P-1 Type Fire Alarm Control Panel : RPP-ABW

advertisement
P-1 Type Fire Alarm Control Panel : RPP-ABW
Features
1. Multi purpose zone configuration
- Versatile zone configuration to suit various alarm need. (Zone 1 is preset and fixed for fire alarm
only)
2. Light weight and compact in size
- 450mm(W) X 650mm(H) X 100mm(D), Approximately 13Kg
3. Easy installation
- By means of ‘Wire Insertion’ terminals
- Wide internal cabinet space of easy wiring
- 180 degree wide panel door opening
4. Improved local bell control with programmable ‘silence’ timer
- If the local bell is put on ‘silence’ mode after an initial alarm signal, any subsequent zone
activation immediately re-triggers the local alarm. And should the system be left at ‘silence’
mode without subsequent zone activation, the local alarm will automatically trigger again after
a custom preset time period from the first alarm activation.
- The custom preset timer can be programmed to reactivate the local alarm after 2,4,6 or 8
minutes from the first alarm activation.
5. New functions
- Improved lightning surge protection
- Easy configuration of local bell and interlook release control, which can be monitored from the
zone panel.
- Functional test equipped with 2 reset modes for heat and smoke detectors.
- ‘Hands-free’ intercom communication at control panel
- Voltage display for ‘Stand by Battery’ test
- Sound alert during ‘Time Delay’ operation
- Optional pre-alarm alert for ‘Time Delay’ operation
- Zone open circuit monitored
HOCHIKI CORPORATION
SINGAPORE BRANCH OFFICE
629 Aljunied Road #03-16 Cititech Industrial Building
Singapore 389838
Tel : 65-6841-9728 Fax : 65-6841-9781
Email : hochiki@singnet.com.sg
HEAD OFFICE
10-43 Kamiosaki 2-Chome. Shinagawa-Ku,
Tokyo 141-8660, Japan
Tel : 81-(3)-3444-4116 Fax : 81-(3)-3444-4167
URL : www.hochiki.co.jp
Hochiki Conventional System
Specifications
Type
Model Name
Circuit Type
Mains
Transformer Capacity
Stand-by Battery
Battery Charger
Main Sounder
Operating Temperature Range
Material
Color
Number of Zones
Weight
Dimension
Made
RPP-ABW
P Type 1st Class Fire Alarm Control Panel (with Time Delay Function)
RPP-ABW (10,15,20) (JE)
RPP-A24A
AC220V 50/60Hz
75VA
DC 24V, 0.6 AH
Ni-Cd Battery Trickle Charger
Speaker (Voice Alarm equipped)
0°C – 40°C
Body, Front Door : Steel, 1.2mm, Baked Paint
Display, Operation Panel : Self Extinguishing Plastic, 2mm
Body, Front Door : Equivalent to Munsell 2.5Y9/1
Display, Operation Panel :Equivalent to Munsell 5Y6/0.5
10,15, or 20 Zones
Approx. 13Kg
450mm(W) X 650mm(H) X 100mm(D)
JAPAN
Wiring Holes & Mounting Holes
Name plate
450
75
Alarm lamp
100
300
20
(450)
30
18.8
390
Zone indication
Operation section
4-mounting hole φ8
177.5
168.5
322.5
272.5
44
30
Operation switch cover
344.5
Door lock screw
φ30 (for AC)
590
(650)
650
91
125 × 50 (for DC)
Download