Submittal Data Sheet

advertisement
Submittal Data Sheet
Project Name:
Location:
Engineer:
Submitted to:
Submitted by:
Reference:
Approval:
Date:
Construction:
Unit #:
Drawing #:
Performance
RWEYQ216PTJU -HR
Outdoor Unit Model No:
Non-Ducted / Ducted
Type:
206000
Rated Cooling Capacity (Btu/hr):
216000
Nom Cooling Capacity (Btu/hr):
12.6
Cooling Input Power (kW):
N/A
SEER:
22.7/22.2
IEER:
232000
Rated Heating Capacity (Btu/hr):
243000
Nom Heating Capacity (Btu/hr):
12
Heating Input Power (kW):
4.8/4.91
Heating COP (Btu/hr / Btu/hr):
N/A
HSPF:
Heating COP 17F (Btu/hr / Btu/hr):
Condensing Unit Details
208-230/60/3ph
Power Supply (V/Hz/Ph):
L1, L2, L3 Ground
Power Supply Connections:
22.4+22.4+22.4
Min. Circuit Amps MCA (A):
40+40+40
Max. Overcurrent Protection (MOP)(A):
Max. Starting Current MSC(A):
11.6+11.6+11.6
Rated Load Amps RLA (A):
39-3/8
Dimensions Height (Inch):
93-3/4
Dimensions Width (Inch):
21-11/16
Dimensions Depth (Inch):
330 x 3
Net Weight (lbs):
System Details
Refrigerant Type:
Holding Refrigerant Charge (lbs):
Additional Charge (lbs/ft):
Pre-charge Piping (Length ft):
Max. Pipe Length (Total ft):
Max. Pipe Length (Vertical ft):
Max Height Seperation (Ind to Ind ft):
R-410A
9.9+9.9+9.9
install data
390 ft
164 ft / 130 ft
49 ft
Condensing Unit Type:
Unit Combination:
Rated Cooling
Conditions
18-Ton VRV-WIII Heat Recovery
RWEYQ72PTJU RWEYQ72PTJU
RWEYQ72PTJU
Indoor: 80.6°F DB/66.2°F WB
Outdoor: 95°F DB/75°F WB
Rated Heating
Conditions
Indoor: 68°F DB/59°F WB
Outdoor: 47°F DB/43°F WB
100 / 50
0
Rated Piping Length (ft)
Rated Height Difference (ft)
Inverter
8 - 100
108 - 280 (130%)
N/A
1-3/8
5/8
1-1/8
Compressor Type:
Capacity Control Range (%):
Capacity Index Limit:
Airflow Rate (CFM):
Gas Pipe Connection (inch):
Liquid Pipe Connection (inch):
H/L Pressure Connection (inch):
H/L Equalizing Connection (inch):
Sound Pressure Level (dBA):
Sound Power Level (dBA):
Max. No. of Indoor Units:
Cooling Operation Range (°F):
Cooling Range w/Baffle (°F):
Heating Operation Range (°F):
Heating Range w/Baffle (°F):
56
22
35 - 104 (Mech. Room)
35 - 104 (Mech. Room)
Daikin AC (Americas), Inc., 1645 Wallace Drive - Suite 110, Carrollton, TX 75006
Daikin AC TRL Generated Submittal Data
Page 1 of 3
www.daikinac.com
(Daikin's products are subject to continuous improvements. Daikin reserves the right to modify product design, specifications and information in this data sheet without notice and without incurring any obligations)
Submittal Data Sheet
Project Name:
Location:
Engineer:
Submitted to:
Submitted by:
Reference:
Approval:
Date:
Construction:
Unit #:
Drawing #:
Dimensional Drawing - Condensing Unit
Daikin AC (Americas), Inc., 1645 Wallace Drive - Suite 110, Carrollton, TX 75006
Daikin AC TRL Generated Submittal Data
RWEYQ216PTJU -HR
Page 2 of 3
www.daikinac.com
(Daikin's products are subject to continuous improvements. Daikin reserves the right to modify product design, specifications and information in this data sheet without notice and without incurring any obligations)
Submittal Data Sheet
Project Name:
Location:
Engineer:
Submitted to:
Submitted by:
Reference:
RWEYQ216PTJU -HR
Approval:
Date:
Construction:
Unit #:
Drawing #:
RWEYQ216PTJU -HR
Std U.S. Warranty: 7yrs Compressor, 1yrs Parts.
Requires Multi Connection Pipe Kit
(BHFP22MA56U).
Daikin AC (Americas), Inc., 1645 Wallace Drive - Suite 110, Carrollton, TX 75006
Daikin AC TRL Generated Submittal Data
Page 3 of 3
www.daikinac.com
(Daikin's products are subject to continuous improvements. Daikin reserves the right to modify product design, specifications and information in this data sheet without notice and without incurring any obligations)