Signal Conditioners and Isolators

advertisement
2002 IS Catalog
Page
Introduction ............................................................................................................................. 139
Loop-Powered Isolators
KFD0-CS-1.50 (Current repeater / driver / isolator / single-channel) .................................................. 140
KFD0-CS-2.50 (Current repeater / driver / isolator / dual-channel) ..................................................... 141
KFD0-CC-1 (Current converter / single channel / isolator) .................................................................. 142
KFD0-VC-1.50m (Voltage to current converter / single-channel / isolator) ......................................... 143
KFD0-VC-1.10 (Voltage to current converter / single-channel / isolator) ............................................ 144
KFD0-TT-1 (Thermocouple / mV input / single-channel / isolator) ...................................................... 145
KFD0-TR-1 (RTD input / single-channel / isolator) .............................................................................. 146
Analog Isolators
KFDX-DCI (DC current input / current/voltage output / isolator) ......................................................... 147
KFDX-DCV (DC voltage input / current/voltage output / isolator) ....................................................... 148
KFD2-CR-1.300 (2- or 3-wire transmitter input / 4-20 mA current output / isolator) .......................... 149
KFD2-CD-1.32 (Current/voltage driver / current output / isolator) ...................................................... 150
KFD2-CR4-1.20 (Single input / dual output transmitter / repeater / isolator) ...................................... 151
KFD2-STC4-1.20 (HART transmitter power supply / isolator) ............................................................. 152
KFDX-RTD (RTD input / current/voltage output / isolator) .................................................................. 153
KFDX-TC (Thermocouple input / isolator) ........................................................................................... 154
KFD2-UT-1 (Universal temperature input / isolator) ............................................................................. 155
KFD2-UT-1-1 (Universal temperature input / isolator) ......................................................................... 156
KFDX-AC (AC current/voltage input / current/voltage output / isolator) ............................................. 157
KFDX-HZ (Frequency input / current/voltage output / isolator) .......................................................... 158
KFA5-DWB-1.D (Rotational speed limit alarm) .................................................................................... 159
KFA6-DWB-1.D (Rotational speed limit alarm) .................................................................................... 160
KFD2-DWB-1.D (Rotational speed limit alarm) ................................................................................... 161
KFU8-UFC-1 (Universal frequency converter) ..................................................................................... 162
KFD2-UFC-1.D (Universal frequency converter with display) .............................................................. 163
KFD2-UFC-1 (Universal frequency converter / isolator) ...................................................................... 164
KFU8-UFC-1.D (Universal frequency converter / isolator with display) ............................................... 165
Limit Alarm Isolators
KFDA-DCI (DC current input / 2 Form C contact outputs / isolator) ................................................... 166
KFDA-DCV (DC voltage input / 2 Form C contact outputs / isolator) .................................................. 167
KFD2-GS-1.2W (DC current/voltage input / 2 Form C contact outputs / isolator) .............................. 168
KFD2-CRG-1.D (Transmitter power supply / isolator) ......................................................................... 169
KFU8-CRG-1.D (Transmitter power supply / isolator) ......................................................................... 170
KFDA-TC (Thermocouple input / 2 Form C contact outputs / isolator) ............................................... 171
KFDA-RTD (RTD input / 2 Form C contact outputs / isolator) ............................................................ 172
KFDA-GU-1 (Universal input / 2 Form C contact outputs / PC interface / isolator) ............................ 173
138
Pepperl+Fuchs® Inc. • Telephone (330) 486-0002 • FAX (330) 425-4607
E-mail: greenteam@us.pepperl-fuchs.com • www.am.pepperl-fuchs.com
2002 IS Catalog
Introduction
With the variety of process control systems available, it is often necessary to convert an input signal into
a format that the control system will accept. Signal conditioners take signals from an assortment of field
instruments such as thermocouples and RTDs, and convert those signals into any of several standard
instrument signals (1-5 V, 4-20 mA, etc.) while providing isolations.
Signal conditioners are also beneficial to the accurate transfer of these signals and the elimination of
ground loops.
Pepperl+Fuchs signal conditioners utilize the latest technology, offering unparalleled protection against
ground loops while maintaining optimum signal accuracy and complete isolation. There are three basic
types of KF signal conditioners:
Loop Powered Repeaters/Isolators: Loop powered repeaters do not require a separate
power supply. Available in single and dual channel models, these transformer isolated
signal conditioners transfer analog DC signals with each channel working as a DC isolator
providing 2,500 VDC isolation between the input and output.
Analog Isolators: These units require a separate power supply and provide signal
conditioning and 3-way isolation to various input signals.
Limit Alarms: This class of signal conditioners provides two Form C relay outputs with
adjustable high and low switchpoints and selectable control safe and normal operation.
They also require a separate power supply and provide 3-way isolation.
The latter two categories are fully field-configurable and provide 1,800 VDC isolation separating input,
output and power supply. Input and output ranges, modes of operation, switchpoints, etc., can be
programmed in the field via DIP switches on the side of the housing. Some models also offer a PC
interface. Input, zero, and span are adjustable by potentiometer to 50% for all input ranges. The wideranging capabilities and field-configurable settings allow for numerous options in a diverse range of
applications.
All P+F analog isolators and limit alarms also contain the ASIC chip for increased reliability. ASIC (Application Specific Integrated Circuitry) substantially reduces failures by virtually eliminating discrete components and their solder joints where most faults occur. Printed circuit board connections are reduced
by 70%.
Pepperl+Fuchs® Inc. • Telephone (330) 486-0002 • FAX (330) 425-4607
E-mail: greenteam@us.pepperl-fuchs.com • www.am.pepperl-fuchs.com
139
2002 IS Catalog
Current Repeater/
Driver Single
Channel Isolator
Model Number
KFD0-CS-1.50
■ 4-20 mA isolator
■ Single-channel
■ Loop powered
The KFD0-CS-1.50 current repeater is a
fully floating isolator for standard 4-20 mA
instruments. The inputs are galvanically
isolated from the outputs. Typical
applications include driving I/P converters
and isolating 2-wire transmitters.
OPERATION:
Signal Conditioners
The KFD0-CS-1.50 is a single-channel
device that does not require a separate
power supply. Due to the 24 VDC input
voltage limitation and the internal voltage
drop, the maximum output voltage under
load is 23 VDC. The maximum internal
resistance is 230 ohms. At input voltages
greater than 26.1 V, the internal voltage
drop is lower than with input voltages
below 26.1 V.
Technical Data
Power Supply
Nominal voltage
Loop powered (not intrinsically safe)
12-35 VDC
Input
Input voltage (Vin)
Input current (Uin)
Terminals 11+, 1210-35 VDC
4-20 mA
Power Dissipation
@ 25 mA (Vin < 26.1 V)
@ 25 mA (Vin > 26.1 V)
< 150 mW
< 400 mW
Output
Output voltage:
10 V < Vin < 26.1 V
Vin > 26.1 V
Output current
Short circuit current
Transfer current
Terminals 1, 2
0.9 x Vin - (0.23 x current in mA) - 0.7
23 V - (0.23 x current in mA)
4-20 mA
≤ 65 mA @ Vin>26.1 V
≤ 40 mA
Transfer Characteristics
Calibrated accuracy
Temperature drift
Response time
Isolation
±20 µA for 1 kΩ load @ 20ºC
(includes linearity and hysteresis)
≤ 2 µA / ºC
≤ 5 ms (@ 4-20 mA and Vin < 26 V)
2500 VDC
Mechanical
Housing:
Material
Style
Mounting
Dimensions (mm)
Weight
Makrolon
KF style (see page 387)
35mm DIN rail or surface mount
115 x 20 x 118
100 g (3.5 oz.)
Ambient Temperature
-20ºC to +60ºC (-4ºF to +140ºF)
Note: For information about programming,
refer to our website at www.am.pepperl-fuchs.com
Connection Diagram
KFD0-CS-1.50
Input
140
(+) 11
1 (+)
(– ) 12
2 (–)
Output
Pepperl+Fuchs® Inc. • Telephone (330) 486-0002 • FAX (330) 425-4607
E-mail: greenteam@us.pepperl-fuchs.com • www.am.pepperl-fuchs.com
2002 IS Catalog
Technical Data
Power Supply
Nominal voltage
Loop powered (not intrinsically safe)
12-35 VDC
Input
Input voltage (Vin)
Input current (Uin)
Terminals 11+, 12- ; 8+, 9+, 1010-35 VDC
4-20 mA
Power Dissipation
@ 25 mA (Vin < 26.1 V)
@ 25 mA (Vin > 26.1 V)
< 150 mW
< 400 mW
Output
Output voltage:
10 V < Vin < 26.1 V
Vin > 26.1 V
Output current
Short circuit current
Transfer current
Transfer Characteristics
Calibrated accuracy
Current
Repeater/Driver
Dual Channel Isolator
Terminals 1+, 2-; 4+, 50.9 x Vin - (0.23 x current in mA) - 0.7
23 V - (0.23 x current in mA)
4-20 mA
≤ 65 mA @ Vin>26.1 V
≤ 40 mA
Model Number
KFD0-CS-2.50
■ 4-20 mA isolator
Mechanical
Housing:
Material
Style
Mounting
Dimensions (mm)
Weight
Makrolon
KF style (see page 387)
35mm DIN rail or surface mount
115 x 20 x 118
100 g (3.5 oz.)
Ambient Temperature
-20ºC to +60ºC (-4ºF to +140ºF)
Note: For information about programming,
refer to our website at www.am.pepperl-fuchs.com
■ Dual-channel
■ Loop powered
The KFD0-CS-2.50 current repeater is a
fully floating isolator for standard 4-20 mA
instruments. Each channel works as a DC
isolator with the inputs galvanically isolated
from the outputs. Typical applications
include driving I/P converters and isolating
2-wire transmitters.
OPERATION:
The KFD0-CS-2.50 is a dual-channel
device that does not require a separate
power supply. Due to the 24 VDC input
voltage limitation and the internal voltage
drop, the maximum output voltage under
load is 23 VDC. The maximum internal
resistance is 230 ohms. At input voltages
greater than 26.1 V, the internal voltage
drop is lower than with input voltages
below 26.1 V.
Signal Conditioners
Temperature drift
Response time
Isolation
±20 µA for 1 kΩ load @ 20ºC
(includes linearity and hysteresis)
≤ 2 µA / ºC
≤ 5 ms (@ 4-20 mA and Vin < 26 V)
2500 VDC
Connection Diagram
KFD0-CS-2.50
(+) 11
1 (+)
(– ) 12
2 (– )
(+) 9
4 (+)
(– ) 10
5 (– )
Input 1
Input 2
Output 1
Output 2
(+) 8
Pepperl+Fuchs® Inc. • Telephone (330) 486-0002 • FAX (330) 425-4607
E-mail: greenteam@us.pepperl-fuchs.com • www.am.pepperl-fuchs.com
141
2002 IS Catalog
Current/Voltage
Converter Single
Channel Isolator
Model Number
KFD0-CC-1
■ Field selectable voltage or
current input
■ Loop-powered
Technical Data
Power Supply
Nominal voltage
Loop powered (not intrinsically safe)
12-35 VDC
Input (selectable)
Input
Current load
Input voltage (Vin)
Voltage load
Terminals 1+, 20-20 mA
≤ 50 Ω
0-10 VDC
≤ 100 kΩ
Output
Output
Burnout fault signal
Load/Ohm
Terminals 9+, 84-20 mA
Downscaled ≤ 3 mA
(Us - 12 V) / 0.02 A
Transfer Characteristics
Voltage surge
Calibrated accuracy
Linearity fault
Temperature drift
6.5 ppm / V
±0.1% of final value @ 20ºC
≤ 0.04% of final value
0.050% of range / ºC
0.060% of span / ºC
≤ 250 ms
safe isolated per DIN VDE 01061
design isolation voltage 253 VEff
Response time
Galvanic Isolation
■ Isolation of input/output
The KFD0-CC-1 loop powered, 2-wire
isolator that converts 2-wire voltage/
current signals to a 4-20 mA signal.
Signal Conditioners
The KFD0-CC-1 provides galvanic
isolation for the loop. The required input
range is set by a switch on the side of the
unit. Zero and span adjustment are
achieved by potentiometers on the top of
the isolator.
Mechanical
Housing:
Material
Style
Mounting
Dimensions (mm)
Weight
Protection (IEC)
Makrolon
KF housing (see page 387)
35mm DIN rail or surface mount
115 x 20 x 118
100 g (3.5 oz.)
IP20
OperatingTemperature
-20ºC to +60ºC (-4ºF to +140ºF)
Note: For information about programming,
refer to our website at www.am.pepperl-fuchs.com
Connection Diagram
KFD0-CC-1
Input
142
(+) 1
9 (+)
(– ) 2
8 (– )
Output
Pepperl+Fuchs® Inc. • Telephone (330) 486-0002 • FAX (330) 425-4607
E-mail: greenteam@us.pepperl-fuchs.com • www.am.pepperl-fuchs.com
2002 IS Catalog
Technical Data
Power Supply
Nominal voltage
Loop powered (not intrinsically safe)
12-35 VDC
Input
Input voltage
Input current
Terminals 1+, 3-50 to + 50 mV
Input monitoring on ≤ 15 nA
Input monitoring off ≤ 1 nA
Output
Output
Lead breakage
Terminals 9+, 84-20 mA
enabled: ≤ 3 mA; disabled: ≥ 22 mA
Transfer Characteristics
Sensing range
- 50 mV to +50 mV
Zero point 1% of final value
Span ± 3.5% of final value
Zero point 0.01% of the span / ºC or
±1 µV / ºC (whichever is larger)
Span 0.005% of span / ºC
≤ 250 ms
safe isolated per DIN VDE 01061
design isolation voltage 253 VEff
Temperature drift
Response time
Galvanic isolation
Voltage to Current
Converter Single
Channel Isolator
Model Number
KFD0-VC-1.50m
■ -50 mV to + 50 mV voltage in
current output isolator
■ Loop powered
■ Lead breakage monitoring
Mechanical
Housing:
Material
Style
Mounting
Dimensions (mm)
Weight
Protection (IEC)
Makrolon
KF housing (see page 387)
35mm DIN rail or surface mount
115 x 20 x 118
100 g (3.5 oz.)
IP20
Ambient Temperature
-20ºC to +60ºC (-4ºF to +149ºF)
The KFD0-VC-1.50m receives a -50 to
+50 mV signal input and produces a 4-20
mA output. This loop powered module also
provides galvanic isolation.
The sensing range of the bipolar input unit
isolates and conditions a 4-20 mA output.
Fine adjustment for zero and span are
performed with the potentiometer on top
of the unit.
Signal Conditioners
Optional lead monitoring is available by the
field configurable DIP switches. Enabling
this feature produces an output ≤ 3 mA
when the input wire is broken, while
disabling produces an output ≥ 22 mA.
Note: For information about programming,
refer to our website at www.am.pepperl-fuchs.com
Connection Diagram
KFD0-VC-1.50m
(+) 1
9 (+)
(– ) 3
8 (– )
Input
Output
Pepperl+Fuchs® Inc. • Telephone (330) 486-0002 • FAX (330) 425-4607
E-mail: greenteam@us.pepperl-fuchs.com • www.am.pepperl-fuchs.com
143
2002 IS Catalog
Voltage to Current
Converter Single
Channel Isolator
Technical Data
Power Supply
Nominal voltage
Loop powered (not intrinsically safe)
12-35 VDC
Input
Input
Load
Terminals 1+, 2-10 to +10 V
≥ 100 kΩ
Output
Output
Load (Ohm)
Terminals 9+, 84-20 mA, ≤ 35 mA
≤ (power supply - 12 V) / 0.02 A
Transfer Characteristics
Operating voltage
Calibrated accuracy
Linearity faults
Sensing range
6.5 ppm / V
0.1% of final value
≤ 0.04% of final value
-10 V to +10 V
Span ± 1.5% of final value
Zero point ±1% of final value
Span 0.005% of span / ºC
Zero point 0.060% of span / ºC
250 ms
Function isolation per EN 50178
design isolation voltage 253 Veff
Model Number
KFD0-VC-1.10
■ -10 to +10 voltage input/4-20
mA output
Temperature drift
Response time
Galvanic isolation
■ Loop powered
■ Isolation of input/output
The KFD0-VC-1.10 receives a -10 to +10
voltage input and produces a 4-20 mA
signal output. This loop powered module
also provides galvanic isolation.
Signal Conditioners
The sensing range of the bipolar input unit
isolates and conditions a 4-20 mA output.
Fine adjustment for zero and span are
performed with the potentiometer on top
of the unit.
Mechanical
Housing
Material
Style
Dimensions (mm)
Weight
Protection
Makrolon
KF housing (see page 387)
115 x 20 x 118
100 g (3.5 oz.)
IP20
Operating Temperature
-20ºC to +60ºC (-4ºF to +140ºF)
Note: For information about programming,
refer to our website at www.am.pepperl-fuchs.com
Connection Diagram
KFD0-VC-1.10
(+) 1
9 (+)
(– ) 2
8 (– )
Input
144
Output
Pepperl+Fuchs® Inc. • Telephone (330) 486-0002 • FAX (330) 425-4607
E-mail: greenteam@us.pepperl-fuchs.com • www.am.pepperl-fuchs.com
2002 IS Catalog
Thermocouple/
mV Input Single
Channel Isolator
Technical Data
Power Supply
Nominal voltage
Loop powered (not intrinsically safe)
12-35 VDC
Input
Thermocouple (terminals 1,2,3)
Input current
Terminals 1+, 2-, 3E,J,K, N,R,S or T (CJC reference to 0ºC)
Input monitoring ‘ON’ ≤ 15 nA
Input monitoring ‘OFF’ ≤ 1 nA
Output
Output
Lead breakage
Terminals 9+, 84-20 mA, ≤ 35 mA
Downscaled ≤ 3 mA
Upscaled > 22 mA
(power supply - 12 V) / 0.02 A
Load
Transfer Characteristics
Voltage surge
Measuring range (adjustable)
Characteristics
Calibrated accuracy
Temperature drift
Response time
Galvanic isolation
6.5 ppm / V
Span 4 to 60 mV
Zero point -12 to 60 mV
Output voltage is proportional to input
0.1% of final value ±1ºC for cold point
Span 0.005% of span / ºC
Zero point 0.01% of span / ºC or ±1µV/ºC
0.01% of span/ºC or ±0.03ºC/ºC (J,K,N,T,E)
0.01% of span/ºC or ±0.06ºC/ºC (R, S)
Cold point ±2.0ºC (calibrated at TA = 20ºC)
≤ 250 ms
Function isolation per EN50178
design isolation voltage 253 Veff
Model Number
KFD0-TT-1
■ Internal CJC
■ Loop powered
■ Lead breakage and short circuit
monitoring
■ Input/output isolation
■ Field-selectable thermocouple inputs
The KFD0-TT-1 is a loop powered isolator
that accepts thermocouple inputs and
conditions to a 4-20 mA output.
Makrolon
KF housing (see page 387)
115 x 20 x 118
150 g (5.3 oz.)
IP20
Operating Temperature
-20ºC to +60ºC (-4ºF to +149ºF)
Types E, J, K, N, R, S, and T thermocouple
inputs with internal cold junction
compensation (CJC) with galvanic
isolation. The input voltage is linear to
output current, not proportional to
temperature. Adjustable zero, span and
burnout detection are field-configurable.
Signal Conditioners
Mechanical
Housing
Material
Style
Dimensions (mm)
Weight
Protection
Note: For information about programming,
refer to our website at www.am.pepperl-fuchs.com
Connection Diagram
KFD0-TT-1
(+) 1
8 (– )
(+) 1
(+) 1
8 (– )
(– ) 2
9 (+)
Output
Input
(– ) 3
(– ) 2
(– ) 3
Input for
Thermocouple
9 (+)
Passive Output
Pepperl+Fuchs® Inc. • Telephone (330) 486-0002 • FAX (330) 425-4607
E-mail: greenteam@us.pepperl-fuchs.com • www.am.pepperl-fuchs.com
145
2002 IS Catalog
RTD Input
Single Channel
Isolator
Technical Data
Power Supply
Nominal voltage
Loop powered (not intrinsically safe)
12-35 VDC
Input
Input
Lead resistance
Test current
Terminals 1+, 2-, 3+
PT100, 2- and 3-wire connection
≤ 100 Ω / lead
≈ 1 mA
Output
Output
Lead breakage
Load (Ohm)
Terminals 9+, 84-20 mA (35 mA max.)
Upscaled ≥ 22 mA
≤ (power supply - 12 V) / 0.02 A
Transfer Characteristics
Voltage surge
Measuring range
6.5 ppm / V
Span w/o linearization 25ºC to 800ºC
Span with linearization 25ºC to 430ºC
Zero point w/o linearization -200ºC to 466ºC
Zero point with linearization -86ºC to 405ºC
0.1% of final accuracy
w/o linearization ≤ 0.04% final value
with linearization ≤ 0.14% final value
span and zero point 0.015% / ºC or
± 10 mΩ / ºC
≤ 250 ms
Function isolation per EN50178
design isolation voltage 50 Veff
Model Number
KFD0-TR-1
Calibrated accuracy
Linearity fault
■ Loop powered
■ PT100, 2- and 3-wire
Temperature drift
■ Lead breakage (LB) monitoring
■ Input/output isolation
■ Field-configurable inputs/outputs
The KFD0-TR-1 is a loop powered isolator
that accepts Pt100 2- and 3-wire inputs and
conditions them to a 4-20 mA output.
The KFD0-TR-1 provides galvanic isolation
and burnout detection (≥22 mA). Fieldconfigurable DIP switches allow linearization
to be turned on and off.
Signal Conditioners
The loop powered 2-wire converter is suited
for the connection of the Pt100 in 2- or 3wire mode.
Response time
Galvanic isolation
Mechanical
Housing
Material
Style
Dimensions (mm)
Weight
Protection (IEC)
Makrolon
KF housing (see page 387)
115 x 20 x 100 mm
150 g (5.3 oz.)
IP20
Operating Temperature
-20ºC to +60ºC (-4ºF to +140ºF)
Note: For information about programming, refer to page 209
or to our website at www.am.pepperl-fuchs.com
Connection Diagram
KFD0-TR-1
(– ) 2
(– ) 2
(– ) 2
Input
1
1
8 (– )
(– ) 2
8 (– )
1
9 (+)
Output
(+) 3
9 (+)
Passive Ouput
(+) 3
(+) 3
Input for Pt100
146
Pepperl+Fuchs® Inc. • Telephone (330) 486-0002 • FAX (330) 425-4607
E-mail: greenteam@us.pepperl-fuchs.com • www.am.pepperl-fuchs.com
2002 IS Catalog
Technical Data
Power Supply
Nominal voltage
Power consumption
Inrush current
Terminals 11+, 12- or Power Rail
9-30 VDC (unregulated acceptable)
≤ 1.5 W, 1 W typical
≤ 200 mA
Input
Input span
Overload
Impedance
Zero
Span
Terminals 1+, 21-100 mA
≤ 170 mA, 60 VDC on input
20 Ω typical
50% of full scale input
50% of full scale input
Output
Voltage output
Impedance
Drive
Current Output
Impedance
0-1 mA
0/4-20 mA
Terminals 7-, 8+
0-5 V, 0-10 V
< 10 Ω
≤ 10 mA
0-1 mA, 0-20 mA, 4-20 mA
> 100 kΩ
7.5 V, max. 7.5 kΩ
12 V, max 600 Ω
Transfer Characteristics
Accuracy (including linearity and hysteresis)
2 mA range
± 0.35% of full scale; 0.5% max.
other ranges
± 1.0% of full scale; 0.2% max.
stability
± 0.025% of full scale / ºC for zero span
Isolation
3-way, 1800 VDC
Common mode rejection
DC to 60 Hz: 120 dB
Response time
200 ms, 400 ms max.
Makrolon
KF housing (see page 387)
115 x 20 x 100 mm
3.5 oz. (100 g)
IP 20
Operating Temperature
0ºC to +55ºC (+32ºF to +131ºF)
Note: For information about programming, refer to page
209 or to our website at www.am.pepperl-fuchs.com
Model Number
KFDX-DCI
■ Field configurable inputs and
outputs
■ Wide range of DC current inputs
■ 3-way isolation
■ Accepts bipolar inputs
The KFDX-DCI accepts a DC current input
and provides a fully isolated proportional
current or voltage output. In order to eliminate
ground loops, the I/O channel is optically
isolated to 1800 VDC and transformer
isolated from the power supply.
The input can be configured in the field for
one of six current ranges from 1-100 mA.
Output is linear to the input, configurable for
five ranges: 0-5 V, 0-10 V, 0-1 mA, 0-20 mA
or 4-20 mA. The KFDX-DCI accepts bipolar
inputs and offers selectable normal or reverse
output modes of operation (4-20 mA, 20-4
mA). For inputs that do not change in polarity,
select unipolar operation.
Signal Conditioners
Mechanical
Housing
Material
Style
Dimensions (mm)
Weight
Protection (IEC)
DC Current Input
Current/Voltage
Output Isolator
The KFDX-DCI is equipped with a dual
function power/signal status LED. When the
unit is powered, this green LED turns on.
When the input signal is over 110% of the
full scale range, the LED flashes at 8 Hz;
below 0% it flashes at 4 Hz.
Connection Diagram
KFDX-DCI
This unit is not intrinsically safe.
DC Current
Input
(+) 1
8 (+)
(– ) 2
7 (– )
11 (+)
12 (– )
Analog
Output
DC Power
Supply
Pepperl+Fuchs® Inc. • Telephone (330) 486-0002 • FAX (330) 425-4607
E-mail: greenteam@us.pepperl-fuchs.com • www.am.pepperl-fuchs.com
147
2002 IS Catalog
DC Voltage Input
Current/Voltage
Output Isolator
Model Number
KFDX-DCV
Technical Data
Power Supply
Nominal voltage
Power consumption
Terminals 11+ and 12- or Power Rail
9-30 VDC (unregulated acceptable)
≤ 1.5 W, 1 W typical
Input
Voltage
Maximum overload
Impedance
Zero
Span
Terminals 1+, 210 mV to 100 V
200 VDC
≥ 100 kΩ typical
50% of full scale input
50% of full scale input
Output
Type
Voltage output
Impedance
Drive
Current output
Impedance
0-1 mA
0/4-20 mA
Terminals 7-, 8+
Selectable DC current or voltage
0-5 V, 0-10 V
< 10 kΩ
10 mA, max.
0-1 mA, 4-20 mA, 0-20 mA
> 100 kΩ
7.5 V, max. 7.5 kΩ
12 V, max. 600 Ω
Transfer Characteristics
Accuracy (all ranges)
Stability
Response time
Isolation
Common mode rejection
± 0.1% of full scale: 0.2% max.
± 0.025% of full scale / ºC max.
≤ 400 ms, 200 ms typical
3-way, 1800 VDC
DC to 60 Hz, 120 dB
Mechanical
Housing
Material
Style
Dimensions (mm)
Weight
Protection (IEC)
Makrolon
KF housing (see page 387)
115 x 20 x 100 mm
100 g (3.5 oz.)
IP20
Operating Temperature
0ºC to +55ºC (+32ºF to +131ºF)
■ Field-configurable inputs/outputs
■ 3-way isolators
■ Accepts bipolar inputs
■ Wide range of DC voltage inputs
The KFDX-DCV accepts a DC voltage input
and provides a fully isolated proportional
current or voltage output. In order to eliminate
ground loops, the I/O channel is optically
isolated to 1,800 VDC and transformer
isolated from the power supply.
Signal Conditioners
The input can be configured in the field for
one of twelve voltage ranges from 10 mV to
100V. Output is linear to the input, configurable
for five ranges: 0-5 V, 0-10 V, 0-1 mA, 0-20
mA, or 4-20 mA. The KFDX-DCV accepts
bipolar inputs and offers selectable normal or
reverse modes of operation (4-20 mA, 20-4
mA). For inputs which do not change in
polarity, select unipolar operation.
The KFDX-DCV is outfitted with a dual function
power/signal status LED. When the unit is
powered, this green LED turns on. When the
input signal is over 110% of the full scale
range, the LED flashes at 8 Hz.
Note: For information about programming, refer to page
209 or to our website at www.am.pepperl-fuchs.com
Connection Diagram
This unit is not intrinsically safe
KFDX-DCV
DC Voltage
Input
(+) 1
8 (+)
(– ) 2
7 (– )
11 (+)
12 (– )
148
Analog
Output
DC Power
Supply
Pepperl+Fuchs® Inc. • Telephone (330) 486-0002 • FAX (330) 425-4607
E-mail: greenteam@us.pepperl-fuchs.com • www.am.pepperl-fuchs.com
2002 IS Catalog
2- and 3-wire Transmitter
Input 4-20 mA Current
Output Isolator
Technical Data
Power Supply
Nominal voltage
Power consumption
Terminals 11+, 12- or Power Rail
20-35 VDC
≤ 1.7 W
Input
Available voltage
Input load (terminals 2, 3)
Terminals 1+, 2-, 3
2-wire: 17.5 V at 20 mA
3-wire: 16.5 V at 25 mA
20 Ω
Output (not intrinsically safe)
Output signal
Available voltage
Load
Terminals 7-, 8+, 90-20 mA
20 VDC
≤ 1 kΩ
Transfer Characteristics
Accuracy @ 20ºC
Temperature drift
≤ ±10 µA
≤ ±0.2 mA / ºC (0ºC to +60ºC)
±1.0 mA / ºC (-20ºC to 0ºC)
≤ 50 µs
Isolation per EN50178
Isolation voltage 253 Veff
Response time
Galvanic isolation, 3 way
Model Number
KFD2-CR-1.300
■ 2- or 3-wire input
■ 20-30 VDC power supply
■ 4-20 mA output
Mechanical
Housing
Material
Style
Dimensions (mm)
Weight
Protection (IEC)
Makrolon
KF Housing (see page 387)
115 x 20 x 100 mm
100 g (3.5 oz.)
IP20
The KFD2-CR-1.300 is an isolator that
powers and repeats a 4-20 mA signal from
a 2- or 3-wire transmitter. It can also isolate
and repeat signals from a current source.
Operating Temperature
-20ºC to +60ºC (-4ºF to +140ºF)
For 2-wire transmitters, connected to
terminals 1 and 3, there is 17.5 V at 20 mA
available to the transmitter.
■ 3-way isolation
Signal Conditioners
For 3-wire transmitters, the power is supplied
on terminals 1 and 2 with a 4-20 mA signal
flowing into terminal 3. The voltage available
is approximately 16.5 V at 25 mA between
terminals 1 and 2. Power, input and output
are galvanically isolated.
This unit is not intrinsically safe.
For information about programming, refer to page 209 or to our website
at www.am.pepperl-fuchs.com
Connection Diagram
KFD2-CR-1.300
(+) 1
(+) 1
(– ) 2
(– ) 2
(+) 1
8 (+)
(– ) 2
7 (– )
3
3
9 (– )
11 (+)
3
3
Input
Analog
Output
12 (–)
DC Power
Supply
Pepperl+Fuchs® Inc. • Telephone (330) 486-0002 • FAX (330) 425-4607
E-mail: greenteam@us.pepperl-fuchs.com • www.am.pepperl-fuchs.com
149
2002 IS Catalog
Current/Voltage
Driver Current
Output Isolator
Model Number
Technical Data
Power Supply
Supply voltage
Nominal current current output
Nominal current voltage output
Terminals 7+, 8- or Power Rail
20-35 VDC
≤ 50 mA
≤ 20 mA
Input
Transmission range
Max. input current
Max. input voltage
Voltage drop
Input current
Terminals 9+, 10-, 11+
Current input
Voltage Input
0-20 mA
0-10 V
40 mA
N/A
35 V
12 VDC
≤ 4 V at 20 mA
N/A
N/A
≤10 µA to 50ºC w/ 10 V
Output
Current
Voltage
Load resistance
Terminals 1+, 20-20 mA
17 V at 20 mA
≤ 850 Ω
KFD2-CD-1.32
■ Current or voltage input options
■ 20-30 VAC power supply
■ 3-way isolation
The KFD2-CD-1.32 provides three-way
isolation and is used for driving I/P converters,
electrically operated valves and positioners.
The KFD2-CD-1.32 is available in several
versions.
CURRENT INPUT OPTION
Signal Conditioners
Current flowing into terminals 10 and 11(9)
passes through resistor Internal Load,
generating a voltage that is transferred to the
DC/DC converter. A current limit circuit in line
with terminal 9 protects Rm from damage. The
maximum voltage drop across the input is only
4 V at 20 mA, allowing the connection of
several KFD2-CD-1.32 input circuits in series.
Transfer Characteristics
Calibrated accuracy @ 20ºC
Temperature drift per ºC
Response time
Galvanic isolation
±0.01% inc. nonlinearity and hysteresis
±0.01%
< 10 ms
Isolation per EN50178
Isolation voltage 253 Veff
Mechanical
Housing
Material
Style
Dimensions (mm)
Weight
Protection (IEC)
Makrolon
KF Housing (see page 387)
115 x 20 x 100 mm
100 g (3.5 oz.)
IP20
Operating Temperature
-20ºC to +60ºC (-4ºF to +140ºF)
VOLTAGE INPUT OPTION
Voltage within the specified input range is
transferred to terminals 9 and 10 via an
amplifier and a DC/DC converter. A voltage
limiter circuit protects the amplifier from
incorrect input switching and overvoltage, but
will draw current through a 50 mA fuse during
operation.
Note: For information about programming, refer to page 209 or to our
website at www.am.pepperl-fuchs.com
Connection Diagram
CURRENT OUTPUT OPTION
Voltage transferred across the DC/DC
converter provides a proportional current at
terminals 1 and 2. For all supply voltages, there
is a minimum of 17 V at 20 mA to drive loads
of up to 850 Ω.
KFD2-CD-1.32
KFD2-CD-1.32-2
KFD2-CD-1.32-8
(+) 9
(+) 9
(+) 11
(+) 9
(– ) 10
This unit is not intrinsically safe.
KFD2-CD-1.32: 0/4 to 20mA input / output
KFD2-CD-1.32-2: 0-20mA input / 4-20mA output
KFD2-CD-1.32-8: 0-10V input / 4-20mA output
150
(– ) 10
Input
(– ) 10
1 (+)
2 (– )
7 (+)
8 (– )
Pepperl+Fuchs® Inc. • Telephone (330) 486-0002 • FAX (330) 425-4607
E-mail: greenteam@us.pepperl-fuchs.com • www.am.pepperl-fuchs.com
Analog
Output
DC Power
Supply
2002 IS Catalog
Single Input/Dual
Output Transmitter/
Repeater Isolator
Technical Data
Power Supply
Nominal voltage
Power consumption
Terminals 14+, 15- or Power Rail
20-32 VDC
≈ 2.5 W
Input
Input signal
Available voltage
Input resistance
Terminals 1, 2, and 3
0-20 mA
≥ 16 V at 20 mA
≤ 85 Ω
Output
Output signal
Load
Terminals 7-, 8+; 10-, 11+
0-20 mA
0-550 Ω
Transfer Characteristics
Calibration accuracy
Temperature drift
Rise time
De-energized delay
Galvanic isolation, 3-way
≤ ±20 µA
≤ 20 ppm / ºC
20 µs with 4-20 mA stage
20 µs with 20-4 mA stage
Isolation per EN50178
Isolation Voltage 253 Veff
Model Number
KFD2-CR4-1.20
■ Single-channel input /
dual output
■ 20-30 VDC supply voltage
Mechanical
Housing
Material
Style
Dimensions (mm)
Weight
Protection (IEC)
Makrolon
KF housing (see page 387)
115 x 20 x 100 mm
100 g (3.5 oz.)
IP20
Operating Temperature
-20ºC to +60ºC (-4ºF to +140ºF)
■ Outputs isolated from each other
■ Power Rail Bus
■ 3-way isolation
The KFD2-CR4-1.20 is suited for the
connection of 2- and 3-wire transmitters.
It may also be employed as a repeater for
0-20 mA signals (current source).
Both outputs provide a 0-20 mA current
corresponding to the input signal.
Signal Conditioners
2-wire transmitters are connected to
terminals 1 and 3. The input for the signal
is terminal 3. The minimum available
voltage is 16V at 20 mA. Current sources
are connected to terminals 2 and 3.
The input, output and power supply are
galvanically isolated from each other.
Note: For information about programming, refer to page 209 or to our
website at www.am.pepperl-fuchs.com
This unit is not intrinsically safe.
Connection Diagram
KFD2-CR4-1.20
(+) 1
(+) 1
(+) 1
(– ) 2
(– ) 2
3
(– ) 2
7 (– )
8 (+)
11 (+)
14 (+)
3
3
Input
3
Output 1
10 (– )
15 (– )
Output 2
DC Power
Supply
Pepperl+Fuchs® Inc. • Telephone (330) 486-0002 • FAX (330) 425-4607
E-mail: greenteam@us.pepperl-fuchs.com • www.am.pepperl-fuchs.com
151
2002 IS Catalog
HART Transmitter
Power Supply
Isolator
Technical Data
Power Supply
Nominal voltage
Power consumption
Power Rail or terminals 14+, 1520-32 VDC
≈2.5 W
Input
Input signal
Available voltage at 20 mA
Terminals 1, 2, 3
0/4-20 mA
≥16 V
Output
Output signal
Ripple
Terminals 9+, 10-, 11+
4-20 mA / load 550 Ω
≤ 50 µArms
Transfer Characteristics
Calibrated accuracy
Temperature drift
Frequency range:
Input/Output:
Band width at 0.5 VppSignal
Output/Input:
Band width at 0.5 VppSignal
Galvanic isolation
Model Number
KFD2-STC4-1.20
■ Single channel input /dual output
■ HART compatible
■ 4-20mA current source output
■ 3-way isolation
SMART transmitter powers a 2-wire
SMART transmitter and isolates the analog
4-20 mA signal from the field to the control
room as two current sources.
Digital signals which can be modulated onto
the analog signal, can also be transmitted
bidirectionally.
≤ 20 µA
≤ 20 ppm / ºC
0 Hz to 7.5 kHz (-3 dB)
300 Hz to 7.5 kHz (-3 dB)
Isolation per EN 50178
Isolation voltage 253 Veff
Mechanical
Housing
Material
Style
Dimensions (mm)
Weight
Protection (IEC)
Makrolon
KF housing (see page 387)
107 x 20 x 115 mm
100 g (3.5 oz.)
IP20
Operating Temperature
-20ºC to +60ºC (-4ºF to +140ºF)
Signal Conditioners
The SMART transmitters are delivered with
the KF-STP-GN terminals. Connector jacks
are integrated in these terminals for the
connection of the handheld terminals.
This unit is not intrinsically safe.
Note: For information about programming, refer to page 209 or to our
website at www.am.pepperl-fuchs.com
Connection Diagram
KFD2-STC4-1.20
(– ) 2
(+) 1
SMART
Communicator
(+) 1
(+) 1
(– ) 2
(– ) 2
3
7 (– )
8 (+)
11 (+)
14 (+)
3
152
3
Input
3
Output 1
10 (– )
15 (– )
Pepperl+Fuchs® Inc. • Telephone (330) 486-0002 • FAX (330) 425-4607
E-mail: greenteam@us.pepperl-fuchs.com • www.am.pepperl-fuchs.com
Output 2
DC Power
Supply
2002 IS Catalog
Technical Data
Power Supply
Supply voltage
Power consumption
Inrush current
Terminals 11+, 12- or Power Rail
9-30 VDC
≤ 2.5 W, 1.5 W typical
≤ 300 mA
Input
Excitation current
Zero
Span
Terminals 1+, 2-, 3
< 2 mA
50% of full scale input
50% of full scale input
Output
Terminals 7-, 8+
Voltage output
0-5 V, 0-10 V
Impedance
> 10 Ω
Drive
≤ 10 mA
Current output
0-1 mA, 0-20 mA, 4-20 mA
Impedance
> 100 kΩ
0-1 mA
7.5 V, max. 7.5 kΩ
0/4-20 mA
12 V, max. 600 Ω
Accuracy (including linearity & hysteresis)
±0.01% typical, 0.2% max. of the max.
input range @ 25ºC, 0Ω lead resistance
Temperature drift
±0.015% of max. temperature range/ºC
Response time
≤ 500 ms, 250 ms typical
Isolation
3-way 1800 VDC
Mechanical
Housing
Material
Style
Dimensions (mm)
Weight
Protection (IEC)
Makrolon
KF housing (see page 387)
115 x 20 x 100 mm
100 g (3.5 oz.)
IP20
Operating Temperature
-20ºC to +60ºC (-4ºF to +140ºF)
Connection Diagram
Model Number
KFDX-RTD
■ Field selectable inputs/ outputs
■ Wide range of RTD inputs
■ 3-way isolation
■ Lead resistance compensation
The KFDX-RTD isolator interfaces 3-wire RTDs
(Pt100, Pt500, Pt1000, Cu10, Cu25 and
Cu100) to a process control system. This
isolator also effectively eliminates ground loops
with 1800 VDC isolation separating input,
output and power supply.
The input range can be configured in the field
for one of sixteen temperature ranges via DIP
switches. The output is linear to temperature,
configurable for five ranges: 0-5 V, 0-10 V, 01 mA, 0-20 mA or 4-20 mA.
Signal Conditioners
Note: For information about programming, refer to page 209 or to our
website at www.am.pepperl-fuchs.com
RTD Input
Current/Voltage
Output Isolator
Span and zero potentiometers provide 50%
adjustability of offset and span turndown for
each input range. To ensure accurate
temperature measurement, the KFDX-RTD
contains constant current circuitry which uses
the third lead of the RTD as a sense line for
lead resistance compensation.
The KFDX-RTD is equipped with three LEDs:
INPUT (green), TROUBLE (yellow) and CAL
(yellow). Upon power-up, the INPUT and CAL
LEDs will alternately flash for 10 seconds.
KFDX-RTD
This unit is not intrinsically safe.
(+) 1
8 (+)
(– ) 2
(R) 3
RTD Input
7 (– )
Analog
Output
11 (+)
12 (– )
DC Power
Supply
Pepperl+Fuchs® Inc. • Telephone (330) 486-0002 • FAX (330) 425-4607
E-mail: greenteam@us.pepperl-fuchs.com • www.am.pepperl-fuchs.com
153
2002 IS Catalog
Thermocouple
Input Isolator
Model Number
KFDX-TC
Technical Data
Power Supply
Supply voltage
Power consumption
Terminals 11+ and 12- or Power Rail
9-30 VDC (unregulated acceptable)
≤ 2.5 W, 1.5 W typical
Input
Maximum overload
Range
Impedance
Burnout detection
Zero
Span
Terminals 1, 2
± 10 VDC on input
selectable
≥ 1 MΩ
selectable up/downscale
50% of full scale input
50% of full scale input
Output
Voltage output
Line impedance
Drive
Current output
Impedance
0-1 mA
0/4-20 mA
Terminals 7-, 8+
0-5 V, 0-10 V
> 10 Ω
≤ 10 mA
0-1 mA, 0-20 mA, 4-20 mA
> 100 kΩ
7.5 V, max. 7.5 kΩ
12V, max. 600 Ω
■ Wide range of thermocouple types
■ Cold junction compensation (CJC)
Transfer characteristics
Temperature drift
Common mode rejection
Isolation
Response time
< ±0.04% of max. input temperature
per ºC change in ambient temperature
DC to 60 Hz: 120 dB
3-way, 1,800 VDC
≤ 750 ms, 400 ms typical
Mechanical
Housing
Material
Style
Dimensions (mm)
Weight
Protection (IEC)
Makrolon
KF housing (see page 387)
115 x 20 x 100 mm
100 g (3.5 oz.)
IP20
Operating Temperature
0ºC to +55ºC (+32ºF to +131ºF)
■ 24 VDC supply voltage
■ 3-way isolation
The KFDX-TC thermocouple input isolator
interfaces B, E, J, K, R, S and T type
thermocouples to a process control system.
It also effectively eliminates ground loops with
1,800 VDC isolation separating input, output
and power supply.
Signal Conditioners
The input range can be configured in the field
for one of 16 thermocouple temperature
ranges via DIP switches on the side of the
housing. The output is linear to temperature,
configurable for five ranges: 0-5 V, 0-10 V, 01 mA, 0-20 mA, or 4-20 mA.
Span and zero potentiometers on the top plate
provide 50% adjustability of offset and span
turn-down for each input range. The KFDXTC also features internal cold junction
compensation (CJC) and selectable
upscale /downscale thermocouple burnout
detection.
Note: For information about programming, refer to page 209
or to our website at www.am.pepperl-fuchs.com
Connection Diagram
The KFDX-TC is outfitted with three LEDs on
the front panel: INPUT (Green), TROUBLE
(Yellow), and CAL (Yellow). Upon power-up,
the INPUT and CAL LEDs alternately flash for
10 seconds.
This unit is not intrinsically safe.
KFDX-TC
(+) 1
8 (+)
(– ) 2
Thermocouple
Input
154
7 (– )
11 (+)
12 (– )
Analog
Output
DC Power
Supply
Pepperl+Fuchs® Inc. • Telephone (330) 486-0002 • FAX (330) 425-4607
E-mail: greenteam@us.pepperl-fuchs.com • www.am.pepperl-fuchs.com
2002 IS Catalog
Technical Data
Power Supply
Supply voltage
Power consumption
Terminals 11+, 12- or Power Rail
20-35 VDC
≈ 1.5 W
Input
Thermocouple
Lead resistance
Test current
Terminals 1-, 2-, 3+, 4+
B,E,J,K,L,N,R,S or T
≤ 50 Ω per lead
400 µA with RTDs
Output
Output current
Fault signal
Load
Terminals 7-, 8+
4-20 mA (20.5 mA at input signal exceeded)
Downscaled 2-4 mA, upscaled 20.522 mA
≤ 500 Ω
Transfer Characteristics
Calibrated accuracy
± (0.01% of value in ºC + 0.05% of
range + 0.1 ºC) (4-wire)
± (0.05% of value in ºC + 0.05% of
range + 1ºC) (inc. ± 0.8ºC error for CJC)
≤ 430 ms
Isolation per EN50178
Isolation voltage 253 Veff
Thermocouple
Rise time
Galvanic isolation
Universal
Temperatur e
Input Isolator
Model Number
KFD2-UT-1
■ Universal temperature inputs
■ Current output
■ Programming & calibration via PC
■ 3-way isolation
Mechanical
Housing
Material
Style
Dimensions (mm)
Weight
Protection (IEC)
Makrolon
KF housing (see page 387)
115 x 20 x 118
100 g (3.5 oz.)
IP20
Operating Temperature
+4ºC to +60ºC (+40ºF to +140ºF)
■ CJC for thermocouple and lead
resistance compensation for RTDs
The KFD2-UT-1 is designed for connection to
RTDs (Pt100 and Ni100) or thermocouples (B, E,
J, K, L, N, R, S and T), and provides three-way
isolation. The inputs, outputs and power supply
are galvanically isolated.
Signal Conditioners
This device also features internal/external cold
junction compensation, burnout monitoring for
thermocouples and burnout and short circuit
monitoring for RTDs.
All settings are programmed and calibrated
through a serial interface to PC (on-line
programming--see the P+F web site for more
information).
Note: For information about programming,
refer to our website at www.am.pepperl-fuchs.com
A signal at terminals 2 and 3 is transmitted across
the isolator and converted to an equivalent output
at terminals 7 and 8. Terminal 7 has the same
polarity as terminal 2.
Connection Diagram
KFD2-UT-1
(+) 4
CJC
Type K-CJC-GN
(+) 3
(+) 3
(+) 3
7 (+)
4
8 (– )
Analog
Output
3
(– ) 2
2
(– ) 2
(– ) 2
(– ) 2
11 (+)
1
12 (– )
(+) 1
(– ) 1
(– ) 1
DC
Power
Supply
All parameters are programmable through a KADP1 cable (sold separately) that provides the
connection between the programming socket of
the KFD2-UT and the RS232 PC interface.
Accessories include removable terminals with
internal cold junction compensation (K-CJC) and
a K-SK programming software kit. The K-ADP1
and K-SK are required unless the KFD2-UT is
configured by P+F.
Input
This unit is not intrinsically safe.
PC
Pepperl+Fuchs® Inc. • Telephone (330) 486-0002 • FAX (330) 425-4607
E-mail: greenteam@us.pepperl-fuchs.com • www.am.pepperl-fuchs.com
155
2002 IS Catalog
Universal
Temperature
Input Isolator
Model Number
KFD2-UT-1-1
■ Universal temperature inputs
■ Voltage output
Technical Data
Power Supply
Supply voltage
Power consumption
Terminals 11+, 12- or Power Rail
20-35 VDC
≈ 1.5 W
Input
Thermocouple
Lead resistance
Test current
Terminals 1-, 2-, 3+, 4+
B,E,J,K,L,N,R,S or T
≤ 50 Ω per lead
400 µA with RTDs
Output
Output voltage
Fault signal
Load
Terminals 7-, 8+
1-5 V; (5.125 V input signal exceeded)
Downscaled 0-5 V, upscaled 5.025 - 5.12 V
≤ 10 KΩ
Transfer Characteristics
Calibrated accuracy
± (0.01% of value in ºC + 0.05% of
range + 0.1 ºC) (4-wire)
± (0.05% of value in ºC + 0.05% of
range + 1ºC) (inc. ± 0.8ºC error for CJC)
≤ 430 ms
Isolation per EN50178
Isolation voltage 253 Veff
Thermocouple
Rise time
Galvanic isolation
■ Programming & calibration via PC
■ 3-way isolation
■ CJC for thermocouples and lead
resistance compensation for RTDs
The KFD2-UT-1-1 is designed for connection to
RTDs (Pt100 and Ni100) or thermocouples (B,
E, J, K, L, N, R, S and T), and provides threeway isolation. The inputs, outputs and power
supply are galvanically isolated.
Mechanical
Housing
Material
Style
Dimensions (mm)
Weight
Protection (IEC)
Makrolon
KF housing (see page 387)
115 x 20 x 118
100 g (3.5 oz.)
IP20
Operating Temperature
+4ºC to +60ºC (+40ºF to +140ºF)
Signal Conditioners
This device also features internal/external cold
junction compensation, burnout monitoring for
thermocouples and burnout and short circuit
monitoring for RTDs.
All settings are programmed and calibrated
through a serial interface to PC (on-line
programming).
A signal at terminals 2 and 3 is transmitted across
the isolator and converted to an equivalent
output at terminals 7 and 8. Terminal 7 has the
same polarity as terminal 2.
All parameters are programmable through a KADP1 cable (sold separately) that provides the
connection between the programming socket
of the KFD2-UT and the RS232 PC interface.
Accessories include removable terminals with
internal cold junction compensation (K-CJC) and
a K-SK programming software kit. The K-ADP1
and K-SK are required unless the KFD2-UT-1-1
is configured by P+F.
Note: For information about programming,
refer to our website at www.am.pepperl-fuchs.com
Connection Diagram
KFD2-UT-1-1
(+) 4
CJC
Type K-CJC-GN
(+) 3
(+) 3
(+) 3
7 (+)
4
8 (– )
(– ) 2
2
(– ) 2
(– ) 2
(– ) 2
11 (+)
1
12 (– )
(+) 1
(– ) 1
(– ) 1
This unit is not intrinsically safe.
PC
156
Analog
Output
3
Pepperl+Fuchs® Inc. • Telephone (330) 486-0002 • FAX (330) 425-4607
E-mail: greenteam@us.pepperl-fuchs.com • www.am.pepperl-fuchs.com
DC
Power
Supply
2002 IS Catalog
Technical Data
Power Supply
Supply voltage
Power consumption
Terminals 11+, 12- or Power Rail
9-30 VDC
≤ 1.5 W, 1 W typical
Input
Input voltage / current
Overload
Zero
Span
Terminals 1+, 2100 mV to 250 V / 10-100 mA
≤ 300 VAC / 170 mA AC (60 Vp for
current inputs)
≥ 100 kΩ (voltage inputs) / 20 Ω
(current inputs)
50% of full scale input
50% of full scale input
Output
Voltage
Impedance
Drive
Current
Impedance
0-1 mA
0/4-20 mA
Terminals 7-, 8+
0-5 V, 0-10 V
< 10 kΩ
≤ 10 mA
0-1 mA, 4-20 mA, 0-20 mA
> 100 kΩ
7.5 V, max. 7.5 kΩ
12 V, max. 600 Ω
Impedance
AC Current/Voltage
Input Current/Voltage
Output Isolator
Model Number
KFDX-AC
■ Wide range of inputs/outputs
■ Field selectable input/output
Transfer Characteristics
Range
Stability
Common mode rejection
Isolation
Response time
± 0.1% of full scale: 0.5% max.
± 0.025% of full scale/ºC for zero and span
DC to 60 Hz: 120 dB
3-way 1,800 VDC
≤ 400 ms, 200 ms typical
Mechanical
Housing
Material
Style
Dimensions (mm)
Weight
Protection (IEC)
Makrolon
KF housing (see page 387)
115 x 20 x 118
100 g (3.5 oz.)
IP20
Operating Temperature
0ºC to +55ºC (+32ºF to +131ºF)
■ 3-way isolation
The KFDX-AC accepts an AC voltage/current
input and provides a fully isolated proportional
DC current or voltage output. In order to
eliminate ground loops, the I/O channel is
optically isolated to 1,800 VDC and
transformer isolated from the power supply.
Note: For information about programming,
refer to our website at www.am.pepperl-fuchs.com
Signal Conditioners
The input can be configured in the field for
one of twelve voltage ranges from 100 mV to
250 V and 4 current ranges from 10 mA to
100 mA. Output is linear to the input,
configurable for five ranges: 0-5 V, 0-10 V, 01 mA, 0-20 mA, or 4-20 mA.
The KFDX-AC is outfitted with a green dual
function power/signal status LED. When the
unit is powered, the LED is illuminated. When
the input signal is over 110% of the full scale
range, the LED flashes at 8 Hz.
This unit is not intrinsically safe.
Connection Diagram
KFDX-AC
AC Input
Current/Voltage
(+) 1
8 (+)
(– ) 2
7 (– )
11 (+)
12 (– )
Analog
Output
DC Power
Supply
Pepperl+Fuchs® Inc. • Telephone (330) 486-0002 • FAX (330) 425-4607
E-mail: greenteam@us.pepperl-fuchs.com • www.am.pepperl-fuchs.com
157
2002 IS Catalog
Frequency Input
Current/Voltage
Output Isolator
Model Number
KFDX-HZ
■ Span from 2 Hz to 10,000 Hz
■ Easy push-button calibration
■ 3-way isolation
The KFDX-HZ accepts a frequency input
and provides a fully isolated proportional
DC current or voltage output. This isolator
also effectively eliminates ground loops
with 1,800 VDC isolation separating input,
output and power supply.
Signal Conditioners
The input range can be configured in the
field for any frequency span from 2 Hz to
10,000 Hz via DIP switches on the side of
the housing. The output is configurable for
five ranges: 0-5 V, 0-10 V, 0-1 mA, 0-20
mA, or 4-20 mA.
The KFDX-HZ is simply configured via
push-buttons rather than a zero and span
potentiometer. Set the input frequency
span by applying the maximum and
minmum frequencies to the system and
pressing the CAL button while the INPUT
LED is lit.
The KFDX-HZ is outfitted with three LEDs:
LEVEL (Green), INPUT (Yellow), and
OUTPUT (Red).
Technical Data
Power Supply
Supply voltage
Inrush current
Power consumption
Terminals 11+, 12- or Power Rail
9-30 VDC
will not exceed stead state current
≤ 2.5 W, 1.4 W typical
Input
Range
Input values
Overload
Impedance
Terminals 1+, 22 Hz to 10 KHz, pulse
150 mVp to 150 Vrms
≤ 180 Vrms
≥ 10 kΩ
Output
Voltage output
Impedance
Drive
Current output
Impedance
0-1 mA
0/4-20 mA
Terminals 7-, 8+
0-5 V, 0-10 V
> 1 kΩ
≤ 10 mA
0-1 mA, 0-20 mA, 4-20 mA
≥ 100 kΩ
7.5 V, max. 7.5 kΩ
12 V, max. 600 Ω
Transfer Characteristics
Accuracy
Temperature drift
Power
Common mode isolation
Isolation
Response time
± 0.1% of selected range @ 25ºC
±0.025% / ºC max. of selected range
< ±0.01% of max. temp. range/% of
power change
DC to 60 Hz: 100 dB
3-way 1,800 VDC
≤ 500 ms, 250 ms typical
Mechanical
Housing
Material
Style
Dimensions (mm)
Weight
Protection (IEC)
Makrolon
KF housing (see page 387)
115 x 20 x 118
100 g (3.5 oz.)
IP20
Operating Temperature
0ºC to +55ºC (+32ºF to +131ºF)
Note: For information about programming,
refer to our website at www.am.pepperl-fuchs.com
Connection Diagram
KFDX-HZ
This unit is not intrinsically safe.
Frequency
Input
(+) 1
8 (+)
(– ) 2
7 (– )
11 (+)
12 (– )
158
Analog
Output
DC Power
Supply
Pepperl+Fuchs® Inc. • Telephone (330) 486-0002 • FAX (330) 425-4607
E-mail: greenteam@us.pepperl-fuchs.com • www.am.pepperl-fuchs.com
2002 IS Catalog
Rotational Speed
Limit Alarm
Technical Data
Power Supply
Nominal voltage
Power consumption
Terminals 23, 24
120 VAC
2 VA
Input
Connection type
Terminals 1+, 32-wire sensor: terminals 1+, 33-wire sensor: terminals 1+, 2- and 3
start-up override terminals: 13+, 14Sensor
4.7 kΩ
≥ 50 µs / ≥ 50 µs
22 V
max. 30 mA; limitation 40 mA
breakage I ≤ 0.15 mA
short circuit I > 6.5 mA
Input I
Input resistance
Input pulse length/interval
Voltage
Current
Lead monitoring
Input II
start-up override: 1-1000 s, in 1s steps
Quiescent voltage/short circuit current:
18 V / 5 mA
Active / passive
I > 4 mA (> 100 ms) / I < 1.5 mA
Outputs
Relay output 1 (SPDT)
Relay output 2 (SPDT)
Contact load
Mechanical life
Energizing / de-energizing
Terminals 10, 11, 12
Terminals 16, 17, 18
250 VAC / 2 A / cos ø > 0.7; 40 VDC / 2 A
Model Number
KFA5-DWB-1.D
■ Operating range 0.06-720,000
RPM (0.001-12,000 Hz)
■ Relay outputs
≥ 5 x 107 operations
≈ 20 ms / ≈ 20 ms
■ Push-button programmable
Transfer Characteristics
Frequency range
0.001-12,000 Hz
Mechanical
Housing
Material
Style
Dimensions (mm)
Weight
Protection (IEC)
■ Lead breakage (LB) and short
circuit (SC) monitoring
Makrolon
KF housing (see page 387)
118 x 40 x 115
300 g (10.6 oz.)
IP20
Operating Temperature
-20ºC to +60ºC (-4ºF to +140ºF)
■ Start-up override
■ LCD display
Note: For information about programming,
refer to our website at www.am.pepperl-fuchs.com
Signal Conditioners
The KFA5-DWB-1.D monitors for an
overspeed or underspeed condition by
comparing the input frequency to the user
programmed reference frequency. The
reference frequency is easily programmed
by the use of a keypad located on the front
of the unit. An overspeed or underspeed
condition is signaled via the relay outputs.
Lead breakage and short circuits in the
sensor are indicated by a red LED. The
start-up override feature sets relay outputs
to default conditions programmed by the
user, for up to 1,000 seconds.
This unit is not intrinsically safe.
Connection Diagram
KFA5-DWB-1.D
Input I
Input II
(+) 1
(+) 1
(+) 1
(+) 1
(+) 1 (+) 1
11
10
12
17
R2
R1
2
2
(– ) 3
(– ) 3
R1
16
18
13 (+)
14 (– )
(– ) 3
LB/SC
Output 1
(– ) 3
LB/SC
(– ) 3
LB
(– ) 3
23
24
Output 2
Start Up
Override
Supply
120 VAC
Pepperl+Fuchs® Inc. • Telephone (330) 486-0002 • FAX (330) 425-4607
E-mail: greenteam@us.pepperl-fuchs.com • www.am.pepperl-fuchs.com
159
2002 IS Catalog
Rotational Speed
Limit Alarm
Technical Data
Power Supply
Nominal voltage
Power consumption
Terminals 23, 24
240 VAC
2 VA
Input
Connection type
Terminals 1+, 32-wire sensor: terminals 1+, 33-wire sensor: terminals 1+, 2- and 3
start-up override terminals: 13+, 14Sensor
4.7 kΩ
≥ 50 µs / ≥ 50 µs
22 V
max. 30 mA; limitation 40 mA
breakage I ≤ 0.15 mA
short circuit I > 6.5 mA
Input I
Input resistance
Input pulse length/interval
Voltage
Current
Lead monitoring
Input II
start-up override: 1-1000 s, in 1s steps
Quiescent voltage/short circuit current:
18 V / 5 mA
Active / passive
I > 4 mA (> 100 ms) / I < 1.5 mA
Model Number
KFA6-DWB-1.D
Outputs
Relay output 1 (SPDT)
Relay output 2 (SPDT)
Contact load
Mechanical life
Energizing / de-energizing
■ Operating range 0.06-720,000
RPM (0.001-12,000 kHz)
■ Relay outputs
■ Push-button programmable
■ Start-up override
■ LCD display
■ Lead breakage (LB) and short
circuit (SC) monitoring
Signal Conditioners
The KFA6-DWB-1.D monitors for an
overspeed or underspeed condition by
comparing the input frequency to the user
programmed reference frequency. The
reference frequency is easily programmed
by the use of a keypad located on the front
of the unit. An overspeed or underspeed
condition is signaled via the relay outputs.
Lead breakage and short circuits in the
sensor are indicated by a red LED. The
start-up override feature sets relay outputs
to default conditions programmed by the
user, for up to 1,000 seconds.
Terminals 10, 11, 12
Terminals 16, 17, 18
250 VAC / 2 A / cos ø > 0.7; 40 VDC / 2 A
≥ 5 x 107 operations
≈ 20 ms / ≈ 20 ms
Transfer Characteristics
Frequency range
0.001-12,000 Hz
Mechanical
Housing
Material
Style
Dimensions (mm)
Weight
Protection (IEC)
Makrolon
KF housing (see page 387)
118 x 40 x 115
300 g (10.6 oz.)
IP20
Operating Temperature
-20ºC to +60ºC (-4ºF to +140ºF)
Note: For information about programming,
refer to our website at www.am.pepperl-fuchs.com
This unit is not intrinsically safe.
Connection Diagram
KFA6-DWB-1.D
(+) 1
(+) 1
(+) 1
(+) 1
R2
(+) 1 (+) 1
2
R1
2
R1
(– ) 3
LB/SC
160
(– ) 3
LB/SC
(– ) 3
LB
(– ) 3
(– ) 3
(– ) 3
Signal Processor
Input I
Input II
11
10
12
Output 1
17
16
18
13 (+)
14 (– )
23
24
Pepperl+Fuchs® Inc. • Telephone (330) 486-0002 • FAX (330) 425-4607
E-mail: greenteam@us.pepperl-fuchs.com • www.am.pepperl-fuchs.com
Output 2
Start Up
Override
Supply
240 VAC
2002 IS Catalog
Rotational Speed
Limit Alarm
Technical Data
Power Supply
Nominal voltage
Power consumption
Terminals 23, 24
20-30 VDC
2W
Input
Connection type
Terminals 1+, 32-wire sensor: terminals 1+, 33-wire sensor: terminals 1+, 2- and 3
start-up override terminals: 13+, 14Sensor
4.7 kΩ
≥ 50 µs / ≥ 50 µs
22 V
max. 30 mA; limitation 40 mA
breakage I ≤ 0.15 mA
short circuit I > 6.5 mA
Input I
Input resistance
Input pulse length/interval
Voltage
Current
Lead monitoring
Input II
start-up override: 1-1000 s, in 1s steps
Quiescent voltage/short circuit current:
18 V / 5 mA
Active / passive
I > 4 mA (> 100 ms) / I < 1.5 mA
Outputs
Relay output 1 (SPDT)
Relay output 2 (SPDT)
Contact load
Mechanical life
Energizing / de-energizing
Model Number
KFD2-DWB-1.D
■ Operating range 0.06-720,000
RPM (0.001-12,000 Hz)
■ Relay outputs
Terminals 10, 11, 12
Terminals 16, 17, 18
250 VAC / 2 A / cos ø > 0.7; 40 VDC / 2 A
≥ 5 x 107 operations
≈ 20 ms / ≈ 20 ms
■ Push-button programmable
■ Collective error messaging
Transfer Characteristics
Frequency range
0.001-12,000 Hz
Mechanical
Housing
Material
Style
Dimensions (mm)
Weight
Protection (IEC)
Makrolon
KF housing (see page 387)
118 x 40 x 115
300 g (10.6 oz.)
IP20
Operating Temperature
-20ºC to +60ºC (-4ºF to +140ºF)
■ LCD display
■ Lead breakage (LB) and short
circuit (SC) monitoring
Note: For information about programming,
refer to our website at www.am.pepperl-fuchs.com
Connection Diagram
Signal Conditioners
The KFD2-DWB-1.D monitors for
overspeed or underspeed conditions by
comparing the input frequency to the userprogrammed reference frequency. The
reference frequency is easily programmed
by push buttons mounted on the front
panel. An overspeed or underspeed
condition is signaled via the relay outputs.
Lead breakage and short circuits in the
sensor are indicated by a red LED and
through the collective error output via
Power Rail. The start-up override feature
sets relay outputs to default conditions
programmed by the user, for up to 1,000
seconds.
This unit is not intrinsically safe.
KFD2-DWB-1.D
(+) 1
(+) 1
(+) 1
(+) 1
R2
(+) 1 (+) 1
2
R1
2
R1
(– ) 3
LB/SC
(– ) 3
LB/SC
(– ) 3
(– ) 3
(– ) 3
Signal Processor
Input I
Input II
(– ) 3
LB
11
10
12
Output 1
17
16
18
Output 2
13 (+)
14 (– )
Start Up
Override
23 (+)
Supply
24 VDC
24 (– )
Collective Error Messaging
Pepperl+Fuchs® Inc. • Telephone (330) 486-0002 • FAX (330) 425-4607
E-mail: greenteam@us.pepperl-fuchs.com • www.am.pepperl-fuchs.com
161
2002 IS Catalog
Universal Frequency
Converter
Technical Data
Power Supply
Nominal voltage
Power consumption
Terminals 23, 24
20-90 VDC; 40-250 VAC
2.2 W; 3 VA
Input
Connection type
Model Number
KFU8-UFC-1
■ 24 VDC / 120 VAC / 240 VAC supply
■ Operating range 0.06-720,000 RPM
(0.001-12,000 kHz)
■ Analog and digital outputs
■ PC programmable
Signal Conditioners
This universal frequency converter converts
a digital input signal into an analog output
signal for connection to standard current
input devices. A passive transistor output
isolates and transfers the digital signal.
Two relay outputs can be programmed to
actuate at desired frequencies. The unit is
programmable with a PC and the
PACTware configuration software.
A debounce filter eliminates extraneous
signals from relay bounce.
Lead breakage and short circuits in the
sensor are indicated by a red LED.
2-wire sensor: terminals 1+, 33-wire sensor: terminals 1+, 2- and 3
start-up override terminals: 13+, 14Input I
Sensor
Input resistance
4.7 kΩ
Input pulse length/interval
≥ 50 µs / ≥ 50 µs
Voltage
22 V
Current (Im)
max. 30 mA; limitation 40 mA
Lead monitoring
breakage I ≤ 0.15 mA
short circuit I > 6.5 mA
Input II
start-up override: 1-1000 s, in 1s steps
Quiescent voltage/short circuit current:
18 V / 5 mA
Active / passive
I > 4 mA (> 100 ms) / I < 1.5 mA
Outputs
Relay output 1 (SPDT)
Relay output 2 (SPDT)
Contact load
Mechanical life
Energizing / de-energizing delay
Output 3 (passive transistor)
Nominal current
Logic 1
Logic 0
Output 4 (current)
Open circuit voltage
Output current
Error signal
Load
Terminals 10, 11 and 12
Terminals 16, 17 and 18
250 VAC / 2 A / cos ø ≥ 0.7; 40 VDC / 2A
≥ 5 x 107 operations
≈ 20 ms / ≈ 20 ms
Terminals 19+ and 2050 mA, short circuit-protected
voltage drop < 2.5 V
output switched off (leakage < 10 µA)
Terminals 8+ and 7≤ 24 VDC
0-20 mA or 4-20 mA
Downscale < 3.6 mA, upscale ≥ 22 mA
≤ 650 Ω
Mechanical
Housing
387)
Dimensions (mm)
Weight
Makrolon KF housing (see page
118 x 40 x 115
300 g (10.6 oz.)
Operating Temperature
-20ºC to +60ºC (-4ºF to +140ºF)
This unit is not intrinsically safe.
Note: For information about programming,
refer to our website at www.am.pepperl-fuchs.com
Connection Diagram
KFU8-UFC-1
Input I
Input II
(+) 1
(+) 1
(+) 1
(+) 1
R2
(+) 1 (+) 1
2
R1
2
R1
(– ) 3
LB/SC
(– ) 3
LB/SC
(– ) 3
LB
(– ) 3
(– ) 3
(– ) 3
RxD
TxD
GND
Programming
Jack
11
10
12
17
16
18
19 (+)
20 (– )
8 (+)
7 (– )
13
14
23
24
162
Pepperl+Fuchs® Inc. • Telephone (330) 486-0002 • FAX (330) 425-4607
E-mail: greenteam@us.pepperl-fuchs.com • www.am.pepperl-fuchs.com
Output 1
Output 2
Output 3
Output 4
0/4-20 mA
Start Up
Override
Supply
24 VDC
120 VAC
240 VAC
2002 IS Catalog
Universal Frequency
Converter with Display
Technical Data
Power Supply
Nominal voltage
Power consumption
Terminals 23, 24
20-30 VDC
2.2 W
Input
Connection type
2-wire sensor: terminals 1+, 33-wire sensor: terminals 1+, 2- and 3
start-up override terminals: 13+, 14Input I
Sensor
Input resistance
4.7 kΩ
Input pulse length/interval
≥ 50 µs / ≥ 50 µs
Voltage
22 V
max. 30 mA; limitation 40 mA
Current (Im)
Lead monitoring
breakage I ≤ 0.15 mA
short circuit I > 6.5 mA
Input II
start-up override: 1-1000 s, in 1s steps
Quiescent voltage/short circuit current:
18 V / 5 mA
Active / passive
I > 4 mA (> 100 ms) / I < 1.5 mA
Terminals 10, 11 and 12
Terminals 16, 17 and 18
250 VAC / 2 A / cos ø ≥ 0.7; 40 VDC / 2A
≥ 5 x 107 operations
≈ 20 ms / ≈ 20 ms
Terminals 19+ and 2050 mA, short circuit-protected
voltage drop < 2.5 V
output switched off (leakage < 10 µA)
Terminals 8+ and 7≤ 24 VDC
0-20 mA or 4-20 mA
Downscale < 3.6 mA, upscale ≥ 22 mA
≤ 650 Ω
Mechanical
Housing
Dimensions (mm)
Weight
Makrolon KF housing (see page 387)
118 x 40 x 115
300 g (10.6 oz.)
Operating Temperature
-20ºC to +60ºC (-4ºF to +140ºF)
KFD2-UFC-1.D
■ 24 VDC supply
■ Operating range 0.06-720,000
RPM (0.001-12,000 kHz)
■ Analog and digital outputs
■ PC and push-button
programmable
■ LCD display
This universal frequency converter converts
a digital input signal into an analog output
signal for connection to standard current
input devices. A passive transistor output
isolates and transfers the digital signal. Two
relay outputs can be programmed to
actuate at desired frequencies. The units is
programmable with a PC and the
PACTware configuration software. A
debounce circuit eliminates extraneous
signals from relay bounce.
Signal Conditioners
Outputs
Relay output 1 (SPDT)
Relay output 2 (SPDT)
Contact load
Mechanical life
Energizing / de-energizing delay
Output 3 (passive transistor)
Nominal current
Logic 1
Logic 0
Output 4 (current)
Open circuit voltage
Output current
Error signal
Load
Model Number
Lead breakage and short circuits in the
sensor are indicated by a red LED and
through the collective error output via
Power Rail.
Note: For information about programming,
refer to our website at www.am.pepperl-fuchs.com
Connection Diagram
This unit is not intrinsically safe.
(+) 1
KFD2-UFC-1.D
Input I
Input II
(+) 1
(+) 1
(+) 1
R2
(+) 1 (+) 1
2
R1
RxD
TxD
GND
Programming
Jack
2
R1
(– ) 3
LB/SC
(– ) 3
LB/SC
(– ) 3
(– ) 3
(– ) 3
(– ) 3
LB
11
10
12
17
16
18
19 (+)
20 (– )
8 (+)
7 (– )
13 (+)
14 (– )
23 (+)
24 (– )
Output 1
Output 2
Output 3
Output 4
0/4-20 mA
Start Up
Override
Supply
24 VDC
Collective Error Messaging
Pepperl+Fuchs® Inc. • Telephone (330) 486-0002 • FAX (330) 425-4607
E-mail: greenteam@us.pepperl-fuchs.com • www.am.pepperl-fuchs.com
163
2002 IS Catalog
Universal Frequency
Converter Isolator
Technical Data
Power Supply
Nominal voltage
Power consumption
Terminals 23, 24 or Power Rail
20-30 VDC
2.2 W
Input
Connection type
Model Number
KFD2-UFC-1
■ 24 VDC supply
■ Operating range 0.06-720,000
RPM (0.001-12,000 kHz)
■ Analog and digital outputs
■ PC programmable
Signal Conditioners
This universal frequency converter converts
a digital input signal into an analog output
signal for connection to standard current
input devices. A passive transistor output
isolates and transfers the digital signal.
Two relay outputs can be programmed to
actuate at desired frequencies. The unit is
programmable with a PC and the
PACTware configuration software.
A debounce filter eliminates extraneous
signals from relay bounce.
Lead breakage and short circuits in the
sensor are indicated by a red LED and
through the collective error output via
Power Rail.
This unit is not intrinsically safe.
2-wire sensor: terminals 1+, 33-wire sensor: terminals 1+, 2- and 3
start-up override terminals: 13+, 14Input I
Sensor
Input resistance
4.7 kΩ
Input pulse length/interval
≥ 50 µs / ≥ 50 µs
Voltage
22 V
max. 30 mA; limitation 40 mA
Current (Im)
Lead monitoring
breakage I ≤ 0.15 mA
short circuit I > 6.5 mA
Input II
start-up override: 1-1000 s, in 1s steps
Quiescent voltage/short circuit current:
18 V / 5 mA
Active / passive
I > 4 mA (> 100 ms) / I < 1.5 mA
Outputs
Relay output 1 (SPDT)
Relay output 2 (SPDT)
Contact load
Mechanical life
Energizing / de-energizing delay
Output 3 (passive transistor)
Nominal current
Logic 1
Logic 0
Output 4 (current)
Open circuit voltage
Output current
Error signal
Load
Terminals 10, 11 and 12
Terminals 16, 17 and 18
250 VAC / 2 A / cos ø ≥ 0.7; 40 VDC / 2A
≥ 5 x 107 operations
≈ 20 ms / ≈ 20 ms
Terminals 19+ and 2050 mA, short circuit-protected
voltage drop < 2.5 V
output switched off (leakage < 10 µA)
Terminals 8+ and 7≤ 24 VDC
0-20 mA or 4-20 mA
Downscale < 3.6 mA, upscale ≥ 22 mA
≤ 650 Ω
Mechanical
Housing
Dimensions (mm)
Weight
Makrolon KF housing (see page 387)
118 x 40 x 115
300 g (10.6 oz.)
Operating Temperature
-20ºC to +60ºC (-4ºF to +140ºF)
Note: For information about programming,
refer to our website at www.am.pepperl-fuchs.com
Connection Diagram
(+) 1
KFD2-UFC-1
Input I
Input II
(+) 1
(+) 1
(+) 1
R2
(+) 1 (+) 1
2
R1
RxD
TxD
GND
Programming
Jack
2
R1
(– ) 3
LB/SC
(– ) 3
LB/SC
(– ) 3
(– ) 3
(– ) 3
(– ) 3
LB
11
10
12
17
16
18
19
20
8
7
13
14
23
24
Collective Error Messaging
164
Pepperl+Fuchs® Inc. • Telephone (330) 486-0002 • FAX (330) 425-4607
E-mail: greenteam@us.pepperl-fuchs.com • www.am.pepperl-fuchs.com
Output 1
Output 2
Output 3
Output 4
0/4-20 mA
Start Up
Override
Supply
24 VDC
2002 IS Catalog
Technical Data
Power Supply
Nominal voltage
Power consumption
Terminals 23, 24
20-90 VDC; 40-250 VAC
2.2 W; 3 VA
Universal Frequency
Converter Isolator
with Display
Input
Connection type
2-wire sensor: terminals 1+, 33-wire sensor: terminals 1+, 2- and 3
start-up override terminals: 13+, 14Input I
Sensor
Input resistance
4.7 kΩ
Input pulse length/interval
≥ 50 µs / ≥ 50 µs
Voltage
22 V
max. 30 mA; limitation 40 mA
Current (Im)
Lead monitoring
breakage I ≤ 0.15 mA
short circuit I > 6.5 mA
Input II
start-up override: 1-1000 s, in 1s steps
Quiescent voltage/short circuit current:
18 V / 5 mA
Active / passive
I > 4 mA (> 100 ms) / I < 1.5 mA
Terminals 10, 11 and 12
Terminals 16, 17 and 18
250 VAC / 2 A / cos ø ≥ 0.7; 40 VDC / 2A
≥ 5 x 107 operations
≈ 20 ms / ≈ 20 ms
Terminals 19+ and 2050 mA, short circuit-protected
voltage drop < 2.5 V
output switched off (leakage < 10 µA)
Terminals 8+ and 7≤ 24 VDC
0-20 mA or 4-20 mA
Downscale < 3.6 mA, upscale ≥ 22 mA
≤ 650 Ω
Mechanical
Housing
Dimensions (mm)
Weight
118 x 40 x 115
300 g (10.6 oz.)
Operating Temperature
-20ºC to +60ºC (-4ºF to +140ºF)
Makrolon KF housing (see page 387)
Note: For information about programming,
refer to our website at www.am.pepperl-fuchs.com
KFU8-UFC-1.D
■ 24 VDC / 120 VAC / 240 VAC supply
■ Operating range 0.06-720,000 RPM
(0.001-12,000 kHz)
■ Analog and digital outputs
■ PC and push-button
programmable
■ LCD display
This universal frequency converter converts
a digital input signal into an analog output
signal for connection to standard current
input devices. A passive transistor output
isolates and transfers the digital signal. Two
relay outputs can be programmed to
actuate at desired frequencies. The units is
programmable with a PC and the
PACTware configuration software. A
debounce circuit eliminates extraneous
signals from relay bounce.
Signal Conditioners
Outputs
Relay output 1 (SPDT)
Relay output 2 (SPDT)
Contact load
Mechanical life
Energizing / de-energizing delay
Output 3 (passive transistor)
Nominal current
Logic 1
Logic 0
Output 4 (current)
Open circuit voltage
Output current
Error signal
Load
Model Number
Lead breakage and short circuits in the
sensor are indicated by a red LED.
This unit is not intrinsically safe.
Connection Diagram
KFU8-UFC-1.D
Input I
Input II
(+) 1
(+) 1
(+) 1
(+) 1
R2
R1
(+) 1 (+) 1
2
2
(– ) 3
(– ) 3
R1
(– ) 3
LB/SC
(– ) 3
LB/SC
(– ) 3
LB
(– ) 3
RxD
TxD
GND
Programming
Jack
11
10
Output 1
12
17
Output 2
16
18
19 (+)
Output 3
20 (–)
Output 4
8 (+)
0/4-20 mA
7 (–)
Start Up
13 (+)
Override
14 (– )
23
Supply
24 VDC
24
120 VAC
240 VAC
Pepperl+Fuchs® Inc. • Telephone (330) 486-0002 • FAX (330) 425-4607
E-mail: greenteam@us.pepperl-fuchs.com • www.am.pepperl-fuchs.com
165
2002 IS Catalog
DC Current Input
2 Form C Contact
Outputs Isolator
Technical Data
Power Supply
Nominal voltage
Power consumption
Terminals 11+, 12- or Power Rail
9-30 VDC
≤ 2.5 W, 1.8 W typical
Input
Input current
Excitation (terminal 3+)
Maximum overload
Impedance
Terminals 1+, 21-100 mA
24 VDC @ 20 mA
170 mA max., 60 VDC on input
20 Ω typical
Output
Terminals 4, 5, and 6; 7, 8, and 9
Type
2 SPDT (Form C) relays
Current ratings (resistive loads) 120 VAC @ 5A
240 VAC @ 2A
28 VDC @ 5A
Mechanical life
≥ 107 operations
Model Number
KFDA-DCI
■ Wide range of DC current inputs
■ Field configurable input/output
■ 3-way isolation
■ Accepts bipolar inputs
The KFDA-DCI accepts a DC current input
and provides two adjustable contact
outputs. This limit alarm also effectively
eliminates ground loops with 1,800 VDC
isolation separating input, output and
power supply.
Signal Conditioners
The KFDA-DCI is outfitted with three
LEDs. The first is a green INPUT LED
which indicates DC power and input signal
status. If this LED is not illuminated upon
power-up, check wiring connections.
When the signal is over 110% of the full
scale range, the INPUT LED flashes at 8
Hz; below 0% it flashes at 4 Hz. Each
setpoint has its own red LED that indicates
the relay state. An illuminated LED
indicates a tripped condition.
This unit is not intrinsically safe.
Repeatability (constant temp.)
> 5 mA
0.1% of full scale
< 5 mA
0.2% of full scale
Limit Differentials (deadbands)
> 5 mA
±0.25-5% of span
< 5 mA
1-5% of span
Stability
Temperature drift
±0.05% of full scale / ºC (max.)
Power
±0.01% of full scale / % of power change
Common Mode Rejection
DC to 60 Hz: 120 dB
Isolation
3-way 1,800 VDC
Response time
Dynamic Deadband
relay condition changes when proper
condition exists for 100 ms
Normal mode (analog filter)
≤ 400 ms, 200 ms typical
Mechanical
Housing
Dimensions (mm)
Weight
Protection (IEC)
115 x 20 x 118
100 g (3.5 oz.)
IP20
Operating Temperature
0ºC to +55ºC (+32ºF to +131ºF)
Makrolon KF style housing (see page 387)
Note: For information about programming,
refer to our website at www.am.pepperl-fuchs.com
Connection Diagram
KFDA-DCI
(+24 VDC) 3
(+) 1
DC Input
(– ) 2
4
Output A
5
6
166
7
8
Output B
9
11 (+) DC Power
Supply
12 (– )
Pepperl+Fuchs® Inc. • Telephone (330) 486-0002 • FAX (330) 425-4607
E-mail: greenteam@us.pepperl-fuchs.com • www.am.pepperl-fuchs.com
2002 IS Catalog
Technical Data
Power Supply
Nominal voltage
Power consumption
Inrush current
Terminals 11+, 12- or Power Rail
9-30 VDC
≤ 2.5 W, 1.8 W typical
≤ 300 mA max.
Input
Input voltage
Excitation (terminal 3+)
Impedance
Terminals 1+, 210 mV to 200 V
24 VDC @ 20 mA
> 100 kΩ typical
Terminals 4, 5, and 6; 7, 8 and 9
120 VAC @ 5 A
240 VAC @ 2 A
28 VDC @ 5 A
Mechanical life
≥ 107 operations
Repeatability (constant temperature):
> 50 mV
0.1% of full scale
< 50 mV
0.2% of full scale
Limit differentials (deadbands):
> 50 mV
0.25-5% of span
< 50 mV
1-5% of span
Temperature drift
± 0.05% of full scale / ºC (max.)
Power
±0.01% of full scale/% of power change
Common mode rejection
DC to 60 Hz: 120 dB
Isolation
3-way 1,800 VDC
Response time:
Dynamic deadband
relay condition changes when proper
condition exists for 100 ms
Normal mode (analog filtering) < 200 ms typical, 400 ms max.
DC Voltage Input
2 Form C Contact
Outputs Isolator
Output
Current rating (resistive loads)
Makrolon KF style housing (see page 387)
115 x 20 x 118
100 g (3.5 oz.)
IP20
Operating Temperature
0ºC to +55ºC (+32ºF to +131ºF)
Note: For information about programming,
refer to our website at www.am.pepperl-fuchs.com
Connection Diagram
KFDA-DCV
(+24 VDC) 3
(+) 1
DC Input
(– ) 2
4
Output A
5
6
7
8
Output B
9
11 (+) DC Power
Supply
12 (– )
KFDA-DCV
■ Wide range of DC voltage inputs
■ Field configurable inputs/outputs
■ 3-way isolation
■ 2 adjustable, independent relay
contact outputs
The KFDA-DCV accepts a DC voltage input
and provides two adjustable relay outputs.
This limit alarm also effectively eliminates
ground loops with 1,800 VDC isolation
separating input, output and power supply.
Setpoints can be configured as HI or LO in
selectable controlsafe or non-controlsafe
operating modes. The KFDA-DCV relies on
deadband (hysteresis) and constant sampling
of the input to prevent false switching when
the input varies slightly on either side of the
setoint. The input must remain beyond the
setpoint for 100ms, uninterrupted, to qualify
as a valid trip condition. To return the alarm
to an untripped condition, the input signal
must be outside the deadband and remain
there for 100 ms. This time-based dynamic
deadband, in addition to the evaluation of
hysteresis, improves setpoint stability. Select
unipolar operation for inputs that do not
change in polarity.
Signal Conditioners
Mechanical
Housing
Dimensions (mm)
Weight
Protection (IEC)
Model Number
The KFDA-DCV is equipped with three LEDs.
The first is a green INPUT LED which indicates
DC power and input signal status. If this LED
does not illuminate on power-up, check wiring
connections. When the signal input is over
110% of the full scale range, the INPUT LED
will flash at 8 Hz; below 0% it will flash at 4
Hz. Each setpoint has its own LED which
indicates the relay state; an illuminated LED
indicates a tripped condition.
This unit is not intrinsically safe.
Pepperl+Fuchs® Inc. • Telephone (330) 486-0002 • FAX (330) 425-4607
E-mail: greenteam@us.pepperl-fuchs.com • www.am.pepperl-fuchs.com
167
2002 IS Catalog
DC Current/Voltage
Input 2 Form C Contact
Outputs Isolator
Technical Data
Power Supply
Nominal voltage
Nominal current
Power consumption
Terminals 14+, 15- or Power Rail
20-30 VDC
≤ 75 mA
≤ 2.25 W, 1.68 W typical
Input
Measuring range voltage (terminals 1+, 3-)
Input load
Measuring range voltage (terminals 1+, 3-)
Input load
Measuring range voltage (terminals 2+, 3)
Input load
Model Number
KFD2-GS-1.2W
■ Single-channel, 24 VDC supply
■ Current and voltage analog inputs
■ 2 programmable trip points
The KFD2-GS-1.2W is a trip amplifier for two
independently field-configurable limit alarms.
Three-way galvanic isolated units convert 0/4-20
mA, 0/1-5 V and 0/2-10 V signals into trip point
outputs.
Signal Conditioners
For high alarm indication, the status of the contact
output changes when the setpoint is exceeded
and will not reset until a lower value is met. The
difference between these states is the adjustable
hysteresis.
The trip alarm is adjustable by a selector switch
and potentiometer.
A monitoring voltage output of 0-10 V can be used
to adjust limit values and hysteresis without
interrupting the input signal.
This unit is not intrinsically safe.
Switch
Position
Function
S1.1
0
1
0/2V...10V input range
0/1V...5V input range
S1.2
0
1
Low alarm output 1
High alarm output 1
S1.3
0
1
Low alarm output 11
High alarm output 11
0/1-5 V
50 kΩ
0/2-10 V
100 kΩ
0/4-20 mA
50 Ω
Output
Output I (terminals 7, 8, 9)
trip value 1
Output II (terminals 10, 11, 12) trip value 2
Contact load
AC: 250V / 5A / 1250VA
DC: 125V / 5A / 150 W
Function
Response time
Accuracy/repeatability
Temperature drift
Isolation
100 ms
< 0.5%
0.01% / ºC in reference to set limits
1000 V
Mechanical
Housing
Material
Style
Dimensions (mm)
Weight
Protection (IEC)
Makrolon
KF housing (see page 387)
115 x 20 x 118
120 g (4.2 oz.)
IP20
Operating Temperature
-20ºC to +60ºC (-4ºF to +140ºF)
Dip switch
functions
on side
of unit
High-/Low alarm
Input
range
Mode of
operation
ON: Limit 1
responds to
both outputs
1
0
1 2 3 4 5 6
Note: For information about programming,
refer to our website at www.am.pepperl-fuchs.com
Connection Diagram
KFD2-GS-1.2W
S1.4
168
0
1
Relays open in alarm state output 1
Relays closed in alarm state output 1
S1.5
0
1
Relays open in alarm state output 11
Relays closed in alarm state output 11
S1.6
0
1
Output 1 independent of output 11
Limit 1 responds to both outputs
1
8
0V...10V
2V...10V
2
0mA...20mA
4mA...20mA
3
Feed Back
4
Trip Value 1
5
Trip Value 2
6
7
9
Output 1
11
10
12
14
15
Output 2
Supply
24 VDC
Pepperl+Fuchs® Inc. • Telephone (330) 486-0002 • FAX (330) 425-4607
E-mail: greenteam@us.pepperl-fuchs.com • www.am.pepperl-fuchs.com
2002 IS Catalog
Transmitter
Power Supply
Isolator
Technical Data
Power Supply
Nominal voltage
Max. voltage Um
Power consumption
Terminals 23+, 24- or Power Rail
20-30 VDC
40 VDC
≈ 2.2 W
Input
Input signal
Available voltage
Terminals 1, 2 and 3
0/4-20 mA
≥ 15 V at 20 mA
Output
Output I
Output II
Output I & II type
Contact loading
Maximum voltage (Um)
Pull-in/drop-out delay
Mechanical life
Output III
Current range
Quiescent voltage
Load
Terminals 10, 11, 12
Terminals 16, 17, 18
Form C, SPDT contact
250 VAC / 2A / cos ϕ ≥ 0.7; 40 VDC/2A
40 VDC
≈ 20 ms / ≈ 20 ms
5 x 107 operations
Terminals 7, 8: analog signal
0/4-20 mA
≤ 24 VDC
≤ 650Ω
Transfer Characteristics
Accuracy
Temperature
Mechanical
Housing
Dimensions (mm)
Weight
Protection (IEC)
Makrolon KF style housing (see page 387)
115 x 40 x 118
300 g (10.5 oz.)
IP20
Operating Temperature
-20ºC to +60ºC (-4ºF to +149ºF)
Linearization
KFD2-CRG-1.D
■ Current source or transmitter
inputs
■ Analog output 0/4-20 mA
■ 2 relay outputs
■ Lead breakage and
short-circuit monitoring
■ Galvanic isolation
The KFD2-CRG-1.D transmitter power
supply is suited for a variet of measuring
tasks. 2- and 3-wire transmitters as well
as active power supplies with 0/4-20 MA
signals can be connected. Two relays and
an active 0/4-20 mA current output are
available.
Signal Conditioners
Input delay
Isolation
0.1% of full scale value (output < 10µA)
current measurement: 0.003% / ºC
current output: 0.005% / ºC
current measurement & output: 0.006% / ºC
current measurement and
current output 0.025%
≤ 200 ms
Galvanic isolation
Model Number
The input has lead breakage and shortcircuit monitoring.
Programming is via a PC (using
PACTware) or by using the control panel
on the front of the device.
Note: For information about programming,
refer to our website at www.am.pepperl-fuchs.com
This unit is not intrinsically safe.
Connection Diagram
KFD2-CRG-1.D
(+) 1
(+) 1
(– ) 2
Relay 1
(+) 1
Relay 2
(– ) 2
0/4...20mA
Output
23 (+)
24 (– )
DCV
Power
Supply
Output 1
Output 2
3
(– ) 2
3
7 (– )
8 (+)
10
11
12
16
17
18
3
3
Input
PC
Collective Error Messaging
Pepperl+Fuchs® Inc. • Telephone (330) 486-0002 • FAX (330) 425-4607
E-mail: greenteam@us.pepperl-fuchs.com • www.am.pepperl-fuchs.com
169
2002 IS Catalog
Transmitter Power
Supply Isolator
Technical Data
Model Number
KFU8-CRG-1.D
■ Current source or transmitter inputs
■ Analog output 0/4-20 mA
Terminals 23, 24
20-90 VDC or 48-253 VAC
253 VDC
≈ 2.2 W / 2.5 VA
Input
Input signal
Available voltage
Terminals 1, 2 and 3
0/4-20 mA
≥ 15 V at 20 mA
Output
Output I
Output II
Output I & II type
Contact loading
Maximum voltage (Um)
Pull-in/drop-out delay
Mechanical life
Output III
Current range
Quiescent voltage
Load
Terminals 10, 11, 12
Terminals 16, 17, 18
Form C, SPDT contact
250 VAC / 2A / cos ϕ ≥ 0.7; 40 VDC/2A
40 VDC
≈ 20 ms / ≈ 20 ms
5 x 107 operations
Terminals 7, 8: analog signal
0/4-20 mA
≤ 24 VDC
≤ 650Ω
Transfer Characteristics
Accuracy
Temperature
■ 2 relay outputs
■ Lead breakage and
short-circuit monitoring
■ Galvanic isolation
Input delay
Isolation
0.1% of full scale value (output < 10µA)
current measurement: 0.003% / ºC
current output: 0.005% / ºC
current measurement & output: 0.006% / ºC
current measurement and
current output 0.025%
≤ 200 ms
Galvanic isolation
Mechanical
Housing
Dimensions (mm)
Weight
Protection (IEC)
115 x 40 x 118
300 g (10.5 oz.)
IP20
Operating Temperature
-20ºC to +60ºC (-4ºF to +149ºF)
Linearization
The KFU8-CRG-1.D transmitter power
supply is suited for a variety of measuring
tasks. 2- and 3-wire transmitters as well
as active power supplies with 0/4-20 MA
signals can be connected. Two relays and
an active 0/4-20 mA current output are
available.
The input has lead breakage and short
circuit monitoring.
Signal Conditioners
Power Supply
Nominal voltage
Max. voltage Um
Power consumption
Makrolon KF style housing (see page 387)
The universal power requirement allows
AC or DC power of unit.
Programming is via a PC (using PACTware)
or by using the control panel on the front
of the device.
Note: For information about programming,
refer to our website at www.am.pepperl-fuchs.com
Connection Diagram
This unit is not intrinsically safe.
KFU8-CRG-1.D
(+) 1
(+) 1
(– ) 2
Relay 1
(+) 1
Relay 2
(– ) 2
170
0/4...20mA
Output
Output 1
Output 2
3
(– ) 2
3
7 (– )
8 (+)
10
11
12
16
17
18
3
3
Input
23 (+)
24 (– )
Universal
Power
Pepperl+Fuchs® Inc. • Telephone (330) 486-0002 • FAX (330) 425-4607
E-mail: greenteam@us.pepperl-fuchs.com • www.am.pepperl-fuchs.com
PC
2002 IS Catalog
Technical Data
Power Supply
Nominal voltage
Power consumption
Inrush current
Terminals 11+, 12- or Power Rail
9-30 VDC
≤ 2.5 W, 1.8 W typical
≤ 300 mA
Input (not intrinsically safe)
Thermocouples
Overload
Impedance
Burnout detection
Terminals 1+, 2B,E,J,K,R,S or T
≤ ±10 VDC on input
> 1 MΩ
< 1.5 µA
Output (not intrinsically safe)
Type
Current rating
Terminals 4, 5, and 6; 7, 8, and 9
2 SPDT (Form C) relays
120 VAC @ 5 A
240 VAC @ 2 A
28 VDC @ 5 A
≥ 107 operations
0.2% for temp. > 0ºC
0.3% for temp. < 0ºC
0.25-5% of span
±0.05% of full scale / ºC (max.)
±0.01% of full scale / % power change
DC to 60 Hz: 120 dB
3-way 1,800 VDC
Mechanical life
Repeatability (constant temp.)
Limit differentials (deadbands)
Temperature drift
Power
Common mode rejection
Isolation
Response time
Dynamic deadband
Mechanical
Housing
Material
Style
Dimensions (mm)
Weight
Protection (IEC)
Makrolon
KF housing (see page 387)
115 x 20 x 118
100 g (3.5 oz.)
IP20
Operating Temperature
0ºC to +55ºC (+32ºF to +131ºF)
Note: For information about programming,
refer to our website at www.am.pepperl-fuchs.com
Connection Diagram
KFDA-TC
Thermocouple
Input
(+) 1
(– ) 2
Output A
4
5
6
7
8
9
11 (+)
12 (– )
Output B
DC Power
Supply
Model Number
KFDA-TC
■ Wide input range of thermocouples
■ Field configurable input/output
■ 3-way isolation
■ 2 adjustable independent relay
contact outputs
The KFDA-TC accepts a B, E, J, K, S, R or T
type thermocouple input and provides two
adjustable contact outputs. This limit alarm also
effectively eliminates ground loops with 1,800
VDC isolation separating input, output and power
supply. The KFDA-TC is configurable for multiple
temperature ranges per thermocouple type. It
also accepts bipolar inputs and offers selectable
upscale and downscale burnout detection.
Signal Conditioners
Normal mode (analog filter)
relay condition changes when proper
condition exists for 100 ms
< 250 ms
Thermocouple Input
2 Form C Contact
Outputs Isolator
Setpoints can be configured as HI or LO in
selectable controlsafe or non-controlsafe
operating modes. The KFDA-TC relies on
deadband (hysteresis) and constant sampling of
the input to prevent false switching when the input
varies slightly on either side of the setpoint. The
input must remain uninterrupted beyond the
setpoint for 100 ms to qualify as a valid trip
condition. To return the alarm to an untripped
condition, the input signal must fall outside the
deadband and remain there for 100 ms. This
time-based dynamic deadband improves
setpoint stability.
The KFDA-TC is equipped with three LEDs. The
first is a green INPUT LED which indicates DC
power and input signal status. If this LED does
not illuminate during power-up, check wiring
connections. When the input signal is over 110%
of the full scale range, the INPUT LED flashes at
8 Hz; below 0% it flashes at 4 Hz. Each setpoint
has its own red LED that indicates the relay state.
An illuminated LED indicates a tripped condition.
This unit is not intrinsically safe.
Pepperl+Fuchs® Inc. • Telephone (330) 486-0002 • FAX (330) 425-4607
E-mail: greenteam@us.pepperl-fuchs.com • www.am.pepperl-fuchs.com
171
2002 IS Catalog
RTD Input
2 Form C Contact
Outputs Isolator
Model Number
KFDA-RTD
■ Wide input range of RTD
■ Field configurable input/output
■ 3-way isolation
■ 2 adjustable independent relay
contact outputs
The KFDA-RTD limit alarm accepts a 3-wire RTD
input (Pt100, Pt500, Pt1000, Cu10, Cu100, Ni120,
NiFe604) and provides two adjustable relay
outputs. This limit alarm also effectively eliminates
ground loops with 1,800 VDC isolation separating
input, output and power supply. The KFDA-RTD
is configurable for up to eight temperature ranges
for each RTD type.
Signal Conditioners
Setpoints can be configured as HI or LO in
selectable controlsafe or non-controlsafe operating
modes. The KFDA-RTD relies on deadband
(hysteresis) and constant sampling of the input to
prevent false switching when the input varies
slightly on either side of the setpoint. The input
must remain uninterrupted beyond the setpoint
for 100 ms to qualify as a valid trip condition. To
return the alarm to an untripped condition, the
input signal must fall outside the deadband and
remain there for 100 ms. This time-based dynamic
deadband improves setpoint stability.
The KFDA-RTD is outiftted with three LEDs. The
first is a green INPUT LED which indicates DC
power and input signal status. If this LED is not
illuminated at power-up, check wiring connections.
When the input signal is over 110% of the full scale
range, the INPUT LED flashes at 8 Hz; below 0%
it flashes at 4 Hz. Each setpoint has its own red
LED that indicates the relay state. An illuminated
LED indicates a tripped condition.
This unit is not intrinsically safe.
172
Technical Data
Power Supply
Nominal voltage
Power consumption
Inrush current
Terminals 11+, 12- or Power Rail
9-30 VDC (unregulated acceptable)
≤ 2.5 W, 1.8 W typical
≤ 300 mA
Input
Type
Input protection
Excitation current:
Pt100, Pt500, Pt1000
Ni120, Cu100, NiFe604
Cu10
Lead resistance
Terminals 1, 2 and 3
3-wire RTDs
withstand ±5 VDC
< 2 mA
< 2 mA
< 10 mA
40% of base sensor resistance or
100 Ω (whichever is less) max. per lead
Output
Terminals 4, 5 and 6; 7, 8 and 9
Type
2 SPDT (Form C) relays
Current rating (resistive loads) 120 VAC @ 5 A
240 VAC @ 2 A
28 VDC @ 5 A
Mechanical life
≥ 107 operations
Repeatability (constant temp.) 0.2% of full scale
Limit differentials (deadbands) 1-5% of span
Temperature drift
±0.05% of full scale / ºC (max.)
Common mode rejection
DC to 60 Hz: 120 dB
Isolation
3-way 1,800 VDC
Response time
Dynamic deadband
Normal mode (analog filter)
relay condition changes when proper
condition exists for 100 ms
≤ 400 ms, 200 ms typical
Mechanical
Housing
Dimensions (mm)
Weight
Protection (IEC)
115 x 20 x 118
100 g (3.5 oz.)
IP20
Operating Temperature
0ºC to +55ºC (+32ºF to +131ºF)
Makrolon KF style housing (see page 387)
Note: For information about programming,
refer to our website at www.am.pepperl-fuchs.com
Connection Diagram
KFDA-RTD
RTD Input
(+) 1
(– ) 2
(R) 3
4
Output A
5
6
7
8
9
11 (+)
12 (– )
Output B
DC Power
Supply
Pepperl+Fuchs® Inc. • Telephone (330) 486-0002 • FAX (330) 425-4607
E-mail: greenteam@us.pepperl-fuchs.com • www.am.pepperl-fuchs.com
2002 IS Catalog
Technical Data
Power Supply
Nominal voltage
Maximum voltage Um
Power consumption
Terminals 14+, 15- or Power Rail
20-35 VDC
40 VDC
1.5 W
Input
Type
Thermocouple
Terminals 1, 2, 3, 4, 5, 6
Pt100, Ni100
B,E,J,K,L,N,R,S or T
0-10 V, 0-20 mA, configuration with
programming jack
≤ 50 Ω per lead
400 µA with RTDs
Max. lead resistance
Test current
Universal Input 2 Form C
Contact Output / PC
Interface Isolator
NOTE: Switch off current for lead breakage monitoring during measurement
Output
Output I (Limit 1)
Output II (Limit 2)
Contact load
Mechanical life
Response time
Temperature drift
Power
Isolation
Terminals 7, 8 and 9
Terminals 10, 11 and 12
253 VAC / 2 A / cos ø ≥ 0.6
2 x 107 operations
≤ 370 ms
±0.007% of switchpoint per ºC∆T
≤ 0.0035% of span
Galvanic isolation
Mechanical
Housing
Dimensions (mm)
Weight
Protection (IEC)
115 x 20 x 118
100 g (3.5 oz.)
IP20
Operating Temperature
-20ºC to +60ºC (-4ºF to +140ºF)
Makrolon KF style housing (see page 387)
Model Number
KFD2-GU-1
■ Universal temperature input
■ Programming & calibration via PC
■ 3-way isolation
■ CJC for thermocouples and lead
resistance compensation for RTDs
Signal Conditioners
The KFD2-GU-1 universal input limit alarm is
field-configurable for 0-10 V, 0-20 mA, Pt100/
Ni100 and all thermocouple inputs with threeway galvanic isolation. This unit also features
internal/external cold junction compensation
(CJC) and burnout detection for thermocouples
and lead short circuit monitoring for RTDs and
current/voltage inputs. Calibration, adjustments
and monitoring are achieved through a serial
interface to a PC.
All parameters are programmable through a KADP1 cable (sold separately) that provides the
connection between the programming
receptacle of the KFD2-GU and the RS232 PC
interface.
Note: For information about programming,
refer to our website at www.am.pepperl-fuchs.com
Accessories include removable terminals with
internal cold junction compensation (K-CJC)
and a K-SK programming software kit. The KADP1 cable and K-SK software kit are required
unless the KFD2-GU is configured by P+F.
Connection Diagram
(+) 6
KFD2-GU-1
(+) 5
(+) 3
(+) 3
(+) 6
(+) 5
(+) 1
(– ) 2
(– ) 2
(– ) 2
(– ) 1
(– ) 1
(– ) 2
(– ) 2
(+) 4
(+) 3
(– ) 1
(– ) 2
Signal Processor
(+) 3
(– ) 2
This unit is not intrinsically safe.
(+) 4
CJC
Type K-CJC-GN
7
8
9
10
11
Output 1
Output 2
12
11 (+)
12 (– )
DC
Power
Supply
PC
K-ADPI
Pepperl+Fuchs® Inc. • Telephone (330) 486-0002 • FAX (330) 425-4607
E-mail: greenteam@us.pepperl-fuchs.com • www.am.pepperl-fuchs.com
173