QuantumR Light Management Hub

advertisement
120 V~ Light Management Hub
Quantum®
Centralized Control Equipment
369375e
1
04.02.2015
QuantumR Light Management Hub
The Quantum® light management hub provides a
centralized connection point for Lutron® EcoSystem®
digital ballast modules, Lutron® power panels,
GRAFIK Eye® QS, and Sivoia® QS shades.
Features
• Designed to control, manage, and monitor EcoSystem®
lighting, Energi Savr NodeTM with EcoSystem®, Lutron®
power panels, GRAFIK Eye® QS, and Sivoia® QS shade
systems in a building or whole campus.
• Supports both astronomic and time-of-day events to
automatically control the lights and shades in
the system.
• Simple reconfiguration of a space without rewiring.
• Individually control, monitor, and adjust any light or
shade in a space.
• QS control links and EcoSystem® loops are
topology-free.
• For EcoSystem® loads, the light management hub
accepts one normally closed (NC) emergency input per
Quantum® bus supply.
• EcoSystem® bus may be wired NEC® Class 1 or
IEC PELV / NEC® Class 2.
Panel Capabilities
• Each hub supports up to 8 EcoSystem® loops,
(4 Quantum® bus supplies).
• Each loop can have a combination of 64 EcoSystem®
ballasts and ballast modules, plus a maximum of
16 daylight sensors, 32 occupancy sensors, and
64 infrared (IR) devices.
• Supports up to 2 Quantum® processors with
2 links each that can be individually configured to
communicate with:
- Quantum® bus supply (limited to one link per bus)
- Lutron® power panels
- Lutron® QS devices
®
S PECIFICAT ION SUB MITTAL
Job Name:
Job Number:
Model Numbers:
Page 1
120 V~ Light Management Hub
Quantum®
Centralized Control Equipment
369375e
2
04.02.2015
Specifications
Regulatory Approvals
•cULus Listed (Reference: UL File E42071)
•CSA Certified
•California Energy Commission Listed
•Seismic Certified (Test Method AC156. Reference
OSHPD Preapproval OSP-0215-10)
•NOM certified models available
•Other certificates may apply
Power
• Input voltage: 1
20 V~, normal/emergency feed
50/60 Hz 15 A
• Output: EcoSystem® - 18 V- 250 mA per loop
Processor - 24 V- 1 A per link
Physical Design
• Enclosure: NEMA Type 1, IP-20 protection
16 U.S. gauge steel
• Weight: 45 Ib (20.4 kg) (with packaging)
• Seismic Certification Limits: SDS = 2.5 g, z/h = 1.0,
IP = 1.5. Contact Lutron for details.
Mounting
• Surface mount only
Environment
• For indoor use only
• 32 ºF to 104 ºF (0 ºC to 40 ºC)
• Relative humidity less than 90% non-condensing
®
S PECIFICAT ION SUB MITTAL
Job Name:
Job Number:
Model Numbers:
Page 2
120 V~ Light Management Hub
Quantum®
Centralized Control Equipment
369375e
How to Build a Model Number
3
04.02.2015
Available Model Numbers
Contact Lutron® for options not listed below.
Example
QP2 - 2P8CSE - 120
Panel
Type
QP2-0P0CSE-120 (for rough-in use)
QP2-1P0CSE-120
QP2-1P2CSE-120
QP2-1P4CSE-120
QP2-1P6CSE-120
QP2-1P8CSE-120
QP2-2P0CSE-120
QP2-2P2CSE-120
QP2-2P4CSE-120
QP2-2P6CSE-120
QP2-2P8CSE-120
Voltage
Number of
Processors
Number
of Loops
Accesory
Device
Panel Type
QP2 = Quantum® Light Management Hub
Number of Processors
0P = 0 Quantum® processors
1P = 1 Quantum® processor
2P = 2 Quantum® processors
Number of Loops
0C
2C
4C
6C
8C
=
=
=
=
=
0
2
4
6
8
EcoSystem®
EcoSystem®
EcoSystem®
EcoSystem®
EcoSystem®
loops
loops
loops
loops
loops
Accessory Device
SE = 5-port Unmanaged Ethernet Switch
Voltage
120 = 120 V~
®
S PECIFICAT ION SUB MITTAL
Job Name:
Job Number:
Model Numbers:
Page 3
120 V~ Light Management Hub
Quantum®
Centralized Control Equipment
369375e
4
04.02.2015
Dimensions
Shown as in (mm)
15.75 (400)
Top View
15.75 (400)
5.81 (148)
12.75 (324)
0.15
(4)
2.5
(63.5)
®
31.5
(800)
26.5
(673)
Left Side View
R
R
31.5
(800)
Front View
Right Side View
Bottom View
®
S PECIFICAT ION SUB MITTAL
Job Name:
Job Number:
Model Numbers:
Page 4
120 V~ Light Management Hub
Quantum®
Centralized Control Equipment
369375e
5
04.02.2015
Mounting and Conduit Entry
• Surface mount indoors.
• Panel generates heat. Mount only where temperature will be 32 ˚F to 104 ˚F (0 ˚C to 40 ˚C).
• This equipment is air-cooled. Do not block vents or warranty will be void. A minimum of 12 in (305 mm) of
unobstructed space is required in front of and below the panel for ventilation.
• Water damages equipment. Mount in a location where the panel and processors will not get wet. Mount within 7˚
of true vertical.
• Digital ballast wiring can be Class 1 or IEC PELV / NECR Class 2; always keep Class 1 and Class 2 wiring
separate, and follow all applicable local and national electric codes.
• Reinforce wall structure for weight and local codes.
Panel
Maximum BTUs/Hour
Weight (without packaging)
All models
220
45 Ib (20.4 kg)
• Mount panels so line (mains) voltage wiring is at least 6 ft (1.8 m) from sound or electric equipment and wiring.
Ceiling
Dedicated feed
Line voltage only
Digital ballast loops
NEC® Class 1 or
IEC PELV / NEC®
Class 2 only
IEC PELV / NEC® Class 2
wiring only for control links
and Ethernet connection
Alternate
ballast
wiring
entry
Alternate IEC
PELV / NEC®
Class 2 entry
Alternate
ballast
wiring
entry
Alternate IEC
PELV / NEC®
Class 2 entry
Alternate IEC
PELV / NEC®
Class 2 entry
Alternate
ballast
wiring
entry
Front View
®
S PECIFICAT ION SUB MITTAL
Job Name:
Job Number:
Wall
Model Numbers:
Side View
Page 5
120 V~ Light Management Hub
Quantum®
Centralized Control Equipment
369375e
Panel Overview
6
04.02.2015
Line voltage input,
normal/emergency feed
Receptacle (for Lutron use only)
Panel power switch
IEC PELV / NEC® Class 2 power
supply board
IEC PELV / NEC® Class 2 wire trough
Ballast wire trough
Quantum® bus supplies
(4 modules, 2 loops per module maximum)
Factory configured
Quantum® bus supply link
Configurable links
(power panel, Lutron® QS,
or Quantum® bus supply)
Processor LEDs
5-port unmanaged Ethernet switch
Quantum® processors
(2 maximum)
®
S PECIFICAT ION SUB MITTAL
Job Name:
Job Number:
Model Numbers:
Page 6
120 V~ Light Management Hub
Quantum®
Centralized Control Equipment
369375e
7
04.02.2015
Line Voltage Wiring
GND
Ground/Earth
(green)
N
Neutral
(white)
120 V~ N/E
Hot/Live
(black)
Notes
• Line voltage must enter panel from top right of panel
• Run a dedicated 120 V~ normal/emergency feed
• Lutron recommends that no more than four Light
Management Hubs are powered by a single derated
20 A circuit
• Run wiring so line (mains) Class 1 voltage is separate
from IEC PELV / NEC® Class 2 wiring
®
S PECIFICAT ION SUB MITTAL
Job Name:
Job Number:
Model Numbers:
Page 7
120 V~ Light Management Hub
Quantum®
Centralized Control Equipment
369375e
Quantum® Inter-Processor Link Wiring
8
04.02.2015
Example of Inter-Processor Wiring:
Riser Diagram
Quantum®
Light
Management
Hub
Floor
Quantum®
Light
Management
Hub
Floor
Ethernet
switch
Quantum®
Light
Management
Hub
Quantum®
Light
Management
Hub
To additional
Quantum®
Light
Management
Hubs
Floor
Notes
• The inter-processor wiring is considered
IEC PELV / NEC® Class 2; do not run in the same
conduit as line (mains) voltage wiring.
• Wiring distance for any single link segment is 330 ft
(100 m) max; use Lutron-provided Ethernet switches
for longer distances.
• Processors cannot be more than 6 “hops” from the
server.
• Processors communicate over the inter-processor
link using multicast UDP; a dedicated network is
recommended for the lighting control system.
• Processors within the panel are prewired to the
Ethernet switch.
®
S PECIFICAT ION SUB MITTAL
Job Name:
Job Number:
Model Numbers:
Quantum®
Light
Management
Hub
Quantum®
server
Unmanaged
Ethernet switch
Page 8
120 V~ Light Management Hub
Quantum®
Centralized Control Equipment
369375e
9
04.02.2015
Dedicated Quantum® Bus Supply Link
Notes
• EcoSystem® bus may be wired in accordance with
NEC® Class 1 or IEC PELV / NEC® Class 2 practices
• Sensors and Quantum® bus supply contact closures must
be wired IEC PELV / NEC® Class 2
Dedicated Quantum® bus supply link; prewired by Lutron
to Quantum® Bus Supply located in panel
Note: If Quantum® bus supply link is not required, this can
be used as a configurable link. Power is not available
from the Quantum® panel on this link. An external
power supply is required to power devices on this link.
QP2-2P8CSE-120 shown
To additional ballasts and
modules (up to 64 total)
EcoSystem® Bus Diagram
1 2 3 4 5 6 7 8
EcoSystem®
ballast
IR receiver
Quantum®
bus supply
(in panel)
EcoSystem®
interface
module
Occupant sensor
(32 maximum per
EcoSystem® loop)
Eco-10® or
Hi-lume®
ballast*
EcoSystem®
ballast
EcoSystem®
keypad
EcoSystem®
ballast
Daylight sensor
(16 maximum per
EcoSystem® loop)
Lighting
remote
*Does not count as one of the ballasts or modules on the EcoSystem® bus
®
S PECIFICAT ION SUB MITTAL
Job Name:
Job Number:
Model Numbers:
Page 9
120 V~ Light Management Hub
Quantum®
Centralized Control Equipment
369375e
10
04.02.2015
Quantum® Bus Supply OPT Switches and LEDs
6
OPT Switches
7
8
OFFON
positionposition
H/L H/L N N
ON 1
2
3
4
5
6
7
8
E2 E2 E1 E1
OPT switches are used to configure
the Bus Supply. The tables below
describe the options. To place an
OPT switch in the OFF position, slide
the switch to the left; away from the
switch’s number. Default is ON (next
to the switch’s number).
E2 E2 E1 E1
OPT Switch Functions
ON 1
ON 1
ON 1
2 ON31 4 2 5 3ON 614 725 836 47 58 6 7 8
3 614 725 ON
2 ON31 4 2 5ON
8361 472 583 6 4 7 5 8 6
2 ON31 4 2 5ON
3 614 725 836 47 58 6 7 8
2 ON31 4 2 5 3ON 614 725 ON
8361 472 583 6 4 7 5 8 6
2 ON31 4 2 5ON
3 614 725 836 47 58 6 7 8
2
7
7
7
7
8
8
8
8
5588
583
58
66
64
6
5
6
6
7
7
8
8
Lights go to
“low” level
Bus Supply 4
Addresses 7, 8
2 3 4 5 6
ON 1
4 2 53ON 614 725 836 47 58 6 7 8
4477
472
47
Lights go to
“low” level
ON31
ON 1
ON 1
ON 1
77 88
75 86
7 8
725 836
725 836
725 ON
8361
725 836
4
5
7
Lights go to
“high” level
Bus Supply 3
Addresses 5, 6
53ON
3 616144
5ON
3 614
5ON
53ON 614
Lights go to
“high” level
Manual override
levels will be used
Lights go
to Off
Lights go
to Off
Lights will go to the level
specified by the system
Status LEDs
ON 1
2
3
BUS
ERR
EMG
4
BUS
V
Bus Supply 2
Addresses 3, 4
42
42
42
42
3
4
6
8
5
Lights stay at
current level
STAT
ERR
EMG
2 ON31
2 ON31
2 ON31
2 ON31
Lights stay at
current level
ERR
EMG
H/L H/L N N
ON 1
ON 1
ON 1
ON 1
2
3
Manual Override
ON31
ON
33 611644 772255 883366 4477 5588 66 77 88
22 ON
31 4422 55ON
2 ON31 4 2 5 3ON 614 725 836 47 58 6 7 8
1
2
8
ON 1
ON 1
ON 1
ON
1
Blue Loop (left side)
Manual Override levels
1 2 ON
3 11644 72255 83366 4477 5588 66 77 88
ON31
22 ON
3 442 553ON
6 7 8
ON
7
4
6
3
7, 8
2
1, 2
Address Numbers:
3, 4
5, 6
Green Loop (right side)
Manual override levels
Bus Supply 1
Addresses 1, 2
ON 1
5
ON 1
ON 1
4
8
3
Addressing
Set address for
bus supply’s loops
(2 loops per bus supply)
7
2
2 ON31 42 53ON 164 725 ON8361 472 583 6 4 7 5 8 6
1
4
ON 1
1
Bus Supply Numbers:
2
3
PWR
BUS
ERR
EMG
BUS
LEDs on the Quantum® Bus
Supply indicate network status.
The specific LEDs, color and
flashing method is detailed
below.
STAT
V
E2 E2 E1 E1
(Blue)
LED
PWR
E2 E2 E1 E1
(Green)
Normal Operation
V~ PWR
On
Off
No Mains power
Steady flash
Off
No Mains power or unit fault
On
Unit fault
On
Unit fault
On
Emergency contact closure is
active
Steady flash
Miswire detected on
corresponding bus
Intermittent flash
or Off
ERR/EMG Off
S PECIFICAT ION SUB MITTAL
Job Name:
Job Number:
Probable Cause
STAT
BUS
®
Problem Indicator
Model Numbers:
Page 10
120 V~ Light Management Hub
Quantum®
Centralized Control Equipment
369375e
11
04.02.2015
Quantum® Bus Supply Wiring
Line voltage in
(prewired by Lutron)
Processor link
(prewired by Lutron;
not visible in this
view)
7 8
5 6
3 4
1 2
DL7
E1
DL8
E1
E2
E2
EM C
Emergency input
(normally closed)
E2
E1
EcoSystem® devices
E2
E1
ire Gauge
W
12 AWG (4.0
14 AWG (2.5
16 AWG (1.5
18 AWG (1.0
mm2)
mm2)
mm2)
mm2)
Max. Bus Length
2200 ft (670 m)
1400 ft (427 m)
900 ft (274 m)
570 ft (175 m)
Notes
•E1 and E2 wires are not polarity sensitive.
•Hot/live, neutral, and ground wires are also
connected to each lighting fixture; some may have
an emergency feed.
•Wire-free topology.
®
S PECIFICAT ION SUB MITTAL
Job Name:
Job Number:
Model Numbers:
To additional
EcoSystem® devices
•If 15 V- +/- 1 V- is not present between E1 and
E2, check the Quantum® bus supply wiring. A short
between E1 and E2 will cause the bus supply to stop
providing voltage on the bus and will cause the ERR
indicator to flash. Removing the short between E1
and E2 will allow the bus supply to operate properly.
•To wire the Quantum® bus supply for IEC PELV / NEC®
Class 2, the Quantum® bus supply wires must be
separated from the mains wiring. Otherwise, the
IEC PELV wiring must be classified as NEC® Class 1.
Page 11
120 V~ Light Management Hub
Quantum®
Centralized Control Equipment
369375e
12
04.02.2015
Power panel
Power panel
1 COM
2 N/C
3 MUX
4 MUX
D DRAIN
5 Sense line
1 COM
2 N/C
3 MUX
4 MUX
D DRAIN
5 Sense line
DRAIN
_
MUX
V+
COM
Power panel
1 COM
2 N/C
3 MUX
4 MUX
D DRAIN
5 Sense line
Configurable Link Wiring: Power Panel Link
5 4 3 2 1
4
3
3
Control wiring Data link
(1) 12 AWG
(1) shielded, twisted pair
(2.5 mm2)
22 AWG (1.0 mm2)
1: Common
3: MUX
4: _
Link
D: Drain wire in shield (keep
terminator
away from ground and all
(LT-1)
electronics)
IEC PELV / NEC® Class 2
Terminal Wiring
(2) 12 AWG
(2.5 mm2)
Drain
Link
terminator
(LT-1)
Emergency/essential
sense line
(1) 18 AWG (1.0 mm²)
5: Sense line
Sense line is used
when there is a panel
being supplied by an
emergency/essential feed
Data link: twisted,
shielded pair
22 AWG (1.0 mm2)
3: MUX
4: _
Sense: 18 AWG (1.0 mm²)
1 2 3 4 D 5
C
1 2 3 4 D 5
Link Link
AB C
MUX
Data B OK
Power OK
Comm
Drain
Sense
24VFW
MUX
MUX
Common
Data A OK
D
Drain
Configurable
links
MUX
Quantum® Bus
Supply link
4
D
SELECT CIRCUIT
Notes
•Power panel link must be daisy-chained (no T-taps).
•Maximum of 32 power panels per link.
•It is not necessary to have the Quantum® panel at the
end of the link.
•The sense wire (terminal 5) is used whenever there is a
panel being supplied by an emergency/essential feed;
see power panel instructions for details.
•Each low-voltage IEC PELV / NEC® Class 2 terminal can
accept only two 18 AWG (1.0 mm2) wires. Two
12 AWG (2.5 mm2) conductors will not fit. Connect as
shown using appropriate wire connectors.
®
S PECIFICAT ION SUB MITTAL
Job Name:
Job Number:
Model Numbers:
•Total length of control link may be no more than
2000 ft (600 m). If MUX-RPTR interface and
GRX-CBL-46L cable are used, length may be up
to 4000 ft (1200 m).
• GRX-CBL-46L IEC PELV / NEC® Class 2 wiring
cable is available from Lutron® and contains two
12 AWG (2.5 mm2) conductors for control power,
one twisted, shielded pair of 22 AWG (1.0 mm2)
for data link, and one 18 AWG (1.0 mm2)
conductor for emergency (essential) sense line.
Page 12
120 V~ Light Management Hub
Quantum®
Centralized Control Equipment
369375e
13
04.02.2015
Configurable Link Wiring: GRAFIK Eye® QS and Sivoia® QS Shades
DRAIN
MUX
MUX
V+
COM
GRAFIK Eye® QS Link
(do not use the “DRAIN” terminal)
GRAFIK Eye® QS control unit
5 4 3 2 1
QS
wallstations
Configurable
links
4
4
4
3
3
3
2
2
2
1
1
1
Note: Wallstations are powered directly from the lighting
management panel (not the GRAFIK Eye® QS control unit)
IEC PELV / NEC® Data link: (1) twisted,
shielded pair
Class 2
22 AWG (1.0 mm2)
Terminal
3: MUX
Wiring
4: _
Drain
GRAFIK Eye® QS control unit
A B C
5 4 3 2 1
1 2
DRAIN
_
MUX
V+
COM
Sivoia® QS Shade Link
(do not use the “DRAIN” terminal)
1 2 3 4
1 2 3 4 5 6 L N
Sivoia® QS
smart power
supply panel
Sivoia®
QS shade
Notes
•System communication uses IEC PELV / NEC®
Class 2 low-voltage wiring.
•Follow all local and national electrical codes when
installing IEC PELV / NEC® Class 2 wiring with line
voltage/mains wiring.
•Each terminal accepts up to two 18 AWG (1.0 mm2)
wires.
•Total length of control link must not exceed 2000 ft
(600 m); extend using up to 3 link repeaters [each
adds 2000 ft (600 m)].
•Make all connections in the control unit’s wallbox.
®
S PECIFICAT ION SUB MITTAL
Job Name:
Job Number:
Model Numbers:
(2) 12 AWG
(2.5 mm2)
4
(2) 12 AWG
(2.5 mm2)
IEC PELV / NEC® Class 2 control
wiring (2) 18 AWG (1.0 mm2)
1: Common
2: 24 V-
C
V+ and COM
Wire Gauge
QS Link
Max. Total Length
12 AWG (2.5 mm2)
2000 ft (600 m)
16 AWG (1.5 mm2)
800 ft (250 m)
18 AWG (1.0 mm2)
500 ft (150 m)
3
2
1
B
A
•A Quantum QS link can have up to 512 switch legs
(outputs) and 99 devices.
•The Quantum Light Management Hub provides
33 power draw units (PDUs) on the QS Link. For
more information, see “Power Draw Units on the QS
Link” (Lutron® P/N 369405), at www.lutron.com/qs.
•Wiring can be T-tapped or daisy-chained.
•Wire sizes:
- Two 12 AWG (2.5 mm2) conductors for control
power.
- One twisted, shielded pair of 22 AWG (1.0 mm2)
for data link.
- Cable is available from Lutron: GRX-CBL-46L.
Page 13