SPECIFICATIONS FOR THREE PHASE PADMOUNT OIL-FILLED TRANSFORMERS A. DESCRIPTION 65 Degrees C rise Pad-mounted Transformer, three phase, OISC, compartmental, type, 60 hz, HV loop-feed, dead-front type conforming w ith ANSI C57.12.26-1987. B. ELECTRICAL High Voltage: Low Voltage: 12,470 Grd Y-7200 volts (95kv BIL) As specified, 480 Grd Y/277 or 208 Grd Y/120 volt 3 phase, 4 w Y Impedance: Per latest ANSI standard (must be stated in bidder’ s quotation) HV – Std. 2-2 ½ % above and 2-2 ½ % below externally operable, non-loadbreak Taps: Connections: Core/Coil Configuration: AU Transformer Spec 5-21-13 HV loop feed (loop-in loop-out) The core and coil assembly shall be w ound core type w ith copper or aluminum w indings. The assembly shall be designed to reduce losses and noise and provide adequate short -circuit strength and heat dissipation. Manufacturer shall design transformers such t hat tank heating problems sometimes associated w ith w ye-w ye connections are eliminated. Internal leads shall be insulated, carefully trained and anchored to prevent phase-to-phase flashover. A tap changing mechanism shall be provided for accurate voltage adjustment w ithout opening the transformer tank. The tap changing mechanism shall be externally operated and shall be for de-energized operation only. The high and low voltage compartments shall be located side-by-side separated by a steel barrier. When facing the transformer, the low voltage compart ment shall be on the right. Terminal compartments shall be full height, air filled w ith individual doors. The high voltage door f astenings shall not be accessible until the low voltage door has been opened. The low voltage door shall have a 3 -point latching mechanism w ith vault type handle having provisions for a single padlock. The doors shall be equipped w ith lift -off type stainless steel hinges and door stops to hold the doors open w hen w orking in the compartments. 1 OF 3 Fusing: C. HV Bay-O-Net Oil Cutout (Current-Sensing Fuse) in series w ith internal ELSP current back-up fuse; one per phase (coordinated t o provide full range protection up to 50,000A) MECHANICAL HV Bushing: 2 loadbreak 200 AMP epoxy bushings per phase, per ANSI C57.12.26, interfaces w ith 200A Load-break, 15 kV, Elbow s. Total of (6) bushing w ells, (6) bushing inserts, (6) parking stands. Elbow s furnished by others. LV Busing: 4 epoxy bushings w ith min.16 hole NEMA tin-= plated CU spades; Externally removable tank ground strap to Xo bushing, per ANSI C57.12.26. Figs. 7 & 8 (a). Provide additional insulated supports for each secondary spade. Enclosure: Steel sealed-tank construction (+ 7.0 psig w ithstand strength), tamper resistant, lift -off doors w ith stainless steel hardw are and captive locking provisions, steel barrier betw een HV & LV compartment, removable sill, lifting eyes and jacking pads w ill be provided, undercoated and painted minimum 3 mils dark bronze. Color t o be Benjamin Moore 16362 or equal. Primary compartment shall be minimum 36” w idth X 18” depth, secondary compartment a minimum 26” w idth X 18” depth. Minimum height to centerline of low est primary bushing 26” minimum and secondary bushing 31” minimum. Accessories: 1. 2. 3. 4. 5. 6. Lighting Arresters: AU Transformer Spec 5-21-13 1” Oil drain valve w ith sampling device (installed in HV Primary compartment, not LV secondary side) 1” Upper filter press and filling plug Liquid level guage Dial type thermometer Pressure/vacuum gauge and pressure relief valve Nameplate in low -voltage compartment Furnish (3) external 9 KV M.O.V. w ith interface to loadbreak expoxy bushings, and st randed ground w ire. 2 OF 3 Grounding Pads: Provide tw o-hole grounded pads in both high and low voltage compartments. Tw o ½ ” dia. threaded holes in each, stainless steel. Transformers shall be furnished w ith: 1. 2. 3. 4. 5. Impedance in percent Guaranteed no-load and load losses, expressed Watts at rated voltage and full load at 60 Hertz, corrected to 85 degrees C, per the latest revision of ANSI C57.12.00 par 8.1.1. Dimensional data including the high and low voltage compartment dimensions (w idt h, height , and depth) and the total w eight of the shipped unit. Insulating Oil shall be FR3 Fluid, as manufactured by Cooper and shall be tested and certified in w riting and a letter accompanying the unit as w ritten below : The dielectric fluid in this unit, serial number _______ has been tested to determine the amount of polychlorinated bipheny(s) PCB content. Manufacturer certifies that based on the test sample, the fluid contains less than 5 ppm PCB and is therefore classified a non-PCB as defined in the August 25, 1982, Vol. 47 No. 165 of t he Federal Register. Unit shall be labeled w ith a non-PCB sticker, conspicuously located to facilitate the inspection by the regulatory compliance officer or any other individual desiring to inspect such equipment. All Impedance, No-Load and Load Losses, and Dimensional Data shall be given prior to the approval by the Ow ner of the construction of the transformer. Failure to furnish Impedance, No-Load and Load Losses, and Dimensional Data including high voltage and low voltage compartment dimensions and w eight s of the transformer may result in rejection of the transformer. Upon aw ard of the transformer, final payment for the unit w ill not be approved until vendor has furnished t he certified oil test report as listed in C.4. above. Approved manufacturers are: Square “ D” , How ard Industries, A.B.B., Cooper (RTE), CG Pow er Systems, and ERMCO. AU Transformer Spec 5-21-13 3 OF 3