MR3-MR6 INSTALLATION
rev. 02-2016
E477827
SUSPENSION MOUNT
SURFACE MOUNT
MR3 & MR6 Luminaires are suitable for use in the following areas as defined by the National
Electrical Code (NEC) and the Canadian Electrical Code (CEC):
cULus:
Certified To CSA 22.2 No. 250.0, Conforms To UL 1598 Standard
MR3 & MR6 luminaires are designed for use indoors, outdoors, wet locations, and areas containing
moisture, dirt, corrosion, vibration, and rough usage.
HOUSING:
Copper-free Aluminium and Polycarbonate lens
MOUNTING:
Surface:
Wall:
Yoke:
Pole:
Suspension:
VOLTAGE:
VAC: 100-277 VAC | 347: 347 VAC
CURRENT Typical:
MR3: 0.29A@120 VAC | 0.13A@277 VAC | 0.11A@347 VAC
MR6: 0.56A@120 VAC | 0.29A@277 VAC | 0.19A@347 VAC
CONNECTIONS:
Black: Line | White: Neutral | Green: Ground
*For connections use wire rated to a minimum of 75° C
TEMPERATURE RANGE:
-40° C to +55° C
INGRESS PROTECTION:
IP 66
Four (4) 1/4-20 OR M6 Screws or Bolts
Four (4) 1/4-20 OR M6 Screws or Bolts
Two (2) to Four (4) 1/4-20 OR M6 Screws or Bolts
1.5” NPT
Cable or Carabiner at 4 locations.
www.nemalux.com | sales@nemalux.com | Tel 403•242•7475 | Fax 403•243•6190
1-4
MR3-MR6 INSTALLATION
rev. 02-2016
WARNING
To avoid the risk of fire, explosion, or electric shock, this
product should be installed, inspected, and maintained
by a qualified electrician only, in accordance with all
applicable electrical codes.
WARNING
POTENTIAL ELECTROSTATIC
CHARGING HAZARD
WARNING
To reduce the risk of ignition of hazardous atmospheres and
to avoid electric shock, disconnect the luminaire from the
supply circuit before opening for installation and servicing.
Avoid electrostatic discharge :
• Clean exterior lens surface with damp cloth only
SURFACE/SUSPENSION INSTALLATION
STEP 1:
Inspect shipping package and contents to
ensure no damage has occurred during
shipping.
STEP 2:
Install included Surface/Suspension Mount
Brackets. See diagram for orientation of
brackets for each version.
SURFACE MOUNTING CONFIGURATION
Install with included M6 bolts and washers to
7 N-m (62 in-lbs).
Note:
If installing with Pole mount, Wall Mount or Yoke
Mount, remove 3/4 NPT plastic bushing and see
respective installation sheet for selected mounting option and install.
STEP 3:
- For surface mounting configuration, mount
fixture to desired locations with 4x 1/4-20 OR
SUSPENSION MOUNTING CONFIGURATION
M6 Screws or Bolts.
- For suspension mounting configuration,
connect 4x anchors to points shown
2x
7mm
SURFACE MOUNTING CONFIGURATION
10mm
SUSPENSION MOUNTING CONFIGURATION
www.nemalux.com | sales@nemalux.com | Tel 403•242•7475 | Fax 403•243•6190
2-4
MR3-MR6 INSTALLATION
rev. 02-2016
STEP 4:
To begin wiring, open Power Supply Lid by loosening the three (3) M4 captive screws with M3 hex
driver.
Allow the captive fasteners to remain in the lid for
ease of re-installation.
The Lid is secured with a retention cable.
STEP 5:
Supply connection to be made through 3/4" NPT
Entry. If using Surface, Suspension or Yoke configuration, install appropriate 3/4” NPT cable gland for
cable size and be sure to follow all applicable local
electrical codes Torque cable gland base to manufacturer's recommended specification.
OR
Install Direct Rigid Conduit as per local electrical
code. For direct rigid conduit installation, torque
hand tight plus 1 to 2 turns
NOTE:
Both installations require thread sealant (i.e. Loctite
565, check with fitting and sealant manufacturers
about compatible sealants with aluminum enclosures.)
to ensure environmental rating. Failure to install with
thread sealant can compromise fixture ingress rating
and void warranty. The MR luminare cannot be mounted with rigid conduit alone.
STEP 6:
Feed wire into Power Supply cavity.
4”
100mm
Strip 100mm (4”) of cable casing and strip conductors 8mm (0.32”).
Tighten Cable gland dome nut to gland manufacturer specification.
NOTE:
If the supply end of the cord provided as a free end
without a cord connector, termination of the cord in a
suitable junction box using a suitable cord connector
for the specific area classification is required.
www.nemalux.com | sales@nemalux.com | Tel 403•242•7475 | Fax 403•243•6190
0.32”
8 mm
3-4
MR3-MR6 INSTALLATION
rev. 02-2016
STEP 7:
Connect each conductor into appropriate quick connectors.
For dimming, connect 18AWG solid conductors to
power supply dimming terminals.
Line - Black
Neutral - White
Ground - Green
LED
Driver
Red (+)
Blue ( - )
Violet
Grey
LED
Module
0-10V
Dimming
Control
STEP 8:
Close Power Supply Cavity Lid.
A.
Hinge the lid in the fixture head
B.
Rotate lid to seat and centre with screw holes
for registration.
C.
Tighten 3x M4 Captive screws to 2 Nm (17in-lbs)
A.
B.
www.nemalux.com | sales@nemalux.com | Tel 403•242•7475 | Fax 403•243•6190
4-4
MR3-MR6 INSTALLATION
rev. 02-2016
E477827
MR3 & MR6 Luminaires are suitable for use in the following areas as defined by the National
Electrical Code (NEC) and the Canadian Electrical Code (CEC):
cULus:
Certified To CSA 22.2 No. 250.0, Conforms To UL 1598 Standard
MR3 & MR6 luminaires are designed for use indoors, outdoors, wet locations, and areas containing
moisture, dirt, corrosion, vibration, and rough usage.
HOUSING:
Copper-free Aluminium and Polycarbonate lens
MOUNTING:
Surface:
Wall:
Yoke:
Pole:
Suspension:
VOLTAGE:
VAC: 100-277 VAC | 347: 347 VAC
CURRENT Typical:
MR3: 0.29A@120 VAC | 0.13A@277 VAC | 0.11A@347 VAC
MR6: 0.56A@120 VAC | 0.29A@277 VAC | 0.19A@347 VAC
CONNECTIONS:
Black: Line | White: Neutral | Green: Ground
*For connections use wire rated to a minimum of 75° C
TEMPERATURE RANGE:
-40° C to +55° C
INGRESS PROTECTION:
IP 66
Four (4) 1/4-20 OR M6 Screws or Bolts
Four (4) 1/4-20 OR M6 Screws or Bolts
Two (2) to Four (4) 1/4-20 OR M6 Screws or Bolts
1.5” NPT
Cable or Carabiner at 4 locations.
www.nemalux.com | sales@nemalux.com | Tel 403•242•7475 | Fax 403•243•6190
1-2
MR3-MR6 INSTALLATION
rev. 02-2016
POLE MOUNT INSTALLATION
STEP 1:
Inspect shipping package and contents to
ensure no damage has occurred during
shipping.
STEP 2:
Install Pole Mount and gasket with adhesive
side applied to mount and included M6 bolts
and washers.
Torque to 7 N-m (62 in-lbs)
STEP 3:
Thread fixture assembly onto 1.5” NPT pole.
STEP 4:
Insert and tension M6 set screw to pole to lock
rotation.
Set Screw
STEP 5:
Resume installation instructions provided
with fixture. (STEP 4)
www.nemalux.com | sales@nemalux.com | Tel 403•242•7475 | Fax 403•243•6190
2-2
MR3-MR6 INSTALLATION
rev. 02-2016
E477827
MR3 & MR6 Luminaires are suitable for use in the following areas as defined by the National
Electrical Code (NEC) and the Canadian Electrical Code (CEC):
cULus:
Certified To CSA 22.2 No. 250.0, Conforms To UL 1598 Standard
MR3 & MR6 luminaires are designed for use indoors, outdoors, wet locations, and areas containing
moisture, dirt, corrosion, vibration, and rough usage.
HOUSING:
Copper-free Aluminium and Polycarbonate lens
MOUNTING:
Surface:
Wall:
Yoke:
Pole:
Suspension:
VOLTAGE:
VAC: 100-277 VAC | 347: 347 VAC
CURRENT Typical:
MR3: 0.29A@120 VAC | 0.13A@277 VAC | 0.11A@347 VAC
MR6: 0.56A@120 VAC | 0.29A@277 VAC | 0.19A@347 VAC
CONNECTIONS:
Black: Line | White: Neutral | Green: Ground
*For connections use wire rated to a minimum of 75° C
TEMPERATURE RANGE:
-40° C to +55° C
INGRESS PROTECTION:
IP 66
Four (4) 1/4-20 OR M6 Screws or Bolts
Four (4) 1/4-20 OR M6 Screws or Bolts
Two (2) to Four (4) 1/4-20 OR M6 Screws or Bolts
1.5” NPT
Cable or Carabiner at 4 locations.
www.nemalux.com | sales@nemalux.com | Tel 403•242•7475 | Fax 403•243•6190
1-2
MR3-MR6 INSTALLATION
rev. 02-2016
WALL MOUNT INSTALLATION
STEP 1:
Inspect shipping package and contents to
ensure no damage has occurred during
shipping.
STEP 2:
Install provided 3/4 NPT conduit plugs in
desired locations with thread sealant (i.e.
Loctite 565, check with fitting and sealant
manufacturers about compatible sealants with
aluminum enclosures.) To maintain ingress
rating all NPT entries not used for wiring
connections are required to be plugged.
Torque to 10 Nm (88 in-lbs)
STEP 3:
Install Wall Mount main body with included
M6 bolts and washers and adhesive backed
gasket. Apply gasket to mount with adhisive
backed side. Torque to 7 N-m (62 in-lbs)
STEP 4:
Install Back Cover Plate with 4x M4 Flat head
screws and adhesive backed gasket. Apply
with Adhesive side applied to mount main
body. Torque to 2 N-m (17 in-lbs)
STEP 5:
Mount fixture assembly to desired location 4x
1/4-20 OR M6 Screws or Bolts.
STEP 6:
Install appropriate 3/4” NPT cable gland for
cable size to desired entry location and be
sure to follow all applicable local electrical
codes Torque cable gland base and dome nut
to manufacturer's recommended specification. OR Install Direct Rigid Conduit as per
local electrical code. For direct rigid conduit
installation, torque hand tight plus 1 to 2
turns.
STEP 6:
Resume installation instructions provided
with fixture. (STEP 4)
145mm
145mm
4x
7mm
www.nemalux.com | sales@nemalux.com | Tel 403•242•7475 | Fax 403•243•6190
2-2
MR3-MR6 INSTALLATION
E477827
MR3 & MR6 Luminaires are suitable for use in the following areas as defined by the National
Electrical Code (NEC) and the Canadian Electrical Code (CEC):
cULus:
Certified To CSA 22.2 No. 250.0, Conforms To UL 1598 Standard
MR3 & MR6 luminaires are designed for use indoors, outdoors, wet locations, and areas containing
moisture, dirt, corrosion, vibration, and rough usage.
HOUSING:
Copper-free Aluminium and Polycarbonate lens
MOUNTING:
Surface:
Wall:
Yoke:
Pole:
Suspension:
VOLTAGE:
VAC: 100-277 VAC | 347: 347 VAC
CURRENT Typical:
MR3: 0.29A@120 VAC | 0.13A@277 VAC | 0.11A@347 VAC
MR6: 0.56A@120 VAC | 0.29A@277 VAC | 0.19A@347 VAC
CONNECTIONS:
Black: Line | White: Neutral | Green: Ground
*For connections use wire rated to a minimum of 75° C
TEMPERATURE RANGE:
-40° C to +55° C
INGRESS PROTECTION:
IP 66
Four (4) 1/4-20 OR M6 Screws or Bolts
Four (4) 1/4-20 OR M6 Screws or Bolts
Two (2) to Four (4) 1/4-20 OR M6 Screws or Bolts
1.5” NPT
Cable or Carabiner at 4 locations.
www.nemalux.com | sales@nemalux.com | Tel 403•242•7475 | Fax 403•243•6190
1-2
MR3-MR6 INSTALLATION
rev. 01-2016
YOKE MOUNT INSTALLATION
STEP 1:
Inspect shipping package and contents to
ensure no damage has occurred during
shipping.
STEP 2:
Remove plastic bushing.
STEP 3:
Assemble Yoke mount with carriage bolts on
inside and with washers and nuts.
Note:
By alternating the rotation mounting hole you
can determine either an upward swing or downward swing.
90° Downward
swing
90° Upward
swing
STEP 4:
Install Yoke Mount with included M6 bolts
and washers to MR Head.
Torque to 7 N-m (62 in-lbs)
STEP 5:
Mount fixture assembly to desired location
2-4x 1/4-20 OR M6 Screws or Bolts.
STEP 6:
Adjust and Aim fixture to desired position. Torque
hardware nuts to 9 N-m (80 in-lbs).
STEP 7:
Resume installation instructions provided
with fixture. (STEP 4)
43mm
51mm
4x
60 deg
7mm
www.nemalux.com | sales@nemalux.com | Tel 403•242•7475 | Fax 403•243•6190