® SOUTHEASTERN PENNSYLVANIA TRANSPORTATION AUTHORITY 1234 MARKET STREET PHILADELPHIA, PENNSYLVANIA 19107 Title: Standard Specification for General Purpose Distribution Transformers Number: SPEC00091 Revision: 001 I. General A. Scope 1) This Specification applies to dry-type transformers for power distribution; typically 3phase, delta-wye, 13.2/4.8 KV primary, 480/277 V secondary, 60 Hz, 500 KVA. Any deviation from these typical characteristics will be detailed in the Bid Request and Purchase Order. 2) Transformers of Vacuum Pressure Impregnation (VPI) or Vacuum Pressure Encapsulated (VPE) construction are anticipated. Open-wound "dip-and-bake" construction is specifically prohibited. 3) This Specification covers the design, manufacturing, testing, and furnishing of all materials, equipment, labor, transportation, permits, equipment, machinery, tools, appliances, and all other facilities or incidentals necessary for the delivery of the transformer. 4) SEPTA will prepare the site for the installation of the new transformer, including new cabling, and will perform the installation of the new transformer. 5) SEPTA will electrically connect and perform in situ testing of the new transformer. B. References The design, manufacturing, testing, and operation of the transformers shall comply with the applicable portions of the latest edition of the relevant standards and codes promulgated by: a) NEMA - National Electrical Manufacturers Association b) ANSI - American National Standards Institute c) IEEE - Institute of Electrical and Electronics Engineers d) ASTM - ASTM International e) NEC - National Electrical Code f) NESC - National Electrical Safety Code g) OSHA - Occupational Safety and Health Administration h) EPA - Environmental Protection Agency i) NETA - National Electrical Testing Association j) AREMA - American Railway Engineering and Maintenance-of-Way Association Page 1 of 7 SOUTHEASTERN PENNSYLVANIA TRANSPORTATION AUTHORITY Number: SPEC00091 Standard Specification for General Purpose Distribution Transformers Revision: 001 Title: k) local codes C. Vendor Qualifications 1) The engineering and manufacturing of the transformer shall be by a firm which is certified to comply with an internationally-recognized quality management system, e.g. ISO9001:2008. 2) The vendor shall have not less than five years' experience in the production of drytype distribution transformers. This requirement is waived if substantially identical equipment has been furnished to SEPTA and has been in satisfactory service for a minimum of two years. D. Submittals Submit the following to SEPTA's Engineer for review and approval. The review and approval of a submission, in part or in whole, shall not constitute acceptance of any errors, omissions, changes, or other deviations from this specification. Wherever possible, submittals shall be text-searchable .pdf files. References or hyperlinks to information on the internet are not acceptable. 1) Product data consisting of manufacturer's catalog sheets, descriptive literature, specifications, diagrams and drawings in sufficient detail to clearly indicate compliance with all specified equipment and standards. 2) Operation and Maintenance manuals. 3) A nameplate drawing showing all tap connections and required nameplate data. 4) Dimensions and weight of the transformer. 5) Electrical schematic drawings. 6) Results of all tests for the transformer. 7) The guaranteed core and winding losses at 50%, 75%, and 100% of full load of the transformer. This information must also be submitted with the shop drawings. E. Quality Assurance 1) Transformers shall be standard products, or equivalent to the standard products, of manufacturers engaged in the production of such equipment for at least the past 5 years. 2) The transformer shall be designed and manufactured for a minimum 40-year life. 3) Any transformer that has been damaged during any testing will not be accepted. II. Products A. Technical Description Page 2 of 7 SOUTHEASTERN PENNSYLVANIA TRANSPORTATION AUTHORITY Number: SPEC00091 Standard Specification for General Purpose Distribution Transformers Revision: 001 Title: Unless otherwise specified on the Purchase Order, the transformer's ratings shall be: 1) Frequency of Operation: 60 Hz ±5 2) Primary Voltage: 13,200/4,800 VAC, 3 phase, delta 3) Secondary Voltage: 480/277 VAC, 3 phase, wye 4) Power Rating: 500 KVA 5) Efficiency: 99.4% minimum at rated KVA 6) Regulation: 3% maximum at 95% Power Factor 7) Taps: The transformer's High Voltage (primary) side winding shall be provided with five sets of taps as follows. These taps are intended for operation only when the transformer is de-energized. a) for an input voltage 5% above nominal b) for an input voltage 2.5% above nominal c) for a nominal input voltage d) for an input voltage 2.5% below nominal e) for an input voltage 5% below nominal 8) BIL: The Basic lightning Impulse insulation Level (BIL) for the High Voltage (primary) winding shall be 110 KV. The Low Voltage (secondary) winding shall have a BIL of 45 KV. 9) The insulation class of the primary shall be 15 KV, and the insulation class of the secondary shall be 600 V. 10) Design equipment to operate as a fully integrated system and within the space limitation to provide protection and reliability of equipment and the system against accidental system failures and mechanical or electrical failures. Minimum clearances of live parts shall be shown on the shop drawings. The equipment arrangement and equipment part locations shall be as shown on the drawings and schematics submitted by the vendor. The clearances of the live parts and workspace of the supplied equipment shall not be less than those on the drawings. The design of the equipment shall provide features for the safety of personnel during installation, operation and maintenance. 11) The transformer shall be suitable for both operation and storage, including prolonged storage, at 100% humidity and at ambient temperatures from -30 °C to +40 °C. 12) The average winding temperature rise shall not exceed +80 °C above an ambient temperature of 40 °C at the rated KVA of the transformer. (The winding temperature Page 3 of 7 SOUTHEASTERN PENNSYLVANIA TRANSPORTATION AUTHORITY Number: SPEC00091 Standard Specification for General Purpose Distribution Transformers Revision: 001 Title: shall be measured by a rise-of-resistance method.) Any bus or wiring connection shall have at least the same thermal limit characteristics as the transformer windings. 13) Percent Impedance (%Z): 5.5% ±0.4125, i.e.: 5.0875% ≤ %Z ≤ 5.9125% 14) Sound Level: The sound level shall not exceed the NEMA recommended value. B. Equipment Components, Construction, and Painting 1) Except as otherwise indicated, provide the transformer of type, size, characteristics, and ratings as indicated, which comply with manufacturer's standard design, materials, components, and construction in accordance with published product information, and as required for a complete and functional installation. 2) The transformer shall be suitable for indoor application (NEMA 1), finished with ANSI #61 Gray paint over phosphatized surface. The structural framework and enclosure shall be sufficiently rigid to withstand any stresses due to short circuit currents or transformer weight during transportation. 3) Provisions shall be made for jacking, lifting, skidding, as well as anchoring the enclosure to the foundation. 4) All iron parts of the core coil assembly, except the core itself, shall be hot-dipped galvanized after fabrication, or shall otherwise be protected from corrosion. 5) Proper clearances shall be maintained between primary and secondary connections and transformer core (grounded) to prevent any arcing or fault. The submittal of shop drawings must indicate the specific clearances for the transformer. A separate copper grounding bus section shall be provided. 6) Provisions shall be made for lifting the whole transformer by a crane. 7) The transformer shall include a winding temperature sensor, two stage, with Form C contacts rated at 125 VDC, 1 Ampere, for separate and independent indications of each stage. 8) Windings: Both high and low voltage windings shall be of copper conductors. The estimated full load winding loss shall be quoted in the shop drawing submittal and as information to the bid evaluation package. The transformer winding design shall take into account the high voltage stresses caused on the insulation system due to lightning and switching surges on the system. The winding insulation shall be adequate to withstand the thermal and mechanical stresses which may be caused due to transient and sustained overloads or short circuits. 9) Terminals and Connections: a) Proper spacing and heights shall be maintained for entry and exit of the cable connections. Proper clearances shall be maintained between primary and Page 4 of 7 SOUTHEASTERN PENNSYLVANIA TRANSPORTATION AUTHORITY Number: SPEC00091 Standard Specification for General Purpose Distribution Transformers Revision: 001 Title: secondary connections and transformer core (grounded) to prevent any arcing or fault. C. Nameplate: Nameplate data shall specify rated KVA, frequency, phase, taps, manufacturer's serial number, style, form, polarity, impedance, decibel rating, temperature rise, and weight of the transformer (total weight, core and coil weights). A nameplate drawing shall be submitted with the shop drawings. D. Factory Test / Performance Test Data The vendor shall perform the following tests. The vendor's test procedures and test results are subject to the approval of the Engineer. SEPTA reserves the right to send one representative for witnessing actual factory tests at SEPTA's expense. Should SEPTA elect to witness any tests, the vendor shall not increase the cost above that in the quotation. The vendor shall notify SEPTA at least four weeks prior to the performance of the tests. The tests below marked with an asterisk (*) shall be witnessed by SEPTA. 1) Ratio Tests - on all tap connections 2) Phase Sequence/Polarity Test 3) Resistance of all windings on the rated voltage tap connections 4) Excitation current at rated voltage and different tap connections, where applicable. 5) *No-load loss at rated voltage and rated frequency. 6) *Impedance and full load loss at rated current on the rated voltage tap connection and rated frequency. 7) Insulation resistance test. 8) *Dielectric withstand test to demonstrate the adequacy of the transformer insulation. The test shall be carried out for both: a) Applied potential b) Induced potential 9) *Impulse Test: The tests shall verify the BIL rating specified. The impulse test shall be carried out for full wave, reduced wave, and chopped wave. The tests shall be performed on fully-assembled transformer, complete with enclosure. 10) *Partial Discharge Test: This test shall be performed on a fully-assembled transformer, complete with enclosure. This test may be performed in conjunction with the Dielectric Withstand Test. 11) *Power Factor Test 12) *Temperature Rise Test Page 5 of 7 SOUTHEASTERN PENNSYLVANIA TRANSPORTATION AUTHORITY Number: SPEC00091 Standard Specification for General Purpose Distribution Transformers Revision: 001 Title: 13) Percent regulation at 85%, 90%, and 95% Power Factor 14) Efficiency at 50%, 75%, and 100% loads. The vendor shall bear the responsibility for any deviation from the quoted losses of the transformer. SEPTA reserves the right to reject the transformer for any deviation exceeding the quoted losses. E. Patented or Copyrighted Material In the event that any equipment or system delivered to SEPTA under this specification shall be protected by any patent or copyright, the manufacturer shall defend, indemnify, and save harmless SEPTA from any and all suits, claims, judgments, costs, and causes of action at law or in equity arising out of or related to the sale, purchase, or use of any such article, which sale, purchase, or use is alleged to be in violation of any rights under a patent or copyright. F. Delivery Delivery shall be to the address noted in the Bid Request and Purchase Order. The vendor shall notify SEPTA at least two (2) working days before delivery. G. Warranty The vendor shall warrant the transformers supplied to be free from defects in workmanship and material for a period of four years from the date of final equipment acceptance by SEPTA. The warranty shall cover manufacturing and design defects, labor, material, and the cost of replacement installation. During this period, the vendor shall replace all items or components which fail, at no cost to SEPTA. III. Execution A. Installation SEPTA will install the transformer per the manufacturer's installation instructions. B. Field Tests 1) Prior to energizing, SEPTA will perform the insulation resistance (meggering) and dielectric strength (hipotting) at the voltage level recommended by the manufacturer, and will check primary and secondary terminations, and equipment grounding. 2) SEPTA will be responsible to check the proper operation of the transformer during commissioning, within the specified parameters recommended by the manufacturer. 3) If any failure occurs during field tests, the vendor shall bear the full cost of retesting the transformer. Page 6 of 7 SOUTHEASTERN PENNSYLVANIA TRANSPORTATION AUTHORITY Number: SPEC00091 Standard Specification for General Purpose Distribution Transformers Revision: 001 Title: Revision Control: Revision Number 001 Description of Change Original Release Approved by: Date: David T. Montvydas 09/17/2015 002 003 004 005 006 Page 7 of 7