1.
2.
3.
STANILITE
Doc No: 29-HPSP001
Cut off the main power first.
Do not touch LEDs while maintaining or cleaning.
Do not use chemicals to clean the fixture.
Thomas & Betts (Australasia) Pty. Ltd. ABN: 062 074 810 898
Head Office: Unit D3, 3-29 Birnie Avenue, Lidcombe NSW 2141, Australia
Manufacturing: 23a Nyrang Street, Lidcombe NSW 2141, Australia
Phone: 1300 666 595 Fax: 1300 666 594 Email: austsales@tnb.com Website: www.tnbaust.com
Environmental protection; waste electrical products
should not be disposed of with household waste.
Please recycle where facilities exist. Check with your
local authority or retailer for recycling advise.
e-Luna Circular LED IP20
Installation Manual
REMOVAL INSTRUCTIONS
1.
2.
3.
4.
5.
Before removing the fitting, de-energise and lock off the supply circuit.
Twist the diffuser in the anti-clockwise direction and remove it, see figure 1.
This step is for emergency version only; disconnect the battery connection from the power pack.
Remove the mains supply cables from the terminal block.
Unscrew the mounting screws and remove the housing.
Note: When the fitting is reconnected to the supply, it will need 24 hours charging time before it will be capable of a full duration discharge.
TESTING PRECAUTIONS
Once the fitting is permanently connected to the mains supply, a commissioning discharge test as required in AS/NZS2293.2 must be
carried out. You will need to allow 24 hours for the battery to fully charge prior to conducting this test, presently (at the time of writing),
the standard requires that fittings operate in emergency mode for a period not less than 2 hours for their commissioning test and for
not less than 90 minutes thereafter (it is required that 6 monthly discharge tests be carried out). You will need to keep the records for
the commissioning test and enter them into the building emergency services logbook or via other recording methods as allowed by
AS/NZ2293.2.
CONSTRUCTION SITES
Continuously switching of the mains power supply that is connected to emergency light fittings during the construction phase of an
installation will cause these fittings to discharge and charge their batteries many times over a short period; this can shorten the life of the
battery and will also result in shortened emergency lamp life for fluorescent fittings. Thomas & Betts does not recommend such practices
and may not honour the warranty on batteries when they are subjected to such harsh operating conditions. Emergency light fittings are
designed to be discharge tested once every 6 months as per AS/NZS2293.2, subjecting the product to repeated discharge or charge
cycles is regarded as an abuse of the fittings.
TROUBLE SHOOTING GUIDE
If you have installed and connected the unit as per the instructions listed earlier and it does not function correctly, use the following table
as a guide to fixing the problem. Look up the type of fault in the left column and check the possible causes from the right column.
#
Fault
Possible Causes
1
LED light source and indicating LED not lit
AC supply not connected or turned off; and/or
Test switch damaged
2
LED light source is lit but indicating LED not lit
Test switch damaged; or
Battery not connected or faulty; or
USA not connected or turned off
3
LED light source does not illuminate when the test button
is pressed
Test switch damaged; or
Battery not connected or faulty
4
LED light source works momentarily when the test button
is pressed
Battery not yet charged (allow up to 24 hours)
If the unit still does not work after checking these possible causes, contact Thomas & Betts Service in Australia on 1300 666 595, Monday
to Friday, 8.30am to 4.30pm (AEST) and ask for help. Our trained service personnel will usually be able to take your call immediately and
assist you in resolving your difficulty. Thomas & Betts is committed to providing valuable Through-Life Support for its products.
© Thomas & Betts (Australasia) Pty. Ltd. 2016
Rev: B 17 June 2016 4
AC, Emergency
This Document Covers
What’s Inside the box
Safety Warning
e-Luna Circular LED IP20
Installation Instructions
Masonry Wall Plugs & Screws
Removal Instructions
Installation Manual
Testing Precautions
Warranty Information
Trouble Shooting Guide
GREETINGS
Congratulations on choosing to use this Thomas & Betts product covered by our unique Through-Life Support system. This document is
designed to assist you during the installation of this product; for the safety of yourself and others Thomas & Betts recommends
that you read this document thoroughly before commencing installation. The fittings are designed for easy
installation. They are advanced pieces of electronic equipment which, when treated with care and maintained through regular and
appropriate servicing, will perform reliably for many years to come.
SAFETY WARNING
In Australia and New Zealand, only licensed electricians are permitted by law to work with 240 Volt electrical installations.
Do not attempt to install or connect this product unless you are a licensed electrician.
Turn off and isolate the electrical supply before connecting this fitting to the building wires.
Do not touch the terminals of the terminal block when the light fitting is energised.
The only user-serviceable parts are fluorescent or halogen lamp/s. LED light sources are not user-servicable.
Do not tamper with the fitting or the warranty will be void.
As the installer, it is your responsibility to ensure compliance with all relevant building and safety codes, (ie: AS3000, AS/NZS2293).
Refer to the applicable standards for data and mains cabling installation procedures and requirements.
Important Note: This product is designed for indoor use only.
© Thomas & Betts (Australasia) Pty. Ltd. 2016
Rev: B
17 June 2016
1
Complete Solutions in Emergency Lighting STANILITE
Complete Solutions in Emergency Lighting STANILITE
INSTALLATION INSTRUCTIONS
1.
2.
3.
4.
5.
6.
Remove the unit from the packing box and inspect it for damage or imperfections. If any damage is found, do not install the unit,
but replace it carefully into the packing box and notify the Thomas & Betts Product Support Hotline in Australia on 1300 666 595.
If all looks okay, installation can proceed.
Twist the diffuser in the anti-clockwise direction and remove it, see figure 1.
Route the mains cable through the cable entry hole, see figure 2.
Secure the base onto the ceiling or wall using the wall plugs and screws supplied or use appropriate fixings to suit the type of
building construction material, see figure 3.
Strip 9mm insulation length from mains cable, connect and terminate wires to the terminal block. Be careful with multi-strand
conductors that all the strands are twisted together before insertion into the terminal. Any stray strands that inadvertently come
into contact with their neighbouring terminal will cause undesirable results when the fitting is powered. Refer table below and see
figure 4.
7.
8.
9.
Wire/Fitting Type
Maintained - with SA
Non-maintained
Switched active (SA)
Wire to terminal L
Not connected
Unswitched active (A)
Wire to terminal L1
Wire to terminal L1
Neutral (N)
Wire to terminal N
Wire to terminal N
Earth
Wire to terminal E or
Wire to terminal E or
This step is for emergency version only; ensure the battery is connected to the emergency module.
Energise the fitting and check operation to ensure that the installation was successful. Refer to the Trouble Shooting Guide on the
last page if abnormal operation or indication is encountered.
This step is for emergency version only; once powered up allow a few minutes to give the battery a small charge then press the
test button adjacent to the indicator LED. Check the operation and LED indications per the following tables. Refer to the Trouble
Shooting Guide on the last page if abnormal operation or indication is encountered.
Daylight Sensor
The daylight threshold can be set on DIP switches, to fit for particular
application.
Stand-by Period (Corridor Function)
This is the time period you would like to keep at the low light output level
before it is completely switched off in the long absence of people.
Fitting Type
Indicator LED State - on initial powering - no fitting faults
Emergency
Solid green
Fitting Type
Normal Operation
Test Switch Pressed
(after few minutes charging)
AC and emergency
without motion detect
LEDs will illuminate to full brightness when
SA is energised.
LEDs will illuminate at approximately 10% of
mains brightness.
AC and emergency
with motion detect
sensor
The operation of the LEDs in normal mains
availability is dependent on the settings of the
motion detect module. Please refer to Motion
Detect Sensor - Settings section for details.
LEDs will illuminate at approximately 10% of
mains brightness.
Note: “0s” means on/off control;
“+ ” means bi-level dimming control, fixure never switches off.
Stand-by Dimming Level
This is the dimmed low light output level you would like to have after the
hold-time in the absence of people.
DETECTION PATTERN
10. Reinstall the diffuser and turn it clockwise direction to lock in place, see figure 5.
Detection Area
Detection area can be reduced by selecting the combination on the DIP
switches to fit precisely for each specific application.
Hold-time
Hold-time means the time period you would like to keep the lamp on 100%
after the person has left the detection area.
Note: For permanent maintained operation, loop unswitched active (L1) to switched active (L)
© Thomas & Betts (Australasia) Pty. Ltd. 2016
MOTION DETECT SENSOR - SETTINGS
Rev: B
17 June 2016
2
© Thomas & Betts (Australasia) Pty. Ltd. 2016
Rev: B
17 June 2016
3