OEM Load Center Parts Program

advertisement
g
GE Industrial Systems
OEM Load Center Parts Program
1
GE OEM Load Center Parts Program
OEM Load Center Manual
A Manual that Helps You Find Solutions
The “Contractor’s Load Center”
GE Industrial Systems is pleased to offer a
comprehensive line of PowerMark GoldTM and
PowerMark PlusTM load center interiors and
components for Original Equipment Manufacturers
(OEM’s). This offering has been assembled to provide
OEM’s with unprecedented flexibility to meet their
customers needs.
In developing the PowerMark Gold load center, GE
consulted with practicing electrical contractors. We
incorporated many features suggested to us by
contractors, features that make PowerMark Gold the
finest quality, easiest-to-use residential load centers.
All PowerMark Gold load centers incorporate a tinplated, solid copper bus for maximum conductivity
and corrosion resistance. All load centers feature
robust neutral bars that extend the full length of the
bus for faster, more professional installations; plus,
the neutral bars are raised, making them more
accessible to speed installation. All enclosures are
commercial-quality, heavy-gage steel with a
protective galvanized finish for superior corrosion
resistance. In addition, Robertson-style square-drive
screws allow higher installation torque and prevent
screwdriver slippage.
GE’s OEM Load Center manual is designed to help
you select and identify GE load center components
quickly and accurately. Based on your amperage
needs and the number of circuits required, this
manual identifies the part numbers for the interior
and all component parts. Envelope drawings are
provided for each interior to assist you in adapting
the GE interior to your own custom installation.
This manual features:
• Selection Guide for Residential Main Lug/
Convertible, Main Breaker and Commercial Load
Centers
Money-Saving THQP Circuit Breakers
All PowerMark Gold load centers accommodate GE’s
reliable THQL one-inch-wide circuit breaker.
PowerMark Gold load centers also accommodate
GE’s unique space-saving one-half-inch THQP circuit
breaker. THQP circuit breakers help save you money
by providing installation flexibility. THQP circuit
breakers are identical in design to THQL circuit
breakers and they are tested to the same UL
specifications. THQP circuit breakers are most
beneficial when size and cost constraints are driving
factors, helping you to be more cost competitive.
They help free up space to allow new circuits to be
added to a crowded load center and thus may
prevent the need to upgrade to a larger load center.
THQP circuit breakers are available in one- and twopole designs up to 50 amps.
• Circuit Breaker Selection Guide
• Accessory Selection Guide
• Part Number Identification for All Load Center
Components
• Dimensioned Envelope Drawings
Dedication to Quality
GE load centers are designed, manufactured, sold,
and serviced with a dedication to quality unequalled
in the electrical components industry. All GE
products are produced in accordance with the
company’s Six Sigma Quality Initiative. Six Sigma is
the disciplined methodology of defining, measuring,
analyzing, improving, and controlling the quality in
all GE products, processes, and transactions—with
the ultimate goal of virtually eliminating all defects.
The Six Sigma initiative has changed the culture of
GE and impacts everything we do and every product
we design.
US National Electrical Code Paragraph 384-15
requires branch-circuit load centers to be provided
with a physical means to prevent the installation of
more circuit breakers than the number for which the
load center was designed, rated, and approved. GE
load centers are designed to limit installation to no
more than 42 total circuits per load center and thus
the number of allowable THQP circuit breaker spaces
may be limited. For information on which load
centers accept THQP circuit breakers, reference the
right-side view of each load center’s envelope
drawing. In addition, each load center page also
provides a chart that indicates the maximum number
of breakers per load center.
GE’s Six Sigma Quality Initiative is reinforced with a
solid warranty program on each GE load center. All
PowerMark Gold™ load centers are backed by a
lifetime warranty. GE warrants that GE PowerMark
Gold residential load centers will be free from defects
in materials and workmanship, under normal care
and proper installation, for the lifetime of the
product.
2
GE OEM Load Center Parts Program
Contents
PowerMark Plus™ & PowerMark Gold™ Load Center Selection Guide .................................................. 4
Q Line Circuit Breakers............................................................................................................................... 7
Load Center Accessories.......................................................................................................................... 11
PowerMark Gold™ Load Center Parts..................................................................................................... 14
PowerMark Plus™ Load Center Parts...................................................................................................... 38
PowerMark Gold™ OEM Specialty Load Center Parts ........................................................................... 82
Note: Text printed in blue on this and the following three pages is linked to the corresponding page in the
manual. As you move the Acrobat hand pointer over the text, it will change to a finger pointer. Click the
mouse button to jump to that page.
3
GE OEM Load Center Parts Program
PowerMark Plus™ & PowerMark Gold™ Load Center Selection Guide
• UL Recognized Component
• 60°/75° C Conductor Rating
• Suitable for Use as Service Entrance Equipment When Installed in Accordance with the National
Electrical Code
• 22 kAIC RMS Symmetrical, Except Where Noted
Single-Phase, Three-Wire, 120/240 Vac
OEM Interiors used in PowerMark Gold Load Centers
• Main Lug and Convertible Load Center Interiors
– Factory-Installed Main Lugs (TLM units convertible to main breaker)
– Copper Bus – Tin-Plated Standard (all OEM interiors with suffix U2)
– OEM interiors are UL-recognized components listed under UL file E21790
Maximum Spaces
Main
Ampere
Rating
70
100
125
150
200
225
1/2"
1" THQL
1p
2p
2
1
2
1
4
2
6
3
8
4
1p
4
—
8
12
16
THQP
2p
1
—
3
4
6
12
6
24
16
8
24
Total
1-Pole
Spaces
OEM Interior
with
Neutral Bar
Cat. No.
OEM Interior
without
Neutral Bar
4
2
8
12
16
TL270U2
—
TL412U
TLM612U2
TLM812U2
10
24
TLM1212U2
—
16
6
24
TLM1612U2
—
12
—
—
24
24
12
12
4
30
TLM2415U2
—
16
8
32
14
32
TLM1620U2
—
20
10
40
18
40
TLM2020U2
32
16
16
6
40
TLM3220U2
—
40
20
—
—
40
TLM4020U2
—
42
20
—
—
42
TLM4222U2
—
TLM2412U2
—
565B837G2
TL412UN
TLM612U2N
TLM812U2N
—
—
Complete Load
Center with
Indoor Enclosure
TL270SCU
—
TPL412C
TLM612SCU
TLM812SCU
TLM1212CCU
TM1210CCU
TM1212CCU
TLM1612CCU
TM1612CCU
TLM2412CCU
TM2412CCU
TLM2415CCU
TM2415CCU
TLM1620CCU
TM1615CCU
TM1620CCU
TLM2020CCU
TM2020CCU
TLM3220CCU
TM3220CCU
TLM4020CCU
TM4020CCU
TLM4222CCU
TM4222CCU
Drawing
Page #
—
—
—
14
17
20
22
24
26
28
30
32
34
36
For Main Breaker, order mounting kit TQMH000. Also order THQL, THHQL, or TXQL circuit breaker separately.
For Main Breaker, order THQMV main breaker (includes mounting base).
For Main Breaker, order THQLRK2 retainer kit plus THQL, THHQL, or TXQL circuit breaker separately.
4
GE OEM Load Center Parts Program
PowerMark Plus™ & PowerMark Gold™ Load Center Selection Guide
Three-Phase, Four-Wire, 208Y/120 Vac
OEM Interiors used in PowerMark Plus Load Centers
• Factory-Installed Main Lug Load Center Interiors
– OEM interiors are UL-recognized components listed under UL file E21790
Maximum Spaces
Main
Ampere
Rating
100
125
150
200
225
1-pole
3
12
18
24
18
30
42
30
42
1" THQL
2-pole
1
6
8
12
8
14
20
14
20
3-pole
1
4
6
8
6
10
14
10
14
Total
1-Pole
Spaces
3
12
18
24
18
30
42
30
42
Cat. No.
Complete-Load
Center,Indoor Drawing
Page-#
Enclosure
OEM-Interior
565B837G1
TL12412U
TL14815U
TL24415U
TL18420U
TL30420U
TL42420U
TL30422U
TL42422U
—
TL12412C
TL18415C
TL24415C
TL18420C
TL30420C
TL42420C
TL30422C
TL42422C
—
38
40
42
44
46
48
50
52
• Main Breaker–Style Load Centers
– Main Lugs Not Included
– OEM interiors are UL-recognized components listed under UL file E21790
Maximum-Spaces
Main
Ampere
Rating
100
125
150
200
225
1-pole
12
18
30
24
30
42
24
30
42
42
1"-THQL
2-pole
6
8
14
12
14
20
12
14
20
20
3-pole
4
6
10
8
10
14
8
10
14
14
Total
1-Pole
Spaces
12
18
30
24
30
42
24
30
42
42
Cat.-No.
Complete-Load
Center,-Indoor Drawing
Page-#
Enclosure
OEM-Interior
TM12410U
TM18410U
TM30412U
TM24415U
TM30415U
TM42415U
TM24420U
TM3042OU
TM42420U
TM42422U
TM12410C
TM18410C
TM30412C
TM24415C
TM30415C
TM42415C
TM24420C
TM30420C
TM42420C
TM42422C
Also UL Listed for 3-phase, 4-wire 240/120 Vac delta and 3-phase, 3-wire 240 Vac branch
breakers installed.
Three-pole plug-in breakers available through 100 amperes.
Main Breaker, THHQL32100 included.
For Main Breaker, order TQD*X2 or THQD*X2 style breaker with appropriate mounting
bracket (see drawings).
5
54
56
58
61
64
67
70
73
76
79
GE OEM Load Center Parts Program
PowerMark Plus™ & PowerMark Gold™ Load Center Selection Guide
Single-Phase, Three-Wire, 120/240 Vac
Specialty OEM interiors used by GE in PowerMark Gold Meter Socket Load Centers
• All Specialty interiors are constructed without the neutral bar attached to the
assembly. They are packaged with or without a separately mounted neutral bar.
• OEM interiors are UL-recognized components listed under UL file E21790
Types
•
•
•
•
•
•
Narrow Style – Breaker mounting rail on one side only (Column style).
Wide Style – Breaker mounting rail on two sides.
Split Bus – Two sections of bus. Used with multiple service disconnects.
Feed-Thru – Feed-Thru lugs factory installed.
Main Lug – Factory-installed main lugs (MLO).
Main Breaker – Main breaker provisions, breaker sold separately.
Maximum-Spaces
Main
Total
1/2"-THQP
1"-THQL
Ampere
1-Pole
1p
2p
1p
2p
Spaces
Rating
Split-Bus-/-Feed- Thru-/-Narrow-Style-(Farm-Panel)
200
4
2
8
3
8
Narrow-Style-/-MLO
200
4
2
8
3
8
Feed-Thru-/-Narrow-Style
200
8
4
16
6
16
Narrow-Style
12
6
24
10
24
125
16
8
32
14
32
200
20
10
40
18
40
Wide-Style-/-Main-Breaker
125
12
6
24
10
24
200
20
10
40
18
40
Cat.-No.
OEM-Interior-with
Neutral-Bar
OEM-Interior
without-Neutral
Bar
TSF420U
TSF420UN
TSLR420U
TSLR420UN
TSM820U
TSM820UN
Main Breaker
87
TSM1212U
TSM1610U
TSM2020U
TSM1212UN
TSM1610UN
TSM2020UN
Main Breaker
Main Breaker
Main Breaker
84
85
86
TSMR1212U
TSMR2015U
TSMR1212UN
TSMR2015UN
Main Breaker
Main Breaker
88
89
For subfeed main breaker, order THQL, THHQL, or TXQL, 110 A max.
for main breaker, order THQMV*WL breaker with main breaker retainer THQLRK1.
For main breaker, order THQL, THHQL, or TXQL with mounting kit TQMH000.
For main breaker, order THQMV main breaker (includes mounting base).
Reverse-fed main breaker retainer is not available; customer supplied.
6
Main-Type
Main Breaker
MLO
Drawing
Page-#
82
83
GE OEM Load Center Parts Program
Q Line Circuit Breakers
Standard Circuit Breakers
Breaker-Type
• UL Listed (Molded-Case Circuit Breakers No. 489)
THQP
• Federal Government Specification Qualified (WC-375B)
• 60°/75° C Conductor Rating
THQL
THHQL
TXQL
• Quick-Make, Quick-Break
• Box-Type Terminals
TQDL
THQDL
10,000-AIC
Ampere
Rating
Type-THQP- 1/2"
Module
120/240- Vac
Cat.-No.
125–200
1/0–250
22,000-AIC
Type-THQL-1"-Module
240- Vac
120/240- Vac
Cat.-No.
Cat.-No.
Single-Pole
15
THQP115
THQL1115
20
THQP120
THQL1120
25
THQP125
THQL1125
30
THQP130
THQL1130
35
THQP135
THQL1135
40
THQP140
THQL1140
45
THQP145
THQL1145
50
THQP150
THQL1150
Std. Pkg.
5 cartons of 20
5 cartons of 10
Two-Pole :-Incorporates-Internal-Common-Trip-Bar
15
THQP215
THQL2115
20
THQP220
THQL2120
25
THQP225
THQL2125
30
THQP230
THQL2130
35
THQP235
THQL2135
40
THQP240
THQL2140
45
THQP245
THQL2145
50
THQP250
THQL2150
60
—
THQL2160
70
—
THQL2170
80
—
THQL2180
90
—
THQL2190
100
—
THQL21100
110
—
THQL21110
125
—
THQL21125
Std. Pkg.
5 cartons of 10
5 cartons of 5
125
—
TQDL21125
150
—
TQDL21150
175
—
TQDL21175
200
—
TQDL21200
Std. Pkg.
—
10 cartons of 1
Three-Pole :-Incorporates-Internal-Common-Trip-Bar
15
—
—
20
—
—
25
—
—
30
—
—
35
—
—
40
—
—
45
—
—
50
—
—
60
—
—
70
—
—
80
—
—
90
—
100
—
—
Std. Pkg.
—
—
Wire-Size-AWG/ kcmil
Cu
Al
14–8
12–8
8–4
8–2
14–8
12–8
8–3
8–2
6–1/0
4–1/0
2–2/0
2–2/0
Ampere-Rating
15–25
30–50
15–30
35–60
70–100
110–125
1/0–250
65,000-AIC
Type-TXQL-1"-Module
Type-THHQL-1"-Module
240- Vac
120/240- Vac
Cat.-No.
Cat.-No.
120/240- Vac
Cat.-No.
—
—
—
—
—
—
—
—
—
THHQL1115
THHQL1120
THHQL1125
THHQL1130
THHQL1135
THHQL1140
THHQL1145
THHQL1150
5 cartons of 10
—
—
—
—
—
—
—
—
—
TXQL1115
TXQL1120
TXQL1125
TXQL1130
—
—
—
—
5 cartons of 10
THQL2215
THQL2220
THQL2225
THQL2230
THQL2235
THQL2240
THQL2245
THQL2250
THQL2260
THQL2270
THQL2280
THQL2290
THQL22100
—
—
5 cartons of 5
—
—
—
—
—
THHQL2115
THHQL2120
THHQL2125
THHQL2130
THHQL2135
THHQL2140
THHQL2145
THHQL2150
THHQL2160
THHQL2170
THHQL2180
THHQL2190
THHQL21100
THHQL21110
THHQL21125
5 cartons of 5
THQDL21125
THQDL21150
THQDL21175
THQDL21200
10 cartons of 1
THHQL2215
THHQL2220
THHQL2225
THHQL2230
THHQL2235
THHQL2240
THHQL2245
THHQL2250
THHQL2260
THHQL2270
THHQL2280
THHQL2290
THHQL22100
—
—
5 cartons of 5
—
—
—
—
—
TXQL2115
TXQL2120
TXQL2125
TXQL2130
—
—
—
—
—
—
—
—
—
—
—
5 cartons of 5
—
—
—
—
—
THQL32015
THQL32020
THQL32025
THQL32030
THQL32035
THQL32040
THQL32045
THQL32050
THQL32060
THQL32070
THQL32080
THQL32090
THQL32100
5 cartons of 3
—
—
—
—
—
—
—
—
—
—
—
—
—
—
THHQL32015
THHQL32020
THHQL32025
THHQL32030
THHQL32035
THHQL32040
THHQL32045
THHQL32050
THHQL32060
THHQL32070
THHQL32080
THHQL32090
THHQL32100
5 cartons of 3
TXQL32015
TXQL32020
TXQL32025
TXQL32030
UL Listed as HACR (heating, air conditioning, and refrigeration).
UL Listed as SWD (switching duty). Suitable for 120 volts ac fluorescent lighting loads.
15–100 A UL Listed as HACR (heating, air conditioning, and refrigeration.).
Requires four 1-inch spaces.
7
5 cartons of 3
GE OEM Load Center Parts Program
Q Line Circuit Breakers
Main Circuit Breaker Kits
• For use with PowerMark Gold OEM Interiors with TLM prefix.
• 60°/75° C Conductor Rating
• Quick-Make, Quick-Break
• Multipole Breakers Incorporate Internal Common Trip
• Box-Type Terminals
PowerMark Gold™ Main Circuit Breakers
PowerMark Plus™ Main Circuit Breakers
•
•
•
•
•
•
•
•
•
Two-pole, 120/240 Vac
For use with 150–225 A PowerMark Gold load centers
22 kAIC RMS symmetrical
Includes mounting base
For Specialty Load Center interiors with a main circuit breaker and
lugs, use catalog number THQMV__WL, with the appropriate main
breaker rating inserted in the space.
Main-Breaker
Rating,-A
100
125
150
175
200
225
Ampere
Rating
100
125
150
175
200
225
Cat.-No.
Top-Feed
Bottom-Feed
THQMV100 THQMV100B
THQMV125 THQMV125B
THQMV150 THQMV150B
THQMV175 THQMV175B
THQMV200 THQMV200B
THQMV225 THQMV225B
THQMV200
PowerMark Gold Main Circuit Breaker Kits
• Two-pole, 120/240 Vac or 240 Vac
• For use with 125 A PowerMark Gold load centers
Main-Breaker-Kit
TQMH000
Cat.-No.
Description
Order appropriate THQL (10
kAIC) or THHQL (22 kAIC)
breakers separately
TQMH000
with breaker
Main Breaker Retainers
For Main Lug Load Centers Using a Back-Fed Branch
Breaker as a Main
Load-Center
Breaker
Cat-No.
TL (225 A max)
THQL
TQDL
PowerMark Gold
THQL
THQLRK
TQDLRK
THQLRK1
THQLRK2
Three-pole, 240 Vac
For use with 125-225A PowerMark Plus Interiors
Line LUgs only included
Breaker Mounting Bracket indicated on Drawings
Std.
Pkg.
1
THQLRK1
For six- or eight-circuit load centers.
8
Catalog-Number
10- kAIC
TQD32100X2
TQD32125X2
TQD32150X2
TQD32175X2
TQD32200X2
TQD32225X2
22- kAIC
THQD32100X2
THQD32125X2
THQD32150X2
THQD32175X2
THQD32200X2
THQD32225X2
Wire
Range
#1–300 Cu
or 2/0–300 Al
GE OEM Load Center Parts Program
Q Line Circuit Breakers
Surge Arrester
CB3® Ground Fault
• UL Listed (1449)
• Meets ANSI/IEEE Standard C62.11-1987
• Protects all circuits connected to load centers in which it is installed
• UL Listed (Molded-Case Circuit Breakers No. 489 and Ground Fault
Circuit Interrupters No. 943)
• Class A (.005 Ampere ground fault trip level)
Response Time:
Clamping voltage;
Maximum surge current:
Reaction time:
Less than 1 nanosecond
500 V
27,000 A
1 microsecond
1-Pole
120- Vac
Ampere
Rating
Cat.-No.
15
THQL1115GF
20
THQL1120GF
10 kAIC
30
THQL1130GF
40
—
50
—
15
THHQL1115GF
22 kAIC
20
THHQL1120GF
30
THHQL1130GF
Std. Pkd. 10 cartons of 1
Cat.-No.
THQLSURGE
THQLSURGE
Arc Fault Circuit
Interrupters
• UL Listed (Molded-Case Circuit Breakers No. 489)
• UL Classified for mitigating the effects of arc faults
• 10 kAIC RMS symmetrical
Ampere
Rating
15
20
2-Pole
120/240- Vac
Cat.-No.
THQL2115GF1
THQL2120GF1
THQL2130GF1
THQL2140GF1
THQL2150GF1
—
—
—
10 cartons of 1
THQL1120GF
Switching Neutral
• UL Listed (Molded-Case Circuit Breakers No. 489)
• 10 kAIC RMS symmetrical
• Standard one- or two-pole automatic breaker plus one fully rated,
nonautomatic pole
1-Pole,-120/240- Vac
Cat.-No.
THQL1115AF
THQL1120AF
THQL1115AF
Rating,-A
15
20
25
30
Std. Pkg.
9
1-Pole-plus
Switching-Neutral
120/240- Vac
Cat.-No.
THQL21WY15
THQL21WY20
THQL21WY25
THQL21WY30
5 cartons of 5
2-Pole-plus
Switching-Neutral
120/240- Vac
Cat.-No.
THQL31WY15
THQL31WY20
THQL31WY25
THQL31WY30
5 cartons of 5
THQL21WY20
GE OEM Load Center Parts Program
Q Line Circuit Breakers
HID Lighting
Molded-Case Switches
• UL Listed (Molded-Case Circuit Breakers No. 489)
• HID breakers have been designed to handle the current and voltage
spikes that result when gaseous discharge lamps, including
fluorescent and HID lamps, are switched on and off.
• UL Listed (Molded-Case Switches No. 1087)
• Without overload or short-circuit protection
Vac
1-Pole
120/240- Vac
Ampere
Rating
Cat.-No.
15
THQL1115HID
10 kAIC
20
THQL1120HID
30
THQL1130HID
15
THHQL1115HID
22 kAIC
20
THHQL1120HID
30
THHQL1130GF
Std. Pkg.
5 cartons of 10
Rating,-A
60
120/240
100
60
240
100
Std. Pkg.
2-Pole
120/240- Vac
Cat.-No.
THQL2115HID
THQL2120HID
THQL2130HID
THHQL2115HID
THHQL2120HID
THHQL2130HID
5 cartons of 10
TQL21Y100
• 3/4-inch wide
• 10 kAIC RMS symmetrical
• UL Classified
• For use in Square D QO® load centers
Rating,-A
15
20
30
40
50
60
Std. Pkg.
THQL1120HID
High Magnetic
• UL Listed (Molded-Case Circuit Breakers No. 489)
• 10 kAIC RMS symmetrical
• High short-circuit setting suitable for circuits with inherent high inrush load currents
1-Pole
120- Vac
Cat.-No.
THQL1115HM
THQL1120HM
THQL1125HM
THQL1130HM
THQL1140HM
THQL1150HM
5 cartons of 10
3-Pole
Cat.-No.
—
—
TQL32Y60
TQL32Y100
5 cartons of 3
TQ Circuit Breakers
UL Listed as SWD (switching duty). Suitable for
120 Vac fluorescent lighting loads.
Ampere
Rating
15
20
25
30
40
50
Std. Pkg.
2-Pole
Cat.-No.
RQL21Y60
TQL21Y100
TQL22Y60
TQL22Y100
5 cartons of 5
THQL1140HM
10
1-Pole
Cat.-No.
TQ1115
TQ1120
TQ1130
TQ1140
TQ1150
—
1 carton of 10
2-Pole
Cat.-No.
TQ2115
TQ2120
TQ2130
TQ2140
TQ2150
TQ2160
1 carton of 5
TQ1120
GE OEM Load Center Parts Program
Load Center Accessories
Equipment Ground Kits
Neutral Kits
PowerMark Plus Equipment Ground Kits
PowerMark Plus Neutral Kits
Small-14–8
Cu,-12–8-Al
4
7
11
14
10
—
—
—
Number-of-Terminals
Large-14–4
Other-AWG/
Cu,-12–4-Al
kcmil-Cu/Al
3
—
—
—
3
—
—
—
2
(1) 14–2
—
(1) 6–2/0
—
(3) 10–1/0
—
(6) 10–1/0
Cat.-No.
TGL1
TGL3
TGL2
TGL4
TGL8
TGL20
TNG3
TNG6
Wire-Size-AWG/ kcmil-Cu/Al
(5) 14–1/0
(3) 1–300
(1) 6–2/0
(1) 1–300 Cu or 2/0–300 Al
Std.-Pkg.
Cat.-No.
TNLK1
TNLK2
286A8894G1
192A7663G13
Std.-Pkg.
1
Suitable only for 400 and 600 amp devices.
Add-on neutral lug kit for 100–200 amp load centers.
20
PowerMark Gold Neutral and Neutral Ground Kits
TGL1 and TGL3 mount interchangeably.
TGL2, TGL4, and TGL8 mount interchangeably.
Add-on equipment ground lug (for use on any TGL kit).
Suitable only for 400 and 600 amp devices.
Description
Neutral
Neutral
Neutral
Neutral/Ground
Neutral/Ground
1
Wire-Size,-Cu/Al
6–1
6–2/0
6–250
6–2/0
6–250
Cat.-No.
TNLK12
TNLK20
TNLK250
TLK20
TLK250
Std.-Pkg.
1
PowerMark Gold and Three-Phase PowerMark Plus Equipment
Ground and Isolated Ground Bus Bar
Description-(4–14-Cu/10–12-Al-Wire
Ranges
per-Hole,-Solid-or-Stranded)
12-hole Ground
24-Hole Ground
32-Hole Ground
42-Hole Ground
Isolated Ground Bus Bar Kit
(Order with TGK Equipment Ground
Kits)
Cat.No.
TGK12
TGK24
TGK32
TGK42
Std.Pkg.
TNLK1
1
TGKIS
TLK20 shown attached to
neutral/ground bar
TLK250 shown attached to
neutral/ground bar
TNLK20
TNLK250
TLK20
TLK250
TGL2
TGK12 with TGKIS
Main Lug Kits
TGK12
Load-Center-Type
PowerMark Plus
PowerMark Gold
THLK200
11
Wire-Size
AWG/kcmil-Cu/Al
2–3/0
1–250
6–2/0
6–250
6–300
Ampere-Rating
150
200
125
200
225
TMLK200
Cat.-No.
THLK150
THLK200
TMLK125
TMLK200
TMLK225
GE OEM Load Center Parts Program
Load Center Accessories
Door Lock
Description
For all indoor load centers
except TPL412
Handle Locks (Padlocking)
Cat.-No.
Std.-Pkg.
TDL106
10
Breaker
THQP
THQL
TQDL
TQD
TDL106
Circuit Directory
Description
Card and holder with
pressure-sensitive backing.
Mounts inside door.
ON or OFF, Snap-On, Padlock Not Included
Cat.-No.
Std.-Pkg.
TD42
1
Cat.-No.
TQPPL
THP100
TQDLPDL1
TQQPLD1
Std.-Pkg.
10
THP100
Handle Locks (Non-Padlocking)
ON or OFF, Snap-On
Description
12.75 oz. spray can of
light-gray enamel
Breaker
THQP
THQL
TD42
Touch-Up Paint
Cat.-No.
Std.-Pkg.
TSP61
1
Cat.-No.
TQPL
THL103
Std.-Pkg.
10
THL103
Handle Ties
For Two Single-Pole Breakers
TSP61
Front Filler Plates
(all multipole breakers have internal common trip)
(to cover rectangular breaker knockouts)
Knockout-Width
1/2"
1"
Cat.-No.
TFH
TQLFP1
Breaker
Std.-Pkg.
100
50
THQP
TFH
Universal Rain-Tight Hubs (Aluminum)
THQL
Description
Solid Snap-On Trip
Indicating
For two THQPs
separated by two
side-by-side THQPs
Solid Snap-On
Trip Indicating
Cat-No.
Std.
Pkg.
THT1
100
THT2
20
THT104
TQHT1
50
20
For Outdoor Enclosures with Removable Closing Caps
Nominal-Conduit-Diameter
in-Inches
3/4
1
11/4
11/2
2
21/2
Closing Cap
3
Cat.-No.
TC75
TC100
TC125
TC150
TC200
TC250
TCCP
TC300
Std.-Pkg.
Cat.-No.
TRL22
TRL22B
Std.-Pkg.
Load Center Hardware & Hardware Kits
Description
PowerMark Gold bond screw
kit with one bond screw
PowerMark Gold hardware kit
with 20 front-mounting screws
10
5
TC150
Door Handles
Location-of-Main-Lugs-or
Main-Breaker
Top
Bottom
1
TRL22
12
Cat.-No.
TBS
THDWRKIT
Std.-Pkg.
1
THT1, THT2,
THT104
GE OEM Load Center Parts Program
Load Center Accessories
Residential Circuit Breaker Enclosures
•
•
•
•
UL Listed
Suitable for use as service entrance
Short-circuit ratings equal to the installed breaker
Steel enclosures
TQD200NRE
Breaker
Type
THQL,
THQL-GF,
TXQL
TQD,
THQD
Max.
Amp
Rating
Poles
100
1, 2, 3
225
THQMV
Type-1-Indoor
Enclosure
—
TQL100F
TQL100S
2
—
2, 3
TQD225F
TQD225S
2
—
Cat.-No.
Type-3R-Outdoor
Enclosure
TQL100RE
TQL100R
TQD225NR
TQD150NRE
TQD200NRE
TQD225R
THMQMV150NRE
THMQMV200NRE
F – flush, S – surface, C – combination
100– 250 A devices have removable closing caps. Larger amp devices
require field-cut openings. Order hubs separately.
100 A circuit breaker factory installed.
Suitable only for two-pole breaker.
150 and 200 A circuit breaker factory installed.
Subfeed and Feed-Through Lugs
• UL Listed
• For use in load centers to economically supply power to subpanel
• Includes mounting base
Poles
2
3
2
2
3
Rating,-A
125
125
150
200
225
Cat.-No.
THLK2125
THLK3125
THLK2150
THLK2200
THLK3225
THLK2125
For use with PowerMark Gold load centers only.
13
GE OEM Load Center Parts Program
TLM612U2
Interior Assembly
Part Number
TLM612U2
TLM612U2N
THDWRKIT2
Description
Min. Qty. Master Pack Qty.
Interior with neutral, 6 Circuit, 125 A, Cu
Interior without neutral, 6 Circuit, 125 A, Cu
Interior Mounting Screw Kit
1
10
10
10
Flush Front, TLM612FCU
Flush Front with Door, TLM612FCUD
Surface Front, TLM612SCU
Surface Front with Door, TLMSCUD
Front Mounting Screw Kit
1
1
1
1
20
1
1
1
1
1
Box Assembly
1
72
Bonding Screw Kit
Equipment Ground Kit
1
1
1
200
Front Assembly
TLM6FC
TLM6FCD
TLM6SC
TLM6SCD
THDWRKIT
Box Assembly
LC612BOX
Accessories
TBS
TGK12
OEM interiors are UL-recognized components listed under UL file E21790.
Main
Ampere
Rating
125
Maximum Spaces
1/2" THQL
1" THQL
1-Pole
2-Pole
1-Pole
2-Pole
6
3
12
4
14
Total
1-Pole
Spaces
12
GE OEM Load Center Parts Program
TLM612U2
Equipment Ground Terminations
UL listed (Panelboards No. 67)
Solid, AWG
14–4 Cu
12–10 Al
Stranded, AWG
14–4 Cu
12–4 Al
60° C and 75° C conductor rating.
22,000 amperes RMS symmetrical
short-circuit rating.
Neutral Terminations
Solid, AWG
14–10 Cu
12–10 Al
Stranded, AWG
14–4 Cu
12–4 Al
Wire Sizes
Line
6–3 Cu-Al
Neutral Lugs
6–2/0 Cu-Al
Flush Mount – TLM612FCU
15
GE OEM Load Center Parts Program
TLM612U2
UL listed (Panelboards No. 67)
60° C and 75° C conductor rating.
22,000 amperes RMS symmetrical
short-circuit rating.
Surface Mount – TLM612SCU
16
GE OEM Load Center Parts Program
TLM812U2
Interior Assembly
Part Number
TLM812U2
TLM812U2N
THDWRKIT2
Description
Min. Qty. Master Pack Qty.
Interior with neutral, 8 Circuit, 125 A, Cu
Interior without neutral, 8 Circuit, 125 A, Cu
Interior Mounting Screw Kit
1
10
10
10
Assembly, Front and Pan, Flush Mount
Door, Flush Mount, Front Assembly
Assembly, Front and Pan, Surface Mount
Door, Surface Mount, Front Assembly
Front Mounting Screw Kit
1
1
1
1
20
1
1
1
1
20
Box Assembly
1
72
Bonding Screw Kit
Equipment Ground Kit
1
1
1
200
Front Assembly
TLM8FC
TLM8FCD
TLM8SC
TLM8SCD
THDWRKIT
Box Assembly
LC612BOX
Accessories
TBS
TGK12
OEM interiors are UL-recognized components listed under UL file E21790.
Main
Ampere
Rating
125
Maximum Spaces
1/2" THQL
1" THQL
1-Pole
2-Pole
1-Pole
2-Pole
8
4
16
6
17
Total
1-Pole
Spaces
16
GE OEM Load Center Parts Program
TLM812U2
Equipment Ground Terminations
Solid, AWG
14–4 Cu
12–10 Al
UL listed (Panelboards No. 67)
Stranded, AWG
14–4 Cu
12–4 Al
60° C and 75° C conductor rating.
22,000 amperes RMS symmetrical
short-circuit rating.
Neutral Terminations
Solid, AWG
14–10 Cu
12–10 Al
Stranded, AWG
14–4 Cu
12–4 Al
Wire Sizes
Line
6–3 Cu-Al
Neutral Lugs
6–2/0 Cu-Al
Flush Mount – TLM812FCU
18
GE OEM Load Center Parts Program
TLM812U2
UL listed (Panelboards No. 67)
60° C and 75° C conductor rating.
22,000 amperes RMS symmetrical
short-circuit rating.
Surface Mount – TLM812SCU
19
GE OEM Load Center Parts Program
TLM1212U2
Interior Assembly
Part Number
TLM1212U2
THDWRKIT2
Description
Interior, 12 circuit, 100–125 A, Cu
Interior Mounting Screw Kit
Min. Qty. Master Pack Qty.
1
10
10
10
Front Assembly
TLM12BC
TM12FC
139C5515P2
192A6597P1
THDWRKIT
Assembly, Front and Pan
For convertible main
For main breaker units
Door
Hinge
Front Mounting Screw Kit
1
1
1
3
20
1
1200
20
Box Assembly
1
40
Bonding Screw Kit
Equipment Ground Kit
1
1
1
200
Box Assembly
LC1212BOX
Accessories
TBS
TGK12, TGK24
OEM interiors are UL-recognized components listed under UL file E21790.
Main
Ampere
Rating
125
Maximum Spaces
1/2" THQL
1" THQL
1-Pole
2-Pole
1-Pole
2-Pole
12
6
24
10
20
Total
1-Pole
Spaces
24
Main
Breaker
Conv Kit
TQMH000
GE OEM Load Center Parts Program
TLM1212U2
Equipment Ground Terminations
Solid, AWG
14–4 Cu
12–10 Al
Stranded, AWG
14–4 Cu
12–4 Al
Neutral Terminations
Solid, AWG
14–10 Cu
12–10 Al
Stranded, AWG
14–4 Cu
12–4 Al
Wire Sizes
Line
6–2/0 Cu-Al (TLM1212)
4–1/0 Cu-Al (TM1210)
1–2/0 Cu-Al (TM1212)
Neutral Lugs
6–2/0 Cu-Al
UL listed (Panelboards No. 67)
60° C and 75° C conductor rating.
22,000 amperes RMS symmetrical
short-circuit rating.
21
GE OEM Load Center Parts Program
TLM1612U2
Interior Assembly
Part Number
TLM1612U2
THDWRKIT2
Description
Interior, 16 circuit, 125 A, Cu
Interior Mounting Screw Kit
Min. Qty. Master Pack Qty.
1
10
10
10
Front Assembly
TLM16DC
TM16EC
139C5515P2
192A6597P1
THDWRKIT
Assembly, Front and Pan
For convertible main
For main breaker units
Door
Hinge
Front Mounting Screw Kit
1
1
1
3
20
1
1200
20
Box Assembly
1
40
1
1
1
200
Box Assembly
LC1212BOX
Accessories
TBS
TGK12, TGK24
Bonding Screw Kit
Equipment Ground Kit
OEM interiors are UL-recognized components listed under UL file E21790.
Main
Ampere
Rating
125
Maximum Spaces
1/2" THQL
1" THQL
1-Pole
2-Pole
1-Pole
2-Pole
16
8
16
6
22
Total
1-Pole
Spaces
24
Main
Breaker
Conv Kit
TQMH000
GE OEM Load Center Parts Program
TLM1612U2
Equipment Ground Terminations
Solid, AWG
14–4 Cu
12–10 Al
Stranded, AWG
14–4 Cu
12–4 Al
Neutral Terminations
Solid, AWG
14–10 Cu
12–10 Al
Stranded, AWG
14–4 Cu
12–4 Al
Wire Sizes
Line
1–2/0 Cu-Al
Neutral Lugs
6–2/0 Cu-Al
UL listed (Panelboards No. 67)
60° C and 75° C conductor rating.
22,000 amperes RMS symmetrical
short-circuit rating.
23
GE OEM Load Center Parts Program
TLM2412U2
Interior Assembly
Part Number
TLM2412U2
THDWRKIT2
Description
Min. Qty. Master Pack Qty.
Interior, 24 circuit, 125 A, Cu
Interior Mounting Screw Kit
1
10
10
10
Assembly, Front and Pan
Door
Hinge
Front Mounting Screw Kit
1
1
3
20
1
1
1200
20
Box Assembly
1
24
Bonding Screw Kit
Equipment Ground Kit
1
1
1
1
Front Assembly
TLM24BC
139C5515P3
192A6597P1
THDWRKIT
Box Assembly
LC24415BOX
Accessories
TBS
TGK24
OEM interiors are UL-recognized components listed under UL file E21790.
Main
Ampere
Rating
125
Maximum Spaces
1/2" THQL
1" THQL
1-Pole
2-Pole
1-Pole
2-Pole
24
12
—
—
24
Total
1-Pole
Spaces
24
Main
Breaker
Conv Kit
TQMH000
GE OEM Load Center Parts Program
TLM2412U2
Equipment Ground Terminations
Solid, AWG
14–4 Cu
12–10 Al
Stranded, AWG
14–4 Cu
12–4 Al
Neutral Terminations
Solid, AWG
14–10 Cu
12–10 Al
Stranded, AWG
14–4 Cu
12–4 Al
Wire Sizes
Line
6–2/0 Cu-Al (TLM)
1–2/0 Cu-Al (TM)
Neutral Lugs
6–2/0 Cu-Al
UL listed (Panelboards No. 67)
60° C and 75° C conductor rating.
22,000 amperes RMS symmetrical
short-circuit rating.
25
GE OEM Load Center Parts Program
TLM2415U2
Interior Assembly
Part Number
TLM2415U2
THDWRKIT2
Description
Min. Qty. Master Pack Qty.
Interior, 24 circuit, 150 A, Cu
Interior Mounting Screw Kit
1
10
10
10
Assembly, Front and Pan
Door
Hinge
Front Mounting Screw Kit
1
1
3
20
1
1
1200
20
Box Assembly
1
24
Bonding Screw Kit
Equipment Ground Kit
1
1
1
1
Front Assembly
TM24EC
139C5515P3
192A6597P1
THDWRKIT
Box Assembly
LC2015BOX
Accessories
TBS
TGK24, TGK32
OEM interiors are UL-recognized components listed under UL file E21790.
Main
Ampere
Rating
150
Maximum Spaces
1/2" THQL
1" THQL
1-Pole
2-Pole
1-Pole
2-Pole
24
12
12
4
26
Total
1-Pole
Spaces
30
Main
Breaker
Conv Kit
THQMV150
GE OEM Load Center Parts Program
TLM2415U2
Equipment Ground Terminations
Solid, AWG
14–4 Cu
12–10 Al
Stranded, AWG
14–4 Cu
12–4 Al
Neutral Terminations
Solid, AWG
14–10 Cu
12–10 Al
Stranded, AWG
14–4 Cu
12–4 Al
Wire Sizes
Line
1–2/0 Cu
2/0–3/0 Al
Neutral Lugs
6–2/0 Cu-Al
UL listed (Panelboards No. 67)
60° C and 75° C conductor rating.
22,000 amperes RMS symmetrical
short-circuit rating.
27
GE OEM Load Center Parts Program
TLM1620U2
Interior Assembly
Part Number
TLM1620U2
THDWRKIT2
Description
Min. Qty. Master Pack Qty.
Interior, 16 circuit, 200 A, Cu
Interior Mounting Screw Kit
1
10
10
10
Assembly, Front and Pan
Door
Hinge
Front Mounting Screw Kit
1
1
3
20
1
1
1200
20
Box Assembly
1
24
Bonding Screw Kit
Equipment Ground Kit
1
1
1
1
Front Assembly
TM16GC
139C5515P3
192A6597P1
THDWRKIT
Box Assembly
LC1620BOX
Accessories
TBS
TGK32
OEM interiors are UL-recognized components listed under UL file E21790.
Main
Ampere
Rating
150
Maximum Spaces
1/2" THQL
1" THQL
1-Pole
2-Pole
1-Pole
2-Pole
16
8
32
16
28
Total
1-Pole
Spaces
32
Main
Breaker
Conv Kit
THQMV200
GE OEM Load Center Parts Program
TLM1620U2
Equipment Ground Terminations
Solid, AWG
14–4 Cu
12–10 Al
Stranded, AWG
14–4 Cu
12–4 Al
Neutral Terminations
Solid, AWG
14–10 Cu
12–10 Al
Stranded, AWG
14–4 Cu
12–4 Al
Wire Sizes
Line
1–250 Cu
2/0–250 Al
Neutral Lugs
6–2/0 Cu-Al
UL listed (Panelboards No. 67)
60° C and 75° C conductor rating.
22,000 amperes RMS symmetrical
short-circuit rating.
29
GE OEM Load Center Parts Program
TLM2020U2
Interior Assembly
Part Number
TLM2020U2
THDWRKIT2
Description
Min. Qty. Master Pack Qty.
Interior, 20 circuit, 200 A, Cu
Interior Mounting Screw Kit
1
10
10
10
Assembly, Front and Pan
Door
Hinge
Front Mounting Screw Kit
1
1
3
20
1
1
1200
20
Box Assembly
1
24
Bonding Screw Kit
Equipment Ground Kit
1
1
1
1
Front Assembly
TM20EC
139C5515P3
192A6597P1
THDWRKIT
Box Assembly
LC2015BOX
Accessories
TBS
TGK24, TGK42
OEM interiors are UL-recognized components listed under UL file E21790.
Main
Ampere
Rating
200
Maximum Spaces
1/2" THQL
1" THQL
1-Pole
2-Pole
1-Pole
2-Pole
20
10
40
18
30
Total
1-Pole
Spaces
40
Main
Breaker
Conv Kit
THQMV200
GE OEM Load Center Parts Program
TLM2020U2
Equipment Ground Terminations
Solid, AWG
14–4 Cu
12–10 Al
Stranded, AWG
14–4 Cu
12–4 Al
Neutral Terminations
Solid, AWG
14–10 Cu
12–10 Al
Stranded, AWG
14–4 Cu
12–4 Al
Wire Sizes
Line
1–250 Cu
2/0–250 Al
Neutral Lugs
6–2/0 Cu-Al
UL listed (Panelboards No. 67)
60° C and 75° C conductor rating.
22,000 amperes RMS symmetrical
short-circuit rating.
31
GE OEM Load Center Parts Program
TLM3220U2
Interior Assembly
Part Number
TLM3220U2
THDWRKIT2
Description
Min. Qty. Master Pack Qty.
Interior, 32 circuit, 200 A, Cu
Interior Mounting Screw Kit
1
10
10
10
Assembly, Front and Pan
Door
Hinge
Front Mounting Screw Kit
1
1
3
20
1
1
1200
20
Box Assembly
1
24
Bonding Screw Kit
Equipment Ground Kit
1
1
1
1
Front Assembly
TM32FC
139C5515P5
192A6597P1
THDWRKIT
Box Assembly
LC3220BOX
Accessories
TBS
TGK32
OEM interiors are UL-recognized components listed under UL file E21790.
Main
Ampere
Rating
200
Maximum Spaces
1/2" THQL
1" THQL
1-Pole
2-Pole
1-Pole
2-Pole
32
16
16
6
32
Total
1-Pole
Spaces
40
Main
Breaker
Conv Kit
THQMV200
GE OEM Load Center Parts Program
TLM3220U2
Equipment Ground Terminations
Solid, AWG
14–4 Cu
12–10 Al
Stranded, AWG
14–4 Cu
12–4 Al
Neutral Terminations
Solid, AWG
14–10 Cu
12–10 Al
Stranded, AWG
14–4 Cu
12–4 Al
Wire Sizes
Line
1–250 Cu
2/0–250 Al
Neutral Lugs
6–2/0 Cu-Al
UL listed (Panelboards No. 67)
60° C and 75° C conductor rating.
22,000 amperes RMS symmetrical
short-circuit rating.
33
GE OEM Load Center Parts Program
TLM4020U2
Interior Assembly
Part Number
TLM4020U2
THDWRKIT2
Description
Min. Qty. Master Pack Qty.
Interior, 40 circuit, 200 A, Cu
Interior Mounting Screw Kit
1
10
6
10
Assembly, Front and Pan
Door
Hinge
Front Mounting Screw Kit
1
1
3
20
1
1
1200
20
Box Assembly
1
24
Bonding Screw Kit
Equipment Ground Kit
1
1
1
1
Front Assembly
TM40BC
139C5515P5
192A6597P1
THDWRKIT
Box Assembly
LC4020BOX
Accessories
TBS
TGK42
OEM interiors are UL-recognized components listed under UL file E21790.
Main
Ampere
Rating
200
Maximum Spaces
1/2" THQL
1" THQL
1-Pole
2-Pole
1-Pole
2-Pole
40
20
—
—
34
Total
1-Pole
Spaces
40
Main
Breaker
Conv Kit
THQMV200
GE OEM Load Center Parts Program
TLM4020U2
Equipment Ground Terminations
Solid, AWG
14–4 Cu
12–10 Al
Stranded, AWG
14–4 Cu
12–4 Al
Neutral Terminations
Solid, AWG
14–10 Cu
12–10 Al
Stranded, AWG
14–4 Cu
12–4 Al
Wire Sizes
Line
1–250 Cu
2/0–250 Al
Neutral Lugs
6–2/0 Cu-Al
UL listed (Panelboards No. 67)
60° C and 75° C conductor rating.
22,000 amperes RMS symmetrical
short-circuit rating.
35
GE OEM Load Center Parts Program
TLM4222U2
Interior Assembly
Part Number
TLM4222U2
THDWRKIT2
Description
Min. Qty. Master Pack Qty.
Interior, 42 circuit, 225 A, Cu
Interior Mounting Screw Kit
1
10
6
10
Assembly, Front and Pan
Door
Hinge
Front Mounting Screw Kit
1
1
3
20
1
1
1200
20
Box Assembly
1
16
Bonding Screw Kit
Equipment Ground Kit
1
1
1
1
Front Assembly
TM42BC
139C5515P5
192A6597P1
THDWRKIT
Box Assembly
LC4222BOX
Accessories
TBS
TGK42
OEM interiors are UL-recognized components listed under UL file E21790.
Main
Ampere
Rating
225
Maximum Spaces
1/2" THQL
1" THQL
1-Pole
2-Pole
1-Pole
2-Pole
42
20
—
—
36
Total
1-Pole
Spaces
42
Main
Breaker
Conv Kit
THQMV225
GE OEM Load Center Parts Program
TLM4222U2
Equipment Ground Terminations
Solid, AWG
14–4 Cu
12–10 Al
Stranded, AWG
14–4 Cu
12–4 Al
Neutral Terminations
Solid, AWG
14–10 Cu
12–10 Al
Stranded, AWG
14–4 Cu
12–4 Al
Wire Sizes
Line
1–250 Cu
2/0–250 Al
Neutral Lugs
6–2/0 Cu-Al
UL listed (Panelboards No. 67)
60° C and 75° C conductor rating.
22,000 amperes RMS symmetrical
short-circuit rating.
37
GE OEM Load Center Parts Program
TL12412U
Interior Assembly
Part Number
TL12412U
THDWRKIT2
Description
Min. Qty. Master Pack Qty.
Interior, 12 circuit, 3-phase, 125 A, MLO
Interior Mounting Screw Kit
1
10
10
10
Assembly, Front and Pan
Door
Hinge
Front Mounting Screw Kit
1
1
3
20
1
1
1200
20
Box Assembly
1
40
Bonding Screw Kit
Equipment Ground Kit
1
1
1
1
Front Assembly
TL12AC3
139C5515P2
192A6597P1
THDWRKIT
Box Assembly
LC1212BOX
Accessories
TBS
TGK12, TGK24
OEM interiors are UL-recognized components listed under UL file E21790.
Main
Ampere
Rating
125
Maximum Spaces
1" THQL
1-Pole
2-Pole
3-Pole
12
6
4
Total
1-Pole
Spaces
12
Alternate backfed main breaker rating: 100 A max. THQL style
Main breaker retainer required: THQLRK
38
GE OEM Load Center Parts Program
TL12412U
Equipment Ground Terminations
Solid, AWG
14–4 Cu
12–10 Al
Stranded, AWG
14–4 Cu
12–4 Al
Neutral Terminations
Solid, AWG
14–8 Cu
12–8 Al
Stranded, AWG
12–4 Cu
12–4 Al
Wire Sizes
Line
6–2/0 Cu-Al
Neutral Lugs
6–2/0 Cu-Al
UL listed (Panelboards No. 67)
60° C and 75° C conductor rating.
22,000 amperes RMS symmetrical
short-circuit rating.
39
GE OEM Load Center Parts Program
TL18415U
Interior Assembly
Part Number
TL18415U
THDWRKIT2
Description
Min. Qty. Master Pack Qty.
Interior, 18 circuit, 3-phase, 150 A
Interior Mounting Screw Kit
1
10
10
10
Assembly, Front and Pan
Door
Hinge
Front Mounting Screw Kit
1
1
3
1
1
1200
20
Box Assembly
1
24
Bonding Screw Kit
Equipment Ground Kit
1
1
1
1
Front Assembly
TL18BC3
139C5515P3
192A6597P1
THDWRKIT
20
Box Assembly
LC24415BOX
Accessories
TBS
TGK24, TGK32
OEM interiors are UL-recognized components listed under UL file E21790.
Main
Ampere
Rating
150
Maximum Spaces
1" THQL
1-Pole
2-Pole
3-Pole
18
8
6
Total
1-Pole
Spaces
18
Alternate backfed main breaker rating: 100 A max.
Main breaker retainer required: THQLRK
40
GE OEM Load Center Parts Program
TL18415U
Equipment Ground Terminations
Solid, AWG
14–4 Cu
12–10 Al
Stranded, AWG
14–4 Cu
12–4 Al
Neutral Terminations
Solid, AWG
14–8 Cu
12–8 Al
Stranded, AWG
12–4 Cu
12–4 Al
Wire Sizes
Line
1–3/0 Cu
2/0–3/0 Al
Neutral Lugs
6–2/0 Cu-Al
UL listed (Panelboards No. 67)
60° C and 75° C conductor rating.
22,000 amperes RMS symmetrical
short-circuit rating.
41
GE OEM Load Center Parts Program
TL24415U
Interior Assembly
Part Number
TL24415U
THDWRKIT2
Description
Min. Qty. Master Pack Qty.
Interior, 24 circuit, 3-phase, 150 A
Interior Mounting Screw Kit
1
10
10
10
Assembly, Front and Pan
Door
Hinge
Front Mounting Screw Kit
1
1
3
20
1
1
1200
20
Box Assembly
1
24
Bonding Screw Kit
Equipment Ground Kit
1
1
1
1
Front Assembly
TL24AC3
139C5515P3
192A6597P1
THDWRKIT
Box Assembly
LC24415BOX
Accessories
TBS
TGK24, TGK32
OEM interiors are UL-recognized components listed under UL file E21790.
Main
Ampere
Rating
150
Maximum Spaces
1" THQL
1-Pole
2-Pole
3-Pole
24
12
8
Total
1-Pole
Spaces
24
Alternate backfed main breaker rating: 100 A max.
Main breaker retainer required: THQLRK
42
GE OEM Load Center Parts Program
TL24415U
Equipment Ground Terminations
Solid, AWG
14–4 Cu
12–10 Al
Stranded, AWG
14–4 Cu
12–4 Al
Neutral Terminations
Solid, AWG
14–8 Cu
12–8 Al
Stranded, AWG
12–4 Cu
12–4 Al
Wire Sizes
Line
1–3/0 Cu
2/0–3/0 Al
Neutral Lugs
6–2/0 Cu-Al
UL listed (Panelboards No. 67)
60° C and 75° C conductor rating.
22,000 amperes RMS symmetrical
short-circuit rating.
43
GE OEM Load Center Parts Program
TL18420U
Interior Assembly
Part Number
TL18420U
THDWRKIT2
Description
Min. Qty. Master Pack Qty.
Interior, 18 circuit, 3-phase, 200 A
Interior Mounting Screw Kit
1
10
10
10
Assembly, Front and Pan
Door
Hinge
Front Mounting Screw Kit
1
1
3
20
1
1
1200
20
Box Assembly
1
24
Bonding Screw Kit
Equipment Ground Kit
1
1
1
1
Front Assembly
TL18DC3
139C5515P3
192A6597P1
THDWRKIT
Box Assembly
LC1620BOX
Accessories
TBS
TGK32
OEM interiors are UL-recognized components listed under UL file E21790.
Main
Ampere
Rating
200
Maximum Spaces
1" THQL
1-Pole
2-Pole
3-Pole
18
8
6
Total
1-Pole
Spaces
18
Alternate backfed main breaker rating: 100 A max.
Main breaker retainer required: THQLRK
44
GE OEM Load Center Parts Program
TL18420U
Equipment Ground Terminations
Solid, AWG
14–4 Cu
12–10 Al
Stranded, AWG
14–4 Cu
12–4 Al
Neutral Terminations
Solid, AWG
14–10 Cu
12–10 Al
Stranded, AWG
14–4 Cu
12–4 Al
Wire Sizes
Line
1–250 Cu
2/0–250 Al
Neutral Lugs
6–2/0 Cu-Al
UL listed (Panelboards No. 67)
60° C and 75° C conductor rating.
22,000 amperes RMS symmetrical
short-circuit rating.
45
GE OEM Load Center Parts Program
TL30420U
Interior Assembly
Part Number
TL30420U
THDWRKIT2
Description
Min. Qty. Master Pack Qty.
Interior, 30 circuit, 3-phase, 200 A
Interior Mounting Screw Kit
1
10
10
10
Assembly, Front and Pan
Door
Hinge
Front Mounting Screw Kit
1
3
Box Assembly
1
24
Bonding Screw Kit
Equipment Ground Kit
1
1
1
1
Front Assembly
TL30BC3
139C5515P5
192A6597P1
THDWRKIT
1
20
1
1
1200
20
Box Assembly
LC30420BOX
Accessories
TBS
TGK32
OEM interiors are UL-recognized components listed under UL file E21790.
Main
Ampere
Rating
200
Maximum Spaces
1" THQL
1-Pole
2-Pole
3-Pole
30
14
10
Total
1-Pole
Spaces
30
Alternate backfed main breaker rating: 100 A max.
Main breaker retainer required: THQLRK
46
GE OEM Load Center Parts Program
TL30420U
Equipment Ground Terminations
Solid, AWG
14–4 Cu
12–10 Al
Stranded, AWG
14–4 Cu
12–4 Al
Neutral Terminations
Solid, AWG
14–8 Cu
12–8 Al
Stranded, AWG
12–4 Cu
12–4 Al
Wire Sizes
Line
1–250 Cu,
2/0–250 Al
Neutral Lugs
6–2/0 Cu-Al
UL listed (Panelboards No. 67)
60° C and 75° C conductor rating.
22,000 amperes RMS symmetrical
short-circuit rating.
47
GE OEM Load Center Parts Program
TL42420U
Interior Assembly
Part Number
TL42420U
THDWRKIT2
Description
Min. Qty. Master Pack Qty.
Interior, 42 circuit, 3-phase, 200 A
Interior Mounting Screw Kit
1
10
10
10
Assembly, Front and Pan
Door
Hinge
Front Mounting Screw Kit
1
1
3
20
1
1
1200
20
Box Assembly
1
24
Bonding Screw Kit
Equipment Ground Kit
1
1
1
1
Front Assembly
TL42BC3
139C5515P5
192A6597P1
THDWRKIT
Box Assembly
LC4020BOX
Accessories
TBS
TGK42
OEM interiors are UL-recognized components listed under UL file E21790.
Main
Ampere
Rating
200
Maximum Spaces
1" THQL
1-Pole
2-Pole
3-Pole
42
20
14
Total
1-Pole
Spaces
42
Alternate backfed main breaker rating: 100 A max.
Main breaker retainer required: THQLRK
48
GE OEM Load Center Parts Program
TL42420U
Equipment Ground Terminations
Solid, AWG
14–4 Cu
12–10 Al
Stranded, AWG
14–4 Cu
12–4 Al
Neutral Terminations
Solid, AWG
14–8 Cu
12–8 Al
Stranded, AWG
12–4 Cu
12–4 Al
Wire Sizes
Line
1–250 Cu
2/0–250 Al
Neutral Lugs
6–2/0 Cu-Al
UL listed (Panelboards No. 67)
60° C and 75° C conductor rating.
22,000 amperes RMS symmetrical
short-circuit rating.
49
GE OEM Load Center Parts Program
TL30422U
Interior Assembly
Part Number
TL30422U
THDWRKIT2
Description
Min. Qty. Master Pack Qty.
Interior, 30 circuit, 3-phase, 225 A
Interior Mounting Screw Kit
1
10
10
10
Assembly, Front and Pan
Door
Hinge
Front Mounting Screw Kit
1
1
3
20
1
1
1200
20
Box Assembly
1
14
Bonding Screw Kit
Equipment Ground Kit
1
1
1
1
Front Assembly
TL30AC3
139C5515P4
192A6597P1
THDWRKIT
Box Assembly
LC30422BOX
Accessories
TBS
TGL2 (two)
OEM interiors are UL-recognized components listed under UL file E21790.
Main
Ampere
Rating
225
Maximum Spaces
1" THQL
1-Pole
2-Pole
3-Pole
30
14
10
Total
1-Pole
Spaces
30
Alternate backfed main breaker rating: 100 A max.
Main breaker retainer required: THQLRK
50
GE OEM Load Center Parts Program
TL30422U
Equipment Ground Terminations
Solid, AWG
14–4 Cu
12–10 Al
Stranded, AWG
14–4 Cu
12–4 Al
Neutral Terminations
Solid, AWG
14–8 Cu
12–8 Al
Stranded, AWG
12–4 Cu
12–4 Al
Wire Sizes
Line
1–300 Cu
2/0–300 Al
Neutral Lugs
6–2/0 Cu-Al
UL listed (Panelboards No. 67)
60° C and 75° C conductor rating.
22,000 amperes RMS symmetrical
short-circuit rating.
51
GE OEM Load Center Parts Program
TL42422U
Interior Assembly
Part Number
TL42422U
THDWRKIT2
Description
Min. Qty. Master Pack Qty.
Interior, 42 circuit, 3-phase, 225 A
Interior Mounting Screw Kit
1
10
10
10
Assembly, Front and Pan
Door
Hinge
Front Mounting Screw Kit
1
1
3
20
1
1
1200
20
Box Assembly
1
14
Bonding Screw Kit
Equipment Ground Kit
1
1
1
1
Front Assembly
TL42AC3
139C5515P4
192A6597P1
THDWRKIT
Box Assembly
LC30422BOX
Accessories
TBS
TGL2 (two)
OEM interiors are UL-recognized components listed under UL file E21790.
Main
Ampere
Rating
225
Maximum Spaces
1" THQL
1-Pole
2-Pole
3-Pole
42
20
14
Total
1-Pole
Spaces
42
Alternate backfed main breaker rating: 100 A max.
Main breaker retainer required: THQLRK
52
GE OEM Load Center Parts Program
TL42422U
Equipment Ground Terminations
Solid, AWG
14–4 Cu
12–10 Al
Stranded, AWG
14–4 Cu
12–4 Al
Neutral Terminations
Solid, AWG
14–8 Cu
12–8 Al
Stranded, AWG
12–4 Cu
12–4 Al
Wire Sizes
Line
1–300 Cu
2/0–300 Al
Neutral Lugs
6–2/0 Cu-Al
UL listed (Panelboards No. 67)
60° C and 75° C conductor rating.
22,000 amperes RMS symmetrical
short-circuit rating.
53
GE OEM Load Center Parts Program
TM12410U
Interior Assembly
Part Number
TM12410U
THDWRKIT2
THHQL32100
THQLRK
Description
Min. Qty. Master Pack Qty.
Interior, 12 circuit, 3-phase, 100 A
Interior Mounting Screw Kit
Main Breaker, 3-pole, 100 A
THQL Retainer Kit
1
10
1
1
10
10
15
200
Assembly, Front and Pan
Door
Hinge
Front Mounting Screw Kit
1
1
3
20
1
1
1200
20
Box Assembly
1
40
Bonding Screw Kit
Equipment Ground Kit
1
1
1
1
Front Assembly
TM12AC3
139C5515P3
192A6597P1
THDWRKIT
Box Assembly
LC18410BOX
Accessories
TBS
TGK12, TGK24
OEM interiors are UL-recognized components listed under UL file E21790.
Main
Ampere
Rating
100
Maximum Spaces
1" THQL
1-Pole
2-Pole
3-Pole
12
6
4
Note: Main breaker included.
54
Total
1-Pole
Spaces
12
GE OEM Load Center Parts Program
TM12410U
Equipment Ground Terminations
Solid, AWG
14–4 Cu
12–10 Al
Stranded, AWG
14–4 Cu
12–4 Al
Neutral Terminations
Solid, AWG
14–8 Cu
12–8 Al
Stranded, AWG
12–4 Cu
12–4 Al
Wire Sizes
Line
6–1/0 Cu,
4–1/0 Al
Neutral Lugs
6–2/0 Cu-Al
UL listed (Panelboards No. 67)
60° C and 75° C conductor rating.
22,000 amperes RMS symmetrical
short-circuit rating.
55
GE OEM Load Center Parts Program
TM18410U
Interior Assembly
Part Number
TM18410U
THDWRKIT2
THHQL32100
THQLRK
Description
Min. Qty. Master Pack Qty.
Interior, 18 circuit, 3-phase, 100 A
Interior Mounting Screw Kit
Main Breaker, 3-pole, 100 A
THQL Retainer Kit
1
10
1
1
10
10
15
200
Assembly, Front and Pan
Door
Hinge
Front Mounting Screw Kit
1
1
3
20
1
1
1200
20
Box Assembly
1
40
Bonding Screw Kit
Equipment Ground Kit
1
1
1
1
Front Assembly
TM18AC3
139C5515P3
192A6597P1
THDWRKIT
Box Assembly
LC18410BOX
Accessories
TBS
TGK24, TGK32
OEM interiors are UL-recognized components listed under UL file E21790.
Main
Ampere
Rating
100
Maximum Spaces
1" THQL
1-Pole
2-Pole
3-Pole
18
8
6
Note: Main breaker included.
56
Total
1-Pole
Spaces
18
GE OEM Load Center Parts Program
TM18410U
Equipment Ground Terminations
Solid, AWG
14–4 Cu
12–10 Al
Stranded, AWG
14–4 Cu
12–4 Al
Neutral Terminations
Solid, AWG
14–8 Cu
12–8 Al
Stranded, AWG
12–4 Cu
12–4 Al
Wire Sizes
Line
6–1/0 Cu,
4–1/0 Al
Neutral Lugs
6–2/0 Cu-Al
UL listed (Panelboards No. 67)
60° C and 75° C conductor rating.
22,000 amperes RMS symmetrical
short-circuit rating.
57
GE OEM Load Center Parts Program
TM30412U
Interior Assembly
Part Number
TM30412U
THDWRKIT2
Description
Min. Qty. Master Pack Qty.
Interior, 30 circuit, 3-phase, 125 A
Interior Mounting Screw Kit
1
10
10
10
Assembly, Front and Pan
Door
Hinge
Front Mounting Screw Kit
1
1
3
20
1
1
1200
20
Box Assembly
1
24
Bonding Screw Kit
Equipment Ground Kit
Circuit Breaker, TQD225 Style
ASM, Support Bracket, Breaker
Screw, Support Bracket Mounting
Screw, Breaker Mounting to Bracket
Screw, Breaker Load Connection
1
1
1
1
1
1
3
1
1
1
200
200
200
200
Front Assembly
TM30EC3
139C5515P5
192A6597P1
THDWRKIT
Box Assembly
LC30420BOX
Accessories
TBS
TGK32
THQD32125X2
315A7060G2
N667CP12004B6
N37P17042B6
192A6976P167
58
GE OEM Load Center Parts Program
TM30412U
OEM interiors are UL-recognized components listed under UL file E21790.
Main
Ampere
Rating
125
Maximum Spaces
1" THQL
1-Pole
2-Pole
3-Pole
30
14
10
Total
1-Pole
Spaces
30
Note: Main breaker and accessories not included with OEM interior; order separately.
59
GE OEM Load Center Parts Program
TM30412U
Equipment Ground Terminations
Solid, AWG
14–4 Cu
12–10 Al
Stranded, AWG
14–4 Cu
12–4 Al
Neutral Terminations
Solid, AWG
14–8 Cu
12–8 Al
Stranded, AWG
12–4 Cu
12–4 Al
Wire Sizes
Line
1–3/0 Cu,
2/0–3/0 Al
Neutral Lugs
6–2/0 Cu-Al
UL listed (Panelboards No. 67)
60° C and 75° C conductor rating.
22,000 amperes RMS symmetrical
short-circuit rating.
60
GE OEM Load Center Parts Program
TM24415U
Interior Assembly
Part Number
TM24415U
THDWRKIT2
Description
Min. Qty. Master Pack Qty.
Interior, 24 circuit, 3-phase, 150 A
Interior Mounting Screw Kit
1
10
10
10
Assembly, Front and Pan
Door
Hinge
Front Mounting Screw Kit
1
1
3
20
1
1
1200
20
Box Assembly
1
24
Bonding Screw Kit
Equipment Ground Kit
Circuit Breaker, TQD225 Style
ASM, Support Bracket, Breaker
Screw, Support Bracket Mounting
Screw, Breaker Mounting to Bracket
Screw, Breaker Load Connection
1
1
1
1
1
1
3
1
1
1
200
200
200
200
Front Assembly
TM24EC3
139C5515P5
192A6597P1
THDWRKIT
Box Assembly
LC30420BOX
Accessories
TBS
TGK32
THQD32150X2
315A7060G2
N667CP12004B6
N37P17042B6
192A6976P167
61
GE OEM Load Center Parts Program
TM24415U
OEM interiors are UL-recognized components listed under UL file E21790.
Main
Ampere
Rating
150
Maximum Spaces
1" THQL
1-Pole
2-Pole
3-Pole
24
12
8
Total
1-Pole
Spaces
24
Note: Main breaker and accessories not included with OEM interior; order separately.
62
GE OEM Load Center Parts Program
TM24415U
Equipment Ground Terminations
Solid, AWG
14–4 Cu
12–10 Al
Stranded, AWG
14–4 Cu
12–4 Al
Neutral Terminations
Solid, AWG
14–8 Cu
12–8 Al
Stranded, AWG
12–4 Cu
12–4 Al
Wire Sizes
Line
1–3/0 Cu,
2/0–3/0 Al
Neutral Lugs
6–2/0 Cu-Al
UL listed (Panelboards No. 67)
60° C and 75° C conductor rating.
22,000 amperes RMS symmetrical
short-circuit rating.
63
GE OEM Load Center Parts Program
TM30415U
Interior Assembly
Part Number
TM30415U
THDWRKIT2
Description
Min. Qty. Master Pack Qty.
Interior, 30 circuit, 3-phase, 150 A
Interior Mounting Screw Kit
1
10
10
10
Assembly, Front and Pan
Door
Hinge
Front Mounting Screw Kit
1
1
3
20
1
1
1200
20
Box Assembly
1
24
Bonding Screw Kit
Equipment Ground Kit
Circuit Breaker, TQD225 Style
ASM, Support Bracket, Breaker
Screw, Support Bracket Mounting
Screw, Breaker Mounting to Bracket
Screw, Breaker Load Connection
1
1
1
1
1
1
3
1
1
1
200
200
200
200
Front Assembly
TM30EC3
139C5515P5
192A6597P1
THDWRKIT
Box Assembly
LC30420BOX
Accessories
TBS
TGK32
THQD32150X2
315A7060G2
N667CP12004B6
N37P17042B6
192A6976P167
64
GE OEM Load Center Parts Program
TM30415U
OEM interiors are UL-recognized components listed under UL file E21790.
Main
Ampere
Rating
150
Maximum Spaces
1" THQL
1-Pole
2-Pole
3-Pole
30
14
10
Total
1-Pole
Spaces
30
Note: Main breaker and accessories not included with OEM interior; order separately.
65
GE OEM Load Center Parts Program
TM30415U
Equipment Ground Terminations
Solid, AWG
14–4 Cu
12–10 Al
Stranded, AWG
14–4 Cu
12–4 Al
Neutral Terminations
Solid, AWG
14–8 Cu
12–8 Al
Stranded, AWG
12–4 Cu
12–4 Al
Wire Sizes
Line
1–3/0 Cu,
2/0–3/0 Al
Neutral Lugs
6–2/0 Cu-Al
UL listed (Panelboards No. 67)
60° C and 75° C conductor rating.
22,000 amperes RMS symmetrical
short-circuit rating.
66
GE OEM Load Center Parts Program
TM42415U
Interior Assembly
Part Number
TM42415U
THDWRKIT2
Description
Min. Qty. Master Pack Qty.
Interior, 42 circuit, 3-phase, 150 A
Interior Mounting Screw Kit
1
10
10
10
Assembly, Front and Pan
Door
Hinge
Front Mounting Screw Kit
1
1
3
20
1
1
1200
20
Box Assembly
1
24
Bonding Screw Kit
Equipment Ground Kit
Circuit Breaker, TQD225 Style
ASM, Support Bracket, Breaker
Screw, Support Bracket Mounting
Screw, Breaker Mounting to Bracket
Screw, Breaker Load Connection
1
1
1
1
1
1
3
1
1
1
200
200
200
200
Front Assembly
TM42EDC3
139C5515P5
192A6597P1
THDWRKIT
Box Assembly
LC4020BOX
Accessories
TBS
TGK42
THQD32150X2
315A7060G2
N667CP12004B6
N37P17042B6
192A6976P167
67
GE OEM Load Center Parts Program
TM42415U
OEM interiors are UL-recognized components listed under UL file E21790.
Main
Ampere
Rating
150
Maximum Spaces
1" THQL
1-Pole
2-Pole
3-Pole
42
20
14
Total
1-Pole
Spaces
42
Note: Main breaker and accessories not included with OEM interior; order separately.
68
GE OEM Load Center Parts Program
TM42415U
Equipment Ground Terminations
Solid, AWG
14–4 Cu
12–10 Al
Stranded, AWG
14–4 Cu
12–4 Al
Neutral Terminations
Solid, AWG
14–8 Cu
12–8 Al
Stranded, AWG
12–4 Cu
12–4 Al
Wire Sizes
Line
1–3/0 Cu,
2/0–3/0 Al
Neutral Lugs
6–2/0 Cu-Al
UL listed (Panelboards No. 67)
60° C and 75° C conductor rating.
22,000 amperes RMS symmetrical
short-circuit rating.
69
GE OEM Load Center Parts Program
TM24420U
Interior Assembly
Part Number
TM24420U
THDWRKIT2
Description
Min. Qty. Master Pack Qty.
Interior, 24 circuit, 3-phase, 200 A
Interior Mounting Screw Kit
1
10
10
10
Assembly, Front and Pan
Door
Hinge
Front Mounting Screw Kit
1
1
3
20
1
1
1200
20
Box Assembly
1
24
Bonding Screw Kit
Equipment Ground Kit
Circuit Breaker, TQD225 Style
ASM, Support Bracket, Breaker
Screw, Support Bracket Mounting
Screw, Breaker Mounting to Bracket
Screw, Breaker Load Connection
1
1
1
1
200
200
200
200
Front Assembly
TM24DC3
139C5515P5
192A6597P1
THDWRKIT
Box Assembly
LC30420BOX
Accessories
TBS
TGK32
THQD32200X2
315A7060G2
N667CP12004B6
N37P17042B6
192A6976P167
70
1
1
1
1
3
GE OEM Load Center Parts Program
TM24420U
OEM interiors are UL-recognized components listed under UL file E21790.
Main
Ampere
Rating
200
Maximum Spaces
1" THQL
1-Pole
2-Pole
3-Pole
24
12
8
Total
1-Pole
Spaces
24
Note: Main breaker and accessories not included with OEM interior; order separately.
71
GE OEM Load Center Parts Program
TM24420U
Equipment Ground Terminations
Solid, AWG
14–4 Cu
12–10 Al
Stranded, AWG
14–4 Cu
12–4 Al
Neutral Terminations
Solid, AWG
14–8 Cu
12–8 Al
Stranded, AWG
12–4 Cu
12–4 Al
Wire Sizes
Line
1–300 MCM Cu,
2/0–300 MCM Al
Neutral Lugs
6–2/0 Cu-Al
UL listed (Panelboards No. 67)
60° C and 75° C conductor rating.
22,000 amperes RMS symmetrical
short-circuit rating.
72
GE OEM Load Center Parts Program
TM30420U
Interior Assembly
Part Number
TM30420U
THDWRKIT2
Description
Min. Qty. Master Pack Qty.
Interior, 30 circuit, 3-phase, 200 A
Interior Mounting Screw Kit
1
10
10
10
Assembly, Front and Pan
Door
Hinge
Front Mounting Screw Kit
1
1
3
20
1
1
1200
20
Box Assembly
1
24
Bonding Screw Kit
Equipment Ground Kit
Circuit Breaker, TQD225 Style
ASM, Support Bracket, Breaker
Screw, Support Bracket Mounting
Screw, Breaker Mounting to Bracket
Screw, Breaker Load Connection
1
1
1
1
1
1
3
1
1
1
200
200
200
200
Front Assembly
TM30DC3
139C5515P5
192A6597P1
THDWRKIT
Box Assembly
LC3220BOX
Accessories
TBS
TGK32
THQD32200X2
315A7060G2
N667CP12004B6
N37P17042B6
192A6976P167
73
GE OEM Load Center Parts Program
TM30420U
OEM interiors are UL-recognized components listed under UL file E21790.
Main
Ampere
Rating
200
Maximum Spaces
1" THQL
1-Pole
2-Pole
3-Pole
30
14
10
Total
1-Pole
Spaces
30
Note: Main breaker and accessories not included with OEM interior; order separately.
74
GE OEM Load Center Parts Program
TM30420U
Equipment Ground Terminations
Solid, AWG
14–4 Cu
12–10 Al
Stranded, AWG
14–4 Cu
12–4 Al
Neutral Terminations
Solid, AWG
14–8 Cu
12–8 Al
Stranded, AWG
12–4 Cu
12–4 Al
Wire Sizes
Line
1–250 MCM Cu,
2/0–250 MCM Al
Neutral Lugs
6–2/0 Cu-Al
UL listed (Panelboards No. 67)
60° C and 75° C conductor rating.
22,000 amperes RMS symmetrical
short-circuit rating.
75
GE OEM Load Center Parts Program
TM42420U
Interior Assembly
Part Number
TM42420U
THDWRKIT2
Description
Min. Qty. Master Pack Qty.
Interior, 42 circuit, 3-phase, 200 A
Interior Mounting Screw Kit
1
10
10
10
Assembly, Front and Pan
Door
Hinge
Front Mounting Screw Kit
1
1
3
1
1
1200
Box Assembly
1
16
Bonding Screw Kit
Equipment Ground Kit
Circuit Breaker, TQD225 Style
ASM, Support Bracket, Breaker
Screw, Support Bracket Mounting
Screw, Breaker Mounting to Bracket
Screw, Breaker Load Connection
1
1
1
1
1
1
3
1
1
1
200
200
200
200
Front Assembly
TM42EC3
139C5515P5
192A6597P1
THDRWKIT
20
20
Box Assembly
LC4222BOX
Accessories
TBS
TGK42
THQD32200X2
315A7060G2
N667CP12004B6
N37P17042B6
192A6976P167
76
GE OEM Load Center Parts Program
TM42420U
OEM interiors are UL-recognized components listed under UL file E21790.
Main
Ampere
Rating
200
Maximum Spaces
1" THQL
1-Pole
2-Pole
3-Pole
42
20
14
Total
1-Pole
Spaces
42
Note: Main breaker and accessories not included with OEM interior; order separately.
77
GE OEM Load Center Parts Program
TM42420U
Equipment Ground Terminations
Solid, AWG
14–4 Cu
12–10 Al
Stranded, AWG
14–4 Cu
12–4 Al
Neutral Terminations
Solid, AWG
14–8 Cu
12–8 Al
Stranded, AWG
12–4 Cu
12–4 Al
Wire Sizes
Line
1–250 MCM Cu,
2/0–250 MCM Al
Neutral Lugs
6–2/0 Cu-Al
UL listed (Panelboards No. 67)
60° C and 75° C conductor rating.
22,000 amperes RMS symmetrical
short-circuit rating.
78
GE OEM Load Center Parts Program
TM42422U
Interior Assembly
Part Number
TM42422U
THDWRKIT2
Description
Min. Qty. Master Pack Qty.
Interior, 42 circuit, 3-phase, 225 A
Interior Mounting Screw Kit
1
10
10
10
Assembly, Front and Pan
Door
Hinge
Front Mounting Screw Kit
1
1
3
20
1
1
1200
20
Box Assembly
1
24
Bonding Screw Kit
Equipment Ground Kit
Circuit Breaker, TQD225 Style
ASM, Support Bracket, Breaker
Screw, Support Bracket Mounting
Screw, Breaker Mounting to Bracket
Screw, Breaker Load Connection
1
1
1
1
1
1
3
1
1
1
200
200
200
200
Front Assembly
TM42BC3
139C5515P5
192A6597P1
THDWRKIT
Box Assembly
LC30422BOX
Accessories
TBS
TGL2 (two)
THQD32225X2
315A7060G4
N667CP12004B6
N37P17042B6
192A6976P167
79
GE OEM Load Center Parts Program
TM42422U
OEM interiors are UL-recognized components listed under UL file E21790.
Main
Ampere
Rating
225
Maximum Spaces
1" THQL
1-Pole
2-Pole
3-Pole
42
20
14
Total
1-Pole
Spaces
42
Note: Main breaker and accessories not included with OEM interior; order separately.
80
GE OEM Load Center Parts Program
TM42422U
Equipment Ground Terminations
Solid, AWG
14–4 Cu
12–10 Al
Stranded, AWG
14–4 Cu
12–4 Al
Neutral Terminations
Solid, AWG
14–8 Cu
12–8 Al
Stranded, AWG
12–4 Cu
12–4 Al
Wire Sizes
Line
1–300 MCM Cu,
2/0–300 MCM Al
Neutral Lugs
6–2/0 Cu-Al
UL listed (Panelboards No. 67)
60° C and 75° C conductor rating.
22,000 amperes RMS symmetrical
short-circuit rating.
81
GE OEM Load Center Parts Program
TSF420U
Interior Assembly
Part Number
TSF420U
THDWRKIT2
TSF420UN
Description
Min. Qty. Master Pack Qty.
Interior, 4 circuits 1" or 8 circuits 1/2",
1-phase, 200 A
Interior Mounting Screw Kit
Interior Without Neutral Assembly
1
10
10
1
10
10
Bonding Screw Kit
Equipment Ground Kit
Main Breaker Retaining Kit
1
1
1
1
1
1
Accessories
TBS
TGK12
THQLRK1
OEM interiors are UL-recognized components listed under UL file E21790.
Main
Ampere
Rating
200
Maximum Spaces
1/2" THQL
1" THQL
1-Pole
2-Pole
1-Pole
2-Pole
4
2
8
3
82
Total
1-Pole
Spaces
8
GE OEM Load Center Parts Program
TSLR420U
Interior Assembly
Part Number
TSLR420U
THDWRKIT2
TSLR420UN
Description
Min. Qty. Master Pack Qty.
Interior, 4 circuits 1" or 8 circuits 1/2",
1-phase, 200 A (125 A for TSLR412CSCU)
Interior Mounting Screw Kit
Interior Without Neutral Assembly
1
10
10
1
10
10
Bonding Screw Kit
Equipment Ground Kit
1
1
1
1
Accessories
TBS
TGK12
OEM interiors are UL-recognized components listed under UL file E21790.
Main
Ampere
Rating
200
Maximum Spaces
1/2" THQL
1" THQL
1-Pole
2-Pole
1-Pole
2-Pole
4
2
8
3
83
Total
1-Pole
Spaces
8
GE OEM Load Center Parts Program
TSM1212U
Interior Assembly
Part Number
TSM1212U
THDWRKIT2
TSM1212UN
Description
Min. Qty. Master Pack Qty.
Interior, 12 circuits 1" or 24 circuits 1/2",
1-phase, 125 A
Interior Mounting Screw Kit
Interior Without Neutral Assembly
1
10
10
1
10
10
Bonding Screw Kit
Equipment Ground Kit
1
1
1
1
Accessories
TBS
TGK12
OEM interiors are UL-recognized components listed under UL file E21790.
Main
Ampere
Rating
125
Maximum Spaces
1/2" THQL
1" THQL
1-Pole
2-Pole
1-Pole
2-Pole
12
6
24
10
Total
1-Pole
Spaces
24
Note: Reverse-fed main breaker retainer not available.
84
GE OEM Load Center Parts Program
TSM1610U
Interior Assembly
Part Number
TSM1610U
THDWRKIT2
TSM1610UN
Description
Min. Qty. Master Pack Qty.
Interior, 16 circuits 1" or 32 circuits 1/2",
1-phase, 100 A
Interior Mounting Screw Kit
Interior Without Neutral Assembly
1
10
10
1
10
10
Bonding Screw Kit
Equipment Ground Kit
1
1
1
1
Accessories
TBS
TGK12
OEM interiors are UL-recognized components listed under UL file E21790.
Main
Ampere
Rating
100
Maximum Spaces
1/2" THQL
1" THQL
1-Pole
2-Pole
1-Pole
2-Pole
16
8
32
14
Total
1-Pole
Spaces
32
Note: Reverse-fed main breaker retainer not available.
85
GE OEM Load Center Parts Program
TSM2020U
Interior Assembly
Part Number
TSM2020U
THDWRKIT2
TSM2020UN
Description
Min. Qty. Master Pack Qty.
Interior, 20 circuits 1" or 40 circuits 1/2",
1-phase, 200 A
Interior Mounting Screw Kit
Interior Without Neutral Assembly
1
10
10
1
10
10
Bonding Screw Kit
Equipment Ground Kit
Main Breaker Retaining Kit
1
1
1
1
1
1
Accessories
TBS
TGK12
THQLRK1
OEM interiors are UL-recognized components listed under UL file E21790.
Main
Ampere
Rating
200
Maximum Spaces
1/2" THQL
1" THQL
1-Pole
2-Pole
1-Pole
2-Pole
20
10
40
18
86
Total
1-Pole
Spaces
40
GE OEM Load Center Parts Program
TSM820U
Interior Assembly
Part Number
TSM820U
THDWRKIT2
TSM820UN
Description
Min. Qty. Master Pack Qty.
Interior, 8 circuits 1" or 16 circuits 1/2", 1phase, 200 A (150 A for TSM820CSCU)
Interior Mounting Screw Kit
Interior Without Neutral Assembly
1
10
10
1
10
10
Bonding Screw Kit
Equipment Ground Kit
Main Breaker Retaining Kit
1
1
1
1
1
1
Accessories
TBS
TGK12
THQLRK1
OEM interiors are UL-recognized components listed under UL file E21790.
Main
Ampere
Rating
200
Maximum Spaces
1/2" THQL
1" THQL
1-Pole
2-Pole
1-Pole
2-Pole
8
4
16
6
87
Total
1-Pole
Spaces
16
GE OEM Load Center Parts Program
TSMR1212U
Interior Assembly
Part Number
TSMR1212U
THDWRKIT2
TSMR1212UN
Description
Min. Qty. Master Pack Qty.
Interior, 12 circuits 1" or 24 circuits 1/2",
1-phase, 125 A
Interior Mounting Screw Kit
Interior Without Neutral Assembly
1
10
10
1
10
10
Bonding Screw Kit
Equipment Ground Kit
Main Breaker Mounting Kit
Reverse-Fed Retaining Kit – Alternate
1
1
1
1
1
1
1
1
Accessories
TBS
TGK12
TQMH000
THQLKR1
OEM interiors are UL-recognized components listed under UL file E21790.
Main
Ampere
Rating
125
Maximum Spaces
1/2" THQL
1" THQL
1-Pole
2-Pole
1-Pole
2-Pole
12
6
24
10
For use with THQL, THHQL, or TXQL main breaker.
88
Total
1-Pole
Spaces
24
GE OEM Load Center Parts Program
TSMR2015U
Interior Assembly
Part Number
TSMR2015U
THDWRKIT2
TSMR2015UN
Description
Min. Qty. Master Pack Qty.
Interior, 20 circuits 1" or 40 circuits 1/2", 1phase, 150 A (200 A for TSMR2020CSCU)
Interior Mounting Screw Kit
Interior Without Neutral Assembly
1
10
10
1
10
10
Bonding Screw Kit
Equipment Ground Kit
1
1
1
1
Accessories
TBS
TGK12
OEM interiors are UL-recognized components listed under UL file E21790.
Main
Ampere
Rating
200
Maximum Spaces
1/2" THQL
1" THQL
1-Pole
2-Pole
1-Pole
2-Pole
20
10
40
18
Total
1-Pole
Spaces
40
For main breaker, order THQMV main breaker; includes mounting base. Reverse-fed
main breaker available, 100 A max. rating, with THQLRK1 retaining kit.
89
Download