ADR-3000 Control Panels Analog Addressable Fire Alarm Control Panel Technical Manual TELEFIRE FIRE & GAS DETECTORS LTD PO Box 7036 Petach Tikva 49250 Israel Tel: 972 3 970 0400 Fax: 972 3 921 1816 eMail: info@telefire.co.il Web: www.telefire.co.il ADRADR-3000En 3000En122 En122.pdf 122.pdf Revision 1.22 March 2013 i Note The terms “Trouble” as used in NFPA 72 guideline and UL standards and “Fault” as used in EN 54 standards are used interchangeably throughout this manual. ADR-3000 © 1999 – 2013 Telefire Fire & Gas Detectors Ltd Revision 1.22 March 2013 Table of Contents 1 SYSTEM INTRODUCTION ............................................................................ 1 2 ADR-3000 FIRE ALARM CONTROL PANEL ................................................ 2 3 2.1 ADR-3001 MAIN BOARD ................................................................................ 3 2.2 ADR-3002 AND ADR-3002C LINE CARDS ....................................................... 4 2.3 ADR-3003 DISPLAY AND KEYBOARD MODULE ................................................. 5 2.4 ADR-4004TSW SWITCHING POWER SUPPLY .................................................. 5 2.5 LON-3000/7000 NETWORK COMMUNICATION MODULE .................................... 6 2.6 NET-3000 INTERNET ENABLED MONITORING AND NOTIFICATION MODULE ........ 6 2.7 GIM-232 GALVANIC ISOLATION MODULE FOR RS-232 INTERFACE .................... 7 2.8 RM-4005 REMOTE PANEL AND ANNUNCIATOR ................................................. 8 INITIATING DEVICES, NOTIFICATION APPLIANCES, AND ACCESSORIES ............................................................................................. 9 3.1 TFO-480A ANALOG ADDRESSABLE PHOTOELECTRIC SMOKE DETECTOR .......... 9 3.2 TFO-440A ANALOG ADDRESSABLE PHOTOELECTRIC SMOKE DETECTOR ........ 10 3.3 TPH-482A ANALOG ADDRESSABLE MULTISENSOR PHOTOELECTRIC SMOKE / HEAT DETECTOR.......................................................................................... 10 3.4 TPH-442A ANALOG ADDRESSABLE MULTISENSOR PHOTOELECTRIC SMOKE / HEAT DETECTOR.......................................................................................... 11 3.5 TFH-280A ANALOG ADDRESSABLE HEAT DETECTOR ..................................... 11 3.6 TFH-220A ANALOG ADDRESSABLE HEAT DETECTOR ..................................... 12 3.7 TFB-180 COMMON BASE FOR ANALOG ADDRESSABLE DETECTORS ................ 12 3.8 TFB-110A COMMON BASE FOR ANALOG ADDRESSABLE DETECTORS ............. 12 3.9 TFL-1AN AUXILIARY INDICATOR FOR ANALOG DETECTORS ............................ 13 3.10 TPB-800ASR MANUAL FIRE ALARM CALL POINT AND TPB-800ASY MANUAL EXTINGUISHING CALL POINT ......................................................................... 13 3.11 ADR-805 FLOW SWITCH INTERFACE MODULE ............................................... 13 3.12 ADR-812 TWO-CHANNEL INPUT MODULE ...................................................... 14 3.13 ADR-818 EIGHT-CHANNEL INPUT MODULE.................................................... 15 3.14 ADR-828 EIGHT-CHANNEL OUTPUT MODULE ................................................ 15 3.15 ADR-823 THREE-CHANNEL INPUT/OUTPUT MODULE ..................................... 16 3.16 ADR-833 EXTINGUISHING CONTROL UNIT ..................................................... 17 3.17 LI-3000 LINE ISOLATION MODULE FOR CLASS A/B ......................................... 18 3.18 TIP-224A ANALOG ADDRESSABLE INDOOR ALARM NOTIFICATION SOUNDER ... 19 3.19 TPS-34A ANALOG ADDRESSABLE AUXILIARY POWER SUPPLY ........................ 19 — I — ADR-3000 © 1999 – 2013 Telefire Fire & Gas Detectors Ltd 4 5 6 7 8 Revision 1.22 March 2013 3.20 EPI-3000 ELECTROMAGNETIC AND SURGE PROTECTION INTERFACE MODULE. 20 3.21 TFP-3000 FIREMAN PHONE ......................................................................... 20 SOFTWARE AND TOOLS ........................................................................... 22 4.1 TCS-3040 PROGRAMMING AND CONTROL SOFTWARE FOR THE ADR-3000..... 22 4.2 MCS-3000 CENTRALIZED FIRE ALARM SYSTEMS MONITORING SOFTWARE ..... 22 4.3 PROG-4000 ANALOG ADDRESSABLE DETECTOR AND ACCESSORY PROGRAMMER ............................................................................................. 22 INSTALLATION ........................................................................................... 23 5.1 CAPACITY PLANNING .................................................................................... 23 5.2 POWER REQUIREMENT CALCULATION ........................................................... 23 5.3 LAYING W IRING ............................................................................................ 23 5.4 INSTALLING DETECTORS, I/O MODULES AND OTHER EQUIPMENT .................... 24 5.5 CABINET MOUNTING ..................................................................................... 24 5.6 CONNECT AC / SLC LOOPS, 24V OUT, ALARM / TROUBLE / DIALER / HORN ..... 25 5.7 PERFORM AUTO PROGRAM........................................................................... 25 5.8 ENTER DESCRIPTIONS .................................................................................. 26 5.9 PROGRAM ACTIVATION MATRICES ................................................................. 26 5.10 COPY .ANL TO ADR-3000 ........................................................................... 26 5.11 WALK TEST ................................................................................................. 26 5.12 TEST ACTIVATIONS ....................................................................................... 26 5.13 CHANGE PASSWORDS .................................................................................. 26 5.14 TERMINAL SPECIFICATION............................................................................. 27 5.15 WIRING ....................................................................................................... 30 5.16 DOCUMENTATION ......................................................................................... 32 SYSTEM DISPLAY AND KEYBOARD ........................................................ 33 6.1 ALPHANUMERIC DISPLAY .............................................................................. 34 6.2 INDICATING LEDS ........................................................................................ 34 6.3 OPERATOR KEYS ......................................................................................... 35 6.4 NUMERIC AND ARROW KEYS ......................................................................... 35 6.5 PROGRAMMING KEYS ................................................................................... 36 SYSTEM SCREENS..................................................................................... 37 7.1 NORMAL OPERATION SCREEN ...................................................................... 37 7.2 MAIN MENU SCREEN .................................................................................... 37 SYSTEM PROGRAMMING .......................................................................... 38 8.1 SYSTEM PROGRAM MENU............................................................................. 38 8.2 DEVICE PROGRAMMING ................................................................................ 39 — II — ADR-3000 © 1999 – 2013 Telefire Fire & Gas Detectors Ltd 9 Revision 1.22 March 2013 8.3 CONDITIONAL ACTIVATION OF OUTPUT DEVICES (ACTIVATION MATRIX) ........... 40 8.4 EDITING DEVICE DESCRIPTION ...................................................................... 45 8.5 STORING DATA IN MEMORY .......................................................................... 45 8.6 TIME PROGRAMMING .................................................................................... 46 8.7 SYSTEM CONFIGURATION ............................................................................. 46 8.8 DAY / NIGHT PROGRAMMING ........................................................................ 47 8.9 CHANGE PASSWORD .................................................................................... 47 8.10 DETECTORS INIT .......................................................................................... 48 8.11 DIAGNOSTICS .............................................................................................. 48 OPERATION AND MAINTENANCE ............................................................ 50 9.1 ON/OFF DEVICE.......................................................................................... 50 9.2 MONITOR TEST ............................................................................................ 51 9.3 PRINTER REPORTS....................................................................................... 51 9.4 DISPLAY REPORTS ....................................................................................... 52 9.5 UTILITIES ..................................................................................................... 53 9.6 WALK TEST ................................................................................................. 54 10 ALARM, TROUBLE, AND SUPERVISORY CONDITIONS ......................... 56 10.1 ALARM EVENTS ............................................................................................ 56 10.2 TROUBLE EVENTS ........................................................................................ 58 10.3 SUPERVISORY EVENTS ................................................................................. 59 11 PEER TO PEER NETWORK........................................................................ 61 11.1 NETWORK CHARACTERISTICS ....................................................................... 61 11.2 NETWORK CONFIGURATION .......................................................................... 61 11.3 NETWORK HIERARCHY ................................................................................. 62 12 SYSTEM FUSES .......................................................................................... 65 12.1 POWER SUPPLY FUSES ................................................................................ 65 12.2 MAIN BOARD FUSES ..................................................................................... 65 12.3 LINE CARD FUSES ........................................................................................ 66 13 PERIODIC TESTING .................................................................................... 67 13.1 WEEKLY INSPECTION – PERFORMED BY THE SITE'S SAFETY SUPERVISOR........ 67 14 WARNINGS AND LIMITATIONS ................................................................. 68 15 TROUBLESHOOTING ................................................................................. 69 15.1 SYSTEM FAILURE ......................................................................................... 69 15.2 REMOTE ANNUNCIATOR PANEL (RM-4005) FAILURE ...................................... 71 15.3 ADDRESSABLE DEVICES FAILURE .................................................................. 71 — III — ADR-3000 © 1999 – 2013 Telefire Fire & Gas Detectors Ltd Revision 1.22 March 2013 15.4 PROGRAMMING TROUBLE ............................................................................. 71 15.5 LONW ORKS TROUBLE .................................................................................. 72 16 DETECTOR SENSITIVITY SELECTION...................................................... 73 16.1 SMOKE DETECTOR SENSITIVITY SELECTION TABLE ........................................ 73 16.2 HEAT DETECTOR SENSITIVITY TABLE ............................................................ 73 16.3 MULTISENSOR PHOTOELECTRIC / HEAT DETECTOR SETTING .......................... 73 17 POWER SUPPLY AND BATTERY CALCULATIONS ................................. 74 18 WIRE CHARACTERISTICS AND LENGTH LIMITATIONS ......................... 77 18.1 WIRE CHARACTERISTICS’ INFLUENCE ON SYSTEM PERFORMANCE .................. 77 18.2 SLC LOOP W IRE .......................................................................................... 77 18.3 NAC (NOTIFICATION APPLIANCE CIRCUIT) ..................................................... 78 18.4 24VDC OUTPUT ........................................................................................... 78 18.5 LON-3000/7000 NETWORK W IRING – COPPER CABLES ................................. 78 18.6 LON-3000/7000 NETWORK W IRING – FIBER-OPTICS CABLES ........................ 78 18.7 RM-4005 CABLING ...................................................................................... 78 19 COMPATIBILITY .......................................................................................... 79 19.1 INPUT DEVICES ............................................................................................ 79 19.2 OUTPUT DEVICES......................................................................................... 79 19.3 OTHER DEVICES .......................................................................................... 79 20 WARNINGS AND LIMITATIONS ................................................................. 80 21 STANDARDS COMPLIANCE ...................................................................... 81 21.1 EN 54 – OPTIONS WITH REQUIREMENTS ....................................................... 81 21.2 CP-10 ......................................................................................................... 81 22 SPECIFICATION .......................................................................................... 82 23 CERTIFICATION .......................................................................................... 83 — IV — ADR-3000 © 1999 – 2013 Telefire Fire & Gas Detectors Ltd 1 Revision 1.22 March 2013 System Introduction The ADR-3000 intelligent fire alarm control panel monitors various analog addressable initiating devices such as ionization and photoelectric smoke detectors, heat detectors, flow switches and manual fire alarm call points. The ADR-3000 intelligent fire alarm control panel controls notification devices such as alarm bells, horns, strobe lights, annunciators, and automatic dialers as well as automatic extinguishers. Non-addressable initiating devices can be connected to the system via analog addressable input modules. Non-addressable output devices can be connected to the general outputs or via analog addressable output modules. The ADR-3000 provides individual control and supervision of each analog addressable device. Sensitivity adjustment, pre-alarm, maintenance and malfunction levels can be set for each device independently. Advanced conditional activation for each output device can be preformed from a single control panel or a multi-unit network. Unlike conventional systems, the ADR-3000 enables processing of analog signals received from detectors, compensation of environment changes and drifts caused by dust accumulation, while the alarm threshold setting values remains unaffected. The system configuration allows considerable flexibility to in planning and installation, starting as small as a single control panel with one SLC loop (127 addresses), and enhanced by connecting two or more (as many as 32) control panels located in one or several buildings in a peer-to-peer network, thus expanding the ADR-3000’s capacity beyond 508 addresses and up to as many as 16,256 addresses. Each control panel on the network can respond to alarm and trouble events that occurred in other control panels. Figure 1 Typical ADR-3000 fire alarm system – Page 1 of 83 – ADR-3000 © 1999 – 2013 Telefire Fire & Gas Detectors Ltd 2 Revision 1.22 March 2013 ADR-3000 Fire Alarm Control Panel The ADR-3000 control panel provides user-friendly operation. The keyboard and the display that are mounted on the front panel contain an illuminated alphanumeric LCD, LED indicators for major events, and functional keys. Access to all operations is secured by multi-level passwords. The interior section of the cabinet is secured by a key-lock. It contains a power supply, the main board, line card(s), battery compartment space, and optional communication modules. The ADR-3000’s main board can contain one or two line cards, enabling control of as many as 508 addressable initiating devices, notification appliances and I/O modules. The ADR-3002 Single Loop Card controls as many as 127 addressable devices in a twowire Class B or Class A SLC loop. The ADR-3002C Dual Loop Card controls as many as 254 Addressable devices in two two-wire Class B or Class A SLC loops. The system can be expanded beyond 508 addresses by networking. An optional LON-3000/7000 network communication module allows the connection of as many as 32 control panels to set up a peer-to-peer network. With appropriate programming each control panel on the network is able to respond to alarm and trouble events that occurred in other control panels. The control panel has an integral real time clock and calendar that enables day and night sensitivity setting for each analog detector according to weekly operation schedule and working hours. Daytime and nighttime hours can be programmed independently for each day of the week. Events such as alarm, trouble, silencing, reset, programming, etc., are stored in the ADR-3000’s memory in the order in which they occur, creating event-list history. An event record contains date, time, device type, and additional details. Event records can be displayed on screen and printed as a report. All operations and configuration can be performed either from the system’s front panel or from a PC. Telefire’s user-friendly proprietary programming and control software (running on Windows XP or Windows 98™ operating system) allows operators/installers to easily configure any system parameter using its advanced graphical interface. – Page 2 of 83 – ADR-3000 © 1999 – 2013 Telefire Fire & Gas Detectors Ltd Figure 2 2.1 Revision 1.22 March 2013 Internal module location in the ADR-3000 cabinet ADR-3001 Main Board The ADR-3001 main board is designed for ease of maintainability. Connectors are located in logical groups; power input from the power supply and easily accessible fuses are on the left side of the ADR-3001 board. Alarm, Trouble, SLC loops and 24Vdc output for each loop card, horn and dialer are on the bottom. Connections to the keyboard and display board; LON-3000/7000 networking module; an RS-232 port for NET-3000, PC, printer, or the GIM-232 galvanic isolation modules; and a connector for RM-4005 remote panels are located on the right. Figure 3 2.1.1 ADR-3001 Main board Low-Voltage Connections The ADR-3000 can interface and activate various output devices that are connected to the addressable loop or directly to the control panel’s general outputs as follows: Alarm outputs Two sets of dry contacts and a programmable level activated supervised output. Trouble outputs Dry contacts and a level activated supervised output. – Page 3 of 83 – ADR-3000 © 1999 – 2013 Telefire Fire & Gas Detectors Ltd Revision 1.22 March 2013 General outputs Supervised reverse polarity horn output; supervised level activated dialer output and two 24Vdc outputs for remote devices. COM-1 (RS-232) Connection to computer, serial printer, GIM-232 module or the NET-3000 Internet Enabled Monitoring and Notification Module. COM-2 (RS-485) Connection to as many as 16 RM-4005 remote panels. LON-COM Connection to the LON-3000/7000 Network Communication Module. The LON-3000/7000 provides control panel peer-to-peer or Master – slave internetworking. SLC Signaling Line Circuit – for connection of analog addressable initiating devices, I/O modules, and notification appliances. One to four SLC loops can be connected to the ADR-3000. Each loop can address as many as 127 devices. 2.2 ADR-3002 and ADR-3002C Line Cards The ADR-3002 and ADR-3002C line cards are mounted on the ADR-3001 main board. System configuration and capacity requirements will determine the appropriate card type. The card controls the bi-directional communication between the control panel and the analog addressable devices on the SLC loop. The loop is electronically protected against shorts, and will be automatically disconnected if a short is sensed. Each line card contains a loop fuse as a secondary protection. Two LEDs for each loop indicate loop condition and serve installers and technicians: • The red LED flashes each time a device is addressed • The yellow LED flashes when a fault is detected, even after a momentary interference that would not activate a trouble condition 2.2.1 Maximum Addressing Capacity As each SLC loop can address as many as 127 devices, the maximum addressing capacity of a single ADR-3000 is 508 addresses. The following table shows the maximum configurable addressing capacity with all possible combinations of ADR-3002 and ADR-3002C line cards in the ADR-3000. Left Right Loops Addresses ADR-3002 – 1 127 ADR-3002 ADR-3002 2 254 3 381 4 508 ADR-3002C ADR-3002 – ADR-3002C ADR-3002C ADR-3002 ADR-3002C ADR-3002C Table 1 Line card combinations – Page 4 of 83 – Figure 4 Line cards ADR-3000 © 1999 – 2013 Telefire Fire & Gas Detectors Ltd 2.3 Revision 1.22 March 2013 ADR-3003 Display and Keyboard Module The ADR-3003 Display and Keyboard Module include system indicators, display and keyboard. System indicators and keyboard conform to both EN 54 and UL 864 standards. The alphanumeric display is a 4 row by 40 characters backlit Liquid Crystal Display (LCD). Figure 5 2.4 ADR-3003 Keyboard and display ADR-4004TSW Switching Power Supply The ADR-4004TSW is a standard switching power supply that is common to the ADR-3000 and the TPS-34A. The ADR-3000 should be connected to a separate dedicated 230Vac fire alarm circuit, labeled “FIRE ALARM”. The primary power circuit must be connected to the line side of the main power feed of the protected premises. No other appliance may be connected to the “FIRE ALARM” circuit. The power cables must run directly, without disconnecting devices, from the power source to the control panel. Wires, circuit breaker or any overcurrent protection device should comply with local electrical wiring codes. The power cable should enter the control panel through either the top left or bottom left knockout hole. Use a plastic bushing that fits the opening. Connect the Live and Neutral wires to the proper terminal. Connect the ground wire to the ground terminal. Figure 6 ADR-4004TSW Power supply module – Page 5 of 83 – ADR-3000 © 1999 – 2013 Telefire Fire & Gas Detectors Ltd 2.5 Revision 1.22 March 2013 LON-3000/7000 Network Communication Module The LON-3000/7000 is a communication module that enables connection between control panels to establish a network. A two-wire copper cable connection is required to interconnect between the control panels. Optionally fiber-optic connection is made possible with additional modules. The length of the wires depends on the connection topology and media type (copper or fiber optic). Please refer to the LON-3000/7000 technical manual for further details. Figure 7 2.5.1 LON-3000/7000 Networking communication module Topology An ADR-3000 LonWorks network can connect from 2 and up to as many as 32 ADR-3000 control panels in a peer-to-peer or Master – slave network. The physical topology of the network may be bus (figure 8), ring (figure 9) or free (figure 10) topology. Logical hierarchy may be peer-to-peer – where all messages are reported in all control panels, master/slave – where slave messages are reported on master control panels, or a combination of the two. Ring topology requires LR-01 or LRW-102 Fiber Optic Repeaters. Please refer to the LON-3000/7000 technical manual for further details. 2.6 NET-3000 Internet Enabled Monitoring and Notification Module The ADR-3000’s internet-enabled features allow it to provide fire alarm control panel monitoring over LAN, WAN, or Internet using a standard web browser or Telefire’s proprietary TCS-3040 software, and distribute alarm and trouble events via a built-in web server, e-mail notification and SMS paging. – Page 6 of 83 – ADR-3000 © 1999 – 2013 Telefire Fire & Gas Detectors Ltd Figure 8 2.7 Revision 1.22 March 2013 Remote control by TCP/IP NET-3000 module GIM-232 Galvanic Isolation Module for RS-232 Interface The GIM-232 Galvanic Isolation Module for RS-232 interface allows the connection of grounded serial devices such as a PC or a serial printer to the ADR-3000 to be free of ground fault disturbance. When connecting a PC or a printer to the control panel, place the GIM-232 in the lower part of the internal mounting plate (see figure 2). Usually laptop computers are not grounded; therefore do not require the galvanic isolation module. Both jumpers should be in the lower position (PC) when connecting a PC to the control panel’s RS-232 port. Both jumpers should be in the upper position (PRINTER) when connecting a printer to the control panel’s RS-232 port. Both the GIM-232 jumpers and the ADR-3000’s COM-1 port should be configured similarly. Please refer to “System Configuration” on page 11 for further details. Figure 9 GIM-232 Module – Page 7 of 83 – ADR-3000 © 1999 – 2013 Telefire Fire & Gas Detectors Ltd Revision 1.22 March 2013 Figure 10 GIM-232 Connection 2.8 RM-4005 Remote Panel and Annunciator The RM-4005 Remote Panel and Annunciator enables control and supervision of the ADR-3000 fire alarm control panel from remote locations and key positions such as security officer, premises manager, or maintenance office. The RM-4005 remote panel consists of an LCD display, keyboard, internal buzzer, and features such as alarm output, trouble output, and an interface relay that reduces the need for additional input/output interface modules. The remote panels are connected to the main control panel via a twisted wire pair (RS-485). As many as 16 remote panels can be connected to the control panel using the same cable. Each remote panel should be configured with a unique address in the range of 1 to 16. The communication and input/output circuits are fully supervised. In large systems incorporating several control panels connected via a peer-to-peer network as many as 16 remote panels can be connected to each of the control panels. The RM-4005 operates with a 24Vdc power source that can be supplied from the main control panel or an auxiliary power supply such as Telefire’s TPS-34A Analog Addressable Auxiliary Power Supply. Please refer to the RM-4005 technical manual for further details. Figure 11 RM-4005 Event flow – Page 8 of 83 – ADR-3000 © 1999 – 2013 Telefire Fire & Gas Detectors Ltd 3 Revision 1.22 March 2013 Initiating Devices, Notification Appliances, and Accessories All Telefire’s analog addressable detectors can be connected to the system using a twowire connection. Each initiating device contains its own addressing circuit. The address is stored in the detector’s memory and can be programmed or verified by using the PROG-4000 programmer. Each detector is equipped with an indicating LED that has 360° visibility. This LED flashes during normal operation and latches on during alarm. Each detector has an output for an external indicating lamp. The sensitivity of any detector in the system may be individually configured in two alarm settings (day- and night-sensitivity), and a prealarm setting. Contamination is a by-product of normal operation and may be caused by various sources, most of which are impossible to eliminate. Accumulation of dust and dirt over time may affect a detector’s performance. The system continuously compensates for these contamination effects using a drift compensation algorithm up to the point in which the sensor requires cleaning. The control panel will indicate that maintenance is required by issuing a maintenance alarm message. Telefire's ADR-3000 Analog Addressable Fire Alarm Control Panel is easily expandable with a variety of analog addressable I/O modules. These modules allow the interfacing of non-addressable devices such as conventional detectors, horns, relays, extinguishers, etc., in order to take advantage of the ADR-3000’s flexibility and advanced capabilities. All the ADR-81X and ADR-82X I/O modules are connected to the SLC analog line. They are powered from an external 24Vdc power source that can be supplied either from the main control panel or an auxiliary power supply such as Telefire’s TPS-34A Analog Addressable Auxiliary Power Supply. The ADR-805 connects to the SLC loop and does not require 24Vdc input. 3.1 TFO-480A Analog Addressable Photoelectric Smoke Detector Telefire’s TFO-480A is an advanced analog addressable photoelectric smoke detector that offers the following advantages: • It is considered “green” (environment friendly), as it does not contain radioactive materials. • The TFO-480A contains a powerful microprocessor that performs initial signal processing locally. The final processing and decision making is performed by the control panel. • The TFO-480A's microprocessor offers a high level of noise immunity and performs drift compensation in order to overcome environmental changes and dust accumulation in the chamber. Once the detector is no longer able to compensate the control panel will display a trouble signal requesting cleaning. The microprocessor also performs signal processing, enables accurate control of the photoelectric chamber according to parameters set at the control panel, and manages the communication process with the control panel. • The TFO-480A detector excels in sensing smoldering smoke and smoke from burning of various materials. The detector consists of a vented chamber (labyrinth), an infrared transmitter and a receiver that detects light scattering from the smoke particles in the chamber. The detector’s sensitivity can be adjusted from the control panel within the range of 0.8% – 2.0%/foot (obscuration) in 0.2% increments. – Page 9 of 83 – ADR-3000 © 1999 – 2013 Telefire Fire & Gas Detectors Ltd Revision 1.22 March 2013 The detector contains an alarm LED that has 360° visibility. This LED flashes during normal operation and is latched on during an alarm. The TFO-480A is designed to protect indoor fire risk areas, except environments where smoke, steam, dust, or corrosive gasses are present under normal conditions. Optical smoke detectors should be used for detecting smoldering fires in corridors and along escape routes, wood- or paper stores, electric cabinets, etc., They should not be used in steamy, dusty, or smoky areas such as kitchens, bathrooms, saunas, laundries, etc. Please refer to the TFO-480A technical manual for further details. 3.2 TFO-440A Analog Addressable Photoelectric Smoke Detector Telefire’s TFO-440A is an advanced analog addressable photoelectric smoke detector that offers the following advantages: • It is considered “green” (environment friendly), as it does not contain radioactive materials. • The TFO-440A contains a powerful microprocessor that performs initial signal processing locally. The final processing and decision making is performed by the control panel. • The TFO-440A's microprocessor offers a high level of noise immunity and performs drift compensation in order to overcome environmental changes and dust accumulation in the chamber. Once the detector is no longer able to compensate the control panel will display a trouble signal requesting cleaning. The microprocessor also performs signal processing, enables accurate control of the photoelectric chamber according to parameters set at the control panel, and manages the communication process with the control panel. • The TFO-440A detector excels in sensing smoldering smoke and smoke from burning of various materials. The detector consists of a vented chamber (labyrinth), an infrared transmitter and a receiver that detects light scattering from the smoke particles in the chamber. The detector’s sensitivity can be adjusted from the control panel within the range of 0.8% – 2.0%/foot (obscuration) in 0.2% increments. The detector contains an alarm LED that has 360° visibility. This LED flashes during normal operation and is latched on during an alarm. The TFO-440A is designed to protect indoor fire risk areas, except environments where smoke, steam, dust, or corrosive gasses are present under normal conditions. Optical smoke detectors should be used for detecting smoldering fires in corridors and along escape routes, wood- or paper stores, electric cabinets, etc., They should not be used in steamy, dusty, or smoky areas such as kitchens, bathrooms, saunas, laundries, etc. Please refer to the TFO-440A technical manual for further details. 3.3 TPH-482A Analog Addressable Multisensor Photoelectric Smoke / Heat Detector. Telefire's TPH-482A is a microprocessor-controlled multisensor detector that combines photoelectric and heat sensors for enhanced fire detection capabilities. The detector consists of a photoelectric sensing mechanism that contains a vented chamber (labyrinth), an infrared transmitter and a receiver that detects light scattered from the smoke particles in the chamber, and a thermal sensor that measures the ambient temperature. The detector uses a smart algorithm to analyze the physical – Page 10 of 83 – ADR-3000 © 1999 – 2013 Telefire Fire & Gas Detectors Ltd Revision 1.22 March 2013 parameters (smoke and heat), evaluate their values and trends, and dynamically modify its sensitivity. This process reduces occurrences of false alarms without reducing sensitivity to real fire. The TPH-482A offers the following advantages: • The TPH-482A's powerful microprocessor performs signal processing and enables precise control of the photoelectric chamber. The microprocessor offers a high level of noise immunity. The microprocessor also performs signal processing, enables accurate control of the photoelectric chamber according to pre-set parameters, and manages the communication process with the control panel. • The TPH-482A detector excels in sensing smoldering smoke and differentiating between fires and false alarms due to other events that produce heat or smoke, such as cooking. • It is considered “green” (environment friendly), as it does not contain radioactive materials. Please refer to the TPH-482A technical manual for further details. 3.4 TPH-442A Analog Addressable Multisensor Photoelectric Smoke / Heat Detector. Telefire's TPH-442A is a microprocessor-controlled multisensor detector that combines photoelectric and heat sensors for enhanced fire detection capabilities. The detector consists of a photoelectric sensing mechanism that contains a vented chamber (labyrinth), an infrared transmitter and a receiver that detects light scattered from the smoke particles in the chamber, and a thermal sensor that measures the ambient temperature. The detector uses a smart algorithm to analyze the physical parameters (smoke and heat), evaluate their values and trends, and dynamically modify its sensitivity. This process reduces occurrences of false alarms without reducing sensitivity to real fire. The TPH-442A offers the following advantages: • The TPH-442A's powerful microprocessor performs signal processing and enables precise control of the photoelectric chamber. The microprocessor offers a high level of noise immunity. The microprocessor also performs signal processing, enables accurate control of the photoelectric chamber according to pre-set parameters, and manages the communication process with the control panel. • The TPH-442A detector excels in sensing smoldering smoke and differentiating between fires and false alarms due to other events that produce heat or smoke, such as cooking. • It is considered “green” (environment friendly), as it does not contain radioactive materials. Please refer to the TPH-442A technical manual for further details. 3.5 TFH-280A Analog Addressable Heat Detector Telefire’s TFH-280A is an advanced analog addressable heat detector that combines two modes of operation – fixed temperature and rate of temperature rise. The detector contains a powerful microprocessor enabling accurate control of the heat sensing element, signal processing and two-way communication between the detector and the control panel. The TFH-280A heat detector can operate in either of two modes that can be configured at the control panel: – Page 11 of 83 – ADR-3000 © 1999 – 2013 Telefire Fire & Gas Detectors Ltd Revision 1.22 March 2013 Fixed temperature mode – the alarm point is selected between 50°C – 90°C in 1°C increments (122°F to 194°F in 1.8°F increments). • Combined mode – rate of temperature rise and fixed heat detection. In this mode the alarm threshold for the rate of temperature rise can be set between 7°C / minute and 13°C / minute (12.6°F / minute and 23.4°F / minute) and the fixed temperature threshold is 60°C (140°F). The ambient temperature, mode of operations, and alarm points can be observed at the control panel using the Monitor Test menu. Please refer to the TFH-280A technical manual for further details. • 3.6 TFH-220A Analog Addressable Heat Detector Telefire’s TFH-220A is an advanced analog addressable heat detector that combines two modes of operation – fixed temperature and rate of temperature rise. The detector contains a powerful microprocessor enabling accurate control of the heat sensing element, signal processing and two-way communication between the detector and the control panel. The TFH-220A heat detector can operate in either of two modes that can be configured at the control panel: • Fixed temperature mode – the alarm point is selected between 50°C – 90°C in 1°C increments (122°F to 194°F in 1.8°F increments). • Combined mode – rate of temperature rise and fixed heat detection. In this mode the alarm threshold for the rate of temperature rise can be set between 7°C / minute and 13°C / minute (12.6°F / minute and 23.4°F / minute) and the fixed temperature threshold is 60°C (140°F). The ambient temperature, mode of operations, and alarm points can be observed at the control panel using the Monitor Test menu. Please refer to the TFH-220A technical manual for further details. 3.7 TFB-180 Common Base for Analog Addressable Detectors The TFB-180 is a standard common base that enables connection between Telefire’s plug-in analog addressable detectors and a Telefire's analog addressable control panels. The base is compatible with a following of Telefire's analog addressable detectors: a. TFO-480A b. TPH-482A c. TFH-280A Please refer to the respective detector’s technical manual for a more detailed description This base is intended for indoor installation in false or regular ceilings. Signaling Line Circuit (SLC) loop wires and the optional TFL-1AN Auxiliary Signaling Indicator connections may be connected either vertically or horizontally. Please refer to the TFB-180 technical manual for further details. 3.8 TFB-110A Common Base for Analog Addressable Detectors The TFB-110A is a standard common base that enables connection between Telefire’s plug-in analog addressable detectors and a Telefire's analog addressable control panels. The base is compatible with a following of Telefire's analog addressable detectors: a. TFO-440A b. TPH-442A c. TFH-220A – Page 12 of 83 – ADR-3000 © 1999 – 2013 Telefire Fire & Gas Detectors Ltd Revision 1.22 March 2013 Please refer to the respective detector’s technical manual for a more detailed description This base is intended for indoor installation in false or regular ceilings. Signaling Line Circuit (SLC) loop wires and the optional TFL-1AN Auxiliary Signaling Indicator connections may be connected either vertically or horizontally. Please refer to the TFB-110A technical manual for further details. 3.9 TFL-1AN Auxiliary Indicator for Analog Detectors Telefire’s TFL-1AN Auxiliary Indicator for Analog Detectors enables auxiliary indication for detectors that are located in hidden areas such as closed rooms and above acoustic ceilings. The remote Signaling Indicator is activated directly from the detector using the detection line’s power without a need for auxiliary power sources. The TFL-1AN can be connected to a single detector or to a group of detectors. When activated, the Remote Signaling Indicator will flash both its LEDs alternately, thereby drawing attention to a detector that is activated. Please refer to the TFL-1AN technical manual for further details. 3.10 TPB-800ASR Manual Fire Alarm Call Point and TPB-800ASY Manual Extinguishing Call Point The TPB-800ASR is an analog addressable call point push-button. It consists of a standard alarm call point unit and an analog addressable interface module mounted behind the front part of the break-glass section. The address is assigned to the TPB-800ASR by using the PROG-4000 Programmer. The TPB-800ASR is connected to the SLC loop in the same way as an analog detector. The TPB-800ASY is an analog addressable extinguishing push-button. It is mechanically and electronically identical to the TPB-800ASR, with the exception of its bright yellow color to alert users that this is an extinguishing push-button rather than a fire alarm push-button. Both the TPB-800ASR and TPB-800ASY are configured as “push button”, but typically they are configured so that pressing the TPB-800ASY manual extinguishing call point activates the system extinguishers, whilst the TPB-800ASR is treated as an alarm. 3.11 ADR-805 Flow Switch Interface Module The ADR-805 interfaces flow-switches or other non-powered initiating devices. The two-wire input connection is fully supervised and is terminated by a 100KΩ end-ofline resistor. The ADR-805 includes an onboard indicating LED that flashes when addressed by the control panel and latches on upon alarm. Please refer to the TFL-1AN technical manual for further details. – Page 13 of 83 – ADR-3000 © 1999 – 2013 Telefire Fire & Gas Detectors Ltd Revision 1.22 March 2013 Figure 12 ADR-805 Flow Switch Interface Module 3.12 ADR-812 Two-Channel Input Module The ADR-812 is a two-IDC, dual-channel input module that operates as an interface between the ADR-3000 analog addressable control panel and compatible two-wire conventional initiating devices. The two NFPA 72 Style C Initiating Device Circuits (IDCs) occupy two consecutive addresses. • If jumper JP6 is removed (factory default) the ADR-812 occupies two consecutive addresses and both input lines are active. • When jumper JP6 is exist the ADR-812 occupies only a single address and only IDC A is active (single loop). The ADR-812 should be connected to a 24Vdc source from the ADR-3000 or a TPS-34A Auxiliary Power Supply. The ADR-812 continuously monitors its power source and reports any problem such as a blown fuse, disconnection, or voltage drop. The ADR-812 reports the following trouble events and conditions of the zone module: short-circuit, cutoff in the IDC loop and 24Vdc input fault. The ADR-812 has a 24Vdc resettable power limited output. This output is interrupted upon Reset, in order to reset devices that were latched on alarm. The optional 3-wire connection allows connecting detectors that have higher power consumption, such as gas detectors or beam detectors. The ADR-812 occupies two consecutive addresses, the first of which is programmed by the PROG-4000. The ADR-812 Two-Channel Input Module can be connected to the following conventional Telefire detectors: TFH-280F; TFO-480, TPH-482, TFH-220F; TFO-440, and TPH-442. Telefire may approve other compliant devices. Please refer to the ADR-812 technical manual for further details. – Page 14 of 83 – ADR-3000 © 1999 – 2013 Telefire Fire & Gas Detectors Ltd Revision 1.22 March 2013 Figure 13 ADR-812 Two-Channel Input Module 3.13 ADR-818 Eight-Channel Input Module The ADR-818 Interfaces 8 supervised non-addressable input lines to be connected to conventional smoke detectors and water flow switches using a two-wire Class-B (NFPA 72 Style C) initiating device circuit (IDC). The ADR-818 should be connected to a 24Vdc source from the ADR-3000 or a TPS-34A Auxiliary Power Supply. The ADR-818 continuously monitors its power source and reports any problem such as a blown fuse, disconnection, or voltage drop. The ADR-818 occupies eight consecutive addresses, the first of which is programmed by the PROG-4000. The ADR-818 Eight-Channel Input Module can be connected to the following conventional Telefire detectors: TFH-280F; TFO-480, TPH-482, TFH-220F; TFO-440, and TPH-442. Telefire may approve other compliant devices. Figure 14 ADR-818 Eight-Channel Input Module 3.14 ADR-828 Eight-Channel Output Module The ADR-828 enables activation of 8 unsupervised outputs for auxiliary indications only. It is used in synoptic panels, indication lights, directing signs, relays, etc. The output can drive 24Vdc lamps or LEDs. The serial resistors required for the LEDs are placed on board. Use either JP4, or JP5 (LEDs only), but not both. – Page 15 of 83 – ADR-3000 © 1999 – 2013 Telefire Fire & Gas Detectors Ltd Revision 1.22 March 2013 The ADR-828 should be connected to a 24Vdc source from the ADR-3000 or a TPS-34A Auxiliary Power Supply. The ADR-828 continuously monitors its power source and reports any problem such as a blown fuse, disconnection, or voltage drop. The ADR-828 occupies eight consecutive addresses, the first of which is programmed by the PROG-4000. Do not use the ADR-828 to activate alarm devices that must be supervised. Figure 15 ADR-828 Eight-Channel Output Module 3.15 ADR-823 Three-Channel Input/Output Module The ADR-823 is a three-channel input/output analog control module that contains two output circuits (NAC – Notification Alarm Circuit) and a single input circuit (IDC – Initiating Device Circuit). This module is intended for use in cases where there is a need for multiple output and input modules to carry out supervisory, alarm, and automatic extinguishing functions. The ADR-823 acts as an interface between an ADR-3000 analog control panel and conventional warning, alarm, and activating devices such as horns, strobes, automatic extinguishing devices, pressure switches, valves, and flow switches. The ADR-823 controls two 2-wire output lines. The first, NAC-A, works as a "changed polarity" and activates an additional dry-contact alarm relay. The other, NAC-B, works in level activation mode. Each output has a separate address. The unit also includes a two-wire input circuit (IDC) intended for connection to a flow switch as a separate address, or a supervisory pressure switch sharing the same address as NAC-A. The ADR-823 has four configurations that are set by jumpers on the card. The logic properties and number of addresses are selected accordingly. The ADR-823 is controlled by and communicates with the control panel through an analog SLC circuit and receives 24Vdc from the control panel or a local addressable power supply such as Telefire's TPS-34A. The module reports supervision status of the connected loads to the control panel. Load circuit status is reported as open or shorted circuit. – Page 16 of 83 – ADR-3000 © 1999 – 2013 Telefire Fire & Gas Detectors Ltd Revision 1.22 March 2013 Figure 16 ADR-823 Three-Channel Input/Output Module The ADR-823 occupies one to three consecutive addresses (jumper setting-dependant), the first of which is programmed by the PROG-4000. Please refer to the ADR-823 technical manual for further details. 3.16 ADR-833 Extinguishing Control Unit The ADR-833 Analog Addressable Extinguishing Control Unit supervises, controls, and activates automatic extinguishing systems. The ADR-833 is a multi-input/output control unit that is connected to and supervised by the ADR-3000 analog addressable control panel. The fire detectors assigned to the automatic extinguishing system are monitored by the control panel. The extinguishing control and command are performed by the ADR-833 when instructed by the ADR-3000 to do so. The ADR-833 contains 3 supervised outputs, 2 relays and 3 supervised inputs. The outputs activate: (a) the automatic extinguishing cylinders, (b) the fire alarm horn and (c) the evacuation annunciators. The relays are: one for trouble and the other for alarm. The inputs are: (a) manual extinguishing release – electrically, (b) extinguishing inhibit and (c) extinguishing cylinder pressure switch. The ADR-833 requires a 24Vdc input that is supplied by the ADR-3000 or a TPS-34A Analog Addressable Auxiliary Power Supply. The ADR-833 occupies only a single address on the SLC loop although several inputs and outputs are connected to it. – Page 17 of 83 – ADR-3000 © 1999 – 2013 Telefire Fire & Gas Detectors Ltd Revision 1.22 March 2013 Figure 17 ADR-833 Extinguishing Control Unit Please refer to the ADR-833 technical manual for further details. 3.17 LI-3000 Line Isolation Module for Class A/B The LI-3000 Analog Addressable Line Isolation Module provides the SLC loop with advanced capability of protection from fault conditions such as short- and open circuit, enabling continuous operation by isolating the faulty section from the rest of the loop. Without an Isolator the line cards ADR-3002 and ADR-3002C would disconnect the loop automatically when sensing a short-circuit. Figure 18 LI-3000 Line Isolation Module The LI-3000 communicates with the ADR-3000 through the addressable SLC loop that supplies its power. The module's address is programmed prior to installation by using the PROG-4000 (please refer to the PROG-4000 technical manual for further details). The LI-3000 enables wiring the SLC loop in a closed loop (NFPA Style 7 Class A) as well as branching T-shaped (NFPA Style 4 Class B) wiring configuration. Class A configuration does not reduce system capacity. Each SLC loop is capable of addressing 127 devices, including the addresses occupied by the LI-3000 modules. A – Page 18 of 83 – ADR-3000 © 1999 – 2013 Telefire Fire & Gas Detectors Ltd Revision 1.22 March 2013 single-loop line card that is configured as Class A can address up to 127 addresses (including LI-3000 line isolators), and a dual-loop line card can address up to 254 addresses (including LI-3000 line isolators) in two Class A loops. Whenever a short-circuit condition occurs the Isolator opens the circuit automatically and disconnects the faulty side of the loop. Three seconds later it resets and performs a second test, and then again a minute later. It repeats the test for eight minutes, and then periodically it will re-test every two minutes. The test cycle restarts when the module is reset. The yellow LED flashes each time the module receives a signal. A short-circuit condition will cause the LED of the shorted side to latch on. An open circuit in a Class A configuration will send a trouble message to the control panel. The LI-3000 will latch on the LED corresponding to the open side. As many as 30 Isolator modules can be installed in each SLC loop. Please refer to the LI-3000 technical manual for further details. 3.18 TIP-224A Analog Addressable Indoor Alarm Notification Sounder Telefire’s TIP-224A is an analog addressable device that integrates an indoor sounder and an addressable output module, eliminating the need for an output module installed in a separate box, and reducing material and labor cost. As an added benefit, the unit contains a high-brightness LED. The TIP-224A should be connected to a 24Vdc source from the ADR-3000 or a TPS-34A Auxiliary Power Supply. The address of the TIP-224A is programmed into the memory of the sounder and can be assigned or changed by using the PROG-4000 programmer. The sounder contains an alarm LED that is visible from 360°. This LED flashes when polled by the control panel, indicating normal operation. During an alarm THE TIP-224A will sound interrupted beeps and the LED will flash more rapidly and brightly than during normal operation. The TIP-224A is intended for indoor use wherever there is a need for an indoor audible alarm. Please refer to the TIP-224A technical manual for further details. 3.19 TPS-34A Analog Addressable Auxiliary Power Supply The TPS-34A is an auxiliary power supply that is fed from a 230Vac input and includes a 24Vdc 4A power supply, battery charger, and a control card that monitors the TPS-34A and reports status and trouble information to the ADR-3000. Reporting is done via the SLC loop and the TPS-34A takes up an address of the loop’s address rage. The TPS-34A’s output is used when the total demand on the ADR-3000’s 24Vdc power supply exceeds its capacity, or to power I/O modules, sounders, or special detectors that are installed a long distance from the control panel. The TPS-34A’s 24Vdc output allows for up to 4A current draw during alarm, and up to 0.5A continuous current draw. The power supply consists of a PSB-3000 cabinet that contains two 12V sealed leadacid batteries in capacity of up to 12AH, and up to 14 (W) by 9.5 (D) by 17 (H) cm each and two printed circuit boards: • ADR-4004TSW – a 4A switching power supply that is also used in the ADR-3000 control panel • APS-900 – an analog addressable power supply monitor card Please refer to the TPS-34A technical manual for further details. – Page 19 of 83 – ADR-3000 © 1999 – 2013 Telefire Fire & Gas Detectors Ltd 3.20 Revision 1.22 March 2013 EPI-3000 Electromagnetic and Surge Protection Interface Module Industrial installations may have strong electromagnetic interference. Install Telefire's EPI-3000 Electromagnetic and Surge Protection Interface Module in order to isolate the SLC loops and 24Vdc outputs from electromagnetic interference. One EPI-3000 module will isolate all four loops, and both 24Vdc outputs (24V_A and 24V_B) of a single control panel. Figure 19 EPI-3000 Electromagnetic and Surge Protection Interface Module 3.21 TFP-3000 Fireman Phone The TFP-3000 is a bi-directional signaling and communication system that is intended for fireman and emergency personnel. The system works in conjunction with and is supervised by the ADR-3000 analog addressable fire alarm control panel and adds communication to various points in the building to the ADR-3000's fire detection capabilities. The TFP-3000 is made of the following modules: • ADR-3000 – Analog Addressable Fire Alarm Control Panel • TFP-3000 – Fireman Phone Control Unit • TFP-6C – handset storage unit (storage for up to 6 handsets) • TFP-1 – handset • TFP-1CP – single phone station (chassis + phone + ADR-806) • TFP-80C – expansion unit for up to 80 zones / floors • TFP-806 – socket module for fireman phone (includes socket and ADR-806 analog addressable module – Page 20 of 83 – ADR-3000 © 1999 – 2013 Telefire Fire & Gas Detectors Ltd • Revision 1.22 March 2013 TFP-828 – an expansion module for the TFP-80C. Each TFP-828 module extends the system's capability by 8 addresses. Figure 20 Fireman Phone – Schematic Diagram – Page 21 of 83 – ADR-3000 © 1999 – 2013 Telefire Fire & Gas Detectors Ltd Revision 1.22 March 2013 4 Software and Tools 4.1 TCS-3040 Programming and Control Software for the ADR-3000 The TCS-3040 (Telefire Control Software) is a powerful interface tool that enables the monitoring of the control panel and performing general tasks such as remote project programming from the PC. If the ADR-3000 is equipped with Telefire’s NET-3000 module, the TCS-3040 can perform the same function over TCP/IP via the organization’s intranet or over the Internet if such a connection exists. The TCS-3040 should be version 3.20 or higher to support TCP/IP connection. Please refer to the TCS-3040 manual for further information. 4.2 MCS-3000 Centralized Fire Alarm Systems Monitoring Software Telefire's MCS-3000 Centralized Fire Alarm Systems Monitoring Software is a Microsoft Windows™-based program that monitors fire alarm systems equipped with the NET-3000 Internet Enabled Monitoring and Notification Module. The NET-3000 can be installed in Telefire's ADR-3000 Analog Addressable Fire Alarm Control Panel and GSA-1000 Multi-Zone Conventional Fire Alarm Control Panel. The MCS-3000 constantly scans over the LAN / WAN all configured panels, allowing the monitoring of multiple fire alarm control panels, using a single screen that concentrates the whole systems status including normal operation, alarm and trouble. The MCS-3000 does not allow remote control (activations) of fire alarm control panels for security reasons. A single screen can display system summary of a large number of systems. Clicking on any of the systems will open a browser window that will display the web page for that system. Please refer to the MCS-3000 manual for further information. 4.3 PROG-4000 Analog Addressable Detector and Accessory Programmer The PROG-4000 is a tool for programming and testing all of Telefire’s analog addressable devices such as detectors, manual fire alarm call points, input modules, output modules, remote power-supplies, etc. Each addressable device connected to the ADR-3000 system can be programmed to an address in the range of 1 to 127. This address will be stored in the device’s permanent memory and can be changed only with the PROG-4000 programmer. Some input and output modules use more than one address. For these modules, the programmer will store the first of several consecutive addresses in the module. In addition to programming device addresses, the PROG-4000 serves as a testing unit for all addressable devices. These tests include verification of features, and conditions of the tested device such as normal operation, alarm, various trouble conditions, etc. The PROG-4000 includes an alphanumeric display, keyboard, analog detector base and a connector with programming cord, to program addressable modules. An add-on conventional base is used with the programming cord to program the TIP-224A Analog Addressable Notification Sounder. Please refer to the PROG-4000 technical manual for further details. – Page 22 of 83 – ADR-3000 © 1999 – 2013 Telefire Fire & Gas Detectors Ltd 5 Installation 5.1 Capacity Planning Revision 1.22 March 2013 Calculate number of addresses required: • One address each for every detector; TPB-800ASR or TPB-800ASY; ADR-805; TPS-34A; ADR-833; TIP-224A; LI-3000; • One or two addresses for every ADR-812 (the ADR-812 occupies one or two addresses, depending on jumper setting) • Up to three addresses for every ADR-823 (the ADR-823 occupies one-, two-, or three addresses, depending on jumper setting) • Eight addresses each for every ADR-818 and ADR-828 Allow for a 10% margin for future expansion and calculate number of required addresses. Divide by 127 and round up to calculate required number of loops. Divide number of loops by 4 and round up to calculate required number of ADR-3000 control panels. 5.2 Power Requirement Calculation Calculate power consumption to check if any TPS-34A Auxiliary Power Supplies are required. Please refer to “Power Supply and Battery Calculations” on page 11 for power requirement tables. TPS-34A is required if any of the following conditions are met: • Quiescence (normal) mode current consumption is more than 0.5A • Alarm current is more than 4.0A • Required battery capacity is more than 12AH Please refer to the TPS-34A technical manual for further details. 5.3 Laying Wiring Consult building plans to estimate cable run lengths. Please refer to “Wire Characteristics and Length Limitations” on page 11 for details on cable types and maximum length. Route the SLC; NAC; 24Vdc Out; LonWorks; and RM-4005 connection cables from the control panel to the required locations. Ensure that cable routing conforms to NFPA guidelines and local codes. – Page 23 of 83 – ADR-3000 © 1999 – 2013 Telefire Fire & Gas Detectors Ltd Revision 1.22 March 2013 Figure 21 Cable Routing in the ADR-3000 chassis 5.4 Installing Detectors, I/O Modules and Other Equipment Install detectors, I/O modules, and other equipment as necessary. Program each device’s address prior to connecting it to the system. 5.5 Cabinet Mounting The control panel’s cabinet should be installed in a clean, dry, vibration-free indoor location. Avoid exposure to severe conditions such as high humidity, dust and air pollution. The ADR-3000 should be mounted on a solid wall in order to allow easy access for installation, daily operations and maintenance. The cabinet should be mounted by using the two sliding slots on the upper back part of it and a screw hole on the lower part. Mains input (AC power) should enter the cabinet through either the top left or bottom left knockout holes. Low voltage connections (SLC loops; 24Vdc; RS-232 to a NET-3000, printer, or PC; LonWorks connection to other control panels; RS-485 to RM-4005; and NAC outputs) should be connected through the top right, bottom right, or back knockout holes – according to the installer’s convenience. – Page 24 of 83 – ADR-3000 © 1999 – 2013 Telefire Fire & Gas Detectors Ltd Revision 1.22 March 2013 Figure 22 Cabinet mounting holes The wiring opening on the top right of the cabinet should be covered with a metal sheet. If no wires enter the cabinet through this opening close it with the plain cover, otherwise use the cover with two round holes and a plastic sealing grommet. i 5.6 Note All power-limited circuit wiring must be at least 0.25” (6.35mm) away from any non power-limited circuit wiring. Use different entries of the cabinet or conduits. See Figure 27 on page 11). Connect AC / SLC Loops, 24V Out, Alarm / Trouble / Dialer / Horn Test all wires for shorts. If any wires are shorted, locate the cause and repair it. Connect AC input and batteries. Use two rechargeable sealed lead-acid 12V batteries. Connect SLC loops; Alarm and Trouble outputs; Auxiliary 24V outputs, LON-3000/7000 and RM-4005 cabling as needed. Do not arm extinguishing devices at this time. Connect a dummy load instead. 5.7 Perform Auto Program • Press * for main menu • Press 1 (System Program) • Enter Password • Select 1 (Device Program) • Enter panel number if required • Select 2 (Automatic Program) • Press Enter to confirm • Select Card Number and press Enter Repeat for second card if present. – Page 25 of 83 – ADR-3000 © 1999 – 2013 Telefire Fire & Gas Detectors Ltd 5.7.1 Revision 1.22 March 2013 Check that all installed devices are identified See DEVICE LIST ACTIVE and compare to “As Made” documentation • Press * for main menu • Press 5 (Display Reports) • Select 3 (Device List) • Enter panel number if required • Press the Up key to step through devices Repeat for second card if present. 5.8 Enter Descriptions Enter device descriptions via panel (see Editing Device Description on page 11) or via a notebook with TCS-3040. Please refer to the TCS-3040 technical manual for further details. 5.9 Program Activation Matrices Program the control panel configuration and activation matrix. Chapter 8 on page 38 has detailed programming information. 5.10 Copy .ANL to ADR-3000 Select COMMUNICATION | DOWNLOAD, click on the “PANEL CONFIGURATION” radio button, select panel number, and click on the “DOWNLOAD” button. Select COMMUNICATION | DOWNLOAD, click on the “CARD” radio button, select panel number, and click on the “DOWNLOAD” button. 5.11 Walk Test Perform a Walk Test and activate each initiating device to verify that it is working properly. See section 10.8 on page 11 for details on performing a Walk Test. 5.12 Test Activations Ensure that extinguishing devices are not armed. Connect a dummy load to extinguishing device outputs and test activations of all output devices. When you are satisfied that all activation programming is according to design specifications and that there are no intermittent errors is the system you can arm the extinguishing devices. 5.13 Change Passwords It is highly recommended that you change the default passwords after installation to prevent unauthorized access. See section 9.12 on page 11 for details on changing passwords. – Page 26 of 83 – ADR-3000 © 1999 – 2013 Telefire Fire & Gas Detectors Ltd 5.14 Revision 1.22 March 2013 Terminal Specification Figure 23 ADR-3001 Connections 5.14.1 Mains Input On the A/C filter on the ADR-3000’s chassis. Mains input is protected by a 3.15A fuse. ADR-4004 JP1-1 [L] AC In (Live) ADR-4004 JP1-3 [N] AC In (Neutral) 5.14.2 Battery JP2 on the ADR-4004TSW Power Supply Card. Charging voltage is 27.3Vdc; charging current is 300mA. Battery current circuit limited by fuse F1 on the ADR-4004TSW power supply card. The ADR-3000’s power supply module can charge batteries in capacity of up to 12AH. The battery enclosure can contain two 12V sealed lead-acid batteries, up to 20 (W) by 7 (D) by 12 (H) cm each. For fire alarm control panels requiring batteries that will not fit in the ADR-3000 chassis use the BC-3000 external battery enclosure. This enclosure can contain two 12V sealed lead-acid batteries, up to 20 (W) by 10 (D) by 15 (H) cm each. If the system requires larger battery capacity than 12AH add the TPS-34A Auxiliary Power Supply with its own batteries. Please refer to the TPS-34A manual for additional details about the TPS-34A auxiliary power supply. – Page 27 of 83 – ADR-3000 © 1999 – 2013 Telefire Fire & Gas Detectors Ltd Revision 1.22 March 2013 Use sealed lead acid batteries ADR-4004 JP2-1 [-]................................................... - Battery ADR-4004 JP2-2 [+] .................................................. + Battery The L2 connections Cards 1 and 2 are active only with ADR-3002C line cards. All terminal blocks should be wired with 12 – 18 AWG wire. 5.14.3 General Trouble Voltage Output ADR-3001 J13-1 [T-] ................................................. - Trouble ADR-3001 J13-2 [T+] ................................................ + Trouble 24Vdc level-activation, not silenced, supervised special application NAC Maximum Current ......................................................... 0.5A, 22.5Vrms, (5 minutes alarm) This circuit is power-limited by electronic cutoff and is also protected by fuse F5 1 E.O.L. ........................................................................... 5.1KΩ resistor 5.14.4 General Trouble Dry Contacts ADR-3001 J13-3 [NO] ............................................... Trouble Relay – Normally Open ADR-3001 J13-4 [C].................................................. Trouble Relay – Common ADR-3001 J13-5 [NC] ............................................... Trouble Relay – Normally Closed One trouble contact relay rated: 0.5A 120Vac, 1.0A 24Vdc. Trouble contacts marking shows normal operation “System OK” condition. 5.14.5 24Vdc Auxiliary Terminal ADR-3001 J13-7 [24Vdc +] ....................................... + 24Vdc ADR-3001 J13-8 [24Vdc -] ........................................ - 24Vdc 24Vdc out for auxiliary devices. Non-resettable 24V output. This circuit is protected by fuse F5 1 Maximum Current 0.5A*. 5.14.6 General Alarm Voltage Output ADR-3001 J12-1 [A-]................................................. - Alarm ADR-3001 J12-2 [A+] ................................................ + Alarm 24Vdc level-activation, programmable output, supervised special application NAC Maximum Current 0.5A, 22.5Vrms, (5 minutes alarm) This circuit is power-limited by electronic cutoff and is also protected by fuse F5 1 E.O.L. 5.1KΩ resistor 5.14.7 General Alarm Dry Contacts ADR-3001 J12-3 [NC] ............................................... Alarm Relay 1 – Normally Closed ADR-3001 J12-4 [C].................................................. Alarm Relay 1 – Common ADR-3001 J12-5 [NO] ............................................... Alarm Relay 1 – Normally Open ADR-3001 J12-6 [NC] ............................................... Alarm Relay 2 – Normally Closed ADR-3001 J12-7 [C].................................................. Alarm Relay 2 – Common ADR-3001 J12-8 [NO] ............................................... Alarm Relay 2 – Normally Open Two sets of alarm contacts, both of which are rated 5.0A / 24Vdc 5.14.8 Addressable SLC Loops – Line Card 1 ADR-3001 J6-1 [-L1] ................................................. - Loop 1 – Page 28 of 83 – ADR-3000 © 1999 – 2013 Telefire Fire & Gas Detectors Ltd Revision 1.22 March 2013 ADR-3001 J6-2 [+L1] ................................................ + Loop 1 ADR-3001 J6-3 [-L2] ................................................. - Loop 2 (active only for ADR3002C) ADR-3001 J6-4 [+L2] ................................................ + Loop 2 (active only for ADR3002C) Maximum loop voltage .................................................. 25.0V Nominal loop voltage .................................................... 21.0V Maximum loop impedance ............................................ 40Ω Maximum loop capacitance........................................... 1.0 µF Supervised power-limited circuit. This circuit is power-limited by electronic cutoff and is also protected by fuses on the line card. 5.14.9 Non-Resettable 24Vdc _A (Auxiliary Terminal) ADR-3001 J11-1 [-24V_A] ........................................ - 24Vdc ADR-3001 J11-2 [+24V_A]........................................ + 24Vdc Non-resettable power-limited circuit. This circuit is power-limited by electronic cutoff and is also protected by fuse F3. 5.14.10 Horn (NAC) ADR-3001 J10-1 [-HORN]......................................... - Horn ADR-3001 J10-2 [+HORN] ........................................ + Horn NFPA 72 Style Y Notification Appliance Circuit, supervised special application NAC Reversed polarity, silenced. This circuit is power-limited by electronic cutoff and is also protected by fuse F1. Max Current 400mA E.O.L. 5.1KΩ resistor 5.14.11 Dialer (NAC) ADR-3001 J9-1 [-DIALER] ........................................ - Dialer ADR-3001 J9-2 [+DIALER] ....................................... + Dialer NFPA 72 Style Y Notification Appliance Circuit, supervised. Level-activation. This circuit is power-limited by electronic cutoff and is also protected by fuse F4. E.O.L. 5.1KΩ resistor 5.14.12 Addressable SLC Loops – Line Card 2 J1 on the main board ADR-3001 is for loops 1 and 2 of card 2. ADR-3001 J1-1 [-L1] ................................................. - Loop 1 ADR-3001 J1-2 [L1+] ................................................ + Loop 1 ADR-3001 J1-3 [-L2] ................................................. - Loop 2 (active only for ADR3002C) ADR-3001 J1-4 [L2+] ................................................ + Loop 2 (active only for ADR3002C) Maximum loop voltage 25.0V Nominal loop voltage 21.0V Maximum loop impedance 40Ω Maximum loop capacitance 1.0 µF – Page 29 of 83 – ADR-3000 © 1999 – 2013 Telefire Fire & Gas Detectors Ltd Revision 1.22 March 2013 Supervised power-limited circuit. This circuit is power-limited by electronic cutoff and is also protected by fuses on the line card. 5.14.13 Non-Resettable 24Vdc _B (Auxiliary Terminal) ADR-3001 J8-1 [-24V_B] .......................................... - 24Vdc ADR-3001 J8-2 [24V_B+] ......................................... + 24Vdc ADR-3001 J8-3 [Ground symbol] Ground Non-resettable 24V output. This circuit is protected by fuse F2 2 5.14.14 Remote Annunciator Connection JP7 on the main board (ADR-3001) is an RS-485 connection terminal to RM-4005 Remote Annunciator. ADR-3001 JP7-1 [+COM2]........................................ + RS-485 ADR-3001 JP7-2 [-COM2] ........................................ - RS-485 ADR-3001 JP7-3 [ground symbol] Ground 5.14.15 Non-Resettable 24Vdc _B (Remote Annunciator) ADR-3001 JP7-4 [+24V_B] ....................................... + 24Vdc ADR-3001 JP7-5 [-24V_B] ........................................ - 24Vdc Intended for supplying 24V to the RM-4005. Non-resettable 24V output. This circuit is protected by fuse F2 3 5.14.16 Communication Connection RS-232 communication connector to a computer, printer, or NET-3000 module (P2 COM 1), not isolated. When using a grounded device such as a serial printer or desktop PC use the optional GIM-232 Galvanic Isolation Module for RS-232 Interface. 5.14.17 LON-3000/7000 Connection J5 on the main board (ADR-3001) Connection to the LON-3000/7000 network communication module for interconnecting as many as 32 control panels and establishing a network. 5.15 Wiring The ADR-3000 control panel is factory-tested and ready to install. Internal wiring and connections should not be changed. The installer should connect field-wiring including addressable loops, the general output wires, communication cables, batteries and AC power. Disconnect all power sources (mains and batteries) before connecting any field wiring. 5.15.1 Power Supply The ADR-3000 should be connected to a separate dedicated 230Vac fire alarm circuit that is labeled “FIRE ALARM”. The primary power circuit must be connected to the line side of the main power feed of the protected premises. No other appliance may be connected to the “FIRE ALARM” circuit. The power cables must run continuously, without any disconnecting devices from the power source to the control panel. Wires, circuit breaker or any over-current protection device must comply with local electrical wiring codes. An additional filter and terminal board are installed for locations that require EN-55022 compliance. – Page 30 of 83 – ADR-3000 © 1999 – 2013 Telefire Fire & Gas Detectors Ltd Revision 1.22 March 2013 The power cable should enter the control panel through either the top left or bottom left knockout opening. Use a plastic bushing that fits the opening. Connect the Live and Neutral wires to the proper terminal. Connect the Ground wire to the ground terminal. 5.15.2 SLC (Signaling Line Circuit) Loop Wiring Address programming must be carried out using the PROG-4000 before connecting each addressable device. Please refer to the PROG-4000 Technical Manual for further information. Input/Output devices such as detectors, switches, horns, etc., should be wired to the SLC (Signaling Line Circuit) in accordance with NFPA 72 Style 4. High current consuming devices such as beam detectors and gas detectors should be wired with 4-wire cable, one pair to be connected to the SLC loop and the other pair to a 24Vdc supply from the control panel or from an external analog addressable power supply TPS-34A. Wire specifications should be of twisted pair type between 12 – 18 AWG according to the device load and cable lengths. The wires must comply with local standards. Maximum permitted SLC loop resistance is 40Ω???Maximum permitted capacitance is 1.0µF. 5.15.3 Wiring 24Vdc Powered Devices To ensure operation of alarm or initiating device that requires relatively high current from a 24Vdc source, use appropriate cables. Wire specifications should be between 12 and 18 AWG and the cable resistance running between the 24Vdc source to the I/O module and from the I/O module to the device should be calculated. Ensure that no device receives a voltage below its specified minimum operating value and that the total voltage drop will not exceed 3 volts. Calculate the total current drawn by the system and system devices at normal operation and alarm modes. Ensure that the total load on the power supply does not exceed its limit of 0.5 Ampere during quiescence mode and 4.0 Ampere at alarm mode. Please refer to the power calculation tables on page 11. 5.15.4 End of Line Device (E.O.L.) Some circuits require an EOL device. A 5.1KΩ EOL resistor is installed in these terminal blocks at the factory. The following circuits require an EOL device. • General Trouble NAC (J13 T-, T+) • General Alarm NAC (J12 A+, A-) • Horn NAC (J10) • Dialer NAC (J9) Remove the EOL resistor from these circuits and install it in the last device on the line if you connect any devices to these circuits. 5.15.5 Shielded Cables Wiring It is highly recommended to avoid outdoor wiring due to the increased susceptibility to lightning strikes. Overhead cables running between buildings or on roofs should be shielded. The shield should be connected to the ground by using the Master Ground Terminal in the control panel. Grounding should not be connected to any other points. Ensure continuous grounding by soldering. – Page 31 of 83 – ADR-3000 © 1999 – 2013 Telefire Fire & Gas Detectors Ltd i ! Revision 1.22 March 2013 Note When installing a system at a site adjacent to high power cables, heavy industrial machinery, or any kind of high electromagnetic fields, shielded cables should be used in the SLC loops and an EPI-3000 module should be connected to each ADR-3000. Warning Disconnect the AC power supply and batteries from the control panel before performing any wiring and connections of accessory circuits or I/O devices. Ensure that the system is in normal working condition and no initiating device is in alarm condition prior to installing or replacing an automatic extinguisher. 5.16 Documentation Attach the followings to the system’s front panel, or place it in a prominent position nearby: • A list of areas/zones as installed in the protected premises • Actions to be taken immediately by the operators • The name of the installing company and the service telephone number should be clearly marked on the panel itself or on an attached diagram See a sample form at the end of this manual. – Page 32 of 83 – ADR-3000 © 1999 – 2013 Telefire Fire & Gas Detectors Ltd 6 Revision 1.22 March 2013 System Display and Keyboard The ADR-3000 display includes an alphanumeric LCD, system indicators, and keyboard that are used by operators for normal operations and by programmers during installation and maintenance. A password is required to respond from the panel keys. The ADR-3000 has a keyboard-locking feature to prevent non-authorized personnel from operating the control panel. Two levels of authorization passwords are required for some operations: • Level 1 (Operator actions) and • Level 2 (Programmer/Supervisor functions). When entering the Programmer/Supervisor password the operator actions: Alarm Silence and Reset are enabled too. The Recall Memory key that scans through current events is enabled without entering a password. The ADR-3000 keyboard is divided to two sections: The upper part (light blue) is used by the operator to display system modes and events, perform operations such as alarm / trouble silencing, event memory recall and dialer enable / disable. The reset actions can only be performed after keying in the operator password. The lower part (dark blue) enables the system Programmer/Supervisor to execute operations such as changing detector’s sensitivity, turning devices Enable / Disable, setting operating modes, etc., Programmer / Supervisor actions can only be performed after keying in a second-level password. Figure 24 Keyboard and display screen – Page 33 of 83 – ADR-3000 © 1999 – 2013 Telefire Fire & Gas Detectors Ltd 6.1 Revision 1.22 March 2013 Alphanumeric Display The ADR-3000’s alphanumeric display is a 4 row by 40 characters Liquid Crystal Display (LCD). The LCD is backlit and is illuminated during alarm events and when front panel keys are pressed. During normal operation the backlight will turn off two minutes after the last keystroke. When the backup battery powers the system, the LCD backlight will turn off ten seconds after the last keystroke. 6.2 Indicating LEDs LED Meaning System OK Green LED. Lit continuously when the system is operating properly. Additionally, a message “SYSTEM OK” is displayed on the LCD. The green light turns off at trouble and / or an alarm condition. Power Green LED. Indicates presence of AC power. When primary power is absent a warning (AC Power not connected) is displayed on the LCD. The LED flashes upon loss of AC. Pressing # button will turn the LED off. System Fault Yellow LED. Indicates a system fault (hung CPU) Fire Alarm Red LED. Indicates a fire alarm condition. Additionally, alarm details are displayed on the LCD. Flashes for new events, turns to solid red upon pressing # button. Pre-Alarm/AVF Yellow LED. Indicates the presence of a pre-alarm condition in the system. Flashes for new events, turns to solid yellow upon pressing # button. Sounders Yellow LED. Flashes if present fault in general sounders, turns to solid yellow upon pressing # button. Silence Sounders Red LED. A flashing red light indicates that the system was silenced following an alarm event. Trouble Yellow LED. A flashing yellow light indicates trouble condition. Additionally, a trouble message is displayed on the LCD. Flashes for new events, turns to solid yellow upon pressing # button. Supervisory Yellow LED. Indicates a supervisory event. Flashes for new events, turns to solid yellow upon pressing # button. Additionally, a message will be displayed on the LCD. Disabled Yellow LED. Indicates that a device or zone is disabled. Additionally, a message will be displayed on the LCD. Evacuate/ Resound Red LED. Lights when evacuation was activated. A message will be displayed on the LCD. Dialer Yellow LED. Indicates that the dialer is disabled or it in the fault condition. – Page 34 of 83 – ADR-3000 © 1999 – 2013 Telefire Fire & Gas Detectors Ltd LED Meaning Recall Memory Red LED. Lights when more then one event occurs simultaneously. The number of events will be displayed on the LCD. Table 2 6.3 Operator Panel – Indicating LEDs Operator Keys Key Function Evacuate/ Resound Allows the Operator to initiate an evacuation procedure. Requires password. If a sounders was silenced, pressing Resound renewal all general sounders. Requires password. Dialer Allows the Operator to enable/disable the automatic dialer. Requires password. Buzzer Off Pressing this key silences only internal buzzer. Recall Memory • • In normal mode – used to scan through the existing events. The top row of the LCD will show the recalled event number and description. The total number of events will be displayed on the lower right. In program mode – moves the address to the next active device. Silence Pressing this key silences the devices connected to the General Alarm NAC (if defined as Silenced), HORN output, and all addressable outputs that are defined as “silenced”. Reset Pressing this key resets and restores the system to normal operation mode. All NACs are turned off, input and output modules return to normal operation mode, addressable detectors receive a reset signal, the LCD displays “System OK” and history report is updated. The system will resound if any Alarm or Trouble occurs. Table 3 6.4 Revision 1.22 March 2013 Operator Panel – Operator Keys Numeric and Arrow Keys 6.4.1 Numeric Keys The numeric keys are used for entering values for system initialization, programming, operation, password entering, and selecting menu field values on the LCD. 6.4.2 Arrow Keys The arrow keys are used for navigating from field to field on the screen during system programming and for browsing through the memory. – Page 35 of 83 – ADR-3000 © 1999 – 2013 Telefire Fire & Gas Detectors Ltd 6.5 Revision 1.22 March 2013 Programming Keys Disable • • • Enable • • • Name In NORMAL MODE – used to disable an addressable device or zone, (secured by operator password) In PROGRAM MODE – used to configure a device as nonexistent. In SYSTEM CONFIG mode – disables partners, line cards, remote panels, and COM1 SUPERVISE mode. In NORMAL MODE – used to enable an addressable device or zone (secured by operator password). In PROGRAM MODE – used to configure a device as existent. In SYSTEM CONFIG mode – enables partners, line cards, remote panels, and COM1 SUPERVISE mode. • • In NORMAL MODE – used to enter and display description In PROGRAM MODE – opens a virtual keyboard to enable entering device descriptions. Address • Used to display a device address details when, an event occurs. Panel, Card, Loop and Address or display device type. Quit • Used to exit a menu screen displayed on the LCD, returning to a previous menu level or main screen. Program • Used to store device parameters in the memory, after configuring or changing parameters when in program mode. Clear • Used to clear a selected field (changes the field value to 1) or wrong password. Enter Table 4 Used to enter or confirm data after typing, when required. Also used for starting Detector Init or Diagnostic operation. Operator Panel – Programming Keys – Page 36 of 83 – ADR-3000 © 1999 – 2013 Telefire Fire & Gas Detectors Ltd Revision 1.22 March 2013 7 System Screens 7.1 Normal Operation Screen Under normal operating conditions, the following screen is displayed: TELEFIRE LTD. Panel:1 System OK 18:38:08 Day Mode Press * for Menu Keyboard:Locked Screen 1 Normal Operation Screen Display Displays the panel number, System OK message, the time, and the system sensitivity mode (day or night). 7.2 Main Menu Screen Press the asterisk (*) key to display the main menu. 1 2 3 4 System Program On/Off Device Monitor Test Printer Reports 5 6 7 8 Display Reports Utilities Walk Test Quit Screen 2 Main Menu Screen Sub-menus of the main menu screen: System Program - Used for configuring the system. Requires programmer password. ON/OFF Device -Used for enabling/disabling devices or zones. Requires operator or programmer password. Monitor Test - Used to monitor a detector’s signal by displaying a bar graph and a numerical value of its sensing physical parameter. The measurements are of smoke density, temperature, etc. A manual test of a detector can also be performed from this screen. Printer Report - Used for entering a sub-menu, to select various printing options, as detailed further. Active only if a printer is configured. Display Report - Used for entering a sub-menu, to display various reports on the LCD as detailed further. Utilities - Used for entering a sub-menu of various service operations. Walk Test - Used to perform an individual device field test in order to check proper system operation. Requires operator or programmer password. Quit - Exits to the normal operations screen. – Page 37 of 83 – ADR-3000 © 1999 – 2013 Telefire Fire & Gas Detectors Ltd 8 Revision 1.22 March 2013 System Programming Configuration of the ADR-3000 can be performed by using a dedicated PC with Telefire’s proprietary software, or trough the system programming menus. During programming, the system does not scan the devices. The system will be in trouble condition until programming is completed. Access to programming modes is secured by the programmer password. This applies both to programming from the control panel or via a PC. To go to the programming menus from the main menu, press SYSTEM PROGRAM. The following screen will be displayed: Type Password ____ and press ENTER Screen 3 Password Screen In order to enter the system-programming mode, type the 4-digit programmer password and press ENTER. Factory default passwords are ‘1111’ (operator password), and ‘2222’ (programmer password). 8.1 System Program Menu After entering the password as required, the following menu will be displayed: 1 Device Program 5 Change Password 2 Time Program 6 Detectors Init 3 System Config 7 Diagnostics 4 Day/Night Program 8 Quit Screen 4 System Program Menu Description of sub-menu options on the system program menu: Device Program-Used for entering the device details and setting all device parameters, including type of device, sensitivity, description and logical functions. Time Program - Used for setting the system’s internal clock date and time. The clock serves for executing day- and night functions. System Config - Used for setting system parameters such as number of line cards, network definitions (Panel No., Partners), remote annunciators, dialer delay, etc. Day/Night Program - Used for setting the day and night hours for each day of the week, in order to change detectors sensitivity accordingly. Change Password - Enables changing the operator and programmer passwords. Detectors Init - Used for fast acquisition of the detectors reference value. Diagnostics - Used to perform several tests on the addressable devices after installation or service operations. Quit - Used to exit this menu and return to the main menu. In order to perform programming operations in any of the items listed above, press the corresponding number on the panel. – Page 38 of 83 – ADR-3000 © 1999 – 2013 Telefire Fire & Gas Detectors Ltd 8.2 Revision 1.22 March 2013 Device Programming The following screen enables selecting between manual and automatic device editing program. 1 Manual Program 2 Automatic Program Screen 5 Device Programming Options Option 1 allows for manual configuration of devices. Option 2 causes the control panel to poll all 127 addresses on all loops, and enter the appropriate device type for each address. 8.2.1 Manual Device Programming After selecting Manual Program the next screen will be displayed: *Card:1 Loop:1 Address:1 Ative:ON Type:Photoelectric Detector Zone:1 Delay:0 -> Screen 6 Device Programming Screen – first page Move to the second page by pressing repeatedly on the right arrow. C1/L1/Adr1 Photoelectric Detector Day Sensitivity:1.4% Night Sensitivity:1.2% Prealarm:-0.2% <- Screen 7 Device Programming Screen – second page Press the left or right arrow keys to move between fields or switch between the first and second page. To change field values or field definitions, press the up and down arrows. Configuration fields are detailed below: Card Line Card number (1 or 2) in the control panel to which the device is connected. Loop The loop number (1 or 2) of the card specified above to which the device is connected. Address The electronic number (address) of the device (as programmed by PROG-4000) in the range of 1 to 127. Active ON – active, or OFF – inactive. Notifies the system on the presence of an addressable device. Type System definition of device types. Initiating Devices: Ionization smoke detector; Photoelectric smoke detector; Heat detector; Gas detector; Input module; Push button; CO & Heat detector; Photo & Heat detector; and Supervisory switch. Output Devices: Sounder; Lamp; Extinguisher; Extinguisher control; and Supervisory output. Miscellaneous Devices: Power supply; and Isolator. Day Sensitivity Used for setting detector sensitivity at daytime. Defined according to detector type. – Page 39 of 83 – ADR-3000 © 1999 – 2013 Telefire Fire & Gas Detectors Ltd Revision 1.22 March 2013 Night Sensitivity Same as above, for nighttime. Pre-Alarm Used to set the difference between day/night and pre-alarm sensitivity values. For example: if the day alarm sensitivity is 1.6% and prealarm field is set to -0.2% the pre-alarm sensitivity will be 1.4%. Zone Used for assigning an initiating device to a logical zone number between 1 and 499, for activation purpose. Delay The alarm verification delay period for initiating devices or delay for activate output devices. Can be set between 0 and 60 seconds. Press the Recall Memory key in order to move to the next active device screen. 8.2.2 Automatic Device Programming Automatic device programming causes the control panel to scan every possible address and populate its device map according to whatever devices are installed. Every connected device shall be configured as “Active” and with the correct device type and the defauly configuration of that device type. Setting logical zones, activation matrices, and other parameters requires operator intervention (manual programming). This will allow comparing the system as installed to planned configuration in order to find any installation-related problems. Please see section 8.2.2 on page 40. 8.3 Conditional Activation of Output Devices (Activation Matrix) The ADR-3000 enables the configuration of activation for addressable output devices and creating complex logical functions by using Advanced Activation Matrix (AAM). The number of devices in alarm, and the sources of the alarm, i.e., device, loop, line card, or logical zone, can be selected for each output device. Activation within a network can be initiated from different input devices connected to different control panels. Please refer to “Global Zone” on page 11 for further details. An output device can be activated from several pre-defined zones and therefore it does not refer to any specific zone. In order to utilize a zone activation matrix function, the initiating devices must be attributed to zones by defining the zone during device programming. Up to 499 zones can be attributed to each matrix. 8.3.1 Configuring an Output Device When programming an output device the following fields are displayed on the LCD: *Card:1 Loop:1 Address:100 Active:ON Type:Sounder Delay:0 Event Ctrl:General Screen 8 Output Device Screen. Select one of the following output device types while the cursor is on the TYPE field: Sounder, Lamp, Extinguisher, Extinguisher Control, or Supervisory Out. The default activation condition for an output device is GENERAL. If a different activation condition is required, move the cursor to the EVENT CTRL field, and press ENTER. The following will be displayed on the LCD screen: – Page 40 of 83 – ADR-3000 © 1999 – 2013 Telefire Fire & Gas Detectors Ltd C1/L1/Adr100 Sounder *OperationType:GENERAL Alarm Events:1 Revision 1.22 March 2013 Silence:ON Screen 9 Default Operation Type. The OPERATION TYPE field defines the output device activation options on alarm: • GENERAL - Activated by any initiating device. • DEVICE MATRIX - Activated according to control panel device matrix. • ZONE MATRIX - Activated according to control panel zone matrix. • GLOBAL ZONE - Activated from any zone in the network (global zone can be configured only with the PC-based TCS-3040 Programming and Control Software for the ADR-3000). The SILENCE field serves to configure whether the output device will be silenced after pressing the Silence Sounders key on the control panel. When ON the device will be silenced by pressing the “Silence Sounders ” key on the operator keyboard. 8.3.2 General Operation An output device defined as GENERAL will be activated by any initiating device of the control panel to which it is connected. On a network of several ADR-3000 systems an output device defined as GENERAL will be activated by any initiating device of any control panel to which it is connected and defined as PARTNER. The control panel with the output device should be defined as “partner” on all panels that will trigger the output device. Note The Extinguisher Output Module and the Automatic Extinguisher Control cannot be defined as GENERAL. They should be defined as DEVICE MATRIX. i 8.3.3 Device Matrix At this option a group of input devices should be selected to form a matrix in order to activate the configured output device. The number of devices in alarm required to activate the output device must be set. The following screen shows the fields that should be defined: C1/L1/Adr8 Extinguisher Selected:2 *OperationType:DEVICE MATRIX Silence:OFF Alarm Events:2 Matrix Input-> Card:1 Loop:1 Add:3 ON Screen 10 Device Matrix Settings. The ALARM EVENTS field defines the number of input devices that should be in alarm in order to activate the output device. Any number between 1 and 5 may be selected. The default is 1. Change the address to the next active device with the arrow keys. – Page 41 of 83 – ADR-3000 © 1999 – 2013 Telefire Fire & Gas Detectors Ltd Revision 1.22 March 2013 Note To comply with fire regulations, an output device will be activated immediately after initiating an alarm from a Call Point, if selected to the matrix, regardless the defined number of alarm events. i Adding a device to a matrix To add an initiating device to the matrix, select its card, loop and address and press the ON key. The SELECTED field displays the number of selected devices, and will be updated on each device addition or subtraction. Note In the CARD field, only a line card installed in the ADR-3001 main board may be selected. i The LOOP field allows selection of a loop number depending on the line card model that is installed on the ADR-3001: • LOOP: 1 in the ADR-3002 line card. • LOOP: 1 or LOOP: 2 in the ADR-3002C line card. Only active input devices can be selected for matrix activation conditions. Removing devices from activation matrix To remove an input device from the matrix, select its card, loop and address and press the OFF key. When the cursor is on the ADD field, pressing the RECALL MEMORY key enables browsing through the selected input device matrix. All the initiating devices related to an output matrix, connected on a certain loop or card, can be removed at once from the matrix, by highlighting the loop or card fields with the cursor and pressing the CLEAR key. Saving to memory Upon completion of selection of all input devices, press the PROGRAM key in order to store the device matrix data in memory. 8.3.4 Zone Matrix A Zone Matrix is an activation array of one or several logical device zones that are assigned to an output device in order to form complex activation functions. The number of alarm events required for activation, should be defined between 1 and 5. When setting the ALARM EVENT field to 1, the output device will be activated on receiving one alarm from any zone comprised in the matrix. When setting the ALARM EVENT field from 2 to 5, the output device will be activated in accordance with one of the followings: ALARMS Activation on receiving 2 to 5 alarms simultaneously from initiating devices of any zone comprised in the matrix. ALARMS IN SAME ZONE Activation on receiving 2 to 5 alarms simultaneously from initiating devices at one of the zones comprised in the matrix. ALARMING ZONES “Alarming Zone” – A zone in which at least one of its initiating devices is in alarm. – Page 42 of 83 – ADR-3000 © 1999 – 2013 Telefire Fire & Gas Detectors Ltd Revision 1.22 March 2013 Activation on receiving 2 to 5 Alarming Zone, from zones comprised in the matrix. C1/L1/Adr101 Sounder Selected: 2 *Operation Type: ZONE MATRIX Silence:ON Number:2 Event Type:ALARM MatrixInput-> Zone:1 OFF Screen 11 Zone Matrix Settings When selecting Zone Matrix | Alarms, the NUMBER field defines the number of alarm events from all zones that are required for activation. The Matrix-Input | Zone field indicates the Zone Number associated with the Activation Matrix. When the cursor is in the ZONE field, the up/down arrow keys are used to browse through the selected Zones, When the cursor is in the Matrix-Input field, the up/down arrow keys are used to browse through active Zone Numbers of the system. An undefined zone (a Zone which has no devices) can not be selected. The EVENT TYPE field will not be displayed when one alarm event is set to activate the output device. When more than one alarm is set, the EVENT TYPE field is displayed and one of the following can be selected: ALARM; ALARMS IN SAME ZONE; and ALARMING ZONES. The SILENCE field allows a device to be defined as Silenced (ON) or unsilenced (OFF). The NUMBER field sets the number of alarm events required to activate the output device. 8.3.5 Global Zone A Global Zone enables the creation of a matrix of initiating devices distributed in a network of several control panels. The Global Zone activation condition applies only to an output device connected to a Control Panel that is connected to a network. When selected, the Global Zone condition does not take under its consideration “Partner” registration within the control panels of the network. A zone number configured on different control panels will be recognized as a single zone by an output device configured as Global Zone. Note The Global Zone can be configured only by using a dedicated PC with Telefire’s propriety TCS-3040 Programming and Control Software for the ADR-3000. i 8.3.6 Validity Checking Validity checking performs activation logic validity check. 8.3.7 • • • Matrix Programming Sequence Programming the system devices (devices ON) Assigning zones to input devices (required only for Zone Matrix) Creating a Device Matrix or a Zone Matrix to activate output devices. – Page 43 of 83 – ADR-3000 © 1999 – 2013 Telefire Fire & Gas Detectors Ltd • Revision 1.22 March 2013 On pressing the QUIT key a validity test is performed at the control panel. If there are any programming errors, they will be displayed at this time. To correct the error, return to the relevant screen. 8.3.8 Advanced Activation Matrix Error Messages Error in Card:1 Loop:1 Address:8 Extinguisher can not be programmed as GENERAL output Screen 12 Activation Matrix Error Messages – Extinguisher Error Extinguisher and Extinguisher Control devices cannot be set to GENERAL activation condition. RESOLUTION: Change the activation condition to device matrix. Error in Card:1 Loop:1 Address:101 DEVICE MATRIX contains a Device which was removed from program – Card:2 Loop:1 Address:120 Screen 13 Activation Matrix Error Messages – Device Matrix Error 1 Displayed when an initiating device belonging to a matrix is programmed OFF, and not deleted from the matrix. RESOLUTION: Restore the device to ACTIVE: ON, or remove the device from the device matrix. Error in Card:1 Loop:1 Address:101 Number of Alarm Events can not be higher than number of Selected Devices Screen 14 Activation Matrix Error Messages – Device Matrix Error 2 Warns when the number of ALARM_EVENTS is higher than the total number of initiating devices selected in the matrix. RESOLUTION: Reduce the number of initiating devices required for activation, or add devices to the device matrix. Error in Card:1 Loop:1 Address:101 Number of Alarm Events can not be higher than number of Devices in the Selected Zones Screen 15 Activation Matrix Error Messages – Zone Matrix Error 1 Warns when the number of ALARM EVENTS is higher than the total number of initiating devices in all zones of the Matrix. RESOLUTION: Reduce the number in the ALARM EVENTS field, or add devices to the Matrix. Error in Card:1 Loop:1 Address:101 ZONE MATRIX contains a Zone which was removed from program – Zone:10 Screen 16 Activation Matrix Error Messages – Zone Matrix Error 2 – Page 44 of 83 – ADR-3000 © 1999 – 2013 Telefire Fire & Gas Detectors Ltd Revision 1.22 March 2013 Is displayed when a zone no longer exists. Occurs after programming OFF the initiating devices of the zone, or changing its zone number. RESOLUTION: Restore the canceled zone, or remove the missing zone from the matrix. Error in Card:1 Loop:1 Address:101 Number of Alarm Events can not be higher than number of Devices in Zone: 123 Screen 17 Activation Matrix Error Messages – Zone Matrix Error 3 Warns When the Alarm Events number is higher than the total number of initiating devices in a specific zone. RESOLUTION: Reduce the number of Alarm Events, or add initiating devices to the Zone. Error in Card:1 Loop:1 Address:101 Number of Alarm Events can not be higher than number of Selected Zones Screen 18 Activation Matrix Error Messages – Zone Matrix Error 4 Warns When the Alarm Events number is higher than the total number of Zones in the Matrix. RESOLUTION: Reduce the number of Alarm Events, or add zones to the Matrix. 8.4 Editing Device Description Each addressable device has a description field of 40 characters. Usually entering the description is done through the PC using Telefire’s proprietary software. Editing an existing description, or adding a new one, can be performed from the keyboard. From the Device Program screen, press the NAME key, the Device Description Screen will be displayed: Push # for Hebrew Photoelectric detector in control room ABCDEFGHIJKLMNOPQRSTUVWXYZ!”#$%&’()*+,-. abcdefghijklmnopqrstuvwxyz0123456789:;<= Screen 19 Device Description Screen Pressing the # key toggles between languages. In order to change or add a description, use the arrow keys to move the cursor to the point where you wish to rewrite. Press the down key to move to the characters row. Press, the right/left key to highlight the required character, and press ENTER. Follow the same procedure for each letter. On completion of writing, press the PROGRAM key in order to save the description, and then press QUIT. 8.5 Storing Data in Memory Press the PROGRAM key in order to store the data in memory after changing field contents in the DEVICE PROGRAM menu. A confirmation buzz will sound in response and the word “SAVED” will be displayed on the LCD. This action should be repeated for each device after completing the entire device configuration. – Page 45 of 83 – ADR-3000 © 1999 – 2013 Telefire Fire & Gas Detectors Ltd Revision 1.22 March 2013 If the QUIT key is pressed before saving, the message “NOT SAVED” will be displayed on the screen. When pressing the QUIT again the last changes will not be saved. The system automatically checks programming validity. On confirmation of programming, the message “PROGRAM COMPLETE” will be displayed. Before proceeding to normal operation, a message asking whether to perform a diagnostics test is displayed on the LCD screen. The system will perform the test (see “DIAGNOSTICS” menu) if you confirm by pressing ENTER. Otherwise the system will proceed to normal operation. 8.6 Time Programming Enter the TIME PROGRAM sub-menu to display the following screen: *Year:2011 Month:11 Date:06 Day:Sunday Hours:18 Minutes:38 18:38:08 Press * for Menu Screen 20 Time Program Screen Use the arrow and number keys to update the date, day of the week, and time fields. Upon completion, exit this screen by pressing the asterisk (*). The seconds revert to 00 on exit. 8.7 System Configuration Upon selecting SYSTEM CONFIG from the System Program menu the following screen is displayed: *Panel:1 Partner:2 Active Card:1 Active RM Control:0 Active RM-Language:English J12 Out:not silence COM 1 Supervise:OFF COM 1:NET3000 -> Screen 21 System Configuration – first page Move to the second page by pressing repeatedly on the right arrow. Dialer Delay:0 min J13 FWRE:ON <- Screen 22 System Configuration – second page Panel - In this field the control panel ID number is defined. Partner - In this field the number of partners of this control panel is displayed. Card - Indicates the number of configured line cards in the control panel, when the cursor is not on the Card Field. Highlighting this field enables the selection of card 1 or 2. Press the ON key to enable or OFF to disable the card. Pressing the ON key when a card is enabled causes the card to switch between Class A and Class B modes. Please refer to the LI-3000 technical manual for details about Class A connections. Rm Control - When the cursor highlights any field other than REMOTE CONTROL field, the REMOTE CONTROL field displays the number of active remote annunciators. When the cursor is on the REMOTE CONTROL field it enables scrolling through the remote panels ID numbers and setting the connection to ON or OFF. Please refer to the RM-4005 manual for further details. – Page 46 of 83 – ADR-3000 © 1999 – 2013 Telefire Fire & Gas Detectors Ltd Revision 1.22 March 2013 Rm Language - Used for defining the interface language (Hebrew or English) in the RM-4005 Remote Panel and Annunciator. J12 Out - Sets the supervised alarm output, located at J12 marked as A+ and A-, to be Silenced or not Silenced, when performing a silencing procedure in the system. Com 1 Supervise - Enables to perform supervision of the RS-232 connection to a PC. Any RS-232 communication fault will be displayed as a system trouble event. Set to ON for supervision. Valid only when a PC is connected with the EVENT MONITOR screen open. When COM 1 is defined as supervised RS-232 errors such as disconnection will show on the event window of TCS-3040. COM 1 - Used for selecting the RS-232 connection to one of the following serial devices: COMPUTER, PRINTER, or NET3000. Configure to OFF for no connection. Dialer Delay - Sets the dialer delay in minutes. Dialer delay applies only to day mode operation. The dialer will activate immediately during night mode. J13 FWRE – Sets the supervised Trouble output J13 marked +T –T to delivered trouble events via a Fault warning routing equipment. 8.8 Day / Night Programming This sub-menu serves for setting system operating modes, by different time settings, to distinguish between normal operating hours (DAY mode) and nighttime hours (NIGHT mode). MODE – This field indicates one of three operating modes. • DAY – Continuous operation in day mode (without automatic change). • NIGHT – Continuous operation in night mode (without automatic change). • TIME-RELATED – Automatic shifting from DAY to NIGHT mode and vice versa, according to time settings. *Mode:Time related Day: Monday Night start Hours:18 Minutes:30 Night end Hours:06 Minutes:00 Screen 23 Day/Night Mode – Time Programming Screen Select one of the modes by using the UP / DOWN keys. At Time-Related mode, each weekday can be programmed by selecting a day and than setting the nighttime between night start and night end. Different time settings can be set for each day of the week. Use the arrow keys to toggle between fields. Detector sensitivity will change according to the day and night sensitivity settings of each detector. The Day/Night modes also affect dialer operation. An alarm that occurs during night mode will activate the dialer immediately. During day mode operation will be delayed if programmed thus. 8.9 Change Password There are two passwords for level 1 (Operator) and level 2 (Programmer). One enables the operator to reset the control panel in case of alarm and operate the SILENCE key, and the second allows the programmer to execute required maintenance and change system characteristics. – Page 47 of 83 – ADR-3000 © 1999 – 2013 Telefire Fire & Gas Detectors Ltd Revision 1.22 March 2013 Factory default passwords are ‘1111’ (operator password), and ‘2222’ (programmer password). Entering the operator password does not allow access to the SYSTEM PROGRAM submenu and its functions. Entering the programmer password permits access and execution of changes in all menus and fields including operator actions. 1 Operator Password 2 Programmer Password Screen 24 Selecting a Password to Change After selecting option 1 or 2, the following screen will be displayed: Old Password XXXX Type New Password ____ and press ENTER Screen 25 Password Change Screen In this field, the current password is displayed, and a new password may be entered. i 8.10 Note Access to this field from SYSTEM PROGRAM is possible only after entering the previous programmer password. Detectors Init Adjust Detectors reference values? (ENTER/QUIT) Screen 26 Detectors Initializing Screen Each detector adjusts itself gradually according to changes of environmental conditions, by measuring and calculating the new reference value needed for signal processing. This process normally requires a period of several hours. When the system is turned on for the first time, or after installing or changing a detector, it is recommended to perform the initialization process. If this action is not performed, the adjustment will be completed automatically within few hours of operation. Pressing ENTER will activate the fast Initializing. The system will display the message “DONE!” upon completion. Pressing the QUIT key exits this window without performing the fast update. 8.11 Diagnostics Diagnostics test is mostly recommended after completing system installation or modifications. – Page 48 of 83 – ADR-3000 © 1999 – 2013 Telefire Fire & Gas Detectors Ltd Revision 1.22 March 2013 When completing device programming and then quitting the programming menu the following screen will be displayed. Panel 1 Program Completed Perform Diagnostics test? ENTER/QUIT Screen 27 Exiting Device Programming. The screen displays a message asking whether to perform a diagnostics test. When choosing ENTER a new screen will be displayed. 8.11.1 Performing Diagnostics Test Diagnostics Select Card number and press ENTER - Screen 28 Diagnostics Test Perform diagnostics by entering the card number for testing. During diagnostics test the system checks the device communication, device type, and address errors. The following trouble messages may be displayed: TYPE-MISMATCH - Installed device type is Incompatible with the programmed device type. EXTRA DEVICE - Is displayed when the system identifies device connecting directly to the loop but not programmed. TROUBLE COMMUNICATION - Indicates a problem of communication with the devices. SAME ADDRESS - Indicates that there are two or more devices in the loop with the same address number. The diagnostics test halts whenever it detects an error. The LCD will display an error message with address details. When the control panel detects two or more devices with the same address it will turn on their LEDs in order to assist the installer to identify those devices. To continue the test press the ENTER key. On completion of the diagnostics, it is possible to perform an additional test on the same or the second card. Press QUIT to exit the test. – Page 49 of 83 – ADR-3000 © 1999 – 2013 Telefire Fire & Gas Detectors Ltd 9 Revision 1.22 March 2013 Operation and Maintenance This chapter describes the actions that should be taken during routine maintenance operations. 9.1 ON/OFF Device The function of the ON/OFF device menu is to enable or disable devices in the system. Alarms from disabled devices are ignored. Access to this function is password protected. After entering the password the following screen is displayed: Select Device and press ON/OFF Panel:1 Card:1 Loop:1 Address:1 (-----------Device Description---------) Device enabled Address Mode Screen 29 Single Device Enable / Disable Enter the Panel; Card; Loop numbers and Address to select a device. Press the OFF key to disable a device or press the ON key to enable it. When a device is disabled the system performs the following actions: • The message DEVICE DISABLED is displayed on the lower left corner of the ON/OFF Device screen • The SYSTEM OK LED is turned off • The TROUBLE LED flashes • The DISABLED LED is turned on • The system’s buzzer will beep • A Trouble event is logged by the control panel Only active devices can be disabled. When the selected device is not programmed, the message DEVICE NOT PROGRAMMED is displayed on the ON/OFF Device screen. Acknowledge the trouble event by pressing the # key. 9.1.1 Enable/Disable Zone The function of the Enable/Disable zone option is to enable or disable all devices in a particular zone simultaneously. From the ON/OFF Device screen press the NAME key to open the Enable / Disable Zone screen. Select Zone Number and press ON/OFF *Zone:10 Zone Mode Screen 30 ENABLE / DISABLE Zone Select a zone by pressing the up/down arrow keys or keying in the zone number and press the OFF key to disable the zone or press the ON key to enable it. This will disable or enable all devices in the zone. Individual device setting will override zone setting. When a zone is disabled the system performs the following actions: • The SYSTEM OK LED is turned off – Page 50 of 83 – ADR-3000 © 1999 – 2013 Telefire Fire & Gas Detectors Ltd Revision 1.22 March 2013 • The TROUBLE LED flashes • The DISABLED LED is turned on • The system’s buzzer will beep • A Trouble event is logged by the control panel Acknowledge the trouble event by pressing the # key. You will need to acknowledge each device in the zone separately. 9.2 Monitor Test This menu enables the display of the addressable device’s signal output and reference values numerically and graphically, and performing a remote test of each detector. The following types of detectors can be monitored: Photoelectric and Ionization Smoke Detectors, Heat Detectors, Multi-Sensor Detectors, and other I/O devices. The device can be selected by its address as described in the following screen: Select Device and press ENTER *Panel:1 Card:1 Loop:1 Address:3 (--------Device Description--------) Device enabled Screen 31 Device Monitor Selection Select the device and press ENTER, the following screen will be displayed: Add: 3 Photoelectric Detector Value=94 Valarm=81 Vref=94 ▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒▒ Press # for Manual Test Version:25 Screen 32 Device Monitoring Mode The screen contains the device address, the alarm threshold value, the numerical values, and bar-graph display of the device signal output. From this screen a manual test of the detector can be performed, by pressing # key. During the test, the message TESTING will be displayed on the screen. On completion of the test, the message TEST OK or the appropriate error message will be displayed. It is possible to browse from this screen through the various devices, using the arrow keys. When selecting a device that is not programmed in the system, the control panel will display Device Not Programmed in the lower left corner of the Device Monitor Selection screen. When selecting a device that is programmed in the system but is disabled, the control panel will display Device Disabled in the lower left corner of the Device Monitor Selection screen. When selecting a device that exists and enabled, the control panel will display Device Enabled in the lower left corner of the Device Monitor Selection screen. 9.3 Printer Reports This screen serves for selecting a report to be printed, as detailed further on in this Manual. For printing, connect a serial printer to COM 1 connector on the main board. – Page 51 of 83 – ADR-3000 © 1999 – 2013 Telefire Fire & Gas Detectors Ltd Revision 1.22 March 2013 Ensure that the COM 1 field in the SYSTEM CONFIG menu is set to PRINTER. If the ADR-3000 is configured with the optional GIM-232 Galvanic Isolation Module, ensure both jumpers setting of the GIM-232 are set to PRINTER. 1 2 3 4 Device List Active Event List Alarm History Trouble History - 103 3 14 25 Screen 33 Printer Reports Menu DEVICE LIST Prints a list of all active system devices. The total number of active devices is displayed next to the Device List field. EVENT LIST Prints the current system events. ALARM HISTORY Prints the last 250 system events such as Fire Alarm, Alarm Silence, Evacuation, Reset and Programming. TROUBLE HISTORY Prints a list of the last 250 Trouble events, such as device failures and system failures. i Note During printing, a message indicating the percentage of material that has been sent to the printer will be displayed. Press the # key to stop printing. Another way for printing reports is by the host computer and the hyper terminal applet. 9.4 Display Reports The DISPLAY REPORTS menu enables to display on the LCD the Alarm and Trouble History and Device List. 1 Alarm History – 15 2 Trouble History – 33 3 Device List Active – 24 Total Accumulated Alarms:41 4 Quit Screen 34 Display Reports Menu ALARM HISTORY Displays the last 250 system events such as Fire Alarm, Alarm Silence, Evacuation, Reset, and Programming. TROUBLE HISTORY Displays a list of the last 250 trouble events, such as device failures and system failures. DEVICE LIST Lists all active devices. TOTAL ACCUMULATED ALARMS Total number of alarms encountered by the control panel. TROUBLE_HISTORY_LIST -Panel:1 2 of 33 TROUBLE IN 11:36:00 04/11/2004 Card:1 Loop:2 Add:13 communication (--------Device Description--------) Screen 35 Alarm or Trouble History Highlighting the Alarm or Trouble History fields displays the event type, date, time, and device details. – Page 52 of 83 – ADR-3000 © 1999 – 2013 Telefire Fire & Gas Detectors Ltd Revision 1.22 March 2013 Each event is displayed on a separate screen. It is possible to browse through the events by using the arrow keys or the RECALL MEMORY key. Device List enables the display of programmed devices. The number of programmed devices is displayed on the top right side. Pressing the up/down arrow keys will display the next device or the previous one. Pressing the # key will display additional details and characteristics of the device and its configuration. Pressing # again returns to the previous screen. DEVICE LIST PANEL:1 2 of 24 Card:1 Loop:1 Address:14 (--------Device Description--------) Zone:10 Delay:0 # for Details Screen 36 Device Characteristics and Configuration 9.5 Utilities Serves for system test and maintenance. Pressing option 6 UTILITIES will open an additional screen offering the following operations: 1 Lamp Test 5 Card Reset 2 Version 6 History Clear 3 Keyboard Locking 7 Advanced 4 Modem Config Screen 37 Utility Operations 9.5.1 Lamp Test The lamp test turns on all the LEDs on the control panel, for test purposes. It also activates the alarm/trouble buzzer for 2 seconds. 9.5.2 Version This option displays the software and hardware versions of the main board, and the type and software version of the line card(s). Panel: ADR-3001 version 03.02P Bord C Card1 ADR-3002C version 01.68 Screen 38 Control Panel Version 9.5.3 Keyboard Locking The KEYBOARD LOCK function prevents unauthorized people from activating functions by pressing accidentally the operator keys such as silencing an alarm or reset. When the keyboard is locked, no action can be taken in the system, except acknowledge, browsing the memory and displaying alarm and trouble events. The ADR-3000 default configuration is locked keyboard. To change the keyboard locking mode, go to the UTILITIES menu and select KEYBOARD LOCKING. You will need to enter the programmer password to access this submenu. The UP/DOWN arrow keys change the locking mode. Changing to UNLOCKED mode enables the operator/programmer access to silence and reset functions without entering a password. The keyboard will stay unlocked until the control panel is powered off. – Page 53 of 83 – ADR-3000 © 1999 – 2013 Telefire Fire & Gas Detectors Ltd Revision 1.22 March 2013 If DIP Switch 7 is down, the control panel powers up in keyboard locked mode. If DIP Switch 7 is up, the control panel powers up in the same mode (keyboard locked or unlocked) as it was prior to powering down. NFPA 72 Recommendation NFPA recommendation and local regulations in most countries require that the keyboard be locked. NFPA 72 Keyboard Mode:Locked Screen 39 Keyboard Locking Warning After performing system operations, the Operator/Programmer must restore the keyboard locking mode to LOCKED. ! 9.5.4 Card Reset Factory use only. 9.5.5 History Clear Allows clear Alarm history, Trouble history and Alarm counter after installing ADR-3000 system and perform testing. For clear history Dipswitch 7 must be turn On. 9.5.6 Advanced Utilities Menu Factory use only. 9.6 Walk Test This feature allows the testing of all the initiating devices of the system. The device test is performed by placing a magnet near the detector’s test point or by activating the alarm call-points with the test key (supplied with the call-points). Entering the Walk Test mode is done through the main menu and requires a password. From the main menu select WALK TEST. The following message is displayed: WALK TEST OPERATION Select Card No._ Screen 40 Walk Test Entering the card number to be tested. If the selected card is an ADR-3002C (two-loop line card), both loops will be in walk test mode. The other card, if installed, will continue to operate in normal mode. Start testing by initiating the devices. Upon activation of the device, the device alarm indicating LED will light and the device address will be – Page 54 of 83 – ADR-3000 © 1999 – 2013 Telefire Fire & Gas Detectors Ltd Revision 1.22 March 2013 displayed on the LCD. After 15 seconds the system will perform automatic reset to the device. During the automatic test no outputs are activated. An alarm received from a device connected to the card that is not in Walk Test mode will abort the Walk Test procedure and activate the alarm. Two simultaneously alarms from the tested card will abort the Walk Test procedure and activate the alarm. A device that is programmed as delayed will respond to the test immediately. To stop the automatic test process, press the QUIT key. The system aborts the walk test and returns to normal operation if no devices are tested for 15 minutes. – Page 55 of 83 – ADR-3000 © 1999 – 2013 Telefire Fire & Gas Detectors Ltd 10 Revision 1.22 March 2013 Alarm, Trouble, and Supervisory Conditions An alarm, trouble, or supervisory event is clearly notified by indicating LEDs marked FIRE, TROUBLE, or SUPERVISORY accordingly. Additionally, a detailed description is displayed on the LCD screen. Fire alarms, trouble situations, and supervisory events are defined as events. When two or more events are displayed simultaneously, the first event will be displayed and the MEMORY LED will indicate the presence of additional events. The appropriate message of the event number and the total number of events will be displayed on the LCD screen and be saved in the event history log. The alarm events have a higher priority than the trouble events and so will be displayed first on the LCD. To sort through the current event sequence, use the RECALL MEMORY key or the UP/DOWN navigating arrows. Events are displayed in the following priority order: • Fire Alarm events in the sequence they entered the system • System Trouble events • Supervisory and Trouble in the addressable devices Pressing on the CLEAR key returns the display to the first event. The event screen displays the event description time, device description and device type. When pressing the “ADDRESS” key, the device type line will change to the device “PANEL No. CARD No. Loop No. and Address No.” Pressing the NAME key will return to the device description. Acknowledge – After viewing the alarm/trouble details, the operator may acknowledge the event by pressing the # key on the numeric keyboard. The # symbol will be displayed on the left side of the event number field. If additional events occur, the # mark will differentiate the events that were acknowledged previously. 10.1 Alarm Events When the control panel goes on alarm, the red FIRE LED will start to flash, the internal buzzer will sound continuously, and the following will be displayed on the screen: Event 1 15:45 ALARM (First alarm description line) (Last Alarm description line) *MENU, # Acknowledge TOTAL EVENTS:14 Screen 41 Alarm Display The top row shows the event number, the time it occurred, and the type of event, in this case: ALARM. When more than one Alarm events occurs simultaneously: On the second row shows description of the first alarm event On the third row shows description of the most resent alarm event. This row blinking and shows changed from Last Alarm to description event. Total of each types of events shows on the lower row. The MEMORY LED will light and the TOTAL EVENTS field will be updated. When an alarm occurs, the notification devices that are activated can be silenced by pressing the ALARM SILENCE key and entering the operator password. A new Incoming alarm event will reactivate the notification devices. – Page 56 of 83 – ADR-3000 © 1999 – 2013 Telefire Fire & Gas Detectors Ltd Revision 1.22 March 2013 10.1.1 Alarm Verification This feature enables the control panel to ignore expected alarm conditions that cause nuisance alarms. It is allowed to be set only for addressable smoke detectors and to conventional smoke detectors that are connected through an input module. The control panel will ignore an alarm signal of the same detector for the delay period, set in the delay field of the detectors programming screen. The delay time can be set between 0 – 60 seconds. In alarm verification period LED Pre Alarm/AVF will blinking until the end of delay time and alarm event appear. At the verification period, any additional alarm signal indicated by the control panel will activate the alarm condition at once although the alarming devise is programmed with a delay. If no additional alarm is indicated during the verification period, the timer resets and the control panel returns to normal mode. 10.1.2 Alarm Event Operations When an alarm occurs, the following outputs are activated: General Outputs General outputs are activated by any alarm in the control panel. • Main horn output (in J10) • Dialer output (in J9) • Two alarm contacts (in J12) • Programmable alarm output +A-A (in J12) Addressable Outputs Addressable outputs are activated according to the Advanced Activation Matrix. • ADR-823 Three-Channel Input/Output Control Module • ADR-828 Eight-Channel Output Module • ADR-833 Analog Addressable Extinguishing Control Unit Communication Actions • Displaying an Alarm Message on the system’s LCD • Sending an Alarm Message to Remote Annunciators RM-4005 connected to COM 2. • Sending an Alarm Message to the computer or printing the events on the printer if available through COM 1. 10.1.3 Display when there is more than one alarm When there are multiple alarms in the system the control panel shall display Screen 42 on page 58. The first line indicates the event number, the time, and event type. If the dialer is activated the word Dialer shall also be shown. The second line shows the description of the device that caused the first alarm. It is possible to see other events by pressing the Recall Memory key. The third line indicates the description of the device that caused the last alarm. This line does not change. The fourth line indicates the total number of alarms and trouble events in the system, and alternates between the field indicating the number of fault events and the number of disabled devices. – Page 57 of 83 – ADR-3000 © 1999 – 2013 Telefire Fire & Gas Detectors Ltd Revision 1.22 March 2013 Event Alarm Description first alarm Description last alarm Menu Total Alarm Dialer Screen 42 Display for multiple alarm events Pressing the Address key shall display the device’s address. Additional pressing of Address shall alternate between the device’s address and type. Pressing Name key shall display the devices description. 10.2 Trouble Events When a trouble event occurs the yellow TROUBLE LED on the operator’s panel will flash, the LCD will display the event details and the internal buzzer will sound a onesecond beep every four seconds. There are two trouble event categories: • System trouble • Addressable device trouble 10.2.1 System Trouble A failure in the back-up batteries, horns, dialer or computer communication (if COM 1 was defined as Supervise and there is a PC connected running TCS-3040 with the Event Monitor window open), power supply, etc., is defined as a system trouble event, and when the system is updating its programming settings. For example: the next screen describes a battery failure. EVENT 1 12:34 TROUBLE Panel:1 Battery not Connected * MENU TOTAL EVENTS:1 Screen 43 System Trouble Display 10.2.2 Device Trouble Failure associated with addressable devices such as detectors, call points, input modules, output modules, etc., is defined as device trouble event. Example: screen describes a trouble event of an addressable device. EVENT 1 14:56 TROUBLE Communication (------Description line-----) * MENU TOTAL EVENTS:2 Screen 44 Addressable Device Trouble Display On occurrence of a trouble, the internal buzzer will sound. Pressing the SILENCE key will silence the buzzer. The occurrence of a new trouble event will renew buzzer operation. i Note Browsing the system and device events is done as described for browsing the alarm events. – Page 58 of 83 – ADR-3000 © 1999 – 2013 Telefire Fire & Gas Detectors Ltd Revision 1.22 March 2013 10.2.3 Trouble Event Operations When a trouble event occurs, the following outputs are activated: General Outputs • Trouble output T-T+ (in J13) • Trouble relay in (J13) Communication Actions • Displaying a Trouble message on the system’s LCD • Sending a Trouble Message to RM-4005 Remote Annunciators connected to COM 2. • Sending a Trouble Message to the computer or printing the events on the printer if available through COM 1. 10.3 Supervisory Events ADR-3000 fire alarm control panels with software version 3.01E or higher support supervisory function according to UL and EN standards. A supervisory event does not “lock” – at the end of the event the system returns to normal mode without operator intervention. A supervisory event signals the need for a system related action that is not a part of the fire detection system although it is supervised by it such as a sprinkler system. The supervisory function allows monitoring switches and activations as a result of change in their condition using the fire alarm infrastructure. In certain cases there is a need to activate an output as a result of a fault such as notification of loss of pressure in an extinguishing container, a closed sprinkler valve, etc., The new supervisory function is intended to respond to this need. A supervisory event will cause the following response in the control panel: • The SUPERVISORY LED will flash • The TROUBLE LED will turn on • The trouble buzzer will sound • An event will be logged in the system’s Trouble History • A supervisory output will be activated if there is a corresponding output defined 10.3.1 Operation during a supervisory event A supervisory event will cause the following response in the control panel: • The SUPERVISORY LED will flash • The TROUBLE LED will turn on • The trouble buzzer will sound • An event will be logged in the system’s Trouble History • A supervisory output will be activated if there is a corresponding output defined i Note Two types of devices can be defined as Supervisory” • SUPERVISORY_SWITCH – only an ADR-805 input module or the IDC input of an ADR-823 module • SUPERVISORY_OUT – any output module Both input and output devices should be configured as the same zone. – Page 59 of 83 – ADR-3000 © 1999 – 2013 Telefire Fire & Gas Detectors Ltd Figure 25 An example of using the supervisory function – Page 60 of 83 – Revision 1.22 March 2013 ADR-3000 © 1999 – 2013 Telefire Fire & Gas Detectors Ltd 11 Peer to Peer Network 11.1 Network Characteristics Revision 1.22 March 2013 A network can consist of as many as 32 control panels establishing a system network. All nodes in such a network are equally connected. By programming, each control panel in the network is able to respond to alarm or trouble events of other programmed control panels. This will be followed by regular event notification and the exact address of it. Every control panel should be given a different ID number called a “Panel Number”. Two control panels with the same number in the same network will cause a fault condition. In order to allow a certain control panel to respond to events of other control panels “Partners” (Overseen control panels) the Partners should be registered as “Partners” in the control panel that oversees them. This registration is done in the System Config menu. The Overseeing control panel is able to execute bell silence of events accrued at the partner control panels, and reset them as well. Corresponding configurations should be done at each control panel separately. 11.2 Network Configuration The registration of partners of each control panel is done separately. For setting the partners numbers: Select 1 – SYSTEM PROGRAM from the Main Menu Screen, 1 System Program 5 Display Reports 2 On/Off Device 6 Utilities 3 Monitor Test 7 Walk Test 4 Printer Reports 8 Quit Screen 45 Main Menu Screen Then select 3 – SYSTEM CONFIG from the System Program Menu, 1 Device Program 5 Change Password 2 Time Program 6 Detector Init 3 System Config 7 Diagnostics 4 Day/Night Program 8 Quit Screen 46 System Program Menu Screen The first two fields should be set to configure the control panel for network operating. PANEL In this field the ID number of the control panel is defined. PARTNER In this field the number of partners of this control panel is displayed. Panel:3 Card:1Active RM-language:English COM 1 Supervise:OFF Partner:2 Active RM Control:3 Active J12 Out: silenced COM 1:Computer Screen 47 System Configuration Screen To register other control panels to the partner list move the cursor to the field then use the up/down arrow key for selecting the control panel you want to register, then press the ON key. – Page 61 of 83 – ADR-3000 © 1999 – 2013 Telefire Fire & Gas Detectors Ltd 11.3 Revision 1.22 March 2013 Network Hierarchy Each control panel can be configured with different supervisory privilege on a peer-topeer basis. The control panels in a network can be set to oversee other control panels and can be overseen at the same time. This peer-to-peer configuration enables flexibility in planning the network configuration. Some configurations are shown in the following examples: 11.3.1 Two control panels configured as peer to peer In this example both control panels are overseeing each other. The settings are: In Panel 1: Partner 2 – ON In Panel 2: Partner 1 – ON Figure 26 Network example 1 11.3.2 Two control panels configured as master / slave In this example Panel 1 oversees Panel 2, while Panel 2 controls itself only. The settings are: In Panel 1: Partner 2 – ON In Panel 2: Partner 1 – OFF Figure 27 Network example 2 11.3.3 Hierarchal Network This example shows a network of five control panels that are located on several floors: (lobby, mezzanine, first, second, and third floors). – Page 62 of 83 – ADR-3000 © 1999 – 2013 Telefire Fire & Gas Detectors Ltd Revision 1.22 March 2013 The control panel at the lobby and the one in the mezzanine need to manage all control panels. The other control panels will only be managed and do not manage any other control panels. Partner setting will be as follows: Panel 1 (Entrance): partner 2, 3, 4, and 5: ON (manage panels 2, 3, 4, and 5). Panel 2 (Maitenance): partner 1, 3, 4, and 5: ON (manage panels 1, 3, 4, and 5). Panel 3 (first floor): all partners are set to OFF (do not manage any panel). Panel 4 (second floor): all partners are set to OFF (do not manage any panel). Panel 5 (third floor): all partners are set to OFF (do not manage any panel). Figure 28 Network example 3 11.3.4 Network Capabilities All network accessories that can be connected to a single control panel are common. In this example: a computer that is connected to panel 1, a NET-3000 to panel 2 and a second computer with a printer to panel 3. A printer can be connected directly to a control panel printing the events of other control panels. In this example, remote annunciator RM-4005 can display events of the control panels that are registered as partners. Downloading or uploading of panel configuration can be executed through one connected PC, regardless of partner registration. – Page 63 of 83 – ADR-3000 © 1999 – 2013 Telefire Fire & Gas Detectors Ltd Figure 29 Network Capabilities – Page 64 of 83 – Revision 1.22 March 2013 ADR-3000 © 1999 – 2013 Telefire Fire & Gas Detectors Ltd 12 System Fuses 12.1 Power Supply Fuses Fuse 12.2 Fuse Function and Location F1 Battery Fuse (located on power supply card) F2 Main Fuse (located on power supply card) Table 5 Revision 1.22 March 2013 Rating1 6.3A 3.15A Power Supply Fuses Main Board Fuses Fuse Fuse Function and Location Rating1 F1 Horn Output (J10) 0.5A F2 24Vdc _B Out (JP7 and J8) 2.0A F3 24Vdc _A Out (J11) 2.0A F4 Dialer (J9) 0.5A F5 General Trouble (J13-1 and J13-2); Alarm (J12-1 and J12-2); and Aux 24V (J13-7 and J13-8) 0.5A Table 6 Main Board Fuses Figure 30 Main Board fuse location 1 Power supply fuses and main board (ADR-3001) fuses are 5 * 20mm slow-blow fuses – Page 65 of 83 – ADR-3000 © 1999 – 2013 Telefire Fire & Gas Detectors Ltd Warning To avoid damage to the system ensure that replacement fuses are rated as per the above tables. Disconnect AC input and backup batteries prior to changing fuses. ! 12.3 Revision 1.22 March 2013 Line Card Fuses Card ADR-3002 ADR-3002C Table 7 Fuse Description Rating F1 Loop fuse 0.5A SB2 F1 and F2 Loop fuses 0.5A SB SMT Line card fuses Note The analog lines are electronically protected against short-circuits. The fuses serve as a secondary protection. i 2 Power ADR-3002 fuse is 5 * 20mm slow-blow fuse – Page 66 of 83 – ADR-3000 © 1999 – 2013 Telefire Fire & Gas Detectors Ltd 13 Revision 1.22 March 2013 Periodic Testing Periodic maintenance shall be, as a minimum, performed per NFPA 72. Maintenance shall be performed by a trained or authorized Telefire representative. The system should be inspected entirely at least twice a year, or as required by national and/or local fire codes. All devices, system wiring and component functions should be tested and maintained. These inspections should be performed in addition to the routine maintenance activities such as cleaning the detectors (which should be performed in accordance with Telefire’s instructions). Maintenance and test actions shall be conducted by a company or service technician authorized by Telefire. Records of all inspection and maintenance activities should be kept. i 13.1 Note This testing shall be performed by authorized service personnel that are employed by authorized companies. Weekly Inspection – performed by the Site's Safety Supervisor The site's safety supervisor should inspect the control panel weekly and verify that all of the following conditions exist: • Both green LEDs are on and are not blinking • None of the yellow or red LEDs are on or blinking • The control panel's trouble buzzer does not sound • The LCD display states SYSTEM OK and the correct time Open the control panel's front door and verify that the red LEDs on the line card flash occasionally. Call you service company if any of these conditions is not met – Page 67 of 83 – ADR-3000 © 1999 – 2013 Telefire Fire & Gas Detectors Ltd 14 Revision 1.22 March 2013 Warnings and Limitations i i Note Fire alarm systems are composed and assembled of different devices and subsystems, such as control panels, annunciators, smoke detectors, heat detectors, manual call points, extinguishing activation devices, and annunciating devices intended to alert to fire / smoke. Using this system does not ensure protection from or prevention of fire and/or smoke damages, but proper use of the system may reduce fire and smoke damages. Proper system configuration design, including all of its components and infrastructure, as well as proper installation according to the manufacturers' instructions and the applicable standards – are a conditioned precedent for the proper and efficient function of the system. The designer and installer should have the appropriate skills and qualifications for performing said installation and all damages or losses resulting from improper design and/or installation lie with the designer and/or installer alone. All loss or damage caused by improper action shall lie with the originator of said improper action. The manufacturer shall not be liable for any fire and/or fire damages caused by fire in location where fire systems are installed and or results of direct or indirect fire damage that may be caused to any persons and/or property and/or third parties as a result of using the product and/or resulting from its inaction. Note Do not install, operate, or maintain this product before fully reading this manual. – Page 68 of 83 – ADR-3000 © 1999 – 2013 Telefire Fire & Gas Detectors Ltd 15 Revision 1.22 March 2013 Troubleshooting This table describes trouble events that may be displayed during installation, normal operation and maintenance operations. Two types of “trouble events” may occur: system- or device trouble. The following table describes the trouble messages, the cause of the trouble and actions to be taken. i 15.1 Note The hex sign (#) in the error message tables below indicate a number that indicates the panel number, card number, loop number, or device address. System Failure The following table lists error messages sorted alphabetically. Locate the error message you encountered and troubleshoot according to the possible cause and recommended repair action. Error Message Possible Causes Repair Action 24V_A F3 fuse_blow 24Vdc OUTPUT A fuse blown. Replace fuse F3. 24V_B F2 fuse_blow 24Vdc OUTPUT B fuse blown. Replace fuse F2. AC power not connected Fault in primary power to control panel, or main fuse burned out. Check mains or fuse. Alarm out Fuse Blow F5 Alarm Output (J12) Fuse (F5) blowout Check Alarm Output voltage and replace fuse Alarm out not connected Cutoff of alarm output (J12 A- and A+). Check the line and EOL resistor 5.1KΩ. Alarm out short_circuit Short of Alarm Output line (J12 A- and A+). Check the cause of the short and eliminate. Battery 24V Low Damaged or uncharged battery Check voltage on JP2 on ADR-4004TSW power supply module. Output should be about 27.3V. Change batteries if voltage is OK, change power supply if not. Battery Low Current Damaged battery, high resistance Replace batteries. Battery not connected Battery not connected Check battery fuse, or battery connections. Card # defective Fault in line card. Replace the line card. Card # Loop # short Short of SLC analog line. Find the short cause and eliminate. – Page 69 of 83 – ADR-3000 © 1999 – 2013 Telefire Fire & Gas Detectors Ltd Error Message Revision 1.22 March 2013 Possible Causes Repair Action Card # Loop # Fuse blow Line card’s fuse burned out. Find the short cause and replace fuse. Card # Program Process Is displayed during card programming process. The message no longer displays after programming. Card configured, not exist Line card programmed but not installed. Check connection, or cancel card programming. Card exists – not configured Line card installed but not programmed. Add the card in SYSTEM CONFIG programming. COM 1 Supervise Error Loss of connection to PC (happens only when COM 1 Supervise is enabled and a PC is running the TCS-3040 software has the Events Monitor window open) Ensure a proper connection between COM 1 and the PC. Dialer Fuse Blow Dialer Fuse blowout (F4). Check dialer current and replace Fuse. Dialer not connected Cutoff of dialer output line. Check the line and EOL resistor 5.1KΩ. Dialer short Short of dialer output line. Check the cause of the short and eliminate. Ground Fault Negative Short or leakage between ground and system’s (–) connections. Find the source in wiring or water leak. Ground Fault Positive Short or leakage between ground and system’s (+) connections. Find the source in wiring or water leak. Horn Fuse Blow_F1 Horn Fuse blown (F1). Check Horn voltage and replace fuse. Horn not connected Cutoff of horn output line. Check the line and EOL resistor 5.1KΩ. Horn short Short of Horn output line. Check the cause of the short and eliminate. Trouble out Fuse Blow Trouble Output (J13) Fuse (F5) blowout. Check Trouble Output voltage and replace fuse. Trouble out not connected Cutoff of Trouble output (J13) Check the line and EOL resistor 5.1KΩ. Trouble out short Short of Trouble Output line (J13) Check the cause of the short and eliminate Table 8 Troubleshooting Table – System Failure – Page 70 of 83 – ADR-3000 © 1999 – 2013 Telefire Fire & Gas Detectors Ltd 15.2 Revision 1.22 March 2013 Remote Annunciator Panel (RM-4005) Failure Error Message Remote Control not connected Possible Causes Improper connection, or 24Vdc problem Repair Action • • Table 9 15.3 Check wiring and connections. Check RM-4005 address. Troubleshooting Table – RM-4005 Addressable Devices Failure Error Message Possible Causes Repair Action Trouble – disabled The device is set to OFF (disabled) To enable device: select ENABLE / DISABLE DEVICE (main menu), select the detector’s address and press the ON key Trouble –Exting. Activate Automatic Extinguisher was activated Replace empty cylinder. Go to device programming mode, select the appropriate device and press PROG Trouble 24V Low Low or nonexistent 24Vdc input to an ADR-8XX module or TIP-224A Check connections and repair Trouble AC Power TPS-34A has no A/C input Check cause and repair Trouble Battery cut TPS-34A open in backup battery connections Check connections and repair Trouble Communication No communication with addressable device Check connections and device presence Trouble Cut Circuit Cutoff circuit in I/O device of non-addressable line Locate the cause and repair Trouble Fuse Battery Blown TPS-34A battery fuse Locate the cause and replace fuse Trouble Fuse_24V 24V Fuse in I/O Module burned out Find the short cause and replace fuse Trouble Maintenance Dusty or contaminated detector Replace detector and bring for maintenance Trouble short-circuit Short in an I/O device of non-addressable line Locate the cause and repair Table 10 Troubleshooting Table – Addressable Devices – Page 71 of 83 – ADR-3000 © 1999 – 2013 Telefire Fire & Gas Detectors Ltd 15.4 Programming Trouble Error Message Possible Causes Repair Action Trouble Message Possible Cause Repair Actions Device Count Device count error Check DEVICE LIST:ACTIVE and compare to “as made” documentation Extra device Device connected to SLC line and not programmed Add device address by programming. Enter SYSTEM PROGRAM, DEVICE PROGRAM, and add the device Same address Two devices with same address Change the address of one of the devices Type mismatch Wrong device type Install the appropriate device or correct device type programming Table 11 15.5 Revision 1.22 March 2013 Troubleshooting Table – Programming Trouble LonWorks Trouble Error Message Partner – Panel# not connected Table 12 Possible Causes Panel # is powered off, or open or short in LON cabling Troubleshooting Table – LonWorks Trouble – Page 72 of 83 – Repair Action Check connections and control panel presence ADR-3000 © 1999 – 2013 Telefire Fire & Gas Detectors Ltd Revision 1.22 March 2013 16 Detector Sensitivity Selection 16.1 Smoke Detector Sensitivity Selection Table Least Sensitive Sensitivity Obscuration (% per foot) Table 13 16.2 2.0 Day Night Default Default 1.8 1.6 1.4 1.2 Most Sensitive 1.0 0.8 Smoke Detector Sensitivity Heat Detector Sensitivity Table Heat Detectors can be set in two modes: • FIXED TEMPERATURE – The alarm point can be set between 50°C – 90°C in steps of 1°C. • RATE OF RISE – The detector will alarm when the rate of temperature rise is equal or higher then the setting in the Sensitivity Field, in the range of 7°C/minute – 13°C/minute in 1°C/minute steps. Sensitivity Fixed Temperature Rate of Rise Table 14 16.3 Least Sensitive Default Most Sensitive 90°C 50°C 50°C 13°C per minute 9°C per minute 7°C per minute Heat Detector Sensitivity Multisensor Photoelectric / Heat Detector Setting A smart algorithm is used by the TPH-442A’s powerful processor to analyze the ambient temperature, its rate of rise and the trend of these parameters. It then passes a value to the control panel. Set the detector’s sensitivity between 2 (most sensitive) and 10 (least sensitive). Sensitivity Multi-sensor setting Least Sensitive 10 – Page 73 of 83 – Default Most Sensitive 5 2 ADR-3000 © 1999 – 2013 Telefire Fire & Gas Detectors Ltd Power Supply and Battery Calculations Fill in the following table to calculate the total load on the system’s power supply during quiescence (standby) and state alarm. Quiescence Device Internal modules and General Output 17 Revision 1.22 March 2013 QTY Current Alarm Total Current Total ADR-3000/1 { } X 70.00 mA = 200.0 mA = ADR-3000/2 { } X 80.00 mA = 200.0 mA = ADR-3000/3 { } X 85.00 mA = 220.0 mA = ADR-3000/4 { } X 95.00 mA = 220.0 mA = LON-3000/7000 { } X 10.00 mA = 10.0 mA = NET-3000 { } X 120.00 mA = 120.0 mA = GIM-232 { } X 1.50 mA = 1.5 mA = 300.0 mA = 40.0 mA = TDM-500i { } X 20.00 mA = TIP-224 { } X 0 mA = Other NAC { } X mA = mA = Other NAC { } X mA = mA = Other NAC { } X mA = mA = ADR-805 Rev B { } X 0.26 mA = 3.0 mA = ADR-805 Rev C { } X 0.20 mA = 2.0 mA = ADR-812 { } X 0.15 mA = 2.1 mA = ADR-818 { } X 0.26 mA = 2.1 mA = ADR-823 { } X 0.30 mA = 2.8 mA = 0 ADR-828 { } X 0.39 mA = 3.0 mA = ADR-833 { } X 6.50 mA = 6.5 mA = LI-3000 { } X 2.20 mA = 4.0 mA = TFH-280A { } X 0.20 mA = TFL-1AN { } X 0 mA = TFO-480A { } X 0.29 mA 2.6 mA = 10.0 mA = = 2.6 mA = 0 TPB-800ASR { } X 0.12 mA = 2.0 mA = TPB-800ASY { } X 0.12 mA = 2.0 mA = TIP-224A { } X 0.12 mA = 5.0 mA = TPB-800ASR { } X 0.12 mA = 2.0 mA = TPB-800ASY { } X 0.12 mA = 2.0 mA = TPH-482A { } X 0.29 mA = 2.6 mA = TPS-34A { } X 0.34 mA = 0.5 mA = TFP-3000 { } X 15.00 mA = 70.0 mA = TFP-1CP { } X 0.25 mA = 2.8 mA = TFP-806 { } X 0.25 mA = 2.8 mA = TFP-828 { } X 0.39 mA = 3.0 mA = (a) = Totals Table 15 (b) = Power Requirement – Internal and SLC At least one and no more than two line cards (ADR-3002 and ADR-3002C) of any combination can be installed in the ADR-3000. Only one module (NET-3000 or GIM-232) can be installed in the lower expansion slot. – Page 74 of 83 – ADR-3000 © 1999 – 2013 Telefire Fire & Gas Detectors Ltd SLC connected modules and devices Device QTY Revision 1.22 March 2013 Quiescence Current Total Alarm Current Total ADR-812 { } X 11.5 mA = 80.0 mA = ADR-818 { } X 40.0 mA = 100.0 mA = ADR-823 { } X 4.0 mA = 32.0 mA = ADR-828 { } X 10.0 mA = 125.0 mA = ADR-833 { } X 20.0 mA = 120.0 mA = TIP-224A { } X 0.1 mA = 45.0 mA = RM-4005 { } X 40.0 mA = 70.0 mA = TLA-22 { } X 2.0 mA = 0.0 mA = TLA-23 { } X 2.0 mA = 0.0 mA = TLA-33 { } X 3.0 mA = 0.0 mA = TLA-42 { } X 2.0 mA = 0.0 mA = TLA-44/1 or TLA-44/4 { } X 5.0 mA = 0.0 mA = TLA-110 { } X 1.5 mA = 0.0 mA = TLA-120 { } X 1.5 mA = 0.0 mA = TLA-130 { } X 1.5 mA = 0.0 mA = TLA-140 { } X 1.5 mA = 0.0 mA = TLA-150 { } X 1.5 mA = 0.0 mA = TLA-160 { } X 1.5 mA = 0.0 mA = TLA-165 { } X 1.5 mA = 0.0 mA = TLA-170 { } X 1.5 mA = 0.0 mA = TLA-180 { } X 1.5 mA = 0.0 mA = TLA-190 { } X 1.5 mA = 0.0 mA = TFP-3000 { } X 34.0 mA = 80.0 mA = TFP-1CP { } X 0.0 mA = 2.0 mA = TFP-806 { } X 0.0 mA = 2.0 mA = TFP-828 { } X 10.0 mA = 125.0 mA = Other NAC { } X mA = mA = Other NAC { } X mA = mA = Other NAC { } X mA = mA = Total 24Vdc current consumption Table 16 (c) (d) Power Requirement – 24Vdc First fill in the quantities of devices attached to the system in Table 15 and calculate total current load of the internal configuration and load on the SLC loop. Secondly calculate the power draw from the system’s 24V output (Table 16). Thirdly copy the appropriate fields into Table 17 and calculate battery requirement and system load. Multiply the number of devices of each type with the current and calculate the total current. When connecting indicating output devices such as horns and bells to output modules, add their current to the total current for both standby mode and alarm mode. – Page 75 of 83 – ADR-3000 © 1999 – 2013 Telefire Fire & Gas Detectors Ltd Standby Mode Current from Control Panel (A) (a) ({ } + + { Revision 1.22 March 2013 Standby Mode Current from the 24Vdc source (A) (c) X 24 Hours 60 Hours 4 Hours }) X { Standby Mode Amp Hr. = } = + Alarm Mode Current from Control Panel (A) (b) ({ } + + { Alarm Mode Current from the 24Vdc source (A) (d) X 5 Minutes (0.084H) }) X { = } = Ampere Hours Sum = Ampere Hours Sum X 1.2 derating factor = Table 17 Alarm Mode Amp Hr. Power Requirement – Final Calculation The ADR-3000’s power supply module can charge batteries in capacity of up to 12AH. The battery enclosure can contain two 12V sealed lead-acid batteries, up to 20 (W) by 7 (D) by 12 (H) cm each. For fire alarm control panels requiring larger batteries use the BC-3000 external battery enclosure. This enclosure can contain two 12V sealed lead-acid batteries, up to 20 (W) by 10 (D) by 15 (H) cm each. If the system requires larger battery capacity than 12 AH add the TPS-34A Auxiliary Power Supply with its own batteries. Please refer to the TPS-34A manual for additional details about the TPS-34A auxiliary power supply. Additional TPS-34A power supplies are required if one or more of the following conditions is true: • The quiescence 24V current draw exceeds the control panel's power supply limitations (0.5A for ADR-4004TSW) • The 24V current draw in alarm exceeds the control panel's power supply limitations (4.0A for ADR-4004TSW) • There is a need for batteries in capacity that exceeds the control panel's power supply limitations (12AH for ADR-4004TSW) • The voltage drop on the 24V lines exceeds allowed limitation (no more than 2V at the furthest device, while still leaving sufficient voltage for the device to operate). i Note TPS-34A Analog Addressable Auxiliary Power Supplies should be installed as close as possible to the devices they activate to reduce power loss. TPS-34A auxiliary power supplies should not be shared between multiple control panels or between line cards on the same control panel. TPS-34A auxiliary power supplies may be shared between the two loops of a single ADR-3002C line card. – Page 76 of 83 – ADR-3000 © 1999 – 2013 Telefire Fire & Gas Detectors Ltd Revision 1.22 March 2013 18 Wire Characteristics and Length Limitations 18.1 Wire Characteristics’ influence on System Performance The following table summarizes the way wiring characteristics influence system performance: Characteristic Voltage Outputs Electric Resistance Minimal Very high Capacitance High No effect Inductance High Minimal Mechanical Strength High High Table 18 18.2 SLC Wiring Characteristics’ influence on System Performance SLC Loop Wire Use a twisted pair wire 12 to 18 AWG and follow the guidelines in the table below for wire selection. Cable Type Cross Section 18 AWG 0.8mm2 950m 3,130 ft 16 AWG 1.3mm2 1,520m 4,970 ft 14 AWG 2.1mm2 2,420m 7,940 ft 12 AWG 3.3mm2 3,830m 12,580 ft Table 19 Maximum Branch Length for Given Cross-Section Maximum SLC Loop Length Resistance measurements: Short the end of one branch and measure the resistance from the connections of the loop to the control panel. Repeat for each branch. Make sure that the sum of all branches in a loop does not exceed 40Ω. Figure 31 Testing Loop Resistance Capacitance measurements: Connect all branches and ensure that the total capacitance of a loop does not exceed 1.0µF Figure 32 Testing Loop Capacitance – Page 77 of 83 – ADR-3000 © 1999 – 2013 Telefire Fire & Gas Detectors Ltd 18.3 Revision 1.22 March 2013 NAC (Notification Appliance Circuit) There are no distance limitations for NAC outputs. Make sure that the voltage drop does not exceed 2V. 18.4 24Vdc Output There are no distance limitations for 24Vdc outputs. Make sure that the voltage drop does not exceed 2V. 18.5 LON-3000/7000 Network Wiring – Copper Cables In order to maximize the distance between ADR-3000 control panels interconnected in a LonWorks network use a twisted pair cable of the types described in the following table. The wires should enter the cabinet through the "POWER LIMITED" wire entrances on either the top right or bottom right of the ADR-3000 cabinet. Belden 85102 Level IV 22 AWG JY (St) Y 2*0.8 Linear Topology: Maximum length between two furthest control panels (meters) 2,700 2,700 1,400 900 Free Topology: Maximum length between two furthest control panels (meters) 500 400 400 320 Free Topology: Total cable length 500 500 500 500 Maximum cable resistance (Ohm per Km) 15 28 55 73 Capacitance (nF per Kilometer) 56 72 56 (@ 1MHz) 98 Table 20 18.6 Belden 8471 Maximum LON Cabling Length LON-3000/7000 Network Wiring – Fiber-Optics Cables Use fiber-optic cables when there exists a cable length limitation, a requirement for galvanic isolation, or the existence of electromagnetic interference. Use LRW-102 to allow the control panels communicate via fiber-optic cables. 18.7 RM-4005 Cabling The RS-485 standard does not specify cable characteristics. However, it is based on the RS-422 standard, which recommends 24 AWG twisted pair cable with a shunt capacitance of 16 pF per foot and 100 Ohm characteristic impedance. These recommendations should be used for RS-485 systems as well. Many available cables are designed specifically to meet the recommendations of RS-422 and RS-485 specification. Another choice is the same cable commonly used in the Shielded Twisted Pair Ethernet cabling. This cable, commonly referred to as STP Category 5 cable, is defined by the EIA / TIA / ANSI 568 specification. The extremely high volume of Category 5 cable used makes it widely available and very inexpensive, often less than half the price of specialty RS-422 / 485 cabling. The cable has a typical capacitance of 14.5pF/ft and characteristic impedance of 100 Ohms. Maximum total cable length is 4,000’ (1,220m). – Page 78 of 83 – ADR-3000 © 1999 – 2013 Telefire Fire & Gas Detectors Ltd 19 Revision 1.22 March 2013 Compatibility The ADR-3000 is compatible with the following devices: 19.1 Input Devices • • • • • • • • • • • • 19.2 Output Devices • • • • • 19.3 TFO-480A Analog Addressable Photoelectric Smoke Detector TPH-482A Analog Addressable Multisensor Photoelectric Smoke / Heat Detector. TFH-280A Analog Addressable Heat Detector TFB-180 Standard Base TFO-440A Analog Addressable Photoelectric Smoke Detector TPH-442A Analog Addressable Multisensor Photoelectric Smoke / Heat Detector. TFH-220A Analog Addressable Heat Detector TFB-110A Common Base for Analog Addressable Detectors TPB-800ASR Manual Fire Alarm Call Point and TPB-800ASY Manual Extinguishing Call Point ADR-805 Flow Switch Interface Module ADR-812 Two-Channel Input Module ADR-818 Eight-Channel Input Module TFL-1AN Auxiliary Indicator for Analog Detectors ADR-828 Eight-Channel Output Module ADR-823 Three-Channel Input/Output Module ADR-833 Extinguishing Control Unit TIP-224A Analog Addressable Indoor Alarm Notification Sounder Other Devices • • • TPS-34A Analog Addressable Auxiliary Power Supply EPI-3000 Electromagnetic and Surge Protection Interface Module LI-3000 Line Isolation Module for Class A/B – Page 79 of 83 – ADR-3000 © 1999 – 2013 Telefire Fire & Gas Detectors Ltd 20 Revision 1.22 March 2013 Warnings and Limitations i i Note Fire alarm systems are composed and assembled of different devices and subsystems, such as control panels, annunciators, smoke detectors, heat detectors, manual call points, extinguishing activation devices, and annunciating devices intended to alert to fire / smoke. Using this system does not ensure protection from or prevention of fire and/or smoke damages, but proper use of the system may reduce fire and smoke damages. Proper system configuration design, including all of its components and infrastructure, as well as proper installation according to the manufacturers' instructions and the applicable standards – are a conditioned precedent for the proper and efficient function of the system. The designer and installer should have the appropriate skills and qualifications for performing said installation and all damages or losses resulting from improper design and/or installation lie with the designer and/or installer alone. All loss or damage caused by improper action shall lie with the originator of said improper action. The manufacturer shall not be liable for any fire and/or fire damages caused by fire in location where fire systems are installed and or results of direct or indirect fire damage that may be caused to any persons and/or property and/or third parties as a result of using the ADR-3000 and/or resulting from its inaction. Note Do not install, operate, or maintain this ADR-3000 before fully reading this manual. – Page 80 of 83 – ADR-3000 © 1999 – 2013 Telefire Fire & Gas Detectors Ltd 21 Standards Compliance 21.1 EN 54 – Options with Requirements Revision 1.22 March 2013 The ADR-3000 conforms fully to European standards BS EN 54-2:1998 and BS EN 54-4:1998 and the following optional features: • Output to fire alarm routing equipment – EN 54-2 Section 7.9 option with requirements • Delays to Outputs – EN 54-2 Section 7.11 option with requirements • Dependencies on more than one alarm signal – EN 54-2 Section 7.12 option with requirements • Alarm Counter – EN 54-2 Section 7.13 option with requirements • Fault signals from points – EN 54-2 Section 8.3 option with requirements • Total loss of power supply – EN 54-2 Section 8.4 option with requirements • Disablement of addressable points – EN 54-2 Section 9.5 option with requirements • Test condition – EN 54-2 Section 10 option with requirements 21.2 CP-10 The ADR-3000 conforms to Singapore standard SS CP 10:2005 and includes the following features: • Fire alarm sounder silencing – Clause 2.5.8 • Fire alarm buzzer silencing – Clause 2.5.9 • Alarm verification feature (AVF) – Clause 2.5.11 – Page 81 of 83 – ADR-3000 © 1999 – 2013 Telefire Fire & Gas Detectors Ltd 22 Revision 1.22 March 2013 Specification Width: ........................................................................... 465mm Height: .......................................................................... 350mm Depth (Including door): ................................................. 98mm Weight (basic configuration – without batteries) ................. 7,290 gr. Operating Temperature Range: .................................... -10°C – +60°C (14°F – 140°F) Relative Humidity Range:.............................................. 10% – 93%, non-condensing Operating Voltage (mains input) ................................... 230Vac +10% / -15% Operating Current (Quiescent mode, basic configuration): .................. 70mA 24Vdc Maximum output Continuous............................................................. 0.5A Alarm ..................................................................... 3.5A Battery capacity The ADR-3000’s power supply module can charge batteries in capacity of up to 12AH. The battery enclosure can contain two 12V sealed lead-acid batteries, up to 20 (W) by 7 (D) by 12 (H) cm each. For fire alarm control panels requiring batteries that will not fit in the ADR-3000 chassis use the BC-3000 external battery enclosure. This enclosure can contain two 12V sealed lead-acid batteries, up to 20 (W) by 10 (D) by 15 (H) cm each. If the system requires battery capacity larger than 12AH add TPS-34A Auxiliary Power Supply with its own batteries. Please refer to the TPS-34A manual for additional details about the TPS-34A auxiliary power supply. Event memory............................................................... 500 events total: 250 Trouble events 250 Alarm events Specifications are subject to change without prior notice. – Page 82 of 83 – ADR-3000 © 1999 – 2013 Telefire Fire & Gas Detectors Ltd 23 Revision 1.22 March 2013 Certification Telefire’s ADR-3000 Analog Addressable Control Panel has the following approvals: • EN 54 Approved • UL 864 Edition 9 Listed – file S9002 • GOST Approved • CP 10 Approved • IS 1220 Approved • CE Marked – Page 83 of 83 –