ILB-CP07 - Architectural Star Lighting

advertisement
IOTA ENGINEERING
ILB-CP07
PRODUCT SPECIFICATION SHEET
LED CONSTANT POWER EMERGENCY BATTERY PACK
MODEL NO:
TYPE:
PROJECT:
COMMENTS:
LED OPERATION
7W LED load at 18-48VDC Nominal
PRODUCT ADVANTAGES
DESCRIPTION:
The ILB-CP07 from IOTA Engineering is a UL Recognized LED emergency battery
pack that allows the same LED fixture to be used for both normal and emergency
operation. In the event of a power failure, the ILB-CP07 switches to the emergency
mode and operates the existing fixture for 90 minutes. The unit contains a battery,
charger, and converter circuit in a single can and is available in different mounting
configurations for individual fixture requirements. The ILB-CP07 will operate a nominal 7W LED load with constant power with a rated output voltage of 18V-48V. The
Constant Power design of the ILB-CP07 maintains the output wattage to the LED
array even as the system voltage diminishes.
TECHNICAL SPECIFICATIONS
Input Voltage............................................ (Universal) 120-277VAC, 50/60Hz
Input Rating....................................................................................... 7 Watts
Output Voltage.............................................................................. 18-48VDC
Output Current.................................. 0.35A (@18VDC) - 0.145A (@48VDC)
Output Power..................................................................7 Watts (Regulated)
Emergency Operation...................................................................90 minutes
Operating Temp............................................................................0° to 50° C
Battery............................................................... High Temp Nickel-Cadmium
24 Hour Recharge
7-10 Year Life Expectancy
Weight................................................................................. (-A, -R) 3.0 lbs.
(-B, -TM) 2.5 lbs. (-J, -R-J) 2.75 lbs.
UL Conditions of Acceptability..................................... Must be factory wired
Battery temperature must not exceed 50° C
Constant Power Design maintains emergency
illumination through 90-minute runtime without
suffering light degradation
Two-wire universal AC input
Self-sensing output voltage allows the CP Series
to operate various product types, such as down
lights, troffers, or strips, reducing product SKUs
for emergency options
FEATURES
Six mounting configurations available
Long life high temperature recyclable
Ni-Cad battery
Galvanized steel case
Includes single-piece TBTS test switch and
charge indicator accessory kit
For use with switched or unswitched fixtures
5-Year Warranty. See Warranty Page
for details.
Meets or exceeds all National Electrical Code
and Life Safety Code Emergency Lighting
Requirements
Suitable for use in Damp Locations
CASE DIMENSIONS
13.0″ x 2.2″ x 1.25″ (mounting center 12.6″)
HEIGHT
1.25"
LENGTH 13.0"
WIDTH 2.2"
MOUNTING CENTER 12.6"
P.O. BOX 11846 TUCSON, AZ 85734
(520) 294-3292 • FAX (520) 741-2837
www.iotaengineering.com
IOTA REV 012014
ILB-CP07
LED CONSTANT POWER EMERGENCY BATTERY PACK
ILB-CP07-A SAMPLE SPECIFICATION
Emergency lighting shall be provided by using a standard LED fixture equipped with
an ILB-CP07-A LED emergency battery pack. The ILB-CP07-A shall consist of
OPTIONS
TEST KIT CONFIGURATION
TBTS
a high temperature, maintenance-free nickel cadmium battery, charger board
and an electronic circuit enclosed in a 13.0″ x 2.2″ x 1.25″ vandal-resistant
galvanized steel case. The unit is designed for installation on the LED fixture or
remote-mounting and is equipped with 3/8″ flex for wiring to the fixture or ballast
compartment. A single-piece test switch and charge indicator accessory kit shall
be included. The LED emergency battery pack shall operate an LED load of up
MOUNTING CONFIGURATION
-A (Dual Flex unit)
to 7W with constant wattage at a rated current output of 0.35A - 0.145A for a
minimum of 90 minutes in the emergency mode. The ILB-CP07-A shall have 7
watts of input power and a battery capacity of 15.5 watt hours. The ILB-CP07-A is
UL Recognized and meets or exceeds all NEC and Life Safety Code Emergency
Lighting Requirements. The ILB-CP07-A features universal input and is warranted
-B (Integral Non-Flex unit)
for a full five (5) years from the date of purchase.
-J (Single Flex Junction Box Mount unit)
ILB-CP07-A SAMPLE WIRING DIAGRAM
ILB-CP WITH TBTS TEST ACCESSORY
-R (Dual Flex unit with Reflector-Mount TBTS switch)
RED/WHITE (+)
ø
-TM (Top-Mounting Non-Flex unit)
÷ UNIT CONNECTOR
WHITE/RED
RED OR RED/BLK
FLEX B
WHITE/BLACK
WHITE/BLACK
ILB
BATTERY
PACK
LED
ARRAY
BLUE/WHITE (-)
FLEX A
BLK/ORG (120 TO 277V, 50/60Hz)
UNSWITCHED
WHITE
COMMON
RED (+)
BLUE (-)
WHITE/BLACK
WHITE/BLACK
COMMON
WHITE
-R-J (Single Flex with Reflector-Mount TBTS switch)
SWITCHED OR
UNSWITCHED LINE
ø
BLACK (120V)
ORANGE (277V)
AC DRIVER
DRIVER (-)
DRIVER (+)
÷ DO NOT MATE CONNECTOR UNTIL INSTALLATION
IS COMPLETE AND AC POWER IS SUPPLIED.
ø TEST ACCESSORY LEADS-OBSERVE PROPER
POLARITY WIRING.
ILBCP_TBTS_A.EPS
REMOTE MOUNTING
When battery packs are remote mounted, consult Customer Service for the maximum allowable distance between the battery
pack and the LEDs.
IOTA REV 012014
IOTA ENGINEERING PO BOX 11846 TUCSON, AZ 85734
TEL: 1-800-866-IOTA (4682) FAX: (520) 741-2837 WEB: www.iotaengineering.com