GENERAL INFORMATION 1) A qualified electrician, in accordance with IEE wiring regulations should carry out connection to mains wiring. 2) This unit must be EARTHED. 3) Ensure that the rated voltage and frequency requirements are compatible with the available mains supply. 4) Cleaning of reflectors and lenses should be carried out using clean, soft and lint free cloths and anti-static cleaning fluid 5) Do not carry out high voltage insulation test, i.e. 500/1000v this may damage internal components. Rapier HIGH FREQUENCY BALLAST In order to protect High Frequency Ballasts, the unit will automatically go into a stand-by state and prevent operation if any of the following occur. 1) The fluorescent lamps are defective, incorrectly fitted or of the wrong type or wattage. 2) The mains voltage is too high, low or disrupted. 3) The ballast overheats. 4) There are poor electrical connections in the circuit. To reactivate the ballast after the fault is corrected, switch the mains off for a minimum of 10 seconds. Do not connect this unit in circuits containing switch start ballasts. FOR MAINTENANCE Remove louvre from aperture. Remove reflector via x4 screws if present. Loosen screws DO NOT REMOVE to free the sliding gear tray. Pull gear tray towards centre of lamp aperture for access to gear. SUSPENDED & SURFACE LUMINAIRE Installation Instructions FURTHER INFORMATION July 14 – Rev B PK/LEAFLETRAPIER TECHNICAL SUPPORT Telephone: 0161 331 5700 E-mail: technical@whitecroftlight.com http://www.whitecroftlighting.com/ Whitecroft Lighting Limited Burlington Street, Ashton-under-Lyne, Lancashire OL7 0AX Telephone +44 (0)870 5 087 087 Facsimile: +44 (0)870 5 084 210 Registered No. 3848973 England Registered Office: As above 3. If the wire SPECIFICATION The Rapier is available as a suspended, surface and close-up-mount product with louvre (semi-specula) which incorporates a number of up and down-light combinations, including 100% down-light. The product has all of the essential and basic features of our core range of fittings, it can be continuously mounted and includes a through wired solution. A single and twin lamp variant of all lamp and optic versions is available, plus a range of blank body infill sections, ensuring the Rapier offers the complete solution for every lighting scheme. The product is easily maintained and simple to install, whilst remaining robust and rigid, especially when utilised as a continuously mounted solution. Once installed, maintenance is achieved via an extractable gear tray (reflector must be removed first on inclusive variants). Please note: not suitable for mounting on suspended trunking. Finish: Luminaire - Textured Silver RAL 9006 Textured polyester powder-coat. - Textured White RAL 9003 Textured polyester powder-coat Canopy/Gear Tray Materials: - White RAL 9003 Textured polyester powder-coat. Luminaire - Aluminium Extrusion Gear Tray - 0.7mm Mild Steel Louvre - Specula MIRO 6 anodised aluminium. Canopy -0.7mm Mild Steel Control: High frequency or DALI dimming gear. Lamps: Single & Twin 28W; 54W; 35W; 49W Single (only) 80W INSTALLATION DETAILS Please note the illustrations used within the installation details are based on the single lamp louvred luminaire. However the installation notes are applicable to all RAPIER variants. IMPORTANT: PLEASE NOTE FITTINGS ARE HANDED. 1. Remove luminaire from packaging, by carefully unwrapping the polythene protective layer and the cardboard end caps. Then check the product is in good condition. Use gloves provided to handle fitting. 4. Mark suspension centres on ceiling, then offer up the ceiling attachments and fix in place (fixings supplied by others). suspension kit is 2. The luminaire can be easily opened by removing the louvre from its aperture by pulling – disengaging the springs from the aluminium profile. used, unpack & check the contents from the kit. This should contain: 4 x clutch and nut 4 x suspension wires 4 x two piece ceiling attachments (skip to step 8 for surface installation) 5. Attach the 4 x clutch mechanisms to the canopy, using the nuts provided. The clutches should be positioned - 2 at either end – into the holes provided. 7. Level the luminaire to the required position, pulling the wire through the clutches. When complete, trim the wire back, remembering to leave some excess for future adjustment 9. Pull cable through the gland before offering fitting to the ceiling. IMPORTANT: check that cable does not restrict louvre retention chords. Once cables are linked into terminals, push away from lamp aperture to avoid clash with louvre. Offer the luminaire up to the pre drilled holes and fix in place using appropriate fixings (supplied by others) Ensure the luminaire is safely secured in position. X4 6. Offer the luminaire up to the suspension wires and push each of the 4 suspension wires through the corresponding clutches (now attached to the canopy.) 8. For SURFACE MOUNTED Level @ 0˚ luminaires, use the circular holes in the canopy as your drilling guide for the ceiling, 2 central fixing points. 10. Should a standalone product be required, unpack the 2 x end caps and clip into place using the square holes provided in the 2 plastic innerend-caps ensuring the moulding pins align with channels in the aluminium profile. X2 11. Should a CONTINUOUS PRODUCT be required, unpack the 4x pins and tap into place ensuring the node is hidden within the channel in the aluminium. For ease apply pins before offering the fitting to the ceiling. 13. Should an infill be required between 2 luminaires, 2 x continuous mount kits are required. Secure 4x pins and 2x nut and bolt to the product (see point 14 - repeat for both ends of infill) 15. Through wiring lays through the 2X open spaces provided in the aluminium body and plastic inner end cap. Linking terminals with link wires supplied. Tuck wires away to prevent louvre trapping cables. X4 12. Add bracket and nut supplied to secure the connection between luminaires through square holes in plastic moulding. Slide black plastic strip inside aluminium profile, to cover any gaps between fittings 14. Offer infill cover plate up to extrusion. Press in to aperture with reasonable force to engage springs. The plate sits flush with extrusion to show successful assembly. DIMENSIONS & FIXING HOLE CENTRES SUSPENDED X2 SURFACE 16. The luminaire can come complete with a mini head sensor pre installed within the louvre. Fit end cap where appropriate. Add lamps and replace louvre to complete install. Description O/A END CAPS LENGTH (WITHOUT END CAPS) CABLE ENTRY TO CENTRE O/A WIDTH SUSPENSION CENTRES SUSPENSION WIDTH CENTRES Dimension A B C D E F PRODUCT VARIANTS 1x /2x 28w or 54w 1x /2x 35w or 49w 1222.5MM 1522.5MM 1171MM 1471MM 550MM 700MM 173MM 173MM 760MM 1420.5MM N/A 71.5MM Please note: All images shown are for illustration purposes only and should be used as a reference guide.