CLOVER SCHOOL DISTRICT TWO CUM Building Value Through Expertise CLOVER REPLACEMENT MIDDLE SCHOOL SE email:kclayton@ccorpusa.com 1466 HIGHWAY 55 CLOVER, SC 29710 BID DOCUMENTS OCT. 31, 2014 9201-131360 TIMMONS GROUP YOUR VISION ACHlEVED THROUGH OURS. CIVIL / LANDSCAPE TIMMONS GROUP 2030 SOUTH TRYON STREET, SUITE 3C CHARLOTTE, NC 28203 tel: 704.376.1073 fax: 704.376.1076 email:brian.crutchfield@timmons.com 042 042 |ff')Q EEIME3|E E RISTS STRUCTURAL ADC ENGINEERING, INC. 7825 BROAD RIVER ROAD IRMO,SC 29063 tel: 803.732.7080 fax: 803.732.7090 email:brian.crutchfield@timmons.com "9'a**''a9 ARCHITECTURAL LS3P ASSOCIATES LTD. 227 WEST TRADE STREETSUITE 700 CHARLOTTE, NC 28202 tel: 704.333.6686 fax:704.333.2926 email:davidbellamy@ls3p.com FIRE PROTECTION PLUMBING MECHANICAL OPTIMA ENGINEERING PA 1927 South Tryon Street CHARLOTTE, NC 28203 tel: 704.338.1292 email:sdaley@optimapa.com ELECTRICAL C CL OV E R M LSD D L E H O O MATERIAL LEGEND (NOTALLMATERIALSAPPLICABLE) PLAN AND SECTION 1466 HIGHWAY 55 CLOVER SC 29710 OSF CONSTRUCTION DOCUMENTS 9201-131360 STRUCTURAL COVER SHEET INDEX OF DRAWINGS BUILDING CODE ANALYSIS FORM F3 (1 of 2) BUILDING CODE ANAYLSIS FORM F3 (2 OF 2) LIFE SAFETY PLAN MIDDLE SCHOOL LIFE SAFETY PLAN FIELD HOUSE AND RESTROOM BUILDING & U.L. DETAILS COM CHECK BUILDING ENVELOPE COMPLIANCE CERTIFICATES CIVIL TIMMONS GROUP 2030 SOUTH TRYON STREET, SUITE 3C CHARLOTTE, NC 28203 tel: 704.376.1073 fax: 704.376.1076 email:brian.crutchfield@timmons.com D - - B C-000 C-001 0-100 C-200 0-201 0-202 C-203 0-204 C-205 C-206 C-300 0-301 0-302 0-303 0-304 C-305 C-306 C-307 C-308 C-400 0-401 0-402 C-403 0-404 OS-001 OS-100 OS-101 OS-102 OS-103 OS-200 OS-201 OS-202 OS-203 OS-204 OS-205 OS-206 OS-207 OS-208 OS-209 OS-300 OS-301 POROUS FILL SPRAY-ON ^ AMSN M C MMON OR FACE) GENERAL G-006 PLYWOOD STRUCTURAL CONCRETE (CAST IN PLACE, ETC.) LIST OF SHEETS G-000 G-001 G-002 G-003 G-004 G-005 EARTH CIVIL COVER SHEET OVERALL SITE PLAN EXISTING CONDITIONS PHASE Ill EROSION CONTROL PLAN PHASE Ill EROSION CONTROL PLAN PHASE Ill EROSION CONTROL PLAN PHASE Ill EROSION CONTROL PLAN EROSION CONTROL NOTES & DETAILS EROSION CONTROL NOTES & DETAILS EROSION CONTROL NOTES & DETAILS SITE & UTILITY PLAN SITE & UTILITY PLAN SITE & UTILITY PLAN SITE & UTILITY PLAN LAYOUT & UTILITIES NOTES & DETAILS LAYOUT & UTILITIES NOTES & DETAILS ATHLETIC FACILITIES NOTES & DETAILS ATHLETIC FACILITIES NOTES & DETAILS ATHLETIC FACILITIES NOTES & DETAILS GRADING & DRAINAGE PLAN GRADING & DRAINAGE PLAN GRADING & DRAINAGE PLAN GRADING & DRAINAGE PLAN BMP DETAILS OVERALL SITE PLAN PHASE I EROSION CONTROL PHASE II EROSION CONTROL PLAN PHASE II EROSION CONTROL PLAN EROSION CONTROL NOTES & DETAILS SITE & UTILITY PLAN SITE & UTILITY PLAN SCDOT ROAD IMPROVEMENTS SCDOT ROAD IMPROVEMENTS SCDOT ROAD IMPROVEMENTS SITE DETAILS STRIPING AND SIGNAGE PLAN STRIPING AND SIGNAGE PLAN SIGHT DISTANCE PROFILES SIGHT DISTANCE PROFILES GRADING & DRAINAGE PLAN GRADING & DRAINAGE PLAN ADC ENGINEERING, INC. 7825 Broad River Road IRMO,SC 29063 tel: 803.732.7080 fax: 803.732.7090 email:KyleM@adcengineering.com S-100 S-101 S-101S S-102 S-102S S-103 S-103S S-104 S-104S S-105 S-105S S-106 S-106S S-107 S-107S S-111 S-112 S-113 S-114 S-115 S-116 S-117 S-121 S-122 S-123 S-124 S-124.1 S-125 S-126 S-127 S-131 S-132 S-133 S-134 S-135 S-136 S-137 S-151 S-152 S-153 S-154 S-155 S-156 S-200 S-210 S-211 S-220 S-221 S-222 S-230 S-231 S-240 S-301 S-302 S-401 S-402 S-501 S-502 S-503 S-504 - GENERAL NOTES & ABBREVIATIONS FOUNDATION PLAN - AREA A.1 SLAB PLAN - AREA A.1 FOUNDATION PLAN - AREA A.2 SLAB PLAN - AREA A.2 HIGH ROOF FRAMING PLAN - AREA A.3 SLAB PLAN - AREA A.3 FOUNDATION PLAN - AREA B.1 SLAB PLAN - AREA B.1 FOUNDATION PLAN - AREA B.2 SLAB PLAN - AREA B.2 FOUNDATION PLAN - AREA C.1 SLAB PLAN - AREA C.1 FOUNDATION PLAN - AREA C.2 SLAB PLAN - AREA C.2 CMU & LINTEL PLAN - AREA A.1 CMU & LINTEL PLAN - AREA A.2 CMU & LINTEL PLAN - AREA A.3 CMU & LINTEL PLAN - AREA B.1 CMU & LINTEL PLAN - AREA B.2 CMU & LINTEL PLAN - AREA C.1 CMU & LINTEL PLAN - AREA C.2 LOW ROOF FRAMING PLAN - AREA A.1 LOW ROOF FRAMING PLAN - AREA A.2 LOW ROOF FRAMING PLAN - AREA A.3 LOW ROOF FRAMING PLAN - AREA B.1 LOW ROOF FRAMING PLAN AREA B.1 LOW ROOF FRAMING PLAN AREA B.2 LOW ROOF FRAMING PLAN AREA C.1 LOW ROOF FRAMING PLAN AREA C.2 HIGH ROOF FRAMING PLAN AREA A.1 HIGH ROOF FRAMING PLAN AREA A.2 HIGH ROOF FRAMING PLAN AREA A.3 HIGH ROOF FRAMING PLAN AREA B.1 HIGH ROOF FRAMING PLAN AREA B.2 HIGH ROOF FRAMING PLAN AREA C.1 HIGH ROOF FRAMING PLAN AREA C.2 PARTIAL AND ENLARGED FRAMING PLANS PARTIAL AND ENLARGED FRAMING PLANS PARTIAL AND ENLARGED FRAMING PLANS PARTIAL AND ENLARGED FRAMING PLANS FIELD HOUSE PLANS RESTROOM BUILDING PLANS SCHEDULES TYPICAL CONCRETE DETAILS TYPICAL CONCRETE DETAILS TYPICAL CMU DETAILS TYPICAL CMU DETAILS TYPICAL CMU DETAILS TYPICAL STEEL DETAILS TYPICAL STEEL DETAILS TYPICAL COLD FORMED METAL BUILDINGS SECTIONS AND DETAILS SECTIONS AND DETAILS SECTIONS AND DETAILS SECTIONS AND DETAILS SECTIONS AND DETAILS SECTIONS AND DETAILS SECTIONS AND DETAILS SECTIONS AND DETAILS ARCHITECTURAL A-001 A-002 A-003 A-004 A-005 A-100 A-101 A-102 A-103 A-104 A-105 A-106 A-107 A-108 A-110A A-110B A-111 A-112 A-113 A-115 A-116 A-117 A-120 A-121 A-122 A-123 A-124 A-125 A-126 A-127 A-151 A-152 A-201 A-202 A-203 A-204 A-205 A-206 A-207 A-208 A-209 A-251 A-252 A-253 A-254 A-255 A-301 A-302 A-303 A-304 A-305 A-306 A-307 A-351 A-352 A-353 A-354 A-355 A-356 A-357 A-401 A-402 A-403 A-404 A-405 A-406 A-408 A-409 A-410 A-411 A-501 A-502 A-503 A-504 A-505 A-506 A-511 A-512 A-513 A-551 A-552 A-553 A-601 A-602 A-603 A-605 A-611 A-612 A-613 A-621 A-622 A-623 A-624 FIRE PROTECTION ARCHITECTURAL SITE PLAN ARCHITECTURAL SITE DETAILS ARCHITECTURAL SITE DETAILS CONSTRUCTION SUBSYSTEMS PARTITION TYPES AND DETAILS OVERALL PLAN AREA A.1 AREA A.2 AREA A.3 AREA B.1 AREA B.2 AREA C.1 AREA C.2 CLERESTORY PLAN FIELD HOUSE PLANS, ELEVATIONS & SECTIONS RESTROOM BUILDING FIELD HOUSE -WALL SECTIONS & ENLARGED DETAILS FIELD HOUSE -WINDOW & DOOR DETAILS FIELD HOUSE ROOM FINISH AND DOOR SCHEDULE OVERALL CANOPY PLANS ENLARGED CANOPY PLANS & DETAILS CANOPY SECTIONS & DETAILS OVERALL REFLECTED CEILING PLAN AREA A.1 REFLECTED CEILING PLAN AREA A.2 REFLECTED CEILING PLAN AREA A.3 REFLECTED CEILING PLAN AREA B.1 REFLECTED CEILING PLAN AREA B.2 REFLECTED CEILING PLAN AREA C.1 REFLECTED CEILING PLAN AREA C.2 REFLECTED CEILING PLAN ROOF PLAN ENLARGED ROOF PLANS OVERALL EXTERIOR ELEVATIONS OVERALL EXTERIOR ELEVATIONS OVERALL EXTERIOR ELEVATIONS BUILDING A ELEVATIONS BUILDING A & B ELEVATIONS BUILDING B ELEVATIONS BUILDING C ELEVATIONS BUILDING B & C ELEVATIONS ELEVATIONS INTERIOR ELEVATIONS INTERIOR ELEVATIONS INTERIOR ELEVATIONS INTERIOR ELEVATIONS INTERIOR ELEVATIONS BUILDING SECTIONS - BUILDING A BUILDING SECTIONS - BUILDING A BUILDING SECTIONS - BUILDING B BUILDING SECTIONS - BUILDING B BUILDING SECTIONS - BUILDING C BUILDING SECTIONS - BLDGS A, B, & C CONNECTORS BUILDING SECTIONS - BLDGS A, B, & C CONNECTORS WALL SECTIONS WALL SECTIONS WALL SECTIONS WALL SECTIONS WALL SECTIONS WALL SECTIONS WALL SECTIONS ENLARGED P.E. TOILET, LOCKER AND SHOWER ROOM PLANS ENLARGED TOILET PLANS ENLARGED SERVICE/ DUMPSTER AREA PLAN ENLARGED SERVICE AND KITCHEN AREA PLAN ENLARGED FLOOR PLANS ENLARGED FLOOR PLANS ATHLETIC FIELD BLEACHERS ENLARGED GYM FLOOR PLAN ENLARGED MECHANICAL PLATFORM STAIR PLANS & SECTIONS PLAN DETAILS PLAN DETAILS ENLARGED DETAILS COMPONENT DETAILS CEILING AND SEISMIC DETAILS CEILING DETAILS SECTION DETAILS SECTION DETAILS SECTION DETAILS LOW SLOPE ROOF DETAILS LOW SLOPE ROOF DETAILS & SKYLIGHT DETAILS METAL ROOF DETAILS DOOR & FRAME SCHEDULE BLDG A DOOR & FRAME SCHEDULE BLDG B & C DOOR, FRAME & WINDOW TYPE LEGEND WINDOW DETAILS INTERIOR FINISH LEGEND INTERIOR FINISH SCHEDULE INTERIOR FINISH SCHEDULE CONT. OVERALL FINISH PLAN ENLARGED FINISH PLAN A.1 & A.2 ENLARGED FINISH PLAN A.3 ENLARGED FINISH PLAN B.1 A-625 A-626 A-627 A-628 A-701 A-702 A-703 A-704 A-705 A-706 A-707 A-708 A-711 A-712 A-751 A-752 A-753 A-754 A-761 A-800 1927 South Tryon Street email: FP-001 FP-101 NOTES, LEGEND, SCHEDULES AND SCHEMATICS - FIRE PROTECTION FLOOR PLANS - FIRE PROTECTION PLUMBING STEEL, IRON BRICK ALUMINUM CERAMIC TILE WOOD (FINISH) 1927 South Tryon Street CHARLOTTE, NC 28203 tel: 704.338.1292 email: P-001 P-002 P-101 P-102 P-103 P-104 P-105 P-106 P-107 P-201 P-202 P-203 P-204 P-205 P-206 P-207 email: gregb@whitmireballington.com CONE / NH / . STUCCO EQUIPMENT PLAN EQUIPMENT PLUMBING ROUGH-INS EQUIPMENT ELECTRICAL ROUGH-INS EQUIPMENT FABRICATED ITEMS sdaley@optimapa.com GLASS WOOD BLOCKING SHINGLES/SIDING NOTES, SCHEDULES, LEGEND - PLUMBING SCHEMATICS - PLUMBING FLOOR PLAN AREA A.1 & A.2 - PLUMBING FLOOR PLAN AREA A.3 - PLUMBING FLOOR PLAN AREA B.1 - PLUMBING FLOOR PLAN AREA B.2 - PLUMBING FLOOR PLAN AREA C.1 - PLUMBING FLOOR PLAN AREA C.2 - PLUMBING MECHANICAL PLATFORM PLANS -PLUMBING FLOOR PLAN AREA A.1 & A.2 -PLUMBING SUPPLY PIPING FLOOR PLAN AREA A.3 -PLUMBING SUPPLY PIPING FLOOR PLAN AREA B.1 -PLUMBING SUPPLY PIPING FLOOR PLAN AREA B.2 -PLUMBING SUPPLY PIPING FLOOR PLAN AREA C.1 -PLUMBING SUPPLY PIPING FLOOR PLAN AREA C.2 -PLUMBING SUPPLY PIPING MECHANICAL PLATFORM PLANS - PLUMBING SUPPLY PIPING ELECTRICAL OPTIMA ENGINEERING PA 1927 South Tryon Street ENGAGE DESIGN TRANSFORM CHARLOTTE, NC 28203 tel: 704.338.1292 email: MECHANICAL E-001 E-002 E-003 E-004 E-005 E-006 E-007 E-008 E-009P E-009P2 E-10 E-11 E-12 E-101 E-102 E-103 E-104 E-105 E-106 E-107 E-108 E-201 E-202 E-203 E-204 E-205 E-206 E-207 E-208 E-209 E-210 E-211 E-301 E-302 E-303 E-304 E-305 E-307 E-501 E-502 E-503 E-504 E-600 E-601 E-700 E-701 E-702 E-703 E-704 E-705 E-706 E-707 OPTIMA ENGINEERING PA 1927 South Tryon Street CHARLOTTE, NC 28203 tel: 704.338.1292 email: M-001 M-002 M-003 M-004 M-005 M-101 M-102 M-103 M-104 M-105 M-106 M-107 M-201 M-202 M-203 M-204 M-205 M-206 M-207 M-301 M-302 M-303 M-304 M-401 M-402 M-403 AREA MAP sdaley@optimapa.com MECHANICAL LEGEND, INDEX, NOTES, AND SCHEDULES MECHANICAL SCHEDULES MECHANICAL SCHEDULES MECHANICAL SEQUENCE OF OPERATION MECHANICAL POINTS LIST FLOOR PLAN AREA A.1 - MECHANICAL FLOOR PLAN AREA A.2 - MECHANICAL FLOOR PLAN AREA B.1 - MECHANICAL FLOOR PLAN AREA B.2 - MECHANICAL FLOOR PLAN AREA C.1 - MECHANICAL FLOOR PLAN AREA C.2 - MECHANICAL ROOF AND FIELD HOUSE PLANS - MECHANICAL FLOOR PLAN AREA A.1 - MECHANICAL PIPING FLOOR PLAN AREA A.2 - MECHANICAL PIPING FLOOR PLAN AREA B.1 - MECHANICAL PIPING FLOOR PLAN AREA B.2 - MECHANICAL PIPING FLOOR PLAN AREA C.1 - MECHANICAL PIPING FLOOR PLAN AREA C.2 - MECHANICAL PIPING MECHANICAL PLATFORM PLANS -MECHANICAL PIPING ENLARGED MECHANICAL PLATFORM PLANS ENLARGED MECHANICAL PLATFORM PLANS ENLARGED MECHANICAL PLATFORM PLANS ENLARGED BOILER ROOM AREA AND FILED HOUSE PLANS MECHANICAL DETAILS MECHANICAL SCHEMATICS AND DETAILS MECHANICAL UL DETAILS mmazzone@optimapa.com 227 WEST TRADE STREET SUITE 700 CHARLOTTE, NORTH CAROLINA 28202 ELECTRICAL NOTES AND LEGENDS ELECTRICAL NOTES ELECTRICAL PENETRATION DETAILS ELECTRICAL DETAILS ELECTRICAL DETAILS ELECTRICAL DETAILS ELECTRICAL DETAILS ELECTRICAL DETAILS PHOTOMETRIC DETAILS ELECTRICAL DETAILS OVERALL ELECTRICAL SITE PLAN ENLARGED ELECTRICAL SITE PLAN ATHLETIC FIELD LIGHTING & ELECTRICAL SITE PLAN FLOOR PLAN - BUILDING A - LIGHTING FLOOR PLAN - BUILDING A - LIGHTING FLOOR PLAN - BUILDING B - LIGHTING FLOOR PLAN - BUILDING B - LIGHTING FLOOR PLAN - BUILDING C - LIGHTING FLOOR PLAN - BUILDING C - LIGHTING FLOOR PLAN - LOFT AREAS - LIGHTING OVERALL FLOOR PLAN - CANOPY FLOOR PLAN - BUILDING A - POWER FLOOR PLAN - BUILDING A - POWER FLOOR PLAN - BUILDING B - POWER FLOOR PLAN - BUILDING B - POWER FLOOR PLAN - BUILDING C - POWER FLOOR PLAN - BUILDING C - POWER ENLARGED KITCHEN ELECTRICAL AND MECHANICAL FIELD HOUSE ELECTRICAL ENLARGED PLAN PLATFORM ELECTRICAL ENLARGED PLAN CLASSROOMS AND PLATFORMS ELECTRICAL ENLARGED PLANS LIGHTING FLOOR PLAN BUILDING A - SPECIAL SYSTEMS FLOOR PLAN BUILDING A - SPECIAL SYSTEMS FLOOR PLAN BUILDING B - SPECIAL SYSTEMS FLOOR PLAN BUILDING B - SPECIAL SYSTEMS FLOOR PLAN BUILDING C - SPECIAL SYSTEMS FLOOR PLAN BUILDING C - SPECIAL SYSTEMS FLOOR PLAN -BUILDING A & B -MECHANICAUELECTRICAL FLOOR PLAN -BUILDING A & B -MECHANICAUELECTRICAL ROOF PLAN - BUILDING A/B - MECHANICAUELECTRICAL ROOF PLAN - BUILDING A/B - MECHANICAUELECTRICAL POWER RISER DIAGRAM ELECTRICAL DETAILS PANEL SCHEDULES PANEL SCHEDULES PANEL SCHEDULES PANEL SCHEDULES PANEL SCHEDULES LIGHTING SCHEDULE AND SEQUENCE OF OPERATIONS LIGHTING SCHEDULE AND SEQUENCE OF OPERATIONS LIGHTING SCHEDULE AND SEQUENCE OF OPERATIONS TEL. 704.333.6686 A/C ADMIN AFF ALT ALUM APPROX ARCH AUTO AUX AV BITUM BL BLDG BOS BOT CAB CJ CL CLG CLG HT C O CLR CMU COL CONC CONF CONT CORR CU FT CU YD DEMO DEPT DET DF DIA .. a) .I 8 PROJECT SITE E 2 3 AIR CONDITION(ING) ADMINISTRATION ABOVE FINISHED FLOOR ALTERNATE ALUMINUM APPROXIMATE(LY) ARCHITECT(URAL) AUTOMATIC AUXILIARY AUDIOVISUAL BITUMINOUS BUILDING LINE BUILDING BOTTOM OF STEEL BOTTOM CABINET CONTROL JOINT CENTER LINE CEILING CEILING HEIGHT C OSET CLEAR(ANCE) CONCRETE MASONRY UNIT COLUMN CONCRETE CONFERENCE CONTINUE. CONTINUOUS CORRIDOR CUBIC FOOT CUBIC YARD DEMOLISH DEPARTMENT DETAIL DRINKING FOUNTAIN DIAMETER 4 FAX 704.333.2926 WWW.LS3P.COM OUT GRAPHIC SYMBOL LEGEND T- BJ408 CENTERLINE M MCAM COLUMN GRID REFERENCE A - - - - AREA REVISED TYPICAL DIMENSION INDICATOR 9 1/2" 0'-9 1/2" DRAWING TITLE DRAWING LOCATION ON SHEET GRID DRAWING NAME A1 DOOR NUMBER FLOOR ELEVATION 0 1/8 L R 1 -0" DRAWING SCALE GLASS TYPE SUBSYSTEM ROOM N UMBER NAME DRAWING LOCATION ON SHEET GRID DRAWING NAME SECTION KEYS NTS DRAWING SCALE SHEET NUMBER WHERE DETAIL IS DRAWN SHEET NUMBER WHERE DETAIL IS REFERENCED SIM A1 A-101 DETAIUPLAN KEY MEMBERS OF THE AMERICAN INSTITUTE OF ARCHITECTS DIRECTION OF SECTION BUILDING SECTION LOCATION ON SHEET GRID A1 A-101 DETAIL LOCATION ON SHEET GRID TERMINATION OF SECTION COPYRIGHT 2014 ALL RIGHTS RESERVED PRINTED OR ELECTRONIC DRAWINGS AND DOCUMENTATION MAY NOT BE REPRODUCED IN ANY FORM WITHOUT WRITTEN PERMISSION FROM LS3P ASSOCIATES LTD. SIM SHEET IDENTIFIER FOR LOCATION OF SECTION SIM DIRECTION OF SECTION WALL SECTION LOCATION ON SHEET GRID A-10 SHEET IDENTIFIER FOR LOCATION OF DETAIL REVISIONS: A1 A-1 1 ENLARGED DETAIL INDICATOR TERMINATION OF SECTION DETAIL LOCATION ON SHEET GRID A1 SO I ENO - | No. Description Date EECR O ELEVATION KEY ELEVATION LOCATION ON SHEET GRID A1 A-201 SHEET IDENTIFIER FOR LOCATION OF ELEVATION ABBREVIATIONS .., 1 - WOOD (ROUGH) SHEET IDENTIFIER FOR LOCAT ON OF DETAIL VICINITY MAP ELEVATION OPTIMA ENGINEERING PA WHITMIRE BALLINGTON 104 HARMON ST LEXINGTON, SC 29072 tel: 803.787.4516 fax: 803.206.4691 KITCHEN KITCHEN KITCHEN KITCHEN MIDDLE SCHOOL SAND, GROUT sdaley@optimapa.com CLOVER CARPET AND PAD PLASTER, CEMENT, CHARLOTTE, NC 28203 tel: 704.338.1292 KITCHEN K-100 K-200 K-300 K-300 MU OPTIMA ENGINEERING PA ENLARGED FINISH PLAN B.2 ENLARGED FINISH PLAN C.1 ENLARGED FINISH PLAN C.2 ENLARGED FNISH PLAN- ROOM PATTERNS TYPICAL CASEWORK LEGEND & SCHEDULE CASEWORK & EQUIPMENT PLAN- AREA A.1 CASEWORK & EQUIPMENT PLAN- AREA A.2 CASEWORK & EQUIPMENT PLAN- AREA A.3 CASEWORK & EQUIPMENT PLAN- AREA B.1 CASEWORK & EQUIPMENT PLAN- AREA B.2 CASEWORK & EQUIPMENT PLAN- AREA C.1 CASEWORK & EQUIPMENT PLAN- AREA C.2 CASEWORK ELEVATIONS CASEWORK ELEVATIONS CASEWORK DETAILS CASEWORK DETAILS CASEWORK DETAILS SCIENCE CASEWORK DETAILS INTERIOR SIGNAGE PERSPECTIVE VIEWS GYPSUM WALLBOARD DIRECTION OF ELEVATION DIAG DIM DIV DS E EA EIFS EJ EL ELEC ELEV ENGL EOS EQ EQUIP EWC EXIST EXP JT EXT F/F FD FE FEC FF EL FHC FIN FLR FLR FOC FOF FOM FOS FOW FT FTG DIAGONAL DIMENSION DIVISION DOWNSPOUT EAST EACH EXTERIOR INSULATION & FINISH SYSTEM EXPANSION JOINT ELEVATION ELECTRIC(AL) ELEVATOR ENCLOSE(D) EDGE OF SLAB EQUAL EQUIPMENT ELECTRIC WATER COOLER EXISTING EXPANSION JOINT EXTERIOR FACE TO FACE FLOOR DRAIN FIRE EXTINGUISHER FIRE EXTINGUISHER CABINET FINISH FLOOR ELEVATION FIRE HOSE CABINET FINISHED FLOOR FLOOR, FILLER FACE OF CURB FACE OF FINISH FACE OF MASONRY FACE OF SLAB FACE OF WALL FOOT, FEET FOOTING FURN GA GALV GC GYP BD GYP PLAS HC HD HDWD HDWR HM HORIZ HT HVAC ID INCL INFO INSUL INT JAN CLO KIT KO LAB LAM LAU LAV LF LVR MAINT MATL MAX MECH MEZZ MFG FURNISH, FURNITURE GAGE GALVANIZED GENERAL CONTRACTOR GYPSUM BOARD GYPSUM PLASTER HANDICAP HEAVY DUTY HARDWOOD HARDWARE HOLLOW METAL HORIZONTAL HEIGHT HEATING, VENTILATION & AIR CONDITIONING INSIDE DIAMETER INCLUDE(D), (ING) INFORMATION INSULATION INTERIOR JANITOR CLOSET KITCHEN KNOCKOUT LABORATORY LAMINATE LAUNDRY LAVATORY LINEAR FEET LOUVER MAINTENANCE MATERIAL MAXIMUM MECHANICAL MEZZANINE MANUFACTURING 5 MFR MIN MISC MO MR MTD MTG MTL N NIC NOM NON COMB NTS OC OD OPP OPT PCF PLAM PLF PLYWD PNL PR PREFAB PREFIN PRKG PSF PSI PT PVC QTR QTY R MANUFACTURER MINIMUM MISCELLANEOUS MASONRY OPENING MOISTURE RESISTANT MOUNTED MOUNTING METAL NORTH NOT IN CONTRACT NOMINAL NON-COMBUSTIBLE NOT TO SCALE ON CENTER OUTSIDE DIAMETER OPPOSITE OPTION(AL) POUNDS PER CUBIC FEET PLASTIC LAMINATE POUNDS PER LINEAR FEET PLYWOOD PANEL PAIR PREFABRICATED PREFINISH PARKING POUNDS PER SQUARE FOOT POUNDS PER SQUARE INCH PAINT, POST-TENSIONED, PRE-TREATED POLYVINYL CHLORIDE (PLASTIC) QUARTER QUANTITY RADIUS, RISER RCP RD REF REQD RL RM RO ROW S SC SD SECT SF SIM SPEC SPKR SQ SS STD STOR SUSP SYS T TEL TEMP TFF THK THRU TO TOB TOC TOF TOJ TOM TOP REFLECTED CEILING PLAN ROOF DRAIN REFRIGERATOR, REFERENCE REQUIRED ROOF LEADER ROOM ROUGH OPENING RIGHT OF WAY SOUTH SOLID CORE STORM DRAIN SECTION SQUARE FEET SIMILAR SPECIFICATION SPEAKER SQUARE STAINLESS STEEL STANDARD STORAGE SUSPENDED SYSTEM TREAD TELEPHONE TEMPORARY TOP OF FINISH FLOOR THICKNESS THROUGH TOP OF TOP OF BEAM TOP OF CONCRETE, CURB TOP OF FOOTING TOP OF JOIST TOP OF MASONRY TOP OF PARAPET 6 TOS TOW TRTD TV TYP UL UNO VERT VEST VIF W W/ W/O W/W WC WD WP WR WT WWF YD TOP OF SLAB TOP OF WALL TREATED TELEVISION TYPICAL UNDERWRITERS LABORATORIES UNLESS NOTED OTHERWISE VERTICAL VESTIBULE VERIFY IN FIELD WEST, WIDE WITH WITHOUT WALL TO WALL WATER CLOSET WOOD WORKING POINT, WATERPROOFING WATER REPELLENT WEIGHT WELDED WIRE FABRIC YARD PROJECT: 9201-131360 DATE: DRAWN BY: OCT. 31, 2014 Author CHECKED BY: Checker INDEX OF DRAWINGS BID DOCUMENTS VENTILATION CALCULATION (IMC TABLE 403.3) CHILLER SCHEDULE E - CHILLER #1 CARRIER 30XA 250 (AIR-COOLED CHILLER) 252 TONS (MIN.); 95* F. AMBIENT; EVAPORATOR: 500 GPM, 44° F. L.W.T., 56° F. E.W.T., 7.5 MAX. P.D., ELEC. DATA: 460V-3ø, COMPRESSORS (2): COMPR. CIRCUIT A: 253.5 RLA, 578 LRA; COMPR. CIRCUIT B: 154.6 RLA, 382 LRA: - WYE DELTA START; FANS: 15 TOTAL, 3.0 FLA (EA); UNIT ELECTRICAL DATA: (SINGLE POINT ELECTRICAL CONNECTION) 516 MCA, 700 MOCP; 20 AMP, 120V CIRCUIT FOR CONTROLS AND HEATERS; CHILLER SHALL BE FURNISHED WITH: 2 COMPRESSORS WITH TWO INDEPENDENT REFRIGERANT CIRCUITS, WYE DELTA STARTER, MICROPROCESSOR BASED CONTROL SYSTEM TO MAINTAIN A CONSTANT LEAVING WATER TEMPERATURE OF 44° F., LEAD-LAG CONTROLS TO MAINTAIN EQUAL COMPRESSOR RUN TIMES, OPEN PROTOCOL TO ALLOW COMMUNICATION WITH THE BUILDING AUTOMATION SYSTEM, FACTORY INSTALLED WATER FLOW SWITCH, ARCHITECTURAL LOUVERED PANELS, PROTECTIVE COIL GUARDS, 5-YEAR COMPRESSOR, PARTS, LABOR, AND REFRIGERANT WARRANTY, MAXIMUM SOUND PRESSURE -80 DBA © 30'. OPERATING WEIGHT = 15720 POUNDS. PROVIDE CHILLER WITH R-134A REFRIGERANT. FULL LOAD EFFICIENCY - 3.14 COP, 4.16 IPLV CHILLER #2 CARRIER 30XA 250 (AIR-COOLED CHILLER) 252 TONS (MIN.); 95* F. AMBIENT; EVAPORATOR: 500 GPM, 44° F. L.W.T., 56° F. E.W.T., 7.5 MAX. P.D., ELEC. DATA: 460V-3ø, COMPRESSORS (2): COMPR. CIRCUIT A: 253.5 RLA, 578 LRA; COMPR. CIRCUIT B: 154.6 RLA, 382 LRA: - WYE DELTA START; FANS: 15 TOTAL, 3.0 FLA (EA); UNIT ELECTRICAL DATA: (SINGLE POINT ELECTRICAL CONNECTION) 516 MCA, 700 MOCP; 20 AMP, 120V CIRCUlT FOR CONTROLS AND HEATERS; CHILLER SHALL BE FURNISHED WITH: -- OCCUPANT DENSITY DEFAULT ACTUAL (#/1000 SF) (PEOPLE) (35) 30 (35) 20 (20) NOTE 2 (20) 30 @ (25) 30 @ (25) 30 @ 5 NOTE 2 50 NOTE 2 ----(100) N/A (10) NOTE 2 35 NOTE 2 25 NOTE 2 20 NOTE 2 70 550 OCCUPANCY CATEGORY CLASSROOMS RESOURCE ROOMS MUSIC/THEATER/DANCE ART ROOM SCIENCE LABS COMPUTER ROOMS OFFICE/ADMIN. CONFERENCE ROOMS CORRIDORS STORAGE ROOMS GYMNASIUM WEIGHT ROOM STAGE (PLATFORM) MEDIA CENTER KITCHEN DINING ROOM 2 COMPRESSORS WITH TWO INDEPENDENT REFRIGERANT VENTILATION REQUIRED PEOPLE O.A. RATE AREA O.A. RATE (CFM/PERSON) (CFM/SQ. FT.) 10 0.12 10 0.12 10 0.06 10 0.18 10 0.18 10 0.12 5 0.06 5 0.06 -0.06 -0.12 -0.3 20 0.06 10 0.06 10 0.12 7.5 0.12 7.5 0.18 REMARKS AGES 9+ PER ARCH PLANS PER ARCH PLANS COORDINATION DRAWINGS DRANNG NUMBER 1. ALL SHOP DRAWINGS AND COORDINATION DRAWNGS NLL BE ¾" SCALE 2. DRAWNGS WILL BE ORIGINAL DRAWNGS AND NOT BE OVERLAYS OF THE CONTRACT/DESIGN DRAWNGS 3. COORDINATION DRAWNGS NLL BE DRAWN ON REPRODUCIBLE MATERIAL 48"x36" 4. COORDINATION DRANNGS ARE NOT SHOP DRANNGS AND ARE REQUIRED IN ADDITION TO SHOP DRAWINGS. 5. ONCE THE COMPLETE COORDINATION DRANNGS HAVE BEEN COMPILED, THE MECHANICAL CONTRACTOR WILL DISTRIBUTE ONE SIGNED SET TO EACH OF THE FOLLOWNG CONTRACTORS: ELECTRICAL, PLUMBING, FIRE PROTECTION, AND GENERAL. ADDITIONAL SETS NLL BE SENT TO THE OWNER, ARCHITECT, AND ENGINEER. NUMBER M-001 M-002 M-003 M-004 M-005 M-101 M-102 M-103 M-104 M-105 M-106 M-107 MECHANICAL INDEX, LEGEND, NOTES, AND SCHEDULES MECHANICAL SCHEDULES MECHANICAL SCHEDULES MECHANICAL SEQUENCE OF OPERATION MECHANICAL POINTS LIST FLOOR PLAN AREA A.1 & A.2 - MECHANICAL FLOOR PLAN AREA A.3 - MECHANICAL FLOOR PLAN AREA B.1 - MECHANICAL FLOOR PLAN AREA B.2 - MECHANICAL FLOOR PLAN AREA C.1 - MECHANICAL FLOOR PLAN AREA C.2 - MECHANICAL ROOF AND FIELD HOUSE PLANS - MECHANICAL M-201 FLOOR PLAN AREA A.1 & A.2 - MECHANICAL PIPING M-202 M-203 M-204 M-205 M-206 M-207 M-301 M-302 M-303 M-304 M-401 M-402 FLOOR PLAN AREA A.3 - MECHANICAL PIPING FLOOR PLAN AREA B.1 - MECHANICAL PIPING FLOOR PLAN AREA B.2 - MECHANICAL PIPING FLOOR PLAN AREA C.1 - MECHANICAL PIPING FLOOR PLAN AREA C.2 - MECHANICAL PIPING MECHANICAL PLATFORM PLANS - MECHANICAL PIPING ENLARGED MECHANICAL PLATFORM PLANS ENLARGED MECHANICAL PLATFORM PLANS ENLARGED MECHANICAL PLATFORM PLANS ENLARGED BOILER ROOM AREA AND FIELD HOUSE PLANS MECHANICAL DETAILS MECHANICAL SCHEMATICS AND DETAILS M-403 MECHANICAL UL DETAILS BT H) BTUH) FLOW (GPM) WATER E.W.T. L.W.T. ('F) ( F) MAX. MANUFACTURER & P.D. MODEL NO. B-1 2,000,000 1,700,000 85 120 160 5' FULTON PHW-2000 B-2 2,000,000 1,700,000 85 120 160 5' FULTON PHW-2000 NOTES: 1. SEE SPECIFICATIONS AND SEQUENCES OF OPERATION FOR ADDITIONAL REQUIREMENTS AND CONTROLS. 2. PROVIDE EACH BOILER WITH A CONDENSATE DRAIN ACID NEUTRALIZATION KIT (AS RECOMMENDED BY BOILER MANUFACTURER). THE OWNER. THE MECHANICAL CONTRACTOR SHALL COORDINATE WITH OWNER'S COMMISSIONING AGENT AND PROVIDE ALL NECESSARY TIME, MATERIALS, AND PROCEDURES REQUIRED FOR A FULLY COMMISSIONED PROJECT. SEE COMMISSIONING REQUIREMENTS IN THE PROJECT MANUAL FOR FURTHER ID.U-1. NOMINAL O.A. COOl lNG CAPACITY HFATING CAPACITY £EM IQ (BTUH) StiC (BTUH) (BTUH) H 35,400 7.5 1200 340 0.4" 33,800 25,600 FI FCTRIC AUXIl lARY HFAT STAGFS AMP_S 1 36.2 3. PROVIDE EACH BOILER WITH A VENTLESS GAS PRESSURE REGULATOR (5 PSIG - 7" W.G.) CHS CHR HWS HWR D CHILLED WATER RETURN HOT WATER SUPPLY HOT WATER RETURN CONDENSATE DRAIN COLD WATER MAKE-UP BALL VALVE BUTTERFLY VALVE GLOBE VALVE CHECK VALVE STRAINER WITH BLOWDOWN VALVE WITH HOSE CONN. CHR HWS HWR D CW ALL DUCTWORK SHALL BE GALVANIZED SHEET METAL CONSTRUCTED IN ACCORDANCE WITH THE LATEST SMACNA STANDARDS. ALL SUPPLY, RETURN AND OUTSIDE AIR DUCTWORK SHALL BE WRAPPED WITH 2" THICK DUCT WRAP WITH VAPOR BARRIER. INSULATION (INCLUDING FLEXIBLE DUCT INSULATION) SHALL HAVE A MINIMUM INSTALLED R-VALUE OF 5.0. TRANSFER DUCTS AND WHERE OTHERWISE INDICATED, DUCTWORK SHALL INSTEAD BE LINED WITH 1" THICK FIBERGLASS DUCT LINER FOR ACOUSTICAL PURPOSES. LINED DUCTWORK DOES NOT ALSO REQUIRE WRAP. DUCT DIMENSIONS ON PLANS ARE INSIDE CLEAR SIZE. PROVIDE BELL MOUTH FITTING AND WELDED WIRE MESH AT OPEN ENDED RETURN DUCTS. INSIDE SURFACE OF LINED DUCTWORK SHALL BE SMOOTH, CLEANABLE, AND TREATED WITH AN EPA APPROVED BIOCIDE TO RESIST FUNGAL/BACTERIAL GROWTH. EXTERNAL DUCT INSULATION TEARS, JOINTS, PUNCTURES AND OTHER PENETRATIONS SHALL BE SEALED WITH MASTIC - DUCT TAPE ALONE IS NOT ACCEPTABLE. $ ALL PIPING, DUCTS, VENTS, ETC., EXTENDING THROUGH WALLS AND ROOF SHALL BE FLASHED AND COUNTERFLASHED IN A WATERPROOF MANNER. 6. ALL PIPING AND DUCTWORK LOCATIONS SHALL BE COORDINATED WITH THE WORK UNDER OTHER DIVISIONS OF THE SPECIFICATIONS, TO AVOID INTERFERENCE. GAGE COCK FLOW SWITCH M lG ECCENTRIC REDUCER CONCENTRIC REDUCER THERMOSTAT (TOP AT 4'-O" ABOVE FLOOR) SWITCH (TOP AT 4'-O" ABOVE FLOOR) ROOM HUMIDISTAT (TOP AT 4'-O" ABOVE FLOOR) BUILDING PRESSURE SENSOR (TOP AT 4'-O" ABOVE FLOOR) 10. PROVIDE MANUFACTURER'S RECOMMENDED CLEARANCES AROUND ALL EQUIPMENT FOR MAINTENANCE AND FILTER REMOVAL (TOP AT 4'-O" ABOVE FLOOR) SUPPLY AIR DIFFUSER OR FI FCTRICAI DATA EU.SE 208v-1ø 4.1 5.1 60 15 50.4 VOI TAGF 208V-1ø MANUFACTURFR CARRIER REFRIGERANT WFIGHT FB4CNF036 144 LBS. MATCHING HP_E OUTDOOR UNIT R-410A 11P-1 RETURN AIR GRILLE WITH SOUND ATTENUATION (SEE DETAIL) DOUBLE LINE DUCTWORK 0 SINGLE LINE DUCTWORK + [ 1. 2. + FIRE DAMPER (3 HR RATED) WITH + + 2Ox14 8"ø __ ALTERNATE #4 - OWNER PREFERRED CONTROLS - AUTOMATED LOGIC. PROVIDE AN ALTERNATE PRICE FOR DDC CONTROLS BY AUTOMATED LOGIC BY HARRIS INTEGRATED SOLUTIONS. SEE ARCHITECTURAL SPECIFICATIONS (SECTION 012300) AND BID FORM FOR -- BAROMETRIC DAMPER WITH COUNTERWEIGHT -- DUCT MOUNTED HUMIDITY SENSOR 14. ANY DEVICE REQUIRING A THERMOSTAT FOR CONTROL SHALL BE FURNISHED WITH A THERMOSTAT WHETHER INDICATED ON THE DRAWINGS OR NOT. DETAILS. 19. KITCHEN HOOD EXHAUST DUCT SHALL BE 16 GAUGE CARBON STEEL. ALL JOINTS AND SEAMS SHALL BE CONSTRUCTED WITH A CONTINUOUS LIQUIDTIGHT EXTERNAL WELD. ALL DUCTWORK SHALL SLOPE A MINIMUM OF ¼ INCH PER FOOT TOWARD HOOD. PROVIDE CLEANOUTS AT EVERY CHANGE OF D C O E EX UST DUCT AND AT 20 -0" (MINIMUM) INTERVALS. HEAT PUMP SCHEDULE NOMINAl B - COOl ING CAPACITY TONNAGE E (BEH) SB£ (BEH) 3 33,800 25,600 BP-1 FFFICIFNCY HFATING CAPACITY EER SEER ER 10.5 13.0 -- (BEH) 35,400 EFFICIENCY COP 3.5 COMPRFSSOR HSPF 7.8 LBA 88.0 ELA 11.7 Eali ELA 0.9 FI FCTRICAI DATA MCA 15.5 EU.SE 25 VOLTAGE 208V-3ø OPERATING MANUFACTURFR MATCHING WElGHT 211 LBS CARRIFR MODFI 25HBB336 INDOOR UNIT 1D.U-1. NCE OF E L CA U OR HAVING UR D TIO CONCEALING KITCHEN HOOD EXHAUST DUCTWORK. P OR T 20. DISHWASHER EXHAUST DUCT SHALL BE STAINLESS STEEL. ALL JOINTS AND SEAMS SHALL HAVE A LIQUID TIGHT CONTINUOUS EXTERNAL WELD. EXHAUST DUCT SHALL SLOPE DOWN IN DIRECTION OF HOOD A MINIMUM OF 1" PER FOOT. NOTES: 1. COOLING CAPACITY @ 95* AMBIENT 2. 3. ALL UNITS SHALL BE U.L LISTED AND ASHRAE 90.1 COMPLIANT HEAT PUMP SUPPLEMENTARY ELECTRIC RESISTANCE HEAT SHALL BE PROVIDED WTH CONTROLS TO PREVENT OPERATION WHEN THE REVERSE CYCLE HEAT CAN MEET HEATING LOAD. SUPPLEMENTAL ELECTRIC HEAT SHALL BE ALLOWED TO OPERATE DURING HEAT PUMP DEFROST CYCLE. SUPPLEMENTAL ELECTRIC HEAT SHALL BE LOCKED OUT WHEN THE OUTDOOR TEMPERATURE IS BETWEEN 35"F AND 40'F AND THE INDOOR TEMPERATURE SETPOINT IS INCREASED. MOUNT UNITS ON A 4" THICK CONCRETE PAD AND PROVIDE MANUFACTURER'S RECOMMENDED CLEARANCES AROUND UNITS. 4. 21. FUME HOOD, PREP ROOM, AND CHEMICAL STORAGE EXHAUST DUCTWORK SHALL BE CONSTRUCTED OF APPROVED G90 GALVANIZED SHEET STEEL WITH A MINIMUM NOMINAL THICKNESS OF 18 GAUGE. DUCTWORK AND EXHAUST SYSTEM SHALL MEET THE REQUIREMENTS OF NCMC SECTION 510. 22. MINIMUM GAS PIPING SIZE SHALL BE ¾". 23. GAS PIPING AND FITTINGS SHALL BE BLACK STEEL, SCHEDULE 40, IN ACCORDANCE WITH ASTM SPECIFICATION A 106, WITH 150 PSI BLACK MALLEABLE IRON FITTINGS IN ACCORDANCE WITH ASTM SPECIFICATION A 47, GRADE 32510, AND ASA SPECIFICATION B16.3, 125 LB. 24. GAS PIPING SHALL BE INSTALLED TO THE REQUIREMENTS OF THE STATE BUILDING CODE AND NFPA STANDARD NO. 54. ALL PIPING TO BE SUPPORTED BY CLEVIS HANGERS WITH GALVANIZED ROD A MAXIMUM OF 8' ON CENTER. PIPING SHALL BE SUPPORTED BY ROD HANGERS IN THE PIPE RUN 12" OR LESS IN LENGTH FROM THE TOP OF THE PIPE TO THE ELECTRIC DUCT HEATER SCHEDULE SYMROI I OCATION £EM EDH-1 KITCHEN OFFICES 215 Bl.SE 44 K.E. S.IEP_S 3.0 1 SUPPORTING STRUCTURE PER THE STATE BUILDING CODE AND ASCE 7. VOLTAGE 460V-3ø MAX. P.D. 0.25- 25. GAS PIPING SHALL BE TESTED IN ACCORDANCE WITH THE PROCEDURES DESCRIBED IN NFPA NO 54. ANY OTHER TEST AS REQUIRED BY THE LOCAL GAS INSPECTION DEPARTMENT OR GAS COMPANY SHALL ALSO BE PERFORMED. 26. PAINT ALL GAS PIPING WITH TWO COATS OF YELLOW ENAMEL AND STENCIL "2-PSI GAS" ON PIPE AT 5'-0" CENTERS. A - 27. GAS VALVES SHALL BE MIN. 125 PSI RATED, NON-LUBRICATED PLUG TYPE WITH BRONZE BODY AND BRONZE PLUG. 28. GAS PIPING BELOW GRADE SHALL BE BLACK STEEL, SCHEDULE 40, IN ACCORDANCE WITH ASTM SPECIFICATION A 53 OR A 120 WITH FORGED STEEL WELDING TYPE FITTINGS IN ACCORDANCE WITH ASTM SPECIFICATION A 234 WITH AWWA C105 POLYETHYLENE JACKET OR DOUBLE LAYER, HALF LAPPED 10 MIL POLYETHYLENE TAPE. JOINTS SHALL BE ANSI B31.1, ANSI B31.2, ANSI B31.9, ASME SEC 1 WELDED. NOTES: 1. ALL HEATERS SHALL BE OPEN-COIL, SLIP-IN TYPE HEATERS. 2. ALL HEATERS SHALL HAVE STEP CONTROL WTH NUMBER OF STEPS AS INDICATED ABOVE. 3. PROVIDE HEATERS NTH THE FOLLOWNG BUILT-IN AND PRE-NRED COMPONENTS: DISCONNECTING TYPE MAGNETIC CONTACTORS, FUSES PER N.E.C., CONTROL VOLTAGE TRANSFORMER, AIR FLOW SNTCH. 29. ALL CHILLED WATER AND HOT WATER PIPING 1" AND LESS SHALL BE SCHEDULE-0 BLACK STEEL OR HARD-DRAWN TYPE-L COPPER PIPE AND FITTINGS. ALL CHILLED WATER AND HOT WATER PIPING GREATER THAN 1" SHALL BE SCHEDULE-40 BLACK STEEL. WWW.LS3P.COM 20"x 14" RECTANGULAR DUCT 8" DIAMETER ROUND DUCT SMOKE DETECTOR (INSTALLER SHALL PROVIDE STATIC PRESSURE READINGS AT ALL INSTALLATIONS) MOTORIZED DAMPER -- 18. DRYER VENT WALL CAPS SHALL BE PROVIDED WITH A BACKDRAFT DAMPER. DRYER VENT SHALL NOT EXCEED A TOTAL EQUIVALENT LENGTH OF 35'-0" WITH A 2.5' DEDUCTION FOR EACH 45' BEND AND A 5' DEDUCTION FOR EACH 90' BEND. 227 WEST TRADE STREET SUITE 700 CHARLOTTE, NORTH CAROLINA 28202 TEL. 704.333.6686 FAX 704.333.2926 MANUAL VOLUME DAMPER -- JACKET AND SEALED WATERTIGHT. 17. MECHANICAL CONTRACTOR SHALL LOCATE EXHAUST FANS, OUTLETS, AND GAS FLUES A MINIMUM OF 15'-0" FROM ANY OUTSIDE AIR INTAKE. ACCESS DOOR (SEE DETAIL) MVD unsus OPTIMA ENGINEERING No. 0710 0F HHnD AIRFLOW MONITORING STATION DIFFERENTIAL PRESSURE SENSOR (FOR PUMP CONTROL) UNDER-CUT DOOR (BY G.C.) O.A. OUTSIDE AIR 2 VARIABLE FREQUENCY DRIVE WITH DISCONNECT SWITCH ABOVE (TOP AT 6'-6" MAX A.F.F.) 16. MECHANICAL CONTRACTOR SHALL VERIFY LOCATION OF ROOF PENETRATIONS FOR RELIEF HOODS AND OUTSIDE AIR HOODS WITH ARCHITECT & OWNER PRIOR TO INSTALLATION. ALTERNATE #3 - OWNER PREFERRED EQUIPMENT - CARRIER. PROVIDE AN ALTERNATE PRICE FOR ALL DX ROOFTOP UNITS, SPLIT SYSTEMS, CHILLERS, AIR HANDLING UNITS, AND TERMINAL UNITS BY CARRIER. ENGAGE DESIGN TRAMSRORM FD3 15. LOCATE THE TOP OF ALL THERMOSTATS AND SWITCHES 4'-0" ABOVE FINISH FLOOR. COORDINATE EXACT THERMOSTAT LOCATION WITH OWNER PRIOR TO INSTALLATION. ANY DEVICE ON A PERIMETER WALL SHALL BE MOUNTED ON A FOAM-FILLED ELECTRICAL BOX, WITH ALL GAPS BETWEEN BOX AND WALL SEALED TO PREVENT INFILTRATION. COOLING CAPACITY BASED ON 80*/67' ENTERING AIR. PROVIDE UNITS WITH: DDC THERMOSTAT, 1" THICK DISPOSABLE FILTER (MERV 8 MINIMUM), FIELD INSTALLED HEATER, U.L LABEL, SINGLE POINT ELECTRICAL CONNECTION, 1-INCH INSULATION. FIRE DAMPER (1½ HR RATED) WITH ACCESS DOOR (SEE DETAIL) FD DP NOTES: - EXHAUST AIR GRILLE CONDENSATE DRAINS SHALL BE INSULATED WITH ½" THICK ARMAFLEX INSULATION. MINIMUM DRAIN SIZE SHALL BE ¾". MCA EU.SE AMP_S Phone: 704-338-1292 042 www.optimapa.com North Carolina License Number C-0914 RETURN AIR GRILLE FITTINGS. DRAINS FROM AIR HANDLING UNITS SHALL BE TRAPPED. FAN MOTOR 1927 South Tryon St., Suite 300, Charlotte NC 28203 DUCT MOUNTED STATIC PRESSURE SENSOR 12. CONDENSATE DRAIN PIPING SHALL BE TYPE 'L' HARD DRAWN COPPER AND ELA engineering CARBON MONOXIDE SENSOR 11. PROVIDE TWO COPIES OF INSTALLATION, OPERATION, AND MAINTENANCE MANUALS TO THE OWNER WITHIN 15 CALENDAR DAYS OF ACCEPTANCE OF THE SYSTEM. VOI TAGF imo CO2 SENSOR (TOP AT 4'-O" ABOVE FLOOR) (SEE SEQUENCE OF OPERABON) REPORT SHALL BE PROVIDED AT NO ADDITIONAL COST. TEST AND BALANCE REPORT TO BE COMPLETED BY AN INDEPENDENT, CERTIFIED NEBB OR AABC TEST AND BALANCE CONTRACTOR. SUBSTANTIAL COMPLETION. ExceNm!cc CLOVER REPLACEMENT MIDDLE SCHOOL PRESSURE GAGE & COCK (AT ENGINEER'S OR Cx AGENT'S REQUEST) AFTER REVIEW OF THE INITIAL 9. PROVIDE A ONE YEAR WARRANTY FOR ALL WORK PERFORMED BEGINNING AT Each ChHci. Eoch Day THERMOMETER 7. THE MECHANICAL CONTRACTOR SHALL BALANCE ALL MECHANICAL SYSTEMS TO THE PERFORMANCE SPECIFICATIONS INDICATED ON PLANS AND PROVIDE THE ENGINEER WITH THREE COPIES OF A COMPLETE TEST AND BALANCE REPORT. THE REPORT IS TO BE ISSUED A MINIMUM OF TWO WEEKS PRIOR TO SUBSTANTIAL COMPLETION. THE TEST AND BALANCE REPORT WILL BE SUBJECT TO REVIEW AND APPROVAL BY THE ENGINEER AND COMMISSIONING AGENT. ANY ADDITIONAL TESTING, ADJUSTING AND BALANCING REQUIRED 8. UPON PROJECT COMPLETION, THE MECHANICAL CONTRACTOR IS RESPONSIBLE FOR PROVIDING THE OWNER INSTALLATION INFORMATION INCLUDING FULL SUBMITTALS AND O&M MANUALS FOR EACH PIECE OF EQUIPMENT INCLUDING ALL SELECTED OPTIONS, THE NAME AND ADDRESS OF AT LEAST ONE SERVICE AGENCY, FULL CONTROL SYSTEM O&M AND CALIBRATION INFORMATION INCLUDING WIRING DIAGRAMS, SCHEMATICS, FULL SEQUENCE OF OPERATION, AND PROGRAMMED SETPOINTS. CLOVER SCHOOL DISTRICT UNION ALL DUCTWORK SHALL BE SEALED FOR THE REQUIREMENTS OF THE INTERNATIONAL MECHANICAL CODE. SEAL MEDIUM PRESSURE SUPPLY DUCTWORK FOR POSITIVE 3" PRESSURE CLASS, SMACNA SEAL CLASS A, SMACNA LEAKAGE CLASS 12. SEAL LOW PRESSURE SUPPLY, RETURN, 5. CS B BALANCING VALVE B&G CIRCUIT SETTER 4. PROVIDE DISCONNECT SWITCH WITH EACH BOILER. INFORMATION. RM NI AI MA N% CHILLED WATER SUPPLY ÞK De( IN CLOVERSCHOOL DISTRICT TWO ABBR. CHS CW- 13. ALL REFRIGERANT PIPE SHALL BE NITROGENIZED ACR COPPER TUBE. SIZE, INSULATE, AND INSTALL REFRIGERANT PIPING PER MANUFACTURER'S RECOMMENDATIONS. REFRIGERANT PIPING SHALL BE INSULATED PER THE MFG. RECOMMENDATIONS, WITH A MINIMUM INSULATIN OF ¾" THICK ARMAFLEX. EXTERIOR PIPING SHALL BE COVERED WITH AN ALUMINUM TONNAGE 3 ALL COST ASSOCIATED WITH SUBSTITUTED EQUIPMENT TO COMPLY WITH BASIS OF DESIGN, INCLUDING PROVIDING MAINTENANCE ACCESS, CLEARANCE, PIPING, SHEET METAL, ELECTRICAL, REPLACEMENT OF OTHER SYSTEM COMPONENTS, BUILDING ALTERATIONS, ETC., SHALL BE INCLUDED IN THE ORIGINAL BASE BID. NO ADDITIONAL COST ASSOCIATED WITH SUBSTITUTED EQUIPMENT WILL BE APPROVED DURING CONSTRUCTION AND ALL COST WILL BE THE RESPONSIBILITY OF THE MECHANICAL CONTRACTOR. THIS INCLUDES ANY MODIFICATIONS TO ANY ASSOCIATED MECHANICAL, PLUMBING, OR ELECTRICAL SYSTEMS REQUIRED BY THIS SPECIFIC MANUFACTURER'S INSTALLATION INSTRUCTIONS. DESCRIPTION [ INDOOR UNIT SCHEDULE THIS PROJECT INCLUDES A THIRD PARTY COMMISSIONING AGENT CONTRACTED BY SYMBOL DO NOT SCALE DRAWINGS. SEE ARCHITECTURAL DRAWINGS AND REFLECTED CEILING PLANS FOR EXACT LOCATION OF DOORS, WINDOWS, CEILING DIFFUSERS, ETC. PRESSURE CLASS, SMACNA SEAL CLASS A, SMACNA LEAKAGE CLASS 12. CONDENSING BOILER SCHEDULE DRAWNG NAME MECHANICAL LEGEND OUTSIDE AIR, AND EXHAUST DUCTWORK FOR POSITIVE/NEGATIVE 2" NOTE: ALL COST ASSOCIATED WITH SUBSTITUTED EQUIPMENT TO COMPLY WITH BASIS OF DESIGN, INCLUDING PROVIDING MAINTENANCE ACCESS, CLEARANCE, PIPING, SHEET METAL, ELECTRICAL, REPLACEMENT OF OTHER SYSTEM COMPONENTS, BUILDING ALTERATIONS, ETC., SHALL BE INCLUDED IN THE ORIGINAL BASE BID. NO ADDITIONAL COST ASSOCIATED WITH SUBSTITUTED EQUIPMENT WILL BE APPROVED DURING CONSTRUCTION AND ALL COST WILL BE THE RESPONSIBILITY OF THE MECHANICAL CONTRACTOR. C - COMMISSIONING NOTE 3. (*) - SEE MECHANICAL ALTERNATES SECTION, THIS PAGE MECHANICAL DRAWING INDEX THE MECHANICAL CONTRACTOR SHALL ORGANIZE COORDINATION MEETINGS TO DEVELOP A SET OF DRANNGS NTH ALL CONTRACTORS (ELECTRICAL, MECHANICAL, PLUMBING, FIRE PROTECTION, AND GENERAL CONTRACTOR). THE MECHANICAL CONTRACTOR WLL HAVE THE LEAD RESPONSIBILITY FOR THE COORDINATION DRAWNGS. THE MECHANICAL CONTRACTOR SHALL PRODUCE THE ORIGINAL DRAWINGS AND FORWARD THE DRANNGS TO EACH OF THE OTHER CONTRACTORS FOR THEM TO ADD THEIR SYSTEMS TO THIS SET OF COORDINATION DRAWNGS. THE CONTRACTORS WILL DEVELOP THE DRAWNGS IN THIS ORDER: MECHANICAL, FIRE PROTECTION, PLUMBING, ELECTRICAL, AND GENERAL. THIS SHALL ALSO BE THE ORDER OF PRECEDENCE FOR INSTALLATION OF SYSTEMS. ANY RELOCATION OF SYSTEM ROUTINGS NLL BE FOUND IN THE COORDINATION PHASE AND NOTICED BY EACH OF THE CONTRACTORS. THESE DRAWNGS, WHEN COMPLETED, SHALL BE SIGNED OFF BY ALL OF THE ABOVE LISTED PARTIES. DRAWINGS SHALL BE COMPLETED PRIOR TO FABRICATION AND INSTALLATION OF DUCTWORK AND PIPING SYSTEMS, OR PURCHASE OF EQUIPMENT. THE FOLLOWING ITEMS REPRESENT THE MINIMUM REQUIREMENTS FOR SHOP DRANNGS AND COORDINATION DRANNGS: __ 2. 4. NOTES: 1. PROVIDE PHASE LOSS/BROWNOUT PROTECTION. 2. PROVIDE LOW AND HIGH-PRESSURE SWITCHES, NOT SIMPLY A LOSS OF CHARGE SWITCH. 3. PROVIDE OIL PROTECTION FOR SEMI-HERMETIC COMPRESSORS. 4. ALL UNITS SHALL HAVE STANDARD 24-VOLT CONTROL CIRCUIT OPERATION WITH CONTROL SYSTEM WITHOUT ADDITIONAL INTERFACES OR GATEWAYS, COORDINATE WITH CONTROLS CONTRACTOR. D - AS INDICATED IN THE SPECIFICATIONS, PRIOR APPROVAL IS REQUIRED FOR ALL MANUFACTURERS NOT LISTED. CONDENSING BOILERS: AERCO, FULTON, LAARS, LOCHINVAR, RAYPACK, R.B.I., PATTERSON KELLY PUMPS & HYDRONIC EQUIPMENT: ARMSTRONG, BELL & GOSSETT, TACO, PEERLESS PUMP (*) AIR-COOl FD CHil I FRS: CARRIER, TRANE, YORK, McQUAY (*) MODULAR AIR HANDLING UNITS: CARRIER, TRANE, YORK, McQUAY VARIABLE FREQUENCY DRIVES: ABB, DANFOSS GRAHAM, CUTLER HAMMER, JOHNSON CONTROLS KITCHEN HOODS: CAPTIVE-AIRE, GREENHECK, HALTON ENERGY RECOVERY UNITS: ANNEXAIRE, ENGINEERED AIR, MUNTERS, INNOVENT, VENTROL (*) DUCTED SPLIT SYSTEMS & DX ROOFTOP UNITS: CARRIER, TRANE, YORK 1. EXHAUST REQUIREMENTS: TOLETS - 75 CFM PER FLUSHING FlXTURE LOCKER ROOMS - 0.5 CFM/SF JANITOR'S CLOSET - 1.0 CFM/SF SCIENCE LABS - 1.0 CFM/SF 2. DEFAULT OCCUPANT DENSITY IS USED WHEN ACTUAL OCCUPANT DENSITY IS NOT KNOWN. 3. ALL AREAS ARE MULTIPLE ZONE RECIRCULATING SYSTEMS PER 6.2.5 NTH VENTILATION REQUIREMENTS ARE BASED ON A ZONE AIR DISTRIBUTION EFFECTIVENESS OF 1.0 FOR COOLING AND O.8 FOR HEATING. SYSTEM, FACTORY INSTALLED WATER FLOW SWITCH, ARCHITECTURAL LOUVERED PANELS, PROTECTIVE COIL GUARDS, 5-YEAR COMPRESSOR, PARTS, LABOR, AND REFRIGERANT WARRANTY, MAXIMUM SOUND PRESSURE -80 DBA © 30'. OPERATING WEIGHT = 15720 POUNDS. PROVIDE CHILLER WITH R-134A REFRIGERANT. FULL LOAD EFFICIENCY -3.14 COP, 4.16 IPLV 1. EaliS; COOK, GREENHECK, PENN AIR DISTRIBUTION: CARNES, METAL*AIRE, NAILOR, PRICE, TITUS, TUTTLE & BAILEY, KRUEGER FIRF DAMPFRS: AIR BALANCE INC., GREENHECK, NAILOR, RUSKIN, POTTORFF, PREFCO, SAFE-AIRE LOUVERS: REMOVED (ALL LOUVERS ARE BY THE G.C.) DUCTI FSS SPI IT SYSTFMS: DAIKIN, MITSUBISHI, PANASONIC, LG (*) VAV TFRMINAl UNITS: TRANE, CARRIER, ENVIRO-TEC, NAILOR, PRICE, TITUS, KRUEGER FI FCTRIC HFATFRS: REZNOR, MARKEL, MODINE, INDEECO, REDD-l SPIRAL DUCTWORK: EASTERN SHEET METAL, LINDAB, UNITED MCGILL, HAMLIN (*) DDC CONTROLS: AUTOMATED LOGIC, SCHNEIDER ELECTRIC, HOFFMAN BUILDING TECHNOLOGIES NOTFS: PROTOCOL TO ALLOW COMMUNICATION WITH THE BUILDING AUTOMATION LISTING OF MANUFACTURER'S NAME DOES NOT GUARANTEE APPROVAL. ALL EQUIPMENT MUST MEET OR EXCEED QUALITY AND CAPACITIES OF SPECIFIED EQUIPMENT. FINAL APPROVAL WILL BE BASED ON EQUIPMENT SUBMITTALS. ANY MANUFACTURER NOT LISTED BUT WISHING TO BID THIS PROJECT SHALL SUBMIT A WRITTEN REQUEST A MINIMUM OF 7 DAYS PRIOR TO BID DATE OR @ - ASSUMES ROOM IS OCCUPIED BY LARGEST CLASSROOM SIZE. CIRCUITS, WYE DELTA STARTER, MICROPROCESSOR BASED CONTROL SYSTEM TO MAINTAIN A CONSTANT LEAVING WATER TEMPERATURE OF 44° F., LEAD-LAG CONTROLS TO MAINTAIN EQUAL COMPRESSOR RUN TIMES, OPEN MECHANICAL 523NERAL NOTES EQUIVALENT MANUFACTURERS LISTING 7 10/31M MEMBERS OF THE AMERICAN INSTITUTE OF ARCHITECTS 29. CHILLED WATER PIPING SHALL BE INSULATED WITH 1½" THICK PHENOLIC CLOSED CELL, ASTM C1126 RIGID FOAM, 2.2 LBS. NOMINAL DENSITY, CFC FREE; ASTM C518, K-VALUE OF 0.13 AT 75° F. HOT WATER PIPING SHALL BE INSULATED WITH 1½" THICK FIBERGLASS INSULATION WITH A DENSITY OF 1.5 LB PER CUBIC FOOT. COPYRIGHT 2014 ALL RIGHTS RESERVED PRINTED OR ELECTRONIC DRAWINGS AND DOCUMENTATION MAY NOT BE REPRODUCED IN ANY FORM WITHOUT WRITTEN PERMISSION FROM LS3P ASSOCIATES LTD. INSULATION SHALL HAVE A FACTORY APPLIED PRESSURIZED VAPOR BARRIER JACKET WITH PRESSURE SENSITIVE ADHESIVE SELF-SEALING LAP. ALL FITTINGS SHALL HAVE PVC FITTING COVERS. ALL PIPING OUTSIDE SHALL HAVE A BITUMINOUS COATING ALUMINUM JACKET AND PVC FITTING COVERS. 30. ALL CHILLED WATER AND HOT WATER PIPING SHALL PITCH DOWN IN DIRECTION OF FLOW WITH MANUAL AIR VENTS AT ALL HIGH POINTS AND ½" DRAIN VALVES AT ALL LOW POINTS. 31. PROVIDE UNIONS, FLANGES OR COUPLINGS AT CONNECTION TO ALL VALVES AND EQUIPMENT. DO NOT USE DIRECT WELDED OR THREADED CONNECTIONS TO VALVES, EQUIPMENT OR OTHER APPARATUS. REVISIONS: _ No. Description PROJECT: 9201-131360 DATE: OCT.31,2014 DRAWN BY: SRD Date 32. PROVIDE NON-CONDUCTING DIELECTRIC UNIONS WHENEVER CONNECTING DISSIMILAR METALS. 33. EQUIPMENT OPERATED DURING CONSTRUCTION SHALL USE TEMPORARY FILTERED MEDIA ON EQUIPMENT AND DUCT OPENINGS TO PREVENT CONSTRUCTION DEBRIS FROM ENTERING COILS, DUCTWORK SYSTEMS, AIR TERMINALS ETC. AT COMPLETION OF CONSTRUCTION, MECHANICAL CONTRACTOR SHALL CLEAN ALL SYSTEMS WITH ALL CONTROL DEVICES WIDE OPEN AND REMOVE ANY REMAINING DEBRIS PRIOR TO TEST AND BALANCING. MECHANICAL CONTRACTOR SHALL REPLACE ALL FILTRATION WITH NEW PERMANENT FILTERS AT COMPLETION OF CONSTRUCTION. ANY DUCTWORK, AIR TERMINALS, AND/OR OTHER EQUIPMENT UPSTREAM OF FILTRATION SHALL BE CLEANED THOROUGHLY OF CONSTRUCTION DEBRIS BEFORE HANDING OVER TO OWNER. 34. THE MECHANICAL CONTRACTOR SHALL BE RESPONSIBLE FOR PROVIDING RESTRAINTS TO RESIST THE EARTHQUAKE EFFECTS ON THE MECHANICAL SYSTEMS. THE REQUIREMENTS FOR THOSE RESTRAINTS ARE FOUND IN THE INTERNATIONAL BUILDING CODE AND ASCE 7. THE ANCHORAGE OF THE MECHANICAL SYSTEMS SHALL COMPLY WITH THE REQUIREMENTS OF THE INTERNATIONAL BUILDING CODE AND ASCE 7. CHECKED BY: RVA 35. CHILLED WATER PIPING BELOW GRADE SHALL BE FACTORY PREINSULATED INSULTEK 250 STEEL AS MANUFACTURED BY PREINSULATED PIPING SYSTEMS, INC. (OR EQUAL). CARRIER PIPE SHALL BE SCHEDULE 40 ASTM A53 GRADE B BEVELED FOR WELDING. INSULATION SHALL BE FOAMED IN-PLACE CLOSED CELL POLYURETHANE FOAM COMPLETELY FILLING THE ANNULUS BETWEEN THE CARRIER PIPE AND JACKETING. OUTER CASING SHALL BE EXTRUDED WHITE PVC TYPE 1, GRADE 1, CLASS 12454-B PER ASTM D 1784. 36. ALL EQUIPMENT LOCATED IN MECHANICAL EQUIPMENT ROOMS SHALL BE LOCATED ON A 4" THICK CONCRETE PAD INSTALLED BY THE GENERAL CONTRACTOR, MECHANICAL CONTRACTOR SHALL COORDINATE PAD LOCATIONS WITH THE GENERAL CONTRACTOR. 37. COMMERCIAL DRYER EXHAUST DUCTWORK SHALL BE CONSTRUCTED OF GALVANIZED SHEET METAL NOT LESS THAN O.0195 INCHES THICK. EXHAUST DUCT SHALL BE ASSEMBLED WITH SMOOTH INTERIOR SURFACE SO THAT THE JOINTS DO NOT PERMIT THE ACCUMULATION OF LINT, DO NOT USE SHEET METAL SCREWS AT JOINTS. ALL 90° TURN SHALL HAVE LONG RADIUS ELBOWS. ALL DUCTWORK SHALL BE INSTALLED PER THE DRYER MANUFACTURER'S RECOMMENDATIONS. MECHANICAL LEGEND, INDEX, - NOTES, AND SCHEDULES M-001 OPTIMA # 13-0238 1 OF 26 SOLUTIONS THROUGH LISTENING THIS DRAWING IS AN INSTRUMENT OF SERVICE. THE DRAWING AND THE INFORMATION THEREON IS THE PROPERTY OF OPTIMA ENGINEERING, P.A. ANY REPRODUCTION, ALTERATION, OR USE FOR OTHER THAN THE INTENDED PROJECT, WITHOUT THE WRITTEN CONSENT CF OPTIMA ENGINEERING, P.A. IS EXPRESSLY FORBIDDEN. COPYRIGHT ©OPTIMA ENGINEERING P.A. 2014, ALL RIGHTS RESERVED. 1 2 3 4 5 I e BID DOCUMENTS ROOFTOP UNIT SCHEDULE (DX COOLING WITH GAS HEAT) NOMINAl RTU-1 4000 O.A. TONNAGE E 10 800 COOllNG CAPACITY 0.5" E (BTUH) 124,100 SjiG (BTUH) 96,200 EFFICIENCY SEER N/A EER 11.10 ENERGY RECOVERY VENTILATOR SCHEDULE HEATING CAPACITY JP..LY 11.8 INPUT (BTUH) 224,000 / 180,000 EFFICIENCY OUTPUT (RTUH) 183,600 AB).E 81% COMPRESSOR (EA) jiQ, 2 ELâ 7.7 DF.M ],,BA 52.0 Q.IY.,. 2 M 0.8 ]M COMB. FAN PWR EXH M 4.4 M 0.30 M -- POWFR SUPPI Y jdCA 26.3 MD..C.P_ 30 OPERATING MANUFACTURER VOLTAGE WEIGHT 460V-3ø 1240 LBS SUPPLY AIR CARRIER MODEL 48TCED12 ERV-1 NOTES: 1. COOLING CAPACITIES BASED ON 95© AMBIENT, 80/67 ENTERING AIR. 2. PROVIDE ALL UNITS NTH: ROOF CURB, DDC THERMOSTAT (SEE NOTE 5), 2" THROWAWAY FILTERS (MERV 8 MINIMUM), ENTHALPY ECONOMlZER, INTERMITTENT PILOT IGNITION, CONDENSER COlL HAlL GUARDS, PHASE LOSS/BROWNOUT PROTECTION, HIGH AND LOW PRESSURE SNTCHES (NOT A LOSS OF CHARGE SNTCH), AND HINGED ACCESS DOORS WITH "TOOL-LESS" ENTRY. 3. ALL UNITS SHALL BE AGA CERTIFIED, U.L. LABELED, AND ASHRAE 90.1 COMPLIANT. 4. PROVIDE EACH UNIT NTH A IONIZATION TYPE SMOKE DETECTOR, INSTALLED IN THE RETURN DUCT WIRED TO SHUT DOWN THE UNIT UPON ACTIVATION. SMOKE DETECTOR SHALL BE SUPPLIED, WIRED FOR INTERFACE WITH FIRE ALARM SYSTEM AND UNIT SHUTDOWN BY THE ELECTRICAL CONTRACTOR. SMOKE DETECTOR SHALL BE INSTALLED IN THE RETURN DUCT BY THE MECHANICAL CONTRACTOR. 5. M 4000 MECH PLATFORM C220 EXHAUST AIR ESP_ FAN HP 0.75" 5 H 4000 CLOVER SCHOOL POWER ESP_ FAN HP 0.75" 5 M.CA MD..C.P_ 17.9 25 SUMMFR SljPPI Y AIR CONDITIONS (* F.) VOLTAGE DRY BULB WET BULB SPEC. HUM. 460V-3ø 79.4 66.8 78 WNTFR SlJPPI Y AIR CONDITIONS (* F.) ENTHAPLY DRY BULB WET BULB SPEC. HUM. 31.3 58.6 47.8 32 MANljFACTljRFR ENTHAPLY 19.0 WEIGHT 1206 LBS GRFFNHFCK MODFl ERV-45-30L - NOTES: 1. 2. 3. 4. 5. ALL UNITS SHALL HAVE STANDARD 24-VOLT CONTROL CIRCUIT OPERATION WTH CONTROL SYSTEM WTHOUT ADDITIONAL INTERFACES OR GATEWAYS, COORDINATE WTH CONTROLS CONTRACTOR. CLOVER SCHOOL DISTRICT ALL TEMPERATURES ARE MEASURED IN DEGREES FAHRENHEIT, SPECIFIC HUMIDITY IS MEASURED IN GRAINS PER POUND DRY AIR, AND ENTHALPY IS MEASURED IN BTU'S PER POUND. OUTDOOR DESIGN CONDITIONS: SUMMER: 94* F. D.B., 77* F. W.B. NNTER: 21* F. D.B. INDOOR DESIGN CONDITIONS: SUMMER: 75© F. D.B., 50% RELATIVE HUMIDITY. WINTER: 72' F. D.B., 35% RELATIVE HUMIDITY. FURNISH UNITS NTH: HINGED ACCESS DOORS, ENTHALPY SENSOR NTH AUTOMATIC WNTER OVERRIDE, PLEATED 30% EXHAUST AND OUTSIDE AIR FILTERS, SINGLE POINT ELECTRICAL CONNECTION, MOTORIZED OUTSIDE AIR AND EXHAUST DAMPERS. UNITS MUST BE AMCA CERTIFIED. CLOVER AIR HANDLING UNIT UNIT SCHEDULE UNIT NUMBER AHU-1 AHU-2 AHU-3 AHU-4 AHU-5 AHU-6 AHU-7 AHU-8 AHU-9 AHU-10 AHU-11 AHU-12 AHU-13 -- LOCATION MECH MECH MECH MECH MECH MECH MECH MECH MECH MECH MECH MECH MECH PLATFORM PLATFORM PLATFORM PLATFORM PLATFORM PLATFORM PLATFORM PLATFORM PLATFORM PLATFORM PLATFORM PLATFORM PLATFORM SUPPLY FAN AIR FLOW E.S.P. (CFM) (IN. H,0) AREA SERVED A220 A220 A220 A220 B220 B220 B220 B220 C220 C220 C220 C220 C220 REPLACEMENT A CLASSROOMS A CLASSROOMS MUSIC/ART WING CAFETERIA B CLASSROOMS B CLASSROOMS ADMIN/CLASSROOMS MEDIA/ADMIN C CLASSROOMS C CLASSROOMS GYMNASIUM GYMNASUIM HEALTH/MULTIPURPOSE 15,750 15,750 12,500 12,940 15,750 15,750 6,500 11,500 15,750 15,750 11,000 14,500 8,000 1.5" 1.5" 2.0" 1.5" 1.5" 1.5" 1.5" 1.5" 1.5" 1.5" 1.5" 1.5" 1.5" RETURN FAN OCCUPIED DESIGN AIR FLOW E.S.P. MIN. OUTSIDE OUTSIDE TOTAL (CFM) (IN. H,0) AIRFLOW (CFM) AIRFLOW (CFM) CAPACITY 14,000 14,000 11,250 -14,000 14,000 5,850 10,750 14,000 14,000 -6,210 7,100 0.75" 0.75" 0.75" -0.75" 0.75" 0.75" 0.75" 0.75" 0.75" -0.75" 0.75" 1,750 1,750 1,250 1,200 1,750 1,750 650 750 1,750 1,750 4,000 1,000 900 4,500 4,500 4,000 4,200 4,500 4,500 1,500 1,500 4,500 4,500 4,000 5,500 3,000 GPM 300,000 300,000 238,400 -300,000 300,000 116,800 188,900 300,000 300,000 --163,100 15 15 11.9 -15 15 5.9 9.4 15 15 --8.2 PREHEAT COll RUNOUT E.W.T. L.W.T. SIZE (7) (7) 1¼" 1¼" 1¼" -1¼" 1¼" 1" 1¼" 1¼" 1¼" --1¼" 160 160 160 -160 160 160 160 160 160 --160 120 120 120 -120 120 120 120 120 120 --120 MAX. P.D. MAX. TOTAL S.P. CAPACITY SENSIBLE CAPACITY 5' 5' 5' -5' 5' 5' 5' 5' 5' --5' O.25" O.25" O.25" -O.25" O.25" O.25" O.25" O.25" O.25" --O.25" 410,300 410,300 328,100 326,300 410,300 410,300 160,100 310,800 410,300 410,300 277,200 366,100 207,300 580,000 580,000 465,100 448,000 580,000 580,000 217,600 432,800 580,000 580,000 383,800 510,300 284,300 COOLING COll. RUNOUT E.W.T. L.W.T. GPM SIZE (7) (7) 97 97 77 75 97 97 36 72 97 97 64 85 47 3" 3" 3" 3" 3" 3" 2" 2½" 3" 3" 2½" 3" 2" 44 44 44 44 44 44 44 44 44 44 44 44 44 56 56 56 56 56 56 56 56 56 56 56 56 56 MAX. P.D. MAX. S.P. TOTAL CAPACITY GPM 10' 10' 10' 10' 10' 10' 10' 10' 10' 10' 10' 10' 10' O.75" O.75" O.75" O.75" O.75" O.75" O.75" O.75" O.75" O.75" O.75" O.75" O.75" ---259,600 ------275,200 313,400 -- ---13 ------14 16 -- REHEAT COIL RUNOUT E.W.T. L.W.T. SIZE (7) (7) ---1¼" ------1¼" 1½" -- ---160 ------160 160 -- ---120 ------120 120 -- MAX. P.D. ---5' ------5' 5' -- ELECTRICAL DATA MAX. SUPPLY FAN RETURN FAN S.P. (H.P.) (H.P.) VOLTS ---O.25" ------O.25" O.25" -- 15 15 15 15 15 15 7½ 15 15 15 10 15 10 5 5 3 -5 5 3 3 5 5 --3 460 460 460 460 460 460 460 460 460 460 460 460 460 PHASE Hz MANUFACTURER & MODEL NO. 3 3 3 3 3 3 3 3 3 3 3 3 3 60 60 60 60 60 60 60 60 60 60 60 60 60 CARRIER CARRIER CARRIER CARRIER CARRIER CARRIER CARRIER CARRIER CARRIER CARRIER CARRIER CARRIER CARRIER SEQUENCE OF OPERATION 39MN-36 39MN-36 39MN-30 39MN-30 39MN-36 39MN-36 39MN-14 39MN-25 39MN-36 39MN-36 39MN-25 39MN-30 39MN-17 VAV VAV VAV SZVAV VAV VAV VAV VAV VAV VAV SZVAV SZVAV VAV OPERATING WEIGHT REMARKS 8800 8800 7500 5200 8800 8800 4400 6195 8800 8800 4200 5200 4900 C,D,E,G,K,L,Q C,D,E,G,K,L,Q C,D,E,G,K,L,Q A,C,D,G,L,N,Q C,D,E,G,K,L,Q C,D,E,G,K,L,Q C,D,E,G,K,L,Q C,D,E,G,K,L,Q C,D,E,G,K,L,Q C,D,E,G,K,L,Q A,C,D,G,L,Q A,C,D,G,L,Q C,D,E,G,K,L,Q LBS LBS LBS LBS LBS LBS LBS LBS LBS LBS LBS LBS LBS UNIT NUMBER AHU-1 AHU-2 AHU-3 AHU-4 AHU-5 AHU-6 AHU-7 AHU-8 AHU-9 AHU-10 AHU-11 AHU-12 AHU-13 MIDDLE SCHOOL - ma engineering 1927 South Tryon St., Suite 300, Charlotte NC 28203 NOTES: D - Phone: 704-338-1292 042 www.optimapa.com North Carolina License Number C-0914 ACCFSSORIFS: 1. COOLING COIL CAPACITY IS BASED ON 80° F. D.B./67° F. W.B. E.A.T. AND 56.0° F. D.B./55.5° F. W.B. L.A.T. 2. MAXIMUM FACE VELOCITY OF COOLING COILS SHALL BE 500 FPM. 3. HEATING COIL CAPACITY IS BASED ON 65° F. E.A.T. A B C D E F 4. ALL AIR HANDLERS SHALL HAVE HIGH EFFICIENCY FAN MOTORS. 5. ALL AIR HANDLING UNITS UNITS SHALL BE PROVIDED WITH A PHOTOELECTRIC TYPE SMOKE DETECTOR MOUNTED IN THE RETURN DUCT. THE SMOKE DETECTOR SHALL BE FURNISHED AND WIRED FOR UNIT SHUT DOWN AND FIRE ALARM INTERFACE BY THE ELECTRICAL CONTRACTOR AND SHALL BE INSTALLED IN THE DUCT BY THE MECHANICAL CONTRACTOR. 6. ALL UNITS SHALL HAVE A FACTORY INSTALLED 6" HIGH BASE RAIL. MOUNT AHU'S ON A 4" THICK CONCRETE PAD. 7. CONTRACTOR SHALL INSTALL NEW BELTS AND A NEW SET OF MERV 8 PLEATED FILTERS AT SUBSTANTIAL COMPLETION, AND PROVIDE SPARE SETS OF BELTS AND FILTERS TO THE OWNER. 8. ALL UNITS SHALL BE DOUBLE WALL CONSTRUCTION WITH 18 GAGE MINIMUM CASING. - OA/RA MIXING BOX WITH FLAT FILTER SECTION PERMANENT METAL FILTER FRAMES WITH REPLACEABLE FABRIC FILTERS (ANGULAR FILTERS) VAV (FREQUENCY DRIVE) FOR SUPPLY FAN PLENUM SUPPLY FAN PLENUM RETURN/RELIEF FAN WITH VFD VERTICAL DRAW THROUGH LS')P G - HORIZONTAL DRAW THROUGH H - 2-SPEED FAN MOTOR (1800/900 RPM) J - ANGULAR FILTER SECTION K - ECONOMlZER SECTION WITH MOTORIZED OUTSIDE AIR, RETURN AIR AND RELIEF AIR DAMPERS. L M N P Q 9. ALL UNITS SHALL HAVE A MINIMUM 14" ACCESS SECTION WITH HINGED DOOR BETWEEN EACH SET OF ADJACENT COILS. 10. SEE SPECIFICATIONS FOR ADDITIONAL REQUIREMENTS. - 2" PLEATED FILTERS (MERV-8 MINIMUM) ROOF CURB INTERLOCK FAN TO RUN CONTINUOUSLY WHEN KITCHEN HOOD EXHAUST FAN IS IN OPERATION CO2 SENSOR FOR DEMAND LIMITING CONTROL INTERNAL VIBRATION ISOLATION ENGAGE DESIGN TRANSRORM PUMP SCHEDULE SYMROI P-1 P_-2 P_-3 P_-4 P-5. P-§. P_-Z P_-8 P-1 GRILLE AND DIFFUSER SCHEOULE SFRVICF ßP_M. jdEAD. CHILLER #1 CHILLER #2 CHILLED WATER LOOP CHILLED WATER LOOP HOT WATER LOOP HOT WATER LOOP BOILER #1 BOILER #2 CHILLER STAND-BY 500 500 1000 1000 170 170 85 85 500 40' 40' 107' 107' 114' 114' 15' 15' 40' EFFICIENCY 85% 85% 81% 81% 70% 70% 72% 72% 85% R.P.M. 1750 1750 1750 1750 1750 1750 1750 1750 1750 jda 7½ 7½ 40 40 10 10 ½ ½ 7½ VOLTAGE 460V-3ø 460V-3ø 460V-3ø 460V-3ø 460V-3ø 460V-3ø 120V-1ø 120V-1ø 460V-3ø B&G MODEL e1510-4AD e1510-4AD e1510-5GB e1510-5GB e1510-2EB e1510-2EB e90-2AAC e90-2AAC e1510-4AD RFMARKS A B C D E F G H J K L M N SUPPLY SUPPLY SUPPLY SUPPLY SUPPLY SUPPLY RET/EXH RET/EXH RET/EXH RET/EXH RET/EXH RET/EXH 0 - 125 12×12 6x6 0 - 125 24x24 6x6 130 - 280 24x24 9x9 285 - 500 24x24 12x12 505 - 780 24x24 15x15 (SEE PLANS FOR NECK SIZE AND CFM) (SEE PLANS FOR NECK SIZE AND CFM) 0 - 195 12x12 8x8 0 - 195 24x24 8x8 200 - 300 24x24 10x10 305 - 450 24x24 12x12 455 - 800 24x24 16x16 LOUVERED LOUVERED LOUVERED LOUVERED LOUVERED DBL. DEFL. FIXED BLADE CUBE CORE CUBE CORE CUBE CORE CUBE CORE CUBE CORE NO NO NO NO NO NO YES NO NO NO NO NO RGS-3 P_BLCE SMD SMD SMD SMD SMD 520 530 80 80 80 80 80 R T U V RETURN SUPPLY SUPPLY RETURN O - 1800 24x24 NON-DUCTED O - 240 TWO 3/4" SLOTS, 48" LONG 245 - 400 THREE 1" SLOTS, 48" LONG (SEE PLANS FOR NECK SIZE AND CFM) CUBE CORE LINEAR LINEAR HEAVY DUTY NO NO NO NO 80 SDS75 SDS100 96 £Bd. 4800 3840 S2... 1.35" 0.6" E-1 E-4 E-5. E-G E-Z E-G E-1 E-10. E-11 E-12 DISHWASHER FIRE PUMP BOILER ROOM MAIN ELEC ROOM KITCHEN TOILET KITCHEN TLT/LKR KILN ART TOILET CLASSROOM CORE SCIENCE LAB EXHAUST EXHAUST EXHAUST EXHAUST EXHAUST EXHAUST EXHAUST EXHAUST EXHAUST EXHAUST 600 1200 3500 1500 75 250 150 75 1650 1600 E-li E-15 E-1E E-1Z E-18 E-1R E-2Q E-21 E-22 SCIENCE LAB SCIENCE LAB SCIENCE PREP CLASSROOM CORE HEALTH TOILETS ADMIN TOILETS CLASSROOM CORE SCIENCE LAB SCIENCE LAB EXHAUST EXHAUST EXHAUST EXHAUST EXHAUST EXHAUST EXHAUST EXHAUST EXHAUST (*) - FOR DEVICES INSTALLED IN GYP CEILINGS, PROVIDE MINIMUM FACE SIZE FOR SPECIFIED NECK SIZE. E-21 E-24 SCIENCE LAB SCIENCE LAB NOTES: E-25 E-2E C - NO N_E EXHAUST MAKE-UP STAND-BY DBL. DEFL. I OCATION KITCHEN HOOD KITCHEN HOOD STAND-BY (SEE PLANS FOR SIZE AND CFM) SYMROI E-1. E-2 STAND-BY SUPPLY FAN SCHEDU _E D.Bü£ FAN RPM BELT BELT 1020 820 WATTS --- jd,P.L 3 2 VOLTAGE 208V-3ø 208V-3ø 1.0" 0.25" 0.25" 0.25" 0.25" 0.25" 0.25" 0.25" 0.375" 0.25" BELT BELT BELT BELT DIRECT DIRECT DIRECT DIRECT DIRECT DIRECT 1650 820 1010 1225 700 1550 1050 700 860 996 ----50 -129 50 --- ¼ ¼ ½ ¼ -1/30 --¼ ½ 120V-1ø 120V-1ø 120V-1ø 120V-1ø 120V-1ø 120V-1ø 120V-1ø 120V-1ø 120V-1ø 120V-1ø CAPTIVE-AIRE NCA24HPFA G12-A2.B GREENHECK CUBE-099-4 SBS-1H20-4 SBS-1L20-5 SBS-1H20-4 SP-890 G-070-D SP-B150 SP-B90 G-163-C G-143-VG 1600 1600 250 700 800 150 1500 1600 1600 0.25" 0.25" 0.25" 0.25" 0.25" 0.25" 0.375" 0.25" 0.25" DIRECT DIRECT DIRECT DIRECT DIRECT DIRECT DIRECT DIRECT DIRECT 996 996 1550 1160 1270 1550 860 996 996 ---------- ½ ½ 1/30 ¼ ¼ 1/30 ¼ ½ ½ 120V-1ø 120V-1ø 120V-1ø 120V-1ø 120V-1ø 120V-1ø 120V-1ø 120V-1ø 120V-1ø EXHAUST EXHAUST 1600 1600 0.25" 0.25" DIRECT DIRECT 996 996 --- ½ ½ SCIENCE PREP CLASSROOM CORE EXHAUST EXHAUST 250 700 0.25" 0.25" DIRECT DIRECT 1550 1160 --- E-28 E-2R E-3Q E-31 E-32 E-Ja E-34 E-3E E-3E E-3Z E-38 SCIENCE LAB SCIENCE LAB SCIENCE LAB SCIENCE LAB SCIENCE PREP CLASSROOM CORE FIELD HOUSE CUSTODIAL ROOM RESTROOM BLDG STORAGE/CUST. ART TOILET EXHAUST EXHAUST EXHAUST EXHAUST EXHAUST EXHAUST EXHAUST EXHAUST EXHAUST EXHAUST EXHAUST 1600 1600 1600 1600 250 700 865 350 1375 500 75 . 0.25 0.25" 0.25" 0.25" 0.25" 0.25" 0.25" 0.25" 0.25" 0.25" 0.25" DIRECT DIRECT DIRECT DIRECT DIRECT DIRECT DIRECT DIRECT DIRECT DIRECT DIRECT 996 996 996 996 1550 1160 1205 1000 1100 1080 700 E-3R RANGE HOOD EXHAUST 600 0.55" BELT 1275 227 WEST TRADE STREET SUITE 700 CHARLOTTE, NORTH CAROLINA 28202 TEL. 704.333.6686 FAX 704.333.2926 WWW.LS3P.COM ACCFSSORIFS CONTROl S A,D,E,P,Q,R A,C,D,M,R 7 7 A,B,D,E A,B,G,K,N A,B,G,K,N A,B,G,K,N A,B,F,J,0 A,B,D,E A,B,F,H,0 A,B,F,J,0 A,B,D,E A,B,D,E 8 1 1 1 2 5 1 2 5 4 G-143-VG G-143-VG G-070-D G-099-VG G-099-VG G-065-D G-163-C G-143-VG G-143-VG A,B,D,E A,B,D,E A,B,D,E A,B,D,E A,B,D,E A,B,D,E A,B,D,E A,B,D,E A,B,D,E 4 4 6 5 5 5 5 4 4 120V-1ø 120V-1ø G-143-VG G-143-VG A,B,D,E A,B,D,E 4 4 1/30 ¼ 120V-1ø 120V-1ø G-070-D G-099-VG A,B,D,E A,B,D,E 6 5 -------121 -285 50 ½ ½ ½ ½ 1/30 ¼ ¼ -¼ --- 120V-1ø 120V-1ø 120V-1ø 120V-1ø 120V-1ø 120V-1ø 120V-1ø 120V-1ø 120V-1ø 120V-1ø 120V-1ø A,B,D,E A,B,D,E A,B,D,E A,B,D,E A,B,D.E A,B,D,E A,B,D.E A,B,F,J,0 A,B,D.E A,B,F,0 A,B,F,J,0 4 4 4 4 6 5 4 6 4 6 2 -- ¼ 120V-1ø G-143-VG G-143-VG G-143-VG G-143-VG G-070-D G-099-VG G-103-VG SP-A410 G-133-VG SP-A710 SP-B90 CAPTIVE-AIRE DU30HFA linfill CA 042 042 OPTIMA ENGINEERING No. 0710 0F filillin NOTES: 1. ALL PUMPS SHALL BE FURNISHED NTH HIGH EFFICIENCY MOTORS PER EPACT REQUIREMENTS. 2. ALL BASE MOUNTED END SUCTION PUMPS SHALL BE FURNISHED NTH TRIPLE DUTY VALVES AND SUCTION DIFFUSERS. 3. PUMPS P-3 & P-4 OPERATE IN PARALLEL AND SHALL BE NON-OVERLOADING. 4. PUMPS P-5 & P-§. OPERATE IN PARALLEL AND SHALL BE NON-OVERLOADING. 5. PUMPS P-3, P-4, P-5, AND P-E SHALL BE FURNISHED WITH VARIABLE FREQUENCY DRIVES AND INVERTOR DUTY MOTORS. 6. SUBMITTALS FOR NON-OVERLOADING PUMPS SHALL SHOW BOTH SINGLE AND DUAL PUMP OPERATION. 7. PUMP VFD AND BYPASS SHALL BE PROVIDED WTH PHASE LOSS PROTECTION. 1. ALL CEILING AND WALL MOUNTED DEVICES SHALL BE FURNISHED WITH AN ENAMEL OFF-WHITE FINISH. 2. ALL DEVICES SHALL BE FURNISHED NTH FRAMES SUITABLE FOR TYPE OF INSTALLATION REQUIRED. 3. ALL LINEAR DIFFUSERS IN LAY-IN CEILINGS SHALL BE FURNISHED NTH END CAPS, ALL LINEAR DIFFUSERS IN HARD CEILINGS SHALL BE FURNISHED NTH END BORDERS. 4. ALL AIR DISTRIBUTION DEVICES LOCATED IN KITCHEN, LOCKER ROOMS, AND TOILETS SHALL BE ALL ALUMINUM CONSTRUCTION. 5. ALL DOUBLE DEFLECTION SUPPLY GRILLES SHALL HAVE DAMPER BLADES ADJUSTED TO PROVIDE AIRFLOW PATTERN INDICATED BY FLOW ARROWS ON PLANS. DAMPERS SHALL BE ADJUSTED TO A 30 DEGREE POSITION UNLESS NOTED OTHERNSE ON PLANS. E-4Q CUSTODIAL ROOM EXHAUST 700 0.25" DIRECT 950 285 -- 120V-1ø SP-A900 . 22 7 10/31M MEMBERS OF THE AMERICAN INSTITUTE OF ARCHITECTS COPYRIGHT 2014 ALL RIGHTS RESERVED PRINTED OR ELECTRONIC DRAWINGS AND DOCUMENTATION MAY NOT BE REPRODUCED IN ANY FORM WITHOUT WRITTEN PERMISSION FROM LS3P ASSOCIATES LTD. REVISIONS: A,D,E,P,Q 9 GRFFNHFCK B - illHff _ A,B,F,H,0 No. Description PROJECT: 9201-131360 DATE: OCT.31,2014 DRAWN BY: SRD Date 1 DUCTLESS SPLIT SYSTEMS (DX COOLING ONLY) INDOOR UNIT COOl ING CAPACITY A/C-1 A/C-2 A/O-1 A/C-4 A/O-E A/C-6 A/O-Z A/C-8 775 775 775 775 775 775 775 775 E (BTUH) SjiG (BTUH) 24,000 18,500 24,000 18,500 24,000 18,500 24,000 18,500 24,000 18,500 24,000 18,500 24,000 18,500 24,000 18,500 HFATING CAPACITY N/A N/A N/A N/A N/A N/A N/A N/A (BTUH) - COOL - COOL - COOL - COOL - COOL - COOL - COOL - COOL ONLY ONLY ONLY ONLY ONLY ONLY ONLY ONLY FI FCTRICAI DATA FAN FLA 0.36 0.36 0.36 0.36 0.36 0.36 0.36 0.36 MCA 1.0 1.0 1.0 1.0 1.0 1.0 1.0 1.0 VOLTAGE 208V-1ø 208V-1ø 208V-1ø 208V-1ø 208V-1ø 208V-1ø 208V-1ø 208V-1ø MANljFACTilRFR MITSUBISHI PKA-A24KA PKA-A24KA PKA-A24KA PKA-A24KA PKA-A24KA PKA-A24KA PKA-A24KA PKA-A24KA OllTDOOR llNIT COOl ING CAPACITY CU-1 CU-2 CU-1 CU-i CU-E CU-E CU-Z CU-R E (BTUH) SjiG (BTUH) 24,000 18,500 24,000 18,500 24,000 18,500 24,000 18,500 24,000 18,500 24,000 18,500 24,000 18,500 24,000 18,500 EEE,. HFATING CAPACITY EEB. 17.0 17.0 17.0 17.0 17.0 17.0 17.0 17.0 N/A N/A N/A N/A N/A N/A N/A N/A (BTUH) - COOL - COOL - COOL - COOL - COOL - COOL - COOL - COOL COMPRESSOR EAR ONLY ONLY ONLY ONLY ONLY ONLY ONLY ONLY 95" 95' 95" 95' 95" 95' 95" 95' F F F F F F F F LBA 14 14 14 14 14 14 14 14 ELA 12 12 12 12 12 12 12 12 ELA 0.75 0.75 0.75 0.75 0.75 0.75 0.75 0.75 Fl FCTRICAI DATA MCA 18 18 18 18 18 18 18 18 EU.SE 30 30 30 30 30 30 30 30 VOLTAGE 208V-1ø 208V-1ø 208V-1ø 208V-1ø 208V-1ø 208V-1ø 208V-1ø 208V-1ø OPERATING MANljFACTilRFR WEIGHT 163 LBS 163 LBS 163 LBS 163 LBS 163 LBS 163 LBS 163 LBS 163 LBS MITSUBISHI PUY-A24NHA PUY-A24NHA PUY-A24NHA PUY-A24NHA PUY-A24NHA PUY-A24NHA PUY-A24NHA PUY-A24NHA NOTES: 1. 2. 3. 4. 5. 6. 7. 8. A 9. ALL UNITS SHALL BE U.L. LISTED AND HAVE A MINIMUM SEER OF 13. COOLING CAPACITIES ARE BASED ON 95© AMBIENT, 80' ENTERING AIR DRY BULB, 67© ENTERING AIR WET BULB. AIRFLOWS INDICATED ARE AT 'HIGH' SPEED. MOUNT GROUND-MOUNTED UNITS ON A 4" THICK CONCRETE PAD INSTALLED BY THE GENERAL CONTRACTOR, COORDINATE LOCABONS NTH THE MECHANICAL CONTRACTOR.. PROVIDE MANUFACTURER'S SUGGESTED CLEARANCES AROUND UNIT. PROVIDE UNITS NTH MANUFACTURER'S NND BAFFLES OR LOW AMBIENT CONTROLS FOR OPERABON DOWN TO O' F, INVERTER COMPRESSOR, 7-DAY PROGRAMMABLE THERMOSTAT (WALL-MOUNTED), INTEGRAL NON-LOCKING DISCONNECT FOR INDOOR UNIT. PROVIDE OUTDOOR UNITS NTH 6 YEAR EXTENDED COMPRESSOR WARRANTY. SEE MANUFACTURER'S RECOMMENDATIONS FOR REQUIRED ADDIBONAL REFRIGERANT CHARGE AND RECOMMENDED LINE-SET LENGTHS. POWER SUPPLY TO CONDENSING UNIT IS A SINGLE POINT ELECTRICAL CONNECTION FOR THE SYSTEM (A/C UNIT AND CONDENSING UNIT). THE ELECTRICAL CONTRACTOR SHALL PROVIDE POWER TO THE CONDENSING UNIT AND FROM THE CONDENSING UNIT TO THE A/C UNIT. CODE REQUIRED DISCONNECT SNTCHES ARE PROVIDED BY MECHANICAL CONTRACTOR. REFRIGERANT PIPING AND NRING FOR WALL-MOUNTED INDOOR UNITS SHALL BE ROUTED IN WALL WHERE POSSIBLE. ANY EXPOSED PIPING SHALL BE PAINTED TO MATCH WALL-FINISH. ACCESSORIES A: B: C: D: E: F: CHECKED BY: RVA CONTROLS M: N: 0: P: Q: R: S: T: U: DISCONNECT SWITCH GRAVITY BACKDRAFT DAMPER MOTORIZED BACKDRAFT DAMPER PREFAB. ROOF CURB BIRDSCREEN ACOUSBCAL LINING G: HANGING BRACKETS NTH VIBRATION ISOLATION H: WL, WALL LOUVER DISCHARGE J: RCC OR GRS ROOF CAP (FLAT ROOF) OR RJ ROOF CAP (PITCHED ROOF) K: WALL MOUNTING COLLAR L: INLET GUARD 2" WASHABLE ALUMINUM FILTERS MOTORSIDE FAN GUARD EXHAUST GRILLE U.L. 762 VENTED ROOF CURB EXTENSION COMBINATION KITCHEN HOOD FAN CURB NOT USED PROVIDE DRAIN PLUG ACCESSORY PRESSURE SENSING SNTCH 1: WALL MOUNTED THERMOSTAT (REVERSE ACTING, SET FOR 80') 2: INTERLOCK NTH ROOM LIGHT SNTCH (FAN SHALL OPERATE WHEN LIGHT IS ON IN ANY ROOM SERVED BY FAN) 3: WALL MOUNTED ON/OFF SNTCH WITH IDENTIFICATION LABEL 4: WALL MOUNTED TNST TIMER WTH 0-3 HOUR RANGE NTH IDENTIFICATION LABEL 5: 6: 7: 8: 9: CONTROLLED BY BUILDING AUTOMATION SYSTEM CONTINUOUS OPERATION INTERLOCK WTH KITCHEN HOOD CONTROLS INTERLOCK WITH DISHWASHER INTERLOCK WITH RANGE HOOD NOTES: 1. ALL FANS SHALL BE U.L LISTED AND LABELED AND SHALL BE AMCA CERTIFIED FOR SOUND AND AIR FLOW. ADJACENT TO OCCUPIED SPACES SHALL HAVE A MAXIMUM 9.0 INLET SONE LEVEL 2. MECHANICAL CONTRACTOR SHALL PROVIDE MAGNETIC STARTER NTH AUXILLARY CONTACTS AS REQUIRED. 3. PROVIDE ALL DIRECT DRIVE FANS NTH SPEED CONTROLLERS. MECHANICAL SCHEDULES ALL FANS INSTALLED INSIDE, ABOVE, OR M-002 OPTIMA # 13-0238 2 OF 26 SOLUTIONS THROUGH LISTENING 1 1 THIS DRAWING IS AN INSTRUMENT OF SERVICE. THE DRAWING AND THE INFORMATION THEREON IS THE PROPERTY OF OPTIMA ENGINEERING, P.A. ANY REPRODUCTION, ALTERATION, OR USE FOR OTHER THAN THE INTENDED PROJECT, WITHOUT THE WRITTEN CONSENT OF OPTIMA ENGINEERING, P.A. IS EXPRESSLY FORBIDDEN. COPYRIGHT ©OPTIMA ENGINEERING P.A. 2014, ALL RIGHTS RESERVED. 2 I 3 I 4 I 5 I 6 BID DOCUMENTS ROOF MOUNTED GRAVITY VENTILATOR SCHEDULE E - MAX. THROAT MAX. S.P. MANUFACTURER H THROAT SIZE VELOCITY (FPM) DROP (IN.) GREENHECK 25,250 14,000 19,850 20,750 13,000 21,100 1,200 3,500 1,500 48x96 48x96 48x96 48x96 48x96 48x96 18x18 24x24 18x18 800 800 800 800 800 800 800 800 800 0.10" 0.10" 0.10" 0.10" 0.10" 0.10" 0.10" 0.10" 0.10" FGR FGR FGR FGR FGR FGR GRSR-18 GRSR-24 GRSR-18 FAN F-7. F-36. F-37 RELIEF 525 12x12 800 0.10" DRYER COMBUSTION AIR -- 8x8 800 0.10" SYMBOL LOCATION SERVICE By-1 RV-2 RV-3 RV-4 RV-5 RV-6 RV-7 RV-8 RV-9 MECH PLATFORM A220 MECH PLATFORM A220 MECH PLATFORM B220 MECH PLATFORM B220 MECH PLATFORM C220 MECH PLATFORM C220 FIRE PUMP A161 BOILER ROOM A160 ELEC ROOM A163 AHU-1 & 3 REUEF AHU-2 RELIEF AHU-5 & 7 REUEF AHU-4 & 6 REUEF AHU-1 & ERV-1 REUEF AHU-10 & 13 RELIEF FAN F-4 REUEF FAN F-5 REUEF FAN F-6 REUEF RV-10 OFFICE A159 RV-11 LAUNDRY C168 ENVIROTEC DUCT ENVIROTEC DUCT SYMBOL MAXIMUM COOLING HEATING CFM MIN CFM CFM BTUH GPM RUNOUT SDR-WC RUNOUT SYMBOL CFM MIN CFM CFM BTUH GPM RUNOUT SDR-WC RUNOUT A,B,C A,B,C A,B,C A,B,C A,B,C A,B,C A,B,D A,B,D A,B,D 1.1 3 1.4 1.5 1.6 1.7 1.8 1.9 1750 40 1600 1500 1250 1250 1925 1250 6 440 360 400 380 320 320 490 320 880 710 800 900 750 750 1160 630 29000 24000 26000 30000 25000 25000 38000 21000 2.0 1.2 1.3 1.5 1.3 1.3 1.9 1.1 3/4 1/2 1/2 1/2 1/2 1/2 3/4 1/2 12 12 12 12 10 10 14 10 14 14 14 14 14 14 16 14 7.1 3 7.4 7.5 7.6 7.7 7.8 7.9 1200 575 1100 450 400 500 470 500 300 600 20000 1/2 550 270 240 0 290 250 18000 9000 8000 0 10000 9000 1 1/2 1/2 1/2 n/a 1/2 1/2 10 8 10 8 8 SDR-8 8 8 10 12 280 120 100 0 120 130 1.4 0 1.0 1.0 1.0 0.0 1.0 1.0 GRSR-12 A,B,C 1.12 1400 350 700 23000 1.2 1/2 12 14 7 12 475 120 240 8000 1 0 1/2 8 10 GRSI-8 A,B,C 7.13 440 110 220 8000 1.0 1/2 8 10 ACCESSORIES HW COIL MAXIMUM COOLING HEATING HW COIL 1665 420 840 28000 1.9 3/4 12 14 2.2 1300 330 650 22000 1.5 1/2 12 14 8.1 450 120 230 8000 1.0 1/2 8 10 2.3 1325 340 670 22000 1.1 1/2 12 14 8.2 510 130 260 9000 1.0 1/2 8 10 2.4 1300 330 650 22000 1.1 1/2 12 14 83 900 230 450 15000 1 0 1/2 10 12 2.5 2.6 1500 1300 380 330 900 780 30000 26000 1.5 1.3 1/2 1/2 12 12 14 14 8.4 1255 320 630 21000 1.1 1/2 10 14 2.7 1300 330 780 26000 1.3 1/2 12 14 8.5 1200 300 720 24000 1.2 1/2 10 12 2.8 2025 510 1220 40000 2.0 3/4 14 16 8.6 1200 300 720 24000 1.2 1/2 10 12 1300 1300 1650 2.12 2160 330 330 420 540 650 650 830 1080 22000 22000 27000 35000 1.1 1.1 1.4 1.8 1/2 1/2 1/2 12 12 12 1/2 14 14 14 14 8.7 8.8 8.9 16 1055 265 1125 270 70 290 640 160 570 21000 6000 19000 1.1 1.0 1.0 1/2 1/2 1/2 10 6 10 580 150 290 10000 1.0 1/2 8 10 8.11 2520 630 1260 41000 2.1 3/4 14 16 1. PROVIDE ALL VENTILATORS WITH FACTORY ROOF CURBS. A: CURBS AND VENTILATORS SHALL BE INSTALLED LEVEL. 3.1 1820 460 910 30000 2.0 3/4 12 14 12 9.1 1750 440 880 29000 2.0 3/4 12 14 ROOF CURB 3.3 2650 670 1330 44000 2.2 3/4 16 16 9.2 500 0 0 0 0.0 n/a SDR-8 10 B: INSECT SCREEN 3.4 495 130 250 9000 1.0 1/2 8 10 9.3 1365 350 690 23000 1.2 1/2 12 14 C: GRAVITY BACKDRAFT DAMPER 3.5 1225 310 740 24000 1.2 1/2 10 12 9.4 1250 320 630 21000 1.1 1/2 10 14 D: MOTORIZED DAMPER (SEE PLANS FOR INTERLOCK DETAILS) 3.6 660 170 400 13000 1.0 1/2 8 10 9.5 1500 380 900 30000 1.5 1/2 12 14 E: WASHABLE ALUMINUM FILTERS 3.7 1590 400 960 32000 1.6 1/2 12 14 9.6 1250 320 750 25000 1.3 1/2 10 14 F: BAROMETRIC DAMPER 3.8 3.9 1440 690 360 180 870 350 29000 12000 1.5 1.0 1/2 1/2 12 8 14 10 9.7 9.8 1250 1925 320 490 750 1160 25000 38000 1.3 1.9 1/2 3/4 10 14 14 16 3.10 1545 390 780 26000 1.3 1/2 12 14 9.9 1250 320 630 21000 1.1 1/2 10 14 3.11 1500 380 750 25000 1.3 1/2 12 14 9.10 1250 320 630 21000 1.1 1/2 10 14 91, 1800 400 800 2e000 13 2 12 ,4 ACCFSSORIFS 3.2 1180 300 590 20000 1.4 1/2 10 ALL MD UNE l··EAER El--EDULE SYMBOL LOCATION FUH-1 EUH-2 EUH-3 EUH-4 EUH-5 FIRE PUMP A161 BOILER A160 STORAGE C176 STORAGE F101 STORAGE F102 D - CBd. 400 400 400 400 400 D.E!]i 11,200 11,200 11,200 11,200 11,200 jm 3.3 3.3 3.3 3.3 3.3 R.P.M. 1500 1500 1500 1500 1500 1/125 1/125 1/125 1/125 1/125 VOLTAGE 277V-1ø 277V-1ø 277V-1ø 208V-1ø 208V-1ø 9.12 REMARKS MARKEL G1G5103N G1G5103N G1G5103N F1F5103N F1F5103N 5.1 AC PREnlN MOUMMER PART 111 PAGF 7 OPTION 1 - FAN SYSTEM MOTOR NAMEPLATE HORSEPOWER .TAG. SUPPI Y NAMFPI ATF HP RETURN NAMEPLATE HP TOTAl NAMFPI ATF HP SUPPLY CFM AHU-1 15 5 20 15,750 AHU-2 15 5 20 15,750 AHU-3 15 3 18 12,500 AHU-4 15 15 12,940 AHU-5 15 5 20 15,750 Al l OWFD NAMFPI ATF HP COMPLIANCE 23.625 YES 23.625 YES 18.75 YES 19.5 YES 23.625 YES FWH-1 TOILET F106 175 6826 2.0 -- -- 208V-1ø F3314TS-RP EWH-2 CONCESSION F107 175 6826 2.0 -- -- 208V-1ø F3314TS-RP FWH-3 EWH-4 FWH-5 EWH-6 FWH-7 TOILET F108 MEN R102 WOMEN R105 CONCESSION R106 STORAGE R107 175 175 175 175 175 6826 10,239 10,239 6826 6826 2.0 3.0 3.0 2.0 2.0 ------ ------ 208V-1ø 208V-1ø 208V-1ø 208V-1ø 208V-1ø F3314TS-RP F3315TS-RP F3315TS-RP F3314TS-RP F3314TS-RP - JAß SUPPLY NAMEPLATE HP AHU-6 15 AHU-9 15 AHU-10 AHU-11 AHU-12 15 10 15 RFTURN NAMFPI ATF HP TOTAL NAMEPLATE HP 5 20 5 20 5 20 10 15 SUPPLY CFM ALLOWED NAMEPLATE HP COMPLIANCE 15,750 23.625 YES 15,750 23.625 YES 15,750 23.625 YES 11,000 16.5 YES 14,500 21.75 YES 1450 370 730 24000 1.6 1/2 12 14 350 400 380 690 800 900 23000 26000 30000 1.2 1.3 1.5 1/2 1/2 1/2 12 12 12 14 14 14 5.2 5.3 5.4 5.5 NOT USED 1365 1600 1500 5.8 1925 490 1160 38000 1.9 3/4 14 16 5.9 5.10 51, 1250 1250 1e00 320 320 400 630 630 800 21000 21000 2e000 1.1 1.1 , 3 1/2 1/2 , ² 10 10 12 14 14 ,4 5.12 1400 350 700 23000 1.2 1/2 12 14 6.1 6.2 6.3 6.4 1665 1000 1325 1300 420 250 340 330 840 500 670 650 28000 17000 22000 22000 1.9 1.2 1.1 1.1 3/4 1/2 1/2 1/2 12 10 12 12 14 12 14 14 1400 10.1 10.2 10.3 10.4 350 1665 600 1365 1300 420 150 350 330 700 840 300 690 650 23000 1.2 28000 10000 23000 22000 1.9 1.0 1.2 1.1 1/2 12 3/4 1/2 1/2 1/2 12 8 12 12 LIGHT FOR EXHAUST FAN, TWO 4' VAPORPROOF FLOURESCENT TWO LAMP LIGHT FIXTURES (2 PER HOOD), AND STAINLESS STEEL GREASE FILTERS. FIRE SUPPRESSION SYSTEM SHALL BE ANSUL R-102 WITH ANSULEX LIQUID FIRE SUPPRESSANT. REMOTE PULL STATION FOR ACTIVATION OF FIRE SUPPRESSION SYSTEM SHALL BE PROVIDED AND INSTALLED WHERE INDICATED ON THE PLANS. FIRE SUPPRESSION SYSTEM SHALL BE UL 300 LISTED. 1650 420 830 27000 1.4 1/2 12 14 540 1080 35000 1.8 1/2 14 16 1. 2. 160 1080 40 80 3000 1.0 1/2 5 10 8 1300 2025 330 510 780 1220 26000 40000 1.3 2.0 1/2 3/4 12 14 14 16 13.4 13.5 1120 1770 280 450 560 1070 19000 35000 1.0 1.8 1/2 1/2 10 12 12 16 6.9 6.10 1300 1300 330 330 650 650 22000 22000 1.1 1.1 1/2 1/2 12 12 14 14 13.6 13.7 2000 1680 500 420 1200 1010 39000 33000 2.0 1.7 3/4 1/2 14 12 16 14 6.11 6.12 1650 2160 420 540 830 1080 27000 æ000 1.4 1.8 1/2 1/2 12 14 14 16 13.8 13 650 500 170 0 390 0 13000 0 1.0 0.0 1/2 Na 8 M-8 10 10 3. 4. AHU-7 5.7 2.2 7.9 AHU-8 10.5 2.9 13.4 AHU-13 7.8 2.6 10.4 SUPPLY CFM 6,500 11,500 8,000 Al l OWFD RRAKF HP COMPLIANCE 8.45 YES 14.95 YES 10.4 YES 7. 'l(NC || NO NC 'll NOTES: 1. ALL OPTION 1 SYSTEMS ARE VAV SYSTEMS USING THE EQUATION: NAMEPLATE HP <= CFMS*0.0015 227 WEST TRADE STREET SUITE 700 CHARLOTTE, NORTH CAROLINA 28202 TEL. 704.333.6686 FAX 704.333.2926 WWW.LS3P.COM FIRE CONTROL SYSTEM BY HOOD MANUFACTURER, WITH FOUR (4) DRY CONTACTS FOR USE BY DMSION 26 untlig CA NO TUBING, CABLE, AND PULLIES BY M.C. OPTIMA ENGINEERING MECHANICAL GAS VALVE BY M.C., INSTALLED BY O O O NOTFS: 1. HEATING CAPACITY BASED ON 65' F. E.A.T., 2. PROVIDE EACH UNIT HEATER WITH: DISCONNECT SWITCH, BUILT-IN THERMOSTAT, ROOF MOUNTED BRACKETS, AND ADJUSTABLE DISCHARGE LOUVERS.. 3. PROVIDE EACH WALL HEATER WITH BUILT-IN DISCONNECT SWITCH AND THERMOSTAT, PENCIL-PROOF LOUVERS, AND CABINET FOR SURFACE MOUNTING. 4. THERMOSTATS SHALL BE LOW VOLTAGE, LINE VOLTAGE THERMOSTATS ARE NOT ACCEPTABLE. HORIZONTAL KITCHEN HOOD EXHAUST DUCT SHALL SLOPE ¼" PER FOOT CONTINUOUSLY TOWARD HOOD. ALL EXPOSED PIPING WITH FIRE SUPPRESSION SYSTEM SHALL TO COVERED WITH A CHROME SLEEVE. MECHANICAL CONTRACTOR SHALL INSTALL 1/2" CONDUlT IN WALL FOR MANUAL PULL STATION. SEE PLANS FOR LOCATION OF MANUAL PULL STATION. MECHANICAL CONTRACTOR SHALL BE RESPONSIBLE FOR HOOD CERTIFICATION IN COMPLIANCE WITH LOCAL CODE REQUIREMENTS. CERTIFICATION SHALL BE WITNESSED AND PERFORMED BY A PERSON CERTIFIED THROUGH AABC, TABB, NEBB OR NBC AND SHALL PROVIDE DOCUMENTATION OF PERFORMANCE TO THE CODE OFFICIAL. THIS SHALL INCLUDE WET TEST CAPTURE & CONTAINMENT. ALL EQUIPMENT SHALL BE ENERGlZED AND IN OPERATION DURING THE TEST. TEST SHALL ALSO INCLUDE VERIFYING ACTUAL FLOW RATES VERSUS DESIGN FLOW RATES. TO SUPPLY FAN COMMON TO CONTACTOR CONTACTOR AT PANEL BY DIV 26 1. MINIMUM INLET PRESSURE TO TERMINAL UNITS SHALL BE O.75" W.G. 2. MAXIMUM PRESSURE DROP THROUGH TERMINAL UNITS SHALL BE 0.25" S.P. 3. FURNISH TERMINAL UNITS WITH: FACTORY MOUNTED DDC CONTROLS (SEE NOTE 5), ACOUSTICAL LINING, THERMOSTAT, CONTROL VOLTAGE TRANSFORMER. 4. MECHANCIAL CONTRACTOR SHALL EXTEND CONTROL POWER WIRING (120 V) FROM J-BOX TO VAV BOX. 120 V J-BOX BY ELECTRICAL CONTRACTOR, WIRING FROM J-BOX AND FINAL CONNECTION TO UNIT BY MECHANICAL CONTRACTOR. COORDINATE LOCATION OF 120 V J-BOXES WITH ELECTRICAL CONTRACTOR. 5. DDC CONTROLS SHALL BE FURNISHED TO THE BOX MANUFACTURER BY THE CONTROLS VENDOR. BOX MANUFACTURER SHALL FACTORY MOUNT AND WIRE CONTROLS. INSTALLATION OF CONTROLS SHALL INCLUDE CONTROLS TRANSFORMER, CONTROL COVER, AND ALL WIRING AND LABOR FOR A COMPLETE AND OPERATIONAL SYSTEM. LS >P - HOOD EXHAUST FAN - REMOTE MANUAL PULL STATION - ALL ASSOCIATED AIR HANDLING UNITS - FIRE ALARM SYSTEM NOTIFICATION (BY ELEC. CONTR.) SEE SHEET M-402 FOR HOOD DETAILS. KITCHEN HOOD EXHAUST DUCT SHALL BE CONSTRUCTED OF 16 GAUGE CARBON STEEL. ALL JOINTS AND SEAMS SHALL BE SEALED WITH A SPARE COMMON TO BUILDING ALARM NOTES: Phone: 704-338-1292 042 www.optimapa.com North Carolina License Number C-0914 FAN SHALL CONTINUE TO OPERATE. PROVIDE INTERLOCK FOR LIQUID TIGHT CONTINUOUS EXTERNAL WELD. OPTION 2 - FAN SYSTEM BRAKE HORSEPOWER .TAG. SUPPI Y RRAKF HP RETURN BRAKE HP TOTAl RRAKF HP 1927 South Tryon St., Suite 300, Charlotte NC 28203 - CONTACTORS (BY ELEC. CONTR.) 6. 6.7 6.8 engineering KITCHEN HOOD SHALL BE CONSTRUCTED AND INSTALLED PER NFPA 96. UPON ACTIVATION OF FIRE CONTROL SYSTEM, KITCHEN HOOD EXHAUST AUTOMATIC OPERATION OF FIRE SUPPRESSION SYSTEM WITH: - SOLENOID GAS VALVE (BY HOOD FIRE SYSTEM SUPPLIER) 5. 13.1 3 ma NOTES: 22° 2160 523c!!au KH-3 CAPTIVE-AIRE MODEL 4824 ND2, 4'-0"x4'-0"x2'-0" DEEP HOOD; 600 CFM EXHAUST EACH @ 0.35" S.P. (MAX.); ALL STAINLESS STEEL CONSTRUCTION. ALL COMPONENTS SHALL BE U.L. LISTED AND LABELED. PROVIDE A REMOTE CONTROL PANEL MOUNTED ON FACE OF HOOD WITH MASTER DISCONNECT SWITCH, STARTER FOR FAN, CONTROL VOLTAGE TRANSFORMER, FIRE CONTROL SYSTEM RELAY AND TERMINAL STRIP. MOUNT HOOD 6'-8" ABOVE FINISH FLOOR, PROVIDE STAINLESS STEEL ENCLOSURE AROUND TOP OF HOOD AS REQUIRED TO CLOSE TO CEILING. HOOD SHALL BE PROVIDED WITH: AUTOMATICALLY OPERATED FIXED PIPE FIRE SUPPRESSION SYSTEM IN ACCORDANCE WITH NFPA 96, CONTROL SWITCHES AND PILOT 14 10 14 14 10.12 h Dun.. CLOVER REPLACEMENT MIDDLE SCHOOL HOOD MANUFACTURER SHALL PROVIDE 12" STAINLESS STEEL ISLAND UTILITY CHASE BETWEEN SECTIONS OF HOOD, INCLUDING WATER, GAS, AND ELECTRICAL, TO SERVE ITEMS UNDER HOOD. PROVIDE QUICK DISCONNECTS FOR ALL UTILITIES. COORDINATE REQUIREMENTS WITH KITCHEN PLANS AND KITCHEN EQUIPMENT SUPPLIER. 14 10.11 wh ch.M E FIRE SUPPRESSION SYSTEM SHALL BE UL 300 LISTED. NOTES: -- CLOVER SCHOOL DISTRICT SUPPRESSION SYSTEM SHALL BE PROVIDED AND INSTALLED WHERE INDICATED ON THE PLANS. 12 8 12 8.10 (FURNISHED AND INSTALLED BY M.C.) KH-1 AND KH-2 CAPTIVE-AIRE MODEL 6024 ND2-4-PSP-F (TYPICAL OF 2 HOODS BACK TO BACK); 12'-0"x5'-0"x2'-0" DEEP HOOD WITH 14" WIDE SUPPLY PLENUM AT FRONT; 2400 CFM EXHAUST EACH © 0.75" S.P. (MAX.); 1920 CFM SUPPLY EACH © 0.375" S.P. (MAX.); ALL STAINLESS STEEL CONSTRUCTION. ALL COMPONENTS SHALL BE U.L. LISTED AND LABELED. PROVIDE A REMOTE CONTROL PANEL MOUNTED ON FACE OF HOOD WITH MASTER DISCONNECT SWITCH, STARTER FOR FAN, CONTROL VOLTAGE TRANSFORMER, FIRE CONTROL SYSTEM RELAY AND TERMINAL STRIP. MOUNT HOOD 6'-8" ABOVE FINISH FLOOR, PROVIDE STAINLESS STEEL ENCLOSURE AROUND TOP OF HOOD AS REQUIRED TO CLOSE TO CEILING. HOOD SHALL BE PROVIDED WITH: AUTOMATICALLY OPERATED FIXED PIPE FIRE SUPPRESSION SYSTEM IN ACCORDANCE WITH NFPA 96, CONTROL SWITCHES AND PILOT LIGHT FOR EXHAUST FAN, TWO 4' VAPORPROOF FLOURESCENT TWO LAMP LIGHT FIXTURES (2 PER HOOD), AND STAINLESS STEEL GREASE FILTERS. FIRE SUPPRESSION SYSTEM SHALL BE ANSUL R-102 WITH ANSULEX LIQUID FIRE SUPPRESSANT. REMOTE PULL STATION FOR ACTIVATION OF FIRE 12 10 8 10 10 10 2.1 2.9 2.10 2.11 CLOVERSCHOOL DISTRICT TWO KITCHEN HOOD SCHEDULE VAV BOX SCHEDULE O O O POWER SUPPLY TO EQUIPMENT R PA No. C00710 MANUAL SHUT-OFF BY DIVISION 22 TO COOKING EQUIPMENT GAS SUPPLY ADDITIONAL FIRE SUPPRESSION NOTES (IBC): lHIHf 904.11.1 A MANUAL ACTUATION DEVICE SHALL BE LOCATED AT OR NEAR A MEANS OF EGRESS FROM THE COOKING AREA, A MINIMUM OF 10 FEET AND A MAXIMUM OF 20 FEET FROM THE KITCHEN EXHAUST SYSTEM. THE MANUAL ACTUATION DEVICE SHALL BE LOCATED A MINIMUM OF 3.5 FEET AND A MAXIMUM OF 4 FEET ABOVE THE FLOOR AND CLEARLY INDICATE THE HAZARD PROTECTED. THE MANUAL ACTUATION SHALL REQUIRE A MAXIMUM FORCE OF 40 POUNDS AND A MAXIMUM MOVEMENT OF 14 INCHES TO ACTUATE THE FIRE SUPPRESSION SYSTEM. 904.11.2 THE ACTUATION OF THE FIRE SUPPRESSION SYSTEM SHALL AUTOMATICALLY SHUT DOWN THE FUEL OF ELECTRICAL POWER SUPPLY TO THE COOKING EQUIPMENT. THE FUEL AND ELECTRICAL SUPPLY RESET SHALL BE MANUAL. 2. ALL OPTION 2 SYSTEMS ARE VAV SYSTEMS USING THE EQUATION: BRAKE HP <= CFMS*0.0013 + A 3. BRAKE HORSEPOWERS ARE FROM MANUFACTURER AHU SELECTIONS. ""* 22 R. MEMBERS OF THE AMERICAN INSTITUTE OF ARCHITECTS HVAC Mandato ProvisionS Part ll, Page 1 Project Name: Clover Replacement Middle School Date: September 22, 2014 HVAC System Designer of Record: Steven R. Daley, PE Telephone: 704-3384292 Contact Person: Steven R. Daley, PE Telephone: 704-338-1292 City: Clover Climate Zone: 3A Zip: 29710 1% Summer DB Temp: 91 1% Summer WB Temp: 74 Equipment Type (Tables 6.8.1A through G) Size Category (Tables 6.8.1A through G) Sub-Category or Rating Condïtion (Tables 6.8.1A through G) Minimum Efficiency (Tables 6.8.1A through G) Rated Chiller#1&#2-~~~-- Allcapacities RTU-1 Aircooledunitary RTU-1 Warm air furnace, gas fired >225,000 btuh - >esooobtun<135000btuhsinglepackage maximum capacity Boiler B-1 & B-2 Boilers, gas fired hot water >s00,000 bluh, <2.500,000 btuh ueyseisumneaircooieomonoomoue IDU/HP-1 us1eryH-=at sumps»cooe neattosmose <65,000 btuh cooling split system A/c/ODU-1 thru7 Air cooled unitary <65,000btuh splitsystem <65,000 btuh split system 2 Required Leaving CHW Temperature (°F) Entering CW Temperature (°F) Condenser Flow Rate (gpm/ton) Load calculations are provided for selection of all equipment and systems (§ 6,4.2). hoods. gravity vents and gravity ventilations are provided with motorized dampers. Exception: Gravity dampers are used since the building is less than 3 stories or in climate zones 1-3. Exception: No vents are required as these systems ventilate unconditioned ] Construction documents require record co s io 7 Contact Person: Steven R. Daley. PE Systems Worksheet (§ 6.4) AHU-4 AHU-7 AHU-8 AHU-11 System Tag AHU-12 AHU-13 RTU-1 IDU-1 A/C-1 THRU 7 Supply CFM 15,75c 13,000 6,500 11,500 11,000 Supply CFM 14,500 7,900 4,000 1,200 775 Supply ESP (in. w.c.) 1.5" 2" 1.5" 1.5" 1.5" 1.5" Supply ESP (in. w.c.) 1.5" 1.5" 0.5" 0.4° N/A Fan System HP 15 15 15 7.5 15 10 Fan System HP 15 10 2 3/4 1/2 OA CFM (i.e. Outdoor Air CFM) 4500 4000 4200 1500 1500 4000 OA CFM (i.e. Outdoor Air CFM) 5,500 3,000 80C 340 0 Automatic Shutdown (§ 6.4.3.2.1) C1 C1 C1 c1 C1 C1 Automatic Shutdown (§ 6.4.3.2.1) C1 C1 C1 c1 N1 Deadband (§ 6.4.3.1.2) C1 C1 C1 C1 C1 C1 Deadband (§ 6.4.3.1.2) C1 C1 C1 C1 N2 Prescriptive Economizers (§ 6.5.1) Systems employ airside economizers Economizer provides up to 100% design aitflow in outdoor air (§ 6.5.1.1.1). Economizer dampers meet or exceed leakage requirements (§ 6.6.1.1.4). Zone minimums were set to <0.4 cfm/ft2 of zone conditioned floor area. System provides relief for up to 100% design aliflow in outdoor air (§ 6.5.1.1.5). Zone minimums are less than 300 cfm. C1 Setback Controls (§ 6.4.3.2.2) C1 C1 C1 C1 N5 EER 11.1 Setup Controls (§ 6.4.3.2.2) C1 C1 C1 c1 C1 C1 Setup Controls (§ 6.4.3.2.2) C1 C1 C1 C1 N1 Optimum Start (§ 6.4.3.1.3) c1 C1 C1 C1 C1 c1 Optimum Start (§ 6.4.3.1.3) c1 C1 N3 N3 N1 Zone Isolation (§ 6.4.3.1.4) N3 N3 N3 N3 N3 N3 Zone Isolation (§ 6.4.3.1.4) N3 N3 N3 N3 N1 Shutoff Dampers (§ 6.4.3.3.3) C1 C1 c1 C1 C1 c1 Shutoff Dampers (§ 6.4.3.3.3) C1 C1 C2 C2 N1 Economizer complies with the heating system impact requirements (§ 6.5.1.4). Heat Pump Aux Heat (§ 6.4.3.4) N1 N1 N1 N1 N1 N1 Heat Pump Aux Heat (§ 6.4.3.4) N1 N1 N1 C1 N1 Systems employ waterside economizers. Humidifier Preheat (§ 6.4.3.5) N1 N1 N1 N1 N1 N1 Humidifier Preheat (§ 6.4.3,5) N1 N1 N1 N1 N1 Humidificatïon/Dehumidification Deadband (§ 6.4,3.6) C1 c1 C1 C1 C1 C1 Humidification/Dehumidification Deadband (§ 6.4.3.6) C1 C1 N1 N1 N1 Ventilation Control (§ 6.4.3.8) DCV DCV DCV DCV DCV N/.A Ventilation Control (§ 6.4.3.8) DCV DCV N/A N/A N/A Economizer can provide 100% of the load at either the outdoor conditions of 50°F db/45°F wb or 45°F db/40°F wb where required for dehumidification purposes (§ 6.5.1.2.1). Duct/Plenum insulation (§ 6.4.4.2.1) C1 C1 C1 C1 C1 C1 Duct/Plenum insulation (§ 6,4.4.2.1) C1 C1 C1 C1 N/A Duct Sealing Levels (§ 6.4.4.2.1) Supply/Return A A A A A A Duct Sealing Levels (§ 6.4.4.2.1) Supply/Retum A A A A N/A Duct Leakage Test (§ 6.4.4.2.2) Y Y Y Y Y Y Duct Leakage Test (§ 6.4.4.2.2) Y Y Y Y N/A 85% 2 80% SEER 13 2 13 HSPF 7.8 2 7.7 SEER 13 2 13 Size Category (Tables 6.8.1H through J) Minimum Efficiency (Tables 6.8.1H through J) 2 Required Special Mandatory Requirements Freeze protection or snow/ice melting systems (if any) have controls to prevent operation in warm weather (§ 6.4.3.7). Independent perímeter heating systems (if any) comply with the control requirements of § 6.4.3.1.1 and § 6.4.3.2. Independent heating and cooling thermostatic controis (if any) are interlocked to prevent crossover of set points (§ 6.4.3.2). Shutdown 042C1 Complying nonresidential time switch with override 042C2 Complying residential time switch with override 042N1 N/A continuous operation 042N2 N/A s15 kbtu/h or s3/4 hp 042N3 N/A hotel/motel guestroom Dead Band 042C1 Dual setpoint control 042C2 Manual change over control 042N1 N/A special occupancy (requires approval) 042N2 N/A heating or cooling only Setback Controls 042C1 Setback provided (down to 55F) 042N1 N/A continuous operation 042N2 N/A s15 kbtu/h or s3/4 hp 042N3 N/A 99.6% Win DB>40F 042N4 N/A radiant heating 042N5 N/A no heating zones. Setup Controls 042C1 Setup provided (up to 90F) 042N1 N/A continuous operation 042N2 N/A s15 kbtu/h or s3/4 hp 042N3 N/A 1% Sum DB<=100F 042N4 N/A no cooling Heat Pump Aux Heat 042C1 Complying controls provided 042N1 N/A system is not a heat pump 042N2 N/A auxiliary is not electric or is not provided 042N3 N/A heat pump covered by NAECA Optimum Start 042C1 Optimum start provided 042N1 N/A continuous ooeration 042N2 N/A s15 kbtu/h or 53/4 hp 042N3 N/A supply<=10,000 cfm Humidifier Preheat 042C1 Complying controls provided 042N1 N/A no humidifier Shutoff Dampers 042C1 Motorized shutoff dampers on OA and Exh 042C2 Gravity shutoff dampers on OA and Exh 042N1 N/A continuous operation 042N2 N/A s15 kbtu/h or s3/4 hp 042N3 N/A OA/EA <=300 cfm Zone Isolation 042C1 Iso|ation zones orovided 042N1 N/A continuous operation 042N2 N/A s15 kbtu/h or s3/4 hp 042N3 N/A all zones on same schedule 042N4 N/A OA/EA <=5,000 cfm Humïdification/Dehumidification Dead Band 042C1 Complying controls provided 042N1 N/A no humidification and/or dehumidification Duct/Plenum insulation 042C1 Complying insulation provided 042N1 N/A all ducts located in conditioned space Duct Sealing 042Enter highest seal level (A, B or C) for supply and return Duct Leakage Test 042Y Ducts will be tested for leakage 042N Ducts will not be tested for leakage In the table above, enter the appropriate codes from this list: Shutdown 042C1 Complying nonresidential time switch withoverride 042C2 Complyíng residential time switch with override 042N1 N/A continuous operation 042N2 N/A s15 kbtu/h or s3/4 hp 042N3 N/A hotel/motel guestroom Dead Band 042C1 Dual setpoint control 042C2 Manual change over control 042N1 N/A special occupancy (requires approval) 042N2 N/A heating or cooling only Setback Controls 042C1 Setback provided (down to 55F) 042N1 N/A continuous operation 042N2 N/A s^15 kbtu/h or s3/4 hp 042N3 N/A 99.6% Win DB>40F 042N4 N/A radiant heating 042N5 N/A no heating Setup Controis 042C1 Setup provided (up to 90F) 042N1 N/A continuous operation 042N2 N/A s15 kbtu/h or s3/4 hp 042N3 N/A 1% Sum DB<=100F 042N4 N/A no cooling Heat Pump Aux Heat 042C1 Complying controls provided 042N1 N/A system is not a heat pump 042N2 N/A auxiliary is not electric or is not Optimurn Start 042C1 Optimum start provided 042N1 N/A continuous operation 042N2 N/A s15 kblu/h or s3/4 hp 042N3 N/A supply<=10,000 cfm Humidifier Preheat 042C1 Complying controls provided 042N1 N/A no humidifier Shutoff Dampers 042C1 Motorized shutoff dampers on OA and Exh 042C2 Gravity shutoff dampers on OA and Exh 042N1 N/A continuous operation 042N2 N/A s15 kbtu/h or s3/4 hp 042N3 N/A OA/EA <=300 cfm Zone Isolation 042C1 Isolation zones provided 042N1 N/A continuous operation 042N2 N/A s15 kbtu/h or s3/4 hp 042N3 N/A all zones on same schedule 042N4 N/A OA/EA <= 5,000 cfm (§ 6.5.4.3). Zone minimums were set to meet the requirements of Standard 62. c1 80% Prescriptive Air-System Requirements Economizer high limït shutoff complies with § 6.5.1.1.3. c1 2 System pumps greater than 10 hp employ variable flow controls (§ 6.5.4.1), pump isolation (§ 6.5.4.2) and temperature reset Simultaneous Heating and Cooling (§ 6.5.2,3). c1 81.9% --¯¯¯¯¯¯¯¯---¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯ Economizer is integrated with the mechanical cooling system (§ 6.5.1.1.2 and § 6.5.1.3). C1 Ec heat addition and loop heat rejection (if any) comply with the requirements of § 6.5.2.2.3. Specify economizer exemptions:_ (§ 6.5.1.1). c1 2 11.0 Telephone: 704-338-1292 Prescriptive Checklist AHU-1.2,5,6,9.10 AHU-3 12.500 Contact Person: Steven R. Daley, PE Telephone: 704-338-1292 System Tag In the table above, enter the appropriate codes from this list: B Piping insulation meets or exceeds the Telephone: 704-338-1292 COPYRIGHT 2014 ALL RIGHTS RESERVED PRINTED OR ELECTRONIC DRAWINGS AND DOCUMENTATION MAY NOT BE REPRODUCED IN ANY FORM WITHOUT WRITTEN PERMISSION FROM LS3P ASSOCIATES LTD. eart iii, ease 1 Project Name: Clover Replacement Middie School Setback Controls (§ 6.4.3.2.2) Rated General Mandatory Requirements HVAC Prescri.tive Re4 uirements 3.14/4.16 2 3.10/3.45 Mandatory Non-Standard Centrifugal Chiller Worksheet (§ 6.4.1,1) System Tag part n, page 2 COP/IPLV Et IDU/HP-1 Provisions Systems Worksheet (§ 6.4) 99.6% Winter Temp: 18 Units of Efficiency (Tables 6.8.1A through G) HVAC Mandato Project Name: Clover Replacement Middle School Contact Person: Steven R. Daley, PE Mandatory Equipment Efficiency Worksheet (§ 6.4.1.1) System Tag part n, eage 2 Project Name: Clover Replacement Middle School Project Address: Highway 55 & Barrett Road B HVAC Mandator Provisions Precooling coils and heat exchangers have either a < 15 ft of WC pressure drop or are bypassed when economizer is not in use (§ 6.5.1.2.2). Economizer is integrated with the mechanical cooling system (§ 6.5.1.3). Economizer complies with the heating system impact requirements (§ 6.5.1.4). Systems are exempt from the economizer requirements. provided 042N3 N/A heat pump covered by NAECA REVISIONS: _ No. Description Date Prescriptive Special System Requirements All heat rejection equipment with motors 2 7.5 hp employ controis that comply with § 6.5.5, Exhaust Air Energy Recovery: all fan systems that have both a design suppiy capacity of 2 5,000 cfm and a minimurn outdoor air supply of 2 70% of the design supply air employ an energy recovery system that complies with § 6.5.6.1. Other (requires special documentation and approval). Heat recovery for service water heating is provided for facilities that operate Humidity controls (if any) comply with the requirements of § 6.5.2,3, continuously, have a total water-cooled heat rejection capacity exceeding 6,000,000 btu/h, and have a design service water heating load exceeding 1,000,000 btu/h. The heat recovery system (if any) complies with Systems that employ hydronic cooling and have humidifïcation (if any) use a waterside economizer that complies with § 6.5.1. § 6.5.6.2. Variable air volume fan controls comply with the requirements of § 6.5.3.2. Kitchen hoods with exhaust flows > 5000 ofm comply with the requirements of § 6.5.7.1. Prescriptive Water-System Requirements Fume hoods with a total exhaust system flow > 15,000 cfm comply with the requirements of Three-pipe systems are not used (§ 6.5.2.2.1). § 6.5.7.2. O Tw°~pipe chan9eover heatin9/°°°'ino systems (if any) comply with the requirements of § 6.5.2.2.2. PROJECT: 9201-131360 Radiant heaters complying with § 6.5.8.1 are used to heat unenclosed spaces (if any). DATE: OCT.31,2014 O Hydronic (ground- or water-loop) heat pump systems that have equipment for both loop The cooling equipment with hot-gas bypass controls (if any) meets the unloading requirements of § 6.5.9. DRAWN BY: SRD Humidification/Dehumidification Dead Band 042C1 Complying controls pmvided 042N1 N/A no humidification and/or dehurnidification CHECKED BY: RVA MECHANICAL SCHEDULES - AND COMPLIANCE FORMS Duct/Plenum insulation 042C1 Complying insulation provided 042N1 N/A all ducts located in conditioned space Duct Sealing 042Enter highest seal level (A, B or C) for supply and return Duct Leakage Test 042Y Ducts will be tested for leakage 042N Ducts will not be tested for leakage M-003 3 OF 26 ANSI/ASHRAE/IESNA Standard 90.1-2007 -- ANSI/ASHRAE!IESNA Standard 90.1-2007 ANSI/ASHRAEllESNA Standard 90.1-2007 -- ANSI/ASHRAE/IESNA Standard 90.1-2007 -- 2 SOLUTIONS TilROUGli LIST[NING THIS DRAWING IS AN INSTRUMENT OF SERVICE. THE DRAWING AND THE INFORMATION THEREON IS THE PROPERTY OF OPTIMA ENGINEERING, P.A. ANY REPRODUCTION, ALTERATION, OR USE FOR OTHER THAN THE INTENDED PROJECT, WITHOUT THE WRITTEN CONSENT OF OPTIMA ENGINEERING, P.A. IS EXPRESSLY FORBIDDEN. COPYRIGHT ©OPTIMA ENGINEERING P.A. 2014, ALL RIGHTS RESERVED. 1 2 3 4 5 6 BID DOCUMENTS CLOVERSCHOOL SEQUENCE OF OPERATION A COMPLETE AND OPERATIONAL DDC CONTROL SYSTEM (ENERGY MANAGEMENT SYSTEM, BAS) SHALL BE INSTALLED IN ACCORDANCE WITH THE SPECIFICATIONS (SECTION 230900) AND AS INTENDED ON THESE PLANS. ALL CONTROL POINTS AND EQUIPMENT SEQUENCES OF OPERATION LISTED IN SPECIFICATION SECTION 230900 SHALL BE CONSIDERED IN ADDITION TO THOSE LISTED HERE. IN THE EVENT THAT THE VERBIAGE IS IN CONFLICT OR CONTRADICTS THE REQUIREMENTS LISTED HERE, THE QUESTION SHALL BE ASKED PRIOR TO BIDDING OR THE MORE STRINGENT SHALL APPLY. MECHANICAL CONTRACTOR SHALL COORDINATE ALL BAS INTEGRATION REQUIREMENTS WITH EQUIPMENT VENDORS AND CONTROLS CONTRACTOR PRIOR TO PURCHASING EQUIPMENT AND PROVIDE ALL EQUIPMENT WITH COMMUNICATION/INTEltFACE CARDS AS REQUIRED FOR SYSTEM INTEGRATION. CHll I FR PI ANT (PRIMARY/SECONDARY WITH AIR COOLED CHILLERS) AIR HANDI ING UNITS THE CHILLED WATER SYSTEM SHALL BE ENABLED TO OPERATE WHEN THE OUTSIDE AIR TEMPERATURE IS ABOVE 50° F OR ANY CHILLED WATER CONTROL VALVE IS COMMANDED OPEN FOR COOLING. THE CHILLED WATER SECONDARY PUMPlNG SYSTEM SHALL BE STARTED FIRST. AFTER A ONE MINUTE DELAY, THE CHILLER CONTROL PANEL SHALL BE ENABLED TO OPERATE THE CHILLERS AND THE PRIMARY CHILLED WATER PUMPS. EACH CHILLER CONTROL PANEL SHALL START EACH PRIMARY CHILLED WATER PUMP PRIOR TO THE START OF THE ASSOCIATED CHILLER. AFTER PROOF OF PRIMARY CHILLED WATER FLOW IN THE CHILLED WATER PRIMARY PIPING THE ASSOCIATED CHILLER WILL START. THE BAS SHALL MONITOR AND DISPLAY PUMP COMMAND AND STATUS. (IF THE CHILLER CONTROL PANEL DOES NOT PROVIDE FOR PUMP CONTROL, THIS SHALL BE ACCOMPLISHED BY THE BAS.) E - CHILLER SUPPLY TEMPERATURE SHALL BE CONTROLLED BY CHILLER CONTROL PANEL. THE BAS SHALL SEND A CHILLED WATER SUPPLY TEMPERATURE SETPOINT COMMAND TO ALL CHILLER CONTROL PANELS. THE SETPOINT SHALL BE MAINTAINED PER THE RESET SCHEDULE BELOW: CHil I FD WATFR SUPPl Y TFMPFRATURF RFSFT SCHFDUI F (ADJ) 44° F CHS AT 85* F OUTSIDE AIR TEMPERATURE (OR ABOVE) 50° F CHS AT 60° F OUTSIDE AIR TEMPERATURE (OR BELOW) CHS SHALL VARY LINEARLY BETWEEN THE HIGH AND LOW TEMPERATURES (AS MEASURED IN THE CHS LOOP, NOT AT THE CHILLERS). THE INITIAL SETPOINT FOR THE CHILLED WATER SUPPLY TEMPERATURE SHALL BE 44° F. CHILLERS AND PRIMARY PUMPS SHALL BE SETUP IN A LEAD/LAG CONFIGURATION. LAG PUMP AND CHILLER SHALL BE STARTED WHEN SECONDARY LOOP SUPPLY WATER TEMPERATURE RISES ABOVE 4* F ABOVE SETPOINT (ADJ). LAG PUMP AND CHILLER SHALL BE STOPPED WHEN SECONDARY LOOP WATER SUPPLY TEMPERATURE RETURNS TO SETPOINT (ADJ). TIME. E LEA CHILLER AN PUMP SHALL E R TA D ON A KLY BASIS. THE BAS SHALL GENERATE AN ALARM IF THE CHILLED WATER SUPPLY TEMPERATURE INCREASES 2° ABOVE THE INDICATED HIGH LIMIT FOR A PERIOD 0F 10 MINUTES. THE ENERGY MANAGEMENT SYSTEM SHALL MONITOR THE PRIMARY PUMP COMMAND. THE BAS SHALL GENERATE AN ALARM IF THE PUMP FAILS TO RUN, OR IF THE CHILLER CONTROLS INDICATE AN ALARM. WHEN ACTIVATED, LAG CHILLER SHALL OPERATE FOR A MINIMUM OF 30 MINUTES, AND WHEN DEACTIVATED LAG CHILLER SHALL REMAIN IDLE FOR A MINIMUM OF 30 MINUTES (ADJUSTABLE). PUMP P-9 SHALL SERVE AS A STAND-BY PUMP TO BACKUP EITHER CHILLED WATER PRIMARY PUMP. VALVES SHALL BE INSTALLED AS INDICATED TO ALLOW IT TO NORMALLY RUN IN A PRIMARY/STAND-BY CONFIGURATION Nm PUMP P-3. SHOULD PUMP P-4 FAIL, VALVES CAN BE MANUALLY ADJUSTED SUCH THAT PUMP P-9 CAN RUN IN ITS PLACE. UNDER NORMALY OPERATION, THE DDC 41SYSTEM SHALL ROTATE RUNNING PUMP P-3 AND PUMP P-9 WITH CHILLER TO EQUALIZE RUN TIMES BETWEEN PUMPS. D - THE CHILLED WATER SECONDARY PUMPS ARE VARIABLE FLOW PUMPS WITH VARIABLE FREQUENCY DRIVES, SETUP IN A PRIMARY/STAND-BY CONFIGURATION. THE BAS SHALL START THE VARIABLE SPEED CHILLED WATER SECONDARY PUMPS. SECONDARY PUMP SPEEDS ARE CONTROLLED BY VFD'S. THE BAS SHALL MONITOR THE VFD OPERATING SPEEDS AND ALARM CONDITIONS. THE VARIABLE FREQUENCY DRIVES FOR THE PUMPS SHALL BE CONTROLLED BY DIFFERENTIAL PRESSURE SENSORS IN THE CHILLED WATER PIPING SYSTEM (SEE PIPING PLANS FOR SENSOR LOCATIONS). AS AIR HANDLING EQUIPMENT CONTROL VALVES OPEN, PUMP SPEED SHALL BE INCREASED VIA VARIABLE FREQUENCY DRIVE TO MAINTAIN SYSTEM PRESSURE SETPOINT. THE INITIAL CHILLED WATER DIFFERENTIAL PRESSURE SETPOINT SHALL BE 12 PSI, THIS SETTING SHALL BE ESTABLISHED DURING TESTING & BALANCING. IF ONE OR MORE OF THE SENSORS ARE BELOW SETPOINT, THE DRIVE SPEED SHALL BE INCREASED IN RESPONSE TO THE SENSOR WITH THE LARGEST DEVIATION BELOW SETPOINT. IF ALL OF THE SENSORS ARE ABOVE SETPOINT, THE DRIVE SPEED SHALL BE DECREASED IN RESPONSE TO THE SENSOR WITH THE SMALLEST DEVIATION ABOVE SETPOINT. PROVIDE DEAD-BAND AND/OR TIME DELAYS TO PREVENT RAPID CYCLING OF PUMPS 3-WAY CONTROL VALVES ARE PROVIDED WITH CERTAIN UNITS TO MAINTAIN MINIMUM PUMP FLOW (SEE PIPING PLANS FOR UNIT LOCATIONS). STAND-BY PUMP SHALL START AUTOMATICALLY UPON FAILURE OF PRIMARY PUMP, AND AN ALARM INDICATING PUMP FAILURE SHALL BE SENT TO THE BAS. BAS SHALL ALTERNATE PRIMARY AND STAND-BY PUMPS TO EQUALIZE RUN TIME. THE BAS SHALL GENERATE AN ALARM IF THE SYSTEM PRESSURE DEVIATES FROM SETPOINT BY GREATER THAN 6 PSI FOR MORE THAN 5 MINUTES, IF THE STAND-BY PUMP FAILS TO START, OR IF THE VARIABLE FREQUENCY DRIVE INDICATES AN ALARM. THE CHILLED WATER SECONDARY PUMPS SHALL OPERATE FOR 10 MINUTES AFTER ALL CHILLERS ARE COMMANDED TO STOP. C - DEMAND CONTROL VENTILATION: OUTSIDE AIR INTAKE SHALL BE PROVIDED WITH A MOTORIZED DAMPER. ON UNIT START UP, THE OUTSIDE AIR INTAKE DAMPER SHALL REMAIN CLOSED UNTIL THE RETURN AIR TEMPERATURE RISES ABOVE 65° F (ADJ) OR FALLS BELOW 75* F. (ADJ). ONCE RETURN AIR TEMPERATURE IS SATISFIED, THE OUTSIDE AIR DAMPER SHALL OPEN TO THE OCCUPIED MINIMUM SETPOINT. OUTSIDE AIR DAMPERS AND AIR FLOW MONITORING STATIONS SHALL MODULATE AS REQUIRED TO MAINTAIN MINIMUM OUTSIDE AIR FLOW. THE OUTSIDE AIR INTAKE DAMPER SHALL BE CLOSED WHILE UNIT IS IN THE UNOCCUPIED MODE. BAS SHALL BE CAPABLE OF OPENING AND CLOSING OUTSIDE AIR DAMPERS. CO2 SENSOR MOUNTED IN THE RETURN DUCT SHALL MODULATE THE OUTSIDE AIR DAMPER BASED ON CO2 LEVELS IN THE SPACE. DAMPER SHALL MODULATE MU AT 200 PPM AN LARM SHA L E T VATED F E S A E CO2 LEVEL RISES ABOVE 1500 PPM. SEE AHU SCHEDULE FOR MINIMUM AND DESIGN OUTSIDE AIR SETPOINTS AIRSIDE ECONOMlZER CYCLE. DURING THE OCCUPIED PERIOD, AND WHEN THE OUTSIDE AIR TEMPERATURE IS BELOW 68* F. AND ABOVE 45° F AND THE OUTDOOR ENTHALPY IS BELOW 28 BTU/LB, THE ECONOMlZER CYCLE SHALL BE ENABLED. UNDER THOSE CONDITIONS, THE OUTDOOR AIR DAMPER CAN MODULATE PAST ITS "DESIGN., POSITION TO FULL OPEN MODULATING DAMPER CONTROL: MODULATING RETURN, RELIEF, AND OUTSIDE AIR DAMPERS SHALL OPERATE IN CONJUNCTION. RELIEF AND OUTSIDE AIR DAMPERS SHALL OPEN TO THE SAME POSITION ON DEMAND CONTROL OR INVERSE ECONOMlZER CONTROL), BASED AND RETURN DAMPER SHALL VENTILATION CLOSE TO THE POSITION OF THE OUTSIDE AND RELIEF DAMPER SETTINGS. SHALL BE PROVIDED WHERE INDICATED IN THE AHU SCHEDULE RETURN FAN SHALL START ALONG WITH OPENING OF ALL ASSOCIATED RETURN AIR SMOKE DAMPERS AND ISOLATION DAMPERS. SUPPLY FAN SHALL START AFTER PROOF OF THE RETURN FAN, AND ONCE ALL ASSOCIATED SUPPLY AIR DAMPERS ARE OPEN. VARIABLE FREQUENCY DRIVE SHALL CONTROL RETURN FAN TO MAINTAIN A CONSTANT DIFFERENTIAL FROM THE SUPPLY AIR VOLUME. RETURN FAN CONTROL MAY BE OVERRIDDEN BY A BUILDING PRESSURE SENSOR, IF THE BUILDING PRESSURE GETS OUT OF THE +/- 0.02" STATIC PRESSURE RANGE FOR A PERIOD OF 10 MINUTES. ONCE BUILDING PRESSURE IS SATISFIED, RETURN FAN CONTROL SHALL REVERT BACK TO TRACKING THE SUPPLY FAN HUMIDITY CONTROL (WHERE INDICATED): OND æ MMæ M, HUMIDITY CONTROL SYSTEM SHALL BE CAPABLE OF BEING ACTIVATED. UNDER NORMAL OPERATION, UNIT SHALL CONTROLLED AS OUTLINED BELOW. PROVIDE HUMIDISTAT AS INDICATED ON PLANS, IF SPACE OR AND RETURN AIR HUMIDITY 65%SHALL R.H. (ADJ), ALARM SHALL BE SENT HUMIDITY CONTROLREACHES SEQUENCE BE ACTIVATED. AIR HANDLING UNIT CHILLED WATER CONTROL VALVE SHALL BE DRIVEN FULL OPEN. AND UNIT REHEAT COIL OR TERMINAL BOX REHEAT SHALL MODULATE TO MAINTAIN SPACE TEMPERATURE. WHEN SPACE HUMIDITY DROPS BELOW 55% R.H. (ADJ), BAS SHALL DEACTIVATE HUMIDITY CONTROL SEQUENCE. CONTROL OF UNIT SHALL REVERT BACK AS INDICATED BELOW. BOLIER(S) AND ASSOCIATED PUMP(S) SHALL BE STARTED IF THE HEATING PLANT IS IDLE AT THE TIME THE HUMIDITY CONTROL SEQUENCE IS ACTIVATED. THE VARIABLE VOLUME (VAV) TERMINAL UNITS SHALL BE CONTROLLED INDEPENDENT OF SYSTEM PRESSURE FLUCTUATIONS BY AN APPLICATION SPECIFIC DDC CONTROLLER UTILIZING ELECTRIC ACTUATION. OCCUPIED AND UNOCCUPIED OPERATIONS ARE THE SAME, A TEMPERATURE SENSOR SHALL BE UTILIZED TO MAINTAIN SPACE TEMPERATURE SETPOINT. UPON A RISE IN SPACE TEMPERATURE ABOVE SETPOINT, THE VOLUME DAMPER SHALL OPEN AS REQUIRED TO MAINTAIN SPACE TEMPERATURE. UPON A DROP IN SPACE TEMPERATURE BELOW SETPOINT, THE VOLUME DAMPER SHALL CLOSE UNTIL THE MINIMUM DAMPER POSITION IS REACHED. UPON CONTINUED DROP IN SPACE TEMPERATURE BELOW SETPOINT, THE HOT WATER CONTROL VALVE SHALL BE MODULATED OPEN TO THE HEATING COIL AND THE TERMINAL UNIT DAMPER SHALL OPEN TO THE HEATING CFM AS INDICATED IN THE WAT ONTR L VALVE SHALL CLOS D THE DAMPER SHAL R RN TO THE MINIMUM POSITION * WHEN WARM AIR IS SENSED BY THE TERMINAL UNIT DURING MORNING WARM-UP, THE DAMPER SHALL RESPOND TO THE SPACE TEMPERATURE. THE TERMINAL UNIT DAMPER SHALL OPEN TO HEATING SETPOINT ON A CALL FOR HEATING AND SHALL REMAIN CLOSED IF THE SPACE TEMPERATURE IS AT OR ABOVE OCCUPIED SETPOINT. HOT WATER CONTROL VALVE SHALL REMAIN CLOSED DURING MORNING WARM-UP. THE TEMPERATURE SENSOR SHALL BE PROVIDED WITH AN OVERRIDE FUNCTION THAT WILL PLACE THE SYSTEM IN THE OCCUPIED MODE FOR A PERIOD OF UP TO 2 HOURS. THE OVERRIDE SHALL ACTIVATE THE SYSTEM AHU AND THE HEATING OR COOLING CENTRAL PLANT AS REQUIRED TO MAINTAIN SPACE TEMPERATURE THERMOSTATS SHALL BE SET WITH INITIAL SETPOINTS OF 75° FOR COOLING AND 72* FOR HEATING. TEMPERATURE SENSORS LOCATED IN CORRIDORS, DINING AREAS, GYMNASIUMS, AND LOCKER ROOMS SHALL HAVE NO SETPOINT ADJUSTMENT CAPABILITY AT THE WALL MOUNTED SENSORS. ALL OTHER TEMPERATURE SENSORS SHALL BE PROVIDED WITH LIMITED MANUAL SETPOINT ADJUSTMENT AT THE WALL MOUNTED TEMPERATURE SENSOR. PROVIDE THE SYSTEM INTO OCCUPIED MODE FOR A PERIOD OF 2 HOURS (ADJ). ROOM NERMOSTATS ARE INTEGRATED Nm NE OCCUPANCY SENSOR C 523BOLLING THE LIGHTS, COORDINATE INTEGRATION REQUIREMENTS WITH THE ELECTRICAL CONBACTOR. SEE SPECIFICATONS FOR ADDITONAL INFæMATON. HEAT TAPE HEAT TAPE FOR ABOVE GRADEFOR EXTERIOR PIPING AND WATER CHILLERSYSTEM. HEATER ASHALL PROVIDE FREEZE PROTECTION EXTERIOR CHILLED TEMPERATURE SENSOR SHALL BE PROVIDED WITHIN THE INSULATION ON ALL EXTERIOR PIPING WITH HEAT TAPE TO VERIFY HEAT TAPE OPERATION. IF W , AN ALARM SHALL BE SENT AND FXTFRIOR I IGHTING CONTROI SYSTFM BAS SHALL INTERFACE WITH EXTERIOR LIGHTING CONTROL SYSTEM PROVIDED BY THE ELECTRICAL CONTRACTOR (SEE ELECTRICAL PLANS). BAS SHALL PROVIDE RELAYS FOR SIX CONTACTORS FOR EXTERIOR LIGHTING ZONES AND PROVIDE TIME SCHEDULE CONTROL AND REMOTE OPERATION (ON/0FF) OF ALL LIGHTING ZONES THROUGH THE BAS. SEE INFORMATION ON ELECTRICAL PLANS AND COORDINATE WITH ELECTRICAL CONTRACTOR. DUCTLESS SPLIT SYSTEMS: DUCTLESS SPLIT SYSTEM UNITS SHALL BE PROVIDED WITH STAND ALONE CONTROLS, PROGRAMMABLE THERMOSTATS BY UNIT MANUFACTURER= SEPARATE FROM THE CENTRAL DDC SYSTEM. DDC VENDOR SHALL PROVIDE TEMPERATURE SENSOR FOR THOSE ROOMS THAT WILL ALARM DDC SYSTEM WHEN TEMPERATURE RANGE OUT OF LIMITS. UNIT FANS SHALL BE STARTED AND STOPPED WITH ISTHERMOSTAT CALL INDOOR FOR COOLING. UPON A RISE IN SPACE TEMPERATURE ABOVE THERMOSTAT SETPOINT, UNIT COMPRESSOR SHALL ACTIVATE TO SATISFY SPACE CONDITIONS. BOILERS AND HOT WATER PUMPS SHALL BE STOPPED/STARTED BY THE BAS ON A PROGRAMMED BASIS. PRIMARY AND SECONDARY HOT WATER PUMPS SHALL BE ENABLED, WITH LEAD BOILER AND ASSOCIATED PRIMARY HOT WATER PUMP AND LEAD SECONDARY HOT WATER PUMP STARTED BY THE BAS. FREEZE PROTECTION: A MIXED AIR TEMPERATURE SENSOR SHALL BE LOCATED UPSTREAM OF THE FIRST COIL IN THE AHU. UPON A DROP IN TEMPERATURE BELOW 40° F AT THE MIXED AIR SENSOR, AN ALARM SHALL BE SENT TO THE CENTRAL BAS. THE OUTSIDE AIR DAMPER SHALL BE OVERRIDDEN TO THE MINIMUM OCCUPIED TOILET EXHAUST FANS CENTRAL BAS SHALL OPERATE EXHAUST FANS ON A PROGRAMMED SCHEDULE. FANS SHALL RUN WHEN ASSOCATED ZONE IS IN THE OCCUPIED MODE, AND BE OFF WHEN ASSOCIATED ZONE IS IN THE UNOCCUPIED MODE. SN A A M M & 20 ME (AM), M MM & THE OA DAMPER SHALL RETURN TO NORMAL OPERATION. MIXED AIR TEMPERATURE SHALL HAVE SOFTWARE RESET AND A 20 MINUTE DELAY (ADJ). MW MN EMM BAS SHALL STOP/START ENERGY RECOVERY VENTILATORS ON A PROGRAMMED BASIS. FANS SHALL RUN CONTINUOUSLY WHILE IN THE OCCUPIED MODE AND SHALL REMAIN OFF WHILE IN THE UNOCCUPIED MODE, UNLESS OVERRIDDEN BY AN OCCUPANCY SENSOR (CONTROLLING THE LIGHTS) IN ANY ROOM SERVED BY THE ERV. FANS SHALL DEENERGlZE WHEN OCCUPANCY SENSOR SENDS OFF SIGNAL TO LIGHTS C N LS AND A ADNG SEQUENCER A IRED TO MAN IN A S HOT WATER SUPPLY TEMPERATURE PER THE RESET SCHEDULE BELOW TEM HOT WATER SUPPLY TEMPERATURE RESET SCHEDULE (ADJ) 160° F HWS AT 30° F. O A TEMP OR BELO 120° F. HWS AT 60° F. O.A. TEMP. (OR ABOVE) HWS SHALL VARY LINEARLY BETWEEN THE HIGH AND LOW TEMPERATURES (AS MEASURED IN THE HWS LOOP, NOT AT THE BOILERS). THE INITIAL SETPOINT FOR THE HOT WATER SUPPLY TEMPERATURE SHALL BE 160° F. BOILER STAGING SHALL EQUALIZE BOILER RUN TIME BY ROTATING LEAD BOILER ON A WEEKLY BASIS. AN ALARM SIGNAL SHALL BE SENT TO THE ENERGY MANAGEMENT SYSTEM IF THE HEATING SUPPLY WATER TEMPERATURE DROPS MORE THAN 20*F BELOW THE OPERATING SETPOINT FOR A PERIOD OF 10 MINUTES. THE BAS SHALL ALSO GENERATE AN ALARM IF ANY BOILER OR HOT WATER PUMP VARIABLE FREQUENCY DRIVE INDICATES AN ALARM. THE HOT WATER SECONDARY PUMPS ARE VARIABLE FLOW PUMPS WITH VARIABLE FREQUENCY DRIVES, SETUP IN A PRIMARY/STAND-BY CONFIGURATION. THE BAS SHALL START THE VARIABLE SPEED SECONDARY HOT WATER PUMPS. SECONDARY PUMP SPEEDS ARE CONTROLLED BY VFD'S. THE BAS SHALL MONITOR THE VFD OPERATING SPEEDS AND ALARM CONDITIONS. THE VARIABLE FREQUENCY DRIVES FOR THE PUMPS SHALL BE CONTROLLED BY DIFFERENTIAL PRESSURE SENSORS IN THE HOT WATER PIPING SYSTEM (SEE PIPING PLANS FOR SENSOR LOCATIONS). AS AIR HANDLING EQUIPMENT CONTROL VALVES OPEN, LEAD PUMP SPEED SHALL BE INCREASED VIA VARIABLE FREQUENCY DRIVE TO MAINTAIN SYSTEM PRESSURE SETPOINT. THE INITIAL HOT WATER DIFFERENTIAL PRESSURE SETPOINT SHALL BE 12 PSI. THIS SETTING SHALL BE ESTABLISHED DURING TESTING & BALANCING. IF ONE OR MORE OF THE SENSORS ARE BELOW SETPOINT, THE DRIVE SPEED SHALL BE INCREASED IN RESPONSE TO THE SENSOR WITH THE LARGEST DEVIATION BELOW SETPOINT. IF ALL OF THE SENSORS ARE ABOVE SETPOINT, THE DRIVE SPEED SHALL BE DECREASED IN RESPONSE TO THE SENSOR WITH THE SMALLEST DEVIATION ABOVE SETPOINT. PROVIDE DEAD-BAND AND/OR TIME DELAYS TO PREVENT RAPID CYCLING OF PUMPS. 3-WAY CONTROL VALVES ARE PROVIDED WITH CERTAIN UNITS TO MAINTAIN MINIMUM PUMP FLOW (SEE PIPING PLANS FOR UNIT LOCATIONS). STAND-BY PUMP SHALL START AUTOMATICALLY UPON FAILURE OF PRIMARY PUMP, AND AN ALARM INDICATING PUMP FAILURE SHALL BE SENT TO THE BAS. BAS SHALL ALTERNATE PRIMARY AND STAND-BY PUMPS TO EQUALIZE RUN TIME. THE BAS SHALL GENERATE AN ALARM IF THE SYSTEM PRESSURE DEVIATES FROM SETPOINT BY GREATER THAN 6 PSI FOR MORE THAN 5 MINUTES, IF THE STAND-BY PUMP FAILS TO START, OR IF THE VARIABLE FREQUENCY DRIVE INDICATES AN ALARM. THE HOT WATER SECONDARY PUMPS SHALL OPERATE FOR 10 MINUTES AFTER THE BOILER SYSTEM IS COMMANDED TO STOP. A LOW VOLTAGE THERMOSTAT SHALL START PUMP ROOM VENTILATION FAN WHEN BOILER ROOM TEMPERATURE RISES ABOVE 85* F (ADJUSTABLE). RELIEF DAMPER SHALL BE INTERLOCKED WITH FAN. A CARBON MONOXIDE/OXYGEN DEPLETION SENSOR SHALL BE PROVIDED IN THE BOILER ROOM AND SHALL ACTIVATE AN AUDIBLE AND VISUAL ALARM INSIDE THE BOILER ROOM, ACTIVATE THE VENTILATION FAN, AND SEND AN ALARM TO THE CENTRAL BAS IF ACTIVATED. A PUSHBUTTON EMERGENCY GAS SHUTOFF SWITCH SHALL BE PROVIDED AT THE BOILER ROOM TO CLOSE A SOLENOID VALVE IN THE GAS LINE SERVING HVAC AND DOMESTIC WATER HEATING EQUIPMENT. ACTIVATION OF THE SWITCH SHALL CLOSE THE GAS VALVE AND ALARM THE CENTRAL BAS (VALVE AND SWITCH BY E.C.) A FREEZE-STAT SHALL BE LOCATED UPSTREAM OF THE COOLING COIL, AND SHALL SHUT DOWN THE AHU FANS AND ALARM THE CENTRAL BAS IF THE TEMPERATURE IS BELOW 38° F. THE SECONDARY CHILLED WATER PUMP AND THE HOT WATER PUMP SHALL START, AND THE HOT WATER AND CHILLED WATER CONTROL VALVES AT THE AIR HANDLING UNIT SHALL OPEN FULLY. FREEZE-STAT SHALL HAVE MANUAL RESET ONLY. SINGLE ZONE VARIABLE VOLUME (SZVAV) AIR HANDLING UNITS: A TEMPERAUTRE SENSOR SHALL BE UTILIZED TO MAINTAIN SPACE TEMPERATURE. THE UNIT SUPPLY FAN SHALL START AT LOW SPEED. ON A RISE IN TEMPERATURE ABOVE SETPOINT, THE CHILLED WATER CONTROL VALVE SHALL OPEN TO THE CHILLED WATER COIL. ON A CONTINUED RISE IN TEMPERATURE, VARIABLE FREQUENCY DRIVE SHALL INCREASE AIR FLOW TO SATISFY SPACE TEMPERATURE REQUIREMENTS. AS THE SPACE TEMPERATURE DROPS BELOW SETPOINT, THE FAN SPEED SHALL RESET FROM MAXIMUM TO MINIMUM. AS THE SPACE TEMPERATURE CONTINUES TO DROP, THE CHILLED WATER CONTROL VALVE SHALL CLOSE TO THE COOLING COIL AND THE HOT WATER CONTROL VALVE SHALL OPEN TO THE HEATING COIL. ON A CONTINUED DROP IN SPACE TEMPERATURE, THE SUPPLY FAN SPEED SHALL INCREASE TO MAINTAIN SETPOINT. THE TEMPERATURE SENSOR SHALL BE PROVIDED WITH AN OVERRIDE FUNCTION THAT WILL PLACE THE SYSTEM IN THE OCCUPIED MODE FOR A PERIOD OF UP TO 2 HOURS. BAS SHALL HAVE GLOBAL CONTROL OVER DOMESTIC WATER HEATING SYSTEM. WATER HEATERS SHALL CYCLE ON AND OFF BASED ON THEIR TANK TEMPERATURES, TO MAINTAIN 140' FOR WH-1 AND 110° FOR WH-2. AN ALARM SHALL BE GENERATED SHOULD EITHER TANK DEVIATE FROM SETPOINT BY 10° EITHER HIGH OR LOW. AN ALARM SHALL ALSO BE GENERATED SHOULD THE DOMESTIC HWS TEMPERATURE DEVIATE FROM SETPOINT BY 10° EITHER HIGH OR LOW. CIRCULATION PUMPS SHALL OPERATE ON A SCHEDULED BASIS BASED ON BUILDING OCCUPANCY. THE PUMPS SHALL BE CAPABLE OF OPERATING ON SEPARATE SCHEDULES, SHOULD THE KITCHEN SCHEDULE DIFFER FROM THE ENTIRE BUILDING. A TEMPERATURE SENSOR SHALL BE MOUNTED IN THE END OF THE LINE CAPABLE OF OVERRIDING THE PUMPS SHOULD THE LOOP TEMPERATURE FALL BELOW 130° FOR CP-L OR 100* FOR CP-2. BAS SHALL ALSO MONITOR BOTH DOMESTIC HWR TEMPERATURES AND DOMESTIC WATER SUPPLY TEMPERATURE FOR TRACKING PURPOSES. SEE PLUMBING PLANS FOR ALL TEMPERATURE SENSOR CLOVER REPLACEMENT MIDDLE SCHOOL FREEZE PROTECTION (LOSS OF POWER) DURING A POWER OUTAGE, THE EMERGENCY GENERATOR SHALL PROVIDE POWER TO THE BOILERS AND HOT WATER PUMPS TO PROVIDE MINIMAL FREEZE PROTECTION THROUGHOUT THE BUILDING. ON A LOSS OF POWER AND THE OUTSIDE AIR TEMPERATURE BELOW 45° (ADJ), ALL HOT WATER CONTROL VALVES SHALL FAIL OPEN AND ALL OUTSIDE AIR DAMPERS SHALL FAIL CLOSED. THE BOILERS AND HOT WATER PUMPS SHALL BE STARTED AND SHALL CIRCULATE THROUGH ALL HOT WATER HEATING COILS. HEAT TAPE FOR EXTERIOR PIPING AT CHILLER AND CHILLER HEATER CIRCUIT SHALL BE PROVIDED WITH EMRGENCY POWER TO PROVIDE FREEZE PROTECTION. A TEMPERATURE SENSOR SHALL BE PROVIDED WITHIN THE INSULATION ON ALL EXTERIOR PIPING WITH HEAT TAPE TO VERIFY HEAT TAPE OPERATION. IF TEMPERATURE FALLS BELOW 35° F. (ADJ), AN ALARM SHALLL BE SENT AND Of fleef 1927SouthTryonSt.,Suite300,CharlotteNC28203 Phone: 704-338-1292 042 www.optimapa.com North Carolina License Number C-0914 KITCHEN EQUIPMENT FREEZER AND COOLER CONTROL PROVIDE NEW WALL MOUTED TEMPERATURE SENSORS TO MONITOR THE TEMPERATURES IN THE FREEZER AND COOLER. HVAC SCHEDULING INITIAL SCHEDULES OF OPERATION SHALL BE COORDINATED AND CONFIRMED BY THE OWNER, AND PROGRAMMED BY THE CONTROLS CONTRACTOR. MODIFICATION OF SCHEDULES SHALL BE A PART OF REQUIRED OWNER TRAINING. DISCREET SCHEDULES SHALL BE PROVIDED FOR EACH AIR HANDLING UNIT. SCHOOL CALENDAR SHALL BE PROGRAMMED INTO THE BAS SUCH THAT THE SYSTEMS UNOCCPUIED ON DAYS THE SCHOOL IS CLOSED AND ON TEACHER REMAIN WORKDAYS ADMINISTRATION AREA SHALL REMAIN IN THE OCCPUIED MODE DURING THE SUMMER, EXACT HOURS TO BE COORDINATED WITH THE OWNER. REMAINING AIR HANDLING UNITS SHALL BE INITIALLY SET TO BE IN THE OCCUPIED MODE FROM 30 MINUTES BEFORE THE OPENING BELL TO 30 MINUTES PRIOR TO THE CLOSING BELL, UNTIL MODIFIED BY START/STOP OPTIMlZATION. AFTER HOURS OPERATION FOR ALL ZONES SHALL BE COORDINATED WITH THE OWNER WITH INPUT FROM THE KITCHEN, ATHLETIC, LIBRARY, AND FINE ARTS STAFF. JWMEDESIGNTRANSPORM 227WEST TRADESTREET SUITE700 CHARLOTTE NORTH CAROLINA 28202 START/STOP OPTIMlZATION BAS SHALL PROVIDE START/STOP OPTIMlZATION (SS0) FOR ALL EQUIPMENT AND SYSTEMS. SSO SHALL BE CAPABLE OF LEARNING BUILDING THERMAL CHARACTERISTICS AND RESPOND TO VARIABLE CONDITIONS. SSO SHALL START/STOP CONTROLLED EQUIPMENT AS LATE AS POSSIBLE PRIOR TO OCCUPIED TIME PERIOD AND AS EARLY AS POSSIBLE PRIOR TO UNOCCUPIED TIME PERIOD. SSO SHALL BE CALCULATED BASED ON OUTDOOR AIR TEMPERATURE, ZONE TEMPERATURES, AND CONTROL SETPOINT SETBACK TEMPERATURES. TEL. 704.333.6686 FAX 704.333.2926 WWW.LS3P.COM untras CA OPTIMA ENGINEERING No. C00710 WALL/UNIT HEATERS A BUILT-IN THERMOSTAT SHALL OPERATE WALL/UNIT HEATER AND FAN TO MAINTAIN A SETPOINT OF 49° (ADJ). ONCE THE UNIT HEATER IS ENERGlZED, IT WILL RUN FOR AT LEAST FIVE MINUTES TO AVOID SHORT CYCLING. BAS DOES NOT INTERFACE WITH UNIT HEATERS. THE HOT WATER SYSTEM WILL BE COMMANDED TO RUN IF THE OUTDOOR TEMPERATURE IS BELOW 60T OR ANY HOT WATER CONTROL VALVE IS COMMANDED OPEN FOR HEATING OR DEHUMIDIFICATION. A - WHILE IN THE OCCUPIED MODE THE SUPPLY FAN SHALL OPERATE CONTINUOUSLY. WHILE IN THE UNOCCUPIED MODE, THE UNIT SUPPLY FAN SHALL CYCLE WITH HEATING AND COOLING LOADS, THE CHILLED WATER AND HOT WATER CONTROL VALVES SHALL BE CLOSED TO THE UNIT. UPON A CALL FOR HEATING OR COOLING TO MEET UNOCCUPIED SETPOINTS, THE UNIT FAN SHALL BE STARTED AND THE UNIT SHALL OPERATE AS DESCRIBED BELOW AS REQUIRED BY THE SPACE TEMPERATURE. THE BOILER PLANT OR CHILLER PLANT SHALL ALSO BE STARTED AS REQUIRED TO SATISFY SETPOINTS. THE UNIT AND ASSOCIATED CENTRAL PLANT SHALL OPERATE FOR A MINIMUM OF 30 MINUTES (OR AS REQUIRED TO SATISFY UNOCCUPIED SETPOINT) AND SHALL NOT BE ALLOWED TO RESTART FOR A MINUM OF 15 MINUTES FOLLOWING SATISFACTION OF UNOCCUPIED SETPOINT AND SYSTEM SHUT-DOWN. DOMFSTIC HOT WATFR SYSTFM SMOKE DETECTION & AHU SHUTDOWN: UPON DETECTION OF SMOKE IN THE AIR HANDLING SYSTEM BY THE DUCT-MOUNTED RETURN AIR SMOKE DETECTOR, AN ALARM CONDITION SHALL BE SENT TO THE BUILDING FIRE ALARM SYSTEM AND ALL AIR HANDLING UNITS SHALL BE SHUTDOWN BY THE BUILDING FIRE ALARM SYSTEM. THE BUILDING FIRE ALARM SYSTEM SHALL PROVIDE ONE DIGITAL OUTPUT TO THE BAS TO INDICATE ACTIVATION OR FAILURE OF ANY SMOKE DETECTOR. BOILER PLANT PRIMARY SECONDARY WITH CONDENSING BOILERS B - VARIARI F AIR VOI UMF ROXFS AIR HANDLING UNITS SHALL BE STOPPED/STARTED ON A TIME OF DAY SCHEDULE THROUGH THE BAS. THIS SCHEDULE SHALL BE MODIFIED BY A START STOP OPTIMlZATION PROGRAM. UPON PROOF OF AIR FLOW THRU THE SUPPLY FAN, AS SENSED BY A RESPECTIVE CURRENT SENSING RELAY, THE NORMALLY CLOSED OUTSIDE AIR DAMPER SHALL BE ENABLED. ..... OF ifmin MISC. EXHAUST FANS PROVIDE WALL SWITCHES, WALL THERMOSTATS, INTERLOCKS, ETC. AS INDICATED ON THE FAN SCHEDULE TO CONTROL FANS AS INDICATED ON PLANS. BOILER ROOM AND ELECTRICAL ROOM THERMOSTATS SHALL BE SET AT 85* F. (USER ADJUSTABLE, BAS REMOTE). lH1888 2 7 rñ MEMBERSOFTHEAMERICANINSTITUTEOFARCHITECTS FIELD HOUSE SPLIT SYSTEM UNIT SHALL BE CONTROLLED BY ITS TEMPERATURE SENSOR. UNIT SUPPLY FAN SHALL RUN CONTINUOUSLY IN THE OCCUPIED MODE, CYCLE WITH HEATING AND COOLING WHILE UNOCCUPIED. UPON A RISE IN SPACE TEMPERATURE, UNIT COMPRESSOR AND CONDENSER FAN SHALL ACTIVATE TO SATISFY SPACE. UPON A DROP IN SPACE TEMPERATURE, UNIT COMPRESSOR SHALL ACTIVATE IN REVERSE CYCLE FOR HEATING. UPON A FURTHER DROP IN SPACE TEMPERATURE, ELECTRIC HEAT SHALL BE ENERGlZED TO SATISFY SPACE TEMPERATURE. THERMOSTATS SHALL PROVIDE A DEADBAND OF 5*, WITHIN WHICH THE SUPPLY OF HEATING OR COOLING ENERGY TO THE ZONE CAN BE REDUCED TO THE MINIMUM. THE TEMPERATURE SENSOR SHALL BE PROVIDED WITH AN OVERRIDE FUNCTION THAT WILL PLACE THE SYSTEM IN THE OCCUPIED MODE FOR A PERIOD OF UP TO 2 HOURS. COPYRIGHT 2014 ALL RIGHTS RESERVED PRINTED OR ELECTRONIC DRAWINGS AND DOCUMENTATION MAY NOT BE REPRODUCED INANYFORMWITHOUTWRITTENPERMISSION FROM LS3P ASSOCIATES LTD. REVISIONS: - No Description PROJECT: 9201-131360 DATE: DRAWN BY: OCT.31,2014 SRD Date NOTES- VARIABLE AIR VOLUME (VAV) AIR HANDLING UNITS: A DISCHARGE AIR TEMPERATURE SENSOR SHALL CONTROL CHILLED WATER AND HOT WATER CONTROL VALVES TO MAINTAIN SUPPLY AIR TEMPERATURE PER THE RESET SCHEDULE BELOW. 1. SEE SPECIFICATIONS FOR ADDITIONAL REQUIREMENTS. 2. ALL CONTROL SETPOINTS SHALL BE ADJUSTABLE AND TRENDABLE BY THE USER WITHOUT ASSISTANCE FROM THE CONTROLS MANUFACTURER. THIS SHALL BE COVERED AS PART OF TRAINING WITH OWNER, SCHOOL STAFF, AND MAINTENANCE DEPARTMENT. INDICATED SCHEDULES AND SETPOINTS SHOULD BE USED FOR ORIGINAL SYSTEM SET-UP. ANY CHANGES IN SETPOINT SETTINGS REQUIRED FOR INTENDED SYSTEM OPERATION SHALL BE APPROVED BY THE ENGINEER AND SHALL BE DISCREETLY INDICATED SUPPLY AIR TEMPERATURE RESET SCHEDULE (ADJ) 55° F. HWS AT 70° F. O.A. TEMP. (OR ABOVE) 65° F. HWS AT 30° F. O.A. TEMP. (OR BELOW) SUPPLY AIR TEMPERATURE SHALL VARY LINEARLY BETWEEN THE HIGH AND ON THE AS-BUILT DRAWINGS. LOW TEMPERATURES. THE INITIAL SETPOINT FOR THE DISCHARGE AIR SUPPLY TEMPERATURE SHALL BE 60° F. SUPPLY AIR TEMPERATURE SETPOINT SHALL HAVE A HIGH LIMIT OF OF 62° REGARDLESS OF OUTSIDE AIR TEMPERATURE, WHEN ANY ZONE ON THE AHU HAS A CALL FOR COOLING. 3. CURRENT SWITCHES SHALL BE PROVIDED IN THE PIPING OF EACH PUMP TO VERIFY PUMP STATUS. 4. PHOTOELECTRIC TYPE DUCT SMOKE DETECTORS WILL BE PROVIDED BY THE ELECTRICAL CONTRACTOR, INSTALLED IN THE DUCT BY THE MECHANICAL CONTRACTOR AND WIRED TO SHUT-DOWN THE UNIT BY THE ELECTRICAL CONTRACTOR. 5. ELECTRICAL CONTRACTOR SHALL PROVIDE A DEDICATED 120V CIRCUIT IN A J-BOX FOR CONTROL POWER. CONTROLS CONTRACTOR SHALL EXTEND 120V POWER FROM J-BOX TO CONTROL PANELS, DAMPER ACTUATORS= TRANSFORMERS, ETC. AS REQUIRED FOR INSTALLATION OF THE CONTROL SYSTEM. ALL CONTROL TRANSFORMERS SHALL BE SEPARATELY INTERNALLY FUSED OR HAVE MANUAL RESETS. 6. BAS SHALL ALLOW GLOBAL OPERATION OF HOT WATER AND CHILLED WATER CONTROL VALVES. 7. CONTROLS CONTRACTOR SHALL PROVIDE A MINIMUM OF 8 HOURS OF OWNER TRAINING PROVIDED BY A FACTORY CERTIFIED REPRESENTATIVE. COORDINATE THROUGH THE MECHANICAL CONTRACTOR AND CONSTRUCTION MANAGEMENT FIRM. 8. THE SEQUENCE OF OPERATION OF OPERATION AND POINTS LIST IS INTENDED TO COMMUNICATE THE MINIMUM REQUIREMENTS AND GENERAL DESIGN INTENT TO THE CONTROLS CONTRACTOR AND IS NOT INTENDED TO BE A FULLY DEVELOPED OR COMPLETE SEQUENCE OF OPEARTION. IN THE CONTROLS SUBMITTAL THE CONTROLS CONTRACTOR SHALL FULLY DEVELOP THE SEQUENCE OF OPERATIONS FOR ALL SYSTEMS IDENTIFIED AN SHALL PRESENT ALL SETPOINTS, CONTROL PARAMETERS, TIME DELAYS, ALARM POINTS, ETC. AS REQUIRED TO COMPLY WITH THE DESIGN INTENT. THE CONTROLS CONTRACTOR SHALL INCORPORATE STANDARD FEATURES SUCH THE STATIC PRESSURE SENSOR IN THE SUPPLY DUCT SHALL MODULATE THE VARIABLE FREQUENCY DRIVE TO MAINTAIN THE SETPOINT ESTABLISHED DURING FINAL TESTING AND BALANCING. THE PRELIMINARY SETPOINT SHALL BE 0.75" STATIC PRESSURE. THIS SETPOINT SHALL BE RESET BASED ON THE ZONE REQUIRING THE MOST PRESSURE; LE., THE SETPOINT IS RESET LOWER UNTIL ONE TERMINAL BOX DAMPER IS NEARLY WIDE OPEN. GAS/DX ROOFTOP UNITS A TEMPERATURE SENSOR SHALL BE UTILIZED TO MAINTAIN SPACE TEMPERATURE. UNIT SUPPLY FAN SHALL RUN CONTINUOUSLY IN THE OCCUPIED MODE, CYCLE WITH HEATING AND COOLING WHILE UNOCCUPIED. UPON A RISE IN SPACE TEMPERATURE, UNIT COMPRESSORS AND CONDENSER FANS SHALL ACTIVATE IN STAGES TO SATISFY SPACE. UPON A DROP IN SPACE TEMPERATURE, GAS HEAT SHALL BE ACTIVATED IN STAGES TO SATISFY SPACE TEMPERATURE. INTERNAL UNIT CONTROLS SHALL OPERATE ENTHALPY ECONOMlZER WHEN OUTSIDE AIR ENTHALPY IS LOWER THAN RETURN AIR ENTHALPY. THERMOSTATS SHALL PROVIDE A DEADBAND OF 5*, WITHIN WHICH THE SUPPLY OF HEATING OR COOLING ENERGY TO THE ZONE CAN BE REDUCED TO THE MINIMUM. THE TEMPERATURE SENSOR SHALL BE PROVIDED WITH AN OVERRIDE FUNCTION THAT WILL PLACE THE SYSTEM IN THE OCCUPIED MODE FOR A PERIOD OF UP TO 2 HOURS. CHECKED BY: RVA SE - UENCE OF OPERATION AS MINIMUM RUN TIME DELAYS AND DEAD BANDS TO PREVENT SHORT CYCLING. ALL MONITORED POINTS SHALL INCLUDE EARLY HIGH/LOW ALARM NOTIFICATIONS PRIOR TO REQUIRED CORRECTIVE ACTIONS OR UNIT SHUT-DOWNS. CONTROL CONTRACTOR SHALL SPECIFY IN THE CONTROL SUBMITTAL FAIL SAFE POSITION FOR OUT OF RANGE, FAIL SAFE POSITIONING FOR OPEN CIRCUITS OR LOSS OF COMMUNICATION. OPTIMA # 13-0238 4 OF 26 SOLUTIONS THROUGH LISTENING THIS DRAWING IS AN INSTRUMENT OF SERV CE. THE DRAWING AND THE INFORMATION THEREON IS THE PROPERTY OF OPTIMA ENGINEERING, P.A. ANY REPR()DUCTION, ALTERATION, OR USE FOR OTHER THAN THE INTENDED PROJECT, WITHOUT THE WRITTEN CONSENT OF OPTIMA ENGINEERING, P.A. IS EXPRESSLY FORBIDDEN. COPYRIGHT ©OPTIMA ENGINEERING P.A. 2014, ALL RIGHTS RESERVED. 1 2 3 4 5 6 BID DOCUMENTS CLOVERSCHOOL INPUT/OUTT UT SUMMARY DISmCT mO INPUTS M -ASURED - OUTF JTS BliAR'' CALC. DIGITAL SYSTEM, RE 3YS1 EM FEATURES ANALOG ALARMS l'ROCRAM3 z GENETAL 540² P0 SUPPLMENT. DESCRIPTION CLOVER SCHOOL DISTRICT 540T " E ChElar Plant X X X Chiller #1 On/off X Chiller #1 Panel Interface Chiller #2 On/off X X ne neerface X X Primary CHR Temp Primary Pump P-3 Primary Pump P-4 Primary Pump P-9 Secondary Pump P-1 Secondary Pump P-2 Secondary CHS Temp Secondary CHR Temp Differential Pressure Boger Plant (Prl/Sae) Boiler Sequencer Interface Boiler #1 On/Off X Boiler #2 Status Primary HWS Temp Primary HWR Temp Primary Pump P-7 Primary Pump P-8 Secondary Pump P-5 Secondary Pump P-6 Secondary HWS Temp Secondary HWR Temp Differential Pressure X X X X X X X X X X X X X X X X X X X X X X X CLOVER X X X X X X * X X X X X X X X X X X X X Building Loop Building Loop Building Loop (Typ of 2) X X X X X X X X X X X X X X X X 1927 South Tryon St., Suite 300, Charlotte NC 28203 X Phone: 704-338-1292 042 www.optimapa.com North Carolina License Number C-0914 X X X X X X X X X X X X X X X X X X X X Building Loop Building Loop Building Loop (Typ of 2) X X X X X 227 WEST TRADE STREET SUITE 700 CHARLOTTE, NORTH CAROLINA 28202 TEL. 704.333.6686 FAX 704.333.2926 WWW.LS3P.COM X X X X X X Smoke Detector X OA Damper OA Airflow Mon. Station Relief Damper untIts X X X Retum Damper Retum Fan VFD on/off OPTIMA X Retum Fan VFD Speed Where Where Where Where X X Retum Fan VFD Status Building Pressure Filter Status X X Indicated Indicated Indicated Indicated PA No. C00710 HHHG X X X X X Freezestat CHW Valve HW Reheat Valve Supply Fan Supply Fan VFD on/off Supply Fan VFD Speed Supply Fan VFD Status Supply Static Pressure Supply Temp Space CO2 Space Humidity Space Temp Over-ride - X Retum RH Retum CO2 Mixed Air Temp HW Preheat Valve MIDDLE SCHOOL X X X X X Air Handlina Unita c - REPLACEMENT X Boiler Rm Oxygen Depletion Boiler Rm Gas Solenoid Retum Temp X X Boiler #1 Status Boiler #2 On/Off D - X X Chiller #1 Status Primary CHS Temp X X lHIHf X X X X X CV Only SZVAV & VAV Only SZVAV & VAV Only X X X X .. 2 SZVAV & VAV Only X VAV Only X 10/31M X X X X X MEMBERS OF THE AMERICAN INSTITUTE OF ARCHITECTS CV & SZVAV Only CV & SZVAV Only X COPYRIGHT 2014 ALL RIGHTS RESERVED PRINTED OR ELECTRONIC DRAWINGS AND DOCUMENTATION MAY NOT BE REPRODUCED IN ANY FORM WITHOUT WRITTEN PERMISSION FROM LS3P ASSOCIATES LTD. VAV Bar Volume Damper HW Valve Discharge Temp Over-ride X X X X X Setpoint Adjust B - Space Temp REVISIONS: X _ X No. Description Date Fnernv Renownrv Ventilators Supply Fan X X Exhaust Fan X X Misc. Pointe OA Temp OA CO2 Dew Point Elec Demand X X X X X X X X X Domestic Water Meter Gas Meter - X X X Fire Alarm Status Exterior Lighting Control - X X X Typical of 6 Contactors Freezer Temp X X DATE: OCT. 31, 2014 Cooler Temp X X DRAWN BY: SRD Toilet Fans Misc. Fans Domestic HW Pump Domestic HWS Temp Domestic HWR Temp Storage Tank End of Line Loop Temp Domestic Water Supply Heat Tape X X X X X X X X X X CHECKED BY: RVA See Fan Schedule Typical of 2 Typical of 2 Typical of 2 Typical of 2 Typical of 2 X X MECHANICAL TYP OF 4 GENERAL NOTE: INPUT/OUTPUT SUMMARY IS A GENERAL LISf OF CONTROL POINTE REQUIRED FOR TH : OPERATION O THE MEC IANICAL SYS EM. IN ADDlllON TO CONTROL POINTS INDICATED, THE CONTROLS JONTRACTOR SHALL BE RESPCNSIBLE FOR PROVIDNG ADDITIONAL POINTS A: REQUIRED FOR OPERATION OF THE MECHANICAL SYSTEM AS SPECIFIED AND OUTLINED IN THl: SEQUENCE OF OPERiTION AhD TO COM *LY WITH THE :PECIFICATloNS. nm OPTIMA # 13-0238 5 OF 26 SOLUTIONS THROUGH LISTENING THIS DRAWING IS AN INSTRUMENT OF SERVICE. THE DRAWING AND THE INFORMATION THEREON IS THE PROPERTY OF OPTIMA ENGINEERING, P.A. ANY REPRODUCTION, ALTERATION, OR USE FOR OTHER THAN THE INTENDED PROJECT, WITHOUT THE WRITTEN CONSENT OF OPTIMA ENGINEERING, P.A. IS EXPRESSLY FORBIDDEN. COPYRIGHT ©OPTIMA ENGINEERING P.A. 2014, ALL RIGHTS RESERVED. 1 2 3 4 5 6 BID DOCUMENTS CLOVER SCHOOL DISTRICT TWO 10"ø 315-E 515+E 10"ø . = 2.2 260-D CS B 260 D 8xf UP TO CLOVER SCHOOL DISTRICT 1 F[ 10"ø WØ suh cMd. ma æv amnenn 300-E E 300-E 300-E P 300-E P M P CLOVER REPLACEMENT MIDDLE SCHOOL 52x24 5 D P 170-D 6 C to"ø 320-E 320 E 2M-D 1FE 12"ø 654 200-D - - "ø 0"ø L F 440- 180-K 12"ø 280-D N - 10= 265+·D 2 5-D 10"ø 265[ -D P P 10"ø --- 210- D 320-E . 320+E n -r __.. 280-D 280- ) rrrrr mn 10"# 6"ø- · 10"ø 210-D · c 150 -D 10"ø 2"ø 1927 South Tryon St., Suite 300, Charlotte NC 28203 P A 270hD 420-E 8"p D - -- .._ _ .-- 12 12 200-D MO C K imo ; 70-D 280-D - 8"ø 420- - 280-0 K LS P 12" t 100+C "ø 18×16 SP 32× 54x 8 40x20 t 5-C 6"ø ST DUCT IP OF CAP)_ TO . , f 50-E( 8" FXHAUST DUCT L P TO ROO -E :: 210 D :: 190-D 370 -- 420-E 420-E 420- 420-F - P 50 10"p 6"ø 38 10"ø 10"ø 33 P 2 0-D o ; 70-D 420-E RI$E 10"ø 350- E P N 350- : Phone: 704-338-1292 042 www.optimapa.com North Carolina License Number C-0914 420-E -12"ø 1 "ø 440-: 10"ø 240 D 227 WEST TRADE STREET SUITE 700 CHARLOTTE, NORTH CAROLINA 28202 TEL. 704.333.6686 FAX 704.333.2926 WWW.LS3P.COM . 6", 305-E 335-E 240K 240-[ K 10"1 FD 4 -12"ø 420- 420-F 440-: 111111 10"ø 0"ø 110-C F -AliV-3 HLMIDISTAT NEE SEQUEhlCE OF OP R 101 - 1 ....... ø 12"ø 100 C 75 -B 42u-E 305 -E 10"ø 1M-C r -E 335-E . 350- E K +1ox10 .*ø .. 3bO- - 10"ø Ó 305 -E 420-E 420-E -129 420- 305-E P (EX END 8"ø E(HAUST DUCT TO WALL LOUVER) - P TO -- -- ERING No. C00710 10x1C STAINLESS STEEL STEEi DUCT UP TO EAN_ --I ON RO)F ON ROOF 10"ø ENG 420-E 10x10 .. 10 = 440- -*- KILN WITH VENT FAN (BY OTHERS), PROVIDE 4"ø 11111## EMENTS WI K N MANUFACTURE L 12'ø P Mx¼ , 12" 305-E -- - 123 - -16x4 12"ø 335-E 40$-E - -16x4 1 N 22× 1GK N NOOD - -··· ROOF 6"ø + 4 ø R G DR R VENT DO IN WALL TO DRYER - 160- 1D"p 320-P MEMBERS OF THE AMERICAN INSTITUTE OF ARCHITECTS _ 10 6"ø 1 x1 - 100-K 340-P K T( l P -.,--r·~···· 16x4 EXHAUST DUCT DOWN TO DISHWASHER (SEE 14/M-402) -. 22xTS 10. 16x14 14×14 75-K 22x COPYRIGHT 2014 ALL RIGHTS RESERVED PRINTED OR ELECTRONIC DRAWINGS AND DOCUMENTATION MAY NOT BE REPRODUCED IN ANY FORM WITHOUT WRITTEN PERMISSION FROM LS3P ASSOCIATES LTD. 6"ø - r 1 W 10×10 \ 40k14 REVISIONS: _ B o ------ K 12"ø l-l 1bO-b CHlHFR @ SUP SS10 S A - A2 EX|-|AU_SI 4800 -600 MAKE-_U.P_ -3840 -- 250 -- HIV-1 -- -- 800 AliU-_4 -- -- 1200 (MINIMUM) 5650 5650 -- 3840 PLAN NORTH N 2000 5840 190 -CFM (POSITIVE) 1/8" = 1'-0" a2 a2 B.1 C.1 OUTSIDF AIR ---- EAN_E-6. SUB-TOTALS _T_QIALS FLOOR PLAN AREAS A.1 AND A.2 - MECHANICAL I DRAWN BY: SRD 4 I 5 -= I FLOOR PLAN AREA A.1 & A.2 - MECHANICAL WALL RATING LEGEND - 042 042 042 3-HOUR FIRE WALL - - - - 2-HOUR FIRE BARRIER OPT MA # 13 0238 == SMpKE PART 040TIONSOLUTIONS THROUGH LISTENING (NOT RATED) THIS DRAWING IS AN INSTRUMENT OF SERVICE. THE DRAWING AND THE INFORMATION THEREON IS THE PROPERTY OF OPTIMA ENGINEERING, P.A. ANY REPRODUCTION, ALTERATION, OR USE FOR OTHER THAN THE INTENDED PROJECT, WITHOUT THE WRITTEN CONSENT OF OPTIMA ENGINEERING, P.A. IS EXPRESSLY FORBIDDEN. COPYRIGHT © OPTIMA ENGINEERING P.A. 2014, ALL RIGHTS RESERVED. 3 OCT. 31, 2014 CHECKED BY: RVA MFCHANICAI FOUIPMFNT (SYSTFM) KITCHFN HOOD FXHAUST KITCHFN HOOD MAKF-UP DISHWASHFR FXHAUST I DATE: 1$0- KITCHEN AREA AIR BALANCE SCHEDULE 2 9201-131360 -36x8 MAKE-UP AIR DUCT CW 1 PROJECT: Date 12x8 400-G 1 Description 10 --- - - -12x12 UP TO 6 No. 6 BID DOCUMENTS PROVIDE OFFSETS TO ALIGN TRANSFER OPENINGS ABOVE A N S ( ICAL A PE IM CLASSROOM TRANSFERS) TRANSFER OPENINGS ABOVE DOOR FRAMES, SEE STRUCTURAL D AWIN S ( CAL ALL PERIMITER R è 360- E 250 D 360-E è 350-E 1 "ø 250 -D ~ 10"ø - 10"Ø- 10"ø 260 -D CLOVER SCHOOL DISTRICT 10"ø r mh cMd, rach Day... ExmHence 250- . 10"ø 250*D ' 260+D I 20x14 10"ø gg 'I F 1 350-E CS B 360- SD D E - CLOVER SCHOOL DISTRICT TWO _ ,_ - -10"ø 10"ø- 10"ø 21x14 P 250 -D 360- E 360-E 360-1 P o"ø P 10"A P 260+D 260 -D P 260 -D 260 -D CLOVER REPLACEMENT MIDDLE SCHOOL HUMIDIS f/ T (SEE 250 D 250--b $EQ 10"ø 350-E NCE ÖF CPCRATION) 350-E t0"W - o*ø 12x12 UP TO 1./ 0 10"ø R)OF 20x12 1 250+D 20x12 Ø Ö $50 D L +L . 250 -D 2 5400-4) 50 C 260+D imo 260 -D 50-C 1927 South Tryon St., Suite 300, Charlotte NC 28203 250- D e $50eD 0"ø 250 -D -10"ø 6"ø 1 1"ø- 2$0-D 290-E 260+D O Phone: 704-338-1292 042 www.optimapa.com North Carolina License Number C-0914 260 -D 10 D .g, -10"ø 290-E - - 10"ø-- 20×12 . 250-D 0 250-D 10 ø- P - -10"ø --- '*- L 290-E 25 0-E 0"Ø 10 -*/- - 22×T6 1 P 0 22× 6 "I4x C 10"i t230 -P × 1500-P 250 D m 22x1 250 -D e P RESIST THE PASSAGE OF SMOKE. SEAL ALL PENETRATIONS OF THESE WALLS PER THE UL DETAILS SHOWN ON SHEET M-403 (TYPICAL) 260+D 260 -D . 10"W 227 WEST TRADE STREET SUITE 700 CHARLOTTE, NORTH CAROLINA 28202 TEL. 704.333.6686 FAX 704.333.2926 WWW.LS3P.COM 10"ø U n 20x11 150 J 10"ø 1 >x16 UP P 0 260-0 10"ø 260+D ' . 9.o. 260 -D 100-C 290-E = 250*D 250-D 250 -D ---E 10"Ø A °" " ° 7 -10'ø 10" - 12k12 UP TO -1 29 1500-P 10 ø 250- D P 250-D ' 260AD 290-E 10"ø e 260 -D 10"Ø Q"ø 29)-E 10"+ tilHN T 1 290 o- ., 10 ø IN 10' RIS 250*D 2qiO¬D T 290-E $50-D No. C00710 -- ° ° 1 6x16 U 10"ø OPTIMA \ ENGINEERING " 290-E 16ft6 UP TO C - GCIENCE CLASSROOM WALLS ARE 22x12 7 T0"ø 250-D ... _ ...- It x16 UP TO EJL -_15 1230 P 90- E 20×12 SCIENCE CLASSROOM WALLS ARE SMOKE PARTITIONS, DESIGNED TO RESIST THE PASSAGE OF SMOKE. SEAL ALL PENETRATIONS OF THESE WALLS PER THE UL DETAILS SHOWN ON SHEET M 103 (TYPICAL) c 1 00-P 29 )-E _ ,, 260 -D -P _, __ \ 260+D - -10"Á - T0"9 P 290-E ---250rD 2)xM 40 ø t ... 250*D LS P TO ø 290-E 0"D 1 P 260+D j260 -D 260+D 260 -D 40" p 10" + 1230- 2 MEMBERS OF THE AMERICAN INSTITUTE OF ARCHITECTS 0 1230-P tiU±t IlUMIDISTAT (SEE SE4tfENCE OF )PERATI )N) 2 254( . . . 22 12 10"ø ROX .12, 1/M 301 CON . T0*ø 1rø 275-D T · ** 250-*D e 250rD 1*tRE SUPRESSIO 1 B - I 250+D -TO M-iU-t 50 C 260-D 300- L N T 10x10 - - 10x8 1Ø"ø 10x8- L Description PROJECT: 9201-131360 DATE: OCT. 31, 2014 DRAWN BY: SRD Date 5-Q L 6"ø I -6 ø 50-B 0-B BB- x r16x16 ..INED -RETURhl AIR / TRANS ER - 6 -- 10"Ø 30 -L a F t4x 4 2$-B " RIGID DR VENT P TO GQ0$Et CK N ROOF DETALL 2/M-403 No. 5- 8x8 310-E . 22x 4 P n 26ß-0 K 10 ø 250AD Kll-3.. 315+E REVISIONS: _ 10"ø- --- - P 15- : 260 -D = 275- D 8 ( xa) 260+D 300-L 35-- C 75-J TTe L 6 ø 6 75-J 40x2d SYSTEM, 0x 0 62x24 50 B COPYRIGHT 2014 ALL RIGHTS RESERVED PRINTED OR ELECTRONIC DRAWINGS AND DOCUMENTATION MAY NOT BE REPRODUCED IN ANY FORM WITHOUT WRITTEN PERMISSION FROM LS3P ASSOCIATES LTD. 22x12 20x12 -10"ø )" p 25(-D 0" K F 0 0"ø 22r 2 10"¢ L 1 10 ø 8"ø- ' 10"ø 10"ø 350-E 10", 0"ø ' 2.2 260 D 260-D CHECKED BY: RVA 8xE UP TO 12x1 , - - . - x6 DBR 12"ø 12x12 1 FD3 FLOOR PLAN AREA A.3 - MECHANICAL -10"ø P A - 300-E P 8"ø ---- - ------ - - -- --- p 300-E P 300+-E 300-E M 1 FD3 M s' A.2 P PLAN FLOOR PLAN AREA A.3 - MECHANICAL NORTH ,fs- _ r_o- N '3 WALL RATING LEGEND - 042 042 042 - 3-HOUR FIRE WALL M-102 - - - - 2-HOUR FIRE BARRIER OPT MA#130238 - 042 042 042 042 - SMOKE PARTITION SOLUTIONS THROUGH LISTENING THIS DRAWING IS AN INSTRUMENT OF SERVICE. THE DRAWING AND THE INFORMATION THEREON IS THE PROPERTY OF OPTIMA ENGINEERING, P.A. ANY REPRODUCTION, ALTERATION, OR USE FOR OTHER THAN THE INTENDED PROJECT, WITHOUT THE WRITTEN CONSENT OF OPTIMA ENGINEERING, P.A. IS EXPRESSLY FORBIDDEN. COPYRIGHT ©OPTIMA ENGINEERING P.A. 2014, ALL RIGHTS RESERVED. 1 2 3 4 5 6 BID DOCUMENTS 260-D O At1U-.5. 50 C 2 Sa -B T W ø ---(3-- 1(x8 > 1C 75-6 ø 50 B 16x1 TRA D 5® 60 D CLOVER SCHOOL DISTRICT TWO CS B ÜNÉD ER CLOVER SCHOOL DISTRICT r mh cMd, rach Day... ExmHence "øj x8 6"ø E 260-D 10"ø 10"ø - 3 0"ø CLOVER REPLACEMENT MIDDLE SCHOOL 10"ø 250-D 2 0- 260eD __ 14×14 0 D 6.2 1Bx6, DROP BELOW BEA A x6 DOWN 2"ø 12×12 350-E 30x6 DO 6 60 D 042 .. 1 FD3 -- 63 - R A 30- BELOW BEAM 300 E M 0-E FD3 TO 042 ... _ .. M 3°°¯Q 400-E M (EXTEND 10"ø DUCT UP TO ROOF CAP) NQIEL CLOSELY COORDINATE EXACT GRILLE LOCATIONS WITH ARCHITECT AND OWNER AROUND OTHER DEVICES INSTALLED ON THESE ELEVATIONS = 00-E imo -eme 040 -- - = 1927 South Tryon St., Suite 300, Charlotte NC 28203 = D - - 3 x6 DOWN 30x6 DO N Phone: 704-338-1292 042 www.optimapa.com North Carolina License Number C-0914 4 0-E 30d-E 1C"ø 10- 2 5- P -- -- -- - 0"ø 40 -D P 4- 0- -E 275 LS P -- -- -- -- -- 2 54b 10"ø 2 1 = 0 === Ñ(96x1 ) 1 L 7 _ . 227 WEST TRADE STREET SUITE 700 CHARLOTTE, NORTH CAROLINA 28202 TEL. 704.333.6686 FAX 704.333.2926 WWW.LS3P.COM 4 0-$ a 4- 0- 3 3 0"ø 0 -E -b © 8 8 UP T P llHH 8 ø 12 !O 00 2 = 50 D P 2 -D Po o ERING No. C00710 T D ENG S E 00- 0 25 D 4c 0st11HII 10x 2 -- INS ABóVE 275 D o = 8 21 ÚLT 4c 0- ( ) MEMBERS OF THE AMERICAN INSTITUTE OF ARCHITECTS 4c 0-$ " T 250 D as - P 225 D P COPYRIGHT 2014 ALL RIGHTS RESERVED PRINTED OR ELECTRONIC DRAWINGS AND DOCUMENTATION MAY NOT BE REPRODUCED IN ANY FORM WITHOUT WRITTEN PERMISSION FROM LS3P ASSOCIATES LTD. 25- D 00 -D . 50 5 B REVISIONS: . B - 250-1 ST DUCT DOWN HER (SEE 14/M-402) T WALL CAP AND 3RYER VENT DOWN ) DRYER ON ROOF .8" 1 C O O _ 180-D O O (8 O = No. Description PROJECT: 9201-131360 DATE: OCT. 31, 2014 DRAWN BY: SRD Date Q h 6 DRYER VENT WALL CAP AND 4"ø RIGID DRYER VENT DOWN __ ___ H(18x12) H(18x12) CHECKED BY: RVA . a 40¾ D 375-G (32×4) 375-G (32×4) o 1 5-c 8- A2 a2 a2 A - A.2 A.1 PLAN NORTH FLOOR PLAN AREA B.1- MECHANICAL N ' - FLOOR PLAN AREA B.1 - MECHANICAL C.1 WALL RATING LEGEND 042 042 042 3-HOUR FIRE WALL - 042 -042 2-HOURFIRE BARRIER SOLUTIONS OPTuA#130238THROUGH LISTENING - 042 042 SMOKE PARTITION THIS DRAWING IS AN INSTRUMENT OF SERVICE. THE DRAWING AND THE INFORMATION THEREON IS THE PROPERTY OF OPTIMA ENGINEERING, P.A. ANY REPRODUCTION, ALTERATION, OR USE FOR OTHER THAN THE INTENDED PROJECT, WITHOUT THE WRITTEN CONSENT OF OPTIMA ENGINEERING, P.A. IS EXPRESSLY FORBIDDEN. COPYRIGHT ©OPTIMA ENGINEERING P.A. 2014, ALL RIGHTS RESERVED 1 2 3 4 5 6 BID DOCUMENTS CLOVER SCHOOL DISTRICT TWO PROVIDE OFFSETS TO ALIGN OR AMES C ASSROOM E STRUCTURAL MSH MMS ABN NSFERS) 60-E :·50-D 3 2540-E J 2540-E S0-D 350 -E 10"ø- 50-D E - 10"ø i 10"ø- - 250 ' D .50+D 250--D r mh cMd, rach Day... ExmHence 230-D N21 1 20xf4 2ex14 P P 260-D ' CLOVER REPLACEMENT MIDDLE SCHOOL 260-D - HUMlplST T (SEE SEQU NCE OF OF ERATION) NI H 3$0-E - 250+D Q_,._IN 350-E 10"ø 250-D 230-0 ,. 1 I $50eD 250+D -10"ø to*ø 12x12 JP TO 50-C 0"ø CLOVER SCHOOL DISTRICT 10 ø t0"Ø 50+D 260-D 10"ø- - -10" 10"ø 50*D 260-D 350- : h 50+D CS B CLASSROOM TRANSFERS) imo 260-D 50-C 7 -_3 --rrlIIIllTI J III I I||IIIII ,. -- - -10"ø 260+D 280¬0 290-E 260-D 29 290-E F .· 1927 South Tryon St., Suite 300, Charlotte NC 28203 Phone: 704-338-1292 042 www.optimapa.com North Carolina License Number C-0914 260-D -1 10"ø LS')P 290-1 50--D WO"ø .50 D P P æ 290- E 2£0-1 260-D 260-D 10 RESIST THE PASSAGE OF SMOKE. SEAL ALL PENETRATIONS OF THESE 10"ø 50-D E 250--D .- 10"ø ' P 260+D 260-D - 0"ø 10"ø 22x16 x 29 -E 6x16 L P TO - T-Mt. --2. t 1230 P 10" 20x1 ! 1230-P MOO-P 90-E )( SCIEN 41 SSROOM WALLS ARE SMOKE PARTITIONS, DESIGNED TO RESIST THE PASSAGE OF SMOKE. SEAL ALL PENETRATIONS OF THESE WALLS PER THE UL DETAILS SHOWN ON SHEET M 103 (TYPICAL) C - : 50-D ' '50-D __ 250-D P _ __ _..y._ .. 50+D s 250-D ' 250+D jyg r-Tr DI II -10"ø 100 C nl m 2 0 D 12xt2 LP TO AN F- 5 ON RQC 290 E 1 fø 2$0-D 11"# 260-D 260+D o" 290 E 042 260+D Q.U.-2. . 9.o. SCIENCE CLASSROOl SMOKE PARTITIONS, RESIST THE PASSAC SEAL ALL PENETRA WALLS PER THE UL ON SHEET M-403 ( rurrn 1 DO- r P 100+J TmmrfmTi '290-E 16x16 VP T) 10"ø 8"ø rrr- 90+E 20x12 450-J 1 x13 UP TO F N F-25 C4 ROOF ' ' 10" 2 x12 22x12 0"# 227 WEST TRADE STREET SUITE 700 CHARLOTTE, NORTH CAROLINA 28202 TEL. 704.333.6686 FAX 704.333.2926 WWW.LS3P.COM = OPTIMA \ ENGINEERING " No. C00710 260*D 10"ø 1500-P 16<16 UP TO 10 ø 50+D ' 290-E $50-D P 90-E 10"ø 290 E 10"ø io"ø- 042 RTSE "50+D e '50-D 290 0"ø 10- P 10"ø 260+D 260+-D 260-D 260-D 4D"ø p 10"ø 1230-P MEMBERS OF THE AMERICAN INSTITUTE OF ARCHITECTS 10 1730-P 290-E FT222 OPEl ATION) r -r# __ COPYRIGHT 2014 ALL RIGHTS RESERVED PRINTED OR ELECTRONIC DRAWINGS AND DOCUMENTATION MAY NOT BE REPRODUCED IN ANY FORM WITHOUT WRITTEN PERMISSION FROM LS3P ASSOCIATES LTD. P 10'ø TO O X 5.12 SIEE 1/M-302 10'ø 10 ø 50+D - $ 20>12 0"ø to"W 5-D "50rD 250*D TO 50-C 2 0- 260+D 260-D REVISIONS: _ 62x24- _)75 Li178=d 6"#- 300 L 65-C 2, 2 40-8 - -- 250-D N 1Bx1 1 1(x8 P 16x16 16xt ._ 14×14 1(X8 L -B 6"ø 50-B r16x16 LINED SFE 10 P ^ ÂS-B -- 2x 4 260-D 250-D ------ A - P 30x6 DOWN 104 30x6 DO 6.2 260 'D 260-D J 300 TL CHECKED BY: RVA A2 -..-300-E _ __ __ O 6t1U.r.7_- - K CLOSELY COORDINATE EXACT GRILLE LOCATIONS WITH ARCHITECT AND OWNER AROUND OTHER DEVICES INSTALLED ON THESE ELEVATIONS - r3Òx6 DOWN a2 $O0-E 0"ø DUCT UP TO ROOF CAP) A.2 A.1 B.1 / PLAN NORTH N '3 WALL RATING LEGEND - 042 042 042 3-HOUR FIRE WALL - - - - 2-HOUR FIRE BARRIER OPT MA # 13 0238 - 042 042 042 042 - THIS DRAWING IS AN INSTRUMENT OF SERVICE. THE DRAWING AND THE INFORMATION THEREON IS THE PROPERTY OF OPTIMA ENGINEERING, P.A. ANY REPRODUCTION, ALTERATION, OR USE FOR OTHER THAN THE INTENDED PROJECT, WITHOUT THE WRITTEN CONSENT OF OPTIMA ENGINEERING, P.A. IS EXPRESSLY FORBIDDEN. COPYRIGHT ©OPTIMA ENGINEERING P.A. 2014, ALL RIGHTS RESERVED. I C.1 30x6 DOWN- - 1/8" = 1'-0" 2 FLOOR PLAN AREA B.2 - MECHANICAL K FLOOR PLAN AREA B.2 - MECHANICAL 1 SRD -- -- 400+E 1 DRAWN BY: 10"ø 0-E -L____ __ - - 0- OCT. 31, 2014 ø W2 "ø 250-D 10'ø 300-L 0"ø - DATE: 260-D 10"ø 10"Ø 9201-131360 g= K 250-D PROJECT: - ... 50-E 10"ø 2545-0 1(x8-* 8x8 1 250-E 11 1&ø- 10"ø 4-· - Date · " 6"ø Description 042· K Ø 50-B No. 300-L 3 I 4 I 5 I e SMOKE PARTITION (NOT RATED) SOLUTIONS THROUGH LISTENING BID DOCUMENTS i"ø -6"ø 50-B 2 275 0 40-E --- - 6"ø- ... . 6 ø 25 -10x8 - .. -- 10x8-* E - CS B 50 B - 8x8 -tDx8 p 65-C g= 6 6' , -16x16 LI ED CLOVER SCHOOL DISTRICT " D 10"ø """3""'E 75- 16x16 5 -D 10 - 3 0-E tax8 P 260-D 300-L 22x 4 10"ø d P 260- [ 10 (109 250-D 2$0-D n 10"ø g"ø 250-0 10"ø . 50-D 2 [ 2 -*D 24x2 M M ___ 400-E 300- P 3p0-E -32"ø LI 5024 50x24 Il 5 11 1 TO At1U-1_1_ -D' 260 D 260 ·D 24x24 34×24 300 E 8x 0 P 34x24 ---. . 3OO-E 300-E 32"ø- ---- -- ljU W 11s 1 Il 5 11, 1 Il 5 11 CLOVER REPLACEMENT MIDDLE SCHOOL ,/ 24x24 1 F to" 65 .. F 10 350-E 150-0 12×12 10"ø 22x12 K 250 -D Cu-a 10"ø r mh cMd, rach Day... ExmHence 300-L K ç_u-_1 CLOVER SCHOOL DISTRICT TWO DROP [2 ,000-V imo TO Al1U-1.1 30" DEEP H ND GRILLE \RISE UP TIGHT TO BOTTOM -- 8"t __ 230 L 80- C 1927 South Tryon St., Suite 300, Charlotte NC 28203 A DE L S (33x9) EAROMETRK DAMPER 3x9) D - 9 (41x9) LD G SURE HEN BOTH GYM AIR G IR DAM 2 33x9) (41x9) [ 3> ) 1 P T3.1 B: l· IN i GRILL ( 2 0-L OU DE RJLL OPEN 725-A - " .- 8 )- 920-A 725-A LS')P #4 P 920- A 8"ø 2- "ø ·· -- SPlilAL DUCT TIGHT TO TRUSSES 5- A Phone: 704-338-1292 042 www.optimapa.com North Carolina License Number C-0914 ..o (1$x12) 125-H - s 5 A (10x 1 ø 227 WEST TRADE STREET SUITE 700 CHARLOTTE, NORTH CAROLINA 28202 TEL. 704.333.6686 FAX 704.333.2926 WWW.LS3P.COM . _ L 80+C 8 ø L lHil ....... = ENG ERING No. C00710 C - 7 25-A 725-A 920-A 920-A 725- 72 i- 4 _ 0×t JF TO Ey -11 EN ø N H M."OtlD WRE MNH t r 250-H 3(0-E 8"ø 250 400-H - =ar 7 A ) 725-A (33x9) 920-A (4Tx9) 20-A (41x9) 725-A (33x9) 7 - MEMBERS OF THE AMERICAN INSTITUTE OF ARCHITECTS 12"ø o COPYRIGHT 2014 ALL RIGHTS RESERVED PRINTED OR ELECTRONIC DRAWINGS AND DOCUMENTATION MAY NOT BE REPRODUCED IN ANY FORM WITHOUT WRITTEN PERMISSION FROM LS3P ASSOCIATES LTD. " OOSENE Y E A A R WTH MAN FACTURER'S INSTALLLATION INSTRUCTIONS = REVISIONS: n a 11 1 n a 11 1 n a 11 1 n a 11 ° M-1M 109- - - s -c 2e o _ B loo-C e"¢ 14 3---L L r 160-D * 160-D * M 8x - - - - - - - - - - - - - - -- -- -- - -c 230-D -- - --- - 280-D - 303-E P 280-D REE BETWEEN TRUSSES PROJECT: 9201-131360 DATE: OCT. 31, 2014 DRAWN BY: SRD Date 2so-o . 1 P 109 1sx14 Description 18x 2 (TTPICAL) 109 [ 280- ) No. = = 20×1e -,-THROUpH fRU)3SES- 280-D 280-D ÑO BLE WALL DAB ROSAFE SELF-SEALING DUCT SYSTEM (OR APPROVED NNER SHE L. E ISTERS N SPI O RECTANGULAR REGIS 280-D P - L 230-D 80-D ________ __. _____ ---------- -1--f__. -- ---A-" P HUMIDISTAT (SEE 28 D CHECKED BY: RVA 2 x14 R TAPS TOP ° uS TA" D .9u-CT DIMENSIONS ARE INSIDE CLEAR SIZES. A - U Fl N - 12" 1 "ø 20×16 FLOOR PLAN AREA C.1 - MECHANICAL v'dAR U N B OC( WALLS AT SPIRAL DUCT PENETRATIONS EM£-.4D.- 14"ø --- ------- A.1 B.1 WALL LOUVER FLOOR PLAN AREA C.1 - MECHANICAL PLAN 1/8- - r-e NORTH N ' WALL RATING LEGEND M-105 - 042 042 042 3-HOUR FIRE WALL - - - - 2-HOUR FIRE BARRIER OPT MA # 13 0238 - 042 042 042 042 - SMOKE PARTITION SOLUTIONS THROUGH LISTENING THIS DRAWING IS AN INSTRUMENT OF SERVICE. THE DRAWING AND THE INFORMATION THEREON IS THE PROPERTY OF OPTIMA ENGINEERING, P.A. ANY REPRODUCTION, ALTERATION, OR USE FOR OTHER THAN THE INTENDED PROJECT, WITHOUT THE WRITTEN CONSENT OF OPTIMA ENGINEERING, P.A. IS EXPRESSLY FORBIDDEN. COPYRIGHT ©OPTIMA ENGINEERING P.A. 2014, ALL RIGHTS RESERVED. | 1 2 3 4 5 6 BIDDOCUMENTS PROMDE TO ABOVE ALIGN TRANSFEROFFSETS OPENINGS DOOR FRAMES, SEE STRUCTURAL AWIN S ( CAL ALL PERIMITER o e CLOVER SCHOOL DISTRICT TWO - PROVIDE TO ABOVE ALIGN TRANSFEROFFSETS OPENINGS DOOR FRAMES, SEE STRUCTURAL DRAWINGS (TYPICAL ALL PERIMITER CLASSROOM TRANSFERS) o CS B CLOVER SCHOOL DISTRICT 50 D 350-E 260-D r mh cMd, rach Day... ExmHence 10"ø E - ___ ___ Ox1 ___ 0"Ë ___ P 604E 360- E 3 0- 20x14 10"ø P 10"ø CLOVER REPLACEMENT MIDDLE SCHOOL 19 AUMIDIS (SE SEQUENC : OF 0 ERATION - 10 ) W oo 6 = O 10 . 50 C imo 50 1927 South Tryon St., Suite 300, Charlotte NC 28203 Phone: 704-338-1292 042 www.optimapa.com North Carolina License Number C-0914 D - LS')P 290-E P . 0- E o = T 0 E 50 T"""T 250 D """ CCIENCE CLASSROOM WALLS ARE SP .. 22 6 4x14 N T . RESIST THE PASSAGE OF SMOKE. = = 50 .. 60 D 2 0-E === . SCIENCE CLASSROOM WALLS ARE SMOKE PARTITIONS, DESIGNED TO RESIST THE PASSAGE OF SMOKE. SEAL ALL PENETRATIONS OF THESE WALLS PER THE UL DETAILS SHOWN ON SHEET M 102 (TYPICAL) 260 D 2 2 P __C-------- WALLS PER THE UL DETAILS SHOWN ON SHEET M-403 (TYPICAL) 227 WEST TRADE STREET SUITE 700 CHARLOTTE, NORTH CAROLINA 28202 TEL. 704.333.6686 FAX 704.333.2926 WWW.LS3P.COM 22 -p-- T = 040 P -3.Q N ADOF 0- 60 D 6 . 9.o. D n m o n énn = O E " OPTIMA \ ENGINEERING % PA No. C00710 = = C 90- E O 0x12 0 = 0 0 E 90 E = --- = stslHII Ox1 = = 10" 6 1 6 - 7 MEMBERS OF THE AMERICAN INSTITUTE OF ARCHITECTS 10 1 ntRL_.9.. HUM DIS AT (SEE SEQUEWCE OF P ? ... 2 20 12 o p 2 x1 T X112 S É /M 30 = O COPYRIGHT 2014 ALL RIGHTS RESERVED PRINTED OR ELECTRONIC DRAWINGS AND DOCUMENTATION MAY NOT BE REPRODUCED IN ANY FORM WITHOUT WRITTEN PERMISSION FROM LS3P ASSOCIATES LTD. 1 """" -10 ø REVISIONS: _ B - 2s - 2sq-o 6 _ P P -B x = Description PROJECT: 9201-131360 DATE: OCT. 31, 2014 DRAWN BY: SRD Date 260-D 2x14 so o P 10"ø 230-4 No. 260- 10 ø 0"ø 350-E so o o so o so tr CHECKED BY: RVA -- 4×g P d4x2 x 300 E A - .. so" DEEP PLENUM P = 34x24 . RISE UP TIGHT TO BOTTOM OF TRUSSES (TYPICAL) BEHIND GRILLE (84x60) = 2 soo ---- A.3 B.2 A.1 B.1 FLOOR PLAN AREA C.2 - MECHANICAL 00-E --- C.1 230ÀL 8 PLAN NORTH __ FLOOR PLAN AREA C.2 - MECHANICAL N ' - WALL RATING LEGEND 042 042 042 3-HOUR FIRE WALL M-106 - 042 -042 2-HOURFIRE BARRIER SOLUTIONS OPTuA#130238THROUGH LISTENING - 042 042 SMOKE PARTITION THIS DRAWING IS AN INSTRUMENT OF SERVICE. THE DRAWING AND THE INFORMATION THEREON IS THE PROPERTY OF OPTIMA ENGINEERING, P.A. ANY REPRODUCTION, ALTERATION, OR USE FOR OTHER THAN THE INTENDED PROJECT, WITHOUT THE WRITTEN CONSENT OF OPTIMA ENGINEERING, P.A. IS EXPRESSLY FORBIDDEN. COPYRIGHT ©OPTIMA ENGINEERING P.A. 2014, ALL RIGHTS RESERVED 1 2 3 4 5 6 BID DOCUMENTS I I I I I CLOVERSCHOOL DISTRICT TWO mmmmm num mmmm DS nem num maamm DS CLOVER SCHOOL DISTRICT CLOVER REPLACEMENT AND 12x12 AND 42x12 AND 12x12 EXHHUSI EXHAUST EXHnUST --- DUG -BOWN----------- AND 1BR111 DS -DU 254T DOW DUCT DOWN DS D GiM --EXHAUST- ------------------------ DUCT DOWN AND 16xf6 EXHAUST EXHAUST DUCT DOVW DUCT DOWN ay-2 AND 48x96 F--y REUE7 DUCT DOWN- ,rf__3 EXHAU DUCT DOWN AND 16xth EXHAUST DUCT DOVN DUCI DOMT 2 EXHAUST DUCT DOWN AND 16x1h DUC ' BOWN -----------------------EXHAUST- DIICI¯DDV W¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯¯ - E EXHAUST EXNAttST DUCT DOW ------AND-16x16 -- 1927 South Tryon St., Suite 300, Charlotte NC 28203 DUCT DOWN --------AND t6 t6 EXHAUST MIDDLE SCHOOL AND 16x¼ ..XFíAüst -------------------------------------------------------------------------DUGT-DOWN-------------------DUCT DOWN -- IN-± AND 48x96 REUEE DUCT DDE Phone: 704-338-1292 042 www.optimapa.com North Carolina License Number C-0914 AND 16x1 EXRAUST EXHAUST DUCT DOVN DUCT DOWN Ry-E AND 48x96 F-- REUEF DUCT DOWN- I,r___a LS P MSFSM T]¾M 227 WEST TRADE STREET A ST DUCT DOWN r-7 Î<____J -BY-L AND 48x96 - REUEF BUGT DOWN RY. ·3 AND 48x96 E MA S --- -------- Q__3 - -HEUEF-OUGT-DOWN-- DUCT DO r-- -BY-.i AND 48x96 Q|$]Si SUITE 700 CHARLOTTE, NORTH CAROLINA 28202 REUEF DUCT DOWN TEL. 704.333.6686 FAX 704.333.2926 WWW.LS3P.COM EELE=3E-4 DS DS AND 8x8 EXHAUST DUCT DOWN DS -- E E L L - ¬-¬u, DS EXHAUST-DUCT-DOWN DS ..... _________ 0 \nlHil 1 7 DS MEMBERS OF THE AMERICAN INSTITUTE OF ARCHITECTS $4AN T=W---AND 12x12 EXHAUST --- DUGT-DOWN------------------- --- COPYRIGHT 2014 ALL RIGHTS RESERVED PRINTED OR ELECTRONIC DRAWINGS AND DOCUMENTATION MAY NOT BE REPRODUCED IN ANY FORM WITHOUT WRITTEN PERMISSION FROM LS3P ASSOCIATES LTD. By-11 AND 8x8 COMBUSTION AIR DUCT DOWN DS ------------------------------------------------ -------------- ----------------------------------- REVISIONS: DS B - e---rht_E-a AND 10x10 DISHWASHER EXHAUST DUCT DOWN EaN_E -2. AND 22x22 KITCHEN HOOD #AKE-UP AIR DUCT DOWN BOILER FLUE 254APS AND INTAKE GOOSENECKS EAN_E-1. AND 22<22 t ITCHEN HOOD EXHAUST DUCT DOWN _ DS ROOF HATCH- AND 10x10 EXHAUST DUCT DOWN PROJECT: 9201-131360 DATE· OCT 31 2014 Date DUCI¯DOW F-- RELIEF DU 254T DOWN By-.R AND 18xtB RELIEF DUCT DOWN Description GOOSENECK AND 8"ø COMMERCIAL DRYER VENT DOWN ND MxR EXHAUST 9·--- -EahLE-.a No. Ai4D 1Sx1B RELIEF IUCT DOWN CHECKED BY: RVA ROOF AND FIELD HOUSE PLANS- MECHANICAL ROOF PLAN - MECHANICAL 1/16" - 1'-0" - NORTH N ' - 042 042 042 3-HOUR FIRE WALL - - - - 2-HOUR FIRE BARRIER OPT MA # 13 0238 - 042 042 042 042 - SMOKE PARTITION SOLUTIONS THROUGH LISTENING THIS DRAWING IS AN INSTRUMENT OF SERVICE. THE DRAWING AND THE INFORMATION THEREON IS THE PROPERTY OF OPTIMA ENGINEERING, P.A. ANY REPRODUCTION, ALTERATION, OR USE FOR OTHER THAN THE INTENDED PROJECT, WITHOUT THE WRITTEN CONSENT OF OPTIMA ENGINEERING, P.A. IS EXPRESSLY FORBIDDEN. COPYRIGHT ©OPTIMA ENGINEERING P.A. 2014, ALL RIGHTS RESERVED 1 2 3 4 5 6 BID DOCUMENTS 1/ -2 C N CLOVER SCHOOL DISTRICT TWO R FRIGERANT P PING UP IN WALL T ) ABOVE 254ElUNG TIO DROP »IPtNG BELOW BE. CLOVER SCHOOL DISTRICT h cMd, rach Day... ExmHence PREMAt UFACTURED EXPANSION BE E , GU O ANL ANCHOI ED PER MFC. REC.--- -4" CLOVER C T ¯ DA MIDDLE SCHOOL F ENS D AN NTO L BOX (WALL BO) BY P.C., SEE 6/M- 402) l imo F 1927 South Tryon St., Suite 300, Charlotte NC 28203 Phone: 704-338-1292 042 www.optimapa.com North Carolina License Number C-0914 LS P 3.3 ENGME DESIGN TRAMMORM 227 WEST TRADE STREET SUITE 700 CHARLOTTE, NORTH CAROLINA 28202 TEL. 704.333.6686 FAX 704.333.2926 WWW.LS3P.COM --EM_E-3 ON ROOF No. C00710 E ON ROOF MEMBERS OF THE AMERICAN INSTITUTE OF ARCHITECTS == ==== PROVIDE THRUST BLOCKS AT ALL ANGES OF D EC N PER ENSULATED COPYRIGHT 2014 ALL RIGHTS RESERVED PRINTED OR ELECTRONIC DRAWINGS AND DOCUMENTATION MAY NOT BE REPRODUCED IN ANY FORM WITHOUT WRITTEN PERMISSION FROM LS3P ASSOCIATES LTD. CHILLED WATER PIPING BELOW RADE, MINIMUM (TYP1CAL) 6" REVISIONS: 11 o £lilkLEB_#1 6" NS O U U _ ARE S No. Description PROJECT: 9201-131360 DATE: OCT. 31, 2014 DRAWN BY: SRD Date -TO EM_E-2 ON1ROOF L__________ INSTALL CONTROLS/ UI N AME TRENCH WITH BURIED ßlflLLEB_#2 PIPING F ------ --- F t r 1. ALL PIPING ABOVE GRADE SHALL HAVE ELECTRIC HEAT Ä TAPE HALL B FURN HED WITH ERMOST T AND SHALL BE INSTALLED PROIR TO INSTALLING INSULATION. PIPE INSULATION SHALL BE COVERED WITH AN OUTER ALUMINUM JACKET SEALED WATERTIGHT. = CHECKED BY: RVA 1 D WA R Pl G TH GREASE WASTE AN ER UTILITIES IN THIS AREA. 3. CHILILERS SHALL BE MOUNTED ON A 4" THICK CONCRETE PAD. PAD$ SHALL BE PROVIDED AND INSTALLED BY THE GENERAL CONTRACTOR. MECHANICAL CONTRACTOR SHALL COORDINATE THE |EXACT SIZE AND LOCATION OF ALL PADS WITH THE GENERAL CONTRACTOR. A.3 | B.2 C.2 A - B.1 PLAN NORTH N FLOOR PLAN AREAS A.1 AND A.2 - MECHANICAL PIPING 1/8" = 1'-0" C.1 FLOOR PLAN AREA A.1 & A.2 - MECHANICAL PIPING W LL RATING LEGEND - 042 042 042 3-HOUR FIRE WALL - - - - 2-HOUR FIRE BARRIER OPT MA # 13 0238 - 042 042 042 042 - SMOKE PARTITION SOLUTIONS THROUGH LISTENING THIS DRAWING IS AN INSTRUMENT OF SERVICE. THE DRAWING AND THE INFORMATION THEREON IS THE PROPERTY OF OPTIMA ENGINEERING, P.A. ANY REPRODUCTION, ALTERATION, OR USE FOR OTHER THAN THE INTENDED PROJECT, WITHOUT THE WRITTEN CONSENT OF OPTIMA ENGINEERING, P.A. IS EXPRESSLY FORBIDDEN. COPYRIGHT ©OPTIMA ENGINEERING P.A. 2014, ALL RIGHTS RESERVED. 1 2 3 4 5 I e BID DOCUMENTS CLOVER SCHOOL DISTRICT TWO CS B CLOVER SCHOOL DISTRICT má cud. ach æv. . uæncnce FM £-2Q E -Cu-a in ANT > IN WALL - 254ElLING DI:OP PIPING BELOW BEA J PIPING TO MECHANICAL PLATFORM, SEE 2/M-207 FOR CONTINUATION PIPING UP IN WALL TO ABOVE CEILING -- 6" CLOVER REPLACEMENT MIDDLE SCHOOL 3"- F || 4" EM_E-M 23" DROP PIPING BEL W BEAM- - L PREMANUFACTURED EXP \NSION L)OP NIH F_EXIBLE TU111NG. L)OP TO BE SIZED, GUIDED, AND ANCHORED PER MFG. REC. o. - -REFRIGERANT PIPING ABOVE CEILING (INSTALLED PER MFG. RECOMMENDATIONS) PREMANUFACTURED EXPANSION LOOP NTH FLEXIBLE TUBING. LOOP TO BE SIZED, GUIDED, AND ANCHORED PER MFG. REC. imo 1927 South Tryon St., Suite 300, Charlotte NC 28203 Phone: 704-338-1292 042 www.optimapa.com North Carolina License Number C-0914 D - LS P -EXTEND ULL SIZE r DNDEN! ATE DRAIN DOWN IN WAl AND iPIL.. INTO WAl L BOX (WA L SOX BY P.C., SEE 6/M-402, TYP4CQ F 8. w-=-, 227 WEST TRADE STREET SUITE 700 CHARLOTTE, NORTH CAROLINA 28202 TEL. 704.333.6686 FAX 704.333.2926 WWW.LS3P.COM REFRIGERANT PIPING UP IN WALL TO ABOVE CEILING- -PREMANilFACTURED EXPANSION LOOP W H FLEX]BLE TUBING. LOOP TO BE SIZED, GUIDED, AND ANCHolRI D PER MFC. REC. A/-E 4 ..7.7 C - PRE.4A4UFACTUREO E PANSIO4 LOO;' NITH FLEXIB.E UBING. LOOi t O SE $1ZEh, G llDED, nND ÁNC JO 4ED FbER M -G. C. . 9.o. 4 = TEND FULL StZ ENG ERING No. C00710 LL A D ILL INTO WALL BOX (WALL BOX BY P.C, SEE 6/M-402) r yr y + r - - - 1] ELL 21 MEMBERS OF THE AMERICAN INSTITUTE OF ARCHITECTS 7. 2 COPYRIGHT 2014 ALL RIGHTS RESERVED PRINTED OR ELECTRONIC DRAWINGS AND DOCUMENTATION MAY NOT BE REPRODUCED IN ANY FORM WITHOUT WRITTEN PERMISSION FROM LS3P ASSOCIATES LTD. o --- REV S ONS: _ B - PROVIDE TERMINAL UNIT NTH 3-WAY HOT WATER CONTROL VALVE - - - No. Descr ption PROJECT: 9201-131360 DATE: OCT. 31, 2014 DRAWN BY: SRD Date F 7.13 - -@PROVIDE TERMINAL UNIT NTH 3-WAY HOT WATER CONTROL VALVE -C c CHECKED BY: RVA Aa a2 a2 A - A1 PLAN NORTH N FLOOR PLAN AREA B.1 - MECHANICAL PIPING 1/8" = 1'-0" 1 1 C.1 WALL RATING LEGEND - 042 042 042 3-HOUR FIRE WALL - - - - 2-HOUR FIRE BARRIER OPT MA # 13 0238 - 042 042 042 042 - THIS DRAWING IS AN INSTRUMENT OF SERVICE. THE DRAWING AND THE INFORMATION THEREON IS THE PROPERTY OF OPTIMA ENGINEERING, P.A. ANY REPRODUCTION, ALTERATION, OR USE FOR OTHER THAN THE INTENDED PROJECT, WITHOUT THE WRITTEN CONSENT OF OPTIMA ENGINEERING, P.A. IS EXPRESSLY FORBIDDEN. COPYRIGHT ©OPTIMA ENGINEERING P.A. 2014, ALL RIGHTS RESERVED. 2 I 3 I 4 I 5 I FLOOR PLAN AREA B.1 - MECHANICAL e SMOKE PARTITION (NOT RATED) SOLUTIONS THROUGH LISTENING BID DOCUMENTS CLO DISTRICT TWO CS B CLOVER SCHOOL DISTRICT r mh cMd, rach Day... ExmHence E - @PRO DE TERMlN\L UNIT P042 OVlbE IERHlNAL LINlT WITH 3-WAY HOf WA R CONTROL VALVE WITH 3-WAY HOT W TER CONTf OL VALVE CLOVER REPLACEMENT MIDDLE SCHOOL EA&M imo r1" 1927 South Tryon St., Suite 300, Charlotte NC 28203 |||||1111111111 111 111 11|| | || 111111 ||11 111 111 111 ||||||||||11111 111 11 ||| Phone: 704-338-1292 042 www.optimapa.com North Carolina License Number C-0914 I||| D - $CIENCE C SSR00M AL.S SMOKE PA TITION$, D SICN RESIST PASSAGE F LS P E TO E. LLS k T t D TAitS ON SHEET -403 ( ICi,L 227 WEST TRADE STREET SUITE 700 CHARLOTTE, NORTH CAROLINA 28202 TEL. 704.333.6686 FAX 704.333.2926 WWW.LS3P.COM O E) TEN Fl .L SIZE 254ONDENSA fE DE AIN IN WiLA. AND SFILL IN f0 WALL BOX (PALL BOX Bf P.1, E /M-4C2) EMAN F TU ) NS N LOOP WITM MBLE T J LOOP TO B SIZED, GLIDED, AND ANCHORED MFG. f EC. m m -f . 9.^. -+-PF EMANUFAC RED EXPA1SIÓN LCOP WITH FLEXIBLE TUBNG. LCOP TO BE D, CUID :D, AND Al' CHOREO R MFG. RE( . 1 I m = L ENG ERING No. C00710 REFR C WALL ElLING RANT PlPRIG ABOVE COMM NDA O REFRIGERANT PIPING UP IN WALL TO ABOVE CEILING ) FI I SCIENCE CLASSROOM UALLS ARE SMQKE PARTITIONS, DESIGNED TO RE$lST PASSAGE JF SMOKE. SEAL /LL ENETRATIONS OF THEEE PER THE UL Di TAILS SHO N O : ET -403 (TYl AL) . e FI + MEMBERS OF THE AMERICAN INSTITUTE OF ARCHITECTS 1 COPYRIGHT 2014 ALL RIGHTS RESERVED PRINTED OR ELECTRONIC DRAWINGS AND DOCUMENTATION MAY NOT BE REPRODUCED IN ANY FORM WITHOUT WRITTEN PERMISSION FROM LS3P ASSOCIATES LTD. r | ||| ||| ||| ||| |||| |||||||||||||||| ||| ||| |||||||| || ||| || F | REVISIONS: _ No. Description PROJECT: 9201-131360 DATE: OCT. 31, 2014 DRAWN BY: SRD Date CHECKED BY: RVA E RIGERANT .L . . PIPING TO MECHANICAL PLATFORM, SEE 2/M-207 FOR CONTINUATION . A2 DI OP PIPING BELOW BEA L J a2 F l llWC O A.1 DROP PIPING BEL W BEAM- - L OP TO BE SIZED, GUI ED, AND CHORED P R MFG. R . REFRIGERANT PIPING ABOVE CEILING (IN_STALLED PER MFG. PREMANUFACTURE EXPANSIO I DOP WITH FI FYlR F TilRING FLOOR PLAN AREA B.2 - MECHANICAL PIPING 1/8" = 1'-0" PLAN NORTH N B.1 2 3 - 4 5 C.1 WALL RATING LEGEND - 042 042 042 3-HOUR FIRE WALL - - - - 2-HOUR FIRE BARRIER OPT MA # 13 0238 042 042 042 042 - THIS DRAWING IS AN INSTRUMENT OF SERVICE. THE DRAWING AND THE INFORMATION THEREON IS THE PROPERTY OF OPTIMA ENGINEERING, P.A. ANY REPRODUCTION, ALTERATION, OR USE FOR OTHER THAN THE INTENDED PROJECT, WITHOUT THE WRITTEN CONSENT OF OPTIMA ENGINEERING, P.A. IS EXPRESSLY FORBIDDEN. COPYRIGHT ©OPTIMA ENGINEERING P.A. 2014, ALL RIGHTS RESERVED. 1 FLOOR PLAN AREA B.2 - MECHANICAL e SMOKE PARTITION (NOT RATED) SOLUTIONS THROUGH LISTENING BID DOCUMENTS CLOVER SCHOOL DISTRICT TWO CS B CLOVER SCHOOL DISTRICT r ch cMci, rach Day... ExmHence E - - n F L 1 L CLOVER REPLACEMENT MIDDLE SCHOOL n DROP PIPING BEt0W BEAM || 3 llE CllS llW P PIPING BEL W BEAM- PREMANUFACTURED EXPANSION C U G NSTA D P R MFG. RECOMMENDATIONS) PREMANUFACTURE EXPANSION LOOP WITH FLEXIB TUBING. LOOP TO BE SIZE , GUIDED, AND ANCHORED PER M G. REC. O BE S ZED G D D ANt Ill 11 111 II) I 11 111 II) I 11 111 II)ll 11 111 II)ll imo I 1927 South Tryon St., Suite 300, Charlotte NC 28203 1 Q IL JLIJüJJ R IL J1JJüJJ R IL JLIJüJ1 Phone: 704-338-1292 042 www.optimapa.com North Carolina License Number C-0914 D - LS P EXTEND iULL S12E ( ONDEN'ATE DRAIN DoWN IN WAL AND ,PIL. B.3 227 WEST TRADE STREET SUITE 700 CHARLOTTE, NORTH CAROLINA 28202 TEL. 704.333.6686 FAX 704.333.2926 WWW.LS3P.COM OJP TO 31 ".12ED, CJDID, AND , f T T 10/31M MEMBERS OF THE AMERICAN INSTITUTE OF ARCHITECTS COPYRIGHT 2014 ALL RIGHTS RESERVED PRINTED OR ELECTRONIC DRAWINGS AND DOCUMENTATION MAY NOT BE REPRODUCED IN ANY FORM WITHOUT WRITTEN PERMISSION FROM LS3P ASSOCIATES LTD. TMTL R K TMTL R K TMTL R K TMTt DR N DOWN IN WAl L AND SP L P.C EE 6 -402 REVISIONS: 11 ]Il Ú 1 Il ]Il Ú 1 11 ]Il Ú11 11 ] _ B - â/..b7_ No. Description PROJECT: 9201-131360 DATE: OCT. 31, 2014 DRAWN BY: SRD Date 1" WATE 4 V 041LVE CHECKED BY: RVA A.3 a2 A.1 B.1 a2 A - A.2 PLAN NORTH N FLOOR PLAN AREA C.1 - MECHANICAL PIPING 1/8" = 1'-0" WALL RATING LEGEND - 042 042 042 3-HOUR FIRE WALL - - - - 2-HOUR FIRE BARRIER OPT MA # 13 0238 - 042 042 042 042 - PROPERTY OF OPTIMA ENGINEERING, P.A. ANY REPRODUCTION, ALTERATION, OR USE FOR OTHER THAN THE INTENDED PROJECT, WITHOUT THE WRITTEN CONSENT OF OPTIMA ENGINEERING, P.A. IS EXPRESSLY FORBIDDEN. COPYRIGHT ©OPTIMA ENGINEERING P.A. 2014, ALL RIGHTS RESERVED. 1 I 1 2 3 4 5 FLOOR PLAN AREA C.1 - MECHANICAL 6 SMOKE PARTITION (NOT RATED) SOLUTIONS THROUGH LISTENING BID DOCUMENTS CLOVER SCHOOL DISTRICT TWO CS B CLOVER SCHOOL DISTRICT r mh cMd, rach Day... ExmHence E - WATER VA .VE WATER CONTROL VALVE CLOVER REPLACEMENT MIDDLE SCHOOL -EAU_E- - ERENTIAL PREESURE imo 1927 South Tryon St., Suite 300, Charlotte NC 28203 Phone: 704-338-1292 042 www.optimapa.com North Carolina License Number C-0914 D - M E P Tl LS P 4 11BES N D EA AL TR T10N 01 ESE AL S PER THE L DETAlt. SHOWN oN HEET M-4C5 (TYP , y- --- u unmmrr 1 rrr m PR: MANUFACTUREb EX A SION SU JL rrr mrrrrrrnm ____£_ R D V E P JulMluuJl I IU ALL ) UI UL 111 MJJEURE SP L 227 WEST TRADE STREET SUITE 700 CHARLOTTE, NORTH CAROLINA 28202 TEL. 704.333.6686 FAX 704.333.2926 WWW.LS3P.COM IMll T F ---PREMA UFACTUREE EXPANSIO BE Z D ND ....... 0 BE I ED GUIDE , AND AN :HORED PEi: MFG. REC. REFRIGERANT PIPING UP IN WALL TO ABOVE CEILING 1" - TA D P RECOMMENDATIONS) . M G. REFRIGERANT N OU N W = ENG ERING No. C00710 C SCI NCE CLASf ROOM WALLS ARE 1- r P O SE/L ALL PENI TRATIONS F THESE WAli-S PER TH : UL DETA1 S SHOWN ON -fA --E-2R stslHII EE #- 03 (TYPtC ) 1 MEMBERS OF THE AMERICAN INSTITUTE OF ARCHITECTS m u un unuinuun unu u ui unuuulu li uinnuu u tu u COPYRIGHT 2014 ALL RIGHTS RESERVED PRINTED OR ELECTRONIC DRAWINGS AND DOCUMENTATION MAY NOT BE REPRODUCED IN ANY FORM WITHOUT WRITTEN PERMISSION FROM LS3P ASSOCIATES LTD. unun REVISIONS: _ B - No. Description PROJECT: 9201-131360 DATE: OCT. 31, 2014 DRAWN BY: SRD Date t0.2 CHECKED BY: RVA G UP N WALL ABOVE CEit1NC - o ON T 2" DROP PIPtNG BELOW BEAM A2 a2 A - L C L G NSTA L D P R MFG. RECOMMENDATIONS) PREMANUFACTURED EXPANSION LOOP WITH FLEXIBLE TUBING. LOOP TO BE S ZED GUIDED, ANI PREMANUFACTURE EXPANSION P BE S ,E NG. A.1 : ' B.1 FLOOR PLAN AREA C.2 - MECHANICAL C.1 ANCHORED PER M G. REC. PLAN NORTH N FLOOR PLAN AREA C.2 - MECHANICAL PIPING 1/8" = 1'-0" 1 I WALL RATING LEGEND - 042 042 042 3-HOUR FIRE WALL - - - - 2-HOUR FIRE BARRIER OPT MA # 13 0238 - 042 042 042 042 - THIS DRAWING IS AN INSTRUMENT OF SERVICE. THE DRAWING AND THE INFORMATION THEREON IS THE PROPERTY OF OPTIMA ENGINEERING, P.A. ANY REPRODUCTION, ALTERATION, OR USE FOR OTHER THAN THE INTENDED PROJECT, WITHOUT THE WRITTEN CONSENT OF OPTIMA ENGINEERING, P.A. IS EXPRESSLY FORBIDDEN. COPYRIGHT ©OPTIMA ENGINEERING P.A. 2014, ALL RIGHTS RESERVED. 2 1 3 I 4 I 5 I e SMOKE PARTITION (NOT RATED) SOLUTIONS THROUGH LISTENING BID DOCUMENTS CLOVER SCHOOL DISTRICT TWO CS B CLOVER SCHOOL DISTRICT r mh cMd, rach Day... ExmHence E - - CLOVER REPLACEMENT MIDDLE SCHOOL imo 1927 South Tryon St., Suite 300, Charlotte NC 28203 Phone: 704-338-1292 042 www.optimapa.com North Carolina License Number C-0914 H0XSL 1. SPILL FULL SIZE CONDENSATE DRAIN FROM EACH AIR HANDLING UNIT OVER NEAREST FLOOR DRAIN (FLOOR DRAINS BY PLUMBING CONTRACTOR). 2. ALL FLOOR MOUNTED EQUIPMENT IN MECHANICAL ROOM SHALL BE MOUNTED ON A 4" THICK CONCRETE PAD. PADS SHALL BE PROVIDED AND INSTALLED BY THE GENERAL CONTRACTOR. MECHANICAL CONTRACTOR SHALL COORDINATE THE EXACT SIZE AND LOCATION OF ALL PADS NTH THE GENERAL CONTRACTOR. 3. MECHANICAL CONTRACTOR SHALL COORDINATE EXACT LOCATION OF FLOOR DRAINS NTH PLUMBING CONTRACTOR PRIOR TO INSTALLATION OF FLOOR DRAINS. INACCESSIBLE FLOOR DRAINS OR DRAINS LOCATED UNDER EQUIPMENT ARE NOT ACCEPTABLE. 1. SPILL FULL SIZE CONDENSATE DRAIN FROM EACH AIR HANDLING UNIT OVER NEAREST FLOOR DRAIN (FLOOR DRAINS BY PLUMBING CONTRACTOR). 2. ALL FLOOR MOUNTED EQUIPMENT IN MECHANICAL ROOM SHALL BE MOUNTED ON A 4" THICK CONCRETE PAD. PADS SHALL BE PROVIDED AND INSTALLED BY THE GENERAL CONTRACTOR. MECHANICAL CONTRACTOR SHALL COORDINATE THE EXACT SIZE AND LOCATION OF ALL PADS NTH THE GENERAL CONTRACTOR. 3. MECHANICAL CONTRACTOR SHALL COORDINATE EXACT LOCATION OF FLOOR DRAINS NTH PLUMBING CONTRACTOR PRIOR TO INSTALLATION OF FLOOR DRAINS. INACCESSIBLE FLOOR DRAINS OR DRAINS LOCATED UNDER EQUIPMENT ARE NOT ACCEPTABLE. DIRECT VENT WATER HEATER (BY P.C.) DIRECT VENT WATER HEATER (BY P C ) -- 1. SPILL FULL SIZE CONDENSATE DRAIN FROM EACH AIR HANDLING UNIT OVER NEAREST FLOOR DRAIN (FLOOR DRAINS BY PLUMBING CONTRACTOR). 2. ALL FLOOR MOUNTED EQUIPMENT IN MECHANICAL ROOM SHALL BE MOUNTED ON A 4" THICK CONCRETE PAD. PADS SHALL BE PROVIDED AND INSTALLED BY THE GENERAL CONTRACTOR. MECHANICAL CONTRACTOR SHALL COORDINATE THE EXACT SIZE AND LOCATION OF ALL PADS NTH THE GENERAL CONTRACTOR. 3. MECHANICAL CONTRACTOR SHALL COORDINATE EXACT LOCATION OF FLOOR DRAINS NTH PLUMBING CONTRACTOR PRIOR TO INSTALLATION OF FLOOR DRAINS. INACCESSIBLE FLOOR DRAINS OR DRAINS LOCATED UNDER EQUIPMENT ARE NOT ACCEPTABLE. At1U-2 LS')P DIRECT VENT WATER HEATER (BY P.C.) BOX 5...11 227 WEST TRADE STREET SUITE 700 CHARLOTTE, NORTH CAROLINA 28202 TEL. 704.333.6686 FAX 704.333.2926 WWW.LS3P.COM BOX 9.11 1UUU ---i - - - I I 1 i . . I I . 9.o. I . . T = " OPTIMA \ ENGINEERING No. C00710 I I MU-A 3- - I _V-2" __J 5"y -- C - - 6" SEE 1 -201 FOR CONTINUATION _n 4. ' ' ' ' N SEE 1/M-203 FOR CONTINUATION L_.__U_JI | 3 mu-12 PROVIDE Al HANDLlt'G UNIT WITH 3-WA HOT AFD CHILLED WATER CONTROl, VAl VES HE 042 ' ~ SEE 1/M-203 FOR ' ' ' ' CONTINUATION - MECH PLATFORM A - MECHANICAL PIPING MECH PLATFORM B - MECHANICAL PIPING 1/8" = 1'-0= 1/8" = 1'-O" DIFFERENTIAL PRESSURE SENSOR FOR CHILLED WATER PUMP CONTROL ",7 - -- my-_t 541 DP r -2" 1 .. MEMBERS OF THE AMERICAN INSTITUTE OF ARCHITECTS , , , ' SEE 1/M-205 FOR CONTINUATION COPYRIGHT 2014 ALL RIGHTS RESERVED PRINTED OR ELECTRONIC DRAWINGS AND DOCUMENTATION MAY NOT BE REPRODUCED IN ANY FORM WITHOUT WRITTEN PERMISSION FROM LS3P ASSOCIATES LTD. MECH PLATFORM C - MECHANICAL PIPING REVISIONS: B - - No. Description Date PROJECT: 9201-131360 DATE: OCT. 31, 2014 DRAWN BY: SRD CHECKED BY: RVA A.2 PLAN NORTH N A2 a2 a2 A.1 B.1 C.1 MECHANICAL PLATFORM - PLANS MECHANICAL PIPING WALL RATING LEGEND EWH " - 042 042 042 3-HOUR FIRE WALL - - - - 2-HOUR FIRE BARRIER OPT MA # 13 0238 - 042 042 042 042 - SMOKE PARTITION V I SOLUTIONS THROUGH LISTENING THIS DRAWING IS AN INSTRUMENT OF SERVICE. THE DRAWING AND THE INFORMATION THEREON IS THE PROPERTY OF OPTIMA ENGINEERING, P.A. ANY REPRODUCTION, ALTERATION, OR USE FOR OTHER THAN THE INTENDED PROJECT, WITHOUT THE WRITTEN CONSENT OF OPTIMA ENGINEERING, P.A. IS EXPRESSLY FORBIDDEN. COPYRIGHT ©OPTIMA ENGINEERING P.A. 2014, ALL RIGHTS RESERVED. 1 2 3 4 5 6 BID DOCUMENTS SCIENCE CLASSROOM WALLS ARE SMOKE PARTITIONS, DESIGNED TO RESIST THE PASSAGE OF SMOKE. SEAL ALL PENETRATIONS OF THESE WALLS PER THE UL DETAILS SHOWN ON SHEET M-403 (TYPICAL) CLOVER SCHOOL DISTRICT TWO FULL SIZE RETURN DUCT DOWN TO AHU CS B FULL SIZE RELIEF DUCT DOWN TO AHU RETURN 2FULLJIZE pA DOCT DOWN TO AMU __ FLEX CONN. 1 12 CLOVER SCHOOL DISTRICT r mh cMd, rach Day._. ExmHence 8'-O"x2'-6" INTAKE LOUVER (BY GEN. CONTR.) x E - FU..L 8'-O"x2'-6" INTAKE LOUVER (BY GEN. CONTR.) L E RELIEF DUCT DOWN TO ANU-- - - - - '-- - --- - --- - - (BY PLBG CONTR.) ____ __ CLOVER REPLACEMENT MIDDLE SCHOOL 62x24 __-36x3 .. __ _____________ 44×24 62x24 RETURN l 52x24 RETURN REGEF l RETURN __ ______ _ 44x24 . _ ...___ ___ __..-1 - '-------___ 44x24 48x96 UP TO RY-2 ON ROOF -8'-O"x2'-6" INTAKE LOUVER (BY GEN. CONTR.) 60x24 DOWN -FULL SIZE 8'-O"x2'-6" INTAKE LOUVER FLEX CONN. 40x24 SUPPLY BELOW REOT RNIOD CHU FULL SIZE OA OUCT DOWN TO AHU 1500-H {30x18) [ [ 44x24 OUTSIDE AIR ABOVE 60x24 FULL SIZE RETURN DUCT DOWN TO AHU - D - imo FULL SIZE 8'-O"x2'-6" INTAKE LOUVER (BY GEN. CONTR.) ¾-----. 1927 South Tryon St., Suite 300, Charlotte NC 28203 Phone: 704-338-1292 042 www.optimapa.com North Carolina License Number C-0914 = ======= = - - - - "WC,,- - ay-t ON ROOF a-8'-O"x2'-6" INTAKE LOUVER (BY GEN. CONTR.) ---- --R -- -- -- -- - --- . _________ .__ __ __ .__ . --4 FLEX CONN.______ 2 EULL SIZE RELIEF DUCT DOWN TO AHU - 40x20 =-8'-O"x2'-6" INTAKE LOUVER (BY GEN. CONTR.) - ----------- 36x28 FLEX CONN. ELECTRICAL PANELS AND EQUIPMENT (BY ELECTRICAL CONTRACTOR). MAINTAIN A MINIMUM OF 6' CLEARANCE BETWEEN TOP OF PANELS AND BOTTOM OF DUCTWORK 36x30 8'-O"x2'-6" INTAKE LOUVER (BY GEN. CONTR.) -----------L- LS')P ___________ 48x96 UP TO --------- 227 WEST TRADE STREET SUITE 700 CHARLOTTE, NORTH CAROLINA 28202 TEL. 704.333.6686 FAX 704.333.2926 WWW.LS3P.COM -- . 111111# 52x24 60x24 !__ __ __. 2 = OPTIMA \ ENGINEERING % " = PA No. C00710 C - A WING MECH PLATFORM - MECHANICAL 1/8" = 1'-O" 111111## . 221 RELIEF VENT ROOF CURB MEMBERS OF THE AMERICAN INSTITUTE OF ARCHITECTS COPYRIGHT 2014 ALL RIGHTS RESERVED PRINTED OR ELECTRONIC DRAWINGS AND DOCUMENTATION MAY NOT BE REPRODUCED IN ANY FORM WITHOUT WRITTEN PERMISSION FROM LS3P ASSOCIATES LTD. _L 5 , 2'-6"x8'-0" INTAKE LOUVER (BY GEN. CONTR.) - -I-- \ 28x36 24x60 1 B - / | I REVISIONS: -2'-6"x8'-0" INTAKE (BY GEN.LOUVER CONTR.) _ No. Description Date 24x44 96x48 60x24 52x24 FULL SIZE OA DUCT FULL SIZE RELIEF DUCT FULL SIZE RETURN DUCT- FLEX CONN. (TYPICAL) RETURN DUCT 24x6d20x40 ___________________________________________________________________________________________J______________________________________________________________________________________________________________________________________________________________________________________ _____________________________________________________________________________________________________________________________ PRoJECT: 9201-131360 DRAWN BY: SRD CHECKED BY: RVA A.3 B.2 C.2 A.1 B.1 C.1 A A.2 ® A WING MECH PLATFORM SECTION p ¹/8" - ¹'-°~ NORTH N eeeNo ENLARGED MECHANICAL - PLATFORM PLANS M 401 - 042 042 042 3-HOUR FIRE WALL - - - - 2-HOUR FIRE BARRIER OPT MA # 13 0238 - 042 042 042 042 - SMOKE PARTITION SOLUTIONS THROUGH LISTENING THIS DRAWING IS AN INSTRUMENT OF SERVICE. THE DRAWING AND THE INFORMATION THEREON IS THE PROPERTY OF OPTIMA ENGINEERING, P.A. ANY REPRODUCTION, ALTERATION, OR USE FOR OTHER THAN THE INTENDED PROJECT, WITHOUT THE WRITTEN CONSENT OF OPTIMA ENGINEERING, P.A. IS EXPRESSLY FORBIDDEN. COPYRIGHT ©OPTIMA ENGINEERING P.A. 2014, ALL RIGHTS RESERVED 1 2 3 4 5 6 BID DOCUMENTS CLOVER SCHOOL DISTRICT TWO SCIENCE CLASSROOM WALLS ARE SMOKE PARTITIONS, DESIGNED TO RESIST THE PASSAGE OF SMOKE. SEAL ALL PENETRATIONS OF THESE WALLS PER THE UL DETAILS SHOWN ON SHEET M-403 (TYPICAL) CS B FULL SIZE RETURN DUCT DOWN TO AHU FULL SIZE RELIEF DUCT UP TO LOUVERED PENTHOUSE CLOVER SCHOOL DISTRICT r mh cMd, rach Day... ExmHence 40x16 RETURN E - 5.12 . ---- , ------------------ FU FULL fZE OA DUCT DOWN TO AHU / I FLEX CONN. I 8'-0"x2'-6" INTAKE LOUVER (BY GEN. CONTR.) 44x24 I ° DIRECT VENT SIZE RI LIEF DUCT DOWN TO AI-1U- 8'-0"x2'-6" INTAKE LOUVER (BY GEN. CONTR.) WATER HEATER (BY PLBG. CONTR.) CLOVER REPLACEMENT MIDDLE SCHOOL 62x24 - RETURN 44x24 32x24 RETURN 11 A / / t s L_ ___.. ______ _ 48xà6u TO t --+ 44x24 44x24 - - _--- ----- --- - -------.., 8'-0"x2'-6" INTAKE LOUVER (BY GEN. CONTR.) 52x24 RETURN a FLEX CONN. 40x24 SUPPLY BELOW n i n -FULL SIZE O FULL SIZE OA DUCT DOWN TO AHU TO U 1927 South Tryon St., Suite 300, Charlotte NC 28203 1500-H (30x18) D FULL SIZE RELIEF DUCT DOWN TO AHU 2 -302 8'-0"x2'-6" INTAKE LOUVER (BY GEN. CONTR.) - I =-hBLANK 0 AND INSULATE REAR OF l NUSED LOUVER T BLANK OFF AND INSULÃlE REAR OF UNUSED |LOUVER L___ ____ ___ __J - --- 24x30 «--8'-0"x2'-6" INTAKE LOUVER (BY GEN. CONTR.) -FLEX CONN. 36x22 8'-O"x2'-6" INTAKE LOUVER (BY GEN. CONTR.) 8'-0"x2'-6" INTAKE LOUVER (BY GEN. CONTR.) ---d----- | 1 ..L-----L. LS P 2 FULL ;SIZE OA DUCT DOWN TO AHU FULL SIZE RETURN DUCT DOWN TO AHU 48x96 UP TO By-3 ON ROOF Phone: 704-338-1292 042 www.optimapa.com North Carolina License Number C-0914 ELECTRICAL PANELS AND EQUIPMENT (BY ELECTRICAL CONTRACTOR). MAINTAIN A MINIMUM OF 6' CLEARANCE BETWEEN TOP OF PANELS AND BOTTOM OF DUCTWORK 44x24 OUTSIDE AIR ABOVE I imo «--8'-0"x2'-6" INTAKE LOUVER (BY GEN. CONTR.) 227 WEST TRADE STREET SUITE 700 CHARLOTTE, NORTH CAROLINA 28202 TEL. 704.333.6686 FAX 704.333.2926 WWW.LS3P.COM | i FLEX CONN. -- . -- 44x18 50x22 N - itHH# CA OPTIMA \ ENGINEERING No. C00710 - FULL SIZE OA DUCT DOWN TO AHU FULL SIZE RELIEF DUCT DOWN TO AHU - nng B WING MECH PLATFORM - MECHANICAL 1/8" = 1'-O- 21 7 RELIEF VENT IHHil 10/31M MEMBERS OF THE AMERICAN INSTITUTE OF ARCHITECTS ROOF CURB COPYRIGHT 2014 ALL RIGHTS RESERVED PRINTED OR ELECTRONIC DRAWINGS AND DOCUMENTATION MAY NOT BE REPRODUCED IN ANY FORM WITHOUT WRITTEN PERMISSION FROM LS3P ASSOCIATES LTD. 2'-6"x8'-O" INTAKE LOUVER (BY GEN. CONTR.) - B - 96x48 F---1 |24x44 REVISIONS: _ I No. Description PROJECT: 9201-131360 DATE: OCT. 31, 2014 DRAWN BY: SRD Date ~2'-6"x8'-0" INTAKE LOUVER (BY GEN. CONTR.) 24x44 36x36- N 4-36x36 30x30 FLEX CONN. (TYPICAL) FULL SIZE RELIEF DUCT FULL SIZE OA DUCT 24x60 24x52 FLEX CONN. 24x40 FLEX CONN. ____L___L___ CHECKED BY: RVA A.3 B.2 C.2 A.1 B.1 C.1 PLAN O B WING MECH PLATFORM SECTION NORTH 2 ,,8- - ,-_O- N WALL RATING LEGEND - 042 042 042 - 3-HOUR FIRE WALL - SMOKE PARTITION ENLARGED MECHANICAL - PLATFORM E W H "U V - - - - 2-HOUR FIRE BARRIER OPT MA#130238 042 042 042 042 - SOLUTIONS THROUGH LISTENING THIS DRAWING IS AN INSTRUMENT OF SERVICE. THE DRAWING AND THE INFORMATION THEREON IS THE PROPERTY OF OPTIMA ENGINEERING, P.A. ANY REPRODUCTION, ALTERATION, OR USE FOR OTHER THAN THE INTENDED PROJECT, WITHOUT THE WRITTEN CONSENT OF OPTIMA ENGINEERING, P.A. IS EXPRESSLY FORBIDDEN. COPYRIGHT ©OPTIMA ENGINEERING P.A. 2014, ALL RIGHTS RESERVED 1 2 3 4 5 6 BID DOCUMENTS