You may use a Commercial Fire Listed 24VDC Power Supply to convert one or both VISTA-128FBPT/VISTA250FBPT 12VDC, 1.7A style-Y supervised Special Application Notification Appliance Circuits to 24V, style-Y supervised, Special Application Notification Appliance Circuits. UL • • Burglary Notification Appliance Circuits must be programmed for a timeout of 16 minutes or longer. Commercial fire alarm systems require Notification Appliance Circuits to be supervised. Notification Appliance Circuit Supervision The VISTA-128FBPT/VISTA-250FBPT monitors the Notification Appliance Circuits wiring for open and short circuit faults while the output is inactive. The system provides a trouble indication (Zone 970 Bell 1; 971 Bell 2) when an open occurs. When a short occurs between the Bell (+) and Bell (-) terminal wiring, or between the Bell (+) terminal wiring and earth ground the system provides a trouble indication (972 Earth Ground). The VISTA-128FBPT/VISTA-250FBPT indicates the trouble condition regardless of whether the system is armed or disarmed. The zone displays on the keypads, reports to the event log, and transmits to the central station (if programmed) on Partition 1. The trouble is cleared from the display by entering the user code + OFF. UL ULC Use only UL Listed sounding devices for UL installations. In Commercial Fire installations, the 4204CF cannot be used to drive sounders in the same audible area as sounders connected to the alarm outputs of the control panel. For ULC fire installations, alarm indicating devices must not be connected to the fire transmitter. These devices must be connected to the Fire Alarm Control Panel. Synchronization Requirements for Commercial Fire Notification Appliance Circuit outputs must be wired to a Sync Module if more than one device is used. Follow instructions provided with Sync Module. Be sure to use the compatible Sync Module for the Alarm Indicating Device selected. MANUFACTURER GENTEX SYNC MODULE MODEL NUMBER AVSM SYSTEM SENSOR MDL WHEELOCK DSM UL All visual notification appliances within the same physical area must be synchronized. The bell outputs are listed as Special Application Notification Appliance Circuits. Compatible Alarm Indicating Devices ALARM INDICATING DEVICE TYPE UL listed Grade A Bell in Housing RX7 UL Indoor Sounder, 12V Horn Strobe 2w Horn Strobe 2w Horn Strobe 4w Horn Strobe 4w Chime, 12/24V, Selectable Tone & Volume, Red Chime, 12/24V, Selectable Tone & Volume, White Chime/Strobe, 12/24V, Selectable Candela, Tone & Volume, Red Chime/Strobe, 12/24V, Selectable Candela, Tone & Volume, White Horn, 12/24V, Red Horn, 12/24V, White Horn, 12/24V, Outdoor, Red 2-Wire Wall Mount Horn/Strobe, 12/24V, Standard Candela, Red 2-Wire Wall Mount Horn/Strobe, 12/24V, High Candela, Red 2-Wire Wall Mount Horn/Strobe, 12/24V, Standard Candela, Red, Outdoor 2-Wire Wall Mount Horn/Strobe, 12/24V, High Candela, Red, Outdoor 27 MANUFACTURER Honeywell/ADEMCO ADT GENTEX GENTEX GENTEX GENTEX SYSTEM SENSOR SYSTEM SENSOR SYSTEM SENSOR SYSTEM SENSOR SYSTEM SENSOR SYSTEM SENSOR SYSTEM SENSOR SYSTEM SENSOR SYSTEM SENSOR SYSTEM SENSOR SYSTEM SENSOR MODEL # AB12M 875936B GEC3-12, GES3-12, GEH-12 GEC3-12, GES3-12, GEH-12 GEC3-12, GES3-12, GEH-12 GEC3-12, GES3-12, GEH-12 CHR CHW CHSR CHSW HR HW HRK P2R P2RH P2RK P2RHK ALARM INDICATING DEVICE TYPE 2-Wire Wall Mount Horn/Strobe, 12/24V, Standard Candela, White 2-Wire Wall Mount Horn/Strobe, 12/24V, High Candela, White 4-Wire Wall Mount Horn/Strobe, 12/24V, Standard Candela, Red 4-Wire Wall Mount Horn/Strobe, 12/24V, High Candela, Red 4-Wire Wall Mount Horn/Strobe, 12/24V, Standard Candela, Red, Outdoor 4-Wire Wall Mount Horn/Strobe, 12/24V, High Candela, Red, Outdoor 4-Wire Wall Mount Horn/Strobe, 12/24V, Standard Candela, White 4-Wire Wall Mount Horn/Strobe, 12/24V, High Candela, White 2-Wire Ceiling Mount Horn/Strobe, 12/24V, Standard Candela, Red 2-Wire Ceiling Mount Horn/Strobe, 12/24V, High Candela, Red 2-Wire Ceiling Mount Horn/Strobe, 12/24V, Standard Candela, Red, Outdoor 2-Wire Ceiling Mount Horn/Strobe, 12/24V, High Candela, Red, Outdoor 2-Wire Ceiling Mount Horn/Strobe, 12/24V, Standard Candela, White 2-Wire Ceiling Mount Horn/Strobe, 12/24V, High Candela, Red 4-Wire Ceiling Mount Horn/Strobe, 12/24V, Standard Candela, Red 4-Wire Ceiling Mount Horn/Strobe, 12/24V, High Candela, Red 4-Wire Ceiling Mount Horn/Strobe, 12/24V, Standard Candela, Red, Outdoor 4-Wire Ceiling Mount Horn/Strobe, 12/24V, High Candela, Red, Outdoor 4-Wire Ceiling Mount Horn/Strobe, 12/24V, Standard Candela, White 4-Wire Ceiling Mount Horn/Strobe, 12/24V, High Candela, White 2-Wire Wall Mount Strobe, 12/24V, Standard Candela, Red 2-Wire Wall Mount Strobe, 12/24V, High Candela, Red Wall Mount Strobe, 12/24V, Standard Candela, Red, Outdoor Wall Mount Strobe, 12/24V, High Candela, Red, Outdoor Wall Mount Strobe, 12/24V, Standard Candela, White Wall Mount Strobe, 12/24V, High Candela, White Ceiling Mount Strobe, 12/24V, Standard Candela, Red Ceiling Mount Strobe, 12/24V, High Candela, Red Ceiling Mount Strobe, 12/24V, Standard Candela, Red, Outdoor Ceiling Mount Strobe, 12/24V, High Candela, Red, Outdoor Ceiling Mount Strobe, 12/24V, Standard Candela, White Ceiling Mount Strobe, 12/24V, High Candela, White Horn Strobe 12V, 4W Horn Strobe 12V, 2W Strobe 12V Horn Strobe 12V, 2W Horn 12V/24V Horn 12V Horn 12V/24V Bell 12V MANUFACTURER SYSTEM SENSOR SYSTEM SENSOR SYSTEM SENSOR SYSTEM SENSOR SYSTEM SENSOR SYSTEM SENSOR SYSTEM SENSOR SYSTEM SENSOR SYSTEM SENSOR SYSTEM SENSOR SYSTEM SENSOR SYSTEM SENSOR SYSTEM SENSOR SYSTEM SENSOR SYSTEM SENSOR SYSTEM SENSOR SYSTEM SENSOR SYSTEM SENSOR SYSTEM SENSOR SYSTEM SENSOR SYSTEM SENSOR SYSTEM SENSOR SYSTEM SENSOR SYSTEM SENSOR SYSTEM SENSOR SYSTEM SENSOR SYSTEM SENSOR SYSTEM SENSOR SYSTEM SENSOR SYSTEM SENSOR SYSTEM SENSOR SYSTEM SENSOR WHEELOCK WHEELOCK WHEELOCK WHEELOCK WHEELOCK WHEELOCK WHEELOCK WHEELOCK MODEL # P2W P2WH P4R P4RH P4RK P4RHK P4W P4WH PC2R PC2RH PC2RK PC2RHK PC2W PC2WH PC4R PC4RH PC4RK PC4RHK PC4W PC4WH SR SRH SRK SRHK SW SWH SCR SCRH SCRK SCRHK SCW SCWH MT-121575W AS-121575W RSS-121575W NS-121575W NH-12/24 AH-12 MT-12/24, MT4-12/24 MB-G6-12, MB-G10-12 Table 3-1: BELL 1 AND BELL 2 MAXIMUM DEVICE RATING NOTE: To use this table, the device Candela Setting and Horn Setting MUST match what is listed in the Table. Mfg Gentex Gentex Gentex Gentex System Sensor System Sensor System Sensor System Sensor System Sensor System Sensor System Sensor System Sensor System Sensor Alarm Indicating Device Type Horn Strobe 12V, 2w Horn Strobe 12V, 2w Horn Strobe 12V, 4w Horn Strobe 12V, 4w Horn, Strobe12/24V Horn, Strobe12/24V Horn, Strobe12/24V Horn, Strobe12/24V Horn, Strobe12/24V Horn, Strobe12/24V Horn, Strobe12/24V Horn, Strobe12/24V Horn, Strobe12/24V Model GEC3-12,GES3-12,GEH-12 GEC3-12,GES3-12,GEH-12 GEC3-12,GES3-12,GEH-12 GEC3-12,GES3-12,GEH-12 HR HW HRK P2R P2RH P2RK P2RHK P2W P2WH 28 Candela Setting 15 75 15 75 15 15 15 15 15 15 Horn Setting Mech-Temporal Mech-Temporal Continuous Mech Continuous Mech Temporal - High Temporal - High Temporal - High Temporal - High Temporal - High Temporal - High Max # of Devices 6 2 6 2 38 38 38 10 10 10 10 10 10 Mfg System Sensor System Sensor System Sensor System Sensor System Sensor System Sensor System Sensor System Sensor System Sensor System Sensor System Sensor System Sensor System Sensor System Sensor System Sensor System Sensor System Sensor System Sensor System Sensor System Sensor System Sensor System Sensor System Sensor System Sensor System Sensor System Sensor System Sensor System Sensor System Sensor System Sensor Wheelock Wheelock Wheelock Wheelock Wheelock Wheelock Wheelock Wheelock Bell Alarm Indicating Device Type Horn, Strobe12/24V Horn, Strobe12/24V Horn, Strobe12/24V Horn, Strobe12/24V Horn, Strobe12/24V Horn, Strobe12/24V Horn, Strobe12/24V Horn, Strobe12/24V Horn, Strobe12/24V Horn, Strobe12/24V Horn, Strobe12/24V Horn, Strobe12/24V Horn, Strobe12/24V Horn, Strobe12/24V Horn, Strobe12/24V Horn, Strobe12/24V Horn, Strobe12/24V Horn, Strobe12/24V Strobe12/24V Strobe12/24V Strobe12/24V Strobe12/24V Strobe12/24V Strobe12/24V Strobe12/24V Strobe12/24V Strobe12/24V Strobe12/24V Strobe12/24V Strobe12/24V Horn Strobe 12V, 4W Horn Strobe 12V, 2W Strobe 12V Horn Strobe 12V, 2W Horn 12V/24V Horn 12V Horn 12V/24V Bell 12V Bell 12V Model P4R P4RH P4RK P4RHK P4W P4WH PC2R PC2RH PC2RK PC2RHK PC2W PC2WH PC4R PC4RH PC4RK PC4RHK PC4W PC4WH SR SRH SRK SRHK SW SWH SCR SCRH SCRK SCRHK SCW SCWH MT-121575W AS-121575W RSS-121575W NS-121575W NH-12/24 AH-12 MT-12/24,MT4-12/24 MB-G6-12,MB-G10-12 AB12M Candela Setting 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 na na na na na Horn Setting Temporal - High Temporal - High Temporal - High Temporal - High Temporal - High Temporal - High Temporal - High Temporal - High Temporal - High Temporal - High Temporal - High Temporal - High Temporal - High Temporal - High Temporal - High Temporal - High Temporal - High Temporal - High Temporal - High Temporal - High Temporal - High Temporal - High Temporal - High Temporal - High Temporal - High Temporal - High Temporal - High Temporal - High Temporal - High Temporal - High Continuous/Hi Continuous/Hi na Hi Hi Hi Continuous Horn na na Max # of Devices 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 4 6 6 7 80 9 10 9 9 Supervising the Notification Appliance Circuits To wire the NAC using the supervision feature, perform the following: Install a 2K EOL resistor (Model 2EOL, supplied) across the last notification appliance on each Notification Appliance Circuit to be supervised. Auxiliary Relay Connections The VISTA-128FBPT/VISTA-250FBPT provides a built-in Form C relay with contacts rated at 28VAC/VDC, 2.8A. The relay may be programmed (field 3∗61) for one of the following functions: • Alarm Activation • Trouble/Supervisory Activation • 4-Wire Smoke Detector Reset • Battery Saver Alarm Activation (3∗61 = 1 or 4) Steady activation in response to an alarm. If field 3∗61 = 1, the auxiliary relay remains active until Aux. Relay Timeout expires or until User Code + OFF is entered. This option can be used to provide an unsupervised Notification Appliance Circuit for supplementary strobes, sounders, etc. when wired to the Aux Power 1 or a separate power supply, see Figure 3-8. If field 3∗61 = 4, the auxiliary relay remains activated until User Code + # + 67 is entered. By default, the relay is set to activate on alarm zones 1-8 with no timeout (field 3∗61 = 1). When field 3∗61 = 1, the auxiliary relay can be programmed to give a brief activation for confirmation of arming ding (field 3∗57) or Chime Mode (field 3∗59). 29