27.00-00A - Progress Energy

advertisement

27.00 PAD-MOUNTED TRANSFORMERS- GENERAL

UNDERGROUND DISTRIBUTION SPECIFICATIONS

UNDERGROUND DISTRIBUTION SPECIFICATIONS

LOCATION OF WARNING AND DANGER LABELS FOR PAD-MOUNTED TRANSFORMERS

(VENDOR APPLIED)

LOCATION OF OPTIONAL LABELS FOR PAD-MOUNTED TRANSFORMERS

(FIELD APPLIED)

SPCC (SPILL PREVENTION, CONTROL & COUNTERMEASURES) PLAN

PAD-MOUNTED TRANSFORMER CATALOG NUMBERS SINGLE-PHASE

AND THREE-PHASE

PAD-MOUNTED TRANSFORMER COMPATIBLE UNITS SINGLE-PHASE

PAD-MOUNTED TRANSFORMER COMPATIBLE UNITS SINGLE-PHASE

SINGLE-PHASE PAD-MOUNTED TRANSFORMER WEIGHTS AND OIL CAPACITIES

THREE-PHASE PAD-MOUNTED TRANSFORMER WEIGHTS AND OIL CAPACITIES

MAXIMUM TRANSFORMER LOADING (UG)

REPLACEMENT STUDS - 200 AMP BUSHING WELLS

LOCID LABELING MATERIALS

IDLE TRANSFORMERS

27.01 GROUNDING

GROUNDING DETAILS FOR SINGLE-PHASE LOW-PROFILE PAD-MOUNTED

TRANSFORMERS

GROUND DETAILS FOR THREE-PHASE LOOP FEED TRANSFORMERS

27.02 FUSING

STANDARD SINGLE-PHASE PAD-MOUNTED TRANSFORMERS AND SINGLE-PHASE

FUSE TABLE

STANDARD THREE-PHASE PAD-MOUNTED TRANSFORMERS AND BAY-O-NET

FUSE TABLE

BAY-O-NET FUSE OPERATING INSTRUCTIONS

BAY-O-NET FUSE OPERATING INSTRUCTIONS

27.03 ELBOW ARRESTERS

OPERATING PROCEDURE FOR INSTALLING ELBOW SURGE ARRESTERS

OPERATING PROCEDURE FOR INSTALLING ELBOW SURGE ARRESTERS

OPERATING PROCEDURE FOR MITIGATION OF FERRORESONANCE

IN UNDERGROUND CIRCUITS

ARRESTER - FEED-THRU SINGLE-PHASE PAD-MOUNT WITH INTERNAL ARRESTER

ARRESTER - ELBOW AND FEED-THRU, SINGLE-PHASE PAD-MOUNT

WITHOUT INTERNAL ARRESTER

ARRESTER-ELBOW THREE-PHASE DEADFRONT LOOP WITH INT-HVLA

ARRESTER-ELBOW THREE-PHASE DEADFRONT LOOP NON INT-HVLA

27.00-01

27.00-02

27.00-04

27.00-05

27.00-06

27.00-07

27.00-08A

27.00-08B

27.00-12A

27.00-12B

27.00-13

27.00-16

27.00-20

27.00-22

27.01-03

27.01-04

27.02-06

27.02-08

27.02-09

27.02-10

27.03-02A

27.03-02B

27.03-02C

27.03-12

27.03-13

27.03-14

27.03-15

3

2

1

8/15/14 KATIGBAK GUINN

10/12/12 KATIGBAK BURLISON

0 6/30/10

REVISED

CECCONI

BY

GUINN

CK'D

ADCOCK

ADCOCK

ELKINS

APPR.

SECTION 27 - PAD-MOUNTED TRANSFORMERS

TABLE OF CONTENTS

DEC DEM DEP

X

27.00-00A

DEF

27.05 CABLE AND CONDUIT ENTRANCES

CABLE AND CONDUIT ENTRANCE SINGLE-PHASE PAD-MOUNTED TRANSFORMER

INSTALLATION 100 KVA AND LARGER (CONCRETE PADS ONLY)

CABLE AND CONDUIT ENTRANCE SINGLE-PHASE PAD-MOUNTED TRANSFORMER

INSTALLATION 25-75 KVA (CONCRETE PADS ONLY)

CABLE TRAINING - PADS-VAULTS SINGLE-PHASE PAD-MOUNTED TRANSFORMERS

Z-BAR SECONDARY TERMINALS FOR SINGLE-PHASE LOW PROFILE PAD-MOUNTED

TRANSFORMERS

COMPOSITE HOOD SINGLE-PHASE TRANSFORMER INSTALLATION

FEED THROUGH BUSHING INSERT IN LOW PROFILE PAD-MOUNTED TRANSFORMERS

OPEN WYE-OPEN DELTA TRANSFORMER BANK, 240/120 VOLT, 4-WIRE SERVICE

USING SINGLE-PHASE 13.2KV AND 19.9KV PAD-MOUNTED TRANSFORMERS

OPEN WYE-OPEN DELTA TRANSFORMER BANK, 240/12OV, 4-WIRE SERVICE USING

SINGLE-PHASE 7.2KV PAD-MOUNTED TRANSFORMERS

OPEN WYE-OPEN DELTA TRANSFORMER BANK 480 VOLT, 3-WIRE SERVICE USING

SINGLE-PHASE 7.2KV X 13.2KV PAD-MOUNTED TRANSFORMERS

THREE-PHASE OPEN WYE-OPEN DELTA CONNECTION 7200/12470 X 13200/22860

TO 240/480V PAD-MOUNTED TRANSFORMER 480 VOLT THREE-PHASE

THREE WIRE SERVICE

27.06 THREE-PHASE PAD-MOUNTS

THREE-PHASE PAD-MOUNTED TRANSFORMER GENERAL INFORMATION

THREE-PHASE PAD-MOUNTED TRANSFORMER GENERAL INFORMATION

LOCATION OF OIL-FILLED PAD-MOUNTED TRANSFORMERS

PROTECTIVE POLES FOR OIL FILLED PAD-MOUNTED TRANSFORMERS

THREE-PHASE PAD-MOUNTED TRANSFORMER WITH CUSTOMER'S SECONDARY CABLE

TERMINATION BOX INSTALLATION

RECOMMENDED NUMBER OF CUSTOMER CONDUCTORS IN SECONDARY

COMPARTMENT OF THREE-PHASE PAD-MOUNTED TRANSFORMERS

TRANSFORMER SECONDARY SPADE BLOCK TERMINALS

THREE-PHASE, THREE-WIRE 480 VOLT SERVICE

THREE WIRE SERVICES, FLOATING WYE CONNECTION

FOUR WIRE SERVICES, GROUNDED WYE CONNECTION

THREE-PHASE PAD-MOUNTED TRANSFORMERS PRIMARY AND SECONDARY WINDING -

NEUTRAL CONNECTIONS VARIATIONS FOR 3-WIRE SERVICES

THREE-PHASE PAD-MOUNTED TRANSFORMERS PRIMARY AND SECONDARY WINDING -

NEUTRAL CONNECTIONS LABELS FOR 3 WIRE SERVICES

2500 KVA, THREE-PHASE, PAD-MOUNTED TRANSFORMER WITH

4160Y/2400 VOLT SECONDARY

2500 KVA, THREE-PHASE, PAD-MOUNTED TRANSFORMER WITH

4160Y/2400 VOLT SECONDARY

FOR MAINTENANCE ONLY DRAWINGS

THE FOR MAINTENANCE ONLY DRAWINGS LISTED BELOW ARE NOT CONTAINED IN

THE PRINTED SPEC BOOK, BUT ARE AVAILABLE ONLINE

MINIPAD THREE-PHASE TRANSFORMER (FMO) 27.06-14

27.06-02A

27.06-02B

27.06-05

27.06-06

27.06-08

27.06-09

27.06-12

27.06-16

27.06-20

27.06-24

27.06-26

27.06-28

27.06-34A

27.06-34B

27.05-01

27.05-03

27.05-04

27.05-06

27.05-08

27.05-10

27.05-12

27.05-13

27.05-14A

27.05-14B

3

2

1

11/13/13 KATIGBAK BURLISON

8/17/12

7/15/11

0 11/16/10

REVISED

KATIGBAK BURLISON

CECCONI BURLISON

CECCONI

BY

GUINN

CK'D

ELKINS

ELKINS

ELKINS

ELKINS

APPR.

SECTION 27 - PAD-MOUNTED TRANSFORMERS

TABLE OF CONTENTS

DWG.

27.00-00B

TRANSFORMERS

THE STANDARD TRANSFORMER FOR SINGLE-PHASE UNDERGROUND SYSTEMS IS THE PAD-MOUNTED TYPE WITH

AN INTERNAL, HIGH VOLTAGE WEAK LINK AND BAYONET FUSE. ALL UNITS HAVE A LOADBREAK ELBOW FOR

VISIBLE DISCONNECT MEANS ON EACH OF THE TWO HIGH-VOLTAGE CABLES.

WHERE TRANSFORMERS HAVE TWO DISCONNECT BUSHING WELLS AND ONLY ONE CABLE ELBOW IS TO BE

CONNECTED, A BUSHING AND DEAD-END RECEPTACLE ARE TO BE INSTALLED IN THE UNUSED WELL. UNUSED

CABLE ELBOWS ARE TO HAVE A PLUG OR BUSHING.

THE STANDARD SINGLE-PHASE TRANSFORMER IS MILD STEEL. SPECIAL 304L SERIES STAINLESS STEEL UNITS

ARE AVAILABLE FOR THE DEFINED COASTAL AREAS.

THE STANDARD TRANSFORMER FOR THREE-PHASE UNDERGROUND WYE-SECONDARY SYSTEMS IS THE

PAD-MOUNTED TYPE WITH AN INTERNAL, HIGH VOLTAGE WEAK LINK AND BAYONET FUSE. ON RADIAL FEED

SYSTEMS, PROTECTION MUST BE PROVIDED BY FUSES ON THE DIP POLE SIZED ACCORDING TO FUSING TABLES.

TRANSFORMER PADS

TRANSFORMER PADS AND ALL ASSOCIATED PREPARATIONS FOR A TRANSFORMER SHALL BE CONSTRUCTED

ACCORDING TO SECTION 24. THE EARTH SHALL BE LEVEL AND THOROUGHLY TAMPED TO GIVE COMPACTION

ESSENTIALLY EQUIVALENT TO UNDISTURBED EARTH BEFORE PADS ARE INSTALLED. THE PADS MAY BE PRECAST

OR POURED AT SITE. THOSE PADS POURED AT SITE SHALL BE ALLOWED TO SET A MINIMUM OF THREE DAYS

BEFORE THE TRANSFORMER IS PLACED.

TRANSFORMER INSTALLATION

AT ALL STAGES OF TRANSPORTING AND INSTALLING, CARE SHALL BE TAKEN TO AVOID SCRATCHING OR

DAMAGING THE TRANSFORMER EXTERIOR. DAMAGED AREAS MUST BE TOUCHED-UP WITH PAINT.

DO NOT INSTALL TRANSFORMERS OVER CULVERTS, DRAIN LINES OR DROP INLETS. CARE SHOULD BE TAKEN IN

PLACING THE TRANSFORMER ON THE PAD SO AS TO AVOID DAMAGE TO CABLES AND OTHER EQUIPMENT. THE

TRANSFORMER SHALL BE SECURELY BOLTED TO PAD USING THE BOLTS CAST INTO THE PAD OR OTHER

APPROVED FASTENERS.

LIFTING BOLTS ON EACH SIDE OF A SINGLE-PHASE TRANSFORMER SHOULD BE REMOVED AFTER THE

TRANSFORMER IS INSTALLED. THESE MAY BE KEPT FOR FUTURE USE.

THE CONTACT SURFACE BETWEEN THE TRANSFORMER AND PAD SHALL BE TAMPER-PROOF. ANY SPACE BETWEEN

THE BOTTOM OF TRANSFORMER CABLE COMPARTMENT AND PAD SHALL BE FILLED WITH GROUT ON THE INSIDE

OF THE TERMINAL COMPARTMENT. NO DIRT SHALL BE IN CONTACT WITH THE TRANSFORMER.

TRANSFORMER SECURITY

TRANSFORMER COMPARTMENTS SHALL BE KEPT LOCKED WITH A PADLOCK AT ALL TIMES EXCEPT WHEN WORK

IS BEING PERFORMED IN THE COMPARTMENT ACCORDING TO ESTABLISHED SAFETY RULES. IN ADDITION, EACH

PAD-MOUNTED TRANSFORMER SHOULD BE SECURED WITH A PENTA-HEAD BOLT TO MEET ENCLOSURE INTEGRITY

GUIDELINES OUTLINED IN ANSI STANDARD C57.12.28. EACH PAD-MOUNTED TRANSFORMER IS SHIPPED FROM

THE MANUFACTURER WITH A PENTA-HEAD BOLT IN THE LOCKING MECHANISM.

REPLACEMENT PENTA-HEAD BOLTS WITH FLAT WASHERS AND RETAINERS ARE AVAILABLE AT THE GENERAL

WAREHOUSE (GMX) FOR MAINTENANCE PURPOSES. A COMPATIBLE UNIT (ASSEMBLY) HAS BEEN ESTABLISHED

FOR THE REPLACEMENT PENTA-HEAD BOLT AS FOLLOWS:

PGN COMP. UNIT

TUAPENTABLTC

CATALOG NUMBER

9220110921

9220110923

9220110924

REPLACEMENT PENTA-HEAD BOLTS

QUANTITY

-

-

-

DESCRIPTION

BOLT, 1/2-13, 1-1/4", PENTAHEAD, STAINLESS STEEL

RETAINER, BOLT, 1/2", NEOPRENE

WASHER, FLAT, 1/2", 1" OD, STAINLESS STEEL

3

2

1

0 6/23/10

REVISED

SIMMONS

BY

GUINN

CK'D

ELKINS

APPR.

UNDERGROUND DISTRIBUTION SPECIFICATIONS

R

DWG.

27.00-01

IDENTIFICATION PROCEDURES

ONE OF THE MAJOR DIFFERENCES BETWEEN OVERHEAD AND UNDERGROUND DISTRIBUTION IS THAT THE SOURCE

OF FEED FOR THE VARIOUS CABLES AND APPARATUS CANNOT BE VISIBLY TRACED IN THE UNDERGROUND SYSTEM.

A COMPLETE IDENTIFICATION METHOD MUST BE USED FOR UNDERGROUND PROJECTS. IT MUST BE SIMPLE,

PERMANENT, AND EASILY IDENTIFIABLE IN ORDER TO KNOW THE SOURCE, DIRECTION OF FEED, AND TERMINATION

POINT OF THE CONDUCTORS.

ALL TERMINAL POLES, PADS, TRANSFORMERS, PEDESTALS, PRIMARY PHASES, AND ANY OTHER APPARATUS SHALL

BE NUMBERED OR LETTERED ON LAYOUT MAPS ON THE SYSTEM BY ENGINEERING BEFORE CONSTRUCTION IS

STARTED. DURING CONSTRUCTION, ALL CABLE ENDS MUST BE TAGGED BEFORE TRENCHES ARE BACKFILLED. IF

TEMPORARY TAGS ARE USED DURING CONSTRUCTION, PERMANENT TAGS MUST BE INSTALLED BEFORE THE

SYSTEM IS ENERGIZED. THE LETTERS X, Y, AND Z ARE USED TO IDENTIFY DIFFERENT UNDERGROUND PHASES.

THIS IS DONE TO PREVENT CONFUSION IF THE OVERHEAD PHASES A, B, AND C SERVING THE UNDERGROUND

ARE LATER SWAPPED.

PROTECTION AND COORDINATION

LIGHTNING PROTECTION SHALL BE PROVIDED BY A DIRECT-CONNECTED RISER POLE TYPE ARRESTERS INSTALLED

ON EACH CABLE AT ALL NEW TERMINAL POLES.

IN ADDITION, ON ALL NEW RESIDENTIAL INSTALLATIONS, IF THE TRANSFORMER AT THE OPENING POINT OF THE

UNDERGROUND SYSTEM DOES NOT CONTAIN AN INTERNAL ARRESTER, AN ELBOW ARRESTER SHALL BE INSTALLED.

PROTECTION AGAINST FAULT CURRENTS SHOULD BE PROVIDED BY A SECTIONALIZING FUSE, ON ALL CABLE

TERMINAL POLES AS SPECIFIED BY THE ENGINEER.

CARE SHOULD BE TAKEN TO ENSURE THAT THE PROTECTIVE DEVICE ON THE TERMINAL POLE PROPERLY

COORDINATES WITH THAT IN THE LARGEST TRANSFORMER IN THE LOOP, AS WELL AS THE NEXT OVERHEAD

PROTECTIVE DEVICE TOWARD THE SUBSTATION.

GROUNDING

DRIVEN GROUND RODS SHALL BE PROVIDED AT EACH CABLE TERMINAL POLE AND AT EACH TRANSFORMER.

GROUND LEADS FROM THE DRIVEN GROUNDS SHALL BE SOLIDLY CONNECTED TO THE PRIMARY NEUTRAL, THE

SECONDARY NEUTRAL, AND TO THE GROUNDING CONNECTION OF ALL EQUIPMENT.

REPLACEMENT POLICY

DISTRIBUTION TRANSFORMERS ARE PRIMARY COST COMPONENTS IN PROVIDING CUSTOMER SERVICE. THE

ESTIMATED SERVICE LIFE FOR TRANSFORMERS IS 30 YEARS. TRANSFORMERS SHOULD NOT BE REPLACED UNLESS

ABSOLUTELY NECESSARY.

DO NOT REPLACE A TRANSFORMER UNLESS:

PHYSICAL DAMAGE OCCURS THAT CANNOT BE FIELD REPAIRED SUCH AS BROKEN BUSHINGS, RUSTING,

LEAKING OIL, LOCKING PROBLEMS, DAMAGED DOORS, ETC. BEFORE REPLACING THREE-PHASE

PAD-MOUNTED TRANSFORMERS, CHECK WITH TRANSFORMER REPAIR SHOP TO SEE IF UNIT CAN BE

REPAIRED IN FIELD.

THE CONDITION OF THE TRANSFORMER IS AN IMMEDIATE SAFETY HAZARD.

THE TRANSFORMER IS OVERLOADED.

THE TRANSFORMER IS UNDERLOADED AND CAN BE ECONOMICALLY DOWNSIZED.

THE TRANSFORMER IS AN OBSOLETE SINGLE-PHASE LIVE FRONT PAD-MOUNTED AND THE UNDERGROUND

CABLE IS ALSO BEING REPLACED.

THE TRANSFORMER IS KNOWN TO HAVE A PCB CONCENTRATION OF 50 PPM OR MORE.

TRANSFORMERS SHOULD NOT BE REPLACED WHEN DOING UNDERGROUND PRIMARY CABLE REPLACEMENT UNLESS

THEY ARE LIVE FRONT SINGLE-PHASE UNITS. ALSO, TRANSFORMERS SHOULD NOT BE REPLACED WHEN THE

PRIMARY NON-LOADBREAK ELBOWS ARE BEING REPLACED WITH LOADBREAK ELBOWS. THE BUSHING INSERTS

SHOULD BE REPLACED RATHER THAN THE ENTIRE TRANSFORMER.

REINSTALLATION POLICY

ONLY NON-PCB TRANSFORMERS (LESS THAN 50 PPM) AS SHOWN BY BLUE DOT, BLUE NON-PCB LABEL, OR

NAMEPLATE SHOULD BE INSTALLED. ANY TRANSFORMER OF UNKNOWN PCB CONTENT THAT HAS BEEN REMOVED

FROM SERVICE SHOULD HAVE A "PCB ARTICLE STORAGE FOR REUSE" LABEL PLACED ON IT ( CN 9220066730 )

AND SENT TO THE GARNER TRANSFORMER SHOP. THE LABEL MUST BE PLACED ON THE TRANSFORMER AS SOON

AS IT ARRIVES AT THE L&S YARD.

NON-PCB TRANSFORMERS IN OPERABLE CONDITION SHOULD BE RESTOCKED AND RE-USED. DO NOT SEND

OPERABLE TRANSFORMERS TO THE TRANSFORMER SHOP UNLESS THEY NEED REPAIR, PAINTING, TESTING, OR

HAVE A KNOWN OR ASSUMED PCB CONTENT OF 50 PPM OR MORE.

A PAD-MOUNTED TRANSFORMER OF UNKNOWN PCB CONTENT MAY NOT BE TRANSFERRED IN THE FIELD.

3

2

1

0 6/23/10

REVISED

SIMMONS

BY

GUINN

CK'D

ELKINS

APPR.

UNDERGROUND DISTRIBUTION SPECIFICATIONS

R

DWG.

27.00-02

1X

37 KVA

LOCID NO.

2"

WARNING/SHRUBBERY

LABEL

750 KVA

14.4

SER. NO.

LOCID NO.

2"

PCB STICKER

2"

3 PHASE PAD-MOUNT

DOORS CLOSED

PCB STICKER

WARNING/SHRUBBERY

LABEL

WARNING/SHRUBBERY LABEL

CN 9220111316

EXTERIOR MOUNTING ONLY

2"

1 PHASE MINI-PAD

DOOR CLOSED

NOTES:

1. SURFACE TEMPERATURE SHOULD NOT BE

2. WIPE METAL SURFACES WITH CABLE

CLEANER (CN 30525000) & A CLEAN

CLOTH BEFORE APPLYING LABEL.

3. LABELS MUST BE APPLIED CAREFULLY.

ONCE THIS MATERIAL IS APPLIED, IT

CANNOT BE MOVED.

4. SPACE LOCID LABELING LINES 1/2" APART.

5. ANY TRANSFORMER WITH MISSING WARNING/SHRUBBERY

OR DANGER LABEL SHALL HAVE THESE ADDED AS SOON AS

POSSIBLE.

10"

7"

6"

X0

X1 X3

X2

CL

Hazardous voltage.

Will shock, burn, or cause death.

6"

Qualified personnel only. Protective equipment required.

8"

H

1A

H

1B

C

L

X1

X3

X2

3 PHASE PAD-MOUNT

DOOR OPEN

3

2

1

10/9/13

0 6/23/10

REVISED

SIMMONS

SIMMONS

BY

GUINN

GUINN

CK'D

ADCOCK

ELKINS

APPR.

4-1/2"

DANGER LABEL

INTERIOR MOUNTING ONLY

DANGER LABEL SHALL BE LOCATED ON THE

INSIDE OF TRANSFORMER DOOR, ON CENTER

LINE OF DOOR HANDLE, SIX INCHES FROM

DOOR EDGE AS SHOWN, CN 21129804.

FIGURE 4

LOCATION OF WARNING AND DANGER LABELS

FOR PAD-MOUNTED TRANSFORMERS

(VENDOR APPLIED)

1 PHASE MINI-PAD

DOOR OPEN

DWG.

27.00-04

WARNING LABEL

SEE DWG. 27.00-04

2"

2"

750 KVA

14.4

SER. NO.

LOCID NO.

2"

THREE-PHASE PAD-MOUNT

DOORS CLOSED

2"

2"

1X

37 KVA

LOCID NO.

NORMAL

OPEN POINT

CN 21156005

T

R

E

N

C

H

J

O

I

N

T

'JOINT TRENCH' STICKER

CN 9220120922

CN 440247

2"

2"

CL

2"

WARNING LABEL

SEE DWG. 27.00-04

SINGLE-PHASE MINI-PAD

DOOR CLOSED

"CAUTION" LABEL SHALL BE LOCATED ON THE

OUTSIDE OF TRANSFORMER NEAR DOOR HANDLE.

6"

DANGER LABEL

SEE DWG. 27.00-04

NOTE: THIS STICKER TO BE USED

TO IDENTIFY OPENING POINTS

WHERE THE SOURCES ARE FROM

DIFFERENT FEEDERS. CONTACT

DCC IS REQUIRED.

H

1A

H 1B X1

X3

X2

SINGLE-PHASE MINI-PAD

DOOR OPEN

NOTES:

2. WIPE METAL SURFACES WITH CABLE CLEANER ( CN 30525000 ) & A CLEAN CLOTH BEFORE APPLYING LABEL.

3. LABELS MUST BE APPLIED CAREFULLY. ONCE THIS MATERIAL IS APPLIED, IT CANNOT BE MOVED.

1

0

3

2

2/4/13

1/4/13

11/30/12

6/23/10

REVISED

GUINN

GUINN

GUINN

SIMMONS

BY

GUINN

GUINN

GUINN

ADCOCK

ADCOCK

ADCOCK

GUINN

CK'D

ELKINS

APPR.

LOCATION OF OPTIONAL LABELS

FOR PAD-MOUNTED TRANSFORMERS

(FIELD APPLIED)

R

DWG.

27.00-05

STANDARD PROCEDURES BULLETIN

ALL OIL-FILLED DISTRIBUTION TRANSFORMERS ARE REQUIRED BY FEDERAL REGULATIONS TITLE 40 CFR

PART 112 TO HAVE AN SPCC PLAN WHENEVER:

A)

AND

THE COMBINED CAPACITY OF ALL TRANSFORMERS ON THE SITE IS 1320 GALLONS OR MORE OF OIL.

B) THE SITE IS SUCH THAT AN OCCURRING OIL SPILL CAN REASONABLY BE EXPECTED TO REACH ANY

NAVIGABLE WATER. (PONDS WITH NO OUTLETS DO NOT COUNT AS NAVIGABLE WATER.)

NOTE: A "SITE IS DEFINED AS EITHER ALL OF THE TRANSFORMERS WITHIN AN ENCLOSED FENCE OR

ALL OF THE PAD-MOUNTED TRANSFORMERS SERVING THE SAME POINT OF DELIVERY.

IF IT IS DETERMINED BY A PROFESSIONAL ENGINEER THAT NO PLAN IS NEEDED FOR A SITE BECAUSE AN OIL

SPILL CANNOT REASONABLY BE EXPECTED TO REACH ANY NAVIGABLE WATER, THAT DETERMINATION SHOULD

BE DOCUMENTED. ANY CALCULATIONS SUCH AS THE MOSES PROGRAM RESULTS SHOULD BE KEPT ON FILE IN

THE REGION AND A LETTER OR MEMO TO DISTRIBUTION STANDARDS TO DOCUMENT THAT NO PLAN IS NEEDED.

ALL SPCC SITE PLANS MUST BE REVIEWED AND SEALED BY A PROFESSIONAL ENGINEER. THE PLAN SHOULD BE

REVIEWED BY DISTRIBUTION STANDARDS. THE MASTER SPCC PLAN HAS BEEN SIGNED AND APPROVED BY THE

DISTRIBUTION DEPARTMENT VP AND REGION VPS.

AN SPCC SITE PLAN MUST BE PREPARED AND IMPLEMENTED BEFORE TRANSFORMERS ARE MOVED ON SITE. THE

PLAN MUST BE REVIEWED AND UPDATED EVERY FIVE YEARS. UPDATED PLANS DO NOT REQUIRE A PROFESSIONAL

ENGINEER REVIEW UNLESS MATERIAL CHANGES HAVE OCCURRED IN THE OIL STORAGE VOLUME OR SPILL

CONTROL SYSTEM. THE REGION ENGINEERING SUPERVISOR IS RESPONSIBLE FOR PREPARING SPCC PLANS AND

ASSURING THEIR REGION IS IN COMPLIANCE WITH THESE FEDERAL REGULATIONS. IF AN UPDATED SPCC SITE

PLAN DOES REQUIRE CHANGES IN THE SPILL CONTROL PROGRAM, ALL CHANGES MUST BE IMPLEMENTED WITHIN

SIX MONTHS.

THE SPCC SITE PLAN SHOULD INCLUDE SITE LAYOUT, SITE DRAINAGE DETAILS, OIL CAPACITIES, OIL SPILL DATA

CALCULATIONS, AND A LIST OF SITE RECOMMENDATIONS FOR OIL SPILL PREVENTION/MITIGATION. THE SPCC

PLAN SHOULD IDENTIFY AN INDIVIDUAL(S) (BY NAME OR POSITION) WHO IS RESPONSIBLE FOR INITIATING OIL

SPILL PREVENTION AND EMERGENCY RESPONSE. THE SPCC PLAN SHOULD BE AVAILABLE FOR USE BY THE LINEMEN

RESPONSIBLE FOR MAINTAINING THE FACILITY. COPIES OF ALL SITE INSPECTIONS SHOULD BE RETAINED FOR A

MINIMUM OF THREE YEARS. ALL CORRECTIVE AND PREVENTIVE MAINTENANCE WORK DONE AT THE FACILITY

SHOULD BE DOCUMENTED AND KEPT IN SUPPORT OF THE SPCC PLAN.

THE REPORTING OF ANY OIL SPILLS INVOLVING THESE FACILITIES SHOULD BE DONE ACCORDING TO THE

PROVISIONS OF PROGRESS ENERGY'S ENVIRONMENTAL GUIDANCE DOCUMENT. COPIES OF THESE OIL SPILL

REPORTS SHOULD BE KEPT WITH THE SPCC PLAN.

INSPECTIONS OF FACILITIES WITH SPCC PLANS SHALL BE DONE AT LEAST ANNUALLY, DOCUMENTED AND FILED

FOR AT LEAST THREE YEARS. THE INSPECTION SHALL DOCUMENT THAT THE BERM IS IN GOOD CONDITION AND

THERE IS NO EVIDENCE OF A SPILL OR LEAK.

DOCUMENT

SPCC MASTER PLAN

SPCC SITE PLANS

FIVE YEAR

PLAN REVIEW

REGULAR SITE

INSPECTIONS

DOCUMENTATION

CORRECTIVE &

PREVENTATIVE

WORK DOCUMENTATION

INITIATED BY

DISTRIBUTION

STANDARDS

SYSTEM ENGINEERING

REGION SUPERVISOR

DIST. EQUIPMENT

TECHNICIAN

DIST. EQUIPMENT

TECHNICIAN

DIST. EQUIPMENT

TECHNICIAN

ORIGINAL

DISTRIBUTION -

ENVIRONMENTAL

DISTRIBUTION

STANDARDS

DIST. EQUIPMENT

TECHNICIAN

DIST. EQUIPMENT

TECHNICIAN

DIST. EQUIPMENT

TECHNICIAN

COPIES TO

SYSTEM ENGINEERING

EACH OPS CENTER

SYSTEM ENGINEERING

OPS CTR OF FACILITY LOCATION

DIST. EQUIPMENT TECHNICIAN

DISTRIBUTION

STANDARDS

3

2

1

0 6/23/10

REVISED

SIMMONS

BY

GUINN

CK'D

ELKINS

APPR.

SPCC (SPILL PREVENTION, CONTROL &

COUNTERMEASURES) PLAN

R

DWG.

27.00-06

CATALOG NUMBER

12944104

12944302

12944401

12944500

12944609

* 12944708

* 12941100

* 12941308

* 12941506

* 12941605

* 12941704

6958

6960

9220157891

6961

9220159649

** 9220180535

** 9220180545

KVA

25

50

75

100

167

250

25

50

100

167

250

25

50

75

100

167

50

100

SINGLE-PHASE UNITS

HV

13.2

13.2

13.2

13.2

13.2

13.2

7.2 X 13.2

7.2 X 13.2

7.2 X 13.2

7.2 X 13.2

7.2 X 13.2

7.2

7.2

7.2

7.2

7.2

7.2 X 13.2

7.2 X 13.2

* NO LONGER PURCHASED BUT MAY BE AVAILABLE IN

SMALL QUANTITY. CHECK AVAILABILITY BEFORE ORDERING.

DUAL VOLTAGE UNITS MAY BE SPECIAL ORDERED IF USED

IN PREPARTION FOR A VOLTAGE CONVERSION.

** NEW CATALOG NUMBER. CHECK ON AVAILABILITY OR

LEAD TIME.

LV

120/240

120/240

120/240

120/240

120/240

120/240

120/240

120/240

120/240

120/240

120/240

120/240

120/240

120/240

120/240

120/240

240/480

240/480

12955605

12955704

12955803

12955902

12955910

12958005

12958104

12958203

12958302

12958401

12958500

12952800

12953014

9220126005

** 9220180427

** 9220180430

** 9220180433

** 9220180436

** 9220180428

** 9220180431

** 9220180434

** 9220180413

CATALOG NUMBER

* 12950606

* 12950705

* 12950804

* 12950903

12951000

12970109

* 12952008

* 12952107

* 12952206

* 12952305

12952404

12952503

12952602

12952701

12952719

150

300

500

750

1000

1500

2500

3750

75

150

300

500

750

75

75

150

300

500

75

150

300

500

KVA

75

150

300

500

750

1000

75

150

300

500

750

1000

1500

2500

2500

THREE-PHASE UNITS

HV

12.47KV DELTA

OR 22.86KV WYE

12.47KV DELTA

OR 22.86KV WYE

12.47KV DELTA

OR 22.86KV WYE

12.47KV DELTA

OR 22.86KV WYE

12.47KV DELTA

OR 22.86KV WYE

12.47KV DELTA

OR 22.86KV WYE

12.47KV DELTA

OR 22.86KV WYE

12.47KV DELTA

OR 22.86KV WYE

12.47KV DELTA

OR 22.86KV WYE

12.47KV DELTA

OR 22.86KV WYE

12.47KV DELTA

OR 22.86KV WYE

12.47KV DELTA

OR 22.86KV WYE

12.47KV DELTA

OR 22.86KV WYE

12.47KV DELTA

OR 22.86KV WYE

12.47KV DELTA

OR 22.86KV WYE

22.86

22.86

22.86

22.86

22.86

22.86

12.47

12.47

22.86

22.86

22.86

22.86

22.86

22.86

22.86

22.86

12.47

12.47

12.47

12.47

12.47

12.47

MINI-PADS - USE FOR REPLACEMENTS ONLY -

NO NEW INSTALLATIONS

** 9220127645

* 12951802

* 12951901

75

75

150

12.47 MINI

22.86 MINI

22.86 MINI

208Y/120

208Y/120

208Y/120 NOTES:

1. THESE CATALOG NUMBERS ARE THE STANDARD UNITS THAT ARE CURRENTLY PURCHASED AND STOCKED. OTHER

SPECIAL ORDER UNITS ARE AVAILABLE ON REQUEST.

2. SEE DWG. 12.06-03 FOR STAINLESS STEEL, SINGLE AND THREE-PHASE PAD-MOUNTED TRANSFORMERS. THESE

UNITS ARE TO BE USED ONLY IN DESIGNATED COASTAL AREAS, HIGHLY CORROSIVE AREAS OR VAULTS THAT

ARE SUBJECT TO FLOODING AND/OR OTHER CONTAMINATION.

3. SINGLE-PHASE UNITS WITH A 7.2 X 13.2 RATING AND THREE-PHASE UNITS WITH A 12.47KV DELTA OR

22.86KV WYE RATING CAN BE USED ON 12.47KV OR 23KV SYSTEMS.

4. SEE DWG. 11.00-09 FOR 4160Y/2400 VOLT METERING REQUIREMENTS.

3

2

1

7/12/13

5/7/12

0 11/9/10

REVISED

SIMMONS

SIMMONS BURLISON

SIMMONS

BY

GUINN

GUINN

CK'D

ADKINS

ELKINS

ELKINS

APPR.

PAD-MOUNTED TRANSFORMER CATALOG NUMBERS

SINGLE-PHASE AND THREE-PHASE

DWG.

27.00-07

LV

208Y/120

208Y/120

208Y/120

208Y/120

208Y/120

208Y/120

480Y/277

480Y/277

480Y/277

480Y/277

480Y/277

480Y/277

480Y/277

480Y/277

4160Y/2400

208Y/120

208Y/120

208Y/120

208Y/120

208Y/120

480Y/277

480Y/277

480Y/277

480Y/277

480Y/277

480Y/277

480Y/277

480Y/277

480Y/277

208Y/120

208Y/120

208Y/120

208Y/120

480Y/277

480Y/277

480Y/277

480Y/277

CATALOG

NUMBER

9220180535

9220180545

12947008

12947206

12947107

12942009

12942207

12942405

12942504

12942512

9220159666

9220159667

9220159668

9220159670

9220159672

9220159650

006958

006960

9220157891

006961

9220159649

12944104

12944302

12944401

12944500

12944609

12944708

12941100

12941308

12941506

12941605

12941704

COMPATIBLE

UNIT

TU25DLM121CC

TU50DLM121CC

TU75DLM121CC

TU100DLM121CC

TU167DLM121CC

TU25DLM231CC

TU50DLM231CC

TU75DLM231CC

TU100DLM231CC

TU167DLM231CC

TU250DLM231CC

TU25DLMK1CC

TU50DLMK1CC

TU100DLMK1CC

TU167DLMK1CC

TU250DLMK1CC

TU50DLMK1DC

TU100DLMK1DC

TU25DL3351CC

TU50DL3351CC

TU100DL3351CC

TU25DL3K1CC

TU50DL3K1CC

TU100DL3K1CC

TU167DL3K1CC

TU250DL3K1CC

TU50DL3121CC

TU100DL3121CC

TU167DL3121CC

TU50DL3231CC

TU100DL3231CC

TU167DL3231CC

SINGLE-PHASE UNITS

DESCRIPTION

25KVA DF LOOP MILD 12.47GY/7.2 KV 1PH 240/120V

50KVA DF LOOP MILD 12.47GY/7.2 KV 1PH 240/120V

75KVA DF LOOP MILD 12.47GY/7.2 KV 1PH 240/120V

100KVA DF LOOP MILD 12.47GY/7.2 KV 1PH 240/120V

167KVA DF LOOP MILD 12.47GY/7.2 KV 1PH 240/120V

25KVA DF LOOP MILD 22.86GY/13.2 KV 1PH 240/120V

50KVA DF LOOP MILD 22.86GY/13.2 KV 1PH 240/120V

75KVA DF LOOP MILD 22.86GY/13.2 KV 1 PH 240/120V

100KVA DF LOOP MILD 22.86GY/13.2 KV 1PH 240/120V

167KVA DF LOOP MILD 22.86GY/13.2 KV 1PH 240/120V

250KVA DF LOOP MILD 22.86GY/13.2 KV 1PH 240/120V

25KVA DF LOOP MILD 12.47GY/7.2 X 22.86GY/13.2KV 1PH 240/120V

50KVA DF LOOP MILD 12.47GY/7.2 X 22.86GY/13.2KV 1PH 240/120V

100KVA DF LOOP MILD 12.47GY/7.2 X 22.86GY/13.2KV 1PH 240/120V

167KVA DF LOOP MILD 12.47GY/7.2 X 22.86GY/13.2KV 1PH 240/120V

250KVA DF LOOP MILD 12.47GY/7.2 X 22.86GY/13.2KV 1PH 240/120V

50KVA DF LOOP MILD 12.47GY/7.2 X 22.86GY/13.2KV 1PH 480/240V

100KVA DF LOOP MILD 12.47GY/7.2 X 22.86GY/13.2KV 1PH 480/240V

25KVA DF LOOP 300 34.5GY/19.92 KV 1PH 240/120V

50KVA DF LOOP 300 34.5GY/19.92 KV 1PH 240/120V

100KVA DF LOOP 300 34.5GY/19.92 KV 1PH 240/120V

25KVA DF LOOP 300 12.47GY/7.2 X 22.86GY/13.2KV 1PH 240/120V

50KVA DF LOOP 300 12.47GY/7.2 X 22.86GY/13.2KV 1PH 240/120V

100KVA DF LOOP 300 12.47GY/7.2 X 22.86GY/13.2KV 1PH 240/120V

167KVA DF LOOP 300 12.47GY/7.2 X 22.86GY/13.2KV 1PH 240/120V

250KVA DF LOOP 300 12.47GY/7.2 X 22.86GY/13.2KV 1PH 240/120V

50KVA DF LOOP 300 12.47GY/7.2 KV 1PH 240/120V

100KVA DF LOOP 300 12.47GY/7.2 KV 1PH 240/120V

167KVA DF LOOP 300 12.47GY/7.2 KV 1PH 240/120V

50KVA DF LOOP 300 22.86GY/13.2 KV 1PH 240/120V

100KVA DF LOOP 300 22.86GY/13.2 KV 1PH 240/120V

167KVA DF LOOP 300 22.86GY/13.2 KV 1PH 240/120V

3

2

1

0 6/23/10

REVISED

SIMMONS

BY

GUINN

CK'D

ELKINS

APPR.

PAD-MOUNTED TRANSFORMER COMPATIBLE UNITS

SINGLE-PHASE

R

DWG.

27.00-08A

CATALOG

NUMBER

9220208470

9220208474

9220208462

9220208476

9220180427

9220180430

9220180433

9220180436

9220180428

9220180431

9220180434

9220180413

9220208467

9220208472

9220208473

9220125211

12951802

12951901

12946505

12946604

12946703

12946802

12946901

12948907

12948808

12948709

12948600

12948501

12948402

12952909

9220127645

12950804

12950903

12951000

12970109

12952008

12952107

12952206

12952305

12952404

12952503

12952602

12952701

12952719

9220066815

9220125190

9220125187

12955605

12955704

12955803

12955902

12955910

12958005

12958104

12958203

12958302

12958401

12958500

12952800

12953014

9220126005

12950606

12950705

COMPATIBLE

UNIT

TU500DL335YFC

TU75MP3M23YBC

TU150MP3M23YBC

TU75DL314DYBC

TU150DL314DYBC

TU300DL314DYBC

TU500DL314DYBC

TU750DL314DYBC

TU75DL314DYFC

TU150DL314DYFC

TU300DL314DYFC

TU500DL314DYFC

TU750DL314DYFC

TU1000DL314DYFC

TU1500DL314DYFC

TU75MP3M12YBC

TU1500DLM23DDFC

TU2500DLM23DDFC

TU3750DLM23DDFC

TU2500DLM23DDJC

TU75DLM12YBC

TU150DLM12YBC

TU300DLM12YBC

TU500DLM12YBC

TU75DLM12YFC

TU150DLM12YFC

TU300DLM12YFC

TU500DLM12YFC

TU1500DLM12YFC

TU2500DLM12YFC

TU2500DLM12YJC

TU75DLM23YBC

TU150DLM23YBC

TU300DLM23YBC

TU500DLM23YBC

TU750DLM23YBC

TU75DLM23YFC

TU150DLM23YFC

TU300DLM23YFC

TU500DLM23YFC

TU750DLM23YFC

TU1000DLM23YFC

TU1500DLM23YFC

TU2500DLM23YFC

TU3750DLM23YFC

TU75DLM14DYBC

TU150DLM14DYBC

TU300DLM14DYBC

TU500DLM14DYBC

TU750DLM14DYBC

TU1000DLM14DYBC

TU75DLM14DYFC

TU150DLM14DYFC

TU300DLM14DYFC

TU500DLM14DYFC

TU750DLM14DYFC

TU1000DLM14DYFC

TU1500DLM14DYFC

TU2500DLM14DYFC

TU2500DLM14DYJC

TU150DL335YBC

TU500DL335YBC

TU150DL335YFC

THREE-PHASE UNITS

DESCRIPTION

75KVA DF LOOP MILD 22.86GY/13.2 KV WYE 208Y/120V

150KVA DF LOOP MILD 22.86GY/13.2 KV WYE 208Y/120V

300KVA DF LOOP MILD 22.86GY/13.2 KV WYE 208Y/120V

500KVA DF LOOP MILD 22.86GY/13.2 KV WYE 208Y/120V

750KVA DF LOOP MILD 22.86GY/13.2 KV WYE 208Y/120V

75KVA DF LOOP MILD 22.86GY/13.2 KV WYE 480Y/277V

150KVA DF LOOP MILD 22.86GY/13.2 KV WYE 480Y/277V

300KVA DF LOOP MILD 22.86GY/13.2 KV WYE 480Y/277V

500KVA DF LOOP MILD 22.86GY/13.2 KV WYE 480Y/277V

750KVA DF LOOP MILD 22.86GY/13.2 KV WYE 480Y/277V

1000KVA DF LOOP MILD 22.86GY/13.2 KV WYE 480Y/277V

1500KVA DF LOOP MILD 22.86GY/13.2 KV WYE 480Y/277V

2500KVA DF LOOP MILD 22.86GY/13.2 KV WYE 480Y/277V

3750KVA DF LOOP MILD 22.86GY/13.2 KV WYE 480Y/277V

75KVA DF LOOP MILD 14.4/24.94Y/14.4 KV DY 208Y/120V

150KVA DF LOOP MILD 14.4/24.94Y/14.4 KV DY 208Y/120V

300KVA DF LOOP MILD 14.4/24.94Y/14.4 KV DY 208Y/120V

500KVA DF LOOP MILD 14.4/24.94Y/14.4 KV DY 208Y/120V

750KVA DF LOOP MILD 14.4/24.94Y/14.4 KV DY 208Y/120V

1000KVA DF LOOP MILD 14.4/24.94Y/14.4 KV DY 208Y/120V

75KVA DF LOOP MILD 14.4/24.94Y/14.4 KV DY 480Y/277V

150KVA DF LOOP MILD 14.4/24.94Y/14.4 KV DY 480Y/277V

300KVA DF LOOP MILD 14.4/24.94Y/14.4 KV DY 480Y/277V

500KVA DF LOOP MILD 14.4/24.94Y/14.4 KV DY 480Y/277V

750KVA DF LOOP MILD 14.4/24.94Y/14.4 KV DY 480Y/277V

1000KVA DF LOOP MILD 14.4/24.94Y/14.4 KV DY 480Y/277V

1500KVA DF LOOP MILD 14.4/24.94Y/14.4 KV DY 480Y/277V

2500KVA DF LOOP MILD 14.4/24.94Y/14.4 KV DY 480Y/277V

2500KVA DF LOOP MILD 14.4/24.94Y/14.4 KV DY 4160Y/2400V

150KVA DF LOOP 300 34.5GY/19.92 KV WYE 208Y/120V

500KVA DF LOOP 300 34.5GY/19.92 KV WYE 208Y/120V

150KVA DF LOOP 300 34.5GY/19.92 KV WYE 480Y/277V

500KVA DF LOOP 300 34.5GY/19.92 KV WYE 480Y/277V

75KVA MINIPAD 3PH MILD 22.86GY/13.2 KV WYE 208Y/120V

150KVA MINIPAD 3PH MILD 22.86GY/13.2 KV WYE 208Y/120V

75KVA DF LOOP 300 14.4/24.94Y/14.4 KV DY 208Y/120V

150KVA DF LOOP 300 14.4/24.94Y/14.4 KV DY 208Y/120V

300KVA DF LOOP 300 14.4/24.94Y/14.4 KV DY 208Y/120V

500KVA DF LOOP 300 14.4/24.94Y/14.4 KV DY 208Y/120V

750KVA DF LOOP 300 14.4/24.94Y/14.4 KV DY 208Y/120V

75KVA DF LOOP 300 14.4/24.94Y/14.4 KV DY 480Y/277V

150KVA DF LOOP 300 14.4/24.94Y/14.4 KV DY 480Y/277V

300KVA DF LOOP 300 14.4/24.94Y/14.4 KV DY 480Y/277V

500KVA DF LOOP 300 14.4/24.94Y/14.4 KV DY 480Y/277V

750KVA DF LOOP 300 14.4/24.94Y/14.4 KV DY 480Y/277V

1000KVA DF LOOP 300 14.4/24.94Y/14.4 KV DY 480Y/277V

1500KVA DF LOOP 300 14.4/24.94Y/14.4 KV DY 480Y/277V

75KVA MINIPAD 3PH MILD 12.47GY/7.2 KV WYE 208Y/120V

1500KVA DF LOOP MILD22.86KV DELTA 480Y/277V

2500KVA DF LOOP MILD22.86KV DELTA 480Y/277V

3750KVA DF LOOP MILD22.86KV DELTA 480Y/277V

2500KVA DF LOOP MILD22.86KV DELTA 4160Y/2400V

75KVA DF LOOP MILD 12.47GY/7.2 KV WYE 208Y/120V

150KVA DF LOOP MILD 12.47GY/7.2 KV WYE 208Y/120V

300KVA DF LOOP MILD 12.47GY/7.2 KV WYE 208Y/120V

500KVA DF LOOP MILD 12.47GY/7.2 KV WYE 208Y/120V

75KVA DF LOOP MILD 12.47GY/7.2 KV WYE 480Y/277V

150KVA DF LOOP MILD 12.47GY/7.2 KV WYE 480Y/277V

300KVA DF LOOP MILD 12.47GY/7.2 KV WYE 480Y/277V

500KVA DF LOOP MILD 12.47GY/7.2 KV WYE 480Y/277V

1500KVA DF LOOP MILD 12.47GY/7.2 KV WYE 480Y/277V

2500KVA DF LOOP MILD 12.47GY/7.2 KV WYE 480Y/277V

2500KVA DF LOOP MILD 12.47GY/7.2 KV WYE 4160Y/2400V

3

2

1

0 6/23/10

REVISED

SIMMONS

BY

GUINN

CK'D

ELKINS

APPR.

PAD-MOUNTED TRANSFORMER COMPATIBLE UNITS

THREE-PHASE

R

DWG.

27.00-08B

SIZE

IN KVA

25

25

50

50

75

75

100

100

100

100

100

167

167

25

25

50

50

50

167

250

250

APPROXIMATE WEIGHT IN POUNDS

HV

12470GRDY/7200

22860GRDY/13200

12470GRDY/7200 X 22860GRDY/13200

34500GRDY/19920

12470GRDY/7200

22860GRDY/13200

12470GRDY/7200 X 22860GRDY/13200

34500GRDY/19920

12470GRDY/7200 X 22860GRDY/13200

12470GRDY/7200

22860GRDY/13200

12470GRDY/7200

22860GRDY/13200

12470GRDY/7200 X 22860GRDY/13200

34500GRDY/19920

12470GRDY/7200 X 22860GRDY/13200

12470GRDY/7200

22860GRDY/13200

12470GRDY/7200 X 22860GRDY/13200

22860GRDY/13200

12470GRDY/7200 X 22860GRDY/13200

LV

240/120

240/120

240/120

240/120

240/120

240/120

240/120

240/120

480/240

240/120

240/120

240/120

240/120

240/120

240/120

480/240

240/120

240/120

240/120

240/120

240/120

TOTAL WEIGHT

(POUNDS)

673

605

846

757

854

873

957

973

991

1609

1645

1695

2297

2399

1027

924

1104

1148

1270

1237

1456

OIL CAPACITY

(GALLONS)

34.2

27

50.1

39

43.4

45

49.5

46.5

52.3

48.4

38

46

47

65

53

72

69

75

90

105

106

NOTES:

1. LISTED WEIGHTS AND GALLONS OF OIL ARE TYPICAL FOR UNITS PRESENTLY BEING PURCHASED. OLDER UNITS

MAY BE HEAVIER AND/OR HAVE MORE OIL.

3

2

1

0 8/15/14

REVISED

SIMMONS

BY

GUINN

CK'D

ADCOCK

APPR.

SINGLE-PHASE PAD-MOUNTED TRANSFORMER

WEIGHTS AND OIL CAPACITIES

DEC DEM DEP

X

27.00-12A

DEF

500

500

500

500

750

750

750

750

1000

1000

1000

150

300

300

300

300

300

300

500

500

500

500

1500

1500

2500

2500

2500

3750

150

150

150

150

150

150

SIZE

IN KVA

75

75

75

75

75

75

150

HV

APPROXIMATE WEIGHT IN POUNDS

12470GRDY/7200

22860GRDY/13200

14400/24940GRDY/14400

12470GRDY/7200

22860GRDY/13200

14400/24940GRDY/14400

12470GRDY/7200

22860GRDY/13200

14400/24940GRDY/14400

34500GRDY/19920

12470GRDY/7200

22860GRDY/13200

14400/24940GRDY/14400

34500GRDY/19920

12470GRDY/7200

22860GRDY/13200

14400/24940GRDY/14400

12470GRDY/7200

22860GRDY/13200

14400/24940GRDY/14400

12470GRDY/7200

22860GRDY/13200

14400/24940GRDY/14400

34500GRDY/19920

12470GRDY/7200

22860GRDY/13200

14400/24940GRDY/14400

34500GRDY/19920

22860GRDY/13200

14400/24940GRDY/14400

22860GRDY/13200

14400/24940GRDY/14400

14400/24940GRDY/14400

22860GRDY/13200

14400/24940GRDY/14400

22860GRDY/13200

14400/24940GRDY/14400

22860GRDY/13200

14400/24940GRDY/14400

14400/24940GRDY/14400

22860GRDY/13200

TOTAL WEIGHT

(POUNDS)

2775

5349

4422

6166

7050

7324

6677

6783

7830

5951

4370

4153

5795

5180

5310

5425

6676

5363

7572

7448

10058

10023

14213

14712

13925

19441

2948

3216

2721

2932

3087

3296

3402

3737

-

3226

3328

3849

6166

4701

4807

LV

208Y/120

208Y/120

208Y/120

480Y/277

480Y/277

480Y/277

208Y/120

208Y/120

208Y/120

208Y/120

480Y/277

480Y/277

480Y/277

208Y/120

208Y/120

480Y/277

480Y/277

208Y/120

480Y/277

480Y/277

480Y/277

480Y/277

480Y/277

480Y/277

4160Y/2400

480Y/277

480Y/277

208Y/120

208Y/120

208Y/120

480Y/277

480Y/277

480Y/277

208Y/120

208Y/120

208Y/120

208Y/120

480Y/277

480Y/277

480Y/277

480Y/277

OIL CAPACITY

(GALLONS)

174

198

222

171

198

206

192

199

240

-

181

201

356

222

211

341

197

205

256

247

308

256

250

297

416

407

542

583

569

697

318

326

299

302

337

302

336

222

222

234

308

NOTES:

1. LISTED WEIGHTS AND GALLONS OF OIL ARE TYPICAL FOR UNITS PRESENTLY BEING PURCHASED. OLDER UNITS

MAY BE HEAVIER AND/OR HAVE MORE OIL.

2. TRANSFORMERS > 500 KVA WILL GENERALLY REQUIRE A CRANE FOR LIFTING. ALWAYS VERIFY LIFTING

CAPACITY VS. TRANSFORMER WEIGHT.

3

2

1

0 8/15/14

REVISED

SIMMONS

BY

GUINN

CK'D

ADCOCK

APPR.

THREE-PHASE PAD-MOUNTED TRANSFORMER

WEIGHTS AND OIL CAPACITIES

DEC DEM DEP

X

27.00-12B

DEF

MAXIMUM KVA LOADING

TYPE OF BUSINESS

LARGE OFFICE BUILDINGS

TYPES OF COMMERCIAL AND INDUSTRIAL BUSINESSES

FAST FOOD

SUPERMARKETS

LARGE & SMALL RETAIL STORES

PEAK DEMAND

DURATION

(HOURS)

8

8

8

8

TYPE OF BUSINESS

CONVENIENCE STORES

HOTELS

SMALL OFFICE BUILDINGS

RESTAURANTS

SCHOOLS

PEAK DEMAND

DURATION

(HOURS)

4

4

4

4

4

TRANSFORMER

SIZE

25

37.5

50

75

SINGLE-PHASE COMMERCIAL PAD-MOUNTED TRANSFORMERS

SUMMER (100%)

25

37.5

50

75

WINTER (140%)

35

52

70

105

TRANSFORMER

SIZE

100

167

250

SUMMER (100%)

100

167

250

WINTER (140%)

140

233

350

TRANSFORMER

SIZE

25

37.5

50

SINGLE-PHASE RESIDENTIAL PAD-MOUNTED TRANSFORMERS

SUMMER

130%

32

49

65

WINTER

160%

40

60

80

TRANSFORMER

SIZE

75

100

167

250

SUMMER

130%

97

130

217

325

WINTER

160%

120

160

267

350

BANK SIZE

OR

TRANSFORMER

SIZE

75

112

150

300

500

750

1,000

1,500

2,500

3,000

3,750

750

1,000

1,500

2,500

3,000

3,750

THREE-PHASE UNDERGROUND TRANSFORMERS

HOSPITAL AND SPECIAL

CARE FACILITIES

SUMMER

100%

WINTER

140%

75 105

112

150

300

500

156

210

420

700

1,050

1,400

2,100

3,500

4,200

4,500

INDUSTRIALS

AND VAULTS

SUMMER

100%

WINTER

140%

75

112

150

300

500

750

1,000

1,500

2,500

3,000

3,750

105

156

210

420

700

1,050

1,400

2,100

3,500

4,200

4,500

4 HOUR PEAK

SUMMER

90

134

180

360

600

900

1,200

1,800

3,000

3,600

4,500

WINTER

122

172

225

450

750

1,125

1,500

2,250

3,750

4,500

5,625

8 HOUR PEAK

SUMMER

77

115

155

309

515

773

1,030

1,545

2,575

3,090

3,862

WINTER

105

157

215

425

710

1,060

1,420

2,125

3,540

4,248

5,312

NOTES:

1. SELECT THE TYPE OF BUSINESS. THE CORRESPONDING DEMAND DURATION IS HOW LONG THE CUSTOMER'S

DEMAND LASTS ON PEAK DAYS BASED ON DATA FROM LOAD RESEARCH STUDIES. THE CUSTOMER'S DEMAND

TYPICALLY DROPS TO 75% OF THE MAXIMUM DURING ALL OTHER TIMES.

2. NOTE THAT TRANSFORMER LOADING IS GIVEN IN KVA. ADJUSTMENTS FOR POWER FACTOR NEED TO BE

DEFINED BY THE ENGINEER.

3. HIGHLY FLUCTUATING INTERMITTENT LOADS (HFIL): TAKE THE SUM OF THE HFILS AND DIVIDE BY THREE

( HFIL/3), AND ADD TO THE CONSTANT LOAD. FUSE CURVES NEED TO BE CHECKED BY USING THE SUM OF

THE HFIL (NOT DERATED BY 3) AND THE CONSTANT LOAD DUE TO FUSE PERFORMANCE.

3

2

1

0 6/29/10

REVISED

SIMMONS

BY

GUINN

CK'D

ELKINS

APPR.

MAXIMUM TRANSFORMER LOADING (UG)

R

DWG.

27.00-13

REPLACEMENT STUDS HEX-SPANNER NUT

FRONT VIEW

REPLACEMENT STUD ABB

(2009 AND BEFORE)

STUD SIZE 3/8 X 3/8

CN 10333201

FRONT VIEW

REPLACEMENT STUD CENTRAL MALONEY AND ABB

(MANUFACTURED IN 2010 OR LATER)

STUD SIZE 7/16 X 3/8

CN 10332906

HEX SPANNER NUT

CN 9220201402

(USE WITH 15/16" SHALLOW WELL SOCKET)

NOTE: MUST BE ORDERED SEPARATE.

REPLACEMENT STUD

ELASTIMOLD TYPE

CN 10332807

HEX-ALLEN WRENCH

BUSHING WELL BUSHING INSERT

SIDE VIEW SIDE VIEW

NOTES:

1. ALL PAD-MOUNTED TRANSFORMERS MANUFACTURED AFTER 1983 COME EQUIPPED WITH REPLACEABLE STUD

BUSHING WELLS.

2. BROKEN BUSHING WELL STUDS SHOULD BE REPLACED IN THE FIELD WHEN POSSIBLE.

3. HEX-SPANNER NUT FOR CENTRAL MALONEY OR ABB MUST NOW BE ORDERED SEPARATELY FROM THE STUDS.

4. HEX-ALLEN WRENCH FOR ELASTIMOLD IS INCLUDED WITH EACH REPLACEMENT STUD.

5. TO REPLACE BROKEN STUDS:

A. IDENTIFY WHICH TYPE OF STUD IS TO BE REPLACED.

B. USE CORRECT WRENCH OR NUT FOR APPROPRIATE STUD TO REMOVE BROKEN STUD.

C. INSERT APPROPRIATE END OF REPLACEMENT STUD INTO BUSHING WELL.

D. TIGHTEN REPLACEMENT STUD UNTIL SEATED (APPROXIMATELY 15 FT-LBS).

3

2

1

0 6/30/10

REVISED

SIMMONS

BY

GUINN

CK'D

ELKINS

APPR.

REPLACEMENT STUDS - 200 AMP BUSHING WELLS

R

DWG.

27.00-16

STICK-ON DECALS - 1.5" H X 1" W

F

G

D

E

A

B

C

K

L

H

J

M

LETTERS

21135009 N

21135108

21135207

21135306

21135405

P

Q

R

S

21135504

21135603

21135702

21135801

21135900

21136007

21136106

V

W

T

U

X

Y

Z

21136205

21136304

21136403

21136502

21136601

21136700

21136809

21136908

21137005

21137104

21137203

21137302

ACCESSORIES

TAG HOLDER - AL 30837405

NAILS 1.5"

BANDING - AL

TAPE, TWO-SIDED

30011308

10014801

21153606

MISCELLANEOUS

PEC

LOCID NO.

21138300

21134606

*

NO LETTER "O" OR "I" IS AVAILABLE IN THE LOCID NUMBERING SYSTEM.

7

8

5

6

9

3

4

1

2

0

NUMBERS

21138201

21137401

21137500

21137609

21137708

21137807

21137906

21138003

21138102

21137906

NOTES:

1. DWG. 02.02-20 SHOWS POLE NUMBERS AND FUSE SIZE LABELS.

2. DWGS. 20.01-01B , 25.01-01 AND 28.00-03 SHOW PAD-MOUNTED LABELING.

3. THE ABOVE LETTERS AND NUMBERS ARE BLACK ON A YELLOW BACKGROUND.

4. SURFACES SHOULD BE CLEAN AND DRY BEFORE INSTALLING DECALS.

5. DECALS CAN BE INSTALLED IN TAG HOLDERS OR APPLIED DIRECTLY TO PRIMARY OR SECONDARY CABLES.

3

2

1

0 6/23/10

REVISED

SIMMONS

BY

GUINN

CK'D

ELKINS

APPR.

LOCID LABELING MATERIALS

DWG.

27.00-20

PROGRESS ENERGY STANDARD PROCEDURES BULLETIN

IDLE TRANSFORMERS

DEFINITION:

AN IDLE TRANSFORMER IS A TRANSFORMER THAT IS INSTALLED ON THE DISTRIBUTION SYSTEM BUT IS SERVING

NO USEFUL PURPOSE. THERE IS NO CUSTOMER BEING SERVED, NO LIGHTS, NO TRAFFIC SIGNALS. THERE IS ALSO

NO REASONABLE POTENTIAL FOR SERVING A CUSTOMER IN THE FUTURE. A TRANSFORMER INSTALLED IN A NEW

UNDERGROUND DEVELOPMENT THAT IS SERVING NO CUSTOMERS BUT WILL IN THE FUTURE IS NOT CONSIDERED

IDLE BECAUSE IT WILL BE SERVING CUSTOMERS IN THE NEAR FUTURE.

EXAMPLES ARE AS FOLLOWS:

1. A TRANSFORMER THAT WAS USED FOR TEMPORARY CONSTRUCTION SERVICE IS IDLE AFTER THE

CONSTRUCTION IS COMPLETED AND THE TRANSFORMER IS NO LONGER NEEDED FOR CONSTRUCTION

SERVICE.

2. A TRANSFORMER THAT SERVED A RESIDENTIAL CUSTOMER IS IDLE IF THE HOME IS NO LONGER OCCUPIED

AND THERE IS NO PROSPECT OF SERVING A CUSTOMER AT THE SAME LOCATION.

3. A TRANSFORMER BANK THAT SERVED A COMMERCIAL/INDUSTRIAL CUSTOMER IS IDLE IF THE CUSTOMER

IS NO LONGER IN BUSINESS AND THE TRANSFORMER BANK IS NOT NEEDED FOR A POTENTIAL NEW

CUSTOMER AT THE SAME LOCATION.

ISSUES WITH IDLE TRANSFORMERS:

THERE ARE SEVERAL REASONS WHY IDLE TRANSFORMERS SHOULD BE REMOVED FROM THE SYSTEM. ONE THAT

IS LEFT ENERGIZED EXPERIENCES "NO-LOAD" CORE LOSSES EVEN WHEN IDLE. THESE ARE ANNUAL LOSSES. A

25 KVA TRANSFORMER IS ESTIMATED TO HAVE $35 OF ANNUAL CORE LOSSES. A 167 KVA TRANSFORMER IS

ESTIMATED TO HAVE $200 OF ANNUAL CORE LOSSES. A TRANSFORMER THAT IS IDLE IS A POTENTIAL FOR

VANDALISM, RESULTING IN AN ENVIRONMENTAL ISSUE, AN OIL SPILL. THERE HAVE BEEN A NUMBER OF SPILLS

DUE TO VANDALISM OF IDLE TRANSFORMERS AND SOME OF THESE REQUIRED SIGNIFICANT COSTS FOR CLEANUP.

A TRANSFORMER THAT IS IDLE IS A POTENTIAL HAZARD FOR CRIMINALS WHO WOULD ATTEMPT TO VANDALIZE

THE UNITS TO STEAL COPPER. THEY WILL TAKE EXTRAORDINARY RISKS WITH NO REGARD FOR THEIR OWN

SAFETY OR PROPERTY OF OTHERS.

TRANSFORMER COSTS HAVE INCREASED SUBSTANTIALLY SINCE 2004 DUE TO THE RISING COSTS OF RAW

MATERIALS: COPPER, CORE STEEL, MINERAL OIL. COSTS WILL INCREASE AGAIN SIGNIFICANTLY IN JANUARY, 2010

AS NEW DEPARTMENT OF ENERGY (DOE) EFFICIENCY REQUIREMENTS ARE IMPLEMENTED. IT IS A SIGNIFICANT

FINANCIAL BENEFIT TO THE COMPANY TO REMOVE AND RE-USE IDLE TRANSFORMERS VERSUS BUYING NEW ONES

AT SIGNIFICANTLY HIGHER PRICES. ONES THAT HAVE BEEN REMOVED AND RE-USED DO NOT HAVE TO MEET THE

MORE STRINGENT EFFICIENCY REQUIREMENTS OF DOE.

PROCEDURE:

ANY TRANSFORMER THAT IS IDLE BUT LEFT ON THE POLE SHALL BE DE-ENERGIZED TO SAVE ANNUAL CORE

LOSSES. TRANSFORMERS WITH NO CUTOUTS (CSP) SHALL HAVE THE HOT LINE CLAMP REMOVED FROM THE

PRIMARY AND GROUNDED TO THE SYSTEM NEUTRAL. TRANSFORMERS WITH CUTOUTS MAY BE DE-ENERGIZED

BY OPENING THE CUTOUT AND REMOVING THE CUTOUT BARREL.

WHEN A TRANSFORMER HAS BEEN DE-ENERGIZED, ASSET ENGINEERING SHALL BE NOTIFIED. ASSET

ENGINEERING WILL EVALUATE AND DETERMINE IF THE TRANSFORMER SHOULD BE REMOVED AND IF SO,

PREPARE A WORK ORDER TO REMOVE. ASSOCIATED EQUIPMENT (CUTOUTS, ARRESTERS, SERVICE CONDUCTORS,

ETC.) SHOULD BE REMOVED AT THE SAME TIME THE TRANSFORMER IS REMOVED.

FOR TRANSFORMER BANKS SERVING COMMERCIAL OR INDUSTRIAL CUSTOMERS, CONTACT WITH ACCOUNT

MANAGERS WILL BE REQUIRED TO DETERMINE IF THERE IS POTENTIAL FOR FUTURE CUSTOMERS OCCUPYING A

VACANT FACILITY.

TRANSFORMERS THAT HAVE BEEN REMOVED SHALL BE PLACED IN STOCK AT THE LOCAL STOREROOM, IF THE

TRANSFORMER IS IN GOOD CONDITION AND IS NON-PCB. IF NOT IN GOOD CONDITION, OR THE PCB CONTENT

IS UNKNOWN, THE TRANSFORMER SHALL BE RETURNED TO THE GARNER TRANSFORMER SHOP WHERE IT WILL

BE EVALUATED, REPAIRED, REPAINTED AND RETURNED TO STOCK, IF POSSIBLE.

3

2

1

0 6/23/10

REVISED

SIMMONS

BY

GUINN

CK'D

ELKINS

APPR.

IDLE TRANSFORMERS

R

DWG.

27.00-22

MAKE SURE BUSHING

INSERT IS BONDED TO

METAL. SEE DETAILS

"D" AND "E"

LOOP DRAIN WIRE

SOLDERED TO GROUND

BRAID, OR CONCENTRIC

NEUTRAL WIRE IF USING

CN CABLE, THROUGH

GROUNDING EYE ON

ELBOW

#4 CONNECTOR

CN 162204

H1A

H1B

GROUND BRAIDS

ENSURE GROUND

LOOP IS BONDED

TO TANK AT THESE

THREE LOCATIONS

SEE DETAIL "A"

BONDING PAD

SEE DETAIL "C"

#4 SD BC GROUND LOOP

CN 9220069244

BOND INSERT TO

MOUNTING STUD WHEN

BUSHING FLANGE IS

PLASTIC

DEEP DRIVEN

SECTIONAL ROD

SEE DETAIL "B"

DETAIL "A"

CN 160182

DETAIL "B"

5/8" COUPLING

CN 060136

DETAIL "E"

PLASTIC BUSHING CLAMP

METAL

BUSHING

CLAMP

BAIL-TAB

EYE 5/8" GND. ROD CLAMP

CN 160123

GND. WIRE MUST BE

INSTALLED ON OPPOSITE

SIDE FROM SET SCREW

PMT

BONDING PAD

ACCEPTS 1/2" X 13

CONNECTOR (PROVIDED

BY OTHER UTILITY)

SILL PAD

5/8" X 5'

GND. ROD

CN 9220192319

DETAIL "C"

NOTES:

1. SEE DWG. 20.00-06B FOR ADDITIONAL INFORMATION ON

EQUIPMENT GROUNDING AND BONDING.

3

2

1

0 12/17/14

REVISED

EANES

BY

FLETCHER ADCOCK

CK'D APPR.

GROUNDING DETAILS FOR SINGLE-PHASE

LOW-PROFILE PAD-MOUNTED TRANSFORMERS

INSERT

GROUNDING

PAD

DETAIL "D"

METALLIC BUSHING CLAMP

DEC DEM DEP DEF

X

27.01-03

X

MAKE SURE BUSHING

INSERT IS BONDED TO

METAL. SEE DETAILS

"A" AND "B"

LOOP DRAIN WIRE

SOLDERED TO GROUND

BRAID, OR CONCENTRIC

NEUTRAL WIRE IF USING

CN CABLE, THROUGH

GROUNDING EYE ON

ELBOW

GROUND BRAIDS

#4 BC SD

#4 BC SD

GROUND LOOP

DEP CN 11061108

DEF CN 9220069244

X 1

X 2

X 3

#4 BC SD GROUND LOOP

BONDING PAD

ACCEPTS 1/2"-13

CONNECTOR (PROVIDED

BY OTHER UTILITY)

METAL

BUSHING

CLAMP

BAIL-TAB

EYE

BOND INSERT TO

MOUNTING STUD WHEN

BUSHING FLANGE IS

PLASTIC

INSERT

GROUNDING

PAD

DETAIL "A"

METALLIC BUSHING CLAMP

DETAIL "B"

PLASTIC BUSHING CLAMP

NOTES:

1. THE DRAWING ABOVE SHOWS A H0-X0 GROUNDING BUSHING. SOME DESIGNS HAVE SEPARATE H0 AND X0

GROUNDING BUSHINGS.

2. GROUND WIRE IS TO BE BONDED TO TANK GROUND PADS IN BOTH COMPARTMENTS THROUGH THE GROUND

STRAP AT THE H0 AND X0 BUSHINGS, AND TO THE PRIMARY CONCENTRIC NEUTRAL WITH A COPPER CONNECTOR.

3. FOR TRANSFORMERS WITH A SEPARATE H0 AND X0 BUSHING USED TO PROVIDE 480Y 3 WIRE SERVICES, THE

GROUNDING STRAP SHOULD BE REMOVED FROM THE X0 BUSHING. DO NOT REMOVE THE GROUNDING STRAP

ON THE H0 BUSHING.

4. SEE DWG. 20.00-06B FOR ADDITIONAL INFORMATION ON EQUIPMENT GROUNDING AND

BONDING.

3

2

1

0 12/17/14

REVISED

5. SEE DWGS. 27.06-16 THROUGH 27.06-28 FOR THE GROUNDING REQUIRED ON 3-WIRE

SECONDARY SERVICES.

EANES

BY

FLETCHER ADCOCK

CK'D APPR.

GROUND DETAILS FOR THREE-PHASE

LOOP FEED TRANSFORMERS

DEC DEM DEP DEF

X

27.01-04

X

SINGLE-PHASE PMTS - GENERAL

GENERAL DESIGN:

LIVE FRONT TRANSFORMERS ARE OBSOLETE. WHENEVER THESE TRANSFORMERS ARE REMOVED THEY SHOULD BE

SCRAPPED. ALL NEW TRANSFORMERS ARE DEAD FRONT WITH TWO PRIMARY BUSHING WELLS.

PRIMARY VOLTAGES:

A 13,200 VOLT PRIMARY RATING IS AVAILABLE FOR INSTALLATION ON 25KV SYSTEMS. A 7200 VOLT PRIMARY

RATING IS AVAILABLE FOR INSTALLATION ON A 12kV SYSTEM. 19,920 VOLT RATING IS AVAILABLE FOR MOREHEAD

CITY OPERATIONS AREA ONLY.

SECONDARY VOLTAGES:

120/240 VOLT 3 WIRE SERVICE IS AVAILABLE. A LIMITED SUPPLY OF 240/480 VOLT TRANSFORMERS ARE

AVAILABLE.

KVA RATINGS:

STANDARD KVA RATINGS ARE 25, 50, 75, 100, AND 167 KVA. A 250 KVA IS AVAILABLE FOR OVERLOADED

167 KVA UNITS, BUT SHOULD NOT BE USED FOR INITIAL DESIGN. 50 KVA AND 100 KVA ARE AVAILABLE AT

240/480 VOLTS.

FUSE PROTECTION:

ALL NEW TRANSFORMERS ARE PROTECTED WITH BAYONET FUSES AND INTERNAL WEAK LINKS ON THE

PRIMARY SIDE. UNTIL 1996, TRANSFORMERS FROM 25 TO 100 KVA WERE PROTECTED WITH CSP SECONDARY

BREAKERS AND INTERNAL WEAK LINKS. THESE CSP TRANSFORMERS WILL CONTINUE TO BE RECYCLED AND

REUSED UNDER THE SAME CATALOG NUMBERS AS NEW TRANSFORMERS WITH BAYONET FUSING.

TRANSFORMER SIZE, KVA

25

37.5

50

75

100

167

250

SINGLE-PHASE FUSE TABLE

TRANSFORMER VOLTAGE RATING

7200 VOLTS

FUSE LINK SIZE

AMPS

6B

12B

15B

25B

25B

40B

65B

CN

21142906

21124201

21124607

21124300

21124300

21143607

21143706

13,200 VOLTS

FUSE LINK SIZE

AMPS

3B

6B

8B

12B

15B

25B

40B

CN

21123906

21142906

21124508

21124201

21124607

21124300

21143607

19,920 VOLTS

FUSE LINK SIZE

AMPS

3B

-

5B

-

8B

-

-

CN

21123906

-

21124102

-

21124508

-

-

3

2

1

0 6/16/10

REVISED

SIMMONS

BY

GUINN

CK'D

ELKINS

APPR.

STANDARD SINGLE-PHASE

PAD-MOUNTED TRANSFORMERS

AND SINGLE-PHASE FUSE TABLE

R

DWG.

27.02-06

THREE-PHASE LOOP-FEED PAD-MOUNTED TRANSFORMERS

GENERAL DESIGN: LOOP FEED TRANSFORMERS HAVE A DEAD-FRONT PRIMARY COMPARTMENT WITH SIX BUSHING WELLS. IN ADDITION,

NEW TRANSFORMERS WITH DELTA-WYE RECONNECTABLE PRIMARY AND THOSE RATED 1000KVA AND ABOVE HAVE A 200 AMP

OPEN-CLOSE OIL SWITCH LOCATED IN THE HIGH VOLTAGE COMPARTMENT.

FUSING: TRANSFORMERS ARE PROTECTED ON THE PRIMARY SIDE WITH BAY-O-NET FUSING AND INTERNAL WEAK LINKS. BAY-O-NET

FUSES IN LOOP FEED DELTA-WYE TRANSFORMERS WILL BE SIZED FOR THE DELTA CONNECTION (12KV) WHEN SHIPPED FROM THE

GENERAL WAREHOUSE. FUTURE CONNECTIONS TO GROUNDED WYE (23KV) WILL REQUIRE FUSE REPLACEMENT.

PRIMARY VOLTAGES: STANDARD PRIMARY VOLTAGES ARE 12,470Y/7200 VOLTS (IN SIZES UP TO 2500KVA) 22,860Y/13,200 VOLTS

(IN SIZES UP TO 3750 KVA) AND14,400 DELTA/24,940Y/14,400 (DELTA-WYE PRIMARY IN SIZES UP TO 2500 KVA). 34,500GRDY/19,920

VOLT TRANSFORMERS ARE AVAILABLE BY SPECIAL ORDER FOR EASTERN REGION ONLY.

DELTA-WYE TRANSFORMERS: DELTA-WYE TRANSFORMERS SHOULD ONLY BE USED WHERE A CONVERSION IS PLANNED WITHIN THE

NEXT THREE YEARS OR WHERE THERE IS NO SINGLE RATED PRIMARY AVAILABLE IN THE REQUIRED SIZE. SINGLE RATED PRIMARY

TRANSFORMERS SHOULD BE USED OTHERWISE.

DELTA-WYE TRANSFORMERS CAN BE USED AT 12 OR 23 KV AND WILL BE SHIPPED FROM THE GENERAL WAREHOUSE IN THE DELTA

CONNECTION (12KV). FUTURE CONNECTION TO GROUNDED WYE (23KV) MUST BE DONE IN THE FIELD BY CHANGING CONNECTIONS

ON THE DELTA-WYE SWITCH (OR TERMINAL BOARD ACCESSIBLE BY WAY OF HANDHOLE), ACCORDING TO THE INSTRUCTIONS

SHOWN ON THE TRANSFORMER NAMEPLATE. ADDITIONALLY, BAY-O-NET FUSES SHOULD BE CHANGED TO SIZE SPECIFIED FOR 23KV.

DELTA-CONNECTED TRANSFORMERS SHOULD BE ENERGIZED (OR DE-ENERGIZED) USING THE THREE-PHASE (OPEN-CLOSE) OIL

SWITCH LOCATED INSIDE THE HIGH VOLTAGE COMPARTMENT (OR OTHER THREE-PHASE SWITCHING) TO PREVENT FERRORESONANT

OVERVOLTAGES. THIS SWITCH IS RATED FOR 200 AMP LOADBREAKS.

VOLTAGE TAP SETTINGS: TWO TAPS, ABOVE AND BELOW AT 2.5% ARE AVAILABLE ON ALL NEW 12,470GRDY/7200, 22,860GRDY/13,200

AND 34,500GRDY/19,920 TRANSFORMERS AND ON DELTA-WYE UNITS. DELTA TAP SETTINGS ARE 14,400,13,500, 13,200, 12,470 AND

12,210 VOLTS. WYE TAP SETTINGS ARE 24,940, 23,380, 22,860, 21,600 AND 21,150 VOLTS.

KVA RATINGS: STANDARD KVA RATINGS ARE 75, 150, 300, 500, 750, 1000, 1500, 2500 AND 3750 KVA. THERE ARE OLDER 112 AND

225 KVA UNITS IN SERVICE THAT ARE NO LONGER PURCHASED.

SECONDARY VOLTAGES: STANDARD 208Y/120 VOLT SECONDARY VOLTAGES ARE AVAILABLE IN SIZES UP TO 750 KVA (A 1000 KVA

UNIT IS AVAILABLE FOR OVERLOADS) FOR USE ON 12,470GRDY/7200 OR 22,860GRDY/13,200 VOLT SYSTEMS. THE 208Y/120 VOLT

SECONDARY IS AVAILABLE IN 75 AND 150KVA SIZES FOR USE ON A 34,500GRDY/19,920 VOLT SYSTEM. 480Y/277 VOLT SECONDARY

IS AVAILABLE IN SIZES UP TO A 3750KVA FOR 22,860GRDY/13,200 VOLT SYSTEMS, 2500 KVA FOR 12470GRDY/7200 VOLT SYSTEMS

AND 500KVA FOR 34,500GRDY/19,920 VOLT SYSTEMS. 4160Y/2400 VOLT SECONDARY IS AVAILABLE IN 2500KVA FOR USE ON EITHER

A 12470GRDY/7200 OR 22,860GRDY/13,200 VOLT SYSTEM.

PRIMARY

RATING (KV)

TRANSFORMER

KVA

12.47

12.47

12.47

12.47

12.47

12.47

12.47

12.47

22.86

22.86

22.86

22.86

22.86

22.86

22.86

22.86

22.86

34.5

34.5

75

150

300

500

750

1000

1500

2500

75

150

300

500

750

1000

1500

2500

3750

150

500

HV BAY-O-NET

FUSE LINK

AMPERE RATING

6

15

25

40

65

100

100

SHORTING BAR

(SEE NOTES 3,4)

5

8

15

25

40

40

65

100 (SEE NOTE 4)

125 (SEE NOTE 6)

5

15

CATALOG

NUMBER

21142906

21124607

21124300

21143607

21143706

21143508

9220176434

9220176433

21124102

21124508

21124607

21124300

21143607

21143607

21143706

9220176434

9220176436

21124102

21124607

MINIMUM DIP POLE

FUSE AMPERE RATING

20K

30K

50K

65K

100K

65KS

65KS

100KS

20K

20K

40K

50K

50KS

50KS

65KS

125E (SEE NOTE 5)

125E

25K

25K

NOTES:

1. DIP POLE FUSES MUST BE EQUAL TO OR LARGER THAN BAY-O-NET FUSE SIZES SHOWN ABOVE.

2. DIP POLE FUSING RECOMMENDATIONS BASED ON SINGLE TRANSFORMER OF INDICATED SIZE. FOR MULTIPLE UNITS ON RADIAL

FEED, CONSULT WITH REGION RELIABILITY AND PROTECTION ENGINEER FOR DIP POLE FUSING.

3. THE SHORTING BAR IS NOTHING MORE THAN A SOLID COPPER LINK WITH AN ISOLATION LINK CONNECTED IN SERIES. THE DIP POLE

OR PAD-MOUNTED SWITCHGEAR FUSES ARE PROTECTING THE TRANSFORMER. IT IS RECOMMENDED THAT MANUAL FAULT INDICATORS

BE USED ON THE TRANSFORMER PRIMARY SOURCE-SIDE CABLES WITH THESE UNITS TO ASSIST WITH IDENTIFYING ANY FUTURE

BLOWN FUSES.

4. UNITS THAT CURRENTLY USE A 140 AMPERE RATED BAY-O-NET FUSE SHOULD BE REFUSED WITH THE SAME ( CN 21144407).

5. AS AN ALTERNATIVE, A 100E DIP POLE FUSE CAN BE USED IN THIS APPLICATION UPON APPROVAL FROM THE REGIONAL

COORDINATION ENGINEER.

6. THE 125 AMP BAY-O-NET FUSE WILL NOT COORDINATE WITH THE 125E DIP POLE FUSE. THESE TRANSFORMERS SHOULD HAVE

MANUAL FAULT INDICATORS PLACED ON THE TRANSFORMER PRIMARY SOURCE-SIDE CABLES TO ASSIST WITH IDENTIFYING ANY

FUTURE TRANSFORMER FAILURES.

7. WHEN ONE FUSE BLOWS ON A DIP POLE THAT SERVES A THREE-PHASE TRANSFORMER OR BANK OF TRANSFORMERS, ALL FUSES

SHALL BE REPLACED. THIS IS NECESSARY BECAUSE THE FAULT AND SINGLE-PHASING CAN CHANGE THE CHARACTERISTICS OF THE

FUSES THAT DID NOT BLOW.

3

2

1

8/27/12

9/9/11

0 6/29/10

REVISED

SIMMONS BURLISON

SIMMONS BURLISON

SIMMONS

BY

GUINN

CK'D

ELKINS

ELKINS

ELKINS

APPR.

STANDARD THREE-PHASE

PAD-MOUNTED TRANSFORMERS

AND BAY-O-NET FUSE TABLE

DWG.

27.02-08

TRANSFORMER WALL

UNLOCKED POSITION

ISOLATION LINK

INSIDE

TRANSFORMER

BAY-O-NET FUSE HOLDER

ASSEMBLY IN LOCKED POSITION

STEP 1

PULL PRESSURE

RELIEF VALVE

(NOT SHOWN)

STEP 2

6"

14"

TANKWALL

STEP 3

FUSE CARTRIDGE *

STEPS 4 & 5

INNER FUSE CARTRIDGE HOLDER

SCREW-IN END PLUG

FUSE ELEMENT *

FUSE HOLDER ASSEMBLY

THE FUSE HOLDER ASSEMBLY

(MINUS THE FUSE) CAN BE

ORDERED AS CN 9220156356

CAM ACTION

FUSE HOLDER

HANDLE

TANK WALL

GASKET

NUT

OUTER

FUSE

TUBE

PROPERLY LATCHED IMPROPERLY LATCHED-1

STEP 6

IMPROPERLY LATCHED-2

*

THE FOLLOWING FUSES COMBINE THE ELEMENT AND CARTRIDGE AS ONE COMPONENT - DO NOT DISASSEMBLE.

140 AMP (CN 21144407 ), 100 AMP (CN 9220176434 ), 125 AMP (CN 9220176436 ) AND SHORTING BAR

(CN 9220176433 ).

3

2

1

0 6/29/10

REVISED

SIMMONS

BY

GUINN

CK'D

ELKINS

APPR.

BAY-O-NET FUSE OPERATING INSTRUCTIONS

DWG.

R

27.02-09

NOTES FOR DWG. 27.02-09

IMPORTANT SAFETY AND ENVIRONMENTAL PRECAUTIONS

FOLLOW ALL SAFETY AND SWITCHING & TAGGING PROCEDURES

BAY-O-NET FUSES MUST BE OPERATED UNDER OIL AT ALL TIMES

BAY-O-NET FUSES MUST NOT BE OPERATED WHEN ANY OF THE FOLLOWING CONDITIONS EXIST:

VISIBLE DAMAGE TO TRANSFORMER

OIL LEVEL GAUGE (IF SO EQUIPPED) INDICATING LOW OIL

TRANSFORMER LEAKING OIL

TRANSFORMER BADLY LEANING (NO OIL ON BAY-O-NET FUSE)

ARCING SOUND COMING FROM TRANSFORMER

IF THE TRANSFORMER IS OPERATING WITH A LOW OIL LEVEL OR ARCING SOUNDS, IT NEEDS

TO BE REPLACED. DE-ENERGIZE THE TRANSFORMER REMOTELY BEFORE OPERATING THE

PRESSURE RELIEF DEVICE, TRANSFORMER ON/OFF SWITCH, BAYONET FUSE, ETC.

STEP 1: USE APPROVED INSULATED STICK TO GENTLY PULL RING ON PRESSURE RELIEF VALVE TO RELEASE

INTERNAL PRESSURE BEFORE UNLATCHING OR REMOVING BAY-O-NET FUSE.

STEP 2: ATTACH APPROVED INSULATED STICK (SHOTGUN) TO FUSE HANDLE. PULL FUSE HANDLE TO THE

OPEN POSITION AND ROTATE FUSE ASSEMBLY 90 DEGREES. THIS WILL BREAK ANY ADHESION

BETWEEN THE SEAL GASKET AND THE OUTER TUBE ASSEMBLY. SOME ADDITIONAL TANK PRESSURE

MAY BE RELEASED.

STEP 3: PULL OUT THE FUSE HOLDER ABOUT SIX INCHES TO INTERRUPT THE LOAD. WAIT A FEW SECONDS

FOR THE OIL TO DRAIN INTO THE TANK. AVOID DRIPPING OIL ON CABLES: IT WILL DAMAGE THE

INSULATION. REMOVE THE FUSE ASSEMBLY.

STEP 4: WIPE OFF THE HOLDER IN PREPARATION TO REMOVING THE FUSE CARTRIDGE. WHILE THERE IS NO

OUTSIDE INDICATING DEVICE THAT SHOWS THE FUSE IS BLOWN, IT CAN BE CHECKED WITH AN

OHM METER BEFORE REMOVING THE FUSE FROM THE FUSE CARTRIDGE. UNSCREW FUSE CARTRIDGE,

REMOVE END PLUG AND INSPECT THE FUSE. TO REMOVE THE FUSELINK, STRAIGHTEN SCALLOPED

END FERRULE AND PUSH THE FUSE LINK OUT OF THE FUSE HOLDER.

CAUTION: COOPER HI-AMP OVERLOAD BAYONET FUSES CANNOT BE REMOVED FROM THE FUSE

CARTRIDGE [CN 9220176434 (100 AMP), CN 9220176436 (125 AMP) AND CN 9220176433 (SHORTING

BAR]. THE COOPER 140 AMP DUAL SENSING BAYONET FUSE ( CN 21144407 ) IS ALSO INTEGRAL TO

THE FUSE CARTRIDGE. THE ENTIRE FUSE CARTRIDGE MUST BE REPLACED ON THESE ITEMS.

STEP 5: TO INSTALL NEW FUSE, BE SURE THE FORMED END-FERRULE OF THE FUSE IS SECURED IN PLACE

BETWEEN THE FUSE CARTRIDGE AND THE HOLDER. TIGHTEN BEFORE THE END PLUG IS INSERTED.

TIGHTEN THE END PLUG TO EXPAND THE SCALLOPED END-FERRULE. USE AN ADJUSTABLE WRENCH

TO TIGHTEN ALL CONNECTIONS. THE FUSE CARTRIDGE HOLDER ASSEMBLY IS READY FOR

REINSTALLING IN THE TRANSFORMER.

STEP 6: USING AN APPROVED INSULATED STICK (SHOTGUN) REINSTALL FUSE ASSEMBLY INTO OUTER FUSE

TUBE TO A FULLY SEATED POSITION. PROPERLY LATCH THE FUSE ASSEMBLY IN THE LOCKED

POSITION UNDER THE LIP OF THE OUTER FUSE TUBE AS SHOWN. IF THE ASSEMBLY IS NOT

PROPERLY LATCHED, ARCING WILL OCCUR BETWEEN THE FUSE CONTACTS AND WILL EVENTUALLY

CAUSE THE TRANSFORMER TO FAIL.

NOTES:

1. ALL THREE FUSE ELEMENTS IN A THREE-PHASE TRANSFORMER SHOULD BE REPLACED WHEN

ENCOUNTERING ONE BLOWN FUSE ELEMENT.

2. TO RAISE OR LOWER THE PRIMARY TAP CHANGER (IF SO EQUIPPED), THE TRANSFORMER MUST BE

DE-ENERGIZED. PRIOR TO CHANGING TAPS, ONE OF THE FOLLOWING MUST BE DONE:

PLACE TRANSFORMER "ON/OFF" SWITCH IN THE "OFF" POSITION OR

COMPLETELY SWITCH OUT THE TRANSFORMER (PARK CABLES ON EITHER SIDE) OR

UTILIZE FEED THRU BUSHINGS

3. THE BAY-O-NET FUSE CAN BE A LOADBREAK DEVICE ON ALL PAD-MOUNT TRANSFORMERS. SEE NOTE 4

FOR SPECIAL OPERATING PROCEDURE ON 2500 AND 3750KVA TRANSFORMERS.

4. BAY-O-NET FUSES IN 2500 KVA AND 3750 KVA TRANSFORMERS AT 23 KV SHOULD BE OPERATED AS

DESCRIBED ABOVE ONLY IF ONE OF THE FOLLOWING ACTIONS HAS BEEN TAKEN:

OPEN INTERNAL OIL SWITCH, IF SO EQUIPPED

HAVE CUSTOMER OPEN MAIN DISCONNECT TO DROP LOAD

SWITCH OUT TRANSFORMER

3

2

1 3/17/14

0 6/29/10

REVISED

SIMMONS

SIMMONS

BY

GUINN

GUINN

CK'D

ADCOCK

ELKINS

APPR.

BAY-O-NET FUSE OPERATING INSTRUCTIONS

DWG.

27.02-10

OPERATING PROCEDURE

PURPOSE:

TO GUIDE IN THE INSTALLATION OF ELBOW SURGE ARRESTERS ON THE UNDERGROUND DISTRIBUTION SYSTEM.

SAFETY:

SAFETY SHALL BE OF FIRST IMPORTANCE IN THE PERFORMANCE OF ALL DUTIES. OBSERVE ALL SAFETY RULES

AND PRACTICES AT ALL TIMES.

GENERAL:

1. MAKE SURE THE MAXIMUM CONTINUOUS OPERATING VOLTAGE (MCOV) OF THE SYSTEM DOES NOT EXCEED

THE MCOV OF THE ARRESTER.

SYSTEM VOLTAGE (KV)

24.94GY/ 14.4

13.2GY / 7.62

12.47GY / 7.2

MAXIMUM CONTINUOUS OPERATING VOLTAGE

REGULATED

DUTY CYCLE (KV)

18

MCOV (KV)

15.3

10

10

8.4

8.4

UNREGULATED

DUTY CYCLE (KV)

21

MCOV (KV)

17

10

10

8.4

8.4

THE MCOV RATING OF THE ARRESTER IS PRINTED ON THE DISC LOCATED BENEATH THE OPERATING EYE.

2. CHECK CONTENTS OF PACKAGE FOR DAMAGE, RATINGS, AND COMPATIBILITY WITH MATING PARTS.

3. PREPLAN SPACE FOR THE ARRESTER AND GROUND LEADS SO THE OPERATION OF THIS OR OTHER LOADBREAK

DEVICES IS NOT RESTRICTED.

4. CAUTION:

A. DO NOT HI-POT WITH ELBOW SURGE ARRESTERS INSTALLED. ARRESTERS ARE NOT RATED FOR HI-POT

OVERVOLTAGES. IF SUBJECTED TO HI-POT OVERVOLTAGES, THEY WILL FAIL.

INSTALLATION PROCEDURE:

A. GROUNDING

CONNECT FREE END OF THE BRAIDED

GROUND LEAD TO THE SYSTEM GROUND.

ATTACH A #14 OR EQUIVALENT WIRE TO

THE ELBOW GROUNDING EYE AND

CONNECT TO THE SYSTEM GROUND IN

THE SAME SPLIT BOLT CONNECTOR AS

THE ELBOW ARRESTER BRAIDED GROUND

LEAD ATTACHES TO THE SYSTEM GROUND.

B. LUBRICATION

APPLY A LIGHT, UNIFORM COAT OF

SUPPLIED GREASE, WORKING

THOROUGHLY INTO SURFACE.

CAUTION:

EXCESS GREASE MAY PREVENT THE

ELBOW ARRESTER FROM BEING FULLY

SEATED IN THE "LOCKED ON" POSITION.

KEEP THE INTERNAL MATING SURFACE

FREE FROM DIRT AND GRIME.

LUBRICATE

PROVIDE SLACK

FOR OPERATION

BRAIDED GROUND

LEAD

#14 WIRE

TO GROUND

LOOP

3

2

1

0 10/12/12

REVISED

SIMMONS BURLISON ADCOCK

BY CK'D APPR.

OPERATING PROCEDURE FOR INSTALLING

ELBOW SURGE ARRESTERS

R

DWG.

27.03-02A

OPERATING PROCEDURE

C. CONNECTION

1. OPERATE PER THE FOLLOWING INSTRUCTIONS: DO NOT OPERATE BY HAND

2. REMOVE EXISTING LOADBREAK ELBOW OR DEADEND RECEPTACLE FROM BUSHING WITH A HOTSTICK.

3. INSTALL A FEED THRU CONNECTOR ON EQUIPMENT PARKING STAND.

4. INSTALL FIRST ELBOW ARRESTER ON THE FEED THRU CONNECTOR.

5. INSTALL LOADBREAK ELBOW ON FEED THRU CONNECTOR ADJACENT TO THE ELBOW ARRESTER.

6. INSTALL SECOND ELBOW ARRESTER ON TRANSFORMER.

7. WHEN INSTALLING ELBOW ARRESTERS ON ENERGIZED CIRCUITS, THE FOLLOWING PROCEDURE SHOULD

BE FOLLOWED:

A. FIRMLY TIGHTEN A HOTSTICK TO THE ELBOW ARRESTER OPERATING EYE.

B. POSITION ELBOW ARRESTER RECEPTACLE SO THAT ITS GROUNDED END POINTS ARE IN A DOWNWARD

DIRECTION. PLACE THE ELBOW ARRESTER RECEPTACLE AREA OVER THE BUSHING, INSERTING THE

PROBE TIP JUST INTO THE BUSHING.

C. TURN FACE AWAY AND FIRMLY THRUST THE ELBOW ARRESTER HOME WITH A FAST, STRAIGHT MOTION,

WHICH WILL ENGAGE THE INTERNAL LOCK OF THE ELBOW ARRESTER ONTO THE BUSHING INTERFACE.

D. INSPECT GROUND LEADS FOR PROPER CONNECTION. IF EITHER GROUND LEAD DISCONNECTS DURING

OPERATION, DO NOT ATTEMPT TO REATTACH WITHOUT FIRST PULLING ARRESTER OFF THE BUSHING

WITH HOTSTICK.

HOTSTICK

3

2

1

0 6/29/10

REVISED

SIMMONS

BY

GUINN

CK'D

ELKINS

APPR.

OPERATING PROCEDURE FOR INSTALLING

ELBOW SURGE ARRESTERS

R

DWG.

27.03-02B

OPERATING PROCEDURE

UNDERGROUND CIRCUITS WHERE OVER VOLTAGES MAY OCCUR FROM FERRORESONANCE

DUKE ENERGY PROGRESS HAS THREE TYPES OF THREE-PHASE DISTRIBUTION TRANSFORMER CONNECTIONS

SERVED WITH UNDERGROUND PRIMARY CABLE THAT ARE SUSCEPTIBLE TO FERRORESONANCE OVERVOLTAGES

IF CERTAIN OPERATIONAL PROCEDURES ARE NOT FOLLOWED.

A. FLOATING WYE-DELTA CONNECTIONS

THIS TYPE CONNECTION IS NORMALLY FOUND IN VAULTS WITH 120/240, FOUR-WIRE SERVICE TO THE

CUSTOMER. BY DESIGN, THESE VAULTS ARE REQUIRED TO HAVE THREE-PHASE SWITCHES OR PROVISIONS

FOR GROUNDING THE FLOATING WYE BEFORE SWITCHING OPERATIONS ARE PERFORMED.

1. VAULTS EQUIPPED WITH GROUNDING PROVISIONS:

BEFORE PERFORMING ANY SWITCHING OPERATIONS, GROUND THE FLOATING NEUTRAL WITH THE

GROUNDING ELBOWS PROVIDED, THEN PROCEED WITH NORMAL SWITCHING OPERATIONS.

2. VAULTS EQUIPPED WITH THREE-PHASE SWITCHES:

DE-ENERGIZING THE TRANSFORMER: DE-ENERGIZE THE TRANSFORMER BANK WITH THE

THREE-PHASE SWITCH, AND THEN DE-ENERGIZE THE CABLE.

ENERGIZING THE TRANSFORMER: ENERGIZE THE CABLE, AND THEN ENERGIZE THE

TRANSFORMER BANK WITH THE THREE-PHASE SWITCH.

B. DELTA-GROUNDED WYE CONNECTIONS

THIS CONNECTION IS NORMALLY FOUND IN PAD-MOUNTED TRANSFORMERS WITH DELTA-WYE SWITCHES

BEING SERVED WITH 12KV PRIMARY VOLTAGE. THESE TRANSFORMERS CONTAIN A THREE-PHASE LOADBREAK

SWITCH IN THE PRIMARY COMPARTMENT TO SWITCH THE WINDING ON AND OFF.

DE-ENERGIZING THE TRANSFORMER: DE-ENERGIZE THE TRANSFORMER FIRST WITH THE

THREE-PHASE SWITCH PROVIDED IN THE TRANSFORMER, AND THEN DE-ENERGIZE THE CABLE.

ENERGIZING THE TRANSFORMER: ENERGIZE THE CABLE FIRST, THEN ENERGIZE THE

TRANSFORMER WITH THE THREE-PHASE SWITCH IN THE TRANSFORMER.

C. GROUNDED WYE-GROUNDED WYE PAD-MOUNTED TRANSFORMERS (WITH NO LOAD CONNECTED)

DE-ENERGIZING THE TRANSFORMER: REMOVE THE ELBOWS FROM THE INSERT BUSHING AND

PLACE THE ENERGIZED CABLE ON INSULATING STANDOFF BUSHINGS. THEN DE-ENERGIZE THE

CABLE. IF TRANSFORMER CONTAINS A THREE-PHASE LOADBREAK SWITCH IN THE PRIMARY

COMPARTMENT, THE TRANSFORMER CAN BE DE-ENERGIZED WITH THIS SWITCH IN LIEU OF

REMOVING THE ELBOWS.

ENERGIZING THE TRANSFORMER: WITH THE ELBOWS ON INSULATING STANDOFF BUSHINGS

IN THE TRANSFORMER, ENERGIZE THE CABLE. THEN ENERGIZE THE TRANSFORMER BY INSERTING

THE ELBOWS ONTO THE BUSHING INSERTS. IF THE TRANSFORMER CONTAINS A THREE-PHASE

LOADBREAK SWITCH IN THE PRIMARY COMPARTMENT, THE TRANSFORMER CAN BE ENERGIZED

WITH THIS SWITCH IF ELBOWS ARE CONNECTED TO THE BUSHING INSERTS.

NOTE: THE IMPORTANT THING TO REMEMBER THAT APPLIES TO ALL THREE TYPES OF THESE TRANSFORMER

CONNECTION/SITUATIONS IS TO NEVER HAVE A PARTIALLY ENERGIZED TRANSFORMER BANK,

BACK-FEEDING UNDERGROUND PRIMARY CABLE.

3

2

1

10/17/13

0 10/12/12

REVISED

SIMMONS GUINN ADCOCK

SIMMONS BURLISON ADCOCK

BY CK'D APPR.

OPERATING PROCEDURE FOR

MITIGATION OF FERRORESONANCE

IN UNDERGROUND CIRCUITS

DWG.

27.03-02C

PRIMARY SIDE

2

3

1

SECONDARY SIDE

MACRO UNIT

2

2

3

3

CU

ITEM

NO.

1

1

2

COMPATIBLE

UNIT

TUA25RECDELB2RC

TUA35RECDELB2C

ARREL10C

ARREL18C

ARREL27C

TUA25PLGFDTLBRC

TUA35PLGFDTLBC

BILL OF MATERIALS

QTY

PER

MACRO

1

1

CATALOG

NUMBER

1

1

1

1

1

11186806

11186814

11126406

11232303

11126406

11232204

051584

11126406

11186400

11185600

QTY

PER

CU

1

1

1

1

1

1

1

1

1

1

DESCRIPTION

RECEPTACLE, DE, LBK, 25KV

RECEPTACLE, DE, LBK, 35KV

CONNECTOR, SPLIT BOLT

ARRESTER, METOX, 10KV

CONNECTOR, SPLIT BOLT

ARRESTER, METOX, 18KV

ARRESTER, ELBOW, METOX, 27KV

CONNECTOR, SPLIT BOLT

CONNECTOR, FEED-THRU, 200A LB

CONNECTOR, FEED-THRU, 35KV

NOTES:

1. TRAIN PRIMARY CABLE TO FINAL ASSEMBLED POSITION ALLOWING SLACK FOR LOADBREAK OPERATION.

2. TRANSFORMERS WITH HIGH VOLTAGE UNDER OIL LIGHTNING ARRESTERS (HVLA) WILL HAVE A HVLA DECAL.

3. INSTALL ARRESTERS AT NORMAL OPENING POINTS.

4. VISE TYPE CONNECTOR CAN BE USED TO CONNECT THE ELBOW ARRESTER GROUND LEAD TO THE #4 BC

GROUND LOOP. DO NOT SHORTEN THE ELBOW ARRESTER GROUND LEAD.

5. SEE DWG. 27.01-03 FOR GROUNDING DETAILS.

3

2

1

0 6/29/10

REVISED

SIMMONS

BY

GUINN

CK'D

ELKINS

APPR.

ARRESTER - FEED-THRU

SINGLE-PHASE PAD-MOUNT

WITH INTERNAL ARRESTER

R

DWG.

27.03-12

PRIMARY SIDE

2

1

1

SECONDARY SIDE

MACRO UNIT

-

1

1

2

2

CU

ITEM

NO.

1

COMPATIBLE

UNIT

ARREL10C

ARREL18C

ARREL27C

TUA25PLGFDTLBRC

TUA35PLGFDTLBC

BILL OF MATERIALS

QTY

PER

MACRO

CATALOG

NUMBER

2

2

2

1

1

11126406

11232303

11126406

11232204

051584

11126406

11186400

11185600

QTY

PER

CU

1

1

1

1

1

1

1

1

DESCRIPTION

CONNECTOR, SPLIT BOLT

ARRESTER, METOX, 10KV

CONNECTOR, SPLIT BOLT

ARRESTER, METOX, 18KV

ARRESTER, ELBOW, METOX, 27KV

CONNECTOR, SPLIT BOLT

CONNECTOR, FEED-THRU, 200A LB

CONNECTOR, FEED-THRU, 35KV

NOTES:

1. TRAIN PRIMARY CABLE TO FINAL ASSEMBLED POSITION ALLOWING SLACK FOR LOADBREAK OPERATION.

2. TRANSFORMERS WITH HIGH VOLTAGE UNDER OIL LIGHTNING ARRESTERS (HVLA) WILL HAVE A HVLA DECAL.

3. INSTALL ARRESTERS AT NORMAL OPENING POINTS AND IN LAST TRANSFORMER OF RADIAL FEED.

4. SPLIT BOLT CONNECTOR CAN BE USED TO CONNECT THE ELBOW ARRESTER GROUND LEADS TO THE #4 BC

GROUND LOOP. DO NOT SHORTEN THE ELBOW ARRESTER GROUND LEAD.

5. SEE DWG. 27.01-03 FOR GROUNDING DETAILS.

3

2

1

0 6/29/10

REVISED

SIMMONS

BY

GUINN

CK'D

ELKINS

APPR.

ARRESTER - ELBOW AND FEED-THRU,

SINGLE-PHASE PAD-MOUNT

WITHOUT INTERNAL ARRESTER

R

DWG.

27.03-13

H

1B

1

2

H

1A

3

H

2B

1

2

3

H

2A

H

3B 1

H

3A

FACE OF

TRANSFORMER

3

2

MACRO UNIT

2

2

3

3

CU

ITEM

NO.

1

1

2

COMPATIBLE

UNIT

TUA25RECDELB2RC

TUA35RECDELB2C

ARREL10C

ARREL18C

ARREL27C

TUA25PLGFDTLBRC

TUA35PLGFDTLBC

QTY

REQ'D

-

-

-

-

-

-

BILL OF MATERIALS

-

CATALOG

NUMBER

11186806

11186814

11126406

11232303

11126406

11232204

11126406

051584

11186400

11185600

QTY

PER

CU

1

1

1

1

1

1

1

1

1

1

DESCRIPTION

RECEPTACLE, DE, LBK, 25KV

RECEPTACLE, DE, LBK, 35KV

CONNECTOR, SPLIT BOLT

ARRESTER, ELBOW, 10KV

CONNECTOR, SPLIT BOLT

ARRESTER, ELBOW, 18KV

CONNECTOR, SPLIT BOLT

ARRESTER, ELBOW, 27KV

CONNECTOR, FEED-THRU, 200A LB

CONNECTOR, FEED-THRU, 35KV

NOTES:

1. TRAIN PRIMARY CABLE TO FINAL ASSEMBLED POSITION ALLOWING FOR LOADBREAK OPERATION.

2. TRANSFORMERS WITH HIGH VOLTAGE UNDER OIL LIGHTNING ARRESTERS (HVLA) WILL HAVE A HVLA DECAL.

3. DO NOT INSTALL PARKING STAND ARRESTERS ON THREE-PHASE PAD-MOUNTED TRANSFORMERS. THEIR PHYSICAL LOCATION AND

LENGTH INTERFERES WITH THE OPERATION OF THE LOADBREAK ELBOW BELOW.

4. INSTALL ARRESTERS AT NORMAL OPENING POINTS.

5. DELTA CONNECTED TRANSFORMERS ON 12.47KV SYSTEM SHALL HAVE 18KV ARRESTERS.

6. CONNECT DRAIN WIRES AND ELBOW ARRESTER GROUNDS TO GROUND LOOP.

3

2

1

0 6/29/10

REVISED

SIMMONS

BY

GUINN

CK'D

ELKINS

APPR.

ARRESTER-ELBOW

THREE-PHASE DEADFRONT LOOP

WITH INT-HVLA

R

DWG.

27.03-14

H

1B

1

H

1A

2

H

2B

1

2

H

2A

1

H

3B

H3A

FACE OF

TRANSFORMER

2

1

MACRO UNIT

-

CU

ITEM

NO.

1

1

1

2

2

COMPATIBLE

UNIT

ARREL10C

ARREL18C

ARREL27C

TUA25PLGFDTLBRC

TUA35PLGFDTLBC

6

6

6

3

3

BILL OF MATERIALS

QTY

REQ'D

CATALOG

NUMBER

11126406

11232303

11126406

11232204

11126406

051584

11186400

11185600

QTY

PER

CU

1

1

1

1

1

1

1

1

DESCRIPTION

CONNECTOR, SPLIT BOLT, #4 CU

ARRESTER, ELBOW, 10KV

CONNECTOR, SPLIT BOLT, #4 CU

ARRESTER, ELBOW, 18KV

CONNECTOR, SPLIT BOLT

ARRESTER, ELBOW, 27KV

CONNECTOR, FEED-THRU, 200A LB

CONNECTOR, FEED-THRU, 35KV

NOTES:

1. TRAIN PRIMARY CABLE TO FINAL ASSEMBLED POSITION ALLOWING FOR LOADBREAK OPERATION.

2. TRANSFORMERS WITH HIGH VOLTAGE UNDER OIL LIGHTNING ARRESTERS (HVLA) WILL HAVE A HVLA DECAL.

3. DO NOT INSTALL PARKING STAND ARRESTERS ON THREE-PHASE PAD-MOUNTED TRANSFORMERS. THEIR

PHYSICAL LOCATION AND LENGTH INTERFERES WITH THE OPERATION OF THE LOADBREAK ELBOW BELOW.

4. INSTALL ARRESTERS AT NORMAL OPENING POINTS AND IN THE LAST TRANSFORMER OF RADIAL FEED.

5. DELTA CONNECTED TRANSFORMERS ON 12.47KV SYSTEM SHALL HAVE 18KV ARRESTERS.

6. CONNECT DRAIN WIRES AND ELBOW ARRESTER GROUNDS TO GROUND LOOP.

3

2

1

0 6/29/10

REVISED

SIMMONS

BY

GUINN

CK'D

ELKINS

APPR.

ARRESTER-ELBOW

THREE-PHASE DEADFRONT LOOP

NON INT-HVLA

R

DWG.

27.03-15

EDGE OF

CONCRETE PAD

OUTSIDE

EDGE OF

PAD-MOUNTED

TRANSFORMER

44"

PAD-MOUNTED

TRANSFORMER

CL

CU PAD1PH44X57CC

CN 9220204450

29"

9" 14-1/2"

SECONDARY CABLE

AND CONDUIT AREA

57"

6"

EDGE OF CONCRETE

PAD OPENING

15"

10" 4"

9"

3"

3"

NO CABLE OR CONDUIT

PERMITTED TO ENTER OR

EXIT IN THIS AREA

3"

4"

CENTERLINE LOCATION

OF PRIMARY CONDUCTORS AND

CONDUITS. CONDUCTORS AND

CONDUITS MUST ENTER AND

EXIT THIS LOCATION

GROUND ROD

LOCATION

INSIDE EDGE OF

FRONT BASE SILL

OF PAD-MOUNTED

TRANSFORMER SHALL

NOT BE SET MORE

THAN 2" FROM

PAD OPENING.

CONDUCTOR OR CONDUIT

FLUSH AGAINST FRONT OF

PAD OPENING. CONDUIT SHALL

EXTEND ABOVE CONCRETE PAD

1" (BUT SHALL NOT EXCEED 2")

PARKING STAND

PRIMARY BUSHING

H 1B

FAULT INDICATOR

X 1

X 3

X 2

PRIMARY CABLE TAG LOCATION

(1 TAG EACH PRIMARY CONDUCTOR, SEE

DWGS. 20.01-01A & 20.01-01B)

SECONDARY CABLE TAG LOCATION

(1 EACH LEG, SEE DWGS. 20.01-01A &

20.01-01B)

GROUND STRAP

TRANSFORMER

BASE SILL

CONCRETE

TRANSFORMER

PAD

H1A

PRIMARY CONDUCTORS/CONDUITS

FINAL GRADE

FINAL GRADE

1"-2"

SEE NOTE 3

SECONDARY CABLE AND/OR

CONDUIT OR CABLES

SEE NOTE 6, DWG. 26.04-02B FOR JACKET AND

CONCENTRIC NEUTRAL TERMINATION.

NOTES:

1. INSTALL A FAULT INDICATOR ON THE LOAD SIDE PRIMARY CABLE (H1B BUSHING). FAULT INDICATORS WILL BE INSTALLED IN

SPECIFIED RDO'S PER DWG. 26.07-03B.

2. ALL TRANSFORMERS SHALL BE BOLTED TO CONCRETE PAD WITH HOLD DOWN CLAMPS. USE CLAMPS SUPPLIED BY TRANSFORMER

MANUFACTURER WITH EACH UNIT OR A SUITABLE SUBSTITUTE ( CN 21334206).

3. ALL CONDUITS SHALL STUB-UP A MINIMUM DISTANCE OF ONE INCH (BUT SHALL NOT EXCEED 2") ABOVE THE TOP OF THE CONCRETE

PAD.

4. FOR FIBERGLASS PADVAULT SINGLE-PHASE PAD-MOUNTED TRANSFORMER INSTALLATIONS, SEE DWG. 24.01-03.

5. FOR SINGLE-PHASE PAD-MOUNTED TRANSFORMER GROUNDING, SEE DWG. 27.01-03.

6. BOTH LOADBREAK ELBOWS SHALL BE PROPERLY CABLE TRAINED AND FREE TO MOVE TO A STAND-OFF PLUG MOUNTED ON THE

PARKING STAND WHILE USING AN INSULATED ELBOW PULLING STICK.

7. FOR CONCRETE PAD DETAILS, SEE DWG. 24.01-05.

8. WHEN CONNECTING SECONDARY CABLES, START AT THE BACK (CLOSEST TO THE TANK) AND WORK TOWARD THE FRONT LEAVING

THE CONNECTION HOLES CLOSEST TO THE FRONT OPEN FOR FUTURE INSTALLATIONS.

9. SECONDARY CABLES THAT ARE NOT TERMINATED ON INITIAL TRANSFORMER INSTALLATION SHOULD BE LEFT ABOVE PAD

LEVEL WITH ENDS INDIVIDUALLY SEALED AND TAPED PER DWG. 23.02-01. ALL SECONDARY NEUTRAL CONDUCTORS MUST

BE TERMINATED AND CONNECTED IN THE TRANSFORMER TO FACILITATE CABLE LOCATING.

3

2

1

0 6/29/10

REVISED

SIMMONS

BY

GUINN

CK'D

ELKINS

APPR.

CABLE AND CONDUIT ENTRANCE SINGLE-PHASE

PAD-MOUNTED TRANSFORMER INSTALLATION

100 KVA AND LARGER (CONCRETE PADS ONLY)

R

DWG.

27.05-01

42"

EDGE OF

CONCRETE PAD

OUTSIDE

EDGE OF

PAD-MOUNTED

TRANSFORMER

SECONDARY CABLE AND

CONDUIT AREA

PAD-MOUNTED

TRANSFORMER

CL

28"

9" 14"

CU PAD1P42X45CC

CN 9220166987

45"

6"

EDGE OF CONCRETE

PAD OPENING

16"

10"

3"

3"

10"

3"

4"

PARKING STAND

PRIMARY BUSHING

4"

GROUND ROD

LOCATION

INSIDE EDGE OF

FRONT BASE SILL

OF PAD-MOUNTED

TRANSFORMER SHALL

NOT BE SET MORE

THAN 2" FROM

PAD OPENING.

NO CABLE OR CONDUIT

PERMITTED TO ENTER OR

EXIT IN THIS AREA

H1B

CONDUCTOR OR CONDUIT

FLUSH AGAINST FRONT OF

PAD OPENING. CONDUIT SHALL

EXTEND ABOVE CONCRETE PAD

1" (BUT SHALL NOT EXCEED 2")

FAULT INDICATOR

CENTERLINE LOCATION

OF PRIMARY CONDUCTORS AND

CONDUITS. CONDUCTORS AND

CONDUITS MUST ENTER AND

EXIT THIS LOCATION

PRIMARY CABLE TAG LOCATION

(1 TAG EACH PRIMARY CONDUCTOR, SEE

DWGS. 20.01-01A & 20.01-01B)

X

1

X 3

SECONDARY CABLE TAG LOCATION

(1 EACH LEG, SEE DWGS. 20.01-01A &

20.01-01B)

GROUND STRAP

X

2

TRANSFORMER

BASE SILL

CONCRETE

TRANSFORMER

PAD

H 1A

PRIMARY CONDUCTORS/CONDUITS

FINAL GRADE

FINAL GRADE

1"-2"

SEE NOTE 3

SECONDARY CABLE AND/OR

CONDUIT OR CABLES

SEE NOTE 6, DWG. 26.04-02B FOR JACKET AND

CONCENTRIC NEUTRAL TERMINATION.

NOTES:

1. INSTALL A FAULT INDICATOR ON THE LOAD SIDE PRIMARY CABLE (H1B BUSHING). FAULT INDICATORS WILL BE INSTALLED IN

SPECIFIED RDO'S PER DWG. 26.07-03B.

2. ALL TRANSFORMERS SHALL BE BOLTED TO CONCRETE PAD WITH HOLD DOWN CLAMPS. USE CLAMPS SUPPLIED BY TRANSFORMER

MANUFACTURER WITH EACH UNIT OR A SUITABLE SUBSTITUTE ( CN 21334206).

3. ALL CONDUITS SHALL STUB-UP A MINIMUM DISTANCE OF ONE INCH (BUT SHALL NOT EXCEED 2") ABOVE THE TOP OF THE CONCRETE

PAD.

4. FOR FIBERGLASS PADVAULT SINGLE-PHASE PAD-MOUNTED TRANSFORMER INSTALLATIONS, SEE DWG. 24.01-03.

5. FOR SINGLE-PHASE PAD-MOUNTED TRANSFORMER GROUNDING, SEE DWG. 27.01-03.

6. BOTH LOADBREAK ELBOWS SHALL BE PROPERLY CABLE TRAINED AND FREE TO MOVE TO A STAND-OFF PLUG MOUNTED ON THE

PARKING STAND WHILE USING AN INSULATED ELBOW PULLING STICK.

7. FOR CONCRETE PAD DETAILS, SEE DWG. 24.01-04.

8. WHEN CONNECTING SECONDARY CABLES, START AT THE BACK (CLOSEST TO THE TANK) AND WORK TOWARD THE FRONT LEAVING

THE CONNECTION HOLES CLOSEST TO THE FRONT OPEN FOR FUTURE INSTALLATIONS.

9. SECONDARY CABLES THAT ARE NOT TERMINATED ON INITIAL TRANSFORMER INSTALLATION SHOULD BE LEFT ABOVE PAD

LEVEL WITH ENDS INDIVIDUALLY SEALED AND TAPED PER DWG. 23.02-01. ALL SECONDARY NEUTRAL CONDUCTORS MUST

BE TERMINATED AND CONNECTED IN THE TRANSFORMER TO FACILITATE CABLE LOCATING.

3

2

1

0 6/29/10

REVISED

SIMMONS

BY

GUINN

CK'D

ELKINS

APPR.

CABLE AND CONDUIT ENTRANCE SINGLE-PHASE

PAD-MOUNTED TRANSFORMER INSTALLATION

25-75 KVA (CONCRETE PADS ONLY)

DWG.

R

27.05-03

HOLD-DOWN

CLEAT

TRANSFORMER

SILL

GROUND

ROD LOCATION

FRONT OF

TRANSFORMER

TOP VIEW

SECONDARY

CABLE LOCATION

PRIMARY

CABLE LOCATION

GROUND LEVEL

2" FROM BOTTOM

OF PAD-VAULT

6"

FRONT VIEW

NOTES:

1. SINGLE PHASE FIBERGLASS PAD-VAULTS ARE TO BE USED IN WESTERN REGION IN LOCATIONS WHICH

HAVE SEVERE SLOPE, AND IN EASTERN REGION IN LOCATIONS WHICH HAVE SHIFTING SOILS CAUSED

BY WIND AND/OR WATER. OTHER REGIONS SHOULD INSTALL PAD-VAULTS WHEN EITHER ABOVE CONDITION

IS ENCOUNTERED.

2. GROUND ROD - TO BE INSTALLED IN LOCATION SHOWN. TO BE DRIVEN AT LEAST TO TOP OF PAD. SEE DWG. 27.01-03 FOR DETAILS.

3. SECONDARIES - ENTER PAD IN LOCATION SHOWN. SECONDARIES ADDED SUBSEQUENT TO PAD/TRANSFORMER INSTALLATION MAY

ENTER PAD AT ANY LOCATION, BUT SHOULD NOT INTERFERE WITH PRIMARY CABLES OR OPERATION OF LOADBREAK ELBOWS. CABLES

THAT ARE NOT TERMINATED ON INITIAL TRANSFORMER INSTALLATION SHOULD BE LEFT ABOVE PAD LEVEL WITH ENDS INDIVIDUALLY

SEALED AND TAPED PER DWG. 23.02-01. ALL SECONDARY NEUTRAL CONDUCTORS MUST BE TERMINATED AND CONNECTED IN

THE TRANSFORMER TO FACILITATE CABLE LOCATING. ADEQUATE SLACK SHOULD BE LEFT IN SECONDARIES TO PROVIDE FOR

EASE IN TERMINATING AND TO PROVIDE A "SAFETY-MARGIN" SHOULD TRANSFORMER CHANGEOUT BE REQUIRED.

4. PRIMARIES - ENTER PAD IN LOCATION SHOWN. PRIMARY CABLES SHOULD BE TRAINED AND TERMINATED SUCH THAT OPERATION OF

LOADBREAK ELBOWS CAN BE PERFORMED WITHOUT INTERFERENCE FROM SECONDARY CABLES, GROUND LEADS, OR GROUNDING

LOOP. OUTER JACKET OF PRIMARY CABLE SHOULD BE CUT BACK TO WITHIN 6" OF GROUND LEVEL. PRIMARY CABLES MUST BE

TERMINATED WITH AN ARC IN THE CABLES AS SHOWN ABOVE, TO PROVIDE ADEQUATE SLACK FOR OPERATION OF LOADBREAK

ELBOWS. CABLE TAGS SHOULD BE LOCATED IMMEDIATELY BELOW THE BASE OF THE ELBOW IN AN EASILY READABLE POSITION.

5. TRANSFORMER - INSTALL TRANSFORMER SUCH THAT EDGE OF SILL IS WITHIN 1" OF PAD OPENING. THIS WILL OPTIMIZE THE OPEN

AREA OF PAD PROVIDING MORE SPACE FOR CABLES. TRANSFORMER SHOULD BE BOLTED DIRECTLY TO PAD. IF HOLD-DOWN CLEATS

MUST BE USED, INSTALL AS SHOWN. NO PART OF HOLD-DOWN CLEAT SHOULD EXTEND INTO PAD OPENING. SEE DWG. 24.01-03 FOR

PAD-VAULT INSTALLATION DETAILS.

3

2

1

0 5/29/10

REVISED

SIMMONS

BY

GUINN

CK'D

ELKINS

APPR.

CABLE TRAINING - PAD-VAULTS

SINGLE-PHASE PAD-MOUNTED TRANSFORMERS

R

DWG.

27.05-04

ORIENT THE THE TOP CONNECTOR AS

NEEDED SO CABLE TRAINING DOES NOT

INTERFERE WITH THE OPERATION OF

THE CSP SWITCH HANDLE

ONE SCREW

FOR 5/8" STUD AND

TWO SCREWS FOR

1" STUD. TORQUE TO

20 FT.-LBS. MINIMUM

SLIDE CONNECTOR OVER

THE TRANSFORMER STUD

LIFT UP TO SEAT

AND THEN TIGHTEN THE

SET SCREW

12 O'CLOCK

1 O'CLOCK

12 O'CLOCK

1 O'CLOCK

HOLE FOR STREET

LIGHT WIRE

NEUTRAL

CONNECTOR

SEE INSTRUCTIONS

BELOW

TANK GROUND STRAP

THE NEUTRAL AND MIDDLE CONNECTOR

MUST BE ORIENTED AS SHOWN IN THE

1 O'CLOCK POSITION

#4 BC

SINGLE-PHASE

PAD-MOUNTED

TRANSFORMER

FRONT VIEW SIDE VIEW

NEUTRAL CONNECTOR AND GROUNDING STRAP INSTALLATION

1. RUN THE JAM NUT ON THE NEUTRAL STUD AS FAR AS POSSIBLE.

2. PUT THE GROUND STRAP ON THE NEUTRAL STUD.

3. INSTALL THE NEUTRAL CONNECTOR UP AGAINST THE GROUND STRAP.

4. LIFT THE CONNECTOR TO SEAT THE THREADS AND TIGHTEN THE CONNECTOR AGAINST THE GROUND STRAP

AND JAM NUT.

5. WITH A WRENCH, TIGHTEN THE JAM NUT AGAINST THE GROUND STRAP.

*

THE CONNECTORS FOR 1" STUDS HAVE TWO SET SCREWS TO SECURE IT TO THE STUD. WITH THE JAM NUT ON

THE NEUTRAL BUSHING, THE OUTER SET SCREW MAY NOT FULLY SEAT ON THE STUD. THE ONE SECURED SET

SCREW IS SUFFICIENT ON THE NEUTRAL BUSHING.

TRANSFORMER

SIZE

25 KVA - 75 KVA

100 KVA - 250 KVA

25 KVA - 250 KVA

SECONDARY BUSHING

STUD SIZE

5/8"

1"

5/8" & 1"

6 HOLE

TERMINAL

11174216

11174232

-

8 HOLE

TERMINAL

11174224

11174240

9220106464

4 HOLE SPADE

FOR MAINT. ONLY

11174000

11174208

-

NOTES:

1. ALUMINUM SET-SCREW TERMINALS WILL ACCEPT #12 AWG - 350 KCMIL ALUMINUM OR COPPER CONDUCTOR EXCEPT CN 9220106464

WHICH WILL ACCEPT #10 - 500 KCMIL AL OR CU.

2. WIRE BRUSH CONDUCTOR AND APPLY GRIT INHIBITOR CN 30524607.

3. TORQUE ALL SET SCREWS TO 30 FT.-LBS.

4. DO NOT INSTALL MORE THAN ONE CONDUCTOR PER SET SCREW POSITION.

5. SEE DWG. 27.05-03 FOR CABLE TRAINING THRU THE PAD.

6. WHEN CONNECTING SECONDARY CABLES, START AT THE BACK (CLOSEST TO THE TANK) AND WORK TOWARD THE FRONT LEAVING

THE CONNECTION HOLES CLOSEST TO THE FRONT OPEN FOR FUTURE INSTALLATIONS.

7. USE THREE SET-SCREW SECONDARY TERMINALS FROM THE SAME MANUFACTURER.

3

2

1

0 6/29/10

REVISED

SIMMONS

BY

GUINN

CK'D

ELKINS

APPR.

Z-BAR SECONDARY TERMINALS

FOR SINGLE-PHASE LOW PROFILE

PAD-MOUNTED TRANSFORMERS

R

DWG.

27.05-06

USE

JAM

NUT

ONLY

ON THE

NEUTRAL

BUSHING

JAM

NUT

*

IF TWO JAM

NUTS ARE

SUPPLIED

USE ONLY

ONE OF

THEM

*

BOLT HOLDDOWN CLEETS TO

PAD FIRST. THEN SET

TRANSFORMER SO SLOTTED

HOLES ARE OVER HOLDDOWN

CLEAT STUDS. BOLT TRANSFORMER

TO HOLDDOWN CLEATS.

LOCK

TOP VIEW

SWING LATCHING ARM INTO UPRIGHT

POSITION AFTER HOOD IS REMOVED

TANK

LATCHING ARM

(INSIDE COMPARTMENT)

COMPOSITE HOOD

PAD

LOCK

STAINLESS STEEL

BOTTOM EDGE

SIDE VIEW

HOLDDOWN CLEATS

NOTES: COMPOSITE HOOD INSTALLATION

1. ANGLE BOTTOM OF HOOD FORWARD AND ALIGN BOTTOM GROOVES OF HOOD WITH TANK EDGES.

2. SWING TOP OF HOOD FORWARD AGAINST TANK. THE REST OF THE GROOVE SHOULD BE AUTOMATICALLY

ALIGNED AND THE LATCHING ARM LOCK HOLE SHOULD PROTRUDE THROUGH THE HOOD.

3. TIGHTEN HEX RETAINING BOLT TO DRAW HOOD UP AGAINST TANK. TIGHTEN HEX BOLT UNTIL IT BOTTOMS

OUT.

4. INSTALL PADLOCK.

3

2

1

0 6/29/10

REVISED

SIMMONS

BY

GUINN

CK'D

ELKINS

APPR.

COMPOSITE HOOD SINGLE-PHASE

TRANSFORMER INSTALLATION

DWG.

27.05-08

SOURCE

#14 BC CONCENTRIC

NEUTRAL WIRE

#4 BC GROUND LOOP

LOAD

POSITION FEED-THROUGH

IN-LINE WITH CENTER

OF PARKING STAND

TO

PAD

X

X

X

X

X

XFMR

PAD

TO

X

X

X

X

X

XFMR

PAD

TO

X

X

X

X

X

#14 BC CONCENTRIC

NEUTRAL WIRE

NOTES:

1. ALL LOADBREAK ELBOWS SHALL BE PROPERLY CABLE TRAINED AND FREE TO MOVE TO AN INSULATING BUSHING

(CN 11186905 ) MOUNTED ON A PARKING STAND WHILE USING AN INSULATED ELBOW PULLING STICK.

2. GROUND FEED THROUGH BUSHING INSERT ( CN 11185709 ), BUSHING INSERT ( CN 11186509 ) AND ALL ELBOWS

(CN 11186707 ) WITH #14 BC CONCENTRIC NEUTRAL WIRE.

3

2

1

0 6/29/10

REVISED

SIMMONS

BY

GUINN

CK'D

ELKINS

APPR.

FEED THROUGH BUSHING INSERT IN

LOW PROFILE PAD-MOUNTED TRANSFORMERS

R

DWG.

27.05-10

13.2 AND 19.9KV CONNECTIONS - SUBTRACTIVE POLARITY

WARNING LABEL

CN 21129309

CT METERING

ENCLOSURE

SEE NOTE 8

LIGHTING TRANSFORMER

DANGER LABEL

CN 21129804 Hazardous voltage.

Will shock, burn, or cause death.

Qualified personnel only. Protective equipment required.

POWER TRANSFORMER

Hazardous voltage.

Will shock, burn, or cause death.

Qualified personnel only. Protective equipment required.

30"

H

1B

X

1

X

3

X

2

SEE NOTE 5

12"

H 1A

H1B

X 1

X

3

X

2

GROUND

STRAP

REMOVED

12"

H

1A

CUSTOMER

PROVIDED

CONDUCTORS

DUKE ENERGY

PROVIDED

CONDUCTORS

2-5' GROUND RODS

SEE DWG. 20.00-06B

2-5' GROUND RODS

SEE DWG. 20.00-06B

#4 BC

NOTES:

1. REMOVE X2 GROUND STRAP ON POWER TRANSFORMER AND TAPE BUSHING WITH VINYL TAPE. GROUND STRAP ON LIGHTING

TRANSFORMER MUST REMAIN ATTACHED BETWEEN TRANSFORMER TANK AND X2 BUSHING.

2. LABEL ALL SECONDARY CABLES.

3. AFFIX "WARNING" LABEL ( CN 21129309) INSIDE EACH TRANSFORMER DOOR. IT MUST BE VISIBLE WHEN THE DOOR IS IN THE

FULLY OPEN POSITION.

4. DO NOT USE AS AN OPEN POINT BETWEEN TWO SEPARATE PHASES IN A SINGLE-PHASE RESIDENTIAL CABLE LOOP.

5. STUB UP CABLES WITH CONNECTOR BLOCK AND COVER ( CU KP4H35N10C).

6. CONSULT DST-EDGX-00033, VOLTAGE FLICKER TO DESIGN THIS INSTALLATION.

7. LIGHTING AND POWER TRANSFORMERS SHALL HAVE THE SAME ASSIGNED DIS (LOCID) NUMBER APPLIED TO THE OUTSIDE OF THE

TRANSFORMER (SEE DWG. 27.00-04) AS WELL AS PRIMARY CONDUCTOR IDENTIFICATION (X, Y OR Z).

8. COMPANY PROVIDES ALL CONDUCTORS TO CT METERING ENCLOSURE FROM PAD-MOUNTED TRANSFORMERS.

CUSTOMER PROVIDES CONDUCTORS FROM THE CT METERING ENCLOSURE TO SERVICE AND THE MOUNTING

PROVISIONS FOR THE CT METERING ENCLOSURE.

4

8/27/14 SIMMONS

3

2

11/13/13

10/9/13

SIMMONS

GUINN

0 6/15/10

REVISED

SIMMONS

BY

GUINN

GUINN

GUINN

GUINN

CK'D

ADCOCK

ADCOCK

ADCOCK

ELKINS

APPR.

OPEN WYE-OPEN DELTA TRANSFORMER BANK,

240/120 VOLT, 4-WIRE SERVICE USING SINGLE-PHASE

13.2KV AND 19.9KV PAD-MOUNTED TRANSFORMERS

DEC DEM DEP

X

27.05-12

DEF

7.2KV CONNECTIONS - ADDITIVE POLARITY

WARNING LABEL

CN 21129309

CT METERING

ENCLOSURE

SEE NOTE 8

LIGHTING TRANSFORMER

DANGER LABEL

CN 21129804 Hazardous voltage.

Will shock, burn, or cause death.

Qualified personnel only. Protective equipment required.

POWER TRANSFORMER

Hazardous voltage.

Will shock, burn, or cause death.

Qualified personnel only. Protective equipment required.

30"

H

1B

X

3

X

1

X

2

SEE NOTE 5

12"

H1A

H1B

X 3

X

1

X

2

GROUND

STRAP

REMOVED

12"

H

1A

CUSTOMER

PROVIDED

CONDUCTORS

DUKE ENERGY

PROVIDED

CONDUCTORS

2-5' GROUND RODS

SEE DWG. 20.00-06B

2-5' GROUND RODS

SEE DWG. 20.00-06B

#4 BC

NOTES:

1. REMOVE X2 GROUND STRAP ON POWER TRANSFORMER AND TAPE BUSHING WITH VINYL TAPE. GROUND STRAP ON LIGHTING

TRANSFORMER MUST REMAIN ATTACHED BETWEEN TRANSFORMER TANK AND X2 BUSHING.

2. LABEL ALL SECONDARY CABLES.

3. AFFIX "WARNING" LABEL ( CN 21129309) INSIDE EACH TRANSFORMER DOOR. IT MUST BE VISIBLE WHEN THE DOOR IS IN THE FULLY

OPEN POSITION.

4. DO NOT USE AS AN OPEN POINT BETWEEN TWO SEPARATE PHASES IN A SINGLE-PHASE RESIDENTIAL CABLE LOOP.

5. STUB UP CABLES WITH CONNECTOR BLOCK AND COVER ( CU KP4H35N10C).

6. CONSULT DST-EDGX-00033 , VOLTAGE FLICKER TO DESIGN THIS INSTALLATION.

7. LIGHTING AND POWER TRANSFORMERS SHALL HAVE THE SAME ASSIGNED DIS (LOCID) NUMBER APPLIED TO THE OUTSIDE OF THE

TRANSFORMER (SEE DWG. 27.00-04) AS WELL AS PRIMARY CONDUCTOR IDENTIFICATION (X, Y OR Z).

8. COMPANY PROVIDES ALL CONDUCTORS TO CT METERING ENCLOSURE FROM PAD-MOUNTED TRANSFORMERS.

CUSTOMER PROVIDES CONDUCTORS FROM THE CT METERING ENCLOSURE TO SERVICE AND THE MOUNTING

PROVISIONS FOR THE CT METERING ENCLOSURE.

4

8/28/14 SIMMONS GUINN ADCOCK

3

2

11/13/13

10/9/13

SIMMONS

GUINN

GUINN

GUINN

ADCOCK

ADCOCK

0 6/15/10

REVISED

SIMMONS

BY

GUINN

CK'D

ELKINS

APPR.

OPEN WYE-OPEN DELTA TRANSFORMER BANK,

240/12OV, 4-WIRE SERVICE USING

SINGLE-PHASE 7.2KV PAD-MOUNTED TRANSFORMERS

DEC DEM DEP

X

27.05-13

DEF

7.2 X 13.2KV CONNECTIONS - SUBTRACTIVE POLARITY

WARNING LABEL

CN 21129309

CT METERING

ENCLOSURE

SEE NOTE 2

DANGER LABEL

CN 21129804 Hazardous voltage.

Will shock, burn, or cause death.

Qualified personnel only. Protective equipment required.

Hazardous voltage.

Will shock, burn, or cause death.

Qualified personnel only. Protective equipment required.

30"

12"

H

1A

H

1B

480/240 V X

1

X

3

X

2

GROUND

STRAP

REMOVED

SEE NOTE 7

12"

H 1A

H1B

480/240 V X

1

X

3

X

2

GROUND

STRAP

REMOVED

2-5' GROUND RODS

SEE DWG. 20.00-06B

#4 BC

CUSTOMER

PROVIDED

CONDUCTORS

DUKE ENERGY

PROVIDED

CONDUCTORS 2-5' GROUND RODS

SEE DWG. 20.00-06B

NOTES:

1. TRANSFORMERS ARE 50 AND 100 KVA 240/480 VOLT PADMOUNTS FOR 480 VOLT, 3-WIRE SERVICE TO 480 VOLT PUMPS.

2. COMPANY PROVIDES ALL CONDUCTORS TO CT METERING ENCLOSURE FROM PAD-MOUNTED TRANSFORMERS. CUSTOMER PROVIDES

CONDUCTORS FROM THE CT METERING ENCLOSURE TO SERVICE AND THE MOUNTING PROVISIONS FOR THE CT METERING ENCLOSURE.

3. REMOVE X2 GROUND STRAP ON BOTH TRANSFORMERS AND TAPE BUSHING WITH VINYL TAPE.

4. LABEL ALL SECONDARY CABLES.

5. AFFIX "WARNING" LABEL ( CN 21129309) INSIDE EACH TRANSFORMER DOOR. IT MUST BE VISIBLE WHEN THE DOOR IS IN THE FULLY

OPEN POSITION.

6. DO NOT USE AS AN OPEN POINT BETWEEN TWO SEPARATE PHASES IN A SINGLE-PHASE RESIDENTIAL CABLE LOOP.

7. STUB UP CABLES WITH CONNECTOR BLOCK AND COVER ( CU KPW4W40C).

8. IF CUSTOMER PROVIDES A NEUTRAL FOR CONNECTION TO THE TRANSFORMER, STOP ALL WORK AND OBTAIN CLARIFICATION FROM

THE PROJECT PLANNER ON TYPE OF SERVICE REQUIRED. NEUTRAL CONNECTION MUST NOT BE INSTALLED ON THIS INSTALLATION.

9. GROUND LOOP IS CONNECTED TO CASE GROUND AND CONCENTRIC NEUTRAL.

10. IF CUSTOMER BRINGS A GROUND BOND TO THE TRANSFORMER, THEN THE BOND SHOULD BE CONNECTED TO THE TRANSFORMER

GROUNDING LOOP.

11. BOTH TRANSFORMERS SHALL HAVE THE SAME ASSIGNED DIS (LOCID) NUMBER APPLIED TO THE OUTSIDE OF

THE TRANSFORMER (SEE DWG. 27.00-04) AS WELL AS PRIMARY CONDUCTOR IDENTIFICATION (X, Y OR Z).

5 9/4/14 SIMMONS GUINN ADCOCK

4 2/7/14 SIMMONS GUINN ADCOCK

3

11/13/13 SIMMONS GUINN ADCOCK

0 6/15/10

REVISED

SIMMONS

BY

GUINN

CK'D

ELKINS

APPR.

OPEN WYE-OPEN DELTA TRANSFORMER BANK

480 VOLT, 3-WIRE SERVICE USING SINGLE-PHASE

7.2KV X 13.2KV PAD-MOUNTED TRANSFORMERS

DEC DEM DEP

X

27.05-14A

DEF

7200/12470 X 13200/22860 TO 240/480V PAD-MOUNTED TRANSFORMER

-SUBTRACTIVE POLARITY-

H

1A

PRIMARY

LEADING PHASE

NEUTRAL

H1A

PRIMARY

LAGGING PHASE

NEUTRAL

X3 X2 X1

CASE GROUND

X3 X2

CASE

GROUND

X1

VOLTAGE CHECK:

PHASE TO PHASE READINGS (a-b, b-c, c-a) WILL BE 480 VOLTS

DO NOT CHECK PHASE TO GROUND VOLTAGE. PHASE TO GROUND VOLTAGE WILL VARY DUE TO THERE BEING NO

GROUND REFERENCE ON SECONDARY CONNECTIONS.

3

2

1

0 6/29/10

REVISED

SIMMONS

BY

GUINN

CK'D

THREE-PHASE OPEN WYE-OPEN DELTA CONNECTION

7200/12470 X 13200/22860 TO 240/480V PAD-MOUNTED

ELKINS

APPR.

TRANSFORMER 480 VOLT THREE-PHASE THREE WIRE SERVICE

R

DWG.

27.05-14B

STANDARD THREE-PHASE, PAD-MOUNTED TRANSFORMERS

THE STANDARD THREE-PHASE PAD-MOUNTED TRANSFORMER IS A DEAD FRONT, LOOP FEED TRANSFORMER.

RADIAL FEED TRANSFORMERS ARE NONSTANDARD AND WILL NO LONGER BE PURCHASED.

EMERGENCY CHANGEOUT OF RADIAL FEED UNITS

USING A LOOP FEED UNIT

(CONVERTING LIVE-FRONT TERMINATIONS TO DEAD-FRONT) AS A TEMPORARY "FIX", IT MAY BE MORE

CONVENIENT TO CUT THE PRIMARY CABLE JUST BELOW THE STRESS CONE AND SPLICE ON A SECTION

OF CABLE AND AN ELBOW IN THE PRIMARY COMPARTMENT OF THE TRANSFORMER. AN OUTAGE SHOULD

BE SCHEDULED WITH THE CUSTOMER AT A LATER DATE TO CUT THE PRIMARY CABLE BACK TO A POINT

WHERE THE SPLICE(S) MAY BE BURIED. IF CABLES ARE INSTALLED IN CONDUIT(S), THE ENTIRE CABLE

RUN SHOULD BE REPLACED IF POSSIBLE.

STATIC VOLTAGE

IN THREE-PHASE PAD-MOUNTED TRANSFORMERS IF ONE PHASE IS OPEN ON THE PRIMARY SIDE YOU

MAY STILL GET STATIC VOLTAGE READINGS ON THE SECONDARY SIDE OF THE TRANSFORMER DUE TO

MAGNETIC FLUX. ANYTIME YOU GET ABNORMALLY HIGH SECONDARY VOLTAGE READINGS ON THE

SECONDARY SIDE OF A THREE-PHASE PAD-MOUNTED TRANSFORMER, THE TRANSFORMER MAY BE SINGLE

PHASING.

SECONDARY BUSHING/TERMINALS

1. THE OVERSIZED SECONDARY TERMINALS WE USE PROVIDE A LONG LEVER ARM AND MAKE BREAKAGE

OF THE SECONDARY BUSHING EASY. IF EXCESS FORCE IS APPLIED TO THE TERMINAL WHEN CONNECTING

CABLES YOU WILL BREAK THE SECONDARY BUSHING. PLEASE EXERCISE CARE WHEN TIGHTENING UP

SECONDARY CABLES.

2. THE PRESENT SECONDARY TERMINALS WE USE ARE PINNED TO THE BUSHING STUD IN ADDITION TO

HAVING A JAM NUT. OLDER SECONDARY BUSHINGS DO NOT HAVE THIS JAM NUT. IT IS POSSIBLE TO

LOOSEN THE TERMINAL/JAM NUT WHEN CONNECTING CABLES TO THIS UNPINNED TERMINAL. ALWAYS

CHECK AND TIGHTEN THE JAM NUT AFTER YOU HAVE FINISHED CONNECTING UP THE CABLES.

3

2

1

0

8/17/12 SIMMONS BURLISON ELKINS

REVISED BY CK'D APPR.

THREE-PHASE PAD-MOUNTED TRANSFORMERS

GENERAL INFORMATION

DWG.

27.06-02A

CONNECTING PARALLEL SECONDARIES

ANY TIME PARALLEL THREE-PHASE SECONDARY CONDUCTORS ARE RUN TO THE CUSTOMER OR THE CUSTOMER

COMES TO THE SECONDARY TERMINALS OF THE TRANSFORMER, EACH PARALLEL CONDUCTOR SHOULD BE THE

SAME LENGTH. HOWEVER, EXCESSIVE CONDUCTOR LENGTH SHOULD BE CUT SO THE CONDUCTORS MAKE A

NEAT, SAFE FIT TO THE SECONDARY TERMINALS. WHEN CUTTING OFF EXCESS CONDUCTORS, DIFFERENT LENGTHS

CAN BE TRIMMED FROM THE THREE-PHASE CONDUCTORS OR THE NEUTRAL, AS LONG AS ALL CONDUCTORS ON

THE SAME PHASE ARE THE SAME LENGTH.

A POSITIVE TEST FOR CONTINUITY (RING-OUT) SHALL BE PERFORMED TO ENSURE ALL CABLES ARE

CONNECTED TO THE CORRECT PHASE.

CABLES SHOULD BE BENT AT THE BOTTOM OF THE SECONDARY COMPARTMENT AND TRAINED TO COME UP

STRAIGHT UNDER THE SECONDARY BUSHING WHERE THEY ARE TO BE CONNECTED. THERE SHOULD BE ENOUGH

SLACK IN THE CABLES TO ALLOW FOR TRENCH SETTLEMENT. CUT THE CABLES TO PROPERLY FIT AT THE

SECONDARY BUSHINGS. ATTACH THE CABLES TO THE SET SCREW BLOCKS STARTING AT THE BACK OF THE

SECONDARY BUSHING. ENSURE BOLTS ARE PLACED IN ALL BOLT HOLES COMMON BETWEEN THE SET SCREW

BLOCKS(S) AND TRANSFORMER BUSHING SPADES.

ALL CONDUCTORS

OF THE SAME PHASE

OR NEUTRAL MUST

BE THE SAME LENGTH

SINGLE PHASING

PAD-MOUNTED TRANSFORMERS SHOULD NOT BE LEFT TO SINGLE PHASE FOR LONG PERIODS OF TIME. SINGLE

PHASING IS AN OUTAGE CONDITION AND SHOULD BE TREATED AS SUCH. PAD-MOUNTED TRANSFORMERS

SUBJECTED TO EXTENDED PERIODS OF SINGLE PHASING WILL OVERHEAT DUE TO CIRCULATING MAGNETIC

CURRENTS.

FAULT INDICATORS

THREE-PHASE TRANSFORMERS - MANUAL FAULT INDICATORS (SEE DWG. 26.07-03A ) SHALL BE INSTALLED ON THE

LOAD SIDE PRIMARY CABLES WHEN THE TRANSFORMER IS WITHIN A LOOP SYSTEM OR ON A RADIAL SYSTEM

CONTAINING MORE THAN ONE TRANSFORMER. FAULT INDICATORS ARE NOT REQUIRED ON A SINGLE, RADIAL-FED,

THREE-PHASE TRANSFORMER.

SEE SECTION 26 FOR MORE DETAIL ON BOTH MANUAL AND AUTOMATIC FAULT INDICATORS.

1

0

3

2

11/15/12

8/17/12

REVISED

GUINN GUINN ADCOCK

SIMMONS BURLISON

BY

ELKINS

CK'D APPR.

THREE-PHASE PAD-MOUNTED TRANSFORMER

GENERAL INFORMATION

R

DWG.

27.06-02B

VENT INTAKE OR EXHAUST

10' MIN.

SEE TABLE 1

WINDOW

LESS THAN

10'

10' MIN.

10' MIN.

10' MIN.

7.5' MIN.

(SEE NOTE 8)

ELEVATION VIEW

SEE TABLE 1

10' MIN.

7.5' MIN.

(SEE NOTE 8)

PLAN VIEW

STRUCTURES

STEEL OR MASONRY

WOOD

TABLE 1

A

1

10'

10'

A

2

3' (SEE NOTE 4)

10'

WINDOW

MORE THAN

10'

A

1 A 2

NOTES:

1. THE TRANSFORMER SHALL BE INSTALLED SO THAT THE FRONT OF THE UNIT DOES NOT FACE THE BUILDING.

2. ADEQUATE PASSAGEWAYS TO ACCOMMODATE LINE TRUCKS OR OTHER NECESSARY LIFTING AND HAULING EQUIPMENT SHALL

BE PROVIDED TO ALLOW FOR MAINTENANCE, OPERATION, OR REPLACEMENT. NO PORTION OF THE BUILDING SHALL EXTEND

OVER THE TRANSFORMER.

3. 20' MINIMUM DIMENSION REQUIRED FOR FIRE ESCAPES. 10' MINIMUM DIMENSION REQUIRED FOR OPEN STAIRWAYS.

4. THERE SHALL BE NO ABOVE GROUND OBSTRUCTIONS WITHIN 10 FEET OF THE FRONT OF THE TRANSFORMER OR WITHIN

3' OF THE SIDES AND BACK. IF METERING TROUGH IS LOCATED BEHIND TRANSFORMER, MINIMUM CLEARANCE BETWEEN BACK OF

TRANSFORMER AND CLOSEST PART OF TROUGH IS 6 FEET.

5. IT SHALL BE THE CUSTOMER'S RESPONSIBILITY TO COMPLY WITH ANY INSURANCE REGULATIONS, BUILDING CODES, AND LOCAL

ORDINANCES AFFECTING THE INSTALLATION.

6. FOR STATE-OWNED BUILDINGS IN NC, STATE CODES REQUIRE 30 FEET CLEARANCE BETWEEN BUILDING AND TRANSFORMER.

7. 10' MINIMUM DIMENSION REQUIRED FOR GENERATORS AND GENERATOR FUEL TANKS.

8. THIS CLEARANCE CAN BE REDUCED TO 3' WHERE CONDITIONS DO NOT PERMIT 7.5'.

3

2

1

8/6/14

5/23/12

0 6/29/10

REVISED

EANES

SIMMONS BURLISON

SIMMONS

BY

EANES

GUINN

CK'D

ADOCK

ELKINS

ELKINS

APPR.

LOCATION OF OIL FILLED

PAD-MOUNTED TRANSFORMERS

DEC DEM DEP

X

27.06-05

DEF

BUILDING WALL

TRANSFORMER PAD

MAXIMUM

5'-2"

TRANSFORMER

MAXIMUM

5'-2"

1'-0"

1'-0"

MAX. 4'-10"

SEE NOTE 1

MAX. 4'-10"

1'-0"

FILL 12" DIA.

MIN. HOLE AND 4"

DIA. CONDUIT WITH

3000 PSI CONCRETE.

SLIP BUMPER SLEEVE

OVER TOP OF CONDUIT

(SEE NOTE 7)

3" MIN.

CONCRETE

ALL AROUND

4" GALV.

STEEL CONDUIT CUT TO

7'-0" LENGTH

CN 21002407

STANDARD POLE

4'-0"

3'-0"

PLAN VIEW

NOTES:

1. ON THREE-PHASE PAD-MOUNTED TRANSFORMERS,

THIS POLE SHOULD BE CENTRALLY LOCATED

2'-0" IN FRONT OF THE TRANSFORMER

BETWEEN THE DOORS TO ACCOMMODATE

THE DOOR SWING AND SHALL BE REMOVABLE.

ON SINGLE-PHASE TRANSFORMERS, THIS

POLE SHOULD BE LOCATED APPROXIMATELY

3'-6" IN FRONT OF THE TRANSFORMER (NO

LESS THAN 3').

FILL 12" DIA.

MIN. HOLE AND 4"

DIA. CONDUIT WITH

3000 PSI CONCRETE.

SLIP BUMPER SLEEVE

OVER TOP OF CONDUIT

(SEE NOTE 7)

2. TRANSFORMER PROTECTION POLES SHOULD BE

INSTALLED ON ALL SIDES OF THE TRANSFORMER

WHICH ARE SUBJECT TO VEHICULAR TRAFFIC.

3. POLES SHOULD BE PAINTED YELLOW.

4. THESE PROTECTIVE POLES SHALL BE PROVIDED

AND INSTALLED BY THE CUSTOMER.

3" MIN.

CONCRETE

ALL AROUND 5. CUSTOMER MAY PROVIDE AN ALTERNATE DESIGN

FOR A REMOVABLE BARRIER, BUT MUST BE

APPROVED BY THE FIELD ENGINEER.

6. ANY SINGLE AND THREE-PHASE

PAD-MOUNTED TRANSFORMERS THAT ARE

EXPOSED TO PAVED AREAS AND/OR

4" GALV.

STEEL CONDUIT CUT TO

7'-0" LENGTH

CN 21002407

VEHICULAR TRAFFIC SHALL HAVE PROTECTIVE

BARRIERS PROVIDED AND INSTALLED BY THE

CUSTOMER.

5" SCH 80

PVC CONDUIT CUT TO

3'-0" LENGTH

7. PLACE A 4" X 52" YELLOW BUMPER SLEEVE

(CN 9220192305) OVER THE CONCRETE

FILLED CONDUIT.

6" COMPACTED

STONE OR GRAVEL

REMOVABLE POLE

4'-0"

3'-0"

3

2

1

5/25/12

1/27/12

0 4/12/10

REVISED

BURLISON ELKINS

SIMPSON SIMPSON ELKINS

SIMPSON SIMPSON

BY CK'D

ELKINS

APPR.

PROTECTIVE POLES FOR OIL FILLED

PAD-MOUNTED TRANSFORMERS

DWG.

27.06-06

THREE-PHASE

PAD-MOUNTED

TRANSFORMER

SECONDARY

COMPARTMENT

JUNCTION

BOX AND PAD

48" MIN.

NOTES:

1. THE NORMAL POINT OF DELIVERY FOR AN INDIVIDUAL CUSTOMER SERVED BY A THREE-PHASE PAD-MOUNTED

TRANSFORMER INSTALLED SOLELY TO SERVE THE CUSTOMER WILL BE AT THE SECONDARY TERMINALS OF THE

TRANSFORMER.

2. IF THE CUSTOMER'S CONDUCTORS EXCEED THE NUMBER ALLOWED IN THE SECONDARY COMPARTMENT OF THE

TRANSFORMER, THE CUSTOMER MUST FURNISH AND INSTALL A SECONDARY JUNCTION BOX. THE COMPANY

WILL OWN AND INSTALL CONDUCTORS TO THE SECONDARY JUNCTION BOX AND MAKE CONNECTIONS TO THE

BUS BARS IN THE JUNCTION BOX.

3. THE COMPANY TO OWN, FURNISH, AND INSTALL ALL CONNECTIONS AND CONDUCTORS CONNECTING THE

CUSTOMER'S BUS BAR INSIDE THE JUNCTION BOX TO THE SECONDARY TERMINALS OF THE PAD-MOUNTED

TRANSFORMER. THE COMPANY WILL ALSO PROVIDE ALL TRENCHING REQUIRED BETWEEN THE PAD-MOUNTED

TRANSFORMER AND THE JUNCTION BOX.

4. PT'S AND CT'S SHALL BE INSTALLED INSIDE SECONDARY COMPARTMENT OF TRANSFORMER.

5. CUSTOMER TO FURNISH AND INSTALL JUNCTION BOX, PAD AND ANY OTHER ASSOCIATED EQUIPMENT.

JUNCTION BOXES ARE AVAILABLE AT ANY ELECTRICAL SUPPLY HOUSE. THE COMPANY WILL SPECIFY HOW

MANY CONDUCTORS WILL CONNECT TO IT AND THEN THE CUSTOMER CAN BUY A BOX.

3

2

1

0 11/16/10

REVISED

SIMPSON SIMPSON

BY CK'D

ELKINS

APPR.

THREE-PHASE PAD-MOUNTED

TRANSFORMER WITH CUSTOMER'S SECONDARY

CABLE TERMINATION BOX INSTALLATION

R

DWG.

27.06-08

PAD-MOUNTED

TRANSFORMER SIZE

(KVA)

NUMBER OF

HOLES IN

SECONDARY

BUSHING SPADE

480Y/277

NUMBER OF

HOLES IN

SECONDARY

BUSHING SPADE

208Y/120

75

150

300

500

750

1000

1500

2500

3750

8

8

8

20

20

20

6

6

6

8

10

20

N/A

N/A

N/A

6

6

6

RECOMMENDED NUMBER OF CUSTOMER CONDUCTORS

PER PHASE IN PAD-MOUNTED TRANSFORMERS

480Y/277

12

12

12

12

12

12

16

16

16

208Y/120

12

12

12

12

16

16

N/A

N/A

N/A

NOTES:

1. IF THE RECOMMENDED CONDUCTOR LIMITS ABOVE ARE EXCEEDED, THE CUSTOMER MUST CONSIDER

INSTALLING A JUNCTION BOX. THE JUNCTION BOX AND ALL ASSOCIATED EQUIPMENT (BOX, BUS, CONNECTORS,

RACEWAY, PAD, PAD GROUNDS AND ALL CONNECTIONS) SHOULD BE OWNED, INSTALLED AND MAINTAINED BY

THE CUSTOMER AS SHOWN ON DWG. 27.06-08 .

2. SEE DWG. 27.06-12 FOR TRANSFORMER SECONDARY SPADE BLOCK TERMINALS.

3. MAXIMUM CUSTOMER CONDUCTOR SIZE IS 750 KCMIL CU/AL.

4. PARALLELED CUSTOMER CONDUCTORS MUST BE "RUNG OUT" PRIOR TO ENERGIZING TO PREVENT CROSS

PHASING.

5. SIX-CONDUCTOR SECONDARY SPADE BLOCK TERMINALS REQUIRE THAT A MINIMUM OF SIX BOLT HOLES BE

ATTACHED TO SECONDARY BUSHING SPADE OF TRANSFORMER. EIGHT-CONDUCTOR BLOCKS REQUIRE A

MINIMUM OF EIGHT BOLT HOLES BE ATTACHED TO SECONDARY BUSHING OF TRANSFORMER.

6. ALL NEW THREE-PHASE PADMOUNT TRANSFORMERS WITH A 4160Y/2400 VOLT SECONDARY HAVE SECONDARY

LIVE-FRONT BUSHINGS WITH A 4-HOLE SPADE (0.56" DIAMETER BOLT HOLES ON 1.75" CENTERS).

4

8/27/12 SIMMONS BURLISON ELKINS

3

2

5/23/12

1/27/12

SIMMONS BURLISON

SIMPSON SIMPSON

ELKINS

ELKINS

0 4/12/10

REVISED

SIMPSON

BY

SIMPSON

CK'D

ELKINS

APPR.

RECOMMENDED NUMBER OF CUSTOMER

CONDUCTORS IN SECONDARY COMPARTMENT

OF THREE-PHASE PAD-MOUNTED TRANSFORMERS

DWG.

27.06-09

5/16" DIA.

1-3/4"

6.19"

1.81"

9.25"

1/2"

1/2" STAINLESS

STEEL BOLT

(SEE DETAIL "A")

TINNED TRANSFORMER SPADE

(BOLT TO BE PLACED IN

EACH HOLE SHARED WITH

TRANSFORMER BUSHING)

STAINLESS STEEL FLAT

WASHER UNDER THE BOLT

HEAD (TIGHTEN TO 40

FT.-LBS. OF TORQUE)

FLAT

WASHER

BELLEVILLE

WASHER

STAINLESS STEEL

BELLEVILLE WASHER

UNDER THE NUT

(SEE DETAIL "A")

Xl

STAINLESS

STEEL FLAT

WASHER

BOLT ASSEMBLY

DETAIL "A"

SECONDARY SPADE BLOCK TERMINAL

CONNECTIONS

SIX HOLE

EIGHT HOLE

COMPATIBLE UNIT

KXB6W7510C

KXB8W75C

CATALOG NUMBER

11174307

050856

SET SCREW TORQUE VALUES

CONDUCTOR SIZE

#12 - 350

500 - 750

RECOMMENDED TORQUE (FT.-LBS.)

30

40

NOTES:

1. ALUMINUM TERMINAL WILL ACCEPT #1/0-#750 KCMIL AL. & CU. TORQUE CONDUCTOR SET SCREWS PER THE

TABLE ABOVE.

2. FOR COPPER TO ALUMINUM AND ALUMINUM TO ALUMINUM FLAT CONNECTIONS, SEE DWGS. 03.02-09A AND

03.02-09B.

3. ALWAYS APPLY GRIT INHIBITOR ( CN 30524607 ) ON ALUMINUM CONDUCTORS AFTER WIRE BRUSHING.

4. ALWAYS APPLY NO GRIT INHIBITOR ( CN 30524300 ) ON COPPER CONDUCTORS AFTER WIRE BRUSHING.

5. RE-USE SECONDARY BLOCK TERMINALS WHEN POSSIBLE. CHECK FOR STRIPPED OR CROSSED THREADS ON

THE CONDUCTOR SET SCREWS. CLEAN WITH BRUSH TO REMOVE ANY CONTAMINANTS.

6. PARALLELED CUSTOMER CONDUCTORS MUST BE "RUNG OUT" PRIOR TO ENERGIZING TO PREVENT CROSS

PHASING.

3

2

1

6/26/13

0 6/29/10

REVISED

ROBESON

SIMMONS

BY

GUINN ADCOCK

GUINN

CK'D

ELKINS

APPR.

TRANSFORMER SECONDARY SPADE

BLOCK TERMINALS

DWG.

27.06-12

THREE-PHASE, THREE WIRE 480 VOLT SERVICE IS SPECIFICALLY LISTED IN THE CUSTOMER SERVICE HANDBOOK

AS "READILY AVAILABLE FOR ALL METERED DEMAND LOADS AND CAN BE SUPPLIED BY MEANS OF A PAD-MOUNTED

TRANSFORMER WHEN THREE-PHASE, FOUR WIRE PRIMARY IS AVAILABLE."

IT IS A SOMEWHAT COMMON REQUEST FROM CUSTOMERS FOR THREE-PHASE, THREE WIRE 480 VOLT SERVICE.

IT IS EASILY DELIVERED FROM A PAD-MOUNTED TRANSFORMER WITH SEPARATE H0 AND X0 BUSHINGS. THE

TRANSFORMER GROUP SPECIFICATIONS FOR TRANSFORMERS INCLUDE PROVISIONS FOR SEPARATE H0 AND X0

BUSHINGS TO MAKE IT EASY TO PROVIDE THIS SERVICE WITH NO TRANSFORMER MODIFICATIONS.

PAD-MOUNTED TRANSFORMERS ARE WOUND WYE-WYE, SO A THREE WIRE DELTA SERVICE CANNOT BE PROVIDED.

HOWEVER, BY FLOATING THE SECONDARY NEUTRAL, A GROUNDED WYE-FLOATING WYE 480 VOLT THREE WIRE

SERVICE IS PROVIDED. IN ACTUAL APPLICATION A FLOATING WYE THREE WIRE SERVICE IS EQUIVALENT TO A

DELTA THREE WIRE SERVICE.

LABELS

SEE DWG. 27.06-28 FOR A LABEL TO AFFIX TO TRANSFORMER WHEN A THREE-PHASE, THREE WIRE 480 VOLT

SERVICE IS PROVIDED. IF TRANSFORMER IS EVER REMOVED FROM SERVICE AND RESTOCKED, THE LABEL MUST

BE REMOVED AND GROUNDLINK REINSTALLED (ON TYPE II TRANSFORMERS).

3

2

1

0

6/29/10 SIMMONS GUINN

REVISED BY

ELKINS

CK'D APPR.

THREE-PHASE, THREE-WIRE 480 VOLT SERVICE

R

DWG.

27.06-16

TYPE III TRANSFORMER

(SEPARATE H0-X0 BUSHING)

TRANSFORMER

PHASE WIRES

CUSTOMER'S PANEL

FAULT CURRENT

FLOW

STRAP TO

TANKS

CONNECTION

TO PAD

NEUTRAL

HO XO

TRANSFORMER MUST NOT HAVE

ANY WIRES CONNECTED TO

SECONDARY NEUTRAL BUSHING

(SEE NOTE 2).

CONNECT TO #4 BC GROUND LOOP

BARE STEEL

CONDUIT

IS BONDED

NEUTRAL

A SINGLE BONDING WIRE (BARE OR GREEN)

COMPANY EMPLOYEE/CONTRACTOR WILL NOT

RUN THE BONDING JUMPER SHOWN ABOVE.

HOWEVER, THE CUSTOMER MAY RUN IT AND

THE COMPANY WILL CONNECT IT TO THE

GROUND LOOP IN THE TRANSFORMER.

CUSTOMERS WITH ELECTRONIC EQUIPMENT ARE

CAUTIONED AGAINST RUNNING THIS CONDUCTOR

(SEE NOTE 6).

NOTES:

1. BONDING WIRE SHALL BE ONE CONDUCTOR ONLY, TYPICALLY A SMALL CONDUCTOR EASY TO ATTACH TO #4 BC

GROUND LOOP IN PAD-MOUNT.

2. IF THE TRANSFORMER IS CONNECTED FOR THREE WIRE SERVICE, THE SECONDARY IS CONNECTED FLOATING

WYE. THE SECONDARY NEUTRAL BUSHING MUST BE CLEAR OF ALL CONNECTIONS, INCLUDING THE SECONDARY

BUSHING GROUND STRAP. THE SECONDARY NEUTRAL BUSHING MUST BE UNGROUNDED SO FAULT CURRENT

WILL ONLY FLOW IN THE PHASE WIRES.

ONE EXCEPTION:

IF CUSTOMER HAS A HIGH RESISTANCE GROUND DETECTION SYSTEM, THEY WILL WANT TO RUN ONE SMALL

CONDUCTOR (EX. #12) TO ATTACH TO XO. THIS IS PERMITTED. GROUND STRAP IS STILL NOT CONNECTED IN

THIS CASE. IF THERE ARE ANY QUESTIONS ABOUT THIS, CONTACT DISTRIBUTION STANDARDS.

3. A TRANSFORMER CONNECTED FOR THREE WIRE SERVICE (NO NEUTRAL) CANNOT SUPPLY FOUR WIRE SERVICES.

4. OPERATIONS PERSONNEL SHALL RUN A BONDING CONDUCTOR (#4 BC) FROM THE GROUND LOOP TO THE

METERING LOCATION TO BOND THE METER BOX MOUNTED ON THE WALL OF THE TRANSFORMER. TANK. IF THE

METER BOX IS MOUNTED TO THE CUSTOMER'S WALL, THE BONDING CONDUCTOR SHALL BE ATTACHED TO THE

CUSTOMER'S GROUND.

5. ONLY PAD-MOUNTED TRANSFORMERS WITH SEPARATE PRIMARY AND SECONDARY NEUTRAL BUSHINGS SHOULD

BE USED TO PROVIDE THREE WIRE SERVICES. SEE DWGS. 27.06-26 AND 27.06-28 FOR ADDITIONAL

INFORMATION ON TRANSFORMERS THAT DO NOT HAVE SEPARATE HO-XO BUSHINGS.

6. CUSTOMER SHOULD BE AWARE THAT A THREE WIRE SERVICE SHOULD ONLY BE USED IN SPECIAL CASES.

CUSTOMER MUST HAVE A GROUND DETECTION SYSTEM INSTALLED (NEC 250.21). CUSTOMER HAVING

ELECTRONIC LOADS SUCH AS VARIABLE SPEED DRIVES OR LIGHTNING CONCERNS SHOULD CONSIDER A

GROUNDED WYE CONNECTION.

3

2

1

O 8/1/14

REVISED

DANNA

BY

DANNA

CK'D

ADCOCK

APPR.

THREE WIRE SERVICES,

FLOATING WYE CONNECTION

DEC DEM DEP DEF

X

27.06-20

X

TYPE III TRANSFORMER

(SEPARATE H0-X0 BUSHINGS)

TRANSFORMER CUSTOMER'S PANEL

PHASE WIRES

GROUND FAULT

CURRENT FLOW

STRAP TO

TANKS

CONNECTION

TO PAD

NEUTRAL

H0

NEUTRAL

NEUTRAL

NEUTRAL

X0

STRAP TO TANK

& CONNECTION TO

PAD NEUTRAL

NEUTRAL

IF TRANSFORMER SYSTEM IS

GROUNDED, NEUTRAL CONDUCTOR

IS REQUIRED BY N.E.C. RULE

250.24(C) TO PROVIDE FAULT

CURRENT PATH.

BONDING WIRES (BARE OR GREEN)

SHOULD NOT BE RUN

BY THE CUSTOMER

DO NOT CONNECT

SEE NOTE 4

JUMPER

BARE STEEL

CONDUIT

IS BONDED

NOTES:

1. IF THE TRANSFORMER SECONDARY NEUTRAL IS GROUNDED, THE CUSTOMER MUST CONNECT A NEUTRAL

CONDUCTOR FROM THEIR PANEL TO THE TRANSFORMER. THIS NEUTRAL CONDUCTOR PROVIDES A PATH FOR

GROUND FAULT CURRENT TO FLOW.

2. A TRANSFORMER CONNECTED FOR FOUR WIRE SERVICE (GROUNDED NEUTRAL) CANNOT SUPPLY THREE WIRE

SERVICES.

3. SEE DWGS. 27.06-26 AND 27.06-28 FOR ADDITIONAL INFORMATION ON TRANSFORMERS THAT DO NOT HAVE

SEPARATE H0-X0 BUSHINGS.

4. A SEPARATE BONDING CONDUCTOR OR CONDUCTORS ARE NOT NECESSARY. ELECTRICIANS SHOULD

BE ADVISED NOT TO RUN BONDING CONDUCTORS. IF THEY INSIST ON RUNNING BONDING

CONDUCTORS, DO NOT CONNNECT THEM TO ANY COMPANY EQUIPMENT: TAPE THEM UP AND LAY

THEM IN THE BOTTOM OF THE TRANSFORMER TANK.

3

2

1

5/2/13

4/1/11

0 4/12/10

REVISED

SIMPSON SIMPSON ADCOCK

SIMPSON SIMPSON ELKINS

SIMPSON SIMPSON

BY CK'D

ELKINS

APPR.

FOUR WIRE SERVICES,

GROUNDED WYE CONNECTION

DWG.

27.06-24

PRIMARY

TYPE I TRANSFORMER

(OBSOLETE OLD TRANSFORMER)

SECONDARY

H1 H2 H3 X1

H0

GROUNDED WYE - GROUNDED WYE

X2 X3

THIS TYPE OF TRANSFORMER HAS

A PERMANENT INTERNAL SECONDARY

GROUND THAT MAKES IT IMPOSSIBLE

TO PROVIDE A 3-WIRE. FLOATING WYE

SERVICE.

NOTES:

1. THE NEUTRAL CONNECTION BETWEEN THE PRIMARY & SECONDARY WINDING MAY BE A BARE CONDUCTOR AND

GROUNDED INTERNAL TO THE TANK. THE H0 X0 BUSHING MAY NOT BE INSULATED.

2. THIS TRANSFORMER CANNOT BE USED TO PROVIDE 3-WIRE SERVICE.

3. TRANSFORMER GROUND IS CONNECTED TO THE Ho Xo BUSHING.

PRIMARY

TYPE III TRANSFORMER

SECONDARY PRIMARY

ISOLATED

NEUTRALS

SECONDARY

H1 H2 H3 X1

H0 X0

GROUNDED WYE - GROUNDED WYE

X2 X3 H1 H2 H3 X1 X2 X3

X0

H0

STRAP REMOVED

NEUTRAL FLOATING

*

GROUNDED WYE - FLOATING WYE

NOTES:

1. PRIMARY AND SECONDARY NEUTRALS ARE NOT CONNECTED INTERNAL.

2. TO PROVIDE 3-WIRE SERVICE, REMOVE THE TANK GROUNDING STRAP ON THE X0 BUSHING. ATTACH

TRANSFORMER GROUND TO Ho BUSHING ONLY.

* REQUIRES "CAUTION" LABEL FOR TYPE III TRANSFORMER INSTALLED IN SECONDARY COMPARTMENT ( CN 21129812 )

3

2

1

0

6/29/10 SIMMONS GUINN

REVISED BY

ELKINS

CK'D APPR.

THREE-PHASE PAD-MOUNTED TRANSFORMERS

PRIMARY AND SECONDARY WINDING - NEUTRAL

CONNECTIONS VARIATIONS FOR 3-WIRE SERVICES

DWG.

R

27.06-26

TYPE II

CN 21129713

Type II Transformer (Combination HoXo Bushing)

This transformer has been modified internally to provide a floating-wye secondary winding, three-wire service to the customer.

The internal secondary grounding link has been removed to isolate the secondary winding from the primary winding neutral and the grounded HoXo bushing. The ground strap and the transformer grounding conductor must be connected to the HoXo bushing to ground the neutral of the primary winding.

Only three wire services may be connected to this transformer.

Certification of correct connection:

DFS/Line Inspector

If this transformer is removed from service, the internal secondary grounding link must be re-connected and this label removed. Refer to the transformer section in the

Distribution Construction Specifications Manual to determine the "type" of replacement transformer and modification that must be done to provide a three-wire floating wye service.

CN 21129713

Date

TYPE III

CN 21129812

Type III Transformer (Separate HoXo Bushing)

This transformer has been modified externally to provide a floating-wye, three-wire service to the customer.

The tank grounding strap has been removed from the Xo bushing and the bushing is not grounded. The Ho bushing in the primary compartment is grounded to provide a ground to the neutral of the primary winding.

Only three wire services may be connected to this transformer.

Certification of correct connection:

DFS/Line Inspector Date

If this transformer is removed from service, the tank grounding strap is to be re-installed on the Xo bushing and this label removed. Refer to the transformer section in the Distribution Construction Specifications Manual to determine the "type" of replacement transformer and modification that must be done to provide a three-wire floating wye service.

CN 21129812

1

0

3

2

6/26/10

REVISED

SIMMONS

BY

GUINN ELKINS

CK'D APPR.

THREE-PHASE PAD-MOUNTED TRANSFORMERS PRIMARY

AND SECONDARY WINDING -

NEUTRAL CONNECTIONS LABELS FOR 3 WIRE SERVICES

DWG.

27.06-28

4.16KV CONDUCTORS

WITH STRESS RELIEF

TERMINATIONS. SEE NOTE 4

ON DWG. 27.06-34B.

4.16KV CONDUCTORS AND

TERMINATIONS TO BE

PROVIDED BY CUSTOMER.

SEE NOTE 3

78"

FRONT VIEW

85"

CN 12952719

TU2500DLM14DYJC

DUAL VOLTAGE

TRANSFORMER FOR

USE ON 12.47KV AND

22.86KV SYSTEMS.

8"

77"

46"

SIDE VIEW

NOTES:

1. SEE DWG. 27.06-34B FOR ADDITIONAL VIEWS AND NOTES.

2. ALL DIMENSIONS ARE APPROXIMATE. OVERALL WEIGHT ~13,925 POUNDS. GALLONS OF OIL ~569.

3. IF TRANSFORMER IS INSTALLED AT OPEN POINT IN THE PRIMARY, INSTALL ELBOW ARRESTERS ON H1B,

H2B AND H3B BUSHINGS. IF 12.47KV, USE 10KV ARRESTERS ( CU ARREL10C , CN 11232303 ). IF 22.86KV,

USE 18KV ARRESTERS ( CU ARREL18C , CN 11232204 ).

3

2

1

0 8/9/13

REVISED

SIMMONS

BY

GUINN

CK'D

ADCOCK

APPR.

2500 KVA, THREE-PHASE, PAD-MOUNTED

TRANSFORMER WITH 4160Y/2400 VOLT SECONDARY

DWG.

27.06-34A

REMOVABLE BARRIER BOARD

WITH DANGER LABEL.

SEE NOTES 2 AND 3.

FRONT VIEW

4.16KV COMPARTMENT DOOR OPEN

SHOWING BARRIER BOARD

SEE NOTE 3

DANGER LABEL

CN 9220247755

FRONT VIEW

DOORS CLOSED

NOTES:

1. SEE DWG. 27.06-34A FOR FRONT AND SIDE VIEWS.

2. TRANSFORMER MUST HAVE REMOVABLE BARRIER BOARD THAT PREVENTS ACCESS TO THE 4.16KV BUSHING

TERMINATIONS WHEN THE 4.16KV COMPARTMENT DOOR IS OPEN. ANY TRANSFORMER FOUND WITHOUT A

REMOVABLE BARRIER BOARD MUST HAVE ONE ADDED BY THE GARNER REPAIR SHOP.

3. THE OUTSIDE OF THE 4.16KV COMPARTMENT DOOR AND THE BARRIER BOARD MUST HAVE A DANGER LABEL

(CN 9220247755 ) APPLIED AT EYE-LEVEL.

4. 4.16KV CABLES MUST HAVE STRESS RELIEF TERMINATIONS AND BE TERMINATED TO THE 4.16KV BUSHINGS

WITH 2-HOLE LUGS ATTACHED WITH STAINLESS STEEL BOLTS TORQUED TO 40 FT/LBS.

3

2

1

0 8/9/13

REVISED

SIMMONS

BY

GUINN

CK'D

ADCOCK

APPR.

2500 KVA, THREE-PHASE, PAD-MOUNTED

TRANSFORMER WITH 4160Y/2400 VOLT SECONDARY

DWG.

27.06-34B

METER MOUNTING RACK

(SEE NOTE 3)

METER BASE

AND METER

METER MOUNTING RACK

NOTES:

1. THE MINIPAD THREE-PHASE TRANSFORMER IS ONLY AVAILABLE WITH THE FOLLOWING RATINGS:

KVA

75

75

150

PRIMARY VOLTAGE

12,470GRDY/7200

22,860GRDY/13,200

22,860GRDY/13,200

SECONDARY VOLTAGE

208Y/120

208Y/120

208Y/120

COMPATIBLE UNIT

TU75MP3M12YBC

TU75MP3M23YBC

TU150MP3M23YBC

CATALOG NUMBER

9220127645

12951802

12951901

2. LIMIT SECONDARY WIRING TO NO MORE THAN 4 CONDUCTORS PER PHASE.

3. THE METER MOUNTING RACK AND METER BOX WILL BE FURNISHED AND INSTALLED BY METERING OPERATIONS.

4. DUE TO SPACE LIMITATIONS WITHIN THE CABINET, USING THESE UNITS AS PERMANENT LOOP OPEN POINTS

SHOULD BE AVOIDED.

3

2

1

0

6/29/10

REVISED

SIMMONS

BY

GUINN ELKINS

CK'D APPR.

MINIPAD THREE-PHASE TRANSFORMER (FMO)

DWG.

27.06-14

Download