NGP-2200D-M5 Nitrogen Generator Features • 7.5 HP lubricated air compressor needed for NFPA 13 required 30 minutes fill for 2200 gallon system at 40 PSI AIR COMPRESSOR AIR MAINTENANCE DEVICE • Handles up to 16,000 gallons of total sprinkler system capacity (based on NFPA 13 allowable leak rates for a new sprinkler system) NITROGEN CABINET • Premium nitrogen membrane • UL 508A listed industrial control panel • Built-in Programmable Logic Controller for leak detection and air bypass alarm systems NITROGEN STORAGE TANK • Form C dry contacts for Building Management System (BMS) notification • 80 gallon air tank and 80 gallon nitrogen tank AIR STORAGE TANK • Includes all filters, relief valves, automatic drains and gauges Description The Potter Nitrogen Generator, NGP-2200D-M5, is specifically designed to provide on-site, high purity nitrogen for use in fire protection sprinkler systems. When used as a supervisory gas in fire sprinkler systems, nitrogen slows corrosion, improves the life of your system, and lowers maintenance costs. The NGP-2200D-M5 includes a tank mounted air compressor, nitrogen cabinet, and a nitrogen storage tank. These systems include all air filtration equipment, an air compressor, nitrogen membrane, as well as tanks required to keep the generator operating at peak efficiency. Potter Nitrogen Generator Systems provide a low cost, reliable, and efficient method of producing a minimum of 98% nitrogen at the point of usage. unit in a location that is conveniently located near fire sprinkler system connections and a drain. The Potter Nitrogen Generator should always be installed in an adequately ventilated room. Nitrogen is nontoxic and largely inert. Rapid release of nitrogen gas into an enclosed space displaces the oxygen and can cause an asphyxiation hazard. Inhalation of nitrogen in excessive concentrations can result in unconsciousness without any warning symptoms. For detailed installation and operation instructions please refer to the Potter Nitrogen Generator Manual #5401550. Technical Specifications The NGP-2200D-M5 utilizes nitrogen membrane technology for gas separation. Nitrogen membranes are highly effective and a cost conscious way of producing on-site nitrogen. Acting as a filter, the smaller oxygen and water vapor molecules can pass through the membrane quickly. The larger nitrogen molecules are less likely to diffuse through the separator tubes; therefore, they continue downstream to the separator outlet, through the air maintenance device and into the fire protection system. As the system fills with nitrogen, the remaining oxygen molecules in the fire protection system are exhausted by using the Potter IntelliPurge® Nitrogen Purge Valve. The Potter IntelliPurge® Nitrogen Purge Valve will periodically monitor the fire protection system to ensure high purity nitrogen is consistent throughout the sprinkler system. Compressor Package Size (HxWxD) 75” x 34” x 29” Nitrogen Cabinet Size (HxWxD) 72” x 30” x 15” Nitrogen Tank Size (HxØ) 70” x 20” Compressor Package Weight 500 lbs Nitrogen Cabinet Weight 250 lbs Nitrogen Tank Weight 200 lbs Power Supply Available in 208V (13.3A), 230V (12.4A), 460V (6.2A) three phase Max Operating Pressure 175 PSI Installation Temperature Range 50ºF (10ºC) to 110ºF (43ºC) Air Purity ISO Class 1.4.1 or better: Free of water 38°F (3°C) Dew Point, compressor oil (0.008 PPM or .01 mg/m3), hydrocarbons, and particles (<0.01 μm microns) The Potter NGP-2200D-M5 should be installed in a dry, clean, and well-ventilated room with ambient temperatures above 50°F at all times. Allow access to the front of the nitrogen cabinet for service and place the Potter Electric Signal Company, LLC • St. Louis, MO 8820030 - REV B • • 9/15 Phone: 800-325-3936 • www.pottersignal.com PAGE 1 OF 3 NGP-2200D-M5 Nitrogen Generator Cabinet Dimensions Fig 1 MEMBRANE PRESSURE GAUGE NITROGEN TANK PRESSURE GAUGE 1/2" COMPRESSION FITTING, NITROGEN OUTLET, PIPE TO NITROGEN STORAGE TANK. C 13 1/8" 1/2" CONDUIT CONNECTION 2 PLCS POWER ON LIGHT NITROGEN SOLENOID LIGHT ALARM LIGHT 72" 67 1/8" ALARM HORN 1/2" COMPRESSION FITTING AIR INLET, PIPE TO AIR COMPRESSOR. A 30" DRAIN SOLENOID INLET PIPE TO AIR TANK. B PS-2 PRESSURE SWITCH 1/4" COMPRESSION FITTING PIPE TO NITROGEN STORAGE TANK. D 2" DRAIN CONNECTION 1/4" OD TUBING, PUSH TO CONNECT (PIPE TO FLOOR DRAIN) 14 1/2" 30" 1/2" FNPT OXYGEN ENRICHED PERMEATE OUTLET (PIPE TO SAFE LOCATION) Tank Dimensions COMPRESSOR Fig 2 MOTOR AFTERCOOLER AIR TANK PRESSURE GAUGE PS-1 PRESSURE SWITCH CHECK VALVE 74 7/8" DRAIN CONNECTION 3/8" OD TUBING, PUSH TO CONNECT (PIPE TO FLOOR DRAIN) 39 1/4" SEPARATOR 1/2" NPT OUTLET CONNECTION, FLEX HOSE CONNECTION TO NITROGEN GENERATOR CABINET. A 26 3/8" 80 GALLON AIR TANK 33 3/8" 28 3/8 " 24" 1/4" COMPRESSION FITTING, CONNECT TO DRAIN SOLENOID INLET ON REAR OF NITROGEN GENERATOR CABINET. B DRAIN VALVE 15" .28 X .88 MOUNTING SLOTS 4 PLCS 15" Potter Electric Signal Company, LLC • St. Louis, MO 8820030 - REV B • • 9/15 Phone: 800-325-3936 • www.pottersignal.com PAGE 2 OF 3 NGP-2200D-M5 Nitrogen Generator Storage Tank Dimensions Fig 3 ASME SAFETY RELIEF VALVE 1/4" COMPRESSION FITTING CONNECT TO PS-2 PRESSURE SWITCH ON CABINET. D 9 7/8" NITROGEN TANK PRESSURE GAUGE 20" 2" FNPT PLUG 1/4" FNPT VENT 1/2" FNPT NITROGEN INLET CONNECT TO NITROGEN OUTLET ON CABINET. C 3/4" FNPT SYSTEM CONNECTION CONNECT TO AIR MAINTENANCE DEVICE 69 7/8" 80 GALLON NITROGEN STORAGE TANK 55 1/8" 49 1/8" 2 1/8" 13 1/8" 1/4" FNPT BALL VALVE 18" 45° TYP 6" TYP 9/16" X 7/8" MOUNTING SLOTS LOCATED 17" BOLT 90 APART ON A CIRCLE PATTERN 4 PLCS Ordering Information Model Description Stock No. Model Description Stock No. NGP-2200D-M5-2B THREE PHASE 208V 1119540 NGP-MK Maintenance Kit NGP-M2-M5 1119785 NGP-2200D-M5-3B THREE PHASE 230V 1119541 NGP-2200D-M5-4B THREE PHASE 460V 1119542 INS-PV Potter IntelliPurge® Nitrogen Purge Valve 1119478 NGP-SPV Potter Purge Valve 1119784 NGP-AMD-1 Potter Air Maintenance Device 1119787 Potter Electric Signal Company, LLC • St. Louis, MO 8820030 - REV B • • 9/15 Phone: 800-325-3936 • www.pottersignal.com PAGE 3 OF 3