This article has been accepted for inclusion in a future issue of this journal. Content is final as presented, with the exception of pagination. IEEE TRANSACTIONS ON POWER DELIVERY 1 Load Leveling Reduces T&D Line Losses Ali Nourai, Senior Member, IEEE, V. I. Kogan, Senior Member, IEEE, and Chris M. Schafer, Member, IEEE Abstract—The benefit of shifting load from the peak to the offpeak period is well known from the viewpoints of demand response and deferral of capacity upgrade. However, the impact of load leveling on reducing transmission and distribution (T&D) losses is often ignored or lightly mentioned in the literature. A detailed analysis of T&D loss reduction is very specific to the considered power system and cannot be readily generalized. Therefore, the objective of this paper is to identify the key parameters and quantify the saved T&D losses as a function of the size or power of the energy storage in a set of normalized charts to help assess the benefits of energy storage as a means to level a utility load. This is a benefit of utility-scale energy storage that is not fully recognized. Index Terms—Dispersed storage and generation, energy management, energy storage, losses, peak shaving, power distribution, power generation peaking capacity, power transmission. NOMENCLATURE Ratio of storage size to peak load. G Ratio of off-peak to peak load (before load leveling). k Ratio of transmission and distribution (T&D) losses to peak load. d Ratio of T&D resistance from off-peak to peak. M Value multiplier = increase in the value of saved losses due to an energy price differential between peak and off-peak periods. C Ratio of energy cost at peak to cost at off-peak. I. INTRODUCTION TILITIES are interested in load leveling because it allows them to defer investment on generation, transmission, and distribution assets. It also allows them to retire old power plants with high emissions. Battery-based, large-scale electricity storage devices are now commercially available and can be located anywhere on the grid to level the load. It also enables utilities to sell low-cost off-peak energy during the peak period to help pay for the cost of the energy storage [1]. As shown in Fig. 1, the flow of energy from central generation sites to load centers throughout the grid involves some losses due to the resistance of wires and other equipment at the transmission, subtransmission, and distribution levels [2], [3]. Since these losses are proportional to the square of the current flow, using energy storage to shift some of this current or load from U Manuscript received April 11, 2007; revised August 29, 2007. Paper no. TPWRD-00189–2007. The authors are with the American Electric Power, Columbus, OH 43215 USA (e-mail: anourai@aep.com). Color versions of one or more of the figures in this paper are available online at http://ieeexplore.ieee.org. Digital Object Identifier 10.1109/TPWRD.2008.921128 Fig. 1. Sample of American Electric Power’s (AEP) transmission and distribution (T&D) resistive losses from generation to load. the peak period to off-peak period decreases the net resistive losses, which can offset some of the storage losses. Besides the squared current relationship that helps reduce the T&D losses by shifting a fraction of load from the peak to offpeak period, two other factors enhance this loss reduction and increase its value. 1) The resistance of T&D wires and transformers is lower at off-peak periods (lower temperature). 2) The cost of the energy (and losses) is generally lower during off-peak periods. II. REDUCTION OF T&D LOSSES A. Factors and Assumptions Since T&D losses are proportional to the square of the load current, shifting any amount of load from peak to off-peak results in a net reduction of T&D losses. It should be noted that this loss reduction is for central generation and only a small fraction, if any, may apply to distributed generation. Despite its exponential growth, distributed generation is still an insignificant portion of the total utility generation and is expected to remain so for another decade. The reduction of the T&D losses is quantified in Section II-B. The mathematical model also considers the impact of the following parameters on the saved losses: 1) storage efficiency; 2) ratio of peak to off-peak loads (before load leveling); 3) equivalent total T&D resistance (derived from known T&D losses); 4) variation of the total T&D resistance from peak to off-peak periods. B. Calculation of T&D Ohmic Losses This calculation of T&D losses is based on a simplified (Thevenin equivalent) circuit as seen by a single load center with local energy storage to shift load from peak to off-peak periods (see Fig. 2). The total (peak and off-peak) T&D loss for a time period with and without load shifting may be approximated as 0885-8977/$25.00 © 2008 IEEE (1) (2) This article has been accepted for inclusion in a future issue of this journal. Content is final as presented, with the exception of pagination. 2 IEEE TRANSACTIONS ON POWER DELIVERY Fig. 3. Drop in T&D losses as a percent of the peak load. T&D losses and its drop due to shifting load can be approximated as (4) This savings in T&D losses may be expressed as a fraction of the original losses (normalized) (5) Fig. 2. Shifting load from peak to off-peak time reduces T&D losses. T&D losses are often expressed as a fraction of the system load in terms of percent of demand or percent of delivered energy. The total loss for a power system like AEP’s is in the range of 10%–15% of the load. Defining the ratio of the total T&D losses to the load as a parameter, (5) may be rewritten to show the ratio of the saved losses to the peak load (before shifting) where T&D losses without any load shift; T&D losses with shifted load (energy storage); , , equivalent T&D resistances during peak and off-peak periods, respectively; load current during peak and off-peak periods, respectively; current provided locally by the storage device; net ac energy efficiency of the storage system; storage discharge time during the peak period; (6) Fig. 3 shows dependence of saved T&D losses on the storage size, both normalized to the peak load. The following values have been assumed for this plot: = storage charge time longer than discharge time due to the storage inefficiency. Now if the storage current is set equal to zero in (2), the T&D losses would be the same as the case without any storage. The savings in T&D losses due to the load leveling effect of the local storage can be written and simplified as (3) Substituting The main conclusion from this chart is the savings in T&D losses increases (losses decrease) with the storage size up to a maximum value beyond which the losses increase again. Another observation from Fig. 3 is the savings in the T&D losses is sensitive to the ratio of the off-peak to peak loads (G). The equations of saved T&D losses could be written to use a more familiar parameter like load factor, instead of the ratio of off-peak load to peak load (G), except load factor depends on the load profile while (G) is independent of it. The percent change in the T&D resistance from peak to offpeak periods is expected to follow the change in resistance from small currents (25 C) to high currents (carrying 75% of its rated capacity at 50 C). This ratio is between 88% to 92% range This article has been accepted for inclusion in a future issue of this journal. Content is final as presented, with the exception of pagination. NOURAI et al.: LOAD LEVELING REDUCES T&D LINE LOSSES 3 Fig. 4. Largest storage size for maximum reduction in T&D losses. for most aluminum cable steel reinforced (ACSR) conductors at 60 Hz [4]. Since energy storage is considered at or near a load site and parallel with it (AEP recommendation and practice), it virtually sees the same voltage as the load and, therefore, the ratio of the storage size to the peak load is the same as their current ratio, in the above equations which was defined as alpha Fig. 5. Drop in T&D losses as a percent of the storage size. Obviously, there is a maximum storage size (load shift) that can be deployed before the T&D losses would start to increase again. Considering that (6) is a parabolic function relative to a, the location of its peak, that is the storage size for realizing maximum T&D loss reduction, can be expressed as (7) Fig. 4 shows a plot of this maximum storage size before T&D losses start to increase again. Note that this maximum storage size is 50% of the gap between peak and off-peak load for an energy storage device that is 90% efficient. This is due to considering a lower T&D resistance at off-peak periods (90%) than peak periods. The maximum storage size decreases for storage devices that are less efficient than 90%. The maximum storage size of 50% is reached for all storage systems with an efficiency . that numerically equals the night/day resistance ratio With an energy storage device present , then (6) can be rewritten to express saved losses as a fraction of the storage size (8) A plot of this equation is shown in Fig. 5 where saved T&D losses (as a percentage of the storage size) are plotted vs. the storage size (as a percentage of peak load). The main observation here again is that the ratio of saved losses to storage size decreases with increased storage size. In other words, the first MW of storage is more effective in offsetting T&D losses than the second additional MW of storage located at the same site. The reason behind this characteristic is that as more and more load is shifted from peak to off-peak period, the gap between the peak and off peak loads decreases Fig. 6. Relative size of reduced T&D losses to the storage losses. and, therefore, the effectiveness of additional load shifting decreases at that location (see Fig. 2). The second observation, as also observed in Fig. 3, is that the savings in the T&D losses is sensitive to the ratio of the off-peak to peak loads G. If the amount of reduced T&D losses would equal or exceed the storage losses, one could claim that the load leveling application of storage devices near loads would effectively render them as “lossless devices.” An obvious question is whether the saved T&D losses would cover or exceed the losses of the energy storage device. Fig. 6 shows the ratio of saved T&D losses to the energy loss of a storage device used to shift load. For the range of parameters considered in this study, the saved T&D losses are up to about 50% of the storage losses. Therefore, if the reduction in the T&D losses is combined with the load leveling losses of an 80% efficient energy storage device, the net efficiency of the storage device would then be effectively increased from about 80% to about 90%, at best. As demonstrated in Appendix A, more T&D losses can be reduced if a number of smaller loads are shifted at multiple sites rather than a larger load shift at a single site. The numerical example in Appendix A shows that the saved T&D losses would double if the total load to be shifted is divided into four and This article has been accepted for inclusion in a future issue of this journal. Content is final as presented, with the exception of pagination. 4 IEEE TRANSACTIONS ON POWER DELIVERY implemented at four different sites. The principle behind this observation is as more load is shifted from peak to off-peak periods, the gap between the peak and off peak loads decreases at that site and; therefore, the effectiveness of additional load shifting decreases at that same location. While this principle is believed to apply in general and regardless of the location, the numerical value mentioned above may be limited to the storage parameters and the specific location it was used on the AEP system. A more detailed study is needed to generalize the numerical value of distributing the load leveling storage units. TABLE I NPV OF REDUCED T&D LOSSES DUE TO LOAD SHIFTING— =kW ( , =MWH) $ Storage Eciency = 77% Energy Value = $35 C. Numerical Example In 2006, AEP installed a 1.0-MW Sodium Sulfur (NaS)-based energy storage system on a 12-kV distribution feeder at Chemical station in North Charleston, West Virginia, for peak shaving [5]. Many of the values for the following parameters are taken from this existing application C Fig. 7. NPV of reduced T&D losses due to load shifting with a 77% efficient energy storage device. Applying the above numerical values to Fig. 5, one concludes that the decrease in T&D losses is around 7%–13% of the 1 MW storage, which is 70 kW–130 kW. Therefore kW kW Considering a discount rate of 7.4%, the net present value (NPV) of this savings over the 15 year life of the energy storage device would be These are values of the saved T&D losses with a flat energy value of $35/MWh. In many cases, however, the energy value does change between peak and off-peak periods and, therefore, the value of the saved T&D losses is higher when load is shifted from the peak to off-peak period. Appendix B demonstrates how to calculate the impact of an energy price differential (between day and night) on the value of the saved T&D losses. Fig. B1 shows this increase as a “value multiplier” expressed in terms of the change in energy cost and the ratio of off-peak to peak loads. These are the two most volatile parameters affecting the saved T&D losses and their value. For the range of numbers used in this example, the value multiplier would be in the 3 to 6 range. While the principles behind the increased value of saved losses are generally valid, the numerical range of the value multiplier may still be limited to the storage parameters and the specific location it was used on the AEP system. A more detailed study may be needed to generalize the impact of energy cost differential on the saved T&D losses. Table I and Fig. 7 show a summary of the NPV for saved T&D losses per kW of a 7.2-h energy storage device similar to what AEP has installed. The average NPV of the saved T&D losses kW for this example. is around III. CONCLUSION Shifting any part of a load from the peak to the off-peak period will reduce T&D losses. However, this drop in losses is very This article has been accepted for inclusion in a future issue of this journal. Content is final as presented, with the exception of pagination. NOURAI et al.: LOAD LEVELING REDUCES T&D LINE LOSSES 5 sensitive to the ratio of peak to off-peak load. Following is a list of conclusions and observation from this study that is based on an actual operating energy storage device on AEP power system. 1) The drop in the T&D losses is equivalent to increasing the efficiency of the energy delivery system by 1% to 3% (Fig. 3). 2) The present value of the reduced T&D losses is a few hundred dollars per kW of the storage device used to shift some load from peak to off-peak over several hours a day (Table I). 3) When using a 75%–80% efficient energy storage system to shift loads from the peak to off-peak period, the saved T&D losses can compensate for up to 50% of the storage losses (Fig. 6). 4) When the savings in T&D losses is combined with the losses of a 75%–80% efficient storage device, the overall efficiency increases by about 10–13%. 5) More T&D losses may be saved if load reduction (peak shaving) is distributed at several locations rather that at a single site (Appendix A). 6) The above benefits are not limited to energy storage and would apply to demand reduction programs, in general. The foregoing study applied some assumptions to demonstrate the nature and relative size of the T&D loss reduction and its value due to shifting some load from peak to off-peak period. A more thorough investigation including system modeling is needed to fine tune these conclusions to any particular power system. APPENDIX A FURTHER REDUCTION OF T&D LOSSES BY USING MULTIPLE SMALL STORAGE DEVICES AT SEPARATE SITES At any given site, the amount of saved T&D losses diminishes with an increase in the storage size. This is due to the gradual improvement in the load profile and the decrease between peak and off-peak loads. In fact, it could be more beneficial to use multiple smaller load shifts at different sites rather than doing a single large load shift at one site, assuming that the load shift in one site would not change the load profile at the other sites. To demonstrate this point, consider splitting a given load to be shifted equally into “N” sites, with independent but similar load profiles. Using the loss equations in Section II-B, the increase in saved losses can be expressed as follows: Fig. A1. Increase in saved T&D losses by distributing the load shift to multiple sites. As noted in Fig. A1, dividing the storage to four sites rather than deploying it all at one site would double the amount of saved T&D losses. APPENDIX B IMPACT OF ENERGY PRICE DIFFERENTIAL ON THE VALUE OF SAVED T&D LOSSES Since an energy storage device shifts part of the T&D losses from the peak period to off-peak period, the energy cost differential between these periods increases the value of the load shift. The “impact” of the energy cost differential may be defined as a value multiplier, M. where Starting with (1) and (2) for losses with and without the storage and simplifying the results with the previously defined parameters, one gets To see this impact in a simple chart, let us consider some average values for the following less significant parameters: (A1) where the parameters are the same as defined in Section II-B. For a numerical example, consider having several sites, each with a peak load of 30 MW. There is a need to shift a total of 10 MW from peak to off-peak. There is an option to shift that entire load at one site or do several smaller shifts at different sites. Fig. A1 shows the increase in the saved T&D losses due to a multisite load shift for the following additional assumptions: Using the above values in (4), the Value Multiplier be simplified as may (B1) Fig. B1 shows the dependence of the Value Multiplier on energy cost and load variation from off-peak to peak. It should be noted that a price differential of 2:1 has more than just a doubling effect as it impacts unequal decreased losses at peak and increased losses at off-peak. This article has been accepted for inclusion in a future issue of this journal. Content is final as presented, with the exception of pagination. 6 IEEE TRANSACTIONS ON POWER DELIVERY [4] Anderson Electrical Connectors, “Square D Company Technical Data—A Reference for The Electrical Power Industry,” 1964, p. 34. [5] A. Nourai, “Installation of the First Distributed Energy Storage System (DESS) at American Electric Power (AEP),” Sandia National Laboratories, SAND2007-3580, Jun. 2007. Fig. B1. Value Multiplier as a function of the energy price and load variation from peak to off-peak periods. ACKNOWLEDGMENT The authors would like to thank Dr. J. M. Schneider for his ideas and guidance throughout this work. REFERENCES [1] A. Nourai, “Large-scale electricity storage technologies for energy management,” in Proc. IEEE Power Eng. Soc. Summer Meeting, 2002, vol. 1, pp. 310–315. [2] G. Koeppel, M. Geidel, and G. Anderson, “Value of storage devices in congestion constrained distribution networks,” in Proc. Int. Conf. Power Syst. Technol.—POWERCON’04, Singapore, Nov. 21–24, 2004, pp. 1–6. [3] J. Eto et al., “Research, development and demonstration needs for large-scale reliability-enhancing integration of distributed energy resources,” in Proc. 33rd Annu. Hawaii Int. Conf. Syst. Sci., Jan. 4–7, 2000, p. 2. Ali Nourai (M’73–SM’87) received the M.B.A. degree from The Ohio State University, Columbus, in 1976 and the Ph.D. degree from Rensselaer Polytechnic Institute, Troy, NY, in 1978. He is currently the Manager of the Distributed Energy Resources program in American Electric Power (AEP), Columbus. During his 29 years of activities in the utility industry, he has developed and applied many techniques to improve energy efficiency and performance of power systems. His latest project was deployment of a 1.2-MW Sodium Sulfur (NAS) battery for load leveling in a distribution substation in AEP. Dr. Nourai received the Walter Fee Award from IEEE’s Power Engineering Society in 1989. He is a member of the Board of Directors of Electricity Storage Association (ESA). V. I. Kogan (M’80–SM’83) received the B.S., M.S., and Ph.D. degrees in mathematics from Kharkov State University, Kharkiv, Ukraine. His publications cover methods of theoretical and engineering reliability, operations research, theory of statistical functions, numerical methods, applied electrodynamics, and spectral theory of differential operations. He is currently with American Electric Power (AEP), Columbus, where he has been able to apply his mathematical skills to utility operations over the last 27 years. Chris M. Schafer (M’03) received the B.S. degree from DeVry University, Columbus, OH, in 2003. He is currently pursuing the M.S. degree at Franklin University, Columbus, and will graduate in 2008. Chris is currently with the Distributed Energy Resources program, American Electric Power (AEP), Columbus. During his three years at AEP, hey has worked at AEP’s research and development laboratory and has been involved with many regulatory matters addressing distributed generation, demand management, and energy efficiency.