Emergency Lighting Interface LUT-ELI-3PH |Installation Guide

advertisement
Emergency Lighting Interface LUT-ELI-3PH | Installation Guide
Please read this guide before installing.
Contents
Listing
Page
Ratings and model number overview............................1
Mounting the Interface.................................................2
Wiring Overview for LUT-ELI-3PH units on:
RadioTouch Systems...............................................2
Panel-Based Systems..............................................4
EcoSystem or Quantum bus supplies.......................8
GRAFIK Eye QS units...............................................9
Energi Savr Node units..........................................10
Emergency Power Mode Setup: LCP Panels..............11
NEC Class 2/PELV Wiring to Fire Alarm
Control Panel (FACP).............................................12
Troubleshooting
RadioTouch............................................................13
Panel Based Systems............................................14
Energi Savr Node Installations................................15
EcoSystem or Quantum System............................16
Grafik Eye QS Installation.......................................17
The Emergency Lighting Interface – LUT-ELI-3PH is
UL924 Listed as “Emergency Lighting and Power
Equipment”. The interface shall be used with: Lutron
GRAFIK Eye GP, XP, and LP panels; LCP128 panels;
Softswitch128 panels; EcoSystem; Quantum; GRAFIK
Eye QS, RadioTouch controllers, and Energi Savr
Node units.
Description
The LUT-ELI-3PH unit senses the line voltage on
all three phases or a single phase and controls the
emergency signal to the following compatible Lutron
products/systems:
• Circuit Selector for GP, LP, XP panels
• LCP/XPS controller for LCP128, and
Softswitch 128 panels
• EcoSystem Bus Supply
• Quantum Bus Supply
• Grafik Eye QS unit
• RadioTouch controller
• Energi Savr Node unit
When one or more phases of normal power are lost,
the LUT-ELI-3PH unit sends a signal to the affected
device(s), activating the emergency mode. Any lights
controlled by these devices will go to the emergency
light level setting (factory set to 100% intensity). When
normal power is restored, the lights will return to their
previous intensities.
9
6
5
4
3
LED1
LED2
TEST
LED3
1
FACF
RADIOTOUCH
2
GND
PHASE
NOT USED
CONTACTS
´FACP´ N/O
7
´FACP´ N/C
8
CONTACTS
10
COMMON
MUX
11
+24VFW
DRAIN
12
MUX
SENSE
Important Safeguards
S1
CLASS 2 LOW VOLTAGE WIRING
System Ratings
• Voltage: 100-347 V 50/60 Hz 30 mA
• Current: 20 A maximum circuit breaker
For use with Lutron®: GRAFIK Eye® GP, LP, and XP
panels; LCP128TM panels; Softswitch128 panels;
EcoSystem® lighting control system; Energi Savr
NodeTM units; Quantum® systems; GRAFIK Eye QS
units, and RadioTouch® lighting controllers.
Note: This device does not provide emergency power.
An Emergency (Essential) power source must be
provided.
LUT-ELI-3PH Installation Guide
• Follow all national and local electrical codes and safety
standards.
• Turn off power before installation.
• Line voltage input to the LUT-ELI-3PH unit must be
from the NORMAL (non-essential) power source.
• Read and follow all safety instructions.
• For indoor use only.
• Equipment should be mounted in locations and
at heights where it will not readily be subjected to
tampering by unauthorized personnel.
• Do not use this equipment for other than intended use.
• All servicing should be performed by qualified service
personnel.
System Limits (per / LUT-ELI-3PH)
•
•
•
•
•
•
32 circuit selectors
100 RadioTouch Controllers
32 EcoSystem bus supplies
32 Quantum bus supplies
32 Energi Savr Node units
32 LCP/XPS Controllers
Lutron® | 1
Emergency Lighting Interface LUT-ELI-3PH | Installation Guide
1. Turn power off.
2. Wire the line voltage leads that protrude from back of
LUT-ELI-3PH unit into the junction box.
3. Mount the LUT-ELI-3PH unit onto a 4 x 4-inch
(102 x 102 mm) junction box (not included, but
available; Lutron part number 241-496).
4. Be sure all the power wires are completely inside the
junction box before tightening the mounting screws.
5. Remove front enclosure cover to expose the terminal
blocks, test switch, and status LEDs.
6. Insert the NEC® Class 2/PELV wires through knockouts
in the LUT-ELI-3PH enclosure as shown in the diagram.
7. Connect the NEC Class 2/PELV wires to the Lutron®
product or system, which the LUT-ELI-3PH will be
controlling. Specific wiring to these devices will be
described in the following sections.
8. Reinstall front enclosure cover.
Note: Call the Lutron Technical Support Center at
(800) 523-9466 for restrictions and wiring requirements
for emergency fixtures (fixtures that never turn off or
have a battery backup ballast in the fixture).
Side View
(Cross-Section)
Mounting the Interface
4 x 4 in (102 x 102 mm)
Junction Box
LUT-ELI-3PH
UNIT
WALL
Insert NEC Class 2/PELV
wires through knockouts
Installing a LUT-ELI-3PH Unit in a
RadioTouch® System
Line Voltage Connections
WARNING! Danger of shock. May result
in serious injury or death. DO NOT WIRE
WHEN LIVE! Switch off power to all power
feeds via circuit breaker or isolator before
wiring or servicing the LUT-ELI-3PH unit and
RadioTouch System
Buttons and LEDs in the unit are used for
troubleshooting. If wiring is exposed when accessing
buttons and LEDs, the unit must be accessed by a
certified electrician, following local codes.
Three-Phase Wiring
Red
Red
Red
White
Green
Normal
Power
Normal
Power
Figure #1
Figure #2
Lutron® | 2
Normal
Lights
Ground
Neutral
Phase C
Phase B
Phase A
Normal
Lights
Ground
Neutral
Hot
Red
Red
Red
White
Green
Single-Phase Wiring
Note: Provide proper short-circuit and overcurrent
protection at the distribution panel. Maximum circuit
breaker rating of 20 A.
LUT-ELI-3PH Installation Guide
Emergency Lighting Interface LUT-ELI-3PH | Installation Guide
Installing a LUT-ELI-3PH Unit in a
RadioTouch® System (continued)
Test the System
Please perform the following tests to ensure proper
installation.
1. Turn off one of the Normal (Non-Essential) phase(s)
breaker(s) that the LUT-ELI-3PH unit is monitoring.
You should see the following:
•All lights controlled by Emergency (Essential) panel
will go to FULL INTENSITY (factory set).
•PHASE ON/OFF status Indicator (green) will turn
OFF as the above test creates a phase failure.
•Upon turning the breaker back on, all lights should
return to their previous intensity.
2. Press and hold switch SW1 on the LUT-ELI-3PH unit.
You should see the following:
•TEST LED (orange) will turn ON.
•All lights controlled by Emergency RadioTouch
controller will go to FULL INTENSITY (factory set).
Note: PHASE ON/OFF status indicator (green) will
not turn OFF as test #2 does not create a phase
failure.
•Upon releasing switch SW1, all lights will return to
their previous intensities.
NEC® Class 2/PELV Connections
Note: When wiring for a backup/emergency source of
power, the RadioTouch Controller (models RTA-RX-F,
RTA-RX-F-SC, RTA-RXSW), being used for the backup/
emergency lights (Unit A and B) cannot be controlled by
an occupancy sensor. Units A and B DIP switch 2 must
be in the down position.
NEC Class 2/PELV Wiring to RadioTouch
Controllers
One LUT-ELI-3PH can be connected in parallel with up
to 100 RadioTouch Controllers.
1. Flip DIP switch 2 on the RadioTouch Controller to the
down position.
2. Disconnect any occupancy sensors wired to the
RadioTouch Controller.
3. Make the following connections.
From LUT-ELI-3PH Unit
Terminal 8 (+V Input)
Terminal 7
(Circuit Common)
Terminal 1 (Signal)
To RadioTouch Controller
Terminal 4 (24 V ), Unit A only
Terminal 6 (Cir Com)
Terminal 2 (Occ Sig)
Note: Only one RadioTouch unit can have its
24 V (number 4) terminal connected to terminal
8 (+V Input) on the LUT-ELI unit regardless of the
number of wired RadioTouch units.
Available power from this unit
for daylight sensors must be
derated to 15 mA.
®
10
9
8
7
6
5
4
2
1
LED2
LED1
LED3
1 2 3 4 5
RTA-R X-F-SC
TEST
FACF
RADIOTOUCH
NOTUSED
3
PHASE
CONTACTS
´FACP´N/O
CONTACTS
´FACP´N/C
COMMON
+24VFW
MUX
MUX
SENSE
DRAIN
11
S1
(8) (7)
Green/V
er de/VStatus
ert
Power
3
4
Flip Dip
Switch 2 to
the down
position
DimmedHot/AtenuadorVivo/CourantTamisé*
SwitchedHot/InterruptorVivo/CourantCommuté
Blue/Bleu/Azul
er de/V ertStatus Program
Power
1 2 3 4 5Green/V
RTA-R X-F-SC
Hot/Vivo/Chargé
Red&Black/Rojo&Negro/Rouge&Noir
Red/Rojo/RougeOR
277V
13
14
1 2 Ground/Tierra/Terre
3
White/Blanco/Blanc
15 16
Hot is for use only with Lutron Hi-Lume FDB-series or Eco-10 ECO-series dimming ballasts.
* Dimmed
V ivo es para ser utilizado únicamente con las series de balastos
*deEl Atenuador
atenuaci ón Hi-Lume FDB o Eco-10 ECO de Lutron.
T amisé doit être utilisé seulement avec le Hi-Lume FDB-series ou avec
* Courant
le ballast de gradation Eco-10 ECO-series de Lutron.
* For 120 V~ use black wire, cap red. For 277 V~ use red wire, cap black.
P/N 500-10634
(2) (4) (6)
CCO5
0-10
V
PowerWiringCableadodePoderCâblaged'alimentation
Black/Negro/Noir
120V
6
7
8
9
10 11 12
DistributionPanel
CLASS 2 LOW VOLTAGE
WIRING
9 10 11 12 13 14 15 16
8
CCO4
6 7
CCO3
5
Orange/Anaranjado/Orange*
Burn-In
(2) Signal
(6) Circuit Common
LUT-ELI-3PH Installation Guide
4
®
1
PaneldeDistribución
PanneaudeDistribution
(1)
3
CCOCom
1 2
Neutral/Neutro/Neutre
5
100Hr/100%
5
CCO2
4
CCO1
3
+
CCO5
1 2 3Ground/Tierra/Terre
Program
White/Blanco/Blanc
2
2
DimmedHot/AtenuadorVivo/CourantTamisé*
Red&Black/Rojo&Negro/Rouge&Noir
1
1
SwitchedHot/InterruptorVivo/CourantCommuté
Red/Rojo/RougeOR
277V
CLASS2LOWVOLTAGEWIRING
CCO4
PowerWiringCableadodePoderCâblaged'alimentation
Blue/Bleu/Azul
12
CCO3
0-10
V
Orange/Anaranjado/Orange*
GND
9 10 11 12 13 14 15 16
8
CCOCom
6 7
CCO2
5
CCO1
4
+
3
15V
OccSig
PELV(Class2:USA)
Flip Dip
Switch 2 to
the down
position
Occ.Com
1 2
PROG
STAT
ON
_
5
_
4
PSSig
3
24V
2
CirCom
1
CONFIGURACIONES
REGLAGES
PWR
SETTINGS
100Hr/100%
®
RefertotheInstallersGuideformore
detailedinstructions.
ConsultelaGuíadeInstaladorespara
informaciónmásdetallada.
RéférerauGuided’installationpourplusde
renseignementsdétaillés.
1-800-523-9466
1-888-235-2910
PSSig
PROG
STAT
ON
LISTED243C
Ind.Cont.Eq.
Coopersburg,PA18036USA
USA,Canada
Mexico
www .lutron.com
15V
CONFIGURACIONES
REGLAGES
PWR
SETTINGS
120/277V60Hz
16AMax.
TM
24V
RefertotheInstallersGuideformore
detailedinstructions.
ConsultelaGuíadeInstaladorespara
informaciónmásdetallada.
RéférerauGuided’installationpourplusde
renseignementsdétaillés.
1-800-523-9466
1-888-235-2910
RadioTouch
RTA-RX-F-SC
CirCom
Coopersburg,PA18036USA
USA,Canada
Mexico
www .lutron.com
®
OccSig
LISTED243C
Ind.Cont.Eq.
Occ.Com
120/277V60Hz
16AMax.
TM
PELV(Class2:USA)
RadioTouch
RTA-RX-F-SC
RadioTouch Unit B
120/277 V feed backup/
Emergency
power
P/N500-10634
©2006LutronElectronicsCo.,Inc.
RadioTouch Unit A
120/277 V feed backup/
Emergency
power
P/N500-10634
©2006LutronElectronicsCo.,Inc.
LUT-ELI-3PH Unit
Additional RadioTouch Controller for Backup/
Emergency Light(s)
2
3
4
Burn-In
Neutral/Neutro/Neutre
Hot/Vivo/Chargé
Black/Negro/Noir
120V
5
6
7
8
9
10 11 12
CLASS 2 LOWDistributionPanel
VOLTAGE WIRING
13
14
15 16
PaneldeDistribución
PanneaudeDistribution
Hot is for use only with Lutron Hi-Lume FDB-series or Eco-10 ECO-series dimming ballasts.
* Dimmed
V ivo es para ser utilizado únicamente con las series de balastos
*deEl Atenuador
atenuaci ón Hi-Lume FDB o Eco-10 ECO de Lutron.
T amisé doit être utilisé seulement avec le Hi-Lume FDB-series ou avec
* Courant
le ballast de gradation Eco-10 ECO-series de Lutron.
* For 120 V~ use black wire, cap red. For 277 V~ use red wire, cap black.
P/N 500-10634
(2)
(6)
To additional
RadioTouch
controllers
(100 maximum)
Lutron® | 3
Emergency Lighting Interface LUT-ELI-3PH | Installation Guide
Installing a LUT-ELI-3PH Unit in a
Panel-Based System
Line Voltage Connections
Note: Provide proper short-circuit and overcurrent
protection at the distribution panel. Maximum circuit
breaker rating of 20 A.
WARNING! Danger of shock. May result
in serious injury or death. DO NOT WIRE
WHEN LIVE! Switch off power to all power
feeds via circuit breaker or isolator before
wiring or servicing the LUT-ELI-3PH unit and
Panel-Based System.
Buttons and LEDs in the unit are used for
troubleshooting. If wiring is exposed when accessing
buttons and LEDs, the unit must be accessed by a
certified electrician, following local codes.
GP3 panel shown
Wiring from Normal (Non-Essential) GP Panel
Typical load
circuit
5
4
3
LED2
LED1
LED3
1
S1
TEST
RADIOTOUCH
6
CLASS2LOWVOLTAGEWIRING
FACF
NOTUSED
2
GND
PHASE
CONTACTS
7
´FACP´N/O
8
CONTACTS
9
´FACP´N/C
10
COMMON
MUX
11
+24VFW
DRAIN
12
MUX
SENSE
DH1 SH1 H1
DH2 SH2 H2
DH3 SH3 H3
Control
wiring to
circuit
selector
N
Red
Red
Red
White
Branch
circuit
breakers
Green (to ground lug)
Terminal
blocks
Neutral
block
Normal power
feed wiring
Ground lug
Wiring from Mains with GP, LP, XP, and XPS/LCP Panels
Lutron® | 4
Red
Red
Red
White
Green
Normal
Power
Normal
to panel
Ground
Neutral
Phase C
Phase B
Phase A
LUT-ELI-3PH Installation Guide
Emergency Lighting Interface LUT-ELI-3PH | Installation Guide
Installing a LUT-ELI-3PH Unit in a
Panel-Based System (continued)
NEC® Class 2/PELV: USA Connections
•
•
•
•
Notes
Pull NEC Class 2/PELV wiring for system
communications.
NEC Class 2/PELV wiring must be daisy-chained.
NEC Class 2/PELV wiring must be run separately from
line (mains) voltage.
A LUT-ELI-3PH unit can be placed anywhere on the
power panel link.
•
•
Wiring Notes
NEC Class 2/PELV wiring link is 500 to 2000 feet
(152 to 610 m), use Lutron® cable GRX-CBL-46L:
- Two 12 AWG (2.5 mm2) for control wiring
(+V and com)
- One twisted, shielded pair 22 AWG (0.5 mm2) for data link
- One 18 AWG (1.0 mm2) for sense line between
panels.
Lutron has also approved smaller-gauge cable
from Belden®, Liberty Wire & Cable®, AlphaWire
Company, and Signature Wire Corp. Ask for Lutron
GRAFIK Eye® Cable.
Processor panel
Dimming panel
LUT-ELI-3PH Unit
Power panel link
Wallstation links
Panel to panel wiring
See above for wiring notes
LUT-ELI-3PH Installation Guide
Lutron® | 5
Emergency Lighting Interface LUT-ELI-3PH | Installation Guide
Installing a LUT-ELI-3PH Unit in a
Panel-Based System (continued)
Emergency Power: The additional 18 AWG (1.0 mm2) wire
is a “sense” line from terminal 12 on the LUT-ELI-3PH. This
sense line allows an Emergency (Essential) lighting panel to
“sense” when Normal (Non-Essential) power is lost. If more
than one emergency lighting panel needs to sense Normal
(Non-Essential) from a specific LUT-ELI-3PH unit, you may
have to run a dedicated wire between each LUT-ELI-3PH
unit and Emergency (Essential) panel(s).
Shield/Drain: Connect shielding as shown below in wiring
example A:
- Do not connect to Ground (Earth) or circuit selector.
- Connect the bare drain wires and cut off the outside
shield.
•
Connections
Wiring Example A
Control
Wiring:
(2) 12 AWG
(2.5 mm2)
1: Common
2: 24 V
1
Data Link:
(1) shielded,
twisted pair
18 AWG
(1.0 mm2)
3: MUX
4: MUX
Shield/
Drain
Each NEC Class 2/PELV terminal can accept only
two 18 AWG (1.0 mm2) wires. Two 12 AWG
(2.5 mm2) conductors won't fit. Connect as shown
below in wiring example B.
LUT-ELI-3PH
Circuit Selector
Terminal 12 (Sense)
Terminal 5 (Sense)
Terminal 11 (Drain)
Terminal D (Drain)
Terminal 10 (MUX)
Terminal 4 (MUX)
Terminal 9 (MUX)
Terminal 3 (MUX)
Terminal 8 (+V Input)
Terminal 2 (+24VFW)
Terminal 7
(Circuit Common)
Terminal 1
(Common)
Sense:
(1) 18 AWG
(1.0 mm2)
5: Sense line
1
2
3,4
3 ,4
5
1 2 3 4 D 5
4
3
LED2
LED1
1
TEST
2
LED3
RADIOTOUCH
5
FACF
NOTUSED
6
PHASE
CONTACTS
7
´FACP´N/O
8
CONTACTS
9
´FACP´N/C
10
COMMON
MUX
11
+24VFW
DRAIN
12
MUX
SENSE
1 2 3 4 D 5
S ELECT CIRCUIT
C
1 2 3 4 D 5
D
S ELECT CIRCUIT
Power
Link
AB
1
S1
CLASS2LOWVOLTAGEWIRING
C
D
1
2
2
Circuit
Circuit
Panel 1
Wiring Example B
Link
DataBOK
MUX
Sense
MUX
Drain
+24VFW
MUX
Common
AB
MUX
Link
DataAOK
Drain
Link
DataBOK
MUX
Power
Common
Sense
MUX
Drain
+24VFW
MUX
Common
DataAOK
Common
1 2 3 4 D 5
GND
To lighting controls
or processors
2
MUX
•
NEC® Class 2/PELV Panel to Panel Wiring Notes
Drain
•
Panel 2
(4) 12 AWG
(2.5 mm2)
1 2 3 4 D 5
Data B OK
LUT-ELI-3PH Installation Guide
n
Power OK
m
n
se
mon
Data A OK
FW
Lutron® | 6
Emergency Lighting Interface LUT-ELI-3PH | Installation Guide
Test the System
Please perform the following tests to ensure proper
installation.
1. Turn off one of the Normal (Non-Essential) phase(s)
breaker(s) that the LUT-ELI-3PH unit is monitoring.
You should see the following:
•PHASE ON/OFF status Indicator (green) will turn OFF as
the above test creates a phase failure.
•Circuit selector on Emergency (Essential) panel will go to
‘ord’ override mode.
•All lights controlled by Emergency (Essential) panel will go
to Full Intensity (Factory Set).
•The circuit selector in Emergency (Essential) panel will read
‘ord’ on the value display when in Emergency mode.
•All lights controlled by Normal (Non-Essential) panel will
freeze at their respective intensities.
2. Press and hold switch SW1 on the LUT-ELI-3PH unit.
You should see the following:
• TEST LED (orange) will turn ON.
Note: PHASE ON/OFF status indicator (green) will not turn
OFF as test #2 does not create a phase failure.
• Circuit Selector on Emergency (Essential) Panel will go to
‘ord’ override mode.
• All lights controlled by Emergency (Essential) panel will go
to FULL INTENSITY (factory set).
• The circuit selector on Emergency (Essential) panel will
read ‘ord’ on the value display when in Emergency Mode.
• All lights controlled by Normal (Non-essential) panel will
freeze at their current intensities.
• Upon releasing switch SW1, all lights will return to their
original intensities.
SELECT CIRCUIT
D
SELECT CIRCUIT
1
1
2
2
Circuit
Circuit
VIEW VALUE
SELECT VALUE
VIEW VALUE
SELECT VALUE
Link A
3
Link A
Link B
4
Link B
3
4
Value
Value
SELECT VALUE DISPLAYED
Circuit Level
Load Type (See Instructions)
SELECT VALUE DISPLAYED
Circuit Level
Load Type (See Instructions)
5
5
Zone Assignment w/ Circuit Schedule
Zone Assignment w/ Zone CaptureTM
Zone Assignment w/ Circuit Schedule
Zone Assignment w/ Zone CaptureTM
Low-End Trim
High-End Trim
Low-End Trim
High-End Trim
Address ('Ad' displayed)
Address ('Ad' displayed)
Warning - Read instructions to set the Load
Type. Instructions show more load types.
Warning - Read instructions to set the Load
Type. Instructions show more load types.
Load Type Quick Reference:
Load Type Quick Reference:
--- Unassigned
3-1 Neon / CC
--- Unassigned
3-1 Neon / CC
1-1 Incandescent
4-1 Non-Dim
1-1 Incandescent
4-1 Non-Dim
2-1 Fluorescent Lutron Hi-lume FDB Ballast
2-2 Fluorescent Lutron Tu-WireTM Ballast
R
LINK 1
Drain
MUX
Comm
Link Link
AB C
MUX
Drain
Sense
MUX
24VFW
1 2 3 4 D 5
MUX
D
MUX
Link Link
AB C
DataBOK
PowerOK
Common
1 2 3 4 D 5
DataAOK
DataBOK
PowerOK
Drain
DataAOK
LUT-ELI-3PH Installation Guide
Circuit Selector in
Emergency (Essential) Panel
1 2 3 4 D 5
Comm
All Emergency Panels
• Move SW6 to the right Emergency (Essential) position. In
this arrangement, the LUT-ELI-3PH unit will be the only unit
controlling the sense line. If one or more phases go down,
the LUT-ELI-3PH unit sends a signal through the sense
line to Emergency (Essential) panel(s). The lights controlled
by these panels will go to ‘ord’ override levels (factory set
to full intensity). When normal power is restored, lights will
return to their previous intensities.
Note: When in ‘ord’ override mode (factory set to full
intensity), ‘ord’ will appear on value display to confirm that
Emergency (Essential) position is in effect.
1 2 3 4 D 5
MUX
Panels are shipped with SW6 (located at the base of each
Circuit Selector) in the middle position. Terminal 5 (sense)
has no affect on the circuit selector operation.
Drain
Sense
Circuit Selector in Normal
(Non-Emergency) Panel
MUX
Setting the Circuit Selector Normal/Emergency
Switch (SW6) Position
24VFW
MUX
Installing a LUT-ELI-3PH Unit in a
Panel-Based System (continued)
Common
LINK 2
(Non-Ess)
Normal
(Essential)
Emergency
Switch is
in center
position
2-1 Fluorescent Lutron Hi-lume FDB Ballast
2-2 Fluorescent Lutron Tu-WireTM Ballast
R
LINK 1
LINK 2
(Non-Ess)
Normal
(Essential)
Emergency
Switch is
moved to
the right
(emergency)
position
Lutron® | 7
Emergency Lighting Interface LUT-ELI-3PH | Installation Guide
Installing a LUT-ELI-3PH Unit in an
EcoSystem® or Quantum® System
Line Voltage and NEC® Class 2/PELV Connections
Note: Provide proper short-circuit and overcurrent
protection at the distribution panel. Maximum circuit
breaker installation of 20 A.
A Lutron® PP-120H or PP-277H power pack must be
used to power the LUT-ELI-3PH unit when used with a
bus supply. Both the power pack and the bus supplies
must be fed from a normal/emergency supply.
WARNING! Danger of shock. May result in
serious injury or death. DO NOT WIRE WHEN
LIVE! Switch off power to all power feeds
via circuit breaker or isolator before wiring or
servicing the LUT-ELI-3PH unit and EcoSystem
lighting control system or Quantum system.
Buttons and LEDs in the unit are used for
troubleshooting. If wiring is exposed when
accessing buttons and LEDs, the unit must be
accessed by a certified electrician, following
local codes.
Wiring to EcoSystem Bus Supply
*PP-120H or PP-277H
24 V
(Red)
100-347 V 50/60 Hz
3-phase
normal supply
See Figure #1
or Figure #2
on page 2 of
this guide.
Power
pack*
Common
(Black)
Hot
From 120 or 277 V
Normal/Emergency
supply
5
4
3
LED1
LED2
TEST
1
LED3
RADIOTOUCH
6
FACF
NOT USED
2
GND
PHASE
CONTACTS
7
´FACP´ N/O
8
CONTACTS
9
´FACP´ N/C
10
COMMON
MUX
11
+24VFW
DRAIN
12
MUX
SENSE
Neutral
S1
CLASS 2 LOW VOLTAGE WIRING
(8) (7) (1)
Common
Common
(pin 5)
Bus supply
24 V
Bus supply
Emerg.
signal
(pin 6)
100-277 V Normal/
Emergency
supply
Connect up to 32 bus supplies
Wiring to Quantum systems
*PP-120H or PP-277H
Hot
Power
From 120 or 277 V
pack*
Normal/Emergency supply
Neutral
24 V
(Red)
Common
(Black)
100-277 V Normal/Emergency
supply
78
56
34
12
Common
5
4
3
LED2
LED1
1
LED3
2
TEST
RADIOTOUCH
6
FACF
NOTUSED
CONTACTS
7
´FACP´N/O
8
GND
PHASE
9
CONTACTS
10
´FACP´N/C
11
COMMON
12
+24VFW
EM C
MUX
E2
MUX
E1
DRAIN
E2
SENSE
E1
S1
CLASS2LOWVOLTAGEWIRING
Connect up to 8
Quantum hubs
Lutron® | 8
Emerg.
signal
(8) (7)
(1)
LUT-ELI-3PH Installation Guide
Emergency Lighting Interface LUT-ELI-3PH | Installation Guide
Installing a LUT-ELI-3PH Unit in a
GRAFIK Eye® QS Unit
NEC® Class 2/PELV Connections
WARNING! Danger of shock. May result in
serious injury or death. DO NOT WIRE WHEN
LIVE! Switch off power to all power feeds
via circuit breaker or isolator before wiring or
servicing the LUT-ELI-3PH unit and GRAFIK Eye
QS unit.
Buttons and LEDs in the unit are used for
troubleshooting. If wiring is exposed when
accessing buttons and LEDs, the unit must be
accessed by a certified electrician, following
local codes.
•
•
•
Notes
Provide proper short-circuit and overcurrent
protection at the distribution panel. Maximum
circuit breaker installation of 20 A.
When normal power loss is detected at the
LUT-ELI-3PH unit, all zones in the GRAFIK Eye QS
units will go to their emergency states.
The GRAFIK Eye QS unit MUST be powered from a
normal/emergency power feed.
Wiring to a GRAFIK Eye QS Control Unit
Note: For 1-phase 2-wire application, connect phase A, B, and C wires on
LUT-ELI-3PH together for phase sensing.
100-347 V 50/60 Hz
3-phase Normal supply
See Figure #1 or Figure #2
on page 2 of this guide.
12
9
8
7
6
5
4
3
LED1
LED2
TEST
LED
LED3
1
GND
FACF
RADIOTOUCH
2
PHASE
NOTUSED
C
ONTACTS
CONTACTS
SENSE
´FACP´N/O
´FACP´
CP´N/O
GRAFIK Eye QS unit QSGRJ model (back view)
S1
TAGEWIRING
(8) (7)
(3) 18 AWG
(1)
Signal
+24 V
CCI SIG
24 V
CCI Com
4
LUT-ELI-3PH Installation Guide
3
2
1
LED3
RADIOTOUCH
5
NOTUSED
6
CLASS2LOWVOLTAGEWIRING
CONTACTS
7
´FACP´N/O
8
CONTACTS
9
´FACP´N/C
10
COMMON
MUX
11
+24VFW
DRAIN
12
MUX
SENSE
Common
Normal/Emergency
20 A 120 V
1-Phase 2-Wire
power feed
(3) 12 AWG (2.5 mm²)
120-127 V
or
220-240 V
distribution panel
Lutron® | 9
Emergency Lighting Interface LUT-ELI-3PH | Installation Guide
Installing a LUT-ELI-3PH Unit with an
Energi Savr NodeTM Unit(s)
Notes: Provide proper short-circuit and overcurrent
protection at the distribution panel. Maximum circuit
breaker installation of 20 A.
NEC® Class 2/PELV Connections
• A Lutron® PP-120H or PP-277H power pack must be
WARNING! Danger of shock. May result
used to power the LUT-ELI-3PH unit when used with an
in serious injury or death. DO NOT WIRE
Energi Savr Node unit(s). Both the power pack and the
WHEN LIVE! Switch off power to all power
Energi Savr Node unit(s) must be fed from a normal/
feeds via circuit breaker or isolator before
emergency supply.
wiring or servicing the LUT-ELI-3PH and
• When normal power loss is detected at the LUT-ELI-3Energi Savr Node unit.
PH unit, all zones in the Energi Savr Node unit will go to
Buttons and LEDs in the unit are used for
their emergency states.
troubleshooting. If wiring is exposed when accessing • The Energi Savr Node unit MUST be powered from a
buttons and LEDs, the unit must be accessed by a
normal/emergency power feed.
certified electrician, following local codes.
Wiring from Energi Savr Node Units
Note: For 1-phase 2-wire application, connect
phase A, B, and C wires on LUT-ELI-3PH together
for phase sensing.
Connections
LUT-ELI-3PH
Terminal 8 (+V Input)
Energi Savr Node Unit
-------------------------
Power Pack
Red Wire
Terminal 7
(Circuit Common)
Com
(Emergency CCI Input)
Black Wire
Terminal 1 (Signal)
Emerg (Emergency CCI Input) ---------------
100-347 V 50/60 Hz
3-phase Normal supply
See Figure #1 or Figure #2
on page 2 of this guide.
PP-120H or
PP-277H
*+24 V
(Red)
2 #12
Input Power
(120 or 277 V )
Normal/Emergency Power
9
6
5
4
3
LED1
LED2
TEST
LED3
1
FACF
RADIOTOUCH
2
GND
PHASE
NOT USED
´FACP´ N/O
CONTACTS
7
CONTACTS
8
´FACP´ N/C
10
COMMON
MUX
11
+24VFW
DRAIN
12
MUX
SENSE
*Common (Black)
S1
CLASS 2 LOW VOLTAGE WIRING
(8) (7)
(1)
*Signal
*Common
*NEC Class 2/PELV Wiring
18 AWG (1.0 mm²)
Note:
Up to 32 QSN-4T16-S or
QSN-4S16-S units can be
connected to 1 LUT-ELI-3PH
Lutron® | 10
*Signal
*Common
LUT-ELI-3PH Installation Guide
Emergency Lighting Interface LUT-ELI-3PH | Installation Guide
Emergency Power Mode
Setup: LCP128TM / Softswitch128®
with LUT-ELI-3PH
This step is only performed if an emergency pattern* is
needed when normal power is lost. All control device inputs and time clock events are ignored while in
emergency power mode. This step will define if the
panel has emergency circuits and how to configure the
emergency pattern.
• For all the emergency (essential) lighting panels, move
the emergency switches to the right position (see illustration below).
• The essential and non-essential panels must be connected by a sense line wired to terminal 5 on the link connector on the LCP128/Softswitch128 controller (see
illustration below). For wiring details, see the Installation
Guide.
* In this configuration, the emergency (essential) lighting
panel will “sense” the normal panels’ power. When
normal power is lost, the emergency panel will go to the
emergency pattern (factory set to all circuits On). When
normal power is restored, lighting circuits and contact
closure outputs return to their previous state.
Use Terminal 5 to connect a sense line
between emergency and normal panels,
or between the LUT-ELI-3PH unit and one
or more emergency panels. An #18 AWG
wire is recommended for the sense line.
Notes:
• If UL 924 certification is required, the Lutron®
Emergency Lighting Interface (LUT-ELI-3PH) may be
used to meet code. The LUT-ELI-3PH unit senses
the normal (non-essential) line voltage on all three
phases (3PH) of normal power. When one or more
phases of power are lost, the LUT-ELI-3PH unit will
send a signal to terminal 5 on the LCP128/Softswitch128 controller(s). When the emergency
switch is set to the right position (essential) the
emergency pattern will be recalled. The LUT-ELI-3PH unit can be used with one or multiple panel
systems.
• Loss of normal power can be simulated by turning
off all connected normal (non-essential) panel control
breakers. • When the emergency switch is in its center position
(as shipped), terminal 5 the panel does not respond
to emergency.
Three position Emergency Switch is located at the
bottom of the LCP128/Softswitch128 controller.
1 2 3 4 D 5
Left Position
Right Position
(Non-Essential)
(Essential)
Center Position
(No response to Emergency)
Top of the LCP128/Softswitch128 Controller
LUT-ELI-3PH Installation Guide
Lutron® | 11
Emergency Lighting Interface LUT-ELI-3PH | Installation Guide
NEC® Class 2/PELV Wiring to
Fire Alarm Control Panel (FACP)
•
•
Use only with normally open (terminals 3 and 4) or normally
closed (terminals 5 and 6) dry contact closure. When the
proper contact state is triggered, it must be maintained
for the LUT-ELI-3PH unit to go into Emergency Mode.
Once the contact is released, the LUT-ELI-3PH unit will
return the GRAFIK SystemsTM GP, LP, XP panels, XPS,
LCP, RadioTouch® controller, EcoSystem® Bus Supply,
Energi Savr NodeTM unit, or Quantum® Bus Supply back to
Normal operation mode.
Normally Open
FACP Input
The LUT-ELI-3PH unit will have a factory installed
jumper to provide the normally closed input signal
for the supervisory circuit when a normally closed
FACP input is not provided.
Consult your Fire Alarm Control Panel’s instruction
manual before connecting to the LUT-ELI-3PH unit.
Do not connect any voltage source to the FACP
inputs on the LUT-ELI-3PH unit. If voltage is
provided by the FACP and connected to the LUTELI-3PH unit, it can damage the LUT-ELI-3PH unit.
•
•
LUT-ELI-3PH unit
6
5
4
3
LED1
LED2
TEST
LED3
1
GND
9
FACF
RADIOTOUCH
2
PHASE
NOTUSED
CONTACTS
´FACP´N/O
7
CONTACTS
8
´FACP´N/C
10
COMMON
MUX
11
+24VFW
DRAIN
12
MUX
SENSE
Fire Alarm Control Panel
(provided by others)
S1
Normally
open
CLASS2LOWVOLTAGEWIRING
To 24 V
Supervisory Circuit
(Normally Closed
FACP Input)
Common
power
LUT-ELI-3PH unit
9
6
5
4
CLASS2LOWVOLTAGEWIRING
To 24 V
Lutron® | 12
3
S1
TEST
LED2
FACF
LED1
1
LED3
RADIOTOUCH
2
GND
PHASE
NOTUSED
CONTACTS
´FACP´N/O
7
CONTACTS
8
´FACP´N/C
10
COMMON
MUX
11
+24VFW
DRAIN
12
MUX
SENSE
Fire Alarm Control Panel
(provided by others)
Normally
closed
Common
power
LUT-ELI-3PH Installation Guide
Emergency Lighting Interface LUT-ELI-3PH | Installation Guide
Troubleshooting RadioTouch®
Symptom
Lights are at full
intensity and can
not be controlled
by an addressed
transmitter
Lights do not
turn ON and do
not go to high
end when the
test switch is
pressed
Lights do not
turn ON and do
not go to high
end when one
or more of the
normal power
phases are
turned OFF
Possible Cause
Solution
LUT-ELI-3PH unit is not connected
to Signal on the RadioTouch
Controller
Connect terminal 2 ‘Occ Sig’ from the RadioTouch
Controller to terminal 1 ‘Signal’ on the LUT-ELI-3PH unit
One or more of the phases feeding
the LUT-ELI-3PH unit are off (phase
LED on the LUT-ELI-3PH unit will
be off)
Turn ON all normal power phases to LUT-ELI-3PH unit
Neutral is not connected on the
LUT-ELI-3PH unit (phase LED on
the LUT-ELI-3PH unit will be OFF)
Connect neutral
24V
is not connected on the
LUT-ELI-3PH unit (phase LED on
the LUT-ELI-3PH unit will be OFF)
Connect terminal 4 ‘24V ’ from RadioTouch Controller to
terminal 8 ‘+ V Input’ on the LUT-ELI-3PH unit
There is a short across FACP and
normally open contact (FACP LED
will be ON)
Remove short
DIP switch 2 on the RadioTouch
Controller is in the UP position
Move DIP switch 2 on the RadioTouch Controller to the
DOWN position
24V
and signal wires are
swapped
Connect terminal 4 ‘24 V ’ from the RadioTouch
Controller to terminal 8 ‘+V Input’ on the LUT-ELI-3PH unit
and connect terminal 2 ‘Occ Sig’ from the RadioTouch
Controller to terminal 1 ‘Signal’ on the LUT-ELI-3PH unit
24V
and common wires are
swapped
Connect terminal 4 ‘24V ’ from the RadioTouch
Controller to terminal 8 ‘+V Input’ on the LUT-ELI-3PH unit
and connect terminal 6 ‘Cir Com’ from the RadioTouch
Controller to terminal 7 ‘Circuit Common’ on the LUT-ELI3PH unit
Common and signal wires are
swapped
Connect terminal 6 ‘Cir Com’ from the RadioTouch
Controller to terminal 7 ‘Circuit Common’ on the LUTELI-3PH unit and connect terminal 2 ‘Occ sig’ from the
RadioTouch Controller to terminal 1 ‘Signal’ on the LUT-ELI3PH unit
DIP switch 2 on the RadioTouch
Controller is in the UP position Move DIP switch 2 on the RadioTouch Controller to the
DOWN position
24V
Connect terminal 4 ‘24V ’ from the RadioTouch Controller
to terminal 8 ‘+V Input’ on the LUT-ELI-3PH unit and
connect terminal 2 ‘Occ Sig’ from the RadioTouch Controller
to terminal 1 ‘Signal’ on the LUT-ELI-3PH unit
and signal are swapped
That RadioTouch Controller is not
powered by the emergency circuit
power
Power the RadioTouch Controller from the emergency
circuit and not from normal
The emergency transfer switch is
not switching over
Consult transfer switch manufacture for troubleshooting
LUT-ELI-3PH unit is connected to
the emergency circuit
Connect the LUT-ELI-3PH unit to normal power
24V
and common wires are
swapped
Connect terminal 4 ‘24V ’ from the RadioTouch
Controller to terminal 8 ‘+V Input’ on the LUT-ELI-3PH unit
and connect terminal 6 ‘Cir Com’ from the RadioTouch
Controller to terminal 7 ‘Circuit Common’ on the LUT-ELI3PH unit
Common and signal wires are
swapped
Connect terminal 6 ‘Cir Com’ from the RadioTouch
Controller to terminal 7 ‘Circuit Common’ on the LUTELI-3PH unit and connect terminal 2 ‘Occ Sig’ from the
RadioTouch Controller to terminal 1 ‘Signal’ on the LUT-ELI3PH unit
LUT-ELI-3PH Installation Guide
Lutron® | 13
Emergency Lighting Interface LUT-ELI-3PH | Installation Guide
Troubleshooting Panel Based Systems
Symptom
Possible Cause
Lights are at
full intensity
and can not be
controlled by
the wallstation
(Circuit selector/
controller
reads “ord”), or
controller reads
Emergency
Mode
Sense wire is not connected from
the Circuit selector/controller to the
LUT-ELI-3PH unit
Connect terminal 5 ‘Sense’ from the Circuit selector/
controller to terminal 12 ‘Sense’ on the LUT-ELI-3PH unit
One or more of the phases feeding
the LUT-ELI-3PH unit are off (phase
LED on the LUT-ELI-3PH unit will
be OFF)
Turn ON all normal power phases to LUT-ELI-3PH unit
Neutral is not connected on the
LUT-ELI-3PH unit (phase LED on
the LUT-ELI-3PH unit will be OFF)
Connect neutral
24VFW is not connected on the
LUT-ELI-3PH unit (phase LED on
the LUT-ELI-3PH unit will be OFF)
Connect terminal 2 ‘24VFW’ from the Circuit selector/
controller to terminal 8 ‘+V Input’ on the LUT-ELI-3PH unit
There is a short across FACP and
normally open contact (FACP LED
will be ON)
Remove short
24VFW and sense wires are
swapped
Connect terminal 2 ‘24VFW’ from the Circuit selector/
controller to terminal 8 ‘+V Input’ on the LUT-ELI-3PH unit
and connect terminal 5 ‘Sense’ from the Circuit selector/
controller to terminal 12 ‘Sense’ on the LUT-ELI-3PH unit
Common and sense wires are
swapped
Connect terminal 1 ‘Common’ from the Circuit selector/
controller to terminal 7 ‘Circuit Common’ on the LUT-ELI3PH unit and connect terminal 5 ‘Sense’ from the Circuit
selector/controller to terminal 12 ‘Sense’ on the LUT-ELI3PH unit
Lights do not
turn ON and do
not go to high
end when the
test switch is
pressed
SW6 on the Circuit selector/
controller is in the middle position or
far left position
Move SW6 on the Circuit selector/controller to the far right
position
24V
and common wires are
swapped
Connect terminal 2 ‘24VFW’ from the Circuit selector/
controller to terminal 8 ‘+V Input’ on the LUT-ELI-3PH unit
and connect terminal 1 ‘Common’ from the Circuit selector/
controller to terminal 7 ‘Circuit Common’ on the LUT-ELI3PH unit
Lights do not
turn ON and do
not go to high
end when one
or more of the
normal power
phases are
turned OFF
SW6 on the Circuit selector/
controller is in the middle position or
far left position
Move SW6 on the Circuit selector/controller to the far right
position
24 V
and common wires are
swapped
Connect terminal 2 ‘24VFW’ from the Circuit selector/
controller to terminal 8 ‘+V Input’ on the LUT-ELI-3PH unit
and connect terminal 1 ‘Common’ from the Circuit selector/
controller to terminal 7 ‘Circuit Common’ on the LUT-ELI3PH unit
That Emergency Panel is not
powered by the emergency circuit
Power the Emergency Panel from the emergency circuit and
not from normal power
The emergency transfer switch is
not switching over
Consult transfer switch manufacture for troubleshooting
LUT-ELI-3PH unit is connected to
the emergency circuit
Connect the LUT-ELI-3PH unit to normal power
Lutron® | 14
Solution
LUT-ELI-3PH Installation Guide
Emergency Lighting Interface LUT-ELI-3PH | Installation Guide
Troubleshooting Energi Savr NodeTM Installations
Symptom
Possible Cause
Solution
Signal wire is not connected from
the LUT-ELI-3PH unit to the Energi
Savr Node unit
Connect ‘Emerg’ terminal from the Energi Savr Node unit to
terminal 1 ‘Signal’ on the LUT-ELI-3PH unit
One or more of the phases feeding
the LUT-ELI-3PH unit are off (phase
LED on the LUT-ELI-3PH unit will
be OFF)
Turn ON all normal power phases to LUT-ELI-3PH unit
Neutral is not connected on the
LUT-ELI-3PH unit (phase LED on
the LUT-ELI-3PH unit will be OFF)
Connect neutral
24VFW is not connected on the
LUT-ELI-3PH unit (phase LED on
the LUT-ELI-3PH unit will be OFF)
Connect red wire (24 V ) from the PP-120H or PP-277H
unit to terminal 8 ‘+V Input’ on the LUT-ELI-3PH unit
There is a short across FACP and
normally open contact (FACP LED
will be ON)
Remove short
Lights do not
turn ON and do
not go to high
end when the
test switch is
pressed
24 V
and common wires are
swapped
Connect red wire (24 V ) from the PP-120H or PP-277H
unit to terminal 8 ‘+V Input’ on the LUT-ELI-3PH unit and
connect black wire (Common) from the PP-120H or
PP-277H unit to terminal 7 ‘Circuit Common’ on the
LUT-ELI-3PH unit
Lights do not
turn ON and do
not go to high
end when one
or more of the
normal power
phases are
turned OFF
24 V
and common wires are
swapped
Connect red wire (24 V ) from the PP-120H or PP-277H
unit to terminal 8 ‘+V Input’ on the LUT-ELI-3PH unit and
connect black wire (Common) from the PP-120H or
PP-277H unit to terminal 7 ‘Circuit Common’ on the
LUT-ELI-3PH unit
Emergency Panel is not powered by
the emergency circuit
Power the Emergency Panel from the emergency circuit and
not from normal power
The emergency transfer switch is
not switching over
Consult transfer switch manufacturer for troubleshooting
LUT-ELI-3PH unit is connected to
the emergency circuit
Connect the LUT-ELI-3PH unit to normal power
Lights are at full
intensity. Unit will
not respond to
local control or
input signals.
LUT-ELI-3PH Installation Guide
Lutron® | 15
Emergency Lighting Interface LUT-ELI-3PH | Installation Guide
Troubleshooting EcoSystem® or Quantum® System Installations
Symptom
Lights are at full
intensity. System
will not respond
to local control
or input signals.
Possible Cause
Solution
Signal wire is not connected from the Connect ‘CCI-EMERG’ terminal from the Ecosystem bus
supply to terminal 1 ‘Signal’ on the LUT-ELI-3PH unit
LUT-ELI-3PH unit to the Ecosystem
bus supply
Signal wire is not connected from the Connect ‘EM’ terminal from the Quantum bus supply to
terminal 1 ‘Signal’ on the LUT-ELI-3PH unit
LUT-ELI-3PH unit to the Quantum
bus supply
One or more of the phases feeding
the LUT-ELI-3PH unit are off (phase
LED on the LUT-ELI-3PH unit will be
OFF)
Turn on all normal power phases to
LUT-ELI-3PH unit
Neutral is not connected on the LUT- Connect neutral
ELI-3PH unit (phase LED on the LUTELI-3PH unit will be OFF)
24VFW is not connected on the LUT- Connect red wire (24 V ) from the PP-120H or PPELI-3PH unit (phase LED on the LUT- 277H unit to terminal 8 ‘+V Input’ on the LUT-ELI-3PH
ELI-3PH unit will be OFF)
unit
There is a short across FACP and
normally open contact (FACP LED
will be ON)
Remove short
Lights do not
turn ON and do
not go to high
end when the
test switch is
pressed
24 V
and common wires are
swapped
Connect red wire (24 V ) from the PP-120H or PP277H unit to terminal 8 ‘+V Input’ on the LUT-ELI-3PH
unit and connect black wire (Common) from the PP-120H
or PP-277H unit to terminal 7 ‘Circuit Common’ on the
LUT-ELI-3PH unit
Lights do not
turn ON and do
not go to high
end when one
or more of the
normal power
phases are
turned OFF 24 V
and common wires are
swapped
Connect red wire (24 V ) from the PP-120H or PP277H unit to terminal 8 ‘+V Input’ on the LUT-ELI-3PH
unit and connect black wire (Common) from the PP-120H
or PP-277H unit to terminal 7 ‘Circuit Common’ on the
LUT-ELI-3PH unit
Emergency Panel is not powered by
the emergency circuit
Power the Emergency Panel from the emergency circuit
and not from normal power
The emergency transfer switch is not Consult transfer switch manufacturer for troubleshooting
switching over
LUT-ELI-3PH unit is connected to
the emergency circuit
Lutron® | 16
Connect the LUT-ELI-3PH unit to normal power
LUT-ELI-3PH Installation Guide
Emergency Lighting Interface LUT-ELI-3PH | Installation Guide
Troubleshooting a GRAFIK Eye® QS Installation
Symptom
Possible Cause
Solution
Lights are at
full intensity.
System will not
respond to
local control or
input signals.
LUT-ELI-3PH unit is not connected
to ‘CCI SIG’ on the GRAFIK Eye QS
unit
Connect the ‘CCI SIG’ terminal from the GRAFIK Eye QS
unit to terminal 1 ‘Signal’ on the LUT-ELI-3PH unit
One or more of the phases feeding
the LUT-ELI-3PH unit are off (phase
LED on the LUT-ELI-3PH unit will be
off)
Turn on all normal power phases to LUT-ELI-3PH unit
Neutral is not connected on the
Connect neutral
LUT-ELI-3PH unit (phase LED on the
LUT-ELI-3PH unit will be OFF)
24 V
is not connected on the
Connect the ‘24 V ’ terminal from the GRAFIK Eye QS
LUT-ELI-3PH unit (phase LED on the unit to terminal 8 ‘+ V Input’ on the LUT-ELI-3PH unit
LUT-ELI-3PH unit will be OFF)
There is a short across FACP and
normally open contact (FACP LED
will be ON)
Lights do not
24 V
and signal are swapped
turn ON and do
not go to high
end when the
test switch is
24 V
and common wires are
pressed
swapped
Lights do not
turn ON and do
not go to high
end when one
or more of the
normal power
phases are
turned OFF
Remove short
Connect the ‘24 V ’ terminal from the GRAFIK Eye QS
unit to terminal 8 ‘+V Input’ on the LUT-ELI-3PH unit and
connect the ‘CCI SIG’ terminal from the GRAFIK Eye QS
unit to terminal 1 ‘Signal’ on the LUT-ELI-3PH unit
Connect the ‘24 V ’ terminal from the GRAFIK Eye QS
unit to terminal 8 ‘+V Input’ on the LUT-ELI-3PH unit and
connect the ‘CCI Com’ terminal from the GRAFIK Eye QS
unit to terminal 7 ‘Circuit Common’ on the LUT-ELI-3PH
unit
Common and signal are swapped
Connect the ‘CCI Com’ terminal from the GRAFIK Eye QS
unit to terminal 7 ‘Circuit Common’ on the LUT-ELI-3PH
unit and connect the ‘CCI SIG’ terminal from the GRAFIK
Eye QS unit to terminal 1 ‘Signal’ on the LUT-ELI-3PH unit
GRAFIK Eye QS unit ‘CCI SIG’ input
has not been set up as an emergency input
Refer to programming guide for the GRAFIK Eye QS unit
on how to program the ‘CCI SIG’ input as an emergency
input.
24V and signal are swapped
Connect the ‘24 V ’ terminal from the GRAFIK Eye QS
unit to terminal 8 ‘+V Input’ on the LUT-ELI-3PH unit and
connect the ‘CCI SIG’ terminal from the GRAFIK Eye QS
unit to terminal 1 ‘Signal’ on the LUT-ELI-3PH unit
The GRAFIK Eye QS unit is not pow- Power the GRAFIK Eye QS unit from the emergency circuit
ered by the emergency circuit power and not from normal
The emergency transfer switch is
not switching over
Consult transfer switch manufacture for troubleshooting
LUT-ELI-3PH unit is connected to
the emergency circuit
Connect the LUT-ELI-3PH unit to normal power
24 V
and common wires are
swapped
Connect the ‘24 V ‘ terminal from the GRAFIK Eye QS
unit to terminal 8 ‘+V Input’ on the LUT-ELI-3PH unit and
connect the ‘CCI Com’ terminal from the GRAFIK Eye QS
unit to terminal 7 ‘Circuit Common’ on the LUT-ELI-3PH
unit
Common and signal wires are
swapped
Connect the ‘CCI Com’ terminal from the GRAFIK Eye QS
unit to terminal 7 ‘Circuit Common’ on the LUT-ELI-3PH
unit and connect the ‘CCI SIG’ terminal from the GRAFIK
Eye QS unit to terminal 1 ‘Signal’ on the LUT-ELI-3PH unit
GRAFIK Eye QS unit ‘CCI SIG’ input
has not been set up as an emergency input
Refer to programming guide for the GRAFIK Eye QS unit
on how to program the ‘CCI SIG’ input as an emergency
input.
LUT-ELI-3PH Installation Guide
Lutron® | 17
Emergency Lighting Interface LUT-ELI-3PH | Installation Guide
NOTES:
LUT-ELI-3PH Installation Guide
Emergency Lighting Interface LUT-ELI-3PH | Installation Guide
NOTES:
LUT-ELI-3PH Installation Guide
Emergency Lighting Interface LUT-ELI-3PH | Installation Guide
Lutron Electronics Co., Inc.
One Year Limited Warranty
For a period of one year from the date of purchase, and subject to the exclusions and restrictions
described below, Lutron warrants each new unit to be free from manufacturing defects. Lutron
will, at its option, either repair the defective unit or issue a credit equal to the purchase price of
the defective unit to the Customer against the purchase price of comparable replacement part
purchased from Lutron. Replacements for the unit provided by Lutron or, at its sole discretion,
an approved vendor may be new, used, repaired, reconditioned, and/or made by a different
manufacturer.
If the unit is commissioned by Lutron or a Lutron approved third party as part of a Lutron
commissioned lighting control system, the term of this warranty will be extended, and any credits
against the cost of replacement parts will be prorated, in accordance with the warranty issued
with the commissioned system, except that the term of the unit’s warranty term will be measured
from the date of its commissioning.
EXCLUSIONS AND RESTRICTIONS
This Warranty does not cover, and Lutron and its suppliers are not responsible for:
1. Damage, malfunction or inoperability diagnosed by Lutron or a Lutron approved third party
as caused by normal wear and tear, abuse, misuse, incorrect installation, neglect, accident,
interference or environmental factors, such as (a) use of incorrect line voltages, fuses or circuit
breakers; (b) failure to install, maintain and operate the unit pursuant to the operating instructions
provided by Lutron and the applicable provisions of the National Electrical Code and of the Safety
Standards of Underwriter's Laboratories; (c) use of incompatible devices or accessories; (d)
improper or insufficient ventilation; (e) unauthorized repairs or adjustments; (f) vandalism; or (g)
an act of God, such as fire, lightning, flooding, tornado, earthquake, hurricane or other problems
beyond Lutron’s control.
2. On-site labor costs to diagnose issues with, and to remove, repair, replace, adjust, reinstall and/
or reprogram the unit or any of its components.
3. Equipment and parts external to the unit, including those sold or supplied by Lutron (which may
be covered by a separate warranty).
4. The cost of repairing or replacing other property that is damaged when the unit does not work
properly, even if the damage was caused by the unit.
EXCEPT AS EXPRESSLY PROVIDED IN THIS WARRANTY, THERE ARE NO EXPRESS OR
IMPLIED WARRANTIES OF ANY TYPE, INCLUDING ANY IMPLIED WARRANTIES OF
FITNESS FOR A PARTICULAR PURPOSE OR MERCHANTABILITY. LUTRON DOES NOT
WARRANT THAT THE UNIT WILL OPERATE WITHOUT INTERRUPTION OR BE ERROR
FREE.
NO LUTRON AGENT, EMPLOYEE OR REPRESENTATIVE HAS ANY AUTHORITY TO BIND
LUTRON TO ANY AFFIRMATION, REPRESENTATION OR WARRANTY CONCERNING THE
UNIT. UNLESS AN AFFIRMATION, REPRESENTATION OR WARRANTY MADE BY AN AGENT,
EMPLOYEE OR REPRESENTATIVE IS SPECIFICALLY INCLUDED HEREIN, OR IN STANDARD
PRINTED MATERIALS PROVIDED BY LUTRON, IT DOES NOT FORM A PART OF THE BASIS
OF ANY BARGAIN BETWEEN LUTRON AND CUSTOMER AND WILL NOT IN ANY WAY BE
ENFORCEABLE BY CUSTOMER.
IN NO EVENT WILL LUTRON OR ANY OTHER PARTY BE LIABLE FOR EXEMPLARY,
CONSEQUENTIAL, INCIDENTAL OR SPECIAL DAMAGES (INCLUDING, BUT NOT LIMITED
TO, DAMAGES FOR LOSS OF PROFITS, CONFIDENTIAL OR OTHER INFORMATION, OR
PRIVACY; BUSINESS INTERRUPTION; PERSONAL INJURY; FAILURE TO MEET ANY DUTY,
INCLUDING OF GOOD FAITH OR OF REASONABLE CARE; NEGLIGENCE, OR ANY OTHER
PECUNIARY OR OTHER LOSS WHATSOEVER), NOR FOR ANY REPAIR WORK UNDERTAKEN
WITHOUT LUTRON’S WRITTEN CONSENT ARISING OUT OF OR IN ANY WAY RELATED
TO THE INSTALLATION, DEINSTALLATION, USE OF OR INABILITY TO USE THE UNIT OR
OTHERWISE UNDER OR IN CONNECTION WITH ANY PROVISION OF THIS WARRANTY, OR
ANY AGREEMENT INCORPORATING THIS WARRANTY, EVEN IN THE EVENT OF THE FAULT,
TORT (INCLUDING NEGLIGENCE), STRICT LIABILITY, BREACH OF CONTRACT OR BREACH
OF WARRANTY OF LUTRON OR ANY SUPPLIER, AND EVEN IF LUTRON OR ANY OTHER
PARTY WAS ADVISED OF THE POSSIBILITY OF SUCH DAMAGES.
NOTWITHSTANDING ANY DAMAGES THAT CUSTOMER MIGHT INCUR FOR ANY REASON
WHATSOEVER (INCLUDING, WITHOUT LIMITATION, ALL DIRECT DAMAGES AND ALL
DAMAGES LISTED ABOVE), THE ENTIRE LIABILITY OF LUTRON AND OF ALL OTHER
PARTIES UNDER THIS WARRANTY ON ANY CLAIM FOR DAMAGES ARISING OUT OF OR IN
CONNECTION WITH THE MANUFACTURE, SALE, INSTALLATION, DELIVERY, USE, REPAIR,
OR REPLACEMENT OF THE UNIT, OR ANY AGREEMENT INCORPORATING THIS WARRANTY,
AND CUSTOMER'S SOLE REMEDY FOR THE FOREGOING, WILL BE LIMITED TO THE
AMOUNT PAID TO LUTRON BY CUSTOMER FOR THE UNIT. THE FOREGOING LIMITATIONS,
EXCLUSIONS AND DISCLAIMERS WILL APPLY TO THE MAXIMUM EXTENT ALLOWED BY
APPLICABLE LAW, EVEN IF ANY REMEDY FAILS ITS ESSENTIAL PURPOSE.
TO MAKE A WARRANTY CLAIM
To make a warranty claim, promptly notify Lutron within the warranty period described above
by calling the Lutron Technical Support Center at (800) 523-9466. Lutron, in its sole discretion,
will determine what action, if any, is required under this warranty. To better enable Lutron to
address a warranty claim, have the unit's serial and model numbers available when making the
call. If Lutron, in its sole discretion, determines that an on-site visit or other remedial action is
necessary, Lutron may send a Lutron Services Co. representative or coordinate the dispatch of a
representative from a Lutron approved vendor to Customer's site, and/or coordinate a warranty
service call between Customer and a Lutron approved vendor.
NEC is a registered trademark of National Fire Protection Association, Quincy, Massachusetts.
Belden is a registered trademark of Belden, Inc., Richmond, Indiana. Liberty Wire & Cable is a
registered trademark of Liberty Wire & Cable, Colorado Springs, Colorado.
Lutron, EcoSystem, GRAFIK Eye, Quantum, RadioTouch, Softswitch128, and the sunburst logo are
registered trademarks and Energi Savr Node and LCP128 are trademarks of Lutron Electronics
Co., Inc.
© 2010 Lutron Electronics Co, Inc.
LUT-ELI-3PH Installation Guide
Internet: www.lutron.com
WORLD HEADQUARTERS
Lutron Electronics Co., Inc.
7200 Suter Road
Coopersburg, PA 18036-1299 U.S.A.
TOLL FREE: 1.800.523.9466
(U.S.A., Canada, and the Caribbean)
Tel: +1.610.282.3800
Fax: +1.610.282.1243
EUROPEAN HEADQUARTERS
Lutron EA Ltd.
Lutron House
6 Sovereign Close
Wapping
London, E1W 3JF, UK
FREEPHONE: 0800.282.107 (U.K.)
Tel: +44.(0)20.7702.0657
Fax: +44.(0)20.7480.6899
ASIAN HEADQUARTERS
Singapore
Lutron GL, Ltd.
15 Hoe Chiang Road
#07-03 Tower Fifiteen
Singapore 089316
TOLL FREE: 800.120.4491
Tel: +65.6220.4666
Fax: +65.6220.4333
HONG KONG SALES OFFICE
Tel: +852.2104.7733
Fax: +852.2104.7633
Lutron Electronics Co., Inc., reserves the right to make
improvements or changes in its products without prior
notice. Although every attempt is made to ensure that
this information is accurate and up to date, please
check with Lutron to confirm product availability, latest
specifications and suitability for your application.
Printed in the U.S.A.
P/N 031-353 Rev. A 09/10