HEATING CABLE TYPE SCBX
Parallel circuit heating cable - Constant
watt for hazardous areas
Certificate NO SIRA 03 ATEX 3376U
Parallel circuit heating cable is designed to
be cut from reel lengths and site
terminated to suit pipework. The heating
cable consists of a number of short
heating zones, each connected across a
pair of continuous bus-wire conductors.
Each complete heating zone will give its
full rated design output with circuit voltage
applied to the bus-wire conductors.
Construction
The heating cable has a core comprising
two bus-wire conductors contained within
an extruded silicone rubber sheath. The
sheath is notched on alternate sides at
predetermined intervals to expose a short
section of bus-wire conductor.
Nickel-chrome resistance wire is wrapped
at regular spacing around the core as a
continuous conductor, making contact with
the bus-wires at the exposed points.
After completion of the heater conductor
wrapping, a high temperature soldered
joint is made at each contact point
ensuring that a number of conductor
strands are securely bonded to the buswires.
An extruded outer sheath of silicone
rubber is then placed over the core and
heater element to complete the heater
cable assembly.
Bus-wire
conductors
Insulation
Soldered joint
Heating element
Outer sheath
Over Braid (B)
Over Jacket (OJ)
The cable has an earth screen outer braid
of tinned copper or stainless steel.
Where additional protection is required for
corrosive conditions extruded silicone
rubber sheathing can be placed over the
braided cover.
1 (3)
Web: www.ihpheating.com - E-mail: info@ihpheating.com - Phone: +46 (0)31 795 30 30 - VAT: SE556689732701
HEATING CABLE TYPE SCBX
Range
Type
Volts
Watt/m
Heather zone
length (m)
Max circuit length
(m)
SC 8
110
8
1,0
110
SC 12
110
12
1,0
80
SC 16
110
16
1,0
75
SC 20
110
20
1,0
69
SC 30
110
30
1,0
60
SC 8
240
8
1,0
250
SC 12
240
12
1,0
170
SC 16
240
16
1,0
145
SC 20
240
20
1,0
120
SC 30
240
30
1,0
105
Specification
Conductors
Core
Heater element
Solder
Outer sheath
Copper stranded flexible -30/0,25mm (1,5mm²)
Silicone rubber
Nickel-chrome 80-20
High melting point 296°C
Silicone rubber
Width
13,3mm (Braided version)
Thickness
9,5mm (Braided version)
Heater zone
Braid
1m
Tinned copper
Temperature range
-60°C to +200°C
Standard
To BS EN 60079
Min bend radius
25mm
SIRA 03ATEX3376U
2 (3)
Web: www.ihpheating.com - E-mail: info@ihpheating.com - Phone: +46 (0)31 795 30 30 - VAT: SE556689732701
HEATING CABLE TYPE SCBX
Electrical
Heater
zone
Heater
zone
Rated
voltage
Insulated
bus-wire
end
Rated voltage – 220V/240V or 110V/120V AC/DC
Heater zone 1m
A 30mA trip Residual Current Circuit Device (RCCD) or Earth Leakage Circuit Breaker (ELCB) is recommended
for use with heating cables.
Maximum temperature within appropriate T class
Maximum temperature of surface to be heated ˚C within
Type
Appropriate T class
T6
T5
T4
T3
SCBX 8 110V
52
70
112
188
SCBX 12 110V
-
50
95
173
SCBX 16 110V
-
-
76
158
SCBX 20 110V
-
-
55
144
SCBX 30 110V
-
-
-
80
SCBX 8 240V
52
70
112
187
SCBX 12 240V
-
50
95
173
SCBX 16 240V
-
-
76
158
SCBX 20 240V
-
-
55
144
SCBX 30 240V
-
-
-
93
3 (3)