Liebert® IntelliSlotTM Unity Card Version 5.1.0.0_95201 Firmware

Liebert® IntelliSlotTM Unity Card
Version 5.1.0.0_95201 Firmware
Release Notes
October 30th, 2015
This document outlines:
1. Version and Compatibility Information
2. What’s New
3. Security Issues Addressed
4. Upgrade Instructions
5. Known Issues
===================================================================================
1. Version and Compatibility
===================================================================================
This release contains the following firmware version:
IS-UNITY_5.1.0.0_95201
This release is compatible with the following Liebert IntelliSlot communication cards:
IS-UNITY-DP
IS-UNITY-LIFE
This release is compatible with the following Liebert power and thermal management equipment:
Liebert APM™
Liebert HPC™
Liebert APS™
Liebert HPC-S,M,R,W,Generic
Liebert CRV™
Liebert HPM™
Liebert CW™*
Liebert NX™ 225-600 KVA
Liebert Challenger™*
Liebert NXC™
Liebert Deluxe System/3™*
Liebert NXL™
Liebert DCP™
Liebert NXR™
Liebert DS™*
Liebert PCW™
Liebert DSE™
Liebert PDX™
Liebert eXL™
Liebert PeX™*
Liebert eXM™
Liebert XDC™ with iCOMTM Control
Liebert GXT3™
Liebert XDP™ with iCOMTM Control
Liebert GXT4™
Liebert XDP-Cray
*iCOM Firmware PA1.04.033.STD versions or later
1
Emerson. Consider it Solved., Emerson Network Power and the Emerson Network Power logo are trademarks and service marks of Emerson Electric Co.
©2015 Emerson Electric Co. All rights reserved. Microsoft and Internet Explorer are either registered trademarks or trademarks of Microsoft Corporation.
Google and Chrome are either registered trademarks or trademarks of Google, Inc. Mozilla and Firefox are either registered trademarks or trademarks of
Mozilla Foundation Corporation. Safari, MacBook, and iPad are registered trademarks of Apple, Inc. All other trademarks, brand names, and service marks are
the property of their respective owners.
This release is compatible with the following sensors:
Liebert SN-2D
Liebert SN-T
Liebert SN-Z02
Liebert SN-3C
Liebert SN-TH
Liebert SN-Z03
Liebert SN-L
Liebert SN-Z01
This release supports the following communication interfaces:
Communication Protocol
Communication
Card
LIFE™
Services
Support
HTTP/
HTTPS
Emerson
Protocol
Email
SMS
SNMP
v1,v2c,v3
BACnet
IP/MSTP
Modbus
TCP/RTU
YDN23
IS-UNITY-DP








NXL &
PeX Only
IS-UNITY-LIFE



-
-
-
-
-
-
Third-Party Protocols
This release supports the following browsers:
o
Microsoft Internet Explorer® - IE9, IE10, and IE11
o
Mozilla Firefox® - ver. 28.0 or later
o
Google ChromeTM - ver. 34.0.1847.116 m or later
o
Safari® (MacBook®) - ver. 6.1.1 and 8.0.5
o
Safari® (iPad®) - ver. 5.1.1 and 7.1
===================================================================================
2. What’s New
===================================================================================
This release contains the following enhancements:


Support for the Liebert NX 225-600 KVA UPS units that includes
o
Web (HTTP/HTTPS)
o
Emerson Protocol
o
SNMP v1/v2c/v3
o
Email
o
BACnet MSTP/IP
o
SMS
o
Modbus RTU/TCP
BACnet & Modbus support for Liebert GXT3 and Liebert GXT4 UPS units
NOTE: The Modbus protocol mapping for the GXT is different from the mapping used with the
OC-485 card. See the Liebert IntelliSlot Modbus 485, Modbus IP and BACnet IP Reference
Guide (SL-28170) for more details.
2
Emerson. Consider it Solved., Emerson Network Power and the Emerson Network Power logo are trademarks and service marks of Emerson Electric Co.
©2015 Emerson Electric Co. All rights reserved. Microsoft and Internet Explorer are either registered trademarks or trademarks of Microsoft Corporation.
Google and Chrome are either registered trademarks or trademarks of Google, Inc. Mozilla and Firefox are either registered trademarks or trademarks of
Mozilla Foundation Corporation. Safari, MacBook, and iPad are registered trademarks of Apple, Inc. All other trademarks, brand names, and service marks are
the property of their respective owners.
This release contains fixes for the following issues:
Component
Description
Web Interface
The Web user interface was enhanced to prevent security vulnerabilities,
including IP forwarding, cross-site scripting, and vulnerability to malformed web
queries. The Web user interface will no longer allow entering angle brackets
("<" and ">") in text input fields.
OpenSSL has been upgraded to version 0.9.8zg which includes recent security
fixes.
Data points unique to some Liebert GXT3/4 Dual Inverter UPS models which
were not included in the previous Unity release are now supported.
Liebert GXT3 Dual Inverter UPS units are now properly discovered.
SSL
Liebert GXT3/4
UPS Support
SNMP
Added some missing RFC1628 MIB product information data values for several
UPS products.
Added and fixed various SNMP data point behavior for GXT3 and GXT4 units.
BACnet
Performance improvements were made to improve response time in BACnet
MSTP token passing.
===================================================================================
3. Security Issues Addressed
===================================================================================
The following highly publicized security vulnerabilities have already been addressed in a previous release:
Name
Description
“ShellShock”
Updated bash version to fix this in release 4.2
“Poodle”
SSLv3 was disabled in release 5.0
===================================================================================
4. Update Instructions
===================================================================================
The Unity cards may be updated to this firmware version using the web-based Firmware Upload feature.
Please refer to the Firmware Updates section of the Liebert IntelliSlot Unity Card User Manual (SL-52645).
===================================================================================
5. Known Issues
===================================================================================
Component
Description
Device Settings
When temperature settings are made on some thermal devices, there may be
some ‘round-off’ error of one tenth of a degree between what was requested and
what the device shows after the change. This is a known limitation of some
thermal device firmware versions and will be corrected in future versions of the
device controller firmware.
3
Emerson. Consider it Solved., Emerson Network Power and the Emerson Network Power logo are trademarks and service marks of Emerson Electric Co.
©2015 Emerson Electric Co. All rights reserved. Microsoft and Internet Explorer are either registered trademarks or trademarks of Microsoft Corporation.
Google and Chrome are either registered trademarks or trademarks of Google, Inc. Mozilla and Firefox are either registered trademarks or trademarks of
Mozilla Foundation Corporation. Safari, MacBook, and iPad are registered trademarks of Apple, Inc. All other trademarks, brand names, and service marks are
the property of their respective owners.
Component
Description
Liebert GXT3/4
UPS Support
The IP address of the Unity card may be displayed on the local display of the
Liebert GXT4 UPS unit. The IP address is pushed to the GXT4 when the card
starts up. If the address changes (for example, if it is changed by the DHCP
server when the DHCP lease runs out), the local GXT4 display will continue to
show the old address until the card is restarted.
While the SNMP OIDS for the GXT are backward compatible with those from the
IS-WEBCARD, the text values in some SNMP varbinds and email/SMS
notifications have changed slightly to use the Unity card equivalent.
The preferred way to change the display order for multiple sensors is through the
Web user interface. If the order is changed using one of the supported protocols
then the entire list of sensors should be set in the correct order (including slots
that should become blank) to ensure all sensors are still included.
Sensor order is not reflected in the SNMP flexible MIB until after the card is
rebooted. Reboot the card after setting the sensor order.
SNMP getnext requests may fail on some tables if there are multiple varbinds in
the request. If this occurs, use single-varbind requests.
When using a recent version of the Firefox browser, do not disable the “Accept
cookies from sites” option, and do not select the “Ask me every time” option for
how long to keep cookies. Either of these settings causes the web page to stall
on the initialization page.
Sensor Support
SNMP
Web
4
Emerson. Consider it Solved., Emerson Network Power and the Emerson Network Power logo are trademarks and service marks of Emerson Electric Co.
©2015 Emerson Electric Co. All rights reserved. Microsoft and Internet Explorer are either registered trademarks or trademarks of Microsoft Corporation.
Google and Chrome are either registered trademarks or trademarks of Google, Inc. Mozilla and Firefox are either registered trademarks or trademarks of
Mozilla Foundation Corporation. Safari, MacBook, and iPad are registered trademarks of Apple, Inc. All other trademarks, brand names, and service marks are
the property of their respective owners.