Rack, Row, and Room-Based Cooling Systems System Design and Total Cost of Ownership Table of Contents 1. Executive Summary...........................................................................................................................3 2. Preamble...........................................................................................................................................3 3. 3.1 3.2 3.3 3.4 3.5 3.6 Basic Setup Data.................................................................................................................................4 Site.............................................................................................................................................................. 4 System Topology / Availability...................................................................................................................... 4 Computer Room.......................................................................................................................................... 5 Air Conditioning System............................................................................................................................... 6 Energy Supply and Distribution.................................................................................................................... 7 Energy Flow – Energy Consumers................................................................................................................. 7 4. 4.1 4.2 Physical and Technical Basics..............................................................................................................8 Mass Transport of Heat Transfer Media......................................................................................................... 8 Cooling...................................................................................................................................................... 12 5. 5.1 5.2 5.3 System Design / Optimization..........................................................................................................16 Passive Cabinet Rear Door Cooling Unit...................................................................................................... 17 Row-Based Cooling Unit............................................................................................................................. 21 Conventional Room-Based Cooling............................................................................................................ 26 6. 6.1 6.2 6.3 6.4 Costing............................................................................................................................................30 Investment................................................................................................................................................. 30 Overview of Operating Data for Air Conditioning Systems.......................................................................... 31 Energy Costs.............................................................................................................................................. 32 Maintenance Costs..................................................................................................................................... 34 7. TCO – 10-Year Comparison...............................................................................................................34 Table of Figures.......................................................................................................................................... 35 Abbreviations and Acronyms...................................................................................................................... 36 List of References........................................................................................................................................ 37 2 1. Executive Summary When building a new data center or retrofitting an existing site, data center operators can choose from several ventilation options. This paper considers three: rack, row, and room-based cooling. These options have features in common. The same fundamental physical laws apply to all three. Moreover, where design and operation are concerned, these options differ only in terms of details. What differentiates the three solutions is their individual advantages and disadvantages. To what extent these advantages and disadvantages are relevant depends on the project under consideration. Row-based cooling, for instance, tends to be used in smaller projects (up to 20 racks). Room-based cooling is best suited for lower load densities, while rack-based cooling is better suited for higher loads. The break-even point above which rack-based cooling is better suited heavily depends on a project’s basic conditions. Generally speaking, the following basic conditions should always be implemented in a cooling system to ensure cost-effective operation: Temperatures should be kept at a maximum within the system Dry or free cooling should be used* Keep temperature difference high and mass/volume flow low throughout the system Install complete hot/cold aisle separation within the IT room For availability reasons, cooling systems usually include redundancy units in each subsystem. Put redundancy units (especially fans and pumps) on and operate all units at low partial load. The decision for the optimum ventilation system must take into account not just the total cost of ownership (TCO), but also all project-specific boundary conditions. In the data center considered in this paper – and the three load cases analyzed: 3, 6 and 9 kW per cabinet – row-based cooling is somewhat less suited than rack and room-based cooling. The break-even point above which rack-based cooling is better suited stands at just over 10 kW per rack. The optimum solution has a PUE (mech) of 1.1 for each load if basic conditions are assumed. Since, however, the optimum solution always depends on a project’s specific circumstances, this paper is merely intended as a guide where cooling system optimization and design are concerned. 2. Preamble This study aims to demonstrate how three solutions for recirculating air conditioning in a data center – rack, row, and room-based cooling – can be designed and optimized for a low TCO over the course of a 10-year operation period. The study will be carried out at a 1,000 kW nominal load model data center in Frankfurt/Main, Germany. The infrastructure analyzed has been designed for this 1,000 kW nominal load, but in this paper the TCO is calculated for three partial load scenarios: 30, 60 and 90 percent load. The cooling system (pumps, heat exchangers, chillers, etc.) will be designed identically for all three scenarios (rack, row, and room-based cooling). Thus, only the effects of the ventilation on the overall system will be demonstrated. Only additional costs incurred by the respective recirculating air conditioning solution are considered in the investment. Any project will have its own boundary conditions. Many parameters affect the TCO. If the boundary conditions are changed, the TCO will thus also be different. This may lead to a different ranking and choice of ventilation design in different circumstances. Given this, the following statements are intended only as guidelines for design and system optimization. * This paper compares 3 ventilation systems only, recooling is set at dry cooling; adiabatic or wet cooling would be more energy efficient than dry, but comes with higher invest and other disadvantages. 3 3. Basic Setup Data 3.1 Site Supply air temperature is set slightly below the upper limit of the recommended envelope for class 1 equipment according to American Society of Heating, Refrigerating and Air-Conditioning Engineers (ASHRAE) TC9.9. Unit Site Location Frankfurt/Main Glycol concentration in outer circuit IT equipment % 34 111 Sea level AMSL IT air temperature difference Kelvin 13 Nominal load per rack kW 10 Number of racks Quantity 100 Total nominal load kW 1,000 Air conditioning system Maximum supply air/room temperature °C 25 Availability Uptime TIER III Other consumers With UPS in percent of the nominal load % 3% Without UPS in percent of the nominal load % 3% Partial loads Partial load 1 % 30% Partial load 2 % 60% Partial load 3 % 90% Figure 1: Site/basic design data 3.2 System Topology / Availability The infrastructure systems shall be designed in accordance with the Uptime Institute TIER III category, or category C of the BITKOM "Planning Guide for Reliable Data Centers" (BITKOM, German Federal Association for Information Technology, Telecommunications and New Media, 2012): Category C MSHV NSHV UPS Cold production UPS UV UV ULKG ULKG STS IT Component IT Component IT Room Figure 2: Topology in accordance with Category C; source: BITKOM 3.3 Computer Room Leaving aside the need for a ventilation system, the IT room for a 1 MW model data center at 10 kW/rack would look as follows: 4 A total of 100 racks Rack dimensions of 2,200H x 1,200D x 800W Arranged in 10 rows for every 10 racks Continuous in accordance with the hot aisle/cold aisle principle Figure 3: Room layout for cabinet door cooling (hot/cold aisles in red/blue) A 500 mm clearance is required above the racks for cabling. Figure 4: Vertical section of computer room A room with an IT area of 262 sqm and a height of 2.7 m is required. 5 3.4 Air Conditioning System As standard, a chilled water based cooling system shall be presupposed in this WP, as illustrated in the presentation "Effiziente Kühlsysteme für Hochleistungsrechner" [Efficient Cooling Systyes For High-Performance Computers] (Koch, 2013, p. 6). off IT Room Cooling System Cooling Water (+ Glycol) Cooling IT Room Air Circulation Computer Equipment Figure 5: Conventional chilled water-based cooling air-conditioning system Thermal load produced by electronic components is generally transferred into air as a first heat transport medium. By means of air as a transport medium, heat load is transported out of the chassis, the racks, and sometimes even out of the room and the building. On the path out of the building, thermal load is transferred into water, which has significantly better heat transport characteristics than air. For rack/row/room cooling, heat load is transferred from air into a liquid medium at the rack/ row/room level. Heat transport by water is usually separated into two circuits: a secondary circuit for transport within the building towards its perimeter, operated with pure water, and a primary circuit for transport outside the building-operated with a frost-resistant mix of glycol and water. Both circuits are connected via a plate heat exchanger. At the end of the heat transport path the load is discharged into the atmosphere by means of a chiller with a free cooling function. In order to only compare the three ventilation systems, an identical cooling system for all ventilation options is assumed. This system is equipped with optimized components (EC fans, speed controlled pumps, etc.) and operated at optimal conditions (all units “ON” under partial load, etc.). Figure 6 illustrates how the unit is equipped in the data center example. Air conditioning system Unit Value Cooling water pumps Approximate necessary volume flow m3/h Pump type Volume flow per unit Nominal power consumption Number (N+1) Installed volume flow 165 WILO IL-E65/150 m3/h 64 kW 5.46 Quantity 4 m3/h 256 Plate heat exchanger, primary and secondary circuit Nominal load Dimensions for nominal load Air conditioning system Approximate necessary volume flow Value Volume flow per unit Nominal power consumption Number (N+1) Installed volume flow 167 WILO IL-E65/150 m3/h 64 kW 5.46 Quantity 4 m3/h 256 Chiller (Liebert HPC-M series, G model) kW 1,150 K 2 Necessary cooling capacity kW Unit type Number (N+1) Figure 6: Units in the air-conditioning system m3/h Pump type Cooling capacity per unit 6 Unit Glycol pumps 1,250 HPC FG0 030 kW 350 Quantity 5 3.5 Energy Supply and Distribution 3.5.1 Cable Paths, Switching Systems In accordance with standards, cable paths should be designed for a maximum voltage drop of 3 percent (based on nominal voltage). If a TIER topology and real partial load operation at 30, 60, and 90 percent IT load are considered, in the majority of cases, two paths are used under basic conditions – each with approximately 15, 30 and 45 percent load. This method reduces conduction losses to 0.9, 1.8 and 2.7 percent in both paths depending on the load. These percentage values will be included in total energy consumption calculations for three load levels. 3.5.2 UPS Systems The latest technologies allow a very high level of efficiency; even when operating at partial load. This depends, however, on the stability of the power grid, ranging from 95 percent (poor grid) to 98 percent (good grid) over a very wide load range. In this paper, a TIER III topology is used along with two power supply paths, only one of which is protected with a UPS. Under normal conditions, only half the load will flow along the UPS path. As stated above, UPS losses will be between 2 and 5 percent (98 / 95 percent efficiency) of the UPS load. As only half of the load will be backed by a UPS in TIER III setup, UPS losses will be 1.5 percent compared to full load. 3.6 Energy Flow – Energy Consumers From an energy flow standpoint, electrical energy is introduced into the building and the computer rooms, fully converted to thermal energy in accordance with the conservation of energy principle, consequently transported back out of the rooms and the building in various heat transfer media. A simplified schematic of the main energy-consuming infrastructure is shown below: Figure 7: Schematic diagram of data center infrastructure The red arrows above indicate the flow of electrical energy arriving at the IT and Telco equipment, while the blue paths symbolize heat that is exiting the building. At current utility prices, utility bills represent a major share of the TCO of a data center. Two essential factors in turn determine the energy efficiency of an air-conditioning system, which consumes the majority of energy within the data center infrastructure: Moving such large flows of heat transfer media away from the load (IT systems, etc.) and out of the building using as little energy input as possible. 7 In terms of the transfer points that are always available (except for direct free cooling) from one heat transfer medium to another, temperature loss should be kept to an absolute minimum so that cooling can occur at the highest possible temperature when the thermal load reaches the outside of the building, consequently allowing for the maximum possible proportion of free cooling. Optimizing an air-conditioning system to make it more energy efficient however is nearly always in direct conflict with reducing investment costs. The lowest possible TCO is always achieved with some sort of a compromise between energy efficiency optimization and low levels of investment. 4. Physical and Technical Basics 4.1 Mass Transport of Heat Transfer Media 4.1.1 Physical Basics Two physical formulas apply for thermal load removal via mass transport of heat transfer media: Mass Transport: The energy ( ) that must be absorbed to move an ideal liquid or gaseous medium (loss-free propulsions required) is determined from the volume flow ( ) and total pressure loss ( ) on the transport route using the following physical formula: Heat Transport: In the cooling system, a heat transfer medium is used to transport a specific thermal load. Volume flow ( ) is determined by the thermal load ( ) and temperature range (the difference between the flow and return temperatures), where c is the specific thermal capacity of the medium, as follows: Mass flow ( ) is related to the volume flow by the density ( ): Mass Transport of a Heat Transfer Medium: The two formulas above lead to the following general formula for ideal liquid and gaseous media with loss-free propulsions: Conclusion: Although this formula only shows the theoretical optimum, the following rules also apply to real conditions (nonideal medium, lossy propulsions, etc.): Keep ΔT as high as possible Keep Δp as low as possible, but in conflict with investment costs (large pipe widths, etc.) 8 4.1.2 Media Transport in the Data Center Air Conditioning System Recirculating Air Conditioning: In this portion of the heat transport path, air is used as the heat transfer medium. To transfer the heat load in air from the heat sources to the first transfer point (i.e. into a liquid) fans are used, and these fans consume electrical power. This power draw depends on the total back pressure along the flow path. In standard air conditions (101.325 Pascal and 25°C), the formula may also be presented as follows: At 15 / 20°C the factor changes to 0.0812 / 0.0826; this is because air density is highly temperature-dependent. A theoretical minimum value of 0.42 percent for fan propulsion is based on typical values of a 50 Pa pressure drop on the entire air path and a 10 Kelvin operating temperature range. Real values for air conditioning units are higher by at least a factor of 5 (2 percent of the load for fan propulsion) due to components and other consumers that are not loss-free (controls, etc.) in optimum operating points. In unfavorable operating points, real values increase by a factor of up to 50 (20 percent of the load for fan drive). In both cases, the temperature range is 10 K. Secondary/Cooling Water Circuit: Here, a certain cooling water volume flow must be displaced in order to transport the thermal load collected out of the computer rooms to the building envelope; generally, a plate heat exchanger is used as the transfer point to a frost-proof external circuit. The pump's operating energy must be absorbed to achieve this. The physical properties for water ( = 1,000 kg/m3) give the following: or A theoretical minimum value of 0.20 percent for the pump drive is based on a standard value of 0.5 bar pressure drop in the circuit as a whole, and a 6 Kelvin operating temperature range. Primary/Glycol Circuit: A certain glycol volume flow must also be displaced in order to transport the thermal load from the building envelope to the heat exchanger. The pump's operating energy must be absorbed to achieve this. The proportion of glycol contained in the mixture will vary depending on climate zone and frost protection requirements. At 34 percent glycol with a media temperature of 20°C, the mixture illustrates the following characteristics for density and thermal capacity: 1,050 kg/m3 and 3.64 kJ/kg K. For pump capacity, this results in: or 9 A theoretical minimum value of 0.22 percent for the pump drive is based on a standard value of 0.5 bar pressure drop in the circuit as a whole, and a 6 Kelvin operating temperature range. Heat Exchange: Here, a certain air flow must again be displaced by the heat exchanger register in order to release the thermal load from the external circuit into the atmosphere. Fan propulsion energy must again be absorbed to achieve this. The formula for air applies again in this situation, whereby temperatures and air densities can vary enormously over the course of the year. A theoretical minimum value of 0.04 percent for fan propulsion is based on a standard value of 5 Pa pressure drop on the entire air path, and a 10 Kelvin operating temperature range. Real values for air conditioning units are usually higher due to components and other consumers that are not loss-free (controls, etc.). On the other hand, the thermal lift of the warm exhaust air is generally used in the heat exchangers, which reduces fan propulsion energy requirements. Conclusion: Theoretically – when speaking of ideal media, loss-free propulsions, etc. – around 1 percent would need to be absorbed for media transport (depending on pipe widths, cable paths, etc.) over the entire transport path of the thermal load from the load out of the building. Real components are not loss-free and are usually operated at non-ideal operating points. Real values are several times higher. 4.1.3 Components and Operating Conditions Fans: In theory, the characteristic curve of fan speed/volume flow plotted against power consumption follows a cubic (third power) course; in reality, however, this relationship is around the power of 2.5. In the example below, from "Optimierte Energieeffizienz durch geregelte Kaltgangeinhausungen" [Optimized energy efficiency through regulated cold aisle enclosures] (Emerson Network Power - Racks and Solutions, 2011), the relationship between output and volume flow at 30 percent speed is 0.2 W per m3/h and, when at a speed of 90 percent it is 0.8 W per m3/h. Figure 8: Characteristic curve of a typical EC fan 10 Primary and Secondary Circuit Pumps: Modern pump drives are similar in their characteristic curves to modern fans. Power consumption is non-linear and depends, to a large extent, on volume flow. Partial load operation is much more energy efficient than full load operation. Figure 9: Typical pump curves (WILO Stratos GIGA 65/1-38/3,8) Conclusion: Modern fans and pumps should be operated at partial load as much as possible, since energy efficiency is noticeably higher with this method of operation than in full load operation. Partial load operation is usually possible for two reasons: The data center infrastructure is generally designed redundantly; at least N+1, often 2 N. Redundant fans and pumps should also be "ON" in controlled operation. The design is based on a nominal load, which is only rarely reached in actual operation. 11 4.2 Cooling 4.2.1 Temperature Levels in the Cooling System Generally speaking, a large part of the thermal load is produced in the data center (i.e. within the ITC components being used, such as servers, storage, network switches, etc.) at a very high temperature that is well above 50°C. This is the case for microprocessors and other components. Only a small part of the load is produced in low-density components at a relatively low temperature of about 20°C. Most current ITC components are air-cooled. A moderate exhaust air temperature is generated in the return air; this temperature mainly depends on the technology being used. The temperature of the supply air delivered by the air conditioning system also has a direct influence. In today's existing systems, this can be just over 10°C and is well over 20°C in the most up-to-date, energy efficiency-optimized systems. Currently, air conditioning systems operate on the air side within a small temperature range of 12/15°C for legacy IT systems, and remain within a temperature range of 27/47°C for blade servers. Figure 10: Typical temperatures in the data center air conditioning system Following the transfer to the medium of water, temperatures in the cooling water circuit are between 5/10°C and 20/28°C. In the primary circuit, the temperature must be 1 to 2 Kelvin lower to compensate for plate heat exchanger losses. Depending on the climate zone and temperatures over the course of the year, certain conditions will apply for the release of the thermal load into the atmosphere: Dry cooling is sufficient (ambient temperature is a few Kelvin colder than cooling circuit) Adiabatic or hybrid cooling is required (ambient temperature is similar to cooling circuit) Mixed operation combining free and compressor-type cooling is used Pure compressor-type cooling is required to raise the temperature level in the cooling circuit above the ambient temperature. From pure dry cooling to pure compressor-type cooling, consumption increases enormously, particularly the energy input required to release the heat into the atmosphere. 12 4.2.2 Cooling via the Freecooling Chiller Conventional chillers should be used with a free cooling function depending on the ambient temperature of the three variants described above (adiabatic and wet cooling systems are an option, but not examined within this study). For many cities, the ambient temperature profile is recorded in climate charts. For dry cooling systems, the "dry bulb" temperature is relevant. For wet cooling systems, the "wet bulb" temperature is important. The following diagrams have been created using the Emerson Network Power design software "Hirating", Version 7.8. Figure 11: Annual "dry bulb" temperature profile, Frankfurt Compressor operation is not necessary at ambient temperatures below a certain temperature threshold (left of the green line in the image below) and the cooling capacity can be supplied with a high level of energy efficiency using the pure free cooling function. In the case of higher ambient temperatures (between the green and the red line), free cooling is no longer sufficient. Part of the cooling capacity must be generated in compressor operation, since free cooling does not contribute anymore past a certain ambient temperature (red line). Thus, the entire cooling capacity must be generated in compressor operation. Figure 12: Cooling based on ambient temperature 13 Partial Load [kW] Partial load operation 170kW load Ambient Temperature [°C] Figure 13: Chiller power consumption with cooling water at 20/26°C; 170 kW partial load operation At high ambient temperatures, the power consumption of the chiller is determined by the COP compressor. Around 25–30 percent of the thermal load is required for energy usage. On cold days, the compressor is off and the chiller is in free cooling mode consuming very little energy for the fans. In the transitional range, the chiller is in mixed mode, which combines both free cooling and compressor cooling. The annual average shows a distinctively higher energy efficiency than pure compressor operation. This attribute, according to the COP compressor (or EER unit), is known as the "Seasonal Performance Factor" (SPF). At high cooling water temperatures, real SPF values of well over 10 are reached. The inverse would mean that far less than 10 percent of the thermal load is being consumed to increase temperature using the cooling unit/heat pump in the chiller. The transition between free cooling, mixed operation, and full compressor cooling mode is within a temperature range of >350 h/K for Frankfurt*. In return, the number of hours of mixed operation and full compressor cooling mode is reduced accordingly. 4.2.3 Components and Operating Conditions Chiller: The total chiller load is made up of the IT load and all other thermal loads (i.e. recirculating air conditioning systems, power distribution, UPS, etc.) inside the building. The design of the chiller is based on a 1,000 kW IT nominal load, plus at least 20 percent extra for losses in the UPS, power supply lines, recirculating air conditioning system fans, lighting, and heat input from outside in the summer. Therefore, the load is at least 1,200 kW in N+1. FG0 030 Outdoor air temperature Glycol 40.0°C Unit fluid flow 59.6 m3/h Sea level 111 m Inlet fluid temperature 26.0°C Refrigerant R410A Outlet fluid temperature 20.0°C Unit power supply ETHYLENE GLYCOL 35% 400 V/3 ph/50 Hz Unit performances Model SPL (@ 1m, f.f, re.ISO3744) (with nominal airflow) 79.5 dB(A) Cooling capacity 374.2 kW PWL (re.ISO3744) (with nominal airflow) 99.5 dB(A) Unit power input 129.1 kW Unit OA 212 A 2.90 Unit FLA 249 A Outlet fluid temperature 20.0°C Unit LRA Inlet fluid temperature 26.0°C Width FG0 030 Unit EER 493 A 5,750 mm Figure 14: Liebert HPC Chiller FG0 030 data sheet * i.e. raising the cooling water temperature by 1 Kelvin increases the number of annual hours of free cooling by approximately 350. 14 At 374 kW nominal output, 4+1 units are thus required for 1200 kW maximum load. As such, in actual operation at 30, 60 or 90 percent IT load, the units are run under appropriate partial load. City Frankfurt Unit FG0 030 Unit fluid flow Fluid 54.0 m3/h ETHYLENE GLYCOL 30% Requested thermal load 170.0 kW Annual absorbed energy SCH 87,909 kWhe Annual absorbed energy CH 283,398 kWhe Annual energy saving 195,489 kWhe Electrical saving 69% Figure 15: Annual energy consumption of the Liebert FG0 030 at 20/26°C in partial load operation At approximately 50 percent partial load (170 kW load), a Super Chiller will consume 88.4 MWh annually. This is equivalent to an SPF of 16.8. The inverse shows that power consumption of the Super Chiller is around 6 percent of the load in the annual average. This average annual power consumption, relative to the load, depends on the cooling water temperature, as shown below: Figure 16: Typical chiller – power consumption relative to load 15 5. System Design / Optimization The operating conditions for three air recirculation variants and three load categories are shown in the diagram below: Figure 17: Schematic diagram of operating data In the upper area of the diagram, the feeding in and supply of electrical energy (in red: output in kW) to all components and systems is shown from right to left. For all scenarios, "other loads" in front of and behind the UPS, each using 30 kW, are taken as constant and independent of the load. The ICT systems are shown on the bottom left side of the diagram. These fully convert the 900 kW, 600 kW or 300 kW electrical power consumed in the three partial load scenarios to thermal load. This thermal load is then discharged through the medium of air and arrives in approximately 288,000, 192,000, or 96,000 m3/h of return air at 35°C (a supply air temperature of 25°C and a mean temperature range of 10 Kelvin for the ICT systems are assumed) at each recirculating air conditioning unit. At the bottom of the diagram, the heat transfer media in the conventional air conditioning system are shown. Above this, temperatures are depicted in green (flow line/supply air below, return line/return air above); the volume flows are shown in blue and the thermal loads in brown. In the following sections, the boxes that represent the units each contain essential design and efficiency parameters. 16 5.1 Passive Cabinet Rear Door Cooling Unit Product descriptions and specifications in this section can generally be found in the product brochure Knürr® DCD – Cooling door for maximum energy efficiency: 35 kW cooling capacity (Emerson Network Power EMEA, 2013). 5.1.1 Product Knürr DCD is an air/water heat exchanger that is integrated into the rear door of a server cabinet. The heat exchanger is suitable for absorbing heat loads from server cabinets of up to 35 kW. It can be configured in such a way that no heat is released from the installation area. Figure 18: Knürr DCD rear door cooling unit Cold air site Housing Steel sheet (powder-coated) Operating temperature 10°C – 35°C (50°F – 95°F) (other temperatures up on request) Maximum humidity 8 g/kg Outlet air temperature (ASHARE specification) 18°C – 27°C (64.4°F – 80.6°F) Air temperature difference 15 K – 20 K Cold water side Cooling capacity 35 kW Inlet cold water temperature 12°C – 18°C (53.6°F – 64.4°F) (other temperatures up on request) Outlet cold water temperature 18°C – 24°C (64.4°F – 75.2°F) (other temperatures up on request) Maximum pressure 10 bar (145 psi) Pipe connection ON/OFF 1" external thread (on edge) (DIN ISO 228 - 1) Figure 19: Knürr DCD specification 5.1.2 Design Recirculating Air Conditioning System: One Knürr DCD per rack As standard, there is no volume flow controller in the Knürr DCD. Volume flow is permanently set to the IT nominal load, although in partial load this results in higher pressure losses in the secondary circuit. An optional volume flow controller (e.g. per row of cabinets) would incur additional costs – a total of 50,000 EUR for every 10 rows. This additional investment would pay for itself through energy savings in the case of the secondary circuit pumps over an extended period of time. The cold room concept is supported and a cold temperature is maintained throughout the whole room. 17 5.1.3 Operating Data Figure 20: Nominal data for Knürr DCD at 1.8 m3/h cooling water volume flow Description Total air recirculation load Minimum volume flow Maximum performance, cooling unit Load 30% 60% 90% 100% kW 300 600 900 1,000 m3/h 73,846 147,692 221,538 246,154 kW 10 10 10 10 100 100 100 100 100% Cooling units in operation Load in normal operation Load per cooling unit Air vol. flow/unit % 30% 60% 90% kW 3.0 6.0 9.0 10.0 m3/h 738 1,477 2,215 2,462 kW 0 0 0 0 m3/h 1.8 1.8 1.8 1.8 CW – flow line °C 22.5 21.0 19.5 19.0 CW – return line °C 23.9 23.9 23.8 23.8 Power consumption/unit Cooling water vol. flow/unit Figure 21: Operating data for passive cabinet rear door cooling unit 5.1.4 Effect on Building and Computer Room Figure 22: Room layout for cabinet door cooling system If assumed that the hot aisles are reduced to approximately 1,000 mm width instead of 1,200 mm, the required floor space remains unchanged in relation to the basic scenario. 18 Figure 23: Vertical section of the floor for rack-based cooling In preferred "back-to-back" layout (in accordance with the "cold aisle/hot aisle concept"), large air flows must be transported from the aisle behind the racks to the front of the racks without a large amount of pressure loss. This requires more "air space" above the racks, increasing the required ceiling height by 300 mm in relation to the basic scenario. A raised floor is not necessary here, since the pipework may be located under the ceiling. 5.1.5 Overview of Operating Data The essential operating parameters for the three load categories are as follows: Figure 24: Overview of operating data for rear door cooling unit at 30 percent load 19 Figure 25: Overview of operating data for rear door cooling unit at 60 percent load Figure 26: Overview of operating data for rear door cooling unit at 90 percent load Even at the highest of the three load categories, the PUE (mech) does not noticeably increase. 20 5.1.6 Rack-based cooling features Benefits: No fan propulsion energy required in the cooling unit No raised floor or suspended ceiling required Low height between floors No partitions or closed intermediate ceilings required No additional floor space required, as hot aisle width usually can be reduced from 1200 mm (basic scenario) to app. 1000 mm (with rear door cooling units) The cold room concept is implemented, with the hot area limited to within the racks, and the whole room representing the cold area. Optimum PUE (mech) at high thermal load density Disadvantages: A large number of cooling units (one for each IT rack) and water connections are required Relatively low cooling water temperature required An additional unit (air handler) may be needed in order to filter the air and keep the humidity within the permitted range (costs are not considered in this paper). 5.2 Row-Based Cooling Unit Product descriptions and specifications in this section can generally be found in the "Knürr DCD – Modular Rack Cooling from 6 kW to 60 kW" product brochure (Emerson Network Power EMEA, 2013). 5.2.1 Product The Knürr DCL is a rack-based cooling unit in chilled water configuration to be installed side-by-side with computing racks. Knürr DCL can be used as a closed air loop rack cooling device (L version) or as a hybrid (H) with perforated front doors connecting air flow to the room. This versatility is achieved by using interchangeable side panels to alter the air flow pattern. The hybrid and closed loop versions support the "cold room" concept. Air is drawn by fans from the rear of the Knürr DCL through the heat exchanger, cooled down, and discharged through the front of the rack. Knürr® DCL-H Knürr® DCL-H 1-1 combination *30/34 kW per DCL-H for 2,000/2,200 mm height version Figure 27: Knürr DCL-H hybrid solution 21 DCL30 Nominal cooling capacity Air flow Water flow Maximum water pressure 34 kW 5,000 m3/h (3,237 CFM) 6,000 m3/h (3,885 CFM) 4.5 m3/h (20 CFM) 5.0 m3/h (22 CFM) 10 bar (145 PSI) 10 bar (145 PSI) 5 6 5 x 170 W 6 x 170 W 300 x 1,000 (1,100) (1,200) x 2,000 [mm] 300 x 1,000 (1,100) (1,200) x 2,200 [mm] 10.72 l / 2.83 gal. 11.93 l / 3.15 gal. Number of fans Fans power consumption Dimensions (W x D x H) DCL34 30 kW Heat exchanger internaI fluid volume Figure 28: Knürr DCL-H specification 5.2.2 Design Recirculating Air Conditioning System: DCL–H in accordance with TIER III Redundancy is maintained per row of cabinets 5.2.3 Operating Data CR0342C Unit inlet air temperature 41.7°C Fluid Unit inlet air relative humidity 24.0% Inlet fluid temperature 20.0°C Outlet fluid temperature 26.0°C Unit airflow ESP Sea level 6,000 m3/h 0 Pa 111 m Unit fluid flow Unit power supply WATER 1.02 l/s 230 V/1 ph/50 Hz Unit performances Unit CR0342C Unit power input Net total cooling capacity 25.6 kW Unit EER Net sensible cooling capacity 25.6 kW Internal filter class (EN779 std) SHR 1.11 kW 23.10 No 1.00 Width 300 mm Off coil air temperature 28.7°C Depth 1,200 mm Off coil air relative humidity 49.2% Height 2,222 mm 72.1 dB(A) Weight 188 kg Fluid pressure drop coil+connections 29 kPa Room SPL (@ 2m, f.f) CW coils Quantity 1 n° Unit fluid flow 1.02 l/s Unit fluid side pressure drop 35 kPa Valve pressure drop 5 kPa CW fans Quantity Type Power supply Power input 6 n° Normal 230 V/1 ph/50 Hz 6 x 0.18 kW Operating ampere 6 x 1.37 A Full load ampere 6 x 1.40 A Locked rotor amp. 6 x 0.10 A Fan input voltage Figure 29: Nominal data for Knürr DCL-H row-based cooling unit 22 10.0 V Description Total air recirculation load Minimum volume flow Maximum performance, cooling unit Load 30% 60% 90% 100% kW 300 600 900 1,000 m3/h 73,846 147,692 221,538 246,154 kW 25.6 25.6 25.6 25.6 40 50 50 50 29% 47% 70% 78% Cooling units in operation Load in normal operation Load per cooling unit Air vol. flow/unit % kW 7.5 12.0 18.0 20.0 m3/h 2,000 2,900 4,250 4,750 0.57 kW 0.09 0.15 0.39 m3/h 1.8 1.8 2.6 2.9 CW – flow line °C 21.3 19.2 17.7 17.2 CW – return line °C 25.3 25.0 23.7 23.2 Power consumption/unit Cooling water vol. flow/unit Figure 30: Design and operating data for row-based cooling system At 30 percent load, many row-based cooling units (two per row of cabinets) enter standby mode, as it is not economically efficient enough to reduce fan speed, and thus cooling capacity, below a minimum rpm rate. 5.2.4 Effect on Building and Computer Room Figure 31: Room layout for row-based cooling system With in-row-cooling units added, as sketched in figure 31, aisle will get longer in this scenario, and the required floor space increases from 262 to 300 sqm – 38 sqm more than in the basic scenario. Figure 32: Vertical section of the floor for row-based cooling The ceiling height remains unchanged for the basic scenario, as hot air is returned to the cold aisle through the rowbased cooling unit. 23 5.2.5 Overview of Operating Data The essential operating parameters for the three load categories are as follows: Figure 33: Overview of operating data for row-based cooling system at 30 percent load Figure 34: Overview of operating data for row-based cooling system at 60 percent load 24 Figure 35: Overview of operating data for row-based cooling system at 90 percent load At the highest load category, the PUE somewhat increases, as both fan speed and power consumption, and (due to lower chilled water temperature) annual chiller energy consumption disproportionately increases. 5.2.6 Row-Based Cooling System Features Benefits: No raised floor or suspended ceiling required Low height between floors The cold room concept is implemented, with the hot area limited to within the racks, and the whole room representing the cold area. Disadvantages: More cooling units; redundancy maintained for each row of cabinets Relatively low cooling water temperature required An additional unit (air handler) may be needed in order to filter the air and keep the humidity within the permitted range (costs are not considered in this paper). 25 5.3 Conventional Room-Based Cooling Product descriptions and specifications in this section can generally be found in the "Liebert® PCW – Cool the Cloud" (Emerson Network Power, 2012) product brochure. 5.3.1 Product Liebert PCW recirculating air conditioning units are ideal for data centers in the 200 kW to 4–6 MW range, that use chilled water as a cooling fluid. The cooling system comprises the PCW cooling unit as well as free cooling chillers, delivering the best efficiency to ensure data center reliability and availability. Figure 36: Liebert PCW recirculating air conditioning unit Version Unit Extended Down PH046 PH066 PH081 PH091 PH111 PH136 PH161 PH201 Gross power overall [kW] 35.8 51.9 63.7 76.9 87.2 116.2 138.4 162.9 Sensible net output [kW] 34.5 50.7 61.9 72.6 84.6 111.8 128.2 150.6 Power consumption [kW] 1.31 1.19 1.79 1.85 2.55 3.69 4.50 5.39 Sensible net EER value 26.3 42.6 34.6 39.2 33.2 30.3 28.5 27.9 11,500 16,100 20,000 19,500 28,000 30,800 34,500 40,400 Air flow [m3/h] Water temperatures 10°C – 15°C Return air 24°C 50% RH Figure 37: Liebert PCW Extended Down - specification 5.3.2 Design Recirculating Air Conditioning System designed as follows: CRAC units according to thermal load and redundancy as well as dimensions of the climate clasp Raised floor for cold air distribution or alternatively suspended ceiling for return air Hot/cold separation via cold/hot aisle containment 26 5.3.3 Operating Data The following example illustrates the PH201EL model, since it is the most economical solution that meets cooling capacity and installation area requirements. PH201EL – Extended Height, Downflow Down, EC Fan 2.0 Unit inlet air temperature 38.2°C Fluid Unit inlet air relative humidity 25.0% Inlet fluid temperature 22.0°C Outlet fluid temperature 28.0°C Unit airflow 53,138 m3/h ESP 5 Pa Sea level 111 m WATER Unit fluid flow 9.19 l/s Unit power supply 400 V/3 ph/50 Hz Unit performances Unit PH201EL Unit power input 10.43 kW Net total cooling capacity 219.4 kW Unit net sensible EER Net sensible cooling capacity 219.4 kW Internal filter class (EN779 std) SHR 21.00 F5 1.00 Width Supply air temperature 25.2°C Depth 890 mm Supply air relative humidity 52.5% Height 1,970 mm 72.9 dB(A) Weight 1,125 kg Room SPL (@ 2m, f.f) 3,350 mm CW coils Quantity 1 n° Unit fluid flow 9.19 l/s Unit fluid side pressure drop 68 kPa Fluid pressure drop coil+connections 51 kPa Valve pressure drop 17 kPa CW fans Quantity 4 n° Type Normal Power supply 400 V/3 ph/50 Hz Power input 4 x 2.60 kW Operating ampere 4 x 3.96 A Full load ampere 4 x 5.00 A Locked rotor ampere 4 x 0.10 A Fan input voltage 10.0 V Figure 38: Liebert PH201EL performance data Description Total air recirculation load Minimum volume flow Maximum performance, cooling unit Load 30% 60% 90% 100% kW 300 600 900 1,000 m3/h 73,846 147,692 221,538 246,154 kW 219 219 219 219 5 6 6 6 27% 46% 68% 76% Cooling units in operation Load in normal operation Load per cooling unit Air vol. flow/unit % kW 60.0 100.0 150.0 166.7 m3/h 15,000 24,500 36,700 40,400 kW 0.43 1.31 3.71 4.83 m3/h 13.4 14.7 22.3 24.6 CW – flow line °C 24.5 23.5 22.8 22.6 CW – return line °C 28.5 29.5 28.8 28.6 Power consumption/unit Cooling water vol. flow/unit Figure 39: Operating data for recirculating air conditioning units Figure 39 also illustrates how a recirculating air conditioning unit can go into standby mode at 30 percent load, as it is not economically efficient to reduce cooling capacity (and fan speed) below a certain threshold. 27 5.3.4 Effect on Building and Room Plan Figure 40: Room layout for room-based cooling system The floor space required for the IT equipment (racks) remains unchanged. The climate clasp adds 60 sqm facility management (FM) space compared to the basic scenario. Figure 41: Vertical section of the floor for room-based cooling In the diagram above, the ceiling height has increased by 900 mm for the raised floor at this thermal load density and room geometry, with a limit of 5 m/s for the airspeed in the raised floor. 5.3.5 Overview of Operating Data The essential operating parameters for the three load categories are as follows: Figure 42: Overview of operating data for room-based cooling at 30 percent load 28 Figure 43: Overview of operating data for room-based cooling at 60 percent load Figure 44: Overview of operating data for room-based cooling at 90 percent load 5.3.6 Room-Based Cooling System Features Benefits: Highest chilled water temperature compared with the two alternatives (i.e. low energy usage for cooling) No cooling water pipework is present in the computer room Optimum PUE (mech) at low thermal load density Disadvantages: Raised floor required or, alternatively, a suspended ceiling A greater height between floors Enclosure required Cold room concept not supported since most areas of the room are warm 29 6. Costing 6.1 Investment Direct share and direct effects on investment costs if the recirculating air conditioning system is selected are as follows: Investment Rack Row Room 0 0 112,700 Raised floor EUR Floor space sqm 0 0 322 Enclosure EUR 0 0 55,000 Cold aisles Quantity 0 0 5 EUR 500,000 425,000 180,000 Recirculating air conditioning Units Cooling water pipework Connections Units Quantity 100 50 6 EUR 50,000 35,000 21,800 Quantity 100 50 6 EUR 550,000 460,000 369,500 0 IT area EUR 0 112,500 Floor space sqm 0 45 0 Technical area EUR 0 0 150,000 Floor space sqm 0 0 60 Height between floors EUR 39,300 0 144,900 Floor space sqm 262 300 322 m 0.3 0.0 0.9 EUR 39,300 112,500 294,900 EUR ('000) 550 573 520 Additional height between floors Building Total for existing construction (without height between floors) Figure 45: Comparison of investment for rack, row, and room-based cooling systems Rack and row-based cooling systems have integrated hot/cold separation; enclosures are needed for room-based cooling as well as raised flooring. Row and room-based cooling systems require additional floor space, whilst rack and room-based cooling systems need a greater height between floors. 30 6.2 Overview of Operating Data for Air Conditioning Systems Under the assumed basic conditions, the following operating conditions have been determined for the three air recirculation variants corresponding to the three partial loads: Unit 30% 60% 90% m3/h 73,846 147,692 221,538 Supply air temperature °C 25 25 25 Return air temperature °C 38 38 38 m3/h 180.0 180.0 180.0 Flow line °C 22.5 21.0 19.5 Return line °C 23.9 23.9 23.8 Partial load operation Air recirculation Total volume flow Cooling water circuit Volume flow Plate heat exchanger Load kW 339 639 939 K 0.18 0.62 1.34 m3/h 55.7 105.0 154.4 Flow line °C 26.0 24.8 23.3 Return line °C 20.0 18.8 17.3 kW 378 694 1,017 Temperature loss Glycol circuit (34%) Volume flow Freecooling chiller Load Figure 46: Overview of operating data for rear door cooling In the case of rack-based cooling, the volume flow in the secondary circuit is assumed to be unregulated. For the smallest load (3 kW per rack), the secondary circuit is generally designed for less than the standard 6 Kelvin, since heat exchangers require a minimum volume flow for efficient heat transfer. Unit 30% 60% 90% m3/h 80,000 145,000 212,500 Supply air temperature °C 25 25 25 Return air temperature °C 38 38 38 129.6 Partial load operation Air recirculation Total volume flow Cooling water circuit Volume flow m3/h 72.0 90.0 Flow line °C 21.3 19.2 17.7 Return line °C 25.3 25.0 23.7 Plate heat exchanger Total load kW 335 639 953 K 0.16 0.62 1.38 m3/h 55.0 105.1 156.7 Flow line °C 26.1 24.5 22.3 Return line °C 20.1 18.5 16.3 kW 373 694 1,033 Temperature loss Glycol circuit (34%) Volume flow Freecooling chiller Load Figure 47: Overview of operating data for row cooling 31 Unit 30% 60% 90% m3/h 75,000 147,000 220,200 Supply air temperature °C 25 25 25 Return air temperature °C 38 38 38 133.7 Partial load operation Air recirculation Total volume flow Cooling water circuit Volume flow m3/h 66.8 87.9 Flow line °C 24.5 23.5 22.8 Return line °C 28.5 29.5 28.8 Plate heat exchanger Total load kW 333 639 957 K 0.16 0.62 1.38 m3/h 54.7 105.1 157.2 Flow line °C 29.3 28.9 27.4 Return line °C 23.3 22.9 21.4 kW 372 694 1,035 Temperature loss Glycol circuit (34%) Volume flow Freecooling chiller Load Figure 48: Overview of operating data for room-based cooling 6.3 Energy Costs The annual energy costs for the site under consideration with regards to the three load categories are determined using an assumed energy price of 125 EUR per MWh (12.5 cents/kWh), as follows: EUR per MWh 125 Average power consumption Partial load operation Unit 30% 60% 90% Air conditioning system kW 0.0 0.0 0.0 Quantity 100 100 100 Consumption per unit kW 0.00 0.00 0.00 Cooling water pumps kW 9.1 9.1 9.1 Quantity 4 4 4 kW 2.26 2.26 2.26 6.2 Air recirculation units Number of units Number of units Consumption per unit kW 0.5 2.4 Quantity 4 4 4 Consumption per unit kW 0.12 0.59 1.54 Cooling unit kW 21.9 46.4 79.0 % 5.8% 6.7% 7.8% kW 31.5 57.8 94.3 Glycol pumps Number of units Average power consumption (1/JAZ) Air conditioning system Power supply UPS losses kW 5.1 9.6 14.2 Power distribution losses kW 3.3 12.5 28.1 Power supply kW 8.4 22.2 42.3 Total power consumption kW 39.8 79.9 136.5 EUR ('000) 43.6 87.5 149.5 Annual energy costs Figure 49: Power consumption and energy costs for rear door cooling 32 EUR per MWh 125 Average power consumption Partial load operation Unit 30% 60% 90% 19.5 Air conditioning system Air recirculation units Number of units Consumption per unit Cooling water pumps Number of units Consumption per unit kW 3.6 7.5 Quantity 40 50 50 kW 0.09 0.15 0.39 4.0 kW 0.9 1.6 Quantity 4 4 4 kW 0.23 0.40 1.00 6.4 kW 0.5 2.4 Quantity 4 4 4 Consumption per unit kW 0.12 0.59 1.60 Cooling unit kW 21.4 48.0 87.6 % 5.7% 6.9% 8.5% kW 26.4 59.5 117.5 Glycol pumps Number of units Average power consumption (1/JAZ) Air conditioning system Power supply UPS losses kW 5.0 9.6 14.4 Power distribution losses kW 3.2 12.6 28.7 Power supply kW 8.3 22.2 43.1 Total power consumption kW 34.6 81.7 160.6 EUR ('000) 37.9 89.4 175.8 Annual energy costs Figure 50: Power consumption and energy costs for row cooling EUR per MWh 125 Average power consumption Partial load operation Unit 30% 60% 90% 22.3 Air conditioning system Air recirculation units Number of units Consumption per unit Cooling water pumps Number of units Consumption per unit kW 2.2 7.9 Quantity 5 6 6 kW 0.43 1.31 3.71 4.3 kW 0.8 1.5 Quantity 4 4 4 kW 0.19 0.38 1.08 6.5 kW 0.5 2.4 Quantity 4 4 4 Consumption per unit kW 0.12 0.59 1.61 Cooling unit kW 12.7 26.0 49.7 % 3.4% 3.8% 4.8% kW 16.1 37.7 82.7 Glycol pumps Number of units Average power consumption (1/JAZ) Air conditioning system Power supply UPS losses kW 5.0 9.6 14.4 Power distribution losses kW 3.2 12.2 27.7 Power supply kW 8.2 21.8 42.2 Total power consumption kW 24.2 59.6 124.9 EUR ('000) 26.5 65.2 136.8 Annual energy costs Figure 51: Power consumption and energy costs for room-based cooling In the case of smaller thermal loads, room-based cooling is best. However, for higher loads, rack-based cooling is most efficient. For subsequent consideration of TCO, the cost of energy is assumed to be constant; yet, in practical scenarios, particularly in Germany, an annual price increase would need to be factored in to obtain more precise figures. 33 6.4 Maintenance Costs The expected maintenance costs over a period of 10 years, including precautionary replacement of wearing parts (fans, filter mats, etc.), if available, are approximately as follows: Maintenance Number of units Total Rack Row Qty. 100 50 Room 6 EUR ('000) 100 350 150 Figure 52: Maintenance costs for recirculation air conditioning system The passive cabinet rear door cooling units do not have fans or motor-driven valves. This simplifies maintenance requirements considerably since wearing parts do not need to be replaced. Overall, despite the fact that there are a larger number of units, maintenance costs are significantly reduced. 7. TCO – 10-Year Comparison As previously stated in the Preamble, this study considers only the additional investment costs incurred as a direct result of procuring the recirculating air conditioning solution. This comparison is thus based only on a partial TCO, comprised of the sum of these additional costs, including energy and maintenance costs over a 10-year period. All air recirculation solutions would be housed in the same building envelope. Additional costs, due to a greater height between floors, would thus not be incurred. TCO Rear door Unit 30% 60% Invest EUR ('000) 550 550 550 Energy costs over 10 years EUR ('000) 436 875 1,495 Partial load operation 90% Maintenance costs over 10 years EUR ('000) 100 100 100 TCO over 10 years EUR ('000) 1,086 1,525 2,145 Unit 30% 60% Invest EUR ('000) 573 573 573 Energy costs over 10 years EUR ('000) 379 894 1,758 TCO Partial load operation Rows 90% Maintenance costs over 10 years EUR ('000) 310 310 310 TCO over 10 years EUR ('000) 1,262 1,777 2,641 Unit 30% 60% Invest EUR ('000) 520 520 520 Energy costs over 10 years EUR ('000) 265 652 1,368 TCO Partial load operation Room 90% Maintenance costs over 10 years EUR ('000) 150 150 150 TCO over 10 years EUR ('000) 935 1,322 2,037 Figure 53: TCO comparison for rack, row, and room-based cooling with 30/60/90 percent load In this example, the break-even point between rear door and room-based cooling is just over 10 kW per rack. Row cooling is more expensive in terms of overall costs and tends to be used for smaller projects (up to approximately 20 racks). In a particular project with specific boundary conditions, the decision to use a certain ventilation system may not be taken based only on the “lowest TCO” criterion, but considering all project-specific boundary conditions. 34 Table of Figures Figure 1: Figure 2: Figure 3: Figure 4: Figure 5: Figure 6: Figure 7: Figure 8: Figure 9: Figure 10: Figure 11: Figure 12: Figure 13: Figure 14: Figure 15: Figure 16: Figure 17: Figure 18: Figure 19: Figure 20: Figure 21: Figure 22: Figure 23: Figure 24: Figure 25: Figure 26: Figure 27: Figure 28: Figure 29: Figure 30: Figure 31: Figure 32: Figure 33: Figure 34: Figure 35: Figure 36: Figure 37: Figure 38: Figure 39: Figure 40: Figure 41: Figure 42: Figure 43: Figure 44: Figure 45: Figure 46: Figure 47: Figure 48: Figure 49: Figure 50: Figure 51: Figure 52: Figure 53: Site/basic design data.............................................................................................................................. 4 Topology in accordance with Category C; source: BITKOM............................................................. 4 Room layout for cabinet door cooling (hot/cold aisles in red/blue).......................................... 5 Vertical section of computer room.................................................................................................... 5 Conventional chilled water-based cooling air conditioning system.......................................... 6 Units in the air conditioning system.................................................................................................... 6 Schematic diagram of data center infrastructure.......................................................................... 7 Characteristic curve of a typical EC fan........................................................................................... 10 Typical pump curves (WILO Stratos GIGA 65/1-38/3,8)....................................................................... 11 Typical temperatures in the data center air conditioning system.............................................. 12 Annual "dry bulb" temperature profile, Frankfurt.......................................................................... 13 Cooling based on ambient temperature............................................................................................ 13 Chiller power consumption with cooling water at 20/26°C; 170 kW partial load operation.... 14 Liebert HPC Chiller FG0 030 data sheet................................................................................................ 14 Annual energy consumption for the Liebert FG0 030 at 20/26°C in partial load operation..... 15 Typical chiller – power consumption relative to load.................................................................. 15 Schematic diagram of operating data............................................................................................... 16 Knürr DCD rear door cooling unit.................................................................................................... 17 Knürr DCD specification........................................................................................................................ 17 Nominal data for Knürr DCD at 1.8 m3/h cooling water volume flow........................................ 18 Operating data for passive cabinet rear door cooling unit......................................................... 18 Room layout for cabinet door cooling system.............................................................................. 18 Vertical section of the floor for rack-based cooling.................................................................. 19 Overview of operating data for rear door cooling unit at 30 percent load............................ 19 Overview of operating data for rear door cooling unit at 60 percent load............................ 20 Overview of operating data for rear door cooling unit at 90 percent load............................ 20 Knürr DCL-H hybrid solution............................................................................................................... 21 Knürr DCL-H specification..................................................................................................................... 22 Nominal data for Knürr DCL-H row-based cooling unit................................................................ 22 Design and operating data for row-based cooling system.......................................................... 23 Room layout for row-based cooling system................................................................................... 23 Vertical section of the floor for row-based cooling................................................................... 23 Overview of operating data for row-based cooling system at 30 percent load...................... 24 Overview of operating data for row-based cooling system at 60 percent load...................... 24 Overview of operating data for row-based cooling system at 90 percent load...................... 25 Liebert PCW recirculating air conditioning unit............................................................................. 26 Liebert PCW Extended Down - specification....................................................................................... 26 Liebert PH201EL performance data...................................................................................................... 27 Operating data for recirculating air conditioning units............................................................. 27 Room layout for room-based cooling system................................................................................. 28 Vertical section of the floor for room-based cooling................................................................ 28 Overview of operating data for room-based cooling at 30 percent load................................. 28 Overview of operating data for room-based cooling at 60 percent load................................. 29 Overview of operating data for room-based cooling at 90 percent load................................. 29 Comparison of investment for rack, row, and room-based cooling systems.......................... 30 Overview of operating data for rear door cooling...................................................................... 31 Overview of operating data for row cooling................................................................................. 31 Overview of operating data for room-based cooling................................................................... 32 Power consumption and energy costs for rear door cooling .................................................. 32 Power consumption and energy costs for row cooling ............................................................. 33 Power consumption and energy costs for room-based cooling .............................................. 33 Maintenance costs for recirculation air conditioning system.................................................. 34 TCO comparison for rack, row, and room-based cooling with 30/60/90 percent load........... 34 35 Abbreviations and Acronyms COP Coefficient of performance CRAC Computer room air conditioning unit CW Cooling water EC fan Electronically commutated fan EER Energy efficiency ratio EUREuro FM Facility management ICT Information and communication technology IT Information technology PUE Power usage effectiveness RACU Recirculating air conditioning unit rpm Revolutions per minute SPF Seasonal performance factor TCO Total cost of ownership UPS Uninterrupted power supply 36 List of References BITKOM - German Federal Association for Information Technology, Telecommunications and New Media (17 April 2012). Reliable Data Centers planning aid. Berlin-Mitte, Berlin, Germany. Emerson Network Power – Racks and Solutions (2011). Optimierte Energieeffizienz durch geregelte Kaltgangeinhausungen. [Optimized energy efficiency through regulated cold aisle enclosures.] Arnstorf, Bavaria, Germany. Emerson Network Power (October 2012). Liebert PCW – Cool the Cloud. Piove di Sacco, Italy. Emerson Network Power EMEA (November 2013). Knürr DCD – Kühltür für höchste Energieeffizienz: 35kW Kühlleistung. [Cooling door for optimum energy efficiency: 35 kW cooling capacity.] Arnstorf, Bavaria, Germany. Emerson Network Power EMEA (November 2013). Knürr DCL – Modulare Rack-Kühlung von 6 bis 60kW. [Modular Rack Cooling from 6kW to 60 kW.] Arnstorf, Bavaria, Germany. Koch, D. P. (22 October 2013). Effiziente Kühlsysteme für Hochleistungsrechner. [Efficient cooling systems for high-performance computers.] Arnstorf, Bavaria, Germany. 37 Ensuring The High Availability Of Mission-Critical Data And Applications. About Emerson Network Power Emerson Network Power, a business of Emerson (NYSE:EMR), delivers software, hardware, and services that maximize availability, capacity, and efficiency for data centers, health care, and industrial facilities. A trusted industry leader in smart infrastructure technologies, Emerson Network Power provides innovative data center infrastructure management solutions that bridge the gap between IT and facility management and deliver efficiency and uncompromised availability regardless of capacity demands. Our solutions are supported globally by local Emerson Network Power service technicians. Learn more about Emerson Network Power products and services at www.EmersonNetworkPower.eu Locations Emerson Network Power Global Headquarters 1050 Dearborn Drive P.O. Box 29186 Columbus, OH 43229, USA T +1 614 8880246 Emerson Network Power Racks and Solutions Europe Middle East And Africa Mariakirchener Straße 38 94424 Arnstorf Germany T +49 8723 27 0 F +49 8723 27 154 knuerr@emerson.com Emerson Network Power United Kingdom George Curl Way Southampton SO18 2RY, UK T +44 (0)23 806 1 0311 F +44(0)23 8061 0852 While every precaution has been taken to ensure accuracy and completeness in this literature, Emerson assumes no responsibility for content, and disclaims all liability for damages resulting from use of this information or for any errors or omissions. Technical data are subject to change without notice. 1101.150.126 MKA4L0ENWP Rev.1.03-06/2014 Globe Park Fourth Avenue Marlow Bucks, SL7 1YG Tel: +44 1628 403200 Fax: +44 1628 403203 UK.Enquiries@Emerson.com Follow us on Social Media: EmersonNetworkPower.eu Emerson. Consider it Solved, Knürr®, Liebert®, Emerson Network Power and the Emerson Network Power logo are trademarks or service marks of Emerson Electric Co. or its affiliated companies. ©2014 Emerson Electric Co. All rights reserved.