Series KD/LD

advertisement
DC Solid State Relay
Series KD/LD
SHORT CIRCUIT PROTECTED OPTICALLY ISOLATED, 10A, 60 VDC
Part Number
Relay Description
KD00CK
5 A Solid State Relay (SSR)
KD02CK
5 A SSR with Switch Status
KD20CK
5 A SSR with Short Circuit Protection
KD22CK
5 A SSR with Short Circuit Protection
and Switch Status
LD00CM
10 A Solid State Relay
LD02CM
10 A SSR with Switch Status
LD20CM
10 A SSR with Short Circuit Protection
LD22CM
10 A SSR with Short Circuit Protection
and Switch Status
DC
FEATURES
* The Y suffix denotes parameters tested to MIL-R-28750 specifications.
The W suffix denotes parameters tested to Teledyne specifications.
ELECTRICAL SPECIFICATIONS
• Available with short circuit/current
overload protection
• Available with switch status output
• TTL and CMOS compatible control
• Low ON resistance power FET
output
• Fast switching speed
• Meets 28 Vdc system requirements
of MIL-STD-704
• Optical isolation
• Low profile hermetic package
• Built and tested to the requirements
of MIL-R-28750
(-55°C TO +105°C UNLESS OTHERWISE NOTED)
DESCRIPTION
INPUT (CONTROL) SPECIFICATION
When used in 2 terminal configuration
(TTL or direct control) (See Fig. 1)
Min
Typ
The KD and LD series solid state
relays are screened utilizing MIL-R28750 test methods and are
packaged in low profile hermetically
sealed cases. These relays are
constructed with state-of-the-art solid
state techniques and feature fully
floating power FET output
technology. This allows the load to be
connected to either output terminal
and provides a low ON resistance.
The input (control) and output are
optically isolated to protect input logic
circuits from output transients.
Available options include short circuit
and current overload protection,
which provides complete protection
for both the relay and system wiring.
This feature not only provides
protection should a short or overload
occur while the relay is on, but will
also provide protection should the
relay be switched into a short. The
second option is a status output line.
Switch status returns the true status
of the output switch and is optically
isolated from the load. It provides
status indication independent of the
control circuit of the relay. The status
line provides a logic 0 (low) when the
relay output is off with load voltage
and continuity present, and a logic 1
(high) when the output is on. These
options are available either together
or separately as standard features.
Input Current @ VBIAS = 5 Vdc (See Fig. 2)
14
Turn-Off Voltage (Guaranteed Off)
Turn-On Voltage (Guaranteed On)
mAdc
1.5
Vdc
3.8
-32
Vdc
32
Vdc
Max
Units
VCONTROL = 5 Vdc
250
µAdc
VCONTROL = 18 Vdc
1
mAdc
0
18
Vdc
3.8
32
Vdc
16
mAdc
Control Voltage Range
Bias Supply Voltage (See Note 1)
Bias Supply Current
Turn-Off Voltage (Guaranteed Off)
Turn-On Voltage (Guaranteed On)
12/96
15
Vdc
INPUT (CONTROL) SPECIFICATION
When used in 3 terminal configuration
(CMOS or open collector TTL) (See Fig. 1)
Min
Typ
Control Current
Units
3.8
Reverse Voltage Protection
Input Supply Range (See Note 1)
Max
14
3.2
Vdc
0.3
Vdc
BD
AC
DC
A
D
©1996 TELEDYNE RELAYS
DC-19
Series KD/LD
DC
(See Note 2)
OUTPUT (LOAD) SPECIFICATIONS
Min
Typ
Continuous Load Current KD and LD series
(See Fig. 3)
without heat sink
BLOCK DIAGRAM
Max
Units
5
Adc
Leakage Current
VLOAD=60Vdc
LD series with
heat sink
10
KD00CK, KD20CK
LD00CM, LD20CM
100
µA
KD02CK, KD22CK
LD02CM, LD22CM
2
mA
KD00CK, KD02CK
KD20CK, KD22CK
.60
.70
LD00CM, LD02CM
LD20CM, LD22CM
1.2
1.4
BD
WITH STATUS
Output Voltage
Drop
Vdc
AC
Continuous Operating Load Voltage
60
Vdc
Transient Blocking Voltage
80
Vdc
ON Resistance
ILOAD = 100 mA
KD00CK, KD20CK
LD00CM, LD20CM
TJ = 25°C
(See Fig. 4)
KD20CK, KD22CK
LD20CM, LD22CM
.075
NO STATUS
Ohms
.100
MECHANICAL SPECIFICATIONS
DIMENSIONS ARE SHOWN IN INCHES (MILLIMETERS)
.200
±.010
Turn-On Time (See Fig. 5)
5
ms
Turn-Off Time (See Fig. 5)
2
ms
0.188 ±.010
22
Electrical System Spike
±600
Vpk
0.140 DIA
(3.556)
6 PLS
1
3
0.
0.60
16
1.000
(25.400) .040 (1.02)
± .002 (0.051)
0.8
6 PL
1.340
(34.04)
1.375
REF (34.925)
MAX
9
12
DC
Output Capacitance at 25 Vdc, 100 KHz
Isolation
(Input to Output)
1600
KD00CK, KD20CK
LD00CM, LD20CM
pF
0.400
(10.160)
Tolerance:
.XXX ± .005
Tolerance:
.XXX ± .005
10
Dielectric Strength
A
0.81
MAX
Vac
109
Ohms
130
Maximum Junction Temperature
150
°C
Thermal Resistance Junction to Ambient (θJA)
30
°C/W
°C
Thermal Resistance Junction to Case (θJC)
7
°C/W
.200 (5.08)
1.000
(25.4)
.040 (1.02) DIA
1.750 ± .002 (0.051)
6 PLS
(44.45)
.600
.800 (15.2)
(20.3)
0.22
(5.59)
MAX
1.370
REF
2.105
(53.47)
MAX
TEMPERATURE
MEASUREMENT POINT
.140 (3.56)
DIA
6 PLS .200
(5.08)
LL PACKAGE
PACKAGE
.400 (10.2)
• Enclosure: Hermetically Sealed DIP
• Leak Rate: 1 x 10-8 CC/Sec Maximum
• Material:
Header:
Pins
• Weight:
20 grams
• Tolerance: .XXX ± .005
SPECIFICATIONS ARE SUBJECT TO CHANGE WITHOUT NOTICE
DC-20
.475
±.015
.551
(14.0)
Output Junction Temperature
@ ILOAD = IMAX RATED
D
.157 (3.99) ±
.003 (.076)
DIA
THRU 2 PLS
.398
(10.1)
15
1000
Insulation Resistance @ 500 Vdc
0.22
(5.59)
MAX
PACKAGE
KKPACKAGE
pF
KD02CK, KD22CK
LD02CM, LD22CM
.475
±.015
0.801
(20.345)
MAX
Cold Rolled Steel
Nickel Plated
Copper Core
Series KD/LD
ENVIRONMENTAL SPECIFICATIONS
VSTATUS
ISO
VSO
IBIAS
RSTATUS
IS
RS
IT
VBIAS
22
ICONTROL
Range
STATUS
OUTPUT (+) OUTPUT
BIAS
VCONTROL
Temperature
16
LOAD
12
CONTROL
Operating
-55°C to +105°C
Storage
-55°C to +125°C
VLOAD
KD02CK
LD02CM
KD22CK
LD22CM
1
Vibration
100 g, 10 to 3000 Hz
Constant Acceleration
3
9
RETURN
(-) OUTPUT
DC
LOAD
LOAD
RETURN
5000 g
Shock
1500 g, 0.5 ms pulse
(A) 3 TERMINAL INPUT WITH STATUS (See Note 5)
STATUS OUTPUT TRUTH TABLE
RS
(KD02CK, LD02CM, KD22CK, LD22CM)
IIN
LOAD
VIN
BIAS
(+) OUTPUT
22
12
VLOAD
KD02CK
LD02CM
KD22CK
LD22CM
KD00CK
LD00CM
CONTROL 1
3
9
RETURN
(-) OUTPUT
1/
Control Voltage
Status Output Level
High
Off
Low (VSO ≤ 0.4 Vdc)
Low
On
High (VSO = VSTATUS)
LOAD
CONTROL
LOAD
RETURN
O.C. TTL
(B) 2 TERMINAL INPUT (OPEN COLLECTOR TTL DRIVE)
STATUS OUTPUT SPECIFICATIONS
(KD02CK, LD02CM, KD22CK, LD22CM)
Min
Max
Units
Status Supply Voltage
30
Vdc
Status Leakage Current @ 15 Vdc
10
µAdc
Status (sink) Current (VSO < 0.4 Vdc)
600
µAdc
Status Turn-On Time (See Fig. 6)
3.5
ms
Status Turn-Off Time (See Fig. 6)
8.0
ms
VSTATUS
ISO
VSO
BD
Relay Output State
RS
S1
RSTATUS
IS
IIN
IT
VIN
BIAS
LOAD
STATUS
OUTPUT (+) OUTPUT
AC
VLOAD
KD02CK
LD02CM
KD22CK
LD22CM
CONTROL
RETURN
Typ
(-) OUTPUT
LOAD
LOAD
RETURN
(C) 2 TERMINAL INPUT (DIRECT DRIVE) WITH STATUS
DC
RS IIN
LOAD
BIAS
(+) OUTPUT
22
12
3
9
RETURN
(-) OUTPUT
CONTROL 1
VLOAD
KD02CK
LD02CM
KD22CK
LD22CM
KD00CK
LD00CM 1 /
LOAD
LOAD
RETURN
(D) 2 TERMINAL INPUT (DIRECT DRIVE)
VBIAS
IBIAS
15
12
9
6
A
3
0
RS
0
BIAS
LOAD
(+) OUTPUT
CONTROL
RETURN
5
10 15 20
25
30 40
BIAS (INPUT) VOLTAGE (Vdc)
50
60
VLOAD
KD02CK
LD02CM
KD22CK
LD22CM
KD00CK
LD00CM
ICONTROL
VCONTROL
18
BIAS (INPUT) CURRENT (mA)
S1
VIN
BIAS (INPUT) CURRENT VS BIAS (INPUT) VOLTAGE
FIGURE 2 (See Note 1)
1/
(-) OUTPUT
LOAD
LOAD
RETURN
1 / KD02CK, KD22CK, LD02CM and LD22CM may be wired without the status
line as shown in (B), (D) and (E) above.
(E) 3 TERMINAL INPUT WITHOUT STATUS
D
WIRING CONFIGURATIONS
FIGURE 1 (See Note 1)
12/96
©1996 TELEDYNE RELAYS
DC-21
Series KD/LD
100
90
PERCENT CURRENT
80
70
60
50
40
KD00CK
KD02CK
LD00CM
LD02CM
30
KD20CK
KD22CK
LD20CM
LD22CM
20
10
5
1.8
30A
-55°
1.6
25A
1.4
20A
1.2
25°
1.0
15A
0.8
10A
100°
0.6
5A
0.4
0.2
10
15 25 35 45 55 65 75 85 95 105 115
25
AMBIENT TEMPERATURE (°C)
LOAD CURRENT DERATING CURVE FOR
KD/LD SERIES WITHOUT A HEAT SINK
(A)
BD
50
75
100
JUNCTION TEMPERATURE (C°)
125
NORMALIZED ON RESISTANCE
VS JUNCTION TEMPERATURE
FIGURE 4 (See Note 3)
PERCENT CURRENT
80
70
60
50
40
30
OUTPUT TURN-ON AND TURN-OFF
TIMING
FIGURE 5
10
0
-55 -45 -35 -5
5
10
100
1000'S
2000
SERIES RESISTOR (Ohms)
90
20
1S
OVERLOAD CURRENT VS TIME TO TRIP
(TYPICAL)
KD20CK, KD22CK, LD20CM, LD22CM
FIGURE 7
100
AC
100
1(s)
0.0
0
-55 -45 -35 -5
NORMALIZED ON RESISTANCE (NR)
2.0
DC
1500
1000
500
15 25 35 45 55 65 75 85 95 105 115 125
0
CASE TEMPERATURE (°C)
0
5
10
15
20
25
30
35
BIAS VOLTAGE (VOLTS)
LOAD CURRENT DERATING CURVE FOR
LD SERIES
(B)
SERIES LIMIT BIAS RESISTOR VS BIAS
VOLTAGE
FIGURE 8 (See Note 1)
THERMAL DERATING CURVES
FIGURE 3
STATUS TURN-ON AND TURN-OFF
TIMING
FIGURE 6
DC
A
NOTES:
1. Control input is compatible with CMOS or open collector TTL (with pull up resistor).
For bias voltages above 6V, a series resistor is required. Use the standard resistor
value equal to or less than the value found in Figure 8.
2. The rated input voltage is 5V for all tests unless otherwise specified.
3. To calculate the maximum ON resistance for a given junction temperature, find the
normalized ON resistance factor (NR) from Figure 4. Calculate the new ON resistance
as follows:
R(ON) = NR • RON @ 25°C
R(ON) =
D
TURN RELAY ON INTO A SHORTED LOAD
21Apk
250uSEC
(KD00CK, LD00CM, KD02CK, LD02CM)
NR(RON @ +25°C ) + .025 ohm
(KD20CK, LD20CM, KD22CK, LD22CM)
4. Overload testing to the requirements of MIL-R-28750 is constrained to the limits
imposed by the short circuit protection characteristics as defined in this specification.
System series inductance for “shorted-load” mode of operation should be 50 µH.
Maximum repetition rate into a shorted load should not exceed 10 Hz.
5. A status pull up resistor is required for proper operation of the status output.
Determine the current (Iso) required by the status interface. Calculate the current (Is)
through the status resistor such that the sink current through the status output is 0.6
mA. Select the status resistor such that it does not allow more than 0.6 mA to flow
through the status output.
VSTATUS - 0.4V
RSTATUS =
Iso
6. Inductive loads should be diode suppressed. Input transitions should be ≤ 1 ms
duration and the input drive should be a bounceless contact type.
SHORT-CIRCUIT LOAD WITH RELAY ON
130ApK
250uSEC
TYPICAL TRIP CURRENT CHARACTERISTICS
FOR SHORT CIRCUIT CONDITIONS
FIGURE 9