Stabilization of a Fixed Speed Wind Turbine with a Variable Speed Wind Turbine Kenneth E. Okedu University of Port Harcourt Nigeria E-mail : kenokedu@yahoo.com amount of wind power after a fault in the network. Nowadays, the most widely used Variable Speed Wind Turbine (VSWT) in wind farms is based on a Doubly Fed Induction Generator (DFIG) due to noticeable advantages; the variable speed generation, the decoupled control of active and reactive powers, the reduction of mechanical stresses and acoustic noise, and the improvement of the power quality [6]. During grid faults the DFIG experiences over currents which lead to increasing DC voltage on the converter side. To avoid damage some special measures are necessary which however should not contravene grid requirement. Therefore, understanding between power engineers and developers of wind turbine converters is one of the pre-requisites for mutually acceptable technical solutions [5]. The crowbar can be used for fast separation of the DFIG from the grid [5],[7],[8], and [9], but is not a favorable option since utilities expect voltage support during the fault and in its aftermath, besides the active power in-feed should not be interrupted for a long period of time[5]. FSWT technology has limited ability to provide voltage and frequency control. Therefore, it is paramount to use a VSWT like the DFIG to stabilize a FSWT (IG) in a wind farm, because the reactive power control can be implemented at a lower cost, since the DFIG system basically operates in a similar manner to that of a synchronous generator, as the excitation is provided by the converter. This paper deals with the stabilization of an Induction Generator (IG) which is a Fixed Speed Wind Turbine (FSWT) that is unstable during grid fault with a Doubly Fed Induction Generation (DFIG) which is a Variable Speed Wind Turbine (VSWT) that is more stable during wind change and grid fault. A simulation model of a wind turbine with a DFIG and an IG developed in PSCAD/EMTDC (Power ABSTRACT This paper tackles the instability of a wind farm made of a Fixed Speed Wind Turbine (FSWT)/an Induction Generator (IG) and a Variable Speed Wind Turbine (VSWT)/Doubly Fed Induction Generator (DFIG) during wind change and grid fault. Simulation results show that the VSWT can effectively stabilize itself and the FSWT because it can provide enough reactive power through the frequency converter control to the wind farm without external reactive power compensation unit during wind speed change and grid fault. INDEX TERMS Grid Fault, Stability, Wind Farm, Wind Turbine. I.INTRODUCTION Wind energy is the fastest growing and most widely utilized of the emerging renewable technologies in electrical systems [1]. Based on the recent growth of wind power capacity, the power system must be able to recover after the loss of a great number of wind farms during a fault due to disconnection. This recovery may be particularly difficult in periods of low load and high wind power penetration. This led to system operators publishing several requirements (grid codes) for the connection of new wind farms, in order to ensure the proper behavior of wind farms after network fault. Wind farms may be required to remain connected and to maintain stability at short-circuits in the network cleared by the primary network protection, as stated by the Danish Operator Eltra or the German Operator E.ON [2]. Recently, the grid codes require to take into account the reactive power of the wind farm in order to contribute to the network stability [3],[4], thus operating the wind farm as active compensator devices [5]. By means of these grid codes, the operator ensures that the power system will not lose a great 25 Systems Computer Aided Design/Electromagnetic Transient Including DC) [10] is presented. The simulation results show the effectiveness of using a VSWT in stabilizing the voltage, rotor speed, active and reactive powers of the FSWT and hence the terminal voltage of the wind farm. power coefficient which can be expressed as a function of the tip speed ratio and pitch angle given by λi II. WIND AND WIND TURBINE MODEL The wind effect is very important in modeling wind turbines. Wind models describe wind fluctuations in wind speed which causes power fluctuation in a generator. Four components are considered in describing a wind model [11] as shown below: Vwind = Vbw + Vgw + Vrm + Vnm ρπ R 3C p (λ , θ )Vwind 2 Pw = ωrotor 2λ = Tw Pw = λ= ρπ R 2 C p (λ , θ )Vwind 3 2 λi (5) 1 (6) 1 0.035 − 3 ) ( λ + 0.08θ θ + 1 Figures 1 and 2 show the wind turbine characteristics [12] used for this study for both FSWT and VSWT respectively. Figure 1. Cp -λ curves for different pitch angles for FSWT (2) Figure 2. Turbine characteristic with maximum power point tracking for VSWT (3) Figures 3 and 4 respectively show the pitch angle controllers for both the FSWT and VSWT used. Rω rotor (4) Vwind Where ρ is the air density in (kg / m3), R is the wind turbine rotor radius in (m), Vwind is the equivalent wind speed in (m / s), θ is the pitch angle of the rotor in (deg.), λ is the tip speed ratio ωrotor,is the mechanical speed of the generator in (rad/s) and Cp is the 26 λi = −12.5 (1) Where, Vbw, Vgw, Vrm, Vnm are the Base wind, Gust wind, Ramp wind and Noise wind components respectively in (m/s). The base component is a constant speed; the wind gust component could be described as a sine or cosine wave function or combination; a simple ramp function and a triangular wave may describe the ramp and the noise components respectively. The wind speed in this study is shown in the simulation results for the dynamic analysis of the system during wind speed change, while a fixed speed was used for the transient analysis, because it is assumed that wind speed does not change dramatically during the short time interval of the simulation. For electrical analysis, a simplified aerodynamic model of a wind turbine is normally recommended as described by the set of equations below where the aerodynamic torque (Nm) extracted from the wind is given by [9],[11]: 116 C p (λ ,= θ ) 0.22( − 0.4θ − 5)e Figure 3. Pitch angle controller for FSWT j o u r n a l o f a p p l i e d s c i e n c e & e n g i n e e r i n g t e c h n o l o g y 2011 Figure 4. Pitch angle controller for VSWT In Figure 1, beta (β) represents the pitch angles of the fixed speed wind turbine at various tip speed ratio. In Figure 2, Pmax represents the maximum power that can be tracked by the variable speed wind turbine, while Pref shows the maximum power point tracking (MPPT) control for the reference active power of the turbine. The red line indicates the range of operation of the rotor speed for the variable speed wind turbine whose limit is chosen between 0.7-1.3pu for the lowest and highest wind speed to be encountered. The rated wind speed of the turbine is 12.43m/s. In Figure 3, the proportionate integral (PI) controls the difference between reference and the active power of the FSWT with a gain Kp and time constant Ti of 100 and 0.001sec respectively, while G and T are the gain and time constant for the control system. The rate of servo-mechanism which affects the mechanical operation of the control is 10(deg. /sec). The output (β2) is the pitch controller that controls the active power when the wind speed is above or below the rated value. The pitch controller for the VSWT works in a quite different way. The controller does not activates until the rotor speed ωr of the turbine exceeds 1.3pu, which is the maximum allowable rotor speed as shown in Figures 2 and 4 respectively. The PI then controls the difference between the reference and the rotor speed of the turbine. The gain and time constant of the PI controller are Kp and Ti. The output which is (β1) is the pitch controller that controls the range of operation of the rotor speed of the VSWT between 0.7pu and 1.3pu at low and high wind speed. Table I gives the parameters of the FSWT and the VSWT [13]. Rated Power Rated Voltage Stator Resistance Stator Leakage Reactance Magnetizing Reactance Rotor Resistance Rotor leakage Reactance Inertia Constant 30MVA(IG) 690V 0.01pu 20MVA(DFIG) 690V 0.01pu 0.07pu 0.15pu 4.1pu 3.5pu 0.007pu 0.01pu 0.07pu 0.15pu 1.5secs 1.5secs Table I: Parameters of FSWT and VSWT From Table 1, the rated power of the FSWT and VSWT used for this study are 30MVA and 20MVA respectively, with a rated voltage each of 690V. The values of the stator resistance, leakage reactance, magnetizing reactance, rotor resistance and the rotor leakage reactance affects the operation of the turbines. These values are based on the designer available data. The inertia constants value affects primarily the rotor speed of the wind turbines. III. MODEL SYSTEM Figure 5. Model system for VSWT and FSWT Figure 5 displays the model system for this study, where the FSWT is connected to the VSWT, then via the transmission lines to an infinite bus. A capacitor bank (QC) is connected to the FSWT for reactive power compensation during the steady state of operation. The frequency converters connections for the VSWT are also shown. The FSWT has no control system for active and reactive power, unlike the VSWT which has two control systems; the Rotor Side Converter (RSC) and the Grid Side Converter (GSC) for active and reactive power control as discussed in the next section. IV. CONTROL SYSTEM FOR THE VSWT The Rotor side converter (RSC) and the Grid side converter (GSC) control blocks for the DFIG are shown in Figures 6 and 7 respectively. In Figure 6, the rotor side converter controls the terminal (grid) voltage Vg to 1.01pu at normal working condition. The daxis current (Idr) controls the active power, while the q-axis current (Iqr) controls the reactive power. Both currents are gotten from an abc-to-dqo transformation of the sources voltages Va, Vb, and Vc through a transformation angle θr gotten from the difference between the angular frequency of the rotor position 2π f and the angle θPLL of the phase locked loop. There are two–stage proportionate integral (PI) con- Stabilization of a Fixed Speed Wind Turbine with a Variable Speed Wind Turbine27 trols with a phase compensator with gain value of G = 0.01, having a leading and lagging time constants of 0.05sec and 0.0009sec respectively, connected in between the two PI controllers. The gain and time constants of the PI controllers are Kp and Ti with their values given in the control block diagram of Figure 6. PDFIG and QDFIG are the active and reactive powers of the DFIG which are been controlled, while Pref is the optimum reference value (MPPT) of the DFIG system. After dq0-to-abc transformation, Vdr * and Vqr * which are the output of the control system are sent to the PWM (Pulse Width Modulation) signal generator and Vabc * are the three-phase voltages desired at the rotor side converter output for switching of the insulated gate bipolar transistors (IGBTs). Also, Figure 7 shows the control block for the GSC control, where PLL provides the angle θPLL and θs is the effective angle for the abc-to-dq0 (and dq0-to-abc) transformation. The direct axis component is used to regulate the DC-link voltage (Edc ) to 1.0pu. The d-axis current (Id) controls the DC-link voltage, while the q-axis current (Iq) controls the reactive power of the grid side converter. The Id and Iq currents are derived from the Va, Vb and Vc transformation through the angle θ s as shown in the block diagram. Edc, Edc*, Qgsc, and Q*ref represents the DClink voltages and the reactive powers of the actual and reference values of the DFIG variables that are been controlled by the GSC. A phase compensator with gain value of G = 0.06, and having a leading and lagging time constants of 0.03sec and 0.002sec respectively, are connected between the two PI controllers. The gain and time constants of the PI controllers are Kp and Ti respectively as shown in the block diagram. After a dq0-to-abc transformation, Vq* and Vd* which are the output variables of the GSC controller are sent to the PWM signal generator. Finally Vabc* are three voltages at the GSC output for the IGBT`s switching. V. SIMULATION RESULTS Simulations were run in PSCAD/EMTDC for 100s with different wind speed for the FSWT and the VSWT for dynamic analysis and simulations for transient analysis was run for 20s, where the wind speed was assumed to be fixed and at rated condition, with a three phase fault 28 Figure 6. Control block for the rotor side converter Figure 7. Control block for the grid side converter applied at 10.1s and the circuit breakers on the faulted lines opened and reclosed at 10.2s and 11.0s respectively. The results are shown in the Figures 8 to 21. 1) Dynamic Analysis Figure 8. Wind speed for VSWT and FSWT j o u r n a l o f a p p l i e d s c i e n c e & e n g i n e e r i n g t e c h n o l o g y 2011 Figure 9. Active and reactive power of VSWT Figure 13. DC-link capacitor voltage of VSWT Figure 10. Active power of FSWT Figure 14. Terminal voltage of FSWT 2) Transient Analysis Figure 11. Pitch angle of FSWT Figure 15. Active power of VSWT Figure 12. Rotor speed of VSWT Figure 16. Active power of FSWT Stabilization of a Fixed Speed Wind Turbine with a Variable Speed Wind Turbine29 Figure 17. DC-link capacitor voltage of VSWT Figure 18. Rotor speed of FSWT Figure 19. Rotor speed of VSWT Figure 20. Reactive power of grid side inverter of VSWT 30 Figure 21. Terminal voltage of FSWT (IG) VI. SIMULATIONS DISCUSSION From the simulation results where a variable speed is used for both the FSWT and the VSWT in Figure 8, it can be seen that both the active and reactive powers of the VSWT changes as the wind speed changes as shown in Figure 9. Despite the high value of the wind speed above the rated wind speed value of 12.43m/s as shown in the turbine characteristics (Figure 2), the active power of the VSWT does not exceed the rated per-unit value of 1.0pu, while reactive power is been absorbed (negative value) or supplied (positive value) to the system, depending on the nature of the wind speed, due to the independent controllability of the active and reactive powers of the DFIG VSWT system by the RSC control system. The active power of the FSWT is also controlled to a limit of 1.0pu in Figure 10 by the pitch angle controller whose response is shown in Figure 11. It could be observed that the pitch angle controller for the FSWT does not work until the active power of the FSWT exceeds its rated value of 1.0pu due to high wind speed above the rated wind speed of 12.43m/s, for the FSWT after 80sec. The rotor speed response for the VSWT is shown in Figure 12, where at 20sec and at 70sec, when the wind speed of the VSWT exceeds the rated wind speed of 12.43m/s, the pitch angle control system tries to limit the rotor speed of the wind turbine to a limit of 1.3pu. The rotor speed varies as the wind speed varies, while the GSC control maintains the DC-link voltage constant at 1.0pu as shown in Figure 13. In Figure 14, the terminal voltage of the FSWT is maintained constant when the VSWT is connected to it despite the changes in the wind speed. When the VSWT was not connected, it is seen that the terminal voltage of the FSWT varies with the wind speed. j o u r n a l o f a p p l i e d s c i e n c e & e n g i n e e r i n g t e c h n o l o g y 2011 Figure 15 and 17 shows the active power of the VSWT and the DC-link voltage for transient analysis. It is seen that the VSWT was able to assume the initial steady state after the three phase fault, thus stabilizing itself. In Figure 16 and 18, the active power and the rotor speed of the FSWT was not able to maintain its steady state after the three phase fault, but when it was connected to the VSWT, the initial steady states were achieved after the three phase fault. The rotor speed of the VSWT and the reactive power of the GSC are shown in Figures 19 and 20 respectively. It could be observed that reactive power was supplied to the system during grid fault through the grid-side inverter control of the VSWT as shown in Figure 20. Figure 21 shows the terminal voltage of the FSWT (IG) with and without the VSWT connected. A better performance of assuming the initial steady state of the FSWT terminal voltage after the three phase fault was achieved when the VSWT is connected to the FSWT. VII.CONCLUSION A simple wind farm composed of a Variable Speed Wind Turbine (VSWT) and a Fixed Speed Wind Turbine (FSWT) connected to an infinite bus has been studied and simulated in PSCAD/EMTDC environment. Stability analyses were carried out when the VSWT is connected and not connected to the FSWT. The VSWT can be used to stabilize the FSWT and hence the wind farm during wind speed change and grid fault as shown in the simulation results, because it can provide enough reactive power to the wind farm system through its frequency converter control without using external reactive power compensation. The results help to understand the transient stability phenomena in fixed speed wind farms, and could help to design fixed speed wind farms attending to transient stability requirements, by including some variable speed wind turbines. REFERENCES [1] [2] [3] [4] T. Ackermann, Wind Power in Power Systems, John Wiley and Sons, Ltd., 2005. P. Ledesma, J. Usaola, and J. L. Rodriguez, “Transient stability of a fixed speed wind farm,” Renewable Energy, vol.28, pp. 13411355, 2003. E.ON NETZ GmbH, Grid Connection Regulation for High and Extra High Voltage, 2006. R. D. Fernanadez, R. J. Mantz, and P. E. Battaiotto, “Potential contribution of wind farms [5] [6] [7] [8] [9] [10] [11] [12] [13] to damp oscillations in weak grids with high wind penetration,” Renewable and Sustainable Energy Reviews, vol. 12, pp. 1692-1711, 2008. I. Erlich, H. Wrede, and C. Feltes, “Dynamic behavior of DFIG-Based wind turbines during grid faults,” IEEJ Trans on Power and Energy, vol. 128, no. 4, pp. 396-401, 2008. L. M. Fernandez, C. A Garcia, and F. Jurado, “Comparative study on the performance of control systems for doubly fed induction generator (DFIG) wind turbines operating with power regulation,” Energy Journal, vol. 33, pp. 1438-1452, 2008. A. D. Hasan, and G. Michalke, “Fault ridethrough capability of DFIG wind turbines,” Renewable Energy, vol. 32, pp. 1594-1610, 2007. B. H. Chowdhury, and S. Chellapilia, “Doublyfed induction generator control for variable speed wind power generation,” Electric Power System Research, vol. 76, pp. 786-800, 2006. T. Sun, Z. Chen, and F. Blaabjerg, “Transient stability of DFIG wind turbines at an external short circuit fault,” Wind Energy Journal, vol. 8, pp. 345-360, 2005. PSCAD/EMTDC Manual, Manitoba HVDC Research Center, 1994. H. Karim-Davijani, A. Sheikjoleslami, H. Livani, and M. Karimi-Davijani, “Fuzzy logic control of doubly fed induction generator wind turbine,” World Applied Science Journal, vol. 6, no. 4, pp. 499-508, 2009. O. Wasynczuk, D. T. Man, and J. P. Sullivan, “Dynamic behavior of a class of wind turbine generator during random wind fluctuations,” IEEE Transactions on Power Apparatus and Systems, vol. PAS-100, no.6, pp. 2837-2845, 1981. R. Takahashi, J. Tamura, M. Futami, M. Kimura and K. Ide, “A new control method for wind energy conversion system using double fed synchronous generator,” lEEJ Transactions o Power and Energy, vol. 126, no.2, pp. 225-235, 2006. Kenneth E. Okedu obtained his Ph.D. in the department of Electrical and Electronic Engineering, Kitami University of Technology, Hokkaido, Japan in 2011. He received his B.Sc. and M. Eng. degrees in Electrical and Electronic Engineering from the University of Port Harcourt, Nigeria in 2003 and 2006 respectively. His research interests include renew- Stabilization of a Fixed Speed Wind Turbine with a Variable Speed Wind Turbine31 able energy, stabilization of wind farm with doubly fed induction generator variable speed wind turbine, augmentation of renewable energy to power system and power system stability analysis. 32 j o u r n a l o f a p p l i e d s c i e n c e & e n g i n e e r i n g t e c h n o l o g y 2011