Exhaust valve KK TECHNICAL DATA - 2006 page 305 KK Exhaust valve KK is an exhaust valve suitable for offices, houses, etc. Product facts KK Exhaust valve Quick-selection Valve Size (m3/h) Air flow l/s at sound level 30 dB(A) 25 dB(A) 35 dB (A) KK-80 23 28 (101) 34 KK-100 30 37 (133) 45 KK-125 46 57 (205) 68 KK-150 58 70 (252) 81 KK-160 64 80 (288) 98 KK-200 120 140 (504) 170 Fläkt Woods FIFLO 4880 EN 2006.09 1 KK Exhaust valve intended for installation in the ceiling or on a wall. Manufactured from steel sheet. Available also in stainless steel. Six sizes. Product code example: Exhaust valve KK-125 Specifications are subject of alteration without further notice. Exhaust valve KK TECHNICAL DATA - 2006 page 306 Air flow, pressure drop, sound level KK-100 Adjustment s (mm) -12 -9 -6 -3 0 36 9 12 300 200 200 100 100 35 30 50 25 Lp 20 20 10 2 5 10 20 qv [l/s] 5 10 10 A 25 0 dB (A) 30 Δpt, Pa 50 -5 ,d B Δpt, Pa 35 -10 -8 Lp 10 A, Adjustment s (mm) -15 300 (A ) KK-80 50 10 100 KK-125 2 3 5 10 qv [l/s] 20 50 KK-150 Adjustment s (mm) -17 -15 -12 -9 -6 -3 0 3 300 Adjustment s (mm) 6 -15 -13 -10 -5 0 5 10 300 9 200 200 100 35 35 Δpt, Pa 30 50 ) 25 (A 25 Lp Lp 10 A 10 A ,d B ,d B 50 ) 30 (A Δpt, Pa 100 20 20 10 10 3 5 10 20 qv [l/s] 50 100 5 10 50 20 100 150 qv [l/s] KK-160 KK-200 Adjustment s (mm) -18 300 -15 -10 -5 0 5 10 300 Adjustment s (mm) -25 -20 -15 -10 -5 0 10 200 200 35 20 100 100 Δpt, Pa B( A) 25 50 35 30 50 A, d Δpt, Pa 30 dB (A ) Lp 10 25 Lp 10 A, 20 20 10 10 10 5 10 20 50 100 150 qv [l/s] Fläkt Woods FIFLO 4480 EN 2006.09 2 20 50 qv [l/s] 100 200 Specifications are subject of alteration without further notice. Exhaust valve KK TECHNICAL DATA - 2006 page 307 Acoustical data, dimensions and weights Sound power level Lw 125 Correction Koct (dB) Octave bands, middle frequency, Hz 250 500 1000 2000 4000 8000 80 100 125 150 160 200 1 5 -6 -6 1 3 -2 -2 0 -5 -1 1 1 -3 0 -4 -3 -1 0 -3 -3 0 1 1 -3 0 0 -1 -2 -4 -10 -8 -13 -13 -15 -12 -22 -20 -25 -28 -32 -25 Tol.± 3 2 2 2 2 2 3 C KK Dimensions and weight exhaust valve KK Sound power levels by octave bands are obtained by adding to total sound pressure level Lp10A, dB(A) the corrections Koct presented in the table according to the following formula: ØB ØA LWoct = Lp10A + Koct Correction Koct is average value in range of use of KK unit. Sound attenuation ΔL Sound attenuation ΔL (dB) KK Slot s(mm) Octave bands, middle frequency, Hz 63 125 250 500 1000 2000 4000 8000 80 -9 0 12 24 24 24 20 19 19 14 13 13 10 9 9 8 6 5 5 3 2 5 4 3 6 5 4 100 -10 0 10 23 23 23 19 16 16 14 11 11 12 8 7 11 7 5 10 6 4 13 9 7 14 8 8 125 -17 0 9 20 18 19 19 16 16 13 10 9 10 6 6 7 4 3 7 4 3 11 5 5 14 8 7 150 -15 0 10 21 20 16 14 13 14 11 9 9 8 6 4 6 4 3 6 4 2 8 7 7 8 6 7 160 -15 -10 0 18 18 17 13 13 13 11 10 9 7 6 5 6 5 4 6 5 3 8 7 6 8 7 6 200 -15 -5 0 17 17 17 12 11 11 8 7 7 7 6 5 6 5 5 7 6 6 8 6 6 9 8 7 6 3 2 2 2 2 2 3 Tol.± KE A B C Weight,g 80 100 125 150 160 200 116 140 170 202 202 254 60 75 99 119 119 157 40 40 46 54 54 64 150 160 230 340 340 510 Dimensions and weight mounting rings ØD1 Ød 30 KKK ØD2 Ød The average sound attenuation ΔL from duct to room including the end reflection of the connecting duct in ceiling installation, is obtained in the table above. Ød 50 50 KKL KKT Definitions qv Δpt Lp10A LWoct ΔL Koct air volume total pressure drop sound pressure level with 4 dB room attenuation (10 m2 sab) sound power level by octave bands sound attenuation correction Fläkt Woods l/s Pa dB(A) ØD2 Size Ød ØD1 ØD2 Weight, g KKK Weight, g KKT/KKL 80 100 125 150 160 200 79 99 124 149 159 199 127 155 176 186 230 105 125 150 175 185 225 50 65 80 90 130 80 100 120 180 190 240 dB dB dB FIFLO 4480 EN 2006.09 3 Specifications are subject of alteration without further notice. Exhaust valve KK TECHNICAL DATA - 2006 page 308 Construction, installation, product code Construction Descriptive text The KK is manufactured from steel sheet painted white. Other paint finishes are available to special order. Stainless steel version KK-C also available. Valve body has a gasket made of cellular plastic and the control disc with screw spindle enables easy regulation and positional locking. Mounting rings KKK, KKT and KKL are manufactured from galvanized steel sheet. KKT is equipped with rubber sealing gasket. KKR is manufactured from stainless steel. Exhaust valve KK, e.g. KK-125 manufactured by Fläkt Woods. Product code Exhaust valve KK-aaa Size 080, 100, 125, 150, 160, 200 Exhaust valve, stainless steel Installation KK-C-aaa Size 100, 125, 160 Mounting ring KKK, KKT , KKL or KKR is fitted into the duct with screws or rivets. The valve is fixed by “a screwing action” to locate the valve lugs into indents in the mounting ring. Regulation and measurement of air flow Mounting ring without rubber seal Regulation of air flow is achieved by turning the control disc to change adjustment dimension s (mm). The measurement of air flow is made by a pressure difference measurement with a separate measuring tube. Refer to air flow measurement diagrams found in the separate installation and measurement instructions for information. Size 080 (only KKL), 100, 125, 150, 160, 200 Mounting ring with rubber seal KKK/KKL-aaa KKT-aaa Size 080, 100, 125, 150, 160, 200 Mounting ring, stainless steel KKR-aaa Size 100, 125, 160 Fläkt Woods FIFLO 4480 EN 2006.09 4 Specifications are subject of alteration without further notice.