ELECTRICAL TEST ANSWERS May 21, 2003 1. A Class 1 signaling circuit shall not exceed ______________ volts. A. 130 B. 150 C. 220 þ D. 600 National Electrical Code, Section 725-21(b) 2. Motors and their associated equipment must be protected against overcurrent (overload, shortcircuit, or ground-fault), but because of the special characteristics of induction motors, overcurrent protection is generally accomplished by having the overload protection separate from the short-circuit and gro und-fault protection. þ A. True National Electrical Code, Section 430-32, 430-52 B. False 3. In multiwire circuits, the continuity of the ___________ conductor shall not be dependent upon the device connections. A. ungrounded þ B. grounded National Electrical Code, Section 300-13(b) C. grounding D. A and B 4. The __________ is defined as the area between the top of the direct burial cable and the finished grade. A. notch þ B. cover National Electrical Code, Section 300-5 Table of the heading C. gap D. none of these 5. What is the power consumed of a 10kW heat strip rated 230 volts connected to a 115-volt circuit? A. 10 kW þ B. 2.5 kW C. 5 kW D. 20 kW R = E2/PR = 230 volts R = 230 volts2/10,000 watts R = 5.29 ohm P = E2/R = 115 volts P = 1152/5.29 ohm P = 2,500 watts/1,000 = 2.5 kW