classification of fire resistance fires-cr-012-14-aure

advertisement
CLASSIFICATION OF FIRE RESISTANCE
FIRES-CR-012-14-AURE
Non-loadbearing wall made of self-supporting double skin metal faced
insulating panels Paneltech PWW-S 150, with mineral wool core
This is an electronic version of a classification report which was made as a copy of classification report officially
issued in a paper form. The electronic version of a classification report shall be used only for informative
purpose. Any information listed in this classification report is the property of the sponsor and shall not be used
or published without written permission. Contents of this file may only be modified by the editor i.e.
FIRES, s.r.o., Batizovce. Sponsor is allowed to publish this classification report in parts only with written
permission of the editor.
FIRES 004/S2-20/12/2012-E-el
CLASSIFICATION OF FIRE RESISTANCE
IN ACCORDANCE WITH
EN 13501-2: 2007 + A1: 2009
with extended field of application
FIRES-CR-012-14-AURE
Name of the product: Non-loadbearing wall made of self-supporting double skin metal faced insulating
panels Paneltech PWW-S 150, with mineral wool core
Sponsor:
PANELTECH Sp.z o.o.
ul. Michałkowicka 24
41-508 Chorzów
Poland
Prepared by:
FIRES, s.r.o.
Approved Body No. SK01
Osloboditeľov 282
059 35 Batizovce
Slovak Republic
Notified Body No.:
1396
Task No.:
Date of issue:
PR-14-0066
20. 02. 2014
Reports:
Copy No.:
3
2
Distribution list:
Copy No. 1
Copy No. 2
Copy No. 3
FIRES, s. r. o., Osloboditeľov 282, 059 35 Batizovce, Slovak Republic
(electronic version)
PaNELTECH Sp.z o.o., ul. Michałkowicka 24, 41-508 Chorzów, Poland
(electronic version)
PaNELTECH Sp.z o.o., ul. Michałkowicka 24, 41-508 Chorzów, Poland
This classification report consists of 4 pages and may only be used or reproduced in its entirety.
This report includes accreditation mark SNAS with additional mark ILAC-MRA. SNAS is signatory of ILAC-MRA, Mutual recognition
agreement (of accreditation), which is focused on promoting of international acceptance of accredited laboratory data and reducing
technical barriers to trade, such as the retesting of products on markets of signatories. More information about ILAC-MRA is on
www.ilac.org. Signatories of ILAC-MRA are e.g. SNAS (Slovakia), CAI (Czech Republic), PCA (Poland), DakkS (Germany) or BMWA
(Austria). Up to date list of ILAC-MRA signatories is on www.ilac.org/documents/mra_signatories.pdf. FIRES, s.r.o. Batizovce is full
member of EGOLF also, more information www.egolf.org.uk.
FIRES 147/S-22/03/2010-E
FIRES, s.r.o., Osloboditeľov 282, 059 35 Batizovce, Slovak Republic
tel. 00421 52 775 22 98, fax. 00421 52 788 14 12, www.fires.sk
Notified Body No. 1396, Approved Body No. SK01, Member of EGOLF
FIRES-CR-012-14-AURE
1.
INTRODUCTION
This classification report defines the resistance to fire classification assigned to element Non-loadbearing
wall made of self-supporting double skin metal faced insulating panels Paneltech PWW-S 150, with
mineral wool core in accordance with the procedures given in EN 13501-2: 2007 + A1: 2009.
2.
DETAILS OF CLASSIFIED PRODUCT
2.1 GENERAL
The element, Non-loadbearing wall made of self-supporting double skin metal faced insulating panels
Paneltech PWW-S 150, with mineral wool core is defined as a non-loadbearing wall with fire separating
function used as either partition or external wall acc. to EN 14509.
2.2 PRODUCT DESCRIPTION
Non-loadbearing wall is made of horizontally oriented double skin metal faced insulating panels Paneltech
PWW-S 150, 150 mm thick with mineral wool core and symmetrical joints.
Panel width
Panel thickness
1190 mm
150 mm
Panel core
The lamellas of mineral wool (Rockwool Polska Sp. z o.o., Poland), with nominal bulk density 105 kg.m-3,
fibres melting point > 1000 oC, orientation of fibres: across the steel sheet surface, type of binder: PUF
phenol-formaldehyde resin, amount 4% (Rockwool Polska Sp. z o.o., Poland). The core is glued to the
facing by two components adhesive, amount 400 g.m-2 (DOW Polska Sp. z o.o., Poland).
Panel covering
- interior steel sheet 0,60 mm thick, grade of metal S280 (Tata Myriad, France) with SP Polyester
organic coating 25 µm thick, RAL 9010, profile geometry: stepped,
- exterior steel sheet 0,60 mm thick, grade of metal S280 (Tata Myriad, France) with SP Polyester
organic coating 25 µm thick, RAL 9010, profile geometry: stepped.
The sealant EVERFLEX 700T (Ever Build, UK) or other sealant of the same type if its ignition temperature
is higher or equal to the ignition temperature of EVERFLEX 700T is applied between the panels inside the
joints on the both faces.
The joints of the panels are not stitched.
More detailed information about product construction and manufacturers of materials is shown in the test
report (see the clause 3.1 of the report [1]).
2.3 PRODUCT FIXING
Each sandwich panel is fixed to two vertical supports by steel screws ∅ (5,5/6,3 x 185) mm. Screws are
placed in distance 300 mm from the panels edges. Amount of the screws: 4 pcs per panel.
Supports, load-bearing profiles are placed in distance 3000 mm.
3.
EXTENDED APPLICATION REPORT AND TEST RESULTS USED FOR CLASSIFICATION
No.
[1]
Name of laboratory
FIRES, s.r.o.,
Batizovce, SK
FIRES 147/S-22/03/2010-E
Name of sponsor
PANELTECH Sp.z o.o.,
41-508 Chorzów, Poland
EXAP report No.
Date of issue
FIRES-ER-001-14-NURE
20. 02. 2014
Page: 2
FIRES-CR-012-14-AURE
4.
CLASSIFICATION AND FIELD OF APPLICATION
4.1 REFERENCE OF CLASSIFICATION
Classification of partition has been carried out in accordance with EN 13501-2: 2007 + A1: 2009, clause
7.5.2.
Classification of external wall has been carried out in accordance with EN 13501-2: 2007 + A1: 2009,
clause 7.5.3.
4.2 CLASSIFICATION
4.2.1 CLASSIFICATION OF PARTITION
The element, Non-loadbearing wall made of self-supporting double skin metal faced insulating panels
Paneltech PWW-S 150, with mineral wool core is classified according to the following combinations of
performance parameters and classes as appropriate.
Fire resistance classification:
E 120 / EI 120 / EW 120
E 120 1) / EI 180 / EW 120
1)
1)
Condition:
B, C (12 000 mm)
B
EN 13501-2, paragraph 7.5.2.4 does not define classes E 180 and EW 180 but the product meets
criteria of integrity and radiation during 180 minutes
Condition A means: Classification is valid for product without change in orientation of panels and there
is allowed to increase the span length up to 12 000 mm provided that panel joints
are stitched every 3 000 mm (in accordance with EN 15254-5).
Condition B means: Classification is valid for product with vertically or horizontally oriented panels
and there is allowed to increase the span length up to 4 000 mm without stitching
of joints provided that expansion allowances are increased pro-rata (in accordance
with EN 14509 and EN 1364-1).
Condition B1 means: Classification is valid for product with vertically or horizontally oriented panels,
without stitching of joints and there is not allowed to increase the span length (in
accordance with EN 14509 and EN 1364-1).
Condition C means: Maximum allowed span without stitching of joints and without change in orientation
of panels (obtained by calculation according to annex B of EN 15254-5).
4.2.2 CLASSIFICATION OF EXTERNAL WALL
The element, Non-loadbearing wall made of self-supporting double skin metal faced insulating panels
Paneltech PWW-S 150, with mineral wool core is classified according to the following combinations of
performance parameters and classes as appropriate.
Fire resistance classification:
E 120 (o↔i) / EI 120 (o↔i) / EW 60 (o↔i) 1)
E 120 (o↔i) 2) / EI 120 (o↔i) 2) / EW 60 (o↔i) 2)
Condition:
B, C (12 000 mm)
B
1)
EN 13501-2, paragraph 7.5.3.4 does not define class EW 120 (o↔i) but the product meets criteria
of radiation during 120 minutes
2)
EN 13501-2, paragraph 7.5.3.4 does not define class E 180 (o↔i), EI 180 (o↔i) and EW 180 (o↔i)
but the product meets criteria of integrity, insulation and radiation during 180 minutes
Condition A means: Classification is valid for product without change in orientation of panels and there
is allowed to increase the span length up to 12 000 mm provided that panel joints
are stitched every 3 000 mm (in accordance with EN 15254-5).
FIRES 147/S-22/03/2010-E
Page: 3
FIRES-CR-012-14-AURE
Condition B means: Classification is valid for product with vertically or horizontally oriented panels
and there is allowed to increase the span length up to 4 000 mm without stitching
of joints provided that expansion allowances are increased pro-rata (in accordance
with EN 14509 and EN 1364-1).
Condition B1 means: Classification is valid for product with vertically or horizontally oriented panels,
without stitching of joints and there is not allowed to increase the span length (in
accordance with EN 14509 and EN 1364-1).
Condition C means: Maximum allowed span without stitching of joints and without change in orientation
of panels (obtained by calculation according to annex B of EN 15254-5).
4.3 FIELD OF APPLICATION
According to clause 5.2 of the report [1].
5.
LIMITATIONS
This classification document does not represent type approval or certification of the product.
The classification is valid provided that the product, field of application and standards and regulations
are not changed.
Approved:
Signed:
Ing. Štefan Rástocký
leader of the testing laboratory
Bc. Dávid Šubert
technician of the testing laboratory
FIRES 147/S-22/03/2010-E
Page: 4
Download