VOLTAGE DROP TABLE - FOR 6 & 12 VOLT SYSTEMS The National Electrical Code limits voltage drop to a maximum of 5% of nominal. The table shows the maximum length of a given battery circuit, assuming that the total load is concentrated at the end of the load circuit. If loads are uniformly spaced (equal watts, equal distances) along the circuit path, all of these distances may be increased, based on the number of heads or fixtures on a given circuit. This may permit a savings by the use of a smaller wire size (see wiring distance formula table below). Wiring Distance Formula Table Number of Heads 2 3 4 5 6 Multiply Feet by 1.33 1.5 1.6 1.67 1.71 For example, a 36 foot long, 6 volt circuit has 7 watt heads spaced 12 feet apart. According to the voltage drop table, #10 wire must be used at 43 feet for a 5% voltage drop. But, multiplying the 27 feet for #12 wire by 1.5, a 401/2 foot wire run is acceptable. Therefore, #12 wire may be used and still meet the 5% voltage drop limitation. Wire size determinations can be made for non-uniformly spaced loads. But for ease and safety, it would be advisable to use the voltage drop tables. For a precise determination of the maximum length of wire run for a concentration load (before applying the adjustment for uniformly distributed loads), divide the total load in watts into the constant at the bottom of each row. (Example: the maximum wire run for #12 wire on a 12 volt system, with a 44 watt load, is 2267÷44, or 51 feet.) Conversely, the maximum load on a run of known length (before applying the adjustment) may be determined by dividing the length into the constant. (Example: On a 12 volt system, a 38 foot run of #12 wire can be loaded to 2267÷38 = 60 watts; on #10 wire, 3604 ÷38 = 94 watts.) Project Name Catalog # 6 VOLT SYSTEM 12 VOLT SYSTEM Total Watts on Wire Run 12 10 8 6 12 10 8 6 6 7 8 10 12 14 16 18 20 21 24 25 28 30 32 35 36 40 42 48 49 50 54 56 60 64 70 72 75 80 84 88 90 96 100 104 108 112 120 125 126 128 132 136 144 150 152 156 160 162 168 175 176 180 184 192 198 200 Constant 94 81 70 56 47 40 35 31 28 27 23 22 20 19 17 16 15 14 13 11 11 11 10 10 9 8 8 7 7 7 6 6 6 6 5 5 5 5 4 4 4 4 4 4 4 3 3 3 3 3 3 3 3 3 3 3 2 2 567 150 128 112 90 75 64 56 50 45 43 37 36 32 30 28 25 25 22 21 18 18 18 16 16 15 14 12 12 12 11 10 10 10 9 9 8 8 8 7 7 7 7 6 6 6 6 6 5 5 5 5 5 5 5 4 4 4 4 901 238 204 179 143 119 102 89 79 71 68 59 57 51 47 44 41 39 35 34 29 29 28 26 25 23 22 20 19 19 18 17 16 16 15 14 13 13 12 11 11 11 11 10 10 10 9 9 9 9 8 8 8 8 8 7 7 7 7 1432 379 325 284 227 189 162 142 126 113 108 94 91 81 76 71 65 63 57 54 47 46 45 42 40 38 35 32 31 30 28 27 25 25 23 22 21 21 20 19 18 18 17 17 16 15 15 15 14 14 14 13 13 12 12 12 11 11 11 2277 377 323 283 226 189 162 141 126 113 108 94 90 81 75 70 64 63 56 54 47 46 45 42 40 37 35 32 31 30 28 27 25 25 23 22 21 21 20 18 18 18 17 17 16 15 15 15 14 14 14 13 13 12 12 12 11 11 11 2267 600 515 450 360 300 257 225 200 180 171 150 144 128 120 112 103 100 90 86 75 73 72 66 64 60 56 51 50 48 45 43 41 40 37 36 34 33 32 30 28 28 28 27 26 25 24 23 23 22 22 21 20 20 20 19 18 18 18 3604 955 818 716 573 477 409 358 318 286 272 238 229 204 191 179 163 159 143 136 119 117 114 106 102 95 89 82 79 76 71 68 65 63 59 57 55 53 51 47 45 45 44 43 42 39 38 37 36 35 35 34 32 32 31 31 29 29 28 5730 1518 1301 1138 911 759 650 569 506 455 433 379 364 325 303 284 260 253 227 217 189 186 182 168 162 151 142 130 126 121 113 108 103 101 95 91 87 84 81 76 72 72 71 69 67 63 60 60 58 57 56 54 52 51 50 49 47 46 45 9109 Wire Gauge (in feet) Fixture Type Wire Gauge (in feet) 12/05/11 © 2012 LSI INDUSTRIES INC.