Eaton 9390 UPS

advertisement
Power Quality Solutions
Eaton 9390
The industry’s best combination of efficiency, management of THD,
power factor and power protection
With Eaton 9390, you can enjoy an unmatched combination of power protection features in a
single system. The three-phase UPS is the result of comprehensive research and user insight
gathered by Eaton to develop the best combination of power performance, battery management, scalable architecture, flexibility, and service.
High efficiency reduces overall
cost of ownership
Product Snapshot
Power Rating : 40/60/80/100/120/160 kVA
Voltage
: 400V
Frequency
: 50Hz
Configuration : Online double conversion
The Eaton 9390 features innovations that
combine to deliver the industry’s best
overall power performance. Built on more
than 40 years of UPS design expertise, the
Eaton 9390 excels in four key factors:
1. Efficiency – maximum usable output power relative to input power
2. Total Harmonic Distortion (THD)
keeping input current distortion within
acceptable limits
3. Power factor – managing phase shifts
between voltage applied and current
drawn by circuits
4. Double-conversion topology – co
plete isolation of protected loads from
input utility power
The efficiency rating of a UPS is a
measure of the energy the UPS
uses for its own operation and dissipates usually in the form of heat.
For example, a UPS that is 90%
efficient delivers 90 kW of useful
output power for every 100 kW
it takes in. The more efficient the
UPS, the less you pay torun your
protected equipment and to cool
the UPS. With an advanced design
and sophisticated sensing and control circuitry, the Eaton 9390 UPS
delivers an efficiency of up to 94%.
In addition to dramatic cost savings, this level of system efficiency
extends battery runtimes and produces cooler operating conditions
within the UPS, which extends the
life of components and increases
overall reliability and performance.
Low THD enhances compatibility with generators
The Eaton 9390 uses a new input
circuit that is uniquely capable of
keeping Total Harmonic Distortion
(THD) at a low level – less than 3
percent – without compromising
efficiency. A key benefit is that the
UPS is therefore compatible with
a wide range of generators, even
though generator output frequencies will fluctuate when the UPS
transitions to generator power and
as other loads are started up.
Power factor performance
maximises compatibility and
meets high power factor load
requirements
The closer the power factor is to
unity, the more efficient the transfer
of power between source and load.
With an input power factor of 0.99,
the Eaton 9390 UPS is exceptionally compatible with diverse power
sources, especially auxiliary generators.
On the output side, the 9390 can
also provide its full power capability
to loads that have a wide range of
leading and lagging power factors,
spanning all known computer loads.
Double-conversion topology
provides the best protection
possible
With the Eaton 9390’s doubleconversion process, your sensitive
electronic systems are completely
isolated from raw utility power and
all its irregularities. Double conversion provides the highest level of
protection available and enables
equipments to perform to manufacturer specifications.
Whether you are selecting a UPS
for a branch office or a large data
centre, there is an Eaton 9390
model that delivers just the right
combination of performance and
price for your needs. Visit our website www.powerquality.eaton.com
for more information.
Eaton 9390 UPS 40-160 kVA
TECHNICAL SPECIFICATIONS
<3% (100% linear load); <5% (reference non
linear load)
0.9 (e.g. 72 kW at 80 kVA)
Output UTHD
UPS output power rating (0.9 p.f.)
kVA
40
60
80
100
120
160
Output power factor
kW
36
54
72
90
108
144
Permitted load power factor 0.7 lagging - 0.8 leading
10 min 100-110%; 30 sec 110-125%;
Overload on inverter
10 sec 125-150%; 300 ms >150%
Continuous 100-110%, 10 min 110-150%, 5 ms
Overload when bypass
1000% Note! Bypass fuses may limit the overavailable
load capability
General
Efficiency in double
conversion mode (full load)
Efficiency in double
conversion mode (half load)
Efficiency in Energy Saver
System (ESS)
Distributed parallelling with
Hot Sync technology
Field upgradeable
94%
92.5%
Battery
up to 99%
6+1
yes
Inverter/rectifier topology
transformer-free IGBT with PWM
Audible noise
<65 dB / <70 dB
Altitude (max)
1000 m without derating (max 2000 m)
Input
3 ph + N + PE
Nominal voltage rating
(configurable)
220/380, 230/400, 240/415 V 50/60 Hz
Input frequency range
Low -20% at 100% load/-50% at 50% load without
battery discharge; High +10%/max +20%
45-65 Hz
Input power factor
0.99
Input ITHD
less than 4.5%
Soft start capability
Yes
Internal backfeed protection Yes
ABM technology or Float
Temperature compensation
Battery nominal voltage
(lead-acid)
Charging current / Model
Default A
Max* A
Optional
480 V (40 x 12 V, 240 cells)
40 60 80 100 120 160
10 20­ 20 30 30 40
20 40 40 60 60 80
Accessories
External battery cabinets with long-life batteries, X-Slot connectivity (Web/
SNMP, ModBus/Jbus, Relay, Hot Sync, ViewUPS-X remote display), Hot Sync
parallel tie cabinet, integrated manual bypass up to 80 kVA, external maintenance bypass switch
Communications
X-Slot
4 communication bays
Serial ports
1 available
Relay inputs/outputs
6/3 programmable
Compliance with standards
Output
Output wiring
Nominal voltage rating
(configurable)
Maintenance free VRLA batteries, NiCd
Charging method
*May be limited by maximum UPS input current rating
Input wiring
Input voltage range
Type
3 ph + N + PE
220/380, 230/400, 240/415 V 50/60 Hz
Safety (CB certified)
IEC 62040-1, IEC 60950-1
EMC
IEC 62040-2
Performance
IEC 62040-3
Standard UPS
Part number
1028510
1028511
1028512
1028513
1028514
1028515
1028516
Description
9390-40-N-4xO
9390-60-U-4xO
9390-80-N-4xO
9390-100-U-4xO
9390-120-N-4xO
9390-120-U-4xO
9390-160-N-4xO
Rating
40 kVA / 36 kW
60 kVA / 54 kW
80 kVA / 72 kW
100 kVA / 90 kW
120 kVA / 108 kW
120 kVA / 108 kW
160 kVA / 144 kW
Dimensions (HxWxD)
1879x519x808 mm
1879x519x808 mm
1879x519x804 mm
1879x944x804 mm
1879x944x804 mm
1879x944x804 mm
1879x944x804 mm
Headquarters
Offices Across India
Eaton’s Electrical Sector
Americas Region
8609 Six Forks Road Raleigh, NC 27615 U.S.A
Mumbai
Bangalore
EL Floor, VITS Luxury Business Hotel,
Andheri Kurla Road, Andheri (East),
Mumbai - 400 059
Tel : +91-22-4005 3817
Fax: +91-22-4005 3810
Unit No. 501, 4th Floor,
Prestige Atrium, Central Street,
Bangalore - 560 001
Tel : +91 80 4901 2200
Fax: +91 80 4901 2239
Chennai
No. 22, Chamier’s Road,
Block “D” Ashika Chambers,
Teynampet, Chennai - 600 018
Tel : +91 44 2432 0249-50
Fax: +91 44 2432 0249
Ahmedabad:
Chandigarh:
Coimbatore:
Cochin:
Gurgaon:
South Asia Office
Eaton’s Electrical Sector
Eaton Power Quality Pvt. Ltd.
6th Floor, Tower- B,
Plot No. 8, Sector - 127, Noida - 201301
Tel: +91 - 0120 - 3855300
Sales and Service
Toll Free Hotline.: 1800 200 7887
E-mail: EatonPowerQualityIndia@eaton.com
In the interests of continuous product improvement all specifications are subject to change without notice.
www.eaton.com/powerquality
Weight
257 kg
313 kg
313 kg
430 kg
430 kg
530 kg
530 kg
Sales and Service Operations
Hyderabad:
Kolkata:
Pune:
+91 932 703 1597
+91 172 501 1578
+91 934 541 9578
+91 934 982 1582
+91 124 410 0047
+91 124 436 6315
+91 40 4018 9601
+91 33 4004 0968
+91 20 3061 1886
Sri Lanka:
+94 112871000
+94 117520031
Nepal:
+97 714429777
+97 714429888
+97 714423376
Bangladesh:
© 2013 Eaton Corporation, All Rights Reserved, 00DATA1018147 rev E, May 2013
Download