Submittal Data Sheet Project Name: Location: Engineer: Submitted to: Submitted by: Reference: Approval: Date: Construction: Unit #: Drawing #: Performance Outdoor Unit Model No: Type: Rated Cooling Capacity (Btu/hr): Nom Cooling Capacity (Btu/hr): Cooling Input Power (kW): SEER: IEER: Rated Heating Capacity (Btu/hr): Nom Heating Capacity (Btu/hr): Heating Input Power (kW): Heating COP (Btu/hr / Btu/hr): HSPF: Heating COP 17F (Btu/hr / Btu/hr): RWEYQ84PYDN Non-Ducted / Ducted 80000 84000 5.6 N/A 22.5/21.3 90000 94500 5.4 4.7/4.5 N/A Condensing Unit Details 460/60/3ph Power Supply (V/Hz/Ph): L1, L2, L3 Ground Power Supply Connections: 10.2 Min. Circuit Amps MCA (A): 15 Max. Overcurrent Protection (MOP)(A): Max. Starting Current MSC(A): 7 Rated Load Amps RLA (A): 39-3/8 Dimensions Height (Inch): 30-3/4 Dimensions Width (Inch): 21-11/16 Dimensions Depth (Inch): 343 Net Weight (lbs): System Details Refrigerant Type: Holding Refrigerant Charge (lbs): Additional Charge (lbs/ft): Pre-charge Piping (Length ft): Max. Pipe Length (Total ft): Max. Pipe Length (Vertical ft): Max Height Seperation (Ind to Ind ft): R-410A 11.5 install data 390 ft 164 ft / 130 ft 49 ft Condensing Unit Type: 7-Ton VRV-WIII Heat Pump Unit Combination: Rated Cooling Conditions RWEYQ84PYDN Indoor: 80.6°F DB/66.2°F WB Outdoor: 95°F DB/75°F WB Rated Heating Conditions Indoor: 68°F DB/59°F WB Outdoor: 47°F DB/43°F WB 50 / 25 0 Rated Piping Length (ft) Rated Height Difference (ft) Inverter 23 - 100 42 - 109 (130%) N/A 7//8 3/8 Compressor Type: Capacity Control Range (%): Capacity Index Limit: Airflow Rate (CFM): Gas Pipe Connection (inch): Liquid Pipe Connection (inch): H/L Pressure Connection (inch): H/L Equalizing Connection (inch): Sound Pressure Level (dBA): Sound Power Level (dBA): Max. No. of Indoor Units: Cooling Operation Range (°F): Cooling Range w/Baffle (°F): Heating Operation Range (°F): Heating Range w/Baffle (°F): 51 14 35 - 104 (Mech. Room) 35 - 104 (Mech. Room) Daikin AC (Americas), Inc., 1645 Wallace Drive - Suite 110, Carrollton, TX 75006 Daikin AC TRL Generated Submittal Data Page 1 of 3 www.daikinac.com (Daikin's products are subject to continuous improvements. Daikin reserves the right to modify product design, specifications and information in this data sheet without notice and without incurring any obligations) Submittal Data Sheet Project Name: Location: Engineer: Submitted to: Submitted by: Reference: Approval: Date: Construction: Unit #: Drawing #: Dimensional Drawing - Condensing Unit Daikin AC (Americas), Inc., 1645 Wallace Drive - Suite 110, Carrollton, TX 75006 Daikin AC TRL Generated Submittal Data RWEYQ84PYDN Page 2 of 3 www.daikinac.com (Daikin's products are subject to continuous improvements. Daikin reserves the right to modify product design, specifications and information in this data sheet without notice and without incurring any obligations) Submittal Data Sheet Project Name: Location: Engineer: Submitted to: Submitted by: Reference: RWEYQ84PYDN Approval: Date: Construction: Unit #: Drawing #: RWEYQ84PYDN Std U.S. Warranty: 7yrs Compressor, 1yrs Parts. A field supplied 1 ¼ strainer (50 Mesh) is required per condensing unit module Daikin AC (Americas), Inc., 1645 Wallace Drive - Suite 110, Carrollton, TX 75006 Daikin AC TRL Generated Submittal Data Page 3 of 3 www.daikinac.com (Daikin's products are subject to continuous improvements. Daikin reserves the right to modify product design, specifications and information in this data sheet without notice and without incurring any obligations)