Three Phase Simplex Control Panel (Model #WS3P-TP-300X)
Installation and Operator’s Manual
WS Series® Simplex Control Panel
The WS Series® simplex control panels will control a pump
in sewage, wastewater, and dewatering applications. See
Water simplex control panels come standard with a clear front
NEMA 4X rated enclosure, three floats (stop, start, and high
liquid alarm), an IEC rated contactor, a circuit breaker, and
adjustable overload. All panels are UL listed for the United
States and Canada and come with a three year warranty.
WS3P-TP-300X
Voltage: 208/240/480 VAC Three Phase, Multi-Tap
transformer (208/240/480VAC Primary) provides 120V
control power.
Models (Ratings):
WS3P-TP-3001 (1.0-1.6 Pump Full Load Amps)
WS3P-TP-3002 (1.6-2.5 Pump Full Load Amps)
WS3P-TP-3003 (2.5-4.0 Pump Full Load Amps)
WS3P-TP-3004 (4.0-6.3 Pump Full Load Amps)
WS3P-TP-3005 (6.0-10.0 Pump Full Load Amps)
WS3P-TP-3006 (9.0-14.0 Pump Full Load Amps)
WS3P-TP-3007 (13.0-18.0 Pump Full Load Amps)
WS3P-TP-3008 (17.0 -23.0 Pump Full Load Amps)
WS3P-TP-3009 (20.0-25.0 Pump Full Load Amps)
WS3P-TP-3010 (24.0-32.0 Pump Full Load Amps)
WS3P-TP-3011 (30.0-40.0 Pump Full Load Amps)
WS3P-TP-3012 (37.0-50.0 Pump Full Load Amps)
WS3P-TP-3013 (48.0 -65.0 Pump Full Load Amps)
Features:
• Designed to Control One 208/240/480VAC pump in
sewage applications
• UL Listed for the United States and Canada (panel and
controls)
• NEMA 4X enclosure: heavy duty polycarbonate with
lockable latches
• Pump control visible features: pump hand-off-auto
(H.O.A.) switch, green pump run light, red pump fault light
with reset button and green power on light
• Alarm visible features: red beacon alarm light, alarm test
and silence buttons
• Alarm horn sounds at 85 decibels at 10’
• Remote monitoring dry contacts: high liquid, pump fault,
pump run (normally open)
• Pump protection: motor protective switch included for
pump (branch circuit protection, adjustable overload and
disconnect) , pump thermal cutout circuit
• Includes three narrow angle float switches with 20′ cords
and mounting hardware (some models do not include
switches)
• Float status indicators (stop, start, high liquid)
IM 715, Rev. 0116
1. All installations must be in accordance with the National Electrical
Code, and any other applicable state and local electrical
requirements.
Panel Installation:
1. Caution: To maintain the NEMA 4X rating, make
all wiring connections with seal tight cable grips
or conduit connections.
2. Determine mounting location for control panel.
Mount panel using mounting feet supplied.
3. The control panel should not be mounted in
an area that is subject to submersion.
4. Run pump cable and float cables through
conduit. Make field connections as shown on
wiring diagram.
5. Run power line conductor through conduit. Wire
to terminals per enclosed schematic. Branch
circuit protection to be provided by contractor.
6. Connect power conductors 208/240/480V to
proper locations on terminal block.
7. Float cables require separate conduit from
power and pump cables.
8. Mount float switches at appropriate levels. Be
sure that the floats have a free range of motion
to prevent entanglement.
Start up:
1. When the power is applied, the green power
light located on the white front swing panel shall
light.
2. The Pump HOA Switch shall be placed to the
A (auto) position to ensure the pump will turn
on from the commands of the floats. The pump
can be tested or turned on manually if the HOA
switch is held in the H (Hand-Manual) position.
To test the alarm circuit, push the test button on the
front panel, the audible alarm shall sound and the
red beacon will light. Press the silence button to
silence the alarm.
www.seewaterinc.com
or www.oilsmart.org
951.487.8073 • 888.733.9283
Email: info@seewaterinc.com
121 North Dillon Avenue • San Jacinto, CA 92583
P.O. Box 1269 • San Jacinto, CA 92581
Three Phase Simplex Control Panel (Model #WS3P-TP-300X)
Additional Panel Options
LL - Low Level Alarm Circuit (optional)
Includes normally closed low level float switch. Alarm horn
will sound and red beacon will light in the event of a low level.
Comes with normally open low level dry contact.
Typical Installation for Simplex Control Panel
A typical installation showing a pump on “start” float,
pump off “stop float, and a high liquid alarm float.
Simplex
Demand
Control
Panel
SF - Seal Failure Circuit (optional)
The seal fail circuit will indicate when there is water in the
pump chamber. The circuit is setup to work with a variety of
pumps with a range of resistance sensitivity settings.
Conduit
sized by
end-user
AF - Alarm Flasher
ET - Elapsed Timer Meter w/ LCD display & reset
CC - Cycle Counter w/LCD display & reset
LA - Lightning Secondary Surge Arrestor
MD - Main Disconnect
HIGH LIQUID
ALARM
Service:
Caution: Before checking electrical connections within
the control or attempting to replace any components, turn
off all branch circuits supplying power to the main control
panel.
PUMP
ON
Troubleshooting
Alarm Circuit
PUMP
OFF
To test the alarm light and buzzer, press the test button on the
front panel. If either the light or buzzer do not indicate, replace
the light bulb or buzzer with same type.
Control Board and Fuse
If the power on light is not illuminating on the front panel,
check the voltage at TS1-1 and TS2-2 with a voltage meter.
The voltage should read 120VAC. If voltage present, check
the fuse in the fuse block. If fuse is blown, replace fuse with
same type. The dry contacts are rated for 0-60VAC, 1 amp
maximum.
Floats
The control board has LED Indicators that will illuminate
when the floats are in the closed position. Check floats for
entanglement, full range of motion. Replace damaged floats.
For additional information regarding
operation and troubleshooting questions,
please call See Water, Inc. at 888-733-9283.
www.seewaterinc.com or www.oilsmart.org