clover, sc 29710 oct. 31, 2014 - Cam

CLOVER SCHOOL DISTRICT TWO
CUM
Building Value Through Expertise
CLOVER REPLACEMENT MIDDLE SCHOOL
SE
email:kclayton@ccorpusa.com
1466 HIGHWAY 55
CLOVER, SC 29710
BID DOCUMENTS
OCT. 31, 2014
9201-131360
TIMMONS GROUP
YOUR VISION ACHlEVED THROUGH OURS.
CIVIL / LANDSCAPE
TIMMONS GROUP
2030 SOUTH TRYON STREET, SUITE 3C
CHARLOTTE, NC 28203
tel: 704.376.1073
fax: 704.376.1076
email:brian.crutchfield@timmons.com
042
042
|ff')Q
EEIME3|E
E
RISTS
STRUCTURAL
ADC ENGINEERING, INC.
7825 BROAD RIVER ROAD
IRMO,SC 29063
tel: 803.732.7080
fax: 803.732.7090
email:brian.crutchfield@timmons.com
"9'a**''a9
ARCHITECTURAL
LS3P ASSOCIATES LTD.
227 WEST TRADE STREETSUITE 700
CHARLOTTE, NC 28202
tel: 704.333.6686
fax:704.333.2926
email:davidbellamy@ls3p.com
FIRE PROTECTION PLUMBING
MECHANICAL
OPTIMA ENGINEERING PA
1927 South Tryon Street
CHARLOTTE, NC 28203
tel: 704.338.1292
email:sdaley@optimapa.com
ELECTRICAL
C CL
OV E R
M
LSD
D L E
H O O
MATERIAL LEGEND
(NOTALLMATERIALSAPPLICABLE)
PLAN AND SECTION
1466 HIGHWAY 55
CLOVER SC 29710
OSF CONSTRUCTION DOCUMENTS
9201-131360
STRUCTURAL
COVER SHEET
INDEX OF DRAWINGS
BUILDING CODE ANALYSIS FORM F3 (1 of 2)
BUILDING CODE ANAYLSIS FORM F3 (2 OF 2)
LIFE SAFETY PLAN MIDDLE SCHOOL
LIFE SAFETY PLAN FIELD HOUSE AND RESTROOM BUILDING
& U.L. DETAILS
COM CHECK BUILDING ENVELOPE COMPLIANCE
CERTIFICATES
CIVIL
TIMMONS GROUP
2030 SOUTH TRYON STREET, SUITE 3C
CHARLOTTE, NC 28203
tel: 704.376.1073
fax: 704.376.1076
email:brian.crutchfield@timmons.com
D
-
-
B
C-000
C-001
0-100
C-200
0-201
0-202
C-203
0-204
C-205
C-206
C-300
0-301
0-302
0-303
0-304
C-305
C-306
C-307
C-308
C-400
0-401
0-402
C-403
0-404
OS-001
OS-100
OS-101
OS-102
OS-103
OS-200
OS-201
OS-202
OS-203
OS-204
OS-205
OS-206
OS-207
OS-208
OS-209
OS-300
OS-301
POROUS FILL
SPRAY-ON
^
AMSN M
C MMON OR FACE)
GENERAL
G-006
PLYWOOD
STRUCTURAL CONCRETE
(CAST IN PLACE, ETC.)
LIST OF SHEETS
G-000
G-001
G-002
G-003
G-004
G-005
EARTH
CIVIL COVER SHEET
OVERALL SITE PLAN
EXISTING CONDITIONS
PHASE Ill EROSION CONTROL PLAN
PHASE Ill EROSION CONTROL PLAN
PHASE Ill EROSION CONTROL PLAN
PHASE Ill EROSION CONTROL PLAN
EROSION CONTROL NOTES & DETAILS
EROSION CONTROL NOTES & DETAILS
EROSION CONTROL NOTES & DETAILS
SITE & UTILITY PLAN
SITE & UTILITY PLAN
SITE & UTILITY PLAN
SITE & UTILITY PLAN
LAYOUT & UTILITIES NOTES & DETAILS
LAYOUT & UTILITIES NOTES & DETAILS
ATHLETIC FACILITIES NOTES & DETAILS
ATHLETIC FACILITIES NOTES & DETAILS
ATHLETIC FACILITIES NOTES & DETAILS
GRADING & DRAINAGE PLAN
GRADING & DRAINAGE PLAN
GRADING & DRAINAGE PLAN
GRADING & DRAINAGE PLAN
BMP DETAILS
OVERALL SITE PLAN
PHASE I EROSION CONTROL
PHASE II EROSION CONTROL PLAN
PHASE II EROSION CONTROL PLAN
EROSION CONTROL NOTES & DETAILS
SITE & UTILITY PLAN
SITE & UTILITY PLAN
SCDOT ROAD IMPROVEMENTS
SCDOT ROAD IMPROVEMENTS
SCDOT ROAD IMPROVEMENTS
SITE DETAILS
STRIPING AND SIGNAGE PLAN
STRIPING AND SIGNAGE PLAN
SIGHT DISTANCE PROFILES
SIGHT DISTANCE PROFILES
GRADING & DRAINAGE PLAN
GRADING & DRAINAGE PLAN
ADC ENGINEERING, INC.
7825 Broad River Road
IRMO,SC 29063
tel: 803.732.7080
fax: 803.732.7090
email:KyleM@adcengineering.com
S-100
S-101
S-101S
S-102
S-102S
S-103
S-103S
S-104
S-104S
S-105
S-105S
S-106
S-106S
S-107
S-107S
S-111
S-112
S-113
S-114
S-115
S-116
S-117
S-121
S-122
S-123
S-124
S-124.1
S-125
S-126
S-127
S-131
S-132
S-133
S-134
S-135
S-136
S-137
S-151
S-152
S-153
S-154
S-155
S-156
S-200
S-210
S-211
S-220
S-221
S-222
S-230
S-231
S-240
S-301
S-302
S-401
S-402
S-501
S-502
S-503
S-504
-
GENERAL NOTES & ABBREVIATIONS
FOUNDATION PLAN - AREA A.1
SLAB PLAN - AREA A.1
FOUNDATION PLAN - AREA A.2
SLAB PLAN - AREA A.2
HIGH ROOF FRAMING PLAN - AREA A.3
SLAB PLAN - AREA A.3
FOUNDATION PLAN - AREA B.1
SLAB PLAN - AREA B.1
FOUNDATION PLAN - AREA B.2
SLAB PLAN - AREA B.2
FOUNDATION PLAN - AREA C.1
SLAB PLAN - AREA C.1
FOUNDATION PLAN - AREA C.2
SLAB PLAN - AREA C.2
CMU & LINTEL PLAN - AREA A.1
CMU & LINTEL PLAN - AREA A.2
CMU & LINTEL PLAN - AREA A.3
CMU & LINTEL PLAN - AREA B.1
CMU & LINTEL PLAN - AREA B.2
CMU & LINTEL PLAN - AREA C.1
CMU & LINTEL PLAN - AREA C.2
LOW ROOF FRAMING PLAN - AREA A.1
LOW ROOF FRAMING PLAN - AREA A.2
LOW ROOF FRAMING PLAN - AREA A.3
LOW ROOF FRAMING PLAN - AREA B.1
LOW ROOF FRAMING PLAN AREA B.1
LOW ROOF FRAMING PLAN AREA B.2
LOW ROOF FRAMING PLAN AREA C.1
LOW ROOF FRAMING PLAN AREA C.2
HIGH ROOF FRAMING PLAN AREA A.1
HIGH ROOF FRAMING PLAN AREA A.2
HIGH ROOF FRAMING PLAN AREA A.3
HIGH ROOF FRAMING PLAN AREA B.1
HIGH ROOF FRAMING PLAN AREA B.2
HIGH ROOF FRAMING PLAN AREA C.1
HIGH ROOF FRAMING PLAN AREA C.2
PARTIAL AND ENLARGED FRAMING PLANS
PARTIAL AND ENLARGED FRAMING PLANS
PARTIAL AND ENLARGED FRAMING PLANS
PARTIAL AND ENLARGED FRAMING PLANS
FIELD HOUSE PLANS
RESTROOM BUILDING PLANS
SCHEDULES
TYPICAL CONCRETE DETAILS
TYPICAL CONCRETE DETAILS
TYPICAL CMU DETAILS
TYPICAL CMU DETAILS
TYPICAL CMU DETAILS
TYPICAL STEEL DETAILS
TYPICAL STEEL DETAILS
TYPICAL COLD FORMED METAL BUILDINGS
SECTIONS AND DETAILS
SECTIONS AND DETAILS
SECTIONS AND DETAILS
SECTIONS AND DETAILS
SECTIONS AND DETAILS
SECTIONS AND DETAILS
SECTIONS AND DETAILS
SECTIONS AND DETAILS
ARCHITECTURAL
A-001
A-002
A-003
A-004
A-005
A-100
A-101
A-102
A-103
A-104
A-105
A-106
A-107
A-108
A-110A
A-110B
A-111
A-112
A-113
A-115
A-116
A-117
A-120
A-121
A-122
A-123
A-124
A-125
A-126
A-127
A-151
A-152
A-201
A-202
A-203
A-204
A-205
A-206
A-207
A-208
A-209
A-251
A-252
A-253
A-254
A-255
A-301
A-302
A-303
A-304
A-305
A-306
A-307
A-351
A-352
A-353
A-354
A-355
A-356
A-357
A-401
A-402
A-403
A-404
A-405
A-406
A-408
A-409
A-410
A-411
A-501
A-502
A-503
A-504
A-505
A-506
A-511
A-512
A-513
A-551
A-552
A-553
A-601
A-602
A-603
A-605
A-611
A-612
A-613
A-621
A-622
A-623
A-624
FIRE PROTECTION
ARCHITECTURAL SITE PLAN
ARCHITECTURAL SITE DETAILS
ARCHITECTURAL SITE DETAILS
CONSTRUCTION SUBSYSTEMS
PARTITION TYPES AND DETAILS
OVERALL PLAN
AREA A.1
AREA A.2
AREA A.3
AREA B.1
AREA B.2
AREA C.1
AREA C.2
CLERESTORY PLAN
FIELD HOUSE PLANS, ELEVATIONS & SECTIONS
RESTROOM BUILDING
FIELD HOUSE -WALL SECTIONS & ENLARGED DETAILS
FIELD HOUSE -WINDOW & DOOR DETAILS
FIELD HOUSE ROOM FINISH AND DOOR SCHEDULE
OVERALL CANOPY PLANS
ENLARGED CANOPY PLANS & DETAILS
CANOPY SECTIONS & DETAILS
OVERALL REFLECTED CEILING PLAN
AREA A.1 REFLECTED CEILING PLAN
AREA A.2 REFLECTED CEILING PLAN
AREA A.3 REFLECTED CEILING PLAN
AREA B.1 REFLECTED CEILING PLAN
AREA B.2 REFLECTED CEILING PLAN
AREA C.1 REFLECTED CEILING PLAN
AREA C.2 REFLECTED CEILING PLAN
ROOF PLAN
ENLARGED ROOF PLANS
OVERALL EXTERIOR ELEVATIONS
OVERALL EXTERIOR ELEVATIONS
OVERALL EXTERIOR ELEVATIONS
BUILDING A ELEVATIONS
BUILDING A & B ELEVATIONS
BUILDING B ELEVATIONS
BUILDING C ELEVATIONS
BUILDING B & C ELEVATIONS
ELEVATIONS
INTERIOR ELEVATIONS
INTERIOR ELEVATIONS
INTERIOR ELEVATIONS
INTERIOR ELEVATIONS
INTERIOR ELEVATIONS
BUILDING SECTIONS - BUILDING A
BUILDING SECTIONS - BUILDING A
BUILDING SECTIONS - BUILDING B
BUILDING SECTIONS - BUILDING B
BUILDING SECTIONS - BUILDING C
BUILDING SECTIONS - BLDGS A, B, & C CONNECTORS
BUILDING SECTIONS - BLDGS A, B, & C CONNECTORS
WALL SECTIONS
WALL SECTIONS
WALL SECTIONS
WALL SECTIONS
WALL SECTIONS
WALL SECTIONS
WALL SECTIONS
ENLARGED P.E. TOILET, LOCKER AND SHOWER ROOM PLANS
ENLARGED TOILET PLANS
ENLARGED SERVICE/ DUMPSTER AREA PLAN
ENLARGED SERVICE AND KITCHEN AREA PLAN
ENLARGED FLOOR PLANS
ENLARGED FLOOR PLANS
ATHLETIC FIELD BLEACHERS
ENLARGED GYM FLOOR PLAN
ENLARGED MECHANICAL PLATFORM
STAIR PLANS & SECTIONS
PLAN DETAILS
PLAN DETAILS
ENLARGED DETAILS
COMPONENT DETAILS
CEILING AND SEISMIC DETAILS
CEILING DETAILS
SECTION DETAILS
SECTION DETAILS
SECTION DETAILS
LOW SLOPE ROOF DETAILS
LOW SLOPE ROOF DETAILS & SKYLIGHT DETAILS
METAL ROOF DETAILS
DOOR & FRAME SCHEDULE BLDG A
DOOR & FRAME SCHEDULE BLDG B & C
DOOR, FRAME & WINDOW TYPE LEGEND
WINDOW DETAILS
INTERIOR FINISH LEGEND
INTERIOR FINISH SCHEDULE
INTERIOR FINISH SCHEDULE CONT.
OVERALL FINISH PLAN
ENLARGED FINISH PLAN A.1 & A.2
ENLARGED FINISH PLAN A.3
ENLARGED FINISH PLAN B.1
A-625
A-626
A-627
A-628
A-701
A-702
A-703
A-704
A-705
A-706
A-707
A-708
A-711
A-712
A-751
A-752
A-753
A-754
A-761
A-800
1927 South Tryon Street
email:
FP-001
FP-101
NOTES, LEGEND, SCHEDULES AND SCHEMATICS - FIRE PROTECTION
FLOOR PLANS - FIRE PROTECTION
PLUMBING
STEEL, IRON
BRICK
ALUMINUM
CERAMIC TILE
WOOD (FINISH)
1927 South Tryon Street
CHARLOTTE, NC 28203
tel:
704.338.1292
email:
P-001
P-002
P-101
P-102
P-103
P-104
P-105
P-106
P-107
P-201
P-202
P-203
P-204
P-205
P-206
P-207
email: gregb@whitmireballington.com
CONE / NH /
.
STUCCO
EQUIPMENT PLAN
EQUIPMENT PLUMBING ROUGH-INS
EQUIPMENT ELECTRICAL ROUGH-INS
EQUIPMENT FABRICATED ITEMS
sdaley@optimapa.com
GLASS
WOOD BLOCKING
SHINGLES/SIDING
NOTES, SCHEDULES, LEGEND - PLUMBING
SCHEMATICS - PLUMBING
FLOOR PLAN AREA A.1 & A.2 - PLUMBING
FLOOR PLAN AREA A.3 - PLUMBING
FLOOR PLAN AREA B.1 - PLUMBING
FLOOR PLAN AREA B.2 - PLUMBING
FLOOR PLAN AREA C.1 - PLUMBING
FLOOR PLAN AREA C.2 - PLUMBING
MECHANICAL PLATFORM PLANS -PLUMBING
FLOOR PLAN AREA A.1 & A.2 -PLUMBING SUPPLY PIPING
FLOOR PLAN AREA A.3 -PLUMBING SUPPLY PIPING
FLOOR PLAN AREA B.1 -PLUMBING SUPPLY PIPING
FLOOR PLAN AREA B.2 -PLUMBING SUPPLY PIPING
FLOOR PLAN AREA C.1 -PLUMBING SUPPLY PIPING
FLOOR PLAN AREA C.2 -PLUMBING SUPPLY PIPING
MECHANICAL PLATFORM PLANS - PLUMBING SUPPLY PIPING
ELECTRICAL
OPTIMA ENGINEERING PA
1927 South Tryon Street
ENGAGE DESIGN TRANSFORM
CHARLOTTE, NC 28203
tel:
704.338.1292
email:
MECHANICAL
E-001
E-002
E-003
E-004
E-005
E-006
E-007
E-008
E-009P
E-009P2
E-10
E-11
E-12
E-101
E-102
E-103
E-104
E-105
E-106
E-107
E-108
E-201
E-202
E-203
E-204
E-205
E-206
E-207
E-208
E-209
E-210
E-211
E-301
E-302
E-303
E-304
E-305
E-307
E-501
E-502
E-503
E-504
E-600
E-601
E-700
E-701
E-702
E-703
E-704
E-705
E-706
E-707
OPTIMA ENGINEERING PA
1927 South Tryon Street
CHARLOTTE, NC 28203
tel:
704.338.1292
email:
M-001
M-002
M-003
M-004
M-005
M-101
M-102
M-103
M-104
M-105
M-106
M-107
M-201
M-202
M-203
M-204
M-205
M-206
M-207
M-301
M-302
M-303
M-304
M-401
M-402
M-403
AREA MAP
sdaley@optimapa.com
MECHANICAL LEGEND, INDEX, NOTES, AND SCHEDULES
MECHANICAL SCHEDULES
MECHANICAL SCHEDULES
MECHANICAL SEQUENCE OF OPERATION
MECHANICAL POINTS LIST
FLOOR PLAN AREA A.1 - MECHANICAL
FLOOR PLAN AREA A.2 - MECHANICAL
FLOOR PLAN AREA B.1 - MECHANICAL
FLOOR PLAN AREA B.2 - MECHANICAL
FLOOR PLAN AREA C.1 - MECHANICAL
FLOOR PLAN AREA C.2 - MECHANICAL
ROOF AND FIELD HOUSE PLANS - MECHANICAL
FLOOR PLAN AREA A.1 - MECHANICAL PIPING
FLOOR PLAN AREA A.2 - MECHANICAL PIPING
FLOOR PLAN AREA B.1 - MECHANICAL PIPING
FLOOR PLAN AREA B.2 - MECHANICAL PIPING
FLOOR PLAN AREA C.1 - MECHANICAL PIPING
FLOOR PLAN AREA C.2 - MECHANICAL PIPING
MECHANICAL PLATFORM PLANS -MECHANICAL PIPING
ENLARGED MECHANICAL PLATFORM PLANS
ENLARGED MECHANICAL PLATFORM PLANS
ENLARGED MECHANICAL PLATFORM PLANS
ENLARGED BOILER ROOM AREA AND FILED HOUSE PLANS
MECHANICAL DETAILS
MECHANICAL SCHEMATICS AND DETAILS
MECHANICAL UL DETAILS
mmazzone@optimapa.com
227 WEST TRADE STREET SUITE 700
CHARLOTTE, NORTH CAROLINA 28202
ELECTRICAL NOTES AND LEGENDS
ELECTRICAL NOTES
ELECTRICAL PENETRATION DETAILS
ELECTRICAL DETAILS
ELECTRICAL DETAILS
ELECTRICAL DETAILS
ELECTRICAL DETAILS
ELECTRICAL DETAILS
PHOTOMETRIC DETAILS
ELECTRICAL DETAILS
OVERALL ELECTRICAL SITE PLAN
ENLARGED ELECTRICAL SITE PLAN
ATHLETIC FIELD LIGHTING & ELECTRICAL SITE PLAN
FLOOR PLAN - BUILDING A - LIGHTING
FLOOR PLAN - BUILDING A - LIGHTING
FLOOR PLAN - BUILDING B - LIGHTING
FLOOR PLAN - BUILDING B - LIGHTING
FLOOR PLAN - BUILDING C - LIGHTING
FLOOR PLAN - BUILDING C - LIGHTING
FLOOR PLAN - LOFT AREAS - LIGHTING
OVERALL FLOOR PLAN - CANOPY
FLOOR PLAN - BUILDING A - POWER
FLOOR PLAN - BUILDING A - POWER
FLOOR PLAN - BUILDING B - POWER
FLOOR PLAN - BUILDING B - POWER
FLOOR PLAN - BUILDING C - POWER
FLOOR PLAN - BUILDING C - POWER
ENLARGED KITCHEN ELECTRICAL AND MECHANICAL
FIELD HOUSE ELECTRICAL
ENLARGED PLAN PLATFORM ELECTRICAL
ENLARGED PLAN CLASSROOMS AND PLATFORMS ELECTRICAL
ENLARGED PLANS LIGHTING
FLOOR PLAN BUILDING A - SPECIAL SYSTEMS
FLOOR PLAN BUILDING A - SPECIAL SYSTEMS
FLOOR PLAN BUILDING B - SPECIAL SYSTEMS
FLOOR PLAN BUILDING B - SPECIAL SYSTEMS
FLOOR PLAN BUILDING C - SPECIAL SYSTEMS
FLOOR PLAN BUILDING C - SPECIAL SYSTEMS
FLOOR PLAN -BUILDING A & B -MECHANICAUELECTRICAL
FLOOR PLAN -BUILDING A & B -MECHANICAUELECTRICAL
ROOF PLAN - BUILDING A/B - MECHANICAUELECTRICAL
ROOF PLAN - BUILDING A/B - MECHANICAUELECTRICAL
POWER RISER DIAGRAM
ELECTRICAL DETAILS
PANEL SCHEDULES
PANEL SCHEDULES
PANEL SCHEDULES
PANEL SCHEDULES
PANEL SCHEDULES
LIGHTING SCHEDULE AND SEQUENCE OF OPERATIONS
LIGHTING SCHEDULE AND SEQUENCE OF OPERATIONS
LIGHTING SCHEDULE AND SEQUENCE OF OPERATIONS
TEL. 704.333.6686
A/C
ADMIN
AFF
ALT
ALUM
APPROX
ARCH
AUTO
AUX
AV
BITUM
BL
BLDG
BOS
BOT
CAB
CJ
CL
CLG
CLG HT
C O
CLR
CMU
COL
CONC
CONF
CONT
CORR
CU FT
CU YD
DEMO
DEPT
DET
DF
DIA
..
a)
.I
8
PROJECT SITE
E 2
3
AIR CONDITION(ING)
ADMINISTRATION
ABOVE FINISHED FLOOR
ALTERNATE
ALUMINUM
APPROXIMATE(LY)
ARCHITECT(URAL)
AUTOMATIC
AUXILIARY
AUDIOVISUAL
BITUMINOUS
BUILDING LINE
BUILDING
BOTTOM OF STEEL
BOTTOM
CABINET
CONTROL JOINT
CENTER LINE
CEILING
CEILING HEIGHT
C OSET
CLEAR(ANCE)
CONCRETE MASONRY UNIT
COLUMN
CONCRETE
CONFERENCE
CONTINUE. CONTINUOUS
CORRIDOR
CUBIC FOOT
CUBIC YARD
DEMOLISH
DEPARTMENT
DETAIL
DRINKING FOUNTAIN
DIAMETER
4
FAX 704.333.2926
WWW.LS3P.COM
OUT
GRAPHIC SYMBOL LEGEND
T-
BJ408
CENTERLINE
M MCAM
COLUMN GRID REFERENCE
A
- - - -
AREA REVISED
TYPICAL DIMENSION INDICATOR
9 1/2"
0'-9 1/2"
DRAWING TITLE
DRAWING LOCATION ON SHEET GRID
DRAWING NAME
A1
DOOR NUMBER
FLOOR ELEVATION
0
1/8
L
R
1 -0"
DRAWING SCALE
GLASS TYPE
SUBSYSTEM
ROOM N
UMBER
NAME
DRAWING LOCATION ON SHEET GRID
DRAWING NAME
SECTION KEYS
NTS
DRAWING SCALE
SHEET NUMBER WHERE DETAIL IS DRAWN
SHEET NUMBER WHERE DETAIL IS REFERENCED
SIM
A1
A-101
DETAIUPLAN KEY
MEMBERS OF THE AMERICAN INSTITUTE OF ARCHITECTS
DIRECTION OF SECTION
BUILDING SECTION LOCATION
ON SHEET GRID
A1
A-101
DETAIL LOCATION ON SHEET GRID
TERMINATION OF SECTION
COPYRIGHT 2014 ALL RIGHTS RESERVED
PRINTED OR ELECTRONIC DRAWINGS AND
DOCUMENTATION MAY NOT BE REPRODUCED
IN ANY FORM WITHOUT WRITTEN PERMISSION
FROM LS3P ASSOCIATES LTD.
SIM
SHEET IDENTIFIER FOR
LOCATION OF SECTION
SIM
DIRECTION OF SECTION
WALL SECTION LOCATION ON SHEET GRID
A-10
SHEET IDENTIFIER FOR
LOCATION OF DETAIL
REVISIONS:
A1
A-1 1
ENLARGED DETAIL INDICATOR
TERMINATION OF SECTION
DETAIL LOCATION ON SHEET GRID
A1
SO
I
ENO
-
| No.
Description
Date
EECR O
ELEVATION KEY
ELEVATION LOCATION ON SHEET GRID
A1
A-201
SHEET IDENTIFIER FOR
LOCATION OF ELEVATION
ABBREVIATIONS
..,
1
-
WOOD (ROUGH)
SHEET IDENTIFIER FOR
LOCAT ON OF DETAIL
VICINITY MAP
ELEVATION
OPTIMA ENGINEERING PA
WHITMIRE BALLINGTON
104 HARMON ST
LEXINGTON, SC 29072
tel: 803.787.4516
fax: 803.206.4691
KITCHEN
KITCHEN
KITCHEN
KITCHEN
MIDDLE SCHOOL
SAND, GROUT
sdaley@optimapa.com
CLOVER
CARPET AND PAD
PLASTER, CEMENT,
CHARLOTTE, NC 28203
tel:
704.338.1292
KITCHEN
K-100
K-200
K-300
K-300
MU
OPTIMA ENGINEERING PA
ENLARGED FINISH PLAN B.2
ENLARGED FINISH PLAN C.1
ENLARGED FINISH PLAN C.2
ENLARGED FNISH PLAN- ROOM PATTERNS
TYPICAL CASEWORK LEGEND & SCHEDULE
CASEWORK & EQUIPMENT PLAN- AREA A.1
CASEWORK & EQUIPMENT PLAN- AREA A.2
CASEWORK & EQUIPMENT PLAN- AREA A.3
CASEWORK & EQUIPMENT PLAN- AREA B.1
CASEWORK & EQUIPMENT PLAN- AREA B.2
CASEWORK & EQUIPMENT PLAN- AREA C.1
CASEWORK & EQUIPMENT PLAN- AREA C.2
CASEWORK ELEVATIONS
CASEWORK ELEVATIONS
CASEWORK DETAILS
CASEWORK DETAILS
CASEWORK DETAILS
SCIENCE CASEWORK DETAILS
INTERIOR SIGNAGE
PERSPECTIVE VIEWS
GYPSUM WALLBOARD
DIRECTION OF ELEVATION
DIAG
DIM
DIV
DS
E
EA
EIFS
EJ
EL
ELEC
ELEV
ENGL
EOS
EQ
EQUIP
EWC
EXIST
EXP JT
EXT
F/F
FD
FE
FEC
FF EL
FHC
FIN FLR
FLR
FOC
FOF
FOM
FOS
FOW
FT
FTG
DIAGONAL
DIMENSION
DIVISION
DOWNSPOUT
EAST
EACH
EXTERIOR INSULATION &
FINISH SYSTEM
EXPANSION JOINT
ELEVATION
ELECTRIC(AL)
ELEVATOR
ENCLOSE(D)
EDGE OF SLAB
EQUAL
EQUIPMENT
ELECTRIC WATER COOLER
EXISTING
EXPANSION JOINT
EXTERIOR
FACE TO FACE
FLOOR DRAIN
FIRE EXTINGUISHER
FIRE EXTINGUISHER CABINET
FINISH FLOOR ELEVATION
FIRE HOSE CABINET
FINISHED FLOOR
FLOOR, FILLER
FACE OF CURB
FACE OF FINISH
FACE OF MASONRY
FACE OF SLAB
FACE OF WALL
FOOT, FEET
FOOTING
FURN
GA
GALV
GC
GYP BD
GYP PLAS
HC
HD
HDWD
HDWR
HM
HORIZ
HT
HVAC
ID
INCL
INFO
INSUL
INT
JAN CLO
KIT
KO
LAB
LAM
LAU
LAV
LF
LVR
MAINT
MATL
MAX
MECH
MEZZ
MFG
FURNISH, FURNITURE
GAGE
GALVANIZED
GENERAL CONTRACTOR
GYPSUM BOARD
GYPSUM PLASTER
HANDICAP
HEAVY DUTY
HARDWOOD
HARDWARE
HOLLOW METAL
HORIZONTAL
HEIGHT
HEATING, VENTILATION & AIR
CONDITIONING
INSIDE DIAMETER
INCLUDE(D), (ING)
INFORMATION
INSULATION
INTERIOR
JANITOR CLOSET
KITCHEN
KNOCKOUT
LABORATORY
LAMINATE
LAUNDRY
LAVATORY
LINEAR FEET
LOUVER
MAINTENANCE
MATERIAL
MAXIMUM
MECHANICAL
MEZZANINE
MANUFACTURING
5
MFR
MIN
MISC
MO
MR
MTD
MTG
MTL
N
NIC
NOM
NON COMB
NTS
OC
OD
OPP
OPT
PCF
PLAM
PLF
PLYWD
PNL
PR
PREFAB
PREFIN
PRKG
PSF
PSI
PT
PVC
QTR
QTY
R
MANUFACTURER
MINIMUM
MISCELLANEOUS
MASONRY OPENING
MOISTURE RESISTANT
MOUNTED
MOUNTING
METAL
NORTH
NOT IN CONTRACT
NOMINAL
NON-COMBUSTIBLE
NOT TO SCALE
ON CENTER
OUTSIDE DIAMETER
OPPOSITE
OPTION(AL)
POUNDS PER CUBIC FEET
PLASTIC LAMINATE
POUNDS PER LINEAR FEET
PLYWOOD
PANEL
PAIR
PREFABRICATED
PREFINISH
PARKING
POUNDS PER SQUARE FOOT
POUNDS PER SQUARE INCH
PAINT, POST-TENSIONED,
PRE-TREATED
POLYVINYL CHLORIDE
(PLASTIC)
QUARTER
QUANTITY
RADIUS, RISER
RCP
RD
REF
REQD
RL
RM
RO
ROW
S
SC
SD
SECT
SF
SIM
SPEC
SPKR
SQ
SS
STD
STOR
SUSP
SYS
T
TEL
TEMP
TFF
THK
THRU
TO
TOB
TOC
TOF
TOJ
TOM
TOP
REFLECTED CEILING PLAN
ROOF DRAIN
REFRIGERATOR, REFERENCE
REQUIRED
ROOF LEADER
ROOM
ROUGH OPENING
RIGHT OF WAY
SOUTH
SOLID CORE
STORM DRAIN
SECTION
SQUARE FEET
SIMILAR
SPECIFICATION
SPEAKER
SQUARE
STAINLESS STEEL
STANDARD
STORAGE
SUSPENDED
SYSTEM
TREAD
TELEPHONE
TEMPORARY
TOP OF FINISH FLOOR
THICKNESS
THROUGH
TOP OF
TOP OF BEAM
TOP OF CONCRETE, CURB
TOP OF FOOTING
TOP OF JOIST
TOP OF MASONRY
TOP OF PARAPET
6
TOS
TOW
TRTD
TV
TYP
UL
UNO
VERT
VEST
VIF
W
W/
W/O
W/W
WC
WD
WP
WR
WT
WWF
YD
TOP OF SLAB
TOP OF WALL
TREATED
TELEVISION
TYPICAL
UNDERWRITERS
LABORATORIES
UNLESS NOTED OTHERWISE
VERTICAL
VESTIBULE
VERIFY IN FIELD
WEST, WIDE
WITH
WITHOUT
WALL TO WALL
WATER CLOSET
WOOD
WORKING POINT,
WATERPROOFING
WATER REPELLENT
WEIGHT
WELDED WIRE FABRIC
YARD
PROJECT:
9201-131360
DATE:
DRAWN BY:
OCT. 31, 2014
Author
CHECKED BY: Checker
INDEX OF
DRAWINGS
BID DOCUMENTS
VENTILATION CALCULATION (IMC TABLE 403.3)
CHILLER SCHEDULE
E -
CHILLER #1
CARRIER 30XA 250 (AIR-COOLED CHILLER)
252 TONS (MIN.); 95* F. AMBIENT; EVAPORATOR: 500 GPM, 44° F. L.W.T.,
56° F. E.W.T., 7.5 MAX. P.D., ELEC. DATA: 460V-3ø, COMPRESSORS (2):
COMPR. CIRCUIT A: 253.5 RLA, 578 LRA; COMPR. CIRCUIT B: 154.6 RLA, 382
LRA: - WYE DELTA START; FANS: 15 TOTAL, 3.0 FLA (EA); UNIT ELECTRICAL
DATA: (SINGLE POINT ELECTRICAL CONNECTION) 516 MCA, 700 MOCP; 20
AMP, 120V CIRCUIT FOR CONTROLS AND HEATERS; CHILLER SHALL BE
FURNISHED WITH: 2 COMPRESSORS WITH TWO INDEPENDENT REFRIGERANT
CIRCUITS, WYE DELTA STARTER, MICROPROCESSOR BASED CONTROL SYSTEM
TO MAINTAIN A CONSTANT LEAVING WATER TEMPERATURE OF 44° F.,
LEAD-LAG CONTROLS TO MAINTAIN EQUAL COMPRESSOR RUN TIMES, OPEN
PROTOCOL TO ALLOW COMMUNICATION WITH THE BUILDING AUTOMATION
SYSTEM, FACTORY INSTALLED WATER FLOW SWITCH, ARCHITECTURAL LOUVERED
PANELS, PROTECTIVE COIL GUARDS, 5-YEAR COMPRESSOR, PARTS, LABOR,
AND REFRIGERANT WARRANTY, MAXIMUM SOUND PRESSURE -80 DBA © 30'.
OPERATING WEIGHT = 15720 POUNDS. PROVIDE CHILLER WITH R-134A
REFRIGERANT.
FULL LOAD EFFICIENCY - 3.14 COP, 4.16 IPLV
CHILLER #2
CARRIER 30XA 250 (AIR-COOLED CHILLER)
252 TONS (MIN.); 95* F. AMBIENT; EVAPORATOR: 500 GPM, 44° F. L.W.T.,
56° F. E.W.T., 7.5 MAX. P.D., ELEC. DATA: 460V-3ø, COMPRESSORS (2):
COMPR. CIRCUIT A: 253.5 RLA, 578 LRA; COMPR. CIRCUIT B: 154.6 RLA, 382
LRA: - WYE DELTA START; FANS: 15 TOTAL, 3.0 FLA (EA); UNIT ELECTRICAL
DATA: (SINGLE POINT ELECTRICAL CONNECTION) 516 MCA, 700 MOCP; 20
AMP, 120V CIRCUlT FOR CONTROLS AND HEATERS; CHILLER SHALL BE
FURNISHED WITH:
--
OCCUPANT DENSITY
DEFAULT
ACTUAL
(#/1000 SF) (PEOPLE)
(35)
30
(35)
20
(20)
NOTE 2
(20)
30 @
(25)
30 @
(25)
30 @
5
NOTE 2
50
NOTE 2
----(100)
N/A
(10)
NOTE 2
35
NOTE 2
25
NOTE 2
20
NOTE 2
70
550
OCCUPANCY
CATEGORY
CLASSROOMS
RESOURCE ROOMS
MUSIC/THEATER/DANCE
ART ROOM
SCIENCE LABS
COMPUTER ROOMS
OFFICE/ADMIN.
CONFERENCE ROOMS
CORRIDORS
STORAGE ROOMS
GYMNASIUM
WEIGHT ROOM
STAGE (PLATFORM)
MEDIA CENTER
KITCHEN
DINING ROOM
2 COMPRESSORS WITH TWO INDEPENDENT REFRIGERANT
VENTILATION REQUIRED
PEOPLE O.A. RATE AREA O.A. RATE
(CFM/PERSON)
(CFM/SQ. FT.)
10
0.12
10
0.12
10
0.06
10
0.18
10
0.18
10
0.12
5
0.06
5
0.06
-0.06
-0.12
-0.3
20
0.06
10
0.06
10
0.12
7.5
0.12
7.5
0.18
REMARKS
AGES 9+
PER ARCH PLANS
PER ARCH PLANS
COORDINATION DRAWINGS
DRANNG NUMBER
1. ALL SHOP DRAWINGS AND COORDINATION DRAWNGS NLL BE ¾" SCALE
2. DRAWNGS WILL BE ORIGINAL DRAWNGS AND NOT BE OVERLAYS OF THE
CONTRACT/DESIGN DRAWNGS
3. COORDINATION DRAWNGS NLL BE DRAWN ON REPRODUCIBLE MATERIAL 48"x36"
4. COORDINATION DRANNGS ARE NOT SHOP DRANNGS AND ARE REQUIRED IN ADDITION TO
SHOP DRAWINGS.
5. ONCE THE COMPLETE COORDINATION DRANNGS HAVE BEEN COMPILED, THE MECHANICAL
CONTRACTOR WILL DISTRIBUTE ONE SIGNED SET TO EACH OF THE FOLLOWNG
CONTRACTORS: ELECTRICAL, PLUMBING, FIRE PROTECTION, AND GENERAL. ADDITIONAL
SETS NLL BE SENT TO THE OWNER, ARCHITECT, AND ENGINEER.
NUMBER
M-001
M-002
M-003
M-004
M-005
M-101
M-102
M-103
M-104
M-105
M-106
M-107
MECHANICAL INDEX, LEGEND, NOTES, AND SCHEDULES
MECHANICAL SCHEDULES
MECHANICAL SCHEDULES
MECHANICAL SEQUENCE OF OPERATION
MECHANICAL POINTS LIST
FLOOR PLAN AREA A.1 & A.2 - MECHANICAL
FLOOR PLAN AREA A.3 - MECHANICAL
FLOOR PLAN AREA B.1 - MECHANICAL
FLOOR PLAN AREA B.2 - MECHANICAL
FLOOR PLAN AREA C.1 - MECHANICAL
FLOOR PLAN AREA C.2 - MECHANICAL
ROOF AND FIELD HOUSE PLANS - MECHANICAL
M-201
FLOOR PLAN AREA A.1 & A.2 - MECHANICAL PIPING
M-202
M-203
M-204
M-205
M-206
M-207
M-301
M-302
M-303
M-304
M-401
M-402
FLOOR PLAN AREA A.3 - MECHANICAL PIPING
FLOOR PLAN AREA B.1 - MECHANICAL PIPING
FLOOR PLAN AREA B.2 - MECHANICAL PIPING
FLOOR PLAN AREA C.1 - MECHANICAL PIPING
FLOOR PLAN AREA C.2 - MECHANICAL PIPING
MECHANICAL PLATFORM PLANS - MECHANICAL PIPING
ENLARGED MECHANICAL PLATFORM PLANS
ENLARGED MECHANICAL PLATFORM PLANS
ENLARGED MECHANICAL PLATFORM PLANS
ENLARGED BOILER ROOM AREA AND FIELD HOUSE PLANS
MECHANICAL DETAILS
MECHANICAL SCHEMATICS AND DETAILS
M-403
MECHANICAL UL DETAILS
BT H)
BTUH)
FLOW
(GPM)
WATER
E.W.T. L.W.T.
('F)
( F)
MAX. MANUFACTURER &
P.D. MODEL NO.
B-1
2,000,000
1,700,000
85
120
160
5'
FULTON PHW-2000
B-2
2,000,000
1,700,000
85
120
160
5'
FULTON PHW-2000
NOTES:
1. SEE SPECIFICATIONS AND SEQUENCES OF OPERATION FOR ADDITIONAL
REQUIREMENTS AND CONTROLS.
2. PROVIDE EACH BOILER WITH A CONDENSATE DRAIN ACID NEUTRALIZATION KIT
(AS RECOMMENDED BY BOILER MANUFACTURER).
THE OWNER.
THE MECHANICAL CONTRACTOR SHALL COORDINATE WITH OWNER'S
COMMISSIONING AGENT AND PROVIDE ALL NECESSARY TIME, MATERIALS, AND
PROCEDURES REQUIRED FOR A FULLY COMMISSIONED PROJECT. SEE
COMMISSIONING REQUIREMENTS IN THE PROJECT MANUAL FOR FURTHER
ID.U-1.
NOMINAL
O.A.
COOl lNG CAPACITY
HFATING CAPACITY
£EM
IQ (BTUH) StiC (BTUH)
(BTUH)
H
35,400
7.5
1200
340
0.4"
33,800
25,600
FI FCTRIC AUXIl lARY HFAT
STAGFS AMP_S
1
36.2
3. PROVIDE EACH BOILER WITH A VENTLESS GAS PRESSURE REGULATOR (5 PSIG -
7" W.G.)
CHS
CHR
HWS
HWR
D
CHILLED WATER RETURN
HOT WATER SUPPLY
HOT WATER RETURN
CONDENSATE DRAIN
COLD WATER MAKE-UP
BALL VALVE
BUTTERFLY VALVE
GLOBE VALVE
CHECK VALVE
STRAINER WITH BLOWDOWN
VALVE WITH HOSE CONN.
CHR
HWS
HWR
D
CW
ALL DUCTWORK SHALL BE GALVANIZED SHEET METAL CONSTRUCTED IN
ACCORDANCE WITH THE LATEST SMACNA STANDARDS. ALL SUPPLY, RETURN
AND OUTSIDE AIR DUCTWORK SHALL BE WRAPPED WITH 2" THICK DUCT
WRAP WITH VAPOR BARRIER. INSULATION (INCLUDING FLEXIBLE DUCT
INSULATION) SHALL HAVE A MINIMUM INSTALLED R-VALUE OF 5.0.
TRANSFER DUCTS AND WHERE OTHERWISE INDICATED, DUCTWORK SHALL
INSTEAD BE LINED WITH 1" THICK FIBERGLASS DUCT LINER FOR ACOUSTICAL
PURPOSES. LINED DUCTWORK DOES NOT ALSO REQUIRE WRAP. DUCT
DIMENSIONS ON PLANS ARE INSIDE CLEAR SIZE. PROVIDE BELL MOUTH
FITTING AND WELDED WIRE MESH AT OPEN ENDED RETURN DUCTS. INSIDE
SURFACE OF LINED DUCTWORK SHALL BE SMOOTH, CLEANABLE, AND
TREATED WITH AN EPA APPROVED BIOCIDE TO RESIST FUNGAL/BACTERIAL
GROWTH. EXTERNAL DUCT INSULATION TEARS, JOINTS, PUNCTURES AND
OTHER PENETRATIONS SHALL BE SEALED WITH MASTIC - DUCT TAPE ALONE
IS NOT ACCEPTABLE.
$
ALL PIPING, DUCTS, VENTS, ETC., EXTENDING THROUGH WALLS AND ROOF
SHALL BE FLASHED AND COUNTERFLASHED IN A WATERPROOF MANNER.
6.
ALL PIPING AND DUCTWORK LOCATIONS SHALL BE COORDINATED WITH THE
WORK UNDER OTHER DIVISIONS OF THE SPECIFICATIONS, TO AVOID
INTERFERENCE.
GAGE COCK
FLOW SWITCH
M
lG
ECCENTRIC REDUCER
CONCENTRIC REDUCER
THERMOSTAT (TOP AT 4'-O" ABOVE FLOOR)
SWITCH (TOP AT 4'-O" ABOVE FLOOR)
ROOM HUMIDISTAT
(TOP AT 4'-O" ABOVE FLOOR)
BUILDING PRESSURE SENSOR
(TOP AT 4'-O" ABOVE FLOOR)
10. PROVIDE MANUFACTURER'S RECOMMENDED CLEARANCES AROUND ALL
EQUIPMENT FOR MAINTENANCE AND FILTER REMOVAL
(TOP AT 4'-O" ABOVE FLOOR)
SUPPLY AIR DIFFUSER
OR
FI FCTRICAI DATA
EU.SE
208v-1ø
4.1
5.1
60
15
50.4
VOI TAGF
208V-1ø
MANUFACTURFR
CARRIER
REFRIGERANT
WFIGHT
FB4CNF036
144 LBS.
MATCHING
HP_E
OUTDOOR UNIT
R-410A
11P-1
RETURN AIR GRILLE WITH SOUND
ATTENUATION (SEE DETAIL)
DOUBLE LINE DUCTWORK
0
SINGLE LINE DUCTWORK
+
[
1.
2.
+
FIRE DAMPER (3 HR RATED) WITH
+
+
2Ox14
8"ø
__
ALTERNATE #4 - OWNER PREFERRED CONTROLS - AUTOMATED LOGIC. PROVIDE
AN ALTERNATE PRICE FOR DDC CONTROLS BY AUTOMATED LOGIC BY HARRIS
INTEGRATED SOLUTIONS.
SEE ARCHITECTURAL SPECIFICATIONS (SECTION 012300) AND BID FORM FOR
--
BAROMETRIC DAMPER WITH COUNTERWEIGHT
--
DUCT MOUNTED HUMIDITY SENSOR
14. ANY DEVICE REQUIRING A THERMOSTAT FOR CONTROL SHALL BE FURNISHED
WITH A THERMOSTAT WHETHER INDICATED ON THE DRAWINGS OR NOT.
DETAILS.
19. KITCHEN HOOD EXHAUST DUCT SHALL BE 16 GAUGE CARBON STEEL. ALL
JOINTS AND SEAMS SHALL BE CONSTRUCTED WITH A CONTINUOUS LIQUIDTIGHT EXTERNAL WELD. ALL DUCTWORK SHALL SLOPE A MINIMUM OF ¼
INCH PER FOOT TOWARD HOOD. PROVIDE CLEANOUTS AT EVERY CHANGE OF
D C O
E EX UST DUCT AND AT 20 -0" (MINIMUM) INTERVALS.
HEAT PUMP SCHEDULE
NOMINAl
B -
COOl ING CAPACITY
TONNAGE E (BEH) SB£ (BEH)
3
33,800
25,600
BP-1
FFFICIFNCY
HFATING CAPACITY
EER SEER ER
10.5 13.0 --
(BEH)
35,400
EFFICIENCY
COP
3.5
COMPRFSSOR
HSPF
7.8
LBA
88.0
ELA
11.7
Eali
ELA
0.9
FI FCTRICAI DATA
MCA
15.5
EU.SE
25
VOLTAGE
208V-3ø
OPERATING
MANUFACTURFR
MATCHING
WElGHT
211 LBS
CARRIFR MODFI
25HBB336
INDOOR UNIT
1D.U-1.
NCE OF
E L CA
U OR
HAVING UR D TIO
CONCEALING KITCHEN HOOD EXHAUST DUCTWORK.
P OR T
20. DISHWASHER EXHAUST DUCT SHALL BE STAINLESS STEEL. ALL JOINTS AND
SEAMS SHALL HAVE A LIQUID TIGHT CONTINUOUS EXTERNAL WELD. EXHAUST
DUCT SHALL SLOPE DOWN IN DIRECTION OF HOOD A MINIMUM OF 1" PER
FOOT.
NOTES:
1.
COOLING CAPACITY @ 95* AMBIENT
2.
3.
ALL UNITS SHALL BE U.L LISTED AND ASHRAE 90.1 COMPLIANT
HEAT PUMP SUPPLEMENTARY ELECTRIC RESISTANCE HEAT SHALL BE PROVIDED WTH
CONTROLS TO PREVENT OPERATION WHEN THE REVERSE CYCLE HEAT CAN MEET
HEATING LOAD. SUPPLEMENTAL ELECTRIC HEAT SHALL BE ALLOWED TO OPERATE
DURING HEAT PUMP DEFROST CYCLE. SUPPLEMENTAL ELECTRIC HEAT SHALL BE
LOCKED OUT WHEN THE OUTDOOR TEMPERATURE IS BETWEEN 35"F AND 40'F AND
THE INDOOR TEMPERATURE SETPOINT IS INCREASED.
MOUNT UNITS ON A 4" THICK CONCRETE PAD AND PROVIDE MANUFACTURER'S
RECOMMENDED CLEARANCES AROUND UNITS.
4.
21. FUME HOOD, PREP ROOM, AND CHEMICAL STORAGE EXHAUST DUCTWORK
SHALL BE CONSTRUCTED OF APPROVED G90 GALVANIZED SHEET STEEL WITH
A MINIMUM NOMINAL THICKNESS OF 18 GAUGE. DUCTWORK AND EXHAUST
SYSTEM SHALL MEET THE REQUIREMENTS OF NCMC SECTION 510.
22. MINIMUM GAS PIPING SIZE SHALL BE ¾".
23. GAS PIPING AND FITTINGS SHALL BE BLACK STEEL, SCHEDULE 40, IN
ACCORDANCE WITH ASTM SPECIFICATION A 106, WITH 150 PSI BLACK
MALLEABLE IRON FITTINGS IN ACCORDANCE WITH ASTM SPECIFICATION A 47,
GRADE 32510, AND ASA SPECIFICATION B16.3, 125 LB.
24. GAS PIPING SHALL BE INSTALLED TO THE REQUIREMENTS OF THE STATE
BUILDING CODE AND NFPA STANDARD NO. 54. ALL PIPING TO BE
SUPPORTED BY CLEVIS HANGERS WITH GALVANIZED ROD A MAXIMUM OF 8'
ON CENTER. PIPING SHALL BE SUPPORTED BY ROD HANGERS IN THE PIPE
RUN 12" OR LESS IN LENGTH FROM THE TOP OF THE PIPE TO THE
ELECTRIC DUCT HEATER SCHEDULE
SYMROI
I OCATION
£EM
EDH-1
KITCHEN OFFICES
215
Bl.SE
44
K.E.
S.IEP_S
3.0
1
SUPPORTING STRUCTURE PER THE STATE BUILDING CODE AND ASCE 7.
VOLTAGE
460V-3ø
MAX. P.D.
0.25-
25. GAS PIPING SHALL BE TESTED IN ACCORDANCE WITH THE PROCEDURES
DESCRIBED IN NFPA NO 54. ANY OTHER TEST AS REQUIRED BY THE LOCAL
GAS INSPECTION DEPARTMENT OR GAS COMPANY SHALL ALSO BE
PERFORMED.
26. PAINT ALL GAS PIPING WITH TWO COATS OF YELLOW ENAMEL AND STENCIL
"2-PSI GAS" ON PIPE AT 5'-0" CENTERS.
A -
27. GAS VALVES SHALL BE MIN. 125 PSI RATED, NON-LUBRICATED PLUG TYPE
WITH BRONZE BODY AND BRONZE PLUG.
28. GAS PIPING BELOW GRADE SHALL BE BLACK STEEL, SCHEDULE 40, IN
ACCORDANCE WITH ASTM SPECIFICATION A 53 OR A 120 WITH FORGED
STEEL WELDING TYPE FITTINGS IN ACCORDANCE WITH ASTM SPECIFICATION A
234 WITH AWWA C105 POLYETHYLENE JACKET OR DOUBLE LAYER, HALF
LAPPED 10 MIL POLYETHYLENE TAPE. JOINTS SHALL BE ANSI B31.1, ANSI
B31.2, ANSI B31.9, ASME SEC 1 WELDED.
NOTES:
1. ALL HEATERS SHALL BE OPEN-COIL, SLIP-IN TYPE HEATERS.
2. ALL HEATERS SHALL HAVE STEP CONTROL WTH NUMBER OF STEPS
AS INDICATED ABOVE.
3. PROVIDE HEATERS NTH THE FOLLOWNG BUILT-IN AND PRE-NRED COMPONENTS:
DISCONNECTING TYPE MAGNETIC CONTACTORS, FUSES PER N.E.C., CONTROL VOLTAGE
TRANSFORMER, AIR FLOW SNTCH.
29. ALL CHILLED WATER AND HOT WATER PIPING 1" AND LESS SHALL BE
SCHEDULE-0 BLACK STEEL OR HARD-DRAWN TYPE-L COPPER PIPE AND
FITTINGS. ALL CHILLED WATER AND HOT WATER PIPING GREATER THAN 1"
SHALL BE SCHEDULE-40 BLACK STEEL.
WWW.LS3P.COM
20"x 14" RECTANGULAR DUCT
8" DIAMETER ROUND DUCT
SMOKE DETECTOR (INSTALLER SHALL PROVIDE
STATIC PRESSURE READINGS AT ALL INSTALLATIONS)
MOTORIZED DAMPER
--
18. DRYER VENT WALL CAPS SHALL BE PROVIDED WITH A BACKDRAFT DAMPER.
DRYER VENT SHALL NOT EXCEED A TOTAL EQUIVALENT LENGTH OF 35'-0"
WITH A 2.5' DEDUCTION FOR EACH 45' BEND AND A 5' DEDUCTION FOR
EACH 90' BEND.
227 WEST TRADE STREET
SUITE 700
CHARLOTTE, NORTH CAROLINA 28202
TEL. 704.333.6686
FAX 704.333.2926
MANUAL VOLUME DAMPER
--
JACKET AND SEALED WATERTIGHT.
17. MECHANICAL CONTRACTOR SHALL LOCATE EXHAUST FANS, OUTLETS, AND
GAS FLUES A MINIMUM OF 15'-0" FROM ANY OUTSIDE AIR INTAKE.
ACCESS DOOR (SEE DETAIL)
MVD
unsus
OPTIMA
ENGINEERING
No.
0710
0F
HHnD
AIRFLOW MONITORING STATION
DIFFERENTIAL PRESSURE SENSOR
(FOR PUMP CONTROL)
UNDER-CUT DOOR (BY G.C.)
O.A.
OUTSIDE AIR
2
VARIABLE FREQUENCY DRIVE WITH DISCONNECT
SWITCH ABOVE (TOP AT 6'-6" MAX A.F.F.)
16. MECHANICAL CONTRACTOR SHALL VERIFY LOCATION OF ROOF PENETRATIONS
FOR RELIEF HOODS AND OUTSIDE AIR HOODS WITH ARCHITECT & OWNER
PRIOR TO INSTALLATION.
ALTERNATE #3 - OWNER PREFERRED EQUIPMENT - CARRIER. PROVIDE AN
ALTERNATE PRICE FOR ALL DX ROOFTOP UNITS, SPLIT SYSTEMS, CHILLERS, AIR
HANDLING UNITS, AND TERMINAL UNITS BY CARRIER.
ENGAGE DESIGN TRAMSRORM
FD3
15. LOCATE THE TOP OF ALL THERMOSTATS AND SWITCHES 4'-0" ABOVE FINISH
FLOOR. COORDINATE EXACT THERMOSTAT LOCATION WITH OWNER PRIOR TO
INSTALLATION. ANY DEVICE ON A PERIMETER WALL SHALL BE MOUNTED ON
A FOAM-FILLED ELECTRICAL BOX, WITH ALL GAPS BETWEEN BOX AND WALL
SEALED TO PREVENT INFILTRATION.
COOLING CAPACITY BASED ON 80*/67' ENTERING AIR.
PROVIDE UNITS WITH: DDC THERMOSTAT, 1" THICK DISPOSABLE FILTER (MERV 8 MINIMUM), FIELD INSTALLED HEATER,
U.L LABEL, SINGLE POINT ELECTRICAL CONNECTION, 1-INCH INSULATION.
FIRE DAMPER (1½ HR RATED) WITH
ACCESS DOOR (SEE DETAIL)
FD
DP
NOTES:
-
EXHAUST AIR GRILLE
CONDENSATE DRAINS SHALL BE INSULATED WITH ½" THICK ARMAFLEX
INSULATION. MINIMUM DRAIN SIZE SHALL BE ¾".
MCA EU.SE AMP_S
Phone: 704-338-1292 042
www.optimapa.com
North Carolina License Number C-0914
RETURN AIR GRILLE
FITTINGS. DRAINS FROM AIR HANDLING UNITS SHALL BE TRAPPED.
FAN MOTOR
1927 South Tryon St., Suite 300, Charlotte NC 28203
DUCT MOUNTED STATIC PRESSURE SENSOR
12. CONDENSATE DRAIN PIPING SHALL BE TYPE 'L' HARD DRAWN COPPER AND
ELA
engineering
CARBON MONOXIDE SENSOR
11. PROVIDE TWO COPIES OF INSTALLATION, OPERATION, AND MAINTENANCE
MANUALS TO THE OWNER WITHIN 15 CALENDAR DAYS OF ACCEPTANCE OF
THE SYSTEM.
VOI TAGF
imo
CO2 SENSOR (TOP AT 4'-O" ABOVE FLOOR)
(SEE SEQUENCE OF OPERABON)
REPORT SHALL BE PROVIDED AT NO ADDITIONAL COST. TEST AND
BALANCE REPORT TO BE COMPLETED BY AN INDEPENDENT, CERTIFIED NEBB
OR AABC TEST AND BALANCE CONTRACTOR.
SUBSTANTIAL COMPLETION.
ExceNm!cc
CLOVER
REPLACEMENT
MIDDLE SCHOOL
PRESSURE GAGE & COCK
(AT ENGINEER'S OR Cx AGENT'S REQUEST) AFTER REVIEW OF THE INITIAL
9. PROVIDE A ONE YEAR WARRANTY FOR ALL WORK PERFORMED BEGINNING AT
Each ChHci. Eoch Day
THERMOMETER
7. THE MECHANICAL CONTRACTOR SHALL BALANCE ALL MECHANICAL SYSTEMS
TO THE PERFORMANCE SPECIFICATIONS INDICATED ON PLANS AND PROVIDE
THE ENGINEER WITH THREE COPIES OF A COMPLETE TEST AND BALANCE
REPORT. THE REPORT IS TO BE ISSUED A MINIMUM OF TWO WEEKS PRIOR
TO SUBSTANTIAL COMPLETION. THE TEST AND BALANCE REPORT WILL BE
SUBJECT TO REVIEW AND APPROVAL BY THE ENGINEER AND COMMISSIONING
AGENT. ANY ADDITIONAL TESTING, ADJUSTING AND BALANCING REQUIRED
8. UPON PROJECT COMPLETION, THE MECHANICAL CONTRACTOR IS
RESPONSIBLE FOR PROVIDING THE OWNER INSTALLATION INFORMATION
INCLUDING FULL SUBMITTALS AND O&M MANUALS FOR EACH PIECE OF
EQUIPMENT INCLUDING ALL SELECTED OPTIONS, THE NAME AND ADDRESS OF
AT LEAST ONE SERVICE AGENCY, FULL CONTROL SYSTEM O&M AND
CALIBRATION INFORMATION INCLUDING WIRING DIAGRAMS, SCHEMATICS, FULL
SEQUENCE OF OPERATION, AND PROGRAMMED SETPOINTS.
CLOVER SCHOOL DISTRICT
UNION
ALL DUCTWORK SHALL BE SEALED FOR THE REQUIREMENTS OF THE
INTERNATIONAL MECHANICAL CODE. SEAL MEDIUM PRESSURE SUPPLY
DUCTWORK FOR POSITIVE 3" PRESSURE CLASS, SMACNA SEAL CLASS A,
SMACNA LEAKAGE CLASS 12. SEAL LOW PRESSURE SUPPLY, RETURN,
5.
CS B
BALANCING VALVE
B&G CIRCUIT SETTER
4. PROVIDE DISCONNECT SWITCH WITH EACH BOILER.
INFORMATION.
RM
NI
AI
MA
N%
CHILLED WATER SUPPLY
ÞK
De(
IN
CLOVERSCHOOL
DISTRICT TWO
ABBR.
CHS
CW-
13. ALL REFRIGERANT PIPE SHALL BE NITROGENIZED ACR COPPER TUBE. SIZE,
INSULATE, AND INSTALL REFRIGERANT PIPING PER MANUFACTURER'S
RECOMMENDATIONS. REFRIGERANT PIPING SHALL BE INSULATED PER THE
MFG. RECOMMENDATIONS, WITH A MINIMUM INSULATIN OF ¾" THICK
ARMAFLEX. EXTERIOR PIPING SHALL BE COVERED WITH AN ALUMINUM
TONNAGE
3
ALL COST ASSOCIATED WITH SUBSTITUTED EQUIPMENT TO COMPLY WITH
BASIS OF DESIGN, INCLUDING PROVIDING MAINTENANCE ACCESS, CLEARANCE,
PIPING, SHEET METAL, ELECTRICAL, REPLACEMENT OF OTHER SYSTEM
COMPONENTS, BUILDING ALTERATIONS, ETC., SHALL BE INCLUDED IN THE
ORIGINAL BASE BID. NO ADDITIONAL COST ASSOCIATED WITH SUBSTITUTED
EQUIPMENT WILL BE APPROVED DURING CONSTRUCTION AND ALL COST WILL
BE THE RESPONSIBILITY OF THE MECHANICAL CONTRACTOR. THIS INCLUDES
ANY MODIFICATIONS TO ANY ASSOCIATED MECHANICAL, PLUMBING, OR
ELECTRICAL SYSTEMS REQUIRED BY THIS SPECIFIC MANUFACTURER'S
INSTALLATION INSTRUCTIONS.
DESCRIPTION
[
INDOOR UNIT SCHEDULE
THIS PROJECT INCLUDES A THIRD PARTY COMMISSIONING AGENT CONTRACTED BY
SYMBOL
DO NOT SCALE DRAWINGS. SEE ARCHITECTURAL DRAWINGS AND REFLECTED
CEILING PLANS FOR EXACT LOCATION OF DOORS, WINDOWS, CEILING
DIFFUSERS, ETC.
PRESSURE CLASS, SMACNA SEAL CLASS A, SMACNA LEAKAGE CLASS 12.
CONDENSING BOILER SCHEDULE
DRAWNG NAME
MECHANICAL LEGEND
OUTSIDE AIR, AND EXHAUST DUCTWORK FOR POSITIVE/NEGATIVE 2"
NOTE:
ALL COST ASSOCIATED WITH SUBSTITUTED EQUIPMENT TO COMPLY WITH BASIS
OF DESIGN, INCLUDING PROVIDING MAINTENANCE ACCESS, CLEARANCE, PIPING,
SHEET METAL, ELECTRICAL, REPLACEMENT OF OTHER SYSTEM COMPONENTS,
BUILDING ALTERATIONS, ETC., SHALL BE INCLUDED IN THE ORIGINAL BASE BID.
NO ADDITIONAL COST ASSOCIATED WITH SUBSTITUTED EQUIPMENT WILL BE
APPROVED DURING CONSTRUCTION AND ALL COST WILL BE THE RESPONSIBILITY
OF THE MECHANICAL CONTRACTOR.
C -
COMMISSIONING NOTE
3.
(*) - SEE MECHANICAL ALTERNATES SECTION, THIS PAGE
MECHANICAL DRAWING INDEX
THE MECHANICAL CONTRACTOR SHALL ORGANIZE COORDINATION MEETINGS TO DEVELOP A
SET OF DRANNGS NTH ALL CONTRACTORS (ELECTRICAL, MECHANICAL, PLUMBING, FIRE
PROTECTION, AND GENERAL CONTRACTOR). THE MECHANICAL CONTRACTOR WLL HAVE THE
LEAD RESPONSIBILITY FOR THE COORDINATION DRAWNGS. THE MECHANICAL CONTRACTOR
SHALL PRODUCE THE ORIGINAL DRAWINGS AND FORWARD THE DRANNGS TO EACH OF THE
OTHER CONTRACTORS FOR THEM TO ADD THEIR SYSTEMS TO THIS SET OF COORDINATION
DRAWNGS. THE CONTRACTORS WILL DEVELOP THE DRAWNGS IN THIS ORDER: MECHANICAL,
FIRE PROTECTION, PLUMBING, ELECTRICAL, AND GENERAL. THIS SHALL ALSO BE THE ORDER
OF PRECEDENCE FOR INSTALLATION OF SYSTEMS. ANY RELOCATION OF SYSTEM ROUTINGS
NLL BE FOUND IN THE COORDINATION PHASE AND NOTICED BY EACH OF THE CONTRACTORS.
THESE DRAWNGS, WHEN COMPLETED, SHALL BE SIGNED OFF BY ALL OF THE ABOVE LISTED
PARTIES. DRAWINGS SHALL BE COMPLETED PRIOR TO FABRICATION AND INSTALLATION OF
DUCTWORK AND PIPING SYSTEMS, OR PURCHASE OF EQUIPMENT. THE FOLLOWING ITEMS
REPRESENT THE MINIMUM REQUIREMENTS FOR SHOP DRANNGS AND COORDINATION DRANNGS:
__
2.
4.
NOTES:
1. PROVIDE PHASE LOSS/BROWNOUT PROTECTION.
2. PROVIDE LOW AND HIGH-PRESSURE SWITCHES, NOT SIMPLY A LOSS OF
CHARGE SWITCH.
3. PROVIDE OIL PROTECTION FOR SEMI-HERMETIC COMPRESSORS.
4. ALL UNITS SHALL HAVE STANDARD 24-VOLT CONTROL CIRCUIT OPERATION
WITH CONTROL SYSTEM WITHOUT ADDITIONAL INTERFACES OR GATEWAYS,
COORDINATE WITH CONTROLS CONTRACTOR.
D -
AS INDICATED IN THE SPECIFICATIONS, PRIOR APPROVAL IS REQUIRED FOR ALL
MANUFACTURERS NOT LISTED.
CONDENSING BOILERS: AERCO, FULTON, LAARS, LOCHINVAR, RAYPACK, R.B.I., PATTERSON
KELLY
PUMPS & HYDRONIC EQUIPMENT: ARMSTRONG, BELL & GOSSETT, TACO, PEERLESS PUMP
(*) AIR-COOl FD CHil I FRS: CARRIER, TRANE, YORK, McQUAY
(*) MODULAR AIR HANDLING UNITS: CARRIER, TRANE, YORK, McQUAY
VARIABLE FREQUENCY DRIVES: ABB, DANFOSS GRAHAM, CUTLER HAMMER, JOHNSON CONTROLS
KITCHEN HOODS: CAPTIVE-AIRE, GREENHECK, HALTON
ENERGY RECOVERY UNITS: ANNEXAIRE, ENGINEERED AIR, MUNTERS, INNOVENT, VENTROL
(*) DUCTED SPLIT SYSTEMS & DX ROOFTOP UNITS: CARRIER, TRANE, YORK
1. EXHAUST REQUIREMENTS: TOLETS - 75 CFM PER FLUSHING FlXTURE
LOCKER ROOMS - 0.5 CFM/SF
JANITOR'S CLOSET - 1.0 CFM/SF
SCIENCE LABS - 1.0 CFM/SF
2. DEFAULT OCCUPANT DENSITY IS USED WHEN ACTUAL OCCUPANT DENSITY IS NOT KNOWN.
3. ALL AREAS ARE MULTIPLE ZONE RECIRCULATING SYSTEMS PER 6.2.5 NTH VENTILATION
REQUIREMENTS ARE BASED ON A ZONE AIR DISTRIBUTION EFFECTIVENESS OF 1.0 FOR COOLING
AND O.8 FOR HEATING.
SYSTEM, FACTORY INSTALLED WATER FLOW SWITCH, ARCHITECTURAL LOUVERED
PANELS, PROTECTIVE COIL GUARDS, 5-YEAR COMPRESSOR, PARTS, LABOR,
AND REFRIGERANT WARRANTY, MAXIMUM SOUND PRESSURE -80 DBA © 30'.
OPERATING WEIGHT = 15720 POUNDS. PROVIDE CHILLER WITH R-134A
REFRIGERANT.
FULL LOAD EFFICIENCY -3.14 COP, 4.16 IPLV
1.
EaliS; COOK, GREENHECK, PENN
AIR DISTRIBUTION: CARNES, METAL*AIRE, NAILOR, PRICE, TITUS, TUTTLE & BAILEY, KRUEGER
FIRF DAMPFRS: AIR BALANCE INC., GREENHECK, NAILOR, RUSKIN, POTTORFF, PREFCO, SAFE-AIRE
LOUVERS: REMOVED (ALL LOUVERS ARE BY THE G.C.)
DUCTI FSS SPI IT SYSTFMS: DAIKIN, MITSUBISHI, PANASONIC, LG
(*) VAV TFRMINAl UNITS: TRANE, CARRIER, ENVIRO-TEC, NAILOR, PRICE, TITUS, KRUEGER
FI FCTRIC HFATFRS: REZNOR, MARKEL, MODINE, INDEECO, REDD-l
SPIRAL DUCTWORK: EASTERN SHEET METAL, LINDAB, UNITED MCGILL, HAMLIN
(*) DDC CONTROLS: AUTOMATED LOGIC, SCHNEIDER ELECTRIC, HOFFMAN BUILDING
TECHNOLOGIES
NOTFS:
PROTOCOL TO ALLOW COMMUNICATION WITH THE BUILDING AUTOMATION
LISTING OF MANUFACTURER'S NAME DOES NOT GUARANTEE APPROVAL. ALL
EQUIPMENT MUST MEET OR EXCEED QUALITY AND CAPACITIES OF SPECIFIED
EQUIPMENT. FINAL APPROVAL WILL BE BASED ON EQUIPMENT SUBMITTALS.
ANY MANUFACTURER NOT LISTED BUT WISHING TO BID THIS PROJECT SHALL
SUBMIT A WRITTEN REQUEST A MINIMUM OF 7 DAYS PRIOR TO BID DATE OR
@ - ASSUMES ROOM IS OCCUPIED BY LARGEST CLASSROOM SIZE.
CIRCUITS, WYE DELTA STARTER, MICROPROCESSOR BASED CONTROL SYSTEM
TO MAINTAIN A CONSTANT LEAVING WATER TEMPERATURE OF 44° F.,
LEAD-LAG CONTROLS TO MAINTAIN EQUAL COMPRESSOR RUN TIMES, OPEN
MECHANICAL 523NERAL
NOTES
EQUIVALENT MANUFACTURERS LISTING
7
10/31M
MEMBERS OF THE AMERICAN INSTITUTE OF ARCHITECTS
29. CHILLED WATER PIPING SHALL BE INSULATED WITH 1½" THICK PHENOLIC
CLOSED CELL, ASTM C1126 RIGID FOAM, 2.2 LBS. NOMINAL DENSITY, CFC
FREE; ASTM C518, K-VALUE OF 0.13 AT 75° F. HOT WATER PIPING SHALL
BE INSULATED WITH 1½" THICK FIBERGLASS INSULATION WITH A DENSITY OF
1.5 LB PER CUBIC FOOT.
COPYRIGHT 2014 ALL RIGHTS RESERVED
PRINTED OR ELECTRONIC DRAWINGS AND
DOCUMENTATION MAY NOT BE REPRODUCED
IN ANY FORM WITHOUT WRITTEN PERMISSION
FROM LS3P ASSOCIATES LTD.
INSULATION SHALL HAVE A FACTORY APPLIED
PRESSURIZED VAPOR BARRIER JACKET WITH PRESSURE SENSITIVE ADHESIVE
SELF-SEALING LAP. ALL FITTINGS SHALL HAVE PVC FITTING COVERS. ALL
PIPING OUTSIDE SHALL HAVE A BITUMINOUS COATING ALUMINUM JACKET
AND PVC FITTING COVERS.
30. ALL CHILLED WATER AND HOT WATER PIPING SHALL PITCH DOWN IN
DIRECTION OF FLOW WITH MANUAL AIR VENTS AT ALL HIGH POINTS AND ½"
DRAIN VALVES AT ALL LOW POINTS.
31. PROVIDE UNIONS, FLANGES OR COUPLINGS AT CONNECTION TO ALL VALVES
AND EQUIPMENT. DO NOT USE DIRECT WELDED OR THREADED CONNECTIONS
TO VALVES, EQUIPMENT OR OTHER APPARATUS.
REVISIONS:
_
No.
Description
PROJECT:
9201-131360
DATE:
OCT.31,2014
DRAWN BY:
SRD
Date
32. PROVIDE NON-CONDUCTING DIELECTRIC UNIONS WHENEVER CONNECTING
DISSIMILAR METALS.
33. EQUIPMENT OPERATED DURING CONSTRUCTION SHALL USE TEMPORARY
FILTERED MEDIA ON EQUIPMENT AND DUCT OPENINGS TO PREVENT
CONSTRUCTION DEBRIS FROM ENTERING COILS, DUCTWORK SYSTEMS, AIR
TERMINALS ETC. AT COMPLETION OF CONSTRUCTION, MECHANICAL
CONTRACTOR SHALL CLEAN ALL SYSTEMS WITH ALL CONTROL DEVICES WIDE
OPEN AND REMOVE ANY REMAINING DEBRIS PRIOR TO TEST AND
BALANCING. MECHANICAL CONTRACTOR SHALL REPLACE ALL FILTRATION
WITH NEW PERMANENT FILTERS AT COMPLETION OF CONSTRUCTION. ANY
DUCTWORK, AIR TERMINALS, AND/OR OTHER EQUIPMENT UPSTREAM OF
FILTRATION SHALL BE CLEANED THOROUGHLY OF CONSTRUCTION DEBRIS
BEFORE HANDING OVER TO OWNER.
34. THE MECHANICAL CONTRACTOR SHALL BE RESPONSIBLE FOR PROVIDING
RESTRAINTS TO RESIST THE EARTHQUAKE EFFECTS ON THE MECHANICAL
SYSTEMS. THE REQUIREMENTS FOR THOSE RESTRAINTS ARE FOUND IN THE
INTERNATIONAL BUILDING CODE AND ASCE 7. THE ANCHORAGE OF THE
MECHANICAL SYSTEMS SHALL COMPLY WITH THE REQUIREMENTS OF THE
INTERNATIONAL BUILDING CODE AND ASCE 7.
CHECKED BY: RVA
35. CHILLED WATER PIPING BELOW GRADE SHALL BE FACTORY PREINSULATED
INSULTEK 250 STEEL AS MANUFACTURED BY PREINSULATED PIPING
SYSTEMS, INC. (OR EQUAL). CARRIER PIPE SHALL BE SCHEDULE 40 ASTM
A53 GRADE B BEVELED FOR WELDING. INSULATION SHALL BE FOAMED
IN-PLACE CLOSED CELL POLYURETHANE FOAM COMPLETELY FILLING THE
ANNULUS BETWEEN THE CARRIER PIPE AND JACKETING. OUTER CASING
SHALL BE EXTRUDED WHITE PVC TYPE 1, GRADE 1, CLASS 12454-B PER
ASTM D 1784.
36. ALL EQUIPMENT LOCATED IN MECHANICAL EQUIPMENT ROOMS SHALL BE
LOCATED ON A 4" THICK CONCRETE PAD INSTALLED BY THE GENERAL
CONTRACTOR, MECHANICAL CONTRACTOR SHALL COORDINATE PAD
LOCATIONS WITH THE GENERAL CONTRACTOR.
37. COMMERCIAL DRYER EXHAUST DUCTWORK SHALL BE CONSTRUCTED OF
GALVANIZED SHEET METAL NOT LESS THAN O.0195 INCHES THICK.
EXHAUST DUCT SHALL BE ASSEMBLED WITH SMOOTH INTERIOR SURFACE SO
THAT THE JOINTS DO NOT PERMIT THE ACCUMULATION OF LINT, DO NOT
USE SHEET METAL SCREWS AT JOINTS. ALL 90° TURN SHALL HAVE LONG
RADIUS ELBOWS. ALL DUCTWORK SHALL BE INSTALLED PER THE DRYER
MANUFACTURER'S RECOMMENDATIONS.
MECHANICAL
LEGEND, INDEX,
- NOTES, AND
SCHEDULES
M-001
OPTIMA # 13-0238
1 OF 26
SOLUTIONS THROUGH LISTENING
THIS DRAWING IS AN INSTRUMENT OF SERVICE. THE DRAWING AND THE INFORMATION THEREON IS THE PROPERTY OF OPTIMA ENGINEERING, P.A. ANY REPRODUCTION, ALTERATION, OR USE FOR OTHER THAN THE INTENDED PROJECT, WITHOUT THE WRITTEN CONSENT CF OPTIMA ENGINEERING, P.A. IS EXPRESSLY FORBIDDEN. COPYRIGHT ©OPTIMA ENGINEERING P.A. 2014, ALL RIGHTS RESERVED.
1
2
3
4
5
I
e
BID DOCUMENTS
ROOFTOP UNIT SCHEDULE (DX COOLING WITH GAS HEAT)
NOMINAl
RTU-1
4000
O.A.
TONNAGE E
10
800
COOllNG CAPACITY
0.5"
E (BTUH)
124,100
SjiG (BTUH)
96,200
EFFICIENCY
SEER
N/A
EER
11.10
ENERGY RECOVERY VENTILATOR SCHEDULE
HEATING CAPACITY
JP..LY
11.8
INPUT (BTUH)
224,000 / 180,000
EFFICIENCY
OUTPUT (RTUH)
183,600
AB).E
81%
COMPRESSOR (EA)
jiQ,
2
ELâ
7.7
DF.M
],,BA
52.0
Q.IY.,.
2
M
0.8
]M
COMB. FAN
PWR EXH
M
4.4
M
0.30
M
--
POWFR SUPPI Y
jdCA
26.3
MD..C.P_
30
OPERATING MANUFACTURER
VOLTAGE WEIGHT
460V-3ø 1240 LBS
SUPPLY AIR
CARRIER MODEL
48TCED12
ERV-1
NOTES:
1. COOLING CAPACITIES BASED ON 95© AMBIENT, 80/67 ENTERING AIR.
2. PROVIDE ALL UNITS NTH: ROOF CURB, DDC THERMOSTAT (SEE NOTE 5), 2" THROWAWAY FILTERS (MERV 8 MINIMUM), ENTHALPY ECONOMlZER,
INTERMITTENT PILOT IGNITION, CONDENSER COlL HAlL GUARDS, PHASE LOSS/BROWNOUT PROTECTION, HIGH AND LOW PRESSURE SNTCHES (NOT
A LOSS OF CHARGE SNTCH), AND HINGED ACCESS DOORS WITH "TOOL-LESS" ENTRY.
3. ALL UNITS SHALL BE AGA CERTIFIED, U.L. LABELED, AND ASHRAE 90.1 COMPLIANT.
4. PROVIDE EACH UNIT NTH A IONIZATION TYPE SMOKE DETECTOR, INSTALLED IN THE RETURN DUCT WIRED TO SHUT DOWN THE UNIT UPON
ACTIVATION. SMOKE DETECTOR SHALL BE SUPPLIED, WIRED FOR INTERFACE WITH FIRE ALARM SYSTEM AND UNIT SHUTDOWN BY THE
ELECTRICAL CONTRACTOR. SMOKE DETECTOR SHALL BE INSTALLED IN THE RETURN DUCT BY THE MECHANICAL CONTRACTOR.
5.
M
4000
MECH PLATFORM C220
EXHAUST AIR
ESP_ FAN HP
0.75"
5
H
4000
CLOVER SCHOOL
POWER
ESP_ FAN HP
0.75"
5
M.CA MD..C.P_
17.9
25
SUMMFR SljPPI Y AIR CONDITIONS (* F.)
VOLTAGE DRY BULB WET BULB SPEC. HUM.
460V-3ø
79.4
66.8
78
WNTFR SlJPPI Y AIR CONDITIONS (* F.)
ENTHAPLY DRY BULB WET BULB SPEC. HUM.
31.3
58.6
47.8
32
MANljFACTljRFR
ENTHAPLY
19.0
WEIGHT
1206 LBS
GRFFNHFCK MODFl
ERV-45-30L
-
NOTES:
1.
2.
3.
4.
5.
ALL UNITS SHALL HAVE STANDARD 24-VOLT CONTROL CIRCUIT OPERATION WTH CONTROL SYSTEM WTHOUT ADDITIONAL INTERFACES OR GATEWAYS, COORDINATE WTH CONTROLS CONTRACTOR.
CLOVER SCHOOL DISTRICT
ALL TEMPERATURES ARE MEASURED IN DEGREES FAHRENHEIT, SPECIFIC HUMIDITY IS MEASURED IN GRAINS PER POUND DRY AIR, AND ENTHALPY IS MEASURED IN
BTU'S PER POUND.
OUTDOOR DESIGN CONDITIONS: SUMMER: 94* F. D.B., 77* F. W.B. NNTER: 21* F. D.B.
INDOOR DESIGN CONDITIONS: SUMMER: 75© F. D.B., 50% RELATIVE HUMIDITY. WINTER: 72' F. D.B., 35% RELATIVE HUMIDITY.
FURNISH UNITS NTH: HINGED ACCESS DOORS, ENTHALPY SENSOR NTH AUTOMATIC WNTER OVERRIDE, PLEATED 30% EXHAUST AND OUTSIDE AIR FILTERS,
SINGLE POINT ELECTRICAL CONNECTION, MOTORIZED OUTSIDE AIR AND EXHAUST DAMPERS.
UNITS MUST BE AMCA CERTIFIED.
CLOVER
AIR HANDLING UNIT UNIT SCHEDULE
UNIT
NUMBER
AHU-1
AHU-2
AHU-3
AHU-4
AHU-5
AHU-6
AHU-7
AHU-8
AHU-9
AHU-10
AHU-11
AHU-12
AHU-13
--
LOCATION
MECH
MECH
MECH
MECH
MECH
MECH
MECH
MECH
MECH
MECH
MECH
MECH
MECH
PLATFORM
PLATFORM
PLATFORM
PLATFORM
PLATFORM
PLATFORM
PLATFORM
PLATFORM
PLATFORM
PLATFORM
PLATFORM
PLATFORM
PLATFORM
SUPPLY FAN
AIR FLOW
E.S.P.
(CFM)
(IN. H,0)
AREA SERVED
A220
A220
A220
A220
B220
B220
B220
B220
C220
C220
C220
C220
C220
REPLACEMENT
A CLASSROOMS
A CLASSROOMS
MUSIC/ART WING
CAFETERIA
B CLASSROOMS
B CLASSROOMS
ADMIN/CLASSROOMS
MEDIA/ADMIN
C CLASSROOMS
C CLASSROOMS
GYMNASIUM
GYMNASUIM
HEALTH/MULTIPURPOSE
15,750
15,750
12,500
12,940
15,750
15,750
6,500
11,500
15,750
15,750
11,000
14,500
8,000
1.5"
1.5"
2.0"
1.5"
1.5"
1.5"
1.5"
1.5"
1.5"
1.5"
1.5"
1.5"
1.5"
RETURN FAN
OCCUPIED
DESIGN
AIR FLOW
E.S.P.
MIN. OUTSIDE
OUTSIDE
TOTAL
(CFM)
(IN. H,0) AIRFLOW (CFM) AIRFLOW (CFM) CAPACITY
14,000
14,000
11,250
-14,000
14,000
5,850
10,750
14,000
14,000
-6,210
7,100
0.75"
0.75"
0.75"
-0.75"
0.75"
0.75"
0.75"
0.75"
0.75"
-0.75"
0.75"
1,750
1,750
1,250
1,200
1,750
1,750
650
750
1,750
1,750
4,000
1,000
900
4,500
4,500
4,000
4,200
4,500
4,500
1,500
1,500
4,500
4,500
4,000
5,500
3,000
GPM
300,000
300,000
238,400
-300,000
300,000
116,800
188,900
300,000
300,000
--163,100
15
15
11.9
-15
15
5.9
9.4
15
15
--8.2
PREHEAT COll
RUNOUT E.W.T. L.W.T.
SIZE
(7)
(7)
1¼"
1¼"
1¼"
-1¼"
1¼"
1"
1¼"
1¼"
1¼"
--1¼"
160
160
160
-160
160
160
160
160
160
--160
120
120
120
-120
120
120
120
120
120
--120
MAX.
P.D.
MAX.
TOTAL
S.P. CAPACITY
SENSIBLE
CAPACITY
5'
5'
5'
-5'
5'
5'
5'
5'
5'
--5'
O.25"
O.25"
O.25"
-O.25"
O.25"
O.25"
O.25"
O.25"
O.25"
--O.25"
410,300
410,300
328,100
326,300
410,300
410,300
160,100
310,800
410,300
410,300
277,200
366,100
207,300
580,000
580,000
465,100
448,000
580,000
580,000
217,600
432,800
580,000
580,000
383,800
510,300
284,300
COOLING COll.
RUNOUT E.W.T. L.W.T.
GPM
SIZE
(7)
(7)
97
97
77
75
97
97
36
72
97
97
64
85
47
3"
3"
3"
3"
3"
3"
2"
2½"
3"
3"
2½"
3"
2"
44
44
44
44
44
44
44
44
44
44
44
44
44
56
56
56
56
56
56
56
56
56
56
56
56
56
MAX.
P.D.
MAX.
S.P.
TOTAL
CAPACITY
GPM
10'
10'
10'
10'
10'
10'
10'
10'
10'
10'
10'
10'
10'
O.75"
O.75"
O.75"
O.75"
O.75"
O.75"
O.75"
O.75"
O.75"
O.75"
O.75"
O.75"
O.75"
---259,600
------275,200
313,400
--
---13
------14
16
--
REHEAT COIL
RUNOUT E.W.T. L.W.T.
SIZE
(7)
(7)
---1¼"
------1¼"
1½"
--
---160
------160
160
--
---120
------120
120
--
MAX.
P.D.
---5'
------5'
5'
--
ELECTRICAL DATA
MAX. SUPPLY FAN RETURN FAN
S.P.
(H.P.)
(H.P.)
VOLTS
---O.25"
------O.25"
O.25"
--
15
15
15
15
15
15
7½
15
15
15
10
15
10
5
5
3
-5
5
3
3
5
5
--3
460
460
460
460
460
460
460
460
460
460
460
460
460
PHASE
Hz
MANUFACTURER &
MODEL NO.
3
3
3
3
3
3
3
3
3
3
3
3
3
60
60
60
60
60
60
60
60
60
60
60
60
60
CARRIER
CARRIER
CARRIER
CARRIER
CARRIER
CARRIER
CARRIER
CARRIER
CARRIER
CARRIER
CARRIER
CARRIER
CARRIER
SEQUENCE OF
OPERATION
39MN-36
39MN-36
39MN-30
39MN-30
39MN-36
39MN-36
39MN-14
39MN-25
39MN-36
39MN-36
39MN-25
39MN-30
39MN-17
VAV
VAV
VAV
SZVAV
VAV
VAV
VAV
VAV
VAV
VAV
SZVAV
SZVAV
VAV
OPERATING
WEIGHT
REMARKS
8800
8800
7500
5200
8800
8800
4400
6195
8800
8800
4200
5200
4900
C,D,E,G,K,L,Q
C,D,E,G,K,L,Q
C,D,E,G,K,L,Q
A,C,D,G,L,N,Q
C,D,E,G,K,L,Q
C,D,E,G,K,L,Q
C,D,E,G,K,L,Q
C,D,E,G,K,L,Q
C,D,E,G,K,L,Q
C,D,E,G,K,L,Q
A,C,D,G,L,Q
A,C,D,G,L,Q
C,D,E,G,K,L,Q
LBS
LBS
LBS
LBS
LBS
LBS
LBS
LBS
LBS
LBS
LBS
LBS
LBS
UNIT
NUMBER
AHU-1
AHU-2
AHU-3
AHU-4
AHU-5
AHU-6
AHU-7
AHU-8
AHU-9
AHU-10
AHU-11
AHU-12
AHU-13
MIDDLE SCHOOL
-
ma
engineering
1927 South Tryon St., Suite 300, Charlotte NC 28203
NOTES:
D -
Phone: 704-338-1292 042
www.optimapa.com
North Carolina License Number C-0914
ACCFSSORIFS:
1. COOLING COIL CAPACITY IS BASED ON 80° F. D.B./67° F. W.B. E.A.T. AND 56.0° F. D.B./55.5° F. W.B. L.A.T.
2. MAXIMUM FACE VELOCITY OF COOLING COILS SHALL BE 500 FPM.
3. HEATING COIL CAPACITY IS BASED ON 65° F. E.A.T.
A
B
C
D
E
F
4. ALL AIR HANDLERS SHALL HAVE HIGH EFFICIENCY FAN MOTORS.
5. ALL AIR HANDLING UNITS UNITS SHALL BE PROVIDED WITH A PHOTOELECTRIC TYPE SMOKE DETECTOR MOUNTED IN THE RETURN
DUCT. THE SMOKE DETECTOR SHALL BE FURNISHED AND WIRED FOR UNIT SHUT DOWN AND FIRE ALARM INTERFACE BY THE
ELECTRICAL CONTRACTOR AND SHALL BE INSTALLED IN THE DUCT BY THE MECHANICAL CONTRACTOR.
6. ALL UNITS SHALL HAVE A FACTORY INSTALLED 6" HIGH BASE RAIL. MOUNT AHU'S ON A 4" THICK CONCRETE PAD.
7. CONTRACTOR SHALL INSTALL NEW BELTS AND A NEW SET OF MERV 8 PLEATED FILTERS AT SUBSTANTIAL COMPLETION, AND
PROVIDE SPARE SETS OF BELTS AND FILTERS TO THE OWNER.
8. ALL UNITS SHALL BE DOUBLE WALL CONSTRUCTION WITH 18 GAGE MINIMUM CASING.
-
OA/RA MIXING BOX WITH FLAT FILTER SECTION
PERMANENT METAL FILTER FRAMES WITH REPLACEABLE FABRIC FILTERS (ANGULAR FILTERS)
VAV (FREQUENCY DRIVE) FOR SUPPLY FAN
PLENUM SUPPLY FAN
PLENUM RETURN/RELIEF FAN WITH VFD
VERTICAL DRAW THROUGH
LS')P
G - HORIZONTAL DRAW THROUGH
H - 2-SPEED FAN MOTOR (1800/900 RPM)
J - ANGULAR FILTER SECTION
K - ECONOMlZER SECTION WITH MOTORIZED OUTSIDE AIR, RETURN AIR AND RELIEF AIR DAMPERS.
L
M
N
P
Q
9. ALL UNITS SHALL HAVE A MINIMUM 14" ACCESS SECTION WITH HINGED DOOR BETWEEN EACH SET OF ADJACENT COILS.
10. SEE SPECIFICATIONS FOR ADDITIONAL REQUIREMENTS.
-
2" PLEATED FILTERS (MERV-8 MINIMUM)
ROOF CURB
INTERLOCK FAN TO RUN CONTINUOUSLY WHEN KITCHEN HOOD EXHAUST FAN IS IN OPERATION
CO2 SENSOR FOR DEMAND LIMITING CONTROL
INTERNAL VIBRATION ISOLATION
ENGAGE DESIGN TRANSRORM
PUMP SCHEDULE
SYMROI
P-1
P_-2
P_-3
P_-4
P-5.
P-§.
P_-Z
P_-8
P-1
GRILLE AND DIFFUSER SCHEOULE
SFRVICF
ßP_M.
jdEAD.
CHILLER #1
CHILLER #2
CHILLED WATER LOOP
CHILLED WATER LOOP
HOT WATER LOOP
HOT WATER LOOP
BOILER #1
BOILER #2
CHILLER STAND-BY
500
500
1000
1000
170
170
85
85
500
40'
40'
107'
107'
114'
114'
15'
15'
40'
EFFICIENCY
85%
85%
81%
81%
70%
70%
72%
72%
85%
R.P.M.
1750
1750
1750
1750
1750
1750
1750
1750
1750
jda
7½
7½
40
40
10
10
½
½
7½
VOLTAGE
460V-3ø
460V-3ø
460V-3ø
460V-3ø
460V-3ø
460V-3ø
120V-1ø
120V-1ø
460V-3ø
B&G MODEL
e1510-4AD
e1510-4AD
e1510-5GB
e1510-5GB
e1510-2EB
e1510-2EB
e90-2AAC
e90-2AAC
e1510-4AD
RFMARKS
A
B
C
D
E
F
G
H
J
K
L
M
N
SUPPLY
SUPPLY
SUPPLY
SUPPLY
SUPPLY
SUPPLY
RET/EXH
RET/EXH
RET/EXH
RET/EXH
RET/EXH
RET/EXH
0 - 125
12×12
6x6
0 - 125
24x24
6x6
130 - 280
24x24
9x9
285 - 500
24x24
12x12
505 - 780
24x24
15x15
(SEE PLANS FOR NECK SIZE AND CFM)
(SEE PLANS FOR NECK SIZE AND CFM)
0 - 195
12x12
8x8
0 - 195
24x24
8x8
200 - 300
24x24
10x10
305 - 450
24x24
12x12
455 - 800
24x24
16x16
LOUVERED
LOUVERED
LOUVERED
LOUVERED
LOUVERED
DBL. DEFL.
FIXED BLADE
CUBE CORE
CUBE CORE
CUBE CORE
CUBE CORE
CUBE CORE
NO
NO
NO
NO
NO
NO
YES
NO
NO
NO
NO
NO
RGS-3
P_BLCE
SMD
SMD
SMD
SMD
SMD
520
530
80
80
80
80
80
R
T
U
V
RETURN
SUPPLY
SUPPLY
RETURN
O - 1800
24x24
NON-DUCTED
O - 240
TWO 3/4" SLOTS, 48" LONG
245 - 400
THREE 1" SLOTS, 48" LONG
(SEE PLANS FOR NECK SIZE AND CFM)
CUBE CORE
LINEAR
LINEAR
HEAVY DUTY
NO
NO
NO
NO
80
SDS75
SDS100
96
£Bd.
4800
3840
S2...
1.35"
0.6"
E-1
E-4
E-5.
E-G
E-Z
E-G
E-1
E-10.
E-11
E-12
DISHWASHER
FIRE PUMP
BOILER ROOM
MAIN ELEC ROOM
KITCHEN TOILET
KITCHEN TLT/LKR
KILN
ART TOILET
CLASSROOM CORE
SCIENCE LAB
EXHAUST
EXHAUST
EXHAUST
EXHAUST
EXHAUST
EXHAUST
EXHAUST
EXHAUST
EXHAUST
EXHAUST
600
1200
3500
1500
75
250
150
75
1650
1600
E-li
E-15
E-1E
E-1Z
E-18
E-1R
E-2Q
E-21
E-22
SCIENCE LAB
SCIENCE LAB
SCIENCE PREP
CLASSROOM CORE
HEALTH TOILETS
ADMIN TOILETS
CLASSROOM CORE
SCIENCE LAB
SCIENCE LAB
EXHAUST
EXHAUST
EXHAUST
EXHAUST
EXHAUST
EXHAUST
EXHAUST
EXHAUST
EXHAUST
(*) - FOR DEVICES INSTALLED IN GYP CEILINGS, PROVIDE MINIMUM FACE SIZE FOR SPECIFIED NECK SIZE.
E-21
E-24
SCIENCE LAB
SCIENCE LAB
NOTES:
E-25
E-2E
C -
NO
N_E
EXHAUST
MAKE-UP
STAND-BY
DBL. DEFL.
I OCATION
KITCHEN HOOD
KITCHEN HOOD
STAND-BY
(SEE PLANS FOR SIZE AND CFM)
SYMROI
E-1.
E-2
STAND-BY
SUPPLY
FAN SCHEDU _E
D.Bü£
FAN RPM
BELT
BELT
1020
820
WATTS
---
jd,P.L
3
2
VOLTAGE
208V-3ø
208V-3ø
1.0"
0.25"
0.25"
0.25"
0.25"
0.25"
0.25"
0.25"
0.375"
0.25"
BELT
BELT
BELT
BELT
DIRECT
DIRECT
DIRECT
DIRECT
DIRECT
DIRECT
1650
820
1010
1225
700
1550
1050
700
860
996
----50
-129
50
---
¼
¼
½
¼
-1/30
--¼
½
120V-1ø
120V-1ø
120V-1ø
120V-1ø
120V-1ø
120V-1ø
120V-1ø
120V-1ø
120V-1ø
120V-1ø
CAPTIVE-AIRE
NCA24HPFA
G12-A2.B
GREENHECK
CUBE-099-4
SBS-1H20-4
SBS-1L20-5
SBS-1H20-4
SP-890
G-070-D
SP-B150
SP-B90
G-163-C
G-143-VG
1600
1600
250
700
800
150
1500
1600
1600
0.25"
0.25"
0.25"
0.25"
0.25"
0.25"
0.375"
0.25"
0.25"
DIRECT
DIRECT
DIRECT
DIRECT
DIRECT
DIRECT
DIRECT
DIRECT
DIRECT
996
996
1550
1160
1270
1550
860
996
996
----------
½
½
1/30
¼
¼
1/30
¼
½
½
120V-1ø
120V-1ø
120V-1ø
120V-1ø
120V-1ø
120V-1ø
120V-1ø
120V-1ø
120V-1ø
EXHAUST
EXHAUST
1600
1600
0.25"
0.25"
DIRECT
DIRECT
996
996
---
½
½
SCIENCE PREP
CLASSROOM CORE
EXHAUST
EXHAUST
250
700
0.25"
0.25"
DIRECT
DIRECT
1550
1160
---
E-28
E-2R
E-3Q
E-31
E-32
E-Ja
E-34
E-3E
E-3E
E-3Z
E-38
SCIENCE LAB
SCIENCE LAB
SCIENCE LAB
SCIENCE LAB
SCIENCE PREP
CLASSROOM CORE
FIELD HOUSE
CUSTODIAL ROOM
RESTROOM BLDG
STORAGE/CUST.
ART TOILET
EXHAUST
EXHAUST
EXHAUST
EXHAUST
EXHAUST
EXHAUST
EXHAUST
EXHAUST
EXHAUST
EXHAUST
EXHAUST
1600
1600
1600
1600
250
700
865
350
1375
500
75
.
0.25
0.25"
0.25"
0.25"
0.25"
0.25"
0.25"
0.25"
0.25"
0.25"
0.25"
DIRECT
DIRECT
DIRECT
DIRECT
DIRECT
DIRECT
DIRECT
DIRECT
DIRECT
DIRECT
DIRECT
996
996
996
996
1550
1160
1205
1000
1100
1080
700
E-3R
RANGE HOOD
EXHAUST
600
0.55"
BELT
1275
227 WEST TRADE STREET
SUITE 700
CHARLOTTE, NORTH CAROLINA 28202
TEL. 704.333.6686
FAX 704.333.2926
WWW.LS3P.COM
ACCFSSORIFS CONTROl S
A,D,E,P,Q,R
A,C,D,M,R
7
7
A,B,D,E
A,B,G,K,N
A,B,G,K,N
A,B,G,K,N
A,B,F,J,0
A,B,D,E
A,B,F,H,0
A,B,F,J,0
A,B,D,E
A,B,D,E
8
1
1
1
2
5
1
2
5
4
G-143-VG
G-143-VG
G-070-D
G-099-VG
G-099-VG
G-065-D
G-163-C
G-143-VG
G-143-VG
A,B,D,E
A,B,D,E
A,B,D,E
A,B,D,E
A,B,D,E
A,B,D,E
A,B,D,E
A,B,D,E
A,B,D,E
4
4
6
5
5
5
5
4
4
120V-1ø
120V-1ø
G-143-VG
G-143-VG
A,B,D,E
A,B,D,E
4
4
1/30
¼
120V-1ø
120V-1ø
G-070-D
G-099-VG
A,B,D,E
A,B,D,E
6
5
-------121
-285
50
½
½
½
½
1/30
¼
¼
-¼
---
120V-1ø
120V-1ø
120V-1ø
120V-1ø
120V-1ø
120V-1ø
120V-1ø
120V-1ø
120V-1ø
120V-1ø
120V-1ø
A,B,D,E
A,B,D,E
A,B,D,E
A,B,D,E
A,B,D.E
A,B,D,E
A,B,D.E
A,B,F,J,0
A,B,D.E
A,B,F,0
A,B,F,J,0
4
4
4
4
6
5
4
6
4
6
2
--
¼
120V-1ø
G-143-VG
G-143-VG
G-143-VG
G-143-VG
G-070-D
G-099-VG
G-103-VG
SP-A410
G-133-VG
SP-A710
SP-B90
CAPTIVE-AIRE
DU30HFA
linfill
CA
042 042
OPTIMA
ENGINEERING
No.
0710
0F
filillin
NOTES:
1. ALL PUMPS SHALL BE FURNISHED NTH HIGH EFFICIENCY MOTORS PER EPACT REQUIREMENTS.
2. ALL BASE MOUNTED END SUCTION PUMPS SHALL BE FURNISHED NTH TRIPLE DUTY VALVES AND
SUCTION DIFFUSERS.
3. PUMPS P-3 & P-4 OPERATE IN PARALLEL AND SHALL BE NON-OVERLOADING.
4. PUMPS P-5 & P-§. OPERATE IN PARALLEL AND SHALL BE NON-OVERLOADING.
5. PUMPS P-3, P-4, P-5, AND P-E SHALL BE FURNISHED WITH VARIABLE FREQUENCY DRIVES AND
INVERTOR DUTY MOTORS.
6. SUBMITTALS FOR NON-OVERLOADING PUMPS SHALL SHOW BOTH SINGLE AND DUAL PUMP OPERATION.
7. PUMP VFD AND BYPASS SHALL BE PROVIDED WTH PHASE LOSS PROTECTION.
1. ALL CEILING AND WALL MOUNTED DEVICES SHALL BE FURNISHED WITH AN ENAMEL OFF-WHITE FINISH.
2. ALL DEVICES SHALL BE FURNISHED NTH FRAMES SUITABLE FOR TYPE
OF INSTALLATION REQUIRED.
3. ALL LINEAR DIFFUSERS IN LAY-IN CEILINGS SHALL BE FURNISHED NTH END CAPS, ALL
LINEAR DIFFUSERS IN HARD CEILINGS SHALL BE FURNISHED NTH END BORDERS.
4. ALL AIR DISTRIBUTION DEVICES LOCATED IN KITCHEN, LOCKER ROOMS, AND TOILETS SHALL BE
ALL ALUMINUM CONSTRUCTION.
5. ALL DOUBLE DEFLECTION SUPPLY GRILLES SHALL HAVE DAMPER BLADES ADJUSTED TO
PROVIDE AIRFLOW PATTERN INDICATED BY FLOW ARROWS ON PLANS. DAMPERS SHALL BE
ADJUSTED TO A 30 DEGREE POSITION UNLESS NOTED OTHERNSE ON PLANS.
E-4Q
CUSTODIAL ROOM
EXHAUST
700
0.25"
DIRECT
950
285
--
120V-1ø
SP-A900
. 22
7
10/31M
MEMBERS OF THE AMERICAN INSTITUTE OF ARCHITECTS
COPYRIGHT 2014 ALL RIGHTS RESERVED
PRINTED OR ELECTRONIC DRAWINGS AND
DOCUMENTATION MAY NOT BE REPRODUCED
IN ANY FORM WITHOUT WRITTEN PERMISSION
FROM LS3P ASSOCIATES LTD.
REVISIONS:
A,D,E,P,Q
9
GRFFNHFCK
B -
illHff
_
A,B,F,H,0
No.
Description
PROJECT:
9201-131360
DATE:
OCT.31,2014
DRAWN BY:
SRD
Date
1
DUCTLESS SPLIT SYSTEMS (DX COOLING ONLY)
INDOOR UNIT
COOl ING CAPACITY
A/C-1
A/C-2
A/O-1
A/C-4
A/O-E
A/C-6
A/O-Z
A/C-8
775
775
775
775
775
775
775
775
E (BTUH) SjiG (BTUH)
24,000
18,500
24,000
18,500
24,000
18,500
24,000
18,500
24,000
18,500
24,000
18,500
24,000
18,500
24,000
18,500
HFATING CAPACITY
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
(BTUH)
- COOL
- COOL
- COOL
- COOL
- COOL
- COOL
- COOL
- COOL
ONLY
ONLY
ONLY
ONLY
ONLY
ONLY
ONLY
ONLY
FI FCTRICAI DATA
FAN FLA
0.36
0.36
0.36
0.36
0.36
0.36
0.36
0.36
MCA
1.0
1.0
1.0
1.0
1.0
1.0
1.0
1.0
VOLTAGE
208V-1ø
208V-1ø
208V-1ø
208V-1ø
208V-1ø
208V-1ø
208V-1ø
208V-1ø
MANljFACTilRFR
MITSUBISHI
PKA-A24KA
PKA-A24KA
PKA-A24KA
PKA-A24KA
PKA-A24KA
PKA-A24KA
PKA-A24KA
PKA-A24KA
OllTDOOR llNIT
COOl ING CAPACITY
CU-1
CU-2
CU-1
CU-i
CU-E
CU-E
CU-Z
CU-R
E (BTUH) SjiG (BTUH)
24,000
18,500
24,000
18,500
24,000
18,500
24,000
18,500
24,000
18,500
24,000
18,500
24,000
18,500
24,000
18,500
EEE,.
HFATING CAPACITY
EEB.
17.0
17.0
17.0
17.0
17.0
17.0
17.0
17.0
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
(BTUH)
- COOL
- COOL
- COOL
- COOL
- COOL
- COOL
- COOL
- COOL
COMPRESSOR EAR
ONLY
ONLY
ONLY
ONLY
ONLY
ONLY
ONLY
ONLY
95"
95'
95"
95'
95"
95'
95"
95'
F
F
F
F
F
F
F
F
LBA
14
14
14
14
14
14
14
14
ELA
12
12
12
12
12
12
12
12
ELA
0.75
0.75
0.75
0.75
0.75
0.75
0.75
0.75
Fl FCTRICAI DATA
MCA
18
18
18
18
18
18
18
18
EU.SE
30
30
30
30
30
30
30
30
VOLTAGE
208V-1ø
208V-1ø
208V-1ø
208V-1ø
208V-1ø
208V-1ø
208V-1ø
208V-1ø
OPERATING MANljFACTilRFR
WEIGHT
163 LBS
163 LBS
163 LBS
163 LBS
163 LBS
163 LBS
163 LBS
163 LBS
MITSUBISHI
PUY-A24NHA
PUY-A24NHA
PUY-A24NHA
PUY-A24NHA
PUY-A24NHA
PUY-A24NHA
PUY-A24NHA
PUY-A24NHA
NOTES:
1.
2.
3.
4.
5.
6.
7.
8.
A 9.
ALL UNITS SHALL BE U.L. LISTED AND HAVE A MINIMUM SEER OF 13.
COOLING CAPACITIES ARE BASED ON 95© AMBIENT, 80' ENTERING AIR DRY BULB, 67© ENTERING AIR WET BULB. AIRFLOWS INDICATED ARE AT 'HIGH' SPEED.
MOUNT GROUND-MOUNTED UNITS ON A 4" THICK CONCRETE PAD INSTALLED BY THE GENERAL CONTRACTOR, COORDINATE LOCABONS NTH THE MECHANICAL CONTRACTOR..
PROVIDE MANUFACTURER'S SUGGESTED CLEARANCES AROUND UNIT.
PROVIDE UNITS NTH MANUFACTURER'S NND BAFFLES OR LOW AMBIENT CONTROLS FOR OPERABON DOWN TO O' F, INVERTER COMPRESSOR, 7-DAY
PROGRAMMABLE THERMOSTAT (WALL-MOUNTED), INTEGRAL NON-LOCKING DISCONNECT FOR INDOOR UNIT.
PROVIDE OUTDOOR UNITS NTH 6 YEAR EXTENDED COMPRESSOR WARRANTY.
SEE MANUFACTURER'S RECOMMENDATIONS FOR REQUIRED ADDIBONAL REFRIGERANT CHARGE AND RECOMMENDED LINE-SET LENGTHS.
POWER SUPPLY TO CONDENSING UNIT IS A SINGLE POINT ELECTRICAL CONNECTION FOR THE SYSTEM (A/C UNIT AND CONDENSING
UNIT). THE ELECTRICAL CONTRACTOR SHALL PROVIDE POWER TO THE CONDENSING UNIT AND FROM THE CONDENSING UNIT TO THE
A/C UNIT. CODE REQUIRED DISCONNECT SNTCHES ARE PROVIDED BY MECHANICAL CONTRACTOR.
REFRIGERANT PIPING AND NRING FOR WALL-MOUNTED INDOOR UNITS SHALL BE ROUTED IN WALL WHERE POSSIBLE. ANY EXPOSED
PIPING SHALL BE PAINTED TO MATCH WALL-FINISH.
ACCESSORIES
A:
B:
C:
D:
E:
F:
CHECKED BY: RVA
CONTROLS
M:
N:
0:
P:
Q:
R:
S:
T:
U:
DISCONNECT SWITCH
GRAVITY BACKDRAFT DAMPER
MOTORIZED BACKDRAFT DAMPER
PREFAB. ROOF CURB
BIRDSCREEN
ACOUSBCAL LINING
G: HANGING BRACKETS
NTH VIBRATION ISOLATION
H: WL, WALL LOUVER DISCHARGE
J: RCC OR GRS ROOF CAP (FLAT ROOF)
OR RJ ROOF CAP (PITCHED ROOF)
K: WALL MOUNTING COLLAR
L: INLET GUARD
2" WASHABLE ALUMINUM FILTERS
MOTORSIDE FAN GUARD
EXHAUST GRILLE
U.L. 762
VENTED ROOF CURB EXTENSION
COMBINATION KITCHEN HOOD FAN CURB
NOT USED
PROVIDE DRAIN PLUG ACCESSORY
PRESSURE SENSING SNTCH
1: WALL MOUNTED THERMOSTAT
(REVERSE ACTING, SET FOR 80')
2: INTERLOCK NTH ROOM LIGHT SNTCH
(FAN SHALL OPERATE WHEN LIGHT IS ON
IN ANY ROOM SERVED BY FAN)
3: WALL MOUNTED ON/OFF SNTCH WITH
IDENTIFICATION LABEL
4: WALL MOUNTED TNST TIMER WTH 0-3 HOUR
RANGE NTH IDENTIFICATION LABEL
5:
6:
7:
8:
9:
CONTROLLED BY BUILDING AUTOMATION SYSTEM
CONTINUOUS OPERATION
INTERLOCK WTH KITCHEN HOOD CONTROLS
INTERLOCK WITH DISHWASHER
INTERLOCK WITH RANGE HOOD
NOTES:
1.
ALL FANS SHALL BE U.L LISTED AND LABELED AND SHALL BE AMCA CERTIFIED FOR SOUND AND AIR FLOW.
ADJACENT TO OCCUPIED SPACES SHALL HAVE A MAXIMUM 9.0 INLET SONE LEVEL
2. MECHANICAL CONTRACTOR SHALL PROVIDE MAGNETIC STARTER NTH AUXILLARY CONTACTS AS REQUIRED.
3. PROVIDE ALL DIRECT DRIVE FANS NTH SPEED CONTROLLERS.
MECHANICAL
SCHEDULES
ALL FANS INSTALLED INSIDE, ABOVE, OR
M-002
OPTIMA # 13-0238
2 OF 26
SOLUTIONS THROUGH LISTENING
1
1
THIS DRAWING IS AN INSTRUMENT OF SERVICE. THE DRAWING AND THE INFORMATION THEREON IS THE PROPERTY OF OPTIMA ENGINEERING, P.A. ANY REPRODUCTION, ALTERATION, OR USE FOR OTHER THAN THE INTENDED PROJECT, WITHOUT THE WRITTEN CONSENT OF OPTIMA ENGINEERING, P.A. IS EXPRESSLY FORBIDDEN. COPYRIGHT ©OPTIMA ENGINEERING P.A. 2014, ALL RIGHTS RESERVED.
2
I
3
I
4
I
5
I
6
BID DOCUMENTS
ROOF MOUNTED GRAVITY VENTILATOR SCHEDULE
E -
MAX. THROAT
MAX. S.P.
MANUFACTURER
H
THROAT SIZE
VELOCITY (FPM)
DROP (IN.)
GREENHECK
25,250
14,000
19,850
20,750
13,000
21,100
1,200
3,500
1,500
48x96
48x96
48x96
48x96
48x96
48x96
18x18
24x24
18x18
800
800
800
800
800
800
800
800
800
0.10"
0.10"
0.10"
0.10"
0.10"
0.10"
0.10"
0.10"
0.10"
FGR
FGR
FGR
FGR
FGR
FGR
GRSR-18
GRSR-24
GRSR-18
FAN F-7. F-36. F-37 RELIEF
525
12x12
800
0.10"
DRYER COMBUSTION AIR
--
8x8
800
0.10"
SYMBOL
LOCATION
SERVICE
By-1
RV-2
RV-3
RV-4
RV-5
RV-6
RV-7
RV-8
RV-9
MECH PLATFORM A220
MECH PLATFORM A220
MECH PLATFORM B220
MECH PLATFORM B220
MECH PLATFORM C220
MECH PLATFORM C220
FIRE PUMP A161
BOILER ROOM A160
ELEC ROOM A163
AHU-1 & 3 REUEF
AHU-2 RELIEF
AHU-5 & 7 REUEF
AHU-4 & 6 REUEF
AHU-1 & ERV-1 REUEF
AHU-10 & 13 RELIEF
FAN F-4 REUEF
FAN F-5 REUEF
FAN F-6 REUEF
RV-10
OFFICE A159
RV-11
LAUNDRY C168
ENVIROTEC
DUCT
ENVIROTEC
DUCT
SYMBOL
MAXIMUM COOLING HEATING
CFM
MIN CFM
CFM
BTUH
GPM
RUNOUT
SDR-WC
RUNOUT
SYMBOL
CFM
MIN CFM
CFM
BTUH
GPM
RUNOUT
SDR-WC
RUNOUT
A,B,C
A,B,C
A,B,C
A,B,C
A,B,C
A,B,C
A,B,D
A,B,D
A,B,D
1.1
3
1.4
1.5
1.6
1.7
1.8
1.9
1750
40
1600
1500
1250
1250
1925
1250
6
440
360
400
380
320
320
490
320
880
710
800
900
750
750
1160
630
29000
24000
26000
30000
25000
25000
38000
21000
2.0
1.2
1.3
1.5
1.3
1.3
1.9
1.1
3/4
1/2
1/2
1/2
1/2
1/2
3/4
1/2
12
12
12
12
10
10
14
10
14
14
14
14
14
14
16
14
7.1
3
7.4
7.5
7.6
7.7
7.8
7.9
1200
575
1100
450
400
500
470
500
300
600
20000
1/2
550
270
240
0
290
250
18000
9000
8000
0
10000
9000
1
1/2
1/2
1/2
n/a
1/2
1/2
10
8
10
8
8
SDR-8
8
8
10
12
280
120
100
0
120
130
1.4
0
1.0
1.0
1.0
0.0
1.0
1.0
GRSR-12
A,B,C
1.12
1400
350
700
23000
1.2
1/2
12
14
7 12
475
120
240
8000
1 0
1/2
8
10
GRSI-8
A,B,C
7.13
440
110
220
8000
1.0
1/2
8
10
ACCESSORIES
HW COIL
MAXIMUM COOLING HEATING
HW COIL
1665
420
840
28000
1.9
3/4
12
14
2.2
1300
330
650
22000
1.5
1/2
12
14
8.1
450
120
230
8000
1.0
1/2
8
10
2.3
1325
340
670
22000
1.1
1/2
12
14
8.2
510
130
260
9000
1.0
1/2
8
10
2.4
1300
330
650
22000
1.1
1/2
12
14
83
900
230
450
15000
1 0
1/2
10
12
2.5
2.6
1500
1300
380
330
900
780
30000
26000
1.5
1.3
1/2
1/2
12
12
14
14
8.4
1255
320
630
21000
1.1
1/2
10
14
2.7
1300
330
780
26000
1.3
1/2
12
14
8.5
1200
300
720
24000
1.2
1/2
10
12
2.8
2025
510
1220
40000
2.0
3/4
14
16
8.6
1200
300
720
24000
1.2
1/2
10
12
1300
1300
1650
2.12
2160
330
330
420
540
650
650
830
1080
22000
22000
27000
35000
1.1
1.1
1.4
1.8
1/2
1/2
1/2
12
12
12
1/2
14
14
14
14
8.7
8.8
8.9
16
1055
265
1125
270
70
290
640
160
570
21000
6000
19000
1.1
1.0
1.0
1/2
1/2
1/2
10
6
10
580
150
290
10000
1.0
1/2
8
10
8.11
2520
630
1260
41000
2.1
3/4
14
16
1.
PROVIDE ALL VENTILATORS WITH FACTORY ROOF CURBS.
A:
CURBS AND VENTILATORS SHALL BE INSTALLED LEVEL.
3.1
1820
460
910
30000
2.0
3/4
12
14
12
9.1
1750
440
880
29000
2.0
3/4
12
14
ROOF CURB
3.3
2650
670
1330
44000
2.2
3/4
16
16
9.2
500
0
0
0
0.0
n/a
SDR-8
10
B:
INSECT SCREEN
3.4
495
130
250
9000
1.0
1/2
8
10
9.3
1365
350
690
23000
1.2
1/2
12
14
C:
GRAVITY BACKDRAFT DAMPER
3.5
1225
310
740
24000
1.2
1/2
10
12
9.4
1250
320
630
21000
1.1
1/2
10
14
D:
MOTORIZED DAMPER (SEE PLANS FOR INTERLOCK DETAILS)
3.6
660
170
400
13000
1.0
1/2
8
10
9.5
1500
380
900
30000
1.5
1/2
12
14
E:
WASHABLE ALUMINUM FILTERS
3.7
1590
400
960
32000
1.6
1/2
12
14
9.6
1250
320
750
25000
1.3
1/2
10
14
F:
BAROMETRIC DAMPER
3.8
3.9
1440
690
360
180
870
350
29000
12000
1.5
1.0
1/2
1/2
12
8
14
10
9.7
9.8
1250
1925
320
490
750
1160
25000
38000
1.3
1.9
1/2
3/4
10
14
14
16
3.10
1545
390
780
26000
1.3
1/2
12
14
9.9
1250
320
630
21000
1.1
1/2
10
14
3.11
1500
380
750
25000
1.3
1/2
12
14
9.10
1250
320
630
21000
1.1
1/2
10
14
91,
1800
400
800
2e000
13
2
12
,4
ACCFSSORIFS
3.2
1180
300
590
20000
1.4
1/2
10
ALL MD UNE l··EAER El--EDULE
SYMBOL
LOCATION
FUH-1
EUH-2
EUH-3
EUH-4
EUH-5
FIRE PUMP A161
BOILER A160
STORAGE C176
STORAGE F101
STORAGE F102
D -
CBd.
400
400
400
400
400
D.E!]i
11,200
11,200
11,200
11,200
11,200
jm
3.3
3.3
3.3
3.3
3.3
R.P.M.
1500
1500
1500
1500
1500
1/125
1/125
1/125
1/125
1/125
VOLTAGE
277V-1ø
277V-1ø
277V-1ø
208V-1ø
208V-1ø
9.12
REMARKS
MARKEL
G1G5103N
G1G5103N
G1G5103N
F1F5103N
F1F5103N
5.1
AC PREnlN MOUMMER
PART 111 PAGF 7
OPTION 1 - FAN SYSTEM MOTOR NAMEPLATE HORSEPOWER
.TAG.
SUPPI Y NAMFPI ATF HP
RETURN NAMEPLATE HP
TOTAl NAMFPI ATF HP
SUPPLY CFM
AHU-1
15
5
20
15,750
AHU-2
15
5
20
15,750
AHU-3
15
3
18
12,500
AHU-4
15
15
12,940
AHU-5
15
5
20
15,750
Al l OWFD NAMFPI ATF HP
COMPLIANCE
23.625
YES
23.625
YES
18.75
YES
19.5
YES
23.625
YES
FWH-1
TOILET F106
175
6826
2.0
--
--
208V-1ø
F3314TS-RP
EWH-2
CONCESSION F107
175
6826
2.0
--
--
208V-1ø
F3314TS-RP
FWH-3
EWH-4
FWH-5
EWH-6
FWH-7
TOILET F108
MEN R102
WOMEN R105
CONCESSION R106
STORAGE R107
175
175
175
175
175
6826
10,239
10,239
6826
6826
2.0
3.0
3.0
2.0
2.0
------
------
208V-1ø
208V-1ø
208V-1ø
208V-1ø
208V-1ø
F3314TS-RP
F3315TS-RP
F3315TS-RP
F3314TS-RP
F3314TS-RP
-
JAß
SUPPLY NAMEPLATE HP
AHU-6
15
AHU-9
15
AHU-10 AHU-11 AHU-12
15
10
15
RFTURN NAMFPI ATF HP
TOTAL NAMEPLATE HP
5
20
5
20
5
20
10
15
SUPPLY CFM
ALLOWED NAMEPLATE HP
COMPLIANCE
15,750
23.625
YES
15,750
23.625
YES
15,750
23.625
YES
11,000
16.5
YES
14,500
21.75
YES
1450
370
730
24000
1.6
1/2
12
14
350
400
380
690
800
900
23000
26000
30000
1.2
1.3
1.5
1/2
1/2
1/2
12
12
12
14
14
14
5.2
5.3
5.4
5.5
NOT USED
1365
1600
1500
5.8
1925
490
1160
38000
1.9
3/4
14
16
5.9
5.10
51,
1250
1250
1e00
320
320
400
630
630
800
21000
21000
2e000
1.1
1.1
, 3
1/2
1/2
, ²
10
10
12
14
14
,4
5.12
1400
350
700
23000
1.2
1/2
12
14
6.1
6.2
6.3
6.4
1665
1000
1325
1300
420
250
340
330
840
500
670
650
28000
17000
22000
22000
1.9
1.2
1.1
1.1
3/4
1/2
1/2
1/2
12
10
12
12
14
12
14
14
1400
10.1
10.2
10.3
10.4
350
1665
600
1365
1300
420
150
350
330
700
840
300
690
650
23000
1.2
28000
10000
23000
22000
1.9
1.0
1.2
1.1
1/2
12
3/4
1/2
1/2
1/2
12
8
12
12
LIGHT FOR EXHAUST FAN, TWO 4' VAPORPROOF FLOURESCENT TWO LAMP LIGHT FIXTURES (2
PER HOOD), AND STAINLESS STEEL GREASE FILTERS.
FIRE SUPPRESSION SYSTEM SHALL BE
ANSUL R-102 WITH ANSULEX LIQUID FIRE SUPPRESSANT. REMOTE PULL STATION FOR
ACTIVATION OF FIRE SUPPRESSION SYSTEM SHALL BE PROVIDED AND INSTALLED WHERE
INDICATED ON THE PLANS. FIRE SUPPRESSION SYSTEM SHALL BE UL 300 LISTED.
1650
420
830
27000
1.4
1/2
12
14
540
1080
35000
1.8
1/2
14
16
1.
2.
160
1080
40
80
3000
1.0
1/2
5
10
8
1300
2025
330
510
780
1220
26000
40000
1.3
2.0
1/2
3/4
12
14
14
16
13.4
13.5
1120
1770
280
450
560
1070
19000
35000
1.0
1.8
1/2
1/2
10
12
12
16
6.9
6.10
1300
1300
330
330
650
650
22000
22000
1.1
1.1
1/2
1/2
12
12
14
14
13.6
13.7
2000
1680
500
420
1200
1010
39000
33000
2.0
1.7
3/4
1/2
14
12
16
14
6.11
6.12
1650
2160
420
540
830
1080
27000
æ000
1.4
1.8
1/2
1/2
12
14
14
16
13.8
13
650
500
170
0
390
0
13000
0
1.0
0.0
1/2
Na
8
M-8
10
10
3.
4.
AHU-7
5.7
2.2
7.9
AHU-8
10.5
2.9
13.4
AHU-13
7.8
2.6
10.4
SUPPLY CFM
6,500
11,500
8,000
Al l OWFD RRAKF HP
COMPLIANCE
8.45
YES
14.95
YES
10.4
YES
7.
'l(NC
|| NO
NC
'll
NOTES:
1. ALL OPTION 1 SYSTEMS ARE VAV SYSTEMS USING THE EQUATION:
NAMEPLATE HP <= CFMS*0.0015
227 WEST TRADE STREET
SUITE 700
CHARLOTTE, NORTH CAROLINA 28202
TEL. 704.333.6686
FAX 704.333.2926
WWW.LS3P.COM
FIRE CONTROL SYSTEM BY HOOD
MANUFACTURER, WITH FOUR (4)
DRY CONTACTS FOR USE BY
DMSION 26
untlig
CA
NO
TUBING, CABLE, AND
PULLIES BY M.C.
OPTIMA
ENGINEERING
MECHANICAL GAS VALVE
BY M.C., INSTALLED BY
O
O
O
NOTFS:
1. HEATING CAPACITY BASED ON 65' F. E.A.T.,
2. PROVIDE EACH UNIT HEATER WITH: DISCONNECT SWITCH, BUILT-IN THERMOSTAT, ROOF MOUNTED BRACKETS,
AND ADJUSTABLE DISCHARGE LOUVERS..
3. PROVIDE EACH WALL HEATER WITH BUILT-IN DISCONNECT SWITCH AND THERMOSTAT, PENCIL-PROOF LOUVERS,
AND CABINET FOR SURFACE MOUNTING.
4. THERMOSTATS SHALL BE LOW VOLTAGE, LINE VOLTAGE THERMOSTATS ARE NOT ACCEPTABLE.
HORIZONTAL KITCHEN HOOD
EXHAUST DUCT SHALL SLOPE ¼" PER FOOT CONTINUOUSLY TOWARD HOOD.
ALL EXPOSED PIPING WITH FIRE SUPPRESSION SYSTEM SHALL TO
COVERED WITH A CHROME SLEEVE.
MECHANICAL CONTRACTOR SHALL INSTALL 1/2" CONDUlT IN WALL FOR
MANUAL PULL STATION. SEE PLANS FOR LOCATION OF MANUAL PULL
STATION.
MECHANICAL CONTRACTOR SHALL BE RESPONSIBLE FOR HOOD CERTIFICATION IN
COMPLIANCE WITH LOCAL CODE REQUIREMENTS. CERTIFICATION SHALL BE WITNESSED
AND PERFORMED BY A PERSON CERTIFIED THROUGH AABC, TABB, NEBB OR NBC AND
SHALL PROVIDE DOCUMENTATION OF PERFORMANCE TO THE CODE OFFICIAL. THIS
SHALL INCLUDE WET TEST CAPTURE & CONTAINMENT. ALL EQUIPMENT SHALL BE
ENERGlZED AND IN OPERATION DURING THE TEST. TEST SHALL ALSO INCLUDE
VERIFYING ACTUAL FLOW RATES VERSUS DESIGN FLOW RATES.
TO SUPPLY FAN
COMMON
TO CONTACTOR
CONTACTOR AT
PANEL BY DIV 26
1. MINIMUM INLET PRESSURE TO TERMINAL UNITS SHALL BE O.75" W.G.
2. MAXIMUM PRESSURE DROP THROUGH TERMINAL UNITS SHALL BE 0.25" S.P.
3. FURNISH TERMINAL UNITS WITH: FACTORY MOUNTED DDC CONTROLS (SEE NOTE 5),
ACOUSTICAL LINING, THERMOSTAT, CONTROL VOLTAGE TRANSFORMER.
4. MECHANCIAL CONTRACTOR SHALL EXTEND CONTROL POWER WIRING (120 V) FROM
J-BOX TO VAV BOX. 120 V J-BOX BY ELECTRICAL CONTRACTOR, WIRING FROM
J-BOX AND FINAL CONNECTION TO UNIT BY MECHANICAL CONTRACTOR. COORDINATE
LOCATION OF 120 V J-BOXES WITH ELECTRICAL CONTRACTOR.
5. DDC CONTROLS SHALL BE FURNISHED TO THE BOX MANUFACTURER BY THE CONTROLS
VENDOR. BOX MANUFACTURER SHALL FACTORY MOUNT AND WIRE CONTROLS. INSTALLATION
OF CONTROLS SHALL INCLUDE CONTROLS TRANSFORMER, CONTROL COVER, AND ALL WIRING
AND LABOR FOR A COMPLETE AND OPERATIONAL SYSTEM.
LS >P
- HOOD EXHAUST FAN
- REMOTE MANUAL PULL STATION
- ALL ASSOCIATED AIR HANDLING UNITS
- FIRE ALARM SYSTEM NOTIFICATION (BY ELEC. CONTR.)
SEE SHEET M-402 FOR HOOD DETAILS.
KITCHEN HOOD EXHAUST DUCT SHALL BE CONSTRUCTED OF 16 GAUGE
CARBON STEEL. ALL JOINTS AND SEAMS SHALL BE SEALED WITH A
SPARE
COMMON
TO BUILDING ALARM
NOTES:
Phone: 704-338-1292 042
www.optimapa.com
North Carolina License Number C-0914
FAN SHALL CONTINUE TO OPERATE. PROVIDE INTERLOCK FOR
LIQUID TIGHT CONTINUOUS EXTERNAL WELD.
OPTION 2 - FAN SYSTEM BRAKE HORSEPOWER
.TAG.
SUPPI Y RRAKF HP
RETURN BRAKE HP
TOTAl RRAKF HP
1927 South Tryon St., Suite 300, Charlotte NC 28203
- CONTACTORS (BY ELEC. CONTR.)
6.
6.7
6.8
engineering
KITCHEN HOOD SHALL BE CONSTRUCTED AND INSTALLED PER NFPA 96.
UPON ACTIVATION OF FIRE CONTROL SYSTEM, KITCHEN HOOD EXHAUST
AUTOMATIC OPERATION OF FIRE SUPPRESSION SYSTEM WITH:
- SOLENOID GAS VALVE (BY HOOD FIRE SYSTEM SUPPLIER)
5.
13.1
3
ma
NOTES:
22°
2160
523c!!au
KH-3
CAPTIVE-AIRE MODEL 4824 ND2, 4'-0"x4'-0"x2'-0" DEEP HOOD; 600 CFM EXHAUST EACH
@ 0.35" S.P. (MAX.); ALL STAINLESS STEEL CONSTRUCTION. ALL COMPONENTS SHALL BE U.L.
LISTED AND LABELED. PROVIDE A REMOTE CONTROL PANEL MOUNTED ON FACE OF HOOD
WITH MASTER DISCONNECT SWITCH, STARTER FOR FAN, CONTROL VOLTAGE TRANSFORMER,
FIRE CONTROL SYSTEM RELAY AND TERMINAL STRIP. MOUNT HOOD 6'-8" ABOVE FINISH
FLOOR, PROVIDE STAINLESS STEEL ENCLOSURE AROUND TOP OF HOOD AS REQUIRED TO
CLOSE TO CEILING. HOOD SHALL BE PROVIDED WITH: AUTOMATICALLY OPERATED FIXED PIPE
FIRE SUPPRESSION SYSTEM IN ACCORDANCE WITH NFPA 96, CONTROL SWITCHES AND PILOT
14
10
14
14
10.12
h Dun..
CLOVER
REPLACEMENT
MIDDLE SCHOOL
HOOD MANUFACTURER SHALL PROVIDE 12" STAINLESS STEEL ISLAND UTILITY CHASE BETWEEN
SECTIONS OF HOOD, INCLUDING WATER, GAS, AND ELECTRICAL, TO SERVE ITEMS UNDER
HOOD. PROVIDE QUICK DISCONNECTS FOR ALL UTILITIES. COORDINATE REQUIREMENTS WITH
KITCHEN PLANS AND KITCHEN EQUIPMENT SUPPLIER.
14
10.11
wh ch.M E
FIRE SUPPRESSION SYSTEM SHALL BE UL 300 LISTED.
NOTES:
--
CLOVER SCHOOL DISTRICT
SUPPRESSION SYSTEM SHALL BE PROVIDED AND INSTALLED WHERE INDICATED ON THE PLANS.
12
8
12
8.10
(FURNISHED AND INSTALLED BY M.C.)
KH-1 AND KH-2
CAPTIVE-AIRE MODEL 6024 ND2-4-PSP-F (TYPICAL OF 2 HOODS BACK TO BACK);
12'-0"x5'-0"x2'-0" DEEP HOOD WITH 14" WIDE SUPPLY PLENUM AT FRONT; 2400 CFM
EXHAUST EACH © 0.75" S.P. (MAX.); 1920 CFM SUPPLY EACH © 0.375" S.P. (MAX.); ALL
STAINLESS STEEL CONSTRUCTION. ALL COMPONENTS SHALL BE U.L. LISTED AND LABELED.
PROVIDE A REMOTE CONTROL PANEL MOUNTED ON FACE OF HOOD WITH MASTER DISCONNECT
SWITCH, STARTER FOR FAN, CONTROL VOLTAGE TRANSFORMER, FIRE CONTROL SYSTEM RELAY
AND TERMINAL STRIP. MOUNT HOOD 6'-8" ABOVE FINISH FLOOR, PROVIDE STAINLESS STEEL
ENCLOSURE AROUND TOP OF HOOD AS REQUIRED TO CLOSE TO CEILING. HOOD SHALL BE
PROVIDED WITH: AUTOMATICALLY OPERATED FIXED PIPE FIRE SUPPRESSION SYSTEM IN
ACCORDANCE WITH NFPA 96, CONTROL SWITCHES AND PILOT LIGHT FOR EXHAUST FAN, TWO
4' VAPORPROOF FLOURESCENT TWO LAMP LIGHT FIXTURES (2 PER HOOD), AND STAINLESS
STEEL GREASE FILTERS.
FIRE SUPPRESSION SYSTEM SHALL BE ANSUL R-102 WITH
ANSULEX LIQUID FIRE SUPPRESSANT. REMOTE PULL STATION FOR ACTIVATION OF FIRE
12
10
8
10
10
10
2.1
2.9
2.10
2.11
CLOVERSCHOOL
DISTRICT TWO
KITCHEN HOOD SCHEDULE
VAV BOX SCHEDULE
O
O
O
POWER SUPPLY
TO EQUIPMENT
R
PA
No. C00710
MANUAL SHUT-OFF
BY DIVISION 22
TO COOKING EQUIPMENT
GAS SUPPLY
ADDITIONAL FIRE SUPPRESSION NOTES (IBC):
lHIHf
904.11.1 A MANUAL ACTUATION DEVICE SHALL BE LOCATED AT OR NEAR A MEANS OF EGRESS
FROM THE COOKING AREA, A MINIMUM OF 10 FEET AND A MAXIMUM OF 20 FEET FROM THE
KITCHEN EXHAUST SYSTEM. THE MANUAL ACTUATION DEVICE SHALL BE LOCATED A MINIMUM
OF 3.5 FEET AND A MAXIMUM OF 4 FEET ABOVE THE FLOOR AND CLEARLY INDICATE THE
HAZARD PROTECTED. THE MANUAL ACTUATION SHALL REQUIRE A MAXIMUM FORCE OF 40
POUNDS AND A MAXIMUM MOVEMENT OF 14 INCHES TO ACTUATE THE FIRE SUPPRESSION
SYSTEM.
904.11.2 THE ACTUATION OF THE FIRE SUPPRESSION SYSTEM SHALL AUTOMATICALLY SHUT
DOWN THE FUEL OF ELECTRICAL POWER SUPPLY TO THE COOKING EQUIPMENT. THE FUEL AND
ELECTRICAL SUPPLY RESET SHALL BE MANUAL.
2. ALL OPTION 2 SYSTEMS ARE VAV SYSTEMS USING THE EQUATION:
BRAKE HP <= CFMS*0.0013 + A
3. BRAKE HORSEPOWERS ARE FROM MANUFACTURER AHU SELECTIONS.
""*
22
R.
MEMBERS OF THE AMERICAN INSTITUTE OF ARCHITECTS
HVAC Mandato
ProvisionS
Part ll, Page 1
Project Name: Clover Replacement Middle School
Date: September 22, 2014
HVAC System Designer of Record: Steven R. Daley, PE
Telephone: 704-3384292
Contact Person: Steven R. Daley, PE
Telephone: 704-338-1292
City: Clover
Climate Zone: 3A
Zip: 29710
1% Summer DB Temp: 91
1% Summer WB Temp: 74
Equipment Type (Tables
6.8.1A through G)
Size Category (Tables
6.8.1A through G)
Sub-Category or Rating
Condïtion (Tables 6.8.1A
through G)
Minimum Efficiency (Tables
6.8.1A through G)
Rated
Chiller#1&#2-~~~-- Allcapacities
RTU-1
Aircooledunitary
RTU-1
Warm air furnace, gas fired >225,000 btuh
-
>esooobtun<135000btuhsinglepackage
maximum capacity
Boiler B-1 & B-2 Boilers, gas fired hot water >s00,000 bluh, <2.500,000 btuh ueyseisumneaircooieomonoomoue
IDU/HP-1
us1eryH-=at sumps»cooe neattosmose <65,000 btuh cooling split system
A/c/ODU-1 thru7 Air cooled unitary
<65,000btuh
splitsystem
<65,000 btuh
split system
2
Required
Leaving CHW
Temperature (°F)
Entering CW
Temperature (°F)
Condenser Flow Rate
(gpm/ton)
Load calculations are provided for selection
of all equipment and systems (§ 6,4.2).
hoods. gravity vents and gravity ventilations
are provided with motorized dampers.
Exception: Gravity dampers are used
since the building is less than 3 stories
or in climate zones 1-3.
Exception: No vents are required as
these systems ventilate unconditioned
] Construction documents require record
co
s io
7
Contact Person: Steven R. Daley. PE
Systems Worksheet (§ 6.4)
AHU-4
AHU-7
AHU-8
AHU-11
System Tag
AHU-12
AHU-13
RTU-1
IDU-1
A/C-1 THRU 7
Supply CFM
15,75c
13,000
6,500
11,500
11,000
Supply CFM
14,500
7,900
4,000
1,200
775
Supply ESP (in. w.c.)
1.5"
2"
1.5"
1.5"
1.5"
1.5"
Supply ESP (in. w.c.)
1.5"
1.5"
0.5"
0.4°
N/A
Fan System HP
15
15
15
7.5
15
10
Fan System HP
15
10
2
3/4
1/2
OA CFM (i.e. Outdoor Air CFM)
4500
4000
4200
1500
1500
4000
OA CFM (i.e. Outdoor Air CFM)
5,500
3,000
80C
340
0
Automatic Shutdown (§ 6.4.3.2.1)
C1
C1
C1
c1
C1
C1
Automatic Shutdown (§ 6.4.3.2.1)
C1
C1
C1
c1
N1
Deadband (§ 6.4.3.1.2)
C1
C1
C1
C1
C1
C1
Deadband (§ 6.4.3.1.2)
C1
C1
C1
C1
N2
Prescriptive Economizers (§ 6.5.1)
Systems employ airside economizers
Economizer provides up to 100% design
aitflow in outdoor air (§ 6.5.1.1.1).
Economizer dampers meet or exceed
leakage requirements (§ 6.6.1.1.4).
Zone minimums were set to <0.4 cfm/ft2 of
zone conditioned floor area.
System provides relief for up to 100% design
aliflow in outdoor air (§ 6.5.1.1.5).
Zone minimums are less than 300 cfm.
C1
Setback Controls (§ 6.4.3.2.2)
C1
C1
C1
C1
N5
EER
11.1
Setup Controls (§ 6.4.3.2.2)
C1
C1
C1
c1
C1
C1
Setup Controls (§ 6.4.3.2.2)
C1
C1
C1
C1
N1
Optimum Start (§ 6.4.3.1.3)
c1
C1
C1
C1
C1
c1
Optimum Start (§ 6.4.3.1.3)
c1
C1
N3
N3
N1
Zone Isolation (§ 6.4.3.1.4)
N3
N3
N3
N3
N3
N3
Zone Isolation (§ 6.4.3.1.4)
N3
N3
N3
N3
N1
Shutoff Dampers (§ 6.4.3.3.3)
C1
C1
c1
C1
C1
c1
Shutoff Dampers (§ 6.4.3.3.3)
C1
C1
C2
C2
N1
Economizer complies with the heating system
impact requirements (§ 6.5.1.4).
Heat Pump Aux Heat (§ 6.4.3.4)
N1
N1
N1
N1
N1
N1
Heat Pump Aux Heat (§ 6.4.3.4)
N1
N1
N1
C1
N1
Systems employ waterside economizers.
Humidifier Preheat (§ 6.4.3.5)
N1
N1
N1
N1
N1
N1
Humidifier Preheat (§ 6.4.3,5)
N1
N1
N1
N1
N1
Humidificatïon/Dehumidification Deadband (§ 6.4,3.6)
C1
c1
C1
C1
C1
C1
Humidification/Dehumidification Deadband (§ 6.4.3.6)
C1
C1
N1
N1
N1
Ventilation Control (§ 6.4.3.8)
DCV
DCV
DCV
DCV
DCV
N/.A
Ventilation Control (§ 6.4.3.8)
DCV
DCV
N/A
N/A
N/A
Economizer can provide 100% of the load at
either the outdoor conditions of 50°F db/45°F
wb or 45°F db/40°F wb where required for
dehumidification purposes (§ 6.5.1.2.1).
Duct/Plenum insulation (§ 6.4.4.2.1)
C1
C1
C1
C1
C1
C1
Duct/Plenum insulation (§ 6,4.4.2.1)
C1
C1
C1
C1
N/A
Duct Sealing Levels (§ 6.4.4.2.1) Supply/Return
A
A
A
A
A
A
Duct Sealing Levels (§ 6.4.4.2.1) Supply/Retum
A
A
A
A
N/A
Duct Leakage Test (§ 6.4.4.2.2)
Y
Y
Y
Y
Y
Y
Duct Leakage Test (§ 6.4.4.2.2)
Y
Y
Y
Y
N/A
85%
2
80%
SEER
13
2
13
HSPF
7.8
2
7.7
SEER
13
2 13
Size Category
(Tables 6.8.1H
through J)
Minimum Efficiency (Tables
6.8.1H through J)
2
Required
Special Mandatory Requirements
Freeze protection or snow/ice melting
systems (if any) have controls to prevent
operation in warm weather (§ 6.4.3.7).
Independent perímeter heating systems (if
any) comply with the control requirements of
§ 6.4.3.1.1 and § 6.4.3.2.
Independent heating and cooling thermostatic
controis (if any) are interlocked to prevent
crossover of set points (§ 6.4.3.2).
Shutdown
042C1 Complying nonresidential time switch
with override
042C2 Complying residential time switch with
override
042N1 N/A continuous operation
042N2 N/A s15 kbtu/h or s3/4 hp
042N3 N/A hotel/motel guestroom
Dead Band
042C1 Dual setpoint control
042C2 Manual change over control
042N1 N/A special occupancy (requires
approval)
042N2 N/A heating or cooling only
Setback Controls
042C1 Setback provided (down to 55F)
042N1 N/A continuous operation
042N2 N/A s15 kbtu/h or s3/4 hp
042N3 N/A 99.6% Win DB>40F
042N4 N/A radiant heating
042N5 N/A no heating
zones.
Setup Controls
042C1 Setup provided (up to 90F)
042N1 N/A continuous operation
042N2 N/A s15 kbtu/h or s3/4 hp
042N3 N/A 1% Sum DB<=100F
042N4 N/A no cooling
Heat Pump Aux Heat
042C1 Complying controls provided
042N1 N/A system is not a heat pump
042N2 N/A auxiliary is not electric or is not
provided
042N3 N/A heat pump covered by NAECA
Optimum Start
042C1 Optimum start provided
042N1 N/A continuous ooeration
042N2 N/A s15 kbtu/h or 53/4 hp
042N3 N/A supply<=10,000 cfm
Humidifier Preheat
042C1 Complying controls provided
042N1 N/A no humidifier
Shutoff Dampers
042C1 Motorized shutoff dampers on OA and
Exh
042C2 Gravity shutoff dampers on OA and Exh
042N1 N/A continuous operation
042N2 N/A s15 kbtu/h or s3/4 hp
042N3 N/A OA/EA <=300 cfm
Zone Isolation
042C1 Iso|ation zones orovided
042N1 N/A continuous operation
042N2 N/A s15 kbtu/h or s3/4 hp
042N3 N/A all zones on same schedule
042N4 N/A OA/EA <=5,000 cfm
Humïdification/Dehumidification Dead Band
042C1 Complying controls provided
042N1 N/A no humidification and/or
dehumidification
Duct/Plenum insulation
042C1 Complying insulation provided
042N1 N/A all ducts located in conditioned
space
Duct Sealing
042Enter highest seal level (A, B or C) for
supply and return
Duct Leakage Test
042Y Ducts will be tested for leakage
042N Ducts will not be tested for leakage
In the table above, enter the appropriate codes
from this list:
Shutdown
042C1 Complying nonresidential time switch
withoverride
042C2 Complyíng residential time switch with
override
042N1 N/A continuous operation
042N2 N/A s15 kbtu/h or s3/4 hp
042N3 N/A hotel/motel guestroom
Dead Band
042C1 Dual setpoint control
042C2 Manual change over control
042N1 N/A special occupancy (requires
approval)
042N2 N/A heating or cooling only
Setback Controls
042C1 Setback provided (down to 55F)
042N1 N/A continuous operation
042N2 N/A s^15 kbtu/h or s3/4 hp
042N3 N/A 99.6% Win DB>40F
042N4 N/A radiant heating
042N5 N/A no heating
Setup Controis
042C1 Setup provided (up to 90F)
042N1 N/A continuous operation
042N2 N/A s15 kbtu/h or s3/4 hp
042N3 N/A 1% Sum DB<=100F
042N4 N/A no cooling
Heat Pump Aux Heat
042C1 Complying controls provided
042N1 N/A system is not a heat pump
042N2 N/A auxiliary is not electric or is not
Optimurn Start
042C1 Optimum start provided
042N1 N/A continuous operation
042N2 N/A s15 kblu/h or s3/4 hp
042N3 N/A supply<=10,000 cfm
Humidifier Preheat
042C1 Complying controls provided
042N1 N/A no humidifier
Shutoff Dampers
042C1 Motorized shutoff dampers on OA and
Exh
042C2 Gravity shutoff dampers on OA and Exh
042N1 N/A continuous operation
042N2 N/A s15 kbtu/h or s3/4 hp
042N3 N/A OA/EA <=300 cfm
Zone Isolation
042C1 Isolation zones provided
042N1 N/A continuous operation
042N2 N/A s15 kbtu/h or s3/4 hp
042N3 N/A all zones on same schedule
042N4 N/A OA/EA <= 5,000 cfm
(§ 6.5.4.3).
Zone minimums were set to meet the
requirements of Standard 62.
c1
80%
Prescriptive Air-System Requirements
Economizer high limït shutoff complies with
§ 6.5.1.1.3.
c1
2
System pumps greater than 10 hp employ
variable flow controls (§ 6.5.4.1), pump
isolation (§ 6.5.4.2) and temperature reset
Simultaneous Heating and Cooling
(§ 6.5.2,3).
c1
81.9%
--¯¯¯¯¯¯¯¯---¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯
Economizer is integrated with the mechanical
cooling system (§ 6.5.1.1.2 and § 6.5.1.3).
C1
Ec
heat addition and loop heat rejection (if any)
comply with the requirements of § 6.5.2.2.3.
Specify economizer exemptions:_
(§ 6.5.1.1).
c1
2 11.0
Telephone: 704-338-1292
Prescriptive Checklist
AHU-1.2,5,6,9.10 AHU-3
12.500
Contact Person: Steven R. Daley, PE
Telephone: 704-338-1292
System Tag
In the table above, enter the appropriate codes
from this list:
B Piping insulation meets or exceeds the
Telephone: 704-338-1292
COPYRIGHT 2014 ALL RIGHTS RESERVED
PRINTED OR ELECTRONIC DRAWINGS AND
DOCUMENTATION MAY NOT BE REPRODUCED
IN ANY FORM WITHOUT WRITTEN PERMISSION
FROM LS3P ASSOCIATES LTD.
eart iii, ease 1
Project Name: Clover Replacement Middie School
Setback Controls (§ 6.4.3.2.2)
Rated
General Mandatory Requirements
HVAC Prescri.tive Re4 uirements
3.14/4.16 2 3.10/3.45
Mandatory Non-Standard Centrifugal Chiller Worksheet (§ 6.4.1,1)
System Tag
part n, page 2
COP/IPLV
Et
IDU/HP-1
Provisions
Systems Worksheet (§ 6.4)
99.6% Winter Temp: 18
Units of Efficiency
(Tables 6.8.1A
through G)
HVAC Mandato
Project Name: Clover Replacement Middle School
Contact Person: Steven R. Daley, PE
Mandatory Equipment Efficiency Worksheet (§ 6.4.1.1)
System Tag
part n, eage 2
Project Name: Clover Replacement Middle School
Project Address: Highway 55 & Barrett Road
B
HVAC Mandator Provisions
Precooling coils and heat exchangers have
either a < 15 ft of WC pressure drop or are
bypassed when economizer is not in use (§
6.5.1.2.2).
Economizer is integrated with the mechanical
cooling system (§ 6.5.1.3).
Economizer complies with the heating system
impact requirements (§ 6.5.1.4).
Systems are exempt from the economizer
requirements.
provided
042N3 N/A heat pump covered by NAECA
REVISIONS:
_
No.
Description
Date
Prescriptive Special System Requirements
All heat rejection equipment with motors 2 7.5
hp employ controis that comply with § 6.5.5,
Exhaust Air Energy Recovery: all fan systems
that have both a design suppiy capacity of 2
5,000 cfm and a minimurn outdoor air supply
of 2 70% of the design supply air employ an
energy recovery system that complies with
§ 6.5.6.1.
Other (requires special documentation and
approval).
Heat recovery for service water heating is
provided for facilities that operate
Humidity controls (if any) comply with the
requirements of § 6.5.2,3,
continuously, have a total water-cooled heat
rejection capacity exceeding 6,000,000 btu/h,
and have a design service water heating load
exceeding 1,000,000 btu/h. The heat
recovery system (if any) complies with
Systems that employ hydronic cooling and
have humidifïcation (if any) use a waterside
economizer that complies with § 6.5.1.
§ 6.5.6.2.
Variable air volume fan controls comply with
the requirements of § 6.5.3.2.
Kitchen hoods with exhaust flows > 5000 ofm
comply with the requirements of § 6.5.7.1.
Prescriptive Water-System Requirements
Fume hoods with a total exhaust system flow
> 15,000 cfm comply with the requirements of
Three-pipe systems are not used (§
6.5.2.2.1).
§ 6.5.7.2.
O Tw°~pipe chan9eover heatin9/°°°'ino
systems (if any) comply with the
requirements of § 6.5.2.2.2.
PROJECT:
9201-131360
Radiant heaters complying with § 6.5.8.1 are
used to heat unenclosed spaces (if any).
DATE:
OCT.31,2014
O Hydronic (ground- or water-loop) heat pump
systems that have equipment for both loop
The cooling equipment with hot-gas bypass
controls (if any) meets the unloading
requirements of § 6.5.9.
DRAWN BY:
SRD
Humidification/Dehumidification Dead Band
042C1 Complying controls pmvided
042N1 N/A no humidification and/or
dehurnidification
CHECKED BY: RVA
MECHANICAL
SCHEDULES
- AND
COMPLIANCE
FORMS
Duct/Plenum insulation
042C1 Complying insulation provided
042N1 N/A all ducts located in conditioned
space
Duct Sealing
042Enter highest seal level (A, B or C) for
supply and return
Duct Leakage Test
042Y Ducts will be tested for leakage
042N Ducts will not be tested for leakage
M-003
3 OF 26
ANSI/ASHRAE/IESNA Standard 90.1-2007
--
ANSI/ASHRAE!IESNA Standard 90.1-2007
ANSI/ASHRAEllESNA Standard 90.1-2007
--
ANSI/ASHRAE/IESNA Standard 90.1-2007
--
2
SOLUTIONS TilROUGli LIST[NING
THIS DRAWING IS AN INSTRUMENT OF SERVICE. THE DRAWING AND THE INFORMATION THEREON IS THE PROPERTY OF OPTIMA ENGINEERING, P.A. ANY REPRODUCTION, ALTERATION, OR USE FOR OTHER THAN THE INTENDED PROJECT, WITHOUT THE WRITTEN CONSENT OF OPTIMA ENGINEERING, P.A. IS EXPRESSLY FORBIDDEN. COPYRIGHT ©OPTIMA ENGINEERING P.A. 2014, ALL RIGHTS RESERVED.
1
2
3
4
5
6
BID DOCUMENTS
CLOVERSCHOOL
SEQUENCE OF OPERATION
A COMPLETE AND OPERATIONAL DDC CONTROL SYSTEM (ENERGY MANAGEMENT SYSTEM, BAS) SHALL BE INSTALLED IN ACCORDANCE WITH THE SPECIFICATIONS (SECTION 230900) AND AS INTENDED ON THESE PLANS.
ALL CONTROL POINTS AND
EQUIPMENT SEQUENCES OF OPERATION LISTED IN SPECIFICATION SECTION 230900 SHALL BE CONSIDERED IN ADDITION TO THOSE LISTED HERE. IN THE EVENT THAT THE VERBIAGE IS IN CONFLICT OR CONTRADICTS THE REQUIREMENTS LISTED HERE, THE
QUESTION SHALL BE ASKED PRIOR TO BIDDING OR THE MORE STRINGENT SHALL APPLY. MECHANICAL CONTRACTOR SHALL COORDINATE ALL BAS INTEGRATION REQUIREMENTS WITH EQUIPMENT VENDORS AND CONTROLS CONTRACTOR PRIOR TO
PURCHASING EQUIPMENT AND PROVIDE ALL EQUIPMENT WITH COMMUNICATION/INTEltFACE CARDS AS REQUIRED FOR SYSTEM INTEGRATION.
CHll I FR PI ANT (PRIMARY/SECONDARY WITH AIR COOLED CHILLERS)
AIR HANDI ING UNITS
THE CHILLED WATER SYSTEM SHALL BE ENABLED TO OPERATE WHEN THE
OUTSIDE AIR TEMPERATURE IS ABOVE 50° F OR ANY CHILLED WATER CONTROL
VALVE IS COMMANDED OPEN FOR COOLING. THE CHILLED WATER SECONDARY
PUMPlNG SYSTEM SHALL BE STARTED FIRST. AFTER A ONE MINUTE DELAY, THE
CHILLER CONTROL PANEL SHALL BE ENABLED TO OPERATE THE CHILLERS AND
THE PRIMARY CHILLED WATER PUMPS. EACH CHILLER CONTROL PANEL SHALL
START EACH PRIMARY CHILLED WATER PUMP PRIOR TO THE START OF THE
ASSOCIATED CHILLER. AFTER PROOF OF PRIMARY CHILLED WATER FLOW IN THE
CHILLED WATER PRIMARY PIPING THE ASSOCIATED CHILLER WILL START. THE
BAS SHALL MONITOR AND DISPLAY PUMP COMMAND AND STATUS. (IF THE
CHILLER CONTROL PANEL DOES NOT PROVIDE FOR PUMP CONTROL, THIS SHALL
BE ACCOMPLISHED BY THE BAS.)
E -
CHILLER SUPPLY TEMPERATURE SHALL BE CONTROLLED BY CHILLER CONTROL
PANEL. THE BAS SHALL SEND A CHILLED WATER SUPPLY TEMPERATURE
SETPOINT COMMAND TO ALL CHILLER CONTROL PANELS. THE SETPOINT SHALL
BE MAINTAINED PER THE RESET SCHEDULE BELOW:
CHil I FD WATFR SUPPl Y TFMPFRATURF RFSFT SCHFDUI F (ADJ)
44° F CHS AT 85* F OUTSIDE AIR TEMPERATURE (OR ABOVE)
50° F CHS AT 60° F OUTSIDE AIR TEMPERATURE (OR BELOW)
CHS SHALL VARY LINEARLY BETWEEN THE HIGH AND LOW TEMPERATURES (AS
MEASURED IN THE CHS LOOP, NOT AT THE CHILLERS). THE INITIAL SETPOINT
FOR THE CHILLED WATER SUPPLY TEMPERATURE SHALL BE 44° F.
CHILLERS AND PRIMARY PUMPS SHALL BE SETUP IN A LEAD/LAG
CONFIGURATION. LAG PUMP AND CHILLER SHALL BE STARTED WHEN
SECONDARY LOOP SUPPLY WATER TEMPERATURE RISES ABOVE 4* F ABOVE
SETPOINT (ADJ). LAG PUMP AND CHILLER SHALL BE STOPPED WHEN
SECONDARY LOOP WATER SUPPLY TEMPERATURE RETURNS TO SETPOINT (ADJ).
TIME.
E LEA CHILLER AN PUMP SHALL E R TA D ON A
KLY BASIS.
THE BAS SHALL GENERATE AN ALARM IF THE CHILLED WATER SUPPLY
TEMPERATURE INCREASES 2° ABOVE THE INDICATED HIGH LIMIT FOR A PERIOD
0F 10 MINUTES. THE ENERGY MANAGEMENT SYSTEM SHALL MONITOR THE
PRIMARY PUMP COMMAND. THE BAS SHALL GENERATE AN ALARM IF THE
PUMP FAILS TO RUN, OR IF THE CHILLER CONTROLS INDICATE AN ALARM.
WHEN ACTIVATED, LAG CHILLER SHALL OPERATE FOR A MINIMUM OF 30
MINUTES, AND WHEN DEACTIVATED LAG CHILLER SHALL REMAIN IDLE FOR A
MINIMUM OF 30 MINUTES (ADJUSTABLE).
PUMP P-9 SHALL SERVE AS A STAND-BY PUMP TO BACKUP EITHER CHILLED
WATER PRIMARY PUMP. VALVES SHALL BE INSTALLED AS INDICATED TO
ALLOW IT TO NORMALLY RUN IN A PRIMARY/STAND-BY CONFIGURATION Nm
PUMP P-3. SHOULD PUMP P-4 FAIL, VALVES CAN BE MANUALLY ADJUSTED
SUCH THAT PUMP P-9 CAN RUN IN ITS PLACE. UNDER NORMALY OPERATION,
THE
DDC 41SYSTEM
SHALL ROTATE
RUNNING
PUMP
P-3 AND PUMP P-9 WITH
CHILLER
TO EQUALIZE
RUN TIMES
BETWEEN
PUMPS.
D -
THE CHILLED WATER SECONDARY PUMPS ARE VARIABLE FLOW PUMPS WITH
VARIABLE FREQUENCY DRIVES, SETUP IN A PRIMARY/STAND-BY
CONFIGURATION. THE BAS SHALL START THE VARIABLE SPEED CHILLED WATER
SECONDARY PUMPS. SECONDARY PUMP SPEEDS ARE CONTROLLED BY VFD'S.
THE BAS SHALL MONITOR THE VFD OPERATING SPEEDS AND ALARM
CONDITIONS. THE VARIABLE FREQUENCY DRIVES FOR THE PUMPS SHALL BE
CONTROLLED BY DIFFERENTIAL PRESSURE SENSORS IN THE CHILLED WATER
PIPING SYSTEM (SEE PIPING PLANS FOR SENSOR LOCATIONS). AS AIR
HANDLING EQUIPMENT CONTROL VALVES OPEN, PUMP SPEED SHALL BE
INCREASED VIA VARIABLE FREQUENCY DRIVE TO MAINTAIN SYSTEM PRESSURE
SETPOINT. THE INITIAL CHILLED WATER DIFFERENTIAL PRESSURE SETPOINT
SHALL BE 12 PSI, THIS SETTING SHALL BE ESTABLISHED DURING TESTING &
BALANCING. IF ONE OR MORE OF THE SENSORS ARE BELOW SETPOINT, THE
DRIVE SPEED SHALL BE INCREASED IN RESPONSE TO THE SENSOR WITH THE
LARGEST DEVIATION BELOW SETPOINT. IF ALL OF THE SENSORS ARE ABOVE
SETPOINT, THE DRIVE SPEED SHALL BE DECREASED IN RESPONSE TO THE
SENSOR WITH THE SMALLEST DEVIATION ABOVE SETPOINT. PROVIDE
DEAD-BAND AND/OR TIME DELAYS TO PREVENT RAPID CYCLING OF PUMPS
3-WAY CONTROL VALVES ARE PROVIDED WITH CERTAIN UNITS TO MAINTAIN
MINIMUM PUMP FLOW (SEE PIPING PLANS FOR UNIT LOCATIONS). STAND-BY
PUMP SHALL START AUTOMATICALLY UPON FAILURE OF PRIMARY PUMP, AND
AN ALARM INDICATING PUMP FAILURE SHALL BE SENT TO THE BAS. BAS
SHALL ALTERNATE PRIMARY AND STAND-BY PUMPS TO EQUALIZE RUN TIME.
THE BAS SHALL GENERATE AN ALARM IF THE SYSTEM PRESSURE DEVIATES
FROM SETPOINT BY GREATER THAN 6 PSI FOR MORE THAN 5 MINUTES, IF THE
STAND-BY PUMP FAILS TO START, OR IF THE VARIABLE FREQUENCY DRIVE
INDICATES AN ALARM. THE CHILLED WATER SECONDARY PUMPS SHALL
OPERATE FOR 10 MINUTES AFTER ALL CHILLERS ARE COMMANDED TO STOP.
C -
DEMAND CONTROL VENTILATION:
OUTSIDE AIR INTAKE SHALL BE PROVIDED WITH A MOTORIZED DAMPER. ON
UNIT START UP, THE OUTSIDE AIR INTAKE DAMPER SHALL REMAIN CLOSED
UNTIL THE RETURN AIR TEMPERATURE RISES ABOVE 65° F (ADJ) OR FALLS
BELOW 75* F. (ADJ). ONCE RETURN AIR TEMPERATURE IS SATISFIED, THE
OUTSIDE AIR DAMPER SHALL OPEN TO THE OCCUPIED MINIMUM SETPOINT.
OUTSIDE AIR DAMPERS AND AIR FLOW MONITORING STATIONS SHALL MODULATE
AS REQUIRED TO MAINTAIN MINIMUM OUTSIDE AIR FLOW. THE OUTSIDE AIR
INTAKE DAMPER SHALL BE CLOSED WHILE UNIT IS IN THE UNOCCUPIED MODE.
BAS SHALL BE CAPABLE OF OPENING AND CLOSING OUTSIDE AIR DAMPERS.
CO2 SENSOR MOUNTED IN THE RETURN DUCT SHALL MODULATE THE OUTSIDE
AIR DAMPER BASED ON CO2 LEVELS IN THE SPACE. DAMPER SHALL MODULATE
MU AT 200 PPM AN LARM SHA L E
T VATED F
E S A E CO2
LEVEL RISES ABOVE 1500 PPM. SEE AHU SCHEDULE FOR MINIMUM AND
DESIGN OUTSIDE AIR SETPOINTS
AIRSIDE ECONOMlZER CYCLE.
DURING THE OCCUPIED PERIOD, AND WHEN THE OUTSIDE AIR TEMPERATURE IS
BELOW 68* F. AND ABOVE 45° F AND THE OUTDOOR ENTHALPY IS BELOW 28
BTU/LB, THE ECONOMlZER CYCLE SHALL BE ENABLED. UNDER THOSE
CONDITIONS, THE OUTDOOR AIR DAMPER CAN MODULATE PAST ITS "DESIGN.,
POSITION TO FULL OPEN
MODULATING DAMPER CONTROL:
MODULATING RETURN, RELIEF, AND OUTSIDE AIR DAMPERS SHALL OPERATE IN
CONJUNCTION. RELIEF AND OUTSIDE AIR DAMPERS SHALL OPEN TO THE SAME
POSITION
ON DEMAND
CONTROL
OR INVERSE
ECONOMlZER
CONTROL), BASED
AND RETURN
DAMPER
SHALL VENTILATION
CLOSE TO THE
POSITION OF
THE OUTSIDE AND RELIEF DAMPER SETTINGS.
SHALL BE PROVIDED WHERE INDICATED IN THE AHU SCHEDULE
RETURN FAN SHALL START ALONG WITH OPENING OF ALL ASSOCIATED RETURN
AIR SMOKE DAMPERS AND ISOLATION DAMPERS. SUPPLY FAN SHALL START
AFTER PROOF OF THE RETURN FAN, AND ONCE ALL ASSOCIATED SUPPLY AIR
DAMPERS ARE OPEN. VARIABLE FREQUENCY DRIVE SHALL CONTROL RETURN
FAN TO MAINTAIN A CONSTANT DIFFERENTIAL FROM THE SUPPLY AIR VOLUME.
RETURN FAN CONTROL MAY BE OVERRIDDEN BY A BUILDING PRESSURE
SENSOR, IF THE BUILDING PRESSURE GETS OUT OF THE +/- 0.02" STATIC
PRESSURE RANGE FOR A PERIOD OF 10 MINUTES. ONCE BUILDING PRESSURE
IS SATISFIED, RETURN FAN CONTROL SHALL REVERT BACK TO TRACKING THE
SUPPLY FAN
HUMIDITY CONTROL (WHERE INDICATED):
OND æ MMæ M, HUMIDITY CONTROL SYSTEM
SHALL BE CAPABLE OF BEING ACTIVATED. UNDER NORMAL OPERATION, UNIT
SHALL CONTROLLED AS OUTLINED BELOW. PROVIDE HUMIDISTAT AS INDICATED
ON
PLANS,
IF SPACE
OR AND
RETURN
AIR HUMIDITY
65%SHALL
R.H. (ADJ),
ALARM
SHALL
BE SENT
HUMIDITY
CONTROLREACHES
SEQUENCE
BE
ACTIVATED. AIR HANDLING UNIT CHILLED WATER CONTROL VALVE SHALL BE
DRIVEN FULL OPEN. AND UNIT REHEAT COIL OR TERMINAL BOX REHEAT SHALL
MODULATE TO MAINTAIN SPACE TEMPERATURE. WHEN SPACE HUMIDITY DROPS
BELOW 55% R.H. (ADJ), BAS SHALL DEACTIVATE HUMIDITY CONTROL SEQUENCE.
CONTROL OF UNIT SHALL REVERT BACK AS INDICATED BELOW. BOLIER(S) AND
ASSOCIATED PUMP(S) SHALL BE STARTED IF THE HEATING PLANT IS IDLE AT
THE TIME THE HUMIDITY CONTROL SEQUENCE IS ACTIVATED.
THE VARIABLE VOLUME (VAV) TERMINAL UNITS SHALL BE CONTROLLED
INDEPENDENT OF SYSTEM PRESSURE FLUCTUATIONS BY AN APPLICATION
SPECIFIC DDC CONTROLLER UTILIZING ELECTRIC ACTUATION.
OCCUPIED AND UNOCCUPIED OPERATIONS ARE THE SAME, A
TEMPERATURE SENSOR SHALL BE UTILIZED TO MAINTAIN SPACE
TEMPERATURE SETPOINT. UPON A RISE IN SPACE TEMPERATURE ABOVE
SETPOINT, THE VOLUME DAMPER SHALL OPEN AS REQUIRED TO MAINTAIN
SPACE TEMPERATURE. UPON A DROP IN SPACE TEMPERATURE BELOW
SETPOINT, THE VOLUME DAMPER SHALL CLOSE UNTIL THE MINIMUM
DAMPER POSITION IS REACHED. UPON CONTINUED DROP IN SPACE
TEMPERATURE BELOW SETPOINT, THE HOT WATER CONTROL VALVE SHALL
BE MODULATED OPEN TO THE HEATING COIL AND THE TERMINAL UNIT
DAMPER SHALL OPEN TO THE HEATING CFM AS INDICATED IN THE
WAT
ONTR L VALVE SHALL CLOS
D THE DAMPER SHAL R
RN
TO THE MINIMUM POSITION
*
WHEN WARM AIR IS SENSED BY THE TERMINAL UNIT DURING MORNING
WARM-UP, THE DAMPER SHALL RESPOND TO THE SPACE TEMPERATURE.
THE TERMINAL UNIT DAMPER SHALL OPEN TO HEATING SETPOINT ON A
CALL FOR HEATING AND SHALL REMAIN CLOSED IF THE SPACE
TEMPERATURE IS AT OR ABOVE OCCUPIED SETPOINT. HOT WATER
CONTROL VALVE SHALL REMAIN CLOSED DURING MORNING WARM-UP.
THE TEMPERATURE SENSOR SHALL BE PROVIDED WITH AN OVERRIDE
FUNCTION THAT WILL PLACE THE SYSTEM IN THE OCCUPIED MODE FOR A
PERIOD OF UP TO 2 HOURS. THE OVERRIDE SHALL ACTIVATE THE SYSTEM
AHU AND THE HEATING OR COOLING CENTRAL PLANT AS REQUIRED TO
MAINTAIN SPACE TEMPERATURE
THERMOSTATS SHALL BE SET WITH INITIAL SETPOINTS OF 75° FOR COOLING
AND 72* FOR HEATING. TEMPERATURE SENSORS LOCATED IN CORRIDORS,
DINING AREAS, GYMNASIUMS, AND LOCKER ROOMS SHALL HAVE NO SETPOINT
ADJUSTMENT CAPABILITY AT THE WALL MOUNTED SENSORS. ALL OTHER
TEMPERATURE SENSORS SHALL BE PROVIDED WITH LIMITED MANUAL SETPOINT
ADJUSTMENT AT THE WALL MOUNTED TEMPERATURE SENSOR. PROVIDE
THE SYSTEM INTO OCCUPIED MODE FOR A PERIOD OF 2 HOURS (ADJ). ROOM
NERMOSTATS ARE INTEGRATED Nm NE OCCUPANCY SENSOR C 523BOLLING
THE LIGHTS, COORDINATE INTEGRATION REQUIREMENTS WITH THE ELECTRICAL
CONBACTOR. SEE SPECIFICATONS FOR ADDITONAL INFæMATON.
HEAT TAPE
HEAT
TAPE
FOR ABOVE
GRADEFOR
EXTERIOR
PIPING
AND WATER
CHILLERSYSTEM.
HEATER ASHALL
PROVIDE
FREEZE
PROTECTION
EXTERIOR
CHILLED
TEMPERATURE SENSOR SHALL BE PROVIDED WITHIN THE INSULATION ON ALL
EXTERIOR PIPING WITH HEAT TAPE TO VERIFY HEAT TAPE OPERATION. IF
W
, AN ALARM SHALL BE SENT AND
FXTFRIOR I IGHTING CONTROI SYSTFM
BAS SHALL INTERFACE WITH EXTERIOR LIGHTING CONTROL SYSTEM PROVIDED
BY THE ELECTRICAL CONTRACTOR (SEE ELECTRICAL PLANS). BAS SHALL
PROVIDE RELAYS FOR SIX CONTACTORS FOR EXTERIOR LIGHTING ZONES AND
PROVIDE TIME SCHEDULE CONTROL AND REMOTE OPERATION (ON/0FF) OF
ALL LIGHTING ZONES THROUGH THE BAS. SEE INFORMATION ON ELECTRICAL
PLANS AND COORDINATE WITH ELECTRICAL CONTRACTOR.
DUCTLESS SPLIT SYSTEMS:
DUCTLESS SPLIT SYSTEM UNITS SHALL BE PROVIDED WITH STAND ALONE
CONTROLS, PROGRAMMABLE THERMOSTATS BY UNIT MANUFACTURER=
SEPARATE FROM THE CENTRAL DDC SYSTEM. DDC VENDOR SHALL PROVIDE
TEMPERATURE SENSOR FOR THOSE ROOMS THAT WILL ALARM DDC SYSTEM
WHEN
TEMPERATURE
RANGE
OUT OF LIMITS.
UNIT FANS
SHALL
BE
STARTED
AND STOPPED
WITH ISTHERMOSTAT
CALL INDOOR
FOR COOLING.
UPON
A RISE
IN SPACE TEMPERATURE ABOVE THERMOSTAT SETPOINT, UNIT COMPRESSOR
SHALL ACTIVATE TO SATISFY SPACE CONDITIONS.
BOILERS AND HOT WATER PUMPS SHALL BE STOPPED/STARTED BY THE BAS
ON A PROGRAMMED BASIS. PRIMARY AND SECONDARY HOT WATER PUMPS
SHALL BE ENABLED, WITH LEAD BOILER AND ASSOCIATED PRIMARY HOT WATER
PUMP AND LEAD SECONDARY HOT WATER PUMP STARTED BY THE BAS.
FREEZE PROTECTION:
A MIXED AIR TEMPERATURE SENSOR SHALL BE LOCATED UPSTREAM OF THE
FIRST COIL IN THE AHU. UPON A DROP IN TEMPERATURE BELOW 40° F AT
THE MIXED AIR SENSOR, AN ALARM SHALL BE SENT TO THE CENTRAL BAS.
THE OUTSIDE AIR DAMPER SHALL BE OVERRIDDEN TO THE MINIMUM OCCUPIED
TOILET EXHAUST FANS
CENTRAL BAS SHALL OPERATE EXHAUST FANS ON A PROGRAMMED
SCHEDULE. FANS SHALL RUN WHEN ASSOCATED ZONE IS IN THE OCCUPIED
MODE, AND BE OFF WHEN ASSOCIATED ZONE IS IN THE UNOCCUPIED MODE.
SN A
A M
M & 20 ME (AM), M MM &
THE OA DAMPER SHALL RETURN TO NORMAL OPERATION. MIXED AIR
TEMPERATURE SHALL HAVE SOFTWARE RESET AND A 20 MINUTE DELAY (ADJ).
MW MN EMM
BAS SHALL STOP/START ENERGY RECOVERY VENTILATORS ON A
PROGRAMMED BASIS. FANS SHALL RUN CONTINUOUSLY WHILE IN THE
OCCUPIED MODE AND SHALL REMAIN OFF WHILE IN THE UNOCCUPIED MODE,
UNLESS OVERRIDDEN BY AN OCCUPANCY SENSOR (CONTROLLING THE LIGHTS)
IN ANY ROOM SERVED BY THE ERV. FANS SHALL DEENERGlZE WHEN
OCCUPANCY SENSOR SENDS OFF SIGNAL TO LIGHTS
C N
LS AND A ADNG SEQUENCER A
IRED TO MAN IN A S
HOT WATER SUPPLY TEMPERATURE PER THE RESET SCHEDULE BELOW
TEM
HOT WATER SUPPLY TEMPERATURE RESET SCHEDULE (ADJ)
160° F HWS AT 30° F. O A TEMP OR BELO
120° F. HWS AT 60° F. O.A. TEMP. (OR ABOVE)
HWS SHALL VARY LINEARLY BETWEEN THE HIGH AND LOW TEMPERATURES (AS
MEASURED IN THE HWS LOOP, NOT AT THE BOILERS). THE INITIAL SETPOINT
FOR THE HOT WATER SUPPLY TEMPERATURE SHALL BE 160° F.
BOILER STAGING SHALL EQUALIZE BOILER RUN TIME BY ROTATING LEAD BOILER
ON A WEEKLY BASIS. AN ALARM SIGNAL SHALL BE SENT TO THE ENERGY
MANAGEMENT SYSTEM IF THE HEATING SUPPLY WATER TEMPERATURE DROPS
MORE THAN 20*F BELOW THE OPERATING SETPOINT FOR A PERIOD OF 10
MINUTES. THE BAS SHALL ALSO GENERATE AN ALARM IF ANY BOILER OR
HOT WATER PUMP VARIABLE FREQUENCY DRIVE INDICATES AN ALARM.
THE HOT WATER SECONDARY PUMPS ARE VARIABLE FLOW PUMPS WITH
VARIABLE FREQUENCY DRIVES, SETUP IN A PRIMARY/STAND-BY
CONFIGURATION. THE BAS SHALL START THE VARIABLE SPEED SECONDARY
HOT WATER PUMPS. SECONDARY PUMP SPEEDS ARE CONTROLLED BY VFD'S.
THE BAS SHALL MONITOR THE VFD OPERATING SPEEDS AND ALARM
CONDITIONS. THE VARIABLE FREQUENCY DRIVES FOR THE PUMPS SHALL BE
CONTROLLED BY DIFFERENTIAL PRESSURE SENSORS IN THE HOT WATER PIPING
SYSTEM (SEE PIPING PLANS FOR SENSOR LOCATIONS). AS AIR HANDLING
EQUIPMENT CONTROL VALVES OPEN, LEAD PUMP SPEED SHALL BE INCREASED
VIA VARIABLE FREQUENCY DRIVE TO MAINTAIN SYSTEM PRESSURE SETPOINT.
THE INITIAL HOT WATER DIFFERENTIAL PRESSURE SETPOINT SHALL BE 12 PSI.
THIS SETTING SHALL BE ESTABLISHED DURING TESTING & BALANCING. IF ONE
OR MORE OF THE SENSORS ARE BELOW SETPOINT, THE DRIVE SPEED SHALL
BE INCREASED IN RESPONSE TO THE SENSOR WITH THE LARGEST DEVIATION
BELOW SETPOINT. IF ALL OF THE SENSORS ARE ABOVE SETPOINT, THE DRIVE
SPEED SHALL BE DECREASED IN RESPONSE TO THE SENSOR WITH THE
SMALLEST DEVIATION ABOVE SETPOINT. PROVIDE DEAD-BAND AND/OR TIME
DELAYS TO PREVENT RAPID CYCLING OF PUMPS.
3-WAY CONTROL VALVES
ARE PROVIDED WITH CERTAIN UNITS TO MAINTAIN MINIMUM PUMP FLOW (SEE
PIPING PLANS FOR UNIT LOCATIONS). STAND-BY PUMP SHALL START
AUTOMATICALLY UPON FAILURE OF PRIMARY PUMP, AND AN ALARM INDICATING
PUMP FAILURE SHALL BE SENT TO THE BAS. BAS SHALL ALTERNATE
PRIMARY AND STAND-BY PUMPS TO EQUALIZE RUN TIME.
THE BAS SHALL GENERATE AN ALARM IF THE SYSTEM PRESSURE DEVIATES
FROM SETPOINT BY GREATER THAN 6 PSI FOR MORE THAN 5 MINUTES, IF THE
STAND-BY PUMP FAILS TO START, OR IF THE VARIABLE FREQUENCY DRIVE
INDICATES AN ALARM. THE HOT WATER SECONDARY PUMPS SHALL OPERATE
FOR 10 MINUTES AFTER THE BOILER SYSTEM IS COMMANDED TO STOP.
A LOW VOLTAGE THERMOSTAT SHALL START PUMP ROOM VENTILATION FAN
WHEN BOILER ROOM TEMPERATURE RISES ABOVE 85* F (ADJUSTABLE). RELIEF
DAMPER SHALL BE INTERLOCKED WITH FAN.
A CARBON MONOXIDE/OXYGEN DEPLETION SENSOR SHALL BE PROVIDED IN THE
BOILER ROOM AND SHALL ACTIVATE AN AUDIBLE AND VISUAL ALARM INSIDE
THE BOILER ROOM, ACTIVATE THE VENTILATION FAN, AND SEND AN ALARM TO
THE CENTRAL BAS IF ACTIVATED.
A PUSHBUTTON EMERGENCY GAS SHUTOFF SWITCH SHALL BE PROVIDED AT
THE BOILER ROOM TO CLOSE A SOLENOID VALVE IN THE GAS LINE SERVING
HVAC AND DOMESTIC WATER HEATING EQUIPMENT. ACTIVATION OF THE SWITCH
SHALL CLOSE THE GAS VALVE AND ALARM THE CENTRAL BAS (VALVE AND
SWITCH BY E.C.)
A FREEZE-STAT SHALL BE LOCATED UPSTREAM OF THE COOLING COIL, AND
SHALL SHUT DOWN THE AHU FANS AND ALARM THE CENTRAL BAS IF THE
TEMPERATURE IS BELOW 38° F. THE SECONDARY CHILLED WATER PUMP AND
THE HOT WATER PUMP SHALL START, AND THE HOT WATER AND CHILLED
WATER CONTROL VALVES AT THE AIR HANDLING UNIT SHALL OPEN FULLY.
FREEZE-STAT SHALL HAVE MANUAL RESET ONLY.
SINGLE ZONE VARIABLE VOLUME (SZVAV) AIR HANDLING UNITS:
A TEMPERAUTRE SENSOR SHALL BE UTILIZED TO MAINTAIN SPACE
TEMPERATURE. THE UNIT SUPPLY FAN SHALL START AT LOW SPEED. ON A
RISE IN TEMPERATURE ABOVE SETPOINT, THE CHILLED WATER CONTROL VALVE
SHALL OPEN TO THE CHILLED WATER COIL. ON A CONTINUED RISE IN
TEMPERATURE, VARIABLE FREQUENCY DRIVE SHALL INCREASE AIR FLOW TO
SATISFY SPACE TEMPERATURE REQUIREMENTS. AS THE SPACE TEMPERATURE
DROPS BELOW SETPOINT, THE FAN SPEED SHALL RESET FROM MAXIMUM TO
MINIMUM. AS THE SPACE TEMPERATURE CONTINUES TO DROP, THE CHILLED
WATER CONTROL VALVE SHALL CLOSE TO THE COOLING COIL AND THE HOT
WATER CONTROL VALVE SHALL OPEN TO THE HEATING COIL. ON A CONTINUED
DROP IN SPACE TEMPERATURE, THE SUPPLY FAN SPEED SHALL INCREASE TO
MAINTAIN SETPOINT. THE TEMPERATURE SENSOR SHALL BE PROVIDED WITH
AN OVERRIDE FUNCTION THAT WILL PLACE THE SYSTEM IN THE OCCUPIED
MODE FOR A PERIOD OF UP TO 2 HOURS.
BAS SHALL HAVE GLOBAL CONTROL OVER DOMESTIC WATER HEATING SYSTEM.
WATER HEATERS SHALL CYCLE ON AND OFF BASED ON THEIR TANK
TEMPERATURES, TO MAINTAIN 140' FOR WH-1 AND 110° FOR WH-2. AN
ALARM SHALL BE GENERATED SHOULD EITHER TANK DEVIATE FROM SETPOINT
BY 10° EITHER HIGH OR LOW. AN ALARM SHALL ALSO BE GENERATED
SHOULD THE DOMESTIC HWS TEMPERATURE DEVIATE FROM SETPOINT BY 10°
EITHER HIGH OR LOW. CIRCULATION PUMPS SHALL OPERATE ON A
SCHEDULED BASIS BASED ON BUILDING OCCUPANCY. THE PUMPS SHALL BE
CAPABLE OF OPERATING ON SEPARATE SCHEDULES, SHOULD THE KITCHEN
SCHEDULE DIFFER FROM THE ENTIRE BUILDING. A TEMPERATURE SENSOR
SHALL BE MOUNTED IN THE END OF THE LINE CAPABLE OF OVERRIDING THE
PUMPS SHOULD THE LOOP TEMPERATURE FALL BELOW 130° FOR CP-L OR
100* FOR CP-2. BAS SHALL ALSO MONITOR BOTH DOMESTIC HWR
TEMPERATURES AND DOMESTIC WATER SUPPLY TEMPERATURE FOR TRACKING
PURPOSES. SEE PLUMBING PLANS FOR ALL TEMPERATURE SENSOR
CLOVER
REPLACEMENT
MIDDLE SCHOOL
FREEZE PROTECTION (LOSS OF POWER)
DURING A POWER OUTAGE, THE EMERGENCY GENERATOR SHALL PROVIDE
POWER TO THE BOILERS AND HOT WATER PUMPS TO PROVIDE MINIMAL FREEZE
PROTECTION THROUGHOUT THE BUILDING. ON A LOSS OF POWER AND THE
OUTSIDE AIR TEMPERATURE BELOW 45° (ADJ), ALL HOT WATER CONTROL
VALVES SHALL FAIL OPEN AND ALL OUTSIDE AIR DAMPERS SHALL FAIL
CLOSED. THE BOILERS AND HOT WATER PUMPS SHALL BE STARTED AND
SHALL CIRCULATE THROUGH ALL HOT WATER HEATING COILS.
HEAT TAPE FOR EXTERIOR PIPING AT CHILLER AND CHILLER HEATER CIRCUIT
SHALL BE PROVIDED WITH EMRGENCY POWER TO PROVIDE FREEZE PROTECTION.
A TEMPERATURE SENSOR SHALL BE PROVIDED WITHIN THE INSULATION ON ALL
EXTERIOR PIPING WITH HEAT TAPE TO VERIFY HEAT TAPE OPERATION. IF
TEMPERATURE FALLS BELOW 35° F. (ADJ), AN ALARM SHALLL BE SENT AND
Of
fleef
1927SouthTryonSt.,Suite300,CharlotteNC28203
Phone: 704-338-1292 042
www.optimapa.com
North Carolina License Number C-0914
KITCHEN EQUIPMENT FREEZER AND COOLER CONTROL
PROVIDE NEW WALL MOUTED TEMPERATURE SENSORS TO MONITOR THE
TEMPERATURES IN THE FREEZER AND COOLER.
HVAC SCHEDULING
INITIAL SCHEDULES OF OPERATION SHALL BE COORDINATED AND CONFIRMED
BY THE OWNER, AND PROGRAMMED BY THE CONTROLS CONTRACTOR.
MODIFICATION OF SCHEDULES SHALL BE A PART OF REQUIRED OWNER
TRAINING. DISCREET SCHEDULES SHALL BE PROVIDED FOR EACH AIR
HANDLING UNIT.
SCHOOL CALENDAR SHALL BE PROGRAMMED INTO THE BAS SUCH THAT THE
SYSTEMS
UNOCCPUIED ON DAYS THE SCHOOL IS CLOSED AND ON
TEACHER REMAIN
WORKDAYS
ADMINISTRATION AREA SHALL REMAIN IN THE OCCPUIED MODE DURING THE
SUMMER, EXACT HOURS TO BE COORDINATED WITH THE OWNER.
REMAINING AIR HANDLING UNITS SHALL BE INITIALLY SET TO BE IN THE
OCCUPIED MODE FROM 30 MINUTES BEFORE THE OPENING BELL TO 30
MINUTES PRIOR TO THE CLOSING BELL, UNTIL MODIFIED BY START/STOP
OPTIMlZATION. AFTER HOURS OPERATION FOR ALL ZONES SHALL BE
COORDINATED WITH THE OWNER WITH INPUT FROM THE KITCHEN, ATHLETIC,
LIBRARY, AND FINE ARTS STAFF.
JWMEDESIGNTRANSPORM
227WEST TRADESTREET SUITE700
CHARLOTTE NORTH CAROLINA 28202
START/STOP OPTIMlZATION
BAS SHALL PROVIDE START/STOP OPTIMlZATION (SS0) FOR ALL EQUIPMENT
AND SYSTEMS. SSO SHALL BE CAPABLE OF LEARNING BUILDING THERMAL
CHARACTERISTICS AND RESPOND TO VARIABLE CONDITIONS. SSO SHALL
START/STOP CONTROLLED EQUIPMENT AS LATE AS POSSIBLE PRIOR TO
OCCUPIED TIME PERIOD AND AS EARLY AS POSSIBLE PRIOR TO UNOCCUPIED
TIME PERIOD. SSO SHALL BE CALCULATED BASED ON OUTDOOR AIR
TEMPERATURE, ZONE TEMPERATURES, AND CONTROL SETPOINT SETBACK
TEMPERATURES.
TEL. 704.333.6686
FAX 704.333.2926
WWW.LS3P.COM
untras
CA
OPTIMA
ENGINEERING
No. C00710
WALL/UNIT HEATERS
A BUILT-IN THERMOSTAT SHALL OPERATE WALL/UNIT HEATER AND FAN TO
MAINTAIN A SETPOINT OF 49° (ADJ). ONCE THE UNIT HEATER IS ENERGlZED,
IT WILL RUN FOR AT LEAST FIVE MINUTES TO AVOID SHORT CYCLING. BAS
DOES NOT INTERFACE WITH UNIT HEATERS.
THE HOT WATER SYSTEM WILL BE COMMANDED TO RUN IF THE OUTDOOR
TEMPERATURE IS BELOW 60T OR ANY HOT WATER CONTROL VALVE IS
COMMANDED OPEN FOR HEATING OR DEHUMIDIFICATION.
A -
WHILE IN THE OCCUPIED MODE THE SUPPLY FAN SHALL OPERATE
CONTINUOUSLY. WHILE IN THE UNOCCUPIED MODE, THE UNIT SUPPLY FAN
SHALL CYCLE WITH HEATING AND COOLING LOADS, THE CHILLED WATER AND
HOT WATER CONTROL VALVES SHALL BE CLOSED TO THE UNIT. UPON A CALL
FOR HEATING OR COOLING TO MEET UNOCCUPIED SETPOINTS, THE UNIT FAN
SHALL BE STARTED AND THE UNIT SHALL OPERATE AS DESCRIBED BELOW AS
REQUIRED BY THE SPACE TEMPERATURE. THE BOILER PLANT OR CHILLER
PLANT SHALL ALSO BE STARTED AS REQUIRED TO SATISFY SETPOINTS. THE
UNIT AND ASSOCIATED CENTRAL PLANT SHALL OPERATE FOR A MINIMUM OF
30 MINUTES (OR AS REQUIRED TO SATISFY UNOCCUPIED SETPOINT) AND
SHALL NOT BE ALLOWED TO RESTART FOR A MINUM OF 15 MINUTES
FOLLOWING SATISFACTION OF UNOCCUPIED SETPOINT AND SYSTEM SHUT-DOWN.
DOMFSTIC HOT WATFR SYSTFM
SMOKE DETECTION & AHU SHUTDOWN:
UPON DETECTION OF SMOKE IN THE AIR HANDLING SYSTEM BY THE
DUCT-MOUNTED RETURN AIR SMOKE DETECTOR, AN ALARM CONDITION SHALL
BE SENT TO THE BUILDING FIRE ALARM SYSTEM AND ALL AIR HANDLING UNITS
SHALL BE SHUTDOWN BY THE BUILDING FIRE ALARM SYSTEM. THE BUILDING
FIRE ALARM SYSTEM SHALL PROVIDE ONE DIGITAL OUTPUT TO THE BAS TO
INDICATE ACTIVATION OR FAILURE OF ANY SMOKE DETECTOR.
BOILER PLANT PRIMARY SECONDARY WITH CONDENSING BOILERS
B -
VARIARI F AIR VOI UMF ROXFS
AIR HANDLING UNITS SHALL BE STOPPED/STARTED ON A TIME OF DAY
SCHEDULE THROUGH THE BAS. THIS SCHEDULE SHALL BE MODIFIED BY A
START STOP OPTIMlZATION PROGRAM. UPON PROOF OF AIR FLOW THRU THE
SUPPLY FAN, AS SENSED BY A RESPECTIVE CURRENT SENSING RELAY, THE
NORMALLY CLOSED OUTSIDE AIR DAMPER SHALL BE ENABLED.
.....
OF
ifmin
MISC. EXHAUST FANS
PROVIDE WALL SWITCHES, WALL THERMOSTATS, INTERLOCKS, ETC. AS
INDICATED ON THE FAN SCHEDULE TO CONTROL FANS AS INDICATED ON
PLANS. BOILER ROOM AND ELECTRICAL ROOM THERMOSTATS SHALL BE SET
AT 85* F. (USER ADJUSTABLE, BAS REMOTE).
lH1888
2
7
rñ
MEMBERSOFTHEAMERICANINSTITUTEOFARCHITECTS
FIELD HOUSE SPLIT SYSTEM
UNIT SHALL BE CONTROLLED BY ITS TEMPERATURE SENSOR. UNIT SUPPLY
FAN SHALL RUN CONTINUOUSLY IN THE OCCUPIED MODE, CYCLE WITH
HEATING AND COOLING WHILE UNOCCUPIED. UPON A RISE IN SPACE
TEMPERATURE, UNIT COMPRESSOR AND CONDENSER FAN SHALL ACTIVATE TO
SATISFY SPACE. UPON A DROP IN SPACE TEMPERATURE, UNIT COMPRESSOR
SHALL ACTIVATE IN REVERSE CYCLE FOR HEATING. UPON A FURTHER DROP
IN SPACE TEMPERATURE, ELECTRIC HEAT SHALL BE ENERGlZED TO SATISFY
SPACE TEMPERATURE. THERMOSTATS SHALL PROVIDE A DEADBAND OF 5*,
WITHIN WHICH THE SUPPLY OF HEATING OR COOLING ENERGY TO THE ZONE
CAN BE REDUCED TO THE MINIMUM. THE TEMPERATURE SENSOR SHALL BE
PROVIDED WITH AN OVERRIDE FUNCTION THAT WILL PLACE THE SYSTEM IN
THE OCCUPIED MODE FOR A PERIOD OF UP TO 2 HOURS.
COPYRIGHT 2014 ALL RIGHTS RESERVED
PRINTED OR ELECTRONIC DRAWINGS AND
DOCUMENTATION MAY NOT BE REPRODUCED
INANYFORMWITHOUTWRITTENPERMISSION
FROM LS3P ASSOCIATES LTD.
REVISIONS:
-
No
Description
PROJECT:
9201-131360
DATE:
DRAWN BY:
OCT.31,2014
SRD
Date
NOTES-
VARIABLE AIR VOLUME (VAV) AIR HANDLING UNITS:
A DISCHARGE AIR TEMPERATURE SENSOR SHALL CONTROL CHILLED WATER AND
HOT WATER CONTROL VALVES TO MAINTAIN SUPPLY AIR TEMPERATURE PER
THE RESET SCHEDULE BELOW.
1. SEE SPECIFICATIONS FOR ADDITIONAL REQUIREMENTS.
2. ALL CONTROL SETPOINTS SHALL BE ADJUSTABLE AND TRENDABLE BY THE
USER WITHOUT ASSISTANCE FROM THE CONTROLS MANUFACTURER. THIS
SHALL BE COVERED AS PART OF TRAINING WITH OWNER, SCHOOL STAFF,
AND MAINTENANCE DEPARTMENT. INDICATED SCHEDULES AND SETPOINTS
SHOULD BE USED FOR ORIGINAL SYSTEM SET-UP. ANY CHANGES IN
SETPOINT SETTINGS REQUIRED FOR INTENDED SYSTEM OPERATION SHALL
BE APPROVED BY THE ENGINEER AND SHALL BE DISCREETLY INDICATED
SUPPLY AIR TEMPERATURE RESET SCHEDULE (ADJ)
55° F. HWS AT 70° F. O.A. TEMP. (OR ABOVE)
65° F. HWS AT 30° F. O.A. TEMP. (OR BELOW)
SUPPLY AIR TEMPERATURE SHALL VARY LINEARLY BETWEEN THE HIGH AND
ON THE AS-BUILT DRAWINGS.
LOW TEMPERATURES. THE INITIAL SETPOINT FOR THE DISCHARGE AIR SUPPLY
TEMPERATURE SHALL BE 60° F. SUPPLY AIR TEMPERATURE SETPOINT SHALL
HAVE A HIGH LIMIT OF OF 62° REGARDLESS OF OUTSIDE AIR TEMPERATURE,
WHEN ANY ZONE ON THE AHU HAS A CALL FOR COOLING.
3. CURRENT SWITCHES SHALL BE PROVIDED IN THE PIPING OF EACH PUMP TO
VERIFY PUMP STATUS.
4. PHOTOELECTRIC TYPE DUCT SMOKE DETECTORS WILL BE PROVIDED BY THE
ELECTRICAL CONTRACTOR, INSTALLED IN THE DUCT BY THE MECHANICAL
CONTRACTOR AND WIRED TO SHUT-DOWN THE UNIT BY THE ELECTRICAL
CONTRACTOR.
5. ELECTRICAL CONTRACTOR SHALL PROVIDE A DEDICATED 120V CIRCUIT IN A
J-BOX FOR CONTROL POWER. CONTROLS CONTRACTOR SHALL EXTEND
120V POWER FROM J-BOX TO CONTROL PANELS, DAMPER ACTUATORS=
TRANSFORMERS, ETC. AS REQUIRED FOR INSTALLATION OF THE CONTROL
SYSTEM. ALL CONTROL TRANSFORMERS SHALL BE SEPARATELY
INTERNALLY FUSED OR HAVE MANUAL RESETS.
6. BAS SHALL ALLOW GLOBAL OPERATION OF HOT WATER AND CHILLED WATER
CONTROL VALVES.
7. CONTROLS CONTRACTOR SHALL PROVIDE A MINIMUM OF 8 HOURS OF
OWNER TRAINING PROVIDED BY A FACTORY CERTIFIED REPRESENTATIVE.
COORDINATE THROUGH THE MECHANICAL CONTRACTOR AND CONSTRUCTION
MANAGEMENT FIRM.
8. THE SEQUENCE OF OPERATION OF OPERATION AND POINTS LIST IS
INTENDED TO COMMUNICATE THE MINIMUM REQUIREMENTS AND GENERAL
DESIGN INTENT TO THE CONTROLS CONTRACTOR AND IS NOT INTENDED TO
BE A FULLY DEVELOPED OR COMPLETE SEQUENCE OF OPEARTION. IN THE
CONTROLS SUBMITTAL THE CONTROLS CONTRACTOR SHALL FULLY DEVELOP
THE SEQUENCE OF OPERATIONS FOR ALL SYSTEMS IDENTIFIED AN SHALL
PRESENT ALL SETPOINTS, CONTROL PARAMETERS, TIME DELAYS, ALARM
POINTS, ETC. AS REQUIRED TO COMPLY WITH THE DESIGN INTENT. THE
CONTROLS CONTRACTOR SHALL INCORPORATE STANDARD FEATURES SUCH
THE STATIC PRESSURE SENSOR IN THE SUPPLY DUCT SHALL MODULATE THE
VARIABLE FREQUENCY DRIVE TO MAINTAIN THE SETPOINT ESTABLISHED DURING
FINAL TESTING AND BALANCING. THE PRELIMINARY SETPOINT SHALL BE 0.75"
STATIC PRESSURE. THIS SETPOINT SHALL BE RESET BASED ON THE ZONE
REQUIRING THE MOST PRESSURE; LE., THE SETPOINT IS RESET LOWER UNTIL
ONE TERMINAL BOX DAMPER IS NEARLY WIDE OPEN.
GAS/DX ROOFTOP UNITS
A TEMPERATURE SENSOR SHALL BE UTILIZED TO MAINTAIN SPACE
TEMPERATURE.
UNIT SUPPLY FAN SHALL RUN CONTINUOUSLY IN THE
OCCUPIED MODE, CYCLE WITH HEATING AND COOLING WHILE UNOCCUPIED.
UPON A RISE IN SPACE TEMPERATURE, UNIT COMPRESSORS AND
CONDENSER FANS SHALL ACTIVATE IN STAGES TO SATISFY SPACE. UPON
A DROP IN SPACE TEMPERATURE, GAS HEAT SHALL BE ACTIVATED IN
STAGES TO SATISFY SPACE TEMPERATURE. INTERNAL UNIT CONTROLS
SHALL OPERATE ENTHALPY ECONOMlZER WHEN OUTSIDE AIR ENTHALPY IS
LOWER THAN RETURN AIR ENTHALPY. THERMOSTATS SHALL PROVIDE A
DEADBAND OF 5*, WITHIN WHICH THE SUPPLY OF HEATING OR COOLING
ENERGY TO THE ZONE CAN BE REDUCED TO THE MINIMUM. THE
TEMPERATURE SENSOR SHALL BE PROVIDED WITH AN OVERRIDE FUNCTION
THAT WILL PLACE THE SYSTEM IN THE OCCUPIED MODE FOR A PERIOD OF
UP TO 2 HOURS.
CHECKED BY: RVA
SE
-
UENCE OF
OPERATION
AS MINIMUM RUN TIME DELAYS AND DEAD BANDS TO PREVENT SHORT
CYCLING. ALL MONITORED POINTS SHALL INCLUDE EARLY HIGH/LOW ALARM
NOTIFICATIONS PRIOR TO REQUIRED CORRECTIVE ACTIONS OR UNIT
SHUT-DOWNS. CONTROL CONTRACTOR SHALL SPECIFY IN THE CONTROL
SUBMITTAL FAIL SAFE POSITION FOR OUT OF RANGE, FAIL SAFE
POSITIONING FOR OPEN CIRCUITS OR LOSS OF COMMUNICATION.
OPTIMA # 13-0238
4 OF 26
SOLUTIONS THROUGH LISTENING
THIS DRAWING IS AN INSTRUMENT OF SERV CE. THE DRAWING AND THE INFORMATION THEREON IS THE PROPERTY OF OPTIMA ENGINEERING, P.A. ANY REPR()DUCTION, ALTERATION, OR USE FOR OTHER THAN THE INTENDED PROJECT, WITHOUT THE WRITTEN CONSENT OF OPTIMA ENGINEERING, P.A. IS EXPRESSLY FORBIDDEN. COPYRIGHT ©OPTIMA ENGINEERING P.A. 2014, ALL RIGHTS RESERVED.
1
2
3
4
5
6
BID DOCUMENTS
CLOVERSCHOOL
INPUT/OUTT UT SUMMARY
DISmCT mO
INPUTS
M -ASURED
-
OUTF JTS
BliAR''
CALC.
DIGITAL
SYSTEM,
RE
3YS1 EM FEATURES
ANALOG
ALARMS
l'ROCRAM3
z
GENETAL
540²
P0
SUPPLMENT.
DESCRIPTION
CLOVER SCHOOL DISTRICT
540T
"
E ChElar Plant
X X X
Chiller #1 On/off
X
Chiller #1 Panel Interface
Chiller #2 On/off
X X
ne neerface
X X
Primary CHR Temp
Primary Pump P-3
Primary Pump P-4
Primary Pump P-9
Secondary Pump P-1
Secondary Pump P-2
Secondary CHS Temp
Secondary CHR Temp
Differential Pressure
Boger Plant (Prl/Sae)
Boiler Sequencer Interface
Boiler #1 On/Off
X
Boiler #2 Status
Primary HWS Temp
Primary HWR Temp
Primary Pump P-7
Primary Pump P-8
Secondary Pump P-5
Secondary Pump P-6
Secondary HWS Temp
Secondary HWR Temp
Differential Pressure
X
X X
X X
X
X
X
X
X X X X
X
X
X
X X
X X
X
X
X
CLOVER
X
X
X X X X *
X
X
X
X
X
X
X
X
X
X
X
X
X
Building Loop
Building Loop
Building Loop (Typ of 2)
X
X X X
X
X
X
X
X
X
X
X X X X
X
1927 South Tryon St., Suite 300, Charlotte NC 28203
X
Phone: 704-338-1292 042
www.optimapa.com
North Carolina License Number C-0914
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
Building Loop
Building Loop
Building Loop (Typ of 2)
X
X
X
X
X
227 WEST TRADE STREET
SUITE 700
CHARLOTTE, NORTH CAROLINA 28202
TEL. 704.333.6686
FAX 704.333.2926
WWW.LS3P.COM
X
X
X
X
X
X
Smoke Detector
X
OA Damper
OA Airflow Mon. Station
Relief Damper
untIts
X
X
X
Retum Damper
Retum Fan VFD on/off
OPTIMA
X
Retum Fan VFD Speed
Where
Where
Where
Where
X
X
Retum Fan VFD Status
Building Pressure
Filter Status
X
X
Indicated
Indicated
Indicated
Indicated
PA
No. C00710
HHHG
X
X
X
X
X
Freezestat
CHW Valve
HW Reheat Valve
Supply Fan
Supply Fan VFD on/off
Supply Fan VFD Speed
Supply Fan VFD Status
Supply Static Pressure
Supply Temp
Space CO2
Space Humidity
Space Temp
Over-ride
-
X
Retum RH
Retum CO2
Mixed Air Temp
HW Preheat Valve
MIDDLE SCHOOL
X
X
X
X
X
Air Handlina Unita
c -
REPLACEMENT
X
Boiler Rm Oxygen Depletion
Boiler Rm Gas Solenoid
Retum Temp
X
X
Boiler #1 Status
Boiler #2 On/Off
D -
X
X
Chiller #1 Status
Primary CHS Temp
X
X
lHIHf
X
X
X
X
X
CV Only
SZVAV & VAV Only
SZVAV & VAV Only
X
X
X
X
..
2
SZVAV & VAV Only
X
VAV Only
X
10/31M
X
X
X
X
X
MEMBERS OF THE AMERICAN INSTITUTE OF ARCHITECTS
CV & SZVAV Only
CV & SZVAV Only
X
COPYRIGHT 2014 ALL RIGHTS RESERVED
PRINTED OR ELECTRONIC DRAWINGS AND
DOCUMENTATION MAY NOT BE REPRODUCED
IN ANY FORM WITHOUT WRITTEN PERMISSION
FROM LS3P ASSOCIATES LTD.
VAV Bar
Volume Damper
HW Valve
Discharge Temp
Over-ride
X
X
X
X
X
Setpoint Adjust
B -
Space Temp
REVISIONS:
X
_
X
No.
Description
Date
Fnernv Renownrv Ventilators
Supply Fan
X
X
Exhaust Fan
X
X
Misc. Pointe
OA Temp
OA CO2
Dew Point
Elec Demand
X
X
X
X
X
X
X
X X
Domestic Water Meter
Gas Meter
-
X
X
X
Fire Alarm Status
Exterior Lighting Control
-
X
X
X
Typical of 6 Contactors
Freezer Temp
X
X
DATE:
OCT. 31, 2014
Cooler Temp
X
X
DRAWN BY:
SRD
Toilet Fans
Misc. Fans
Domestic HW Pump
Domestic HWS Temp
Domestic HWR Temp
Storage Tank
End of Line Loop Temp
Domestic Water Supply
Heat Tape
X
X
X
X
X
X
X
X
X
X
CHECKED BY: RVA
See Fan Schedule
Typical of 2
Typical of 2
Typical of 2
Typical of 2
Typical of 2
X
X
MECHANICAL
TYP OF 4
GENERAL NOTE:
INPUT/OUTPUT SUMMARY IS A GENERAL LISf OF CONTROL POINTE REQUIRED FOR TH : OPERATION O THE MEC IANICAL SYS EM. IN ADDlllON TO CONTROL
POINTS INDICATED, THE CONTROLS JONTRACTOR SHALL BE RESPCNSIBLE FOR PROVIDNG ADDITIONAL POINTS A: REQUIRED FOR OPERATION OF THE MECHANICAL
SYSTEM AS SPECIFIED AND OUTLINED IN THl: SEQUENCE OF OPERiTION AhD TO COM *LY WITH THE :PECIFICATloNS.
nm
OPTIMA # 13-0238
5 OF 26
SOLUTIONS THROUGH LISTENING
THIS DRAWING IS AN INSTRUMENT OF SERVICE. THE DRAWING AND THE INFORMATION THEREON IS THE PROPERTY OF OPTIMA ENGINEERING, P.A. ANY REPRODUCTION, ALTERATION, OR USE FOR OTHER THAN THE INTENDED PROJECT, WITHOUT THE WRITTEN CONSENT OF OPTIMA ENGINEERING, P.A. IS EXPRESSLY FORBIDDEN. COPYRIGHT ©OPTIMA ENGINEERING P.A. 2014, ALL RIGHTS RESERVED.
1
2
3
4
5
6
BID DOCUMENTS
CLOVER SCHOOL
DISTRICT TWO
10"ø
315-E
515+E
10"ø
.
=
2.2
260-D
CS B
260 D
8xf UP TO
CLOVER SCHOOL DISTRICT
1 F[
10"ø
WØ
suh cMd. ma æv
amnenn
300-E
E 300-E
300-E
P
300-E
P
M
P
CLOVER
REPLACEMENT
MIDDLE SCHOOL
52x24
5 D
P
170-D
6
C
to"ø
320-E
320 E
2M-D
1FE
12"ø
654
200-D
-
- "ø
0"ø
L F
440-
180-K
12"ø
280-D
N
-
10=
265+·D
2 5-D
10"ø
265[ -D
P
P
10"ø
---
210- D
320-E
.
320+E
n -r
__..
280-D
280- )
rrrrr mn
10"#
6"ø- ·
10"ø
210-D
·
c
150 -D
10"ø
2"ø
1927 South Tryon St., Suite 300, Charlotte NC 28203
P
A
270hD
420-E
8"p
D -
--
.._ _
.--
12 12
200-D
MO C
K
imo
; 70-D
280-D
- 8"ø
420-
-
280-0
K
LS P
12" t
100+C
"ø
18×16
SP
32×
54x 8
40x20
t
5-C
6"ø
ST DUCT IP
OF CAP)_
TO
.
, f 50-E(
8"
FXHAUST DUCT
L P TO ROO
-E
::
210 D
::
190-D
370
--
420-E
420-E
420-
420-F
-
P
50
10"p
6"ø
38
10"ø
10"ø
33
P
2 0-D
o
; 70-D
420-E
RI$E
10"ø
350- E
P
N
350- :
Phone: 704-338-1292 042
www.optimapa.com
North Carolina License Number C-0914
420-E
-12"ø
1 "ø
440-:
10"ø
240 D
227 WEST TRADE STREET
SUITE 700
CHARLOTTE, NORTH CAROLINA 28202
TEL. 704.333.6686
FAX 704.333.2926
WWW.LS3P.COM
.
6",
305-E
335-E
240K
240-[
K
10"1
FD
4
-12"ø
420-
420-F
440-:
111111
10"ø
0"ø
110-C
F
-AliV-3 HLMIDISTAT NEE
SEQUEhlCE OF OP R 101
-
1
.......
ø
12"ø
100 C
75 -B
42u-E
305 -E
10"ø
1M-C
r
-E
335-E
.
350- E
K
+1ox10
.*ø
..
3bO- -
10"ø
Ó
305 -E
420-E
420-E
-129
420-
305-E
P
(EX END 8"ø E(HAUST
DUCT TO WALL LOUVER)
-
P TO
--
--
ERING
No. C00710
10x1C STAINLESS STEEL
STEEi DUCT UP TO
EAN_ --I ON RO)F
ON ROOF
10"ø
ENG
420-E
10x10
..
10
=
440-
-*-
KILN WITH VENT FAN (BY OTHERS), PROVIDE 4"ø
11111##
EMENTS WI
K N MANUFACTURE
L
12'ø
P
Mx¼ ,
12"
305-E
-- -
123
- -16x4
12"ø
335-E
40$-E
- -16x4
1
N
22×
1GK
N NOOD
- -···
ROOF
6"ø
+
4 ø R G DR R VENT DO
IN WALL TO DRYER
-
160-
1D"p
320-P
MEMBERS OF THE AMERICAN INSTITUTE OF ARCHITECTS
_
10
6"ø
1 x1
- 100-K
340-P
K
T( l
P
-.,--r·~····
16x4 EXHAUST DUCT DOWN
TO DISHWASHER (SEE 14/M-402)
-.
22xTS
10.
16x14
14×14
75-K
22x
COPYRIGHT 2014 ALL RIGHTS RESERVED
PRINTED OR ELECTRONIC DRAWINGS AND
DOCUMENTATION MAY NOT BE REPRODUCED
IN ANY FORM WITHOUT WRITTEN PERMISSION
FROM LS3P ASSOCIATES LTD.
6"ø
-
r
1
W
10×10
\ 40k14
REVISIONS:
_
B o
------
K
12"ø
l-l
1bO-b
CHlHFR @
SUP
SS10
S
A -
A2
EX|-|AU_SI
4800
-600
MAKE-_U.P_
-3840
--
250
--
HIV-1
--
--
800
AliU-_4
--
--
1200 (MINIMUM)
5650
5650
--
3840
PLAN
NORTH
N
2000
5840
190 -CFM (POSITIVE)
1/8" = 1'-0"
a2
a2
B.1
C.1
OUTSIDF AIR
----
EAN_E-6.
SUB-TOTALS
_T_QIALS
FLOOR PLAN AREAS A.1 AND A.2 - MECHANICAL
I
DRAWN BY:
SRD
4
I
5
-=
I
FLOOR PLAN
AREA A.1 & A.2 - MECHANICAL
WALL RATING LEGEND
- 042
042
042
3-HOUR FIRE WALL
- - - - 2-HOUR FIRE BARRIER OPT MA # 13 0238
==
SMpKE PART 040TIONSOLUTIONS THROUGH LISTENING
(NOT RATED)
THIS DRAWING IS AN INSTRUMENT OF SERVICE. THE DRAWING AND THE INFORMATION THEREON IS THE PROPERTY OF OPTIMA ENGINEERING, P.A. ANY REPRODUCTION, ALTERATION, OR USE FOR OTHER THAN THE INTENDED PROJECT, WITHOUT THE WRITTEN CONSENT OF OPTIMA ENGINEERING, P.A. IS EXPRESSLY FORBIDDEN. COPYRIGHT © OPTIMA ENGINEERING P.A. 2014, ALL RIGHTS RESERVED.
3
OCT. 31, 2014
CHECKED BY: RVA
MFCHANICAI FOUIPMFNT (SYSTFM)
KITCHFN HOOD FXHAUST
KITCHFN HOOD MAKF-UP
DISHWASHFR FXHAUST
I
DATE:
1$0-
KITCHEN AREA AIR BALANCE SCHEDULE
2
9201-131360
-36x8 MAKE-UP AIR DUCT
CW
1
PROJECT:
Date
12x8
400-G
1
Description
10
--- - - -12x12 UP TO
6
No.
6
BID DOCUMENTS
PROVIDE OFFSETS TO ALIGN
TRANSFER OPENINGS ABOVE
A N S (
ICAL A PE IM
CLASSROOM TRANSFERS)
TRANSFER OPENINGS ABOVE
DOOR FRAMES, SEE STRUCTURAL
D AWIN S (
CAL ALL PERIMITER
R
è 360- E
250 D
360-E è
350-E
1 "ø
250 -D
~ 10"ø
-
10"Ø-
10"ø
260 -D
CLOVER SCHOOL DISTRICT
10"ø
r mh cMd, rach Day... ExmHence
250-
.
10"ø
250*D '
260+D
I
20x14
10"ø
gg
'I F 1
350-E
CS B
360-
SD D
E -
CLOVER SCHOOL
DISTRICT TWO
_
,_ - -10"ø
10"ø-
10"ø
21x14
P
250 -D
360- E
360-E
360-1
P
o"ø
P
10"A
P
260+D
260 -D
P
260 -D
260 -D
CLOVER
REPLACEMENT
MIDDLE SCHOOL
HUMIDIS f/ T (SEE
250 D
250--b
$EQ
10"ø
350-E
NCE ÖF CPCRATION)
350-E
t0"W
-
o*ø
12x12 UP TO
1./
0
10"ø
R)OF
20x12
1
250+D
20x12
Ø
Ö
$50 D
L
+L
.
250 -D
2 5400-4)
50 C
260+D
imo
260 -D
50-C
1927 South Tryon St., Suite 300, Charlotte NC 28203
250- D e
$50eD
0"ø
250 -D
-10"ø
6"ø
1 1"ø-
2$0-D
290-E
260+D
O
Phone: 704-338-1292 042
www.optimapa.com
North Carolina License Number C-0914
260 -D
10
D .g,
-10"ø
290-E
-
-
10"ø--
20×12
.
250-D
0
250-D
10 ø-
P
- -10"ø
--- '*-
L
290-E
25 0-E
0"Ø
10
-*/- - 22×T6
1
P
0
22× 6
"I4x C
10"i
t230 -P
×
1500-P
250 D
m
22x1
250 -D
e
P
RESIST THE PASSAGE OF SMOKE.
SEAL ALL PENETRATIONS OF THESE
WALLS PER THE UL DETAILS SHOWN
ON SHEET M-403 (TYPICAL)
260+D
260 -D
.
10"W
227 WEST TRADE STREET
SUITE 700
CHARLOTTE, NORTH CAROLINA 28202
TEL. 704.333.6686
FAX 704.333.2926
WWW.LS3P.COM
10"ø
U
n
20x11
150 J
10"ø
1 >x16 UP
P
0
260-0
10"ø
260+D
'
. 9.o.
260 -D
100-C
290-E
=
250*D
250-D
250 -D
---E
10"Ø
A °" " °
7
-10'ø
10"
-
12k12 UP TO
-1
29
1500-P
10 ø
250- D
P
250-D '
260AD
290-E
10"ø
e
260 -D
10"Ø
Q"ø
29)-E
10"+
tilHN
T
1
290
o-
.,
10 ø
IN
10'
RIS
250*D
2qiO¬D
T
290-E
$50-D
No. C00710
--
° °
1
6x16 U
10"ø
OPTIMA
\
ENGINEERING
"
290-E
16ft6 UP TO
C -
GCIENCE CLASSROOM WALLS ARE
22x12
7
T0"ø
250-D
... _
...-
It x16 UP TO
EJL -_15 1230 P
90- E
20×12
SCIENCE CLASSROOM WALLS ARE
SMOKE PARTITIONS, DESIGNED TO
RESIST THE PASSAGE OF SMOKE.
SEAL ALL PENETRATIONS OF THESE
WALLS PER THE UL DETAILS SHOWN
ON SHEET M 103 (TYPICAL)
c
1 00-P
29 )-E
_ ,,
260 -D
-P
_, __
\
260+D
-
-10"Á
-
T0"9
P
290-E
---250rD
2)xM
40 ø
t
...
250*D
LS P
TO ø
290-E
0"D
1
P
260+D
j260 -D
260+D
260 -D
40"
p
10" +
1230- 2
MEMBERS OF THE AMERICAN INSTITUTE OF ARCHITECTS
0
1230-P
tiU±t IlUMIDISTAT
(SEE SE4tfENCE OF
)PERATI )N)
2 254(
.
. .
22 12
10"ø
ROX .12,
1/M 301
CON .
T0*ø
1rø
275-D
T
· **
250-*D e
250rD
1*tRE SUPRESSIO
1
B -
I
250+D
-TO M-iU-t
50 C
260-D
300- L
N
T
10x10
-
-
10x8
1Ø"ø
10x8-
L
Description
PROJECT:
9201-131360
DATE:
OCT. 31, 2014
DRAWN BY:
SRD
Date
5-Q
L
6"ø
I -6 ø
50-B
0-B
BB-
x
r16x16 ..INED
-RETURhl AIR
/ TRANS ER
-
6
--
10"Ø
30 -L
a
F
t4x 4
2$-B
" RIGID DR
VENT
P TO GQ0$Et CK
N ROOF
DETALL
2/M-403
No.
5-
8x8
310-E
.
22x 4
P
n
26ß-0
K
10 ø
250AD
Kll-3..
315+E
REVISIONS:
_
10"ø-
--- -
P
15- :
260 -D
=
275- D
8
( xa)
260+D
300-L
35-- C
75-J
TTe
L
6 ø 6
75-J
40x2d
SYSTEM,
0x 0
62x24
50 B
COPYRIGHT 2014 ALL RIGHTS RESERVED
PRINTED OR ELECTRONIC DRAWINGS AND
DOCUMENTATION MAY NOT BE REPRODUCED
IN ANY FORM WITHOUT WRITTEN PERMISSION
FROM LS3P ASSOCIATES LTD.
22x12
20x12
-10"ø
)"
p
25(-D
0"
K
F
0
0"ø
22r 2
10"¢
L
1
10 ø
8"ø- '
10"ø
10"ø
350-E
10",
0"ø
'
2.2
260 D
260-D
CHECKED BY: RVA
8xE UP TO
12x1
,
-
-
.
-
x6 DBR
12"ø
12x12
1 FD3
FLOOR PLAN
AREA A.3 - MECHANICAL
-10"ø
P
A -
300-E
P
8"ø
---- - ------ - - -- ---
p
300-E
P
300+-E
300-E
M
1 FD3
M s'
A.2
P
PLAN
FLOOR PLAN AREA A.3 - MECHANICAL
NORTH
,fs- _ r_o-
N
'3
WALL RATING LEGEND
- 042
042
042
-
3-HOUR FIRE WALL
M-102
- - - - 2-HOUR FIRE BARRIER OPT MA#130238
-
042
042
042
042
-
SMOKE PARTITION
SOLUTIONS THROUGH LISTENING
THIS DRAWING IS AN INSTRUMENT OF SERVICE. THE DRAWING AND THE INFORMATION THEREON IS THE PROPERTY OF OPTIMA ENGINEERING, P.A. ANY REPRODUCTION, ALTERATION, OR USE FOR OTHER THAN THE INTENDED PROJECT, WITHOUT THE WRITTEN CONSENT OF OPTIMA ENGINEERING, P.A. IS EXPRESSLY FORBIDDEN. COPYRIGHT ©OPTIMA ENGINEERING P.A. 2014, ALL RIGHTS RESERVED.
1
2
3
4
5
6
BID DOCUMENTS
260-D
O At1U-.5.
50 C
2
Sa
-B
T W
ø
---(3--
1(x8
>
1C
75-6 ø
50 B
16x1
TRA
D
5®
60 D
CLOVER SCHOOL
DISTRICT TWO
CS B
ÜNÉD
ER
CLOVER SCHOOL DISTRICT
r mh cMd, rach Day... ExmHence
"øj
x8
6"ø
E 260-D
10"ø
10"ø
-
3
0"ø
CLOVER
REPLACEMENT
MIDDLE SCHOOL
10"ø
250-D
2 0-
260eD
__
14×14
0
D
6.2
1Bx6, DROP
BELOW BEA A
x6 DOWN
2"ø
12×12
350-E
30x6 DO
6
60 D
042
..
1 FD3
--
63 -
R
A
30-
BELOW BEAM
300 E
M
0-E
FD3
TO
042
...
_
..
M
3°°¯Q
400-E
M
(EXTEND 10"ø DUCT
UP TO ROOF CAP)
NQIEL
CLOSELY COORDINATE EXACT GRILLE
LOCATIONS WITH ARCHITECT AND OWNER
AROUND OTHER DEVICES INSTALLED ON
THESE ELEVATIONS
=
00-E
imo
-eme
040
-- -
=
1927 South Tryon St., Suite 300, Charlotte NC 28203
=
D -
- 3 x6 DOWN
30x6 DO N
Phone: 704-338-1292 042
www.optimapa.com
North Carolina License Number C-0914
4 0-E
30d-E
1C"ø
10-
2
5-
P
-- -- -- -
0"ø
40 -D
P
4- 0-
-E
275
LS P
-- -- -- -- --
2 54b
10"ø
2
1
=
0
===
Ñ(96x1 )
1
L
7
_ .
227 WEST TRADE STREET
SUITE 700
CHARLOTTE, NORTH CAROLINA 28202
TEL. 704.333.6686
FAX 704.333.2926
WWW.LS3P.COM
4 0-$
a
4- 0-
3
3
0"ø
0 -E
-b
©
8 8 UP T
P
llHH
8 ø
12
!O
00
2
=
50 D
P
2
-D
Po
o
ERING
No. C00710
T
D
ENG
S E
00-
0
25 D
4c 0st11HII
10x 2
--
INS
ABóVE
275 D
o
=
8
21
ÚLT
4c 0-
(
)
MEMBERS OF THE AMERICAN INSTITUTE OF ARCHITECTS
4c 0-$
"
T
250 D
as
-
P
225 D
P
COPYRIGHT 2014 ALL RIGHTS RESERVED
PRINTED OR ELECTRONIC DRAWINGS AND
DOCUMENTATION MAY NOT BE REPRODUCED
IN ANY FORM WITHOUT WRITTEN PERMISSION
FROM LS3P ASSOCIATES LTD.
25- D
00 -D
.
50
5
B
REVISIONS:
.
B -
250-1
ST DUCT DOWN
HER (SEE 14/M-402)
T WALL CAP AND
3RYER VENT DOWN
) DRYER
ON ROOF
.8"
1
C
O
O
_
180-D
O
O
(8
O
=
No.
Description
PROJECT:
9201-131360
DATE:
OCT. 31, 2014
DRAWN BY:
SRD
Date
Q h
6
DRYER VENT WALL CAP AND
4"ø RIGID DRYER VENT DOWN
__ ___
H(18x12)
H(18x12)
CHECKED BY: RVA
.
a 40¾ D
375-G
(32×4)
375-G
(32×4)
o
1 5-c
8-
A2
a2
a2
A -
A.2
A.1
PLAN
NORTH
FLOOR PLAN AREA B.1- MECHANICAL
N
'
-
FLOOR PLAN
AREA B.1 - MECHANICAL
C.1
WALL RATING LEGEND
042
042
042
3-HOUR FIRE WALL
- 042
-042
2-HOURFIRE
BARRIER SOLUTIONS
OPTuA#130238THROUGH LISTENING
- 042
042
SMOKE PARTITION
THIS DRAWING IS AN INSTRUMENT OF SERVICE. THE DRAWING AND THE INFORMATION THEREON IS THE PROPERTY OF OPTIMA ENGINEERING, P.A. ANY REPRODUCTION, ALTERATION, OR USE FOR OTHER THAN THE INTENDED PROJECT, WITHOUT THE WRITTEN CONSENT OF OPTIMA ENGINEERING, P.A. IS EXPRESSLY FORBIDDEN. COPYRIGHT ©OPTIMA ENGINEERING P.A. 2014, ALL RIGHTS RESERVED
1
2
3
4
5
6
BID DOCUMENTS
CLOVER SCHOOL
DISTRICT TWO
PROVIDE OFFSETS TO ALIGN
OR
AMES
C ASSROOM
E
STRUCTURAL
MSH MMS ABN
NSFERS)
60-E
:·50-D
3 2540-E
J 2540-E
S0-D
350 -E
10"ø- 50-D
E -
10"ø i
10"ø- -
250 ' D
.50+D
250--D
r mh cMd, rach Day... ExmHence
230-D
N21
1
20xf4
2ex14
P
P
260-D
'
CLOVER
REPLACEMENT
MIDDLE SCHOOL
260-D
- HUMlplST T (SEE
SEQU NCE OF OF ERATION)
NI
H
3$0-E
-
250+D
Q_,._IN
350-E
10"ø
250-D
230-0
,.
1 I
$50eD
250+D
-10"ø
to*ø
12x12 JP TO
50-C
0"ø
CLOVER SCHOOL DISTRICT
10 ø
t0"Ø
50+D
260-D
10"ø-
- -10"
10"ø
50*D
260-D
350- :
h
50+D
CS B
CLASSROOM TRANSFERS)
imo
260-D
50-C
7 -_3 --rrlIIIllTI J III
I I||IIIII
,.
--
- -10"ø
260+D
280¬0
290-E
260-D
29
290-E
F
.·
1927 South Tryon St., Suite 300, Charlotte NC 28203
Phone: 704-338-1292 042
www.optimapa.com
North Carolina License Number C-0914
260-D
-1
10"ø
LS')P
290-1
50--D
WO"ø
.50 D
P
P
æ
290- E
2£0-1
260-D
260-D
10
RESIST THE PASSAGE OF SMOKE.
SEAL ALL PENETRATIONS OF THESE
10"ø
50-D
E
250--D
.- 10"ø
'
P
260+D
260-D
- 0"ø
10"ø
22x16
x
29 -E
6x16 L P TO
- T-Mt. --2. t 1230 P
10"
20x1 !
1230-P
MOO-P
90-E
)(
SCIEN 41 SSROOM WALLS ARE
SMOKE PARTITIONS, DESIGNED TO
RESIST THE PASSAGE OF SMOKE.
SEAL ALL PENETRATIONS OF THESE
WALLS PER THE UL DETAILS SHOWN
ON SHEET M 103 (TYPICAL)
C -
: 50-D
'
'50-D
__
250-D
P
_ __ _..y._ ..
50+D s
250-D '
250+D
jyg
r-Tr
DI
II -10"ø
100 C
nl m
2 0 D
12xt2 LP TO
AN F- 5
ON RQC
290 E
1 fø
2$0-D
11"#
260-D
260+D
o"
290 E
042
260+D
Q.U.-2.
. 9.o.
SCIENCE CLASSROOl
SMOKE PARTITIONS,
RESIST THE PASSAC
SEAL ALL PENETRA
WALLS PER THE UL
ON SHEET M-403 (
rurrn
1 DO-
r
P
100+J
TmmrfmTi
'290-E
16x16 VP T)
10"ø
8"ø
rrr-
90+E
20x12
450-J
1 x13 UP TO
F N F-25
C4 ROOF
' '
10"
2 x12
22x12
0"#
227 WEST TRADE STREET
SUITE 700
CHARLOTTE, NORTH CAROLINA 28202
TEL. 704.333.6686
FAX 704.333.2926
WWW.LS3P.COM
=
OPTIMA
\
ENGINEERING
"
No. C00710
260*D
10"ø
1500-P
16<16 UP TO
10 ø
50+D '
290-E
$50-D
P
90-E
10"ø
290 E
10"ø
io"ø- 042
RTSE
"50+D e
'50-D
290
0"ø
10-
P
10"ø
260+D
260+-D
260-D
260-D
4D"ø
p
10"ø
1230-P
MEMBERS OF THE AMERICAN INSTITUTE OF ARCHITECTS
10
1730-P
290-E
FT222
OPEl ATION)
r
-r#
__
COPYRIGHT 2014 ALL RIGHTS RESERVED
PRINTED OR ELECTRONIC DRAWINGS AND
DOCUMENTATION MAY NOT BE REPRODUCED
IN ANY FORM WITHOUT WRITTEN PERMISSION
FROM LS3P ASSOCIATES LTD.
P
10'ø
TO O X 5.12
SIEE 1/M-302
10'ø
10 ø
50+D
-
$
20>12
0"ø
to"W
5-D
"50rD
250*D
TO
50-C
2 0-
260+D
260-D
REVISIONS:
_
62x24- _)75
Li178=d
6"#-
300 L
65-C
2, 2
40-8
- --
250-D
N
1Bx1
1
1(x8
P
16x16
16xt
._
14×14
1(X8
L
-B
6"ø
50-B
r16x16 LINED
SFE
10
P
^ ÂS-B
--
2x 4
260-D
250-D
------
A -
P
30x6 DOWN
104
30x6 DO
6.2
260 'D
260-D
J
300
TL
CHECKED BY: RVA
A2
-..-300-E
_ __ __
O 6t1U.r.7_- -
K
CLOSELY COORDINATE EXACT GRILLE
LOCATIONS WITH ARCHITECT AND OWNER
AROUND OTHER DEVICES INSTALLED ON
THESE ELEVATIONS
- r3Òx6 DOWN
a2
$O0-E
0"ø DUCT
UP TO ROOF CAP)
A.2
A.1
B.1
/
PLAN
NORTH
N
'3
WALL RATING LEGEND
- 042
042
042
3-HOUR FIRE WALL
- - - - 2-HOUR FIRE BARRIER OPT MA # 13 0238
-
042
042
042
042
-
THIS DRAWING IS AN INSTRUMENT OF SERVICE. THE DRAWING AND THE INFORMATION THEREON IS THE PROPERTY OF OPTIMA ENGINEERING, P.A. ANY REPRODUCTION, ALTERATION, OR USE FOR OTHER THAN THE INTENDED PROJECT, WITHOUT THE WRITTEN CONSENT OF OPTIMA ENGINEERING, P.A. IS EXPRESSLY FORBIDDEN. COPYRIGHT ©OPTIMA ENGINEERING P.A. 2014, ALL RIGHTS RESERVED.
I
C.1
30x6 DOWN- -
1/8" = 1'-0"
2
FLOOR PLAN
AREA B.2 - MECHANICAL
K
FLOOR PLAN AREA B.2 - MECHANICAL
1
SRD
-- --
400+E
1
DRAWN BY:
10"ø
0-E
-L____ __
- -
0-
OCT. 31, 2014
ø
W2
"ø
250-D
10'ø
300-L
0"ø
-
DATE:
260-D
10"ø
10"Ø
9201-131360
g=
K
250-D
PROJECT:
-
...
50-E
10"ø
2545-0
1(x8-*
8x8
1
250-E
11 1&ø-
10"ø 4-·
-
Date
·
"
6"ø
Description
042· K
Ø
50-B
No.
300-L
3
I
4
I
5
I
e
SMOKE PARTITION
(NOT RATED)
SOLUTIONS THROUGH LISTENING
BID DOCUMENTS
i"ø
-6"ø
50-B
2
275 0
40-E
--- -
6"ø-
... .
6 ø
25
-10x8
-
..
--
10x8-*
E -
CS B
50 B
-
8x8
-tDx8
p
65-C
g=
6
6'
, -16x16 LI ED
CLOVER SCHOOL DISTRICT
"
D
10"ø
"""3""'E
75-
16x16
5 -D
10 -
3 0-E
tax8
P
260-D
300-L
22x 4
10"ø
d
P
260-
[
10
(109
250-D
2$0-D
n
10"ø
g"ø
250-0
10"ø
.
50-D
2
[
2
-*D
24x2
M
M
___
400-E
300-
P
3p0-E
-32"ø
LI
5024
50x24
Il 5 11 1
TO At1U-1_1_
-D'
260 D
260 ·D
24x24
34×24
300 E
8x 0
P
34x24
---.
.
3OO-E
300-E
32"ø-
---- -- ljU W 11s 1 Il 5 11, 1 Il 5 11
CLOVER
REPLACEMENT
MIDDLE SCHOOL
,/
24x24
1 F
to"
65
..
F
10
350-E
150-0
12×12
10"ø
22x12
K
250 -D
Cu-a
10"ø
r mh cMd, rach Day... ExmHence
300-L
K
ç_u-_1
CLOVER SCHOOL
DISTRICT TWO
DROP
[2
,000-V
imo
TO Al1U-1.1
30" DEEP
H ND GRILLE
\RISE UP TIGHT TO BOTTOM
--
8"t
__
230 L
80- C
1927 South Tryon St., Suite 300, Charlotte NC 28203
A
DE
L S
(33x9) EAROMETRK DAMPER
3x9)
D -
9
(41x9)
LD G
SURE
HEN BOTH GYM AIR
G
IR DAM
2
33x9)
(41x9)
[
3> )
1
P
T3.1
B: l· IN i GRILL
(
2 0-L
OU DE
RJLL OPEN
725-A
- "
.-
8 )-
920-A
725-A
LS')P
#4
P
920- A
8"ø
2-
"ø
·· --
SPlilAL DUCT TIGHT TO TRUSSES
5- A
Phone: 704-338-1292 042
www.optimapa.com
North Carolina License Number C-0914
..o
(1$x12)
125-H
-
s
5 A
(10x
1
ø
227 WEST TRADE STREET
SUITE 700
CHARLOTTE, NORTH CAROLINA 28202
TEL. 704.333.6686
FAX 704.333.2926
WWW.LS3P.COM
. _
L
80+C
8 ø
L
lHil
.......
=
ENG
ERING
No. C00710
C -
7 25-A
725-A
920-A
920-A
725-
72 i- 4
_
0×t JF TO Ey -11
EN
ø
N H M."OtlD WRE MNH
t r
250-H
3(0-E
8"ø
250
400-H
- =ar
7
A
)
725-A
(33x9)
920-A
(4Tx9)
20-A
(41x9)
725-A
(33x9)
7
-
MEMBERS OF THE AMERICAN INSTITUTE OF ARCHITECTS
12"ø
o
COPYRIGHT 2014 ALL RIGHTS RESERVED
PRINTED OR ELECTRONIC DRAWINGS AND
DOCUMENTATION MAY NOT BE REPRODUCED
IN ANY FORM WITHOUT WRITTEN PERMISSION
FROM LS3P ASSOCIATES LTD.
"
OOSENE
Y E A
A
R
WTH MAN FACTURER'S INSTALLLATION INSTRUCTIONS
=
REVISIONS:
n a 11 1 n a 11 1 n a 11 1 n a 11
° M-1M
109- - -
s
-c
2e
o
_
B loo-C e"¢
14
3---L
L
r
160-D
*
160-D
*
M
8x
-
-
-
-
-
-
-
-
-
-
-
-
-
-
--
--
--
-
-c
230-D
--
- ---
-
280-D
-
303-E
P
280-D REE
BETWEEN
TRUSSES
PROJECT:
9201-131360
DATE:
OCT. 31, 2014
DRAWN BY:
SRD
Date
2so-o
.
1
P
109
1sx14
Description
18x 2
(TTPICAL)
109
[
280- )
No.
=
=
20×1e
-,-THROUpH fRU)3SES-
280-D
280-D
ÑO BLE WALL
DAB
ROSAFE
SELF-SEALING DUCT SYSTEM (OR APPROVED
NNER SHE L.
E ISTERS
N SPI
O RECTANGULAR REGIS
280-D
P
-
L
230-D
80-D
________ __. _____ ---------- -1--f__. -- ---A-"
P
HUMIDISTAT (SEE
28
D
CHECKED BY: RVA
2 x14
R TAPS TOP
° uS
TA" D
.9u-CT
DIMENSIONS ARE INSIDE CLEAR SIZES.
A -
U
Fl N
- 12"
1 "ø
20×16
FLOOR PLAN
AREA C.1 - MECHANICAL
v'dAR U
N B OC(
WALLS AT SPIRAL DUCT PENETRATIONS
EM£-.4D.-
14"ø
--- -------
A.1
B.1
WALL LOUVER
FLOOR PLAN AREA C.1 - MECHANICAL
PLAN
1/8- - r-e
NORTH
N
'
WALL RATING LEGEND
M-105
- 042
042
042
3-HOUR FIRE WALL
- - - - 2-HOUR FIRE BARRIER OPT MA # 13 0238
-
042
042
042
042
-
SMOKE PARTITION
SOLUTIONS THROUGH LISTENING
THIS DRAWING IS AN INSTRUMENT OF SERVICE. THE DRAWING AND THE INFORMATION THEREON IS THE PROPERTY OF OPTIMA ENGINEERING, P.A. ANY REPRODUCTION, ALTERATION, OR USE FOR OTHER THAN THE INTENDED PROJECT, WITHOUT THE WRITTEN CONSENT OF OPTIMA ENGINEERING, P.A. IS EXPRESSLY FORBIDDEN. COPYRIGHT ©OPTIMA ENGINEERING P.A. 2014, ALL RIGHTS RESERVED.
|
1
2
3
4
5
6
BIDDOCUMENTS
PROMDE
TO ABOVE
ALIGN
TRANSFEROFFSETS
OPENINGS
DOOR FRAMES, SEE STRUCTURAL
AWIN S (
CAL ALL PERIMITER
o
e
CLOVER SCHOOL
DISTRICT TWO
- PROVIDE
TO ABOVE
ALIGN
TRANSFEROFFSETS
OPENINGS
DOOR FRAMES, SEE STRUCTURAL
DRAWINGS (TYPICAL ALL PERIMITER
CLASSROOM TRANSFERS)
o
CS B
CLOVER SCHOOL DISTRICT
50 D
350-E
260-D
r mh cMd, rach Day... ExmHence
10"ø
E -
___
___
Ox1
___
0"Ë
___
P
604E
360- E
3 0-
20x14
10"ø
P
10"ø
CLOVER
REPLACEMENT
MIDDLE SCHOOL
19 AUMIDIS
(SE
SEQUENC : OF 0 ERATION -
10
) W
oo
6
=
O
10
.
50 C
imo
50
1927 South Tryon St., Suite 300, Charlotte NC 28203
Phone: 704-338-1292 042
www.optimapa.com
North Carolina License Number C-0914
D -
LS')P
290-E
P
.
0- E
o
=
T
0 E
50
T"""T
250 D
"""
CCIENCE CLASSROOM WALLS ARE
SP
..
22 6
4x14
N
T
.
RESIST THE PASSAGE OF SMOKE.
=
=
50
..
60 D
2 0-E
===
.
SCIENCE CLASSROOM WALLS ARE
SMOKE PARTITIONS, DESIGNED TO
RESIST THE PASSAGE OF SMOKE.
SEAL ALL PENETRATIONS OF THESE
WALLS PER THE UL DETAILS SHOWN
ON SHEET M 102 (TYPICAL)
260 D
2 2
P
__C--------
WALLS PER THE UL DETAILS SHOWN
ON SHEET M-403 (TYPICAL)
227 WEST TRADE STREET
SUITE 700
CHARLOTTE, NORTH CAROLINA 28202
TEL. 704.333.6686
FAX 704.333.2926
WWW.LS3P.COM
22
-p-- T
=
040
P
-3.Q
N ADOF
0-
60 D
6
. 9.o.
D
n
m
o
n
énn
=
O E
"
OPTIMA
\
ENGINEERING %
PA
No. C00710
=
=
C 90- E
O
0x12
0
=
0
0 E
90 E
=
--- =
stslHII
Ox1
=
=
10"
6
1
6 -
7
MEMBERS OF THE AMERICAN INSTITUTE OF ARCHITECTS
10
1
ntRL_.9.. HUM DIS AT
(SEE SEQUEWCE OF
P
?
...
2
20 12
o
p
2 x1
T
X112
S É /M 30
=
O
COPYRIGHT 2014 ALL RIGHTS RESERVED
PRINTED OR ELECTRONIC DRAWINGS AND
DOCUMENTATION MAY NOT BE REPRODUCED
IN ANY FORM WITHOUT WRITTEN PERMISSION
FROM LS3P ASSOCIATES LTD.
1
""""
-10 ø
REVISIONS:
_
B -
2s -
2sq-o
6
_ P
P
-B
x
=
Description
PROJECT:
9201-131360
DATE:
OCT. 31, 2014
DRAWN BY:
SRD
Date
260-D
2x14
so o
P
10"ø
230-4
No.
260-
10 ø
0"ø
350-E
so o
o
so o
so tr
CHECKED BY: RVA
--
4×g
P
d4x2
x
300 E
A -
..
so" DEEP
PLENUM
P
=
34x24
.
RISE UP TIGHT TO BOTTOM
OF TRUSSES (TYPICAL)
BEHIND GRILLE
(84x60)
= 2
soo
----
A.3
B.2
A.1
B.1
FLOOR PLAN
AREA C.2 - MECHANICAL
00-E
---
C.1
230ÀL
8
PLAN
NORTH
__
FLOOR PLAN AREA C.2 - MECHANICAL
N
'
-
WALL RATING LEGEND
042
042
042
3-HOUR FIRE WALL
M-106
- 042
-042
2-HOURFIRE
BARRIER SOLUTIONS
OPTuA#130238THROUGH LISTENING
- 042
042
SMOKE PARTITION
THIS DRAWING IS AN INSTRUMENT OF SERVICE. THE DRAWING AND THE INFORMATION THEREON IS THE PROPERTY OF OPTIMA ENGINEERING, P.A. ANY REPRODUCTION, ALTERATION, OR USE FOR OTHER THAN THE INTENDED PROJECT, WITHOUT THE WRITTEN CONSENT OF OPTIMA ENGINEERING, P.A. IS EXPRESSLY FORBIDDEN. COPYRIGHT ©OPTIMA ENGINEERING P.A. 2014, ALL RIGHTS RESERVED
1
2
3
4
5
6
BID DOCUMENTS
I
I
I
I
I
CLOVERSCHOOL
DISTRICT TWO
mmmmm
num
mmmm
DS
nem
num
maamm
DS
CLOVER SCHOOL DISTRICT
CLOVER
REPLACEMENT
AND 12x12
AND 42x12
AND 12x12
EXHHUSI
EXHAUST
EXHnUST
--- DUG -BOWN-----------
AND 1BR111
DS
-DU 254T
DOW
DUCT DOWN
DS
D GiM
--EXHAUST- ------------------------
DUCT DOWN
AND 16xf6
EXHAUST
EXHAUST
DUCT DOVW
DUCT DOWN
ay-2 AND 48x96
F--y
REUE7 DUCT DOWN-
,rf__3
EXHAU
DUCT DOWN
AND 16xth
EXHAUST
DUCT DOVN
DUCI DOMT
2
EXHAUST
DUCT DOWN
AND 16x1h
DUC ' BOWN
-----------------------EXHAUST-
DIICI¯DDV W¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯
-
E
EXHAUST
EXNAttST
DUCT DOW
------AND-16x16 --
1927 South Tryon St., Suite 300, Charlotte NC 28203
DUCT DOWN
--------AND t6 t6
EXHAUST
MIDDLE SCHOOL
AND 16x¼
..XFíAüst
-------------------------------------------------------------------------DUGT-DOWN-------------------DUCT DOWN
-- IN-± AND 48x96
REUEE DUCT DDE
Phone: 704-338-1292 042
www.optimapa.com
North Carolina License Number C-0914
AND 16x1
EXRAUST
EXHAUST
DUCT DOVN
DUCT DOWN
Ry-E AND 48x96
F--
REUEF DUCT DOWN-
I,r___a
LS P
MSFSM T]¾M
227 WEST TRADE STREET
A ST
DUCT DOWN
r-7
Î<____J
-BY-L AND 48x96
-
REUEF BUGT DOWN
RY. ·3 AND 48x96
E MA S
--- -------- Q__3 - -HEUEF-OUGT-DOWN--
DUCT DO
r--
-BY-.i AND 48x96
Q|$]Si
SUITE 700
CHARLOTTE, NORTH CAROLINA 28202
REUEF DUCT DOWN
TEL. 704.333.6686
FAX 704.333.2926
WWW.LS3P.COM
EELE=3E-4
DS DS
AND 8x8
EXHAUST
DUCT DOWN
DS
--
E
E
L
L
- ¬-¬u,
DS
EXHAUST-DUCT-DOWN
DS
.....
_________
0
\nlHil
1
7
DS
MEMBERS OF THE AMERICAN INSTITUTE OF ARCHITECTS
$4AN T=W---AND 12x12
EXHAUST
--- DUGT-DOWN------------------- ---
COPYRIGHT 2014 ALL RIGHTS RESERVED
PRINTED OR ELECTRONIC DRAWINGS AND
DOCUMENTATION MAY NOT BE REPRODUCED
IN ANY FORM WITHOUT WRITTEN PERMISSION
FROM LS3P ASSOCIATES LTD.
By-11 AND 8x8
COMBUSTION AIR DUCT DOWN
DS
------------------------------------------------ --------------
-----------------------------------
REVISIONS:
DS
B -
e---rht_E-a
AND 10x10 DISHWASHER
EXHAUST DUCT DOWN
EaN_E -2.
AND 22x22 KITCHEN HOOD
#AKE-UP AIR DUCT DOWN
BOILER FLUE
254APS
AND INTAKE
GOOSENECKS
EAN_E-1.
AND 22<22 t ITCHEN HOOD
EXHAUST DUCT DOWN
_
DS
ROOF HATCH-
AND 10x10
EXHAUST
DUCT DOWN
PROJECT:
9201-131360
DATE·
OCT 31 2014
Date
DUCI¯DOW
F--
RELIEF DU 254T
DOWN
By-.R AND 18xtB
RELIEF DUCT DOWN
Description
GOOSENECK AND 8"ø COMMERCIAL
DRYER VENT DOWN
ND MxR
EXHAUST
9·--- -EahLE-.a
No.
Ai4D 1Sx1B
RELIEF IUCT DOWN
CHECKED BY: RVA
ROOF AND FIELD
HOUSE PLANS- MECHANICAL
ROOF PLAN - MECHANICAL
1/16" - 1'-0"
-
NORTH
N
'
- 042
042
042
3-HOUR FIRE WALL
- - - - 2-HOUR FIRE BARRIER OPT MA # 13 0238
-
042
042
042
042
-
SMOKE PARTITION
SOLUTIONS THROUGH LISTENING
THIS DRAWING IS AN INSTRUMENT OF SERVICE. THE DRAWING AND THE INFORMATION THEREON IS THE PROPERTY OF OPTIMA ENGINEERING, P.A. ANY REPRODUCTION, ALTERATION, OR USE FOR OTHER THAN THE INTENDED PROJECT, WITHOUT THE WRITTEN CONSENT OF OPTIMA ENGINEERING, P.A. IS EXPRESSLY FORBIDDEN. COPYRIGHT ©OPTIMA ENGINEERING P.A. 2014, ALL RIGHTS RESERVED
1
2
3
4
5
6
BID DOCUMENTS
1/ -2
C
N
CLOVER SCHOOL
DISTRICT TWO
R FRIGERANT
P PING UP IN WALL
T ) ABOVE 254ElUNG
TIO
DROP »IPtNG BELOW BE.
CLOVER SCHOOL DISTRICT
h cMd, rach Day... ExmHence
PREMAt UFACTURED EXPANSION
BE
E , GU O ANL
ANCHOI ED PER MFC. REC.---
-4"
CLOVER
C
T ¯
DA
MIDDLE SCHOOL
F
ENS
D AN
NTO
L
BOX (WALL BO) BY
P.C., SEE 6/M- 402)
l
imo
F
1927 South Tryon St., Suite 300, Charlotte NC 28203
Phone: 704-338-1292 042
www.optimapa.com
North Carolina License Number C-0914
LS P
3.3
ENGME DESIGN TRAMMORM
227 WEST TRADE STREET
SUITE 700
CHARLOTTE, NORTH CAROLINA 28202
TEL. 704.333.6686
FAX 704.333.2926
WWW.LS3P.COM
--EM_E-3 ON ROOF
No. C00710
E
ON ROOF
MEMBERS OF THE AMERICAN INSTITUTE OF ARCHITECTS
==
====
PROVIDE THRUST BLOCKS AT ALL
ANGES OF D EC N PER
ENSULATED
COPYRIGHT 2014 ALL RIGHTS RESERVED
PRINTED OR ELECTRONIC DRAWINGS AND
DOCUMENTATION MAY NOT BE REPRODUCED
IN ANY FORM WITHOUT WRITTEN PERMISSION
FROM LS3P ASSOCIATES LTD.
CHILLED WATER PIPING
BELOW RADE, MINIMUM
(TYP1CAL)
6"
REVISIONS:
11
o
£lilkLEB_#1
6"
NS O
U U
_
ARE S
No.
Description
PROJECT:
9201-131360
DATE:
OCT. 31, 2014
DRAWN BY:
SRD
Date
-TO EM_E-2 ON1ROOF
L__________
INSTALL CONTROLS/
UI N AME
TRENCH WITH BURIED
ßlflLLEB_#2
PIPING
F
------
---
F
t
r
1. ALL PIPING ABOVE GRADE SHALL HAVE ELECTRIC HEAT
Ä TAPE HALL B FURN HED WITH
ERMOST T AND
SHALL BE INSTALLED PROIR TO INSTALLING INSULATION. PIPE
INSULATION SHALL BE COVERED WITH AN OUTER ALUMINUM
JACKET SEALED WATERTIGHT.
=
CHECKED BY: RVA
1 D WA R Pl G TH GREASE WASTE AN
ER
UTILITIES IN THIS AREA.
3. CHILILERS SHALL BE MOUNTED ON A 4" THICK CONCRETE PAD.
PAD$ SHALL BE PROVIDED AND INSTALLED BY THE GENERAL
CONTRACTOR. MECHANICAL CONTRACTOR SHALL COORDINATE
THE |EXACT SIZE AND LOCATION OF ALL PADS WITH THE
GENERAL CONTRACTOR.
A.3
|
B.2
C.2
A -
B.1
PLAN
NORTH
N
FLOOR PLAN AREAS A.1 AND A.2 - MECHANICAL PIPING
1/8" = 1'-0"
C.1
FLOOR PLAN
AREA A.1 & A.2 - MECHANICAL
PIPING
W LL RATING LEGEND
- 042
042
042
3-HOUR FIRE WALL
- - - - 2-HOUR FIRE BARRIER OPT MA # 13 0238
-
042
042
042
042
-
SMOKE PARTITION
SOLUTIONS THROUGH LISTENING
THIS DRAWING IS AN INSTRUMENT OF SERVICE. THE DRAWING AND THE INFORMATION THEREON IS THE PROPERTY OF OPTIMA ENGINEERING, P.A. ANY REPRODUCTION, ALTERATION, OR USE FOR OTHER THAN THE INTENDED PROJECT, WITHOUT THE WRITTEN CONSENT OF OPTIMA ENGINEERING, P.A. IS EXPRESSLY FORBIDDEN. COPYRIGHT ©OPTIMA ENGINEERING P.A. 2014, ALL RIGHTS RESERVED.
1
2
3
4
5
I
e
BID DOCUMENTS
CLOVER SCHOOL
DISTRICT TWO
CS B
CLOVER SCHOOL DISTRICT
má cud. ach æv. . uæncnce
FM £-2Q
E -Cu-a
in
ANT
> IN WALL
- 254ElLING
DI:OP PIPING BELOW BEA J
PIPING TO MECHANICAL PLATFORM,
SEE 2/M-207 FOR CONTINUATION
PIPING UP IN WALL
TO ABOVE CEILING
--
6"
CLOVER
REPLACEMENT
MIDDLE SCHOOL
3"-
F
||
4"
EM_E-M
23"
DROP PIPING BEL W BEAM- -
L
PREMANUFACTURED EXP \NSION
L)OP NIH F_EXIBLE TU111NG.
L)OP TO BE SIZED, GUIDED, AND
ANCHORED PER MFG. REC.
o.
- -REFRIGERANT PIPING ABOVE
CEILING (INSTALLED PER MFG.
RECOMMENDATIONS)
PREMANUFACTURED EXPANSION
LOOP NTH FLEXIBLE TUBING.
LOOP TO BE SIZED, GUIDED, AND
ANCHORED PER MFG. REC.
imo
1927 South Tryon St., Suite 300, Charlotte NC 28203
Phone: 704-338-1292 042
www.optimapa.com
North Carolina License Number C-0914
D -
LS P
-EXTEND ULL SIZE r DNDEN! ATE
DRAIN DOWN IN WAl AND iPIL..
INTO WAl L BOX (WA L SOX BY
P.C., SEE 6/M-402, TYP4CQ
F
8.
w-=-,
227 WEST TRADE STREET
SUITE 700
CHARLOTTE, NORTH CAROLINA 28202
TEL. 704.333.6686
FAX 704.333.2926
WWW.LS3P.COM
REFRIGERANT
PIPING UP IN WALL
TO ABOVE CEILING-
-PREMANilFACTURED EXPANSION
LOOP W H FLEX]BLE TUBING.
LOOP TO BE SIZED, GUIDED, AND
ANCHolRI D PER MFC. REC.
A/-E 4
..7.7
C -
PRE.4A4UFACTUREO E PANSIO4
LOO;' NITH FLEXIB.E UBING.
LOOi t O SE $1ZEh, G llDED, nND
ÁNC JO 4ED FbER M -G.
C.
. 9.o.
4
=
TEND FULL StZ
ENG
ERING
No. C00710
LL A D
ILL INTO WALL
BOX (WALL BOX BY
P.C, SEE 6/M-402)
r yr y +
r - - -
1]
ELL
21
MEMBERS OF THE AMERICAN INSTITUTE OF ARCHITECTS
7. 2
COPYRIGHT 2014 ALL RIGHTS RESERVED
PRINTED OR ELECTRONIC DRAWINGS AND
DOCUMENTATION MAY NOT BE REPRODUCED
IN ANY FORM WITHOUT WRITTEN PERMISSION
FROM LS3P ASSOCIATES LTD.
o
---
REV S ONS:
_
B -
PROVIDE TERMINAL UNIT
NTH 3-WAY HOT
WATER CONTROL VALVE - - -
No.
Descr ption
PROJECT:
9201-131360
DATE:
OCT. 31, 2014
DRAWN BY:
SRD
Date
F
7.13
- -@PROVIDE TERMINAL UNIT
NTH 3-WAY HOT
WATER CONTROL VALVE
-C
c
CHECKED BY: RVA
Aa
a2
a2
A -
A1
PLAN
NORTH
N
FLOOR PLAN AREA B.1 - MECHANICAL PIPING
1/8" = 1'-0"
1
1
C.1
WALL RATING LEGEND
- 042
042
042
3-HOUR FIRE WALL
- - - - 2-HOUR FIRE BARRIER OPT MA # 13 0238
-
042
042
042
042
-
THIS DRAWING IS AN INSTRUMENT OF SERVICE. THE DRAWING AND THE INFORMATION THEREON IS THE PROPERTY OF OPTIMA ENGINEERING, P.A. ANY REPRODUCTION, ALTERATION, OR USE FOR OTHER THAN THE INTENDED PROJECT, WITHOUT THE WRITTEN CONSENT OF OPTIMA ENGINEERING, P.A. IS EXPRESSLY FORBIDDEN. COPYRIGHT ©OPTIMA ENGINEERING P.A. 2014, ALL RIGHTS RESERVED.
2
I
3
I
4
I
5
I
FLOOR PLAN
AREA B.1 - MECHANICAL
e
SMOKE PARTITION
(NOT RATED)
SOLUTIONS THROUGH LISTENING
BID DOCUMENTS
CLO
DISTRICT TWO
CS B
CLOVER SCHOOL DISTRICT
r mh cMd, rach Day... ExmHence
E -
@PRO DE TERMlN\L UNIT
P042
OVlbE IERHlNAL LINlT
WITH 3-WAY HOf
WA R CONTROL VALVE
WITH 3-WAY HOT
W TER CONTf OL VALVE
CLOVER
REPLACEMENT
MIDDLE SCHOOL
EA&M
imo
r1"
1927 South Tryon St., Suite 300, Charlotte NC 28203
|||||1111111111
111
111
11||
|
|| 111111
||11
111
111
111
||||||||||11111
111
11
|||
Phone: 704-338-1292 042
www.optimapa.com
North Carolina License Number C-0914
I|||
D -
$CIENCE C SSR00M AL.S
SMOKE PA TITION$, D SICN
RESIST
PASSAGE F
LS P
E
TO
E.
LLS
k T t D TAitS
ON SHEET -403 (
ICi,L
227 WEST TRADE STREET
SUITE 700
CHARLOTTE, NORTH CAROLINA 28202
TEL. 704.333.6686
FAX 704.333.2926
WWW.LS3P.COM
O
E) TEN Fl .L SIZE 254ONDENSA
fE
DE AIN
IN WiLA. AND SFILL
IN f0 WALL BOX (PALL BOX Bf
P.1,
E /M-4C2)
EMAN F TU
) NS N
LOOP WITM
MBLE T J
LOOP TO B SIZED, GLIDED, AND
ANCHORED
MFG. f EC.
m m -f
. 9.^.
-+-PF EMANUFAC RED EXPA1SIÓN
LCOP WITH FLEXIBLE TUBNG.
LCOP TO BE
D, CUID :D, AND
Al' CHOREO R MFG. RE( .
1 I
m
=
L
ENG
ERING
No. C00710
REFR
C WALL
ElLING
RANT PlPRIG ABOVE
COMM NDA O
REFRIGERANT
PIPING UP IN WALL
TO ABOVE CEILING
)
FI I
SCIENCE CLASSROOM UALLS ARE
SMQKE PARTITIONS, DESIGNED TO
RE$lST
PASSAGE JF SMOKE.
SEAL /LL ENETRATIONS OF THEEE
PER THE UL Di TAILS SHO N
O
: ET -403 (TYl AL)
.
e FI +
MEMBERS OF THE AMERICAN INSTITUTE OF ARCHITECTS
1
COPYRIGHT 2014 ALL RIGHTS RESERVED
PRINTED OR ELECTRONIC DRAWINGS AND
DOCUMENTATION MAY NOT BE REPRODUCED
IN ANY FORM WITHOUT WRITTEN PERMISSION
FROM LS3P ASSOCIATES LTD.
r
|
|||
|||
|||
|||
||||
||||||||||||||||
|||
|||
||||||||
||
|||
||
F
|
REVISIONS:
_
No.
Description
PROJECT:
9201-131360
DATE:
OCT. 31, 2014
DRAWN BY:
SRD
Date
CHECKED BY: RVA
E RIGERANT
.L
. .
PIPING TO MECHANICAL PLATFORM,
SEE 2/M-207 FOR CONTINUATION
.
A2
DI OP PIPING BELOW BEA
L
J
a2
F l
llWC
O
A.1
DROP PIPING BEL W BEAM- -
L OP TO BE SIZED, GUI ED, AND
CHORED P R MFG. R .
REFRIGERANT PIPING ABOVE
CEILING (IN_STALLED PER MFG.
PREMANUFACTURE
EXPANSIO
I DOP WITH FI FYlR F TilRING
FLOOR PLAN AREA B.2 - MECHANICAL PIPING
1/8" = 1'-0"
PLAN
NORTH
N
B.1
2
3
-
4
5
C.1
WALL RATING LEGEND
- 042
042
042
3-HOUR FIRE WALL
- - - - 2-HOUR FIRE BARRIER OPT MA # 13 0238
042
042
042
042
-
THIS DRAWING IS AN INSTRUMENT OF SERVICE. THE DRAWING AND THE INFORMATION THEREON IS THE PROPERTY OF OPTIMA ENGINEERING, P.A. ANY REPRODUCTION, ALTERATION, OR USE FOR OTHER THAN THE INTENDED PROJECT, WITHOUT THE WRITTEN CONSENT OF OPTIMA ENGINEERING, P.A. IS EXPRESSLY FORBIDDEN. COPYRIGHT ©OPTIMA ENGINEERING P.A. 2014, ALL RIGHTS RESERVED.
1
FLOOR PLAN
AREA B.2 - MECHANICAL
e
SMOKE PARTITION
(NOT RATED)
SOLUTIONS THROUGH LISTENING
BID DOCUMENTS
CLOVER SCHOOL
DISTRICT TWO
CS B
CLOVER SCHOOL DISTRICT
r ch cMci, rach Day... ExmHence
E -
-
n
F L
1
L
CLOVER
REPLACEMENT
MIDDLE SCHOOL
n
DROP PIPING BEt0W BEAM
||
3
llE
CllS
llW
P PIPING BEL W BEAM- PREMANUFACTURED EXPANSION
C U G NSTA D P R MFG.
RECOMMENDATIONS)
PREMANUFACTURE EXPANSION
LOOP WITH FLEXIB TUBING.
LOOP TO BE SIZE , GUIDED, AND
ANCHORED PER M G. REC.
O BE S ZED G D D ANt
Ill 11 111 II) I 11 111 II) I 11 111 II)ll 11 111 II)ll
imo
I
1927 South Tryon St., Suite 300, Charlotte NC 28203
1 Q IL JLIJüJJ R IL J1JJüJJ R IL JLIJüJ1
Phone: 704-338-1292 042
www.optimapa.com
North Carolina License Number C-0914
D -
LS P
EXTEND iULL S12E ( ONDEN'ATE
DRAIN DoWN IN WAL AND ,PIL.
B.3
227 WEST TRADE STREET
SUITE 700
CHARLOTTE, NORTH CAROLINA 28202
TEL. 704.333.6686
FAX 704.333.2926
WWW.LS3P.COM
OJP TO 31 ".12ED, CJDID, AND
,
f T T
10/31M
MEMBERS OF THE AMERICAN INSTITUTE OF ARCHITECTS
COPYRIGHT 2014 ALL RIGHTS RESERVED
PRINTED OR ELECTRONIC DRAWINGS AND
DOCUMENTATION MAY NOT BE REPRODUCED
IN ANY FORM WITHOUT WRITTEN PERMISSION
FROM LS3P ASSOCIATES LTD.
TMTL R K TMTL R K TMTL R K TMTt
DR N DOWN IN WAl L AND SP L
P.C
EE 6
-402
REVISIONS:
11 ]Il Ú 1 Il ]Il Ú 1 11 ]Il Ú11 11 ]
_
B -
â/..b7_
No.
Description
PROJECT:
9201-131360
DATE:
OCT. 31, 2014
DRAWN BY:
SRD
Date
1"
WATE 4
V 041LVE
CHECKED BY: RVA
A.3
a2
A.1
B.1
a2
A -
A.2
PLAN
NORTH
N
FLOOR PLAN AREA C.1 - MECHANICAL PIPING
1/8" = 1'-0"
WALL RATING LEGEND
- 042
042
042
3-HOUR FIRE WALL
- - - - 2-HOUR FIRE BARRIER OPT MA # 13 0238
-
042
042
042
042
-
PROPERTY OF OPTIMA ENGINEERING, P.A. ANY REPRODUCTION, ALTERATION, OR USE FOR OTHER THAN THE INTENDED PROJECT, WITHOUT THE WRITTEN CONSENT OF OPTIMA ENGINEERING, P.A. IS EXPRESSLY FORBIDDEN. COPYRIGHT ©OPTIMA ENGINEERING P.A. 2014, ALL RIGHTS RESERVED.
1
I
1
2
3
4
5
FLOOR PLAN
AREA C.1 - MECHANICAL
6
SMOKE PARTITION
(NOT RATED)
SOLUTIONS THROUGH LISTENING
BID DOCUMENTS
CLOVER SCHOOL
DISTRICT TWO
CS B
CLOVER SCHOOL DISTRICT
r mh cMd, rach Day... ExmHence
E -
WATER
VA .VE
WATER CONTROL VALVE
CLOVER
REPLACEMENT
MIDDLE SCHOOL
-EAU_E-
-
ERENTIAL PREESURE
imo
1927 South Tryon St., Suite 300, Charlotte NC 28203
Phone: 704-338-1292 042
www.optimapa.com
North Carolina License Number C-0914
D -
M
E P
Tl
LS P
4 11BES N D
EA AL
TR T10N 01
ESE
AL S PER THE L DETAlt. SHOWN
oN HEET M-4C5 (TYP
, y-
---
u
unmmrr 1 rrr m
PR: MANUFACTUREb EX A SION
SU
JL
rrr mrrrrrrnm
____£_
R
D V
E
P
JulMluuJl
I
IU
ALL
)
UI
UL
111
MJJEURE
SP L
227 WEST TRADE STREET
SUITE 700
CHARLOTTE, NORTH CAROLINA 28202
TEL. 704.333.6686
FAX 704.333.2926
WWW.LS3P.COM
IMll
T F
---PREMA UFACTUREE EXPANSIO
BE Z
D ND
.......
0 BE I ED GUIDE , AND
AN :HORED PEi: MFG. REC.
REFRIGERANT
PIPING UP IN WALL
TO ABOVE CEILING
1"
-
TA D P
RECOMMENDATIONS)
.
M G.
REFRIGERANT
N OU N W
=
ENG
ERING
No. C00710
C SCI NCE CLASf ROOM WALLS ARE
1-
r
P
O
SE/L ALL PENI TRATIONS F THESE
WAli-S PER TH : UL DETA1 S SHOWN
ON
-fA --E-2R
stslHII
EE #- 03 (TYPtC )
1
MEMBERS OF THE AMERICAN INSTITUTE OF ARCHITECTS
m
u
un
unuinuun
unu
u
ui
unuuulu
li
uinnuu
u
tu
u
COPYRIGHT 2014 ALL RIGHTS RESERVED
PRINTED OR ELECTRONIC DRAWINGS AND
DOCUMENTATION MAY NOT BE REPRODUCED
IN ANY FORM WITHOUT WRITTEN PERMISSION
FROM LS3P ASSOCIATES LTD.
unun
REVISIONS:
_
B -
No.
Description
PROJECT:
9201-131360
DATE:
OCT. 31, 2014
DRAWN BY:
SRD
Date
t0.2
CHECKED BY: RVA
G UP N WALL
ABOVE CEit1NC
- o
ON
T
2"
DROP PIPtNG BELOW BEAM
A2
a2
A -
L
C L G NSTA L D P R MFG.
RECOMMENDATIONS)
PREMANUFACTURED EXPANSION
LOOP WITH FLEXIBLE TUBING.
LOOP TO BE S ZED GUIDED, ANI
PREMANUFACTURE EXPANSION
P
BE S
,E
NG.
A.1
: '
B.1
FLOOR PLAN
AREA C.2 - MECHANICAL
C.1
ANCHORED PER M G. REC.
PLAN
NORTH
N
FLOOR PLAN AREA C.2 - MECHANICAL PIPING
1/8" = 1'-0"
1
I
WALL RATING LEGEND
- 042
042
042
3-HOUR FIRE WALL
- - - - 2-HOUR FIRE BARRIER OPT MA # 13 0238
-
042
042
042
042
-
THIS DRAWING IS AN INSTRUMENT OF SERVICE. THE DRAWING AND THE INFORMATION THEREON IS THE PROPERTY OF OPTIMA ENGINEERING, P.A. ANY REPRODUCTION, ALTERATION, OR USE FOR OTHER THAN THE INTENDED PROJECT, WITHOUT THE WRITTEN CONSENT OF OPTIMA ENGINEERING, P.A. IS EXPRESSLY FORBIDDEN. COPYRIGHT ©OPTIMA ENGINEERING P.A. 2014, ALL RIGHTS RESERVED.
2
1
3
I
4
I
5
I
e
SMOKE PARTITION
(NOT RATED)
SOLUTIONS THROUGH LISTENING
BID DOCUMENTS
CLOVER SCHOOL
DISTRICT TWO
CS B
CLOVER SCHOOL DISTRICT
r mh cMd, rach Day... ExmHence
E -
-
CLOVER
REPLACEMENT
MIDDLE SCHOOL
imo
1927 South Tryon St., Suite 300, Charlotte NC 28203
Phone: 704-338-1292 042
www.optimapa.com
North Carolina License Number C-0914
H0XSL
1. SPILL FULL SIZE CONDENSATE DRAIN FROM EACH AIR
HANDLING UNIT OVER NEAREST FLOOR DRAIN (FLOOR
DRAINS BY PLUMBING CONTRACTOR).
2. ALL FLOOR MOUNTED EQUIPMENT IN MECHANICAL
ROOM SHALL BE MOUNTED ON A 4" THICK CONCRETE
PAD. PADS SHALL BE PROVIDED AND INSTALLED BY
THE GENERAL CONTRACTOR. MECHANICAL CONTRACTOR
SHALL COORDINATE THE EXACT SIZE AND LOCATION
OF ALL PADS NTH THE GENERAL CONTRACTOR.
3. MECHANICAL CONTRACTOR SHALL COORDINATE EXACT
LOCATION OF FLOOR DRAINS NTH PLUMBING
CONTRACTOR PRIOR TO INSTALLATION OF FLOOR
DRAINS. INACCESSIBLE FLOOR DRAINS OR DRAINS
LOCATED UNDER EQUIPMENT ARE NOT ACCEPTABLE.
1. SPILL FULL SIZE CONDENSATE DRAIN FROM EACH AIR
HANDLING UNIT OVER NEAREST FLOOR DRAIN (FLOOR
DRAINS BY PLUMBING CONTRACTOR).
2. ALL FLOOR MOUNTED EQUIPMENT IN MECHANICAL
ROOM SHALL BE MOUNTED ON A 4" THICK CONCRETE
PAD. PADS SHALL BE PROVIDED AND INSTALLED BY
THE GENERAL CONTRACTOR. MECHANICAL CONTRACTOR
SHALL COORDINATE THE EXACT SIZE AND LOCATION
OF ALL PADS NTH THE GENERAL CONTRACTOR.
3. MECHANICAL CONTRACTOR SHALL COORDINATE EXACT
LOCATION OF FLOOR DRAINS NTH PLUMBING
CONTRACTOR PRIOR TO INSTALLATION OF FLOOR
DRAINS. INACCESSIBLE FLOOR DRAINS OR DRAINS
LOCATED UNDER EQUIPMENT ARE NOT ACCEPTABLE.
DIRECT VENT
WATER HEATER
(BY P.C.)
DIRECT VENT
WATER HEATER
(BY P C )
--
1. SPILL FULL SIZE CONDENSATE DRAIN FROM EACH AIR
HANDLING UNIT OVER NEAREST FLOOR DRAIN (FLOOR
DRAINS BY PLUMBING CONTRACTOR).
2. ALL FLOOR MOUNTED EQUIPMENT IN MECHANICAL
ROOM SHALL BE MOUNTED ON A 4" THICK CONCRETE
PAD. PADS SHALL BE PROVIDED AND INSTALLED BY
THE GENERAL CONTRACTOR. MECHANICAL CONTRACTOR
SHALL COORDINATE THE EXACT SIZE AND LOCATION
OF ALL PADS NTH THE GENERAL CONTRACTOR.
3. MECHANICAL CONTRACTOR SHALL COORDINATE EXACT
LOCATION OF FLOOR DRAINS NTH PLUMBING
CONTRACTOR PRIOR TO INSTALLATION OF FLOOR
DRAINS. INACCESSIBLE FLOOR DRAINS OR DRAINS
LOCATED UNDER EQUIPMENT ARE NOT ACCEPTABLE.
At1U-2
LS')P
DIRECT VENT
WATER HEATER
(BY P.C.)
BOX 5...11
227 WEST TRADE STREET
SUITE 700
CHARLOTTE, NORTH CAROLINA 28202
TEL. 704.333.6686
FAX 704.333.2926
WWW.LS3P.COM
BOX 9.11
1UUU
---i - - -
I
I
1
i . .
I
I
. 9.o.
I
. .
T
=
"
OPTIMA
\
ENGINEERING
No. C00710
I
I
MU-A 3- -
I
_V-2" __J 5"y
--
C
- -
6"
SEE 1 -201 FOR
CONTINUATION
_n
4.
' ' ' '
N
SEE 1/M-203 FOR
CONTINUATION
L_.__U_JI
|
3
mu-12
PROVIDE Al HANDLlt'G UNIT
WITH 3-WA HOT AFD CHILLED
WATER CONTROl, VAl VES
HE
042
' ~ SEE 1/M-203 FOR
' ' ' '
CONTINUATION
-
MECH PLATFORM A - MECHANICAL PIPING
MECH PLATFORM B - MECHANICAL PIPING
1/8" = 1'-0=
1/8" = 1'-O"
DIFFERENTIAL PRESSURE
SENSOR FOR CHILLED
WATER PUMP CONTROL
",7 - -- my-_t 541
DP
r
-2"
1
..
MEMBERS OF THE AMERICAN INSTITUTE OF ARCHITECTS
, , ,
'
SEE 1/M-205 FOR
CONTINUATION
COPYRIGHT 2014 ALL RIGHTS RESERVED
PRINTED OR ELECTRONIC DRAWINGS AND
DOCUMENTATION MAY NOT BE REPRODUCED
IN ANY FORM WITHOUT WRITTEN PERMISSION
FROM LS3P ASSOCIATES LTD.
MECH PLATFORM C - MECHANICAL PIPING
REVISIONS:
B -
-
No.
Description
Date
PROJECT:
9201-131360
DATE:
OCT. 31, 2014
DRAWN BY:
SRD
CHECKED BY: RVA
A.2
PLAN
NORTH
N
A2
a2
a2
A.1
B.1
C.1
MECHANICAL
PLATFORM
- PLANS MECHANICAL
PIPING
WALL RATING LEGEND
EWH "
- 042
042
042
3-HOUR FIRE WALL
- - - - 2-HOUR FIRE BARRIER OPT MA # 13 0238
-
042
042
042
042
-
SMOKE PARTITION
V I
SOLUTIONS THROUGH LISTENING
THIS DRAWING IS AN INSTRUMENT OF SERVICE. THE DRAWING AND THE INFORMATION THEREON IS THE PROPERTY OF OPTIMA ENGINEERING, P.A. ANY REPRODUCTION, ALTERATION, OR USE FOR OTHER THAN THE INTENDED PROJECT, WITHOUT THE WRITTEN CONSENT OF OPTIMA ENGINEERING, P.A. IS EXPRESSLY FORBIDDEN. COPYRIGHT ©OPTIMA ENGINEERING P.A. 2014, ALL RIGHTS RESERVED.
1
2
3
4
5
6
BID DOCUMENTS
SCIENCE CLASSROOM WALLS ARE
SMOKE PARTITIONS, DESIGNED TO
RESIST THE PASSAGE OF SMOKE.
SEAL ALL PENETRATIONS OF THESE
WALLS PER THE UL DETAILS SHOWN
ON SHEET M-403 (TYPICAL)
CLOVER SCHOOL
DISTRICT TWO
FULL SIZE RETURN
DUCT DOWN TO AHU
CS B
FULL SIZE RELIEF DUCT
DOWN TO AHU
RETURN
2FULLJIZE pA DOCT
DOWN TO AMU
__
FLEX CONN.
1 12
CLOVER SCHOOL DISTRICT
r mh cMd, rach Day._. ExmHence
8'-O"x2'-6" INTAKE LOUVER
(BY GEN. CONTR.)
x
E -
FU..L
8'-O"x2'-6" INTAKE LOUVER
(BY GEN. CONTR.)
L E RELIEF DUCT DOWN TO ANU--
- - - - '-- - --- - --- - -
(BY PLBG CONTR.)
____
__
CLOVER
REPLACEMENT
MIDDLE SCHOOL
62x24
__-36x3
.. __ _____________
44×24
62x24 RETURN
l
52x24 RETURN
REGEF
l
RETURN
__
______ _
44x24
.
_ ...___ ___ __..-1
- '-------___
44x24
48x96 UP TO
RY-2 ON ROOF
-8'-O"x2'-6" INTAKE LOUVER
(BY GEN. CONTR.)
60x24 DOWN
-FULL SIZE
8'-O"x2'-6" INTAKE LOUVER
FLEX CONN.
40x24 SUPPLY BELOW
REOT RNIOD CHU
FULL SIZE OA OUCT DOWN TO AHU
1500-H
{30x18) [
[
44x24 OUTSIDE AIR ABOVE
60x24
FULL SIZE
RETURN DUCT
DOWN TO AHU
-
D -
imo
FULL SIZE
8'-O"x2'-6" INTAKE LOUVER
(BY GEN. CONTR.)
¾-----.
1927 South Tryon St., Suite 300, Charlotte NC 28203
Phone: 704-338-1292 042
www.optimapa.com
North Carolina License Number C-0914
= ======= =
- - - - "WC,,- -
ay-t ON ROOF
a-8'-O"x2'-6" INTAKE LOUVER
(BY GEN. CONTR.)
---- --R
-- -- -- -- -
---
. _________ .__ __ __
.__ .
--4
FLEX CONN.______
2
EULL SIZE
RELIEF DUCT
DOWN TO AHU -
40x20
=-8'-O"x2'-6" INTAKE LOUVER
(BY GEN. CONTR.)
- -----------
36x28
FLEX CONN.
ELECTRICAL PANELS AND EQUIPMENT
(BY ELECTRICAL CONTRACTOR). MAINTAIN
A MINIMUM OF 6' CLEARANCE BETWEEN TOP
OF PANELS AND BOTTOM OF DUCTWORK
36x30
8'-O"x2'-6" INTAKE LOUVER
(BY GEN. CONTR.)
-----------L-
LS')P
___________
48x96 UP TO
---------
227 WEST TRADE STREET
SUITE 700
CHARLOTTE, NORTH CAROLINA 28202
TEL. 704.333.6686
FAX 704.333.2926
WWW.LS3P.COM
--
.
111111#
52x24
60x24
!__
__ __.
2
=
OPTIMA
\
ENGINEERING %
"
=
PA
No. C00710
C -
A WING MECH PLATFORM - MECHANICAL
1/8" = 1'-O"
111111##
. 221
RELIEF VENT
ROOF CURB
MEMBERS OF THE AMERICAN INSTITUTE OF ARCHITECTS
COPYRIGHT 2014 ALL RIGHTS RESERVED
PRINTED OR ELECTRONIC DRAWINGS AND
DOCUMENTATION MAY NOT BE REPRODUCED
IN ANY FORM WITHOUT WRITTEN PERMISSION
FROM LS3P ASSOCIATES LTD.
_L
5
,
2'-6"x8'-0"
INTAKE LOUVER
(BY GEN. CONTR.) -
-I--
\
28x36
24x60
1
B -
/
|
I
REVISIONS:
-2'-6"x8'-0"
INTAKE
(BY GEN.LOUVER
CONTR.)
_
No.
Description
Date
24x44
96x48
60x24
52x24
FULL SIZE OA DUCT
FULL SIZE RELIEF DUCT FULL SIZE RETURN DUCT-
FLEX CONN. (TYPICAL)
RETURN DUCT
24x6d20x40
___________________________________________________________________________________________J______________________________________________________________________________________________________________________________________________________________________________________
_____________________________________________________________________________________________________________________________
PRoJECT:
9201-131360
DRAWN BY:
SRD
CHECKED BY: RVA
A.3
B.2
C.2
A.1
B.1
C.1
A A.2
® A WING MECH PLATFORM SECTION
p
¹/8" - ¹'-°~
NORTH
N
eeeNo
ENLARGED
MECHANICAL
- PLATFORM
PLANS
M 401
- 042
042
042
3-HOUR FIRE WALL
- - - - 2-HOUR FIRE BARRIER OPT MA # 13 0238
-
042
042
042
042
-
SMOKE PARTITION
SOLUTIONS THROUGH LISTENING
THIS DRAWING IS AN INSTRUMENT OF SERVICE. THE DRAWING AND THE INFORMATION THEREON IS THE PROPERTY OF OPTIMA ENGINEERING, P.A. ANY REPRODUCTION, ALTERATION, OR USE FOR OTHER THAN THE INTENDED PROJECT, WITHOUT THE WRITTEN CONSENT OF OPTIMA ENGINEERING, P.A. IS EXPRESSLY FORBIDDEN. COPYRIGHT ©OPTIMA ENGINEERING P.A. 2014, ALL RIGHTS RESERVED
1
2
3
4
5
6
BID DOCUMENTS
CLOVER SCHOOL
DISTRICT TWO
SCIENCE CLASSROOM WALLS ARE
SMOKE PARTITIONS, DESIGNED TO
RESIST THE PASSAGE OF SMOKE.
SEAL ALL PENETRATIONS OF THESE
WALLS PER THE UL DETAILS SHOWN
ON SHEET M-403 (TYPICAL)
CS B
FULL SIZE RETURN
DUCT DOWN TO AHU
FULL SIZE RELIEF DUCT UP
TO LOUVERED PENTHOUSE
CLOVER SCHOOL DISTRICT
r mh cMd, rach Day... ExmHence
40x16
RETURN
E -
5.12
.
----
,
------------------
FU
FULL fZE OA DUCT
DOWN TO AHU
/
I
FLEX CONN.
I
8'-0"x2'-6" INTAKE LOUVER
(BY GEN. CONTR.)
44x24
I
°
DIRECT VENT
SIZE RI LIEF DUCT DOWN TO AI-1U-
8'-0"x2'-6" INTAKE LOUVER
(BY GEN. CONTR.)
WATER HEATER
(BY PLBG. CONTR.)
CLOVER
REPLACEMENT
MIDDLE SCHOOL
62x24
-
RETURN
44x24
32x24 RETURN
11
A
/
/
t
s
L_ ___.. ______ _ 48xà6u TO
t
--+
44x24
44x24
- - _--- ----- --- - -------..,
8'-0"x2'-6" INTAKE LOUVER
(BY GEN. CONTR.)
52x24 RETURN
a
FLEX CONN.
40x24 SUPPLY BELOW
n
i
n
-FULL SIZE
O
FULL SIZE OA DUCT DOWN TO AHU
TO
U
1927 South Tryon St., Suite 300, Charlotte NC 28203
1500-H
(30x18)
D FULL SIZE RELIEF DUCT
DOWN TO AHU
2
-302
8'-0"x2'-6" INTAKE LOUVER
(BY GEN. CONTR.)
-
I
=-hBLANK 0 AND INSULATE
REAR OF l NUSED LOUVER
T
BLANK OFF AND INSULÃlE
REAR OF UNUSED |LOUVER
L___ ____ ___ __J
- ---
24x30
«--8'-0"x2'-6" INTAKE LOUVER
(BY GEN. CONTR.)
-FLEX CONN.
36x22
8'-O"x2'-6" INTAKE LOUVER
(BY GEN. CONTR.)
8'-0"x2'-6" INTAKE LOUVER
(BY GEN. CONTR.)
---d-----
|
1
..L-----L.
LS P
2
FULL ;SIZE OA DUCT
DOWN TO AHU
FULL SIZE
RETURN DUCT
DOWN TO AHU
48x96 UP TO
By-3 ON ROOF
Phone: 704-338-1292 042
www.optimapa.com
North Carolina License Number C-0914
ELECTRICAL PANELS AND EQUIPMENT
(BY ELECTRICAL CONTRACTOR). MAINTAIN
A MINIMUM OF 6' CLEARANCE BETWEEN TOP
OF PANELS AND BOTTOM OF DUCTWORK
44x24 OUTSIDE AIR ABOVE
I
imo
«--8'-0"x2'-6" INTAKE LOUVER
(BY GEN. CONTR.)
227 WEST TRADE STREET
SUITE 700
CHARLOTTE, NORTH CAROLINA 28202
TEL. 704.333.6686
FAX 704.333.2926
WWW.LS3P.COM
|
i
FLEX CONN.
--
.
--
44x18
50x22
N
-
itHH#
CA
OPTIMA
\
ENGINEERING
No. C00710
-
FULL SIZE OA
DUCT DOWN TO AHU
FULL SIZE RELIEF
DUCT DOWN TO AHU
-
nng
B WING MECH PLATFORM - MECHANICAL
1/8" = 1'-O-
21
7
RELIEF VENT
IHHil
10/31M
MEMBERS OF THE AMERICAN INSTITUTE OF ARCHITECTS
ROOF CURB
COPYRIGHT 2014 ALL RIGHTS RESERVED
PRINTED OR ELECTRONIC DRAWINGS AND
DOCUMENTATION MAY NOT BE REPRODUCED
IN ANY FORM WITHOUT WRITTEN PERMISSION
FROM LS3P ASSOCIATES LTD.
2'-6"x8'-O"
INTAKE LOUVER
(BY GEN. CONTR.) -
B -
96x48
F---1
|24x44
REVISIONS:
_
I
No.
Description
PROJECT:
9201-131360
DATE:
OCT. 31, 2014
DRAWN BY:
SRD
Date
~2'-6"x8'-0"
INTAKE LOUVER
(BY GEN. CONTR.)
24x44
36x36- N
4-36x36
30x30
FLEX CONN. (TYPICAL)
FULL SIZE RELIEF DUCT
FULL SIZE OA DUCT
24x60
24x52
FLEX CONN.
24x40
FLEX CONN.
____L___L___
CHECKED BY: RVA
A.3
B.2
C.2
A.1
B.1
C.1
PLAN
O B WING MECH PLATFORM SECTION
NORTH
2 ,,8- - ,-_O-
N
WALL RATING LEGEND
- 042
042
042
-
3-HOUR FIRE WALL
-
SMOKE PARTITION
ENLARGED
MECHANICAL
- PLATFORM
E W H "U V
- - - - 2-HOUR FIRE BARRIER OPT MA#130238
042
042
042
042
-
SOLUTIONS THROUGH LISTENING
THIS DRAWING IS AN INSTRUMENT OF SERVICE. THE DRAWING AND THE INFORMATION THEREON IS THE PROPERTY OF OPTIMA ENGINEERING, P.A. ANY REPRODUCTION, ALTERATION, OR USE FOR OTHER THAN THE INTENDED PROJECT, WITHOUT THE WRITTEN CONSENT OF OPTIMA ENGINEERING, P.A. IS EXPRESSLY FORBIDDEN. COPYRIGHT ©OPTIMA ENGINEERING P.A. 2014, ALL RIGHTS RESERVED
1
2
3
4
5
6
BID DOCUMENTS