Issued January 2010 11452 DATA SHEET CK TYPE CONTACTORS Based on GE Contactor CK Series Datasheet 11452 Series CK Three and four pole contactors Three and four pole contactors 150 to 825A (AC-3) 200 to 1250A (AC-1) • Control circuit: Alternating current up to 690V Direct current up to 500V • Degree of protection IP00 (IPxxB with accessories) • CK07...CK13: auxiliary and coil terminals originally protected against accidental contacts. Protection for power contacts on request (see accessories) • Terminals protected against accidental contacts according to VDE 0106 T.100, VBG4. • CK_ _E_with electronic module suitable for DC and AC. (50/60Hz) • CK contactors always provided with one auxiliary contact block BCLL11 (1NO+1NC) Standards IEC/EN 60947-1 IEC/EN 60947-4-1 IEC/EN 60947-5-1 EN 50005 UL 508 NEMA ICS 1 BS 5424 & 775 Standard voltages CSA 22.2/14 CENELEC HD 419 NFC 63-110 ASE 1025 UNE 20109 VDE 0660/102 To complete the catalogue number, replace the symbol © by the code corresponding to the voltage and frequency of the control circuit. Alternating current (V) Three-pole contactors: Four-pole contactors: © C 50Hz Approvals 60Hz D F CK75CA3..., CK08CA3..., CK85BA3... CK07BA4..., CK08BA4... G H I 24 42 48 24 48 J K 110 127 110 120 M N R S T 220 240 230 220 277 U V 380 400 W X Y Z 415 440 500 660 690 240 380 480 440 600 Alternating current (V). Dual-frequency coil Three-pole contactors: CK75CA3..., CK08CA3..., CK85BA3... Four-pole contactors: CK07BA4..., CK08BA4... cULus © 1 2 3 6 13 50/60Hz 24 48 110 230 400 Alternating current(V) Lloyd’s Register Bureau Veritas RINA Three-pole contactors: Four-pole contactors: © 50/60Hz J N U CK13BA3... CK13BA4... Y Control circuit with rectifier bridge Z © 110 220 380 480 600 240 440 500 660 J N U 50Hz 110 220 380 230 400 60Hz 120 240 480 Direct current (V). With electronic module (0.7 ... 1.3 x Us) Three-pole contactors: CK75CE3...., CK08CE3..... © Voltage WD WE WF WH WJ WN 24 33 48 72 110 220 Alternating c. / Direct c. (V). With electronic module (0.8 ... 1.10 x Us) Order codes ! Aux. contact blocks ! Accessories & Spares ! Technical data ! Dimensional drawings ! C.18 pg. 2 pg. 3 pg. 4 pg. 5 pg. 12 Based on GE Contactor CK Series Datasheet Three-pole & four-pole contactors: © Voltage D F J N U CK ....... E...... Y 24 42 110 220 380 440 28 48 127 250 415 500 Page 1 of 13 11452 Three pole contactors Max.operat.current Admissible power AC-3 NonMotors inductive <440V, 220V 380V 415V 440V 500V 230V 400V 440V load 3~ 50/60Hz kW kW kW kW kW AC-1 AC-3 HP HP HP HP HP A A 250 150 45 75 80 80 100 60 100 108 108 135 Electrical Control circuit: endurance Alternating current Cat. AC-3 Operations Cat. no. (1) Pack Control circuit: A.C. / D.C. Cat. no. (1) Pack 1.7x106 Ref. no. see bottom CK75CA311 © 1 Ref. no. see bottom CK75CE311 © 1 185 55 75 90 100 100 110 125 135 135 150 1.2x106 CK08CA311 © 1 CK08CE311 © 1 315 205 65 88 110 125 125 132 150 170 170 180 1.7x106 CK85BA311 © 1 CK85BE311 © 1 315 250 75 132 132 132 160 100 180 180 180 220 1.5x106 CK09BE311 © 1 450 309 90 160 160 185 200 125 220 220 250 270 1,1x106 CK95BE311 © 1 600 420 125 220 230 230 300 170 300 312 312 405 1x106 CK10CE311 © 1 700 550 160 280 315 315 400 220 380 425 425 540 0.8x106 CK11CE311 © 1 1000 700 220 375 400 425 480 300 510 540 650 0.7x106 CK12BE311 © 1 1250 825 250 450 450 450 500 340 610 610 610 680 0.7x106 Spare coil CK75CA3 ... CK08CA3 CK85BA3 CK13BA3 Control circuit with incorporated rectifier bridge CK13BA3 Coil Electronic module CK75CE3 ... CK08CE3 CK85BE3 ... CK95BE3 CK12BE3 CK10CE3 ... CK11CE3 CK75CE3 ... CK08CE3 CK85BE3 ... CK95BE3 CK12BE3 CK10CE3 ... CK11CE3 Series CK 250 CK13BA311 © 1 C12168 C04255 C08998 C09120 © © © © 1 1 1 1 KB4E KB5E KB6E KB7E KM4E KM5E KM6E KM7E © © © © © © © © 1 1 1 1 1 1 1 1 (1)To complete the catalogue number, replace the symbol © by the code corresponding to the voltage and frequency of the control circuit. (see pg .1) For reference numbers, see index in chapter X. Based on GE Contactor CK Series Datasheet C.19 Page 2 of 13 11452 Series CK Three and four pole contactors Four pole contactors Max.oper. Electrical Admissible power current AC-3 endurance AC-1 380V 220V 380V 415V 440V 500V Non230V 400V inductive 400V Cat. loads AC-3 AC-1 kW A kW kW kW kW kW Operations A 200 55 105 76 131 143 151 173 1x106 Control circuit: Alternating current Control circuit: A.C. / D.C. Cat. no. (1) Cat. no. (1) Pack Pack Ref. no. see bottom CK07BA411 © 1 Ref. no. see bottom CK07BE411 © 1 CK08BA411 © CK08BE411 © 1 1 325 100 185 123 214 233 247 281 0.6x106 400 132 250 152 263 287 304 346 0.6x106 CK09BE411 © 1 500 160 309 191 329 359 380 415 0.6x106 CK95BE411 © 1 600 220 408 228 395 431 456 519 0.5x106 CK10CE411 © 1 700 280 530 266 460 503 533 606 0.4x106 CK11CE411 © 1 1000 375 680 381 658 719 762 866 0.4x106 CK12BE411 © 1 1250 450 800 476 822 898 952 1082 0.6x106 KB5E KB6E KB7E KM5E KM6E KM7E 1 1 1 1 1 1 Spare coil CK07BA4 CK08BA4 CK13BA4 Control circuit with incorporated rectifier bridge CK13BA4 Coil CK07BE4 CK08BE4 ... CK95BE4, CK12BE4 CK10CE4 ... CK11CE4 CK07BE4 CK08BE4 ... CK95BE4, CK12BE4 CK10CE4 ... CK11CE4 Electronic module CK13BA411 © 1 C04255 C04787 C08998 C09120 1 1 1 1 © © © © © © © © © © (1)To complete the catalogue number, replace the symbol © by the code corresponding to the voltage and frequency of the control circuit. (see pg .1) Auxiliary instantaneous contact block Number of contacts Contacts Cat. no. Ref. no. Pack 0 0 BCLL20 BCLL11 104706 104707 10 10 combinations of more than 2 blocks 2 2 0 0 0 2 1 1 0 0 2 0 2 0 0 BRLL20 BRLL11 BRLL02 104704 104705 106622 10 10 10 •3 •4 Side mounting 2 2 2 1 •1 •7 •2 •8 0 1 0 0 •5 •6 For reference numbers, see index in chapter X. C.20 Based on GE Contactor CK Series Datasheet Page 3 of 13 11452 Accessories For use with: Transient voltage suppressor Mounting Pole terminal protection Ue Cat. no. Fixation to the coil terminals, that allows simultaneous use with the auxiliary contact blocks. CK75 ... CK08 AC 24V - 48V BSLR3G CK75 ... CK08 AC 50V - 127V BSLR3K CK75 ... CK08 AC 130V - 240V BSLR3R CK75 ... CK08 AC 227V - 500V BSLV3U CK85 ... CK13 CK85 ... CK13 CK85 ... CK13 Mechanical interlock Voltage AC AC AC 24V 260V 415V KRC24 KRC48/260 KRC380/415 Ref. no. Pack 104716 104717 104718 110836 10 10 10 10 104760 104761 104762 10 10 10 CK07B ... CK12 Horizontal BEKH 104763 1 CK07B ... CK95 CK10C ... CK12B CK13 Vertical Vertical Vertical BEKVS 1 BEKVA 1 BEKV 104786 104785 104764 1 1 1 CK75C ... CK08C CK85B ... CK12B CK08B ... CK12B 1 pole. VDE0106 1 pole. VDE0106 1 pole. VDE0106 CM1CA5F C09476 C09479 105200 104766 204800 1 6 8 CK75C ... CK08C CK85B ... CK95B CK10C ... CK12B 1 pole IPXXB 1 pole IPXXB 1 pole IPXXB PTPCK75 PTPCK95 PTPCK11 103747 103748 103749 1 3 1 Type Cat. no. Ref. no. Pack 113612 113613 113614 113505 113615 113616 113899 113617 113618 113619 113620 113621 1 1 1 1 1 1 1 1 1 1 1 1 Contactors 3P Contactors 4P Spares For use with: Contact kits One set consists of two fixed contacts, one moving contact and accessory parts. When contact replacement is needed, it is recommended to replace all the contacts at the same time. CK07B CK75C CK08C CK08B CK85B CK09B CK09B CK95B CK10C CK11C CK12B CK13B NA NA NA NA NA NA NA NA NA NA NA NA Based on GE Contactor CK Series Datasheet Contactors 4P Contactors 4P V1107BA V1175CA V1108CA V1108B4 V1185BA V1109BA V1109B4 V1195BA V1110CE V1111CE V1112BA V1113BA Page 4 of 13 11452 Three and four pole contactors Series CK Conformity to standards IEC/EN 60947-1 IEC/EN 60947-4-1 CENELEC HD 419 UL 508 EN 50005 Mounting positions NF C 63-110 ASE 1025 CSA 22.2/14 UNE 20109 BS 5424 & 775 NEMA ICS 1 VDE 0660/102 Approvals cULus NOM Lloyd’s Register RINA FI Bureau Veritas With the same pick-up and drop-out voltage With the same rated power Ambient conditions Storage temperature Operation temperature Altitude -55ºC to +80ºC -40ºC to +60ºC Nominal values 90%Ie 80%Ue 80%Ie 75%Ue up to 3000m from 3000 up to 4000m from 4000 up to 5000m Climatic resistance (IEC 68-2) Continuous tests 40 / 125 / 56 Cold (72h) Temperature Dry heat (96h) Temperature Relative humidity Humid heat (56h) Temperature Relative humidity Cyclical test First half-cycle (12h)) Low temperature Relative humidity Second half-cycle (12h) Low temperature Relative humidity Number of consecutive cycles -40ºC +125ºC < 50% +40ºC 95% +25ºC 93% +55ºC 95% 6 Terminal capacity and tightening torque CK07B Solid Finely stranded w/end sleeve Finely stranded w/o end sleeve Stranded AWG wires Tightening torque (mm2) (mm2) (mm2) (mm2) (mm2) (Nm) (Lb x in) Finely stranded w/end sleeve (mm2) AWG wires with end sleeve Busbars Tightening torque (mm2) (Nm) (Lb x in) Based on GE Contactor CK Series Datasheet CK75C CK08C CK08B CK95B CK10C CK11C CK12B CK13B 1 x 120 2 x 95 1 x 300 2 x 107 2 (25 x 5) 8 70 1 x 240 2 x 150 1 x 500 2 x 300 2 (25 x 5) 23 200 2 x 185 2 x 240 – – 2 x 500 2 (35 x 10) 31.5 275 – 2 (35 x 10) 31.5 275 – 2 (60 x 10) 31.5 275 1.5...95 2...35 2...50 1.5...95 16...00 8 70 2 x 350 2 (35 x 10) 31.5 275 Page 5 of 13 11452 Power circuit Three pole contactors CK75C CK08C CK85B CK09B CK95B CK10C CK11C CK12B CK13B Rated thermal current Ith at θ ≤ 40ºC (A) Rated operational current Ie AC-3 (A) Rated operational voltage Ue (V) Rated insulation voltage Ui (V) Maximum continuous current AC-1 (A) Frequency limits (Hz) Making capacity (RMS) (IEC 947) (A) Breaking capacity (RMS) (IEC 947) Ue ≤ 400V (A) Ue = 500V (A) Ue = 690V (A) Ue = 1000V (A) Short-time current 1 sec. (A) 5 sec. (A) 10 sec. (A) 30 sec. (A) 1 min. (A) 3 min. (A) Short-time current(min.) Protec. against short-circuits with fuses. Without TOR Coord. type “1” gL/gG (A) Coord. type "2" gL/gG (A) Without welding gL/gG (A) Impedance per pole (mΩ) Power dissipation AC-1 (W) per pole AC-3 (W) Insulation resistance Between adjacent poles (MΩ) Between poles and earth (MΩ) Between input and output (MΩ) 250 150 1000 1000 250 25...400 1850 250 185 1000 1000 250 25...400 2200 315 205 1000 1000 315 25...400 2500 315 250 1000 1000 315 25...400 2500 450 309 1000 1000 450 25...400 3700 600 420 1000 1000 600 25...400 6500 700 550 1000 1000 700 25...400 6500 1000 700 1000 1000 1000 25...400 8400 1250 825 1000 1000 1250 25...400 8250 1600 1600 1000 350 2500 2500 2300 1250 900 600 10 1850 1850 1200 350 2500 2500 2300 1250 900 600 10 2000 2000 1660 850 4000 3200 2400 1400 1000 750 10 3500 3500 2200 1100 5500 3500 2500 1600 1200 900 10 3500 3500 2200 1100 5500 3500 2500 1600 1200 900 10 5600 5600 5000 3000 7500 5200 4000 2800 1800 1200 10 5600 5600 5000 3000 7500 5200 4000 2800 1800 1200 10 7300 7000 6700 3500 9700 7700 6100 4400 3500 2300 10 6600 6600 6000 3500 11600 8800 7350 5300 4500 2800 10 355 250 200 0.30 19 6.8 355 250 200 0.30 19 10.3 500 315 250 0.28 27.7 11.7 500 400 315 0.28 27.7 17.5 630 500 425 0.28 56.7 26.7 1250 630 500 0.15 54.3 26.5 1250 800 630 0.13 63.7 45.3 1250 1000 800 0.14 140 68.6 2x800 1250 1000 0.11 171.8 74.8 > 10 > 10 > 10 > 10 > 10 > 10 > 10 > 10 > 10 > 10 > 10 > 10 > 10 > 10 > 10 > 10 > 10 > 10 > 10 > 10 > 10 > 10 > 10 > 10 > 10 > 10 > 10 Four pole contactors CK07B CK08B CK09B Rated thermal current Ith at θ ≤ 40ºC (A) Rated operational voltage Ue (V) Rated insulation voltage Ui (V) Maximum continuous current AC-1 (A) Frequency limits (Hz) Making capacity (RMS) (IEC 947) (A) Breaking capacity (RMS) (IEC 947) Ue ≤ 400V (A) Ue = 500V (A) Ue = 690V (A) Ue = 1000V (A) Short-time current 1 sec. (A) 5 sec. (A) 10 sec. (A) 30 sec. (A) 1 min. (A) 3 min. (A) Recovery time (min.) Short-circuit protection with fuse Without TOR Coord. type "1" gL/gG (A) Coord. type “2” gL/gG (A) Without welding gL/gG (A) Impedance per pole (mΩ) Power dissipation per pole AC-1 (W) Insulation resistance Between adjacent poles (MΩ) Between poles and earth (MΩ) Between input and output (MΩ) CK95B CK10C CK11C CK12B CK13B 200 690 1000 200 25...400 1150 325 1000 1000 325 25...4000 1850 400 1000 1000 400 25...400 2500 500 1000 1000 500 25...400 3700 600 1000 1000 600 25...400 6500 700 1000 1000 700 25...400 6500 1000 1000 1000 1000 25...400 6700 1250 1000 1000 1250 25...400 8250 950 950 800 – 2100 1500 1150 750 550 350 10 1600 1600 1000 350 2500 2500 2300 1250 900 600 10 3500 3500 2200 1100 5500 3500 2500 1600 1200 900 10 3500 3500 2200 1100 5500 3500 2500 1600 1200 900 10 5600 5600 3500 2000 7500 5200 4000 2800 1800 1200 10 5600 5600 3500 2000 7500 5200 4000 2800 1800 1200 10 6700 6700 6000 3500 9700 7700 6100 4400 3500 2300 10 6600 6600 6000 3500 11600 8800 7350 5300 4500 2800 10 315 250 0.45 200 18 500 400 0.32 315 33.8 500 400 0.28 315 44.8 630 500 0.28 425 56.7 1250 630 0.15 500 61.2 1250 800 0.13 630 68.6 1250 1000 0.14 800 140 2x800 1250 0.11 1000 171.8 > 10 > 10 > 10 > 10 > 10 > 10 > 10 > 10 > 10 > 10 > 10 > 10 > 10 > 10 > 10 > 10 > 10 > 10 > 10 > 10 > 10 > 10 > 10 > 10 Based on GE Contactor CK Series Datasheet Page 6 of 13 11452 Three and four pole contactors Series CK Electrical endurance Mixed category AC4 / AC3 Electrical endurance for mixed category (AC-3/ AC-4) is calculated with the following formula: Electrical endurance (AC-3/AC-4) Electrical endurance (AC-3) = 1 + % ops AC-4 100 X ( Elec.endur. (AC-3) -1 Elec.endur. (AC-4) ) Category AC1 Number of operations Ic=Ie for all voltages Category AC2 . Number of operations Rated motor power (Ic = 2.5 Ie) Based on GE Contactor CK Series Datasheet Page 7 of 13 11452 Electrical endurance (continued) Category AC3 . Number of operations Rated motor power (Ic = Ie) Category AC4 . Number of operations Rated motor power (Ic = 6 Ie) Based on GE Contactor CK Series Datasheet Page 8 of 13 11452 Three and four pole contactors Series CK Three pole contactors. Control circuit Alternating current Rated insulation voltage Ui Standard voltages Us (50/60 Hz) Operating limits Switch-on Switch-off Consumption. Monofrequency coils Magnetic circuit CK....A closed CK....E Magnetic circuit CK....A openCK....E (VA) Power CK....A dissipation CK....E Consumption. Bifrequency coils Magnetic circuit 50Hz closed (CK....A) 60Hz Magnetic circuit 50Hz open (CK....A) 60Hz Power 50Hz dissipation (CK....A) 60Hz Power factor Magnetic circuit CK....A closed CK....E Magnetic circuit CK....A open CK....E Opening and closing times at Us Making time at excitation (NO) Breaking time at de-energisation (NO) Mechanical endurance Maximum rate No load AC-1/AC-3 at rated power. AC-2 at rated power AC-4 at rated power CK75CA CK08CA CK85BA CK85BE CK09BE CK95BE CK10CE CK11CE CK12BE CK13BA (V) (V) 1000 24...690 1000 24...690 1000 24...690 1000 24...690 1000 24...690 1000 24...690 1000 24...690 1000 24...690 1000 24...440 xUs xUs 0.8...1.1 0.4...0.6 0.8...1,1 0.4...0,6 0.8...1.1 0.4...0.6 0.8...1,1 0.4...0.6 0.8...1.1 0.4...0.6 0.8...1.1 0.4...0.6 0.8...1.1 0.4...0.6 0.8...1.1 0.4...0.6 0.8...1.1 0,.25...0.55 (VA) (VA) (VA) (W) (W) 42 500 21 - 42 500 21 - 46 20 830 425 17 3.5 20 425 3.5 20 425 3.5 23 680 4 23 680 4 25 750 4.5 6 2760 5 - (VA) (VA) (VA) (VA) (W) (W) 46 38.3 568 473 23 19.1 46 38.3 568 473 23 19.1 60 50 1082 901 22.2 18.5 - - - - - - (cos ϕ) (cos ϕ) (cos ϕ) (cos ϕ) 0.4 0.6 - 0.4 0.6 - 0.37 0.6 - - - - - - approx. 1 approx. 1 - (ms) 20...25 20...25 36...40 60...70 60...70 80...90 80...90 70...80 50...55 (ms) 10...13 10...13 10...15 13...17 13...17 40...50 40...50 70...80 115...130 106 ops 10 10 10 10 10 10 10 10 3 ops./h ops./h ops./h ops./h 2400 600 250 150 2400 600 250 150 2400 600 250 150 1200 600 250 150 1200 600 250 150 900 300 200 120 900 300 200 120 900 300 200 120 600 120 120 120 CK75CE CK08CE CK85BE CK09BE CK95BE CK10CE CK11CE CK12BE 1000 24...500 1000 24...500 1000 24...500 1000 24...500 1000 24...500 1000 24...500 1000 24...500 1000 24...500 0.8...1.1 0.4...0.6 0.8...1.1 0.4...0.6 0.8...1.1 0.35...0.5 0.8...1.1 0.4...0.6 0.8...1.1 0.4...0.6 0.8...1.1 0.4...0.6 0.8...1,1 0.4...0,6 0.8...1.1 0.4...0.6 2 135 2 135 3.5 350 3.5 350 3.5 350 4 405 4 405 4.5 650 60...70 60...70 60...70 60...70 60...70 80...90 80...90 70...80 13...17 13...17 13...17 13...17 13...17 40...50 40...50 40...50 10 10 10 10 10 10 10 10 1200 600 150 1200 600 150 1200 600 150 1200 600 150 1200 600 150 900 300 120 900 300 120 900 300 120 Direct current Rated insulation voltage Ui (V) Standard voltages Us (50/60 Hz) (V) Operating limits Switch-on xUs Switch-off xUs Consumption. Magnetic circuit closed (W) Magnetic circuit open (W) Opening and closing times at Us Making time (ms) at excitation (NO contacts) Breaking time (ms) at de-energisation (NO contacts) Mechanical endurance 106 ops. Maximum rate No load ops./h AC-3 at rated power ops./h AC-4 at rated power ops./h Based on GE Contactor CK Series Datasheet Page 9 of 13 11452 Four pole contactors. Control circuit Alternating current Rated insulation voltage Ui (V) Standard voltages Us (50/60 Hz) (V) Operating limits Switch-on xUs Switch-off xUs Consumption. Monofrequency coils Magnetic circuit CK....A (VA) closed CK....E (VA) Magnetic circuit CK....A (VA) openCK....E (VA) Power CK....A (W) dissipation CK....E (W) Consumption. Bifrequency coils Magnetic circuit 50Hz (VA) closed (CK....A) 60Hz (VA) Magnetic circuit 50Hz (VA) open (CK....A) 60Hz (VA) Power 50Hz (W) dissipation (CK....A) 60Hz (W) Power factor Magnetic circuit CK....A (cos ϕ) closed CK....E (cos ϕ) Magnetic circuit CK....A (cos ϕ) open CK....E (cos ϕ) Opening and closing times at Us Making time (ms) at excitation (NO) Breaking time (ms) at de-energisation (NO) Mechanical endurance 106 ops. Maximum rate No load ops./h AC-1/AC-3 at rated power ops./h CK07BA CK07BE CK08BA CK08BE CK09BE CK95BE CK10CE CK11CE CK12BE CK13BA 1000 24...690 1000 24...690 1000 24...690 1000 24...690 1000 24...690 1000 24...690 1000 24...690 1000 110...440 0.8...1.1 0.4...0.6 0.8...1.1 0.4...0.6 0.8...1.1 0.4...0.6 0.8...1.1 0.4...0.6 0.8...1.1 0.4...0.6 0.8...1.1 0.4...0.6 0.8...1.1 0.4...0.6 0.8...1.1 0.25...0.55 46 20 830 425 17 3.5 130 25 2860 750 53 4.5 25 750 4.5 25 750 4.5 23 680 4 23 680 4 25 750 4.5 6 2760 5 - 60 50 1082 901 22.2 18.5 159.3 132.7 3509 2924 65.3 54.4 - - - - - - 0.37 0.6 - 0.37 0.6 - - - - - - approx. 1 approx. 1 - 36...40 60...70 70...80 70...80 110...115 80...90 110...115 50...55 10...15 13...17 70...80 70...80 70...80 40...50 70...80 70...80 10 10 10 10 10 10 10 3 2400 600 900 600 900 600 900 600 900 300 900 300 900 300 600 120 CK07BE CK08BE CK08BE CK95BE CK10CE CK11CE CK12BE 1000 24...500 1000 24...500 1000 24...500 1000 24...500 1000 24...500 1000 24...500 1000 24...500 0.75...1.1 0.4...0.6 0.8...1.1 0.4...0.6 0.8...1.1 0.4...0.6 0.8...1.1 0.4...0.6 0.8...1.1 0.4...0.6 0.8...1.1 0.4...0.6 0.8...1.1 0.4...0.6 3.5 350 4.5 650 4.5 650 4.5 650 4.5 650 4.5 650 4.5 650 60...70 70...80 70...80 70...80 80...90 80...90 110...115 13...17 70...80 70...80 70...80 40...50 40...50 70...80 10 10 10 10 10 10 10 1200 600 900 600 900 600 900 600 900 600 900 300 900 300 Direct current Rated insulation voltage Ui (V) Standard voltages Us (V) Operating limits Switch-on xUs Switch-off xUs Consumption. Magnetic circuit closed (W) Magnetic circuit open (W) Opening and closing times at Us Making time (ms) at excitation (NO contacts) Breaking time (ms) at de-energisation (NO contacts) Mechanical endurance 106 ops Maximum rate No load ops./h AC-3 at rated power ops./h Based on GE Contactor CK Series Datasheet Page 10 of 13 11452 Three and four pole contactors Series CK Contact sequence Basic contactor Auxiliary contact blocks Lateral mounted BCLL 20 BRLL 20 Three-pole contactors 3 NO CK75C... CK08C... 0 CK85B... CK09B... CK95B... 0 10.4 14 0 CK10C... CK11C... 0 12 17 0 CK12B... CK13B... 0 12.6 17.5 0 CK07B... 0 7.7 10.7 0 CK08B... CK09B... CK95B... 0 10.4 14 0 CK10C... CK11C... 0 12 17 0 CK12B... CK13B... 0 12.6 17.5 0 7.3 10.4 0 3.5 BCLL 11 BRLL 11 10.4 0 14 0 3.5 17 0 3.5 17.5 0 10.7 0 14 0 3.5 17 0 3.5 17.5 0 3.5 10.4 1,8 3.5 3.5 14 1,8 3.5 17 1.8 3.5 17.5 1.8 3.5 3.5 10.7 3.5 14 1.8 3.5 1.8 3.5 17 1.8 3.5 17.5 1.8 Numbering of the terminals Three pole contactors Four pole contactors CK75C_ _3_ ... CK13B _ _3_ CK07B_ _4_ ... CK13B _ _4_ Auxiliary contact blocks. Lateral mounting Voltage suppressor block BCLL20 BCLL11 K/RC... BRLL20 BRLL11 Mechanical interlock BEKV, BEKVA1, BEKVS1, BEKVH Based on GE Contactor CK Series Datasheet Page 11 of 13 11452 Dimensional drawings Three pole contactors 3.500 kg 3.500 kg . . . . CK75C CK08C . Three and four pole contactors Series CK CK85B CK09B CK95B 6.100 kg 6.200 kg 6.300 kg CK10C CK11C 11.00 kg 11.00 kg CK12B 18.00 kg CK13B 35.00 kg . Based on GE Contactor CK Series Datasheet Page 12 of 13 Mechanical interlock Four pole contactors CK07B 4.700 kg Mechanical interlock . BEKH 0.350 kg CK75C3... - CK08C3... CK85B3... - CK95B3... CK10C3... - CK11C3... CK12B3... CK08B CK09B CK95B 22.30 kg 22.80 kg CK12B 23.30 kg . A 55 55 33 75 14.90 kg 15.10 kg 15.30 kg CK10C CK11C CK13B 11452 BEKVA1 BEKVS1 A 550 0.900 kg 350 0.800 kg BEKV 1.200 kg 44.00 kg . Based on GE Contactor CK Series Datasheet Page 13 of 13