Module Set: PUHY-HP192TSHMU-A Job Name: Drawing Reference: Schedule No. System No.: FeAtuReS • Innovative flash technology enables tremendous heating capacity at lower outdoor temperatures • Exhibits 100% of rated heated capacity at 5ºF; 87% of rated heating capacity at -4ºF • Inverter-driven (variable speed) scroll compressor • Reduced defrost time • Modular variable refrigerant flow zoning (VRFZ) systems combine two outdoor units • Compact size • Required Twinning Kits (sold separately) to allow for easy field piping connection Module Set SPeCIFICAtIoNS Power Source………..……………..208 / 230V, 3-phase, 60Hz Capacity Cooling……………………....………………………192,000 Btu/h Power Input……………………………………….......17.98 kW Current (208 / 230)……………………………….55.5 - 50.2 A Heating...…………………....………………………216,000 Btu/h Power Input…………………………………………...18.81 kW Current (208 / 230)……………………………….58.1 - 52.5 A CItY MultI Indoor unit Total Capacity…………..50% - 130% of Outdoor Unit Capacity Model / Quantity…………………….…………..P06-P96 / 1 ~ 24 Sound level (Cooling/Heating)...……..…..........……60 dB(A) 65 dB(A) if heating at -5°F (-21°C) outdoor temperature operating temperature Range Cooling (Outdoor)………………..23°F ~ 109°F (-5 ~ +43°C) DB Heating (Outdoor)…………….-13°F ~ +60°F (-25 ~ +16°C) WB PIPING dIAMeteR (FRoM tWINNING KIt to INdooR uNItS Liquid (High Pressure)………………….5/8" / 15.88 mm Brazed Gas (Low Pressure)………………….1-1/8" / 28.58 mm Brazed outdooR uNItS 1 and 2 (SPeCIFICAtIoNS FOR EACH PuHY-HP96tHMu-A uNIt) electrical Power Requirements Minimum Circuit Ampacity (MCA)*……………………........71.0 A Maximum Overcurrent Protection (MOCP) Fuse*..…...........75 A * Each unit must be wired separately. external Finish………….Pre-coated Galvanized Steel Sheets Munsell No.: 5Y 8 / 1 external dimensions Inches………………………….......65 h x 36-1/4 w x 29-15/16 d mm…………………………………….....1,650 h x 920 w x 760 d Net Weight………………..…...…………….......486 lbs. / 220 kg Piping diameter (From outdoor unit to twinning Kit) Liquid (High Pressure)…..………3/8" / 9.52 mm Brazed + Flare Gas (Low Pressure)……………..………7/8" / 22.22 mm Brazed Fan Type x Quantity………………………………....Propeller Fan x 1 Airflow Rate……………………………....……………….7,950 cfm Motor Output………………………………………......…...0.92 kW Compressor Type…………………………….....Inverter-driven Scroll Hermetic Motor Output………………………………………......……..6.7 kW Case Heater……………………………………………….0.057 kW Refrigerant………………..…...…………….…………......R410A lubricant………………..…...…………….…………........MEL32 Protection devices High Pressure Protection………..………......601 psi / 4.15 MPa Compressor / Fan….Discharge Thermo / Overcurrent Protection Inverter……..Overcurrent / Overheat Protection, Thermal Switch Anti-corrosion Protection Blue Fin treatment applied to condenser coil protects coil from air contaminants. oPtIoNS □ Twinning Kit**…………………………………………CMY-Y100VBK2 □ T-Branch Joint (≤ 72,000 Btu/h)………………..........CMY-Y102S-G2 □ T-Branch Joint (≤ 144,000 Btu/h)……………….…....CMY-Y102L-G2 □ T-Branch Joint (≤ 234,000 Btu/h)……………….......CMY-Y202S-G2 □ Header (4-Branch; ≤ 72,000 Btu/h)........……………...CMY-Y104-G □ Header (8-Branch; ≤ 144,000 Btu/h)......………………CMY-Y108-G □ Header (10-Branch; ≤ 234,000 Btu/h)....………………CMY-Y1010-G ** Twinning Kit is necessary to combine the refrigerant flows of the outdoor units. Module Set: PUHY-HP192TSHMU-A – DIMENSIONS 920(36-1/4) Discharge air Outdoor unit 1 1650(64-31/32) 760(29-15/16) Intake air 30(1-3/16) Outdoor unit 2 Intake air Intake air Left view Twinning pipe connection size Package unit name Component unit name Outdoor unit 1 Outdoor unit 2 Outdoor Twinning Kit(optional parts) Liquid a Indoor unit Twinning pipe Gas b 920(36-1/4) e c f d PUHY-HP144TSHMU-A(-BS) PUHY-HP192TSHMU-A(-BS) PUHY-HP96THMU-A(-BS) PUHY-HP72THMU-A(-BS) PUHY-HP96THMU-A(-BS) PUHY-HP72THMU-A(-BS) CMY-Y100VBK2 15.88(5/8) 28.58(1-1/8) b To indoor unit Gas Twinning pipe<optional parts> Front view Unit model Twinning pipe Outdoor unit P72 P96 Liquid c or e a To indoor unit Liquid Twinning pipe<optional parts> Gas d or f 9.52(3/8) 19.05(3/4) 9.52(3/8) 22.2(7/8) Note 1.Connect the pipes as shown in the figure above. Refer to the table above for the pipe size. 2.Twinning pipes should not be tilted more than 15 degrees from the ground. See the Installation Manual for details. Unit : mm(in) Inches (mm) <Reducer Pipe (Accessory)> 7-1/4 (183) OD ø 1 (25.4) 6-5/16 (160) ID ø 7/8 (22.2) OD ø 1-1/8 (28.58) ID ø 7/8 (22.2) OD ø 5/8 (15.88) ID ø 1/2 (12.7) ID ø 1/2 (12.7) ID ø 5/8 (15.88) OD ø 1/2 (12.7) 13-1/2 (342) 23-3/16 (588) ID ø 3/8 (9.52) OD ø 5/8 (15.88) 1-15/16 (49) OD ø 7/8 (22.2) 3-5/16 (83) ID ø 1-1/8 (28.58) OD ø 1/2 (12.7) 3-7/8 (98) 19-15/16 (505) OD ø 1/2 (12.7) 2-1/2 (62) ID ø 1/2 (12.7) 1-15/16 (49) ID ø 1-1/8 OD ø 7/8 (28.58) (22.2) ID ø 3/4 (19.05) 2-1/2 (62) OD ø 1 (25.4) 9-1/2 (241) For instructions on piping the units together using the twinning kit, see the Installation Manual. (1) (2-3/16) 760 (29-15/16) (1) 25 Left side view 25 55 54 (2-5/32) A (2-3/16) 55 B Refrigerant service valve <gas> Refrigerant service valve <liquid> 204 (9-29/32) 251 (8-1/16) 1 Front view (4-1/32) 102 98 (3-7/8) 6 5 80 (3-5/32) 760 (29-15/16) 80 Refrigerant service valve <gas> Bottom view Intake air 1650 (64-31/32) Unit : mm(in) NO. For transmission cables For wires For pipes Usage Gas 19.05 Brazed (3/4) 22.2 Brazed (7/8) Liquid Multiple unit 9.52 Flare installation (3/8) (Single unit ( 12.7 Brazed) installation) (1/2) Connection specifications for the refrigerant service valve *1 Indicates the dimensions for use with the pipe that is supplied. *2 Indicates dimensions and connection specifications appropriate to installing the unit as a single unit. Position dimensions for the refrigerant service valve Liquid Gas B *1 A C 161 290 145 PUHY-HP72THMU (6-11/32) (5-23/32) (11-7/16) (242) *2 142 165 PUHY-HP96THMU (9-17/32) (5-19/32) (6-1/2) Model Connecting pipe specifications Front access hole Bottom access hole Front access hole Front access hole Bottom access hole Front access hole Specifications 102 X 72 Access hole (4-1/32)(2-27/30) 150 X 92 Access hole (5-29/32)(3-5/8) 65 or 40 Access hole (2-9/16) (1-19/32) 52 or 27 Access hole (2-1/16) (1-3/32) 52 Access hole (2-1/16) 34 Access hole (1-11/32) Note. Refer to the Installation Manual for information regarding necessary clearance around the unit and foundation. <Accessories>(Supplied only with the unit listed below) Connecting pipe <gas> 1 pc. PUHY-HP72THMU Models Packaged with other accessories PUHY-HP96THMU Models Mounted on the refrigerant service valve Connecting pipe <liquid> 1 pc. PUHY-HP72,96THMU Models Packaged with other accessories (For standalone use) Packing for connecting pipe <gas> 1 pc. Mounted adjacent to the refrigerant service valve on the gas side PUHY-HP72,96THMU Models 2X2-14(9/16)X20(13/16) Oval hole Service panel (Mounting pitch) (3-5/32) 2 (8-23/32) 221 150 (5-29/32) (9-29/32) 251 83 (3-9/32) (7-11/32) 186 3 4 Refrigerant service valve <liquid> 131 (5-3/16) Intake air Control box 72 90 Intake air (5-7/32) 132 88 (3-15/32) 145 (5-23/32) Top view C (2-27/32) (3-13/32) 920 (36-1/4) (28-17/32) (23/32) Discharge air (760) (29-15/16) (3-9/16) 86 92 760 (29-15/16) 18 724(721 727) 18 (28-13/32 28-5/8) (23/32) (3-5/8) 240 (9-15/32) 1410 (55-17/32) (Mounting pitch) Outdoor Units 1 and 2: PUHY-HP96THMU-A – DIMENSIONS NOTES Mitsubishi Electric Air Conditioning & Refrigeration Systems Works acquired ISO 9001 certification under Series 9000 of the International Standard Organization (ISO) based on a review of quality warranties for the production of refrigeration and air conditioning equipment. Certificate Number FM33568 ISO Authorization System The ISO 9000 series is a plant authorization system relating to quality warranties as stipulated by the ISO. ISO 9001 certifies quality warranties based on the "design, development, production, installation and auxiliary services" for products built at an authorized plant. Mitsubishi Electric Air Conditioning & Refrigeration Systems Works acquired environmental management system standard ISO 14001 certification. The ISO 14000 series is a set of standards applying to environmental protection set by the International Standard Organization (ISO). Certificate Number EC97J1227 C SD - PUHY-HP192TSHMU-A - 1 - 200712 © MITSUBISHI ELECTRIC / HVAC 2007 HVAC Advanced Products division Mitsubishi Electric & Electronics USA, Inc. 3400 Lawrenceville Suwanee Rd. Suwanee, GA 30024 Tele: 678-376-2900 • Fax: 800-889-9904 Toll Free: 800-433-4822 (#4) www.mehvac.com Specifications are subject to change without notice.