Section N - Steven Engineering

advertisement
SECTION
Occupancy Sensors & Lighting Control Products
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
Occupancy Sensors Applications Guide
Occupancy
Sensor Series
ODC0S-ILW
ODS10-ID ODS15-ID ODS0D-ID ODS0D-TD OSSMT-MD ODC0S-I2W OSC04-I0W OSC15-I0W OSC20-U0W OSC10-U0W OSC05-U0W OSC20-M0W
ODC0S-I7W
SPECIFICATIONS
Technology
PIR
Mounting
Multi-Tech
Switch Box
PIR
Ultrasonic
Multi-Tech
Ceiling
Coverage Sq. Ft.
2100
2100
2100
2100
1200
530
450
1500
2000
1000
500
Pattern
180°
180°
180°
180°
180°
360°
360°
360°
360°
360°
180°
4'
4'
4'
4'
4'
8' - 15'
Mounting Height
Adjustment
Self-Adjusting
Time Delay
30s - 20m
Voltage
Wattage/VA
30s - 30m
120/277VAC
1200/2700 1800/4000 800/2700
Power Pack
800/2700
800/2700
8' - 15'
2000
360°
8' - 10'
8' - 10'
Manual
Self-Adjusting, Self-Calibrating
20s - 15m
30 Seconds to 30 Minutes, 6 Second Test Mode
120-220-277
Utilizes 24VDC Power Packs and Add-A-Relays
1000/2700
Unlimited Through Use of Power Packsand Add-A-Relays
External Power Pack Not Required
Photocell
24VDC Required
Internal
Internal Photocell 20-3000 Lux Adjustable
Not Applicable
Use -RDO or -R30 Relay with 0.5A 125VAC 1.0A30VDC Relay
-32° F to 104° F / 0 to 95% Non-Condensing, Indoor Use Only
-32° F to 104° F / 0 to 95% Non-Condensing, Indoor Use Only
Standards
UL/CSA, California Title 24, ASHRAE 90.1
cULus Listed, ANCE, NOM 057, CA Title 24 and ASHRAE 90.1
Warranty
5-Year Limited
5-Year Limited
HVAC Relay
Occupancy Sensors
PIR
Ceiling
Environmental
Operating Temperature/
Humidity
Feature
S-P
S-P
Dual-Circuit Dual-Circuit
S-P
Self-Contained
S-P
A
B
S-P
Dual-Circuit Dual-Circuit
S-P
Self-Contained
APPLICATIONS
Cafeteria
Closet Utility
Computer Room
B
B
Conference Room
B
B
Copy Room
C
C
B
A
B
B
B
B
File Room
Hallway
C
C
C
C
A
B
B
B
A
A
A
A
B
C
C
C
A
C
C
B
B
B
B
Loading Dock
Office Executive
B
A
A
A
A
Office Open
C
Office Private
B
A
A
A
Office Small
B
A
A
A
A
B
A
B
Office w/Cubicles
B
B
B
A
A
A
A
B
A
A
A
C
A
A
A
B
B
C
C
C
C
Warehouse Open
C
C
C
C
C
Work Space General
A
C
C
C
B
Open Area
B
Outdoor Grounds
Refrigerated Storage
Restroom Non-Partitioned
B
A
C
C
B
Restroom Partitioned
C
C
C
C
B
Storage Room
B
A
Vending Room
C
C
C
C
A
B
Security
Stairwell
B
A
B
B
B
Warehouse Aisles
N
1
Power packs and add-a-relays available. See page N27
Rating Key: A = Best sensor for application, B = Better sensor for application, C = Good sensor for application
** 1:1 Ratio (40' Mounting height equals a 40' diameter.)
www.leviton.com
To learn more about Leviton devices or for answers to technical questions call our Techline at
1-800-824-3005 or visit us at:
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
Occupancy Sensors Applications Guide
Occupancy
Sensor Series
OSC10-M0W OSC05-M0W OSW12-M0W OSWWV-I0W OSWHB-I0W
OSWLR-I0W
PS200-10
PS200-1F
OSFHB-ITW
PS110-10
PS110-1F
SPECIFICATIONS
Technology
Multi-Technology
Mounting
PIR Passive Infrared
Ceiling
Coverage Sq. Ft.
1000
Pattern
360°
Mounting Height
Wall, Corner, or Ceiling
500
1200
180°
110°
8' - 15'
2500
55x7
PIR Passive Infrared
Fixture
100x14
Outdoor Sensor
1500**
4000
200°
110°
8°
27°
360°
8' - 15'
10' - 40'
8' - 15'
Up to 40'
2500
110°
8' - 16'
Adjustment
Self-Adjusting, Self Calibrating
Manual
Time Delay
30 Seconds to 30 Minutes, 6 Second Test Mode
20s-15m
Voltage
Wattage/VA
Utilizes 24VDC Power Packs and Add-A-Relays
120/277/347
120VAC
Unlimited through use of Power Packs and Add-A-Relays
800/1200/1500VA
1000W/500VA
Power Pack
Photocell
HVAC Relay
24VDC Required
Line Voltage
Internal Photocell 20-3000 Lux Adjustable
Internal
Use -RD0 or -R30 Relay with 0.5A 125VAC 1.0A 30VDC Relay
N/A
-14°F to 160°F
20 to 95%
Non-Condensing
-32° F to 104° F / 0 to 95% Non-Condensing, Indoor Use Only
-4°F to 131°F
20 to 95% Non-Condensing
Standards
cULus Listed, ANCE, NOM 057, CA Title 24 and ASHRAE 90.1
UL/CSA ASHRAE 90.1
Warranty
5-Year Limited
5-Year
Feature
Wide View
High Bay
Long Range
B
B
C
Hallway
B
A
Loading Dock
B
B
High Bay
Avail. w/ Dual Floodlight Lampholder
APPLICATIONS
Cafeteria
A
A
A
Computer Room
A
A
C
Conference Room
B
B
B
A
A
B
Closet Utility
Copy Room
File Room
B
C
Office Executive
B
B
A
Office Open
C
C
A
Office Private
B
B
A
Office w/Cubicles
A
A
A
Open Area
B
B
A
Occupancy Sensors
Environmental Operating
Temp. / Humidity
B
A
C
Office Small
A
Outdoor Grounds
Refrigerated Storage
Restroom Non-Partitioned
C
C
Restroom Partitioned
B
B
Storage Room
A
C
C
A
A
A
A
A
C
Security
Stairwell
A
B
B
A
B
Vending Room
B
B
B
Warehouse Aisles
A
A
A
Warehouse Open
C
C
A
A
A
A
A
Work Space General
B
B
A
A
A
A
A
N
Power packs and add-a-relays available. See page N27
Rating Key: A = Best sensor for application, B = Better sensor for application, C = Good sensor for application
** 1:1 Ratio (40' Mounting height equals a 40' diameter.)
2
www.leviton.com
To learn more about Leviton devices or for answers to technical questions call our Techline at
1-800-824-3005 or visit us at:
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
M
M
M
M
M
M
M
M
Energy Management &
Dimming
Products
M
M
M
M
M
M
Product Types
Occupancy Sensors & Lighting Control Products
CENTURA™ SYSTEM
M
M
Centura™
Fluorescent
Energy
Management
System
M
M
M
M
M
M
D
D
M
M D
D
MD
D
MD
D
D
D
I D
M
M
M
M
M
F
M
M
M
M
Decora® WallSwitch Infrared
D
ML
Occupancy
ML
Sensor
ML
Features automatic
“walk-through” sensing
and self-adjusting
delayed off. DualM
relay
versions available.
PAGE N16
ML
M
Ultrasonic CeilingM
Mount Occupancy
M
Sensor
Highly accurate smallmotion detection. D
Selfadjusting sensitivity
and time off.
ML
D
ML
ML
ML
D
HID
M
M
M
Fluorescent
Electronic
ML
ML Magnetic
ML
MD Low Voltage
MD
D
D
D Neon Cold
D
Cathode
NCC
ML
MD
PAGE N4
ML
ML
M Self-Contained
D Infrared
DCeilingD
ML
ML
Mount OccupancyML
ML Sensor
ML
ML
ML Features
ML
built-in relayML
D
ML
ML
ML
ML
ML
M
M
OCCUPANCY
SENSORS
D
PAGE N20
ML
ML
ML
All-digital self-adjusting
Ideal in small,
MD
All-digital self-adjusting sensors in wideview, high-bayML
and
D
long-range versions.
ML
For commercial
applications. Fits inML
corner.
PAGE N23
ML
ML
MD
D
D
MD
D
D
ML
ML
ML
ML
D
ML
ML
ML
PAGE N21ML
ML
PAGE N24
RELAY PANELS
Infrared Outdoor
Motion Sensor
Adjustable delayed-off
plus sensitivity to
reduce false triggers.
For commercial and
residential applications.
PAGE N28
Z-MAX™/
EZ-MAX Relay
Systems
Combines time clock
and switching controller functions.
Networkable configurations, wall stations
and other accessories
PAGE N40
available.
DAYLIGHT HARVESTING
Decora Plus™
Preset Timer
Switches ML
Decora®
Programmable
Timer Switches
Timed control of
lighting and appliances
in a sleek Decora unit.
Available in 4 interval
options.
14-hour, 24-hour, and
countdown
on/off timers.
PAGE N36
ML D
ML
IR and ultrasonic
combine for accurate
monitoring while minimizing false triggers.
Fits in corner.
MLcommercial areas.
D
M
M
M
Multi-tech
Wall-Mount
Occupancy
Sensor
MLsensor with high
MLaccuracy monitoring.
Infrared Indoor
Wall-Mount
Occupancy ML
Sensor
D
D
D
ML
Infrared CeilingMount Occupancy
Sensor
PAGE D
N22
DM
D
ML D
ML
IR
and ultrasonic
combine for accurate
monitoring while minimizing false triggers.
For larger, open
areas. Self adjusting.
D
D
ML
M
Multi-tech
Ceiling-Mount
D
D
ML
ML
Occupancy
ML
ML
Sensor
and 360° coverage.
For small spaces.
ML
ML
Motor Load
ML
M
High Intensity
Discharge
D
M
Fan Speed
Control M
ML
D
ML
M
DM
D
M
M
FS
M
ML
ML
D Low Voltage
D
ML
ML
E
ELECTRONIC TIMERS
3
D
ML
D
ML
PAGE N25
N
Incandescent
ML
D
ML
MD
D ballasts that
D may includeDa
A modular lighting control system for dimming
fluorescent
power pack, several wall controllers, a handheld
remote
control,
a
photocell,
and aD
D
D
D
SmartJack. Uses photocell to adjust lights to ambient D
light conditionsDfor substantialD
D
energy savings. Optional Leviton software enables lighting control via computer.
ML
Load Icon Legend
MD
MD
D
D
miniZ™ Intelligent
Daylight
Management
System
miniZ and Dual Room
miniZ offer daylight
harvesting in a single,
easily installed package.
PAGE N37
PAGE N47
www.leviton.com
To learn more about Leviton devices or for answers to technical questions call our Techline at
1-800-824-3005 or visit us at:
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
Energy Management & Dimming Products
Centura™ Overview
CENTURA™ FLUORESCENT ENERGY MANAGEMENT SYSTEM
Leviton’s Centura™ is a modular fluorescent lighting control system that brings increased
energy efficiency to commercial spaces. Using a technique known as daylight harvesting,
Centura automatically adjusts lighting to take advantage of ambient light conditions.
Centura offers a PC lighting control interface that is especially useful where access to
individual wall switches is impractical. Occupancy sensors can be incorporated into the
system for even greater energy savings — up to a proven 50%!
Low-voltage connector
Address wheels for
easy programming
CN200
IR receiver for use with
handheld remote control
• Daylight harvesting automatically adjusts lights to changing conditions
• Occupancy sensors automatically turn lights off when room is unoccupied
• Conserves energy and lowers electric bills; meets ASHRAE Standard 90.1 requirements
• Accessible through controllers or via Leviton Personal Dimmer software
• Can reduce eye fatigue — for optimum employee comfort and productivity
• Modular system design expands energy-saving options with an interface for building
emergency systems, load shedding programs, and time clock systems
Occupancy Sensors & Lighting Control Products
Illuminated LED buttons
Available Colors
White
Ivory
NOTE: Not all models come in all colors. See listings for color availability for specific devices.
N
4
www.leviton.com
To learn more about Leviton devices or for answers to technical questions call our Techline at
1-800-824-3005 or visit us at:
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
Energy Management & Dimming Products
Centura™ Product Listing
CENTURA™ POWER PACK, PHOTOCELL &
COMPATIBLE OCCUPANCY SENSORS
The key to Centura’s energy management functionality is the interplay between the system’s power
pack, photocell units, and occupancy sensors. These technologies combine to automate lighting and
create the optimal work atmosphere while also conserving energy. Leviton offers a number of
compatible ceiling- and wall-mount occupancy sensors to accommodate a broad range of applications.
SPECIFICATIONS & FEATURES
Power Pack / System
Occupancy Sensors & Lighting Control Products
• Provides low-voltage power supply for controllers, photocell, occupancy
sensors and jack
Centura™ adjusts lights to automatically provide
optimal lighting throughout the day.
• When hardwired to photocell, reduces electric usage through daylight
harvesting
• When hardwired to occupancy sensor, provides hands-free lights-on
when room is entered and turns lights off when room becomes vacant,
for increased energy savings
• Retains all LCnet system settings such as addresses, light (including preset)
levels, load shed and emergency status, unoccupied state, and
30-minute timeout state
• Features a built-in, low-voltage HVAC relay and a programmable
(via PC) time clock
• Meets environmental regulations (including California’s Title 24)
by defaulting to a 30-minute override of manually brightened settings
Photocell Only
• Measures light from any source in the visible spectrum within a 60° cone
Dims lights during a bright day.
• Provides continual measurements to the Dimming Power Pack
• Mounts on ceiling
TESTING & CODE COMPLIANCE
• CEC Title 24 compliant and meets ASHRAE Standard 90.1 requirements
• Power Pack and Photocell are UL Listed, CSA Certified, and FCC Part 15
(where applicable)
• Occupancy sensors are CUL/US Certified
• Centura Power Pack backed by a Limited Two-Year Warranty
• Photocell and Occupancy Sensors backed by a Limited
Five-Year Warranty
NOTE: See “Applications” on Pages N10 and N11 for additional information on
daylight harvesting, addressing, Centura design scenarios, and photocell and
occupancy sensor placement.
Brightens lights when evening falls.
Turns lights off when space becomes unoccupied.
N
5
www.leviton.com
To learn more about Leviton devices or for answers to technical questions call our Techline at
1-800-824-3005 or visit us at:
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
Energy Management & Dimming Products
Centura™ Product Listing
CENTURA™ POWER PACK, PHOTOCELL & COMPATIBLE OCCUPANCY SENSORS
Centura Power Pack & Photocell
COMMERCIAL GRADE
RATING
COLOR
2400VA @ 120VAC 60Hz, 5500VA @
Gray
277VAC 60Hz. For use with 0–10VDC
Metallic
Advance Mark 7™, OSRAM Sylvania
Quicktronic® Helios™, Energy
Savings SuperDim™ and comparable
ballasts only
DESCRIPTION
CAT. NO.
Centura Dimming Power Pack: On/off and dim/bright
CN100-0D0
control of 0-10VDC dimming fluorescent ballasts.
Responds to wall controller, occupancy sensor and
photocell input, and provides +24VDC power supply
for these devices. Programmed via wall controller or
via Leviton Personal Dimmer software from a PC.
Secondary relay sends control signals to HVAC system
ODC0P
No load rating. For use with CN100
only. 0–70 footcandles
White
Note: See Page N12 for wiring diagrams.
Centura-Compatible Occupancy Sensors
DESCRIPTION
Multi-tech Ceiling Sensor
CAT. NO.
OSC05-M0W
COVERAGE
180°, 500SF
COMMERCIAL GRADE
COLOR
PAGE NO.
White
N21
Multi-tech Ceiling Sensor
OSC10-M0W
360° 1000SF
White
N21
Multi-tech Ceiling Sensor
OSC20-M0W
360°, 2000SF
White
N21
Ultrasonic Ceiling Sensor
OSC05-U0W
180°, 500SF
White
N22
Ultrasonic Ceiling Sensor
OSC10-U0W
360° 1000SF
White
N22
Ultrasonic Ceiling Sensor
OSC20-U0W
360°, 2000SF
White
N22
Passive Infrared Ceiling Sensor
OSC04-I0W
360°, 450SF
White
N23
Passive Infrared Ceiling Sensor
OSC15-I0W
360°, 1500SF
White
N23
Multi-tech Wall Sensor
OSW12-M0W
115°, 1200SF
White
N24
Passive Infrared Wide-View Sensor
OSWWV-I0W
115°, 2500SF
White
N25, N26
Passive Infrared Long Range Sensor
OSWLR-I0W
100ft. @ 10ft. high
White
N26
Passive Infrared High-Bay Sensor
OSWHB-I0W
55 ft., 7 ft. wide @ 30 ft. high
White
N26
(Additional information on these sensors, including photos and dimensions, can be found on the pages indicated.)
NOTE: These Leviton occupancy sensors can be powered by the CN100. Within a Centura System, a separate Occupancy Sensor Power Pack is not required.
0.99
(25.1)
4.30
(109.2)
Occupancy Sensors & Lighting Control Products
Centura Photocell: Allows Centura system to maintain
a programmed light level by constantly adjusting
fluorescent light output to compensate for changes
in ambient light
2.51
(63.8)
3.62
(91.9)
4.00
(101.6)
CN100
ODC0P
N
6
www.leviton.com
To learn more about Leviton devices or for answers to technical questions call our Techline at
1-800-824-3005 or visit us at:
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
Energy Management & Dimming Products
Centura™ Product Listing
CENTURA™ CONTROLLERS
A number of controllers (including an entry-pad dimmer, rocker style switch or dimmer and a handheld
remote control) can be incorporated into a Centura system. All wall-mounted controllers feature sleek
Decora® styling.
SPECIFICATIONS & FEATURES
Occupancy Sensors & Lighting Control Products
CN200
• Dimming and switching functionality
X
• One-touch full brightness Max button
X
• Manual controls override automatic settings
X
• Compatible with a handheld remote control
X
• Service switch temporarily cuts power to fixtures
• For use programming Centura™ system
X
• Sleek Decora styling
X
CN220
CN221
NE200
X
X
X
X
X
X
X
X
X
X
X
TESTING & CODE COMPLIANCE
• UL Listed
• CSA and NOM Certified
CN200
• FCC Part 15 and CEC Title 24 compliant (except for Remote Controller)
• Backed by a Limited Two-Year Warranty
N
7
www.leviton.com
To learn more about Leviton devices or for answers to technical questions call our Techline at
1-800-824-3005 or visit us at:
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
Energy Management & Dimming Products
Centura™ Product Listing
CENTURA™ WALL AND REMOTE CONTROLLERS
DESCRIPTION
Centura Dimming Controller with Infrared Receiver:
Decora-style 5-button unit for on/off, dim/bright and
max override. Built-in IR receiver for use with Centura
NE200 Remote. Programs energy
management functions
CAT. NO.
CN200-00C
COMMERCIAL GRADE
COLOR
W + I*
RATING
No load rating. For use
with Centura Dimming
Power Pack only
CN220-00C
Same as Above
W + I*
Centura Dimming Controller: Decora-style rocker
for on/off switching with built-in arrow-shaped
rocker for dim/bright control. LED display indicates
selected brightness level. Back of wallplate
provides instruction label that lines up with
LEDs to facilitate programming
CN221-00C
Same as Above
W + I*
Centura Handheld Infrared Remote Controller:
Convenient on/off, dim/bright control presets
and programming.
NE200-00E
No load rating. For use
with CN200 Controller only
* Comes standard in White with matching Decora wallplate and Ivory Color Change Kit
Note: See Page N13 for wiring diagrams.
0.84
(21.4)
1.10
(27.9)
2.69
(68.3)
4.71
(119.6)
CN200
6.80
(172.6)
1.76
(44.7)
NE200
1.32
(33.6)
CN220
1.32
(33.6)
2.66
(67.5)
4.11
(104.4)
1.75
(44.5)
2.00
(50.8)
2.66
(67.5)
4.11
(104.4)
CN221
Black
Occupancy Sensors & Lighting Control Products
Centura Switching Controller: Decora-style rocker
for on/off switching
N
1.75
(44.5)
8
www.leviton.com
To learn more about Leviton devices or for answers to technical questions call our Techline at
1-800-824-3005 or visit us at:
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
Energy Management & Dimming Products
Centura™ Product Listing
CENTURA™ SMARTJACK/SOFTWARE PACKAGE
1.40
(35.6)
With Centura not only can lighting administrators view and control the entire lighting system from a PC,
but the average user can also adjust lighting from his or her PC. Visit www.leviton.com/centura for the
latest Centura software updates.
SPECIFICATIONS & FEATURES
• Provides PC interface for individual control of lights, to ease setup, and to back up settings
• CD includes Leviton HTTP Server, LPD, and LPDA software modules
• Comes with RJ11-to-DB9 cable
Occupancy Sensors & Lighting Control Products
2.69
(68.3)
4.41
(112.0)
• LEDs blink red or green to confirm message status
• SmartJack fits inside a standard NEMA wallbox
TESTING & CODE COMPLIANCE
• UL Listed, CSA Certified
• Backed by a Limited Two-Year Warranty
DESCRIPTION
LCnet SmartJack Package: Includes
a cable for connecting the SmartJack
to a PC and a mini-CD containing
server, administrator, and user
software. For the latest software
updates, check Leviton’s Web site:
www.leviton.com
CAT. NO.
NE100-00C
RATING
No load rating. For use
with Centura Power Pack
COMMERCIAL GRADE
COLOR
White + Ivory*
1.76
(44.7)
NE100
* Comes standard in White with matching Decora wallplate plus Ivory jack insert option (Ivory Decora wallplate sold separately).
Note: See Page N12 & N13 for wiring diagrams.
N
9
www.leviton.com
To learn more about Leviton devices or for answers to technical questions call our Techline at
1-800-824-3005 or visit us at:
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
Energy Management & Dimming Products
Centura™ Applications
GENERAL APPLICATION
Leviton’s Centura™ Fluorescent Energy Management System is ideally suited to commercial environments in which at
least one of the following needs is present:
• Saving money by reducing electric consumption
• Increasing employee productivity through optimal lighting that reduces eye fatigue
• Meeting environmental regulations and conserving energy
• Providing individual control of lighting to workers via a PC interface
• Offering hands-free convenience by automatically turning lights on and off when appropriate
• Linking emergency, time clock, HVAC and fluorescent lighting control systems to achieve optimal synergy
and efficiencies
Typical Daylight Harvesting Operation within a 12-hour period
Footcandles
Energy
Savings
Begin
Light
Maintain
Level
Min.
Light
Level
Perceived
Light
Level
6 AM
8 AM
10 AM
NOON
Light generated from
fluorescent fixture
attached to LCnet
2 PM
4 PM
6 PM
Natural & Artificial
Ambient Light
A comprehensive energy management system, such as Centura, does require planning and programming. A number
of key issues to consider beforehand include:
• Ambient light conditions and usage of space to determine optimal photocell placement
Occupancy Sensors & Lighting Control Products
The key to Centura’s energy management feature is “daylight harvesting.” By using surrounding ambient light to
supplement light from fixtures within the room, Leviton’s Centura System can maintain a constant lighting level while
saving electricity. The "Light Maintain Level" must be programmed into the power pack either via Leviton-provided
software, one of the wall-mounted controllers, or through a handheld remote control. Once wired, the power pack will
receive the photocell’s comprehensive light measurement and, when necessary, adjust its own output to keep steady
the Light Maintain Level within the photocell’s area of detection.
• Selecting the appropriate occupancy sensors to monitor an area
• How the wiring should be laid out and which Centura components are needed to create the desired system (taking
into account load capacity and addressing limitations)
• The appropriate addressing scheme and light levels that will need to be programmed
Addressing
The Centura Power Pack, all three wall controllers and the Leviton Personal Dimmer must be assigned addresses.
More specifically, they must be programmed to the same address in order for a number of these components to work
together. After all components that require it are addressed, either the Daylight Maintain Level or the Minimum Light
Level may need to be set for each address. This will be the case if either (1) there is a photocell hooked up to the
power pack or (2) the drawings require a Minimum Light Level above 0%.
N
10
www.leviton.com
To learn more about Leviton devices or for answers to technical questions call our Techline at
1-800-824-3005 or visit us at:
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
Energy Management & Dimming Products
Centura™ Applications
DESIGN SCENARIOS
Since each Centura™ system is configured based on job-specific requirements, each application must be clearly defined before a Centura
System can be designed. Applications can be broken down into different system scenarios geared towards achieving specific goals within
a certain type of space.
For illustrative purposes, a closed room is defined as a typical room with a window to the outside. If installing an energy management
system in a closed room with no such window, there is no need to include a photocell. On the other hand, we define an open space as a
large area where there is little if any natural light — and often plenty of cubicles. In general the lack of wall space in such areas makes
standard wall switches impractical and PC control desirable.
Occupancy Sensors & Lighting Control Products
The chart below presents a number of typical Centura applications, and which Centura components you might need to do the job.
SAMPLE CENTURA
APPLICATIONS
POWER PACK
OCCUPANCY
SENSOR
PHOTOCELL
1. Energy Management
System with maximum user
control for closed rooms
X
X
X
2. Basic Energy Management
System for closed rooms
X
X
X
3. Dimming System with
maximum user control for
closed rooms
X
4. Energy Management
System for open spaces
X
5. Dimming System with
maximum user control for
open spaces
X
11
DIMMING
CONTROLLER
X
X
X
X
Application 1
In a closed room with at least one window to the outside, the fullest
range of energy management features can be utilized: including a
photocell and occupancy sensors. In an office where lighting needs
may change with the task at hand — such as doing design work on
a computer or projecting a presentation — automatic lighting control
can be supplemented with a handheld remote control, a wall-mounted
dimmer, as well as a Leviton Personal Dimmer on the computer.
Application 2
As long as there is a window to the outdoors every Centura energy
management feature can be incorporated into the automatic lighting
control system. The occupancy sensor and photocell take care of
the automatic on/off as well as maintaining the Light Maintain Level.
A CN221 controller is added to give the user the ability to set
light levels and for the occasional, manual dim/bright or on/off
adjustment. This scenario is ideal for offices where the user doesn’t
need to change the level often and energy savings are a goal.
Application 3
Suited to a basic room where the user wants full control over all
lighting and an automated system IS NOT desired. For instance: an
Art Director’s office where a variety of light levels are necessary to
perform daily tasks such as doing layout on the computer and
making presentations to executives. Because no automation is
required, this application requires no occupancy sensor or photocell.
The user will have complete (including remote) control over all
lighting without any unoccupied “timeouts” or automatic light
adjustments.
SMARTJACK
+ SOFTWARE
X
X
Application 4
Ideal for the average cube farm or open space where the absence
of walls makes it more practical for users to control lighting via
computer. In this scenario, a Leviton Personal Dimmer is loaded
onto each PC. Occupancy sensors are added to make sure that no
load is inadvertently left on, therefore conserving energy and saving
money. Leviton software can also be used by building management
to track how individuals use lighting. This information can be used to
devise methods for achieving even greater cost savings.
N
CONTROLLER
+ REMOTE
X
X
X
Application 5
In applications where automatic light adjustments are not required,
Centura may be used simply as a comprehensive dimming system.
In an open area, especially with cubicles, Centura is a superb
choice because it provides a Leviton Personal Dimmer that can be
loaded onto individual PCs. This allows occupants to adjust their
lighting without having to walk across a large room to a wall switch
that may be bunched up with so many other switches as to be hard
to distinguish. The CN200 must be selected as a controller if remote
controllability is also desired.
PHOTOCELL PLACEMENT
Installing a photocell can save electricity in any indoor space with
windows or with substantial ambient light from adjacent indoor spaces.
On the other hand, installing a photocell in a room without windows
(especially an enclosed one) is of little value. In those applications
where automatic light adjustments are desired, the placement of each
photocell is a key factor in determining how daylight harvesting will
work. Since light reflects off ceilings, walls, floors and furniture,
ambient light levels can vary throughout different areas in a room. In
order to ensure that lights brighten and dim appropriately, care must
be taken in choosing a mounting location. Leviton recommends that
the photocell be placed directly above the workspace where lighting is
most critical. Tabletop or floor lamps can be used to supplement
lighting. Only one photocell should be installed per power pack.
OCCUPANCY SENSOR SELECTION & PLACEMENT
Sensors can be mounted in the middle of walls, in corners, or on
ceilings. In order to ensure motion is detected throughout an entire
space, occupancy sensors must be intelligently placed. With a variety
of models from which to choose, care should be taken to select the
proper combination of sensors to cover an entire area with motion
detection. Each sensor covers a specific pattern and square footage
that must be taken into account. Additional factors include usage
patterns, false-ons from nearby traffic, and airflow that can falsely
register as motion. Additional information about Centura-compatible
occupancy sensors can be found in the Occupancy Sensor section
that follows.
Leviton provides a complimentary occupancy-sensor layout service.
This service provides suggested sensor selection and placement on a
customer’s drawings in either paper or electronic form, along with a bill
of material detailing the components necessary for that layout. E-mail
oslayout@leviton.com to request this service.
www.leviton.com
To learn more about Leviton devices or for answers to technical questions call our Techline at
1-800-824-3005 or visit us at:
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
Energy Management & Dimming Products
Centura™ Technical Information
WIRING
LEVITON CONTROL NETWORK
Before installing individual Centura™ components, low-voltage communication wiring (the LCnet) must be installed. Leviton recommends using
stranded Cat-5 premise patch cable for best performance. Power Packs chosen as the first and last nodes on the bus must be terminated if the
wiring between LCnet components is longer than 10 feet.
Note: Do not connect the 24VDC low voltage bus between two power packs.
LCnet Wiring Schematic
CAN H-blue
2
Terminated
0
Drop
Length
n < 20 feet
1
1
0
CAN L-blue-white
2
2
o
Controller
Dimming
Power Pack
Occupancy
Sensor
Terminated
15
Photocell
System Wiring Diagram
ODxxx
OCCUPANCY SENSOR
CN220
SWITCHING
CONTROLLER
CN221
DIMMING
CONTROLLER
Low-Voltage
Line Voltage
CN100 DIMMING POWER PACK
Red Bundle
Occupancy Sensors & Lighting Control Products
SmartJack
Gray
POWER (+24V) - Green/White
DC GROUND - Green
CAN_H - Blue
CAN_L - Blue/White
PHOTOCELL - Orange
OCCUPANCY - Blue
Violet
Hot (Black)
Line
120/277VAC
Neutral (White)
Black
4
3
2
1
White
DIM - Violet
RETURN - Gray
Blue
HVAC NO - Brown/White
HVAC NC - Brown
HVAC COMM. - Green
Blue
Blue Bundle
HVAC
System
ON
MAX
BRIGHT
DIM
Green
Ground
OFF
Gray
Black
White
O-10V DC Ballast
Violet
Alternate Ballast Connection
ODC0P
PHOTOCELL
CN200
DIMMING
CONTROLLER
w/IR RECEIVER
NE100
SMARTJACK
N
12
www.leviton.com
To learn more about Leviton devices or for answers to technical questions call our Techline at
1-800-824-3005 or visit us at:
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
Energy Management & Dimming Products
Centura™ Technical Information
INDIVIDUAL COMPONENTS
The SmartJack is powered by a power pack. Because it is not associated with any single address on
the LCnet, the SmartJack’s power wires can be connected to whichever is the nearest power pack. We
suggest that Controllers be wired to a power pack with the same address. Although it will function
otherwise, powering Controllers from a pack within its own address makes troubleshooting and future
expansion easier. Additional information on Centura-compatible occupancy sensors, including wiring
diagrams and mounting illustrations, can be found in the Occupancy Sensor section that follows.
Occupancy Sensors & Lighting Control Products
CN200 Dimming Controller and
NE100 SmartJack Wiring Diagram
CN220/221 Controller Wiring Diagram
Power (24 VOC) (Green/White)
To
Power
Pack
GND (Green)
CAN-L (Blue/White)
Not Used
CAN-H (Blue)
+24V DC (Green/White)
GND
CAN-L
Not Used
CAN-H
+24V DC
Power (24VDC)(Green/White)
DC
(Green)
DCGnd
Ground
(Green)
Twisted Pair
To Power Pack
CAN H(Blue)
(Blue)
CAM_H
CAN
L (Blue/White)
CAM_L (Blue/White)
LOAD CAPACITY
Although numerous Centura peripherals (or components) in a multitude of combinations can be
attached to the low-voltage bus, there is a limit to what can be attached to a single Centura Power Pack
based on the pack’s 500mA maximum load current. Most Centura components can be powered by ANY
power pack because either its address determines which devices it talks to (as with controllers) or it
listens to all messages (for example SmartJack). In contrast, occupancy sensors and photocells must
be hardwired to a specific Centura Power Pack. Never connect two CN100 low-voltage power wires
together.
SOFTWARE
To use a PC to set up and store settings, the PC must be connected to a SmartJack wired to the LCnet
and the following software modules must be installed: HTTP Server, LPDA, and LPD (optional). See
www.leviton.com/centura for software updates.
Operating System Requirements: Windows 95/98/Me/2000*/NT 4.0 Service Pack 6*/XP* (*with
administrative access); see www.leviton.com for latest OS compatibility.
N
13
www.leviton.com
To learn more about Leviton devices or for answers to technical questions call our Techline at
1-800-824-3005 or visit us at:
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
Energy Management & Dimming Products
Occupancy Sensor Overview
LEVITON OCCUPANCY SENSOR LIGHTING CONTROLS
Leviton’s wall and ceiling-mounted occupancy sensors use passive infrared and/or ultrasonic sensing technology to provide cost-effective lighting control. Leviton occupancy sensors can be used in everything from conference rooms to hallways and from restrooms to
outdoor areas — turning lights on when motion is detected and off when it is not. Leviton’s
comprehensive line includes commercial and residential, wide-view and high-bay, dualrelay, and even outdoor models that span a broad range of coverage areas and patterns.
Accessories, including cages and power packs, are available for many models.
Adjustable blinders
block peripheral signals
Fresnel lens for
optimal field of view
Time, range and
light adjustments
Photocell detects light to
enable energy-saving
ambient light override
Ground clip to ensure
solid connection
ODS15-ID
Wall-Switch Occupancy Sensor
Push button for manual on/off
LED indicator flashes when
sensor detects motion
• Advanced ultrasonic sensing technology for highly accurate small-motion monitoring
• Advanced passive infrared (PIR) technology for monitoring obstruction-free areas
• Adjustable delayed-off and/or self-adjusting delayed-off interval compensates for
occupancy patterns—preventing unnecessary on/off switching
• Many with self-adjusting settings that continuously analyze and adjust for
optimum performance
Occupancy Sensors & Lighting Control Products
PIR sensors detect
IR signal
Available Colors
All devices come in white. Wall-switch occupancy sensors may also come in ivory, almond, light almond and gray.
White
Ivory
Almond
Light Almomd
N
Gray
14
www.leviton.com
To learn more about Leviton devices or for answers to technical questions call our Techline at
1-800-824-3005 or visit us at:
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
Energy Management & Dimming Products
Occupancy Sensor Product Listing
DECORA® WALL-SWITCH INFRARED OCCUPANCY SENSORS
Convenient switch and occupancy sensor combo in sleek Decora® style unit. Advanced passive infrared technology provides highly accurate
monitoring in a variety of commercial applications. The OSSMT Multi-Tech unit combines passive infrared and ultrasonic technologies to
provide maximum sensitivity with immunity to false triggering.
SPECIFICATIONS & FEATURES
Occupancy Sensors & Lighting Control Products
ODS0D-ID ODS0D-TD ODS10
ODS15
PR150
PR180
OSSMT
• Ambient light override prevents lights from turning
on when there is ample natural light
(S = self adjusting)
S
S
X
S
X
X
X
• Manual override turns lights on at any
time regardless of override setting
X
X
X
X
X
X
X
• Dual pushbuttons provide manual ON/OFF switching
for 2 separate banks from a single unit
X
X
• Exclusive automatic “walk-through” sensing increases
energy savings by shutting lights within 2-1/2 minutes
after momentary occupancy
X
X
• Unit beeps to indicate load is going to be switched
off automatically
X
X
• Choice of “Conference Room” or “Classroom”
modes for maximum performance and energy
savings in a variety of installations
X
• Manual delayed-off-time settings: 5, 10, and
20 minutes, with 30-second test mode
X
X
OSSNL
OSS10
IPP15
X
X
X
X
X
X
• Manual delayed-off-time settings: 10, 20, and
30 minutes, with 30-second test mode
X
X
X
• Manual delayed-off-time settings: 15 seconds
to 15 minutes
X
• Manual delayed-off-time settings: 30 seconds
to 30 minutes
X
X
• Manual delayed-off-time settings: 30 seconds,
30 minutes, 1 hour, 2 hours
• Three-position service switch with off, auto, on
X
X
X
X
X
X
• Elegant Decora styling complements any interior,
uses Decora wallplates
X
X
X
X
X
X
X
X
X
X
• Fits in standard wallbox; units may be ganged
X
X
X
X
X
X
X
X
X
X
• Night Light mode or “Guide Light” feature
X
X
• Night Light dim feature
X
X
X
X
X
X
X
• Single-pole and 3-way wiring
• Adjustable integral blinders with 180° to 32° field-of-view
X
X
X
X
X
• Manual ON/Auto OFF operation for CEC Title 24
compliance
X
X
X
X
X
X
IDEAL FOR USE IN:
ODS0D-ID/ODS0D-TD— Classrooms, multimedia and conference rooms, day care centers, office, lounges
ODS10-ID — Enclosed areas: small offices, conference rooms, storage rooms, copy rooms, closets
ODS15-ID — Commercial areas: small offices, conference rooms, classrooms, stockrooms, lounges, restrooms, warehouses
PR150-1L — Wide variety of residential applications
PR180-1L — Large rooms, home offices, and a variety of light commercial and residential applications
OSSMT — Private and executive offices, conference rooms, storage areas, restrooms, classrooms, lounges, and training areas
OSSNL/OSS10 — Hotel restrooms, hospital restrooms, conference rooms, classrooms, small offices, lounges, storage areas, and bathrooms
IPP15 — Kitchens, bathrooms, laundry rooms and garages
TESTING & CODE COMPLIANCE
• UL Listed; Cat. No. ODS0D-ID is CUL/US Certified
• CSA Certified
N
15
• CEC Title 24 compliant (ODSXX, OSS10, OSSMT and IPP15 models only) and meets ASHRAE Standard 90.1 requirements
• Backed by a Limited Five-Year Warranty; Limited Two-Year Warranty on PR1XX models
www.leviton.com
To learn more about Leviton devices or for answers to technical questions call our Techline at
1-800-824-3005 or visit us at:
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
Energy Management & Dimming Products
Occupancy Sensor Product Listing
DECORA® WALL-SWITCH INFRARED OCCUPANCY SENSORS
Occupancy Sensors
COMMERCIAL GRADE
COLOR*
W, I, A, T, G
CAT. NO.
ODS10-ID
RATING
Incandescent: 800W @
120V. Fluorescent:
1200VA @ 120V,
2700VA @ 277V.
For 60Hz AC only.
Motor: 1/4HP @ 120V
COVERAGE
180°, 2100SF
Decora Wall-Switch PIR
Occupancy Sensor with
Self-adaptive Technology
ODS15-ID
Incandescent: 1800W @
120V. Fluorescent:
1800VA @ 120V,
4000VA @ 277V.
Motor: 1/4HP @ 120V
180°, 2100SF
W, I, A, T, G
Dual-Relay Decora WallSwitch PIR Occupancy
Sensor with Self-Adaptive
Technology. Default setting =
Conference Room mode,
alternate setting = Classroom
mode**
ODS0D-ID
Primary Relay–Fluorescent:
1200VA @ 120V, 2700VA
@ 277V; Incandescent:
800W @ 120V. Secondary
Relay–Fluorescent: 800VA
@ 120V, 1200VA @ 277V;
Incandescent: 800W @ 120V
180°, 2100SF
W, I, A, T, G
Dual-Relay Decora WallSwitch PIR Occupancy
Sensor with Self-Adaptive
Technology. Secondary relay
provides manual ON only
for CEC Title 24 compliance
ODS0D-TD
Primary Relay–Fluorescent:
1200VA @ 120V, 2700VA
@ 277V; Incandescent:
800W @ 120V. Secondary
Relay–Fluorescent: 800VA
@ 120V, 1200VA @ 277V;
Incandescent: 800W @ 120V
180°, 2100SF
W, I, A, T, G
Decora Wall-Switch PIR
Occupancy Sensor with
LED Night Light
OSSNL-ID
Incandescent: 800W @ 120V
Fluorescent: 1200VA @ 120V,
2700VA @ 277V
Motor: 1/8 HP @ 120V
180°, 1200 SF
W, I, A, T, G
CEC Title 24 Compliant Decora
Wall-Switch PIR Manual-ON Sensor
with LED Night Light
OSS10-ID
Incandescent: 800W @ 120V
Fluorescent: 1200VA @ 120V,
2700VA @ 277V
Motor: 1/8 HP @ 120V
180°, 1200 SF
W, I, A, T, G
DESCRIPTION
Decora Manual-ON Occupancy Sensor,
CEC Title 24 Compliant. Single-Pole,
3-Way or more when used with IPP0R
Remote and/or Vizia™ Remotes and
Remote Switches
CAT. NO.
IPP15-1L
RATING
Incandescent: 1800W. @ 120V.
Fluorescent: 1800VA @ 120V.
Motor: 1/4HP @ 120V
COVERAGE
180°, 900SF
RESIDENTIAL GRADE
COLOR*
W, I, A, T
Decora Manual-ON Occupancy Sensor
Remote. For use with IPP15 Sensor or
Vizia Dimmers.
IPP0R-1L
120VAC–No load rating.
For use with IPP15 or
Vizia Dimmers
180°, 900SF
W, I, A, T
Decora Wall-Switch PIR
Occupancy Sensor,
Single-Pole
PR150-1L
Incandescent: 500W.
Fluorescent: 400VA
rapid start magnetic
only @ 120VAC.
Motor: 1⁄8HP @ 120VAC
150°, 350SF
W, I
Decora Wall-Switch PIR
Occupancy Sensor,
Single-Pole, 3-Way
PR180-1L
Incandescent: 500W.
Fluorescent: 400VA rapid
start magnetic only @ 120VAC.
Motor: 1⁄8HP @ 120VAC
180°, 400SF
W, I
Occupancy Sensors
DECORA® WALL-SWITCH MULTI-TECH OCCUPANCY SENSORS
Occupancy Sensors
DESCRIPTION
Decora Wall-Switch Multi-Tech
Occupancy Sensor with
Self-adaptive Technology
CAT. NO.
OSSMT-MD
RATING
Incandescent/Tungsten:
800W @ 120V.
Fluorescent: 1200VA @ 120V,
2700VA @ 277V
Motor: 1/4HP @ 120V
COVERAGE
180°, 1200 SF
Occupancy Sensors & Lighting Control Products
DESCRIPTION
Decora Wall-Switch PIR
Occupancy Sensor
COMMERCIAL GRADE
COLOR*
W, I, A, T, G
* Add to end of catalog number suffix for color of switch: White (W), Ivory (I), Almond (A), Light Almond (T) and Gray (G).
Wallplates sold separately.
** In Conference Room Mode, both primary and secondary relays respond to ambient light override. In Classroom Mode, primary
relay responds only to ambient light override.
N
NOTE: See Page N32 for wiring diagrams, Page N17 for dimensioned photos and Page N18 for Field of View
16
www.leviton.com
To learn more about Leviton devices or for answers to technical questions call our Techline at
1-800-824-3005 or visit us at:
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
Energy Management & Dimming Products
Occupancy Sensor Wall-Switch Dimensions
DECORA® WALL-SWITCH INFRARED OCCUPANCY SENSORS DIMENSIONS
Occupancy Sensors & Lighting Control Products
2.60
(66.1)
4.06
(103.2)
2.66
(67.5)
4.11
(104.4)
2.60
(66.1)
4.06
(103.2)
1.75
(44.4)
1.75
(44.5)
1.75
(44.4)
ODS10-ID/ODS15-ID/IPP15
ODS0D-ID/ODS0D-TD
PR180-1L
1.35
(33.6)
1.32
(33.6)
2.66
(67.5)
4.11
(104.4)
1.35
(34.3)
1.35
(33.6)
1.35
(34.3)
1.35
(33.6)
2.66
(67.5)
4.11
(104.4)
1.75
(44.5)
1.75
(44.5)
OSSNL-ID/OSSI0-ID
OSSNL-ID1/OSS10-ID
Shown with Night Light ON
2.66
(67.5)
4.11
(104.4)
1.75
(44.5)
OSSMT-MD
Multi-Tech Sensor
N
17
www.leviton.com
To learn more about Leviton devices or for answers to technical questions call our Techline at
1-800-824-3005 or visit us at:
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
Energy Management & Dimming Products
Occupancy Sensor Wall-Switch Field of View
DECORA® WALL-SWITCH INFRARED OCCUPANCY SENSOR FIELDS OF VIEW
40
TOP VIEW
TOP VIEW
TOP VIEW
30
10
10
0
0
10
10
15
0
30
Major Motion, IR
40
5
4
0
SIDE VIEW
SIDE VIEW
Minor Motion, IR
5
4
5
4
SIDE VIEW
0
0
0
15
40
0
ODSXX-ID/ODS0D-TD Field of View (in feet)
0
20
PR150-1L Field of View (in feet)
20
PR180-1L Field of View (in feet)
TOP VIEW
30 ft (9.1 m)
30
20 ft (6.1 m)
small motion
15
20 ft (6.1 m)
minor motion
40 ft
(12.2 m)
0
15
30
5
4
SIDE VIEW
0
0
OSSNL/OSS10/OSSMT Field of View (in feet)
15
30
IPP15 Field of View (in feet)
Occupancy Sensors & Lighting Control Products
15
N
18
www.leviton.com
To learn more about Leviton devices or for answers to technical questions call our Techline at
1-800-824-3005 or visit us at:
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
Energy Management & Dimming Products
Occupancy Sensor Product Listing
SELF-CONTAINED FIXTURE-MOUNT HIGH BAY SENSOR/POWER BASE ADAPTOR
SPECIFICATIONS & FEATURES
• Mounts easily in standard 2.125" deep x 4" octagon or 2.125"
deep x 4" square electrical box with a 2-gang mud ring; flying
leads provide fast line voltage connections
Fixture-Mount High Bay Occupancy Sensor
• Mounts directly to industrial-style fluorescent luminaires or
electrical junction box
• Two-piece terminal block provides fast, easy low-voltage
connections to the sensor
• Self-contained PIR sensor and relay turn individual fixtures
ON/OFF based on occupancy
• Relay uses zero-crossing circuitry for enhanced reliability and
long-life operation
• Up to 40 ft mounting height
Occupancy Sensors & Lighting Control Products
• Relay uses zero-crossing circuitry for enhanced reliability and
long-life operation
• Delayed-OFF time adjustment from 30 sec to 20 min
• Cat. No. OSFOA-00W Offset Adapter Accessory snaps into 1/2"
knockout to position sensor below fixture body for improved field
of view with deep-body fixtures
Ideal For Use In:
OSFHB-1TW — Commercial facilities with high ceilings, including
warehouses, manufacturing and others.
OPB15-0DW — Lavatories, remodels in hard ceiling spaces, energy conservation retrofits and any installation with limited access for
low-voltage wiring.
Self-Contained Power Bases Adaptor
TESTING & CODE COMPLIANCE
• Patent-pending design converts Leviton low-voltage ceiling
sensors to line-voltage
• UL and cUL Listed
• Ideal for both existing buildings with limited access to low-voltage
wiring and new constructions with line-voltage circuiting only.
• CEC Title 24 compliant
• NOM Certified (OPB15-0DW)
• Backed by a Limited Five-Year Warranty
40 ft
3.50
(88.9)
Ø4.50
(114.3)
20 ft
0 ft
1.75
(44.5)
3.50
(88.9)
OSFHB-ITW
OPB15-0DW
0 ft
11 ft
20 ft
OSFHB Field of View
COMMERCIAL GRADE
COVERAGE
COLOR
360°, 1:1 space
White
to mounting height
DESCRIPTION
High Bay Fixture-Mount
PIR Occupancy Sensor
CAT. NO.
OSFHB-ITW
RATING
Fluorescent: 800VA @ 120V,
1200VA @ 277V,
1500VA @ 347V
Motor: 1/4HP @ 120V
Offset Adaptor Accessory for
High Bay Fixture-Mount
Occupancy Sensor
OSFOA-00W
—
—
POWER INPUT/OUTPUT
Power Input: 120/277VAC
Control Output: 24VDC, 40mA
COMMERCIAL GRADE
RATING
COLOR
15A Incandescent,
White
Electronic or Magnetic
Fluorescent Ballast,
3/4 HP @ 120V
DESCRIPTION
Power Base Adaptor — converts any
Leviton low-voltage ceiling or wallmount occupancy sensor to a
self-contained line voltage unit
19
11 ft
SELF-CONTAINED INFRARED FIXTURE-MOUNT HIGH BAY OCCUPANCY SENSOR
Occupancy Sensors
SELF-CONTAINED POWER BASE ADAPTOR
Occupancy Sensors
N
20 ft
1.25
(31.8)
CAT. NO.
OPB15-0DW
White
For OSFHB-1TW and OPB15-0DW wiring diagrams, see page N33.
www.leviton.com
To learn more about Leviton devices or for answers to technical questions call our Techline at
1-800-824-3005 or visit us at:
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
Energy Management & Dimming Products
Occupancy Sensor Product Listing
SELF-CONTAINED INFRARED CEILING-MOUNT OCCUPANCY SENSORS
2.15
(54.6)
SPECIFICATIONS & FEATURES
• Ideal for use in storage areas, small bathrooms, copy rooms, and a variety of
small spaces without wall switches
• Sensor and switching relay combined in a single, self-contained unit — no control unit
(power pack) required
• Ambient light override option prevents lights from turning on when there is
ample natural light
4.30
(109.2)
• Adjustable delayed-off-time settings from 20 seconds (for test mode) to 15 minutes
TESTING & CODE COMPLIANCE
• UL Listed and CSA Certified
• CEC Title 24 compliant and meets ASHRAE Standard 90.1 requirements
ODC0S-I1W
• Backed by a Limited Five-Year Warranty
COMMERCIAL GRADE
COVERAGE
COLOR
DESCRIPTION
CAT. NO.
RATING
Self-Contained Ceiling-Mount
Infrared Occupancy Sensor
and Switching Relay, 120V
ODC0S-I1W
Incandescent: 1000W
@120V. Fluorescent:
1000VA @ 120V.
Motor: 1HP @ 120V.
For 60Hz AC only
360°, 530SF*
White
Self-Contained Ceiling-Mount
Infrared Occupancy Sensor
and Switching Relay, 220V
ODC0S-I2W
Incandescent: 1000W
@220V. Fluorescent:
500VA @ 220V. For
50Hz AC only
360°, 530SF*
White
Self-Contained Ceiling-Mount
Infrared Occupancy Sensor
and Switching Relay, 277V
ODC0S-I7W
Fluorescent: 2700VA
@277V. For 60Hz
AC only
360°, 530SF*
White
Protective Cage
ODCCG
–
–
White
* When surface mounted on standard, 8-foot ceiling
NOTE: See Page N33 for wiring diagrams.
TOP VIEW
13
0
Occupancy Sensors & Lighting Control Products
• Small, unobtrusive self-contained unit
13
SIDE VIEW
8
0
13
7
3
0
3
7
13
ODCOS-I Field of View (in feet)
N
20
www.leviton.com
To learn more about Leviton devices or for answers to technical questions call our Techline at
1-800-824-3005 or visit us at:
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
Energy Management & Dimming Products
Occupancy Sensor Product Listing
1.55
(39.4)
MULTI-TECHNOLOGY CEILING-MOUNT OCCUPANCY SENSORS
These advanced motion sensors combine infrared and ultrasonic technology for highly accurate
monitoring without false triggers. All-digital self-adjusting technology provides “install and forget”
solution for automatic lighting control. Available in a variety of coverage patterns to suit many
applications. Use with Leviton Power Pack or, where compatible, with Centura Dimming Power Pack.
SPECIFICATIONS & FEATURES
• Ideal for use in classrooms, office areas with cubicles, cafeterias, and public areas in
commercial facilities
4.20
(106.7)
Occupancy Sensors & Lighting Control Products
Functional
• Ultrasonic sensing for maximum sensitivity combined with passive infrared (PIR) sensing
to prevent false triggers from air conditioning and corridor activity
• Self-adjusting settings continuously analyze and adjust sensitivity, timer operation,
and air current compensation for reliable, long-term performance
• Ambient light override to prevent lights from turning on when there is ample natural light
OSC05-M0W
• Manual delayed-off-time settings of 30 seconds to 30 minutes
• Self-adjusting delayed-off-time interval settings for 30 seconds to 30 minutes
1.55
(39.4)
• Compensates for real-time occupancy patterns — preventing unnecessary on/off switching
• Non-volatile memory preserves all automatic and manual settings during power outages
Physical
• Small, unobtrusive unit blends in with any décor
• Fast, simple installation using 4 color-coded low-voltage wires and a single mounting post
• Compatible with Wiremold® surface raceways for mounting to hard ceilings
4.20
(106.7)
TESTING & CODE COMPLIANCE
• CUL/US, FCC and NOM Certified
• California Title 24 compliant and meets ASHRAE Standard 90.1 requirements
• Backed by a Limited Five-Year Warranty
DESCRIPTION
CAT. NO.
Multi-tech Ceiling-Mount
Occupancy Sensor*
COMMERCIAL GRADE
COLOR
COVERAGE
OSC05-M0W
OPERATING
FREQUENCY
40kHz
180°, 500SF
White
Multi-tech Ceiling-Mount
Occupancy Sensor*
OSC10-M0W
40kHz
360°,1000SF
White
Multi-tech Ceiling-Mount
Occupancy Sensor*
OSC20-M0W
32kHz
360°, 2000SF
White
Protective Cage
ODCCG-000
—
—
White
OSC20-M0W
NOTE: See Page N33 for wiring diagrams.
Minor Motion, IR
Major Motion, IR
Minor Motion, Ultrasonic
Major Motion, Ultrasonic
*Compatible with Centura Fluorescent Energy Management System.
NOTE: Use low-voltage wiring to connect sensors to OSPXX Power Pack or if Centura-compatible, to a CN100 Power Pack
(purchased separately). See Page N27 for information on OSP Power Packs.
TOP VIEW
20
TOP VIEW
TOP VIEW
20
20
16
11.5
11.5
8.5
11.5
8.5
0
0
0
8.5
8.5
11.5
11.5
11.5
16
20
20
20
SIDE VIEW
8
SIDE VIEW
21
8
0
0
N
SIDE VIEW
8
0
3 5.6
9 11
15
17
20
23
OSC05-M0W Field of View (in feet)
23
20
17
15
11 9
5.6 3
OSC10-M0W Field of View
0
3 5.6
9 11
15
20
17
23
20
32
15
11 9 5.5 3
0
22.5
3 5.5 9 11
15
20
22.5
32
OSC20-M0W Field of View
Wiremold ® is a registered trademark of the Wiremold Company.
www.leviton.com
To learn more about Leviton devices or for answers to technical questions call our Techline at
1-800-824-3005 or visit us at:
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
Energy Management & Dimming Products
Occupancy Sensor Product Listing
ULTRASONIC CEILING-MOUNT OCCUPANCY SENSORS
1.34 (34.0)
Advanced ultrasonic sensing technology for highly accurate monitoring, including small-motion
detection. All-digital self-adjusting technology provides “install and forget” solution for automatic lighting
control. Use with Leviton Power Pack or, where compatible, Centura Dimming Power Pack.
SPECIFICATIONS & FEATURES
• Ideal for restrooms, office areas with cubicles, warehouse and storage facilities,
cafeterias, and public areas in commercial facilities
4.20
(106.7)
Functional
• Ultrasonic sensing for maximum range and sensitivity combined with accurate
small-motion detection
• Ambient light override to prevent lights from turning on when there is ample natural light
OSC05-U0W
• Manual delayed-off-time settings of 30 seconds to 30 minutes
1.34 (34.0)
• Self-adjusting delayed-off time interval settings for 30 seconds to 30 minutes.
Compensates for real-time occupancy patterns — preventing unnecessary on/off switching
• Non-volatile memory preserves all automatic and manual settings during power outages
Physical
• Small, unobtrusive unit blends in with any décor
• Fast, simple installation using 4 color-coded low-voltage wires and a single mounting post
4.20
(106.7)
• Compatible with Wiremold® surface raceways for mounting to hard ceilings
TESTING & CODE COMPLIANCE
• CUL/US Certified
• Meets ASHRAE Standard 90.1 requirements
• Backed by a Limited Five-Year Warranty
DESCRIPTION
CAT. NO.
Ultrasonic Ceiling-Mount
Occupancy Sensor*
OSC05-U0W
OPERATING
FREQUENCY
40kHz
Ultrasonic Ceiling-Mount
Occupancy Sensor*
OSC10-U0W
Ultrasonic Ceiling-Mount
Occupancy Sensor*
OSC20-U0W
Protective Cage
ODCCG-000
OSC20-U0W
COMMERCIAL GRADE
COVERAGE
COLOR
180°, 500SF
White
40kHz
360°, 1000SF
White
32kHz
360°, 2000SF
White
11.5
8.5
0
—
—
White
* Compatible with Centura Fluorescent Energy Management System.
8.5
NOTE: Use low-voltage wiring to connect sensors to OSPXX Power Pack Power Pack or if Centura-compatible, to a CN100
Power Pack (purchased separately). See Page N25 for information on OSP Power Packs.
11.5
NOTE: See Page N27 for wiring diagrams.
5
0
10
20
Minor Motion, Ultrasonic
17
Major Motion, Ultrasonic
OSC05-U0W Field of View (in feet)
23
16
11.5
Occupancy Sensors & Lighting Control Products
• Self-adjusting settings continuously analyze and adjust sensitivity, timer operation,
and air current compensation for reliable, long-term performance
11.5
8.5
0
0
8.5
11.5
11.5
16
23
17
0
OSC10-U0W Field of View
Wiremold ® is a registered trademark of the Wiremold Company.
17
23
32
22.5
0
22.5
OSC20-U0W Field of View
32
N
22
www.leviton.com
To learn more about Leviton devices or for answers to technical questions call our Techline at
1-800-824-3005 or visit us at:
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
Energy Management & Dimming Products
Occupancy Sensor Product Listing
INFRARED CEILING-MOUNT OCCUPANCY SENSORS
1,55
(39.4)
SPECIFICATIONS & FEATURES
• Ideal for use in small offices, closets, open offices, and other areas in commercial facilities
with unobstructed view of the sensor
Functional
• Self-adjusting settings continuously analyze and adjust sensitivity, timer operation,
and long-term performance
• Ambient light override prevents lights from turning on when there is ample natural light
4.20
(106.7)
Occupancy Sensors & Lighting Control Products
• Manual delayed-off-time settings of 30 seconds to 30 minutes
• Self-adjusting delayed-off-time interval settings for 30 seconds to 30 minutes.
Compensates for real-time occupancy patterns — preventing unnecessary on/off switching
• Non-volatile memory preserves all automatic and manual settings during power outages
Physical
• Small, unobtrusive unit blends in with any décor
OSC04-I0W
• Fast, simple installation using 4 color-coded low-voltage wires and a single mounting post
• Compatible with Wiremold® surface raceways for mounting to hard ceilings
TESTING & CODE COMPLIANCE
• CUL/US Certified
• Meets ASHRAE Standard 90.1 requirements
• Backed by a Limited Five-Year Warranty
COMMERCIAL GRADE
COLOR
White
DESCRIPTION
Infrared Ceiling-Mount Occupancy Sensor*
CAT. NO.
OSC04-I0W
COVERAGE
360°, 450SF
Infrared Ceiling-Mount Occupancy Sensor*
OSC15-I0W
360°, 1500SF
White
Protective Cage
ODCCG-000
—
White
*Compatible with Centura Fluorescent Energy Management System.
NOTE: Use low-voltage wiring to connect sensors to OSPXX Power Pack or if Centura-compatible, CN100 Power Pack (purchased
separately). See Page N27 for information on OSP Power Packs.
NOTE: See Page N33 for wiring diagrams.
Minor Motion, IR
TOP VIEW
12
Major Motion, IR
TOP VIEW
20
5
10
0
0
5
10
12
20
SIDE VIEW
8
SIDE VIEW
8
0
12
N
9
7
5
3
0
3
5
7
9
12
OSC04-I0W Field of View (in feet)
20
15 11 9 5.6 3
0
3 5.6 9 11 15
20
OSC15-I0W Field of View
Wiremold ® is a registered trademark of the Wiremold Company.
23
www.leviton.com
To learn more about Leviton devices or for answers to technical questions call our Techline at
1-800-824-3005 or visit us at:
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
Energy Management & Dimming Products
Occupancy Sensor Product Listing
MULTI-TECHNOLOGY WALL-MOUNT OCCUPANCY SENSORS
4.12
(104.6)
SPECIFICATIONS & FEATURES
• Ideal for conference rooms, stairwells, high-ceiling rooms, open areas, storage rooms,
and classrooms — including corner mounting in a variety of applications
• Ultrasonic sensing for maximum sensitivity combined with passive infrared (PIR) sensing
to prevent false triggers from air conditioning and corridor activity
• Adjustable swivel neck rotates 80° vertically and 60° horizontally. Can be used for
ceiling or wall mounting
3.67
(93.2)
• Self-adjusting settings continuously analyze and adjust sensitivity, timer operation,
and air current compensation for reliable, long-term performance
5.50
(139.7)
• Manual delayed-off-time settings of 30 seconds to 30 minutes
• Self-adjusting delayed-off-time interval settings of 30 seconds to 30 minutes. Compensates for
real-time occupancy patterns, preventing unnecessary on/off switching
• Non-volatile memory preserves all automatic and manual settings during power outages
• Fast, simple installation using 3 color-coded low-voltage wires and a single mounting post
2.80
(71.1)
TESTING & CODE COMPLIANCE
• CUL/US Certified
OSW12-M0W
• Meets ASHRAE Standard 90.1 requirements
• Backed by a Limited Five-Year Warranty
DESCRIPTION
CAT. NO.
Multi-tech Wall-Mount
Occupancy Sensor *
OSW12-M0W
OPERATING
FREQUENCY
32kHz
COVERAGE
115°,1200SF
COMMERCIAL GRADE
COLOR
White
*Compatible with Centura Fluorescent Energy Management System.
NOTE: Use low-voltage wiring to connect sensors to OSPXX Power Pack or if Centura-compatible, to a CN100 Power Pack (purchased
separately). See Page N27 for information on OSP Power Packs.
NOTE: See Page N34 for wiring diagrams.
(
)
Minor Motion, IR
TOP VIEW
58
Major Motion, IR
Minor Motion, Ultrasonic
Major Motion, Ultrasonic
31
16
11.5
0
11.5
16
31
Occupancy Sensors & Lighting Control Products
• Ambient light override to prevent lights from turning on when there is ample natural light
58
SIDE VIEW
8
0
0 3 8 15
23
31
32
68
N
OSW12-M0W Field of View (in feet)
24
www.leviton.com
To learn more about Leviton devices or for answers to technical questions call our Techline at
1-800-824-3005 or visit us at:
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
Energy Management & Dimming Products
Occupancy Sensor Product Listing
INFRARED INDOOR WALL-MOUNT OCCUPANCY SENSORS
3.67
(93.2)
Advanced PIR technology for highly accurate monitoring. All-digital self-adjusting technology
provides “install and forget” solution for automatic lighting control. Use with Leviton Power Pack
or, where compatible, Centura Dimming Power Pack.
SPECIFICATIONS & FEATURES
Occupancy Sensors & Lighting Control Products
• OSWWV-I: Ideal for conference rooms, stairwells, high-ceiling rooms, large open areas,
parking garages, storage rooms, and rooms with pendant fixtures. Also ideal for
corner mounting
• OSWHB-I & OSWLR-I: Ideal for monitoring long, narrow spaces such as warehouse aisles,
hallways, closets, and storage areas. Also ideal for corner mounting
• Self-adjusting settings continuously analyze and adjust for optimum performance
5.50
(139.7)
• Adjustable swivel neck rotates 80° vertically and 60° horizontally. Can be used for ceiling
or wall mounting
• Ambient light override prevents lights from turning on when there is ample natural light
• Manual delayed-off-time settings of 30 seconds to 30 minutes
• Self-Adjusting delayed-off-time interval settings for 30 seconds to 30 minutes.
Compensates for real-time occupancy patterns — preventing unnecessary on/off switching
• Non-volatile memory preserves all automatic and manual settings during power outages
4.12
(104.6)
• Fast, simple installation using 3 color-coded low-voltage wires and a single mounting post
2.80
(71.1)
TESTING & CODE COMPLIANCE
• CUL/US Certified
OSWWV-I0W
• Meets ASHRAE Standard 90.1 requirements
• Backed by a Limited Five-Year Warranty
N
25
www.leviton.com
To learn more about Leviton devices or for answers to technical questions call our Techline at
1-800-824-3005 or visit us at:
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
Energy Management & Dimming Products
Occupancy Sensor Product Listing
WIDE-VIEW, HIGH-BAY & LONG RANGE INFRARED WALL-MOUNT
OCCUPANCY SENSORS
DESCRIPTION
Wide-View Infrared Wall-Mount
Occupancy Sensor*
CAT. NO.
OSWWV-I0W
COVERAGE
115°, 2500SF
COLOR
White
High-Bay Infrared Wall-Mount Occupancy Sensor* OSWHB-I0W
55 ft., 7 ft. wide White
@ 30 ft. high
Long-Range Infrared Wall-Mount
Occupancy Sensor*
100ft., 110°
@ 10ft. high
OSWLR-I0W
White
*Compatible with Centura Fluorescent Energy Management System.
Occupancy Sensors & Lighting Control Products
NOTE: Use low-voltage wiring to connect sensors to OSPXX Power Pack or if Centura-compatible,
to a CN100 Power Pack (purchased separately). See Page N27 for information on OSP Power Packs.
NOTE: See Page N34 for wiring diagrams.
TOP VIEW
TOPVIEW
58
3.5
0
3.5
29
SIDE VIE
W
30
0
29
0 3
13
25
52
OSWHB Field of View
58
SIDE VIEW
8
TOP VIEW
16.6
0
0 3 8 15
31
68
0
OSWWV Field of View (in feet)
16.6
SIDE VIEW
10
Minor Motion, IR
Major Motion, IR
0
0
14
42
71
100
OSWLR Field of View
N
26
www.leviton.com
To learn more about Leviton devices or for answers to technical questions call our Techline at
1-800-824-3005 or visit us at:
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
Energy Management & Dimming Products
Occupancy Sensor Product Listing
OCCUPANCY SENSOR POWER PACKS
Occupancy Sensors & Lighting Control Products
Power packs provide power for occupancy sensors as well as load switching circuitry.
A Leviton Power Pack is required with any low voltage occupancy sensor. Add-A-Relay
units can be used to expand control capability.
3.66
(93.0)
SPECIFICATIONS & FEATURES
Power Pack
• For use with all OS Series occupancy sensors
• Power supply for OS Series occupancy sensors
• Switches incandescent, magnetic and electronic fluorescent, magnetic and
electronic low voltage, and motor loads
• Compact size and light weight allows easy mounting through knockout in junction box
(from either inside or outside the box) with a simple twist-on nut
Add-A-Relay
• Expands power pack load capacity by functioning as a supplementary relay
• Provides ability to switch loads in different voltage systems
• Compatible with electronic ballasts
• Same compact size and mounting features as Power Pack
2.35
(59.7)
1.38
(35.1)
OSP20-RD0
Nipple Adapter
• Simplifies the connection of occupancy sensor to the low-voltage side of a power
pack mounted inside a fluorescent ballast cavity
• 1/2" conduit lock nut included
TESTING & CODE COMPLIANCE
• CUL/US, FCC and NOM Certified
• Meets ASHRAE Standard 90.1 requirements
• Backed by a Limited Five-Year Warranty
Power Packs and Accessories
DESCRIPTION
Power Pack
CAT. NO.
POWER
INPUT
OSP20-0D0 120/220/277VAC,
60Hz
RELAY RATING
20A Fluorescent/Incandescent @ 120V,
20A Fluor.@ 277V; 1HP @120V,
2HP @ 240V
COMMERCIAL GRADE
CONTROL POWER SUPPLY
INPUT
OUTPUT
5mA,
150mA,
24VDC
24VDC
Power Pack with
HVAC relay
OSP20-RD0 120/220/277VAC,
60Hz
20A Fluorescent/Incandescent @ 120V,
20A Fluor.@ 277V; 1HP @ 120V,
2HP @ 240V; HVAC: 0.5A @ 125VAC,
1A @ 30VDC
5mA,
24VDC
150mA,
24VDC
Power Pack with
HVAC relay
OSP15-R30 347VAC, 60Hz
15A Fluorescent @ 347V; 1HP @ 120V,
2HP @ 240V; HVAC: 0.5A @ 125VAC,
1A @ 30VDC
5mA,
24VDC
120mA,
24VDC
Add-A-Relay Unit
with HVAC relay
OSA20-R00 —
15A Incandescent @120V, 20A Fluorescent 5mA,
@120V, 20A Fluor. @ 277V, 15A
24VDC
Fluor. @ 347V; HVAC: 0.5A @ 125VAC,
1A @ 30VDC
Low-Voltage Nipple Adapter with 1/2" Lock Nut for Power Pack and Add-A-Relay units
—
OSPNA-000
Power Pack Capacity Formula
Leviton power packs can be used to provide power to one or more occupancy sensors. Since current consumptions of
occupancy sensors may vary, the best way to ensure you order the correct number of power packs and add-a-relays is by using
this formula:
# of sensor
Model As
X
Sensor A current
consumption rating
+
# of sensor
Model Bs
X
Sensor B current
consumption rating…
+
# of Add a
Relays
X
50mA
≤ 150mA per power pack
SENSOR
CURRENT CONSUMPTION
OSC04-I, OSC15-I, OSWHB-I, OSWLR-I, OSWWV-I 20mA
N
27
OSC05-M, OSC05-U, OSW12-M
30mA
OSC20-M, OSC20-U
32mA
OSC10-M, OSC10-U
40mA
OSA20-R00 Add a Relay
50mA
www.leviton.com
To learn more about Leviton devices or for answers to technical questions call our Techline at
1-800-824-3005 or visit us at:
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
Energy Management & Dimming Products
Occupancy Sensor Product Listing
OUTDOOR MOTION SENSORS
9.16
(232.7)
Passive Infrared (PIR) outdoor motion sensors provide outstanding
value in security lighting, as well as convenience, safety and energy
savings for a wide range of commercial and residential applications.
SPECIFICATIONS & FEATURES
5.36
(136.1)
Professional Series
• Ideal for a wide range of commercial/industrial settings including parking
areas, storage facilities, warehouses, loading docks, marina, garages, walkways,
campus grounds, meat lockers, walk-in refrigerators/freezers, and outbuildings
4.50
(114.3)
• Ambient light override prevents lights from turning on when there is ample
natural light
Occupancy Sensors & Lighting Control Products
• Adjustable sensitivity and immunity to RFI signals reduces false triggers
2.43
(63.0)
• Surge suppression minimizes likelihood of damage due to electrical surges
• Temperature compensation feature ensures uniform performance in extreme
hot or cold weather and during temperature fluctuations
Residential Series
PS200
• Ideal for a wide range of residential settings including backyards, garages,
entranceways, porches, swimming pool areas, doorways, and private docks
• Adjustable sensitivity reduces false triggers
Both Series
• Sensor neck adjustment allows accurate monitoring: 110° vertical, 180° horizontal,
110° rotational
• With or without with dual floodlight lampholder
• Adjustable delayed-off-time settings from 20 seconds (for test mode) to 15 minutes
• Provides automatic, test and continuous modes. Test mode simulates automatic
operation with short delayed-off-time for easy adjustments. Continuous mode
enables manual override for constant “lights on” operation (when used with
standard on/off switch)
TESTING & CODE COMPLIANCE
• UL Listed and CSA Certified
• Meets ASHRAE Standard 90.1 requirements
• Backed by a Limited Five-Year Warranty
N
28
www.leviton.com
To learn more about Leviton devices or for answers to technical questions call our Techline at
1-800-824-3005 or visit us at:
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
Energy Management & Dimming Products
Occupancy Sensor Product Listing
OUTDOOR MOTION SENSORS
Professional Series
RATING
Incandescent: 1000W @ 120V.
Fluorescent/Inductive: 500VA @ 120V.
For 60Hz AC only
COVERAGE
200°
COMMERCIAL GRADE
COLOR
White
Outdoor PIR Motion Sensor
PS200-1F
with Dual Floodlight Lampholder
Same as Above
200°
White
Outdoor PIR Motion Sensor
PS110-10
Same as Above
110°
White
Outdoor PIR Motion Sensor
PS110-1F
with Dual Floodlight Lampholder
Same as Above
110°
White
CAT. NO.
RS110-10W
RATING
Incandescent: 500W @ 120V.
Fluorescent/Inductive: 500VA @ 120V.
For 60Hz AC only
COVERAGE
110°
RESIDENTIAL GRADE
COLOR
White
Outdoor PIR Motion Sensor
RS110-1FW
with Dual Floodlight Lampholder
Incandescent: 500W @ 120V.
Fluorescent/Inductive: 500VA @ 120V.
For 60Hz AC only
110°
White
Occupancy Sensors & Lighting Control Products
DESCRIPTION
Outdoor PIR Motion Sensor
CAT. NO.
PS200-10
Residential Series
DESCRIPTION
Outdoor PIR Motion Sensor
TOP VIEW
50
TOP VIEW
50
0
0
50
50
SIDE VIEW
SIDE VIEW
10
10
0
0
0
PS110/RS110 Field of View (in feet)
50
0
50
PS200 Field of View
N
29
www.leviton.com
To learn more about Leviton devices or for answers to technical questions call our Techline at
1-800-824-3005 or visit us at:
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
Energy Management & Dimming Products
Occupancy Sensor Applications
UNDERSTANDING SENSOR CATALOG NUMBERS
First 2 Letters
3rd Character:
type of product
Last 2 Characters
OS = Occupancy
Sensor
C = Ceiling Mount
OD = Occupancy
Detector
1st Character of
Suffix: sensor
technology
2nd Character of
Suffix: voltage
3rd Character of
Suffix: color
04 = 400sf
I = Infrared
1 = 120V
W = White
W = Wall Mount
05 = 500sf or 5A
M = Multi-technology
2 = 230V
I = Ivory
P = Power Pack
10 = 1000sf or 10A
R = Relay (HVAC)
3 = 347V
A = Almond
A = Add-A-Relay
12 = 1200sf
T = California Title 24
Compliant
7 = 277V
T = Light Almond
S = Switch
Replacement
15 = 15A
U = Ultrasonic
D = Dual Voltage
120/277V
20 = 2000sf
0 = N/A
0 = N/A
G = Gray
B = Brown
0 = N/A
0 = N/A
0D = Dual relay
0S = Self-contained
CG = Cage
HB = High Bay
LR = Long Range
NA = Nipple Adapter
RA = Raceway
Adapter
WV = Wide View
ABOUT SENSING TECHNOLOGIES
Passive Infrared (PIR)
Infrared occupancy sensors are passive devices designed to detect the movement of heat-emitting
bodies. They are installed to monitor areas where there are no physical obstructions to block the
sensor’s field of view. HOW IT WORKS: People naturally emit a small amount of infrared heat. As a
person passes through the field of view, the sensor detects the motion as a change in the infrared
background and responds by switching on area lights. After the field of view is unoccupied for a
user-defined delayed-off time, the sensor will automatically turn off the lights.
Ultrasonic (US)
Ultrasonic sensing technology provides highly accurate small-motion detection. Leviton sensors
employing ultrasonic technology are well suited to monitoring areas, especially smaller or narrow ones,
with inanimate objects (such as furniture) that block the line of sight and hence are likely to block the
field of view of PIR sensors. They are also ideal where more sensitive detection is required. HOW IT
WORKS: Ultrasonic occupancy sensors generate high frequency sound waves beyond the capability of
human hearing, due to the Doppler Effect. These controls are active: continually emitting sound waves
and monitoring changes in the return time of the reflected sound waves. Movement in the sound wave
field causes a change in wave frequency and the sensor responds by switching on area lights. When the
change in frequency is no longer detected after a delayed-off time, the sensor turns off the lights.
Leviton ultrasonic sensors operate at a frequency outside the range of most hearing aid products and
will not interfere with their ability to operate properly.
Multi-technology
Multi-technology occupancy sensors combine ultrasonic sensing for maximum sensitivity with PIR
technology to prevent false triggers from air conditioning and corridor activity. These sensors are ideal
for large, open areas including office areas with cubicles, general workspaces, warehouse and storage
facilities, cafeterias, and public areas in commercial facilities. HOW IT WORKS: Leviton multi-technology
sensors utilize both sensor technologies to determine when to turn the lights off.
Occupancy Sensors & Lighting Control Products
F = Fixture Mount
–
Adaptive Definition
A dedicated internal microprocessor continually analyzes the room environment and adjusts itself
automatically. The internal timer, detection sensitivity and thresholds are automatically adjusted. Once
installed, a sensor incorporating adaptive technology should never require manual adjustment or
calibration.
N
30
www.leviton.com
To learn more about Leviton devices or for answers to technical questions call our Techline at
1-800-824-3005 or visit us at:
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
Energy Management & Dimming Products
Occupancy Sensor Applications
Occupancy Sensors & Lighting Control Products
ABOUT DIFFERENT SENSOR DESIGNS
Sensor Type
When to Use
Wall-Switch
When you don’t want to install a separate device, choose this sensor because it replaces an
existing wall switch. Get both occupancy sensing and manual on/off switching in a single device.
Ceiling-Mount
For 180° or 360° coverage of an area (360° sensor shown).
Wall-Mount
For coverage of irregularly shaped areas and those with varying ceiling heights, as well as narrow
hallway and high-bay corridor applications. For detection in spaces outside the field of view
of other occupancy sensors. Can be pointed in different directions.
SELECTION & PLACEMENT
Sensors can be mounted in the middle of walls, in corners, or on ceilings. Occupancy sensors must be intelligently placed in order to ensure
that motion is detected throughout an entire space. With a variety of models from which to choose, care should be taken to select the proper
combination of sensors to cover an entire area with motion detection.
Factors to consider before selecting and placing an occupancy sensor include:
• Size and shape of area needing coverage compared to ranges of occupancy sensors
• Obstacles that may block the sensor’s line of sight
• How much activity there is in a space
• Ceiling height
• Airflow that can falsely register as motion
• Location of HVAC ducts
Select a Centura-compatible occupancy sensor when installing an occupancy sensor within a Centura Energy Management System. In this
case, the CN100 Power Pack provides power to the occupancy sensor (no OSPXX is required). Please note that Centura’s Dimming Power
Pack also has its own built-in HVAC relay.
Leviton’s Lighting Management Systems Division provides a complimentary occupancy-sensor layout service. This service provides
suggested sensor selection and placement on a customer’s drawings in either paper or electronic form, along with a bill of material detailing
the components necessary for that layout. Send an e-mail to oslayout@leviton.com to request this service.
APPLICATION WIRING DIAGRAMS
Occupancy Sensor and Dimmer Controlling One Load
(manual override off)
Two Occupancy Sensors Controlling One Load
(manual override off)
Neutral
Neutral
Rocker Switch
LOAD
White (if necessary) White
0 Line
Ballast
Blue Black
Line
Black
Blue
Blue
Green Ground
Black
Line
Green Ground
Note: Ground must be connected
Blue
Black
Any Dimmer
Green Ground
Green Ground
Note: Ground must be connected
3-Way applications for Manual-On Occupancy Sensor, Remote
and Vizia Devices
Manual-On
Occupancy
Sensor
(IPP15)
or
Dimmer
(VZI06)
Switch Remote
(VZ0SR)
or
Manual-On
Occupancy
Sensor Remote
(IPP0R-1L)
N
31
www.leviton.com
To learn more about Leviton devices or for answers to technical questions call our Techline at
1-800-824-3005 or visit us at:
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
Energy Management & Dimming Products
Occupancy Sensor Techincal Information
WIRING DIAGRAMS
WALL-SWITCH OCCUPANCY SENSORS
ODS0D Wall-Switch Occupancy Sensor Wiring Diagram
(For Single Pole, Two Phase Applications)
ODS0D Wall-Switch Occupancy Sensor Wiring Diagram
(For Single Pole, Single Phase Applications)
ODS0D
ODS0D
Red (To Phase 2)
Red
Hot (Black)
Phase 1
Hot (Black)
Phase 1
Red
Black
Red
Black
Blue
Blue
Green
Ground
Secondary
Load
Line 1
120/277VAC,
60Hz
Primary
Load
Green
Ground
Secondary
Load
Neutral 1 (White)
Neutral (White)
Neutral 2
Note: Ground must be connected
Note: Ground must be connected
ODS10/15 Wall-Switch Occupancy Sensor Wiring Diagram,
Single Location Control
ODS10/15 Wall-Switch Occupancy Sensor Wiring Diagram,
Two-Location Control
ODS10/15
ODS10/15
Blue
Blue
Hot (Black)
Black
Black
Black
Blue
Hot (Black)
Black
Black
Line
120/277VAC,
60Hz
Load
Green
Ground
White
Neutral (White)
Load
Green
Ground
Neutral (White)
Note: Ground must be connected
Note: Ground must be connected
PR150 Wall-Switch Occupancy Sensor Wiring Diagram
PR180 Wall-Switch Occupancy Sensor 3-Way Wiring Diagram
PR150
Switch #1
Common
Terminal
(Black Screw)
Hot (Black) Black
Black
Jumper
Traveler
A
Red
Line
120VAC,
60Hz
Traveler B
Neutral (White)
Yellow
Load
Green
Ground
Green
Ground
White
White
Hot (Black)
Black
Load
Green
Ground
PR180
Black
Black
Line
120VAC,
60Hz
White
Green
Ground
Line
120/277VAC,
60Hz
Occupancy Sensors & Lighting Control Products
Primary
Load
Line 2
Line
120/277VAC,
60Hz
Neutral (White)
N
32
www.leviton.com
To learn more about Leviton devices or for answers to technical questions call our Techline at
1-800-824-3005 or visit us at:
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
Energy Management & Dimming Products
Occupancy Sensor Techincal Information
CEILING-MOUNT OCCUPANCY SENSOR WIRING DIAGRAMS
OS-Series Ceiling Mount Occupancy Sensor
(with Power Pack) Wiring Diagram
OSPxx Series
Power Pack
ODC0S-I2 Ceiling Mount Occupancy Sensor,
Single-Location Wiring Diagram
Sensor
NC-Brown
Common-Green
NO-Brown/White
Red (24VDC)
Black
Blue
Red
Black
Blue* (occupancy)
(control)
Blue
Black
Gray*
Load
(photocell
+ occupancy)
Neutral (White)
ODC0S-I2 Ceiling Mount Occupancy Sensor,
Two-Location Wiring Diagram
ODC0S-I1 Ceiling Mount Occupancy Sensor Wiring Diagram
Hot (Black)
Blue
Black
Blue
Blue
Black
Black
Hot (Black)
Blue
Black
Blue
Blue
Line 120VAC, 60Hz
White
White
Sensor
Black
Load
Line 220-240VAC
50Hz
White
Sensor
Load
White
Neutral (White)
Neutral (White)
ODC0S-I7 Ceiling Mount Occupancy Sensor Wiring Diagram
OPB15-0DW Power Base Adapter
Hot (Black)
Red
Blue
Blue
Sensor
Load
Neutral (White)
Black
Line 277VAC, 60Hz
White
Hot (Black)
120/277V
Load (Blue)
Load
OPB15 Power Base
White
Occupancy Sensors & Lighting Control Products
VAC60Hz
Black
Neutral (White)
White
Blue
Black
Blue
Sensor
Load
Blue* (occupancy)
Gray*
White
Line 120/277/347
Red
Black
Blue
Black
Line 220-240VAC 50Hz
White
(photocell
+ occupancy)
Hot
Black
Hot (Black)
To HVAC System
Any Leviton Low-Voltage
Ceiling Sensor
Neutral (White)
OSFHB-ITW Occupancy Sensor Wiring Diagram
Hot (Black)
Black
Red
Line
120VAC, 60Hz
Black
Sensor
White
Load
*When the photocell function is not
being used, connect the Blue
Occupancy Sensor lead to the Blue
Power Pack lead. When using the
Photocell function, connect the Gray
Occupancy Sensor lead to the Blue
Power Pack lead – Do not use the
Blue Occupancy Sensor lead for the
photocell function.
White
N
33
Neutral (White)
www.leviton.com
To learn more about Leviton devices or for answers to technical questions call our Techline at
1-800-824-3005 or visit us at:
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
Energy Management & Dimming Products
Occupancy Sensor Techincal Information
WALL-MOUNT OCCUPANCY SENSOR WIRING DIAGRAMS
OSWxx Occupancy Sensor Wiring Diagram with
Single Power Pack
OSPxx Series
Power Pack
OSWxx Occupancy Sensor Wiring Diagram with
Multiple Power Packs
Sensor
OSPxx Series
Power Pack
NC-Brown
Common-Green To HVAC
System
NO-Brown/White
Sensor
NC-Brown
Common-Green
NO-Brown/White
Red (24VDC)
Black
Red (24VDC)
Blue
(Control)
To HVAC
System
Black
Black
Red
Blue
(Control)
Black
Black
Red
Black
Gray*
Hot (Black)
Load
(photocell +
occupancy)
Blue
(occupancy)
Hot (Black)
Black
Line
120/277/347VAC
60Hz
White
Gray*
Blue
Red
Black
Blue*
Blue
Black
Blue*
Red
White
(occupancy)
Black
Line
120/277/347VAC
60Hz
Gray*
(photocell +
occupancy)
White
Gray*
(photocell +
occupancy)
Neutral (White)
NC-Brown
Common-Green
NO-Brown/White
To HVAC
System
OSWxx Occupancy Sensor Wiring Diagram with
Power Pack and Add-A-Relay
OSPxx Series
Power Pack
OSPxx Series
Power Pack
Sensor
Hot (Black)
NC-Brown
Common-Green
NO-Brown/White
Red (24VDC)
Line
120/277/347VAC
60Hz
To HVAC
System
Black
Blue
(Control)
Blue
Blue
Black
Black
White
Load
Neutral (White)
Black
White
Red
Black
Blue*
(occupancy)
Gray*
Blue
Load
(photocell +
occupancy)
Blue
Red
Black
Black
Line
120/277/347VAC
60Hz
White
White
Blue*
(occupancy)
Gray*
(photocell +
occupancy)
Neutral (White)
NC-Brown
Common-Green
NO-Brown/White
To HVAC
System
OSA20
Add-A-Relay
Hot (Black)
Line
120/277/347VAC
60Hz
White
Blue*
(occupancy)
Neutral (White)
Hot (Black)
Load
(photocell +
occupancy)
Blue
Occupancy Sensors & Lighting Control Products
Blue*
(occupancy)
Blue
Blue
Black
Load
Neutral (White)
White
*When the photocell function is not being used, connect the Blue Occupancy Sensor lead to the Blue Power Pack lead.
When using the Photocell function, connect the Gray Occupancy Sensor lead to the Blue Power Pack lead–Do not use
the Blue Occupancy Sensor lead for the photocell function.
N
34
www.leviton.com
To learn more about Leviton devices or for answers to technical questions call our Techline at
1-800-824-3005 or visit us at:
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
Energy Management & Dimming Products
DECORA® ELECTRONIC TIMER SWITCHES
Occupancy Sensors & Lighting Control Products
The Leviton line of timer switches provides quiet, accurate electronic timing for reliable lighting and motor control. Electronic timers can be used not only to reduce energy costs, but
automated switching also contributes to anti-theft measures if used when a home is left
unoccupied; to general safety by turning lights on before you arrive home; and to convenience, for example, by turning on the pool filter automatically. A variety of preset electronic
and fully programmable models feature specifications to fit every application. All switches
come with matching Decora® or Decora Plus wallplates.
Relay switches lights on/off
LED indicates selection
Tactile switches for
time-out selection
6215M-W
Locator LED illuminates
when lights are off
• Preset timers with settings from 2 minutes to 12 hours
• Programmable units initiate scheduled switching at the touch of a button
(Second touch to turn load off)
• Programmable units retain schedule during power outages via backup batteries
• No moving parts to break or rotary wind-up ticking noise
• Contemporary styling coordinates with other Decora designer devices
• Install in single-gang wallboxes in place of standard switches — ideal for new construction,
retrofitting, and remodeling
Available Colors
N
35
White
Ivory
Almond
www.leviton.com
To learn more about Leviton devices or for answers to technical questions call our Techline at
1-800-824-3005 or visit us at:
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
Energy Management & Dimming Products
Electronic Timer Switches
DECORA PLUS™ PRESET ELECTRONIC TIMER SWITCHES
1.53
(38.9)
Leviton timers add contemporary styling to any commercial or residential application.
Built to the highest performance standards, Decora electronic timers provide long-lasting,
trouble-free service life. Decora Plus preset timers are ideal for heat lamps, foyer and
outdoor lights, hot tubs, spas, and attic and exhaust fans.
SPECIFICATIONS & FEATURES
• Four preset buttons plus Off for timed control of lights and appliances
• LEDs indicate time elapsed and last LED flashes a two-minutes-until-off warning
• Installs easily in single gang wallbox in place of standard switch
2.67
(67.8)
4.13
(104.9)
• Matching Decora Plus wallplate included
• UL Listed and CSA and NOM Certified
• Meets ASHRAE Standard 90.1 requirements
• Backed by a Limited Two-Year Warranty
2.38
(60.5)
6215M-W
3-Wire Timer Switches (single pole, neutral required)
COMMERCIAL GRADE
COLOR
W, I, A*
DESCRIPTION
3-Wire 15-minute Timer with
4 Preset Buttons & Off
CAT. NO.
6215M
RATING
120VAC 60Hz, 1000W Incandescent,
20A Inductive, 1 HP @ 120V.
Compatible with electronic ballasts
INTERVAL
2-5-10-15 minutes
3-Wire 30-minute Timer with
4 Preset Buttons & Off
6230M
Same As Above
5-10-15-30 minutes W, I, A*
3-Wire 1-hour Timer with
4 Preset Buttons & Off
6260M
Same As Above
10-20-30-60 minutes
W, I, A*
3-Wire 12-hour Timer with
4 Preset Buttons & Off
6212H
Same As Above
2-4-8-12 hours
W, I, A*
2-Wire Timer Switches (single pole)
RESIDENTIAL GRADE
COLOR
W, I, A*
DESCRIPTION
15-minute Timer with
4 Preset Buttons & Off
CAT. NO.
6515M
RATING
120VAC 60Hz, 600W Incandescent,
5A Inductive. Not compatible with
electronic ballasts
INTERVAL
2-5-10-15 minutes
60-minute Timer with
4 Preset Buttons & Off
6560M
Same As Above
10-20-30-60 minutes
W, I, A*
12-hour Timer with
4 Preset Buttons & Off
6512H
Same As Above
2-4-8-12 hours
W, I, A*
* Add suffix to catalog number for color: White (-W), Ivory (-I), Almond (-A). Comes with matching Decora wallplate.
NOTE: See Page N38 for guidelines to selecting the appropriate timer and Page N39 for wiring diagrams.
Occupancy Sensors & Lighting Control Products
TESTING & CODE COMPLIANCE
N
36
www.leviton.com
To learn more about Leviton devices or for answers to technical questions call our Techline at
1-800-824-3005 or visit us at:
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
Energy Management & Dimming Products
Electronic Timer Switches
1.53
(38.9)
DECORA® ELECTRONIC PROGRAMMABLE TIMER SWITCHES
This residential line of programmable timers features Decora styling to enhance any interior.
Impact-resistant thermoplastic face and quality construction provides long service life and
superior performance.
SPECIFICATIONS & FEATURES
24-hour Timer
Occupancy Sensors & Lighting Control Products
• Ideal for a wide variety of commercial and residential applications including outdoor lighting,
pools, motors, sprinklers, exhaust and attic fans, bathroom heat lamps, hot tubs and spas, whole
house exhaust fans, office lights, janitor closets, and landscape and security lighting
2.67
(67.8)
4.13
(104.9)
• Permits separate on or off scheduling for half-hour periods of the day; on/off manual
control available
• Features easy-to-read LCD and easy-to-use programming buttons
14-hour Timer
• Ideal for residential incandescent lighting control including indoor, outdoor, and seasonal lighting
2.38
(60.5)
• Automatic daily control with manual override for set-it-and-forget-it convenience
• Automates daily switching program (up to 14 hours) by responding to dip switch on or
off position for each hour; repeats until function switch is moved to manual or off mode
6124H
Countdown Timer
1.43
(36.3)
• For residential and light commercial applications including indoor and outdoor lighting,
office lights, and ceiling fans
• Simple rotary-dial time selection of settings from 1 minute to 18 hours; on/off manual
control available
• Illuminated LED indicates load is on. Blinking LED and annunciator sound indicate end of time cycle
TESTING & CODE COMPLIANCE
• UL Listed and CSA Certified
2.73
(69.2)
4.13
(104.9)
1.73
(43.9)
6651
DESCRIPTION
24-Hour LCD
Programmable Timer Switch
CAT. NO.
6124H
RATING
1200W Incandescent; 1200VA
Inductive @ 120VAC 60Hz;
Motor:1 HP @ 120VAC 60Hz UL,
3/4 HP @ 120VAC 60Hz CSA.
Neutral connection required.
Compatible with electronic ballasts
INTERVAL
24-Hour on/off
scheduling in
30-minute
intervals
DESCRIPTION
14-Hour SegmentProgrammable Timer Switch
CAT. NO.
6651
RATING
40W min, 500W max. @120VAC
60Hz, Incandescent only.
Neutral not required.
Not compatible with electronic
ballasts
INTERVAL
14-Hour ON/OFF
scheduling in
hourly intervals
Rotary-Dial Variable
Countdown Timer
Switch
6652
600W Incandescent; 20A Inductive
Motor: 1 HP @ 120VAC 60Hz
Neutral connection required.
Compatible with electronic ballasts
1 Minute to
18 Hours
COMMERCIAL GRADE
COLOR
W, I, A*
RESIDENTIAL GRADE
COLOR
W, I, A*
W, I, A*
* Add suffix to catalog number for color: White (-W), Ivory (-I), Almond (-A). Comes with matching Decora wallplate. (6124H cannot be used
with Decora Plus Screwless Snap-On Wallplates.)
N
37
NOTE: See Page N38 for guidelines to selecting the appropriate timer and Page N39 for wiring diagrams.
www.leviton.com
To learn more about Leviton devices or for answers to technical questions call our Techline at
1-800-824-3005 or visit us at:
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
Energy Management & Dimming Products
Electronic Timer Switches
SELECTING THE RIGHT TIMER
When to Use
Typical Applications
Prevent lights/appliances
from being left on, for
energy management
Heat lamps, foyers, outdoor lights,
hot tubs, spas, and attic and
exhaust fans
24-Hour
Programmable Timer
Automate light/appliance
switching over a
24-hour period
To ensure that whatever is turned on
does not remain on after a certain
period of time, while giving the user
some flexibility as to how long this
“on”-period lasts
When you want to schedule something
to go on or off multiple times, that
may span a period of up to 24 hours
14-Hour
Programmable Timer
Automate light/appliance
switching over a 14-hour
period
Variable
Countdown Timer
Residential security systems
When you want to schedule something
to go on or off multiple times over a
period no longer than 14 hours. For
example, if you need something to go
on and off only at night time (such as
holiday lights that turn on in the
evening and off later at night)
If you want lights and/or appliances to
automatically turn on and off at
somewhat random times each day.
An ideal choice for giving your house
a lived-in look while you are away,
to help deter break-ins
Commercial and residential outdoor
lighting, pools, motors, sprinklers,
exhaust and attic fans, bathroom heat
lamps, hot tubs and spas, wholehouse exhaust fan scheduling, office
lights, janitor closets, landscape
and security lighting
Residential incandescent lighting
control including indoor, outdoor,
and seasonal lighting
Residential applications including
indoor and outdoor lighting, and
ceiling fans
MAIN ADVANTAGES OF ELECTRONIC TIMERS OVER MANUAL TIMERS
• Retain programmed schedules during power outages
• Quieter: no moving parts means that electronic timers do not make noise while operating or programming
Occupancy Sensors & Lighting Control Products
Primary Use
Preset Electronic Timer
N
38
www.leviton.com
To learn more about Leviton devices or for answers to technical questions call our Techline at
1-800-824-3005 or visit us at:
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
Energy Management & Dimming Products
Electronic Timer Switch Technical Information
ELECTRONIC TIMER SWITCH WIRING DIAGRAMS
6651 Timer Wiring Diagram, Single Pole Application
Blue
Black
Black
Line 120V AC/CA 60Hz
Yellow
Load
Green Ground
White
Neutral (White)
6651 Timer Wiring Diagram, 3-Way Application
Timer Switch
6212H Timer Wiring Diagram
3-Way Black Screw –
Switch Common
Terminal
Black
Hot (Black)
Blue
Black (Hot)
Brass Screw –
Leave one
traveler
terminal
unused
Brass Screw
Load
Blue
Black
White
120V AC/CA,
60Hz
Load
White (Neutral)
TOP
White
Yellow
Occupancy Sensors & Lighting Control Products
Hot (Black)
Line
Green
Green Ground Green Ground
Neutral
Ground
Neutral (White)
N
39
www.leviton.com
To learn more about Leviton devices or for answers to technical questions call our Techline at
1-800-824-3005 or visit us at:
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
Energy Management & Dimming Products
Z-MAX™ Relay Overview
LIGHTING CONTROL RELAY SYSTEMS
NEMA Type-1 enclosure
with removable door
Modular connectors for
wiring outside cabinet
Keyed lock
Multi-voltage power
supply (120V-347V)
Revolutionary Z-Max
relay circuit provides
unmatched durability
Contractor-friendly
oversized lugs accept
#8-16 AWG wire
Keypad with LCD and
oversized buttons eases
programming
• In four versions: 8-relay non-networked and 8-relay, 24-relay, 48-relay networked
• Single-circuit relay cards simplify maintenance and expansion
• Integrated astronomical time clock
• Individually replaceable relays rated for all light sources as well as motors
• Single-pole and two-pole relays fit in the same location
• Normal or emergency panel capability
• Compatible with occupancy sensors, photocells, digital and low-voltage wall stations and more
Occupancy Sensors & Lighting Control Products
The Leviton Z-MAX™ line of timed lighting controls and relays provides advanced scheduling
of lighting and other loads in applications where a time clock is typically used in conjunction
with switching contactors. All Z-MAX models feature easy-to-use menu-driven programming
and configuration, a programmable time clock and output relays in a compact cabinet, and
several optional accessories for remote control. Z-MAX relay panels are ideal for cafeterias,
auditoriums, offices, parking facilities, gymnasiums, pools, educational facilities, and landscape and security lighting. A number of wall stations, flush trim kits and other accessories
are available.
Available Colors
N
Blue
40
www.leviton.com
To learn more about Leviton devices or for answers to technical questions call our Techline at
1-800-824-3005 or visit us at:
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
Energy Management & Dimming Products
Z-MAX™ Relay Product Listing
Z-MAX™ RELAY CABINETS
Leviton Z-MAX relay cabinets come in four versions: 8-relay non-networked and 8-relay, 24-relay and
48-relay networked. Standalone cabinets are best suited to advanced scheduling of a single area,
while networked cabinets provide centralized control for large multi-office and multi-building sites.
The 24-relay and 48-relay models are available in slave versions. The main control module handles up
to 96 inputs and 96 relays, and utilizes low voltage wiring as the panel interconnect. All cabinets are
pre-wired and factory tested.
SPECIFICATIONS & FEATURES
• Easy-to-program keypad control module with LCD screen and straightforward menus — in plain
English (not code)
Occupancy Sensors & Lighting Control Products
• Internal time clock with astronomical clock, daylight savings time, and holiday scheduling features
• Generous wiring space and easy-to-wire terminals
• Switch inputs with override capability for each relay
• Hinged, removable door with keyed lock
• Works with analog controllers, low voltage switches, discrete and analog photocells, and occupancy
sensors; Networkable versions also with Z-MAX Digital Switches, Dimensions D4200/D8000 and
DMX 512 controllers
Accessories
• Telephone and modem interface modules
• Z-MAX Switch Stations
• Additional switch input board
• Ethernet module
• Photocell
• Flush trim kits
• Voltage barriers
8-Relay and 24-Relay Z-MAX Cabinets
• PC-based programming software
TESTING & CODE COMPLIANCE
• UL Listed (for individual load types) and CUL Listed
• CEC Title 24 compliant and meets ASHRAE Standard 90.1 requirements
• NOM certified
• Limited Two-Year Warranty on cabinet
• Ten-Year Warranty on relay cards
N
41
www.leviton.com
To learn more about Leviton devices or for answers to technical questions call our Techline at
1-800-824-3005 or visit us at:
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
Energy Management & Dimming Products
Z-MAX™ Relay Product Listing
Z-MAX™ RELAY CABINETS
8-Relay Z-MAX Cabinets
With 8 switch inputs and 20A output relays
DESCRIPTION
CAT. NO.
NETWORK VERSION
Standard 8-Relay Cabinet (no relays)
R08ND-000
CAT. NO.
STAND-ALONE VERSION
R08BD-000
INPUT POWER
COLOR
120, 277, 347V
Blue
R08ND-104
R08BD-104
120, 277, 347V
Blue
8-Relay Cabinet with 8 standard relays
R08ND-108
R08BD-108
120, 277, 347V
Blue
8-Relay Cabinet with 4 2-pole relays
R08ND-204
R08BD-204
120, 277, 347V
Blue
8-Relay Cabinet with 8 2-pole relays
R08ND-208
R08BD-208
120, 277, 347V
Blue
8-Relay Cabinet with 4 347V relays
R08ND-C04
R08BD-C04
120, 277, 347V
Blue
8-Relay Cabinet with 8 347V relays
R08ND-C08
R08BD-C08
120, 277, 347V
Blue
CAT. NO.
SLAVE VERSION
R24SD-000
INPUT POWER
COLOR
120, 277, 347V
Blue
24-Relay Z-MAX Cabinets
With 12 switch inputs and 20A output relays
DESCRIPTION
CAT. NO.
MASTER VERSION
Standard 24-Relay Cabinet (no relays)
R24MD-000
24-Relay Cabinet with 12 standard relays
R24MD-112
R24SD-112
120, 277, 347V
Blue
24-Relay Cabinet with 24 standard relays
R24MD-124
R24SD-124
120, 277, 347V
Blue
24-Relay Cabinet with 12 2-pole relays
R24MD-212
R24SD-212
120, 277, 347V
Blue
24-Relay Cabinet with 24 2-pole relays
R24MD-224
R24SD-224
120, 277, 347V
Blue
24-Relay Cabinet with 12 347V relays
R24MD-C12
R24SD-C12
120, 277, 347V
Blue
24-Relay Cabinet with 24 347V relays
R24MD-C24
R24SD-C24
120, 277, 347V
Blue
CAT. NO.
SLAVE VERSION
R48SD-000
INPUT POWER
COLOR
120, 277, 347V
Blue
48-Relay Z-MAX Cabinets
With 12 switch inputs and 20A output relays
DESCRIPTION
CAT. NO.
MASTER VERSION
Standard 48-Relay Cabinet (no relays)
R48MD-000
48-Relay Cabinet with 12 standard relays
R48MD-112
R48SD-112
120, 277, 347V
Blue
48-Relay Cabinet with 24 standard relays
R48MD-124
R48SD-124
120, 277, 347V
Blue
48-Relay Cabinet with 36 standard relays
R48MD-136
R48SD-136
120, 277, 347V
Blue
48-Relay Cabinet with 48 standard relays
R48MD-148
R48SD-148
120, 277, 347V
Blue
48-Relay Cabinet with 12 2-pole relays
R48MD-212
R48SD-212
120, 277, 347V
Blue
48-Relay Cabinet with 24 2-pole relays
R48MD-224
R48SD-224
120, 277, 347V
Blue
48-Relay Cabinet with 36 2-pole relays
R48MD-236
R48SD-236
120, 277, 347V
Blue
48-Relay Cabinet with 48 2-pole relays
R48MD-248
R48SD-248
120, 277, 347V
Blue
48-Relay Cabinet with 12 347V relays
R48MD-C12
R48SD-C12
120, 277, 347V
Blue
48-Relay Cabinet with 24 347V relays
R48MD-C24
R48SD-C24
120, 277, 347V
Blue
48-Relay Cabinet with 36 347V relays
R48MD-C36
R48SD-C36
120, 277, 347V
Blue
48-Relay Cabinet with 48 347V relays
R48MD-C48
R48SD-C48
120, 277, 347V
Blue
Occupancy Sensors & Lighting Control Products
8-Relay Cabinet with 4 standard relays
PHYSICAL DIMENSIONS
8-Relay (Standalone and Networkable): 13.00 (330.2) x 13.00 (330.2) x 4.34 (110.6)
24-Relay Cabinet: 20.00 (514.4) x 34.00 (863.6) x 4.34 (110.6)
48-Relay Cabinet: 20.00 (514.4) x 54.00 (1371.6) x 4.34 (110.6)
NOTE: See Page N50 for wiring and mounting diagrams.
N
42
www.leviton.com
To learn more about Leviton devices or for answers to technical questions call our Techline at
1-800-824-3005 or visit us at:
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
Energy Management & Dimming Products
Z-MAX™ Relay Product Listing
Z-MAX™ RELAY CABINETS WITH INTEGRATED
ELECTRICAL DISTRIBUTION
SPECIFICATIONS & FEATURES
• Single or Three Phase configurations
• 120V, 277V or 347V systems
• Main lugs or main breaker
• Custom load center configuration
• Field replaceable standard breakers
• All standard Z-MAX operational features
• Uses Cutler-Hammer CH, GHQ and GBH frame snap-in breakers, locked in place by the
enclosure
• Ships as one complete pre-wired assembly
• Up to 100,000A AIC, short Circuit Current Rating, available on all panelboards
(Consult factory for details)
• 277/480V panelboards, main lugs, 65k AIC @ 120/208V, 14k AIC @ 277/480V standard
• 277/480V panelboard, main breaker, 35k AIC standard
• 120/208V or 120/240V panelboards, main lugs, 10k AIC standard
• 120/208V or 120/240V panelboards, main breaker, 25k AIC standard depending on main
breaker
• 347/600V panelboards, main lugs, 10k AIC standard
• 347/600V panelboards, main breaker, 19k AIC standard
Z-MAX Relay Cabinet
TESTING & CODE COMPLIANCE
• UL and cUL Listed
ORDERING INFORMATION
Common configuration shown. Many custom configurations are available upon request. Contact quotations for additional information.
Other Z-Max accessories may be applicable to your project. Reference Z-Max data sheets for information on these accessories.
BREAKER SECTION
RB423-L1C
120/208 3 Phase 42 Pole Breaker Cabinet w/Main Lugs
RB423-B1C
120/208 3 Phase 42 Pole Breaker Cabinet w/Main Breaker
RB421-L1C
120/240 1 Phase 42 Pole Breaker Cabinet w/Main Lugs
RB421-B1C
120/240 1 Phase 42 Pole Breaker Cabinet w/Main Breaker
277V SYSTEMS
RB423-L2C
277/480 3 Phase Breaker Cabinet w/Main Lugs
RB423-B2C
277/480 3 Phase Breaker Cabinet w/Main Breaker
347V SYSTEMS
RB423-L3C
347/600 3 Phase Cabinet, Custom/Configured, Main Lugs
RB423-B3C
347/600 3 Phase Cabinet, Custom/Configured, Main Breaker
Indicate Main Breaker Size (if applicable)
and quantity of branch breakers required.
120V SYSTEMS
Pick Only One
Occupancy Sensors & Lighting Control Products
Z-MAX Relay Panels with an integrated electrical distribution system offer the convenience of a
single feed with the flexibility of our popular Z-MAX relay system. Each includes all the award
winning features of the Z-MAX product line, integrated with a standard system of electrical
distribution and over current protection. These integrated systems use commonly available
Cutler-Hammer breakers.
Main Breaker Options (pick one if main breaker cabinet)
150A
175A
200A
225A
250A*
300A*
*277/480V panels only
Branch Breaker Options
Quantity
BRC01-120
BRC02-120
BRC01-115
BRC02-115
BRCG1-120
BRCG2-120
BRC01-220
BRC02-220
BRC01-215
BRC02-215
BRC01-C20
BRC01-C15
Branch
Branch
Branch
Branch
Branch
Branch
Branch
Branch
Branch
Branch
Branch
Branch
Breaker – 120V, 1P, 20A
Breaker – 240V, 2P, 20A
Breaker – 120V, 1P, 15A
Breaker – 240V, 2P, 15A
Breaker, GFCI – 120V, 1P, 20A
Breaker, GFCI – 240V, 2P, 20A
Breaker – 277V, 1P, 20A
Breaker – 480V, 2P, 20A
Breaker – 277V, 1P, 15A
Breaker – 480V, 2P, 15A
Breaker – 347V, 1P, 20A
Breaker – 347V, 1P, 15A
RELAY-STD
Z-MAX Standard Relay Module,
up to 277VAC, 20A Continuous
RELAY-2PL
Z-MAX 2 Pole Relay Module,
up to 480VAC, 20A Continuous
RELAY-347
Z-MAX 347V 1 Pole Relay Module,
up to 347VAC, 20A Continuous
RELAY-LAT
Z-MAX Latching Relay Module,
up to 277VAC, 20A Continuous
or 15A at 347V
Pick Only One
R24MD-00C
N
43
R24SD-00C
Z-Max Relay Cabinet with Master Control Module, up to (24)
Relay Modules (for use only with 120/208 Breaker Panels)
Z-Max Relay Cabinet with Slave Control Module, up to (24)
Relay Modules (for use only with 120/208 Breaker Panels)
R48MD-B0C
Z-Max Relay Cabinet with Master Control Module, up to (48)
Relay Modules (R48M2-B0C on 277 & 347V panels)
R48SD-00C
Z-Max Relay Cabinet with Slave Control Module, up to (48)
Relay Modules (R48S2-B0C required on 277 & 347V panels)
Indicate Quantity and
type of relay modules
as appropriate
R E L AY S E C T I O N
www.leviton.com
To learn more about Leviton devices or for answers to technical questions call our Techline at
1-800-824-3005 or visit us at:
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
Energy Management & Dimming Products
Z-MAX™ Relay Product Listing
RRP—REMOTE 4-RELAY PANEL (CONTROLLED BY Z-MAX™ MASTER CABINET)
The RRP (Remote Relay Panel) provides distributed switching of up to four 20 amp lighting circuits, enabling
multiple units to be networked and controlled from a Z-MAX Master Relay Panel. With photocell, occupancy
sensor and local switch inputs, the RRP is an ideal solution for applications such as school classrooms
where daylight harvesting, occupancy sensor control, local switching and central control scheduling are
desired. Revolutionary Z-MAX switching circuit with 10,000,000 cycle life employed in the 120-277V
standard relay model.
Accessories
• Low-voltage switch adapter (reduces required wire count of GE style
switch by 1)
• 1–10 Button low voltage switches
• Indoor and outdoor 0-10V photocells
• Atrium and skylight 0-10V photocells
For more information on Z-MAX Remote Relay Panels and Accessories,
refer to Z-MAX data sheets.
RRP – Rmote 4-Relay Panel
ORDERING INFORMATION
Description
Cat. No.
Rating
Remote Relay Panel with 4,
Single Pole 20 Amp Relays
for use with Z-MAX. 120/277V
RE4SD-104
20A per relay
Remote Relay Panel with 4,
Double Pole 20 Amp Relays
for use with Z-MAX. 120/277V
RE4SD-204
20A per relay
Remote Relay Panel with 4,
Single Pole 20 Amp Relays
for use with Z-MAX. 347V
RE4SD-304
20A per relay
Dimensions: 10.0 (254.0) W x 10.0 (254.0) H x 4.0 (101.6) D
Occupancy Sensors & Lighting Control Products
SPECIFICATIONS & FEATURES
• Network ready for up to 96 total relays
• USB port for software updates and network configuration
• 120/277V dual voltage standard
• 347V available
• Removable interior allows rough-in without risk of damage to components
• Rated for 100% load capacity
• Handles in-rush currents in excess of 50 times load current
• Low-voltage switch inputs support Leviton low voltage switches and GEstyle, ON/OFF switches with optional LED output
N
44
www.leviton.com
To learn more about Leviton devices or for answers to technical questions call our Techline at
1-800-824-3005 or visit us at:
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
Energy Management & Dimming Products
EZ-MAX Relay Product Listing
EZ-MAX RELAY CABINETS
EZ-MAX relay lighting control panels combine the power and performance of the
larger Z-MAX relay cabinets in a cost-effective four-circuit package that’s housed in
a compact 10" X 10" standard electrical enclosure. It is the ideal contractor friendly,
quick-to-install solution for smaller, stand-alone applications that do not require the
field configuration or advanced networking features of the larger Z-MAX cabinets. It
serves as a smart replacement for time clock/contactor installations for any
application requiring reliable and cost-effective automatic lighting control.
SPECIFICATIONS & FEATURES
Occupancy Sensors & Lighting Control Products
• Refer to page N39 for Z-MAX general features
• 120-277V standard relay model features revolutionary, patent-pending Z-MAX
switching circuit with an unprecedented 10,000,000 cycle life
• 347V available
• Low-voltage inputs allow connection of photocells, occupancy sensors and lowvoltage switches for a comprehensive, easy-to-install energy management solution
TESTING & CODE COMPLIANCE
• ASHRAE 90.1 compliant
• CEC Title 24 compliant
EZ-MAX Relay Cabinet
• Ten-Year Warranty
Accessories
• Modem module for touch tone control or remote configuration
• Low-voltage switch adapter (reduces required wire count of GE style switch by 1)
• 1–4 Button low voltage switches
• Indoor and outdoor 0-10V photocells
• Atrium and skylight 0-10V photocells
For more information on EZ-MAX Relay Cabinets and Accessories, refer to
EZ-MAX data sheets. Refer to pages N14–N34 for information on compatible
Leviton Occupancy Sensors.
ORDERING INFORMATION
Model
Description
Rating
RE4BD-104
EZ-MAX with 4 120-277V relays
20A per relay
RE4BD-204
EZ-MAX with 4 208-480V 2-pole relays
20A per relay
RE4BD-C04
EZ-MAX with 4 120-347V relays
20A per relay
Dimensions: 10.0 (254.0) W x 10.0 (254.0) H x 4.0 (101.6) D
N
45
www.leviton.com
To learn more about Leviton devices or for answers to technical questions call our Techline at
1-800-824-3005 or visit us at:
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
Energy Management & Dimming Products
Z-MAX™ Relay Product Listing
Z-MAX™ DIGITAL & LOW VOLTAGE SWITCH STATIONS
The Z-MAX system can incorporate either digital or low-voltage stations. Although they look identical,
there are a few differences in how they operate. Both contain buttons that are programmable to a variety
of functions and custom labels are available.
SPECIFICATIONS & FEATURES
Common Features
• Available in 8 configurations
• Programmable functions include: on, off, and group and scene select
• Compatible with standard and midway size Decora® wallplates
• Custom labeling available; contact a factory representative
• Wired via Luma-Net® to compatible products including D4200, D8000, a-2000,
i Series e, i Series Quad, and Z-MAX Relay Cabinets
• Networks with up to 127 devices
• Compatible with handheld IR remote control
Low-Voltage Station
• Compatible with EZ-MAX and Z-MAX Relay Cabinets, MDS cabinets, a-2000 cabinets
(with analog card), network protocol converter, and other low-voltage devices
ZMDSW-03W
• Cat. No. LV240 for use with miniZ Intelligent Daylight Management System, Z-MAX and EZ-MAX
• Cat. No. LV200 for use with miniZ Intelligent Daylight Management System only
WARRANTY
• Limited Two-Year Warranty
Z-MAX Switch Stations
DESCRIPTION
On/Off switch
DIGITAL SWITCH
CAT. NO.*
ZMDSW-01W
LOW-VOLTAGE SWITCH
CAT. NO.**
LVS-01W
COLOR
White
Zones 1 and 2
ZMDSW-02W
LVS-02W
White
Zones 1 to 3
ZMDSW-03W
LVS-03W
White
Zones 1 to 4
ZMDSW-04W
LVS-04W
White
Zones 1 to 5
ZMDSW-05W
LVS-05W
White
Zones 1 to 6
ZMDSW-06W
LVS-06W
White
Zones 1 to 8
ZMDSW-08W
LVS-08W
White
Zones 1 to 10
ZMDSW-10W
LVS-10W
White
Note: Wallplate sold separately
*Support network and master Z-MAX versions only
**Support EZ-MAX and Z-MAX stand-alone and slave versions only
miniZ™ Low-Voltage Switch Stations
LVS-08W
DESCRIPTION
CAT. NO.
COLOR
5-Button dimming controller with On/Off, for use with miniZ only.
LV200-00W
White
On/Off switch controller for use with miniZ, Z-MAX and EZ-MAX
LV240-00W
White
Occupancy Sensors & Lighting Control Products
Digital Station
Dimensions: 4.31 (109.5) H x 1.13 (28.7) W x 1.75 (44.5) D
N
46
www.leviton.com
To learn more about Leviton devices or for answers to technical questions call our Techline at
1-800-824-3005 or visit us at:
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
Energy Management & Dimming Products
miniZ™ Product Listing
miniZ™ INTELLIGENT DAYLIGHT
MANAGEMENT SYSTEM
miniZ combines occupancy sensing, daylight harvesting and flexible lighting
control functions into a single, easily installed package. miniZ features several
methods of ladderless commissioning, including the AutoCal™ feature, the
world’s first 100% self-configuring daylight harvesting system. Installation
requires little more than any other power-pack type product. The performance
features and capabilities of the miniZ product provide a package that
surpasses all others in the industry at a price anyone can afford.
Occupancy Sensors & Lighting Control Products
DUAL ROOM miniZ™ INTELLIGENT DAYLIGHT
MANAGEMENT SYSTEM
The dual room miniZ offers the same performance features as the miniZ, but
instead of working in one room using one photocell to control three zones, it
provides dual room/ one zone per room daylight harvesting control using a
separate photocell and occupancy sensor for each room.
SPECIFICATIONS & FEATURES
• Automatic Correction setting for Light Loss Factor
(LLF) recognizes and corrects for lumen maintenance issues
• Cost-effective energy code compliance
• Ladderless Commissioning™ provides installand-forget convenience
• Automatic closed-loop, multi-zone daylight control
• Convenient occupancy sensor and photocell
integration
• Simplified daylight harvesting with 3% to 100%
dimming capabilities (0-10V fluorescent dimming
ballasts required)
• Autocal™ (patent pending) automatic photocell calibration
• Accepts external time clock inputs
• Simplified integration with emergency and building
automation systems
• Automatic Daylight Harvest Mode provides optimum lighting output for additional energy savings
potential
• Daylight switching full range 0-10V dimming and
network models available
• Cost effective energy code compliance
• Accepts external time clock inputs
• Closed loop or open loop daylight control
• Isolated contacts for HVAC relay
• miniZ works in one room using one photocell and
occupancy sensor to control three zones
• Dual Room miniZ controls one zone per room
using a separate photocell and occupancy sensor
for each room
6.65
(168.9)
2.1
(53.3)
6.65
(168.9)
miniZ/ Dual Room miniZ
NETWORK FEATURES
• Luma-CAN® Network support
• Network digital switch support
• Z-MAX master/slave network
participation
• Remote shared network inputs
• Scalable system expansion
TESTING & CODE COMPLIANCE
• UL and cUL Listed
• CEC Title-24 Listed
• Limited Two-Year Warranty
miniZ ORDERING INFORMATION
Model
20A Power 0-10V Control Control Input
Circuits
Circuits
Voltage
Network
Functionality
MZB00-102
2
0
100-277VAC
No
MZD20-102
2
2
100-277VAC
No
MZD30-101
1
3
100-277VAC
No
MZN20-102
2
2
100-277VAC
Yes
MZN30-101
1
3
100-277VAC
Yes
MZB00-C02
2
0
200-347VAC
No
MZD20-C02
2
2
200-347VAC
No
MZD30-C01
1
3
200-347VAC
No
MZN20-C02
2
2
200-347VAC
Yes
MZN30-C01
1
3
200-347VAC
Yes
miniZ DUAL ROOM ORDERING INFORMATION
Model
N
47
Description
Basic, Dual Room, 2 Relay, 120V–277V
0-10V Outputs
Relay Outputs
CAN Network
0
2
No
MZB02-102
miniZ™
MZD22-102
miniZ™ Dimming, Dual Room, 2 Relay, 120V–277V
2
2
No
MZN22-102
miniZ™ Dimming, Dual Room, 2 Relay, 120V–277V
2
2
Yes
MZB02-C02
miniZ™ Basic, Dual Room, 2 Relay, 347V
0
2
No
MZD22-C02
miniZ™ Dimming, Dual Room, 2 Relay, 347V
2
2
No
MZN22-C02
miniZ™ Dimming, Dual Room, 2 Relay, 347V
2
2
Yes
www.leviton.com
To learn more about Leviton devices or for answers to technical questions call our Techline at
1-800-824-3005 or visit us at:
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
Energy Management & Dimming Products
Z-MAX™ Relay Applications
Z-MAX™ RELAY CARDS & ACCESSORIES
The Z-MAX system offers several relay cards in addition to a
number of accessories, including a modem that enables the system
to be operated remotely. The standard, single-pole 20-amp relay
card features proprietary circuitry that completely eliminates arc
shower pitting at the contacts and thus provides an extended life
over traditional relay circuits. This unique feature is the source of
the Z-MAX name: Z-MAX stands for zero current maximum life.
SPECIFICATIONS & FEATURES
Relay Cards
• Rated at 20A for lighting loads
Z-MAX Relay Card (RELAY-STD)
• Rated for resistive, inductive, and capacitive sources
• Zero cross circuitry eliminates arcing at mechanical contacts when loads are
switched — prolonging relay life to an average of 10,000,000 on/off cycles
• Handles inrush currents up to 50X greater than connected load
Handheld Remote Control
• Features 4, 8 or 16 selection buttons plus off
• Use with any Z-MAX Digital Station
• Operates at 56kHz frequency; 30- to 50-foot range
TESTING & CODE COMPLIANCE
• UL Listed (for individual load types) and CUL Listed under both Industrial
Control Equipment and Energy Management Equipment
• NOM certified
• Limited Ten-Year Warranty
Z-MAX Relay Cards
DESCRIPTION
Standard 20A Single-Pole
Relay Card*
CAT. NO.
INPUT POWER
RELAY-STD 120-277V
RATING
For incandescent, electronic
fluorescent, magnetic fluorescent,
electronic low voltage, neon cold
cathode, high intensity discharge
and motor loads
2-Pole 20A Relay Card
RELAY-2PL 240/480V
Same as Above
347V Single-Pole 20A Relay Card RELAY-347 120-347V
Same as Above
Normally Closed Relay Card
Same as Above
RELAY-NCL 120-347V
*NOTE: Relay cabinets ship with RELAY-STD modules unless otherwise specified.
Accessories
DESCRIPTION
Remote Control with 4 selections
CAT. NO.
D42IR-04L
COLOR
Black
Remote Control with 8 selections
D42IR-08L
Black
Remote Control with 16 selections
D42IR-16L
Black
Flush Trim Kit for 8-Relay Cabinet
RAC00-08F
—
Flush Trim Kit for 24-Relay Cabinet
RAC00-24F
—
Flush Trim Kit for 48-Relay Cabinet
RAC00-48F
—
Switch Input Board with 32 discrete inputs
RAC00-SIB
—
Modem with Touch Tone input capability (consult factory)
RAC00-MOD
—
Ethernet Module (consult factory)
RAC00-ETH
—
Voltage Barrier between relay cards
RAC00-VBR
—
Occupancy Sensors & Lighting Control Products
• Specifically designed to control electronic ballasts
D42IR-16L
N
48
www.leviton.com
To learn more about Leviton devices or for answers to technical questions call our Techline at
1-800-824-3005 or visit us at:
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
Energy Management & Dimming Products
Z-MAX™ Relay Technical Information
CATALOG NUMBERING SYSTEM, RELAY CABINETS
Relay systems are an excellent choice for providing time- and eventbased switching on a customized schedule for everything from basic
stand-alone applications to building and campus-wide energy
management systems. Z-MAX™ Lighting Control Relay Systems are
ideally suited to all sizes of applications where you need a system
that switches lights on and off based on a customized schedule but
do not require other functionality such as dimming or scene control.
Z-MAX cabinets offer a single, integrated solution that takes the
place of several individual components including: time clock, cabinet,
terminal blocks and contactors.
R 24MD-2 24
No. of relays
Occupancy Sensors & Lighting Control Products
BASIC APPLICATION
Relay type
0 = No relays in cabinet
1 = Standard (single-pole
120V, 277V)
2 = 2-pole relay (240/480V)
C = International
(single-pole, 347V)
Z-MAX SYSTEMS BENEFIT APPLICATIONS REQUIRING:
• Control of various loads from one or more locations
Input Voltage for Control Module
D = Multi-volt 120V, 277V, 347V
F = International 100V, 220V,
230V, 240V
Control Module Type
B = Basic, for 8-relay cabinet only
N = Networkable, for 8-relay
cabinet only
M = Master, for 24- and 48-relay
cabinets only
S = Slave, for 24- and 48-relay
cabinets only
Cabinet Size
(Maximum number of relays:
8, 24 or 48)
• Time based lighting control ordinarily provided by separate time
clock and lighting controllers
• Compliance with energy codes requiring automatic lighting control
• Integration of photocells and occupancy sensors into a centrally
controlled switching system
TYPICAL Z-MAX RELAY APPLICATIONS
• Auditoriums
• Parking facilities
• Gymnasiums and pools
• Educational facilities
• Warehouses
• Office buildings
• Arenas
• Landscape and security lighting
Z-MAX Applications
Control Station
Entry Station
Dimmer or
Z-MAX Relay
Cabinet
Equipped with
Luma-Net
Photocell
Z-MAX
Network Relay
Cabinet
N
49
Occupancy
Sensor
NOTE: Dimensions™ D4200 and D8000 controls are readily incorporated into a Z-MAX network cabinet system. Z-MAX 8-channel stand-alone cabinets
use the 000-LVS series of low voltage entry stations.
www.leviton.com
To learn more about Leviton devices or for answers to technical questions call our Techline at
1-800-824-3005 or visit us at:
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
Energy Management & Dimming Products
Z-MAX™ Relay Technical Information
CONTROL WIRING
BASIC MOUNTING DIAGRAMS
Every Z-MAX relay cabinet is wired in exactly the same way and
communicates via Luma-Net® III or DMX512. Through the use of the
Network Protocol Converter, Z-MAX cabinets can be integrated with
RS232 and standard 10/100 TCP/IP routers and networks. We
strongly recommend the use of either Belden 9829 or Belden 9729
for the Luma-Net wire runs. A second pair of stranded wire is
required for power. At the last control station or dimmer cabinet on
both ends of the run, a small jumper wire must be run from the
terminal labeled “Rem-” to the terminal marked “Term” on that last
station. This jumper wire properly terminates the digital
communications lines at the end of the line.
8-Relay Z-MAX
Wiring Raceway
Feed and/or
switch legs
to loads
DMX OUT
DMX IN
Class 2/PELV
Wiring to
Controls 2 locations
W
A
L
L
Top and Bottom Feed
and /or switch legs to loads
Drain/Shield - Insulated
and tied together
(Ground at one point onlyprobably an end)
Feed wiring to relays
DATA -
Data +
3
COM
1
2
Distribution panel
Surface Mounting Shown
1
2
3
Front View
Side View
DMX Connector (Blue)
24-Relay (& 48-Relay) Z-MAX
Wiring Raceway
Luma-Net Wiring to Connector
Feed and/or
switch legs
to loads
Feed and/or
switch legs
to loads
LOCK
6
TERM
5
COM
+V
4
REM -
W
A
L
L
Distribution panel
3
2
1
REM+
Class 2/PELV
Wiring to
Controls 2 locations
Occupancy Sensors & Lighting Control Products
DMX Wiring to Connector
12
34
56
Top and Bottom Feed
and /or switch legs to loads
Feed wiring to relays
Phoenix/Luma-Net
Connector
Install termination jumper
if last station on a run
Surface Mounting Shown
Front View
Side View
N
50
www.leviton.com
To learn more about Leviton devices or for answers to technical questions call our Techline at
1-800-824-3005 or visit us at:
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
Our Complete Line of
Industrial Products
Just a click away:
www.leviton.com/industrial
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
Download