLE PROVIDED BY OTHERS.
C CLAMP
PROVIDE ALL NECESSARY ACCESSORIES AND CONNECTORS FOR INTEGRATION
WITH DMX THEATRICAL LIGHTING CONSOLE. PROVIDE 18" WHITE SAFETY CABLE
WITH 5/16" SPRINGHOOK AND C-CLAMP. ALL MOUNTING HARDWARE AND CABLES
TO BE WHITE. DMX CONSOLE PROVIDED BY OTHERS. PROVIDE WIDE SNOOT
ACCESSORY. PROVIDE A TOTAL OF 20 DIFFUSE LENS ACCESSORIES. PROVIDE A
TOTAL OF 20 CUSTOM GLASS LENS HOLDERS THAT CAN ACCEPT COLORED
THEATRICAL GEL FILTERS.
TRACK MOUNTED PROVIDE ALL NECESSARY ACCESSORIES AND CONNECTORS FOR INTEGRATION
WITH DMX THEATRICAL LIGHTING CONSOLE. CONSOLE PROVIDED BY OTHERS.
PROVIDE SHOP DRAWINGS SHOWING LENGTH AND CURVATURE OF TRACK
SECTION PRIOR TO FINAL APPROVAL. SEE ARCHITECTURAL DRAWINGS FOR
EXACT TRACK RUN LENGTHS.
TRACK MOUNTED PROVIDE ALL NECESSARY ACCESSORIES AND CONNECTORS FOR INTEGRATION
WITH DMX THEATRICAL LIGHTING CONSOLE. CONSOLE PROVIDED BY OTHERS.
PROVIDE SHOP DRAWINGS SHOWING LENGTH AND CURVATURE OF RECESSED
TRACK SECTION PRIOR TO FINAL APPROVAL. SEE ARCHITECTURAL DRAWINGS
FOR EXACT TRACK RUN LENGTHS.
TRACK USED FOR STORAGE OF UNUSED L6, L6A AND L6B FIXTURES. NO POWER
REQUIRED, DO NO CIRCUIT.
SURFACE
PROVIDE MINIMUM QUANTITY OF 1' AND 4' FIXTURES TO FILL ENTIRE FIXTURE
RUN. PROVIDE ALL NECESSARY DATA BOXES, ACCESSORIES AND CONNECTORS
FOR INTEGRATION WITH DMX THEATRICAL LIGHTING CONSOLE. CONSOLE
PROVIDED BY OTHERS. PROVIDE 3" JUMPER CABLE BETWEEN FIXTURES.
120 V
SURFACE
PROVIDE MINIMUM QUANTITY OF 1' AND 4' FIXTURES TO FILL ENTIRE FIXTURE
RUN. PROVIDE ALL NECESSARY DATA BOXES, ACCESSORIES AND CONNECTORS
FOR INTEGRATION WITH DMX THEATRICAL LIGHTING CONSOLE. CONSOLE
PROVIDED BY OTHERS.
120 V
SURFACE
MIN 400
LUMENS/FT RGB
LED ARRAY
120 V
SURFACE
PROVIDE MINIMUM QUANTITY OF 1' AND 4' FIXTURES TO FILL ENTIRE FIXTURE
RUN. PROVIDE ALL NECESSARY DATA BOXES, ACCESSORIES AND CONNECTORS
FOR INTEGRATION WITH DMX THEATRICAL LIGHTING CONSOLE. CONSOLE
PROVIDED BY OTHERS.
PROVIDE MINIMUM QUANTITY OF 1' AND 4' FIXTURES TO FILL ENTIRE FIXTURE
RUN. PROVIDE ALL NECESSARY DATA BOXES, ACCESSORIES AND CONNECTORS
FOR INTEGRATION WITH DMX THEATRICAL LIGHTING CONSOLE. CONSOLE
PROVIDED BY OTHERS.
WHITE LED; 720
LUMENS; 3000K
CCT; 80+CRI;
MAX 4 SDCM
WHITE LED; 720
LUMENS; 4000K
CCT; 80+CRI;
MAX 4 SDCM
WHITE LED; 720
LUMENS; 4000K
CCT; 80+CRI;
MAX 4 SDCM
14W T5; 3000K
CCT; 80+ CRI
120 V
RECESSED
120 V
RECESSED
120 V
RECESSED
WHITE LED; MIN
240 LUMENS/FT;
3000K CCT;
80+CRI; MAX 4
SDCM
WHITE LED; MIN
700 LUMENS/FT;
4000K CCT; 80+
CRI; 4 SDCM
MAX
WHITE LED; MIN
1000 LUMENS;
4000K CCT;
80+CRI; MAX 4
SDCM
WHITE LED; 20W;
4000K CCT; 80+
CRI; 4 SCDM
MAX
MIN 1400
LUMENS; RGB
LED ARRAY
SITE/BUILDING PLAN & NORTH ARROW
NOT
FOR
CON
STRU
CTIO
N
GM DISCLAIMER & TYPICAL NOTES
NO.
120 V
SURFACE
120 V
SURFACE
120 V
SURFACE
PROVIDE SPECIALFX LIGHTING FADE-NOT POLYSLEEVE NEUTRAL DENSITY
FILTER FOR EACH LAMP. PROVIDE SAMPLES OF 2' T5 FADE-NOT POLY SLEEVES IN
COLOR OPTIONS ROSCO N.15 #3415, ROSCO N.3 #3402, ROSCO N.6 #3403 AND
ROSCOSUN N.9 #3404 FOR ON-SITE MOCKUP. FINAL FADE-NOT POLY SLEEVE
COLOR SPECIFICATION TO BE DETERMINED AFTER ON-SITE MOCKUP.
COORDINATE MOCKUP WITH LIGHTING DESIGNER.
PROVIDE ALL NECESSARY DATA BOXES, ACCESSORIES AND CONNECTORS FOR
INTEGRATION WITH DMX THEATRICAL LIGHTING CONSOLE. CONSOLE PROVIDED
BY OTHERS.
RECESSED
PROVIDE 15% DIMMING DRIVER AND ALL NECESSARY CONNECTORS AND
ACCESSORIES FOR INTEGRATION WITH DMX THEATRICAL LIGHTING CONSOLE
120 V
SURFACE
PROVIDE CAST WEIGHTED BASE ACESSORY WITH RUBBER FOOTINGS. FIXTURE
SHALL NOT BE PERMANENTLY MOUNTED TO DESK.
SURFACE
DEPT. MGR/SUPR
APPROVAL
R E V I S I O N S
CERTIFIED BY
SUPPLIER PROJECT NO.
22733.000
SUPPLIER DRAWN BY
120 V
120 V
PROJECT ARCH/
ENGR APPROVAL
DATE
SUPPLIER CHECKED BY
SUPPLIER PE/PM
CONSULTANT A/E
FIRM INFO & LOGO
SMITHGROUPJJR, INC
500 GRISWOLD SUITE 1700
DETROIT, MI 48226
T 313.983.3600 F 313.983.3636
www.smithgroupjjr.com
PROVIDE ALL NECESSARY CONTROL EQUIPMENT AND CONNECTORS FOR
INTEGRATION WITH THEATRICAL LIGHTING CONSOLE
Worldwide Facilities Group
General Motors Corporation
Warren Technical Center Campus
Site ID: 1563
Structure ID: 4235
Level:
LIGHT FIXTURE SCHEDULE
WFG PE/PM
WFG JOB NO
N. WEINGARTZ
DRAWN BY
1200912
SHEET NUMBER
Author
SCALE
DATE
22MAY13
FILE PLOT DATE STAMP
E0−003
5/21/2013 12:15:47 PM
WFG JOB NO.
−
SHEET NO.
SHEET NOTES
1
39
36
2
A.
40
38
3
B.
C.
D.
35
37
4
E.
5
F.
G.
H.
P-9B
6
P-9A ED13
34
AIR COMP
ED13
E1-12
I.
ED13
ED13
J.
EF-8
P-5A
ED13
MECHANICAL
EQUIPMENT
ROOM
UP
P-5B
P-6B
ED13
MECHANICAL
EQUIPMENT
ROOM
P-6A
K.
7
UH-4
UP
ED13
002
L.
ED21
001
ED21
UH
ED13
M.
33
SF-1 ED13
N.
8
SF-2
ED13
CP
FA
DN
ED12
REMOVE EXISTING ELECTRICAL DEVICES, EQUIPMENT,
BRANCH CIRCUITS AND FEEDERS IN THEIR ENTIRETY
BACK TO THEIR POINT OF ORIGIN UNLESS OTHERWISE
INDICATED. TURN OFF AND LABEL CIRCUIT BREAKERS
AS SPARES FOR NEW WORK.
QUANTITY AND LOCATION OF DEVICES SHOWN ON
PLANS ARE APPROXIMATE. FIELD VERIFY DEVICES AND
LOCATIONS.
PROTECT EXISTING-TO-REMAIN CEILING, FLOORS,
WALLS AND PANELS.
SELECT DEMOLITION MAY BE REQUIRED FOR NEW
CONSTRUCTION AND MAY NOT BE DELINEATED ON THIS
DRAWING. CAREFULLY COORDINATE DEMOLITION WITH
NEW CONSTRUCTION (PARTITION AND REFLECTED
CEILING) PLANS TO VERIFY ACTUAL EXTENT OF
DEMOLITION.
EXAMINE THE DRAWINGS OF OTHER TRADES AND BE
FAMILIAR WITH THE DEMOLITION REQUIRED BY OTHER
TRADES. PERFORM INCIDENTAL ELECTRICAL
DEMOLITION WORK AND/OR RELOCATION REQUIRED
TO FACILITATE THE DEMOLITION WORK OF OTHER
TRADES, WHETHER OR NOT SPECIFICALLY INDICATED
RECYCLE OR DISPOSE MATERIALS OFF SITE OR IN
COMPLIANCE WITH OWNER POLICY AND INCLUDE ALL
COSTS IN BID. HANDLE ALL MATERIALS IN ACCORDANCE
WITH LEED REQUIREMENTS, ALL FEDERAL, STATE,
AND LOCAL REGULATIONS,
PROVIDE BLANK COVER PLATES WHERE DEVICES ARE
REMOVED BUT EXISTING WALLS REMAIN INTACT.
WHERE EXISTING BUILDING SERVICES AND/OR
EQUIPMENT THAT IS TO REMAIN IN USE ARE REQUIRED
TO BE SHUT DOWN COORDINATE WITH THE OWNER'S
REPRESENTATIVE. , INCLUDE ALL ASSOCIATED
OVERTIME COSTS TO PERFORM THIS WORK DURING
WEEKENDS AND EVENINGS. INCLUDE ALL COSTS FOR
PROVIDING TEMPORARY POWER WHERE SHUT DOWN
MUST OCCUR FOR PERIODS LONGER THAN THESE
HOURS. COORDINATE ELECTRICAL SHUT DOWNS WITH
THE OWNER ONE WEEK PRIOR TO SHUT DOWN.
PROVIDE NEW TYPED DIRECTORIES FOR PANELS
AFFECTED BY THIS ALTERATION.
REMOVE ELECTRICAL EQUIPMENT INDICATED WITH
HEAVY WEIGHT DASHED LINES OR INDICATED WITH
KEYNOTES.
PROVIDE CODE-COMPLIANT SUPPORT TO EXISTING-TOREMAIN UNSUPPORTED CONDUITS AND BOXES WHERE
CEILINGS ARE TO BE REMOVED. RE-ROUTE BRANCH
CIRCUITS AND RELOCATE JUNCTION BOXES AS
REQUIRED TO FACILITATE INSTALLATION OF NEW
EQUIPMENT AND SYSTEMS IN CEILING SPACES.
MAINTAIN ELECTRICAL SERVICE TO LIGHTING FIXTURES
AND DEVICES THAT ARE TO REMAIN. EXTEND CONDUIT
AND WIRE AS REQUIRED WHERE DEMOLITION WORK
AFFECTS ELECTRICAL SERVICE TO DOWNSTREAM
DEVICES THAT ARE TO REMAIN.
EXISTING FIRE ALARM NOTIFICATION APPLIANCES AND
INITIATION DEVICES (AND ASSOCIATED WIRING AND
CONDUIT) SHALL BE REMOVED UNLESS NOTED
OTHERWISE.
OWNER HAS FIRST RIGHT OF REFUSAL FOR ALL
REMOVED EQUIPMENT AND DEVICES. OWNER WISHES
TO SALVAGE SELECT EQUIPMENT AS HISTORIAL
RELICS. COORDINATE WITH OWNER PRIOR TO
DISPOSAL OF ANY EQUIPMENT.
DATE
PROJECT ARCH/
ENGR APPROVAL
ISSUED FOR
DEPT. MGR/SUPR
APPROVAL
22MAY13 BIDS
SITE/BUILDING PLAN & NORTH ARROW
NOT
FOR
CON
STRU
CTIO
N
GM DISCLAIMER & TYPICAL NOTES
ED13
MECHANICAL
CONTROLS
(E)EF-6
32
LDP-1
T-B-11
LP-B-8
KEYED NOTES
PDP-1
9
T
ED12
REMOVE EXISTING FIRE ALARM
CONTROL PANEL. UPON COMPLETION
OF DEMOLITION, EXTEND EXISTING TO
REMAIN FIRE ALARM CIRCUITS TO NEW
FIRE ALARM CONTROL PANEL IN SAME
LOCATION.
ED13
REMOVE CIRCUIT (CONDUIT, WIRING,
DISCONNECT, STARTER, ETC...) FEEDING
MECHANICAL EQUIPMENT BACK TO
SOURCE. COORDINATE WITH
MECHANICAL PLANS AND TRADES.
ED15
REFER TO DEMOLITION ELECTRICAL ONE
LINE DIAGRAM FOR DETAILS REGARDING
REMOVAL OF EXISTING ELECTRICAL
EQUIPMENT.
REMOVE AND REPLACE EXISTING CARD
READER. REUSE EXISTING CONDUIT
AND WIRING. VERIFY EXACT LOCATION
IN FIELD. EXTEND CIRCUIT (CONDUIT
AND WIRING) TO NEW SECURITY PANEL
LOCATED IN FIRST FLOOR STORAGE
127D.
ATS
LP-B-8E
LDP-2
SUB
6B
TRANSFORMER
ROOM
T-B-8
T
31
ELEVATOR
CONTROL
PANEL
10
003
ED16
SUB
6A
ED26
ED21
30
11
ED26
ELEVATOR
DISCONNECT EXISITNG ELEVATOR
MOTOR AND CONTROLS AS REQUIRED
FOR MECHANICAL
RELACEMENT/RESTORATION.
RECONNECT UPON COMPLETION OF
REPLACEMENT/RESTORATION.
COORDINATE EXACT REQUIREMENTS
WITH MECHANICAL CONTRACTOR.
NO.
PROJECT ARCH/
ENGR APPROVAL
DATE
DEPT. MGR/SUPR
APPROVAL
R E V I S I O N S
CERTIFIED BY
SUPPLIER PROJECT NO.
22733.000
SUPPLIER DRAWN BY
SUPPLIER CHECKED BY
UP
12
STAIR LOBBY
29
ED26
REVISE EXISTING LIGHT FIXTURE
LAYOUT TO ACCOMMODATE NEW
MECHANICAL WORK WITHIN THIS SPACE.
EXTEND LIGHTING CIRCUIT (CONDUIT
AND WIRING) AS REQUIRED FOR NEW
LAYOUT.
007
SUPPLIER PE/PM
CONSULTANT A/E
FIRM INFO & LOGO
CR
ED16
SMITHGROUPJJR, INC
500 GRISWOLD SUITE 1700
DETROIT, MI 48226
T 313.983.3600 F 313.983.3636
www.smithgroupjjr.com
CR
IN ELEVATOR
ED16
CR
ELEVATOR
008
ED16
28
TUNNEL #5
13
005
Worldwide Facilities Group
ED16
CR
General Motors Corporation
SDP-1
T-COM
CABINET
PROJECTION
SCREEN
Warren Technical Center Campus
TURN
TABLE
CONTROL
PANEL
ED13
27
ED15
HV-1
Site ID: 1563
14
Structure ID: 4235
TUNNEL #6
Level:
006
STORAGE ROOM
15
004
BASEMENT FLOOR ELECTRICAL
DEMOLITION PLAN
26
WFG PE/PM
WFG JOB NO
N. WEINGARTZ
16
DRAWN BY
1200912
SHEET NUMBER
Author
SCALE
25
24
23
22
21
20
19
18
17
1/8" = 1'-0"
DATE
22MAY13
FILE PLOT DATE STAMP
ED1−200
5/21/2013 12:15:54 PM
WFG JOB NO.
−
SHEET NO.
SHEET NOTES
A.
1
39
36
2
40
38
B.
3
C.
D.
37
E.
4
JC
122
DC
DC DC
STAIR
DC
BASEBOARD
HEATER
MEN'S WASH
ROOM
BOARDROOM
BASEBOARD
HEATER
ED09
JC
102
UP
SUB-PANEL
UP
H.
104
126
F
MEN'S TOILET
G.
WOMEN'S WASH
103
ROOM
STAIR
121
35
6
WOMEN'S TOILET
ED06
BOARDROOM
DIMMING PANEL
120
F.
5
125
ED18
105
F
I.
EM
34
J.
EM
MECH EQUIP
ROOM
ED08
K.
ED08
119
DN
EF
EF
ED13
UP
L.
UP
106
ED13
UH
7
MECH EQUIP
DN
ROOM
ED13
M.
N.
33
8
BASEBOARD
HEATER
ED13
BASEBOARD
HEATER
ED10
SEC
COAT ROOM
ED08
101
ED18
DN
HC
CCTV
CR
31
ED16
10
ED17
ED14
ON FACE OF CANOPY
ED14
LOBBY
CCTV
F
116
F
ED17
ENTRY
ENTRY
117
109
ED02
LOBBY
ON FACE OF CANOPY
CCTV
108
ED17
ED17
ED16
CCTV
HC
ED23
ED23
CR
CHAIR STORAGE
RM
F
ED17
ED16 HC
CCTV
CR
F
30
11
UNDERSIDE
OF CANOPY
111
LOAD CENTER
FA-BP11A
(TO REMAIN)
29
MULTI-PURPOSE
ROOM
ED18
DN
STAIR LOBBY
110
12
ED15
115
FA-BP11
CR
ED16
ELEVATOR
124
CR
ED16
ED15
28
CORRIDOR
FA-BL14
DN
DN
SERVICE ENTRY
112
F
ED07
13
ED19
114
STAGE
DIMMER
CONTROL
PANEL
ED07
ED22
F
F
F
ED19
DC
PLATFORM
DC
ED16
113
DN
14
CR
27
22MAY13 BIDS
SITE/BUILDING PLAN & NORTH ARROW
NOT
FOR
CON
STRU
CTIO
N
GM DISCLAIMER & TYPICAL NOTES
ED08 REMOVE LIGHT FIXTURES, LIGHT
SWITCHES, ELECTRICAL FIXTURES,
TELECOM OUTLETS, FIRE ALARM DEVICES,
AND ASSOCIATED CONDUIT AND WIRES
(BACK TO SOURCE OR NEAREST
UPSTREAM DEVICE THAT IS TO REMAIN)
WITHIN THIS AREA U.O.N.. CONDUIT AND
WIRES PASSING THROUGH THIS AREA
SHALL REMAIN OR BE REROUTED AS
REQUIRED TO ACCOMMODATE NEW
CONSTRUCTION. REFER TO MECHANICAL
DEMOLITION PLANS AND REMOVE POWER
CONNECTIONS TO MECHANICAL
EQUIPMENT BACK TO SOURCE AS
REQUIRED.
ED09 REMOVE EXISTING SUB-PANEL AND
FEEDER (CONDUIT AND WIRING) BACK TO
SOURCE. UPON COMPLETION OF
DEMOLITION EXTEND EXISTINGTO REMAIN
BRANCH CIRCUITS (CONDUIT AND WIRING)
TO NEW PROJECTION ROOM PANEL OF
SAME VOLTAGE LOCATED ON MEZZANINE
ABOVE AS REQUIRED.
ED10 REMOVE EXISTING SECURITY PANEL.
EXTEND EXISTING TO REMAIN POWER AND
SECURITY CIRCUITS TO NEW SECURITY
PANELS LOCATED IN FIRST FLOOR
STORAGE 102J. REFER TO NEW POWER
AND AUXILIARY SYSTEMS PLANS FOR NEW
LOCATION.
ED13 REMOVE CIRCUIT (CONDUIT, WIRING,
DISCONNECT, STARTER, ETC...) FEEDING
MECHANICAL EQUIPMENT BACK TO
SOURCE. COORDINATE WITH MECHANICAL
PLANS AND TRADES.
DC
ED17
HC
FA-BL13
DISPLAY AREA
DC
CCTV
CR
9
ED15
F
UNDERSIDE
OF CANOPY
SEC
ED15
FA-BL12
ED16
DEPT. MGR/SUPR
APPROVAL
ED02 REMOVE LIGHT FIXTURES FROM COVE.
REMOVE CONDUIT AND WIRING BACK TO
SOURCE.
ED06 REMOVE CURTAIN CONTROLS FROM
DIMMING PANEL THAT IS TO BE
DEMOLISHED AND REINSTALL IN LOCATION
INDICATED.
ED07 REMOVE STAGE DIMMER CONTROL PANEL.
OWNER TO PROVIDE NEW WIRELESS
CONTROLS TO REPLACE INTEGRAL TURN
TABLE CONTROLS. COORDINATE
RELOCATION OF NEW TURN TABLE
CONTROLS TO EXTERIOR OF BUILDING
WITH OWNER DURING CONSTRUCTION.
ED10
ED20
118
PROJECT ARCH/
ENGR APPROVAL
ISSUED FOR
KEYED NOTES
ED13
32
REMOVE EXISTING ELECTRICAL DEVICES, EQUIPMENT,
BRANCH CIRCUITS AND FEEDERS IN THEIR ENTIRETY
BACK TO THEIR POINT OF ORIGIN UNLESS OTHERWISE
INDICATED. TURN OFF AND LABEL CIRCUIT BREAKERS
AS SPARES FOR NEW WORK.
QUANTITY AND LOCATION OF DEVICES SHOWN ON
PLANS ARE APPROXIMATE. FIELD VERIFY DEVICES AND
LOCATIONS.
PROTECT EXISTING-TO-REMAIN CEILING, FLOORS,
WALLS AND PANELS.
SELECT DEMOLITION MAY BE REQUIRED FOR NEW
CONSTRUCTION AND MAY NOT BE DELINEATED ON THIS
DRAWING. CAREFULLY COORDINATE DEMOLITION WITH
NEW CONSTRUCTION (PARTITION AND REFLECTED
CEILING) PLANS TO VERIFY ACTUAL EXTENT OF
DEMOLITION.
EXAMINE THE DRAWINGS OF OTHER TRADES AND BE
FAMILIAR WITH THE DEMOLITION REQUIRED BY OTHER
TRADES. PERFORM INCIDENTAL ELECTRICAL
DEMOLITION WORK AND/OR RELOCATION REQUIRED
TO FACILITATE THE DEMOLITION WORK OF OTHER
TRADES, WHETHER OR NOT SPECIFICALLY INDICATED
RECYCLE OR DISPOSE MATERIALS OFF SITE OR IN
COMPLIANCE WITH OWNER POLICY AND INCLUDE ALL
COSTS IN BID. HANDLE ALL MATERIALS IN ACCORDANCE
WITH LEED REQUIREMENTS, ALL FEDERAL, STATE,
AND LOCAL REGULATIONS,
PROVIDE BLANK COVER PLATES WHERE DEVICES ARE
REMOVED BUT EXISTING WALLS REMAIN INTACT.
WHERE EXISTING BUILDING SERVICES AND/OR
EQUIPMENT THAT IS TO REMAIN IN USE ARE REQUIRED
TO BE SHUT DOWN COORDINATE WITH THE OWNER'S
REPRESENTATIVE. , INCLUDE ALL ASSOCIATED
OVERTIME COSTS TO PERFORM THIS WORK DURING
WEEKENDS AND EVENINGS. INCLUDE ALL COSTS FOR
PROVIDING TEMPORARY POWER WHERE SHUT DOWN
MUST OCCUR FOR PERIODS LONGER THAN THESE
HOURS. COORDINATE ELECTRICAL SHUT DOWNS WITH
THE OWNER ONE WEEK PRIOR TO SHUT DOWN.
PROVIDE NEW TYPED DIRECTORIES FOR PANELS
AFFECTED BY THIS ALTERATION.
REMOVE ELECTRICAL EQUIPMENT INDICATED WITH
HEAVY WEIGHT DASHED LINES OR INDICATED WITH
KEYNOTES.
PROVIDE CODE-COMPLIANT SUPPORT TO EXISTING-TOREMAIN UNSUPPORTED CONDUITS AND BOXES WHERE
CEILINGS ARE TO BE REMOVED. RE-ROUTE BRANCH
CIRCUITS AND RELOCATE JUNCTION BOXES AS
REQUIRED TO FACILITATE INSTALLATION OF NEW
EQUIPMENT AND SYSTEMS IN CEILING SPACES.
MAINTAIN ELECTRICAL SERVICE TO LIGHTING FIXTURES
AND DEVICES THAT ARE TO REMAIN. EXTEND CONDUIT
AND WIRE AS REQUIRED WHERE DEMOLITION WORK
AFFECTS ELECTRICAL SERVICE TO DOWNSTREAM
DEVICES THAT ARE TO REMAIN.
EXISTING FIRE ALARM NOTIFICATION APPLIANCES AND
INITIATION DEVICES (AND ASSOCIATED WIRING AND
CONDUIT) SHALL BE REMOVED UNLESS NOTED
OTHERWISE.
OWNER HAS FIRST RIGHT OF REFUSAL FOR ALL
REMOVED EQUIPMENT AND DEVICES. OWNER WISHES
TO SALVAGE SELECT EQUIPMENT AS HISTORIAL
RELICS. COORDINATE WITH OWNER PRIOR TO
DISPOSAL OF ANY EQUIPMENT.
DATE
15
ED14 REMOVE EXISTING CEILING MOUNTED
LIGHT FIXTURES WITHIN THIS ROOM.
OTHER ELECTRICAL DEVICES LOCATED
WITHIN ROOM TO REMAIN UNLESS NOTED
OTHERWISE.
NO.
22733.000
SUPPLIER DRAWN BY
SUPPLIER CHECKED BY
SUPPLIER PE/PM
CONSULTANT A/E
16
FIRM INFO & LOGO
SMITHGROUPJJR, INC
500 GRISWOLD SUITE 1700
DETROIT, MI 48226
T 313.983.3600 F 313.983.3636
www.smithgroupjjr.com
ED17 REMOVE AND REPLACE EXISTING CAMERA.
REROUTE EXISTING CONDUIT WHERE
EXISTING CONDUIT IS EXPOSED,
OTHERWISE REUSE. PROVIDE NEW WIRING
PER SPECIFICATIONS. VERIFY EXACT
LOCATION IN FIELD.
Worldwide Facilities Group
General Motors Corporation
Warren Technical Center Campus
Site ID: 1563
Structure ID: 4235
Level:
ED19 REMOVE AND REPLACE EXISTING
SECURITY DEVICE AND ASSOCIATED
CIRCUIT BACK TO PANEL OR NEAREST
UPSTRAM DEVICE TO REMAIN. VERIFY
EXACT LOCATION IN FIELD.
ED22 RELOCATE EXISTING TO REMAIN CABLES
AND CONDUITS PASSING THROUGH PANEL
LOCATION THAT ARE SERVING OTHER
AREAS AS REQUIRED. COORDINATE NEW
ROUTING WITH OWNER PRIOR TO
INSTALLATION. CAREFULLY REMOVE FIBER
OPTIC CABLE CONNECTED TO EXISTING
CONTROL AREA AND TURN OVER TO
OWNER.
26
CERTIFIED BY
SUPPLIER PROJECT NO.
ED20 EXISTING WIRELESS ACCESS POINT TO
REMAIN. TEMPORARILY SUPPORT FROM
STRUCTURE DURING DEMOLITION AND
REINSTALL IN SAME LOCATION UPON
COMPLETION OF NEW CONSTRUCTION.
DN
DEPT. MGR/SUPR
APPROVAL
R E V I S I O N S
ED15 REFER TO DEMOLITION ELECTRICAL ONE
LINE DIAGRAM FOR DETAILS REGARDING
REMOVAL OF EXISTING ELECTRICAL
EQUIPMENT.
ED16 REMOVE AND REPLACE EXISTING CARD
READER. REUSE EXISTING CONDUIT AND
WIRING. VERIFY EXACT LOCATION IN FIELD.
EXTEND CIRCUIT (CONDUIT AND WIRING)
TO NEW SECURITY PANEL LOCATED IN
FIRST FLOOR STORAGE 127D.
ED18 REMOVE LIGHT FIXTURES, LIGHT
SWITCHES, FIRE ALARM DEVICES, AND
ASSOCIATED CONDUIT AND WIRES (BACK
TO SOURCE OR NEAREST UPSTREAM
DEVICE THAT IS TO REMAIN) WITHIN THIS
AREA U.O.N.. REMOVE WIRING DEVICES
AND TELCOMMUNICATIONS EQUIPMENT
ONLY ON WALLS THAT ARE TO BE
DEMOLISHED U.O.N.. CONDUIT AND WIRES
PASSING THROUGH THIS AREA SHALL
REMAIN OR BE REROUTED AS REQUIRED
TO ACCOMMODATE NEW CONSTRUCTION.
REFER TO MECHANICAL DEMOLITION
PLANS AND REMOVE POWER
CONNECTIONS TO MECHANICAL
EQUIPMENT BACK TO SOURCE AS
REQUIRED. EXISTING RECEPTACLES AND
TLECOMMUNICATIONS OUTLETS TO
REMAIN. EXTEND CIRCUITS TO NEW PANEL
AS REQUIRED.
PROJECT ARCH/
ENGR APPROVAL
DATE
ED23 REMOVE EXISTING POWER AND LIGHTING
CABLES DRAPED OVER FLOOR AND STEPS
IN THIS AREA. REVISE CIRCUITING AS
REQUIRED FOR EXISTING TO REMIAN
UPSTREAM/DOWNSTREAM DEVICES.
FIRST FLOOR ELECTRICAL
DEMOLITION PLAN
WFG PE/PM
WFG JOB NO
N. WEINGARTZ
DRAWN BY
1200912
SHEET NUMBER
Author
SCALE
1/8" = 1'-0"
DATE
25
24
23
22
21
20
19
18
17
22MAY13
FILE PLOT DATE STAMP
ED1−201
5/21/2013 12:15:59 PM
WFG JOB NO.
−
SHEET NO.
SHEET NOTES
A.
1
39
36
2
40
38
B.
3
C.
D.
37
E.
4
A/V MACHINE
ROOM (E) I/T RACK
SUB-PANEL
201
ED25 ED24 ED21
DN
F.
5
G.
ED05
PROJECTION ROOM
PANEL
H.
DN
ED15
35
6
UP
EM
EM
MECH EQUIP
ROOM
34
F
203
DN
ED02
ED21
UP
F
I.
MECH EQUIP
ROOM
ED21
J.
202
K.
MCC-21
MCC-22
ED15
ED15
ED11
7
ED15
ED15
FA-L21
FA-L22
UH
M.
DIMMER CABINET #22
DIMMER CABINET #21
UH
ED13
ED15
L.
DN
DWH-1
ED13
FA-BL22
ED15
FA-BL22
N.
33
8
32
9
31
10
REMOVE EXISTING ELECTRICAL DEVICES, EQUIPMENT,
BRANCH CIRCUITS AND FEEDERS IN THEIR ENTIRETY
BACK TO THEIR POINT OF ORIGIN UNLESS OTHERWISE
INDICATED. TURN OFF AND LABEL CIRCUIT BREAKERS
AS SPARES FOR NEW WORK.
QUANTITY AND LOCATION OF DEVICES SHOWN ON
PLANS ARE APPROXIMATE. FIELD VERIFY DEVICES AND
LOCATIONS.
PROTECT EXISTING-TO-REMAIN CEILING, FLOORS,
WALLS AND PANELS.
SELECT DEMOLITION MAY BE REQUIRED FOR NEW
CONSTRUCTION AND MAY NOT BE DELINEATED ON THIS
DRAWING. CAREFULLY COORDINATE DEMOLITION WITH
NEW CONSTRUCTION (PARTITION AND REFLECTED
CEILING) PLANS TO VERIFY ACTUAL EXTENT OF
DEMOLITION.
EXAMINE THE DRAWINGS OF OTHER TRADES AND BE
FAMILIAR WITH THE DEMOLITION REQUIRED BY OTHER
TRADES. PERFORM INCIDENTAL ELECTRICAL
DEMOLITION WORK AND/OR RELOCATION REQUIRED
TO FACILITATE THE DEMOLITION WORK OF OTHER
TRADES, WHETHER OR NOT SPECIFICALLY INDICATED
RECYCLE OR DISPOSE MATERIALS OFF SITE OR IN
COMPLIANCE WITH OWNER POLICY AND INCLUDE ALL
COSTS IN BID. HANDLE ALL MATERIALS IN ACCORDANCE
WITH LEED REQUIREMENTS, ALL FEDERAL, STATE,
AND LOCAL REGULATIONS,
PROVIDE BLANK COVER PLATES WHERE DEVICES ARE
REMOVED BUT EXISTING WALLS REMAIN INTACT.
WHERE EXISTING BUILDING SERVICES AND/OR
EQUIPMENT THAT IS TO REMAIN IN USE ARE REQUIRED
TO BE SHUT DOWN COORDINATE WITH THE OWNER'S
REPRESENTATIVE. , INCLUDE ALL ASSOCIATED
OVERTIME COSTS TO PERFORM THIS WORK DURING
WEEKENDS AND EVENINGS. INCLUDE ALL COSTS FOR
PROVIDING TEMPORARY POWER WHERE SHUT DOWN
MUST OCCUR FOR PERIODS LONGER THAN THESE
HOURS. COORDINATE ELECTRICAL SHUT DOWNS WITH
THE OWNER ONE WEEK PRIOR TO SHUT DOWN.
PROVIDE NEW TYPED DIRECTORIES FOR PANELS
AFFECTED BY THIS ALTERATION.
REMOVE ELECTRICAL EQUIPMENT INDICATED WITH
HEAVY WEIGHT DASHED LINES OR INDICATED WITH
KEYNOTES.
PROVIDE CODE-COMPLIANT SUPPORT TO EXISTING-TOREMAIN UNSUPPORTED CONDUITS AND BOXES WHERE
CEILINGS ARE TO BE REMOVED. RE-ROUTE BRANCH
CIRCUITS AND RELOCATE JUNCTION BOXES AS
REQUIRED TO FACILITATE INSTALLATION OF NEW
EQUIPMENT AND SYSTEMS IN CEILING SPACES.
MAINTAIN ELECTRICAL SERVICE TO LIGHTING FIXTURES
AND DEVICES THAT ARE TO REMAIN. EXTEND CONDUIT
AND WIRE AS REQUIRED WHERE DEMOLITION WORK
AFFECTS ELECTRICAL SERVICE TO DOWNSTREAM
DEVICES THAT ARE TO REMAIN.
EXISTING FIRE ALARM NOTIFICATION APPLIANCES AND
INITIATION DEVICES (AND ASSOCIATED WIRING AND
CONDUIT) SHALL BE REMOVED UNLESS NOTED
OTHERWISE.
OWNER HAS FIRST RIGHT OF REFUSAL FOR ALL
REMOVED EQUIPMENT AND DEVICES. OWNER WISHES
TO SALVAGE SELECT EQUIPMENT AS HISTORIAL
RELICS. COORDINATE WITH OWNER PRIOR TO
DISPOSAL OF ANY EQUIPMENT.
DATE
PROJECT ARCH/
ENGR APPROVAL
ISSUED FOR
DEPT. MGR/SUPR
APPROVAL
22MAY13 BIDS
SITE/BUILDING PLAN & NORTH ARROW
NOT
FOR
CON
STRU
CTIO
N
GM DISCLAIMER & TYPICAL NOTES
KEYED NOTES
ED01
ED02
11
30
ED03
ED01
ED04
UP
ED05
12
29
13
28
ED11
REMOVE CIRCUIT (CONDUIT, WIRING,
DISCONNECT, STARTER, ETC...) FEEDING
MECHANICAL EQUIPMENT BACK TO
SOURCE. COORDINATE WITH
MECHANICAL PLANS AND TRADES.
ED15
REFER TO DEMOLITION ELECTRICAL ONE
LINE DIAGRAM FOR DETAILS REGARDING
REMOVAL OF EXISTING ELECTRICAL
EQUIPMENT.
REVISE EXISTING LIGHT FIXTURE
LAYOUT TO ACCOMMODATE NEW
MECHANICAL WORK WITHIN THIS SPACE.
EXTEND LIGHTING CIRCUIT (CONDUIT
AND WIRING) AS REQUIRED FOR NEW
LAYOUT.
ED21
ED24
ED25
ED03
14
ED03
27
REMOVE SPOT LIGHT FIXTURES FROM
UNDERSIDE OF RIM. REMOVE CONDUIT
AND WIRING BACK TO SOURCE.
REMOVE DEAD DISTRIBUTION PANEL.
PANEL FEEDER HAS ALREADY BEEN
REMOVED. REMOVE CONDUIT BACK TO
SOURCE.
DISCONNECT DOMESTIC WATER HEATER
'DWH-1' AND ASSOCIATED
RECIRCULATION PUMP AND RELOCATE
(R) AS INDICATED ON NEW MEZZANINE
POWER PLAN. COORDINATE EXACT
LOCATION IN FIELD WITH MECHANICAL
TRADES.
ED13
ED04
(TYP.)
REMOVE LIGHT FIXTURES FROM
SUSPENDED RING. REMOVE CONDUIT
AND WIRING BACK TO SOURCE.
REMOVE LIGHT FIXTURES FROM COVE.
REMOVE CONDUIT AND WIRING BACK TO
SOURCE.
REMOVE SPOT LIGHT FIXTURES AND
EMERGENCY LIGHT FIXTURE FROM
PROJECTION AREA ABOVE AND TRACK
LIGHT FIXTURES ILLUMINATING STAGE.
REMOVE CONDUIT AND WIRING BACK TO
SOURCE.
NO.
DEPT. MGR/SUPR
APPROVAL
R E V I S I O N S
CERTIFIED BY
SUPPLIER PROJECT NO.
22733.000
SUPPLIER DRAWN BY
SUPPLIER CHECKED BY
SUPPLIER PE/PM
CONSULTANT A/E
FIRM INFO & LOGO
SMITHGROUPJJR, INC
500 GRISWOLD SUITE 1700
DETROIT, MI 48226
T 313.983.3600 F 313.983.3636
www.smithgroupjjr.com
Worldwide Facilities Group
REMOVE ABANDONED CONDUCTORS,
CUT AND CAP UNUSED CONDUITS
PENTRATING A/V MACHINE ROOM FLOOR
LEVEL WITH FLOOR UPON COMPLETION
OF DEMOLITION.
REMOVE ALL ABANDONED LIGHTING
CONTROL PANELS, LIGHTING
EQUIPMENT, ETC... WITHIN THIS SPACE.
REMOVE ASSOCIATED CONDUCTORS
AND CONDUITS BACK TO SOURCE.
U.O.N..
PROJECT ARCH/
ENGR APPROVAL
DATE
General Motors Corporation
Warren Technical Center Campus
Site ID: 1563
Structure ID: 4235
(TYP.)
Level:
15
MEZZANINE FLOOR
ELECTRICAL DEMOLITION PLAN
ED02
26
WFG PE/PM
WFG JOB NO
N. WEINGARTZ
DRAWN BY
1200912
SHEET NUMBER
Author
16
SCALE
1/8" = 1'-0"
25
24
23
22
21
20
19
18
17
DATE
22MAY13
FILE PLOT DATE STAMP
ED1−202
5/21/2013 12:16:03 PM
WFG JOB NO.
−
SHEET NO.
SHEET NOTES
PROJECT ARCH/
ENGR APPROVAL
ISSUED FOR
DEPT. MGR/SUPR
APPROVAL
22MAY13 BIDS
A.
1
39
36
2
40
38
REMOVE EXISTING ELECTRICAL DEVICES, EQUIPMENT,
BRANCH CIRCUITS AND FEEDERS IN THEIR ENTIRETY
BACK TO THEIR POINT OF ORIGIN UNLESS OTHERWISE
INDICATED. TURN OFF AND LABEL CIRCUIT BREAKERS
AS SPARES FOR NEW WORK.
B. QUANTITY AND LOCATION OF DEVICES SHOWN ON
PLANS ARE APPROXIMATE. FIELD VERIFY DEVICES AND
LOCATIONS.
C. PROTECT EXISTING-TO-REMAIN CEILING, FLOORS,
WALLS AND PANELS.
D. SELECT DEMOLITION MAY BE REQUIRED FOR NEW
CONSTRUCTION AND MAY NOT BE DELINEATED ON THIS
DRAWING. CAREFULLY COORDINATE DEMOLITION WITH
NEW CONSTRUCTION (PARTITION AND REFLECTED
CEILING) PLANS TO VERIFY ACTUAL EXTENT OF
DEMOLITION.
E. EXAMINE THE DRAWINGS OF OTHER TRADES AND BE
FAMILIAR WITH THE DEMOLITION REQUIRED BY OTHER
TRADES. PERFORM INCIDENTAL ELECTRICAL
DEMOLITION WORK AND/OR RELOCATION REQUIRED
TO FACILITATE THE DEMOLITION WORK OF OTHER
TRADES, WHETHER OR NOT SPECIFICALLY INDICATED
F. RECYCLE OR DISPOSE MATERIALS OFF SITE OR IN
COMPLIANCE WITH OWNER POLICY AND INCLUDE ALL
COSTS IN BID. HANDLE ALL MATERIALS IN ACCORDANCE
WITH LEED REQUIREMENTS, ALL FEDERAL, STATE,
AND LOCAL REGULATIONS,
G. PROVIDE BLANK COVER PLATES WHERE DEVICES ARE
REMOVED BUT EXISTING WALLS REMAIN INTACT.
H. WHERE EXISTING BUILDING SERVICES AND/OR
ED15
REFER THAT
TO DEMOLITION
ONE
EQUIPMENT
IS TO REMAIN ELECTRICAL
IN USE ARE REQUIRED
LINE
DIAGRAM
FOR DETAILS
TO BE
SHUT
DOWN COORDINATE
WITHREGARDING
THE OWNER'S
REMOVAL OF, INCLUDE
EXISTING
REPRESENTATIVE.
ALLELECTRICAL
ASSOCIATED
EQUIPMENT.
OVERTIME
COSTS TO PERFORM THIS WORK DURING
WEEKENDS AND EVENINGS. INCLUDE ALL COSTS FOR
PROVIDING TEMPORARY POWER WHERE SHUT DOWN
MUST OCCUR FOR PERIODS LONGER THAN THESE
HOURS. COORDINATE ELECTRICAL SHUT DOWNS WITH
THE OWNER ONE WEEK PRIOR TO SHUT DOWN.
I. PROVIDE NEW TYPED DIRECTORIES FOR PANELS
AFFECTED BY THIS ALTERATION.
J. REMOVE ELECTRICAL EQUIPMENT INDICATED WITH
HEAVY WEIGHT DASHED LINES OR INDICATED WITH
KEYNOTES.
K. PROVIDE CODE-COMPLIANT SUPPORT TO EXISTING-TOREMAIN UNSUPPORTED CONDUITS AND BOXES WHERE
CEILINGS ARE TO BE REMOVED. RE-ROUTE BRANCH
CIRCUITS AND RELOCATE JUNCTION BOXES AS
REQUIRED TO FACILITATE INSTALLATION OF NEW
EQUIPMENT AND SYSTEMS IN CEILING SPACES.
L. MAINTAIN ELECTRICAL SERVICE TO LIGHTING FIXTURES
AND DEVICES THAT ARE TO REMAIN. EXTEND CONDUIT
AND WIRE AS REQUIRED WHERE DEMOLITION WORK
AFFECTS ELECTRICAL SERVICE TO DOWNSTREAM
DEVICES THAT ARE TO REMAIN.
M. EXISTING FIRE ALARM NOTIFICATION APPLIANCES AND
INITIATION DEVICES (AND ASSOCIATED WIRING AND
CONDUIT) SHALL BE REMOVED UNLESS NOTED
OTHERWISE.
N. OWNER HAS FIRST RIGHT OF REFUSAL FOR ALL
REMOVED EQUIPMENT AND DEVICES. OWNER WISHES
TO SALVAGE SELECT EQUIPMENT AS HISTORIAL
RELICS. COORDINATE WITH OWNER PRIOR TO
DISPOSAL OF ANY EQUIPMENT.
DATE
3
37
4
5
35
6
34
7
33
8
32
SITE/BUILDING PLAN & NORTH ARROW
NOT
FOR
CON
STRU
CTIO
N
GM DISCLAIMER & TYPICAL NOTES
9
KEYED NOTES
ED15
31
REFER TO DEMOLITION ELECTRICAL
ONE LINE DIAGRAM FOR DETAILS
REGARDING REMOVAL OF EXISTING
ELECTRICAL EQUIPMENT.
10
EXISTING 150KVA
TRANSFORMER TO BE
RELOCATED
T
LP-RING
ED15
LTG CNTL DIMMING
PANEL
(E)EF-4
NO.
11
30
PROJECT ARCH/
ENGR APPROVAL
DATE
DEPT. MGR/SUPR
APPROVAL
R E V I S I O N S
CERTIFIED BY
SUPPLIER PROJECT NO.
22733.000
SUPPLIER DRAWN BY
SUPPLIER CHECKED BY
SUPPLIER PE/PM
12
29
CONSULTANT A/E
FIRM INFO & LOGO
SMITHGROUPJJR, INC
500 GRISWOLD SUITE 1700
DETROIT, MI 48226
T 313.983.3600 F 313.983.3636
www.smithgroupjjr.com
13
28
Worldwide Facilities Group
General Motors Corporation
Warren Technical Center Campus
Site ID: 1563
14
27
Structure ID: 4235
Level:
15
UPPER MEZZANINE FLOOR
ELECTRICAL DEMOLITION PLAN
26
WFG PE/PM
WFG JOB NO
N. WEINGARTZ
DRAWN BY
1200912
SHEET NUMBER
Author
16
SCALE
1/8" = 1'-0"
25
24
23
22
21
20
19
18
17
DATE
22MAY13
FILE PLOT DATE STAMP
ED1−203
5/21/2013 12:16:05 PM
−
SHEET NO.
KEYED NOTES
BASEMENT
SUBSTATION NO. 6A
B-4
80E
6A-3
800AF
400AT
6A-4
6B-2
6B-3
DISCONNECT EXISTING 5HP SMOKE
EXHAUST FAN (EF-4) FROM EXISTING
MOTOR CONTROL CENTER. INTERCEPT
AND EXTEND EXISTING CONDUCTORS TO
NEW 480V PANELBOARD FA-L22 VIA NEW
COMBINATION MOTOR STARTER.
PROVIDE NEW MOTOR STARTER PER
SPECIFICATIONS.
ED503
REMOVE EXISTING PANEL. UPON
COMPLETION OF DEMOLITION, REFFEED
EXISTING TO REMAIN LOADS FROM NEW
PANEL 'FABL-22'. EXTEND CIRCUIT
(CONDUIT AND WIRING0 AS REQUIRED.
REFER TO NEW ONE LINE DIAGRAM AND
POWER AND AUXILIARY SYSTEMS PLANS
FOR DETAILS AND LOCATION OF NEW
PANEL.
ED504
REMOVE EXISTING PANEL. UPON
COMPLETION OF DEMOLITION, REFFEED
EXISTING TO REMAIN LOADS FROM NEW
PANEL 'LP-2'. REFER TO NEW POWER
PLAN FOR PANEL LOCATION.
ED505
DISCONNECT AND RELOCATE EXISTING
150KVA TRANSFORMER. REFEED
TRANSFORMER FROM NEW PANEL AS
INDICATED ON NEW ONE LINE DIAGRAM.
REFER TO MEZZANINE LEVEL POWER
PLANS FOR NEW LOCATION.
800AF
TIE
1600AF
1000AT
800AF
600AT
800AF
800AT
480Y/277V
3PH,4W BUS
SPARE
SPARE
SPARE
PROJECT ARCH/
ENGR APPROVAL
ISSUED FOR
DEPT. MGR/SUPR
APPROVAL
22MAY13 BIDS
NOT
FOR
CON
STRU
CTIO
N
800AF
800AT
SPACE
800AF
DATE
SITE/BUILDING PLAN & NORTH ARROW
6B-1
SPACE
SPACE
800AF
800AT
1600AF
1200AT
SPACE
6A-2
ED502
SUB 6B
750/1000 KVA
13.2KV-480Y/277V
1600AF
1200AT
6A-1
REMOVE EXISTING PANEL. UPON
COMPLETION OF DEMOLITION, REFFEED
EXISTING TO REMAIN LOADS FROM NEW
PANEL OF SAME NAME TO BE INSTALLED
IN APPROXIMATE SAME LOCATION.
REFER TO NEW ONE LINE DIAGRAM AND
POWER AND AUXILIARY SYSTEMS PLANS
FOR DETAILS AND LOCATION OF NEW
PANEL.
80E
SUB 6A
750/1000 KVA
13.2KV-480Y/277V
480Y/277V
3PH,4W BUS
ED501
BASEMENT
SUBSTATION NO. 6B
A-4
GM DISCLAIMER & TYPICAL NOTES
600A
480V
3P,3W
T-B-11
300 KVA
480 ∆-208Y/120V
60A/3/45A
60A/3/40A
30A/3/20A
ED501
ED501
FA-L22
DIM
CAB
#21
DIM
CAB
#22
LP-B-8
B-11
DOME
1ST FL
J-CLOSET
FA-BP11
ELEVATOR
CONTROLLER
ED501
ED501
1 1/2 HP
HV-1
AUDITORIUM
SPARE
SPARE
DIM
CAB
#1
FA-BL-2
FA-BP11
30A
10A
200A
200A
200A
FA-BL-22
ED501
30A
30A
30A
200A
200A
200A
100A
100A
100A
100A
100A
200A
200A
200A
200A
200A
200A
100A
100A
400A
400A
400A
300A
SPACE
SPACE
200A
175A
200A
FA-L21
NO.
1 1/2 HP
EF-6
2 SPEED
22733.000
ED504
FA-B14
FA-BP11A
DEPT. MGR/SUPR
APPROVAL
CERTIFIED BY
SUPPLIER PROJECT NO.
PROJ.
PANEL
T
PROJECT ARCH/
ENGR APPROVAL
DATE
R E V I S I O N S
ED503
SUPPLIER DRAWN BY
TO TUNNEL
ED501
ED501
FA-BL12
LP-B-8E
SUPPLIER CHECKED BY
FA-BL13
SUPPLIER PE/PM
CONSULTANT A/E
FIRM INFO & LOGO
SMITHGROUPJJR, INC
500 GRISWOLD SUITE 1700
DETROIT, MI 48226
T 313.983.3600 F 313.983.3636
www.smithgroupjjr.com
MEZZANINE
MCC-22
MEZZANINE
Worldwide Facilities Group
General Motors Corporation
200A
800A
800A
MCC-21
200A
800A, 480V, 3PH, 4W
800A, 480V, 3PH, 4W
4 SPACES
11 SPACES
Warren Technical Center Campus
Site ID: 1563
Structure ID: 4235
EF-7
UH#1
?
WEST AUDIT
SF
P6A
P6B
TOILET
EF
AIR
KITCHEN
EF COMPRESSOR
SPARE
SPARE
Level:
SPARE
T-B-8
30 KVA
480V-208Y/120V
SPACE
ED501
SDP-1
SPACE
FA-BL-21
SPACE
SPARE
ATS-1
100A
SPACE
175A
1200A, 208Y/120V, 3PH, 4W
800A, 480V, 3PH, 3W
SPACE
200A
800A, 480Y/277V, 3PH, 4W
BASEMENT
SPACE
125A
MCC-1
BASEMENT
SPACES
100A
800A, 480Y/277V, 3PH, 4W
PDP-1
BASEMENT
200A
LDP-2
125A
BASEMENT
PDP-PV
MAIN
FOUNTAIN VAULT
1000A
LDP-1
100A
WFG JOB NO.
SPARE
ED502
60A OUTLET
UH-4
P-9B
P-9A
P5
ALT
P-9
ALTERNATOR
(E)EF-4
AUDITORIUM EXHAUST
ED505
EAST
AUDITORIUM
P-5A
P-5B
TOILET
ROOM
EF-2
EF-3
DEMOLITION ELECTRICAL
ONE−LINE DIAGRAM
150 KVA
480V-208Y/120V
3 PHASE
400A, 3PH
ED501
WFG PE/PM
96 CKT
"SENSOR"
WFG JOB NO
N. WEINGARTZ
DRAWN BY
LP-RING
LIGHTING
CONTROL
DIMMING PANEL
(RING LIGHTING)
1200912
SHEET NUMBER
Author
SCALE
12" = 1'-0"
DATE
22MAY13
FILE PLOT DATE STAMP
ED6−511
5/21/2013 12:16:07 PM
WFG JOB NO.
−
SHEET NO.
ROOM LEGEND
1
39
36
2
40
38
001
002
003
004
005
006
007
008
3
DATE
PROJECT ARCH/
ENGR APPROVAL
ISSUED FOR
DEPT. MGR/SUPR
APPROVAL
22MAY13 BIDS
MECHANICAL EQUIPMENT ROOM
MECHANICAL EQUIPMENT ROOM
TRANSFORMER ROOM
STORAGE ROOM
TUNNEL #5
TUNNEL #6
STAIR LOBBY
ELEVATOR
35
37
4
SHEET NOTES
A.
5
B.
C.
NEW FA-BL21- 2
PC
M
34
UH-6
TS
PC
WF
E244
SAF-AHU-4
001
NEW FA-BL21- 4
D
VF
D
VF
SAF-AHU-3
E201
E201
VF
D
E.
6
CRU-1
HWP-2
VF
D
VF
HWP-1 D
NEW FA-L21- 7,9,11
RAF-AHU-4
UP
NEW FA-L22- 8
SP-1 & 2
NEW FA-BL22- 9,11,13
NEW FA-L21- 8,10,12
D.
TO MCC-1. REFER TO ONE LINE
DIAGRAM FOR CIRCUITING
DETAILS
COORDINATE FINAL LOCATION OF MECHANICAL
EQUIPMENT AND ASSOCIATED DISCONNECT SWITCHES,
STARTERS, VFDS, CONTROL POWER AND OTHER
POWER REQUIREMENTS WITH DIV 15.
SURFACE MOUNTED RACEWAY SHALL NOT BE UTILIZED
IN FINISHED AREAS WITHOUT ARCHITECT APPROVAL
U.O.N.
PROVIDE ALL NECESSARY CABLING FROM SECURITY
DEVICES (CAMERAS, DOOR HARDWARE, ETC...) BACK
TO NEW SECURITY PANELS.
COORDINATE MOUNTING HEIGHT AND LOCATION OF
NEW ELECTRICAL EQUIPMENT AND DEVICES WITH
ARCHITECTURAL PLANS PRIOR TO INSTALLTION.
PROVIDE SEPARATE ISOLATED GROUND CONDUCTOR
FOR EACH CIRCUIT FED FROM ISOLATED GROUND
PANEL 'LP-AV'.
M
E244
HU-1
VF
D
RAF-AHU-3
E201 (TYP.)
E220
NEW FA-BL22- 1
LP-B-8- 22
KEYED NOTES
RECEPTACLE FOR
GLYCOL PUMP GLF-1
7
WF TS
AHU LIGHTS
UP
E220 LP-B-8- 22
E204
AHU LIGHTS
E204
E220
LP-B-8- 22
M UH-5
002
CHWP-2
LP-B-8E- 23
E220 CONNECT TO NEW 20A, 1 POLE CIRCUIT
BREAKER IN PANELBOARD 'LP-B-8'
LOCATED IN ADJACENT ELECTRICAL
ROOM. CIRCUIT AS INDICATED.
E230 DISCONNECT EXISTING 4' CHAIN HUNG
INDUSTRIAL LIGHT FIXTURE INSIDE DOOR
OF MECHANICAL/ELECTRICAL SPACE
FROM EXISTING NORML CIRCUIT.
CONNECT EXISTING FIXTURE TO SPARE
20A CIRCUIT BREAKER IN PANEL BOARD
'LP-B-8E'. FIXTUE SHALL FUNCTION AS
NIGHTLIGHT. EXTEND EXISTING NORMAL
CIRCUIT AS REQUIRED TO COMPLETE THE
CIRCUIT.
D
VF
D
VF
30
E201
CP
FA
E204 PROVIDE ELECTRICAL CONNECTIONS
BETWEEN AIR HANDLING UNIT SECTIONS
DURING INSTALLATION AS REQUIRED.
COORDINATE EXACT REQUIREMENTS
WITH MECHANICAL TRADES.
DRY PIPE
COMPRESSOR
M
CHWP-1
33
E201 COORDINATE EXACT VFD LOCATION WITH
MECHANICAL PLANS AND MECHANICAL
TRADES PRIOR TO INSTALLATION.
PROVIDE INTERCONNECTING WIRING
BETWEEN VFD AND MOTOR(S) AS
REQUIRED.
TO MCC-1. REFER TO ONE LINE
DIAGRAM FOR CIRCUITING
DETAILS
8
DN
(TYP.)
E230
75
(E)EF-6
32
LDP-1
T-B-11
LP-B-8
PDP-1
9
T
ATS
LP-B-8E
SITE/BUILDING PLAN & NORTH ARROW
NOT
FOR
CON
STRU
CTIO
N
GM DISCLAIMER & TYPICAL NOTES
E244 PROVIDE 120V POWER AND DATA
CONNECTION FOR NEW DDC CONTROLS
DEVICES AS REQUIRED. COORDINATE
LOCATION WITH MECHANICAL TRADES.
PROVIDE POWER FROM NEAREST 120V
PANELBOARD SERVING AREA.
LDP-2
SUB
6B
T-B-8
T
31
10
003
SUB
6A
MCC-1
11
30
NO.
PROJECT ARCH/
ENGR APPROVAL
DATE
DEPT. MGR/SUPR
APPROVAL
R E V I S I O N S
ELEVATOR
CERTIFIED BY
SUPPLIER PROJECT NO.
22733.000
75
SUPPLIER DRAWN BY
UP
SUPPLIER CHECKED BY
12
29
007
SUPPLIER PE/PM
CONSULTANT A/E
FIRM INFO & LOGO
CR
F
CR
IN ELEVATOR
CR
008
SMITHGROUPJJR, INC
500 GRISWOLD SUITE 1700
DETROIT, MI 48226
T 313.983.3600 F 313.983.3636
www.smithgroupjjr.com
13
28
005
CR
Worldwide Facilities Group
NEW SPD-1
PROJECTION
SCREEN
General Motors Corporation
110
Warren Technical Center Campus
Site ID: 1563
14
27
110
Structure ID: 4235
F
?
Level:
006
15
004
BASEMENT FLOOR POWER AND
AUXILIARY SYSTEMS PLAN
26
WFG PE/PM
WFG JOB NO
N. WEINGARTZ
16
25
24
23
22
21
20
19
18
17
DRAWN BY
1200912
SHEET NUMBER
Author
SCALE
1/8" = 1'-0"
DATE
22MAY13
FILE PLOT DATE STAMP
EP1−200
5/21/2013 12:16:40 PM
WFG JOB NO.
−
SHEET NO.
ROOM LEGEND
1
39
36
2
40
38
3
MOTORIZED SHADES
E236 NEW FA-BL21- 42
37
125
E248
CR
101
102
103
104
105
106
108
109
110
111
112
113
114
115
116
117
118
119
120
121
122
124
125
126
127A
127B
127C
127D
4
E248
J
CR
DC P
SD DC
NEW FA-BL21-40
DC
DC PSD
NEW FA-BL21-40
NEW LP-AV- 63 FB1
5
126
E218
75
E231 J
J
48"
NEW FA-BL12-3
E206
15
CR
F
15
DC
35
E249
E232
48"
E218
NEW FA-BL21- 44
FB2
NEW FA-BL13-7
15
CR
F
6
15
NEW FA-BL13-9
NEW LP-AV- 67
J
119
UP
NEW FA-BL12- 2
E219
E235
E235
106
WF
J
104
E219
TS
NEW LP-M-1E- 6
C.
UP
TS
D.
NEW FA-BL13- 2
105
M
M
E219
NEW LP-AV- 71
NEW FA-BL13
C
SE
CR
NEW LP-AV- 42
SEC
SEC
E219
DR
E243 NEW LP-AV- 42
127B
ELECTRICAL OUTLETS ON GREENROOM
WALLS SHALL BE MOUNTED
HORIZONTALLY IN BASE OF WALL U.O.N..
NEW FA-BL13- 3
NEW FA-BL13- 3
E243 NEW LP-AV- 38
E216
15
E206
NEW FA-BL13- 13
NEW LP-AV- 36
E224
E225
E219
BELOW STEPS
NEW FA-BL12- 8
H
E251
60"
30
E219
48"
C1
NEW FA-BL12-4
E209
CCTV
108
E209
E233
E233
NEW LP-AV- 68
HC
NEW FA-BL13- 10
J
NEW LP-AV- 70
L6-30R
CONNECT TO NEW 208V, 2P,
30A CIRCUIT BREAKER IN
PANEL 'FA-BP11A' VIA NEW
208-230V, 2P, 5KVA BUCKBOOST TRANSFORMER.
NEW FA-BL13-8
E224
L6-30R
J
C1
CCTV
DC
DC
30
E225
FEED VIA NEW 208-230V, 2P, 5KVA BUCKBOOST TRANSFORMER.
E240
111
ON CANOPY FACE
F
109
117
DC
DC
C2
116
F
CCTV
10
NEW FA-BL13- 13
ELECTRICAL/DATA/AV OUTLETS ON THIS
WALL SHALL BE MOUNTED
HORIZONTALLY IN BASE OF WALL U.O.N..
(TYP.)
60"
DC DC
HC
NEW FA-BL12- 8
48"
E251
ELECTRICAL/DATA/AV OUTLETS ON THIS
DN
WALL SHALL BE MOUNTED
HORIZONTALLY IN BASE OF WALL U.O.N..
NEW FA-BL13- 13
J
J
H
J
E237
HC
H CR 40"
K
C2
HC
CR
CCTV
J
DC
NEW FA-BL12- 6
101
E243 NEW LP-AV- 36
H H
30
DC
ON FACE OF CANOPY
E237
HC
31
40"
CR H
DC
HC
DC PSD
CCTV
K
C1
CR
J
60"
60"
IWH-1
NEW FA-BL13- 4,6
DR
15
C1
11
UNDERSIDE
OF CANOPY
FAAP
E203
DN
75
110
12
NEW FA-BP11
115
15
15
DN
E233 J
J
CR
E219
E219
J
E232
114
NEW FA-BP11- 26,28
NEW LP-AV- 68
J
E219
DN
NEW LP-AV- 68
NEW LP-AV- 68
J
J
E233
L6-30R
FEED VIA NEW 208-230V, 2P, 5KVA
BUCK-BOOST TRANSFORMER.
E232
E246
J
NEW LP-AV- 70
MOUNT BELOW PLATFORM. CONNECT
NEW DUPLEX RECEPTACLE TO EXISTING
ADJACENT 120V RECEPTACLE CIRCUIT.
13
15
DC
E246
CR
DC
DC
15
F
J
E219
J
E219
NEW LP-AV- 70
NEW LP-AV- 70
CR
J
113
D
PS
DC E247
CR
NEW FA-BP11-24
14
J
TV
CC
CC
TV
15
C3
E223
C3
CCTV
C3
26
16
25
24
23
22
21
20
19
18
17
E218 FLOORBOX 'FB1'. PROVIDE WIREMOLD CCBB
16"X12"X6"D SERIES. ROUTE (3) 1"C. BELOW
SLAB TO A/V MACHINE ROOM. ROUTE 3/4"C
BELOW SLAB TO ISOLATED GROUND PANEL
'LP-AV' FOR CIRCUITING AND 1"C. TO
ACCESSIBLE CEILING SPACE FOR DATA.
NO.
DEPT. MGR/SUPR
APPROVAL
CERTIFIED BY
SUPPLIER PROJECT NO.
22733.000
SUPPLIER DRAWN BY
SUPPLIER CHECKED BY
E224 MOUNT DOOR ACTIVATION SWITCH ON STEEL
COLUMN/MULLION. POWER/CONTROL
CABLING SHALL BE ROUTED WITHIN
COLUNM/MULLION. REFE RT OACCESS
CONTROL DOOR DETAIL NO.3 ON ELECTRICAL
DETAIL SHEET.
SUPPLIER PE/PM
CONSULTANT A/E
FIRM INFO & LOGO
SMITHGROUPJJR, INC
500 GRISWOLD SUITE 1700
DETROIT, MI 48226
T 313.983.3600 F 313.983.3636
www.smithgroupjjr.com
E233 PROVIDE 10"X10"X4"D JUNCTION BOX WITH
(3)1"C. TO A/V MACHINE ROOM. PROVIDE (1)
GM LAN CABLE/CONNECTION. COORDINATE
EXACT LOCATION IN FIELD.
E235 PROVIDE (2) SINGLE GANG JUNCTION BOXES,
EACH WITH 1"C. TO A/V MACHINE ROOM.
COORDINATE EXACT REQUIREMENTS WITH AV
SYSTEM CONTRACTOR. COORDINATE
LOCATION WITH ARCHITECTURAL PLANS.
E238 PROVIDE ELECTRONIC HORN SECURITY
NOTIFICATION APPLIANCE ON MULLION AT
CEILING.
E240 EXTEND EXISTING 208V, 30A, 2P CIRCUIT IN
CHAIR STORAGE RM 111 TO FEED NEW
RECEPTACLE INDICATED.
E242 EXISTING POWER RECEPTACLES BELOW
STEPS TO REMAIN. PROVIDE NEW DATA
OUTLETS IN SAME LOCATION.
E243 PROVIDE DESK TOP RECEPTACLE. CIRCUIT AS
INDICATED. COORDINATE LOCATION WITH
ARCHITECTURAL TRADES. SEE E0.1 SHEET
FOR MODEL.
E245 REFER TO ACCESS CONTROL DOOR DETAIL
NO.6 ON ELECTRICAL DETAILS SHEET.
E246 REFER TO ACCESS CONTROL DOOR DETAIL
NO.4 ON ELECTRICAL DETAILS SHEET.
E247 REFER TO ACCESS CONTROL DOOR DETAIL
NO.5 ON ELECTRICAL DETAILS SHEET.
E248 REFER TO ACCESS CONTROL DOOR DETAIL
NO.1 ON ELECTRICAL DETAILS SHEET.
E249 REFER TO ACCESS CONTROL DOOR DETAIL
NO.8 ON ELECTRICAL DETAILS SHEET.
E250 REFER TO ACCESS CONTROL DOOR DETAIL
NO.7 ON ELECTRICAL DETAILS SHEET.
E251 PROVIDE SINGLE GANG JUNCTION BOX WITH
1"C. TO A/V MACHINE ROOM. COORDINATE
EXACT REQUIREMENTS WITH AV SYSTEM
CONTRACTOR. COORDINATE LOCATION WITH
ARCHITECTURAL PLANS.
PROJECT ARCH/
ENGR APPROVAL
DATE
R E V I S I O N S
E219 PROVIDE SINGLE GANG JUNCTION BOX WITH
1"C. TO A/V MACHINE ROOM. PROVIDE (1) GM
LAN CABLE/CONNECTION. COORDINATE
EXACT REQUIREMENTS WITH AV SYSTEM
CONTRACTOR. COORDINATE LOCATION WITH
ARCHITECTURAL PLANS.
Worldwide Facilities Group
E236 PROVIDE POWER AND CONTROLS
CONNECTIONS FOR MOTORIZED SHADES.
COORDINATE CONTROLS WITH AV SYSTEM
CONTRACTOR. CIRCUIT AS INDICATED.
E237 PROVIDE NEW BI-DIRECTIONAL SURFACE
MOUNTED HANDICAP PUSHBUTTON CONTROL
ON STEEL COLUMN/MULLION.
POWER/CONTROL CABLING SHALL BE ROUTED
WITHIN COLUNM/MULLION.
110
110
27
112
DC
DC
MOUNT BELOW PLATFORM.
(TYP.)
DC
28
124
DC
E217 9.38"X10.85" BACKBOX FOR WALL MOUNTED
AV TOUCH PANEL PROVIDED BY OTHERS WITH
3/4"C. TO A/V MACHINE ROOM AND 1/2"C. TO
PROJECTION SCREEN FOR MOTORIZED
SCREEN CONTROL. COORDINATE
REQUIREMENTS WITH AV SYSTEM
CONTRACTOR. COORDINATE LOCATION WITH
ARCHITECTURAL PLANS.
E225 REFER TO ACCESS CONTROL DOOR DETAIL
NO.2 ON ELECTRICAL DETAILS SHEET.
E231 PROVIDE SINGLE GANG JUNCTION BOX
MOUNTED IN CEILING WITH 1/2"C. TO A/V
MACHINE ROOM FOR WIRELESS ACCESS
POINT.
E232 PROVIDE SINGLE GANG JUNCTION BOX FOR
PTZ CAMERA WITH 3/4"C. TO A/V MACHINE
ROOM AND ADJACENT ISOLATED GROUND
RECEPTACLE. COORDINATE EXACT LOCATION
WITH AV CONTRACTOR.
CR F
DC
CR
E245
E216 PROVIDE BLACK 2-CHANNEL WIREMOLD V4000
SERIES STEEL RACEWAY BELOW DESKTOP
FOR POWER/DATA. PROVIDE BLACK CABOFIL
CFG 50/200 STEEL 'G' TRAY. REFER TO
ARCHITECTURAL PLANS FOR MOUNTING
LOCATION. SEGMENT RACEWAY/'G' TRAY AS
REQUIRED FOR MOUNTING. CIRCUIT AS
INDICATED.
E223 PROVIDE SECURITY CAMERA ON ADJACENT
DESIGN CENTER BUILDING ROOF. PROVIDE
CONDUIT AND WIRING BACK TO SECOND
FLOOR SECURITY CLOSET. COORDINATE
EXACT MOUNTING LOCATION WITH OWNER
PRIOR TO INSTALLATION.
FA-BP11A
29
GM DISCLAIMER & TYPICAL NOTES
E209 RECESS MOUNT FIRE ALARM PULL STATION
BACKBOX WITHIN STEEL COLUMN. FIRE
ALARM CABLING SHALL BE ROUTED WITHIN
COLUNM.
E211 PROVIDE (6) SINGLE GANG JUNCTION BOXES
BELOW STEPS WITH 1"C. TO A/V MACHINE
ROOM FOR A/V EQUIPMENT. COORDINATE
EXACT REQUIREMENTS AND LOCATION WITH
AV SYSTEM CONTRACTOR.
NEW FA-BL13- 5
CCTV
E242
ER
HEAT
NEW LP-AV- 36
9
NEW FA-BL13- 5
DC DC
DR
E242
E250
NEW FA-BL13- 3
CR DC
NEW LP-AV- 38
J
60"
E219
60"
NOT
FOR
CON
STRU
CTIO
N
E203 PROVIDE FIRE ALARM ANNUNCIATOR PANEL.
COORDINATE EXACT LOCATION WITH OWNER
PRIOR TO INSTALLATION.
E206 PROVIDE SINGLE GANG JUNCTION BOX WITH
3/4"C. TO A/V MACHINE ROOM FOR LIGHTING
CONTROL. COORDINATE EXACT
REQUIREMENTS WITH AV SYSTEM
CONTRACTOR. COORDINATE LOCATION WITH
ARCHITECTURAL PLANS.
NEW FA-BL13- 3
127C
E242
30
UNDERSIDE
OF CANOPY
SITE/BUILDING PLAN & NORTH ARROW
127A
NEW LP-AV- 40
E238
COORDINATE FINAL LOCATION OF MECHANICAL
EQUIPMENT AND ASSOCIATED DISCONNECT SWITCHES,
STARTERS, VFDS, CONTROL POWER AND OTHER
POWER REQUIREMENTS WITH DIV 15.
SURFACE MOUNTED RACEWAY SHALL NOT BE UTILIZED
IN FINISHED AREAS WITHOUT ARCHITECT APPROVAL
U.O.N.
PROVIDE ALL NECESSARY CABLING FROM SECURITY
DEVICES (CAMERAS, DOOR HARDWARE, ETC...) BACK
TO NEW SECURITY PANELS.
COORDINATE MOUNTING HEIGHT AND LOCATION OF
NEW ELECTRICAL EQUIPMENT AND DEVICES WITH
ARCHITECTURAL PLANS PRIOR TO INSTALLTION.
PROVIDE SEPARATE ISOLATED GROUND CONDUCTOR
FOR EACH CIRCUIT FED FROM ISOLATED GROUND
PANEL 'LP-AV'.
KEYED NOTES
8
E250
NEW LP-AV- 40
NEW FA-BL12
DISPLAY AREA
BOARDROOM
JC
WOMEN'S WASH ROOM
WOMEN'S TOILET
MECH EQUIP ROOM
LOBBY
ENTRY
STAIR LOBBY
CHAIR STORAGE RM
CORRIDOR
PLATFORM
SERVICE ENTRY
MULTI-PURPOSE ROOM
LOBBY
ENTRY
COAT ROOM
MECH EQUIP ROOM
MEN'S TOILET
MEN'S WASH ROOM
JC
ELEVATOR
STAIR
STAIR
COPY ROOM/CIRCULATION
GREEN ROOM
CLOSET
SECURITY CLOSET
J
PROVIDE (3)2"C. BACK TO A/V MACHINE ROOM.
SAWCUT FLOOR AS REQUIRED. REFER TO
ARCHITECTURAL PLANS FOR DETAILS.
J
118
J
DC DC
NEW LP-AV- 42
UH-1
32
22MAY13 BIDS
UH-2
DC PSD
33
E.
NEW FA-BL13- 1
M
NEW FA-BL12- 1
B.
7
DN
EF-1
M
J
NEW LP-AV- 71
DC
DRY PIPE
COMPRESSOR
J
J
TS
121
M
EF-2
NEW LP-AV- 71
NEW LP-AV- 69
J
TS
E211
NEW LP-AV- 69
DN
A.
30
30
NEW LP-AV- 69
DEPT. MGR/SUPR
APPROVAL
NEW FA-BL13-7
NEW LP-AV- 67
120
PROJECT ARCH/
ENGR APPROVAL
ISSUED FOR
SHEET NOTES
E232
122
NEW FA-BL12-3
E217
E249
(1)3/4"C,
(1)1-1/4"C.
(1)3/4"C,
(1)1-1/4"C.
J
NEW FA-BL13-9
NEW LP-AV- 65 FB1
MOTORIZED SCREEN
NEW LP-AV- 61
NEW FA-BL21- 44
FB2
ELTD
NEW FA-BL12-5
34
UP
102
J
NEW FA-BL12-5
DC
UP
DATE
General Motors Corporation
Warren Technical Center Campus
Site ID: 1563
Structure ID: 4235
Level:
FIRST FLOOR POWER AND
AUXILIARY SYSTEMS PLAN
WFG PE/PM
WFG JOB NO
N. WEINGARTZ
DRAWN BY
1200912
SHEET NUMBER
Author
SCALE
1/8" = 1'-0"
DATE
22MAY13
FILE PLOT DATE STAMP
EP1−201
5/21/2013 12:16:51 PM
WFG JOB NO.
−
SHEET NO.
ROOM LEGEND
1
39
36
201
202
203
2
40
38
4
PROVIDE RACK GROUNDING
PROJECTOR LIFT
E201
(R)DWH-1
35
NEW FA-BL21-6
RC-1
M CP-3
NEW FA-L21- 2,4,6
NEW FA-BL21- 11,13
J
J
NEW LP-M-1E
NEW LP-AV
J
E215
1,3,5,7,9,11
2,4,6,8,74,76
E226
T
201
DN
(TYP.)
CP-1
M
NEW FA-BL21- 6
T
30
NEW FA-BL22- 2
RC-2
B.
RELOCATED
T-LP-AV
ATS-2
F
M
30
J
F
UH-4
CP-4
M
J
C.
GROUND BAR
UP T0 (E)EF-4
E205
CP-2
NEW FA-L22- 1,3,5
SAF-AHU-2
E212
E213
MOTOIZED SCREEN
NEW LP-AV- 72
DN
NEW FA-BL21- 7
J
J
E214
J
E211
J
KEYED NOTES
RAF-AHU-2
7
AHU LIGHTS
NEW FA-BL22- 4
E204
J
DN
185
185
NEW FA-BL22- 8
E202 FIRE ALARM DEVICE SHALL BE MOUNTED
AT UNDERSIDE OF DOME RIM SOFFIT.
COORDINATE EXACT LOCATION WITH
LIGHT FIXTURES AND SPRINKLER HEADS
MOUNTED ON SAME SURFACE.
UH-3
NEW FA-BL21- 23
E204
E201 COORDINATE EXACT VFD LOCATION WITH
MECHANICAL PLANS AND MECHANICAL
TRADES PRIOR TO INSTALLATION.
PROVIDE INTERCONNECTING WIRING
BETWEEN VFD AND MOTOR(S) AS
REQUIRED.
NEW FA-BL22- 6
NEW FA-BL22- 8
NEW FA-BL21- 23
AHU LIGHTS
E244
E201
E214
30
NEW FA-BL21- 8,10,12
33
E241
E241
3/4"C. TO A/V MACHINE ROOM
J
J
TV
CC
NEW LP-AV- 30
NEW FA-BL22- 15,17,19
NEW LP-AV- 32
TV
CC
C2
C2
(TYP.)
32
9
NEW FA-BL22- 10
FPB-2
NEW FA-BL21- 15
DC
3/4"C.
(TYP.)
R1
E202
(TYP.)
R2
CKTS 12,14,16
185
CKTS 21,23,25,27,29
E207
R1
NEW FA-BL21- 19
R1
NEW FA-BL22- 12
10
(TYP.)
R2
R2
CKTS 24,26,28
E241
185
(TYP.)
LP-RING-41 & 43
CKTS 2,4,6,8,10
31
E202
CKTS 11,13,15,17,19
CKTS 13,15,17
R1
R1
E241
J
CKTS 31,33,35,37,39
NEW LP-AV- 32
NEW LP-AV- 30
CKTS 22,24,26,28,30
30
NEW FA-BL22- 12
CKTS 19,21,23
LP-RING-42 & 44
NEW FA-BL21- 19
R1
R2
E221
(TYP.)
UP
11
CKTS 45,47,49,51,53
CKTS 32,34,36,38,40
CKTS 18,20,22
CKTS 46,48,50,52,54
R1
R1
E222
(TYP.) E221
(TYP.)
NEW FA-BL22- 14
12
29
NEW FA-BL21- 17
3/4"C.
(TYP.)
NEW FA-BL22- 14
TV
CC
NEW FA-BL21- 17
E241
J
J
NEW LP-AV- 30
C2
CC
TV
C2
E241
13
NEW LP-AV- 32
28
185
120V CKTS 44,46,48,50
208V CKTS 52,54 & 56,58 & 60,62 & 64,66
185
NEW FA-BL22- 16
E214
NEW FA-BL21- 21
NEW LP-AV- 73
MOTORIZED
SCREEN
NEW LP-AV- 34
9
9
9
11
27
11
13
J
J
13
15 15
15
NEW FA-BP11- 4
15
17
17
E227
17 19
25
27
27
27
27
25
14
23
NEW FA-BP11- 6
17
E227
NEW FA-BP11- 8 NEW FA-BP11- 12
NEW FA-BP11- 10
E227
3/4"C.
(TYP.)
3/4"C. TO A/V MACHINE ROOM
J
J
E227
J
E227
NEW FA-BP11- 2
E210
J
E210
E211
E227
NEW FA-BL22- 16
19
19
19
21
21
21 21
23
E228
(TYP.)
NEW FA-BP11- 20
NEW FA-BP11- 14
15
NEW FA-BP11- 20
NEW FA-BP11- 14
NEW FA-BP11- 16
(TYP.)
26
NEW FA-BP11- 18
NEW FA-BP11- 16
16
NO.
PROJECT ARCH/
ENGR APPROVAL
DATE
CERTIFIED BY
SUPPLIER PROJECT NO.
22733.000
SUPPLIER DRAWN BY
SUPPLIER CHECKED BY
SUPPLIER PE/PM
CONSULTANT A/E
FIRM INFO & LOGO
SMITHGROUPJJR, INC
500 GRISWOLD SUITE 1700
DETROIT, MI 48226
T 313.983.3600 F 313.983.3636
www.smithgroupjjr.com
Worldwide Facilities Group
General Motors Corporation
Warren Technical Center Campus
Site ID: 1563
E227 RECEPTACLE SHALL BE MOUNTED WITHIN
UPPER MEZZANINE SPACE FOR TYPE 'L1'
LIGHT FIXTURE POWER. COORDINATE
EXACT LOCATION IN FIELD. CIRCUIT VIA
LIGHTING RELAY PANEL TO CIRCUIT
INDICATED.
Structure ID: 4235
Level:
E228 PROVIDE PERFORMANCE ELECTRIC
MODEL# PPBD-2-520R (OR EQUAL BY
OTHERS) PIPE MOUNTED BOX. MOUNT
BOX WITH RECEPTACLE ORIENTED
TOWARD CEILING. VERIFY COLOR
CUSTOM REQUIREMENTS WITH
ARCHITECT. DAISY CHAIN RECEPTACLE
BOXES TO MINIMIZE CONDUIT RUNS.
COORDINATE ROUTING WITH SGJJR
ELECTRICAL ENGINEER. CIRCUIT
NUMBERS SHOWN ARE FROM
PANELBOARD 'FA-BP11' VIA RELAY PANEL.
E244 PROVIDE 120V POWER AND DATA
CONNECTION FOR NEW DDC CONTROLS
DEVICES AS REQUIRED. COORDINATE
LOCATION WITH MECHANICAL TRADES.
PROVIDE POWER FROM NEAREST 120V
PANELBOARD SERVING AREA.
DEPT. MGR/SUPR
APPROVAL
R E V I S I O N S
E222 TYPE 'R2' MULTI-OUTLET ASSEMBLY,
PROVIDE WIREMOLD 2400 SERIES
RACEWAY. MOUNT TO TOPSIDE OF
BOTTOM PAN OF SUSPENDED RING
TRUSS STRUCTURE FOR A/V POWER.
REFER TO ELECTRICAL DETAILS SHEETS
FOR RING A/V RACEWAY DIAGRAM.
CIRCUIT NUMBERS SHOWN ARE FROM
PANELBOARD 'LP-AV' U.O.N.. CIRCUIT AS
INDICATED.
E229 PROVIDE FINAL CONNECTION TO TYPE 'L5'
LIGHT FIXTURES AS REQUIRED. REFER TO
RING LIGHTING DETAIL ON ELECTRICAL
DETAILS SHEET. CIRCUIT AS INDICATED.
E241 PROVIDE TWO GANG JUNCTION BOX IN
UPPER MEZZANINE FOR SPEAKER.
COORDINATE EXACT REQUIREMENTS AND
LOCATION WITH AV SYSTEM
CONTRACTOR AND ARCHITECTURAL
DRAWINGS.
NEW FA-BP11- 18
E207
E221 TYPE 'R1' MULTI-OUTLET ASSEMBLY,
PROVIDE WIREMOLD 2400 SERIES
RACEWAY. MOUNT TO TOPSIDE OF
BOTTOM PAN OF SUSPENDED RING
TRUSS STRUCTURE FOR LIGHTING
POWER. REFER TO ELECTRICAL DETAILS
SHEETS FOR RING LIGHTING RACEWAY
DIAGRAM. PROVIDE (2)2"FMC CONDUITS
WITHIN EACH STRUCTURAL CEILING
SUPPORT PIPE TO ACCOMMODATE
POWER AND LOW VOLTAGE
CONDUCTORS. DERATE POWER
CONDUCTORS AS REQUIRED.CIRCUIT
NUMBERS SHOWN ARE FROM
PANELBOARD 'LP-RING' U.O.N.. CIRCUIT
VIA LIGHTING RELAY PANEL.
E226 PROVIDE POWER CONNECTION (2-120V
CIRCUITS PER BOX) TO 6"X6" JUNCTION
BOX MOUNTED ON TOP OF EACH AV
RACK. COORDINATE EXACT LOCATION
WITH A/V CONTRACTOR. PROVIDE
ISOLATED GROUND FOR EACH CIRCUIT.
CONNECT TO NEW 'LP-AV' CIRCUITS AS
INDICATED.
E214
E213
J
E210
NEW LP-AV- 34
NEW FA-BL21- 21
E212
J
9
NEW LP-AV- 34
E214 PROVIDE JUNCTION BOX FOR 208V, 3PH
PROJECTOR POWER CONNECTION.
COORDINATE EXACT REQUIREMENTS AND
LOCATION WITH AV SYSTEM
CONTRACTOR. REFER TO ONE LINE
DIAGRAM AND PANEL SCHEDULES FOR
CIRCUITING DETAILS.
E215 PROVIDE 12" WIDE ALIUMINUM LADDER
TRAY MOUNTED ABOVE AV RACKS AT
90"A.F.F. WITH (3)2"C. FROM END OF
LADDER RACK TO CONTROL CONSOLE.
COORDINATE EXACT REQUIREMENTS AND
LOCATION WITH AV SYSTEM
CONTRACTOR.
R2
R1
E212 PROVIDE 12"X12"X4" BACKBOX TO
CONTAIN (4) 208V, 20A L6-20R
RECEPTACLES AND (4) 120V POWER
CONNECTIONS (ALL ISOLATED GROUND
CIRCUITS) FOR A/V EQUIPMENT.
COORDINATE EXACT REQUIREMENTS AND
LOCATION WITH AV SYSTEM
CONTRACTOR. CIRCUIT TO PANELBOARD
'LP-AV' AS INDICATED.
E213 PROVIDE 10"X10"X4" BACKBOX WITH
1-1/2"C. TO A/V MACHINE ROOM FOR A/V
EQUIPMENT. COORDINATE EXACT
REQUIREMENTS AND LOCATION WITH AV
SYSTEM CONTRACTOR.
J
CKTS 12,14,16,18,20
E210 PROVIDE SINGLE GANG JUNCTION BOX IN
UPPER MEZZANINE FOR SPEAKER.
COORDINATE EXACT REQUIREMENTS AND
LOCATION WITH AV SYSTEM
CONTRACTOR AND ARCHITECTURAL
DRAWINGS.
E211 PROVIDE (6) SINGLE GANG JUNCTION
BOXES BELOW STEPS WITH 1"C. TO A/V
MACHINE ROOM FOR A/V EQUIPMENT.
COORDINATE EXACT REQUIREMENTS AND
LOCATION WITH AV SYSTEM
CONTRACTOR.
R1
CKTS 1,3,5,7,9
GM DISCLAIMER & TYPICAL NOTES
E205 PROVIDE UNISTRUT STRUCTURE TO
MOUNT NEW ELECTRICAL EQUIPMENT AT
OUTER DOME WALL.
E207 RECEPTACLE SHALL BE MOUNTED WITHIN
LIGHT COVE FOR TYPE 'L3' LIGHT FIXTURE
POWER. COORDINATE EXACT LOCATION
IN FIELD. CIRCUIT VIA LIGHTING RELAY
PANEL TO CIRCUIT INDICATED.
FPB-1
NEW FA-BL21- 15
E207
NOT
FOR
CON
STRU
CTIO
N
E204 PROVIDE ELECTRICAL CONNECTIONS
BETWEEN AIR HANDLING UNIT SECTIONS
DURING INSTALLATION AS REQUIRED.
COORDINATE EXACT REQUIREMENTS
WITH MECHANICAL TRADES.
8
3/4"C. TO A/V MACHINE ROOM
NEW FA-BL22- 10
COORDINATE FINAL LOCATION OF MECHANICAL
EQUIPMENT AND ASSOCIATED DISCONNECT SWITCHES,
STARTERS, VFDS, CONTROL POWER AND OTHER
POWER REQUIREMENTS WITH DIV 15.
SURFACE MOUNTED RACEWAY SHALL NOT BE UTILIZED
IN FINISHED AREAS WITHOUT ARCHITECT APPROVAL
U.O.N.
PROVIDE ALL NECESSARY CABLING FROM SECURITY
DEVICES (CAMERAS, DOOR HARDWARE, ETC...) BACK
TO NEW SECURITY PANELS.
COORDINATE MOUNTING HEIGHT AND LOCATION OF
NEW ELECTRICAL EQUIPMENT AND DEVICES WITH
ARCHITECTURAL PLANS PRIOR TO INSTALLTION.
PROVIDE SEPARATE ISOLATED GROUND CONDUCTOR
FOR EACH CIRCUIT FED FROM ISOLATED GROUND
PANEL 'LP-AV'.
SITE/BUILDING PLAN & NORTH ARROW
M
VF
D
SAF-AHU-1
120V CKTS 37,39,41,43
208V CKTS 45,47 & 49,51 & 53,55 & 57,59
203
D
VF
VF
D
E201
22MAY13 BIDS
A/V MACHINE ROOM
MECH EQUIP ROOM
MECH EQUIP ROOM
NEW FA-L22- 2,4,6
D
VF
E244
E.
202
UP
RAF-AHU-1
34
6
NEW FA-L22
NEW FA-BL22
NEW FA-BL21- 6
NEW FA-BL22- 2
D.
NEW FA-L22- 13,15,17
(TYP.)
M
(TYP.) UP
NEW FA-L21- 1,3,5
A.
5
T-LP-M
30
F
NEW FA-BL21- 9
DN
J
F
VFD
E205
PROVIDE (3) ANALOG PHONE
LINES PER VOICE JUNCTION BOX
NEW LP-AV- 10
PROJECTOR
NEW FA-BL21- 39,41,43
NEW FA-L21
NEW FA-BL21
DEPT. MGR/SUPR
APPROVAL
SHEET NOTES
GROUND BAR
FC-1
PROJECT ARCH/
ENGR APPROVAL
ISSUED FOR
3
37
GROUND BAR
DATE
MEZZANINE FLOOR POWER
AUXILIARY SYSTEMS PLAN
WFG PE/PM
WFG JOB NO
N. WEINGARTZ
DRAWN BY
1200912
SHEET NUMBER
Author
SCALE
1/8" = 1'-0"
25
24
23
22
21
20
19
18
17
DATE
22MAY13
FILE PLOT DATE STAMP
EP1−202
5/21/2013 12:17:01 PM
WFG JOB NO.
−
SHEET NO.
SHEET NOTES
A.
1
39
36
2
B.
40
38
3
C.
D.
E.
37
4
DATE
PROJECT ARCH/
ENGR APPROVAL
ISSUED FOR
DEPT. MGR/SUPR
APPROVAL
22MAY13 BIDS
COORDINATE FINAL LOCATION OF MECHANICAL
EQUIPMENT AND ASSOCIATED DISCONNECT SWITCHES,
STARTERS, VFDS, CONTROL POWER AND OTHER
POWER REQUIREMENTS WITH DIV 15.
SURFACE MOUNTED RACEWAY SHALL NOT BE UTILIZED
IN FINISHED AREAS WITHOUT ARCHITECT APPROVAL
U.O.N.
PROVIDE ALL NECESSARY CABLING FROM SECURITY
DEVICES (CAMERAS, DOOR HARDWARE, ETC...) BACK
TO NEW SECURITY PANELS.
COORDINATE MOUNTING HEIGHT AND LOCATION OF
NEW ELECTRICAL EQUIPMENT AND DEVICES WITH
ARCHITECTURAL PLANS PRIOR TO INSTALLTION.
PROVIDE SEPARATE ISOLATED GROUND CONDUCTOR
FOR EACH CIRCUIT FED FROM ISOLATED GROUND
PANEL 'LP-AV'.
5
110
KEYED NOTES
110
35
E239 DISCONNECT POWER FROM EXISTING
WENCH UTILIZED TO RAISE AND LOWER
ITEMS FROM THE DOME CEILING. WENCH
SHALL BE REFURBISHED OR REPLACED
BY MECHANICAL TRADES. RECONNECT TO
EXISTING CIRCUIT UPON REINSTALLTION.
REPAIR OR REPLACE CONTROLS AS
NECESSARY.
6
SITE/BUILDING PLAN & NORTH ARROW
34
NOT
FOR
CON
STRU
CTIO
N
7
110
GM DISCLAIMER & TYPICAL NOTES
110
33
8
32
9
31
110
10
T-LP-RING
LP-RING
T
E239
(E)EF-4
NO.
30
11
110
PROJECT ARCH/
ENGR APPROVAL
DATE
DEPT. MGR/SUPR
APPROVAL
R E V I S I O N S
CERTIFIED BY
SUPPLIER PROJECT NO.
22733.000
SUPPLIER DRAWN BY
SUPPLIER CHECKED BY
SUPPLIER PE/PM
12
29
CONSULTANT A/E
FIRM INFO & LOGO
SMITHGROUPJJR, INC
500 GRISWOLD SUITE 1700
DETROIT, MI 48226
T 313.983.3600 F 313.983.3636
www.smithgroupjjr.com
13
28
Worldwide Facilities Group
110
General Motors Corporation
110
Warren Technical Center Campus
Site ID: 1563
14
27
Structure ID: 4235
Level:
15
110
UPPER MEZZANINE FLOOR
POWER AUXILIARY SYSTEMS
PLAN
26
WFG PE/PM
WFG JOB NO
N. WEINGARTZ
DRAWN BY
1200912
SHEET NUMBER
Author
16
SCALE
1/8" = 1'-0"
25
24
23
22
21
20
19
18
17
DATE
22MAY13
FILE PLOT DATE STAMP
EP1−203
5/21/2013 12:17:09 PM
WFG JOB NO.
−
SHEET NO.
ROOM LEGEND
1
39
36
2
40
38
37
121
EMERGENCY
LIGHTING (1 ROW)
NEW LP-M-1E-8
101
102
103
104
105
106
108
109
110
111
112
113
114
115
116
117
118
119
120
121
122
124
125
126
127A
127B
127C
127D
3
4
EMERGENCY
LIGHTING (1 ROW)
NEW LP-M-1E-8
E331
(TYP.)
WEST FIXTURES TO
NEW LP-BL22-18
EAST FIXTURES TO
NEW LP-BL22-20
5
E313
E310
L12 (TYP.)
L14
UP
E310
DT
E311
35
L13
(TYP.)
F5
(TYP.)
126
125
(TYP.) L12
L6B
L11 (TYP.)
E309
L13
(TYP.)
34
E310
L12 (TYP.)
DT
NEW FA-BL13- 11
L16
L16
102
EM
DT
L11
A.
(TYP.)
L13
(TYP.)
104
E311
120
105
E311
E323
DN
EL
TD
7
DN
UP
B.
C.
UP
D.
119
106
E.
3
33
F.
OS
127A
CONNECT TYPE 'L17' LIGHT FIXTURE TO
GENERAL USE 120V, RECEPTACLE CIRCUIT
SERVING EXISTING RECEPTACLES
MOUNTED BELOW STEPS (TYP.)
127C
NEW FA-BL13- 11
F6
EM/NL
L22
J J
(TYP.)
NEW FA-BL21-37
E319
101
L6A
E317 NEW LP-M-1E- 4
(TYP.)
NEW FA-BL21-38
K
31
3
D D NEW FA-BL12- 7
E319
NEW FA-BL21- 38
(TYP.)
NEW FA-BL21- 37
DN
E309
E317
L6A
NEW LP-M-1E- 2
L7
(TYP.)
10
L7
NEW FA-BL21-37
116
EM-NL
(TYP.)
4
EM-NL
4
109
117
L6A (TYP.)
NEW FA-BL21-38
EM-NL
E308
30
L7
L9
L7
EM-NL
L22
(TYP.)
F2
E326
(TYP.)
DT
NEW FA-BL21-37
NEW FA-BL13- 12
LRP
(TYP.)
L6C
E312
(TYP.)
111
L22
EM-NL
11
K
(TYP.)
E312
DN
E323
E328
110
12
ELT
D
DT
115
114
NEW FA-BP11- 7
28
112
DT
DT
DN
DN
E301
13
DT
E327
E327
DT
E301
14
E319
NEW FA-BP11- 22
J
113
NEW LP-M-1E- 7
J
27
E317
15
E308
L8 L10
(TYP.)
GM DISCLAIMER & TYPICAL NOTES
E311 FIXTURE TYPE L13 TO BE SURFACE
MOUNTED WITHIN ARCHITECTURAL COVE.
SEE A9 SERIES DRAWINGS FOR DETAIL.
CONTINUE FINISHED WALL TREATMENT
INTO CEILING COVE CAVITY. TYPICAL FOR
ALL L13 FIXTURES.
E312 FIXTURE TYPE L22 TO BE SURFACE
MOUNTED TO CONCRETE FOOTER. SEE A9
SERIES DRAWINGS FOR DETAIL. TYPICAL
FOR ALL L22 FIXTURES.
E313 FIXTURE TYPE L14 TO BE SURFACE
MOUNTED WITHIN ARCHITECTURAL
CAVITY TO UNIFORMLY BACKLIGHT
DIFFUSE MATERIAL. SEE A9 SERIES
DRAWINGS FOR MOUNTING DETAIL.
TYPICAL FOR ALL F14 FIXTURES.
CONCEAL DATA ENABLER IN ACCESIBLE
LOCATION.
NO.
E306
DEPT. MGR/SUPR
APPROVAL
R E V I S I O N S
CERTIFIED BY
SUPPLIER PROJECT NO.
22733.000
SUPPLIER DRAWN BY
SUPPLIER CHECKED BY
SUPPLIER PE/PM
CONSULTANT A/E
E317 JUNCTION BOX FOR TYPE L7/L8 LIGHT
FIXTURES, MOUNT JUNNCTION BOX
HIDDEN IN COVE. REFER TO COVE
EMERGENCY LIGHTING DETAIL ON
ELECTRICAL DETAILS SHEET.
COORDINATE WITH LIGHTING CONTROLS
CONTRACTOR. UTILIZE CIRCUIT
INDICATED.
FIRM INFO & LOGO
SMITHGROUPJJR, INC
500 GRISWOLD SUITE 1700
DETROIT, MI 48226
T 313.983.3600 F 313.983.3636
www.smithgroupjjr.com
Worldwide Facilities Group
E323 PROVIDE ONE EMERGENCY LOAD
TRANSFER DEVICE (ELTD) FOR EACH
SWITCHED CIRCUIT FOR EXISTING STAIR
LIGHTING. CONNECT EMERGENCY SIDE OF
ELTD TO SPARE 20A CIRCUIT BREAKER IN
PANEL BOARD 'LP-M-1E'. CONNECT
NORMAL SIDE TO EXISTING NORMAL
CIRCUIT. VERIFY QUANTITY AND
LOCATION IN FIELD.
E325 CONNECT EMERGENCY/NIGHT LIGHT TO
PANELBOARD LP-M-1E CIRCUIT AS
INDICATED.
E326 PROVIDE KEY SWITCH FOR CONTROL OF
LOBBY AND CANOPY LIGHT FIXTURES.
CIRCUIT AS INDICATED.
E327 DISCONNECT EXISTING LIGHT FIXTURE
FROM EXISTING NORML CIRCUIT.
CONNECT EXISTING FIXTURE LIFE SAFETY
LIGHTING CIRCUIT SERVING ADJACENT
AREA. FIXTURE SHALL FUNCTION AS
NIGHTLIGHT.
PROJECT ARCH/
ENGR APPROVAL
DATE
E319 JUNCTION BOX FOR TYPE L9/L10 LIGHT
FIXTURE, MOUNT JUNCTION BOX HIDDEN
IN COVE. COVE LIGHTING DETAIL NO.3 ON
ELECTRICAL DETAILS SHEET.
COORDINATE WITH LIGHTING CONTROLS
CONTRACTOR. UTILIZE CIRCUITS
INDICATED.
124
E301
NOT
FOR
CON
STRU
CTIO
N
E308 FIXTURE TYPES L7, L8, L9 AND L10 TO BE
SURFACE MOUNTED TO ANGLED BRACKET
WITHIN COVE SO THAT NO DIRECT VIEW
OF FIXTURE IS POSSIBLE. SEE A9 SERIES
DRAWINGS FOR MOUNTING DETAIL.
PROVIDE 2 BRACKETS PER FIXTURE.
MOUNT ALL FIXTURES IN CROSS SECTION
TO SAME ANGLED MOUNTNG BRACKET.
SPACE FIXTURES EVENLY WITHIN
FIXTURE RUN SO THERE ARE NO UNLIT
SECTIONS. TYPICAL FOR ALL L7, L8, L9
AND L10 FIXTURES WITHIN CENTER DOME
COVE, ENTRY COVE, AND STAGE COVE.
E310 FIXTURE TYPE L12 INCLUDES VANITY
MIRROR WITH INTEGRAL LIGHTING
COMPONENT. SEE A9 SERIES DRAWINGS
FOR MOUNTING DETAIL. TYPICAL FOR ALL
L12 FIXTURES.
L7
NEW FA-BL21-37 L6A
E309
NEW FA-BL21-38
L6A (TYP.)
29
E325
(TYP.)
E308
L7 L9
(TYP.)
(TYP.)
NEW FA-BL21-38
SITE/BUILDING PLAN & NORTH ARROW
E309 FIXTURE TYPE L6A AND L6B TO BE TRACK
MOUNTED. SEE A9 SERIES DRAWINGS
FOR TRACK MOUNTING CONDITION. SEE
PLANS FOR TRACK LENGTH. TYPICAL FOR
ALL L6A AND L6B FIXTURES.
108
L6A
(TYP.)
NEW FA-BL21-37
K
(TYP.)
L11B
(TYP.)
EM-NL
L11B
(TYP.)
L11A
(TYP.)
L11A
E325
CONNECT CEILING MOUNTED OCCUPANCY SENSORS
TO POWER PACKS WITH LOW VOLTAGE WIRING.
PROVIDE NUMBER OF POWER PACKS
RECOMMENDED BY MANUFACTURER. COORDINATE
COMPATABILITY WITH LIGHTING CONTACTORS OR
INDICATED SWITCHES. REFER TO MANUFACTURER
WIRING DIAGRAMS.
REFER TO ARCH. REFLECTED CEILING PLANS FOR
EXACT LOCATION OF LIGHT FIXTURES AND OTHER
CEILING MOUNTED DEVICES.
PROVIDE SEPARATE NEUTRALS FOR DIMMING
CIRCUITS.
POWER TO DMX CONTROLLED LIGHT FIXTURES
SHALL BE VIA RELAY PANELS AS INDICATED ON
PANELBOARD PANEL SCHEDULES.
FOR LIGHT FIXTURES SPECIFIED WITH PLUG AND
CORD, REFER TO POWER PLANS FOR RECEPTACLE
AND CIRCUITING INFORMATION AND LOCATION.
COORDINATE MOUNTING HEIGHT AND LOCATION OF
NEW DEVICES WITH ARCHITECTURAL PLANS PRIOR
TO INSTALLTION.
PROVIDE NEW LED SCREW-IN TYPE LAMPS FOR
EXISITNG TO REMAIN INCANDESCENT LIGHT
FIXTURES.
E306 FIXTURE TYPE L3 TO BE SURFACE
MOUNTED AND CENTERED WITHIN
ARCHITECTURAL CAVITY SO THAT
FIXTURE HAS UNIMPEDED FULL RANGE OF
MOTION. SEE A9 SERIES DRAWINGS FOR
MOUNTING DETAIL. TYPICAL FOR ALL L3
FIXTURES.
E312
NEW FA-BL13- 11
J J
L22
EM-NL
4
NEW FA-BL13- 11
9
F6A
(TYP.)
K
NEW FA-BL21-38
EM-NL
4
127B
118
E326
DISPLAY AREA
BOARDROOM
JC
WOMEN'S WASH ROOM
WOMEN'S TOILET
MECH EQUIP ROOM
LOBBY
ENTRY
STAIR LOBBY
CHAIR STORAGE RM
CORRIDOR
PLATFORM
SERVICE ENTRY
MULTI-PURPOSE ROOM
LOBBY
ENTRY
COAT ROOM
MECH EQUIP ROOM
MEN'S TOILET
MEN'S WASH ROOM
JC
ELEVATOR
STAIR
STAIR
COPY ROOM/CIRCULATION
GREEN ROOM
CLOSET
SECURITY CLOSET
E301 PROVIDE NEW OCCUPANCY SENSOR FOR
AUTOMATIC CONTROL OF EXISTING
LIGHTING WITHIN THIS SPACE. EXISTING
MANUAL LIGHTING CONTROLS SHALL
REMAIN.
CONNECT EMERGENCY/NIGHT LIGHT
LIGHT TO 120V LIFE SAFETY CIRCUIT
FEEDING ADJACENT ENTRY.
D
F3
(TYP.)
NEW FA-BL12- 9
22MAY13 BIDS
KEYED NOTES
OS
(TYP.)
32
G.
F4
F4
DT
E312
8
NEW FA-BL13- 11
L17
(TYP. OF 6)
DEPT. MGR/SUPR
APPROVAL
SHEET NOTES
E311
NEW LP-M-1E-8
NEW LP-M-1E-8
PROJECT ARCH/
ENGR APPROVAL
ISSUED FOR
6
L13
NEW FA-BL12- 7
EM
E310
E329
(TYP.)
ELTD
DT
F5 L12 (TYP.)
UP
DATE
General Motors Corporation
Warren Technical Center Campus
Site ID: 1563
Structure ID: 4235
Level:
E328 PROVIDE ETC SMARTSWITCH RELAY
PANELS TO ACCOMMODATE DMX
LIGHTING CIRCUITS FED FROM 'FA-BP11'.
REFER TO PANEL SCHEDULES FOR
QUANTITY REQUIRED. PROVIDE 25%
SPARE RELAY CAPACITY. COORDINATE
MOUNTING LOCATION IN FIELD. CONNECT
TO SPARE 20A, 1P CIRUIT BREAKER FROM
'FA-BP11' FOR RELAY PANEL CONTROL
POWER.
FIRST FLOOR LIGHTING PLAN
E329 FIXTURE TYPE F5 TO BE RECESSED IN
WALL TO BACKLIGHT TRANSLUCENT PANE
IN MIRROR. SEE ARCHITECTURAL
DRAWING AE4-712 DRAWINGS FOR DETAIL
AND EXACT MOUNTING LOCATION.
TYPICAL FOR ALL F5 FIXTURES.
L3
(TYP.)
26
16
E331 BOARDROOM LIGHT FIXTURES SHALL BE
CONTROLLED VIA LOCAL LIGHTING
CONTROLS IN CONJUNCTION WITH DMX
CONTROL PROVIDED BY OTHERS.
COORDINATE INTERCONNECTING WIRING
REQUIREMENTS WITH AV CONTRACTOR.
WFG PE/PM
WFG JOB NO
N. WEINGARTZ
DRAWN BY
1200912
SHEET NUMBER
Author
SCALE
1/8" = 1'-0"
DATE
25
24
23
22
21
20
19
18
17
22MAY13
FILE PLOT DATE STAMP
EL1−301
5/21/2013 12:16:17 PM
WFG JOB NO.
−
SHEET NO.
ROOM LEGEND
1
39
36
201
202
203
2
40
38
4
B.
C.
D.
5
E.
201
ELTD
ELTD
35
F.
DN
G.
E323
E324
E324
E322
E318
34
CONNECT CEILING MOUNTED OCCUPANCY SENSORS
TO POWER PACKS WITH LOW VOLTAGE WIRING.
PROVIDE NUMBER OF POWER PACKS
RECOMMENDED BY MANUFACTURER. COORDINATE
COMPATABILITY WITH LIGHTING CONTACTORS OR
INDICATED SWITCHES. REFER TO MANUFACTURER
WIRING DIAGRAMS.
REFER TO ARCH. REFLECTED CEILING PLANS FOR
EXACT LOCATION OF LIGHT FIXTURES AND OTHER
CEILING MOUNTED DEVICES.
PROVIDE SEPARATE NEUTRALS FOR DIMMING
CIRCUITS.
POWER TO DMX CONTROLLED LIGHT FIXTURES
SHALL BE VIA RELAY PANELS AS INDICATED ON
PANELBOARD PANEL SCHEDULES.
FOR LIGHT FIXTURES SPECIFIED WITH PLUG AND
CORD, REFER TO POWER PLANS FOR RECEPTACLE
AND CIRCUITING INFORMATION AND LOCATION.
COORDINATE MOUNTING HEIGHT AND LOCATION OF
NEW DEVICES WITH ARCHITECTURAL PLANS PRIOR
TO INSTALLTION.
PROVIDE NEW LED SCREW-IN TYPE LAMPS FOR
EXISITNG TO REMAIN INCANDESCENT LIGHT
FIXTURES.
KEYED NOTES
UP
NEW FA-BL21-18 & 20
SITE/BUILDING PLAN & NORTH ARROW
E307
L9 L7
(TYP.)
E302
J
202
203
7
L7
DN
DN
J
L3
(TYP.)
E308 L7
L9 L10 (TYP.)
L8
E306
J
FIXTURE TYPES L1, L2 AND L6 TO BE
C-CLAMP MOUNTED TO THEATRICAL PIPE
AND SECURED WITH SAFETY CABLE. SEE
A9 SERIES DRAWINGS FOR MOUNTING
DETAIL. TYPICAL FOR ALL L1, L2 AND L6
FIXTURES MOUNTED ON STAGE
THEATRICAL PIPE.
E304
FIXTURE TYPE L1 TO BE C-CLAMP
MOUNTED TO THEATRICAL PIPE ABOVE
CATWALK AND SECURED WITH SAFETY
CABLE. TYPICAL FOR ALL L1 FIXTURES
MOUNTED ABOVE CATWALK.
E305
FIXTURE TYPE L5 TO BE SURFACE
MOUNTED TO CENTER DOME RING TRUSS
TO LIGHT DOME CEILING. SEE A9 SERIES
DRAWINGS FOR MOUNTING DETAIL.
TYPICAL FOR ALL L5 FIXTURES.
E306
FIXTURE TYPE L3 TO BE SURFACE
MOUNTED AND CENTERED WITHIN
ARCHITECTURAL CAVITY SO THAT
FIXTURE HAS UNIMPEDED FULL RANGE OF
MOTION. SEE A9 SERIES DRAWINGS FOR
MOUNTING DETAIL. TYPICAL FOR ALL L3
FIXTURES.
E307
FIXTURE TYPES L7 AND L9 TO BE
SURFACE MOUNTED WITHIN
ARCHITECTURAL COVE SO THAT NO
DIRECT VIEW OF FIXTURE IS POSSIBLE.
SEE A9 SERIES DRAWINGS FOR
MOUNTING DETAIL. SHIM SO TOP OF
FIXTURE IS FLUSH WITH TOP OF COVE LIP.
CONNECT FIXTURES END-TO-END
WITHOUT JUMPER CABLES. EVENLY
SPACE UNLIT PORTIONS OF COVE AT
BOTH ENDS OF FIXTURE RUN. TYPICAL
FOR ALL L7 AND L9 FIXTURES LOCATED
WITHIN PERIMETER DOME COVE.
E308
FIXTURE TYPES L7, L8, L9 AND L10 TO BE
SURFACE MOUNTED TO ANGLED BRACKET
WITHIN COVE SO THAT NO DIRECT VIEW
OF FIXTURE IS POSSIBLE. SEE A9 SERIES
DRAWINGS FOR MOUNTING DETAIL.
PROVIDE 2 BRACKETS PER FIXTURE.
MOUNT ALL FIXTURES IN CROSS SECTION
TO SAME ANGLED MOUNTNG BRACKET.
SPACE FIXTURES EVENLY WITHIN FIXTURE
RUN SO THERE ARE NO UNLIT SECTIONS.
TYPICAL FOR ALL L7, L8, L9 AND L10
FIXTURES WITHIN CENTER DOME COVE,
ENTRY COVE, AND STAGE COVE.
E309
FIXTURE TYPE L6A AND L6B TO BE TRACK
MOUNTED. SEE A9 SERIES DRAWINGS FOR
TRACK MOUNTING CONDITION. SEE PLANS
FOR TRACK LENGTH. TYPICAL FOR ALL
L6A AND L6B FIXTURES.
E316
NEW FA-BL21-26 & 28
E317
33
8
L7
E317
L7
J
J
NEW LP-M-1E- 5
E316
NEW FA-BL21-25 & 27
NEW FA-BL21-22 & 24
E318
J
9
J
E318
(4 ROWS TYP.) L5 E305
NEW FA-BL21-14 & 16
E302
NEW FA-BL21-16
L1
L1
L1
L1
L2
L1
L1
L6
(TYP.)
L1
31
L1
L2
L1
L2
E317
L1
(TYP.)
L7
E309
NEW LP-M-1E- 3
L1
L2
L2
L1
30
J
E302
L1
E309
J
(TYP.)
L6A
L1
L1
L7
NEW FA-BL21-30 & 32
L1
L1
10
E316
L1
E302
L1
L6A
NEW FA-BL21-24
L1
L1
L1
L1
L2
L2
L1
L2
L1
L1
L1
L1
L1
11
L1
L1
E316
L1
UP
E317
29
12
E317
NEW LP-M-1E- 1
J
E318
J
E316 NEW FA-BL21-29 & 31
NEW LP-M-1E- 1
L7
L7
E317
E320
E316
J
28
NEW FA-BL21-33 & 35
NEW FA-BL21-34 & 36
J
13
E316
E317
J
NEW LP-M-1E- 3
J
E306
L3
E322
(TYP.)
L7
L7
L1
L1
(TYP.)
L6
27
L1
E304
(TYP.)
L6
L1
L1
L2
L1
L2
L1
L2
L2
L2
L6
E323
E303
L2
L6
(TYP.)
14
(TYP.)
L2
L2
(TYP.)
L6
(TYP.)
(TYP.)
15
FIXTURE TYPES L1, L2 AND L6 TO BE
C-CLAMP MOUNTED TO THEATRICAL PIPE
AND SECURED WITH SAFETY CABLE. SEE
A9 SERIES DRAWINGS FOR MOUNTING
DETAIL. TYPICAL FOR ALL L1, L2 AND L6
FIXTURES MOUNTED ON CENTER DOME
RING TRUSS.
E303
L7
NEW LP-M-1E- 5
32
22MAY13 BIDS
6
LR
P
E322
UP
DEPT. MGR/SUPR
APPROVAL
SHEET NOTES
37
LRP
PROJECT ARCH/
ENGR APPROVAL
ISSUED FOR
A/V MACHINE ROOM
MECH EQUIP ROOM
MECH EQUIP ROOM
3
A.
DN
E323
DATE
E324
JUNCTION BOX FOR TYPE L8, L9, AND L10
LIGHT FIXTURE, MOUNT JUNCTION BOX
HIDDEN IN COVE. REFER TO COVE
LIGHTING DETAIL NO.1 ON ELECTRICAL
DETAILS SHEET. COORDINATE WITH
LIGHTING CONTROLS CONTRACTOR.
UTILIZE CIRCUITS INDICATED.
JUNCTION BOX FOR TYPE L7/L8 LIGHT
FIXTURES, MOUNT JUNNCTION BOX
HIDDEN IN COVE. REFER TO COVE
EMERGENCY LIGHTING DETAIL ON
ELECTRICAL DETAILS SHEET.
COORDINATE WITH LIGHTING CONTROLS
CONTRACTOR. UTILIZE CIRCUIT
INDICATED.
NOT
FOR
CON
STRU
CTIO
N
GM DISCLAIMER & TYPICAL NOTES
NO.
DEPT. MGR/SUPR
APPROVAL
R E V I S I O N S
CERTIFIED BY
SUPPLIER PROJECT NO.
22733.000
SUPPLIER DRAWN BY
SUPPLIER CHECKED BY
SUPPLIER PE/PM
CONSULTANT A/E
JUNCTION BOX FOR TYPE L7, AND L9
LIGHT FIXTURE, MOUNT JUNCTION BOX
HIDDEN IN COVE. COVE LIGHTING DETAIL
NO.2 ON ELECTRICAL DETAILS SHEET.
COORDINATE WITH LIGHTING CONTROLS
CONTRACTOR. UTILIZE CIRCUITS
INDICATED.
FIRM INFO & LOGO
SMITHGROUPJJR, INC
500 GRISWOLD SUITE 1700
DETROIT, MI 48226
T 313.983.3600 F 313.983.3636
www.smithgroupjjr.com
PROVIDE ETC SMARTSWITCH RELAY
PANELS TO ACCOMMODATE LIGHTING
CIRCUITS ON THE SUSPENDED RING.
REFER TO PANEL SCHEDULE FOR
'LP-RING' FOR QUANTITY REQUIRED.
PROVIDE 25% SPARE RELAY CAPACITY.
COORDINATE MOUNTING LOCATION IN
UPPER MEZZANINE IN FIELD. CONNECT TO
SPARE 20A, 1P CIRUIT BREAKER FROM
'LP-RING' FOR RELAY PANEL CONTROL
POWER.
PROVIDE ETC SMARTSWITCH RELAY
PANELS TO ACCOMMODATE DMX
LIGHTING CIRCUITS FED FROM
'FA-BL21/FA-BL22'. REFER TO PANEL
SCHEDULES FOR QUANTITY REQUIRED.
PROVIDE 25% SPARE RELAY CAPACITY.
COORDINATE MOUNTING LOCATION IN
FIELD. CONNECT TO SPARE 20A, 1P CIRUIT
BREAKER FROM 'FA-BL21/FA-BL22' FOR
RELAY PANEL CONTROL POWER.
COORDINATE CONTROL WIRING
REQUIREMENTS WITH DMX LIGHTING
CONTROLS PROVIDER.
PROJECT ARCH/
ENGR APPROVAL
DATE
Worldwide Facilities Group
General Motors Corporation
Warren Technical Center Campus
Site ID: 1563
Structure ID: 4235
PROVIDE ONE EMERGENCY LOAD
TRANSFER DEVICE (ELTD) FOR EACH
SWITCHED CIRCUIT FOR EXISTING STAIR
LIGHTING. CONNECT EMERGENCY SIDE OF
ELTD TO SPARE 20A CIRCUIT BREAKER IN
PANEL BOARD 'LP-M-1E'. CONNECT
NORMAL SIDE TO EXISTING NORMAL
CIRCUIT. VERIFY QUANTITY AND LOCATION
IN FIELD.
Level:
DISCONNECT EXISTING 4' CHAIN HUNG
INDUSTRIAL LIGHT FIXTURE INSIDE DOOR
OF MECHANICAL/ELECTRICAL SPACE
FROM EXISTING NORML CIRCUIT.
CONNECT EXISTING FIXTURE TO SPARE
20A CIRCUIT BREAKER IN PANEL BOARD
'LP-M-1E'. FIXTUE SHALL FUNCTION AS
NIGHTLIGHT. EXTEND EXISTING NORMAL
CIRCUIT AS REQUIRED TO COMPLETE THE
CIRCUIT.
MEZZANINE FLOOR LIGHTING
PLAN
26
WFG PE/PM
WFG JOB NO
N. WEINGARTZ
DRAWN BY
1200912
SHEET NUMBER
Author
16
SCALE
25
1/8" = 1'-0"
24
23
22
21
20
19
18
17
DATE
22MAY13
FILE PLOT DATE STAMP
EL1−302
5/21/2013 12:16:27 PM
−
SHEET NO.
SHEET NOTES
1
39
36
A.
2
40
38
3
B.
C.
D.
37
4
E.
F.
5
G.
DATE
PROJECT ARCH/
ENGR APPROVAL
ISSUED FOR
DEPT. MGR/SUPR
APPROVAL
22MAY13 BIDS
CONNECT CEILING MOUNTED OCCUPANCY SENSORS
TO POWER PACKS WITH LOW VOLTAGE WIRING.
PROVIDE NUMBER OF POWER PACKS
RECOMMENDED BY MANUFACTURER. COORDINATE
COMPATABILITY WITH LIGHTING CONTACTORS OR
INDICATED SWITCHES. REFER TO MANUFACTURER
WIRING DIAGRAMS.
REFER TO ARCH. REFLECTED CEILING PLANS FOR
EXACT LOCATION OF LIGHT FIXTURES AND OTHER
CEILING MOUNTED DEVICES.
PROVIDE SEPARATE NEUTRALS FOR DIMMING
CIRCUITS.
POWER TO DMX CONTROLLED LIGHT FIXTURES
SHALL BE VIA RELAY PANELS AS INDICATED ON
PANELBOARD PANEL SCHEDULES.
FOR LIGHT FIXTURES SPECIFIED WITH PLUG AND
CORD, REFER TO POWER PLANS FOR RECEPTACLE
AND CIRCUITING INFORMATION AND LOCATION.
COORDINATE MOUNTING HEIGHT AND LOCATION OF
NEW DEVICES WITH ARCHITECTURAL PLANS PRIOR
TO INSTALLTION.
PROVIDE NEW LED SCREW-IN TYPE LAMPS FOR
EXISITNG TO REMAIN INCANDESCENT LIGHT
FIXTURES.
KEYED NOTES
35
E320 PROVIDE ETC SMARTSWITCH RELAY
PANELS TO ACCOMMODATE LIGHTING
CIRCUITS ON THE SUSPENDED RING.
REFER TO PANEL SCHEDULE FOR
'LP-RING' FOR QUANTITY REQUIRED.
PROVIDE 25% SPARE RELAY CAPACITY.
COORDINATE MOUNTING LOCATION IN
UPPER MEZZANINE IN FIELD. CONNECT TO
SPARE 20A, 1P CIRUIT BREAKER FROM
'LP-RING' FOR RELAY PANEL CONTROL
POWER.
6
34
E321 PROVIDE ONE EMERGENCY LOAD
TRANSFER DEVICE (ELTD) FOR EACH
SWITCHED CIRCUIT FOR EXISTING UPPER
MEZZANINE LIGHTING. CONNECT
EMERGENCY SIDE OF ELTD TO SPARE 20A
CIRCUIT BREAKER IN PANEL BOARD
'LP-M-1E'. CONNECT NORMAL SIDE TO
EXISTING NORMAL CIRCUIT. VERIFY
QUANTITY AND LOCATION IN FIELD.
7
SITE/BUILDING PLAN & NORTH ARROW
NOT
FOR
CON
STRU
CTIO
N
GM DISCLAIMER & TYPICAL NOTES
33
8
32
9
31
10
E321
ELTD ELTD ELTD ELTD
LRP LRP
WFG JOB NO.
(TYP.)
E320
(TYP.)
NO.
PROJECT ARCH/
ENGR APPROVAL
DATE
11
30
DEPT. MGR/SUPR
APPROVAL
R E V I S I O N S
CERTIFIED BY
SUPPLIER PROJECT NO.
22733.000
SUPPLIER DRAWN BY
SUPPLIER CHECKED BY
SUPPLIER PE/PM
12
29
CONSULTANT A/E
FIRM INFO & LOGO
SMITHGROUPJJR, INC
500 GRISWOLD SUITE 1700
DETROIT, MI 48226
T 313.983.3600 F 313.983.3636
www.smithgroupjjr.com
13
28
Worldwide Facilities Group
General Motors Corporation
Warren Technical Center Campus
Site ID: 1563
14
27
Structure ID: 4235
Level:
15
UPPER MEZZANINE FLOOR
LIGHTING PLAN
26
WFG PE/PM
WFG JOB NO
N. WEINGARTZ
16
DRAWN BY
1200912
SHEET NUMBER
Author
SCALE
25
24
23
22
21
20
19
18
17
1/8" = 1'-0"
DATE
22MAY13
FILE PLOT DATE STAMP
EL1−303
5/21/2013 12:16:32 PM
WFG JOB NO.
SHEET NO.
−
30" MAXIMUM LENGTH
L14
L14
DATE
DATA ENABLER (TYP.)
EMERGENCY BYPASS
CONTROLLER (TYP.)
LV DATA
TO DMX CONTROL
(BY OTHERS)
EBC
CKT-1
CKT-2
CKT-3
CKT-4
CKT-5
TO DMX CONTROL
(BY OTHERS)
NORMAL
NOTES:
L1
L6
L1
L6
L1
L6
1. PROVIDE QUANTITY OF DATA ENABLERS AS REQUIRED FOR CONTINUOUS FIXTURE RUN. CONCEAL DATA ENABLER IN LIGHT COVE AS NOT TO INTERFERE WITH LIGHT DISTRIBUTION.
2. REFER TO ARCHITECTURAL PLANS FOR MOUNTING.
3. REFER TO LIGHTING PLANS AND PANEL SCHEDULES FOR CIRCUITING INFORMATION. COORDINATE WITH LIGHTING CONTROLS CONTRACTOR.
L2
EMERGENCY CONTROL NOTES:
1. PROVIDE DEVICE QUANTITIES AS NEEDED. COORDINATE WITH LIGHTING CONTROL SYSTEM PROVIDER FOR INSTALLATION LOCATIONS AND QUANTITIES.
2. EMERGENCY LIGHTING CONTROL OPERATION:
A. UNDER" NORMAL" POWER CONDITIONS, ALL LIGHT FIXTURES SHALL BE CONTROLLED VIA THEIR RESPECTIVE DMX CHANNELS.
B. UPON LOSS OF "NORMAL" POWER AND SUBSEQUENTS CONNECTION TO "EMERGENCY" POWER, SELECTED FIXTURES SHALL ILLUMINATE TO FULL OUTPUT REGARDLESS OF ON/OFF/DIMMING STATE PRIOR TO LOSS OF "NORMAL" POWER.
C. UPON RETURN TO "NORMAL" POWER, FULL CONTROL CAPABILITY SHALL AUTOMATICALLY RETURN TO THE LIGHTING CONTROL SYSTEM.
3. COORDINATE EXACT REQUIREMENTS FOR POWER WIRING, CONTROL WIRING, AND INTERFACE DEVICES WITH LIGHTING CONTROL SUPPLIER.
LIGHT FIXTURE TYPE (TYP)
NOTES:
1. PROVIDE MISC. FITTINGS/COMPONENTS AS REQUIRED FOR A COMPLETE AND FUNTIONAL RACEWAY.
2. LIGHT FIXTURE PLUG DESIGNATION LOCATIONS SHOWN FOR FIXTURE TYPE COUNTS PER CIRCUIT. ACTUAL LOCATIONS MAY VARY DUE TO LIGHT FIXTURE LAYOUT.
3. MOUNT RACEWAY HORIZONTALLY ON TOP OF SHEET METAL PANEL MOUNTED WITHIN TRUSS STRUCTURE. REFER TO POWER AND ARCHITECTURAL PLANS FOR MOUNTING LOCATION.
4. PROVIDE WIRE MANAGEMENT SYSTEM SIMILAR TO PANDUIT G2X2WH6 SERIES IN TRUSS STRUCTURE SECTIONS (WHERE NO RACEWAY IS REQUIRED) FOR ROUTING OF LIGHT FIXTURE CORDS AND LOW VOLTAGE WIRING.
1
R1 - RING LIGHTING RACEWAY DIAGRAM
8
SCALE: NOT TO SCALE
BOARDROOM DMX LIGHTING DETAIL
SITE/BUILDING PLAN & NORTH ARROW
SCALE: NOT TO SCALE
COUNTER CLOCKWISE
AROUND COVE (WHERE APPLICABLE)
CLOCKWISE AROUND COVE (WHERE APPLICABLE)
120V EMERGENCY CIRCUIT
VIA DMX RELAY PANEL
30" MAXIMUM
L7 OR L8
L7 OR L8 L7 OR L8
L7 OR L8
DE
J
DAISY CHAIN UTILIZING
MANUFACTURER'S
JUMPER CABLES
LV DATA
TO DMX CONTROL
(BY OTHERS)
EBC
NOT
FOR
CON
STRU
CTIO
N
GM DISCLAIMER & TYPICAL NOTES
DATA ENABLER (TYP.)
EMERGENCY BYPASS
CONTROLLER (TYP.)
24-DWND-FW
L7 OR L8 L7 OR L8
DE
DAISY CHAIN UTILIZING
MANUFACTURER'S ENDTO-END CONNECTORS
(TYP.)
WIREMOLD
2400 SERIES
FMC CONDUIT
120V CIRCUIT VIA
DMX RELAY PANEL
BY OTHERS (TYP.)
480V OR 208V, 3P, 20A NORMAL POWER
SOURCE SENSING FEED. DETERMINE
SOURCE UPON VERIFICATION OF NORMAL
FEED SOURCE TO EXISTING ATS.
SPARE
L6
J
DATA ENABLER (TYP.)
EMERGENCY
DUPLEX RECEPTACLE
UNDER FACE (TYP)
L14
DE
DAISY CHAIN UTILIZING
MANUFACTURER'S ENDTO-END CONNECTORS
(TYP.)
EMERGENCY BYPASS
DETECTOR (TYP.)
EBD
L14
BY OTHERS (TYP.)
120V, 20A EMERGENCY POWER FEED.
DETERMINE SOURCE UPON VERIFICATION OF
EMERGENCY FEED SOURCE TO EXISTING ATS.
2410FC-FW
DEPT. MGR/SUPR
APPROVAL
22MAY13 BIDS
L14
24-DWND-FW
PROJECT ARCH/
ENGR APPROVAL
ISSUED FOR
J
DE
DAISY CHAIN UTILIZING
MANUFACTURER'S ENDTO-END CONNECTORS
(TYP.)
WIREMOLD
2400 SERIES
FMC CONDUIT
L14
120V EMERGENCY CIRCUIT
VIA DMX RELAY PANEL
BY OTHERS (TYP.)
LV DATA
EMERGENCY BYPASS
DETECTOR (TYP.)
EBD
EMERGENCY BYPASS
CONTROLLER (TYP.)
EBD
TO DMX CONTROL
(BY OTHERS)
EBC
120V, 20A EMERGENCY POWER FEED.
DETERMINE SOURCE UPON VERIFICATION OF
EMERGENCY FEED SOURCE TO EXISTING ATS.
120V, 20A EMERGENCY POWER FEED.
DETERMINE SOURCE UPON VERIFICATION OF
EMERGENCY FEED SOURCE TO EXISTING ATS.
2410FC-FW
CKT-1
CKT-2
480V OR 208V, 3P, 20A NORMAL POWER
SOURCE SENSING FEED. DETERMINE
SOURCE UPON VERIFICATION OF NORMAL
FEED SOURCE TO EXISTING ATS.
CKT-3
NOTES:
ER
1. PROVIDE QUANTITY OF DATA ENABLERS AS REQUIRED FOR CONTINUOUS FIXTURE RUN. CONCEAL DATA ENABLER IN LIGHT COVE AS NOT TO INTERFERE WITH LIGHT DISTRIBUTION.
2. TOP OF COVE MOUNTED LIGHT FIXTURES SHALL BE FLUSH WITH TOP OF COVE LIP. PROVIDE MOUNTING HARWARE AS REQUIRED.
3. INDIVIDUAL FIXTURE RUN LENGTH SHALL NOT EXCEED 40' FOR CIRCUITING PURPOSES. REFER TO LIGHTING PLANS FOR CIRCUITING INFORMATION. COORDINATE WITH LIGHTING CONTROLS CONTRACTOR.
AK
TO
R
SP
E
PR
O
SP
E
JE
C
AK
DUPLEX ISOLATED
GROUND RECEPTACLE
UNDER FACE (TYP)
ER
NOTES:
1. PROVIDE MISC. FITTINGS/COMPONENTS AS REQUIRED FOR A COMPLETE AND FUNTIONAL RACEWAY.
2. A/V EQUIPMENT PLUG DESIGNATION LOCATIONS SHOWN FOR EQUIPMENT TYPE COUNTS PER CIRCUIT. ACTUAL LOCATIONS MAY VARY DUE TO LIGHT FIXTURE AND A/V EQUIPMENT LAYOUT.
3. MOUNT RACEWAY HORIZONTALLY ON TOP OF SHEET METAL PANEL MOUNTED WITHIN TRUSS STRUCTURE BELOW PROJECTOR. REFER TO POWER AND ARCHITECTURAL PLANS FOR MOUNTING LOCATION.
4. PROVIDE WIRE MANAGEMENT SYSTEM SIMILAR TO PANDUIT G2X2WH6 SERIES IN TRUSS STRUCTURE SECTIONS (WHERE NO RACEWAY IS REQUIRED) FOR ROUTING OF A/V CORDS AND LOW VOLTAGE WIRING.
2
R2 - RING A/V RACEWAY DIAGRAM
EMERGENCY CONTROL NOTES:
1. PROVIDE DEVICE QUANTITIES AS NEEDED. COORDINATE WITH LIGHTING CONTROL SYSTEM PROVIDER FOR INSTALLATION LOCATIONS AND QUANTITIES.
2. EMERGENCY LIGHTING CONTROL OPERATION:
A. UNDER" NORMAL" POWER CONDITIONS, ALL LIGHT FIXTURES SHALL BE CONTROLLED VIA THEIR RESPECTIVE DMX CHANNELS.
B. UPON LOSS OF "NORMAL" POWER AND SUBSEQUENTS CONNECTION TO "EMERGENCY" POWER, SELECTED FIXTURES SHALL ILLUMINATE TO FULL OUTPUT REGARDLESS OF ON/OFF/DIMMING STATE PRIOR TO LOSS OF "NORMAL" POWER.
C. UPON RETURN TO "NORMAL" POWER, FULL CONTROL CAPABILITY SHALL AUTOMATICALLY RETURN TO THE LIGHTING CONTROL SYSTEM.
3. COORDINATE EXACT REQUIREMENTS FOR POWER WIRING, CONTROL WIRING, AND INTERFACE DEVICES WITH LIGHTING CONTROL SUPPLIER.
5
SCALE: NOT TO SCALE
COVE EMERGENCY LIGHTING DETAIL
SCALE: NOT TO SCALE
NO.
PROJECT ARCH/
ENGR APPROVAL
DATE
DEPT. MGR/SUPR
APPROVAL
R E V I S I O N S
CERTIFIED BY
SUPPLIER PROJECT NO.
22733.000
(2) 120V CIRCUITS
VIA DMX RELAY PANEL
L7
L7
L7
DE
L9
L9
SUPPLIER DRAWN BY
L7
L7
DE
DATA
L9
L7
DATA
SUPPLIER CHECKED BY
L9
L9
120V CIRCUIT
VIA DMX RELAY PANEL
L9
SUPPLIER PE/PM
J
DE
DAISY CHAIN UTILIZING
MANUFACTURER'S ENDTO-END CONNECTORS
(TYP.)
DATA
DE
L9 OR L10
L9 OR L10
L9 OR L10
L9 OR L10
L9 OR L10
L9 OR L10
DATA
DAISY CHAIN UTILIZING
MANUFACTURER'S
JUMPER CABLES
BY OTHERS
(TYP.)
DATA ENABLER (TYP.)
J
DE
DAISY CHAIN UTILIZING
MANUFACTURER'S ENDTO-END CONNECTORS
(TYP.)
DATA
CONSULTANT A/E
DE
DATA
DAISY CHAIN UTILIZING
MANUFACTURER'S
JUMPER CABLES
BY OTHERS
(TYP.)
DATA ENABLER (TYP.)
(1)CIRCUIT COUNTER
CLOCKWISE
AROUND COVE
(1)CIRCUIT CLOCKWISE
AROUND COVE
FIRM INFO & LOGO
COUNTER CLOCKWISE
AROUND COVE (WHERE
APPLICABLE)
SMITHGROUPJJR, INC
500 GRISWOLD SUITE 1700
DETROIT, MI 48226
T 313.983.3600 F 313.983.3636
www.smithgroupjjr.com
CIRCUIT CLOCKWISE AROUND
COVE AS REQUIRED (WHERE
APPLICABLE)
NOTES:
NOTES:
1. PROVIDE QUANTITY OF DATA ENABLERS AS REQUIRED FOR CONTINUOUS FIXTURE RUN. CONCEAL DATA ENABLER IN LIGHT COVE AS NOT TO INTERFERE WITH LIGHT DISTRIBUTION.
2. TOP OF COVE MOUNTED LIGHT FIXTURES SHALL BE FLUSH WITH TOP OF COVE LIP. PROVIDE MOUNTING HARWARE AS REQUIRED.
3. INDIVIDUAL FIXTURE RUN LENGTH SHALL NOT EXCEED 44' FOR CIRCUITING PURPOSES. REFER TO LIGHTING PLANS FOR CIRCUITING INFORMATION. COORDINATE WITH LIGHTING CONTROLS CONTRACTOR.
1. PROVIDE QUANTITY OF DATA ENABLERS AS REQUIRED FOR CONTINUOUS FIXTURE RUN. CONCEAL DATA ENABLER IN LIGHT COVE AS NOT TO INTERFERE WITH LIGHT DISTRIBUTION.
2. TOP OF COVE MOUNTED LIGHT FIXTURES SHALL BE FLUSH WITH TOP OF COVE LIP. PROVIDE MOUNTING HARWARE AS REQUIRED.
3. INDIVIDUAL FIXTURE RUN LENGTH SHALL NOT EXCEED 48' FOR CIRCUITING PURPOSES. REFER TO LIGHTING PLANS FOR CIRCUITING INFORMATION. COORDINATE WITH LIGHTING CONTROLS CONTRACTOR.
Worldwide Facilities Group
3
COVE LIGHTING DETAIL NO.2
6
SCALE: NOT TO SCALE
COVE LIGHTING DETAIL NO.3
SCALE: NOT TO SCALE
General Motors Corporation
Warren Technical Center Campus
(2) 120V CIRCUITS
VIA DMX RELAY PANEL
L5
L5
L5
(2) 120V CIRCUITS
VIA DMX RELAY PANEL
L5
DE
L8A
L8A
L8A
DE
L9
DAISY CHAIN UTILIZING
MANUFACTURER'S ENDTO-END CONNECTORS
(TYP.)
L9
DATA
L10
DATA
J
DE
L10
L9
L5
L5
L5
DAISY CHAIN UTILIZING
MANUFACTURER'S ENDTO-END CONNECTORS
(TYP.)
DATA
DE
L10
L10
DAISY CHAIN UTILIZING
MANUFACTURER'S
JUMPER CABLES
L5
(1)CIRCUIT COUNTER
CLOCKWISE
AROUND COVE
(1)CIRCUIT CLOCKWISE
AROUND COVE
L5
L5
L5
DATA ENABLER (TYP.)
BY OTHERS
(TYP.)
L5
Level:
DATA
DE
DATA
L5
DE
L5
DE
DATA
J
DATA
L5
L5
DATA
L5
DE
L5
L5
DE
DATA
L9
DE
L10
(1)CIRCUIT COUNTER
CLOCKWISE
AROUND COVE
L5
Structure ID: 4235
DATA
DE
L9
L10
DATA ENABLER (TYP.)
L8A
DE
DATA
L9
L8A
L5
DE
DATA
L8A
Site ID: 1563
L5
L5
L5
DAISY CHAIN UTILIZING
MANUFACTURER'S
JUMPER CABLES
ELECTRICAL DETAILS
DE
DATA
DATA
BY OTHERS
(TYP.)
(1) CIRCUIT CLOCKWISE
AROUND COVE
NOTES:
NOTES:
1. PROVIDE QUANTITY OF DATA ENABLERS AS REQUIRED FOR CONTINUOUS FIXTURE RUN. CONCEAL DATA ENABLER IN LIGHT COVE AS NOT TO INTERFERE WITH LIGHT DISTRIBUTION.
2. TOP OF COVE MOUNTED LIGHT FIXTURES SHALL BE FLUSH WITH TOP OF COVE LIP. PROVIDE MOUNTING HARWARE AS REQUIRED.
3. INDIVIDUAL FIXTURE RUN LENGTH SHALL NOT EXCEED 32' FOR CIRCUITING PURPOSES. REFER TO LIGHTING PLANS FOR CIRCUITING INFORMATION. COORDINATE WITH LIGHTING CONTROLS CONTRACTOR.
1. PROVIDE QUANTITY OF DATA ENABLERS AS REQUIRED FOR CONTINUOUS FIXTURE RUN. CONCEAL DATA ENABLER IN RING TRUSS AS NOT TO INTERFERE WITH LIGHT DISTRIBUTION.
2. PROVIDE MOUNTING HARWARE AS REQUIRED.
3. INDIVIDUAL FIXTURE RUN LENGTH SHALL NOT EXCEED 28' FOR CIRCUITING PURPOSES. REFER TO LIGHTING PLANS FOR CIRCUITING INFORMATION. COORDINATE WITH LIGHTING CONTROLS CONTRACTOR.
WFG PE/PM
WFG JOB NO
N. WEINGARTZ
DRAWN BY
1200912
SHEET NUMBER
Author
SCALE
4
RIM COVE LIGHTING DETAIL NO.1
SCALE: NOT TO SCALE
7
RING LIGHTING DETAIL NO.1
SCALE: NOT TO SCALE
NOT TO SCALE
DATE
22MAY13
FILE PLOT DATE STAMP
EP5−511
5/21/2013 12:17:10 PM
WFG JOB NO.
−
SHEET NO.
DATE
PROJECT ARCH/
ENGR APPROVAL
ISSUED FOR
DEPT. MGR/SUPR
APPROVAL
22MAY13 BIDS
1" C. WITH PULL STRING AND BUSHING
AT END TERMINATED IN ACCESSIBLE
CEILING SPACE (TYP.)
EXTEND 1" (MINIMUM) CONDUIT
TO SECURITY PANEL.
3/4" C. FOR 120V BRANCH CIRCUIT SHOWN ON
POWER PLANS FOR DOOR POWER SUPPLIES
WALL
POWER SUPPLY
3/4" C.
PROVIDE 12"X12" JUNCTION BOX
ON SECURE SIDE OF DOOR
PSD
JB
PROVIDE CONNECTION TO FIRE ALARM
SYSTEM AT CONTROLLED EXIT DOORS AND
EMERGENCY EGRESS DOORS AS REQUIRED.
GENERATOR
ROOM
GROUND BUS
ACCESSIBLE
CEILING (TYP.)
PATCH HOLE TO
MATCH FIRE
RATING
ACCESSIBLE
CEILING (TYP.)
CEILING
TO GENERATOR
PRIMARY
SWITCHGEAR
ROOM PERIMETER
GROUND BUS
TO BUILDING STEEL
3/4" C.
RECESSED SINGLE-GANG BOX
FOR ACCESS CONTROL ON
NON-SECURE SIDE OF DOOR
(PROVIDE ROUGH IN FOR
ACCESS CONTROL ON BOTH
SIDES OF DOOR WHERE
SPECIFIED)
1"C. (TYP.)
REQUEST TO EXIT
DETECTOR (WHERE
SPECIFIED)
#4/0 AWG BARE COPPER
#4/0 AWG INSULATED GREEN GROUND CABLE
SUBSTATION
4-11/16" SQUARE, 2 1/8" DEEP
DOUBLE GANG BOX WITH
PLASTER RING (TYP.)
TO BUILDING STEEL
DOOR CONTACT
N
1/2" FLEX CONDUIT, RECESSED IN FRAME.
#4/0 AWG MAIN
BONDING JUMPER
COVER PLATE (TYP.)
COVER PLATE (TYP.)
4-11/16" SQUARE, 2 1/8"
DEEP DOUBLE GANG
BOX WITH PLASTER
RING (TYP.)
G
#4 AWG
TO CONCRETE
ENCASED ELECTRODE
TO
COUNTERPOISE
GROUNDING
BOND 1#4AWG TO EACH METAL PIPING
SYSTEM PER NFPD70 250.166 (B),
INCLUDING SUPPLY AND RETURN, STEAM,
CHILLED WATER, COMPRESSED AIR,
CONDENSATE.
ACCESS CONTROL SYSTEM DIAGRAM
3
SCALE: NOT TO SCALE
LOWER LEVEL
GND-GROUNDING SYSTEM INTERCONNECTIONS
4
SCALE: NOT TO SCALE
NOT
FOR
CON
STRU
CTIO
N
GM DISCLAIMER & TYPICAL NOTES
1. PROVIDE DATA CABLING AND FACEPLATE TO ACCOMMODATE (4) DATA CONNECTIONS.
2. COORDINATE TERMINATION LOCATION WITH OWNER.
3. PROVIDE LABELS TO DIFFERENTIATE GM NETWORK FROM AV NETWORK FOR ALL OUTLETS.
NOTE:
BOND AROUND ALL DOMESTIC WATER
DIELECTRIC FITTINGS WITH 1#4.
WATER
SERVICE
FLOOR
NOTES:
ONE PER PIPING SYSTEM
GAS
SERVICE
1
FLOOR
18" OR AS NOTED
ELECTRIC
STRIKE\ELECTRIC
POWER TRANSFER
DEVICE AS SPECIFIED
18" OR AS NOTED
TO GROUNDING BAR
IN FIBER ROOM
SITE/BUILDING PLAN & NORTH ARROW
TYPICAL TELECOM OUTLET DETAIL
SCALE: NOT TO SCALE
SEPARATELY
DERIVED
SOURCE
TO NEXT FIRE ALARM
JUNCTION
BOX OR NAC PANEL.
SEE FIRE ALARM RISER
DIAGRAM
DO NOT CONNECT THE IG
CONDUCTOR TO ANY PART OF THE
EQUIPMENT GROUND SYSTEM.
ROUTE IG CONDUCTORS AS
INDICATED.
AHU SUPPLY
FAN (TYP FOR 4)
TYPICAL FIRE ALARM JUNCTION BOX OR
NAC PANEL IN ELECTRICAL ROOM
ROOM
AHU RETURN
FAN (TYP FOR 4)
VFD
5
3
AI
AI
AR
AR
AR
WF
TS
ELM
FS
TP
1
VFD
4
F
AR
N
N
N
IG
EG
IG
EG
G
TYP FOR
4 AHU'S
CONDUIT
AR
UPSTREAM ELECTRICAL
EQUIPMENT AS
INDICATED
ON THE ONE LINE
DIAGRAM.
FIRE ALARM
INTELLIGENT
DEVICES
(MONITORING
AND CONTROL)
2
IG
N EG
FEEDER SERVING IG PANELBOARD
WITH 1#6 EG MINIMUM
NO.
PROJECT ARCH/
ENGR APPROVAL
DATE
DEPT. MGR/SUPR
APPROVAL
R E V I S I O N S
FIRE ALARM
VISUAL
INDICATORS
(STROBES) INDIVIDUAL AND
COMBINATION
TYPES
22733.000
NEUTRAL BUS
N
SUPPLIER DRAWN BY
EG
SUPPLIER CHECKED BY
IG
EG
IG
TO IG RECEPTACLE
SUPPLIER PE/PM
KEYED NOTES:
1
EQUIPMENT
GROUND BUS
ISOLATED/INSULATED
GROUND BUS
TYPICAL FIRE ALARM ZONE WIRING DIAGRAM
FIRE ALARM AUDIBLE
DEVICES-INDIVIDUAL
AND
COMBINATION TYPES
PROVIDE ONE ADDRESSABLE INTERFACE (AI) FOR EACH OF THE
FOLLOWING DEVICES:
a. WATER FLOW SWITCH
b. TAMPER SWITCH
2
TO NEXT FIRE ALARM JUNCTION BOX OR NAC PANEL
FIRE ALARM INDICATING CIRCUIT
FIRE ALARM SPEAKER CIRCUIT
PROVIDE ONE ADDRESSABLE RELAY (AR) FOR EACH OF THE
FOLLOWING DEVICES: REFER TO DOOR HARDWARE
SPECIFICATIONS FOR LOCATIONS AND TYPES OF DOOR HARDWARE
DEVICES.
THREE PHASE IG BRANCH
CIRCUIT
PANELBOARD AS INDICATED
ON
PANEL SCHEDULE WITH
EQUIPMENT
GROUND BUS AND ISOLATED
GROUND BUS
CONSULTANT A/E
FIRM INFO & LOGO
SMITHGROUPJJR, INC
500 GRISWOLD SUITE 1700
DETROIT, MI 48226
T 313.983.3600 F 313.983.3636
www.smithgroupjjr.com
NOTE: THIS DIAGRAM IS FOR BASIC GROUNDING DESIGN
INTENT AND DOES NOT NECESSARILY REFLECT ALL
CONDITIONS ON THIS PROJECT. FOR POWER DISTRIBUTION
DESIGN REFER TO ONE-LINE DIAGRAMS.
a. FIRE / SMOKE DAMPER
GENERAL NOTES:
FIRE ALARM INTELLIGENT LOOP CIRCUIT
CERTIFIED BY
SUPPLIER PROJECT NO.
A B C
b. ELECTROPNEUMATIC SWITCH
A
REFER TO SPECIAL SYSTEMS PLANS FOR LOCATIONS AND NUMBER OF FIRE
ALARM DEVICES.
B
WIRING REQUIREMENTS SHALL COMPLY WITH THE SYSTEM SUPPLIERS APPROVED
SHOP DRAWINGS AND INSTALLATION INSTRUCTIONS.
C
REFER TO MECHANICAL DRAWINGS FOR LOCATIONS OF WATER FLOW AND
SUPERVISORY SWITCHES.
c. ELECTRIC LOCK
3
PROVIDE WIRING AND CONNECTIONS FROM ADDRESSABLE RELAY
(AR) TO DEVICES FURNISHED AND INSTALLED BY OTHER TRADES
SUCH AS FIRE DAMPERS, ELECTRIC DOOR LOCKS, FIRE/SMOKE
VENTS AND EP SWITCHES.
4
ADDRESSABLE RELAY (AR) CONTACTS TO BE CONNECTED TO
MOTOR STARTERS AND VARIABLE FREQUENCY DRIVE (VFD) MOTOR
CONTROLLERS FOR SUPPLY AND RETURN FANS IN RESPECTIVE AIR
HANDLING UNITS.
5
2
GND-IG PANEL GROUNDING
Worldwide Facilities Group
SCALE: NOT TO SCALE
General Motors Corporation
12
"L
PROVIDE REMOTE VISUAL INDICATOR FOR EACH DUCT SMOKE
DETECTOR. LOCATE INDICATOR IN RESPECTIVE MECHANICAL
ROOM OR RECESSED IN CORRIDOR CEILING TILE. COORDINATE
WITH OTHER TRADES TO AVOID ANY INTERFERANCES
Warren Technical Center Campus
1/4"
Site ID: 1563
STAND-OFF
2"
3"W
Structure ID: 4235
Level:
COPPER BAR
5
EXOTHERMIC WELD
OR CLAMP CONNECTION
FA-TYPICAL FIRE ALARM WIRING DIAGRAM
#6 AWG GROUNDING
CONDUCTOR
SCALE: NOT TO SCALE
6
INSULATOR
9/16"
GND-GROUND BUS DETAIL - 12"L
ELECTRICAL DETAILS
SCALE: NOT TO SCALE
WFG PE/PM
WFG JOB NO
N. WEINGARTZ
DRAWN BY
1200912
SHEET NUMBER
Author
SCALE
As indicated
DATE
22MAY13
FILE PLOT DATE STAMP
EP5−512
5/21/2013 12:17:12 PM
−
SHEET NO.
DATE
PROJECT ARCH/
ENGR APPROVAL
ISSUED FOR
DEPT. MGR/SUPR
APPROVAL
22MAY13 BIDS
D
E
F
G
H
I
J
K
L
M
N
O
P
Q
R
S
T
U
SUPERVISORY ANNUNCIATION FACP
BY DEVICE
SOUND "FIRE ZONE" MESSAGE ON
B, 1ST AND MZ FLOORS
SOUND "FIRE ZONE" MESSAGE ON
B, 1ST AND MZ FLOORS
SOUND "FIRE ZONE" MESSAGE ON FLOOR OF
SIGNAL ORIGIN AND FLOORS DIRECTLY ABOVE AND BELOW
ACTIVATE VISIBLE NOTIFICATION DEVICES ON
B, 1ST AND MZ FLOORS
ACTIVATE VISIBLE NOTIFICATION DEVICES ON
B, 1ST AND MZ FLOORS
ACTIVATE VISIBLE NOTIFICATION DEVICES ON FLOOR OF
SIGNAL ORIGIN AND FLOORSDIRECTLY ABOVE AND BELOW
SOUND "SAFE ZONE" MESSAGE ON FLOORS OTHER THAN FLOOR
OF SIGNAL ORIGIN AND FLOORS DIRECTLY ABOVE AND BELOW
TRANSMIT TROUBLE SIGNAL CENTRAL STATION
TRANSMIT SUPERVISORY SIGNAL CENTRAL STATION
SHUNT TRIP OPERATION OF ELEVATOR POWER
RECALL ELEVATORS TO PRIMARY RECALL FLOOR
RECALL ELEVATORS TO SECONDARY RECALL FLOOR(S)
ELEVATOR CAB FIRE HAT FLASH
ANNUNCIATE ASSOCIATED INFORMATION ON
ALL REMOTE LCD FAAPS
CLOSE ASSOCIATED SMOKE DAMPER
SHUT-DOWN ONLY THE ASSOCIATED AHU
1
MANUAL STATION - B FLOORS ONLY
X
2
MANUAL STATION - 1ST & MZ FLOOR ONLY
X
3
SMOKE DETECTORS - ELEVATOR LOBBIES
B AND 1ST FLOOR ONLY
X
X
X
X
X
X
X
TRANSMIT ALARM SIGNAL TO CENTRAL STATION
C
PRINT CHANGE OF SYSTEM STATUS
B
TROUBLE ANNUNCIATION FACP BY
DEVICE
INITIATING DEVICE
A
ALARM ANNUNCIATION FACP BY DEVICE
SYSTEM OUTPUT
X
X
X
X
X
X
X
X
X
X
SITE/BUILDING PLAN & NORTH ARROW
4
SMOKE DETECTORS - ELEVATOR MACHINE ROOMS ONLY
5
DUCT MOUNTED SMOKE DETECTOR @ AHU (SUPPLY) FOR
AHUs SERVING B THROUGH MEZZANINE FLOORS ONLY
X
X
X
X
6
DUCT MOUNTED SMOKE DETECTOR FOR SMOKE DAMPER
OPERATION B THROUGH MEZZANINE FLOORS ONLY
X
X
X
X
7
HEAT DETECTOR - ELEVATOR MACHINE ROOMS ONLY
X
8
WATERFLOW SWITCH - B FLOORS ONLY
X
9
WATERFLOW SWITCH - 1ST AND MZ FLOOR ONLY
X
10
WATERFLOW SWITCH - ELEVATOR MACHINE ROOMS ONLY
X
11
SPRINKLER VALVE SUPERVISORY SWITCH
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
GM DISCLAIMER & TYPICAL NOTES
X
FIRE ALARM AC POWER FAIL
X
X
X
X
13
FIRE ALARM SYSTEM LOW BATTERY
X
X
X
X
14
OPEN CIRCUIT
X
X
X
X
15
GROUND FAULT
X
X
X
X
16
SLC/INITIATING DEVICE CIRCUIT FAULT
X
X
X
X
17
NOTIFICATION APPLIANCE CIRCUIT SHORT
X
X
X
X
18
LOSS OF VOLTAGE FOR ELEVATOR POWER SHUT DOWN CONTROL CIRCUIT
X
X
NOT
FOR
CON
STRU
CTIO
N
X
12
X
X
X
X
X
X
X
FIRE ALARM EVACUATION SEQUENCE:
* IF FIRE ZONE MESSAGE ON FLOORS B THRU MEZZANINE - MESSAGE SHALL INDICATED BUILDING EVACUATION ON AFFECTED FLOORS
NO.
PROJECT ARCH/
ENGR APPROVAL
DATE
DEPT. MGR/SUPR
APPROVAL
R E V I S I O N S
CERTIFIED BY
SUPPLIER PROJECT NO.
22733.000
SUPPLIER DRAWN BY
SUPPLIER CHECKED BY
SUPPLIER PE/PM
CONSULTANT A/E
Load
Red (Line)
POWER PACK
Blk
Red (Load)
Local
Off
Switch
Worldwide Facilities Group
General Motors Corporation
Red
Hot
Wht
Blk
Neutral
FIRM INFO & LOGO
SMITHGROUPJJR, INC
500 GRISWOLD SUITE 1700
DETROIT, MI 48226
T 313.983.3600 F 313.983.3636
www.smithgroupjjr.com
White (Neutral)
Blu
WFG JOB NO.
+24VDC
Common
Warren Technical Center Campus
OCCUPANCY SENSOR
Site ID: 1563
Control Output
Structure ID: 4235
Level:
2
LTG-SINGLE OCC SENSOR
SCALE: NOT TO SCALE
ELECTRICAL DETAILS
WFG PE/PM
WFG JOB NO
N. WEINGARTZ
DRAWN BY
1200912
SHEET NUMBER
Author
SCALE
12" = 1'-0"
DATE
22MAY13
FILE PLOT DATE STAMP
EP5−513
5/21/2013 12:17:13 PM
WFG JOB NO.
−
SHEET NO.
DATE
110VAC
PROJECT ARCH/
ENGR APPROVAL
ISSUED FOR
DEPT. MGR/SUPR
APPROVAL
22MAY13 BIDS
TO ACCESS CONTROL SYSTEM EQUIPMENT
PSD
J
ACCESS CONTROL DOOR GENERAL NOTES
CEILING LINE
1.
ALL RACEWAYS INCLUDING JUNCTION BOXES TO BE RECESSED UNLESS OTHERWISE NOTED.
2.
DETERMINE EXACT RACEWAY ROUTING BASED ON FIELD CONDITIONS.
3.
POWER FOR ELECTRIFIED DEVICES OBTAINED FROM POWER SUPPLIES
AT ACCESS CONTROL PANEL ASSEMBLY UNLESS OTHERWISE NOTED.
4.
PROVIDE WEATHER-PROOF (WP) JUNCTION BOXES IN EXTERIOR LOCATIONS
5.
WIRE SIZES SHALL BE IN ACCORDANCE WITH MANUFACTURERS INSTRUCTIONS.
6.
COORDINATE REQUIREMENTS WITH ACHITECTURAL DOOR HARDWARE SCHEDULE AND SPECIFICATIONS.
1/2"C.
DC
_
DC
_
1/2" FLEX IN DOOR FRAME OR
1/2"C. OUTSIDE DOOR FRAME
(TYP.)
3/4"C.
PTD
_
PTD
110VAC
CR
ELECTRIC EXIT
DEVICE
PSD
_
1910-1 HORN
ELECTRIC EXIT
DEVICE
CEILING LINE
CORE DOOR FOR
POWER ROUTING (TYP FOR 2)
DC
_
DC
_
DC
_
DC
_
DC
_
DC
_
DC
_
DC
_
GENERAL NOTES
1.
REFER TO ACCESS CONTROL DOOR GENERAL NOTES.
KEY
SWITCH
LEGEND
CR
CARD READER.
DC
_
DOOR CONTACT SWITCH
PSD
_
POWER SUPPLY FOR DOOR(S) WITH ELECTRICAL HARDWARE
SITE/BUILDING PLAN & NORTH ARROW
NOT
FOR
CON
STRU
CTIO
N
JUNCTION BOX
J
PTD
_
POWER TRANSFER DEVICE
GENERAL NOTES
TYPICAL ACCESS DOOR DETAIL NO.1
1
1. REFER TO ACCESS CONTROL DOOR GENERAL NOTES.
SCALE: NOT TO SCALE
GM DISCLAIMER & TYPICAL NOTES
LEGEND
DC
_
PSD
_
110VAC
TO ACCESS CONTROL SYSTEM EQUIPMENT
PSD
J
2
DOOR CONTACT SWITCH
POWER SUPPLY FOR DOOR (S) WITH ELECTRICAL HARDWARE
TYPICAL ACCESS DOOR DETAIL NO.2
SCALE: NOT TO SCALE
CEILING LINE
1/2"C.
DC
_
DC
_
ELECTRIC
STRIKE
110VAC
TO ACCESS CONTROL SYSTEM EQUIPMENT
1/2" FLEX IN DOOR FRAME OR 1/2"C.
OUTSIDE DOOR FRAME (TYP.)
J
DO
CEILING LINE
CEILING LINE
3/4"C.
PTD
_
PTD
CR
DELAYED
EGRESS EXIT
DEVICE
DELAYED
EGRESS EXIT
DEVICE
DC
_
CR
DC
_
(2) EA. @ PAIRS
CORE DOOR FOR
POWER ROUTING (TYP.)
HC
HC
ACTIVATION
SWITCHES
GENERAL NOTES
1.
REFER TO ACCESS CONTROL DOOR GENERAL NOTES.
NO.
PROJECT ARCH/
ENGR APPROVAL
DATE
LEGEND
R E V I S I O N S
CR
CARD READER.
DC
_
DOOR CONTACT SWITCH
CERTIFIED BY
SUPPLIER PROJECT NO.
GENERAL NOTES
GENERAL NOTES
PSD
_
J
POWER SUPPLY FOR DOOR(S) WITH ELECTRICAL HARDWARE
1.
1.
SUPPLIER DRAWN BY
JUNCTION BOX
POWER TRANSFER DEVICE
DC
_
J
TYPICAL RACCESS DOOR DETAIL NO.5
5
4
SCALE: NOT TO SCALE
22733.000
REFER TO ACCESS CONTROL DOOR GENERAL NOTES.
REFER TO ACCESS CONTROL DOOR GENERAL NOTES.
LEGEND
LEGEND
PTD
_
DEPT. MGR/SUPR
APPROVAL
DOOR CONTACT SWITCH
DO
DOOR OPERATING EQUIPMENT
JUNCTION BOX
HC
_
DOOR OPERATOR SWITCH
TYPICAL ACCESS DOOR DETAIL NO.4
3
SCALE: NOT TO SCALE
SUPPLIER CHECKED BY
SUPPLIER PE/PM
ACCESS DOOR DETAIL NO.3
CONSULTANT A/E
FIRM INFO & LOGO
SCALE: NOT TO SCALE
SMITHGROUPJJR, INC
500 GRISWOLD SUITE 1700
DETROIT, MI 48226
T 313.983.3600 F 313.983.3636
www.smithgroupjjr.com
TO ACCESS CONTROL SYSTEM
EQUIPMENT AND POWER
SUPPLY FOR ELECTRIC STRIKE.
TO ACCESS CONTROL SYSTEM
EQUIPMENT AND POWER SUPPLY
FOR ELECTRIC STRIKE.
TO ACCESS CONTROL SYSTEM
EQUIPMENT AND POWER
SUPPLY FOR MAG LOCK.
CONNECT TO FIRE ALARM PANEL.
J
CEILING LINE
J
J
CEILING LINE
1/2"C.
1/2"C.
1/2"C.
DC
DC
MD
DC
General Motors Corporation
ELM
1/2" FLEX IN DOOR FRAME OR 1/2"C.
OUTSIDE DOOR FRAME (TYP.)
1/2" FLEX IN DOOR FRAME OR
1/2"C. OUTSIDE DOOR FRAME
Warren Technical Center Campus
Site ID: 1563
3/4"C.
ELECTRIC STRIKE
Worldwide Facilities Group
CEILING LINE
3/4"C.
CR
3/4"C.
CR
Structure ID: 4235
CR
Level:
ELECTRIC STRIKE
GENERAL NOTES
1.
GENERAL NOTES
REFER TO ACCESS CONTROL DOOR GENERAL NOTES.
1.
GENERAL NOTES
REFER TO ACCESS CONTROL DOOR GENERAL NOTES.
1.
ELECTRICAL DETAILS
REFER TO ACCESS CONTROL DOOR GENERAL NOTES.
LEGEND
CR
CARD READER. MOUNT JUNCTION BOX ON LATCH SIDE OF DOOR WHEN POSSIBLE.
DC
_
DOOR CONTACT SWITCH
CR
CARD READER. MOUNT ON JUNCTION BOX ON LATCH SIDE OF DOOR WHEN POSSIBLE.
JUNCTION BOX
DC
_
DOOR CONTACT SWITCH
J
LEGEND
J
LEGEND
JUNCTION BOX
CR
CARD READER. MOUNT ON JUNCTION BOX ON LATCH SIDE OF DOOR WHEN POSSIBLE.
DC
_
DOOR CONTACT SWITCH
ELM
MAG LOCK HARDWARE
MD
MOTION DETECTOR - CEILING OR WALL MOUNTED
J
6
7
TYPICAL ACCESS DOOR DETAIL NO.7
SCALE: NOT TO SCALE
8
TYPICAL ACCESS DOOR DETAIL NO.8
SCALE: NOT TO SCALE
WFG JOB NO
N. WEINGARTZ
DRAWN BY
1200912
SHEET NUMBER
Author
JUNCTION BOX
TYPICAL ACCESS DOOR DETAIL NO.6
SCALE: NOT TO SCALE
WFG PE/PM
SCALE
12" = 1'-0"
DATE
22MAY13
FILE PLOT DATE STAMP
EP5−514
5/21/2013 12:17:15 PM
WFG JOB NO.
SHEET NO.
−
DATE
PROJECT ARCH/
ENGR APPROVAL
ISSUED FOR
DEPT. MGR/SUPR
APPROVAL
22MAY13 BIDS
SITE/BUILDING PLAN & NORTH ARROW
NOT
FOR
CON
STRU
CTIO
N
GM DISCLAIMER & TYPICAL NOTES
NO.
PROJECT ARCH/
ENGR APPROVAL
DATE
DEPT. MGR/SUPR
APPROVAL
R E V I S I O N S
CERTIFIED BY
SUPPLIER PROJECT NO.
22733.000
SUPPLIER DRAWN BY
SUPPLIER CHECKED BY
SUPPLIER PE/PM
CONSULTANT A/E
FIRM INFO & LOGO
SMITHGROUPJJR, INC
500 GRISWOLD SUITE 1700
DETROIT, MI 48226
T 313.983.3600 F 313.983.3636
www.smithgroupjjr.com
Worldwide Facilities Group
General Motors Corporation
Warren Technical Center Campus
Site ID: 1563
Structure ID: 4235
Level:
ELECTRICAL DETAILS
WFG PE/PM
WFG JOB NO
N. WEINGARTZ
DRAWN BY
1200912
SHEET NUMBER
Author
SCALE
12" = 1'-0"
DATE
22MAY13
FILE PLOT DATE STAMP
EP5−515
5/21/2013 12:17:16 PM
−
SHEET NO.
DATE
PROJECT ARCH/
ENGR APPROVAL
ISSUED FOR
DEPT. MGR/SUPR
APPROVAL
22MAY13 BIDS
BASEMENT
SUBSTATION NO. 6A
BASEMENT
SUBSTATION NO. 6B
A-4
B-4
80E
80E
SUB 6A
750/1000 KVA
13.2KV-480Y/277V
SUB 6B
750/1000 KVA
13.2KV-480Y/277V
1600AF
1200AT
SITE/BUILDING PLAN & NORTH ARROW
KEYED NOTES
PROVIDE QUANTITY OF
CIRCUITS AS REQUIRED
1600AF
1200AT
E501
E502
6A-2
800AF
400AT
6A-4
6B-2
6B-3
800AF
TIE
1600AF
1000AT
800AF
600AT
800AF
800AT
E503
DATA CABLING TO A/V MACHINE
ROOM FOR RELAY CONTROL
800AF
800AT
NEW A/V PANELBOARD SHALL CONTAIN
ISOLATED GROUND BUS.
MOUNT FUSED DISCONNECT WITHIN LINE
OF SIGHT OF PROJECTOR.
VERIFY THE ORIGINATION OF THE
NORMAL POWER SOURCE OF THE
EXISITNG AUTOMATIC TRANSFER SWITCH
'ATS-1'. NEW SWITCH 'ATS-2' NORMAL
POWER SOURCE SHALL ORIGINATE FROM
THE SAME SUBSTATION BRANCH AS THE
EXISTING ATS.
NOT
FOR
CON
STRU
CTIO
N
GM DISCLAIMER & TYPICAL NOTES
TYPICAL LIGHTING RELAY PANEL DETAIL
SPARE
SPARE
SPARE
TO LIGHT FIXTURES/
RECEPTACLES
LRP
480Y/277V
3PH,4W BUS
SPACE
800AF
6B-1
SPACE
SPACE
800AF
800AT
6A-3
LP-RING
225A
SPACE
6A-1
480Y/277V
3PH,4W BUS
600A
480V
3P,3W
T-B-11
300 KVA
480 ∆-208Y/120V
30A
30A
60A
30A
30A
30A
30A
200A
200A
20A
20A
40A
20A
20A
10A
20A
200A
200A
100A
125A
100A
100A
100A
200A
200A
200A
200A
100A
100A
400A
400A
400A
400A
SPACE
FA-BL21
400A
FA-BL22
400A
LP-B-8
RELOCATED
60A/3/45A
T-B-8
30 KVA
480V-208Y/120V
60A/3/40A
FABL-12
T
1 1/2 HP
(E)EF-6
2 SPEED
ELEVATOR
CONTROLLER
FA-BP11A
FABL-13
30A,
3P
VFD
N
FA-L22
T-LP-RING
75 KVA
480V-208Y/120V
3 PHASE
E
E501
TO TUNNEL
LP-B-8E
FA-BP11
200A
T-LP-AV
150 KVA
480V-208Y/120V
3 PHASE
30A/3/15A
DEPT. MGR/SUPR
APPROVAL
CERTIFIED BY
22733.000
30A,
3P
FA-L21
PROJECT ARCH/
ENGR APPROVAL
DATE
SUPPLIER PROJECT NO.
ATS-1
100A
SPD-1
NO.
R E V I S I O N S
SPARE
B-11
DOME
1ST FL
J-CLOSET
SPACE
SPACE
800A, 480V, 3PH, 3W
SPACE
400A
1200A, 208Y/120V, 3PH, 4W
400A
BASEMENT
SPACE
200A
MCC-1
SPACE
125A
BASEMENT
800A, 480Y/277V, 3PH, 4W
SPACES
100A
800A, 480Y/277V, 3PH, 4W
PDP-1
BASEMENT
200A
LDP-2
100A
BASEMENT
PDP-PV
MAIN
FOUNTAIN VAULT
1000A
LDP-1
100A
WFG JOB NO.
HWP-1
30A,
3P
VFD
30A,
3P
VFD
30A,
3P
VFD
30A,
3P
VFD
SUPPLIER DRAWN BY
VFD
SUPPLIER CHECKED BY
HWP-2
RAFAHU-3
SAFAHU-3
CHWP-1 CHWP-2
SUPPLIER PE/PM
CONSULTANT A/E
FIRM INFO & LOGO
ATS-2 E503
45A
100A FEEDER
LP-AV
400A
L
E502
E502
J
100A FEEDER
(TYP.)
60A,
3P
60A,
3P
J
(TYP.)
60A,
3P
T-LP-M
30 KVA
480V-208Y/120V
3 PHASE
J
SMITHGROUPJJR, INC
500 GRISWOLD SUITE 1700
DETROIT, MI 48226
T 313.983.3600 F 313.983.3636
www.smithgroupjjr.com
LP-RING
225A
60A,
3P
LP-M-1E
SOUTH AUDITORIUM
PROJECTOR (REDUNDANT)
NORTH AUDITORIUM
PROJECTOR (REDUNDANT)
(E)EF-4
AUDITORIUM EXHAUST
Worldwide Facilities Group
General Motors Corporation
Warren Technical Center Campus
Site ID: 1563
Structure ID: 4235
Level:
ELECTRICAL ONE−LINE
DIAGRAM
WFG PE/PM
WFG JOB NO
N. WEINGARTZ
DRAWN BY
1200912
SHEET NUMBER
Author
SCALE
12" = 1'-0"
DATE
22MAY13
FILE PLOT DATE STAMP
EP6−511
5/21/2013 12:17:17 PM
WFG JOB NO.
SHEET NO.
−
DATE
PROJECT ARCH/
ENGR APPROVAL
ISSUED FOR
DEPT. MGR/SUPR
APPROVAL
22MAY13 BIDS
Branch Panel: NEW SPD-1
Branch Panel: LP-B-8E
Location:
Supply From: LDP-1
Mounting: Surface
Enclosure: Type 1
Volts: 480Y/277
Phases: 3
Wires: 4
A.I.C. Rating:
Mains Type:
Mains Rating:
MCB Rating:
Location:
Supply From: T-B-8
Mounting: Surface
Enclosure: Type 1
65,000
MAIN CIRCUIT BREAKER
125 A
125 A
Notes:
CKT
1
3
5
7
9
11
13
15
17
19
21
23
25
27
29
Volts: 208Y/120
Phases: 3
Wires: 4
A.I.C. Rating:
Mains Type: MAIN LUGS ONLY
Mains Rating: 100 A
MCB Rating: 100 A
Notes:
Circuit Description
RESERVED FOR EXISTING LOAD
RESERVED FOR EXISTING LOAD
RESERVED FOR EXISTING LOAD
RESERVED FOR EXISTING LOAD
RESERVED FOR EXISTING LOAD
RESERVED FOR EXISTING LOAD
Spare
Spare
Spare
Spare
Spare
Spare
Space
Space
Space
Trip
Poles
A
B
C
Poles
20 A
1
750 VA 750 VA
1
20 A
1
750 VA 750 VA
1
20 A
1
750 VA 750 VA
1
20 A
1
750 VA 750 VA
1
20 A
1
750 VA 750 VA
1
20 A
1
750 VA 750 VA
1
20 A
1
0 VA
0 VA
1
20 A
1
0 VA
0 VA
1
20 A
1
0 VA
0 VA
1
20 A
1
0 VA
0 VA
1
20 A
1
0 VA
0 VA
1
20 A
1
0 VA
0 VA
1
--0 VA
0 VA
---0 VA
0 VA
---0 VA
0 VA
-3000 VA
3000 VA
3000 VA
Total Load:
11 A
11 A
11 A
Total Amps:
Trip
20 A
20 A
20 A
20 A
20 A
20 A
20 A
20 A
20 A
20 A
20 A
20 A
----
Circuit Description
RESERVED FOR EXISTING LOAD
RESERVED FOR EXISTING LOAD
RESERVED FOR EXISTING LOAD
RESERVED FOR EXISTING LOAD
RESERVED FOR EXISTING LOAD
RESERVED FOR EXISTING LOAD
Spare
Spare
Spare
Spare
Spare
Spare
Space
Space
Space
CKT
2
4
6
8
10
12
14
16
18
20
22
24
26
28
30
CKT
1
3
5
7
9
11
13
15
17
19
21
23
Circuit Description
EXISTING LOAD
EXISTING LOAD
EXISTING LOAD
EXISTING LOAD
EXISTING LOAD
EXISTING LOAD
EXISTING LOAD
EXISTING LOAD
EXISTING LOAD
EXISTING LOAD
EXISTING LOAD
DRY PIPE COMPRESSOR
Demand Factor
125.00%
B
C
750 VA 750 VA
750 VA 750 VA
750 VA 750 VA
750 VA 750 VA
750 VA 750 VA
750 VA
0 VA
750 VA
0 VA
750 VA 750 VA
750 VA 750 VA
750 VA 750 VA
5250 VA
44 A
5250 VA
44 A
200 VA 750 VA
5450 VA
45 A
Poles
1
1
1
1
1
1
1
1
1
1
1
1
Trip
20 A
20 A
20 A
20 A
20 A
20 A
20 A
20 A
20 A
20 A
20 A
20 A
Circuit Description
EXISTING LOAD
EXISTING LOAD
EXISTING LOAD
EXISTING LOAD
EXISTING LOAD
EXISTING LOAD
Spare
Spare
EXISTING LOAD
EXISTING LOAD
EXISTING LOAD
EXISTING LOAD
CKT
2
4
6
8
10
12
14
16
18
20
22
24
Legend:
Load Classification
Mechanical Equipment
Existing Load
Connected Load
9000 VA
A
750 VA 750 VA
SITE/BUILDING PLAN & NORTH ARROW
NOT
FOR
CON
STRU
CTIO
N
GM DISCLAIMER & TYPICAL NOTES
Legend:
Load Classification
Existing Load
Trip
Poles
20 A
1
20 A
1
20 A
1
20 A
1
20 A
1
20 A
1
20 A
1
20 A
1
20 A
1
20 A
1
20 A
1
20 A
1
Total Load:
Total Amps:
Estimated Demand
11250 VA
Connected Load
200 VA
15750 VA
Demand Factor
80.00%
125.00%
Estimated Demand
160 VA
19688 VA
Panel Totals
Total Conn. Load:
Total Est. Demand:
Total Conn. Current:
Total Est. Demand Current:
9000 VA
11250 VA
11 A
14 A
Panel Totals
Total Conn. Load:
Total Est. Demand:
Total Conn. Current:
Total Est. Demand Current:
15950 VA
19848 VA
44 A
55 A
Notes:
Notes:
Branch Panel: NEW FA-BP11
Location:
Supply From:
Mounting:
Enclosure:
Branch Panel: LP-B-8
Volts: 208Y/120
Phases: 3
Wires: 4
MULTI-PURPOSE ROOM 115
LDP-2
Surface
Type 1
A.I.C. Rating:
Mains Type:
Mains Rating:
MCB Rating:
Location:
Supply From: LDP-2
Mounting: Surface
Enclosure: Type 1
MATCH EXISTING
MCB
225 A
200 A
Notes:
Volts: 208Y/120
Phases: 3
Wires: 4
A.I.C. Rating:
Mains Type: MAIN LUGS ONLY
Mains Rating: 125 A
MCB Rating: 125 A
NO.
PROJECT ARCH/
ENGR APPROVAL
DATE
Notes:
DEPT. MGR/SUPR
APPROVAL
R E V I S I O N S
CERTIFIED BY
SUPPLIER PROJECT NO.
22733.000
CKT
1
3
5
7
9
11
13
15
17
19
21
23
25
27
29
31
33
35
37
39
41
43
45
47
49
51
53
55
57
59
Circuit Description
Trip
Poles
A
B
C
1500... 1000...
FA-BP11A
125 A
3
1500... 1000...
1500... 1000...
MULTI-PURPOSE ROOM 115 LIGHTING
STAGE LIGHT PIPE RECEPTS VIA RELAY PANEL
STAGE LIGHT PIPE RECEPTS VIA RELAY PANEL
STAGE LIGHT PIPE RECEPTS VIA RELAY PANEL
STAGE LIGHT PIPE RECEPTS VIA RELAY PANEL
STAGE LIGHT PIPE RECEPTS VIA RELAY PANEL
STAGE LIGHT PIPE RECEPTS VIA RELAY PANEL
STAGE LIGHT PIPE RECEPTS VIA RELAY PANEL
STAGE LIGHT PIPE RECEPTS VIA RELAY PANEL
STAGE LIGHT PIPE RECEPTS VIA RELAY PANEL
STAGE LIGHT PIPE RECEPTS VIA RELAY PANEL
Spare
Spare
Spare
Spare
Spare
RESERVED FOR EXISTNG LOADS
RESERVED FOR EXISTNG LOADS
RESERVED FOR EXISTNG LOADS
RESERVED FOR EXISTNG LOADS
RESERVED FOR EXISTNG LOADS
Space
Space
Space
Space
Space
Space
20 A
1
20 A
1
20 A
1
20 A
1
20 A
1
20 A
1
20 A
1
20 A
1
20 A
1
20 A
1
20 A
1
20 A
1
20 A
1
20 A
1
20 A
1
20 A
1
20 A
1
20 A
1
20 A
1
20 A
1
20 A
1
------------Total Load:
Total Amps:
576 VA 1000...
1162... 1000...
1500... 1000...
1660... 1360...
948 VA 1360...
1414... 1360...
1414... 1360...
948 VA 1526...
1660... 100 VA
1500... 900 VA
1162... 900 VA
0 VA
0 VA
0 VA
0 VA
0 VA
0 VA
0 VA
0 VA
0 VA
0 VA
750 VA 750 VA
750 VA 750 VA
750 VA 750 VA
750 VA 750 VA
750 VA 750 VA
0 VA
0 VA
0 VA
0 VA
0 VA
0 VA
0 VA
0 VA
0 VA
13770 VA
116 A
0 VA
14506 VA
122 A
0 VA
0 VA
12534 VA
104 A
Poles
1
1
1
1
1
1
1
1
1
1
1
1
Trip
20 A
20 A
20 A
20 A
20 A
20 A
20 A
20 A
20 A
20 A
20 A
20 A
Circuit Description
STAGE LIGHTING RECEPTS VIA RELAY PANEL
STAGE LIGHTING RECEPTS VIA RELAY PANEL
STAGE LIGHTING RECEPTS VIA RELAY PANEL
STAGE LIGHTING RECEPTS VIA RELAY PANEL
STAGE LIGHTING RECEPTS VIA RELAY PANEL
STAGE LIGHTING RECEPTS VIA RELAY PANEL
STAGE COVE LTG RECEPTS VIA RELAY PANEL
STAGE COVE LTG RECEPTS VIA RELAY PANEL
STAGE COVE LTG RECEPTS VIA RELAY PANEL
STAGE COVE LTG RECEPTS VIA RELAY PANEL
STAGE COVE LTG VIA RELAY PANEL
ACCESS CONTROL DOOR POWER SUPPLY
2
30 A
RECEPT - STAGE
1
1
1
1
1
1
1
1
1
1
-------
20 A
20 A
20 A
20 A
20 A
20 A
20 A
20 A
20 A
20 A
-------
Spare
Spare
Spare
Spare
Spare
RESERVED FOR EXISTNG LOADS
RESERVED FOR EXISTNG LOADS
RESERVED FOR EXISTNG LOADS
RESERVED FOR EXISTNG LOADS
RESERVED FOR EXISTNG LOADS
Space
Space
Space
Space
Space
Space
CKT
2
4
6
8
10
12
14
16
18
20
22
24
26
28
30
32
34
36
38
40
42
44
46
48
50
52
54
56
58
60
CKT
1
3
5
7
9
11
13
15
17
19
21
23
Circuit Description
EXISTING LOAD
EXISTING LOAD
EXISTING LOAD
EXISTING LOAD
EXISTING LOAD
EXISTING LOAD
EXISTING LOAD
EXISTING LOAD
EXISTING LOAD
EXISTING LOAD
Trip
20 A
20 A
20 A
20 A
20 A
20 A
20 A
20 A
20 A
20 A
Poles
1
1
1
1
1
1
1
1
1
1
Existing Load
500 A
2
Total Load:
Total Amps:
A
750 VA 750 VA
B
750 VA 750 VA
750 VA 750 VA
750 VA 750 VA
750 VA 750 VA
750 VA 750 VA
750 VA 750 VA
750 VA 523 VA
6000 VA
51 A
5773 VA
49 A
C
Poles
1
1
750 VA 750 VA
1
1
1
750 VA 750 VA
1
1
1
750 VA 750 VA
1
1
1
750 VA 0 VA
-5250 VA
44 A
Trip
20 A
20 A
20 A
20 A
20 A
20 A
20 A
20 A
20 A
20 A
20 A
--
Circuit Description
EXISTING LOAD
EXISTING LOAD
EXISTING LOAD
EXISTING LOAD
EXISTING LOAD
EXISTING LOAD
EXISTING LOAD
EXISTING LOAD
EXISTING LOAD
EXISTING LOAD
MECHANICAL EQUIPMENT ROOM 002
Space
CKT
2
4
6
8
10
12
14
16
18
20
22
24
SUPPLIER DRAWN BY
SUPPLIER CHECKED BY
SUPPLIER PE/PM
CONSULTANT A/E
SMITHGROUPJJR, INC
500 GRISWOLD SUITE 1700
DETROIT, MI 48226
T 313.983.3600 F 313.983.3636
www.smithgroupjjr.com
Legend:
Load Classification
Lighting
Mechanical Equipment
Existing Load
Connected Load
200 VA
323 VA
16500 VA
Demand Factor
100.00%
80.00%
125.00%
Estimated Demand
200 VA
258 VA
20625 VA
FIRM INFO & LOGO
Panel Totals
Total Conn. Load:
Total Est. Demand:
Total Conn. Current:
Total Est. Demand Current:
17023 VA
21083 VA
47 A
59 A
Worldwide Facilities Group
Notes:
General Motors Corporation
Warren Technical Center Campus
Site ID: 1563
Legend:
Structure ID: 4235
Load Classification
Power
Lighting
Receptacle
Existing Load
Connected Load
100 VA
26910 VA
1800 VA
12000 VA
Demand Factor
100.00%
100.00%
100.00%
125.00%
Estimated Demand
100 VA
26910 VA
1800 VA
15000 VA
Panel Totals
Total Conn. Load:
Total Est. Demand:
Total Conn. Current:
Total Est. Demand Current:
Level:
40810 VA
43810 VA
113 A
122 A
Notes:
ELECTRICAL PANEL
SCHEDULES
WFG PE/PM
WFG JOB NO
N. WEINGARTZ
DRAWN BY
1200912
SHEET NUMBER
Author
SCALE
DATE
22MAY13
FILE PLOT DATE STAMP
EB7−711
5/21/2013 12:15:48 PM
WFG JOB NO.
SHEET NO.
−
DATE
PROJECT ARCH/
ENGR APPROVAL
ISSUED FOR
DEPT. MGR/SUPR
APPROVAL
22MAY13 BIDS
Branch Panel: NEW FA-BL12
Location:
Supply From:
Mounting:
Enclosure:
Branch Panel: NEW FA-BL13
Volts: 208Y/120
Phases: 3
Wires: 4
COAT ROOM 118
NEW FA-BL21
Surface
Type 1
A.I.C. Rating:
Mains Type:
Mains Rating:
MCB Rating:
Location:
Supply From:
Mounting:
Enclosure:
22,000
MCB
100 A
100 A
Notes:
CKT
1
3
5
7
9
11
13
15
17
19
21
23
25
27
29
Volts: 208Y/120
Phases: 3
Wires: 4
SECURITY CLOSET 127D
NEW FA-BL22
SURFACE
Type 1
A.I.C. Rating:
Mains Type:
Mains Rating:
MCB Rating:
22,000
MAIN CIRCUIT BREAKER
125 A
125 A
Notes:
Circuit Description
UH-1
MENS TOILET AUTO FLUSH/FAUCET RECEPT
MENS TOILET AUTO FLUSH/FAUCET RECEPT
COAT ROOM 118, MENS TLT 120, 121 LIGHTING
WEST LOBBY, CANOPY LIGHTING
Spare
Spare
Spare
Spare
Spare
RESERVED FOR EXISTING LOADS
RESERVED FOR EXISTING LOADS
RESERVED FOR EXISTING LOADS
RESERVED FOR EXISTING LOADS
RESERVED FOR EXISTING LOADS
Trip
Poles
A
20 A
1
230 VA 1127...
20 A
1
20 A
1
20 A
1
755 VA 400 VA
20 A
1
20 A
1
20 A
1
0 VA
0 VA
20 A
1
20 A
1
20 A
1
0 VA
0 VA
20 A
1
20 A
1
20 A
1
750 VA 750 VA
20 A
1
20 A
1
4012 VA
Total Load:
33 A
Total Amps:
B
C
Poles
1
1060... 100 VA
1
1560... 500 VA
1
1
168 VA 0 VA
1
0 VA
0 VA
1
1
0 VA
0 VA
1
0 VA
0 VA
1
1
750 VA 750 VA
1
750 VA 750 VA
1
1
750 VA 750 VA
1
750 VA 750 VA
1
4328 VA
5060 VA
36 A
43 A
Trip
20 A
20 A
20 A
20 A
20 A
20 A
20 A
20 A
20 A
20 A
20 A
20 A
20 A
20 A
20 A
Circuit Description
EF-2
WEST DOOR CHEXIT
ADA DOOR WEST LOBBY
FLAT PANEL TV
Spare
Spare
Spare
Spare
Spare
Spare
RESERVED FOR EXISTING LOADS
RESERVED FOR EXISTING LOADS
RESERVED FOR EXISTING LOADS
RESERVED FOR EXISTING LOADS
RESERVED FOR EXISTING LOADS
CKT
2
4
6
8
10
12
14
16
18
20
22
24
26
28
30
Legend:
Load Classification
Power
Lighting
Mechanical Equipment
Receptacle
Appliance
Existing Load
Connected Load
100 VA
923 VA
3757 VA
720 VA
400 VA
7500 VA
Demand Factor
100.00%
100.00%
80.00%
100.00%
100.00%
125.00%
Estimated Demand
100 VA
923 VA
3006 VA
720 VA
400 VA
9375 VA
Panel Totals
Total Conn. Load:
Total Est. Demand:
Total Conn. Current:
Total Est. Demand Current:
13400 VA
14524 VA
37 A
40 A
CKT
1
3
5
7
9
11
13
15
17
19
21
23
25
27
29
31
33
35
37
39
41
Circuit Description
UH-2
RECEPTS - GREEN ROOM
RECEPTS - COPIER, GREEN ROOM
WOMENS TOILET AUTO FLUSH/FAUCET,...
WOMENS TOILET AUTO FLUSH/FAUCET,...
GREEN RM, COPY RM, WOMEN TLT LTG
FLAT PANEL TV'S
Spare
Spare
Spare
Spare
Spare
Spare
RESERVED FOR EXISTING LOADS
RESERVED FOR EXISTING LOADS
RESERVED FOR EXISTING LOADS
RESERVED FOR EXISTING LOADS
RESERVED FOR EXISTING LOADS
RESERVED FOR EXISTING LOADS
RESERVED FOR EXISTING LOADS
RESERVED FOR EXISTING LOADS
Trip
Poles
20 A
1
20 A
1
20 A
1
20 A
1
20 A
1
20 A
1
20 A
1
20 A
1
20 A
1
20 A
1
20 A
1
20 A
1
20 A
1
20 A
1
20 A
1
20 A
1
20 A
1
20 A
1
20 A
1
20 A
1
20 A
1
Total Load:
Total Amps:
A
230 VA 7567...
B
C
720 VA 3000...
1180... 3000...
1060... 100 VA
1360... 500 VA
452 VA 168 VA
600 VA
0 VA
0 VA
0 VA
0 VA
0 VA
0 VA
0 VA
0 VA
0 VA
0 VA
0 VA
0 VA
0 VA
750 VA 750 VA
750 VA 750 VA
750 VA 750 VA
750 VA 750 VA
750 VA 750 VA
750 VA 750 VA
750 VA 750 VA
12557 VA
106 A
10080 VA
85 A
750 VA 750 VA
9300 VA
78 A
Poles
1
Trip
20 A
Circuit Description
EF-1
2
40 A
IWH-1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
20 A
20 A
20 A
20 A
20 A
20 A
20 A
20 A
20 A
20 A
20 A
20 A
20 A
20 A
20 A
20 A
20 A
20 A
EAST EXTERIOR DOOR SECURITY
ADA DOOR EAST LOBBY
EAST VESTIBULE AND CANOPY LIGHTING
Spare
Spare
Spare
Spare
Spare
Spare
Spare
RESERVED FOR EXISTING LOADS
RESERVED FOR EXISTING LOADS
RESERVED FOR EXISTING LOADS
RESERVED FOR EXISTING LOADS
RESERVED FOR EXISTING LOADS
RESERVED FOR EXISTING LOADS
RESERVED FOR EXISTING LOADS
RESERVED FOR EXISTING LOADS
CKT
2
4
6
8
10
12
14
16
18
20
22
24
26
28
30
32
34
36
38
40
42
Legend:
Load Classification
Power
Lighting
Mechanical Equipment
Receptacle
Appliance
Existing Load
Notes:
Connected Load
100 VA
620 VA
15997 VA
2620 VA
600 VA
12000 VA
Demand Factor
100.00%
100.00%
80.00%
100.00%
100.00%
125.00%
Estimated Demand
100 VA
620 VA
12798 VA
2620 VA
600 VA
15000 VA
Panel Totals
Total Conn. Load:
Total Est. Demand:
Total Conn. Current:
Total Est. Demand Current:
31937 VA
31738 VA
89 A
88 A
SITE/BUILDING PLAN & NORTH ARROW
NOT
FOR
CON
STRU
CTIO
N
GM DISCLAIMER & TYPICAL NOTES
Notes:
Branch Panel: NEW FA-BL21
Location:
Supply From:
Mounting:
Enclosure:
Branch Panel: NEW FA-BL22
Volts: 208Y/120
Phases: 3
Wires: 4
MECH EQUIP ROOM 203
LDP-2
Surface
Type 1
A.I.C. Rating:
Mains Type:
Mains Rating:
MCB Rating:
Location:
Supply From:
Mounting:
Enclosure:
22,000
MAIN CIRCUIT BREAKER
400 A
400 A
Notes:
CKT
1
3
5
7
9
11
13
15
17
19
21
23
25
27
29
31
33
35
37
39
41
43
45
47
49
51
53
55
57
59
61
63
65
67
69
71
73
75
77
79
81
83
Volts: 208Y/120
Phases: 3
Wires: 4
MECH EQUIP ROOM 202
LDP-2
Surface
Type 1
A.I.C. Rating:
Mains Type:
Mains Rating:
MCB Rating:
22,000
MAIN CIRCUIT BREAKER
400 A
400 A
Notes:
Circuit Description
Trip
Poles
A
4012...
NEW FA-BL12
100 A
3
AHU LIGHTS
UH-4
20 A
20 A
1
1
(R)DWH-1
30 A
2
L3 LIGHTING RECEPT VIA RELAY PANEL
L3 LIGHTING RECEPT VIA RELAY PANEL
L3 LIGHTING RECEPT VIA RELAY PANEL
L3 LIGHTING RECEPT VIA RELAY PANEL
L3 LIGHTING RECEPT VIA RELAY PANEL
INNER RIM COVE LIGHTING VIA RELAY PANEL
INNER RIM COVE LIGHTING VIA RELAY PANEL
INNER RIM COVE LIGHTING VIA RELAY PANEL
INNER RIM COVE LIGHTING VIA RELAY PANEL
INNER RIM COVE LIGHTING VIA RELAY PANEL
INNER RIM COVE LIGHTING VIA RELAY PANEL
EAST ENTRY LIGHTING VIA RELAY PANEL
20 A
20 A
20 A
20 A
20 A
20 A
20 A
20 A
20 A
20 A
20 A
20 A
1
1
1
1
1
1
1
1
1
1
1
1
FCU-1
20 A
3
B
0 VA
C
Poles
1
4328... 200 VA
1
5060... 1610...
1
Circuit Description
UH-6
AHU LIGHTS
CP-1,3, & 4
200 VA 756 VA
403 VA 756 VA
3
20 A
FPB-2
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
----1
1
1
1
1
1
1
1
20 A
20 A
20 A
20 A
20 A
20 A
20 A
20 A
20 A
20 A
20 A
20 A
20 A
20 A
20 A
20 A
20 A
20 A
20 A
20 A
20 A
20 A
20 A
20 A
----20 A
20 A
20 A
20 A
20 A
20 A
20 A
20 A
OUTER RIM COVE LIGHTING VIA RELAY PANEL
OUTER RIM COVE LIGHTING VIA RELAY PANEL
OUTER RIM COVE LIGHTING VIA RELAY PANEL
OUTER RIM COVE LIGHTING VIA RELAY PANEL
OUTER RIM COVE LIGHTING VIA RELAY PANEL
O. RIM COVE & ENTRY TRK LTG VIA RELAY...
INNER RIM COVE LIGHTING VIA RELAY PANEL
INNER RIM COVE LIGHTING VIA RELAY PANEL
INNER RIM COVE LIGHTING VIA RELAY PANEL
INNER RIM COVE LIGHTING VIA RELAY PANEL
INNER RIM COVE LIGHTING VIA RELAY PANEL
INNER RIM COVE LIGHTING VIA RELAY PANEL
WEST ENTRY LIGHTING VIA RELAY PANEL
ACCESS CONTROL DOOR POWER SUPPLY
MOTOIZED SHADES - BOARDROOM
FLOOR BOXES - BOARD ROOM
Spare
Spare
Spare
Spare
Spare
Spare
Spare
Spare
Space
Space
Space
Space
RESERVED FOR EXISTING LOAD
RESERVED FOR EXISTING LOAD
RESERVED FOR EXISTING LOAD
RESERVED FOR EXISTING LOAD
RESERVED FOR EXISTING LOAD
RESERVED FOR EXISTING LOAD
RESERVED FOR EXISTING LOAD
RESERVED FOR EXISTING LOAD
2250... 756 VA
2250... 1100...
1360... 1424...
1360... 1100...
1360... 1100...
1360... 1100...
1360... 1424...
1200... 1200...
1200... 1200...
1200... 1200...
1200... 1200...
1200... 1200...
1200... 1200...
862 VA 862 VA
720 VA 200 VA
720 VA 200 VA
720 VA 360 VA
Spare
Spare
Spare
Spare
Spare
Spare
Spare
Spare
Space
Space
Space
Space
RESERVED FOR EXISTING LOAD
RESERVED FOR EXISTING LOAD
RESERVED FOR EXISTING LOAD
RESERVED FOR EXISTING LOAD
RESERVED FOR EXISTING LOAD
RESERVED FOR EXISTING LOAD
RESERVED FOR EXISTING LOAD
RESERVED FOR EXISTING LOAD
Trip
20 A
20 A
20 A
20 A
1
0 VA
0 VA
20 A
1
0 VA
0 VA
20 A
1
0 VA
0 VA
20 A
1
0 VA
0 VA
20 A
1
0 VA
0 VA
20 A
1
0 VA
0 VA
20 A
1
0 VA
0 VA
20 A
1
0 VA
0 VA
--0 VA
0 VA
--0 VA
0 VA
--0 VA
0 VA
--0 VA
0 VA
20 A
1
750 VA 750 VA
20 A
1
750 VA 750 VA
20 A
1
750 VA 750 VA
20 A
1
750 VA 750 VA
20 A
1
750 VA 750 VA
20 A
1
750 VA 750 VA
20 A
1
750 VA 750 VA
20 A
1
750 VA 750 VA
21382 VA
21151 VA
25140 VA
Total Load:
178 A
176 A
210 A
Total Amps:
CKT
2
4
6
8
10
12
14
16
18
20
22
24
26
28
30
32
34
36
38
40
42
44
46
48
50
52
54
56
58
60
62
64
66
68
70
72
74
76
78
80
82
84
CKT
1
3
5
7
9
11
13
15
17
19
21
23
25
27
29
31
33
35
37
39
41
43
45
47
49
51
53
55
57
59
Circuit Description
RECEPT - GLYCOL PUMPS BASEMENT
Trip
20 A
Poles
A
1
864 VA 870 VA
B
C
12557... 200 VA
NEW FA-BL13
125 A
3
10080... 403 VA
9300... 1360...
2904... 1360...
CRU-1
20 A
3
2904... 1360...
2904... 1360...
756 VA 1360...
FBP-1
20 A
3
756 VA 1444...
756 VA 1444...
Spare
Spare
Spare
Spare
Spare
Spare
Spare
RESERVED FOR EXISTING LOAD
RESERVED FOR EXISTING LOAD
RESERVED FOR EXISTING LOAD
RESERVED FOR EXISTING LOAD
RESERVED FOR EXISTING LOAD
RESERVED FOR EXISTING LOAD
RESERVED FOR EXISTING LOAD
RESERVED FOR EXISTING LOAD
Space
Space
Space
Space
Space
20 A
1
0 VA
0 VA
20 A
1
0 VA
0 VA
20 A
1
0 VA
0 VA
20 A
1
0 VA
0 VA
20 A
1
0 VA
0 VA
20 A
1
0 VA
0 VA
20 A
1
0 VA
0 VA
20 A
1
750 VA 750 VA
20 A
1
750 VA 750 VA
20 A
1
750 VA 750 VA
20 A
1
750 VA 750 VA
20 A
1
750 VA 750 VA
20 A
1
750 VA 750 VA
20 A
1
750 VA 750 VA
20 A
1
750 VA 750 VA
--0 VA
0 VA
--0 VA
0 VA
--0 VA
0 VA
--0 VA
0 VA
--0 VA
0 VA
23358 VA
22137 VA
21447 VA
Total Load:
196 A
185 A
179 A
Total Amps:
Poles
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
------
Trip
20 A
20 A
20 A
20 A
20 A
20 A
20 A
20 A
20 A
20 A
20 A
20 A
20 A
20 A
20 A
20 A
20 A
20 A
20 A
20 A
20 A
20 A
20 A
20 A
20 A
------
Circuit Description
RC-2
AHU LIGHTS
UH-3
L3 LIGHTING RECEPTS VIA RELAY PANEL
L3 LIGHTING RECEPTS VIA RELAY PANEL
L3 LIGHTING RECEPTS VIA RELAY PANEL
L3 LIGHTING RECEPTS VIA RELAY PANEL
L3 LIGHTING RECEPTS VIA RELAY PANEL
WEST BOARDROOM LIGHTING VIA RELAY...
EAST BOARDROOM LIGHTING VIA RELAY...
Spare
Spare
Spare
Spare
Spare
Spare
Spare
RESERVED FOR EXISTING LOAD
RESERVED FOR EXISTING LOAD
RESERVED FOR EXISTING LOAD
RESERVED FOR EXISTING LOAD
RESERVED FOR EXISTING LOAD
RESERVED FOR EXISTING LOAD
RESERVED FOR EXISTING LOAD
RESERVED FOR EXISTING LOAD
Space
Space
Space
Space
Space
CKT
2
4
6
8
10
12
14
16
18
20
22
24
26
28
30
32
34
36
38
40
42
44
46
48
50
52
54
56
58
60
NO.
PROJECT ARCH/
ENGR APPROVAL
DATE
R E V I S I O N S
CERTIFIED BY
SUPPLIER PROJECT NO.
22733.000
SUPPLIER DRAWN BY
SUPPLIER CHECKED BY
SUPPLIER PE/PM
CONSULTANT A/E
FIRM INFO & LOGO
SMITHGROUPJJR, INC
500 GRISWOLD SUITE 1700
DETROIT, MI 48226
T 313.983.3600 F 313.983.3636
www.smithgroupjjr.com
Worldwide Facilities Group
Legend:
Load Classification
Power
Lighting
Mechanical Equipment
Receptacle
Appliance
Existing Load
Connected Load
100 VA
10508 VA
29114 VA
2620 VA
600 VA
24000 VA
Demand Factor
100.00%
100.00%
80.00%
100.00%
100.00%
125.00%
Estimated Demand
100 VA
10508 VA
23291 VA
2620 VA
600 VA
30000 VA
General Motors Corporation
Panel Totals
Total Conn. Load:
Total Est. Demand:
Total Conn. Current:
Total Est. Demand Current:
66942 VA
67119 VA
186 A
186 A
Warren Technical Center Campus
Site ID: 1563
Structure ID: 4235
Notes:
Legend:
Load Classification
Power
Lighting
Mechanical Equipment
Receptacle
Appliance
Existing Load
DEPT. MGR/SUPR
APPROVAL
Level:
Connected Load
860 VA
31495 VA
14698 VA
720 VA
400 VA
19500 VA
Demand Factor
100.00%
100.00%
80.00%
100.00%
100.00%
125.00%
Estimated Demand
860 VA
31495 VA
11758 VA
720 VA
400 VA
24375 VA
Panel Totals
Total Conn. Load:
Total Est. Demand:
Total Conn. Current:
Total Est. Demand Current:
67673 VA
69608 VA
188 A
193 A
ELECTRICAL PANEL
SCHEDULES
Notes:
WFG PE/PM
WFG JOB NO
N. WEINGARTZ
DRAWN BY
1200912
SHEET NUMBER
Author
SCALE
DATE
22MAY13
FILE PLOT DATE STAMP
EB7−712
5/21/2013 12:15:50 PM
WFG JOB NO.
SHEET NO.
−
DATE
PROJECT ARCH/
ENGR APPROVAL
ISSUED FOR
DEPT. MGR/SUPR
APPROVAL
22MAY13 BIDS
Branch Panel: NEW FA-L21
Location:
Supply From:
Mounting:
Enclosure:
Branch Panel: NEW FA-L22
Volts: 480Y/277
Phases: 3
Wires: 4
MECH EQUIP ROOM 203
LDP-1
Surface
Type 1
A.I.C. Rating:
Mains Type:
Mains Rating:
MCB Rating:
Location:
Supply From:
Mounting:
Enclosure:
65,000
MCB
400 A
400 A
Notes: PROVIDE PANEL WITH DOUBLE LUGS
CKT
1
3
5
7
9
11
13
15
17
19
21
23
25
27
29
Circuit Description
RAF-1
Trip
Poles
20 A
3
A
2550... 5845...
B
C
2550... 5845...
Poles
Trip
3
40 A
Circuit Description
SAF-1
2550... 5845...
20 A
3
2550... 5845...
3
40 A
SAF-4
1
1
1
1
1
1
----
20 A
20 A
20 A
20 A
20 A
20 A
----
Spare
Spare
Spare
Spare
Spare
Spare
Space
Space
Space
2550... 5845...
5462...
ATS-2
45 A
0 VA
3
3600...
0 VA
4800...
Spare
Spare
Spare
Space
Space
Space
A.I.C. Rating:
Mains Type:
Mains Rating:
MCB Rating:
65,000
MCB
225 A
200 A
Notes: PANEL SHALL CONTAIN DOUBLE LUGS
2550... 5845...
RAF-4
Volts: 480Y/277
Phases: 3
Wires: 4
MECH EQUIP ROOM 202
PDP-1
Surface
Type 1
20 A
1
20 A
1
20 A
1
------Total Load:
Total Amps:
0 VA
0 VA
0 VA
0 VA
0 VA
0 VA
0 VA
0 VA
0 VA
0 VA
22252 VA
81 A
0 VA
0 VA
0 VA
21590 VA
79 A
20390 VA
74 A
CKT
2
4
6
8
10
12
14
16
18
20
22
24
26
28
30
CKT
1
3
5
7
9
11
13
15
17
19
21
23
25
27
29
Circuit Description
SAF-2
Trip
Poles
40 A
3
B
C
5845... 2550...
Poles
Trip
Circuit Description
3
20 A
RAF-2
1
20 A
SP-1 & 2
3
45 A
ATS-2 (EMERGEMCY FEED)
1
1
1
1
1
1
1
1
20 A
20 A
20 A
20 A
20 A
20 A
20 A
20 A
Spare
Spare
Spare
Spare
Spare
Spare
Spare
Spare
5845... 2550...
0 VA
(E)60A RECEPTACLE
60 A
0 VA
2019...
(E)EF-4
20 A
Spare
Spare
Spare
Spare
Spare
Spare
20 A
20 A
20 A
20 A
20 A
20 A
1828...
3
1
1
1
1
1
1
2019...
0 VA
0 VA
0 VA
2019...
0 VA
0 VA
0 VA
0 VA
0 VA
0 VA
0 VA
0 VA
0 VA
3
20
Total Amps:
Legend:
A
5845... 2550...
0 VA
0 VA
0 VA
12242 VA
44 A
0 VA
10414 VA
38 A
0 VA
0 VA
10414 VA
38 A
CKT
2
4
6
8
10
12
14
16
18
20
22
24
26
28
30
Legend:
Load Classification
Power
Lighting
Mechanical Equipment
Existing Load
Connected Load
0 VA
7662 VA
50570 VA
6000 VA
Demand Factor
0.00%
100.00%
80.00%
125.00%
Estimated Demand
0 VA
7662 VA
40456 VA
7500 VA
Panel Totals
Total Conn. Load:
Total Est. Demand:
Total Conn. Current:
Total Est. Demand Current:
Load Classification
Power
Mechanical Equipment
64232 VA
55618 VA
77 A
67 A
Notes:
Connected Load
0 VA
33071 VA
Demand Factor
0.00%
80.00%
Estimated Demand
0 VA
26456 VA
Panel Totals
Total Conn. Load:
Total Est. Demand:
Total Conn. Current:
Total Est. Demand Current:
33071 VA
26456 VA
40 A
32 A
SITE/BUILDING PLAN & NORTH ARROW
NOT
FOR
CON
STRU
CTIO
N
GM DISCLAIMER & TYPICAL NOTES
Notes:
Branch Panel: NEW LP-AV
Location:
Supply From:
Mounting:
Enclosure:
Branch Panel: NEW LP-M-1E
Volts: 208Y/120
Phases: 3
Wires: 4
MECH EQUIP ROOM 202
T-LP-AV
Surface
Type 1
A.I.C. Rating:
Mains Type:
Mains Rating:
MCB Rating:
Location:
Supply From:
Mounting:
Enclosure:
10,000
MAIN CIRCUIT BREAKER
400 A
400 A
Notes:
PROVIDE INTEGRAL ISOLATED GROUND BUS AND ISOLATED GROUND CONDUCTOR FROM NEW TRANSFORMER.
MECH EQUIP ROOM 202
T-LP-M
Surface
Type 1
Volts: 208Y/120
Phases: 3
Wires: 4
A.I.C. Rating:
Mains Type:
Mains Rating:
MCB Rating:
10,000
MAIN CIRCUIT BREAKER
100 A
100 A
Notes:
NO.
CKT
1
3
5
7
9
11
13
15
17
19
21
23
25
27
29
31
33
35
37
39
41
43
45
47
49
51
53
55
57
59
61
63
65
67
69
71
73
75
77
79
81
83
Circuit Description
A/V RACK
A/V RACK
A/V RACK
A/V RACK
A/V RACK
A/V RACK
RECEPT - RING SPEAKER
RECEPT - RING PROJECTOR
RECEPT - RING SPEAKER
RECEPT - RING SPEAKER
RECEPT - RING PROJECTOR
RECEPT - RING SPEAKER
Trip
20 A
20 A
20 A
20 A
20 A
20 A
20 A
20 A
20 A
20 A
20 A
20 A
Poles
1
1
1
1
1
1
1
1
1
1
1
1
A
1000... 1000...
B
C
1000... 1000...
1000... 1000...
1000... 1000...
1000... 700 VA
1000... 500 VA
500 VA 1500...
1500... 500 VA
500 VA 500 VA
500 VA 1500...
1500... 500 VA
500 VA 500 VA
4560... 1500...
AUDITORIUM PROJECTORS SOUTH
100 A
3
4560... 500 VA
4560... 1200...
4560... 1200...
AUDITORIUM PROJECTORS NORTH
100 A
3
4560... 1200...
4560... 1180...
AV SPEAKERS
AV SPEAKERS
AV SPEAKERS
AV SPEAKERS
20 A
20 A
20 A
20 A
1
1
1
1
AV SPEAKERS
20 A
2
AV SPEAKERS
20 A
2
AV SPEAKERS
20 A
2
AV SPEAKERS
20 A
2
BOARDROOM MOTORIZED SCREEN
FLOOR BOX BOARDROOM
FLOOR BOX BOARDROOM
PTZ CAMERAS
RECEPTS - DIPLAY AREA STEPS
RECEPTS - DIPLAY AREA STEPS
MOTORIZED SCREEN
Spare
Spare
Spare
Spare
Spare
20 A
20 A
20 A
20 A
20 A
20 A
20 A
20 A
20 A
20 A
20 A
20 A
1
1
1
1
1
1
1
1
1
1
1
1
Total Amps:
960 VA 680 VA
960 VA 1000...
960 VA 860 VA
960 VA 960 VA
480 VA 960 VA
480 VA 960 VA
480 VA 960 VA
480 VA 480 VA
480 VA 480 VA
480 VA 480 VA
480 VA 480 VA
480 VA 480 VA
500 VA 480 VA
360 VA 480 VA
360 VA 480 VA
360 VA 1080...
540 VA 1080...
540 VA 500 VA
500 VA 1000...
0 VA
1000...
0 VA
0 VA
0 VA
0 VA
0 VA
29700 VA
252 A
0 VA
27300 VA
232 A
0 VA
0 VA
24060 VA
201 A
Poles
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
Trip
20 A
20 A
20 A
20 A
20 A
20 A
20 A
20 A
20 A
20 A
20 A
20 A
20 A
20 A
20 A
20 A
20 A
20 A
20 A
20 A
20 A
20 A
20 A
20 A
20 A
Circuit Description
A/V RACK
A/V RACK
A/V RACK
A/V RACK
BOARDROOM PROJECTOR AND LIFT
RECEPT - RING SPEAKER
RECEPT - RING PROJECTOR
RECEPT - RING SPEAKER
RECEPT - RING SPEAKER
RECEPT - RING PROJECTOR
RECEPT - RING SPEAKER
RECEPT - RING SPEAKER
RECEPT - RING PROJECTOR
RECEPT - RING SPEAKER
AV SPEAKERS
AV SPEAKERS
AV SPEAKERS
RECEPTS - CONTROL CONSOLE
RECEPTS - CONTROL CONSOLE
RECEPTS - CONTROL CONSOLE
RECEPTS - CONTROL CONSOLE
AV SPEAKERS
AV SPEAKERS
AV SPEAKERS
AV SPEAKERS
2
20 A
AV SPEAKERS
2
20 A
AV AV SPEAKERS
2
20 A
AV SPEAKERS
2
20 A
AV SPEAKERS
1
1
1
1
1
1
1
1
1
20 A
20 A
20 A
20 A
20 A
20 A
20 A
20 A
20 A
PTZ CAMERAS, STAGE RECEPT, STORAGE
STAGE RECEPTS
MOTORIZED SCREEN
A/V RACK
A/V RACK
Spare
Spare
Spare
Spare
CKT
2
4
6
8
10
12
14
16
18
20
22
24
26
28
30
32
34
36
38
40
42
44
46
48
50
52
54
56
58
60
62
64
66
68
70
72
74
76
78
80
82
84
CKT
1
3
5
7
9
11
13
15
17
19
21
23
25
27
29
Circuit Description
INNER RIM COVE EM LTG VIA RELAY PANEL
INNER RIM COVE EM LTG VIA RELAY PANEL
INNER RIM COVE EM LTG VIA RELAY PANEL
STAGE COVE EM LTG VIA RELAY PANEL
Spare
Spare
Spare
Spare
Space
Space
Space
RESERVED FOR EXISTING LIGHTING
RESERVED FOR EXISTING LIGHTING
RESERVED FOR EXISTING LIGHTING
RESERVED FOR EXISTING LIGHTING
Trip
Poles
A
B
C
Poles
20 A
1
1600... 556 VA
1
20 A
1
1600... 500 VA
1
20 A
1
1600... 200 VA
1
20 A
1
1526... 280 VA
1
20 A
1
0 VA
0 VA
1
20 A
1
0 VA
0 VA
1
20 A
1
0 VA
0 VA
1
20 A
1
0 VA
0 VA
1
--0 VA
0 VA
---0 VA
0 VA
---0 VA
0 VA
-20 A
1
750 VA 750 VA
1
20 A
1
750 VA 750 VA
1
20 A
1
750 VA 750 VA
1
20 A
1
750 VA 750 VA
1
5462 VA
3600 VA
4800 VA
Total Load:
47 A
30 A
42 A
Total Amps:
Trip
20 A
20 A
20 A
20 A
20 A
20 A
20 A
20 A
---20 A
20 A
20 A
20 A
Circuit Description
EAST ENTRY COVE EM LTG VIA RELAY PANEL
WEST ENTRY COVE EM LTG VIA RELAY PANEL
DRY PIPE COMPRESSOR
BOARDROOM EM LTG VIA RELAY PANEL
Spare
Spare
Spare
Spare
Space
Space
Space
RESERVED FOR EXISTING LIGHTING
RESERVED FOR EXISTING LIGHTING
RESERVED FOR EXISTING LIGHTING
RESERVED FOR EXISTING LIGHTING
CKT
2
4
6
8
10
12
14
16
18
20
22
24
26
28
30
Connected Load
7662 VA
200 VA
6000 VA
Demand Factor
100.00%
80.00%
125.00%
Estimated Demand
7662 VA
160 VA
7500 VA
CERTIFIED BY
SUPPLIER PROJECT NO.
22733.000
SUPPLIER DRAWN BY
SUPPLIER CHECKED BY
SUPPLIER PE/PM
CONSULTANT A/E
FIRM INFO & LOGO
SMITHGROUPJJR, INC
500 GRISWOLD SUITE 1700
DETROIT, MI 48226
T 313.983.3600 F 313.983.3636
www.smithgroupjjr.com
Panel Totals
Total Conn. Load:
Total Est. Demand:
Total Conn. Current:
Total Est. Demand Current:
DEPT. MGR/SUPR
APPROVAL
R E V I S I O N S
Legend:
Load Classification
Lighting
Mechanical Equipment
Existing Load
PROJECT ARCH/
ENGR APPROVAL
DATE
13862 VA
15322 VA
38 A
43 A
Worldwide Facilities Group
Notes:
General Motors Corporation
Warren Technical Center Campus
Site ID: 1563
Structure ID: 4235
Level:
Legend:
Load Classification
Receptacle
AV Equipment
Connected Load
1080 VA
79980 VA
Demand Factor
100.00%
100.00%
Estimated Demand
1080 VA
79980 VA
Panel Totals
Total Conn. Load:
Total Est. Demand:
Total Conn. Current:
Total Est. Demand Current:
81060 VA
81060 VA
225 A
225 A
ELECTRICAL PANEL
SCHEDULES
Notes:
WFG PE/PM
WFG JOB NO
N. WEINGARTZ
DRAWN BY
1200912
SHEET NUMBER
Author
SCALE
DATE
22MAY13
FILE PLOT DATE STAMP
EB7−713
5/21/2013 12:15:51 PM
WFG JOB NO.
SHEET NO.
−
DATE
PROJECT ARCH/
ENGR APPROVAL
ISSUED FOR
DEPT. MGR/SUPR
APPROVAL
22MAY13 BIDS
Branch Panel: LP-RING
Location:
Supply From: T-LP-RING
Mounting: Surface
Enclosure: Type 1
Volts: 208Y/120
Phases: 3
Wires: 4
A.I.C. Rating:
Mains Type:
Mains Rating:
MCB Rating:
10,000
MCB
225 A
200 A
Notes:
CKT
1
3
5
7
9
11
13
15
17
19
21
23
25
27
29
31
33
35
37
39
41
43
45
47
49
51
53
55
57
59
61
63
65
67
69
71
73
75
77
79
81
83
Circuit Description
RING LIGHTING RECEPTACLE VIA RELAY...
RING LIGHTING RECEPTACLE VIA RELAY...
RING LIGHTING RECEPTACLE VIA RELAY...
RING LIGHTING RECEPTACLE VIA RELAY...
RING LIGHTING RECEPTACLE VIA RELAY...
RING LIGHTING RECEPTACLE VIA RELAY...
RING LIGHTING RECEPTACLE VIA RELAY...
RING LIGHTING RECEPTACLE VIA RELAY...
RING LIGHTING RECEPTACLE VIA RELAY...
RING LIGHTING RECEPTACLE VIA RELAY...
RING LIGHTING RECEPTACLE VIA RELAY...
RING LIGHTING RECEPTACLE VIA RELAY...
RING LIGHTING RECEPTACLE VIA RELAY...
RING LIGHTING RECEPTACLE VIA RELAY...
RING LIGHTING RECEPTACLE VIA RELAY...
RING LIGHTING RECEPTACLE VIA RELAY...
RING LIGHTING RECEPTACLE VIA RELAY...
RING LIGHTING RECEPTACLE VIA RELAY...
RING LIGHTING RECEPTACLE VIA RELAY...
RING LIGHTING RECEPTACLE VIA RELAY...
TYPE L5 RING LIGHTS VIA LIGHTING RELAY...
TYPE L5 RING LIGHTS VIA LIGHTING RELAY...
RING LIGHTING RECEPTACLE VIA RELAY...
RING LIGHTING RECEPTACLE VIA RELAY...
RING LIGHTING RECEPTACLE VIA RELAY...
RING LIGHTING RECEPTACLE VIA RELAY...
RING LIGHTING RECEPTACLE VIA RELAY...
Spare
Spare
Spare
Spare
Spare
Spare
Space
Space
Space
Space
Space
Space
Space
Space
Trip
20 A
20 A
20 A
20 A
20 A
20 A
20 A
20 A
20 A
20 A
20 A
20 A
20 A
20 A
20 A
20 A
20 A
20 A
20 A
20 A
20 A
20 A
20 A
20 A
20 A
20 A
20 A
20 A
20 A
20 A
20 A
20 A
20 A
---------
Poles
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
---------
Total Load:
Total Amps:
A
180 VA 180 VA
B
C
1027... 1027...
1027... 1027...
1027... 1027...
707 VA 707 VA
180 VA 180 VA
1027... 1027...
1027... 1027...
1027... 1027...
707 VA 707 VA
180 VA 180 VA
1027... 1027...
1027... 1027...
1027... 1027...
707 VA 707 VA
180 VA 180 VA
1027... 1027...
1027... 1027...
1027... 1027...
707 VA 707 VA
1400... 1400...
1400... 1400...
180 VA 180 VA
1027... 1027...
1027... 1027...
1027... 1027...
707 VA 707 VA
0 VA
0 VA
0 VA
0 VA
0 VA
0 VA
0 VA
0 VA
0 VA
0 VA
0 VA
0 VA
0 VA
0 VA
0 VA
0 VA
0 VA
0 VA
0 VA
0 VA
0 VA
0 VA
0 VA
0 VA
0 VA
0 VA
0 VA
15204 VA
128 A
0 VA
13818 VA
115 A
0 VA
16258 VA
137 A
Poles
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
----------
Trip
20 A
20 A
20 A
20 A
20 A
20 A
20 A
20 A
20 A
20 A
20 A
20 A
20 A
20 A
20 A
20 A
20 A
20 A
20 A
20 A
20 A
20 A
20 A
20 A
20 A
20 A
20 A
20 A
20 A
20 A
20 A
20 A
20 A
----------
Circuit Description
RING LIGHTING RECEPTACLE VIA RELAY...
RING LIGHTING RECEPTACLE VIA RELAY...
RING LIGHTING RECEPTACLE VIA RELAY...
RING LIGHTING RECEPTACLE VIA RELAY...
RING LIGHTING RECEPTACLE VIA RELAY...
RING LIGHTING RECEPTACLE VIA RELAY...
RING LIGHTING RECEPTACLE VIA RELAY...
RING LIGHTING RECEPTACLE VIA RELAY...
RING LIGHTING RECEPTACLE VIA RELAY...
RING LIGHTING RECEPTACLE VIA RELAY...
RING LIGHTING RECEPTACLE VIA RELAY...
RING LIGHTING RECEPTACLE VIA RELAY...
RING LIGHTING RECEPTACLE VIA RELAY...
RING LIGHTING RECEPTACLE VIA RELAY...
RING LIGHTING RECEPTACLE VIA RELAY...
RING LIGHTING RECEPTACLE VIA RELAY...
RING LIGHTING RECEPTACLE VIA RELAY...
RING LIGHTING RECEPTACLE VIA RELAY...
RING LIGHTING RECEPTACLE VIA RELAY...
RING LIGHTING RECEPTACLE VIA RELAY...
TYPE L5 RING LIGHTS VIA LIGHTING RELAY...
TYPE L5 RING LIGHTS VIA LIGHTING RELAY...
RING LIGHTING RECEPTACLE VIA RELAY...
RING LIGHTING RECEPTACLE VIA RELAY...
RING LIGHTING RECEPTACLE VIA RELAY...
RING LIGHTING RECEPTACLE VIA RELAY...
RING LIGHTING RECEPTACLE VIA RELAY...
Spare
Spare
Spare
Spare
Spare
Spare
Space
Space
Space
Space
Space
Space
Space
Space
Space
CKT
2
4
6
8
10
12
14
16
18
20
22
24
26
28
30
32
34
36
38
40
42
44
46
48
50
52
54
56
58
60
62
64
66
68
70
72
74
76
78
80
82
84
SITE/BUILDING PLAN & NORTH ARROW
NOT
FOR
CON
STRU
CTIO
N
GM DISCLAIMER & TYPICAL NOTES
Legend:
Load Classification
Lighting
Connected Load
45280 VA
Demand Factor
100.00%
Estimated Demand
45280 VA
Panel Totals
Total Conn. Load:
Total Est. Demand:
Total Conn. Current:
Total Est. Demand Current:
45280 VA
45280 VA
126 A
126 A
Notes:
NO.
PROJECT ARCH/
ENGR APPROVAL
DATE
DEPT. MGR/SUPR
APPROVAL
R E V I S I O N S
CERTIFIED BY
SUPPLIER PROJECT NO.
22733.000
SUPPLIER DRAWN BY
SUPPLIER CHECKED BY
SUPPLIER PE/PM
CONSULTANT A/E
FIRM INFO & LOGO
SMITHGROUPJJR, INC
500 GRISWOLD SUITE 1700
DETROIT, MI 48226
T 313.983.3600 F 313.983.3636
www.smithgroupjjr.com
Worldwide Facilities Group
General Motors Corporation
Warren Technical Center Campus
Site ID: 1563
Structure ID: 4235
Level:
ELECTRICAL PANEL
SCHEDULES
WFG PE/PM
WFG JOB NO
N. WEINGARTZ
DRAWN BY
1200912
SHEET NUMBER
Author
SCALE
DATE
22MAY13
FILE PLOT DATE STAMP
EB7−714
5/21/2013 12:15:52 PM