AC LINK LOAD FLOW CONTROL IN ELECTRIC POWER SYSTEMS by Fernando Mancilla−David A Dissertation submitted in partial fulfillment of the requirements for the degree of Doctor of Philosophy (Electrical Engineering) at the UNIVERSITY OF WISCONSIN−MADISON 2007 © Copyright by Fernando A. Mancilla−David 2007 All Rights Reserved i Abstract As congestion in AC power transmission systems increases due to technical limitations, environmental pressures, economic necessities and developmental demands, devices with the ability to control power flow with much greater ease than presently possible would be highly desirable. Furthermore, devices that channel power flow in the network to fulfill contractual obligations for purchase agreements between power producers and consumers would facilitate improved operation of the power system in the emerging deregulated scenario. Following this trend, several power electronic-based devices capable of accomplishing these objectives have been developed, unified under the rubric of Flexible AC Transmission Systems, FACTS. This thesis proposes a new family of FACTS devices: the Π−controller, the Ξ−controller and the Γ−controller. Based on the vector switching converter (VeSC), these devices feature similar functional characteristics to the ones encountered in the voltage source HVDC interties, the Static Synchronous Series Compensator (SSSC) and the Unified Power Flow Controller (UPFC), respectively. The control function, however, is realized by direct AC↔AC conversion without frequency change, adopting the strategy of pulse width modulation (PWM). A comprehensive analysis is performed, including operating principles, equivalent circuits, design consideration and dynamic modeling and control. Computer simulations of illustrative examples are executed to validate the approach. For the series compensation case, this new technology is contrasted against the state−of−the−art. A detailed comparative study between the Ξ−controller and the SSSC shows that the use of VeSC−based power flow controllers could become an alternative for the next generation of FACTS devices. In order to fully prove the concept of VeSC−based power flow controllers, a ii laboratory prototype was built and tested. The Γ−controller was chosen for experimental verification, as its topology is the most general of all three controllers. Finally, a system point of view is studied, incorporating the Ξ−controller into an Optimal Power Flow (OPF) program. iii Acknowledgments I would like to express my sincere gratitude and thanks to my advisor Professor Giri Venkataramanan for his guidance, counsel and encouragement at every stage of this research. I also thank my former advisor Professor Fernando Alvarado who gave me the opportunity to become a graduate student at the University of Wisconsin and guided my studies towards my M.S. degree. I acknowledge the Wisconsin Electric Machines and Power Electronics Consortium (WEMPEC), the Electric Power Research Institute (EPRI), and the Electrical and Computer Engineering Department at the University of Wisconsin for funding this research. I have been fortunate to work with the WEMPEC and power area professors, students and support staff who provided an excellent working environment with all the resources that made this research possible. I also thank Professor Subhashish Bhattacharya from North Carolina State University for his contributions to Chapter 6 of this thesis. I acknowledge the cooperation and support of Patrick Flannery who helped me implement my experiments at the WEMPEC laboratory. Last but not least, I express thanks to my dearest father for his effort, encouragement and inspiration. ¡Te quiero mucho papá! iv Table of Contents Abstract............................................................................................. i Acknowledgments ........................................................................... iii Table of Contents ............................................................................iv List of Figures .............................................................................. xiii List of Tables .................................................................................. xx Chapter 1 Introduction ................................................................22 1.1...... General ...................................................................................................... 22 1.1.1 Congestion in Transmission Systems............................................ 24 1.1.2 Loop Flows ................................................................................... 24 1.2...... Power Flow Control through FACTS Technology...................................... 26 1.3...... Dynamic Compensation of Power System with FACTS Devices............... 28 1.4...... Literature Survey....................................................................................... 28 1.5...... State−of−the−Art....................................................................................... 33 1.5.1 The Convertible Static Compensator ............................................ 33 1.5.2 Distributed FACTS .......................................................................... 34 1.6...... Outline of the Research............................................................................. 36 v Chapter 2 Vector Switching Converters ..................................... 39 2.1...... Introduction ............................................................................................... 39 2.2...... Three−Phase Vector Switching Converters .............................................. 39 2.2.1 Converter Model ........................................................................... 39 2.2.2 Equivalent Circuit ......................................................................... 43 2.2.3 Switch Realization ........................................................................ 46 2.2.4 VeSC Pulse Width Modulation...................................................... 47 2.3...... Multiple−Secondary Phase−Shifter Transformer ..................................... 50 Chapter 3 AC Link Power Flow Controllers............................... 54 3.1...... Introduction ............................................................................................... 54 3.2...... Π−Controller: An AC Link Back−to−Back Intertie................................... 55 3.2.1 Topology ....................................................................................... 55 3.2.2 Equivalent Circuit ......................................................................... 57 3.2.3 Principle of Operation ................................................................... 58 3.2.4 Control Capabilities ...................................................................... 61 3.2.4.1 Active Power Control............................................................. 62 3.2.4.2 Reactive Power Control ......................................................... 63 3.2.4.3 Angle Control......................................................................... 64 3.2.5 Design Considerations .................................................................. 65 3.2.5.1 Parameter Calculations........................................................... 65 vi 3.2.5.2 Feasible operating range ........................................................ 66 3.2.6 Simulation Results ........................................................................ 67 3.2.7 Summary ....................................................................................... 69 3.3...... Ξ−Controller: An AC Link Series Compensator ....................................... 70 3.3.1 Topology ....................................................................................... 71 3.3.2 Equivalent Circuit ......................................................................... 72 3.3.3 Principle of Operation ................................................................... 74 3.3.4 Control Capabilities ...................................................................... 75 3.3.5 Design Considerations .................................................................. 77 3.3.6 Simulation Results ........................................................................ 78 3.3.7 Summary ....................................................................................... 81 3.4...... Γ−Controller: An AC Link Unified Power Flow Controller...................... 81 3.4.1 Topology ....................................................................................... 82 3.4.2 Equivalent Circuit ......................................................................... 85 3.4.3 Principle of Operation ................................................................... 86 3.4.4 Control Capabilities ...................................................................... 89 3.4.4.1 Transmitted Power Control .................................................... 90 3.4.4.2 Tap−changing/phase−shifting control.................................... 91 3.4.5 Design Considerations .................................................................. 93 3.4.5.1 Transformers turn ratio .......................................................... 93 3.4.5.2 Filter Capacitors / Switching Frequency................................ 93 3.4.6 Simulation Results ........................................................................ 95 vii 3.4.7 Summary ..................................................................................... 101 Chapter 4 Dynamic Modeling of AC Link Power Flow Controllers 103 4.1...... Introduction ............................................................................................. 103 4.2...... Generalized Averaging Theory ............................................................... 104 4.2.1 Index symmetry........................................................................... 105 4.2.2 Reconstruction............................................................................. 105 4.2.3 Derivative with respect to time ................................................... 106 4.2.4 Average of a product................................................................... 106 4.3...... Dynamics for electric elements............................................................... 106 4.3.1 Resistor........................................................................................ 107 4.3.2 Inductor ....................................................................................... 107 4.3.3 Capacitor ..................................................................................... 108 4.4...... Application to State Space Models for Vector Switching Converters.... 108 4.4.1 Real Excitation ............................................................................ 114 4.4.2 Complex Excitation..................................................................... 117 4.5...... Case Studies ............................................................................................ 121 4.5.1 Generalized Averaging Applied to the Ξ−controller .................. 121 4.5.1.1 The Model ............................................................................ 121 4.5.1.2 Model Accuracy ................................................................... 124 viii 4.5.1.3 4.5.2 Eigenvalues Pattern.............................................................. 126 Generalized Averaging Applied to the Γ−controller .................. 127 4.5.2.1 The Model ............................................................................ 127 4.5.2.2 Model Accuracy ................................................................... 130 4.6...... Summary ................................................................................................. 133 Chapter 5 Feedback Control for AC Link Power Flow Controllers 134 5.1...... Introduction ............................................................................................. 134 5.2...... Feedback Control for the Ξ−controller ................................................... 135 5.2.1 Proposed Controller .................................................................... 136 5.2.1.1 Small Signal Model.............................................................. 138 5.2.1.2 Controller Design via Bode Plots......................................... 141 5.2.2 Simulation Results ...................................................................... 145 5.2.2.1 Response to a step change in the reference.......................... 145 5.2.2.2 Response to disturbances ..................................................... 146 5.3...... Feedback Control for the Γ−controller.................................................... 148 5.4...... Summary ................................................................................................. 149 ix Chapter 6 A comparative evaluation of Power Flow Controllers using AC Link and DC Link Converters........................................ 150 6.1...... Introduction ............................................................................................. 150 6.2...... Candidate Compensators......................................................................... 152 6.2.1 DC Link Series Compensator....................................................... 152 6.2.2 AC Link Series Compensator....................................................... 153 6.3...... Test system description ........................................................................... 155 6.4...... Steady state performance evaluation....................................................... 156 6.4.1 Operating Modes......................................................................... 156 6.4.2 Design Considerations ................................................................ 158 6.4.2.1 Choice of power semiconductors ......................................... 159 6.4.2.2 Injection Transformer........................................................... 161 6.4.2.3 Capacitor .............................................................................. 164 Capacitor Selection ............................................... 164 6.4.2.3.1 SSSC 6.4.2.3.2 Ξ−Controller Capacitor Selection ................................. 166 6.4.2.4 Converter.............................................................................. 168 6.4.2.4.1 Semiconductors Ratings................................................ 168 6.4.2.4.2 Device Losses................................................................ 170 6.4.2.4.3 Waveform Quality......................................................... 174 6.5...... Dynamic performance evaluation ........................................................... 175 6.5.1 Dynamic Modeling...................................................................... 175 x 6.5.2 Control Structure......................................................................... 176 6.5.3 Regulator Design......................................................................... 178 6.5.4 Command Response.................................................................... 179 6.5.5 Disturbance Response ................................................................. 180 6.6...... Summary ................................................................................................. 180 Chapter 7 Experimental Verification of the Γ−Controller .......182 7.1...... Introduction ............................................................................................. 182 7.2...... Experiment Layout.................................................................................. 183 7.2.1 Laboratory Prototype of a Transmission Line ............................ 183 7.2.2 Laboratory Prototype of a Γ−Controller ..................................... 185 7.3...... Experimental Waveforms........................................................................ 188 7.3.1 Steady Sate Operation ................................................................. 189 7.3.2 Dynamic Operation ..................................................................... 194 7.4...... Summary ................................................................................................. 195 Chapter 8 Optimal Power Flow with AC Link Power Flow Controllers Embedded .................................................................197 8.1...... Introduction ............................................................................................. 197 8.2...... Standard OPF ............................................................................................ 199 8.3...... OPF with Ξ−controllers embedded ......................................................... 201 xi 8.3.1 The model.................................................................................... 201 8.3.2 OPF 8.3.3 Amount and Location.................................................................. 204 8.3.4 Case Study................................................................................... 205 Formulation .......................................................................... 202 8.3.4.1 Economic Dispatch .............................................................. 206 8.3.4.2 Interface Power Maximization............................................. 208 8.4...... Summary ................................................................................................. 210 Chapter 9 Conclusions and Future Work................................. 211 9.1...... Contributions........................................................................................... 213 9.1.1 Modeling and control .................................................................. 213 9.1.2 Computer simulation................................................................... 213 9.1.3 Comparison against the state−of−the−art technology for series compensation........................................................................................... 214 9.1.4 Experimental verification............................................................ 215 9.1.5 System level modeling ................................................................ 215 9.2...... Proposed Continuing Research ............................................................... 215 9.2.1 Feedback Control for Γ−controller ............................................. 215 9.2.2 OPF with 9.2.3 System level dynamics................................................................ 216 9.2.4 Multilevel realization for the Ξ−Controller ................................ 217 9.2.5 Additional topologies .................................................................. 217 embedded Γ−controllers............................................... 216 xii 9.2.6 Field demonstration..................................................................... 218 References ....................................................................................225 xiii List of Figures Figure 1-1 Example of a power system. ............................................................... 22 Figure 1-2 Schematic of a 2-bus system example................................................. 24 Figure 1-3 Schematic of a 3-bus system example................................................. 25 Figure 1-4 Schematic Illustrating Power Flow Control through a Transmission Line. .......................................................................... 26 Figure 1-5 Power Flow Control Evolution............................................................ 29 Figure 1-6 Schematic diagrams of DC link realizations for power flow control.............................................................................................. 31 Figure 1-7 Schematic of the Marcy Substation CSC.............................................. 34 Figure 1-8 Distributed Static Series Compensator (DSSC) Schematic. ................. 35 Figure 2-1 Circuit schematic of a three-phase VeSC synthesizing an adjustable pole voltage obtained from N throws.............................. 40 Figure 2-2 Single−phase equivalent circuit of a VeSC. ......................................... 44 Figure 2-3 Region of pole voltage obtainable for different throw realizations....................................................................................... 45 Figure 2-4 IGBT-Diode realization for the switch.................................................. 47 Figure 2-5 Waveforms Illustrating Pulse Width Modulation for Vector Switching Converters. ..................................................................... 49 Figure 2-6 A Simulink/DSP strategy to generate the gate pulses described in Figure 2-5. ................................................................................... 50 Figure 2-7 A four−winding three phase transformer to generate three secondary vector voltages 120° phase−shifted................................ 51 xiv Figure 2-8 A five−winding three−phase transformer to generate four secondary vector voltages 90° phase−shifted.................................. 52 Figure 3-1 Schematic of a VeSC−based AC link intertie. ....................................... 55 Figure 3-2 Topology of a VeSC −based AC link intertie. ....................................... 56 Figure 3-3 Single−Phase averaged equivalent circuit........................................... 57 Figure 3-4 The ideal AC link intertie. .................................................................... 58 Figure 3-5 The “unity” rhombus. Permissible duty ratio values........................... 60 Figure 3-6 Variation of sets of duty ratios, (a), (b) and reactive power at receiving end, (c) as a function of active power control while Qs=0pu and θ=─20°. ....................................................................... 62 Figure 3-7 Variation of sets of duty ratios, (a), (b) and reactive power at receiving end, (c) as a function of reactive power control while PS =1.5pu and θ=─20°. .......................................................... 63 Figure 3-8 Variation of sets of duty ratios, (a), (b) and reactive power at receiving end, (c) as a function of phase−shifting control while PS =1.5pu QS=0pu. ................................................................. 64 Figure 3-9 Complex Power Nomogram at the sending end. (a) Entire operating range, (b) restricted and more practical operating range. ............................................................................................... 67 Figure 3-10 Phase−A voltage and current waveforms at the sending end............ 68 Figure 3-11 Phase−A voltage and current waveforms at the receiving end. ........ 69 Figure 3-12 Schematic of a VeSC−based AC link series compensator................... 71 Figure 3-13 Topology of a VeSC−based AC link series compensator.................... 72 Figure 3-14 Single−Phase Averaged Equivalent Circuit. ..................................... 73 Figure 3-15 The ideal AC link series compensator................................................ 74 Figure 3-16 Equivalent impedance (a) and power at the receiving end (b) as a function of the duty ratio. ......................................................... 76 xv Figure 3-17 Phase−A Current and Injected Voltage shown over a 60Hz period. .............................................................................................. 79 Figure 3-18 Simulation results for a step−change of the duty ratio (a) from 20 to 80%. (b) and (c) show the response of the line current and the power at the receiving end, respectively............................ 80 Figure 3-19 Simulation results for a ramp−change of the duty ratio (a) from 20 to 80%. (b) and (c) show the response of the line current and the power at the receiving end, respectively. .............. 80 Figure 3-20 Schematic of a VeSC−based AC link Unified Power Flow Controller......................................................................................... 82 Figure 3-21 Topology of a VeSC−based AC link Unified Power Flow Controller......................................................................................... 83 Figure 3-22 Single−Phase Averaged Equivalent Circuit. ..................................... 86 Figure 3-23 The ideal AC link Unified Power Flow Controller. ........................... 87 Figure 3-24 Receiving−end power control. .......................................................... 91 Figure 3-25 Tap−changing, phase−shifting control. ............................................. 92 Figure 3-26 Resonance frequency as a function of the capacitor value................ 94 Figure 3-27 Phase−A Voltage and Current at the receiving−end. ........................ 96 Figure 3-28 Phase−A Capacitor voltages.............................................................. 97 Figure 3-29 Phase−A SPT transformer currents. .................................................. 98 Figure 3-30 Duty Ratio Commands. Stepped from d1=33%, d2=35%, d3=32% d4=0% to d1=0%, d2=18%, d3=57% d4=25%. ................... 99 Figure 3-31 Response to a duty ratio step change of the (a) line current, (b) active power and (c) reactive power, all at the receiving end. .................................................................................................. 99 Figure 3-32 Duty Ratio Commands. Ramped from d1=33%, d2=35%, d3=32% d4=0% to d1=0%, d2=18%, d3=57% d4=25%. ................. 100 xvi Figure 3-33 Response to a duty ratio ramp change of the (a) line current, (b) active power and (c) reactive power, all at the receiving end. ................................................................................................ 101 Figure 4-1 Schematic of a generic power system with a vector switching converter embedded....................................................................... 109 Figure 4-2 Waveforms corresponding to the switching function, index {0} approximation (duty ratio) and index {0, -N, N} approximation. All with d=50%. .................................................. 113 Figure 4-3 Exact model for the Ξ−controller. ..................................................... 122 Figure 4-4 Waveform of the switched capacitor current along with the traditional and augmented approximations. FP=60(Hz), FS=1020(Hz), d=50%. ................................................................... 125 Figure 4-5 Eigenvalues distribution for the different models. FR=30(Hz), FP=60(Hz), FS=1020(Hz)............................................................... 127 Figure 4-6 Exact model for the Γ−controller. ..................................................... 128 Figure 4-7 Capacitor voltage waveforms with FR=1862(Hz) and FS=2400(Hz).................................................................................. 131 Figure 4-8 Capacitor voltage waveforms with FR=1862(Hz) and FS=1800(Hz).................................................................................. 132 Figure 5-1 Configuration for classical control design......................................... 134 Figure 5-2 Block diagram of the control system................................................. 137 Figure 5-3 Block diagram for the small signal model......................................... 140 Figure 5-4 Bode Plot for the partial loop gain βg(jω)......................................... 143 Figure 5-5 Bode Plot for the PI controller h(jω). ................................................ 144 Figure 5-6 Gain and Phase margins from the loop gain T(jω)= βh(jω)g(jω)........................................................................ 144 Figure 5-7 Response to a 15% step change in the reference power. (a) shows the step change applied to the reference power while (b) and (c) show the response on the line current and the measured power at the receiving end, respectively. ...................... 146 xvii Figure 5-8 Response to a 5% step change in the sending end voltage. (a) shows the step change applied to the magnitude of the sending end voltage while (b) and (c) show the response on the line current and the measured power at the receiving end, respectively.................................................................................... 147 Figure 5-9 Response to a 3° step change in the transmission angle. (a) shows the step change applied to the transmission angle while (b) and (c) show the response on the line current and the measured power at the receiving end, respectively. ................ 147 Figure 5-10 Control system for the Γ−controller. ............................................... 148 Figure 6-1 Schematic of candidate compensators. (a) SSSC (b) Ξ−controller................................................................................... 153 Figure 6-2 Converter realizations. (a) SSSC (b) Ξ−controller.............................. 154 Figure 6-3 Waveforms illustrating AC voltage synthesis. (a) SSSC. (b) Ξ−controller................................................................................... 154 Figure 6-4 One line diagram of the candidate series compensation system. ...... 155 Figure 6-5 Steady sate equivalent circuits. (a) SSSC (b) Ξ−controller................. 157 Figure 6-6 Switch realization in terms of real semiconductors. For the SSSC, 4 series IGCT with antiparallel diode (ABB 5SHX 08F4510) are used. The clamping diode is also realized using 4 diodes in series (ABB 5SDF 03D4502). For the Ξ−controller, 3 parallel IGBT with antiparallel diode (EUPEC FZ600R65KF1) are used. .............................................................. 169 Figure 6-7 Pole current breakup. (a) SSSC, (b) Ξ−controller............................... 173 Figure 6-8 Voltage/Current injected into the transmission line. (a) SSSC, (b) Ξ−controller. ............................................................................ 175 Figure 6-9 Dynamic equivalent circuits. (a) SSSC, (b) Ξ−controller. .................. 176 Figure 6-10 Feedback control loop. TS=5 (ms), β=10-6. (a) SSSC, (b) Ξ−controller................................................................................... 177 Figure 6-11 Dc voltage equalizing algorithm ..................................................... 177 xviii Figure 6-12 Small signal frequency response of loop gain of (a) SSSC, (b) Ξ−controller................................................................................... 178 Figure 6-13 Computer simulation waveforms illustrating response to command changes. (a) SSSC, (b) Ξ−controller............................... 179 Figure 6-14 Computer simulation waveforms illustrating response to bus voltage and angle disturbances. (a) SSSC, (b) Ξ−controller. ......... 180 Figure 7-1 Schematic of the Γ−controller system implemented in the laboratory....................................................................................... 182 Figure 7-2 Laboratory prototype of a transmission line...................................... 184 Figure 7-3 Laboratory prototype of a transmission line connecting two stiff voltage busbars....................................................................... 185 Figure 7-4 Laboratory prototype of a Γ−controller............................................. 186 Figure 7-5 Detailed laboratory prototype of a Γ−controller system. ................. 187 Figure 7-6 Picture of hardware built at the laboratory....................................... 188 Figure 7-7 Attainable pole voltage (a) and the corresponding power diagram (b). ................................................................................... 189 Figure 7-8 Experimental waveforms showing the gate voltage applied to the IGBTs. ....................................................................................... 191 Figure 7-9 Waveforms showing the voltage at location V2. (a) Experimental (b) Simulated........................................................... 191 Figure 7-10 Waveforms showing the line current. (a) Experimental (b) Simulated....................................................................................... 192 Figure 7-11 Waveforms showing the injected voltage. (a) Experimental (b) Simulated. ................................................................................ 193 Figure 7-12 Waveforms showing the fundamental component of the injected voltage. (a) Experimental (b) Simulated.......................... 193 Figure 7-13 Waveforms showing the injected voltage at the switching frequency timescale. (a) Experimental (b) Simulated. .................. 194 xix Figure 7-14 Experimental waveforms illustrating the transition from one operating point to another by means of duty ratio ramping. ......... 195 Figure 8-1. A 3−area electric power system. ...................................................... 198 Figure 8-2 Simplified Equivalent Circuit for the Ξ−controller........................... 201 Figure 8-3 The IEEE 39−bus system. ................................................................... 205 xx List of Tables Table 1-1 Complex Power Sensitivities................................................................ 27 Table 6-1 System Data ........................................................................................ 156 Table 6-2 Operating Modes ................................................................................ 158 Table 6-3 Injection Transformer Rating ............................................................. 163 Table 6-4 Capacitor Requirements Summary ..................................................... 167 Table 6-5 Devices Stress..................................................................................... 169 Table 6-6 Devices Capability.............................................................................. 170 Table 6-7 Device Count ...................................................................................... 170 Table 6-8 Converter Losses ................................................................................ 172 Table 6-9 Active state for semiconductors.......................................................... 173 Table 6-10 Analytical description for IT1A .......................................................... 173 Table 6-11 Converter Losses for PL=160(MW), QINJ=7.7(MVAr) .................... 174 Table 6-12 Total Harmonic Distortion (THD).................................................... 175 Table 6-13 Regulator Design Results ................................................................. 179 Table 7-1 Γ−controller component rating ........................................................... 186 Table 7-2 Operating Point................................................................................... 190 Table 8-1 Active Constraints .............................................................................. 206 Table 8-2 Interface Flows ................................................................................... 207 Table 8-3 Active Constraints .............................................................................. 207 Table 8-4 Interface Flows ................................................................................... 209 xxi Table 8-5 Interface Flows ................................................................................... 209 22 Chapter 1 Introduction 1.1 General The electric power industry has traditionally been divided into three sectors: generation, transmission and distribution. At the generation stage, electricity is produced from sources such as fossil fuel, nuclear fuel, or waterfalls. Then, the electric power is injected into the transmission system which is configured as an interconnected network of transmission lines and control devices. Finally, at the distribution stage, the power is taken from the transmission system and delivered to consumers at specific standards of quality and reliability. These three stages together −generation, transmission and distribution− are generically known as a power system. Figure 1-1 illustrates a possible realization of such a system. Distribution Transmission Network Figure 1-1 Example of a power system. 23 Since the ultimate goal of a power system is to deliver power to consumers, a perfectly valid question is why an interconnected transmission system is needed. Why not deliver power via radial lines from local generators to local consumers without being part of a meshed network? The real need for an interconnected transmission system is twofold: (i) it allows for the pooling of power plants and load centers in order to minimize the total power generation capacity and fuel cost and (ii) it improves the reliability of power supply through redundancy. Following this trend, transmission networks throughout the world have developed into enormous, complex systems containing thousands of transmission line segments interconnecting large geographical areas. However, during the last few decades the electricity industry has had to face two new issues. On the one hand, due to environmental pressures and right−of−way matters, it is becoming increasingly difficult, if not impossible, to build new transmission lines in order to satisfy the always increasing demand for electric power. As a result of this, existing transmission systems are being pushed to operate close to their capacity limits and transmission line congestion is being observed in several regions particularly those with large load growth at large populated centers. On the other hand, due to the deregulation of the electricity industry that has taken place, channeling power flows through pre−established contractual paths has become a priority for the system participants. This issue is known as the loop flow problem. These issues are briefly reviewed in the following sections. 24 1.1.1 Congestion in Transmission Systems The concept of congestion in transmission networks can be understood by considering a simple case of a generator serving a load through two parallel transmission lines, as suggested in Figure 1-2. Say the transmission line l1 has an impedance X and a maximum capacity to carry power given by Pm. The second line, l2, has exactly the same impedance as l1 but its maximum capacity is only 0.5Pm. Since both lines have the same impedance, the power sent from the generator G to the load L equally splits into the two transmission lines, as suggested in the figure. When the power demanded by L is less than Pm, the system operates within its capacity margins since each line is carrying less power than 0.5Pm. However, when the load L demands more power than Pm, say 1.2Pm, each line carries 0.6Pm, which overloads the line l2. Notice that the combined capacity of both lines is 1.5Pm, but the system is unable to carry such an amount of power due to the congestion in one of the lines. Situations like this, in a more complex context, are frequently encountered in modern power systems [1]. G P l1: X, Pm L P l2: X, 0.5Pm Figure 1-2 Schematic of a 2-bus system example. 1.1.2 Loop Flows The concept of loop flows, also known as parallel flows, is formally discussed in Chapter 8, but here it can be described considering a simplified 3−bus system as 25 suggested in Figure 1-3. Say the generator G1 has a contractual obligation of serving the load L2 by an amount of Pc. For that purpose, the generator “reserves” capacity on the line 1−2 for that amount. However, since power flows obey Kirchhoff’s laws and not contractual paths, only a fraction of such a flow (κPc) will actually follow the contractual path and the remaining amount, (1−κ)Pc, will flow through the bus 3, creating an undesired loop flow. Figure 1-3 Schematic of a 3-bus system example. Thus, the philosophy for modern transmission system operation can be summarized as follows: “Optimal utilization of the existing transmission network subject to both system limits and security requirements”. “Optimal” can mean, among other things, minimum fuel cost, maximum loadability, or minimum loop flows, depending on the goals pursued. System limits are threefold: thermal limits on transmission lines, voltage profile limits, and stability limits. The security requirement, known as (n−1) contingency criterion, is that the system must satisfy the same quality standard even when any of its facilities has an outage. In order to satisfy these new needs, power engineers have developed the concept of Flexible AC Transmission Systems, FACTS [1-3]. 26 1.2 Power Flow Control through FACTS Technology The basics of power flow control can be understood by considering a purely inductive transmission line connecting two buses, as suggested in Figure 1-4(a). (a) A purely inductive transmission line (b) A transmission line with an embedded FACTS device Figure 1-4 Schematic Illustrating Power Flow Control through a Transmission Line. Using elementary phasor ideas it can be shown that the complex power flow measured at the bus 1 of the line is given by, S = P + j⋅ Q = V1V2 V2 V V sin θ + j ⋅ ( 1 − 1 2 cos θ) X X X (1-1) where P and Q are the active and reactive power, respectively. It can be seen from Equation (1-1) that value of the power flow depends upon four parameters, namely, the magnitude of the voltage at each bus, V1 and V2, the transmission angle, θ, and the line reactance, X. Consider now the insertion of a FACTS device as shown in Figure 1-4(b)1. By means of a power electronics−based control, FACTS devices are able to modify one (or 1 The symbol shown in the figure has been introduced in [14] to represent a generic FACTS device. 27 more) of the parameters that define the power flow equation, and therefore realize power flow control. This simple but powerful idea is the core of FACTS technology. It is evident from Equation (1-1) that the modification of any of the parameters affects both the active and reactive power simultaneously. Table 1-1 shows the sensitivity functions of the complex power with respect to the system parameters for a typical set of values encountered in a power system. Table 1-1 Complex Power Sensitivities. V1=V2=1pu, θ=10°, X=0.5pu. ∂→ ∂↓ θ X V1 P Q 1.97 0.35 -0.69 -0.06 0.35 2.03 As can be seen, the transmission angle and the line reactance have a much bigger relative influence on the active power while the value of the bus voltage mostly affects the value of the reactive power. Thus, the control of either the transmission angle or the line reactance can be considered as active power compensation whereas the control of the bus voltage can be considered as reactive power compensation. This decoupling effect has been successfully used in other areas of power engineering as well, such as the DC power flow method [4, 5]. As will be discussed in the Literature Review Section, the power electronics−based control can take different forms, with semiconductors with no gate turn−off (only gate turn−on), or with power devices with gate turn−off capability, depending on the application pursued [6]. 28 1.3 Dynamic Compensation of Power System with FACTS Devices Although the focus of this research is on steady state power flow control, it is important to mention that FACTS devices can also enhance the various types of stability limits of a power system [7]. With respect to the large−signal stability, it can be shown by means of the equal area criterion [4], that FACTS devices can enlarge the stability margin of a system upon a short−circuit fault. In the small−signal stability arena, it can be demonstrated that FACTS are able to damp power oscillations that occur as a result of minor system disturbances. Finally, voltage stability can also be improved as FACTS devices are able to reshape the nose−curve [5, 8]. 1.4 Literature Survey Although the concept of FACTS was introduced by Dr. Narain G. Hingorani as a response of modern power systems needs, the aim of controlling power flows in transmission network is not new. Ever since power systems were conceived, there was an interest in controlling the power flows through the transmission network. The literature review can be performed by following the evolution that the power flow control technology has featured throughout the years. Figure 1-5 shows the various technologies that have been applied to effectively realize power flow control. 29 Figure 1-5 Power Flow Control Evolution. The earliest devices conceived for power flow control, well before the introduction of FACTS, are the mechanically switched phase−shifter and tap−changer transformers. The former control the transmission angle and therefore realize active power flow control whereas the latter control the bus voltage to realize reactive power compensation [4]. These devices, although still broadly used, have two major drawbacks. Since they are mechanically switched, they are difficult to operate and have a slow speed of response. Moreover, since they have a small number of tap positions, they can only act in a discrete way. With the development of semiconductor devices, however, proposals have been made to realize the switching with for example, back−to−back thyristors, in 30 order to improve the speed of response [9, 10]. In addition, hybrid approaches embedding DC−AC inverters have been proposed for the purpose of achieving continuous control [11, 12]. The invention of the mercury valve allowed the development of the high voltage direct current (HVDC) transmission technology [7, 13]. Modern semiconductors such as the thyristor, GTOs and IGBTs have also been use to realize HVDC systems. The basic idea behind HVDC technology is to cascade a rectifier, a DC−link, and an inverter. The DC−link can be either a capacitor or an inductor, leading to a voltage or current sourced system, respectively. The control takes place in the rectification and inversion process, as the firing angle (or the pulse duration) can be externally manipulated. These systems can continuously control the active power and in the case of converters with gate turn−off capability, they can realize independent reactive power flow control as well. In addition, HVDC interties feature the unique property of decoupling the AC dynamics of the systems being interconnected and, as a result of this, they can be used to interconnect systems operated at different frequency, as it is done, for example, in the Itaipu interconnection, that joins the 60Hz Brazilian system with the 50Hz Paraguayan system. The major disadvantage of these systems is the high rating needed for the semiconductors. They have to carry the entire power throughput and consequently the cost is high. Phase controlled devices correspond to the next technology that came about and are consider the first generation of FACTS controller [14]. Based on thyristors, they come in two flavors. The shunt connected device, called Static Var Compensator (SVC) [7, 14], injects an adjustable amount of reactive power in to the system and as a result of the 31 sensitivities explained in Table 1-1 is credited as a voltage regulator. The series connected device called Thyristor Controlled Series Capacitor (TCSC) [7, 14], can continuously adjust the reactance of the transmission line hence realizing active power flow control. Moreover, as these controllers do not involve any change of frequency to realize the power flow function, they may be considered AC↔AC devices. The development of high−power semiconductors with turn−off capability paved the way to the next generation of engineers from SIEMENS FACTS devices. Led by Dr. Laszlo Gyugyi, a group of have developed the Static Synchronous Compensator (STATCOM) [15], the Static Synchronous Series Compensator (SSSC) [16], the Unified Power Flow Controller (UPFC) [17], and the Interline Power flow Controller (IPFC) [18]. Together, these devices constitute the family of voltage source DC link power flow controllers that have been unified under the Convertible Static Compensator (CSC) [19]. Figure 1-6 shows the various ways these devices are embedded into a transmission line. (a) The shunt connected STATCOM (b) The series connected SSSC Transmission line 1 DC link Transmission line 2 (c) The shunt−series connected UPFC (d) The series−series connected IPFC Figure 1-6 Schematic diagrams of DC link realizations for power flow control. 32 The and TCSC STATCOM i. e., the and the STATCOM SSSC have, respectively, an analogous function to the provides voltage support and the SSSC SVC injects quadrature voltage into the line hence realizing active power flow control. The UPFC can simultaneously and selectively provide voltage support, and realize active and reactive power through the line. Lastly, the IPFC can provide series compensation to two (or more) transmission lines and also allow transfer of real power between the cross−connected lines. It is important to notice that for each of these devices the inverter realization as well as the modulation strategy can take different forms [20]. Finally, a few devices that follow the approach of fast switching direct AC↔AC conversion without frequency change to realize power flow control have recently appeared in the literature. The research has been conducted in terms of matrix converter [21] based power flow controllers [22, 23] and in terms of more restricted configurations such as the vector switching converter (VeSC) [24-28]. As may be observed from Figure 1-5 (left part), there has been a continuous push and pull between DC link and AC link technology, driven mostly by the availability of switching power semiconductors. This research focuses on the next leap introducing fast switching FACTS devices with the potential of better performance and controllability. 33 1.5 State− −of− −the− −Art The current state−of−the−art for FACTS controllers may be conveniently divided into two categories. The Convertible Static Compensator installed in the Marcy Substation in New York may qualify as the state−of−the−art already available technology while the concept of distributed FACTS devices may be eligible for the state−of−the−art technology still in a research stage. 1.5.1 The Convertible Static Compensator The Convertible Static Compensator (CSC), installed at the Marcy 345 kV substation in Central New York, has been developed through a joint effort between the New York Power Authority (NYPA), SIEMENS Power Transmission & Distribution, and the Electric Power Research Institute (EPRI) [19]. It can be considered as the unification of the various DC link FACTS devices described in Figure 1-6, as it can adapt to operate as a STATCOM, SSSC, UPFC or IPFC. The general CSC configuration shown in Figure 1-7 consists of two 100MVA inverters, two 100MVA series transformers, and a single 200MVA shunt transformer with two identical secondary windings. The low voltage disconnect switches allow utilization of the two inverters in various shunt and series configurations, resulting in eleven different configurations. 34 Line 1 To New Scotland Line 2 To Coopers Corners Figure 1-7 Schematic of the Marcy Substation CSC. This device is already operative and has proven its versatility in controlling the Marcy 345kV bus voltage as well as in regulating the power flow on the Marcy−New Scotland and Marcy−Coopers Corners lines. 1.5.2 Distributed FACTS The concept of distributed FACTS (D−FACTS) has very recently been introduced [29]. The idea is to use low rated power converters that can be (i) mass−manufactured, (ii) massively dispersed, and (ii) remotely operated to realize power flow control. The proposal, shown in Figure 1-8, consists of Distributed Static Series Compensator (DSSC) modules realized by means of a small rated (~10 kVA) single phase 35 DC link voltage source inverter and a single turn transformer, along with associated controls, power supply circuits and built−in communications capability. Figure 1-8 Distributed Static Series Compensator (DSSC) Schematic. As shown in the above figure, the module consists of two parts that can be physically clamped around a transmission conductor. The transformer and mechanical parts of the module form a complete magnetic circuit only after the module is clamped around the conductor. The weight and size of the DSSC module is low, allowing the unit to be suspended mechanically from the power line. The module is self−excited from the power line itself. The unit normally sits in bypass mode until the inverter is activated. Once the inverter is turned on, the DSSC module can inject a quadrature voltage into the line, allowing a “small” power flow control action. The overall system control function is achieved by using a large number of modules coordinated through communications and 36 smart controls. As can be seen, the state−of−the−art corresponds to FACTS devices based on DC link voltage source converters. The research proposed in this thesis represents an alternative to this technology. 1.6 Outline of the Research The background necessary to understand AC link power flow controllers is provided in Chapter 2. The concept of the vector switching converter (VeSC) is introduced, along with the corresponding converter model, equivalent circuit, switch realization, and modulation strategy. In some of the applications pursued in this thesis, VeSCs commute between phase−shifted voltage sources of equal magnitude. For that purpose, multiple−secondary phase−shifter transformers are also discussed. Chapter 3 is the core of this thesis proposal. It introduces a new family of FACTS devices: the Π−controller, the Ξ−controller and the Γ−controller. Based on the vector switching converter, these devices feature functional characteristics similar to the ones encountered in the voltage source HVDC interties, the Static Synchronous Series Compensator (SSSC) and the Unified Power Flow Controller (UPFC), respectively. The control function, however, is realized by direct AC↔AC conversion without frequency change, adopting the strategy of pulse width modulation (PWM). In Chapter 4, generalized averaging theory is used to develop the dynamical model for the controllers proposed in Chapter 3. Averaging theory is a generalization of the concept of dynamic phasors and becomes especially useful when the natural modes of 37 the physical system are located in the vicinity to the switching frequency. It that case, it gives a more accurate description of the system behavior, as it is able to capture the dynamics of the waveforms’ ripple. Using the dynamical model developed in Chapter 4, closed loop regulation is assessed in Chapter 5. In the case of the Ξ−controller, the regulator design is performed analyzing the frequency response of the small−signal transfer function. The ideas of security margins for stability are used as design criteria. The Γ−controller regulator design is briefly discussed and proposed as a part of the future work. For the series compensation case, this new technology is contrasted against the state−of−the−art in Chapter 6. A detailed comparative study between the Ξ−controller and the SSSC shows that the use of VeSC−based power flow controllers may become a real alternative for the next generation of FACTS devices. In order to fully prove the concept of VeSC−based power flow controllers, a laboratory prototype was built and tested. The Γ−controller was chosen for experimental verification, as its topology is the most general of all three controllers. These results are presented in Chapter 7. Chapter 8 gives a system point of view of the power flow control problem, incorporating the Ξ−controller into an optimal power flow (OPF) program. A case study of the IEEE 39−bus system shows that the economic dispatch as well as control of the power exchange between control areas can be enhanced by embedding the Ξ−controller into the transmission lines. Optimal power flow with Γ−controllers is proposed as a part of the continuing research. Finally, the conclusions and continuing work for this dissertation are given in 38 Chapter 9. All computations throughout this thesis were executed using the MATLAB mathematical analysis software package. Simulations were developed using MATLAB’s simulator package SIMULINKTM. 39 Chapter 2 Vector Switching Converters 2.1 Introduction This chapter introduces the three−phase vector switching converters as well as multiple−secondary phase−shifter transformers. The former represent the foundations to realize AC link power flow control while the latter is an auxiliary tool needed in some applications. 2.2 Three− −Phase Vector Switching Converters The principles of operation of three−phase vector switching converters (VeSC) have been described in detail in [26]. Although their realization and applications for power flow control can take various forms, herein the attention is focused on point−to−point applications. More generalized configurations and operations may be found in [26]. 2.2.1 Converter Model A schematic of an N throw single pole three−phase VeSC is illustrated in Figure 40 2-1. The system synthesizes an adjustable three phase pole voltage (VP(A-C)) by switching among N stiff three−phase voltage sources (VT1(A-C), VT2(A-C)… VTN(A-C)). VT1A IT1A VT1B IT1B VT1C IT1C VT2A IT2A t1A SA t2A tNA t1B SB VPA IPA VT2B IT2B t2B VPB IPB VT2C IT2C tNB VPC IPC VTNA ITNA t1C SC t2C VTNB ITNB tNC VTNC ITNC Figure 2-1 Circuit schematic of a three-phase VeSC synthesizing an adjustable pole voltage obtained from N throws. The throws of the switches are assumed ideal for the purpose of the discussion herein, as is common in preliminary functional analysis of switching power converters. These assumptions include: (i) negligible forward voltage drop of the switch throws in their on−state; (ii) sufficient on−state current carrying capacity and off−state voltage blocking capacity commensurate and compatible with the voltage and current ratings of the system; and (iii) negligible transition periods between open and closed of the switch throws that permit repetitive high frequency switching. Furthermore, the nominal frequency of the three−phase voltages and currents (power frequency) are assumed 41 identical, in the absence of which there could be no net steady state power transfer among them. The voltages at the throw terminals of the switch are assumed stiff such that their variations during a switching period can be neglected. Similarly, the switch pole currents are assumed stiff such that their variations over a switching period can be neglected. These assumptions essentially allow the focus to be on the power transfer process and the functional features. In practical power converters, filter elements appropriately applied at the input and output ports of the system would ensure that these assumptions are valid. Snubber circuits may further be applied to provide for appropriate commutation features during the finite transition periods between switch states. It is important to notice that in AC systems, the designation of the stiff voltage and stiff currents is arbitrary. Stiff voltage sources and stiff current sources can be transformed into either by adding series inductors or shunt capacitors, respectively, in order to fit application considerations. As indicated in Figure 2-1, the three poles are ganged together i.e., they switch concurrently between the throws to which they are connected. This can be mathematically expressed as tiA = tiB = tiC = ti, for i = 1, 2…N. The transfer properties can be represented using the vector equations consisting of three components for each of the terminal quantities. In this case, the vectors representing the throw voltages, throw currents, pole voltages and pole currents become VTi = [VTiA VTiB VTiC]T, ITi = [ITiA ITiB ITiC]T, VP = [VPA VPB VPC]T, IP = [IPA IPB IPC]T respectively, for i=1,2…N. Thus, the pole voltage and throw currents can be expressed as, 42 N VP (t) = ∑ q i (t) ⋅ VTi (2-1) i =1 I Ti (t) = q i (t) ⋅ I P for i = 1, 2,…N 1 where q i (t) = 0 if t i is closed otherwise (2-2) is the switching function of a throw connecting the voltage VTi to the current IP. When the repetition frequency of the switching function (or simply the switching frequency) is large with respect to the power frequency, net power transfer between the voltage ports and the current ports arises from the average value (DC component) of the switching function. The DC component of the switching function may be readily represented by the duty ratio of the particular throw. Thus, under proper assumptions (discussed in Chapter 4), the transfer relationships (2-1) and (2-2) may be simplified as N VP (t) = ∑ d i (t) ⋅ VTi (2-3) i =1 I Ti (t) = d i (t) ⋅ I P for i = 1, 2,…N (2-4) where the duty ratio of the ith throw is defined as 1 d i (t ) = TS t + TS ∫ q ( τ ) ⋅ dτ i for i = 1, 2...N t where TS is the switching period. As may evident from the definition of q(t), (2-5) 43 N ∑ d i (t) = 1 (2-6) i =1 Since the operating principle of these converters is based on controlling the connectivity between various three−phase AC voltage and/or current vectors by switching among their components concurrently, these converters have been termed vector switching converters [26]. The distinguishing features of vector switching converters as compared to matrix switching converters have been explored also in [26]. 2.2.2 Equivalent Circuit Relationships (2-3) and (2-4) indicate a reciprocal input↔output transfer property similar to that of a transformer. Therefore, the fundamental component averaged vector (or single−phase) equivalent circuit of the converter system may be represented as shown in Figure 2-2. Figure 2-2(a) describes the input↔output reciprocal relationships explicitly as dependent sources, while Figure 2-2(b) implicitly represents them in the form of a magnetically coupled transformer with winding turns ratios equivalent to the duty ratios of the throws. 44 VT1 VT1 d1IP IT1 1/d1 d1VT1 + VT2 d2IP + dNVT1 VTN VT2 d2VT1 IP + dNIP VP IT2 1/d2 VTN 1 IP ITN 1/dN (a) Controlled source coupling (b) Magnetic coupling Figure 2-2 Single−phase equivalent circuit of a VeSC. As is evident in either realization, the net pole voltage, VP, depends on the value (magnitude and phase) of the throw voltages as well as the corresponding duty ratios. These equivalent circuits may be conveniently utilized to derive and study the application of three−phase vector switching converter for AC power flow control by incorporating them in power system load flow and dynamic analysis programs. Figure 2-3 shows the realizable pole voltage values, represented by the gray shaded region in the phasor plane, for different combinations of throw voltages and number of throws. 45 VT3 VT1 VT3 VT4 VT1 VT2 VˆP VT4 VT2 (a) Quadruple−throw switch with random magnitude/phase throw voltages (b) Quadruple−throw switch with random magnitude/phase throw voltages and one redundant throw voltage. VT2 VT2 VˆP VˆP VT3 VT1 VT3 VT1 VT4 (c) Triple−throw switch with identical magnitude, 120° phase−shifted throw voltages (d) Quadruple−throw switch with identical magnitude, 90° phase−shifted throw voltages Figure 2-3 Region of pole voltage obtainable for different throw realizations. Figure 2-3(a) and Figure 2-3(b) show realizable pole voltage with arbitrary voltages (VT1–VT4) available for each of the throws (1−4). It may be observed that the region of the realizable pole voltages is given by the largest polygon whose vertices are the locations of the corresponding throw voltages and the phasor origin. For power flow control applications [14, 19], one is usually interested in synthesizing voltages within symmetric regions in all directions about the origin, which would be given by the largest circle that can be inscribed inside the polygon about the origin. It can be seen in Figure 2-3(a) that there is a large unused area outside the circumference. Figure 2-3(b) shows that not only is it impossible to trace a complete 46 circle circumference but also that there is a redundant voltage source, namely VT2. On the other hand, Figure 2-3(c) and Figure 2-3(d) show symmetric realizations with three throws and four throws, respectively. The adaptation of these realizations for power flow control will be explored in Section 2.3. 2.2.3 Switch Realization Although the operation of the VeSC converter presented in Figure 2-1 does not require the three−phase AC sources and loads to be balanced, the analytical development presented herein is limited to the case of balanced sources and loads. Since balanced three−phase AC systems may operate as three wire systems, the reference terminal that provides the return path for the three−phase currents carries no current (shown in gray line on Figure 2-1) and may be eliminated. As a result, due to inherent symmetry in three−phase voltage and current waveforms, when all the three−phase AC ports are three wire systems, the throws may be realized using bi−directional current conducting, but unidirectional voltage blocking capability as illustrated in Figure 2-4 in terms of IGBT−diode pairs. Other devices such as GTOs may be used instead of IGBTs in order to fit rating considerations. 47 Figure 2-4 IGBT-Diode realization for the switch. 2.2.4 VeSC Pulse Width Modulation Pulse Width Modulation (PWM) is widely used to create the train of pulses that define the converter switches output waveform [30, 31]. ON times, which create a desired low−frequency target The basic strategy is to switch at the intersection of a reference signal and a high−frequency carrier signal. The reference signal carries the information that defines the properties of the target waveform whereas the carrier signal defines the switching frequency. The main advantage of PWM is that it moves the harmonics generated from the switching process to frequencies high enough to make filtering possible with smaller components [32]. All PWM algorithms have to address the following three fundamental issues [30]: • Switch pulse width calculation • Switch pulse position within a carrier interval • Switch pulse sequence within a carrier interval 48 Thus, depending on the strategy selected, the target output waveform will feature the properties needed for the specific application. For power flow control applications using the vector switching converter, both input and output waveforms have the same frequency, therefore there is no frequency change and, similarly to the case of PWM DC/DC converters, a simple algorithm that compares the duty ratio against a sawtooth carrier signal can be used to generate the pulses. Figure 2-5 graphically shows the process to determine the width of the pulses for a triple throw single pole switch. As can be seen, it uses a predetermined sequence (d1, d2 d3 in this case) and turns a switch on every time the accumulated references intercept the carrier signal. In addition, every time a switch is turned on, the previous switch in sequence in turned off. The practical implementation of this strategy is presented in Figure 2-6 in a Simulink/DSP environment. It takes the duty ratios as inputs and compares the corresponding summations against the carrier signal. The output of these comparisons are transformed into Boolean variables and then manipulated as shown in the figure in order to fit the restriction of turning off the previous switch in the sequence when the current switch in turned on. Finally, the various signals are transformed back into real numbers to generate the pulses. This process can be readily generalized to any number of throws by simply adding more duty ratios in Figure 2-5 and Figure 2-6. In addition, in order to fit practical applications, adequate dead times should be added to avoid switches ON−states 49 overlapping. Figure 2-5 Waveforms Illustrating Pulse Width Modulation for Vector Switching Converters. The performance of this strategy clearly depends on the sequence selected to aggregate the duty ratios. Any arrangement would produce the same fundamental 50 frequency waveforms, but the harmonics content would vary depending on the sequence selected. Optimal sequence arrangement can be designed for a specific application but such a topic is beyond the scope of the present study. 1 d1 2 d2 3 d3 > + + + + + > > True=1 False=0 NOT NOT AND double 1 P1 double 2 P2 AND Boolean Stage double Back to Real Numbers 3 P3 Carrier Figure 2-6 A Simulink/DSP strategy to generate the gate pulses described in Figure 2-5. 2.3 Multiple− −Secondary Phase− −Shifter Transformer The synthesis of multiple throws is an essential requirement for using vector switching converters as power flow controllers some applications. Indeed, as can be seen in Figure 2-3, the adjustable pole voltage is realized by switching among different stiff voltage sources. Three−phase systems feature the property that, given one set of three−phase voltages, it is possible to synthesize multiple electrically isolated sets of voltages using multi−winding transformers. Consider the four−winding three−phase transformer presented in Figure 2-7(a). The windings drawn parallel are physically located in the same magnetic path. All 51 windings are Y−connected and one of them corresponds to the primary while the remaining three make a multiple−secondary set. Since there are three sets of three−phase windings at the secondary side, three isolated voltage sets are created, say {A1, B1, C1}, {A2, B2, C2} and {A3, B3, C3}. Moreover, as a result of the convenient phase designation given to the various windings, the corresponding phase−to−neutral voltage of each set is 120° phase−shifted with respect to each other, as shown in the corresponding phasor diagram presented in Figure 2-7(b). Thus, using vector notation, the various sets can be expressed as VT1=[A1 B1 C1]T, VT2=[A2 B2 C2]T and VT3=[A3 B3 C3]T. It readily follows that the phasor diagram for the vectors VT1, VT2 and VT3 is as shown if Figure 2-3(c) and therefore this four−winding three−phase transformer can be used to generate such throws. n2 n1 n2 n2 Figure 2-7 A four−winding three phase transformer to generate three secondary vector voltages 120° phase−shifted. 52 The major drawback of the topology introduced above is the relatively large unused area outside the circle in Figure 2-3(c). Specifically, for a given magnitude of the throw voltages, say VT, the maximum pole voltage that can be obtained is V̂P = VT / 2 . This limitation can be improved considering the topology sketched in Figure 2-8(a). The transformer in this case has five three−phase windings. The primary side winding is ∆−connected while in the secondary side there are two windings ∆−connected and two Y−connected. In addition, as suggested in Figure 2-8(a), the turn ratio of the ∆−connected windings is 3 times the turn ratio of the Y−connected windings. Thus, with the phase designation given in Figure 2-8(a), it is possible to create four vector throws phase−shifted 90° with respect to each other, as shown in the phasor diagram of Figure 2-8(b). n2 n2 3 n1 n2 n2 3 Figure 2-8 A five−winding three−phase transformer to generate four secondary vector voltages 90° phase−shifted. 53 Similar to the case with three secondary windings, by defining the vector voltages as VT1=[A1 B1 C1]T, VT2=[A2 B2 C2]T, VT3=[A3 B3 C3]T and VT4=[A4 B4 C4]T, it can readily be seen that they resemble the phasor diagram shown in Figure 2-3(d). For this topology, the maximum obtainable pole voltage is V̂P = VT / 2 , which represents a significant improvement with respect to the topology with three secondary windings. In order to obtain larger useful pole voltage, other configurations with six or more secondary winding might be developed but they lack practicality due to the large number of windings needed. 54 Chapter 3 3.1 AC Link Power Flow Controllers Introduction This chapter introduces the family of power flow controllers proposed in this research work: the Π−controller [24], the Ξ−controller and the Γ−controller [25]. These devices are based on the vector switching converter (VeSC) and feature similar functional properties as some of the DC link controllers discussed Chapter 1. Specifically, as will become evident through this chapter, there is an intimate correlation between the Π−controller, the Ξ−controller and the Γ−controller and the HVDC intertie, the Static Synchronous Series Compensator (SSSC) and the Unified Power Flow Controller (UPFC). Although functionally AC link controllers are similar to their DC link counterparts, the control function is realized by direct AC↔AC conversion without frequency change, adopting the strategy of pulse width modulation (PWM). As stated in Chapter 1, the HVDC intertie, the SSSC and the UPFC appeared in the literature chronologically in that order, so in this chapter the same tendency is chosen, introducing first the Π−controller, followed by the Ξ−controller and the Γ−controller. 55 3.2 Π−Controller: An AC Link Back− −to− −Back Intertie DC link interties have been extensively used to interconnect AC systems throughout the world. They feature the unique property of decoupling the dynamics of the systems being interconnected and, as a result, they can be used to interconnect systems operated at different frequencies. However, the most important property of these devices is the ability to continuously and independently control the active and reactive power flow through them. The latter property can also be achieved by using AC link interties based on the vector switching converter, as suggested in Figure 3-1. Figure 3-1 Schematic of a VeSC−based AC link intertie. In this section, the details on the implementation of the vector switching converter to function as an intertie are provided, along with computer simulation results that validate the approach. 3.2.1 Topology The schematic of the configuration proposed is presented in Figure 3-2. The main 56 goal is to control the power flowing across the two three−phase AC systems, namely the sending System S and the receiving System R. As indicated in the figure, the intertie is configured by including a phase−shifting transformer (SPT), filter capacitors (TFC), a quadruple throw−single pole three−phase VeSC, and boost transformer (BIT). Figure 3-2 Topology of a VeSC −based AC link intertie. The transformer SPT has the double function of lowering the voltage to the level where the switches can safely operate and of simultaneously phase−shifting the input voltage in 0, 90, 180 and 270° to generate four sets of three−phase voltages of equal magnitude. The capacitor bank TFC is used to absorb the high frequency currents introduced due to switching process from permeating into the system across the transformer. The controlled voltage is synthesized at the poles by modulating the duty ratios d1, d2, d3, d4. Finally, the transformer BIT located at the receiving side raises the voltage to the corresponding level 57 of the receiving end. 3.2.2 Equivalent Circuit By following the procedure explained in Chapter 2, the single−phase averaged equivalent circuit shown in Figure 2-3 can readily be obtained. As can be seen, the controlled source approach has been chosen to represent the converter. In addition, the turn ratios of transformer STP have been made complex numbers in order to reflect the corresponding phase−shift. Notice as well that the Systems S and R have been replaced by their Thévenin equivalent circuits. Although resistive elements are not shown in the figure, they may be easily added to represent the power losses throughout the various stages. Figure 3-3 Single−Phase averaged equivalent circuit. This equivalent circuit may be conveniently utilized to derive and study the 58 application of VeSC−based interties for AC power flow control by incorporating them in power system load flow and dynamic analysis programs. 3.2.3 Principle of Operation In order to understand the principle of operation, consider a purely inductive link between the sending end system S and the receiving end system R, as indicated in Figure 3-4(a). Also, assume that the voltages VS and VR have equal magnitude, say V, and they are displaced by a transmission angle of, say θ°. (a) Systems S and R connected via a purely inductive link (b) System S and R connected via an inductive link plus the intertie. Figure 3-4 The ideal AC link intertie. Under these assumptions, the power flow equations are V2 sin θ P= X Q S = −Q R = (3-1) V2 (1 − cos θ) X (3-2) 59 Now consider a fully ideal AC link intertie i.e., both transformer SPT and BIT are ideal and have unity turn ratio and also the reactive power injected by the capacitor bank FTC is negligible so it may be removed. Under these assumptions, the equivalent circuit of the intertie sketched in Figure 3-2 may be further reduced to the equivalent circuit presented in Figure 3-4(b). The turn ratio of the transformer is given by D = (d1 − d 3 ) + j (d 2 − d 4 ) = d13 + j d 24 and reflects both the phase−shift introduced by (3-3) SPT transformer as well as the action of the converter. Now the power flow equations take the form of, V2 [d13 sin θ + d 24 cos θ] X V2 2 QS = (d13 + d 224 − d13 cos θ + d 24 sin θ) X P= QR = V2 (d13 cos θ − d 24 sin θ − 1) X (3-4) (3-5) (3-6) Equations (3-4) through (3-6) along with restriction imposed by the continuity of the converter i. e., d1 + d 2 + d 3 + d 4 = 1 (3-7) fully described the ideal AC link intertie. Equations (3-4) through (3-6) also show that the 60 duty ratio differences d13 and d24 give two degrees of freedom that can be conveniently chosen to control P and Q at one of the ends. In addition, as can be seen from Figure 3-4, the equivalent circuit has two legs in shunt that resemble the Greek letter pi, Π, so the AC link intertie can be termed Π−controller. Although it is strictly valid only for the ideal case, it is convenient for visualization purposes to represent the feasible range of values for the various duty ratios in d13─d24 plane, as shown in Figure 3-5. Values inside the “unity” rhombus only are valid for the duty ratio differences, given the restriction of non−negativity for each duty ratio (di≥0, for i=1..4) as well as the continuity equation. In the real case, the response of the converter also depends on d i2 factors, but it is largely dominated by the duty ratio differences, that is, a given set point {P,Q} is determined mostly by a duple {d13, d24}. Figure 3-5 The “unity” rhombus. Permissible duty ratio values. 61 3.2.4 Control Capabilities Although the model presented in the previous section demonstrates the control capabilities, a more realistic model would account for the effect of the transformers as well as the capacitor bank. A 110kV/100MVA/60Hz case−study system was developed to explore the performance of the intertie further. In reference to Figure 3-2, consider the system S (modeled as a stiff voltage source of VS = 1∠0 pu) is connected to the system R (modeled as a stiff voltage source of VR = 1∠ − 20 pu) through a resistive−inductive link of Z L = 0.34∠86 pu. Thus, without the Π−controller embedded, one would measure {Ps=1pu Qs=0.1pu} and {PR=0.99pu QR=─0.2pu} at the sending and receiving end, respectively. This will be considered as the base case for the following discussion. Now consider the insertion of the Π−controller, say at the midpoint of the link, splitting it into two equal impedances ( ZS = Z R = 0.17∠86 pu). The turn ratio of transformers SPT and BIT were selected to be ap=10:1 and as=1:20, respectively. Typical values were selected for the parasitic elements of the transformers. Finally, the capacitor bank was selected to be XC=3pu. Refer to the Design Considerations Section for further details on the selection of these values and to the Appendix 1 for the complete list of parameters. Next, based on the operating point described above, various control strategies are discussed. The attention is focused on the sending end control variables, namely, PS and 62 QS. 3.2.4.1 Active Power Control Figure 3-6(a) and (b) show the values of d13 and d24 that must be set in order to transmit active power in the range {-2pu, 2pu} shown on the horizontal axis, with zero reactive power maintained at the sending end. Figure 3-6(c) shows the corresponding reactive power needed at the receiving end. d1 - d3 1 0 -1 d2 - d4 1 0 -1 QR(pu) 1.5 1 0.5 0 -2 -1.5 -1 -0.5 0 0.5 1 1.5 2 Figure 3-6 Variation of sets of duty ratios, (a), (b) and reactive power at receiving end, (c) as a function of active power control while Qs=0pu and θ=─20°. It can be seen that control points around PS=0pu are achieved at a high requirement of reactive power at the other end, therefore becoming impractical. However, that can be solved by local reactive power injection at the bus, as it is done in some HVDC ties [13]. Although the reactive power at the sending end was set at QS=0pu in this example, it can be set at any other reasonable value that may be desired. 63 Since the intertie can transfer power in both directions, it can be named as a back−to−back system and the terms sending and receiving ends become interchangeable. 3.2.4.2 Reactive Power Control Figure 3-7(a) and (b) show the values of d13 and d24 that must be set in order to regulate the reactive power at the sending end within the range {-1pu, 1pu} shown on the horizontal axis, with the active power transfer fixed at PS=1.5pu. Figure 3-7(c) shows the corresponding reactive power needed at the receiving end. d1 - d3 1 0 -1 d2 - d4 1 0 -1 QR(pu) 1 0 -1 -1 -0.8 -0.6 -0.4 -0.2 0 0.2 0.4 0.6 0.8 1 Figure 3-7 Variation of sets of duty ratios, (a), (b) and reactive power at receiving end, (c) as a function of reactive power control while PS =1.5pu and θ=─20°. As can be seen from Figure 3-7(c), the intertie can provide voltage support (QS<0 and QR>0) at both ends while keeping a fixed level of active power transfer. 64 3.2.4.3 Angle Control Figure 3-8(a) and (b) show the values of d13 and d24 that must be set in order to keep a given transfer level while the transmission angle θ is varied within the range {90°, 90°} shown on the horizontal axis. Figure 3-8(c) shows the corresponding reactive power needed at the receiving end. The excellent performance of the intertie as a phase−shifting controller is evident from Figure 3-8(c). It can keep PS, QS and QR at a fixed level for a wide transmission angle range. 1 0 -1 1 0 -1 1 0.5 0 -80 -60 -40 -20 0 20 40 60 80 Figure 3-8 Variation of sets of duty ratios, (a), (b) and reactive power at receiving end, (c) as a function of phase−shifting control while PS =1.5pu QS=0pu. 65 3.2.5 Design Considerations 3.2.5.1 Parameter Calculations As a general rule, power converters need filter capacitors across the throw terminals and filter inductors in series with the pole terminals [33]. In the Π−controller, the pole terminals appear in series with the boost transformer SIT and the transmission line. These elements provide enough series inductance naturally, eliminating the need for separate filter reactors. On the other hand, at the throw terminals, filter capacitors are needed to isolate the high frequency currents introduced due to the switching process from propagation into the transformer SPT, and further into the system. However, as the capacitors bank appears directly shunt−connected into the systems, it ends up playing an undesired major role on the reactive power balance of the entire system. Furthermore, the selection of the turn ratios of both phase shifting and boost transformers also plays an important role in system operation. The turn ratio of the transformer at the sending end also must be compatible with voltage levels where the switches can safely operate. Hence, the capacitors bank and both transformer turn ratios must be selected to simultaneously fulfill the various system requirements. Detailed time−domain simulations showed that the capacitive reactance needs to be less than 5pu in order to realize satisfactory system performance. With that bound, and recognizing the operation at zero reactive power at both ends to be a desirable target under a wide range of power flow conditions, the process of finding an acceptable set of design parameters can be formulated as an optimization problem. By running 66 optimizations at various points within the range of active power control (-2pu to 2pu in this case), it is possible to converge to a set of values that satisfactorily meet the system requirements. For the system data specified in Appendix 1, XC=3pu and turn ratios aP=0.1 and aS=20 give acceptable performance. 3.2.5.2 Feasible operating range The full feasible operating range for the Π−controller can be obtained by mapping the unity rhombus from Figure 3-5 into the PS−QS plane, which is sketched in Figure 3-9(a). However, this operating nomogram is only theoretical, due to the enormous values of reactive power needed to realize some of the operating conditions. Thus, only a subset of these operating conditions is practical. By discarding all the impractical points (accepting a maximum of 1pu of reactive power at both ends), the operating nomogram becomes restricted as illustrated in Figure 3-9(b). This corresponds to a subset of the region from Figure 3-9(a). The axis of the figure has been changed to emphasize the practical feasible region. It can be seen that the resulting restricted operating region still provides a wide range of controllability, with a limited variation in duty ratios, especially with low levels of reactive power requirements, validating the proposed design process. 67 6 4 2 0 -2 2 1 0 -1 -2 -3 -2 -1 0 1 2 3 Figure 3-9 Complex Power Nomogram at the sending end. (a) Entire operating range, (b) restricted and more practical operating range. 3.2.6 Simulation Results A detailed computer simulation model of the system shown in Figure 3-2 was developed to verify the operation of the Π−controller at various operating conditions. The switching frequency to operate the converter was selected to be FS=2.4kHz. The base values and per unit values of the parameters used in the computer simulation example are shown in Appendix 1. As an illustration, consider the base case described in the Control Capabilities Section. It was stated that, without the Π−controller embedded, one would measure {Ps=1pu Qs=0.1pu} at the sending end. Now, by inserting the Π−controller, the operating point described by {Ps=2pu Qs=0pu} is selected as target, that is, the active power transfer will be doubled while reducing to zero the requirements of reactive power. From 68 either the power nomogram or the equivalent circuit, the values for the duty ratios for this condition are easily obtainable: d1=66%, d2=17.4%, d3=16.6%, d4=0. With these duty ratio values, the simulation is executed, whose results are described next. Figure 3-10 shows the terminal variables at the sending end over a 60Hz cycle. As can be seen, the voltage and current appear approximately in−phase so the reactive power is zero. In addition, these waveforms have been perunitized with respect to their maximum base values, therefore it can be implied that the active power is effectively PS=2pu, as predicted early. Figure 3-10 Phase−A voltage and current waveforms at the sending end. Figure 3-11 shows the same waveforms but at the receiving end. Although the fundamental components agree with the predictions made by the equivalent circuit, the 69 main drawback of this approach becomes evident. The rich harmonics content makes the feasibility of the Π−controller dependent upon big−sized output filters, which may be impractical at the power level considered. Figure 3-11 Phase−A voltage and current waveforms at the receiving end. 3.2.7 Summary This section has introduced the Π−controller: an application of the vector switching converter acting as a back−to−back intertie. A simplified illustration of the system was used to demonstrate the principles of power flow control using duty ratio modulation. Reactive power control, active power flow control and voltage phase shift were variables identified as controllable. The capabilities of the system under different modes of operation were demonstrated using more detailed transformer equivalent circuit 70 model. The variation of duty ratio and power flow quantities under three different operating modes was demonstrated. The results from a computer simulation of the system including the dynamics of the switching process were presented to validate the approach. A brief discussion of design considerations indicates the trade−offs in the design of converter parameters. Although the capabilities of operation of the converter have been illustrated by analytical methods and their feasibility has been demonstrated using computer simulations, the power rating of the converter system and harmonics content are seen as major limitations of the approach. Therefore, further augmentation of the approach by embedding the converter in a shunt−series configuration such as the UPFC is seen to be advantageous in reducing the power converter throughput in relation to the controlled power flow. The operation of such a configuration is the subject of Section 3.4. In addition, since with present technology this FACTS device seems impractical, it will not be discussed further in this thesis. 3.3 Ξ−Controller: An AC Link Series Compensator The concept of transmission lines compensation by means of series capacitor has its roots in elementary phasor ideas. Transmission lines have inductive reactance that can be compensated by adding series capacitive reactance. This very simple concept has prompted many different devices throughout the years. First, mechanically switched fixed capacitors were installed onto transmission lines to provide a static amount of 71 reactive compensation. Then, with the development of power semiconductors, devices such us the Thyristor Controlled Series Capacitor (TCSC) and the Static Synchronous Series Compensator (SSSC) have been developed. The former has the ability of continuously controlling the equivalent impedance of the line whereas the latter can inject a variable amount of quadrature voltage into the line. Both devices though seek the same ultimate goal of controlling the active power through the line. In this section, yet another approach to seek the same goal is described. Using the vector switching converter as a controller, it is possible to modulate the amount of capacitance injected into a transmission line, as suggested in Figure 3-12. Figure 3-12 Schematic of a VeSC−based AC link series compensator. This device has already been introduced in the literature [34] in a slightly different context. In this thesis, it is adapted onto the formalisms of AC link vector AC link series switching power flow controllers. 3.3.1 Topology Figure 3-13 shows the detailed three−phase realization of the 72 compensator. As can be seen, the double throw−single pole three−phase VeSC commutes between a fixed capacitor bank and a short circuit node. As a result of the switching, a controlled amount of capacitance is generated which is injected into the line via the SIT transformer. Figure 3-13 Topology of a VeSC−based AC link series compensator. Notice as well that the requirements of stiff voltage at the throw side and stiff current at the pole side are naturally given by the compensation capacitors and the leakage inductance of the SIT transformer, respectively. 3.3.2 Equivalent Circuit By following the procedure explained in Chapter 2, the single−phase averaged 73 equivalent circuit shown in Figure 3-14 can readily be obtained. As can be seen, the controlled source approach has been chosen to represent the converter. Notice as well that the systems S and R, the transmission line impedances, and the secondary−side impedance of the transformer (the one in series with the transmission line), have all been aggregated into Thévenin equivalent circuits. Figure 3-14 Single−Phase Averaged Equivalent Circuit. This equivalent circuit may be conveniently utilized to derive and study the application of VeSC−based AC link series capacitors for AC power flow control by incorporating them in power system load flow and dynamic analysis programs. 74 3.3.3 Principle of Operation In order to understand the principle of operation, consider the same situation as in Section 3.2.3, repeated here for convenience. A purely inductive transmission line is connecting the sending end system S and the receiving end system R, as indicated in Figure 3-15(a). Also, assume that the voltages VS and VR have equal magnitude, say V, and they are displaced by a transmission angle of, say θ°. (a) Systems S and R connected via a purely inductive transmission line (b) System S and R connected via a transmission line plus an AC link compensation capacitor. Figure 3-15 The ideal AC link series compensator. Under these assumptions, the active power flow is given by V2 P= sin θ X (3-8) Now consider the AC link series compensator is connected into transmission line by an ideal transformer. Under this assumption, the equivalent circuit of the converter and the SIT transformer can be combined into one as suggested in Figure 3-15(b). By 75 reflecting the capacitor into the transmission line−side of the transformer, the active power flow equation takes the form of, P= V2 sin θ X − d2XC (3-9) where X C = 1 / ω p C is the 60Hz impedance of the capacitor. It becomes evident that by modulating the duty ratio of the converter, it is possible to control the active power flow through the transmission line. In addition, as can be seen from 3-15(b), the equivalent circuit has two legs in series that resemble the Greek letter xi, Ξ, so the AC link series compensator can be termed Ξ−controller. 3.3.4 Control Capabilities A 110kV/100MVA/60Hz case study system was developed to explore the performance of the Ξ−controller further. In reference to Figure 3-13, consider the system S (modeled as a stiff voltage source of VS = 1∠0 pu) connected to the system R (modeled as a stiff voltage source of VR = 1∠ − 20 pu) through a transmission line of Z L = 0.24∠85 pu. Thus, without the Ξ−controller embedded, the active power at the receiving end would be PR=1.4pu. This will be considered as the base case for the following discussion. 76 Now consider the insertion of the Ξ−controller splitting the transmission line into impedances ( Z S = 0.17∠86 pu and Z R = 0.07∠82 pu). The turn ratio of the SIT transformer was selected to be 1:1. Typical values were selected for the parasitic elements of the transformer. Refer to the Appendix 2 for the complete list of parameters. The reactance of the compensation capacitor was selected to be XC=0.05pu so it can provide a maximum compensation of around 20% of the transmission line impedance base value. Figure 3-16(a) show the variation of the equivalent impedance as a function of the duty ratio, and Figure 3-16(b) show the corresponding active power at the receiving end. Figure 3-16 Equivalent impedance (a) and power at the receiving end (b) as a function of the duty ratio. It can be seen that the control only becomes effective for values greater than d=30% This is due to the quadratic nature of control action, as can be observed in 77 Equation (3-9). 3.3.5 Design Considerations As may be evident from Equation 3-9, the maximum degree of compensation is achieved when d=100%. Therefore, this operating point determines the rating of the various devices. The design process starts with deciding the maximum degree of compensation for the transmission line. This allows computation of the capacitance as, C = 1 / (ωP ⋅ %Compensation ⋅ XL) (3-10) where XL is the line impedance. Since for maximum compensation the capacitor appears directly in series with the transmission line, it has to handle the transmission line maximum current. Therefore, the voltage and kVAs can be respectively determined as, VC=IL⋅ XC (3-11) SC=VC⋅IL (3-12) where IL is the maximum line current. Finally, since the converter as well as the SIT transformer is cascaded with the capacitor, they have to handle the same kVAs as the capacitor. In addition, it is well known that capacitive series compensation introduces a 78 resonance between inductive reactance of the transmission line and the compensation capacitor. The resonant frequency can be determined as FR = d ⋅ FP ⋅ XC XL (3-13) where FP is the power frequency of the transmission system. As may be evident from the last equation, the resonance frequency varies between zero and a maximum values as the duty ratio is varied between zero and unity. Thus, if there exist system modes at resonance frequencies of sustained operation, the dynamic effect should be assessed to prevent Subsynchronous Resonances (SSR). 3.3.6 Simulation Results A detailed computer simulation model of the system shown in Figure 3-13 was developed to verify the operation of the Ξ−controller at various operating conditions. The switching frequency to operate the converter was selected to be FS=2.4kHz. The base values and per unit values of the parameters used in the computer simulation example are shown in Appendix 2. Figure 3-17 shows, over a 60Hz period, the perunitized waveforms of the voltage injected into the transmission line as well as the line current for a typical operating point. As expected, the current leads the fundamental component of the voltage by exactly 90° so the Ξ−controller is providing reactive power only. 79 Figure 3-17 Phase−A Current and Injected Voltage shown over a 60Hz period. Although the voltage waveform appears to be rich in harmonics, it only represents a small percentage of the transmission line voltage, therefore the actual phase−to−ground as well as the phase−to−phase voltages are mostly free of harmonics. As an illustration of the open loop dynamic performance of the Ξ−controller, consider the transition from operating at d=20% to d=80%. Figure 3-18 and Figure 3-19 show the response of the line current and the response of the measured power at the receiving end, when the duty ratio is stepped up or ramped up, respectively. 80 100 50 0 2 0 -2 1.2 1.1 1 0.9 0.9 0.95 1 1.05 1.1 1.15 1.2 1.25 1.3 Figure 3-18 Simulation results for a step−change of the duty ratio (a) from 20 to 80%. (b) and (c) show the response of the line current and the power at the receiving end, respectively. Figure 3-19 Simulation results for a ramp−change of the duty ratio (a) from 20 to 80%. (b) and (c) show the response of the line current and the power at the receiving end, respectively. 81 It can be seen that in both cases the system is able to stabilize although in the step case a significant overshoot is observed, suggesting that for open loop operation it would more appropriate to slowly tune the duty ratio. Closed loop operation will be studied in Chapter 5. 3.3.7 Summary This section has introduced the Ξ−controller: an application of the vector switching converter acting as a series compensator. A simplified illustration of the system was used to demonstrate the principles of power flow control using duty ratio modulation. It was demonstrated that, as other semiconductor−based series compensators, the Ξ−controller can continuously adjust the transmission line impedance and therefore realize active power control. The results from a computer simulation of the system including the dynamics of the switching process were presented to validate the approach. A brief discussion of design considerations indicates the trade−offs in the design of converter parameters. A quantitative comparison of Ξ−controller against its DC link counterpart (SSSC) is studied in Chapter 6. Γ− −Controller: An AC Link Unified Power Flow 3.4 Controller The DC link Unified Power Flow Controller (UPFC) has been presented as the 82 ultimate solution for power flow control in transmission network. This is due to its unique capabilities of simultaneously controlling the bus voltage and both the active and reactive power down the line [17]. However, it has been recognized, and also realized in practice, that the main operating mode is power flow control [17]. Bus voltage can usually be locally controlled at the substation. It has also been agued that by controlling the three parameters at the same time the system becomes unreliable upon the possible loss of the UPFC. Thus, controlling two parameters at a time seems to be the most suitable mode of operation. The AC link counterpart of UPFC is introduced in this section. The connection into the system, shown in Figure 3-20, is similar to the DC link UPFC but the topology as well as the control function is realized in a different manner. Figure 3-20 Schematic of a VeSC−based AC link Unified Power Flow Controller. This device can also simultaneously control the active and reactive power through a transmission line, therefore it can be thought of as a UPFC. 3.4.1 Topology Figure 3-21 shows the detailed three−phase realization of the AC link UPFC. The 83 central feature of the approach is to control the power flow along the transmission line by injecting an AC voltage with controllable magnitude and phase angle in series with the line. The system is configured by including a shunt phase−shifting transformer (SPT), filter capacitors (TFC), a quadruple−throw single−pole three−phase VeSC, and a series injection transformer (SIT). This system may be located at any point throughout the line. Figure 3-21 Topology of a VeSC−based AC link Unified Power Flow Controller. The SPT transformer (with four secondary winding sets) has the double function of lowering the impressed voltage to match the capability of the semiconductor switches and simultaneously phase−shifting the impressed voltage by 0o, 90o, 180o and 270° respectively, to obtain four sets of three−phase voltage vectors. This clearly resembles 84 the situation sketched in Figure 2-3(d), with (VT1−VT4) representing the throws. The SPT may be implemented as a five winding per leg three−phase transformer as indicated in Figure 3-21, where all the set of windings that are drawn parallel are magnetically coupled together and physically located in the same leg. The capacitor bank TFC is used to absorb the high frequency currents introduced due to switching from permeating into the system across the transformer. The VeSC uses a quadruple−throw single−pole three−phase switch to synthesize a controllable voltage at the pole terminals by modulating the duty ratios d1, d2, d3, d4. Invoking Figure 2-3(d) again, given the throw voltages generated by the SPT, the range of values the pole voltage can take is 0 ≤ VP ≤ V̂P for the magnitude, and 0 ≤ ∠VP ≤ 360 for the phase angle, both which can be independently controlled. Finally, the SIT transformer accommodates the voltage to an appropriate level to be injected back in series with the transmission line and also provides the necessary electrical isolation. It is important to note that the stiff voltage and stiff current requirements assumed in the previous section are given by the capacitor bank and SIT transformer leakage inductance, respectively. The SPT AC link UPFC system may also be realized by using a four−winding per leg transformer instead. In this case, the throws should be generated as shown in Figure 2-3(c), which is physically obtained by the transformer illustrated in Figure 2-7. This realization only needs triple throw−single pole switches and therefore is simpler and easier to control; however, as is evident from Figure 2-3(c), it needs higher throw 85 voltages to synthesize the same V̂P . 3.4.2 Equivalent Circuit By following the procedure explained in Chapter 2, the single−phase averaged equivalent circuit shown in Figure 3-22 can readily be obtained. As can be seen, the controlled source approach has been chosen to represent the converter. Notice as well that the systems S and R, the transmission line impedances, and the secondary−side impedance of the transformer (the one in series with the transmission line) have all been aggregated into the Thévenin equivalent circuit. In addition, the turn ratios of transformer STP have been made complex numbers in order to reflect the phase−shift introduced. Although resistive elements are not shown in the figure, they may be easily added to represent the power losses throughout the various stages. This equivalent circuit may be conveniently utilized to derive and study the application of VeSC−based AC link UPFC power flow control by incorporating them in power system load flow and dynamic analysis programs. 86 Figure 3-22 Single−Phase Averaged Equivalent Circuit. 3.4.3 Principle of Operation In order to understand the principle of operation, consider the same situation as in Sections 3.2.3 and 3.3.3, repeated here for convenience. A purely inductive transmission line is connecting the sending end system S and the receiving end system R, as indicated in Figure 3-23(a). Also, assume that the voltages VS and VR have equal magnitude, say V, and they are displaced by a transmission angle of, say θ°. Thus, the active and reactive 87 power flows through the transmission line are, respectively P= V2 sin θ X Q S = −Q R = (3-14) V2 (1 − cos θ) X (3-15) Consider now the insertion of the AC link UPFC at the sending end of the line. In order to limit the discussion to the principle of operation, assume that transformers and SIT SPT are ideal and have a unity transformation ratio. Furthermore, assume that the reactive power injection at the fundamental frequency due to the bank TFC is negligible so it may be removed. Under these assumptions, the single−phase equivalent circuit for the system as shown in Figure 3-23(b) can be readily obtained following the standard procedure described in Chapter 2. (a) Systems S and R connected via a purely inductive transmission line (b) System S and R connected via a transmission line plus an AC link Unified Power Flow Controller. Figure 3-23 The ideal AC link Unified Power Flow Controller. 88 The transformation ratio of the SPT transformer becomes, as in the case of the Π−controller, a complex quantity that may be represented as D = (d 1 − d 3 ) + j (d 2 − d 4 ) = d 13 + j d 24 reflecting the simultaneous phase−shifting introduced by the (3-16) SPT. Furthermore, in order to satisfy the continuity of switched variables of the VeSC, the duty ratio components must satisfy d1 + d 2 + d 3 + d 4 = 1 (3-17) The power flow equations now take the form of, P= V2 [sin θ − d 13 sin θ − d 24 cos θ] X QS = V2 2 2 [ 1 − cos θ + d13 + d13 cos θ − 2d13 + d 24 − d 24 sin θ] X V2 [cos θ − 1 − d 13 cos θ + d 24 sin θ] QR = X (3-18) (3-19) (3-20) Equations (3-18) through (3-20), along with (3-16)−(3-17) dictate the control capabilities of the ideal AC link unified power flow controller. It can be seen that, by choosing appropriate values for d13 and d24, it is possible to control either (P,QS) or (P,QR), that is, it can independently control the active power and reactive power at either end of the transmission line. In addition, for a given (P,Q) operating point, it can keep 89 such a point unchanged as the angle θ varies i.e., it has phase−shifting capabilities, or as the voltage V varies i.e., it also has tap−changer capabilities. Altogether, these capabilities are comparable to that of the DC link UPFC. Since the embedded transformer shown in Figure 3-23(b) has a leading shunt leg followed by a series leg coupled to it, the schematic has the appearance of the uppercase Greek letter gamma, Γ, so this particular interconnection may be termed Γ−controller. 3.4.4 Control Capabilities A 110kV/100MVA/60Hz case study system was developed to explore the performance of the Γ−controller further. In reference to Figure 3-21, consider the system S (modeled as a stiff voltage source of VS = 1∠0 pu) connected to the system R (modeled as a stiff voltage source of VR = 1∠ − 20 pu) through a transmission line of Z L = 0.24∠85 pu. Thus, without the Γ−controller embedded, the active and reactive power at the receiving end would be PR=1.4pu and QR=−0.36pu, respectively. This will be considered as the base case for the following discussion. Now consider the insertion of the Γ−controller splitting the transmission line into two impedances ( Z S = 0.07∠82 pu and Z R = 0.17∠86 pu). The turn ratios of the SPT and SIT transformers was selected to be 10 : 2 and 1:1, respectively. Typical values were selected for the parasitic elements of each transformer. Finally, the capacitor bank was selected to be XC=3pu. Refer to the Design Considerations Section for further details on 90 the selection of these values and to the Appendix 3 for the complete list of parameters. Next, based on the operating point described above, various control strategies are discussed. The attention will be focused on the receiving end control variables, namely, PR and QR. The discussion that follows will be based on the d13−d14 plane, with the variables of interest implicitly displayed. This is in contrast with the Control Capabilities Section for the Π−controller, where similar information was generated but with the controlled variables explicitly displayed. 3.4.4.1 Transmitted Power Control Figure 3-24 shows the operating plane of d13 and d14. Similar to Figure 3-5, the unity rhombus represents the operating boundaries in d13 and d24 that are realizable given the restrictions for each duty ratio. The three lines that are drawn inside the unity rhombus representing the loci of d13 and d24 that must be set in order to independently control a particular quantity as labeled. These lines take into account operating constraints of the design posed by the turn ratios of the transformers, size of the capacitor, voltage ratings of the different elements, etc. 91 θ = 20 Q max = 0.17 R PRmin = 1.01 PRmin = 0.95, Q max = −0.25 R Q min R = −0.81 PRmax = 1.83 PRmax = 1.90, Q min R = −0.50 Figure 3-24 Receiving−end power control. Thus, the line labeled as “Active Power” shows that the Γ−controller can vary PR in the range [1.01, 1.83] while keeping the rest of the parameters from the base case unchanged. Similarly, the line labeled as “Reactive Power” shows that the Γ−controller can vary QR in the range [-0.81, 0.17] while keeping the rest of the parameters from the base case unchanged. Furthermore, the line labeled “Both”, shows that it is possible to simultaneously control both the active and reactive power in such a way that the power factor (pf) at the receiving end remains constant. 3.4.4.2 Tap− −changing/phase− −shifting control Often during system operation, it may be desirable to deliver constant active and 92 reactive power at the receiving end, while the system operating conditions (VS, VR or θ) may vary. Figure 3-25 shows the values of d13 and d24 that must be set in order to deliver constant active and reactive power while either VS, VR or θ are changing within the specified range. VRmax = 1.12 θ = 20 θ max = 27 VSmax = 1.12 VSmin = 0.88 VRmin = 0.91 θ min = 14 Figure 3-25 Tap−changing, phase−shifting control. The line labeled as “Sending End Voltage” shows that the Γ−controller can maintain base operating conditions while VS varies in the range [0.88, 1.12]. Similarly, the line labeled as “Receiving End Voltage” shows that the Γ−controller can maintain base operating conditions while VR varies in the range [0.91, 1.12]. Furthermore, the line labeled “Transmission Angle,” shows that it is possible to simultaneously hold the active and reactive power received steady as the transmission angle θ varies in the range [14o, 27o]. 93 3.4.5 Design Considerations The major circuit parameters that need to be selected are the transformer turn−ratios, filter capacitors, and switching frequency. 3.4.5.1 Transformers turn ratio The main criteria driving the selection for the transformer turn ratios are the desired maximum voltage to be injected into the line and the voltage level at which the switches can safely operate. The former can be expressed as V̂P = a P a S VL / 2 , where aP, aS and VL are the SPT and SIT transformer turn ratios and the transmission line rated voltage, respectively. For the latter, the restriction is that aPVL<VB, where VB is the voltage−withstand capability of the switch. For the particular case studied here, a P = 2 / 10 and a S = 1 are selected. 3.4.5.2 Filter Capacitors / Switching Frequency As a general rule, switching power converters need filter capacitors across the throw terminals and filter inductors in series with the pole terminals. In the Γ−controller, the pole terminals appear in series with the injection transformer SIT and the transmission line. These elements provide enough series inductance naturally, eliminating the need for separate filter reactors. However, at the throw terminals, filter capacitors are necessary to isolate the high frequency currents introduced due to the switching process from propagation into the SPT transformer and further into the system. These capacitors also introduce resonances into the system (three different in this 94 case) so the capacitance needs to be carefully selected in order to obtain satisfactory performance. Figure 3-26 shows the variations of these resonance frequencies ( FR1 , FR2 and FR3 ) as a function of the capacitance. For each value considered for the capacitance, the resonance frequency for all possible values of the various duty ratios is computed. Thus, each entry in the scatter graph actually consists of a cluster of points. The resonance frequency FR1 (= 1 / 2 π L PS C ) is independent of the duty ratios. FR2 has some dependence on the duty ratios but is largely dominated by the term 1 / 2 π L PS C , as may be evident from the figure. However, FR3 results from the interaction between the capacitor and the rest of the system and is more sensitive to the duty ratios, as shown in the expanded plot in Figure 3-26, for a particular capacitance value. 5000 4500 FR1 4000 FR2 FR3 3500 375 370 3000 365 360 2500 355 350 2000 345 340 109 110 1500 FR3 1000 500 0 0 50 100 150 200 250 Figure 3-26 Resonance frequency as a function of the capacitor value. 95 On the other hand, the switching process introduces harmonics into the system with frequency of the form nFS ± FP (n=1,2,…∞), where FS and FP are the switching and power frequency, respectively [33, 35]. All of these frequencies must far exceed the resonances of the system in order to avoid excitation of such frequencies. Clearly the critical case is when n=1. Thus, since normally FP<<FS, it is sufficient to show that FS exceed the various resonances. As can be seen from Figure 3-26, this issue may be readily solved by choosing a large capacitance or a high switching frequency. However, neither of these solutions comes at low cost. A high switching frequency implies high switching losses whereas a large capacitance results in large physical size and reactive power circulation. Thus, the selection of the capacitor and switching frequency involves a difficult trade−off. For the particular case studied here, we select C=73µF and FS=2.4kHz, which provides sufficient operating margin, as indicated in the figure. 3.4.6 Simulation Results A detailed computer simulation model of the system shown in Figure 3-21 was developed to verify the operation of the Γ−controller embedded in a transmission system at various operating conditions. The complete set of parameters used in the computer simulation is shown in Appendix 3. The first case−study chosen for the simulation corresponds to moving from the base case stated in Control Capabilities Section i. e., PR=1.4pu and QR=−0.36pu, to a 96 new operating point given by PR=1.5pu and QR=0. This condition is achieved by setting the duty ratios to d1=0, d2=18%, d3=57% and d4=25%. Figure 3-27 shows, over a 60Hz period, the voltage/current waveforms at the receiving−end perunitized with respect to their maximum base value. It can be seen that the voltage and current waveforms are in−phase so QR=0 and the maximum values match the set point for 1.5pu active power (vR=1pu, iR=1.5pu). 2 1.5 1 0.5 0 -0.5 -1 -1.5 -2 0.25 0.255 0.26 0.265 0.27 0.275 0.28 Figure 3-27 Phase−A Voltage and Current at the receiving−end. Figure 3-28 and Figure 3-29 show the internal workings of the converter. Figure 3-28 shows, over a 60Hz period, the switch SA (refer to Figure 3-21 and Figure 3-22) throw voltages. As can be seen, they are 90° phase−shifted as predicted early. On the 97 other hand, Figure 3-29 shows the currents through the various terminal of phase−A transformer. As can be seen, harmonics, although the SPT SPT secondary currents (ips(1-4)) are rich in the actual current absorbed from the transmission line (isht) is fairly sinusoidal. 1 0 -1 1 0 -1 1 0 -1 1 0 -1 0.25 0.255 0.26 0.265 0.27 0.275 Figure 3-28 Phase−A Capacitor voltages. 0.28 98 1 0 -1 1 0 -1 1 0 -1 1 0 -1 1 0 -1 0.25 0.255 0.26 0.265 0.27 0.275 0.28 Figure 3-29 Phase−A SPT transformer currents. A second case study was developed to evaluate the open−loop dynamic response of the Γ−controller upon a change on the commanded duty ratios. The transition studied is a change on an operating point given by PS=1.2pu and QS=─0.2pu to a different one given by PS=1.5pu and QS=0pu. Two different simulations are carried out. First, the duty ratios are directly stepped to achieve the new operating point. Second, the duty ratios are ramped, within a 100ms interval, to smoothly move to the new operating point. Results for the step−change case are presented in Figure 3-30 and Figure 3-31. The former shows the commanded duty ratios whereas the latter shows the response of the line current, the active power, and the reactive power. As can be seen, the response is as a second−order system. Power oscillations take place, which are damped out after approximately seven 60Hz cycles. 99 40 20 0 40 30 20 60 40 20 30 20 10 0 0.9 0.95 1 1.05 1.1 1.15 1.2 1.25 1.3 Figure 3-30 Duty Ratio Commands. Stepped from d1=33%, d2=35%, d3=32% d4=0% to d1=0%, d2=18%, d3=57% d4=25%. 1 0 -1 1.6 1.4 1.2 1 0.1 0 -0.1 -0.2 0.9 0.95 1 1.05 1.1 1.15 1.2 1.25 1.3 Figure 3-31 Response to a duty ratio step change of the (a) line current, (b) active power and (c) reactive power, all at the receiving end. 100 Results for the ramp−change case are presented in Figure 3-32 and Figure 3-33. The former shows the commanded duty ratios whereas the latter shows the response of the line current, the active power, and the reactive power. As can be seen, the transition is free of oscillation, which makes the ramping strategy very attractive to be selected to actually operate the Γ−controller. 40 20 0 40 30 20 60 40 20 30 20 10 0 0.9 0.95 1 1.05 1.1 1.15 1.2 1.25 1.3 Figure 3-32 Duty Ratio Commands. Ramped from d1=33%, d2=35%, d3=32% d4=0% to d1=0%, d2=18%, d3=57% d4=25%. 101 1 0 -1 1.6 1.4 1.2 1 0.1 0 -0.1 -0.2 0.9 0.95 1 1.05 1.1 1.15 1.2 1.25 1.3 Figure 3-33 Response to a duty ratio ramp change of the (a) line current, (b) active power and (c) reactive power, all at the receiving end. 3.4.7 Summary This section has introduced the Γ−controller: an application of the vector switching converter acting as a unified power flow controller. It is capable of independently controlling the active and reactive power flow along a transmission line. The system consists of a multiple quadrature phase−shifting transformer operated in conjunction with multiple−throw three−phase switches, which are pulse width modulated to synthesize an adjustable voltage that is injected in series into the line. The capabilities of the Γ−controller under different modes of operation have been demonstrated using a detailed transformer equivalent circuit model. The results from a computer simulation of the system, including the dynamics of the switching process, have been presented to validate the approach. A brief discussion of design considerations 102 indicates the trade−offs in the design of converter parameters. The Γ−controller can be considered to be the AC link counterpart of the more classical UPFC system based on DC link voltage source converters (VSC). It is based on the well−established technology of classical phase−shifting transformers with solid−state electronic control using pulse width modulation. While the control capabilities of both approaches are similar as has been illustrated in this chapter, they utilize entirely different topological structures for the realization of the function. The utilizes well−established multipulse/multilevel VSC DC link based approach technologies with advanced high voltage, high current power semiconductor switching devices such as the gate turn−off thyristor with modest switching speeds. The integration of the multipulse VSC converters to realize high quality waveforms requires the use of multiple phase−shifting transformers. On the other hand, the AC link VeSC−based approach utilizes gate turn−off switch technology as well but is operated under pulse width modulation at reasonably high switching frequencies. Furthermore, it also utilizes multiple phase−shifting transformers to realize the topological functionality. While it can be shown that the throughput ratings of the power converters used in both the approaches will be identical, given identical range of operation and control capabilities, their cost, size and complexity involve complex trade−offs that are unclear at first glance. A more detailed comparison of the converter design aspects and their dynamic capabilities will reveal further trade−offs between the two approaches, which is proposed as one of the future research paths in Chapter 9. 103 Chapter 4 Dynamic Modeling of AC Link Power Flow Controllers 4.1 Introduction Dynamic modeling of vector switching converters can be performed based on traditional state space averaging techniques to predict performance at power frequencies. Using the equivalent circuits developed in Section 2.2.2, the dynamic phasors’ state space model can readily be obtained [8, 36-39]. While this approach provides results acceptable for the development of load flow models, it falls short in providing design−oriented information for the realization of these systems, particularly with respect to the sensitivity of circuit parameters. The main reason for this is that the switching frequencies attainable with these converters are only a small multiple of the power frequency, due to the high levels of power throughput involved in relation to the power capability of switching semiconductors. Therefore, the dynamic phenomena are often overwhelmed by interactions between power frequency, switching frequency and the natural modes inherent in the network structure. Thus, refinements to the classical state space averaging techniques are necessary to obtain better models for the system. Generalized averaging theory based on Fourier techniques have been developed to study switching frequency dynamics for DC−DC converters [40-44]. The goal of this chapter is 104 to extend generalized averaging tools for AC link power flow controllers to predict system behavior with fidelity that extends up to the switching frequency [35]. 4.2 Generalized Averaging Theory Generalized averaging theory has its roots [44] in the fact that a periodic signal x (τ) can be represented to an arbitrary accuracy on the interval τ ∈ [ t − T, t ] using Fourier series as x ( τ) = ∞ ∑ 〈 x〉 k ( t ) e jk ω τ (4-1) k = −∞ where ω = 2π / T is the corresponding frequency and th 〈 x〉 k ( t ) is the k Fourier th coefficient, also referred to as the k phasor or the index {k} average, given by: t 1 〈 x 〉 k ( t ) = ∫ x (τ) e − j k ω τ dτ T t −T (4-2) Notice that these Fourier coefficients are function of time as the interval [ t − T, t ] slides over the actual waveform. The aim is to determine an appropriate state space model in which the coefficients given by Equation (4-2) are the state variables. 105 These coefficients feature the properties listed below, which are key for applying averaging theory to describe the dynamic behavior of vector switching converters. 4.2.1 Index symmetry When x ( t ) is a real−valued waveform, it readily follows from Equation (4-2) that 〈 x 〉 − k ( t ) = 〈 x 〉 *k ( t ) (4-3) where 〈⋅〉 * stands for the complex conjugate of 〈⋅〉 . 4.2.2 Reconstruction It can be shown using Equation (4-1) that the reconstruction formula takes the form of ∞ Im x (τ) = 〈 x 〉 0 (τ) + 2∑ [〈 x 〉 Re k ( τ) cos( kωτ) − 〈 x 〉 k ( τ) sin( kωτ)] (4-4) k =1 where the super indices 〈⋅〉 Re and 〈⋅〉 Im stand for real and imaginary components of 〈⋅〉 , respectively. 106 4.2.3 Derivative with respect to time Differentiating Equation (4-1) yields the following formula to express the derivative of the kth phasor with respect to time d d 〈 x〉 k ( t ) = − j ω k 〈 x〉 k (t ) + 〈 x〉 k ( t ) dt dt 4.2.4 (4-5) Average of a product Using Equation (4-1), the index {k} average of a product can be expressed by means of the following discrete convolution relationship 〈 x y〉 k ( t ) = ∞ ∑ 〈 x〉 k −i ( t ) 〈 y〉 i ( t ) (4-6) i = −∞ 4.3 Dynamics for electric elements As will become evident in the next section, the index {k} dynamics for the various elements present in electric power systems are needed to develop the state space models using generalized averaging theory. Next, the index {k} dynamics for resistors, inductors and capacitors are developed. 107 4.3.1 Resistor The equation that governs the dynamic of a resistive element is the well−known Ohm’s Law, v( t ) = R ⋅ i( t ) (4-7) Averaging both sides of Equation (4-7) and since averaging is a linear operator, it readily follows that the index {k} dynamics for a resistor is, 〈 v〉 k ( t ) = R ⋅ 〈i〉 k ( t ) 4.3.2 (4-8) Inductor Voltage and current are related in an inductor through Faraday’s Law as, v( t ) = L ⋅ di( t ) dt (4-9) Averaging the above equation and using Equation (4-5) the index {k} dynamics for an inductor becomes, 〈 v〉 k ( t ) = L d 〈i〉 k ( t ) + j ω kL〈i〉 k ( t ) dt (4-10) 108 4.3.3 Capacitor The terminal current−voltage relationship for a capacitive element is, i( t ) = C ⋅ dv( t ) dt (4-11) With a similar argument as in the inductor case, the index {k} dynamics for a capacitor becomes, 〈 i〉 k ( t ) = C d 〈 v〉 k ( t ) + j ω kC〈 v〉 k ( t ) dt 4.4 (4-12) Application to State Space Models for Vector Switching Converters Vector switching converters realize power flow control synthesizing a desirable pole voltage obtained by switching among stiff−voltage throws. The requirements of stiff voltage at the throw side and stiff current at the pole side are obtained by respectively adding capacitors and inductors. The switch itself is modeled by means of controlled sources, where the switching function q(t) takes the discrete values of {0,1} at a switching frequency, say FS, depending on the position of the switch. Furthermore, 109 vector switching power flow controllers are embedded in power systems excited by sinusoidal voltage sources at a power frequency, say FP. This is schematically described in Figure 4-1. Figure 4-1 Schematic of a generic power system with a vector switching converter embedded. The development of the state space model shows that the differential equation that governs the system has the form of d x ( t ) = A (q ( t )) x ( t ) + Bu ( t ) dt (4-13) where the state vector, x(t), corresponds to a collection of capacitor voltages and inductor currents, and the input vector, u(t), corresponds to a collection of excitation voltages. Notice that the Linear Time Variant (LTV) system described by Equation (4-13) has no approximations whatsoever i.e., q(t) represents the true switching function and the excitation voltages embedded in u(t) are the sinusoidal waveforms. Due to the discrete nature of q(t), the exact determination of the states from Equation (4-13) in an extremely difficult problem. The classical approach has been to, under proper assumptions, directly replace the 110 switching function q(t) by the duty ratio d(t). This makes the system described by Equation (4-13) continuous and therefore solvable. The key underlying assumption for this is that the switching frequency should exceed both the power frequency and the natural modes of the physical system. Under these conditions, the ripple becomes negligible and the response of the states is largely dominated by the interaction between the DC component of the switching function (i.e., the duty ratio) and the excitation frequency quantities. Indeed, the response becomes independent of the switching frequency. However, in the case of vector switching converters, this assumption may not always be satisfied. Switching at high frequency may not be possible due to the inherent switching losses. Thus, the need for a more refined method becomes evident. Generalized averaging provides the framework in which the dynamic modeling for vector switching power flow controllers can be achieved at an arbitrary accuracy. Thus, the analysis, component sizing, and control design can be performed with a greater degree of accuracy. To apply the generalized averaging scheme to a system described by Equation (413), it is necessary that the system have a unique identifiable period. In the state equation presented above, however, there are two different periods: the power period TP associated with ve(t) and the switching period TS associated with q(t). Therefore, averaging would not be applicable if TP and TS were arbitrarily chosen. However, that limitation can be overcome if the analysis is restricted to the special case when the ratio power period/switching period is an integer number, say N, because then the switching function 111 is also TP−periodic. Averaging (4-13), the index {k} differential equation takes the form of 〈 d x 〉 k ( t ) = 〈 A (q ( t )) x ( t ) + Bu ( t )〉 k dt (4-14) Using the fact that averaging is a linear operator and also using (4-5), the equation above can be further reduced to d 〈 x 〉 k ( t ) = − j ω k 〈 x 〉 k ( t ) + A ' 〈 q ( t ) x ( t )〉 k + B〈 u ( t )〉 k dt (4-15) where A’ can readily be deduced from A(q(t)). The simplifying task now becomes the representation of 〈 q ( t ) x ( t )〉 k in Equation (4-15) to a summation of various terms at distinct frequencies using the convolution property (4-6). Therefore, it is first necessary to develop expressions for q(t) and x(t) in terms of their corresponding phasors. As stated earlier, q(t) is a TS−periodic function so in terms of the power period (TP=N⋅TS) it can be expressed as q(t ) = ∞ ∑ 〈 q〉 Nk (t ) e j Nk ω p t k = −∞ Expanding this series, (4-16) 112 q ( t ) = 〈 q〉 0 + 〈 q 〉 N e jN ωp t + 〈 q〉 − N e − jN ω P t + ∞ ∑ 〈 q〉 Nk e j Nk ω p t (4-17) k = −∞ k ≠ 0 ,1, −1 Notice that the time dependency for the phasor quantities has been dropped to avoid notational clutter. Since the interest is to capture phenomena at switching frequency, the switching function is approximated by its three first terms. Therefore, Equation (4-17) becomes q( t ) ≈ 〈 q〉 0 + 〈 q〉 N e j N ωp t Conceptually + 〈 q〉 − N e this j N ωp t corresponds (4-18) to augmenting the switching function representation by including the fundamental component in addition to the traditional representation of the duty ratio only, as suggested in Figure 4-2, shown for the particular case of d=50%. This allows capture of the high frequency (ripple) dynamics in the state space model. 113 Figure 4-2 Waveforms corresponding to the switching function, index {0} approximation (duty ratio) and index {0, -N, N} approximation. All with d=50%. On the other hand, it is known that x(t) is a TP−periodic function but its harmonics content is not known a−priori. Therefore, it will be assumed that the harmonics are all present, i.e., x(t) = ∞ ∑< x > k e jk ωp t (4-19) k = −∞ Now it is possible to apply Equation (4-6) to obtain the various index averages that result from the product 〈 q ( t ) x ( t )〉 k , 114 〈q x 〉1 = 〈q〉 0 〈 x 〉1 + 〈 q〉 − N 〈 x 〉 ( N +1) + 〈q〉 N 〈 x 〉 − ( N −1) (4-20) 〈 qx 〉 N −1 = 〈 q〉 0 〈 x 〉 N −1 + 〈 q〉 N 〈 x 〉 −1 (4-21) 〈 q x 〉 N +1 = 〈 q 〉 0 〈 x 〉 N +1 + 〈 q 〉 N 〈 x 〉 1 (4-22) 〈 q x 〉 −1 = 〈 q〉 0 〈 x 〉 −1 + 〈 q〉 − N 〈 x 〉 N −1 + 〈 q〉 N 〈 x 〉 − ( N +1) (4-23) 〈q x 〉 − ( N −1) = 〈 q〉 0 〈 x 〉 −( N −1) + 〈 q〉 − N 〈 x 〉 1 (4-24) 〈 qx 〉 − ( N +1) = 〈 q〉 0 〈 x 〉 − ( N +1) + 〈 q〉 − N 〈 x 〉 −1 (4-25) 〈 qx 〉 g = 〈 q〉 0 〈 x 〉 g (4-26) g ≠ ±1, ±(N-1), ± (N+1) In order to exploit certain properties, the various indices presented above are grouped into (a) positive group: index {1, (N-1), (N+1)}; (b) negative group: index {-1, (N-1), -(N+1)}; and (c) zero group: index {g}. The above equations can be notably simplified by examining the nature of the excitation functions. Although the excitation frequency is always ωP (usually 2π⋅60Hz), the actual excitation index can take two different forms, as discussed next. 4.4.1 Real Excitation When the three−phase system is balanced and no phase shifts are introduced by transformers (resulting from a ∆−Y connection, for example), the equivalent circuit may be represented by only one of the three−phases (usually phase A). The other two phases carry no extra information as they are just a phase−shifted repetition of phase A. Hence, 115 for a three−phase system given by VA ( t ) = 2V sin(ω P t + θ) (4-28) VB ( t ) = 2V sin(ω P t + θ − 120) (4-29) VC ( t ) = 2V sin(ω P t + θ + 120) (4-30) the excitation in the single−phase equivalent circuit takes the form of, u ( t ) = 2 V sin(ω P t + θ) (4-31) In terms of the average index, u(t) can be expressed as ∞ u (t ) = ∑ 〈 u〉 k (t ) e jk ωp t = 〈 u〉 1 e j ωp t + 〈 u 〉 −1 e − j ωp t (4-32) k = −∞ where, 〈 u〉 1 = 〈 u 〉 −1 = V 2 (sin θ − j ⋅ cos θ) V 2 (sin θ + j ⋅ cos θ) (4-33) (4-34) 116 Notice that since u(t) is a real−valued waveform, 〈 u 〉 −1 = 〈 u 〉 1* . Thus, considering the expression for the index products and the series expansions for the excitation waveforms, the averaged dynamics given by Equation (4-15) becomes d 〈 x 〉 1 = − j ω P 〈 x 〉 1 + A '{〈 q〉 0 〈 x 〉 1 + 〈 q〉 − N 〈 x 〉 ( N +1) + 〈 q〉 N 〈 x 〉 − ( N −1) } + B〈 u 〉 1 dt (4-35) d 〈 x 〉 N −1 = − j ω P ( N − 1)〈 x 〉 N −1 + A '{〈 q〉 0 〈 x 〉 N −1 + 〈 q〉 N 〈 x 〉 −1 } dt (4-36) d 〈 x 〉 N +1 = − j ω P ( N + 1)〈 x 〉 N +1 + A '{〈 q〉 0 〈 x 〉 N +1 + 〈 q〉 N 〈 x 〉 1 } dt (4-37) d 〈 x 〉 −1 = j ω P 〈 x 〉 −1 + A '{〈q〉 0 〈 x 〉 −1 + 〈 q〉 − N 〈 x 〉 N −1 + 〈 q〉 N 〈 x 〉 − ( N +1) } + B〈 u 〉 −1 dt (4-38) d 〈 x 〉 −( N −1) = j ω P ( N − 1)〈 x 〉 − ( N −1) + A '{〈 q〉 0 〈 x 〉 − ( N −1) + 〈 q〉 − N 〈 x 〉 1 } dt (4-39) d 〈 x 〉 −( N +1) = j ω P ( N + 1)〈 x 〉 −( N +1) + A '{〈 q〉 0 〈 x 〉 −( N +1) + 〈q〉 − N 〈 x 〉 −1 } dt (4-40) d 〈 x 〉 g ( t ) = − j ω P g 〈 x 〉 g + A '{〈 q〉 0 〈 x 〉 g } dt (4-41) g ≠ ±1, ±(N-1), ± (N+1) The examination of Equations (4-35) through (4-41) brings to the discussion two important conclusions: (i) Since the excitation is at index {-1, 1} only, the state variables from the zero group have no forcing function and therefore do not exist whatsoever, assuming no initial condition at those indices. Therefore, Equation (4-41) can be eliminated, 117 as it bears no information. (ii) Since the input signals are real−valued waveforms, positive−index variables are the complex conjugate of the corresponding negative−index variable, therefore it is possible to solve the positive group or the negative group independently of each other. Moreover, each of them gives a closed−form solution for the state variables and therefore can be used to predict the dynamic behavior of the entire system. Therefore, the initially infinite number of averaged differential equations described by (4-15) has been reduced to three differential equations, namely Equations (4-35) through (4-37). Notice the final number of variables is (two) x (three) x (number of original states). Each original state is augmented by three ( x ( t ) → 〈 x 〉 1 ( t ), 〈 x 〉 N −1 ( t ), 〈 x 〉 N +1 ( t ) ) and by two after separating in real and imaginary parts each complex index variable. These equations, as mention before, described the dynamics of a phase−shift free balanced power systems with vector switching power flow controllers embedded. 4.4.2 Complex Excitation In the case of a power system with phase−shifting elements, it is necessary to generalize the notion of the single−phase equivalent circuit introduced in the previous section. For example, as discussed in Section 2.3, for the case of multiple secondary transformers, the desired 90° phase−shift on the secondary side voltage VA2 was obtained 118 by designating as phase A the corresponding primary side voltage VBC. The notion of complex state vectors [38] fits perfectly in this framework as complex vectors carry the information concerning the three phases simultaneously. Complex vectors are defined as x V (t) = 2 ( x A ( t ) + γx B ( t ) + γ ∗ x C ( t )) 3 where γ = e j 2π 3 (4-42) . The real and imaginary parts of the space vector are equal to the α and β components when the three−phase quantities are transformed to the Clarke’s αβ stationary reference frame [45]. For balanced systems, there is a simple inverse transformation, x A ( t ) = Re( x V ( t )) x B ( t ) = Re( γ * x V ( t )) x C ( t ) = Re( γx V ( t )) (4-43) Applying this transformation to the set of balanced voltages described by Equations (428) through (4-30), the state vector for the excitation voltages becomes u ( t ) = 2V (sin(ω P t + θ) − j ⋅ cos(ω P t + θ)) In terms of the average index, u(t) can be expressed as (4-44) 119 u (t ) = ∞ ∑ 〈 u〉 k (t ) e jk ωp t = 〈 u〉 1 e j ωp t (4-45) k = −∞ where, 〈 u 〉 1 = 2V (sin θ − j ⋅ cos θ) (4-46) Notice that in contrast with the previous case, now the only excitation index is {1}. Thus, considering the expression for the index products and the series expansions for the excitation waveforms, the averaged dynamics given by Equation (4-15) becomes d 〈 x 〉 1 = − j ω P 〈 x 〉 1 + A '{〈 q〉 0 〈 x 〉 1 + 〈 q〉 − N 〈 x 〉 ( N +1) + 〈 q〉 N 〈 x 〉 − ( N −1) } + B〈 u 〉 1 dt (4-47) d 〈 x 〉 N −1 = − j ω P ( N − 1)〈 x 〉 N −1 + A '{〈 q〉 0 〈 x 〉 N −1 + 〈 q〉 N 〈 x 〉 −1 } dt (4-48) d 〈 x 〉 N +1 = − j ω P ( N + 1)〈 x 〉 N +1 + A '{〈 q〉 0 〈 x 〉 N +1 + 〈 q〉 N 〈 x 〉 1 } dt (4-49) d 〈 x 〉 −1 = j ω P 〈 x 〉 −1 + A '{〈q〉 0 〈 x 〉 −1 + 〈 q〉 − N 〈 x 〉 N −1 + 〈 q〉 N 〈 x 〉 − ( N +1) } dt (4-50) d 〈 x 〉 −( N −1) = j ω P ( N − 1)〈 x 〉 − ( N −1) + A '{〈 q〉 0 〈 x 〉 − ( N −1) + 〈 q〉 − N 〈 x 〉 1 } dt (4-51) d 〈 x 〉 −( N +1) = j ω P ( N + 1)〈 x 〉 −( N +1) + A '{〈 q〉 0 〈 x 〉 −( N +1) + 〈q〉 − N 〈 x 〉 −1 } dt (4-52) d 〈 x 〉 g ( t ) = − j ω P g 〈 x 〉 g + A '{〈 q〉 0 〈 x 〉 g } dt (4-53) g ≠ ±1, ±(N-1), ± (N+1) 120 As in the case with real excitation, the examination of Equations (4-47) through (4-53) brings to the discussion two important conclusions: (i) Since the excitation is at index {1} only, the state variables from the zero group have no forcing function and therefore do not exist whatsoever, assuming no initial condition at those indices. Therefore, Equation (4-53) can be eliminated, as it bears no information. (ii) Since the only equation that exhibits excitation is (4-47), the indices present on that equation {1, N+1, -(N-1)} represent the corresponding state variables that are different than zero. Thus, Equations (4-48), (4-50) and (4-52) may also be eliminated, as they have no forcing function on the RHS. Therefore, the initially infinite number of averaged differential equations described by (4-15) has been reduced to three differential equations, namely Equations (4-47), (4-49) and (4-51). As in the case of the real excitation, the final count for variables is (two) x (three) x (Number of original states). These equations described the dynamics of a balanced power systems with vector switching power flow controllers embedded. Since this is a generalization of the case with real excitation, it should be noted that the vector space approach may also be used in the case of a power system fully Y−connected. The final time−domain waveforms should be identical. The augmented schemes developed above have the advantage of incorporating the 121 ripple into the model and therefore could be used for design purposes in the sense that the predicted RMS quantities give a better approximation of the actual stress that the various devices will have to tolerate. Also, closed−loop regulators that are switching frequency dependent can be designed and therefore capture phenomena that are out of reach with the traditional approach of approximating the switching function by the duty ratio only. Finally, note that when approximating the switching function by the duty ratio only, the traditional state space in terms of dynamic phasors is recovered. This will become evident in the following examples. The number of variables in this case is (two) x (number of original states). 4.5 Case Studies In this section the techniques of generalized averaging are applied to the modeling of the Ξ−controller and the Γ−controller. In the Ξ−controller case, the advantages towards the design process are investigated, whereas in the Γ−controller case the attention is focused on the dynamic performance. 4.5.1 Generalized Averaging Applied to the Ξ−controller 4.5.1.1 The Model In order to develop the generalized averaged model, consider the equivalent 122 circuit for Ξ−controller presented in Figure 3-14, but now the converter is modeled directly using the switching function rather that the duty ratio. As usual, the switching function q(t) takes values {0,1} according to a switching frequency FS (or ωS) and a duty ratio d. This is shown in Figure 4-3. Figure 4-3 Exact model for the Ξ−controller. Let the sending end voltage and receiving end voltage be represented as v S ( t ) = 2V sin(ω P t ) and v R ( t ) = 2V sin(ω P t + θ) , respectively. Considering i(t) and v(t) as state variables, the instantaneous state equation takes the form of R d i( t ) − L = dt v( t ) q ( t ) C − q(t ) 1 L i( t ) + v ( t ) L SR 0 v( t ) 0 (4-54) 123 where R = R S + R R , L = L S + L R + L T and v SR ( t ) = v S ( t ) − v R ( t ) . Since this is a phase−shifting free system, the rules developed for real excitation apply. Hence, the generalized averaged state space model becomes 〈 q〉 0 〈q〉 *N 〈 q〉 N d R 1 〈 i〉 1 = ( − j ω p − ) 〈 i〉 1 − 〈 v〉 1 − 〈 v〉 N +1 − 〈 v〉 *N −1 + 〈 v SR 〉 1 dt L L L L L (4-55) 〈q〉 N 〈 q〉 0 d R 〈i〉 N −1 = (− j ω p ( N − 1) − )〈i〉 N −1 − 〈 v〉 N −1 − 〈 v〉 1* dt L L L (4-56) 〈 q〉 N 〈 q〉 0 d R 〈i〉 N +1 = (− j ω p ( N + 1) − )〈i〉 N +1 − 〈 v〉 N +1 − 〈 v〉 1 dt L L L (4-57) 〈 q〉 0 〈 q〉 N 〈 q〉 *N d 〈 v〉 1 = − j ω p 〈 v〉 1 + 〈 i〉 1 + 〈i〉 N +1 + 〈i〉 *N −1 dt C C C (4-58) 〈 q〉 N 〈 q〉 0 d 〈 v〉 N −1 = − j ω p ( N − 1)〈 v〉 N −1 + 〈i〉 N −1 + 〈i〉 1* dt C C (4-59) 〈 q〉 N 〈 q〉 0 d 〈 i〉 1 〈 v〉 N +1 = − j ω p ( N + 1) 〈 v〉 N +1 + 〈i〉 N +1 + dt C C (4-60) where < v SR >1 = −(V / 2 )(sin(θ) + j (cos(θ) − 1)) , 〈 q〉 0 = d , and 〈 q〉 N = (1 / π)(sin(dπ) cos(dπ) − j sin 2 (dπ)) As can be seen, the state space model described by Equations (4-55) through (459) has six complex differential equations and captures the interaction between the fundamental and high frequency quantities, as there is an explicit dependency on the 124 switching frequency (ωS=NωP). On the other hand, approximating q(t) by the duty ratio only ( q ( t ) ≈ 〈 q〉 0 ( t ) ), the traditional state space model in term of the fundamental quantities is recovered, R d 〈 i〉 1 − j ω p − L = dt 〈 v〉 1 〈 q〉 0 C 〈 q〉 0 1 L 〈 i〉 1 + 〈 v 〉 L SR 1 − j ω p 〈 v〉 1 0 − (4-61) The above state space has two complex differential equations and there is no switching frequency dependency. Notice that this index {1} model differs from the exact model only in two aspects: (i) the switching function has been replaced by the duty ratio and (ii) the diagonal elements of the state matrix have been augmented by the term –jωP. 4.5.1.2 Model Accuracy The generalized averaged model can bring insights to the design process. For example, say the interest is in calculating the steady state capacitor stress, specifically the RMS current. In order to investigate the accuracy of each model, a comparison of the prediction made by the traditional model and the generalized averaged scheme against the true switched waveforms can be made. Figure 4-4 shows the results obtained. The switched waveform is obtained from a detailed computer simulation. On the other hand, the index {1} and {1, N-1, N+1} approximations are obtained by first setting to zero the 125 left hand side (LHS) of their corresponding state space representation. This gives the capacitor voltages so by using Equation (4-12) the corresponding phasor current can readily be obtained. Finally, the reconstruction formula (4-4) allows determination of the time−domain waveforms. 1.5 Switched 1 Index {1, N-1, N+1} Index {1} 0.5 0 -0.5 -1 -1.5 1.7 1.705 1.71 1.715 1.72 1.725 1.73 Time (s) Figure 4-4 Waveform of the switched capacitor current along with the traditional and augmented approximations. FP=60(Hz), FS=1020(Hz), d=50%. As can be seen, the prediction made by the augmented model is much better than the traditional model. The RMS values for this particular case are ISW=722(A), I1=510(A) and IN=685(A) for the switched, index {1} and index {1, N-1, N+1} waveforms, respectively. Although the augmented model still falls short, it gives a more realistic insight about the current stress the capacitor has to manage. 126 4.5.1.3 Eigenvalues Pattern It is well known that capacitive series compensation introduces a resonance between the inductive reactance of the line and the compensation capacitor. However, the frequency at which this resonance occurs is usually on the order of a few tens of hertz. On the other hand, the switching frequency is at a few thousands of hertz, therefore a dynamic interaction between the switching frequency and the modes of the system should not be expected. The pattern followed by the eigenvalues is of special interest as it directly relates to the physical resonance of the system as well as to the power and switching frequency. The system exhibits a physical resonance of approximately FR=30(Hz) which, neglecting the various resistances, can be computed as FR = (1 / 2 π)(d / LC ) . When the system is modeled by the index {1} approximation, two extra oscillatory modes are added into the state matrix whose imaginary parts are given by ±FR±FP (±30, ±90(Hz)). When the system is augmented to include the fundamental component of the switching frequency eight extra modes are incorporating, yielding to a total of 12 modes whose imaginary parts are ±FR±FP±FS (±30, ±90, ±930, ±990, ±1050, ±1110(Hz)). This is summarized in Figure 4-5. 127 Figure 4-5 Eigenvalues distribution for the different models. FR=30(Hz), FP=60(Hz), FS=1020(Hz). This observation illustrates a simple litmus test that may be employed to identify the need for modeling higher index dynamics. By examining the system dynamic resonant frequencies, power frequency and switching frequency, it is possible to determine the degree of mathematical complexity needed to obtain a faithful representation. 4.5.2 Generalized Averaging Applied to the Γ−controller 4.5.2.1 The Model Similarly to the Ξ−controller case, the exact dynamic model for the Γ−controller 128 can be obtained from its corresponding equivalent circuit (Figure 3-22) using q(t) instead of d(t). This is shown in Figure 4-6. Figure 4-6 Exact model for the Γ−controller. In this case, vS and vR represent the corresponding space vectors, v S ( t ) = 2V(sin(ω P t ) − j ⋅ cos(ω P t )) (4-62) v R ( t ) = 2V (sin(ω P t + θ) − j ⋅ cos(ω P t + θ)) (4-63) 129 Considering as state variables the voltages and currents shown in the equivalent circuit above, the exact state space model can be constructed as follows, d x ( t ) = A (q ( t )) ⋅ x ( t ) + B ⋅ u ( t ) dt (4-64) where the matrices A and B, as well as the state and input vectors are described below. z4 -z z5 1 - jz 1 z1 A (q ( t )) = jz 1 q 1a s / C q a / C 2 s q 3 a s / C q a / C 4 s z3 - R ps /L ps - jz 3 - z3 jz 3 - (q 1 z 6 - z 8 ) - (q 2 z 6 + jz 8 ) - (q 3 z 6 + z 8 ) - jz 5 - z5 jz 5 q 1 z 7 + z 2 - 1/L ps q 2 z 7 - jz 2 (q 3 z 7 - z 2 ) jz 5 z 5 - R ps /L ps - jz 5 - z5 j(q 1 z 7 + z 2 ) j(q 2 z 7 − jz 2 ) - 1/L ps j(q 3 z 7 - z 2 ) - z5 jz 5 z 5 - R ps /L ps - jz 5 - (q 1 z 7 + z 2 ) - (q 2 z 7 − jz 2 ) - (q 3 z 7 − z 2 ) - 1/L ps - jz 5 1/ C - z5 0 jz 5 0 z 5 - R ps /L ps 0 - j(q 1 z 7 + z 2 ) 0 - j(q 2 z 7 − jz 2 ) 0 - j(q 3 z 7 - z 2 ) 0 0 1/ C 0 0 0 0 0 0 0 1/ C 0 0 0 0 0 0 0 1/ C 0 0 0 - (q 4 z 6 - jz 8 ) j(q 4 z 7 + jz 2 ) - (q 4 z 7 + jz 2 ) - j(q 4 z 7 + jz 2 ) − 1 / L ps 0 0 0 0 q 4 z 7 + jz 2 (4-65) z9 z 11 jz 11 − z11 B = − jz 11 0 0 0 0 z 10 z 8 jz 8 − z8 − jz 8 0 0 0 0 (4-66) i R (t ) i (t) PS1 i PS 2 ( t ) i PS3 ( t ) x ( t ) = i PS 4 ( t ) v C1 ( t ) v ( t ) C2 v C3 (t ) v ( t ) C4 (4-67) v (t ) u (t ) = S v R ( t ) (4-68) The constants zi (i=1,2,..,11) are functions of the parameters of the equivalent circuit. See Appendix 4 for a complete description of them. Also, notice that the explicit 130 time dependence of qi (i=1,2,…,4) in the state matrix has been dropped to avoid notational clutter. Since in this case the excitation is complex, the rules developed in Section 4.4.2 have to be applied in order to develop the generalized averaged model. However, the resulting model is a (two) x (three) x (nine) = 54 state space system. Therefore, it will not be shown here. It can easily be calculated via symbolic computation using standard software such as MatlabTM, MapleTM or MathematicaTM. As in the case of the Ξ−controller, the traditional index {1} state space model can be computed by adding -jωP onto the diagonal elements of the state matrix (4-65) and replacing the switching functions by the corresponding duty ratios. The resulting model in this case would be a (two) x (nine) = 18 state space system. 4.5.2.2 Model Accuracy The Γ−controller exhibits a resonance between the phase−shifter transformer secondary−side leakage inductor and the filter capacitor ( FR = 1 / 2π L PS C ), which might be in the order of the switching frequency and therefore lead to unstable operation. Although in the Design Considerations Section for the Γ−controller (Section 3.2.5) the way in which to approach this issue qualitatively was discussed, it will now be formally discussed in terms of the generalized averaging theory. It has been shown that the switching process introduces harmonics into the system with frequencies of form nFS ± FP (n=1,2,…∞). These frequencies need to far exceed the 131 resonances of the system in order to avoid their excitation. Clearly, the critical case is when n=1 ( FS ± FP ), since (FS ± FP ) > FR ⇒ (nFS ± FP ) > FR . The case of n=1 is fully captured by the index {1, N-1, N+1} model and therefore it can describe the actual system at a much higher degree of accuracy as discussed in the example below. As an illustration, the parameters that define the resonance frequency are selected as Lps= 0.3mH and C=73µF so the resonance occurs at 1862(Hz). These values are the same ones used to show steady state operation in the Control Capabilities Section (Section 3.4.4), so they may be considered reasonable. Detailed switched simulations were conducted considering FS=2400(Hz) and FS=1800(Hz), whose results are shown in Figure 4-7 and Figure 4-8, respectively. 1 0 -1 (a) Switched, Index {1} and Index {1, N+1, -(N-1)} 1 0 -1 (b) 1 0 -1 (c) 1 0 -1 (d) 0.25 0.255 0.26 0.265 0.27 0.275 0.28 Time (sec) Figure 4-7 Capacitor voltage waveforms with FR=1862(Hz) and FS=2400(Hz). 132 1 0 -1 1 0 -1 1 0 -1 1 0 -1 0.25 0.255 0.26 0.265 0.27 0.275 0.28 Figure 4-8 Capacitor voltage waveforms with FR=1862(Hz) and FS=1800(Hz). The state variables plotted are the capacitor voltages vCi (i=1,2,…4) from the equivalent circuit shown in Figure 4-6. The simulated switched waveforms are plotted against the index {1} and index {1, N+1, -(N-1)} approximations, which are obtained from their corresponding state space models. As can be seen in Figure 4-7, when the resonance frequency and switching frequency are sufficiently different, the index {1} model describes the system accurately and the augmented scheme gives no extra information. However, when the resonance frequency becomes closer to the switching frequency, Figure 4-8 shows that the duty ratio based model fails to predict the oscillatory behavior of the state variables. The augmented scheme does capture such behavior and hence its potential becomes evident. Since these devices have been developed to control power flows along transmission lines, it is likely that a closed−loop regulator would be used to maintain 133 appropriate set−points. In such cases, the ripple phenomena would not be captured whatsoever by measuring net P and/or Q at 60Hz. Therefore, the duty ratio−based approximation would be blind to the potential instabilities that may be incipient in the system. 4.6 Summary This Chapter has introduced the dynamic modeling for AC link power flow controllers under the generalized averaging framework. The presence of excitation at power frequencies that interact with the switching frequency requires a systematic integration of the techniques developed for multifrequency averaging for converters and phasor dynamic modeling common for study of AC DC−DC converters. The mathematical development of the integration is presented under the condition that the switching frequency be an integer multiple of the power frequency. The application of the technique to predict system behavior was illustrated using the Ξ−controller and the Γ−controller. The results indicate that the augmented multifrequency averaged model is superior to the traditional DC averaged model in predicting high frequency interactions. The nature of the augmentation of the eigenspace of the system under DC averaged and multifrequency averaged models was also illustrated. In addition, it was briefly discussed how the augmented state matrix can lead to identifying potential system resonances, especially when the system exhibits oscillatory modes in the vicinity of the switching frequency. 134 Chapter 5 5.1 Since Feedback Control for AC Link Power Flow Controllers Introduction AC link vector switching power flow controllers have been developed to control power flows along transmission lines, it is likely that a closed−loop regulator would be needed to maintain appropriate set−points. Figure 5-1 shows, in the Laplace domain [46, 47], the basic structure for a feedback control system. The plant, g(s), represents the power circuit whose outputs, y, need to be maintained at a certain level dictated by yREF. The approach is to measure the outputs via a transducer (β) and compare such measurements against the references to generate an error signal (ε). This error is then processed by an appropriate compensator h(s) to generate the manipulated inputs uM, which drive the controllable devices of the plant. In addition, the plant usually has other inputs represented by u. u yREF Controller h(s) uM Plant g(s) Figure 5-1 Configuration for classical control design. y 135 The control design problem is to determine h(s) in order to meet the functional requirements of the overall system. These requirements include, among others, stability, maintenance of the desired operating condition in case of disturbances, and acceptable dynamic performance (overshoot, settling time). As will become evident throughout this chapter, the Ξ−controller, although it corresponds to a nonlinear system, is a single−input, single−output (SISO) system so the control design problem for a nominal operating condition can be assessed by classical techniques such as Bode plots [46, 47]. On the other hand, the Γ−controller, in addition to being nonlinear, is a multiple−input, multiple−output (MIMO) system; therefore, techniques that are more refined are required for the analysis [48]. 5.2 Feedback Control for the Ξ−controller The control design problem starts with the identification of the dynamic model for the power circuit. The model chosen for this purpose is based on the single−phase index {1} averaged equivalent circuit shown in Figure 3-14. The mathematical description was deduced in Section 4.5.1.1. It was found that the corresponding state space is described by Equation (4-61), repeated here for convenience, 136 R d 〈 I〉 1 − j ω p − L = ⋅ d dt 〈 V〉 1 C d 1 L ⋅ 〈 I〉 1 + ⋅ [〈 V 〉 ] SR 1 L − j ω p 〈 V〉 1 0 − (5-1) As the interest is in controlling the active power at the receiving end, the output of the system can be defined as, PR = {〈 VR 〉 1 〈 I〉 1* }Re (5-2) Before proceeding further, notice the following: (i) Equations (5-1) and (5-2) presented above are both in terms of complex quantities, so separation into real and imaginary parts is necessary; (ii) Since there is a single (manipulated) input, d, and a single output, PR, Equations (5-1) and (5-2) describe a SISO system; (iii) Due to the inherent nonlinearities introduced by the products between the manipulated input, d, and the state variables, 〈 I〉 1 and 〈 V〉 1 , linearization is needed in order to apply classical control techniques. 5.2.1 Proposed Controller Traditionally, the first attempt in controlling a process has been to linearize the plant around a nominal operating condition and try a combination of a proportional (P), integral (I), and/or derivative (D) controller. PID controllers are widely used in industry 137 and have become the standard for control system design. Only when the PID approach fails are more sophisticated techniques considered. In the case of processes involving switching power converters, differentiation is particularly undesirable. Switching power converters are rich in high frequency noise generated by the switching process. Derivative controllers have a gain that increases with frequency and hence tends to amplify high frequency noise. Thus, as in most processes involving switching power converters, a PI controller is proposed here. A formal justification will be given in Section 5.2.1.2. The overall closed loop system is shown in Figure 5-2. The PI controller acts upon the error to generate the duty ratio as, t d ( t ) = K P ε ( t ) + K I ∫ ε ( τ ) dτ (5-3) 0 vS(t) PREF PI Controller d PWM Pulse Generator Pulses vR(t) Power System with a -Controller PR Carrier Figure 5-2 Block diagram of the control system. Since the model for the power circuit is the index {1} average, the PWM pulse generator 138 may be considered to have a unity transfer function so the duty ratio, d, acts directly upon the plant. In addition, since the power circuit is nonlinear, the plant may be modeled by its small signal transfer function. 5.2.1.1 Small Signal Model The small signal model for the plant can be obtained by linearizing Equations (51) and (5-2) around a nominal operating point. For that purpose, consider the general form of Equations (5-1) and (5-2), xɺ ( t ) = f ( x ( t ), u ( t ), u M ( t )) (5-4) y( t ) = g( x ( t ), u ( t ), u M ( t )) (5-5) Since the interest is in the transfer function with respect to the manipulated inputs, the linearization of f(x(t),u(t),uM(t)) and g(x(t),u(t),uM(t)) around x 0 becomes f ( x ( t ), u ( t ), u M ( t )) = f ( x 0 , u 0 , u M 0 ) + ∂f ∂f (x(t) − x 0 ) + (u M ( t ) − u M 0 ) + h.o.t. (5-6) ∂x 0 ∂u M 0 g ( x ( t ), u ( t ), u M ( t )) = g ( x 0 , u 0 , u M 0 ) + ∂g ∂g (x(t) − x 0 ) + (u M ( t ) − u M 0 ) + h.o.t. (5-7) ∂x 0 ∂u M 0 where h.o.t. stands for higher order terms. The operating point x0 can readily be obtained 139 by assigning some value to the duty ratio, say d0, and then solving Equation (5-4) for steady state i. e., making the LHS equal to zero. Applying Laplace’s transform to Equations (5-4) through (5-7), the small signal model becomes ~ ~ s ⋅ ∆x = A ⋅ ∆x + B ⋅ ∆u M (5-8) ~ ~ ∆y = C ⋅ ∆x + D ⋅ ∆u M (5-9) where, ~ ∂f A= ∂x 0 ∂f ~ , B= ∂u M 0 ~ ∂g , C= ∂x 0 ∂g ~ , D= ∂u M , and ∆x = ( x − x 0 ) , ∆y = ( y − y 0 ) , 0 ∆u M = (u M − u M 0 ) . For the particular case of the Ξ−controller, each term of Equations (5-8) and (5-9) becomes, [ x = 〈 I〉 1Re 〈 I〉 1Im [ Im 〈 I〉 10 y = PR (5-12) Re x 0 = 〈 I〉 10 〈 V〉 1Re Re 〈 V〉 10 〈 V〉 1Im ] Im 〈 V〉 10 y 0 = PR 0 T ] (5-10) T (5-13) ωp − d0 / L 0 − R L −ω −R L 0 − d 0 / L ~ p A= d0 / C 0 0 ωp d0 / C − ωp 0 0 [ ~ C = 〈 VR 〉 1Re 〈 VR 〉 1Im 0 0 ] (5-11) uM = d (5-14) u M0 = d 0 (5-16) − 〈 VSR 〉 1Re − 〈 VSR 〉 1Im ~ B= Re 〈 I〉 10 C Im 〈 I〉 10 C (5-18) ~ D=0 L L (5-15) (5-17) (5-19) 140 Notice that the separation in real and imaginary parts for the states variables has taken place. The plant’s input/output transfer function, g(s), readily follows from Equations (5-8) and (5-9), g (s) = ∆PR ~ ~ ~ = (sI − A ) −1 B + C ∆d On the other hand, the (5-20) PI controller’s input/output transfer function, h(s), can be obtained applying Laplace’s transform to Equation (5-3), h (s) = K ∆d = (K P + I ) s ∆ε (5-21) The overall small signal model developed in this section is shown in Figure 5-3. The control design problem can now be visualized as calculating appropriate values for the gains KP and KI in order to satisfy system performance. PREF KP + KI s d ~ ~ ~ (sI − A) −1 B + C Figure 5-3 Block diagram for the small signal model. Notice that the global input/output transfer function is PR 141 ∆PR 1 T (s) = ⋅ ∆PREF β 1 + T (s) (5-22) where T(s) is the loop gain defined as T (s) = β ⋅ h (s) ⋅ g (s) (5-23) 5.2.1.2 Controller Design via Bode Plots The controller design is usually done by “shaping” the frequency response of the loop gain, T(s), as it carries most of the information of interest [46, 47]. The Bode Plots approach focuses on three performance indices: (i) Stability margins: As may be evident from Equation (5-22), the situation T( jω) = 1∠180 o should be avoided in order to maintain stability in the bounded−input, bounded−output (BIBO) sense. In practical situations, control designers impose security margins to keep the system away from such a critical value. The quantitative definition of these security margins begins by introducing the gain crossover frequency (GCF) and the phase inversion frequency (PIF). The former refers to the frequency at which the magnitude of T(jω) equals one ( | T ( jω) |= 1 ) while the latter refers to the frequency at which the angle of T(jω) becomes 180° ( ∠T ( jω) = 180 o ). Thus, at the GCF, the 142 corresponding angle should be away from 180° by an acceptable phase margin (φM). In addition, at the PIF, the corresponding magnitude should be away from 1 by an acceptable gain margin (GM). Furthermore, it should be evident that in order to have a stable system, the PIF (GCF GCF has to occur before the < PIF). This provides a positive φM at GCF and a positive GM at PIF. A GM of 2 and a φM of 60° are usually considered acceptable, and are used as targets in the control design process. (ii) Bandwidth: Equation (5-22) shows that the feedback is effective only for large values of T(s). The GCF is also called the bandwidth of the regulator as it defines the value at which the feedback becomes ineffective. The bandwidth also features the property of being proportional to the speed of response of the regulator. For both of these reasons, it is important to keep the bandwidth as high as possible. (iii) Steady state error: The steady state error can be directly evaluated from T(0). It should be evident from Equation (5-22) that it T(0)=∞ drives the steady state error to zero. These indices sometimes conflict with each other and the designer has to evaluate the tradeoffs involved in the design process. Based on the data shown in Appendix 2, the regulator for the Ξ−controller is designed as follows. The transducer β is considered as a pure gain free of noise. The value of β=10−6 is selected as it measures power in the order of MW. The frequency response of the partial loop gain βg(s) is shown in Figure 5-4. It can be seen that PIF<GFC which is a 143 sufficient condition for instability, so the first and most important task is to stabilize the system with an appropriate regulator. 50 0 -50 -100 0 -100 -200 -300 -400 -2 10 -1 10 0 10 1 10 2 10 3 10 4 10 Figure 5-4 Bode Plot for the partial loop gain β g(j ω). Notice that as a result of modeling the system with the index {1} average, two resonant peaks are observed in the frequency response. These peaks occur at FR±FP, as predicted early by analyzing the eigenvalues’ pattern. Figure 5-5 shows the frequency response for the proposed PI regulator, which is obtained by selecting the gains as KP=10-4 and KI=0.5. Cascading this regulator as shown in Figure 5-3, the frequency response of the final loop gain, T(s)=βh(s)g(s), becomes as shown in Figure 5-6. 144 50 0 -50 -100 0 -100 -200 -300 -400 -2 10 -1 10 0 10 1 10 2 10 3 10 4 10 Figure 5-5 Bode Plot for the PI controller h(j ω). 50 0 -50 -100 0 -100 -200 -300 -400 -2 10 -1 10 0 10 1 10 2 10 3 10 4 10 Figure 5-6 Gain and Phase margins from the loop gain T(j ω)= β h(j ω)g(j ω). It can be seen that now GFC<PIF and the Nyquist’s criterion for stability [46] would show that the system is indeed stable. It can also be seen that the stability security margins are within the specified range (GM=7.5dB=2.4, φM=89°) and the integral part of 145 the regulator guarantees to have T(0)=∞. The bandwidth, however, seems low but adequate for the application, as will become evident in the next section. 5.2.2 Simulation Results Once the regulator has been designed, computer simulations are carried out in order to verify the regulator performance. The typical tests evaluated are the response of the system upon a step change in the reference and upon small disturbances on the non−manipulated inputs. 5.2.2.1 Response to a step change in the reference This test is carried out to verify the BIBO stability of the system as well as to evaluate the dynamic performance of the regulator. Figure 5-7 shows the results for a 15% step change in the reference power. As can be seen, a first order stable response is obtained. The regulator is also able to track the reference and the speed of response is about 0.5s, which indicates that the bandwidth is adequate. 146 1.2 1.1 1 0.9 2 0 -2 1.2 1.1 1 0.9 0.9 1 1.1 1.2 1.3 1.4 1.5 Figure 5-7 Response to a 15% step change in the reference power. (a) shows the step change applied to the reference power while (b) and (c) show the response on the line current and the measured power at the receiving end, respectively. In addition, Figure 5-7 may be directly compared to the open loop response shown in Figure 3-18, as the step change in the reference power was made coincident to the duty ratio step change (notice that the steady state measured power in both figures is the same). It can be seen that the closed loop regulator dramatically improves both the overshoot and the oscillatory behavior observed in the open loop case. 5.2.2.2 Response to disturbances This test is carried out to evaluate the ability of the system to track the reference upon small disturbances on the non−manipulated inputs. Figure 5-8 shows the response of the system for a step change of 5% in the magnitude of the sending end voltage. Figure 5-9 shows the response of the system to a step change of 3° in the transmission angle. 147 1.05 1 0.95 0.9 2 0 -2 1.1 1 0.9 0.8 0.7 0.9 1 1.1 1.2 1.3 1.4 1.5 Figure 5-8 Response to a 5% step change in the sending end voltage. (a) shows the step change applied to the magnitude of the sending end voltage while (b) and (c) show the response on the line current and the measured power at the receiving end, respectively. 24 22 (a) 20 2 (b) 0 -2 1.1 1 (c) 0.9 0.8 0.7 0.9 1 1.1 1.2 1.3 1.4 1.5 Time(s) Figure 5-9 Response to a 3° step change in the transmission angle. (a) shows the step change applied to the transmission angle while (b) and (c) show the response on the line current and the measured power at the receiving end, respectively. It can be seen that the regulator is able in both cases to track the reference, 148 although the oscillatory response of the power might not be acceptable. Suitable changes in the regulator design, including a different control approach, may be needed in order to improve these responses. This is discussed in the Future Work Chapter. 5.3 Feedback Control for the Γ− −controller The overall control system for the Γ−controller is shown in Figure 5-10. Since this device was realized to simultaneously control the active and reactive power through a transmission line, it naturally has two outputs. References to track the corresponding outputs are likely to be used as shown in the figure. It becomes evident that, under these circumstances, this is the case of a MIMO system. Classical techniques such as the Nyquist’s stability criterion or feedback loop design using Bode Plots are not easily extendable. vS(t) PREF QREF P Q ? Controller d1 d2 d3 d4 PWM Pulse Generator Pulses vR(t) Power System with a -Controller Carrier P Q Figure 5-10 Control system for the Γ−controller. PR QR 149 Therefore, as suggested in the figure, at first glance it is not clear what regulator to use in order to satisfy the various performance indices introduced in the previous section. In addition, notice that the regulator needs to generate three outputs (one of the duty ratios can be expressed as 1−summation of the other three) from two input errors. It has also been observed that there is cross−coupling between the outputs i. e., a change in say εP would also affect the output value of QR. On the other hand, as discussed in Section 4.5.2.2, it is not clear whether the index {1} average model is precise enough to describe the behavior of the Γ−controller, as it exhibits a resonance that might be in the same order the switching frequency. The augmentation to the indices {1, N+1, -(N-1)} average might be needed for satisfactory closed loop performance. All of these issues make the Γ−controller regulator design a challenging problem that is under investigation is proposed as future research in Chapter 9. 5.4 Summary This chapter has introduced the notion of closed loop regulation for AC link power flow controllers. In the case of the Ξ−controller, the dynamic modeling for the power circuit was made by using the index {1} average model introduced in Chapter 4. Classical control techniques indicated that a PI regulator would perform satisfactorily. On the other hand, in the case of the Γ−controller, a brief introduction to the control design problem was made, indicating that the subject is left as an open question for further investigations. 150 Chapter 6 A comparative evaluation of Power Flow Controllers using AC Link and DC Link Converters 6.1 Introduction When introducing a new technology it is customary to contrast its features against the state−of−the−art. As pointed out in Chapter 1, power flow controllers that use a DC link voltage source inverter are considered to be superior to previous realizations in terms of harmonic performance, dynamic response and ease of operation. Although the functional equivalency between the AC link and DC link approaches has been illustrated in the literature [14, 27], a detailed comparison between their features was not attempted. It is the goal of this chapter to present a comparative evaluation of the two approaches. A comparative evaluation of particular solutions for a given application may be made on the basis of several performance features. Salient features include: harmonics of waveforms, operating losses, ratings of power converters, reactive component requirements, transformer kVA requirements, complexity of control, dynamic response in terms of improving voltage stability, small signal and large signal stability, damping of 151 sub−synchronous resonance, etc. Given the degree of variability based on the application of these devices in the form of shunt, series, shunt−series and interline connections, a definitive evaluation appears to be a formidable task. Therefore, in order to maintain a focus in the evaluation, a particular application, namely series compensation is considered in this chapter. Furthermore, the evaluation is limited to solutions that feature superior waveform quality arising from high frequency or high pulse number switching with sinusoidal line current waveforms. This precludes the consideration of and GCSC TCSC, TSSC [14] solutions from evaluation in this study. It is felt that due to their fundamentally different harmonic characteristics due to phase controlled switching, the benchmarking would not be consistent, and unreasonably extend the scope of the chapter. In this chapter, a focused analytical modeling and design study of a candidate application using the DC link and the AC link power converters is performed in order to evaluate their performance. The comparison criteria used for the evaluation include voltage, current and power throughput ratings of the main power circuit components (including transformers, capacitors, and semiconductors), quality of terminal voltage and current waveforms in terms of harmonics, losses in power semiconductors and transient performance of the solutions in tracking commands and rejecting disturbances. No attempt is made herein to estimate the comparative cost of these solutions, as such costs are a complex function of market trends, economic factors and engineering development, and would change considerably with respect to time and location. However, the design ratings for transformers, capacitors and power semiconductors together may be considered to be a proxy for the capital costs of equipment. 152 6.2 Candidate Compensators 6.2.1 DC The link series compensator, termed manners. DC DC Link Series Compensator capacitors or DC SSSC, can be realized in a variety of inductors could be used to realize the DC link, leading to the use of a voltage source inverter or a current sourced inverter, respectively. Moreover, multi−pulse or PWM can be selected as a modulation strategy to synthesize the output voltage. The multi−pulse (48−pulse) voltage source inverter option is chosen here as it is considered the state−of−the−art approach and it is commercially available with ratings up to 100(MVA) [19]. Figure 6-1(a) shows a simplified schematic of the main stages involved in the realization of the 48−pulse system [49]. As can be seen, the DC link is realized using two series connected DC capacitors with access to their mid−point N [50-52]. This allows three voltage levels (VC1, VC2, 0). Four independent diode−clamped three−phase three−level converters are connected to the DC bus. Figure 6-2(a) shows the detailed switch realizations for each converter. The voltage synthesis for phase A is shown in Fig. 3(a). Phase−shifted waveforms (±120o) are synthesized for phases B and C. As suggested in Figure 6-1(a), each three−level converter is then connected to a magnetic structure based on Y−zigzag ∆−zigzag phase−shifting transformers that allows creation of a 24−pulse waveform. The final 48−pulse waveform is obtained by making the conduction angle of each converter σ=172.5o. Thus, the lowest characteristic harmonic numbers 153 present in the output waveforms are 47 and 49. It may be concluded from Figure 6-1(a) and Figure 6-2(a) that stable operating points are achieved only when the output voltage is in quadrature (±90o) with the output current, because otherwise there would be active power exchange between the capacitors and the AC DC system, leading to a permanent charge or discharge of the capacitors and therefore unstable operation. The same argument is used to control the magnitude of the AC output voltage. By allowing a small real power exchange for a short duration between the DC link and the AC system, it is possible to drive the capacitors’ voltage to a desirable value and therefore adjust the output voltage. Finally, it should be noted that in order to generate symmetric AC output voltage waveforms, a suitable algorithm for equalizing the average value of VDC1 and VDC2 needs to be implemented [53]. Section 6.5.2 describes the implementation of such algorithm. Figure 6-1 Schematic of candidate compensators. (a) SSSC (b) Ξ−controller. 6.2.2 AC Link Series Compensator The Ξ−controller was extensively studied in Section 3.3. As the goal of this chapter is to contrast the features of this device against the SSSC, some schematics and 154 concepts will be repeated here for convenience. Figure 6-1(b) shows a realization for the Ξ−controller that naturally follows from the SSSC topology introduced in the previous section. As can be seen, four banks of three−phase AC capacitor make up the link. Each bank is switched using a AC three−phase vector−switching converter whose principle of operation is depicted in Figure 6-2(b) and Figure 6-3(b). The former shows the switch realization of a double−throw single−pole three−phase switch and the latter the voltage synthesis process for phase A. Phase−shifted waveforms (±120o) are synthesized for phases B and C. VCA IDC1 + T1A D1A T1B D1B DC1A VDC1 T2A D2A T1C T2B D2B VCB D1C DC1B DC1C T2C IA D2C T3A D3A T3B D3B DC2A VDC2 T4A IDC2 D4A T3C T4B D4B IA VA T1B IB VB T1C IC VC T2A IC DC2C T4C D1C VB D3C DC2B D1A VCC D1B VA IB N T1A VC D4C D2A T2B D2B T2C N (a) - (b) D2C Figure 6-2 Converter realizations. (a) SSSC (b) Ξ−controller. PWM Injected Voltage Carrier Multi-pulse Injected Voltage T2AT3A T1AT2A T2AT3A T3AT4A T2AT3A Duty Ratio VDC1 (a) T1A T 2A (b) VDC2 0 180 360 t (deg) t (deg) Figure 6-3 Waveforms illustrating AC voltage synthesis. (a) SSSC. (b) Ξ−controller. As can be seen from Figure 6-3(b), the AC voltage generated by each capacitor 155 bank is rich in harmonics and hence unless output filters are used, the resulting waveform would be unacceptable for utility applications. However, by using the magnetic structure suggested in Figure 6-1(b) and phase−shifting the PWM carriers of each bank by 90o, it is possible to operate with no output filter at a modest frequency of FS=720(Hz). This, as in the SSSC case, also limits the lowest characteristic harmonic numbers to be 47 and 49. A more detailed contextual comparison of the waveforms injected by each compensator is discussed later in Section 6.4.2.4.3. 6.3 Test system description Figure 6-4 shows the case study system that will be used to perform the comparative evaluation. As can be seen, it corresponds to a simple transmission line with a two bus power system on which a series compensator has been embedded. The compensator can be either the SSSC or the Ξ−controller. Figure 6-4 One line diagram of the candidate series compensation system. In order to make the comparison meaningful, both the SSSC and the Ξ−controller are assumed to provide the same amount of compensation. Table 6-1 shows the specific values for the transmission system considered in this case study. Due to the lumped 156 resistance of the transmission line, the line power slightly varies depending on the location where the measurement is taken. The location downstream of the converter (at V2 in Figure 6-4) is selected to measure the power. It readily follows that, without compensation, the nominal line power is PL{Nom}=140(MW). A 40(MW) increase is selected for full compensation, which represents a ~30% increase above the nominal value. Thus, at full compensation, one would measure PL{Comp}=180(MW). Table 6-1 System Data Base Values: 110kV/100MVA/60Hz Bus Voltage (pu) Impedance (pu) VS = 1∠0 ZS=0.01+j 0.17 VR = 1∠ − 20 6.4 6.4.1 ZR=0.01+j 0.07 Steady state performance evaluation Operating Modes As suggested in Figure 6-4, each compensator can operate in different control modes. Although the ultimate objective is the control of the active power through the line, this can be achieved through different regulation strategies. The most direct approach involves commanding a certain amount of desired power PL and synthesizes a voltage waveform to achieve such an amount. This approach has the advantage of maintaining the active power through the line at a pre−established value but, under some contingences, this may not be desirable or possible [14]. Alternatively, one can command a certain amount of injected voltage VINJ or a certain amount of injected impedance 157 ZINJ=VINJ/IL. These three control methods, namely power mode, voltage mode and impedance mode, can be used in each approach to realize power flow control. The remarks made in Section 6.2 readily lead to the steady state equivalent circuits presented in Figure 6-5. As can be seen, the natural steady state representation of the SSSC is a controlled voltage source while for the Ξ−controller is a controlled capacitor. For the SSSC, the manipulated input is the magnitude of the while for the Ξ−controller it is the duty ratio (d). The operation of the the synthesis of AC synchronized to the DC voltage (VDC) SSSC depends on voltage waveforms using the constituent inverters appropriately AC line using a phase−locked−loop (PLL). On the other hand, the Ξ−controller is regulated through a simple duty ratio control that varies the amount of injected AC capacitance with the line in the open loop mode. However, through appropriate feedback control, both of these devices can be regulated to operate in any o the operating modes described above. Figure 6-5 Steady sate equivalent circuits. (a) SSSC (b) Ξ−controller. In order to explicitly show the ability of each compensator to operate under the various operating modes, formulas that relate the line power (PL), the injected voltage 158 (VINJ) and the injected impedance (ZINJ), with respect to the manipulated inputs are presented in Table 6-2 [29]. These formulas readily follow from the equivalent circuits from Fig. 5. For the sake of simplicity, it is assumed that the transmission line is purely inductive and |VS|=|VR|=V. In addition, it is assumed that the injection transformer is ideal (XT=0) and has unity turn ratio. Finally, it is also supposed that the line current is instantaneously available for control purposes. In the case of the Ξ−controller the assumption of XT=0 is removed to explicitly show that this device can provide a certain degree of inductive compensation (when XT>d2XC). However, it has been pointed out in the literature [16] that series compensators seldom provide steady state inductive compensation due to the increase in reactive power circulation associated with it, so the focus herein is on capacitive compensation only. Table 6-2 Operating Modes Operating Mode Voltage VINJ = mVDC Impedance ZINJ = Power PL = 6.4.2 Ξ−Controller SSSC 1 XL 1 ± (2V sin θ / 2) / mVDC V2 V θ sin θ ± mVDC cos XL XL 2 VIJN = 2V θ sin 2 2 1 + X L /(X T − d X C ) Z INJ = X T − d 2 X C PL = V2 sin θ X L + (X T − d 2 X C ) Design Considerations As may be evident from Figure 6-4, the main components to be rated are the injection transformer, the compensation capacitors and the power converter. The overall design process begins by assuming that the bus voltages at locations VS and VR are 159 known so that the nominal operation of the transmission line without compensation can be found. Next, defining the percentage (say λ) by which the line power is going to be increased above its nominal value, the line power at full compensation can be computed as PL{Comp} = (1 + λ)PL{Nom} . Finally, in reference to Figure 6-4, by solving Equations (6-1) and (6-2), the electrical variables at the injection transformer terminals, VINJ and IINJ(=IL) can be found. VS − ZS ⋅ IL − | VINJ | ∠(∢IL − 90°) − ZR ⋅ IL − VR = 0 (6-1) ℜ{3 ⋅ (VR + ZR ⋅ IL ) ⋅ I*L } = PL{Comp} (6-2) It should be noted that Equations (6-1) and (6-2) provide three scalar equations that allow the unknown variables |IL|, ∢IL and |VINJ| to be solved. The values of VINJ and IINJ are independent of the type of compensator used and provide the basis for the design process. For the case study, λ=30% so the solution of Equations (6-1) and (6-2) gives VINJ=6.1(kV) and IINJ=965(A). It follows that the injected power is QINJ=3VINJIINJ=17.6(MVAr). 6.4.2.1 Choice of power semiconductors Power semiconductor switch ratings and properties remain the limiting factor that determines the highest possible power throughput in any application. Selection and application of switching devices involves a careful trade−off between the various families of power semiconductors matched against the ratings required for the particular power converter. An examination of the topology of the converters indicates that single quadrant force commutated semiconductors and diodes form the building block for both 160 realizations. The device families that fit these needs at voltage levels in the order of a few kV are GTOs, IGCTs and IGBTs. family of devices while the Among these, IGBT GTOs and IGCTs belong to the thyristor belongs to the transistor family of devices. While both families of devices are capable of turning off without the need for any snubbers, due to the regenerative mechanism that dominates the turn on process in thyristors, IGCTs GTOs and require di/dt limiting reactors to be included in their realizations. The introduction of di/dt limiting reactor further necessitates a ‘pole clamp’ that captures the trapped stored energy in the di/dt limiting reactors and diverts it to the DC bus during each turn−off event. A detailed discussion of realization and performance of devices for DC link converters along with a comparison with GTO IGCT switching devices may be found in the literature [54]. Furthermore, series connected IGCT devices for continued converter operation during device failures in such applications to enhance system reliability have also been demonstrated. However, such series operation requires RC networks in parallel with the devices to ensure steady state and dynamic voltage sharing. On the basis of these evaluations, IGCT may be concluded to be the preferable switching device for the SSSC system. In comparison to the DC link converter used in realizing the SSSC which involves single quadrant switching during commutations, the switching mechanism in the three−phase vector switching converters to realize the Ξ−controller involves four−quadrant switching during commutations. For each throw, the commutation process involves leaving a forward or reverse conducting state and entering a forward or reverse voltage blocking state during turn−off and vice−versa during turn−on. The actual 161 quadrants of conduction and commutation sequence are in fact determined by the phase of the three−phase excitation waveforms and also the operating duty ratio. Due to this situation, the viability of including a di/dt limiting reactor for each throw and devising a suitable mechanism for absorbing the trapped energy in a lossless and effective manner is challenging. Therefore, the use of IGCTs in the realization of Ξ−controller is considered to be demanding. On the other hand, high power IGBTs are capable of operation without snubbers for turn−on and turn−off, and are capable of operating in parallel with ease [55]. Furthermore, various laboratory prototypes of three−phase vector switching converters have been realized using IGBTs [27, 56]. The application of a four−step switching strategy during commutation for effective and efficient clamp−free four quadrant switching using IGBT realizations have been demonstrated in matrix converters, and can be readily extended to the three−phase vector switching converters [26]. Therefore, the IGBT is chosen to be the preferred power semiconductor for realizing the Ξ−controller. The detailed engineering design of the switch realization including appropriate snubbers to manage the commutation, thermal management and protection features for both the SSSC and Ξ−controller are beyond the scope of this evaluation and is not considered in this thesis. However, the ratings and selection of particular devices and the losses in them will be considered further in the evaluation. 6.4.2.2 Injection Transformer The total transformer fundamental kVA ratings are the same for both types of 162 compensators as they are meant to deliver the same amount of compensation for the line. However, the number of transformers and turn ratio of the transformers are selected on the basis of harmonics and voltage compatibility with the power converters. The selection of the number of transformers (T) is related to the harmonic pulse number that can be realized across the entire series compensator, given a switching strategy or frequency. Recommendations of acceptable harmonics injected in power systems from power converters are specified up to the 40th harmonic [57]. As discussed earlier, the realizations illustrated in Figure 6-1 with T=4 transformers in series, limits the lowest harmonic numbers to be 47 and 49, thereby meeting the recommended waveform quality levels. The turn ratio of each transformer (n) is selected on the basis of the maximum voltage blocking capability of the semiconductor switches, namely IGCTs for the SSSC and IGBTs for the Ξ−controller. A more detailed discussion of this including the provision for (n−1) reliability for each of the realization is presented in a subsequent sub−section (Section 6.4.2.4.1). The chosen values for the turns ratio and different transformer parameters are summarized in Table 6-3. It should also be noted that, in the case of the SSCC, minor arrangements ought to be made in order to properly rate each winding considering the zigzag and ∆ connections [58]. Although the current through each of the transformers are substantially sinusoidal, as will be illustrated further, the excitation voltage waveforms for both type of compensators contain a significant amount of harmonics. Thus, the transformer design features will have to be modified to accommodate this. First, the core area of the transformers will have to be derated to 163 account for the increased flux arising from the non−sinusoidal voltage waveforms in order to prevent saturation. A core area derating factor DFφ for each of the compensators may be defined as the ratio of the area of one half cycle of the excitation voltage waveforms shown shaded in Figure 6-3 to the area of one half cycle of a sinusoidal waveform with a corresponding amplitude of the fundamental component. Secondly, the non−sinusoidal nature of the waveforms leads to variations in core losses in the transformer [59, 60]. Various loss penalty factors corresponding to classical eddy current losses (PFCE), excess eddy current losses (PFEE) and hysteresis losses (PFH) for each of the compensator that accounts for any increase in core losses have been determined by studying the excitation waveforms in each case. These derating factors and penalty factors for the both the compensators are shown in Table 6-3 [60]. Table 6-3 Injection Transformer Rating Rated Power: ST =3·(VINJ/T)·IINJ , Turn Ratio: n= VLS/VCS Transmission Line Side (LS): VLS = √3 (VINJ/T), ILS = IINJ Converter Side (CS): VCS = √3 (1/n) (VINJ/T), ICS = n IINJ Ξ−controller SSSC ST = 4.4(MVA), n= ¼ ST = 4.4(MVA), n= 1 VLS = 2.6(kV), ILS = 965(A) VLS = 2.6(kV), ILS = 965(A) VCS = 10.6(kV), ICS = 241(A) VCS = 2.6(kV), ICS = 965(A) DFφ = (8sin σ / 2) /(σπ) = 0.86 DFφ = (2d max ) / ξ = 0.99 PFCE = 8 /(σπ) = 0.84 PFCE = (4d max ) /(ξ 2 ) = 1.1 PFEE = 16 /(7 2σ ) = 1.44 PFCE = (12 2) /(7ξ 2 ) = 1.0 PFH = 1 PFH = 1 3 The parameter σ, dmax and ξ are properties of the converters operating conditions 164 and therefore are properly defined in the next subsections. It may be observed from these derating and penalty factors, that although the SSSC would require a marginally larger core size, and larger excess eddy current losses in comparison to the Ξ−controller, it would feature correspondingly smaller classical eddy current losses. It may be concluded that on balance, the transformer features would be comparable for both cases. 6.4.2.3 Capacitor As a general rule, capacitors in power converters must be selected so that the ripple is minimized and the resonance frequency resulting from the interaction of the capacitor and the AC side inductors is far away from the harmonics associated with the switching process. 6.4.2.3.1 SSSC Capacitor Selection The “Unit Capacitance Constant” (UCC) was introduced in the literature [53] as a rule of thumb for the preliminary selection of the total capacitance value of the DC link. It is defined as 2 UCC = (1/ 2 ⋅ C ⋅ VDC ) / SCONV (Joule/MVA) where C, VC and SCONV represent the DC (6-3) link capacitance value, the DC voltage, and the converter’s throughput power (MVA), respectively. It is analogous to the unit inertia constant in synchronous rotary condensers. As in Equation (6-3) each variable represents equivalent total values, it follows that 165 VDC = (1/ m) ⋅ (1/ n) ⋅ (VINJ / T) = 13.6(kV) (6-4) SCONV = 3 ⋅ VINJ ⋅ I INJ = 17.6(MVA) (6-5) In (6-4), m = (√2/π)·sin(σ/2) is the converter gain that relates the total DC voltage to the fundamental RMS output voltage. For ideal shunt connected reactive power compensators, the UCC value can be quite small – in the range of 1000 to 1500 (Joule/MVA) [53, 61]. This is because the voltage source converter does not exchange any real power with the utility and DC bus capacitance requirement for only reactive power compensation is rather small [61]. However, for voltage source converters used in an SSSC, any line disturbance will transiently cause real power transfer between the converter and system. Therefore, UCC values ranging from 3000 to 6000 (Joule/MVA) are considered typical for voltage source converters used for series reactive power compensators [16, 62, 63]. Using Equations (6-4) and (6-5) and choosing UCC=5250, C=1000(µF). However, as shown if Figure 6-2(a), the DC the solution of (6-4) gives link in the three level neutral point clamped converter is actually realized using two capacitors connected in series. Therefore, the ratings for each capacitor are, C1 = C2 = 2C = 2000(µF) (6-6) VDC1 = VDC2 = VDC / 2 = 6.8(kV) (6-7) The RMS current through the DC capacitors can be computed analytically in terms of IINJ considering the converter’s switching function [51] and the phase−shift introduced by the 166 various transformers, IRMS DC = (6-8) 1 3 6 3 5 2 1 3 6 3 3 3 2 3 ⋅ [( + + + )⋅π + ( + + + ) ⋅ cos σ] ⋅ I INJ 2π 16 4 16 2 4 4 4 2 At full compensation it turns out to be I RMS DC = 130(A) . 6.4.2.3.2 Ξ−Controller Capacitor Selection In this case, as all variables are AC, the selection of the capacitance value is directly determined by the amount of compensation required by the transmission line. For security reasons, the operation of the PWM switches is usually restricted to dmin<d<dmax, so the targeted increase in the line power should be achieved at d=dmax. Typical values for dmin and dmax are 10% and 90%, respectively. Considering the realization shown in Figure 6-1(b), the capacitance of each individual capacitor bank can be computed as C= T ⋅ (d max )2 ⋅ n 2 = 1360(µF) (2πFP )VINJ / IINJ (6-9) where FP=60(Hz) is the line frequency. As the capacitor is by nature a voltage−stiff variable, the voltage across it can be assumed to be harmonic−free and therefore the RMS value can be computed as, (6-10) VC = (1/ d max ) ⋅ (1/ n) ⋅ (VINJ / T) = 1.7(kV) On the other hand, the capacitor current is a switched variable so the RMS value has to 167 account for both the fundamental as well as the harmonics generated from the switching process. From the converter’s switching functions, the RMS capacitor current can be computed a RMS IC = d max ⋅ n ⋅ I INJ = 915(A) (6-11) On the other hand, the fundamental component alone, as computed from Equations (6-9) and (6-10) is (6-12) IC = VC ⋅ (2πFP ) ⋅ C = d max ⋅ n ⋅ IINJ = 869(A) The amount of stored energy is a rough measure of the physical size of the capacitors and may be determined from the voltage and capacitance ratings. Table 6-4 summarizes the capacitor requirements for each compensator. Table 6-4 Capacitor Requirements Summary Capacitance (µF) Voltage (kV) Rms Current (A) Number of Capacitor Banks Total stored energy capacity (kJ) Computer simulations have shown that in the SSSC Ξ−Controller 2000 6.8 (DC) 130 2 92.48 1360 1.7 (RMS AC) 915 12 47.16 SSSC case and the Ξ−controller case, these choices for the capacitance leads to acceptable voltage ripple with no resonant interactions. 168 6.4.2.4 Converter 6.4.2.4.1 Semiconductors Ratings High power semiconductor datasheets usually specify the maximum voltage a device can block, the maximum average on−state current and the maximum controlled interruptible current. Analytical formulas to express these requirements in terms of the compensation level have been developed and are presented in Table 6-5, along with the numerical values for the case study system. In addition, any realization of switch using discrete power semiconductors needs to account for continued operation during possible failures. This generally requires a parallel and/or series connection of power semiconductors, typically with ‘n−1’ reliability. Parallel connected devices are able to ride−through an open circuit failure, while series connected devices are able to withstand a short circuit failure, if the remaining devices in the realization have adequate margins of safety. This leads to the choice of series connected string of IGCTs for the SSSC and a parallel connected IGBTs for the Ξ−controller. Since IGCTs have been readily available as press−packs and IGBTs have been readily available as planar modules, the choice naturally fits the ride−through criteria. Such realizations have been demonstrated and definitively evaluated in previous investigations [54, 55]. A simplified schematic of the switch realization is shown in Figure 6-6. The blocking voltage / conducting current capability of each of these arrangements under normal operation as well as under ‘n−1’ contingency are summarized in Table 6-6. These 169 may be compared against the converter operating requirements listed in Table 6-5. Table 6-7 shows the device count for each compensator. As can be seen, although the device count for the SSSC largely exceeds the Ξ−controller, total semiconductor MVA required is only 60% higher. Figure 6-6 Switch realization in terms of real semiconductors. For the SSSC, 4 series IGCT with antiparallel diode (ABB 5SHX 08F4510) are used. The clamping diode is also realized using 4 diodes in series (ABB 5SDF 03D4502). For the Ξ−controller, 3 parallel IGBT with antiparallel diode (EUPEC FZ600R65KF1) are used. Table 6-5 Devices Stress sssc Ξ−Controller Blocking Voltage VDC/2 = 6.8(kV) √3·√2·VC=4.2(kV) 2 ⋅ n ⋅ I INJ ⋅ ξ =390(A) 2π Max. Ave. 2 σ sin(2d max − 1)π / q ⋅ n ⋅ IINJ (cos + 1) =58(A) Notes: ξ = 1+ On−State Current 2π 2 sin π / q q= FSW / FP =12 Max. Switching Current 2 ⋅ n ⋅ I INJ sin σ =339(A) 2 2 ⋅ n ⋅ IINJ =1360(A) 170 Table 6-6 Devices Capability Ξ−Controller 3 Parallel IGBT−Diode SSSC 4 Series IGCT−Diode Normal Operation Blocking Voltage 4·2.8 = 11.2(kV) 6.5 (kV) Max. Ave. On−State Current 250 (A) 3·600 =1800(A) Max. Switching Current 630 (A) 3·1200=3600(A) n−1 Contingency Blocking Voltage 3·2.8 = 8.4(kV) 6.5 (kV) Max. Ave. On−State Current 250 (A) 2·600 =1200(A) Max. Switching Current 630 (A) 2·1200 =2400(A) Table 6-7 Device Count Device 6.4.2.4.2 SSSC Ξ−Controller IGBT − 72 IGCT 192 − Diode 288 72 Total semiconductor MVA 561.6 336 Device Losses Typically, semiconductor losses are categorized as conduction loss and switching loss. The former occur during the semiconductor’s on−state while the latter take place at the transition from on−state to off−state (or vice−versa). The conduction loss for diodes as well as for IGBT and IGCT is usually modeled by the product of the voltage drop across the device and the current through it. If the voltage drop is approximated by a linear dependence on the current 171 (6-13) VON (ION ) = V0 + rON ION then, it readily follows that the average power loss can be determined as 2 PON = V0 ION{ave} + rON ION{rms} (6-14) The on−state voltage V0 and rON are usually available on the device datasheet. On the other hand, the switching loss depends on the energy dissipated at every switching event. The switching energy is usually assumed to be proportional to the blocking voltage and the conducting current at the switching event Ei = ER V R IR (6-15) Vi Ii where, ER, VR, and IR represent the reference values for the energy loss, the blocking voltage and the conducting current. These values are usually available on the manufacturer’s datasheets. The subindex i represents the switching event. The power loss over a power period is computed as P = FP ∑ Ei (6-16) i where, the subindex i sweeps all switching events that occur during the corresponding period. In the case of IGBT and IGCT there is loss at both the turn−on and turn−off events. While for diodes switching loss occurs only during the reserve recovery 172 that takes place at the turn−off. Given the symmetries encountered in the voltage and current waveforms, analytical formulas to express the losses in terms of the compensation level have been developed and are presented in Table 6-8. Table 6-8 Converter Losses Type SSSC PC = s ⋅ 24 ⋅ n ⋅ I INJ ⋅ Conduction Switching 2 n ⋅ I INJ (VCE0 + VF0 ) + (rCE + rF ) π 2 3πVINJ I INJ PS = FP ⋅ 2 E ON E OFF E RR 4 R R + 4 R R + 6 R R VOFF IOFF VRR I RR VON ION Ξ−Controller PC = p ⋅12 ⋅ (n ⋅ I INJ / p) ⋅ 2 (n ⋅ I INJ / p) (VCE0 + VF0 ) + (rCE + rF ) 2 π 2π 2π cos d cos(1 − d) VINJ ⋅ IINJ q q ⋅ ⋅ 3q +9 PS = FP 2π d s in q E ON E E R R + R OFFR + R RRR VON ION VOFF IOFF VRR IRR Notes: 1) Subindex CE refers to IGBTs and IGCTs and subindex F refers to diodes 2) s is the number of IGCTs connected in series 3) p is the number of IGBTs connected in parallel In order to illustrate the development of these formulas, the situation presented in Figure 6-7 may be considered. The top plot shows the Phase−A pole current along with the pole voltage. Depending on the throw connected to the pole is, the pole current flows through different semiconductors. The waveforms of current carried by the different semiconductors for the positive half cycle of the current is shown in the various plots. The labels are consistent with Figure 6-2 and Figure 6-3. Table 6-9 summarizes the semiconductors’ active states for an entire cycle of the current. 173 IA VA IA VA 0 360 180 (a) 0 360 180 t (deg) (b) t (deg) Figure 6-7 Pole current breakup. (a) SSSC, (b) Ξ−controller. Table 6-9 Active state for semiconductors Ξ−controller SSSC VDC1 VDC2 N IA>0 T1A T2A D3A D4A DC1A T2A IA<0 D1A D2A T3A T4A DC2A T3A VCA N T1A D1A T2A D2A IA>0 IA<0 As established by Equations (6-13) through (6-16), the calculation of losses involves computing an average or RMS quantity, or the identification of a switching instant, for waveforms such as the ones presented in Figure 6-7. Once these waveforms are described analytically, then the formulas for the losses are easily computed using the definitions of Equations (6-13) through (6-16). As an example, Table 6-10shows the analytical description for the current through T1A. Table 6-10 Analytical description for IT1A Ξ−Controller SSSC IT1A = ˆIA sin(ωt) (π − σ) / 2 < ωt < (π + σ) / 2 IT1A = ˆIA sin(ωt) i ⋅ 2π / q < ωt < (i + d) ⋅ 2π / q i=0..q/2 174 These formulas can further be integrated and/or summed in order to obtain the final formulae presented in Table 6-8. Table 6-11 shows the numerical values of loss distribution for a typical operating point given by PL=160(MW). In order to achieve such operating point, the compensators need to inject QINJ=7.7(MVAr). It can be seen that the total converter losses are very similar for each approach, and they represent about 1% of the converter’s throughput power. In addition, the power loss in the transmission line is in the order of few megawatts, so the losses added by the converter represent a very small fraction of the losses of the entire system. Table 6-11 Converter Losses for PL=160(MW), QINJ=7.7(MVAr) SSSC Ξ−Controller (kW) Conduction Diode 36.0 14.1 Conduction IGCT/IGBT 21.0 18.9 Turn−on 0.4 23.5 Turn−off 4.8 13.9 Reverse Recovery 3.7 6.3 65.9 76.7 Total 6.4.2.4.3 (kW) Waveform Quality Figure 6-8 shows typical injected waveforms for each compensator. The IEEE Std. 519−1992 [57] establishes that for the power level involved in this case study, the total harmonic distortion (THD) for the bus voltage should be <2.5% and <10% for the line current. As can be seen in Table 6-12, the injected voltage’s THD does not meet the values established by the standard, but this is a differential voltage. The actual 175 line−to−ground voltages (V1 and V2 in Figure 6-4) as well as the line current are well below the value established by the standard. Table 6-12 Total Harmonic Distortion (THD) Variable SSSC (%) Ξ−Controller (%) VINJ 3.60 17.50 IL 0.01 0.04 V1 0.30 0.60 V2 0.10 0.20 Figure 6-8 Voltage/Current injected into the transmission line. (a) SSSC, (b) Ξ−controller. 6.5 6.5.1 Dynamic performance evaluation Dynamic Modeling The dynamic equivalent circuits presented in Figure 6-9 can be used to develop the state space model for each compensator. These circuits are a generalization of the steady state equivalent circuit presented in Figure 6-5. It should be noticed that only the interaction between fundamental quantities is considered, so the resulting state space is a 176 dynamic phasors−based model [35, 51]. IL + VINJ IL - IDC + VDC IC m VDC -m IL + + VINJ - d VC + VC (a) - -d IL + (b) - Figure 6-9 Dynamic equivalent circuits. (a) SSSC, (b) Ξ−controller. In the SSSC case, the converter gain is a phasor quantity defined as m = m∠(∢I L ± 90 + α) (6-17) where, α is the control angle that allows charging/discharging the capacitors in order to achieve the desired compensation. In the Ξ−controller case, the duty ratio, d, provides the means to vary the compensation level. 6.5.2 Control Structure Section 6.4.1 has shown that both the SSSC and the Ξ−controller can operate in voltage, impedance or power control mode. The operation under power control mode has been chosen in order to illustrate the regulator design process. Figure 6-10 shows the control structure for each compensator under power control mode. As can be seen, the main loop that allows the line power to be set to a reference value is the same in both cases. In order to compute the instantaneous value of the line power, the voltage/current at location V2 are measured, transformed into the dq coordinates and processed through a first order filter. This allows computation of the line power as PL=VdId+VqIq. The value of PL is then passed through a feedback gain and 177 compared to the reference power P*. The error signal generated is processed through a regulator to finally obtain the control variable of each compensator (α, d). Figure 6-10 Feedback control loop. TS=5 (ms), β =10-6. (a) SSSC, (b) Ξ−controller. In the case of the SSSC two additional inner loops are necessary to operate the converter. As shown in Figure 6-10(a), a phase−lock−loop is needed to assure that the injected voltage is in quadrature with the line current. In addition, a voltage equalizing algorithm is needed to ensure that the DC capacitors share the same voltage. Details of the implementation of such an algorithm are presented in Figure 6-11 and discussed in the literature [53]. Figure 6-11 Dc voltage equalizing algorithm. 178 6.5.3 Regulator Design The procedure for the design of the feedback regulator was extensively discussed in Chapter 5. The same approach is used here for both the SSSC and the Ξ−controller. The transfer functions g(s)=PL/α for the SSSC and g(s)=PL/d for the Ξ−controller are both nonlinear functions so small−signal transfer functions linearized around a typical operating point are actually considered in the design process. Figure 6-12 illustrate the design process: T(s) is first deployed without compensation (T(s)=β·g(s)). Next, adequate regulators h(s) are introduced in order to achieve acceptable gain margin (GM), phase margin (PM) and bandwidth (BW). In the SSSC case, only proportional action is needed as T(s) has a natural infinite gain [64]. In contrast, the Ξ−controller needs both DC proportional and integral action in order to achieve adequate performance. Table 6-13 summarizes the particulars of each design. SSSC Bode Diagram -Controller Bode Diagram 200 200 150 150 g(s)| 100 GM=20(dB) 50 50 0 0 -50 g(s)| 100 BW=1.8(Hz) -50 h(s)g(s)| -100 270 GM=16(dB) h(s)g(s)| -100 360 PM=84o 180 180 90 0 g(s) PM=86o g(s) h(s)g(s) h(s)g(s) 0 10 BW=1.7(Hz) -180 -1 10 0 10 1 Freq (Hz) 2 10 3 10 (a) 10 -1 10 0 10 1 2 10 Freq (Hz) Figure 6-12 Small signal frequency response of loop gain of (a) SSSC, (b) Ξ−controller. 3 10 (b) 179 Table 6-13 Regulator Design Results Variable 6.5.4 Ξ−Controller SSSC -3 3.0 10-7 KP 3.7 10 KI 0 0.16 GM (dB) 20 16 PM (deg) 84 86 BW (Hz) 1.8 1.7 Command Response Figure 6-13 shows the system response upon changes in the commanded power. The top trace shows the changes applied to the reference power along with the response of the line power. The line current, capacitor voltage and the control variables are also shown in the figure. The comparison of Figure 6-13(a) and (b) shows that the SSSC and the Ξ−controller respond in a very similar manner, as predicted by similar values of GM, PM and BW. Instantaneous Line Power 170 Instantaneous Line Power 170 PMEAS PREF PMEAS PREF 160 160 Instantaneous Line Current Instantaneous Line Current 1.2 1.2 1.1 1.1 DC Link Voltage 0.8 AC Link Voltage 1 0.6 0.4 Control Angle 3 Duty Ratio 80 0 -3 1 2 3 Time (sec) 4 5 (a) 60 1 2 3 4 5 (b) Time (sec) Figure 6-13 Computer simulation waveforms illustrating response to command changes. (a) SSSC, (b) Ξ−controller. 180 6.5.5 Disturbance Response In order to test the ability of the SSSC and the Ξ−controller to maintain control upon system’s changes, two types of disturbances are considered. Figure 6-14 shows the system’s response when a voltage sag/swell at the sending end bus occur and when disturbances on the transmission angle take place. These are four independent events that have been plotted together for convenience. The two top plots show the disturbances while the two bottom ones show the response of the line power and the line current, respectively. The response of the Ξ−controller and the SSSC response are similar to each other. Voltage Disturbance Voltage Disturbance 1 1 Sag Sag Swell 0.95 Swell 0.95 Transmission Angle Disturbance Transmission Angle Disturbance 20 20 Increase Decrease Increase Decrease 17 17 Instantaneous Line Power PREF 170 Instantaneous Line Power PREF 170 160 160 PMEAS 150 PMEAS 150 Instantaneous Line Current Instantaneous Line Current 1.2 1.2 1.1 1.1 1 1 1 2 3 Time (sec) 4 5 (a) 1 2 3 Time (sec) 4 5 (b) Figure 6-14 Computer simulation waveforms illustrating response to bus voltage and angle disturbances. (a) SSSC, (b) Ξ−controller. 6.6 Summary This chapter has presented an analytical comparative evaluation of a modern DC link based power flow control device, namely the Static Synchronous Series Compensator and one of the devices introduced in this thesis, namely the Ξ−controller. 181 Although these approaches represent radically different principles of operation to realize reactive series compensation for power flow control, they feature similar functional capabilities. Extensive analytical formulations that determine the various design elements have been developed in this chapter. They have been used to realize a benchmark case study to provide numerical values for various design features. The measures of comparison that have been presented in various tables in the chapter include: transformer ratings, capacitor ratings, semiconductor ratings, semiconductor losses, waveform quality indices and dynamic control properties. The analytical solutions and operation of both the designs have been verified using detailed computer simulations. Selected computer simulation results that compare the performance have been presented in this chapter. Based on the comparison of the results from the case study, it may be concluded that suitably designed DC link and AC link approaches are both competitive against each other in realizing series power flow control. The DC link approach requires about twice as much capacitive energy storage and about 66% additional power semiconductor MVA rating, while the AC link approach has about 15% more losses in power semiconductors, using state of the art semiconductor devices. All other summative measures indicate similar levels of steady state and dynamic performance. 182 Chapter 7 Experimental Verification of the Γ−Controller 7.1 Introduction This chapter describes efforts aimed at experimentally proving the concept of using a vector switching converter for realizing power flow control. Out of the Π, Ξ and Γ controllers introduced in Chapter 3, the Γ−controller was selected for experimental verification as it can be considered the most general case. The reason for this is twofold: (i) the circuital interconnection involves a shunt−series arrangement and (ii) the converter involves the realization of a multiple−throw switch. Figure 7-1 shows a schematic of the system implemented in the laboratory. VS S Bus S VR -Controller SPT AC link VESC SIT Transmission Line R Bus R Figure 7-1 Schematic of the Γ−controller system implemented in the laboratory. Notice that the above figure strongly resembles Figure 3-20, which was use to introduced the Γ−controller in Section 3.4. The following sections describe the experiment layout, 183 along with experimental waveforms contrasted against computer simulation results. 7.2 Experiment Layout As explained in Chapter 3, the Γ−controller operates embedded into a transmission line. Therefore, a laboratory prototype of a transmission line is discussed first followed by a laboratory prototype of the Γ−controller itself. Also, given the availability of resources at the laboratory, the prototype described below is conceived to operate in a three−phase 230V/60Hz system. 7.2.1 Laboratory Prototype of a Transmission Line A complete model of a transmission line usually includes four distributed parameters: series resistance, series inductance, shunt conductance and shunt capacitance. However, it is customary in power flow controller studies to consider only the effect of the series elements. Moreover, the distributed nature of these parameters is also neglected which leads to the representation of the transmission line as shown in Figure 1-1 i.e., as a series combination of constant resistance and constant inductance [4]. This is implemented with an adjustable inductor available in the laboratory. The inductor is set at L=5.6mH and the measured series resistance is R=0.27Ω. This leads to a ratio XL/R of 7.8 which is within the typical values encountered in transmission lines. The inductor is rated at Imax=40A. 184 Figure 7-2 Laboratory prototype of a transmission line. As suggested in Figure 7-1, the transmission line connects busbars whose voltages (magnitude and angle) are stiff quantities. This reflects the operation of actual power systems where at every busbar the voltage magnitude is kept very close to its nominal value and the power flows result mostly from angle differences between the busbars. Figure 7-3 shows a laboratory prototype of a transmission line connecting two busbars that properly takes into account these effects [65]. As can be seen in the figure, a phase−shifted transformer connected in the so−called “Marserau configuration” [66] has been introduced in order to create a transmission angle. This configuration allows introduction of a transmission angle between the busbars without changing the magnitude of the voltage. This is shown in the phasor−diagram accompanying the figure. The actual value of the transmission angle θ is determined by the windings turn ratio. Each transformer is rated at 230V at the primary side and 36V at the secondary side. This allows creation of a transmission angle θ=15o. 185 sin n= θ Vax / 2 = 2 Va nH 3 = n L 2 ⋅ tg θ 2 Figure 7-3 Laboratory prototype of a transmission line connecting two stiff voltage busbars. 7.2.2 Laboratory Prototype of a Γ−Controller Figure 7-4 shows the schematic of the Γ−controller laboratory prototype. The blocks labeled as SPT, AC link and 3T−1P 3φ VeSC were built for a different application and in this thesis they have been adapted to operate as a power flow controller. As can be seen, a realization with one primary and three secondary transformers is being considered. This leads to the implementation of a triple throw single pole three−phase vector switching converter for synthesizing the pole voltage. This topology with Y−connected transformers was studied in detail in Chapter 2. The use of ∆−connected transformers does not change any of the claims made in Chapter 2 whatsoever. On the contrary, it adds to the versatility of VeSC−based topologies. 186 Sa Va1 a1 SIT Va2 c1 Vai b1 Va3 Sb Vb1 b2 A Vb2 C a2 B Vbi c2 Vb3 SPT Sc Vc1 c3 Vb2 b3 Vci a3 Vc3 AC LINK 3T-1P 3 VESC Figure 7-4 Laboratory prototype of a Γ−controller. The ratings of the main components are presented in Table 7-1. Table 7-1 Γ−controller component rating Item SPT Transformer AC Capacitor IGBT−Diode Ratings 240V/240V 6kVA 30µF 300V 4A Modules 600V 15A Fuji 1MB15D−060 SIT Transformer The IGBTs are driven by a standard 230V/36V 5.4kVA DSP/FPGA/PC system developed at the University of Wisconsin [67]. The switching frequency was randomly picked to be FSW=5kHz. Computer simulations showed that no resonance frequencies are excited at 5kHz. The converter is embedded in the system as shown in Figure 7-1. For completeness, the entire system is shown again in Figure 7-5 along with a picture of the hardware built in the laboratory in Figure 7-6. Figure 7-5 Detailed laboratory prototype of a Γ−controller system. 187 188 Figure 7-6 Picture of hardware built at the laboratory. 7.3 Experimental Waveforms Although the system was designed to operate at 230V, experimental waveforms were captured with the variac set at 100V. This was for the safety of the semiconductors because no protective devices were installed. In reference to Figure 7-3, Equation (1-1) allows calculation of the complex power without the Γ−controller embedded in the transmission line, which is found to be S=1246 +j 11 (VA). This is the base power which will be subject to alterations by the insertion of the Γ−controller. A detailed computer simulation of the Γ−controller system shown in Figure 7-5 was implemented in order to contrast experimental waveforms against theoretical 189 predictions. Two sets of measurements are considered. A steady state case study is used to show the internal workings of the Γ−controller operation and a dynamic case study is also implemented in order to show the system level operation of the Γ−controller. 7.3.1 Steady Sate Operation As mentioned in Section 7.3, the complex power flow through the transmission line without the Γ−controller embedded is given by S=1246 +j 11 (VA). The insertion of the Γ−controller into the transmission line allows complex flow control over a region determined by the voltage synthesized by the converter. Figure 7-7(a) shows that this voltage can be anywhere inside the triangle formed by the throw voltages of the converter. However, it was explained in Chapter 3 that the interest is in symmetrical realizations for the pole voltage and therefore the operation of the converter is limited to the circle inscribed in the triangle. 1 400 V1 300 200 0.5 Q (VAr) Im 100 0 Base case 0 Target -100 -200 -0.5 V2 V3 -300 -1 -1 -0.5 0 Re 0.5 1 (a) -400 800 900 1000 1100 1200 1300 P (W) 1400 1500 1600 1700 (b) Figure 7-7 Attainable pole voltage (a) and the corresponding power diagram (b). Figure 7-7(b) shows the power diagram that results from mapping the pole 190 voltage circle into the P−Q plane. The complex power to generate this diagram is measured right before the RL branch, at location V2 in Figure 7-5. The power diagram indicates all reachable values for the complex power that can be obtained by modulating the duty ratios of the converter. In order to show the operation of the converter, a random operating point specified in Table 7-2 was selected. Table 7-2 Operating Point Item Value Duty ratios d1=33% d2=50% d3=17% Voltage @ V2 (peak) V2= 81(V) Line Current (peak) IL= 8.4 (A) Injected Voltage (peak) Vinj= 3.8 (V) Active Power P= 1023 (W) Reactive Power Q= −40 (VAr) Figure 7-8 shows the gate voltage applied to the IGBTs. The top, middle and bottom trace shows the gate voltage applied to the IGBTs corresponding to the throws 1, 2 and 3, respectively. It should be noted that the average value of those voltages corresponds to the duty ratios specified in Table 7-2. 191 Figure 7-8 Experimental waveforms showing the gate voltage applied to the IGBTs. Figure 7-9 and Figure 7-10 show the voltage at location V2 and the line current, respectively. In both figures, part (a) shows the experimental waveforms while part (b) shows waveforms obtained from simulations. 125 100 75 50 25 0 -25 -50 -75 -100 -125 Figure 7-9 Waveforms showing the voltage at location V2. (a) Experimental (b) Simulated. 192 Ia Ib 10 Ic Ia Ib Ic 8 6 4 2 0 -2 -4 -6 -8 -10 Time (a) (b) Figure 7-10 Waveforms showing the line current. (a) Experimental (b) Simulated. In order to help the visualization, the grid from the simulated waveforms has been made to match the division from the oscilloscope screen. The match between experimental and simulated waveforms is evident. In the experimental case, some unbalance between the phases is observed. This is because the inductors used to emulate the transmission line were not exactly equal. Figure 7-11 through Figure 7-13 illustrate the pole voltage synthesized by the converter. Again, part (a) shows experimental results and part (b) shows the corresponding simulated waveforms and the grid of the simulated waveforms is made to match the divisions of the oscilloscope screen. Figure 7-11 shows the actual three−phase switched voltages, but due to the high frequency switching process taking place the pictures in both cases are blurry. 193 25 20 15 10 5 0 -5 -10 -15 -20 -25 Time (a) (b) Figure 7-11 Waveforms showing the injected voltage. (a) Experimental (b) Simulated. Thus, in order to be able to contrast these waveforms, two extra sets of plots are presented. Figure 7-12 shows the fundamental component of the switched waveforms depicted above and Figure 7-13 shows an experimental versus simulated comparison of one of the phases at the switching frequency timescale. Once again, the match between experiments and predictions made by simulations is evident. 25 20 15 10 5 0 -5 -10 -15 -20 -25 Figure 7-12 Waveforms showing the fundamental component of the injected voltage. (a) Experimental (b) Simulated. 194 25 20 15 10 5 0 -5 -10 -15 -20 -25 Time (a) (b) Figure 7-13 Waveforms showing the injected voltage at the switching frequency timescale. (a) Experimental (b) Simulated. 7.3.2 Dynamic Operation The previous section has shown an experimental verification of the Γ−controller from the converter’s point of view. The intent of this section is to illustrate the operation of the Γ−controller from the system’s point of view i.e., to show the transition between different operating points. These ideas were discussed in Section 3.4 where the Γ−controller was first introduced. It was shown through computer simulations that the transitions between operating points are smooth and free of oscillation if the converter’s duty ratios are slowly ramped from one value into another. Figure 7-14 shows an example of this. The top trace shows the duty ratios applied to the converter. It can be seen that the transition takes place in “one division” which corresponds to two seconds. The next traces show, from top to bottom, the voltage at location V2, the line current and the injected voltage, respectively. 195 Figure 7-14 Experimental waveforms illustrating the transition from one operating point to another by means of duty ratio ramping. As can be seen from all three traces, the transition is smooth and free of oscillation which confirms the theoretical claim that duty ratio ramping is an appropriate strategy for the operation of VeSC−based power flow controllers. 7.4 Summary This chapter has been devoted to discussion of efforts to experimentally prove the concept of using VeSC−based devices for realizing power flow control in transmission networks. Out of the three topologies proposed in this thesis, the Γ−controller was selected for experimental verification as it is seen by the author as the most general case. 196 A Γ−controller prototype was built and tested at the WEMPEC laboratory. Experimental waveforms were contrasted against predictions made by computer simulations. Several illustrative experimental waveforms were presented which very closely matched the corresponding simulated waveforms. Also, the idea of duty ratio ramping to change operating points was implemented in the hardware. Once again, the results from experiments confirmed theoretical predictions. As mentioned above, this experiment did not include the actual measurement of the complex power. The reason is that the laboratory does not have proper equipment to measure instantaneous complex power, especially in the presence of harmonics and unbalanced currents. This is indeed an ongoing research topic that is beyond the scope of this thesis. 197 Chapter 8 Optimal Power Flow with AC Link Power Flow Controllers Embedded 8.1 Introduction In the previous chapters, AC link power flow controllers were analyzed in great detail, but the focus was on the device itself rather than its function. This chapter is intended to give a system point of view for the problem of load flow control in electric power systems with AC link power flow controllers embedded. Electric power systems can be operated in a variety of ways, depending on the specific goals to be attained. Typically, such goals may include the minimization of the overall energy production cost of the system (economic dispatch), the minimization of the emission of particles (environmental dispatch), the minimization of system losses, or a combination of these goals [5]. In addition, modern power systems consist of various control areas, so the optimization of the power exchange between them is an additional goal that one may want to achieve. This particular issue is of special interest within the deregulated power markets framework. This is closely related to what is referred to as loop flow problem, as explained next [68]. Consider a power system consisting of three control areas, as suggested in Figure 198 8-1. The control areas are connected via interfaces, which correspond to a number of transmission lines that interconnect the corresponding control areas [69]. Assume that, initially, area A is exchanging power with areas B and C by an amount of PAB and PAC, respectively. Figure 8-1. A 3−area electric power system. In addition, consider that areas A and B want to increase their power exchange by an amount of ∆PAB, but the power exchange between areas A and C needs to be held constant, because, for example, the interface is at its limit. In order to perform the transaction, Area A increases its net power by ∆PAB and Area B decreases its net production by the same amount. However, the actual flows would be as shown in the figure. A portion of ∆PAB would effectively flow through the corresponding interface, but some of it, a loop flow, would go through the Area C, violating the restriction of holding the AC interface flow constant. This is because power flows are not ruled by contractual paths but by Kirchhoff’s laws. Loop flows, as well as the optimal dispatch problem, can be greatly improved by embedding FACTS devices into the transmission system, as has been shown in numerous 199 publications [1, 3, 7, 69-78]. The methodology consists of developing a steady state model for the corresponding FACTS device and incorporating this model into the so−called Optimal Power Flow problem (OPF). Next, the standard OPF problem is formulated followed by its adaptation when Ξ−controllers are present. A case study is also discussed. 8.2 Standard OPF The standard optimal power flow [5] is formulated as follows: Objective Function Optimize f (Vb , θ b ) b∈B B: All system Buses (8-1) g∈G G: Generation Buses (8-2) Equality Constraints Pg = P(Vb , θ b ) + PgL Q g = Q(Vb , θ b ) + Q gL PdL = P(Vb , θ b ) (8-3) d∈D D: Load Buses Q dL = Q(Vb , θ b ) (8-4) (8-5) Inequality Constraints Vbmin ≤ Vb ≤ Vbmax max θ min bS ≤ θ bS ≤ θ bS (8-6) b S ∈ BS BS: Same as B excluding slack bus Pgmin ≤ Pg ≤ Pgmax (8-7) (8-8) Q gmin ≤ Q g ≤ Q gmax g∈G | S l (Vb , θ b ) |≤ S lmax l∈L (8-9) L: Transmission Lines (8-10) 200 The state of a power system is fully defined by the magnitude and angle of the bus voltages, Vb’s and θb’s, so they are used as explicit variables in the problem formulation. Equation (8-1) represents the objective function to be optimized. In the economic dispatch case, it corresponds to the minimization of the energy production costs summation, Min ∑C g (Pg (Vb , θ b )) g∈G (8-11) g where Cg represents the cost function of the various generators. If the goal is to maximize the power exchange through an interface, the objective function becomes, Max ∑ P (V , θ i b b ) i∈I (8-12) i where I represents the set of transmission lines belonging to the interface. Other objective function can be readily formulated; and via the Pareto’s optimality criterion [76], multiple objective functions can be pursued. The equality constraints described by Equations (8-2) through (8-5) represent the power flow equations that dictate the physical restrictions of the problem. They force a balance between the power injected into the network by the generators and the power demanded by the loads plus the transmission losses. 201 Finally, the inequality constraints described by Equations (8-6) through (8-10) represent the operational limits of the various components. Equations (8-6) and (8-7) say that every bus in the system has to operate within acceptable voltage ranges. Equations (8-8) and (8-9) dictate the capacity limits for generators. Lastly, Equation (8-10) specify the most important restriction within the FACTS context, saying that transmission lines have a limited capacity to carry power. This transmission line limit can be expressed in terms of either current, active power, or apparent power. The last approach is chosen here. 8.3 8.3.1 OPF with Ξ−controllers embedded The model The steady state model for the Ξ−controller readily follows from its equivalent circuit. Aggregating the distributed parameters of Figure 3-14, the following simplified model can be obtained, Figure 8-2 Simplified Equivalent Circuit for the Ξ−controller. where X L = ω P (L S + L R + L T ) , R L = R S + R R , and X C = 1 / ω P C . Thus, the overall transmission line impedance can now be thought of as, 202 Z = R L + j (X L − d 2 X C ) (8-13) The additional degree of freedom introduced by the controllable variable d can be interpreted as having a tunable line reactance within range X L − X C ≤ X ≤ X L . Once the value for X has been determined, the corresponding duty ratio can be calculated as, d= XL − X XC 8.3.2 (8-14) OPF Formulation The OPF problem for a power system with Ξ−controllers embedded can be formulated as follows, Objective Function Optimize f (Vb , θ b , X ξ ) b∈B B: All system Buses ξ∈Ξ Ξ: Lines with a Ξ−controller g∈G G: Generation Buses (8-15) Equality Constraints Pg = P(Vb , θ b , X ξ ) + PgL Q g = Q(Vb , θ b , X ξ ) + Q gL PdL = P(Vb , θ b , X ξ ) Q dL = Q(Vb , θ b , X ξ ) (8-16) (8-17) d∈D D: Load Buses (8-18) (8-19) 203 Inequality Constraints Vbmin ≤ Vb ≤ Vbmax max θ min bS ≤ θ bS ≤ θ bS (8-20) b S ∈ BS BS: Same as B excluding slack bus (8-21) Pgmin ≤ Pg ≤ Pgmax (8-22) Q gmin ≤ Q g ≤ Q gmax (8-23) | S l (Vb , θ b , X ξ ) |≤ S lmax L: Transmission Lines l∈L X Lξ − X Cξ ≤ X ξ ≤ X Lξ (8-24) (8-25) Equations (8-15) through (8-24) have the same interpretation as in the standard OPF formulation, but now they feature an extra degree of freedom introduced by the explicit variables Xξ. Equation (8-25) forces the corresponding duty ratios for Xξ to be within admissible range ( 0 ≤ d ξ ≤ 1 ). When control areas are present, additional constraints in the form of inequalities or equalities can be added on the corresponding interfaces in order to satisfy operating restrictions. For example, to avoid the loop flow between areas A and B in the introductory discussion, the following equality constraints can be added, Additional Equality Constraints ∑ P (V , θ b ) = PAC i ∈ I AC IAC: AC Interface (8-26) ∑ P (V , θ b ) = PBC i ∈ I BC IBC: BC Interface (8-27) i b i i i b where PAC and PBC represent pre−established values for the total power exchange 204 between the areas. The OPF problem described above was implemented in the MATLAB environment. It clearly corresponds to a non−linear optimization problem. The optimality conditions, known as Karush−Kuhn−Tucker (KKT) conditions, are obtained by successively approximating the objective function by a quadratic function and the constraints by linear functions. This problem, known as a quadratic programming (QP), is solved by standard methods described in the literature [79, 80]. As will become evident in the case study discussed below, the presence of the Ξ−controllers allows for more flexible operation of the overall system, yielding better results in the objective function pursued. 8.3.3 Amount and Location In the OPF formulation discussed above, nothing was said about the nature of the set Ξ (the set of transmission lines containing Ξ−controllers), in terms of how many devices should be used and where to locate them. The number of controllers as well as the allocation within the system has been the subject of many publications throughout the last few years [69, 74, 78, 81, 82]. Results vary depending on the objective function to be pursued and the nature of the controller considered. This topic however, is beyond the scope of this thesis. In addition, since the Ξ−controller is functionally similar to the SSSC and TCSC, previous studies for these devices can be utilized for this purpose. 205 8.3.4 Case Study In order to appreciate the flexibility resulting from the presence of the Ξ−controller, consider the IEEE 39−bus system sketched in Figure 8-3. This system represents a simplification of the New England interconnection, in the Northeastern U.S. The 39−bus system has 10 generators, 19 loads, 35 transmission lines and 12 transformers. In addition, the system is organized into three areas. The complete set of data is presented in Appendix 5. 32 9 31 8 Buses Loads Lines Generators 10 34 33 11 7 36 13 6 Area C 5 20 12 23 14 19 39 4 24 IAC 15 22 IBC 21 3 17 2 Area A 27 18 IAB Area B 30 35 16 1 38 26 28 25 29 37 Figure 8-3 The IEEE 39−bus system. The study considers the economic dispatch OPF and the interface power maximization OPF separately. In each case, the results obtained with the system as is i.e., 206 without any Ξ−controller, are compared against the results obtained with a fully controlled system i. e., with a Ξ−controller embedded in every transmission line. The amount of maximum compensation for each Ξ−controller is assumed to be 50% of the corresponding transmission line reactance. Thus, the value of the equivalent reactance of each line can vary within the range, XL ≤ Xξ ≤ XL 2 8.3.4.1 ξ∈L L: Transmission Lines (8-28) Economic Dispatch For the economic dispatch OPF, Equation (8-11) describes the objective function. The cost function for each generator is assumed quadratic, as shown in TABLE II, Appendix 5. (i) Results without Ξ−controllers embedded Objective function: 98,674 ($/h) Table 8-1 Active Constraints Bus Max V Min V 38 20, 30, 33, 36 Generator Max P Max Q Min Q 30, 31, 32, 36, 31, 32, 39 37, 38, 39 Line Max MVA 16-17 Since this case will be used as base case for the interface power maximization discussion, these results are also provided, 207 Table 8-2 Interface Flows Line 28-26 16-17 29-26 Total A− B Rating P (MVA) (MW) 500 181 500 499 500 232 1500 912 A− C P Rating (MVA) (MW) 15-14 500 178 Total 500 178 Line B−C P Rating (MVA) (MW) 1-39 500 363 3-4 500 102 Total 1000 465 Line In the above table, the total values represent the power exchange between the corresponding control areas. (ii) Results with Ξ−controllers embedded Objective function: 80,106 ($/h) Table 8-3 Active Constraints Bus Max Min V V 10, 19, 22, 25, 29, 36 Generator Max Max Min P Q Q 30, 31 31, 33, 36, 37, 38, 39 Line Max MVA 16-17 For this case, Equation (8-28) is added into the Equivalent Impedance Max Min 3-18, 4-14, 2-3, 2-25, 5-6, 6-7, 3-4, 4-5, 10-13, 13-14, 7-8, 8-9, 17-27, 21-29, 9-39, 14-15, 25-26, 16-17, 15-16, 16-19, 16-21, 16-24, 19-20 17-18, 21-22, 22-23, 28-29, 12-13, 6-31, 23-36 OPF formulation. As can be seen, embedding Ξ−controllers into the transmission lines leads to a reduction of almost 20% in the operation cost of the overall system. An adequate economic evaluation based on the cost benefit ratio (C/B) would give insights about whether it is worth it to invest in 208 these devices [83, 84]. In addition, the active constraints on the equivalent impedance of the lines give valuable information about the real need of Ξ−controllers. Thus, as may be implied from Equation (8-25), the equivalent impedances at their maximum limit are not receiving any compensation from the Ξ−controllers whatsoever and may therefore be eliminated. Similarly, equivalent impedances at their minimum limit are receiving 100% of compensation indicating a potential need for an even larger compensator. Finally, although the active constraints on the bus voltages and generators have changed, the interface AB remains congested, limiting Area B from obtaining cheaper power from Area A. This leads to the next discussion on power exchange between control areas. 8.3.4.2 Interface Power Maximization As was seen in the previous case study, the transmission line 16-17 is acting as a bottleneck binding further power exchange from Area A to B. Say the interest is in somehow increasing the power transfer through the Interface AB. However, due to contractual paths restrictions [71], this must be done while keeping the power exchange between Areas A and C and Areas B and C at their nominal values specified in Table 8-2. For the situation described above, Equation (8-12) describes the OPF objective function while Equations (8-26) and (8-27) force the total power exchange through interfaces AC and BC to remain constant. 209 Results without Ξ−controllers embedded (i) Objective function: 968 (MW) Table 8-4 Interface Flows Line 28-26 16-17 29-26 Total A− B Rating P (MVA) (MW) 500 209 500 499 500 260 1500 968 A− C P Line Rating (MVA) (MW) 15-14 500 178 Total 500 178 B−C P Line Rating (MVA) (MW) 1-39 500 363 3-4 500 102 Total 1000 465 As can be seen, although it is possible to boost the A−C power transfer without using controllable devices, the actual increase is 56(MW), only a 6% of the nominal value. (ii) Results with Ξ−controllers embedded Objective function: 1288 (MW) Table 8-5 Interface Flows Line 28-26 16-17 29-26 Total A− B Rating P (MVA) (MW) 500 368 500 499 500 421 1500 1288 A− C P Line Rating (MVA) (MW) 15-14 500 178 Total 500 178 B−C Line Rating P (MVA) (MW) 1-39 500 454 3-4 500 11 Total 1000 465 210 As in the previous case study, a considerable improvement in the objective function is now observed. The power exchange has been boosted by 376(MW), a 41% with respect to its nominal value. Notice that the flows through the Interface BC have readjusted but the total exchange has remained constant. 8.4 Summary This chapter has given a system point of view for AC link power flow controllers. It has been demonstrated that, by embedding Ξ−controllers into the transmission network, dramatic improvements can be achieved in the flexibility of operation for the overall power system. It was shown that the system model of the Ξ−controller can be thought as having transmission lines with tunable reactance. Using the IEEE 39−bus system as an example, typical operational issues were addressed. Specifically, the optimal power flow formulation showed that the economic operation as well as the loop flow problem can be greatly improved by adding the extra degree of freedom provided by Ξ−controller. 211 Chapter 9 Conclusions and Future Work This thesis has introduced a new family of FACTS devices: the Π−controller, the Ξ−controller and the Γ−controller. Based on the vector switching converter (VeSC), these devices feature similar functional characteristics to those encountered in the voltage source HVDC interties, the Static Synchronous Series Compensator (SSSC) and the Unified Power Flow Controller (UPFC), respectively. The control function, however, is realized by direct AC↔AC conversion without frequency change, adopting the strategy of pulse width modulation (PWM). A comprehensive analysis of each of these devises has been performed, including operating principles, equivalent circuits, design considerations, and dynamic modeling and control. Computer simulations of illustrative examples were executed to validate the approach. Due to the level of power involved, it was concluded that the Π−controller may not be practical with the current state−of−the−art gate turn−off semiconductors. However, the Ξ−controller and Γ−controller would be able to compete with their DC link counterparts. A case study for series compensation has shown the Ξ−controller is indeed favorably comparable to the SSSC. The dynamic modeling for these devices was accomplished using generalized 212 averaging theory. This approach, in contrast with the traditional dynamic phasors model, explicitly incorporates the switching frequency into the state space model, and therefore is able to predict oscillatory behavior of the state variables due to switching and thus preclude potential instabilities in cases when there are system modes in the vicinity of the switching frequency. It was also shown that it can be used for design purposes, as it can predict component stress levels as RMS quantities with a higher degree of accuracy than the traditional model. Feedback control of power flow using the proposed devices was also investigated. For the Ξ−controller case, it was shown that closed loop regulation can be approached by means of classical control design techniques, such us Bode plots and Nyquist’s stability criterion. For the Γ−controller, however, more sophisticated techniques are needed. A laboratory prototype of the Γ−controller developed at the WEMPEC laboratory has proved further the real viability of the use of VeSC−based topologies for power flow control. Laboratory results indicate excellent agreement with the analytical predictions and computer simulations. Finally, a system point of view was given, incorporating the Ξ−controller into an Optimal Power Flow (OPF) program. It was shown that the Ξ−controller adds extra flexibility to the OPF program and dramatically improves the objective function for different goals pursued. 213 9.1 Contributions The main contribution of this thesis is the introduction of AC link VeSC-based power flow controllers. Within this context, several specific contributions are enumerated below. 9.1.1 Modeling and control • Development of equivalent circuits based on controlled sources as presented here allows easy representation of VeSC-based topologies for circuit analysis, computer simulations, steady state and dynamic interaction between the converter and the rest of system, and sizing the various components (capacitors, semiconductors, transformers). • Novel approach for dynamic modeling based on generalized averaging theory applicable to VeSC-based topologies when the ratio between switching frequency and power frequency is an integer number leads to capturing the oscillatory behavior of the state variables when the switching process excites the physical resonances. • The development of the small signal loop gain of the power flow control permits application of classical feedback control design with ease. 9.1.2 Computer simulation • Switched simulations modeling the switches as switching function−controlled sources allow capturing the dynamic of the switching process and can be used to 214 estimate the behavior of the converter during commutation events. The main drawback of switched simulations is the relatively long time they take to run. • Averaged simulation modeling the switches as duty ratio−controlled sources are useful when the interest is in the interaction between the fundamental quantities only. They can be used to test the selection of feedback control gains and for system level dynamic behavior. They run much faster than switched simulations. 9.1.3 Comparison against the state−of−the−art technology for series compensation A detailed comparison between the SSSC and the Ξ−controller was performed. The particulars considered in the comparative evaluation are as follows: • Detailed design considerations of power circuit components − capacitors and semiconductors • Topological approach integrating transformers and appropriate modulation techniques for meeting benchmark harmonic performance levels. • Semiconductors loss modeling using analytical techniques to allow fast computation of thermal performance • Injection transformer design considerations including core loss components • Design and verification of closed loop regulator with more than adequate dynamic performance • Computer simulations verifying functional operation and controller performance during command changes and disturbances. 215 9.1.4 Experimental verification • Experimental waveforms were contrasted against computer simulation predictions. This validated the concept of using VeSC-based topologies for power flow control. • Experimental verification of dynamic operation via duty ratio damping. Experiments confirmed that the best strategy to move from one operating point on to another was via duty ratio ramping. Duty ratio ramping leads to a smooth transition of the line current with no oscillations or overshoot. 9.1.5 System level modeling • Incorporation of AC link VeSC-based series power flow controllers into the optimal power flow problem. It was shown that by embedding VeSC-based series power flow controllers in the transmission lines, a much flexible operation of the system is achieved. 9.2 Proposed Continuing Research Several opportunities for future investigation have been identified that would provide valuable extensions of the research conducted in this thesis. 9.2.1 Feedback Control for Γ−controller The problem of power flow control using the Γ−controller being a MIMO system with multiple degrees of freedom was stated in Section 5.3 referring to Figure 5-10 [48]. 216 The aim is to find an appropriate regulator that can guarantee stable operation of the overall system as well as an adequate dynamic performance, in terms of DC error, speed of response, overshot and oscillations. Since the Γ−controller has been conceived as a complex power flow controller, a proper method to measure instantaneous three−phase reactive power in the presence of harmonics is seen as a critical part of the implementation of the feedback regulator. Advanced control techniques such Mode Predictive Control (MPC) [85] and Passivity Based Control (PBC) [86] are seen by the author as particularly suitable for developing the control structure. There are several needs and opportunities for investigations of feedback control for the Γ−controller, as well as other topologies. 9.2.2 OPF with embedded Γ−controllers The development of a suitable model for the Γ−controller to be incorporated into an OPF program. A research group at CINVESTAV in Mexico has recently initiated work on this topic [87, 88]. 9.2.3 System level dynamics The performance of AC link power flow controllers for system level dynamics present wide opportunities for research work. System level dynamics topics include subsynchronous resonance damping, power oscillations damping, transient stability enhancement, voltage stability, etc. Numerous publications have shown the performance of DC link power flow controllers in this area [1-3, 14]. Similar studies using AC link 217 power flow controllers may reveal further tradeoffs between these two technologies. The same Mexican group has been working on this topic as well [87]. 9.2.4 Multilevel realization for the Ξ−Controller This thesis presented the Ξ−controller as a series device whose principle of operation was based on commuting between a three−phase capacitor bank and a short circuit node. A natural expansion of this concept that may lead to better performance is to use multilevel converters [30] extended to AC link. This would be achieved by using one (or more) three−phase capacitor bank instead of (or in combination with) the short circuit node. 9.2.5 Additional topologies This thesis has studied the use of VeSC–based AC link power flow controllers connected in back−to−back, series and shunt−series configurations. As pointed out in the introduction, DC link power flow controllers can be configured, in addition of these three configurations just mentioned, as shunt (STATCOM) and series−series (IPFC) devices. Topologies based on AC link VeSC can also be derived for these configurations, which could bring forth a treasure−trove of research opportunities. For example, the VeSC−based AC link shunt configuration was studied for a flicker mitigation application [89]. This topology can readily be extended to operate as an AC link STATCOM. 218 9.2.6 Field demonstration It is the hope of the author that the ideas discussed in this thesis may become a reality through a field demonstration in a utility power system. This thesis has established that this technology is viable and the natural continuation of this work would be the actual construction of a utility scale AC link VeSC−based power flow controller. 219 Appendix 1 Parameters for the Π−controller case study Symbol VS RS XS VR RR XR FP TABLE I SYSTEM PARAMETERS Actual value Per unit 110kV 100MVA value 60Hz TABLE II TRANSFORMER STP PARAMETERS Actual value Symbol Per unit value 110/11/6.3/11/6.3kV 180MVA 60Hz 1 0.01 0.17 1 0.01 0.17 1 VP RP XP VS1 RS1 XS1 VS2 RS2 XS2 VS3 RS3 XS3 VS4 RS4 XS4 110kV 1.21 Ω 54.5 mH 110kV 1.21 Ω 54.5 mH 60 Hz TABLE III FILTER CAPACITOR FTC PARAMETERS Symbol Per unit value XC 3 Actual value 11 kV 100MVA 60Hz 730 µF 1 0.001 0.01 1 0.001 0.01 1 0.001 0.01 1 0.001 0.01 1 0.001 0.01 TABLE IV TRANSFORMER BIT PARAMETERS Actual value Per unit Symbol 5.5/110 kV 180MVA value 60 Hz VP RP XP VS RS XS 1 0.0001 0.01 1 0.0001 0.01 TABLE V CONVERTER PARAMETERS Actual Value Symbol Per unit Value 60 Hz FS 40 110kV 0.2 Ω 5.3 mH 11kV 2 mΩ 53 µH 6.3kV 0.67 mΩ 18 µH 11kV 2 mΩ 53 µH 6.3kV 0.67 mΩ 18 µH 2400 Hz 5.5 kV 16 µΩ 5.3 mH 110kV 6.7 mΩ 53 µH 220 Appendix 2 Parameters for the Ξ−controller case study Symbol VS RS XS VR RR XR FP TABLE I SYSTEM PARAMETERS Actual value Per unit 110kV 100MVA value 60Hz 1 0.01 0.07 1 0.01 0.17 1 110kV 1.21 Ω 22.4 mH 110kV 1.21 Ω 54.5 mH 60 Hz TABLE III TRANSFORMER SIT PARAMETERS Actual value Per unit Symbol 15.5/15.5 kV 20MVA value 60Hz VSP RSP XSP VSS RSS XSS RPM XPM 1 0.0001 0.01 1 0.0001 0.01 500 500 15.5 kV 1.2 mΩ 0.3 mH 15.5kV 1.2 mΩ 0.3 mH 6 kΩ 16 H Symbol XC RC TABLE II CAPACITOR PARAMETERS Actual value Per unit 15.5 kV 20MVA value 60Hz 1 500 438 µF 6 kΩ TABLE IV CONVERTER PARAMETERS Symbol Per unit value Actual value 60Hz FS 40 2.4kHz 221 Appendix 3 Parameters for the Γ−controller case study Symbol VS RS XS VR RR XR FP TABLE I SYSTEM PARAMETERS Actual value Per unit 110kV 100MVA value 60Hz TABLE II TRANSFORMER SPT PARAMETERS Actual value Per unit Symbol 110/15.5/8.9/15.5/8.9kV value 20MVA 60Hz 1 0.01 0.07 1 0.01 0.17 1 VPP RPP XPS VPS1 RPS1 XPS1 VPS2 RPS2 XPS2 VPS3 RPS3 XPS3 VPS4 RPS4 XPS4 RPM XPM 110kV 1.21 Ω 22.4 mH 110kV 1.21 Ω 54.5 mH 60 Hz 1 0.001 0.01 1 0.001 0.01 1 0.001 0.01 1 0.001 0.01 1 0.001 0.01 500 500 110kV 0.6 Ω 16.0 mH 15.5kV 12 mΩ 0.3 mH 8.9kV 4 mΩ 0.1 mH 15.5kV 12 mΩ 0.3 mH 8.9kV 4 mΩ 0.1 mH 302 kΩ 800 H TABLE III FILTER CAPACITOR FTC PARAMETERS Actual value Per unit Symbol 15.5 kV 20MVA value 60Hz TABLE IV TRANSFORMER SIT PARAMETERS Actual value Per unit Symbol 15.5/15.5 kV 20MVA value 60Hz XC RC VSP RSP XSP VSS RSS XSS RPM XPM 3 500 73 µF 6 kΩ 1 0.0001 0.01 1 0.0001 0.01 500 500 TABLE V CONVERTER PARAMETERS Symbol Per unit value Actual value 60Hz FS 40 2400Hz 15.5 kV 1.2 mΩ 0.3 mH 15.5kV 1.2 mΩ 0.3 mH 6 kΩ 16 H 222 Appendix 4 Parameters zi for the Γ−controller state space description z0=(4*Lsp*as^2*Ls*ap^2+4*Lsp*as^2*Lpp*ap^2+4*Lr*Ls*ap^2+... 4*Lr*Lpp*ap^2+4*Ls*Lpp*ap^2+4*Lss*Ls*ap^2+4*Lss*Lpp*ap^2+... Lsp*as^2*Lps+Ls*Lps+Lss*Lps+Lr*Lps); z1=ap*(Rs*Lsp*as^2+Rs*Lr+Rs*Lss-Rss*Ls-Rr*Ls-Rsp*as^2*Ls)/z0; z2=1/Lps*ap*(Lsp*as^2*Lpp*ap+Lsp*as^2*Ls*ap+Lss*Lpp*ap+... Lss*Ls*ap+Ls*Lpp*ap+Lr*Lpp*ap+Lr*Ls*ap)/z0; z3=((4*Ls*Rpp-4*Rs*Lpp)*ap^3-(-Ls*Rps+Rs*Lps)*ap)/z0; z4=(-Rsp*as^2*Lps-4*ap^2*Lpp*Rsp*as^2-4*ap^2*Lpp*Rss... -4*ap^2*Lpp*Rr-4*ap^2*Ls*Rss-4*ap^2*Rs*Lpp-4*... ap^2*Ls*Rr-Rr*Lps-Rss*Lps-Rs*Lps-4*ap^2*Ls*Rsp*as^2)/z0; z5=1/Lps*ap^2*(Lpp*Rps*Lr+Lpp*Rps*Lss+Lpp*Rps*Ls+... Rps*Ls*Lr+Rps*Ls*Lss-Rs*Lps*Lr-Rs*Lps*Lsp*as^2-... Rs*Lps*Lss+Rps*Ls*Lsp*as^2+Lpp*Rps*Lsp*as^2-Rpp*Lps... *Lsp*as^2-Rpp*Lps*Ls-Rpp*Lps*Lss-Rpp*Lps*Lr)/z0; z6=as*(Lps+4*ap^2*Lpp+4*ap^2*Ls)/z0; z7=1/Lps*ap*as*Ls*Lps/z0; z8=ap*Ls/z0; z9=(4*Lpp*ap^2+Lps)/z0; z10=(-(4*Lpp+4*Ls)*ap^2-Lps)/z0; z11=ap*(Lr+as^2*Lsp+Lss)/z0; 223 Appendix 5 Number Type Pd (MW) 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36 37 38 39 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 2 3 2 2 2 2 2 2 2 2 0 0 322 500 0 0 233.8 522 0 0 0 8.5 0 0 320 329.4 0 158 0 680 274 0 247.5 308.6 224 139 281 206 283.5 0 9.2 0 0 0 0 0 0 0 1104 TABLE I BUS DATA Qd (MVA) Vmax (pu) 0 0 2.4 184 0 0 84 176.6 0 0 0 88 0 0 153 32.3 0 30 0 103 115 0 84.6 -92.2 47.2 17 75.5 27.6 26.9 0 4.6 0 0 0 0 0 0 0 250 1.1 1.1 1.1 1.1 1.1 1.1 1.1 1.1 1.1 1.1 1.1 1.1 1.1 1.1 1.1 1.1 1.1 1.1 1.1 1.1 1.1 1.1 1.1 1.1 1.1 1.1 1.1 1.1 1.1 1.1 1.1 1.1 1.1 1.1 1.1 1.1 1.1 1.1 1.1 OPF Data Vmin (pu) θmax ° θmin ° 0.9 0.9 0.9 0.9 0.9 0.9 0.9 0.9 0.9 0.9 0.9 0.9 0.9 0.9 0.9 0.9 0.9 0.9 0.9 0.9 0.9 0.9 0.9 0.9 0.9 0.9 0.9 0.9 0.9 0.9 0.9 0.9 0.9 0.9 0.9 0.9 0.9 0.9 0.9 90 90 90 90 90 90 90 90 90 90 90 90 90 90 90 90 90 90 90 90 90 90 90 90 90 90 90 90 90 90 90 90 90 90 90 90 90 90 90 -90 -90 -90 -90 -90 -90 -90 -90 -90 -90 -90 -90 -90 -90 -90 -90 -90 -90 -90 -90 -90 -90 -90 -90 -90 -90 -90 -90 -90 -90 -90 -90 -90 -90 -90 -90 -90 -90 -90 224 TABLE II GENERATOR DATA Number Pmax (MW) 30 31 32 33 34 35 36 37 38 39 Pmin (MW) 300 500 750 1000 1000 1000 1000 400 1000 500 Qmax (MVA) 0 0 0 0 0 0 0 0 0 0 From To R(pu) X(pu) Rating (MVA) 1 1 2 2 3 3 4 4 5 5 6 6 7 8 9 10 10 13 14 15 16 16 16 2 39 3 25 4 18 5 14 6 8 7 11 8 9 39 11 13 14 15 16 19 21 24 0.0035 0.001 0.0013 0.007 0.0013 0.0011 0.0008 0.0008 0.0002 0.0008 0.0006 0.0007 0.0004 0.0023 0.001 0.0004 0.0004 0.0009 0.0018 0.0009 0.0016 0.0008 0.0003 0.0411 0.025 0.0151 0.0086 0.0213 0.0133 0.0128 0.0129 0.0026 0.0112 0.0092 0.0082 0.0046 0.0363 0.025 0.0043 0.0043 0.0101 0.0217 0.0094 0.0195 0.0135 0.0059 2500 500 2500 2500 500 2500 2500 2500 2500 2500 2500 2500 2500 2500 2500 2500 2500 2500 500 2500 2500 2500 2500 Qmin (MVA) 300 500 750 1000 1000 1000 1000 400 1000 500 TABLE III BRANCH DATA From Tap 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 17 17 21 21 22 23 25 26 26 16 26 28 12 12 6 10 19 20 22 23 25 2 29 19 -300 -500 -750 -1000 -1000 -1000 -1000 -400 -1000 -500 Cost ($/h) aP2+bP+c a 0.06 0.01 0.05 0.01 0.04 0.07 0.01 0.02 0.006 0.006 b 0.1 0.4 0.3 0.3 0.2 0.3 0.5 0.7 0.3 0.3 c 0 0 0 0 0 0 0 0 0 0 To R(pu) X(pu) Rating (MVA) 18 27 22 29 23 24 26 27 28 17 29 29 11 13 31 32 33 34 35 36 37 30 38 20 0.0007 0.0013 0.0008 0.0008 0.0006 0.0022 0.0032 0.0014 0.0043 0.0007 0.0057 0.0014 0.0016 0.0016 0 0 0.0007 0.0009 0 0.0005 0.0006 0 0.0008 0.0007 0.0082 0.0173 0.014 0.014 0.0096 0.035 0.0323 0.0147 0.0474 0.0089 0.0625 0.0151 0.0435 0.0435 0.025 0.02 0.0142 0.018 0.0143 0.0272 0.0232 0.0181 0.0156 0.0138 2500 2500 2500 2500 2500 2500 2500 2500 500 500 500 2500 2500 2500 2500 2500 2500 2500 2500 2500 2500 2500 2500 2500 Tap 0 0 0 0 0 0 0 0 0 0 0 0 1.006 1.006 1.07 1.07 1.07 1.009 1.025 1 1.025 1.025 1.025 1.06 225 References [1] N. G. Hingorani, "FACTS technology and opportunities," in proceeding of the IEE Colloquium on Flexible AC Transmission Systems (FACTS), London, UK, 1994. [2] N. G. Hingorani, "Power electronics in electric utilities: role of power electronics in future power systems," Proceedings of the IEEE, vol. 76, 1988. [3] N. G. Hingorani, "Role of FACTS in a deregulated market," in proceeding of the Power Engineering Society Summer Meeting, 2000. [4] A. R. Bergen and V. Vittal, "Power systems analysis," 2nd ed. Upper Saddle River, NJ: Prentice Hall, 2000. [5] A. J. Wood and B. F. Wollenberg, "Power generation, operation, and control," 2nd ed: J. Wiley & Sons, 1996. [6] N. Mohan, T. M. Undeland, and W. P. Robbins, "Power electronics: converters, applications, and design," 3rd ed: John Wiley & Sons, 2003. [7] Y.-H. Song and A. Johns, "Flexible ac transmission systems (FACTS)." London: Institution of Electrical Engineers, 1999. [8] M. D. Ilic and J. Zaborszky, "Dynamics and control of large electric power systems," Wiley, 2000. [9] M. R. Iravani, P. L. Dandeno, K. H. Nguyen, D. Zhu, and D. Maratukulam, "Applications of static phase shifters in power systems," IEEE Transactions on Power Delivery, vol. 9, 1994. 226 [10] M. R. Iravani and D. Maratukulam, "Review of semiconductor-controlled (static) phase shifters for power systems applications," IEEE Transactions on Power Systems, vol. 9, 1994. [11] B. K. Johnson and G. Venkataramanan, "A hybrid solid state phase shifter using PWM AC converters," IEEE Transactions on Power Delivery, vol. 13, 1998. [12] B. K. Johnson, G. Venkataramanan, and M. Manjrekar, "A hybrid solid state phase shifter for continuous phase shift control in transmission lines," in proceeding of the Canadian Conference on Electrical and Computer Engineering, 1996. [13] GE Industrial and Power Systems, "HVDC Handbook." [14] N. G. Hingorani and L. Gyugyi, "Understanding FACTS: concepts and technology of flexible AC transmission systems," IEEE Press, 2000. [15] L. Gyugyi, "Dynamic compensation of AC transmission lines by solid-state synchronous voltage sources," IEEE Transactions on Power Delivery, vol. 9, 1994. [16] L. Gyugyi, C. D. Schauder, and K. K. Sen, "Static synchronous series compensator: a solid-state approach to the series compensation of transmission lines," IEEE Transactions on Power Delivery, vol. 12, 1997. [17] L. Gyugyi, C. D. Schauder, S. L. Williams, T. R. Rietman, D. R. Torgerson, and A. Edris, "The unified power flow controller: a new approach to power transmission control," IEEE Transactions on Power Delivery, vol. 10, 1995. [18] L. Gyugyi, K. K. Sen, and C. D. Schauder, "The interline power flow controller concept: a new approach to power flow management in transmission systems," IEEE Transactions on Power Delivery, vol. 14, 1999. 227 [19] J. Sun, L. Hopkins, B. Shperling, B. Fardanesh, M. Graham, M. Parisi, S. MacDonald, S. Bhattacharya, S. Berkowitz, and A. Edris, "Operating characteristics of the convertible static compensator on the 345 kV network," in proceeding of the IEEE PES Power Systems Conference & Exposition, New York, NY, USA, 2004. [20] C. Hochgraf, R. Lasseter, D. Divan, and T. A. Lipo, "Comparison of multilevel inverters for static VAr compensation," in proceeding of the Industry Applications Conference IAS Annual Meeting, Denver, CO, USA, 1994. [21] P. W. Wheeler, J. Rodriguez, J. C. Clare, L. Empringham, and A. Weinstein, "Matrix converters: a technology review," IEEE Transactions on Industrial Electronics, vol. 49, 2002. [22] B. T. Ooi and M. Kazerani, "Voltage-source matrix converter as a controller in flexible AC transmission systems," IEEE Transactions on Power Delivery, vol. 13, 1998. [23] B.-T. Ooi and M. Kazerani, "Unified power flow controller based on matrix converter," in proceeding of the IEEE Power Electronics Specialists Conference (PESC), 1996. [24] F. Mancilla-David and G. Venkataramanan, "A Synchronous Back-to-Back Intertie Using the Vector Switching Converter," in proceeding of the Thirty-Sixth Annual North American Power Symposium (NAPS), Moscow, Idaho, 2004. [25] F. Mancilla-David and G. Venkataramanan, "A pulse width modulated AC link unified power flow controller," in proceeding of the IEEE Power Engineering Society General Meeting, San Francisco, CA, 2005. [26] G. Venkataramanan, "Three-phase vector switching converters for power flow control," IEE Proceedings on Electric Power Applications, vol. 151, 2004. 228 [27] G. Venkataramanan and B. K. Johnson, "Pulse width modulated series compensator," IEE Proceedings on Generation, Transmission and Distribution, vol. 149, 2002. [28] G. Venkataramanan, B. K. Johnson, and A. Sundaram, "An AC-AC power converter for custom power applications," IEEE Transactions on Power Delivery, vol. 11, 1996. [29] D. Divan, W. Brumsickle, R. Schneider, B. Kranz, R. Gascoigne, D. Bradshaw, M. Ingram, and I. Grant, "A distributed static series compensator system for realizing active power flow control on existing power lines," in proceeding of the IEEE PES Power Systems Conference & Exposition, New York, NY, USA, 2004. [30] G. Holmes and T. A. Lipo, "Pulse width modulation for power converters: principles and practice." New York: Chichester, 2002. [31] J. Holtz, "Pulsewidth modulation-a survey," in proceeding of the IEEE Power Electronics Specialists Conference, Toledo, Spain, 1992. [32] J. G. Kassakian, M. F. Schlecht, and G. C. Verghese, "Principles of Power Electronics." Reading, Massachusetts: Addison-Wesley Publishing Company, 1991. [33] P. Wood, "Switching power converters." New York: Van Nostrand Reinhold Co., 1981. [34] G. Venkataramanan and B. K. Johnson, "Pulse width modulated series compensator," Generation, Transmission and Distribution, IEE Proceedings-, vol. 149, 2002. [35] F. Mancilla-David and G. Venkataramanan, "Generalized Averaged Dynamic Modeling of Vector Switching AC Power Flow Controllers," in proceeding of the 36th IEEE Power Electronics Specialists Conference (PESC), Recife, Brazil, 229 2005. [36] A. M. Stankovic and T. Aydin, "Analysis of asymmetrical faults in power systems using dynamic phasors," IEEE Transactions on Power Systems, vol. 15, 2000. [37] A. M. Stankovic, P. Mattavelli, V. Caliskan, and G. C. Verghese, "Modeling and analysis of FACTS devices with dynamic phasors," in proceeding of the IEEE Power Engineering Society Winter Meeting, Singapore, 2000. [38] A. M. Stankovic, S. R. Sanders, and T. Aydin, "Dynamic phasors in modeling and analysis of unbalanced polyphase AC machines," IEEE Transactions on Energy Conversion, vol. 17, 2002. [39] P. C. Stefanov and A. M. Stankovic, "Modeling of UPFC operation under unbalanced conditions with dynamic phasors," IEEE Transactions on Power Systems, vol. 17, 2002. [40] V. A. Caliskan, O. C. Verghese, and A. M. Stankovic, "Multifrequency averaging of DC/DC converters," IEEE Transactions on Power Electronics, vol. 14, 1999. [41] B. Lehman and R. M. Bass, "Extensions of averaging theory for power electronic systems," in proceeding of the IEEE Power Electronics Specialists Conference, Taipei, Taiwan, 1994. [42] B. Lehman and R. M. Bass, "Switching frequency dependent averaged models for PWM DC-DC converters," IEEE Transactions on Power Electronics, vol. 11, 1996. [43] S. R. Sanders, "On limit cycles and the describing function method in periodically switched circuits," IEEE Transactions on Circuits and Systems I: Fundamental Theory and Applications, vol. 40, 1993. 230 [44] S. R. Sanders, J. M. Noworolski, X. Z. Liu, and G. C. Verghese, "Generalized averaging method for power conversion circuits," IEEE Transactions on Power Electronics, vol. 6, 1991. [45] D. W. Novotny and T. A. Lipo, "Vector control and dynamics of AC drives." Oxford: Clarendon Press: New York, 1996. [46] R. C. Dorf and R. H. Bishop, "Modern control systems," 9th ed. Upper Saddle River, NJ: Prentice Hall, 2001. [47] K. Ogata, "Modern control engineering," 3rd ed. Upper Saddle River, N.J.: Prentice Hall, 1997. [48] J. M. Maciejowski, "Multivariable feedback design." Wokingham, England: Reading, Mass., 1989. [49] M. S. El-Moursi and A. M. Sharaf, "Novel controllers for the 48-pulse VSC STATCOM and SSSC for voltage regulation and reactive power compensation," IEEE Transactions on Power Systems, vol., 2005. [50] J. B. Ekanayake and M. Jenkins, "A three-level advanced static VAr compensator," IEEE Transactions on Power Delivery, vol. 11, 1996. [51] J. B. Ekanayake and M. Jenkins, "Mathematical models of a three-level advanced static VAr compensator," IEE Proceedings on Generation, Transmission and Distribution, vol. 144, 1997. [52] J. B. Ekanayake and M. Jenkins, "Selection of passive elements for a three-level inverter based static synchronous compensator," IEEE Transactions on Power Delivery, vol. 14, 1999. [53] H. Fujita, S. Tominaga, and H. Akagi, "Analysis and design of a DC voltagecontrolled static VAr compensator using quad-series voltage-source inverters," 231 IEEE Transactions on Industry Applications, vol. 32, 1996. [54] S. Bhattacharya, "Series Connected IGCT based High Power Three-Level Neutral Point Clamped Voltage Source Inverter Pole for FACTS Application," in proceeding of the 36th IEEE Power Electronics Specialists Conference (PESC), Recife, Brazil, 2005. [55] J. Nelson, G. Venkataramanan, and B. Beihoff, "Investigation of parallel operation of IGBTs," in proceeding of the 37th IAS Annual Meeting Industry Applications Conference, 2002. [56] L. A. C. Lopes and G. Joos, "Pulse width modulated capacitor for series compensation," IEEE Transactions on Power Electronics, vol. 16, 2001. [57] IEEE, "Recommended Practices and Requirements for Harmonic Control in Electrical Power Systems, IEEE Std 519-1992," 1992. [58] H. K. Høidalen and R. Sporild, "Using Zigzag Transformers with Phase-shift to reduce Harmonics in AC-DC Systems," 2005, Avialable online: http://www.ipst.org/TechPapers/2005/IPST05_Paper044.pdf. [59] A. Boglietti, P. Ferraris, M. Lazzari, and F. Profumo, "Iron losses in magnetic materials with six-step and PWM inverter supply," IEEE Transactions on Magnetics, vol. 27, 1991. [60] W. A. Roshen, "A Practical, Accurate and Very General Core Loss Model for Nonsinusoidal Waveforms," IEEE Transactions on Power Electronics, vol. 22, 2007. [61] H. Akagi, Y. Kanazawa, and A. Nabae, "Instantaneous reactive power compensators comprising switching devices without energy storage components," IEEE Transactions on Industry Applications, vol. 20, 1984. 232 [62] S. Bhattacharya, B. Fardenesh, and B. Sherpling, "Convertible Static Compensator: Voltage Soucre Converter Based FACTS Application in the New York 345 kV Transmission System," in proceeding of the 5th International Power Electronics Conference, Niigata, Japan, 2005. [63] B. Sherpling, J. Sun, and S. Bhattacharya, "Power Flow Control on 345 kV Lines with the 200 MVA Convertible Static Compensator," in proceeding of the PES PowerTech 2005 Conference, St. Petersburg, Russia, 2005. [64] F. Mancilla-David and G. Venkataramanan, "Modeling and Control of the Static Synchronous Series Compensator under Different Operating Modes," in proceeding of the 38th IEEE Power Electronics Specialists Conference (PESC), Orlando, Florida, 2007. [65] H. Fujita, Y. Watanabe, and H. Akagi, "Transient Analysis of a Unified Power Flow Controller and its Application to Design of the DC-Link Capacitor," IEEE Transactions on Power Electronics, vol. 16, 2001. [66] L. A. C. Lopes, G. Joos, and B. Ooi, "A high-power PWM quadrature booster phase shifter based on amultimodule AC controller," IEEE Transactions on Power Electronics, vol. 13, 1998. [67] V. Srinivasan, "A Real-Time Digital Controller with Re-Configurable Analog and Logic Subsystems," M.S. Thesis, University of Wisconsin-Madison, 2003 [68] D. Hayward, "Operating problems with parallel flows," IEEE Transactions on Power Systems, vol. 6, 1991. [69] L. Naihu, X. Yan, and C. Heng, "FACTS-based power flow control in interconnected power system," IEEE Transactions on Power Systems, vol. 15, 2000. [70] E. Acha, "FACTS: modelling and simulation in power networks," Wiley, 2004. 233 [71] R. Baldick and E. Kahn, "Contract paths, phase-shifters, and efficient electricity trade," IEEE Transactions on Power Systems, vol. 12, 1997. [72] B. Baran, J. Vallejos, R. Ramos, and U. Fernandez, "Multi-objective reactive power compensation," in proceeding of the IEEE/PES Transmission and Distribution Conference and Exposition, Atlanta, GA, USA, 2001. [73] D. B. Das and C. Patvardhan, "New multi-objective stochastic search technique for economic load dispatch," IEE Proceedings-Generation, Transmission and Distribution, vol. 145, 1998. [74] D. J. Gotham and G. T. Heydt, "Power flow control and power flow studies for systems with FACTS devices," IEEE Transactions on Power Systems, vol. 13, 1998. [75] A. Nabavi-Niaki and M. R. Iravani, "Steady-state and dynamic models of unified power flow controller (UPFC) for power system studies," IEEE Transactions on Power Systems, vol. 11, 1996. [76] A. Schmitt and J. F. Verstege, "A multi-criteria optimization of ancillary services in a competitive energy market," in proceeding of the IEEE Power Engineering Society Winter Meeting, Columbus, OH, USA, 2001. [77] S. N. Singh and A. K. David, "A new approach for placement of FACTS devices in open power markets," IEEE Power Engineering Review, vol. 21, 2001. [78] X. Ying, Y. H. Song, and Y. Z. Sun, "Power flow control approach to power systems with embedded FACTS devices," IEEE Transactions on Power Systems, vol. 17, 2002. [79] O. L. Mangasarian, "Nonlinear programming." New York: McGraw-Hill, 1969. [80] J. Nocedal and S. J. Wright, "Numerical optimization." New York: Springer, 234 1999. [81] F. D. Alvarado, C., "Computational Tools for Planning and Operation Involving FACTS Devices," in proceeding of the Cigre Brazil - Worshop on FACTS, Rio de Janeiro, Brazil, 1995. [82] M. R. Begovic, B; Lambert, F; Novosel, D, "Optimization of Capacitor Allocation in Tranmission and Distribution Networks," in proceeding of the Bulk Power System Dynamics and Control, Cortina d'Ampezzo, Italy, 2004. [83] C. Schaffner and G. Andersson, "Value of controllable devices in a liberalized electricity market," in proceeding of the Seventh International Conference on ACDC Power Transmission, London, UK, 2001. [84] C. Schaffner and G. Andersson, "Determining the value of controllable devices in a liberalized electricity market: a new approach," in proceeding of the PowerTech, Bologna, Italy, 2003. [85] L. Kay-Soon and Z. Hualiang, "Robust model predictive control and observer for direct drive applications," IEEE Transactions on Power Electronics, vol. 15, 2000. [86] R. Ortega, A. Loria, P. Nicklasson, and H. Sira-Ramirez, "Passivity-based Control of Euler-Lagrange Systems: Mechanical, Electrical and Electromechanical Applications." Berlin: Springer-Verlag, 1998. [87] J. M. Gonzalez and J. M. Ramirez, "AC-AC controller for steady state and transient stability analysis," in proceeding of the 38th North American Power Symposium (NAPS), Carbondale, IL, 2006. [88] J. M. Ramirez and J. M. Gonzalez, "Incorporating AC/AC Controllers into a Power Flow Formulation," in proceeding of the Transmission & Distribution Conference and Exposition: Latin America, Caracas, Venezuela, 2006. 235 [89] M. Gutierrez, G. Venkataramanan, and A. Sundaram, "Solid State Flicker Controller using a Pulse Width Modulated AC-AC converter," in proceeding of the 2000 IEEE Industry Applications Conference, 2000.