NGP-2200D-M5 - Potter Electric Signal Company, LLC

advertisement
NGP-2200D-M5
Nitrogen Generator
Features
• 7.5 HP lubricated air compressor needed for NFPA 13 required 30
minutes fill for 2200 gallon system at 40 PSI
AIR
COMPRESSOR
AIR
MAINTENANCE
DEVICE
• Handles up to 16,000 gallons of total sprinkler system capacity
(based on NFPA 13 allowable leak rates for a new sprinkler system)
NITROGEN
CABINET
• Premium nitrogen membrane
• UL 508A listed industrial control panel
• Built-in Programmable Logic Controller for leak detection and air
bypass alarm systems
NITROGEN
STORAGE TANK
• Form C dry contacts for Building Management System (BMS)
notification
• 80 gallon air tank and 80 gallon nitrogen tank
AIR
STORAGE TANK
• Includes all filters, relief valves, automatic drains and gauges
Description
The Potter Nitrogen Generator, NGP-2200D-M5, is specifically
designed to provide on-site, high purity nitrogen for use in fire
protection sprinkler systems. When used as a supervisory gas in fire
sprinkler systems, nitrogen slows corrosion, improves the life of your
system, and lowers maintenance costs. The NGP-2200D-M5 includes
a tank mounted air compressor, nitrogen cabinet, and a nitrogen
storage tank. These systems include all air filtration equipment, an
air compressor, nitrogen membrane, as well as tanks required to keep
the generator operating at peak efficiency. Potter Nitrogen Generator
Systems provide a low cost, reliable, and efficient method of producing
a minimum of 98% nitrogen at the point of usage.
unit in a location that is conveniently located near fire sprinkler system
connections and a drain.
The Potter Nitrogen Generator should always be installed in an
adequately ventilated room. Nitrogen is nontoxic and largely inert.
Rapid release of nitrogen gas into an enclosed space displaces the
oxygen and can cause an asphyxiation hazard. Inhalation of nitrogen
in excessive concentrations can result in unconsciousness without any
warning symptoms.
For detailed installation and operation instructions please refer to the
Potter Nitrogen Generator Manual #5401550.
Technical Specifications
The NGP-2200D-M5 utilizes nitrogen membrane technology for
gas separation. Nitrogen membranes are highly effective and a cost
conscious way of producing on-site nitrogen. Acting as a filter, the
smaller oxygen and water vapor molecules can pass through the
membrane quickly. The larger nitrogen molecules are less likely
to diffuse through the separator tubes; therefore, they continue
downstream to the separator outlet, through the air maintenance device
and into the fire protection system. As the system fills with nitrogen,
the remaining oxygen molecules in the fire protection system are
exhausted by using the Potter IntelliPurge® Nitrogen Purge Valve. The
Potter IntelliPurge® Nitrogen Purge Valve will periodically monitor
the fire protection system to ensure high purity nitrogen is consistent
throughout the sprinkler system.
Compressor Package Size
(HxWxD)
75” x 34” x 29”
Nitrogen Cabinet Size
(HxWxD)
72” x 30” x 15”
Nitrogen Tank Size (HxØ)
70” x 20”
Compressor Package
Weight
500 lbs
Nitrogen Cabinet Weight
250 lbs
Nitrogen Tank Weight
200 lbs
Power Supply
Available in 208V (13.3A), 230V (12.4A), 460V
(6.2A) three phase
Max Operating Pressure
175 PSI
Installation
Temperature Range
50ºF (10ºC) to 110ºF (43ºC)
Air Purity
ISO Class 1.4.1 or better: Free of water 38°F (3°C)
Dew Point, compressor oil (0.008 PPM or .01
mg/m3), hydrocarbons, and particles (<0.01 μm
microns)
The Potter NGP-2200D-M5 should be installed in a dry, clean, and
well-ventilated room with ambient temperatures above 50°F at all times.
Allow access to the front of the nitrogen cabinet for service and place the
Potter Electric Signal Company, LLC
•
St. Louis, MO
8820030 - REV B
•
• 9/15
Phone: 800-325-3936
•
www.pottersignal.com
PAGE 1 OF 3
NGP-2200D-M5
Nitrogen Generator
Cabinet Dimensions
Fig 1
MEMBRANE PRESSURE
GAUGE
NITROGEN TANK
PRESSURE GAUGE
1/2" COMPRESSION FITTING,
NITROGEN OUTLET, PIPE TO
NITROGEN STORAGE TANK. C
13 1/8"
1/2" CONDUIT
CONNECTION
2 PLCS
POWER ON LIGHT
NITROGEN SOLENOID
LIGHT
ALARM LIGHT
72"
67 1/8"
ALARM HORN
1/2" COMPRESSION FITTING
AIR INLET, PIPE TO AIR
COMPRESSOR. A
30"
DRAIN SOLENOID INLET
PIPE TO AIR TANK. B
PS-2 PRESSURE SWITCH
1/4" COMPRESSION FITTING
PIPE TO NITROGEN STORAGE TANK. D
2"
DRAIN CONNECTION
1/4" OD TUBING,
PUSH TO CONNECT
(PIPE TO FLOOR DRAIN)
14 1/2"
30"
1/2" FNPT OXYGEN ENRICHED
PERMEATE OUTLET
(PIPE TO SAFE LOCATION)
Tank Dimensions
COMPRESSOR
Fig 2
MOTOR
AFTERCOOLER
AIR TANK
PRESSURE
GAUGE
PS-1 PRESSURE SWITCH
CHECK VALVE
74 7/8"
DRAIN CONNECTION
3/8" OD TUBING,
PUSH TO CONNECT
(PIPE TO FLOOR DRAIN)
39 1/4"
SEPARATOR
1/2" NPT OUTLET CONNECTION,
FLEX HOSE CONNECTION TO
NITROGEN GENERATOR
CABINET.
A
26 3/8"
80 GALLON
AIR TANK
33 3/8"
28 3/8 "
24"
1/4" COMPRESSION FITTING,
CONNECT TO DRAIN SOLENOID INLET
ON REAR OF NITROGEN GENERATOR
CABINET. B
DRAIN VALVE
15"
.28 X .88
MOUNTING SLOTS
4 PLCS
15"
Potter Electric Signal Company, LLC
•
St. Louis, MO
8820030 - REV B
•
• 9/15
Phone: 800-325-3936
•
www.pottersignal.com
PAGE 2 OF 3
NGP-2200D-M5
Nitrogen Generator
Storage Tank Dimensions
Fig 3
ASME SAFETY RELIEF VALVE
1/4" COMPRESSION FITTING
CONNECT TO PS-2 PRESSURE SWITCH
ON CABINET. D
9 7/8"
NITROGEN TANK
PRESSURE GAUGE
20"
2" FNPT PLUG
1/4" FNPT VENT
1/2" FNPT NITROGEN INLET
CONNECT TO NITROGEN OUTLET
ON CABINET. C
3/4" FNPT SYSTEM CONNECTION
CONNECT TO AIR MAINTENANCE DEVICE
69 7/8"
80 GALLON NITROGEN STORAGE TANK
55 1/8"
49 1/8"
2 1/8"
13 1/8"
1/4" FNPT BALL VALVE
18"
45° TYP
6"
TYP
9/16" X 7/8" MOUNTING SLOTS LOCATED
17" BOLT
90 APART ON A
CIRCLE PATTERN
4 PLCS
Ordering Information
Model
Description
Stock No.
Model
Description
Stock No.
NGP-2200D-M5-2B
THREE PHASE 208V
1119540
NGP-MK
Maintenance Kit NGP-M2-M5
1119785
NGP-2200D-M5-3B
THREE PHASE 230V
1119541
NGP-2200D-M5-4B
THREE PHASE 460V
1119542
INS-PV
Potter IntelliPurge® Nitrogen
Purge Valve
1119478
NGP-SPV
Potter Purge Valve
1119784
NGP-AMD-1
Potter Air Maintenance Device
1119787
Potter Electric Signal Company, LLC
•
St. Louis, MO
8820030 - REV B
•
• 9/15
Phone: 800-325-3936
•
www.pottersignal.com
PAGE 3 OF 3
Download