© Siemens AG 2008
SIRIUS . SENTRON . SIVACON
Catalog News LV 1 N • April 2008
Low-Voltage Controls and Distribution
© Siemens AG 2008
3RW Soft Starters
General data
■ Overview
The advantages of the SIRIUS soft starters at a glance:
• Soft starting and smooth ramp-down1)
• Stepless starting
• Reduction of current peaks
• Avoidance of mains voltage fluctuations during starting
• Reduced load on the power supply network
Rated current up to 40 °C
Rated operational voltage
Motor rating at 400 V
• Inline circuit
• Inside-delta circuit
Ambient temperature
6
Soft starting/ramp-down
Voltage ramp
Starting/stopping voltage
Starting and ramp-down time
Torque control
Starting/stopping torque
Torque limit
Ramp time
SIRIUS 3RW30
Standard applications
SIRIUS 3RW40
Standard applications
SIRIUS 3RW44
High-Feature applications
A
V
3 ... 106
200 ... 480
12.5 ... 432
200 ... 600
29 ... 1214
200 ... 690
kW
kW
°C
1.5 ... 55
--25 ... +60
5.5 ... 250
--25 ... +60
15 ... 710
22 ... 1200
0 ... +60
✔1)
✔
40 ... 100
0 ... 20
-----
✔
✔
40 ... 100
0 ... 20
-----
✔
✔
20 ... 100
1 ... 360
✔
20 ... 100
20 ... 200
1 ... 360
✔
--------------------1
-2 controlled phases
✔
✔
✔
✔
--
✔
✔
✔
✔2)
✔3)
✔
---------------1
-2 controlled phases
✔
✔
✔
✔
--
✔
✔
✔
✔
✔
✔
✔
✔
✔
✔4)
✔4) 5)
✔4) 5)
✔
With PROFIBUS DP (optional)
(optional)
✔
✔
✔
✔
✔6)
✔
3
✔
3 controlled phases
✔
✔
✔
✔
✔4)
%
s
%
%
s
Integral bypass contact system
Intrinsic device protection
Motor overload protection
Thermistor motor protection
Integrated remote RESET
Adjustable current limiting
Inside-delta circuit
Breakaway pulse
Creep speed in both directions of rotation
Pump ramp-down
DC braking
Combined braking
Motor heating
Communication
External display and operator module
Operating measured value display
Error logbook
Event list
Slave pointer function
Trace function
Programmable control inputs and outputs
Number of parameter sets
Parameterization software (Soft Starter ES)
Power semiconductors (thyristors)
Screw terminals
Spring-loaded terminals
UL/CSA
CE marking
Soft starting under heavy starting conditions
Configuring support
Win-Soft Starter, electronic selection slider ruler, Technical Assistance ++49 911 895 5900
✔ Function is available; -- Function is not available.
1)
2)
3)
Only soft starting available for 3RW30.
Optional up to size S3 (device variant).
Available for 3RW40 2. to 3RW40 4.; optional for 3RW40 5. and
3RW40 7..
6/2
Siemens LV 1 N · 04/2008
• Reduction of the mechanical load in the operating mechanism
• Considerable space savings and reduced wiring compared
with conventional starters
• Maintenance-free switching
• Very easy handling
• Fits perfectly in the SIRIUS modular system
4)
5)
6)
Calculate soft starter and motor with size allowance where required.
Not possible in inside-delta circuit.
Trace function with Soft Starter ES software.
You can find more information on the Internet at:
http://www.siemens.com/softstarter
© Siemens AG 2008
3RW Soft Starters
3RW30
for standard applications
■ Overview
The SIRIUS 3RW30 soft starters reduce the motor voltage
through variable phase control and increase it in ramp-like mode
from a selectable starting voltage up to mains voltage. During
starting, these devices limit the torque as well as the current and
prevent the shocks which arise during direct starts or wye-delta
starts. In this way, mechanical loads and mains voltage dips can
be reliably reduced.
Soft starting reduces the stress on the connected equipment
and results in lower wear and therefore longer periods of troublefree production. The selectable start value means that the soft
starters can be adjusted individually to the requirements of the
application in question and unlike wye-delta starters are not
restricted to two-stage starting with fixed voltage ratios.
The SIRIUS 3RW30 soft starters are characterized above all by
their small space requirements. Integrated bypass contacts
mean that no power loss has to be taken into the bargain at the
power semiconductors (thyristors) after the motor has started
up. This cuts down on heat losses, enabling a more compact
design and making external bypass circuits superfluous.
■ Application
The 3RW30 soft starters are suitable for soft starting of
three-phase asynchronous motors.
Due to two-phase control, the current is kept at minimum values
in all three phases throughout the entire starting time. Due
to continuous voltage influencing, current and torque peaks,
which are unavoidable in the case of wye-delta starters, for
instance, do not occur.
Application areas
• Pumps
• Heat pumps
• Hydraulic pumps
• Presses
• Conveyors
• Roller conveyors
• Screw conveyors
Various versions of the SIRIUS 3RW30 soft starters are available:
• Standard version for fixed-speed three-phase motors, sizes
S00, S0, S2 and S3, with integrated bypass contact system
• Version for fixed-speed three-phase motors in a 22.5 mm
enclosure without bypass
6
Soft starters rated up to 55 kW (at 400 V) for standard applications in three-phase networks are available. Extremely small
sizes, low power losses and simple start-up are just three of the
many advantages of this soft starter.
Siemens LV 1 N · 04/2008
6/3
© Siemens AG 2008
3RW Soft Starters
3RW30
for standard applications
■ Selection and ordering data
3RW30 18-1BB14
3RW30 28-1BB14
3RW30 38-1BB14
Ambient temperature 40 °C
Ambient temperature 50 °C
Rated
Rated power of inducoperation motors for rated
tional cur- operational voltage Ue
1)
rent Ie
Rated
Rated power of induction
operamotors for rated operational
tional cur- voltage Ue
1)
rent Ie
A
230 V
400 V
500 V
kW
kW
kW
A
200 V
230 V
460 V
575 V
hp
hp
hp
hp
3RW30 47-1BB14
Size
DT
Order No.
3RW30 03-2CB54
Price
per PU
PU
PS*
(UNIT,
SET, M)
PG
Weight
per PU
approx.
Rated operational voltage Ue 200 ... 480 V2)
• With screw terminals
3.6
6.5
9
0.75
1.5
2.2
1.5
3
4
----
3
4.8
7.8
0.5
1
2
0.5
1
2
1.5
3
5
----
S00
S00
S00
}
}
}
3RW30 13-1BB@4
3RW30 14-1BB@4
3RW30 16-1BB@4
1 1 unit 131
1 1 unit 131
1 1 unit 131
0.580
0.580
0.580
12.5
17.6
3
4
5.5
7.5
---
11
17
3
3
3
3
7.5
10
---
S00
S00
}
}
3RW30 17-1BB@4
3RW30 18-1BB@4
1 1 unit 131
1 1 unit 131
0.580
0.580
• With spring-loaded terminals
3.6
6.5
9
0.75
1.5
2.2
1.5
3
4
----
3
4.8
7.8
0.5
1
2
0.5
1
2
1.5
3
5
----
S00
S00
S00
B
B
B
3RW30 13-2BB@4
3RW30 14-2BB@4
3RW30 16-2BB@4
1 1 unit 131
1 1 unit 131
1 1 unit 131
0.580
0.580
0.580
12.5
17.6
3
4
5.5
7.5
---
11
17
3
3
3
3
7.5
10
---
S00
S00
B
B
3RW30 17-2BB@4
3RW30 18-2BB@4
1 1 unit 131
1 1 unit 131
0.580
0.580
----
23
29
34
5
7.5
10
5
7.5
10
15
20
25
----
S0
S0
S0
}
}
}
3RW30 26-1BB@4
3RW30 27-1BB@4
3RW30 28-1BB@4
1 1 unit 131
1 1 unit 131
1 1 unit 131
0.690
0.690
0.690
23
29
34
5
7.5
10
5
7.5
10
15
20
25
----
S0
S0
S0
B
B
B
3RW30 26-2BB@4
3RW30 27-2BB@4
3RW30 28-2BB@4
1 1 unit 131
1 1 unit 131
1 1 unit 131
0.690
0.690
0.690
15
20
20
30
40
40
----
S2
S2
S2
B
B
B
3RW30 36-@BB@4
3RW30 37-@BB@4
3RW30 38-@BB@4
1 1 unit 131
1 1 unit 131
1 1 unit 131
1.200
1.200
1.200
25
30
50
75
---
S3
S3
B
B
3RW30 46-@BB@4
3RW30 47-@BB@4
1 1 unit 131
1 1 unit 131
1.710
1.710
1 1 unit 131
1 1 unit 131
0.207
0.188
6
• With screw terminals
25
32
38
5.5
7.5
11
11
15
18.5
• With spring-loaded terminals
25
32
38
5.5
7.5
11
11
15
18.5
----
• With screw terminals or spring-loaded terminals
45
63
72
11
18.5
22
22
30
37
----
42
58
62
10
15
20
• With screw terminals or spring-loaded terminals
80
106
22
30
45
55
---
73
98
20
30
Order No. supplement for connection types
• With screw terminals
• With spring-loaded terminals3)
1
2
Order No. supplement for rated control supply voltage Us
• 24 V AC/DC
• 110 ... 230 V
0
1
Soft starters for easy starting conditions and high switching frequency
Rated operational voltage Ue 200 ... 400 V
Rated control supply voltage Us 24 ... 230 V AC/DC
3
0.55
1.1
--
2.6
0.5
0.5
--
• With screw terminals
• With spring-loaded terminals
1)
2)
3)
Stand-alone installation.
Soft starter with screw terminals: delivery time } (preferred type).
Main circuit connection: screw terminals.
--
22.5 mm
}
A
3RW30 03-1CB54
3RW30 03-2CB54
Note:
Selection of the soft starter depends on the rated motor current.
The SIRIUS 3RW30 solid-state soft starters are designed for
easy starting conditions. JLoad < 10 x JMotor . In the event of
deviating conditions or increased switching frequency, it may be
necessary to choose a larger device.
Siemens recommends the use of the selection and simulation
program Win-Soft Starter. For information about rated currents
for ambient temperatures > 40 °C, see technical specifications
(see Technical Information LV 1 T).
* You can order this quantity or a multiple thereof.
6/4
Siemens LV 1 N · 04/2008
© Siemens AG 2008
3RW Soft Starters
3RW30
for standard applications
Accessories
For soft starters
Motor starter protector
Type
Size
Size
DT
Order No.
Price
per PU
PU
PS*
(UNIT,
SET,
M)
PG
Weight
per PU
approx.
kg
Auxiliary terminals
Auxiliary terminals, 3-pole
3RW30 4.
B
3RT19 46-4F
1
1 unit
101
0.035
}
}
3RT19 36-4EA2
3RT19 46-4EA2
1
1
1 unit
1 unit
101
101
0.020
0.025
}
3RT19 46-4EA1
1
1 unit
101
0.040
S0
}
3RA19 21-1A
1
10 units 101
0.028
S3
Covers for soft starters
Terminal covers for box terminals
Additional touch protection to be fitted at the box
terminals (2 units required per device)
3RW30 3.
3RW30 4.
S2
S3
Terminal covers for cable lugs and busbar connections
For complying with the phase clearances and as touch
protection if box terminal is removed
(2 units per contactor required)
3RW30 4.
S3
Link modules to motor starter protectors
3RW30 13,
3RW30 14,
3RW30 16,
3RW30 17,
3RW30 18
S00
3RW30 26
S0
3RW30 27,
3RW30 28
3RW30 36
S2
3RW30 37,
3RW30 38
3RW30 46,
3RW30 47
S3
S0
}
3RA19 21-1A
1
10 units 101
0.028
S2
D
3RA19 31-1D
1
5 units 101
0.041
S2
}
3RA19 31-1A
1
5 units 101
0.033
S3
D
3RA19 41-1D
1
5 units 101
0.042
S3
}
3RA19 41-1A
1
5 units 101
0.072
6
Operating instructions1)
For soft starters
3RW30 1.
3RW30 2.
3RW30 3.
3RW30 4.
1)
3ZX10 12-0RW30-2DA1
S00
S0
S2
S3
The operating instructions are included in the scope of supply.
Version
Functionality
Functions
Use
DT
Order No.
Price
per PU
PU
PS*
(UNIT,
SET,
M)
PG
Weight
per PU
approx.
kg
Covers and push-in lugs (only for 3RW30 03)
3RP1 902
Sealable covers For securing against For devices
unauthorized adjust- with 1 or
ment of setting knobs 2 CO
contacts
}
3RP1 902
1
5 units
101
0.004
For devices
with 1 or
2 CO
contacts
}
3RP1 903
1 10 units
101
0.002
Push-in lugs
For screw fixing
3RP1 903
* You can order this quantity or a multiple thereof.
Siemens LV 1 N · 04/2008
6/5
© Siemens AG 2008
3RW Soft Starters
3RW40
for standard applications
■ Overview
■ Application
SIRIUS 3RW40 soft starters have all the same advantages as the
3RW30 soft starters.
The SIRIUS 3RW40 soft starters are characterized above all by
their small space requirements. Integrated bypass contacts
mean that no power loss has to be taken into the bargain at the
power semiconductors (thyristors) after the motor has started
up. This cuts down on heat losses, enabling a more compact
design and making external bypass circuits superfluous.
At the same time this soft starter comes with additional integrated functions such as adjustable current limiting, motor
overload and intrinsic device protection, and optional thermistor
motor protection. The higher the motor rating, the more important these functions because they make it unnecessary to
purchase and install protection equipment such as overload relays.
Internal intrinsic device protection prevents the thermal
overloading of the thyristors and the power section defects this
can cause. As an option the thyristors can also be protected by
semiconductor fuses from short-circuiting.
Thanks to integrated status monitoring and fault monitoring, this
compact soft starter offers many different diagnostics options.
Up to four LEDs and relay outputs permit differentiated monitoring and diagnostics of the operating mechanism by indicating
the operating state as well as for example mains or phase failure,
missing load, non-permissible tripping time/class setting, thermal overloading or device faults.
Soft starters rated up to 250 kW (at 400 V) for standard
applications in three-phase networks are available. Extremely
small sizes, low power losses and simple start-up are just three
of the many advantages of the SIRIUS 3RW40 soft starters.
6
"Increased safety" type of protection EEx e according to
ATEX directive 94/9/EC
The 3RW40 soft starter sizes S6, S10 and S12 are suitable for the
starting of explosion-proof motors with "increased safety" type of
protection EEx e.
See "Appendix" –> "Standards and approvals" –> "Type overview of approved devices for potentially explosive areas (ATEX
explosion protection)".
6/6
Siemens LV 1 N · 04/2008
The SIRIUS 3RW40 solid-state soft starters are suitable for soft
starting and stopping of three-phase asynchronous motors.
Due to two-phase control, the current is kept at minimum values
in all three phases throughout the entire starting time and disturbing direct current components are eliminated in addition. This
not only enables the two-phase starting of motors up to 250 kW
(at 400 V) but also avoids the current and torque peaks which
occur e.g. with wye-delta starters.
Application areas
• Pumps
• Heat pumps
• Hydraulic pumps
• Presses
• Conveyors
• Roller conveyors
• Screw conveyors
• Escalators
• Piston compressors
• Screw compressors
• Small fans
• Centrifugal blowers
• Bow thrusters
• Stirrers
• Extruders
• Lathes
• Milling machines
© Siemens AG 2008
3RW Soft Starters
3RW40
for standard applications
■ Selection and ordering data
3RW40 28-1BB14
3RW40 38-1BB14
Ambient temperature 40 °C
Ambient temperature 50 °C
Rated
Rated power of induction
operatio- motors for rated operational cur- nal voltage Ue
rent Ie1)
Rated
Rated power of induction
operatio- motors for rated operational
nal cur- voltage Ue
rent Ie1)
A
230 V
400 V
500 V
kW
kW
kW
Size
3RW40 47-1BB14
DT Order No.
Price
per PU
PU
PS*
(UNIT,
SET,
M)
PG
Weight
per PU
approx.
200 V 230 V 460 V 575 V
A
hp
hp
hp
hp
kg
Rated operational voltage Ue 200 ... 480 V2)
• With screw terminals
12.5
25
32
38
3
5.5
7.5
11
5.5
11
15
18.5
-----
11
23
29
34
3
5
7.5
10
3
5
7.5
10
7.5
15
20
25
-----
S0
S0
S0
S0
}
}
}
}
3RW40 24-1BB@4
3RW40 26-1BB@4
3RW40 27-1BB@4
3RW40 28-1BB@4
1
1
1
1
1 unit
1 unit
1 unit
1 unit
131
131
131
131
0.770
0.770
0.770
0.770
11
23
29
34
3
5
7.5
10
3
5
7.5
10
7.5
15
20
25
-----
S0
S0
S0
S0
B
B
B
B
3RW40 24-2BB@4
3RW40 26-2BB@4
3RW40 27-2BB@4
3RW40 28-2BB@4
1
1
1
1
1 unit
1 unit
1 unit
1 unit
131
131
131
131
0.770
0.770
0.770
0.770
15
20
20
30
40
40
----
S2
S2
S2
B
B
B
3RW40 36-@BB@4
3RW40 37-@BB@4
3RW40 38-@BB@4
1
1
1
1 unit 131
1 unit 131
1 unit 131
1.350
1.350
1.350
25
30
50
75
---
S3
S3
B
B
3RW40 46-@BB@4
3RW40 47-@BB@4
1
1
1 unit 131
1 unit 131
1.900
1.900
• With spring-loaded terminals
12.5
25
32
38
3
5.5
7.5
11
5.5
11
15
18.5
-----
• With screw terminals or spring-loaded terminals
45
63
72
11
18.5
22
22
30
37
----
42
58
62
10
15
20
• With screw terminals or spring-loaded terminals
80
106
22
30
45
55
---
73
98
20
30
Rated operational voltage Ue 400 ... 600 V
12.5
25
32
38
-----
5.5
11
15
18.5
6
• With screw terminals
7.5
15
18.5
22
11
23
29
34
-----
-----
7.5
15
20
25
10
20
25
30
S0
S0
S0
S0
B
B
B
B
3RW40 24-1BB@5
3RW40 26-1BB@5
3RW40 27-1BB@5
3RW40 28-1BB@5
1
1
1
1
1 unit
1 unit
1 unit
1 unit
131
131
131
131
0.770
0.770
0.770
0.770
11
23
29
34
-----
-----
7.5
15
20
25
10
20
25
30
S0
S0
S0
S0
B
B
B
B
3RW40 24-2BB@5
3RW40 26-2BB@5
3RW40 27-2BB@5
3RW40 28-2BB@5
1
1
1
1
1 unit
1 unit
1 unit
1 unit
131
131
131
131
0.770
0.770
0.770
0.770
----
30
40
40
40
50
60
S2
S2
S2
B
B
B
3RW40 36-@BB@5
3RW40 37-@BB@5
3RW40 38-@BB@5
1
1
1
1 unit 131
1 unit 131
1 unit 131
1.350
1.350
1.350
---
50
75
60
75
S3
S3
B
B
3RW40 46-@BB@5
3RW40 47-@BB@5
1
1
• With spring-loaded terminals
12.5
25
32
38
-----
5.5
11
15
18.5
7.5
15
18.5
22
• With screw terminals or spring-loaded terminals
45
63
72
----
22
30
37
30
37
45
42
58
62
----
• With screw terminals or spring-loaded terminals
80
106
---
45
55
55
75
73
98
---
1 ST
1 ST
131
131
1,900
1,900
Order No. supplement for connection types
• With screw terminals
• With spring-loaded terminals3)
1
2
Order No. supplement for rated control supply voltage Us
• 24 V AC/DC
• 110 ... 230 V AC/DC
1)
Stand-alone installation without auxiliary fan.
2)
Soft starter with screw terminals: delivery time } (preferred type).
3)
Main circuit connection: screw terminals.
0
1
Note:
Selection of the soft starter depends on the rated motor current.
The SIRIUS 3RW40 solid-state soft starters are designed for
easy starting conditions. Jload < 10 x Jmotor. In the event of
deviating conditions or increased switching frequency, it may be
necessary to choose a larger device. Siemens recommends the
use of the selection and simulation program Win-Soft Starter. For
information about rated currents for ambient temperatures >
40 °C, see technical specifications (see Technical Information
LV 1 T).
* You can order this quantity or a multiple thereof.
Siemens LV 1 N · 04/2008
6/7
© Siemens AG 2008
3RW Soft Starters
3RW40
for standard applications
3RW40 28-1TB04
3RW40 38-1TB04
Ambient temperature 40 °C
Ambient temperature 50 °C
Rated
Rated power of induction
operatio- motors for rated operational cur- nal voltage Ue
rent Ie1)
Rated
Rated power of induction
operatio- motors for rated operational
nal cur- voltage Ue
rent Ie1)
A
230 V
400 V
500 V
kW
kW
kW
Size
3RW40 47-1TB04
DT Order No.
Price
per PU
PU
PS*
(UNIT,
SET,
M)
PG
Weight
per PU
approx.
200 V 230 V 460 V 575 V
A
hp
hp
hp
hp
kg
Rated operational voltage Ue 200 ... 480 V2)
With thermistor motor protection
Rated control supply voltage Us 24 V AC/DC
• With screw terminals
12.5
25
32
38
3
5.5
7.5
11
5.5
11
15
18.5
-----
11
23
29
34
3
5
7.5
10
3
5
7.5
10
7.5
15
20
25
-----
S0
S0
S0
S0
}
}
}
}
3RW40 24-1TB04
3RW40 26-1TB04
3RW40 27-1TB04
3RW40 28-1TB04
1
1
1
1
1 unit
1 unit
1 unit
1 unit
131
131
131
131
0.770
0.770
0.770
0.770
11
23
29
34
3
5
7.5
10
3
5
7.5
10
7.5
15
20
25
-----
S0
S0
S0
S0
B
B
B
B
3RW40 24-2TB04
3RW40 26-2TB04
3RW40 27-2TB04
3RW40 28-2TB04
1
1
1
1
1 unit
1 unit
1 unit
1 unit
131
131
131
131
0.770
0.770
0.770
0.770
15
20
20
30
40
40
----
S2
S2
S2
B
B
B
3RW40 36-@TB04
3RW40 37-@TB04
3RW40 38-@TB04
1
1
1
1 unit 131
1 unit 131
1 unit 131
1.350
1.350
1.350
25
30
50
75
---
S3
S3
B
B
3RW40 46-@TB04
3RW40 47-@TB04
1
1
1 unit 131
1 unit 131
1.900
1.900
• With spring-loaded terminals
12.5
25
32
38
3
5.5
7.5
11
5.5
11
15
18.5
-----
• With screw terminals or spring-loaded terminals
45
63
72
11
18.5
22
22
30
37
----
42
58
62
10
15
20
• With screw terminals or spring-loaded terminals
6
80
106
22
30
45
55
---
73
98
20
30
Rated operational voltage Ue 400 ... 600 V
With thermistor motor protection
Rated control supply voltage Us 24 V AC/DC
• With screw terminals
12.5
25
32
38
-----
5.5
11
15
18.5
7.5
15
18.5
22
11
23
29
34
-----
-----
7.5
15
20
25
10
20
25
30
S0
S0
S0
S0
B
B
B
B
3RW40 24-1TB05
3RW40 26-1TB05
3RW40 27-1TB05
3RW40 28-1TB05
1
1
1
1
1 unit
1 unit
1 unit
1 unit
131
131
131
131
0.770
0.770
0.770
0.770
11
23
29
34
-----
-----
7.5
15
20
25
10
20
25
30
S0
S0
S0
S0
B
B
B
B
3RW40 24-2TB05
3RW40 26-2TB05
3RW40 27-2TB05
3RW40 28-2TB05
1
1
1
1
1 unit
1 unit
1 unit
1 unit
131
131
131
131
0.770
0.770
0.770
0.770
----
30
40
40
40
50
60
S2
S2
S2
B
B
B
3RW40 36-@TB05
3RW40 37-@TB05
3RW40 38-@TB05
1
1
1
1 unit 131
1 unit 131
1 unit 131
1.350
1.350
1.350
---
50
75
60
75
S3
S3
B
B
3RW40 46-@TB05
3RW40 47-@TB05
1
1
1 unit 131
1 unit 131
1.900
1.900
• With spring-loaded terminals
12.5
25
32
38
-----
5.5
11
15
18.5
7.5
15
18.5
22
• With screw terminals or spring-loaded terminals
45
63
72
----
22
30
37
30
37
45
42
58
62
----
• With screw terminals or spring-loaded terminals
80
106
---
45
55
55
75
73
98
---
Order No. supplement for connection types
• With screw terminals
• With spring-loaded terminals3)
1)
Stand-alone installation without auxiliary fan.
2)
Soft starter with screw terminals: delivery time } (preferred type).
3)
Main circuit connection: screw terminals.
1
2
Note:
Selection of the soft starter depends on the rated motor current.
The SIRIUS 3RW40 solid-state soft starters are designed for
easy starting conditions. Jload < 10 x Jmotor. In the event of
deviating conditions or increased switching frequency, it may be
necessary to choose a larger device. Siemens recommends the
use of the selection and simulation program Win-Soft Starter. For
information about rated currents for ambient temperatures >
40 °C, see technical specifications (see Technical Information
LV 1 T).
* You can order this quantity or a multiple thereof.
6/8
Siemens LV 1 N · 04/2008
© Siemens AG 2008
3RW Soft Starters
3RW40
for standard applications
3RW40 56-6BB44
3RW40 76-6BB44
Ambient temperature 40 °C
Ambient temperature 50 °C
Rated
Rated power of induction
operatio- motors for rated operational cur- nal voltage Ue
rent Ie1)
Rated
Rated power of induction
operatio- motors for rated operational
nal cur- voltage Ue
rent Ie1)
A
230 V
400 V
500 V
kW
kW
kW
Size
DT Order No.
Price
per PU
PU
PS*
(UNIT,
SET,
M)
PG
Weight
per PU
approx.
200 V 230 V 460 V 575 V
A
hp
hp
hp
hp
kg
40
50
75
100
---
S6
B
B
3RW40 55-@BB@4
3RW40 56-@BB@4
1
1
1 unit 131
1 unit 131
4.900
6.900
S12
B
B
3RW40 73-@BB@4
3RW40 74-@BB@4
1
1
131
131
8.900
8.900
B
B
3RW40 75-@BB@4
3RW40 76-@BB@4
1
1
1 unit
1 unit
1 unit
1 unit
131
131
8.900
8.900
Rated operational voltage Ue 200 ... 460 V2)
• With screw terminals or spring-loaded terminals
134
162
37
45
75
90
---
117
145
30
40
• With screw terminals or spring-loaded terminals
230
280
75
90
132
160
---
205
248
60
75
75
100
150
200
---
356
432
110
132
200
250
---
315
385
100
125
125
150
250
300
---
---
75
100
100
150
S6
B
B
3RW40 55-@BB@5
3RW40 56-@BB@5
1
1
1 unit 131
1 unit 131
4.900
6.900
---
---
150
200
200
250
S12
B
B
3RW40 73-@BB@5
3RW40 74-@BB@5
1
1
131
131
8.900
8.900
---
---
250
300
300
400
B
B
3RW40 75-@BB@5
3RW40 76-@BB@5
1
1
1 unit
1 unit
1 unit
1 unit
131
131
8.900
8.900
Rated operational voltage Ue 400 ... 600
V3)
• With screw terminals or spring-loaded terminals
134
162
---
75
90
90
110
117
145
---
• With screw terminals or spring-loaded terminals
---
132
160
160
200
205
248
356
432
---
200
250
250
315
315
385
Order No. supplement for connection types
4)
6
230
280
• With screw terminals
• With spring-loaded terminals
Order No. supplement for the rated control supply voltage Us
6
2
5)
• 115 V AC
• 230 V AC
1)
Stand-alone installation.
2)
Soft starter with screw terminals: delivery time } (preferred type).
3)
Soft starter with screw terminals: delivery time A.
4)
Main circuit connection: busbar connection.
5)
Control by way of the internal 24 V DC supply and direct control by means
of PLC possible.
3
4
Note:
Selection of the soft starter depends on the rated motor current.
The SIRIUS 3RW40 solid-state soft starters are designed for
easy starting conditions. Jload < 10 x Jmotor. In the event of
deviating conditions or increased switching frequency, it may be
necessary to choose a larger device. Siemens recommends the
use of the selection and simulation program Win-Soft Starter. For
information about rated currents for ambient temperatures >
40 °C, see technical specifications (see Technical Information
LV 1 T).
* You can order this quantity or a multiple thereof.
Siemens LV 1 N · 04/2008
6/9
© Siemens AG 2008
3RW Soft Starters
3RW40
for standard applications
Accessories
For soft starters
Type
Version
DT Order No.
Size
Price
per PU
PU
PS*
(UNIT,
SET,
M)
PG
Weight
per PU
approx.
kg
Box terminal blocks for soft starters
For round and ribbon cables
3RW40 5.
S6
• Up to 70 mm2
• Up to 120 mm2
}
}
3RT19 55-4G
3RT19 56-4G
1
1
1 unit 101
1 unit 101
0.230
0.260
3RW40 7.
S12
• Up to 240 mm2
}
3RT19 66-4G
1
1 unit 101
0.676
B
3RT19 46-4F
1
1 unit 101
0.035
0.020
0.025
Auxiliary terminals
Auxiliary terminals, 3-pole
3RW40 4.
S3
Covers for soft starters
Terminal covers for box terminals
Additional touch protection to be fitted at the box terminals
(2 units required per device)
3RW40 3.
3RW40 4.
S2
S3
}
}
3RT19 36-4EA2
3RT19 46-4EA2
1
1
3RW40 5.
3RW40 7.
S6
S12
}
}
3RT19 56-4EA2
3RT19 66-4EA2
1
1
1 unit 101
1 unit 101
1 unit 101
1 unit 101
For complying with the phase clearan- }
ces and as touch protection if box ter- }
minal is removed
}
(2 units per device required)
3RT19 46-4EA1
1
1 unit 101
0.040
3RT19 56-4EA1
3RT19 66-4EA1
1
1
1 unit 101
1 unit 101
0.070
0.130
0.030
0.040
Terminal covers for cable lugs and busbar connections
3RW40 4.
S3
3RW40 5.
3RW40 7.
S6
S12
Sealing covers
S0,
S2,
S3
}
3RW49 00-0PB10
1
1 unit 131
0.005
3RW40 5. and S6,
3RW40 7.
S12
}
3RW49 00-0PB00
1
1 unit 131
0.010
}
}
}
3RU19 00-2AB71
3RU19 00-2AF71
3RU19 00-2AM71
1
1
1
1 unit 101
1 unit 101
1 unit 101
0.066
0.067
0.066
3RU19 00-1A
1
1 unit 101
0.038
3SB30 00-0EA11
1
1 unit 102
0.020
3SX13 35
1
1 unit 102
0.004
3RU19 00-1B
3RU19 00-1C
1
1
1 unit 101
1 unit 101
0.063
0.073
6
3RW40 2. to
3RW40 4.
Modules for RESET1)
Modules for remote RESET, electrical
Operating range 0.85 ... 1.1 x Us
Power consumption AC 80 VA, DC 70 W
On period 0.2 s ... 4 s
Switching frequency 60/h
3RW40 5. and S6,
3RW40 7.
S12
• 24 ... 30 V AC/DC
• 110 ... 127 V AC/DC
• 220 ... 250 V AC/DC
Mechanical RESET comprising
3RW40 5. and S6,
3RW40 7.
S12
• Resetting plungers, holders and for- }
mers
• Suitable pushbutton IP65, Ø 22 mm, B
12 mm stroke
• Extension plunger
A
Cable releases with holder for RESET
For Ø 6.5 mm holes in the control panel;
max. control panel thickness 8 mm
3RW40 5. and S6,
3RW40 7.
S12
1)
• Length 400 mm
• Length 600 mm
}
}
Remote RESET already integrated in the
3RW40 2. to 3RW40 4.. soft starters
* You can order this quantity or a multiple thereof.
6/10
Siemens LV 1 N · 04/2008
© Siemens AG 2008
3RW Soft Starters
3RW40
for standard applications
For soft starters
Motor starter protectors
Type
Size
Size
DT Order No.
Price
per PU
PU
PS*
(UNIT,
SET,
M)
PG
Weight
per PU
approx.
kg
Link modules to motor starter protectors
3RW40 24,
3RW40 26
S0
3RW40 27,
3RW40 28
3RW40 36
S2
3RW40 37,
3RW40 38
3RW40 46,
3RW40 47
S3
S0
}
3RA19 21-1A
1
10 units 101
0.028
S2
D
3RA19 31-1D
1
5 units 101
0.041
S2
}
3RA19 31-1A
1
5 units 101
0.033
S3
D
3RA19 41-1D
1
5 units 101
0.042
S3
}
3RA19 41-1A
1
5 units 101
0.072
Fans (to increase switching frequency and for device mounting in
positions different from the normal position)
3RW40 2.
S0
}
3RW49 28-8VB00
1
1 unit 131
0.010
3RW40 3.,
3RW40 4.
S2,
S3
}
3RW49 47-8VB00
1
1 unit 131
0.020
Operating instructions1)
For soft starters
1)
3RW40 2.
3RW40 3.
3RW40 4.
S0
S2
S3
3ZX10 12-0RW40-1AA1
3RW40 5.
3RW40 7.
S6
S12
3ZX10 12-0RW40-2DA1
The operating instructions are included in the scope of supply.
For soft starters
Type
Version
Size
DT Order No.
Rated control supply
voltage Us
Price
per PU
PU
PS*
(UNIT,
SET,
M)
PG
Weight
per PU
approx.
kg
Fans
Fans
3RW40 5.-.BB3.
3RW40 5.-.BB4.
S6
S6
115 V AC
230 V AC
}
}
3RW49 36-8VX30
3RW49 36-8VX40
1
1
3RW40 7.-.BB3.
3RW40 7.-.BB4.
S12
S12
115 V AC
230 V AC
}
}
3RW49 47-8VX30
3RW49 47-8VX40
1
1
1 unit 131
1 unit 131
1 unit 131
1 unit 131
0.300
0.300
0.500
0.500
* You can order this quantity or a multiple thereof.
Siemens LV 1 N · 04/2008
6/11
6
Spare parts
© Siemens AG 2008
3RW Soft Starters
3RW30
for standard applications
■ Function
The space required by the compact SIRIUS 3RW30 soft starter
is often only about one third of that required by a contactor assembly for wye-delta starting of comparable rating. This not only
saves space in the control cabinet and on the standard mounting rail but also does away completely with the wiring work
needed for wye-delta starters. This is notable in particular for
higher motor ratings which are only rarely available as fully wired
solutions.
At the same time the number of cables from the starter to the
motor is reduced from six to three. Compact dimensions, short
start-up times, easy wiring and fast commissioning make
themselves felt as clear-cut cost advantages.
The bypass contacts of these soft starters are protected during
operation by an integrated solid-state arc quenching system.
This prevents damage to the bypass contacts in the event of a
fault, e.g. brief disconnection of the control voltage, mechanical
shocks or life-related component defects on the coil operating
mechanism or main contact spring.
The new series of devices comes with the "polarity balancing"
control method, which is designed to prevent direct current components in two-phase controlled soft starters. On two-phase
controlled soft starters the current resulting from superimposition
of the two controlled phases flows in the uncontrolled phase.
This results for physical reasons in an asymmetric distribution of
the three phase currents during the motor ramp-up. This phenomenon cannot be influenced, but in most applications it is
non-critical.
method used for these soft starters eliminates these direct current components during the ramp-up phase and prevents the
braking torque which they can cause.
It creates a motor ramp-up that is uniform in speed, torque and
current rise, thus permitting a particularly gentle, two-phase
starting of the motors. At the same time the acoustic quality of
the starting operation comes close to the quality of a threephase controlled soft starter. This is made possible by the on-going dynamic harmonizing and balancing of current half-waves of
different polarity during the motor ramp-up. Hence the name
"polarity balancing".
• Soft starting with voltage ramp; the starting voltage setting
range Us is 40 % to 100 % and the ramp time tR can be set
from 0 s to 20 s.
• Integrated bypass contact system to minimize power loss
• Setting with two potentiometers
• Simple mounting and start-up
• Mains voltages at 50/60 Hz, 200 to 480 V
• Two control voltage versions 24 V AC/DC and
110 to 230 V AC/DC
• Wide temperature range from -25 °C to +60 °C
• The built-in auxiliary contact ensures user-friendly control and
possible further processing within the system
(for status graphs see Page 6/37)
Controlling the power semiconductors results not only in this
asymmetry, however, but also in the previously mentioned direct
current components which can cause severe noise generation
on the motor at starting voltages of less than 50 %. The control
Type
3RW30 1. , 3RW30 2.
3RW30 3., 3RW30 4.
V
%
24
±20
110 ... 230
-15/+10
24
±20
110 ... 230
-15/+10
Rated control supply current
• STANDBY
• During pick-up
• ON
mA
mA
mA
< 50
< 100
< 100
6
15
15
20
< 4000
20
< 50
< 500
< 50
Rated frequency
• Tolerance
Hz
%
50/60
±10
Control input
IN
Power consumption with version
• 24 V DC
• 110/230 V AC
mA
mA
6
■ Technical specifications
Control electronics
Terminal
A1/A2
Rated values
Rated control supply voltage
• Tolerance
Relay outputs
Output 1
Rated operational current
ON/OFF
ON
13/14
Approx. 12
AC: 3/6; DC: 1.5/3
Operating indication (NO)
A
A
3 AC-15/AC-14 at 230 V,
1 DC-13 at 24 V
Protection by means of varistor through contact
4 A gL/gG operational class;
6 A quick (fuse is not included in scope of supply)
Protection against overvoltages
Short-circuit protection
LED
Off
Start
Bypass
Green
Green
Green
STATE/BYPASSED/
FAILURE
Off
Green flashing
Green
Error signals
• 24 V DC:
U < 0.75 x Us or U > 1.25 x Us
• 110 ... 230 V AC: U < 0.75 x Us or U > 1.15 x Us
Off
Off
Red
Red
Off
Off
Red
Red
Yellow
Red
--
--
Green
Red
Red
Red
Green
Red
Red
Red
Operating indications
Electrical overloading of bypass
(reset by removing IN command)
Missing mains voltage, phase failure, missing load
Device fault
DEVICE
DEVICE
Green
Green
Green
STATE/BYPASSED/
FAILURE
Off
Green flashing
Green
Siemens LV 1 N · 04/2008
6/27
© Siemens AG 2008
3RW Soft Starters
3RW30
for standard applications
Type
3RW30 1. ... 3RW30 4.
Factory default
Control times and parameters
Control times
Closing delay (with connected control voltage)
Closing delay (automatic/mains contactor mode)
ms
ms
< 50
< 300
Mains failure bridging time
Control supply voltage
ms
50
Mains failure response time1)
Load current circuit
ms
500
Starting parameters
• Starting time
• Starting voltage
s
%
0 ... 20
40 ... 100
No
Start-up detection
Operating mode output 13/14
Rising edge at
Falling edge at
1)
7.5
40
Start command
Off command
ON
Mains failure detection only in standby state, not during operation.
Type
3RW30 1.-.BB.4 ... 3RW30 4.-.BB.4
Power electronics
Rated operational voltage
Tolerance
V AC
%
200 ... 480
-15/+10
Rated frequency
Tolerance
Hz
%
50/60
±10
Continuous duty at 40 °C (% of Ie)
%
115
Minimum load (% of Ie)
%
10 (at least 2 A)
Maximum cable length between soft starter and motor
m
300
Permissible installation height
m
5000
(derating from 1000, see characteristic curves); higher on request
6
Permissible ambient temperature
Operation
Storage
10°
°C
°C
10°
10°
10°
NSB0_01897
Permissible mounting position
(auxiliary fan not available)
-25 ... +60; (derating from +40)
-40 ... +80
Degree of protection
IP20 for 3RW30 1. and 3RW30 2.;
IP00 for 3RW30 3. and 3RW30 4.
Type
3RW30 13
3RW30 14
3RW30 16
3RW30 17
3RW30 18
A
A
A
3.6
3.3
3
6.5
6
5.5
9
8
7
12.5
12
11
17.6
17
14
W
0.25
0.5
1
2
4
W
6
13
20
20
29
- Rated motor current IM2), starting time 3 s
- Starts per hour3)
A
1/h
3.6
200
6.5
87
9
50
12.5
85
17.6
62
- Rated motor current IM2), starting time 4 s
- Starts per hour3)
A
1/h
3.6
150
6.5
64
9
35
12.5
62
17.6
45
Power electronics
Load rating with rated operational current Ie
• According to IEC and UL/CSA1), for individual mounting, AC-53a
- At 40 °C
- At 50 °C
- At 60 °C
Power loss
• In operation after completed starting with uninterrupted rated
operational current (40 °C) approx.
• During starting with 300 % IM (40 °C)
Permissible rated motor current and starts per hour
For normal starting (Class 10)
1)
Measurement at 60 °C according to UL/CSA not required.
2)
With 300 % IM.
3)
For intermittent duty S4 with ON period = 30 %, Tu = 40 °C, stand-alone
installation vertical. The quoted switching frequencies do not apply for
automatic mode.
6/28
Siemens LV 1 N · 04/2008
© Siemens AG 2008
3RW Soft Starters
3RW30
for standard applications
Type
3RW30 26
3RW30 27
3RW30 28
A
A
A
25.3
23
21
32.2
29
26
38
34
31
W
8
13
19
W
47
55
64
- Rated motor current IM2), starting time 3 s
- Starts per hour3)
A
1/h
25
23
32
23
38
19
- Rated motor current IM2), starting time 4 s
- Starts per hour3)
A
1/h
25
15
32
16
38
12
Power electronics
Load rating with rated operational current Ie
• According to IEC and UL/CSA1), for individual mounting, AC-53a
- At 40 °C
- At 50 °C
- At 60 °C
Power loss
• In operation after completed starting with uninterrupted rated
operational current (40 °C) approx.
• During starting with 300 % IM (40 °C)
Permissible rated motor current and starts per hour
For normal starting (Class 10)
1)
Measurement at 60 °C according to UL/CSA not required.
2)
With 300 % IM.
3)
Type
For intermittent duty S4 with ON period = 30 %, Tu = 40 °C, stand-alone
installation vertical. The quoted switching frequencies do not apply for
automatic mode.
3RW30 36
3RW30 37
3RW30 38
3RW30 46
3RW30 47
A
A
A
45
42
39
65
58
53
72
62.1
60
80
73
66
106
98
90
W
6
12
15
12
21
W
79
111
125
144
192
- Rated motor current IM2), starting time 3 s
- Starts per hour3)
A
1/h
45
38
63
23
72
22
80
22
106
15
- Rated motor current IM2), starting time 4 s
- Starts per hour3)
A
1/h
45
26
63
15
72
15
80
15
106
10
Power electronics
Load rating with rated operational current Ie
• According to IEC and UL/CSA1), for individual mounting, AC-53a
- At 40 °C
- At 50 °C
- At 60 °C
Power loss
• In operation after completed starting with uninterrupted rated
operational current (40 °C) approx.
• During starting with 300 % IM (40 °C)
1)
Measurement at 60 °C according to UL/CSA not required.
2)
With 300 % IM.
3)
For intermittent duty S4 with ON period = 70 %, Tu = 40 °C, stand-alone
installation vertical. The quoted switching frequencies do not apply for
automatic mode.
Siemens LV 1 N · 04/2008
6
Permissible rated motor current and starts per hour
For normal starting (Class 10)
6/29
© Siemens AG 2008
3RW Soft Starters
3RW30
for standard applications
Soft starters
Type
3RW30 1.
3RW30 2.
3RW30 3.
3RW30 4.
Conductor cross-sections
Main conductors
Front clamping point
connected
• Solid
mm2
2 x (1 ... 2.5);
2 x (2.5 ... 6)
according to
IEC 60947
2 x (1 ... 2.5);
2 x (2.5 ... 6)
according to
IEC 60947;
max. 1 x 10
2 x (1.5 ... 16)
2 x (2.5 ... 16)
• Finely stranded with end sleeve
mm2
2 x (1.5 ... 2.5);
2 x (2.5 ... 6)
2 x (1 ... 2.5);
2 x (2.5 ... 6)
1 x (0.75 ... 25)
1 x (2.5 ... 35)
• Stranded
mm2
--
--
1 x (0.75 ... 35)
1 x (4 ... 70)
• AWG cables
- Solid
- Solid or stranded
- Stranded
AWG
AWG
AWG
2 x (16 ... 12)
2 x (14 ... 10)
1x8
2 x (16 ... 12)
2 x (14 ... 10)
1x8
1 x (18 ... 2)
--
1 x (10 ... 2/0)
--
NSB00479
Screw terminals
NSB00480
Rear clamping point
connected
NSB00481
Both clamping points
connected
• Solid
mm2
--
--
2 x (1.5 ... 16)
2 x (2.5 ... 16)
• Finely stranded with end sleeve
mm2
--
--
1 x (1.5 ... 25)
1 x (2.5 ... 50)
• Stranded
mm2
--
--
1 x (1.5 ... 35)
1 x (10 ... 70)
• AWG cables
- Solid or stranded
AWG
--
--
1 x (16 ... 2)
1 x (10 ... 2/0)
• Solid
mm
2
--
--
2 x (1.5 ... 16)
2 x (2.5 ... 16)
• Stranded
mm2
--
--
2 x (1.5 ... 25)
2 x (10 ... 50)
• Finely stranded with end sleeve
mm2
--
--
2 x (1.5 ... 16)
2 x (2.5 ... 35)
• AWG cables
- Solid or stranded
AWG
--
--
2 x (16 ... 2)
2 x (10 ... 1/0)
Nm
lb.in
2 ... 2.5
18 ... 22
2 ... 2.5
18 ... 22
4.5
40
6.5
58
Tools
PZ 2
PZ 2
PZ 2
Allen screw 4 mm
Degree of protection
IP20
IP20
IP20
IP20
(terminal compart- (terminal compartment IP00)
ment IP00)
• Tightening torque
6
Spring-loaded terminals Main conductors
Busbar connections
Soft starters
• Solid
mm2
1 ... 4
1 ... 10
--
--
• Finely stranded with end sleeve
mm2
1 ... 2.5
1 ... 6, end
sleeves without
plastic collar
--
--
• AWG cables
- Solid or stranded (finely stranded)
- Stranded
AWG
AWG
16 ... 14
16 ... 12
16 ... 10
1x8
---
---
Tools
DIN ISO 23801A0; 5 x 3
DIN ISO 23801A0; 5 x 3
--
--
Degree of protection
IP20
IP20
--
--
• With cable lug according to DIN 46234 or
max. 20 mm wide
- Stranded
mm2
- Finely stranded
mm2
---
---
---
2 x (10 ... 70)
2 x (10 ... 50)
• AWG cables, solid or stranded
--
--
--
2 x (7 ... 1/0)
Main conductors
AWG
Type
3RW30 1. ... 3RW30 4.
Conductor cross-sections
Auxiliary conductors (1 or 2 conductors can be connected):
Screw terminals
• Solid
• Finely stranded with end sleeve
mm2
mm2
2 x (0.5 ... 2.5)
2 x (0.5 ... 1.5)
• AWG cables
- Solid or stranded
- Finely stranded with end sleeve
AWG
AWG
2 x (20 ... 14)
2 x (20 ... 16)
Nm
lb.in
0.8 ... 1.2
7 ... 10.3
mm2
mm2
AWG
2 x (0.25 ... 2.5)
2 x (0.25 ... 1.5)
2 x (24 ... 14)
• Terminal screws
- Tightening torque
Spring-loaded terminals
• Solid
• Finely stranded with end sleeve
• AWG cables, solid or stranded
6/30
Siemens LV 1 N · 04/2008
© Siemens AG 2008
3RW Soft Starters
3RW30
for standard applications
Type
3RW30 03
Control electronics
Rated values
Rated control supply voltage
• Tolerance
V
%
24 ... 230 AC/DC
± 10
Rated control supply current
mA
25 ... 4
Rated frequency at AC
• Tolerance
Hz
%
50/60
± 10
Starting time
s
0.1 ... 20 (adjustable)
Starting voltage
%
40 ... 100 (adjustable)
Ramp-down time
s
0 ... 20 (adjustable)
Rated operational voltage
Tolerance
V AC
%
200 ... 400
± 10
Rated frequency
Tolerance
Hz
%
50/60
±10
Continuous duty (% of Ie)
%
100
Minimum load1) (% of Ie); at 40 °C
%
9
Maximum conductor length between soft starter and motor
m
1002)
Power electronics
IP20 (IP00 terminal compartment)
5000
(derating from 1000, see characteristic curves); higher on request
Permissible mounting position
10°
10°
10°
10°
Permissible ambient temperature
Operation
Storage
°C
°C
-25 ... +60; (derating from +40)
-40 ... +80
Load rating with rated operational current Ie
• According to IEC and UL/CSA1), for individual mounting, AC-53a
- At 40 °C
- At 50 °C
- At 60 °C
A
A
A
3
2.6
2.2
• According to IEC and UL/CSA1), for butt-mounting, AC-53a
- At 40 °C
- At 50 °C
- At 60 °C
A
A
A
2.6
2.2
1.8
W
6.5
W
3
Power loss
• In operation after completed starting with uninterrupted rated
operational current (40 °C) approx.
• At utilization of max. switching frequency
6
m
NSB0_01897
Degree of protection according to IEC 60529
Permissible installation height
Permissible starts per hour
• For intermittent duty S4, Tu = 40 °C, stand-alone installation vertical
• ON period = 70 %
1/h
1500
% Ie/s 300/0.2
Conductor cross-sections
Screw terminals
(1 or 2 conductors can be
connected)
For standard screwdriver
size 2 and Pozidriv 2
• Main conductors
- Solid
mm²
AWG
1 x (0.5 ... 4);
2 x (0.5 ... 2.5)
1 x (0.5 ... 2.5);
2 x (0.5 ... 1.5)
-2 x (20 ... 14)
Nm
lb.in
M3, PZ2
0.8 ... 1.2
7.1 ... 8.9
mm²
- Finely stranded with end sleeve mm²
- Stranded
- AWG cables
solid or stranded
- Terminal screws
- Tightening torque
• Auxiliary conductors
- Solid
mm²
- Finely stranded with end sleeve mm²
- AWG cables,
AWG
solid or stranded
- Terminal screws
- Tightening torque
Nm
lb.in
Spring-loaded terminals
1)
1 x (0.5 ... 4);
2 x (0.5 ... 2.5)
1 x (0.5 ... 2.5); 2 x (0.5 ... 1.5)
2 x (20 ... 14)
M3, PZ2
0.8 ... 1.2
7 ... 8.9
Main and auxiliary conductors
• Solid
mm2
2 x (0.25 ... 1.5)
• Finely stranded with end sleeve
mm2
2 x (0.25 ... 1)
• AWG cables,
solid or stranded
mm2
2 x (24 ... 16)
The rated motor current (specified on the motor's name plate) should at
least amount to the specified percentage of the SIRIUS soft starter unit's
rated operational current Ie.
2)
If this value is exceeded, problems with line capacities may arise, which
can result in false firing.
Siemens LV 1 N · 04/2008
6/31
© Siemens AG 2008
3RW Soft Starters
3RW30
for standard applications
Standard
Parameters
Electrostatic discharge (ESD)
EN 61000-4-2
±4 kV contact discharge, ±8 kV air discharge
Electromagnetic RF fields
EN 61000-4-3
Frequency range: 80 ... 2000 MHz with 80 % at 1 kHz
Degree of severity 3: 10 V/m
Conducted RF interference
EN 61000-4-6
Frequency range: 150 kHz ... 80 MHz with 80 % at 1 kHz
Interference 10 V
• Burst
EN 61000-4-4
±2 kV/5 kHz
• Surge
EN 61000-4-5
±1 kV line to line
±2 kV line to earth
EMC interference field strength
EN 55011
Limit value of Class A at 30 ... 1000 MHz,
limit value of Class B with 3RW30 2.; 24 V AC/DC
Radio interference voltage
EN 55011
Limit value of Class A at 0.15 ... 30 MHz,
limit value of Class B with 3RW30 2.; 24 V AC/DC
Electromagnetic compatibility according to EN 60947-4-2
EMC interference immunity
RF voltages and RF currents on cables
EMC interference emission
Radio interference suppression filters
Degree of noise suppression A (industrial applications)
Degree of noise suppression B (applications for residential areas)
Control voltage
• 230 V AC/DC
• 24 V AC/DC
1)
Not available1)
Not necessary with 3RW30 1. and 3RW30 2.;
Necessary with 3RW30 3. and 3RW30 4. (see Table)
Degree of noise suppression B cannot be obtained through the use of
filters as the strength of the electromagnetic field is not attenuated by the
filter.
Soft starter type
Rated current
Recommended filters1)
Soft starters
Voltage range 200 ... 480 V
Filter type
A
6
Not required
Rated current filter
Terminals
A
mm2
3RW30 36
3RW30 37
3RW30 38
45
63
72
4EF1512-1AA10
4EF1512-2AA10
4EF1512-3AA10
50
66
90
16
25
25
3RW30 46
3RW30 47
80
106
4EF1512-3AA10
4EF1512-4AA10
90
120
25
50
1)
The radio interference suppression filter is used to remove the conducted
interference from the main circuit. The field-related emissions comply with
degree of noise suppression B. Filter selection applies under standard
conditions: 10 starts per hour, start time 4 s at 300 % Ie.
6/32
Siemens LV 1 N · 04/2008
© Siemens AG 2008
3RW Soft Starters
3RW30
for standard applications
Fuse assignment
The type of coordination to which the motor feeder with soft
starter is mounted depends on the application-specific requirements. Normally, fuseless mounting (combination of motor
starter protector/circuit breaker and soft starter) is sufficient.
If type of coordination "2" is to be fulfilled, semiconductor fuses
must be fitted in the motor feeder.
Fuseless version
Q1
NSB0_01935
Q11
M
3~
Motor starter protectors1)
Soft starters
Rated
current
Q11
Type
A
400 V +10 %
Rated current
Q1
Iq max
Type
kA
A
3RW30 03
3
3RV10 11-1EA10
50
4
3RW30 13
3RW30 14
3.6
6.5
3RV10 21-1FA10
3RV10 21-1HA10
10
10
5
8
3RW30 16
3RW30 17
3RW30 18
9
12.5
17.6
3RV10 21-1JA10
3RV10 21-1KA10
3RV10 21-4BA10
10
10
10
10
12.5
20
3RW30 26
3RW30 27
3RW30 28
25
32
38
3RV10 21-4DA10
3RV10 31-4EA10
3RV10 31-4FA10
55
55
55
25
32
40
3RW30 36
3RW30 37
3RW30 38
45
63
72
3RV10 31-4GA10
3RV10 41-4JA10
3RV10 41-4KA10
20
20
20
45
63
75
3RW30 46
3RW30 47
80
106
3RV10 41-4LA10
3RV10 41-4MA10
11
11
90
100
1)
The rated motor current must be considered when selecting the devices.
2)
The types of coordination are explained in more detail in Catalog LV 1,
"Load Feeders, Motor Starters and Soft Starters"
––> "Fuseless Load Feeders".
Fused version (line protection only)
F1
Q21
M
3~
Soft starters
Line protection, maximum
Rated
current
Q11
Type
NSB0_01936
Q11
F1
Type
A
Line contactor
Rated current Size
(optional)
Q21
A
Type of coordination 11): Iq = 65 kA at 480 V 10 %
3RW30 032)
3
3NA3 8053)
20
000
3RT10 15
3RW30 13
3RW30 14
3.6
6.5
3NA3 803-6
3NA3 805-6
10
16
000
000
3RT10 15
3RT10 15
3RW30 16
3RW30 17
3RW30 18
9
12.5
17.6
3NA3 807-6
3NA3 810-6
3NA3 814-6
20
25
35
000
000
000
3RT10 16
3RT10 24
3RT10 26
3RW30 26
3RW30 27
3RW30 28
25
32
38
3NA3 822-6
3NA3 824-6
3NA3 824-6
63
80
80
00
00
00
3RT10 26
3RT10 34
3RT10 35
3RW30 36
3RW30 37
3RW30 38
45
63
72
3NA3 130-6
3NA3 132-6
3NA3 132-6
100
125
125
1
1
1
3RT10 36
3RT10 44
3RT10 45
3RW30 46
3RW30 47
80
106
3NA3 136-6
3NA3 136-6
160
160
1
1
3RT10 45
3RT10 46
1)
The types of coordination are explained in more detail in Catalog LV 1,
"Load Feeders, Motor Starters and Soft Starters"
––> "Fuseless Load Feeders".
2)
Iq = 50 kA at 400 V.
3)
3NA3 805-1 (LV HRC 00), 5SB2 61 (DIAZED), 5SE2 201-6 (NEOZED).
Siemens LV 1 N · 04/2008
6/33
6
Type of coordination 12)
© Siemens AG 2008
3RW Soft Starters
3RW30
for standard applications
Fused version with 3NE1 SITOR fuses (semiconductor and line protection)
F’1
Q21
M
3~
Soft starters
All-range fuses
Rated
current
Q11
Type
NSB0_01937
Q11
F'1
Type
A
Line contactors
Rated current Size
(optional)
Q21
A
6
Type of coordination 21): Iq = 65 kA at 480 V 10 %
3RW30 032)
3
3NE1 813-03)
16
000
3RT10 15
3RW30 13
3RW30 14
3.6
6.5
3NE1 813-0
3NE1 813-0
16
16
000
000
3RT10 15
3RT10 15
3RW30 16
3RW30 17
3RW30 18
9
12.5
17.6
3NE1 813-0
3NE1 813-0
3NE1 814-0
16
16
20
000
000
000
3RT10 16
3RT10 24
3RT10 26
3RW30 26
3RW30 27
3RW30 28
25
32
38
3NE1 803-0
3NE1 020-2
3NE1 020-2
35
80
80
000
00
00
3RT10 26
3RT10 34
3RT10 35
3RW30 36
3RW30 37
3RW30 38
45
63
72
3NE1 020-2
3NE1 820-0
3NE1 820-0
80
80
80
00
000
000
3RT10 36
3RT10 44
3RT10 45
3RW30 46
3RW30 47
80
106
3NE1 021-0
3NE1 022-0
100
125
00
00
3RT10 45
3RT10 46
1)
The types of coordination are explained in more detail in Catalog LV 1,
"Load Feeders, Motor Starters and Soft Starters"
––> "Fuseless Load Feeders".
The type of coordination "2" refers only to soft starters,
not to any components in the feeder.
2)
Iq = 50 kA at 400 V.
3)
No SITOR fuse required!
Alternatively: 3NA3 803 (LV HRC H00), 5SB2 21 (DIAZED), 5SE2 206
(NEOZED).
6/34
Siemens LV 1 N · 04/2008
© Siemens AG 2008
3RW Soft Starters
3RW30
for standard applications
Fused version with 3NE3 SITOR fuses (semiconductor protection by fuse, line and overload protection by motor starter protector;
alternatively, installation with contactor and overload relay possible)
F1
F3
Q21
Q1
F3
Q11
Soft starters
Semiconductor fuses, minimum
Rated
current
A
Q11
Type
M
3~
Rated current
F3
Type
NSB0_01939
M
3~
NSB0_01938
Q11
Semiconductor fuses, maximum
Size
A
Rated current
F3
Type
A
Semiconductor fuses, minimum
Size
Rated current
F3
Type
Size
A
Type of coordination 21): Iq = 65 kA at 480 V 10 %
3RW30 032)
3
--
--
--
--
--
--
3RW30 13
3RW30 14
3.6
6.5
---
---
---
---
---
---
3NE4 101
3NE4 101
32
32
0
0
3RW30 16
3RW30 17
3RW30 18
9
12.5
17.6
----
----
----
--3NE3 221
--100
--1
3NE4 101
3NE4 101
3NE4 101
32
32
32
0
0
0
3RW30 26
3RW30 27
3RW30 28
25
32
38
----
----
----
3NE3 221
3NE3 222
3NE3 222
100
125
125
1
1
1
3NE4 102
3NE4 118
3NE4 118
40
63
63
0
0
0
3RW30 36
3RW30 37
3RW30 38
45
63
72
--3NE3 221
--100
--1
3NE3 224
3NE3 225
3NE3 227
160
200
250
1
1
1
3NE4 120
3NE4 121
--
80
100
--
0
0
--
3RW30 46
3RW30 47
80
106
3NE3 222
3NE3 224
125
160
1
1
3NE3 225
3NE3 231
200
350
1
1
---
---
---
Soft starters
Q11
Type
Semiconductor fuses max.
Rated
current
A
Semiconductor fuses min.
Rated current Size
F3
Type
F3
Type
A
Semiconductor fuses max.
Rated current Size
F3
Type
A
Cylindrical fuses
Rated current Size
F3
Type
A
Rated
current
A
3RW30 032)
3
--
--
--
3NE8 015-1
25
00
3NE8 015-1
25
00
3NC1 010 10
3RW30 13
3RW30 14
3.6
6.5
---
---
---
3NE8 015-1
3NE8 015-1
25
25
00
00
3NE8 015-1
3NE8 015-1
25
25
00
00
3NC2 220 20
3NC2 220 20
3RW30 16
3RW30 17
3RW30 18
9
12.5
17.6
----
----
----
3NE8 015-1
3NE8 015-1
3NE8 003-1
25
25
35
00
00
00
3NE8 015-1 25
3NE8 018-1 63
3NE8 021-1 100
00
00
00
3NC2 220 20
3NC2 250 50
3NC2 263 63
3RW30 26
3RW30 27
3RW30 28
25
32
38
3NE4 117
3NE4 118
3NE4 118
50
63
63
0
0
0
3NE8 017-1
3NE8 018-1
3NE8 020-1
50
63
80
00
00
00
3NE8 021-1 100
3NE8 022-1 125
3NE8 022-1 125
00
00
00
3NC2 263 63
3NC2 280 80
3NC2 280 80
3RW30 36
3RW30 37
3RW30 38
45
63
72
3NE4 120
3NE4 121
--
80
100
--
0
0
--
3NE8 020-1 80
3NE8 021-1 100
3NE8 022-1 125
00
00
00
3NE8 024-1 160
3NE8 024-1 160
3NE8 024-1 160
00
00
00
3NC2 280 80
-----
3RW30 46
3RW30 47
80
106
---
---
---
3NE8 022-1 125
3NE8 024-1 160
00
00
3NE8 024-1 160
3NE8 024-1 160
00
00
---
Soft starters
Rated
current
Q11
Type
Line contactors
Motor starter protectors
(optional)
400 V +10 %
Rated current
Q21
Q1
Type
A
A
6
Type of coordination 21): Iq = 65 kA at 480 V 10 %
---
Line protection, maximum
Rated current Size
F1
Type
A
1)
Type of coordination 2 : Iq = 65 kA at 480 V 10 %
3RW30 032)
3
3RT10 15
3RV10 11-1EA10
4
3NA3 8053)
20
000
3RW30 13
3RW30 14
3.6
6.5
3RT10 15
3RT10 15
3RV10 21-1FA10
3RV10 21-1HA10
5
8
3NA3 803-6
3NA3 805-6
10
16
000
000
3RW30 16
3RW30 17
3RW30 18
9
12.5
17.6
3RT10 16
3RT10 24
3RT10 26
3RV10 21-1JA10
3RV10 21-1KA10
3RV10 21-1BA10
10
12.5
20
3NA3 807-6
3NA3 810-6
3NA3 814-6
20
25
35
000
000
000
3RW30 26
3RW30 27
3RW30 28
25
32
38
3RT10 26
3RT10 34
3RT10 35
3RV10 31-4DA10
3RV10 31-4EA10
3RV10 31-4FA10
25
32
40
3NA3 822-6
3NA3 824-6
3NA3 824-6
63
80
80
00
00
00
3RW30 36
3RW30 37
3RW30 38
45
63
72
3RT10 36
3RT10 44
3RT10 45
3RV10 31-4GA10
3RV10 41-4JA10
3RV10 41-4KA10
45
63
75
3NA3 130-6
3NA3 132-6
3NA3 132-6
100
125
125
1
1
1
160
160
1
1
3RW30 46
80
3RT10 45
3RV10 41-4LA10
90
100
3RW30 47 106
3RT10 46
3RV10 41-4MA10
1)
The types of coordination are explained in more detail in Catalog LV 1,
"Load Feeders, Motor Starters and Soft Starters"
––> "Fuseless Load Feeders". The type of coordination "2" refers only to
soft starters, not to any components in the feeder.
3NA3 136-6
3NA3 136-6
2)
Iq = 50 kA at 400 V.
3)
3NA3 805-1 (LV HRC 00), 5SB2 61 (DIAZED).
Siemens LV 1 N · 04/2008
6/35
© Siemens AG 2008
3RW Soft Starters
3RW30
for standard applications
■ Characteristic curves
Permissible installation height
NSB0_01704
105
Operational rated current I e in %
100
95
90
85
80
75
70
0
1000
2000
3000
4000
Mounting height in m
5000
At an installation height above 2000 m, the max. permissible operational
voltage is reduced to 460 V.
■ More information
Application examples for normal starting (Class 10)
Normal starting Class 10 (up to 20 s with 300 % In motor),
The soft starter rating can be selected to be as high as the rating of the motor used
Application
Conveyor belt
Roller conveyor
Compressor
Small fan
Pump
Hydraulic pump
70
10
60
10
50
20
40
20
40
10
40
10
Starting parameters
6
• Voltage ramp and current
limiting
- Starting voltage
- Starting time
%
s
Note:
These tables present sample set values and device sizes. They
are intended only for the purposes of information and are not
binding. The set values depend on the application in question
and must be optimized during start-up.
The soft starter dimensions should be checked where necessary
with the Win-Soft Starter software or with the help of Technical
Assistance.
6/36
Siemens LV 1 N · 04/2008
© Siemens AG 2008
3RW Soft Starters
3RW30
for standard applications
Configuration
Status graphs
If necessary, an overload relay for heavy starting must be selected where long starting times are involved. PTC sensors are
recommended.
In the motor feeder between the SIRIUS 3RW soft starter and the
motor, no capacitive elements are permitted (e.g. no reactivepower compensation equipment). In addition, neither static systems for reactive-power compensation nor dynamic PFC (Power
Factor Correction) must be operated in parallel during starting
and ramp-down of the soft starter. This is important to prevent
faults arising on the compensation equipment and/or the soft
starter.
All elements of the main circuit (such as fuses, controls and overload relays) should be dimensioned for direct starting, following
the local short-circuit conditions. Fuses, controls and overload
relays must be ordered separately. Please observe the maximum switching frequencies specified in the technical specifications.
Note:
When induction motors are switched on, voltage drops occur as
a rule on starters of all types (direct starters, wye-delta starters,
soft starters). The infeed transformer must always be dimensioned such that the voltage dip when starting the motor remains
within the permissible tolerance. If the infeed transformer is dimensioned with only a small margin, it is best for the control voltage to be supplied from a separate circuit (independently of the
main voltage) in order to avoid the potential switching off of the
soft starter.
U
UN
US
t R on
t
t R on
t
ON 13/14
NSB0_01941
The 3RW solid-state motor controllers are designed for easy
starting conditions. In the event of deviating conditions or increased switching frequency, it may be necessary to choose a
larger device. For accurate dimensioning, use the Win-Soft
Starter selection and simulation program.
Win-Soft Starter selection and simulation program
With this software, you can simulate and select all Siemens soft
starters, taking into account various parameters such as mains
properties, motor and load data, and special application
requirements.
The software is a valuable tool, which makes complicated,
lengthy manual calculations for determining the required soft
starters superfluous.
You can order the CD-ROM under the following order number:
Order No. E20001-D1020-P302-V2-7400.
You can find more information on the Internet at:
http://www.siemens.com/softstarter
6
Power electronics schematic circuit diagram
L2
L3
T1
T2
T3
NSB0_01940
L1
A bypass contact system is already integrated in the 3RW30 soft
starter and therefore does not have to be ordered separately.
Siemens LV 1 N · 04/2008
6/37
© Siemens AG 2008
3RW Soft Starters
3RW40
for standard applications
■ Function
The space required by the compact SIRIUS 3RW40 soft starter
is often only about one third of that required by a contactor assembly for wye-delta starting of comparable rating. This not only
saves space in the control cabinet and on the standard mounting rail but also does away completely with the wiring work
needed for wye-delta starters. This is notable in particular for
higher motor ratings which are only rarely available as fully wired
solutions.
At the same time the number of cables from the starter to the
motor is reduced from six to three. Compact dimensions, short
start-up times, easy wiring and fast commissioning make
themselves felt as clear-cut cost advantages.
The bypass contacts of these soft starters are protected during
operation by an integrated solid-state arc quenching system.
This prevents damage to the bypass contacts in the event of a
fault, e.g. brief disconnection of the control voltage, mechanical
shocks or life-related component defects on the coil operating
mechanism or main contact spring.
6
The starting current of particularly powerful operating mechanisms can place an unjustifiable load on the local supply system.
Soft starters reduce this starting current by means of their voltage ramp. Thanks to the adjustable current limiting, the SIRIUS
3RW40 soft starter takes even more pressure off the supply system. It leaves the set start ramp during the ramp-up – the ramp
gradient is fixed by the starting voltage and the ramp time – as
soon as the selected current limit is reached. From this moment
the voltage of the soft starter is controlled so that the current supplied to the motor remains constant. This process is ended either
by completion of the motor ramp-up or by tripping by the intrinsic device protection or the motor overload protection. As the result of this function the actual motor ramp-up can well take
longer than the ramp time selected on the soft starter.
Thanks to the integrated motor overload protection according to
IEC 60947-4-2 there is no need of an additional overload relay
on the new soft starters. The rated motor current, the setting of
the overload tripping time (Class times) and the reset of the motor overload protection function can be adjusted easily and
quickly. Using a 4-step rotary potentiometer it is possible to set
different overload tripping times on the soft starter. In addition to
Class 10, 15 and 20 it is also possible to switch off the motor
overload protection if a different motor management control device is to be used for this function, e.g. with connection to
PROFIBUS.
Device versions with thermistor motor protection evaluation are
available up to a rating of 55 kW (at 400 V). A "Thermoclick" measuring probe can be connected directly, as can a PTC of type A.
Thermal overloading of the motor, open circuits and short-circuits in the sensor circuit all result in the direct disconnection of
the soft starter. And if ever the soft starter trips, various reset options are available the same as with intrinsic device protection
and motor load protection: manually with the reset button, automatically or remotely through brief disconnection of the control
voltage.
The new series of devices comes with the "polarity balancing"
control method, which is designed to prevent direct current components in two-phase controlled soft starters. On two-phase
controlled soft starters the current resulting from superimposition
of the two controlled phases flows in the uncontrolled phase.
This results for physical reasons in an asymmetric distribution of
the three phase currents during the motor ramp-up. This phenomenon cannot be influenced, but in most applications it is
non-critical.
6/38
Siemens LV 1 N · 04/2008
Controlling the power semiconductors results not only in this
asymmetry, however, but also in the previously mentioned direct
current components which can cause severe noise generation
on the motor at starting voltages of less than 50 %.
The control method used for these soft starters eliminates these
direct current components during the ramp-up phase and prevents the braking torque which they can cause. It creates a motor ramp-up that is uniform in speed, torque and current rise,
thus permitting a particularly gentle, two-phase starting of the
motors. At the same time the acoustic quality of the starting operation comes close to the quality of a three-phase controlled
soft starter. This is made possible by the on-going dynamic harmonizing and balancing of current half-waves of different polarity during the motor ramp-up. Hence the name "polarity balancing".
As an option the thyristors can also be protected by SITOR semiconductor fuses from short-circuiting so that the soft starter is
still functional after a short-circuit (coordination type 2). Three
LEDs are used to indicate the operating state as well as possible
errors, e.g. non-permissible tripping time (CLASS setting),
mains or phase failure, missing load, thermal overloading or device faults.
• Soft starting with voltage ramp; the starting voltage setting
range Us is 40 to 100 % and the ramp time tR can be set from
0 to 20 s.
• Smooth ramp-down with voltage ramp; the running down time
toff can be set between 0 s to 20 s.
• Solid-state motor overload and intrinsic device protection
• Optional thermistor motor protection (up to size S3)
• Remote reset
(integrated up to size S3, optional for size S6 and larger)
• Adjustable current limiting
• Integrated bypass contact system to minimize power loss
• Setting with potentiometers
• Simple mounting and start-up
• Integrated status monitoring and fault monitoring
• Mains voltages 50/60 Hz, 200 ... 600 V
• Various control voltage versions
- Sizes S0 to S3:
24 V AC/DC and 110 to 230 V AC/DC
- sizes S6 to S12:
115 V AC and 230 V AC.
Control by way of the internal 24 V DC supply and direct
control by means of PLC possible.
• Wide temperature range from -25 to +60 °C
• Built-in auxiliary contacts ensure user-friendly control and
possible further processing within the system
(for status graphs see Page 6/51).
© Siemens AG 2008
3RW Soft Starters
3RW40
for standard applications
■ Technical specifications
Type
3RW40 2.
3RW40 3., 3RW40 4.
Control electronics
Terminal
A1/A2
Rated values
Rated control supply voltage
• Tolerance
V
%
24
±20
110 ... 230
-15/+10
24
±20
110 ... 230
-15/+10
Rated control supply current
• STANDBY
• During pick-up
• ON without fan
• ON with fan
mA
mA
mA
mA
< 150
< 200
< 250
< 300
< 50
< 100
< 50
< 70
< 200
< 5000
< 200
< 250
< 50
< 1500
< 50
< 70
Rated frequency
• Tolerance
Hz
%
50/60
±10
3/6
1.5/3
Approx. 12
Approx. 12
3/6
1.5/3
Control inputs
IN
ON/OFF
Rated operational current
• AC
• DC
Relay outputs
Output 1
Output 2
Output 3
mA
mA
ON/RUN mode1)
13/14
BYPASSED
23/24
OVERLOAD/FAILURE 95/96/98
Rated operational current
Approx. 12
Approx. 12
Operating indication (NO)
Bypass indication (NO)
Overload/error signal (NC/NO)
A
A
3 AC-15/AC-14 at 230 V,
1 DC-13 at 24 V
Protection against overvoltages
Protection by means of varistor through contact
Short-circuit protection
4 A gL/gG operational class;
6 A quick (fuse is not included in scope of supply)
1)
Factory default: ON mode.
Type
3RW40 5.
3RW40 7 .
Control electronics
Terminal
A1/A2
Rated values
Rated control supply voltage
• Tolerance
V AC
%
115
-15/+10
Rated control supply current STANDBY
Rated control supply current ON1)
Rated frequency
• Tolerance
mA
mA
Hz
%
15
440
50/60
±10
Control inputs
IN
Rated operational current
Rated operational voltage
mA
V DC
ON/OFF
Approx. 10 according to DIN 19240
24 from internal supply dc+ or external DC voltage (according to DIN 19240)
through terminals and IN
Relay outputs
Output 1
Output 2
Output 3
ON/RUN mode2)
13/14
BYPASSED
23/24
OVERLOAD/FAILURE 95/96/98
Rated operational current
230
15
660
50/60
±10
360
6
200
115
-15/+10
Operating indication (NO)
Bypass indication (NO)
Overload/error signal (NC/NO)
A
A
Protection against overvoltages
Short-circuit protection
1)
230
3 AC-15/AC-14 at 230 V,
1 DC-13 at 24 V
Protection by means of varistor through contact
4 A gL/gG operational class;
6 A quick (fuse is not included in scope of supply)
2)
Values for the coil power consumption at +10 % Un, 50 Hz.
Type
Factory default: ON mode.
3RW40 2., 3RW40 3., 3RW40 4.
Control electronics
Operating indications
Off
Start
Bypass
Ramp-down
LED
DEVICE
Green
Green
Green
Green
STATE/BYPASSED/FAILURE
Off
Green flashing
Green
Green flashing
OVERLOAD
Off
Off
Off
Off
Green
Yellow flashing
Not relevant
Not relevant
Red flashing
Off
Off
Off
Red
Red
Off
Off
Motor protection shut-down (overload thermistor)
Thermistor defective (open circuit, short-circuit)
Green
Green
Green
Red
Off
Off
Red flashing
Red
Red flickering
Thermal overloading of the thyristors
Missing mains voltage, phase failure, missing load
Device fault
Yellow
Green
Red
Red
Red
Red
Off
Off
Off
Alarm signals
Ie/class setting not permissible
Start inhibited/thyristors too hot
Error signals
• 24 V:
U < 0.75 x Us or U > 1.25 x Us
• 110 ... 230 V: U < 0.75 x Us or U > 1.15 x Us
Non-permissible Ie/Class setting for edge 0 –> 1 on input IN
Siemens LV 1 N · 04/2008
6/39
© Siemens AG 2008
3RW Soft Starters
3RW40
for standard applications
Type
3RW40 5. and 3RW40 7.
Control electronics
LEDs
Operating indications
Off
Start
Bypass
Ramp-down
DEVICE
Green
Green
Green
Green
STATE/BYPASSED
Off
Green flashing
Green
Green flashing
FAILURE
Off
Off
Off
Off
OVERLOAD
Off
Off
Off
Off
Green
Yellow flashing
Not relevant
Not relevant
Not relevant
Not relevant
Red flashing
Off
Off
Off
Red
Off
Green
Green
Off
Off
Red
Off
Red flashing
Red
Thermal overloading of the thyristors
Missing mains voltage, phase failure, missing load
Device fault
Yellow
Green
Red
Off
Off
Off
Red
Red
Red
Off
Off
Off
Type
3RW40 . .
Alarm signals
Ie/class setting not permissible
Start inhibited/thyristors too hot
Error signals
U < 0.75 x Us or U > 1.15 x Us
Ie/class setting not permissible
for edge 0 –> 1 on input IN
Motor protection shut-down
Factory default
Protection functions
Motor protection functions
Trips in the event of
Trip class to IEC 60947-4-1
Phase failure sensitivity
Class
%
Thermal overloading of the motor
10/15/20
> 40
min
No
Yes1)
Manual/automatic/remote reset2)
(MAN/AUTO/REMOTE2))
5
Overload warning
Thermistor protection according to IEC 60947-8, type A/IEC 60947-5-1
Reset option after tripping
Recovery time
Device protection functions
Trips in the event of
Thermal overloading of the thyristors or
bypass3)
Manual/automatic/remote reset2)
(MAN/AUTO/REMOTE2))
Reset option after tripping
Recovery time
• During overloading of the thyristors
• During overloading of the bypass
6
10
s
s
30
60
Control times
Closing delay (with connected control voltage)
Closing delay (automatic/mains contactor mode)
Recovery time (closing command in active ramp-down)
ms
ms
ms
< 50
<300
100
Mains failure bridging time
Control supply voltage
ms
50
Mains failure response time
Load current circuit
ms
500
min
5
s
s
30
60
s
%
0 ... 20
40 ... 100
1.3 ... 5 x Ie
7.5
40
5 x Ie
s
Control times and parameters
Reclosing lockout after overload trip
Motor protection trip
Device protection trip
• During overloading of the thyristors
• During overloading of the bypass
Starting parameters
Starting time
Starting voltage
Starting current limit
Ramp-down parameters
Ramp-down time
0 ... 20
0
Reset mode parameters (for motor/device protection shut-down)
Manual reset
LEDs
Automatic reset
LEDs
Remote reset (REMOTE)2)
LEDs
Off
Yellow
Green
Off
Start-up detection
Yes
Operating mode output 13/14
Rising edge at
Falling edge at
Start command
Off command
Ramp-down end
1)
Optional up to size S3 (device variant).
2)
Integrated remote reset (REMOTE) available only for
3RW40 2. to 3RW40 4.; remote reset with 3RU19 accessory module
available for 3RW40 5. and 3RW40 7.
3)
Bypass protection up to size S3.
6/40
Siemens LV 1 N · 04/2008
ON
RUN
ON
© Siemens AG 2008
3RW Soft Starters
3RW40
for standard applications
Type
3RW40 2.-. .B.4, 3RW40 2.-. .B.5, 3RW40 5.-.BB.4, 3RW40 5.-.BB.5,
3RW40 3.-. .B.4, 3RW40 3.-. .B.5, 3RW40 7.-.BB.4 3RW40 7.-.BB.5
3RW40 4.-. .B.4 3RW40 4.-. .B.5
Power electronics
Rated operational voltage
Tolerance
V AC
%
200 ... 480
-15/+10
400 ... 600
-15/+10
200 ... 460
-15/+10
400 ... 600
-15/+10
Rated frequency
Tolerance
Hz
%
50/60
±10
Continuous duty at 40 °C (% of Ie)
%
115
Minimum load (% of minimum selectable rated motor current IM)
%
20 (at least 2 A)
Maximum cable length between soft starter and motor
m
300
Permissible installation height
m
5000
(derating from 1000, see characteristic curves); higher on request
• With auxiliary fan (for 3RW40 2. ... 3RW40 4.)
2 2 ,5 ° 2 2 ,5 °
9 0 °
• Without auxiliary fan (for 3RW40 2. ... 3RW40 4.)
Permissible ambient temperature
Operation
Storage
10°
°C
°C
10°
-- (fan integrated in the soft starter)
10°
10°
NSB0_01897
9 0 °
N S B 0 _ 0 0 6 4 9
Permissible mounting position
-25 ... +60; (derating from +40)
-40 ... +80
Degree of protection
IP20 for 3RW40 2.; IP00 for 3RW40 3. IP00
and 3RW40 4.
Type
3RW40 24
3RW40 26
3RW40 27
3RW40 28
Load rating with rated operational current Ie
• According to IEC and UL/CSA1), for individual mounting, AC-53a
- At 40 °C
- At 50 °C
- At 60 °C
A
A
A
12.5
11
10
25.3
23
21
32.2
29
26
38
34
31
Smallest adjustable rated motor current IM
For the motor overload protection
A
5
10
17
23
W
2
8
13
19
W
17
47
55
64
A
1/h
12.5
50
25
23
32
23
38
19
- Rated motor current IM2)4), starting time 4 s
- Starts per hour3)
A
1/h
12.5
36
25
15
32
16
38
12
• For heavy starting (Class 15)
- Rated motor current IM2), starting time 4.5 s
- Starts per hour3)
A
1/h
11
49
23
21
30
18
34
18
- Rated motor current IM2)4), starting time 6 s
- Starts per hour3)
A
1/h
11
36
23
14
30
13
34
13
A
1/h
10
47
21
21
27
20
31
18
A
1/h
10
34
21
15
27
14
31
13
Power loss
• In operation after completed starting with uninterrupted rated
operational current (40 °C) approx.
• During starting with current limit set to 300 % IM (40°C)
6
Power electronics
Permissible rated motor current and starts per hour
• For normal starting (Class 10)
- Rated motor current IM2), starting time 3 s
- Starts per hour3)
• For heavy starting (Class 20)
- Rated motor current IM2), starting time 6 s
- Starts per hour3)
- Rated motor current IM2)4), starting time 8 s
- Starts per hour3)
1)
Measurement at 60 °C according to UL/CSA not required.
2)
Current limit on soft starter set to 300 % IM.
3)
For intermittent duty S4 with ON period = 30 %, Tu = 40 °C, stand-alone
installation vertical. The quoted switching frequencies do not apply for
automatic mode.
4)
Maximum adjustable rated motor current IM, dependent on CLASS setting.
Siemens LV 1 N · 04/2008
6/41
© Siemens AG 2008
3RW Soft Starters
3RW40
for standard applications
Type
3RW40 36
3RW40 37
3RW40 38
3RW40 46
3RW40 47
Power electronics
Load rating with rated operational current Ie
• According to IEC and UL/CSA1), for individual mounting, AC-53a
- At 40 °C
- At 50 °C
- At 60 °C
A
A
A
45
42
39
63
58
53
72
62.1
60
80
73
66
106
98
90
Smallest adjustable rated motor current IM
For the motor overload protection
A
23
26
35
43
46
W
6
12
15
12
21
W
79
111
125
144
192
A
1/h
45
38
63
23
72
22
80
22
106
15
- Rated motor current IM2)4), starting time 4 s
- Starts per hour3)
A
1/h
45
26
63
15
72
15
80
15
106
10
• For heavy starting (Class 15)
- Rated motor current IM2), starting time 4.5 s
- Starts per hour3)
A
1/h
42
30
50
34
56
34
70
24
84
23
- Rated motor current IM2)4), starting time 6 s
- Starts per hour3)
A
1/h
42
21
50
24
56
24
70
16
84
17
A
1/h
38
30
46
31
50
34
64
23
77
23
A
1/h
38
21
46
22
50
24
64
16
77
16
Power loss
• In operation after completed starting with uninterrupted rated
operational current (40 °C) approx.
• During starting with current limit set to 300 % IM (40°C)
Permissible rated motor current and starts per hour
• For normal starting (Class 10)
- Rated motor current IM2), starting time 3 s
- Starts per hour3)
• For heavy starting (Class 20)
- Rated motor current IM2), starting time 6 s
- Starts per hour3)
- Rated motor current IM2)4), starting time 8 s
- Starts per hour3)
1)
Measurement at 60 °C according to UL/CSA not required.
2)
Current limit on soft starter set to 300 % IM.
3)
For intermittent duty S4 with ON period = 30 %, Tu = 40 °C, stand-alone
installation vertical. The quoted switching frequencies do not apply for
automatic mode.
4)
Maximum adjustable rated motor current IM, dependent on CLASS setting.
Type
3RW40 55
3RW40 56
3RW40 73
3RW40 74
3RW40 75
3RW40 76
6
Power electronics
Load rating with rated operational current Ie
• According to IEC and UL/CSA1), for individual mounting, AC-53a
- At 40 °C
- At 50 °C
- At 60 °C
A
A
A
134
117
100
162
145
125
230
205
180
280
248
215
356
315
280
432
385
335
Smallest adjustable rated motor current IM
For the motor overload protection
A
59
87
80
130
131
207
W
60
75
75
90
125
165
W
1043
1355
2448
3257
3277
3600
A
1/h
134
20
162
8
230
14
280
20
356
16
432
17
A
1/h
134
7
162
1.4
230
3
280
8
356
5
432
5
A
1/h
134
11
152
8
210
11
250
13
341
11
402
12
A
1/h
134
1.2
152
1.7
210
1
250
6
341
2
402
2
A
1/h
124
12
142
9
200
10
230
10
311
10
372
10
A
1/h
124
2
142
2
200
1
230
5
311
1
372
1
Power loss
• In operation after completed starting with uninterrupted rated
operational current (40 °C) approx.
• During starting with current limit set to 350 %2) IM (40°C)
Permissible rated motor current and starts per hour
• For normal starting (Class 10)
- Rated motor current IM2), starting time 10 s
- Starts per hour3)
- Rated motor current IM2)4), starting time 20 s
- Starts per hour3)
• For heavy starting (Class 15)
- Rated motor current IM2), starting time 15 s
- Starts per hour3)
- Rated motor current IM2)4), starting time 30 s
- Starts per hour3)
• For heavy starting (Class 20)
- Rated motor current IM2), starting time 20 s
- Starts per hour3)
- Rated motor current IM2)4), starting time 40 s
- Starts per hour3)
1)
Measurement at 60 °C according to UL/CSA not required.
2)
Current limit on soft starter set to 350 % IM.
3)
For intermittent duty S4 with ON period = 70 %, Tu = 40 °C, stand-alone
installation vertical. The quoted switching frequencies do not apply for
automatic mode.
4)
Maximum adjustable rated motor current IM, dependent on CLASS setting.
6/42
Siemens LV 1 N · 04/2008
© Siemens AG 2008
3RW Soft Starters
3RW40
for standard applications
Soft starters
Type
3RW40 2.
3RW40 3.
3RW40 4.
Conductor cross-sections
Main conductors
Front clamping point
connected
• Solid
mm2
2 x (1.5 ... 2.5);
2 x (2.5 ... 6) according
to IEC 60947; max.
1 x 10
2 x (1.5 ... 16)
2 x (2.5 ... 16)
• With end sleeve
mm2
2 x (1.5 ... 2.5);
2 x (2.5 ... 6)
1 x (0.75 ... 25)
1 x (2.5 ... 35)
• Stranded
mm2
--
1 x (0.75 ... 35)
1 x (4 ... 70)
- Solid
AWG
2 x (16 ... 12)
- Solid or stranded
AWG
2 x (14 ... 10)
1 x (18 ... 2)
2 x (10 ... 1/0)
- Stranded
AWG
1x8
--
--
• Solid
mm2
--
2 x (1.5 ... 16)
2 x (2.5 ... 16)
• With end sleeve
mm2
--
1 x (1.5 ... 25)
1 x (2.5 ... 50)
• Stranded
mm2
--
1 x (1.5 ... 35)
1 x (10 ... 70)
NSB00479
Screw terminals
• AWG cables
NSB00480
Rear clamping point
connected
NSB00481
Both clamping points
connected
• AWG cables
AWG
--
1 x (16 ... 2)
2 x (10 ... 1/0)
• Solid
- Solid or stranded
mm2
--
2 x (1.5 ... 16)
2 x (2.5 ... 16)
• With end sleeve
mm2
--
2 x (1.5 ... 16)
2 x (2.5 ... 35)
• Stranded
mm2
--
2 x (1.5 ... 25)
2 x (10 ... 50)
AWG
--
2 x (16 ... 2)
1 x (10 ... 2/0)
Nm
lb.in
2 ... 2.5
18 ... 22
4.5
40
6.5
58
Tools
PZ 2
PZ 2
Allen screw 4 mm
Degree of protection
IP20
IP20
(terminal compartment
IP00)
IP20
(terminal compartment
IP00)
• AWG cables
- Solid or stranded
• Tightening torque
Spring-loaded terminals Main conductors
mm2
1 ... 10
--
• Finely stranded with end sleeve
mm2
1 ... 6 end sleeves
without plastic collar
--
- Solid or stranded (finely stranded)
AWG
16 ... 10
--
- Stranded
AWG
1x8
--
6
• Solid
• AWG cables
Busbar connections
Tools
DIN ISO 2380-1A0; 5 x 3 --
Degree of protection
IP20
--
Main conductors
• With cable lug according to DIN 46234 or
max. 20 mm wide
- Stranded
mm2
--
2 x (10 ... 70)
- Finely stranded
mm2
--
2 x (10 ... 50)
AWG
--
2 x (7 ... 1/0)
• AWG cables, solid or stranded
Siemens LV 1 N · 04/2008
6/43
© Siemens AG 2008
3RW Soft Starters
3RW40
for standard applications
Soft starters
Type
3RW40 5.
3RW40 7.
Conductor cross-sections
Screw terminals
Main conductors
3RT19 55-4G (55 kW)
3RT19 66-4G
• Finely stranded with end sleeve
• Finely stranded without end sleeve
• Stranded
mm2
mm2
mm2
16 ... 70
16 ... 70
16 ... 70
70 ... 240
70 ... 240
95 ... 300
• Ribbon cable conductors
(number x width x thickness)
• AWG cables, solid or stranded
mm
AWG
Min. 3 x 9 x 0.8, max. 6 x 15.5 x 0.8 Min. 6 x 9 x 0.8
Max. 20 x 24 x 0.5
6 ... 2/0
3/0 ... 600 kcmil
• Finely stranded with end sleeve
• Finely stranded without end sleeve
• Stranded
mm2
mm2
mm2
16 ... 70
16 ... 70
16 ... 70
120 ... 185
120 ... 185
120 ... 240
• Ribbon cable conductors
(number x width x thickness)
• AWG cables, solid or stranded
mm
AWG
Min. 3 x 9 x 0.8,
Max. 6 x 15.5 x 0.8
6 ... 2/0
Min. 6 x 9 x 0.8
Max. 20 x 24 x 0.5
250 ... 500 kcmil
• Finely stranded with end sleeve
• Finely stranded without end sleeve
• Stranded
mm2
mm2
mm2
Max. 1 x 50, 1 x 70
Max. 1 x 50, 1 x 70
Max. 2 x 70
Min. 2 x 50; max. 2 x 185
Min. 2 x 50; max. 2 x 185
Max. 2 x 70; max. 2 x 240
• Ribbon cable conductors
(number x width x thickness)
• AWG cables, solid or stranded
mm
Max. 2 x (6 x 15.5 x 0.8)
Max. 2 x (20 x 24 x 0.5)
AWG
Max. 2 x 1/0
Min. 2 x 2/0 Max. 2 x 500 kcmil
Nm
lb.in
M10 (hexagon socket, A/F4)
10 ... 12
90 ... 110
M12 (hexagon socket, A/F5)
20 ... 22
180 ... 195
With box terminal
NSB00479
Front clamping point
connected
NSB00480
Rear clamping point
connected
NSB00481
Both clamping points
connected
• Terminal screws
- Tightening torque
Screw terminals
Main conductors
3RT19 56-4G
With box terminal
mm2
mm2
mm2
16 ... 120
16 ... 120
16 ... 120
• Ribbon cable conductors
(number x width x thickness)
• AWG cables, solid or stranded
mm
AWG
Min. 3 x 9 x 0.8
Max. 6 x 15.5 x 0.8
6 ... 250 kcmil
• Finely stranded with end sleeve
• Finely stranded without end sleeve
• Stranded
mm2
mm2
mm2
Max. 1 x 95, 1 x 120
Max. 1 x 95, 1 x 120
Max. 2 x 120
• Ribbon cable conductors
(number x width x thickness)
• AWG cables, solid or stranded
mm
Max. 2 x (10 x 15.5 x 0.8)
AWG
Max. 2 x 3/0
mm2
mm2
AWG
16 ... 951)
25 ... 1201)
4 ... 250 kcmil
50 ... 2402)
70 ... 2402)
2/0 ... 500 kcmil
mm
17
M8 x 25 (A/F13)
10 ... 14
89 ... 124
25
M10 x 30 (A/F17)
14 ... 24
124 ... 210
NSB00479
NSB00480
Front or rear clamping point • Finely stranded with end sleeve
connected
• Finely stranded without end sleeve
• Stranded
NSB00481
6
Both clamping points
connected
Screw terminals
Main conductors
Without box terminal/busbar connection
• Finely stranded with cable lug
• Stranded with cable lug
• AWG cables, solid or stranded
• Connecting bar (max. width)
• Terminal screws
- Tightening torque
1)
When connecting cable lugs to DIN 46235, use 3RT19 56-4EA1 terminal
cover for conductor cross-sections from 95 mm² to ensure phase spacing.
Soft starters
Nm
lb.in
2)
Type
When connecting cable lugs to DIN 46234, the 3RT19 66-4EA1 terminal
cover must be used for conductor cross-sections of 240 mm² and more as
well as DIN 46235 for conductor cross-sections of 185 mm² and more to
keep the phase clearance.
3RW40 . .
Conductor cross-sections
Auxiliary conductors (1 or 2 conductors can be connected):
Screw terminals
• Solid
• Finely stranded with end sleeve
mm2
mm2
2 x (0.5 ... 2.5)
2 x (0.5 ... 1.5)
• AWG cables
- Solid or stranded
- Finely stranded with end sleeve
AWG
AWG
2 x (20 ... 14)
2 x (20 ... 16)
Nm
lb.in
0.8 ... 1.2
7 ... 10.3
• Solid
- 3RW40 2. ... 3RW40 4.
- 3RW40 5., 3RW40 7.
mm2
mm2
2 x (0.25 ... 2.5)
2 x (0.25 ... 1.5)
• Finely stranded with end sleeve
• AWG cables, solid or stranded
mm2
AWG
2 x (0.25 ... 1.5)
2 x (24 ... 14) for 3RW40 2. ... 3RW40 4.;
2 x (24 ... 16) for 3RW40 5. and 3RW40 7.
• Terminal screws
- Tightening torque
Spring-loaded terminals
6/44
Siemens LV 1 N · 04/2008
© Siemens AG 2008
3RW Soft Starters
3RW40
for standard applications
Standard
Parameters
Electrostatic discharge (ESD)
EN 61000-4-2
±4 kV contact discharge, ±8 kV air discharge
Electromagnetic RF fields
EN 61000-4-3
Frequency range: 80 ... 1000 MHz with 80 % at 1 kHz
Degree of severity 3: 10 V/m
Conducted RF interference
EN 61000-4-6
Frequency range: 150 kHz ... 80 MHz with 80 % at 1 kHz
Interference 10 V
• Burst
EN 61000-4-4
±2 kV/5 kHz
• Surge
EN 61000-4-5
±1 kV line to line
±2 kV line to earth
EMC interference field strength
EN 55011
Limit value of Class A at 30 ... 1000 MHz,
limit value of Class B with 3RW40 2. 24 V AC/DC
Radio interference voltage
EN 55011
Limit value of Class A at 0.15 ... 30 MHz,
limit value of Class B with 3RW40 2. 24 V AC/DC
Electromagnetic compatibility
according to EN 60947-4-2
EMC interference immunity
RF voltages and RF currents on cables
EMC interference emission
Radio interference suppression filters
Degree of noise suppression A (industrial applications)
Not required
Degree of noise suppression B
(applications for residential areas)
Control voltage
• 110 ... 230 V AC/DC
• 115/230 V AC
• 24 V AC/DC
Not available1)
Not available1)
Not required for 3RW40 2.; required for 3RW40 3. and 3RW40 4. (see Table)
Degree of noise suppression B cannot be obtained through the use of
filters as the strength of the electromagnetic field is not attenuated by the
filter.
Soft starter type
Rated current
Recommended filters1)
Soft starters
Voltage range 200 ... 480 V
Filter type
A
Rated current filter
Terminals
A
mm2
3RW40 36
3RW40 37
3RW40 38
45
63
72
4EF1512-1AA10
4EF1512-2AA10
4EF1512-3AA10
50
66
90
16
25
25
3RW40 46
3RW40 47
80
106
4EF1512-3AA10
4EF1512-4AA10
90
120
25
50
1)
6
1)
The radio interference suppression filter is used to remove the conducted
interference from the main circuit. The field-related emissions comply with
degree of noise suppression B. Filter selection applies under standard
conditions:10 starts per hour, start time 4 s at 300 % Ie.
Siemens LV 1 N · 04/2008
6/45
© Siemens AG 2008
3RW Soft Starters
3RW40
for standard applications
Fuse assignment
The type of coordination to which the motor feeder with soft
starter is mounted depends on the application-specific requirements. Normally, fuseless mounting (combination of motor
starter protector/circuit breaker and soft starter) is sufficient. If
type of coordination "2" is to be fulfilled, semiconductor fuses
must be fitted in the motor feeder.
Fuseless version
Q1
NSB0_01902
Q11
M
3~
Motor starter protectors/circuit breakers1)
Soft starters
Rated
current
Q11
Type
A
400 V +10 %
400 V +10 %
Rated current
575 V +10 %
Rated current
Q1
Q1
Iq max
Q1
Iq max
Type
Type
kA
A
Type
kA
A
Type of coordination 12)
3RW40 24
3RW40 26
3RW40 27
3RW40 28
12.5
25
32
38
3RV1 021-1KA10
3RV1 021-4DA10
3RV1 031-4EA10
3RV1 031-4FA10
3RV1 321-1KC10
3RV1 321-4DC10
3RV1 331-4EC10
3RV1 331-4FC10
55
55
55
55
16
25
32
40
-----
-----
-----
3RW40 36
3RW40 37
3RW40 38
45
63
72
3RV1 031-4GA10
3RV1 041-4JA10
3RV1 041-4KA10
3RV1 331-4GC10
3RV1 341-4JC10
3RV1 341-4KC10
20
20
20
45
63
75
----
----
----
3RW40 46
3RW40 47
80
106
3RV1 041-4LA10
3RV1 041-4MA10
3RV1 341-4LC10
3RV1 341-4MC10
11
11
90
100
---
---
---
3RW40 55
3RW40 56
134
162
3VL3 720-2DC36
3VL3 720-2DC36
35
35
200
200
3VL3 720-1DC36
3VL3 720-1DC36
12
12
200
200
3RW40 73
3RW40 74
3RW40 75
3RW40 76
230
280
356
432
3VL4 731-2DC36
3VL4 731-2DC36
3VL4 740-2DC36
3VL5 750-2DC36
65
65
65
65
315
315
400
500
3VL5 731-3DC36
3VL5 731-3DC36
3VL5 740-3DC36
3VL5 750-3DC36
35
35
35
35
315
315
400
500
6
1)
The rated motor current must be considered when selecting the devices.
2)
The types of coordination are explained in more detail in Catalog LV 1,
"Load Feeders, Motor Starters and Soft Starters"
––> "Fuseless Load Feeders".
Fused version (line protection only)
F1
Q21
M
3~
Soft starters
NSB0_01904
Q11
Line protection, maximum
Rated
current
Q11
Type
A
Line contactor
Rated current Size
F1
Type
(optional)
Q21
A
Type of coordination "1"1): Iq = 65 kA at 600 V +5 %
3RW40 24
3RW40 26
3RW40 27
3RW40 28
12.5
25
32
38
3NA3 820-6
3NA3 822-6
3NA3 824-6
3NA3 824-6
50
63
80
80
00
00
00
00
3RT10 24
3RT10 26
3RT10 34
3RT10 35
3RW40 36
3RW40 37
3RW40 38
45
63
72
3NA3 130-6
3NA3 132-6
3NA3 132-6
100
125
125
1
1
1
3RT10 36
3RT10 44
3RT10 45
3RW40 46
3RW40 47
80
106
3NA3 136-6
3NA3 136-6
160
160
1
1
3RT10 45
3RT10 46
3RW40 55
3RW40 56
134
162
3NA3 244-6
3NA3 244-6
250
250
2
2
3RT10 55-6A.36
3RT10 56-6A.36
3RW40 73
3RW40 74
3RW40 75
3RW40 76
230
280
356
432
2 x 3NA3 354-6
2 x 3NA3 354-6
2 x 3NA3 365-6
2 x 3NA3 365-6
2 x 355
2 x 355
2 x 500
2 x 500
3
3
3
3
3RT10 65-6A.36
3RT10 66-6A.36
3RT10 75-6A.36
3RT10 76-6A.36
1)
The types of coordination are explained in more detail in Catalog LV 1, "Load
Feeders, Motor Starters and Soft Starters" ––> "Fuseless Load Feeders".
6/46
Siemens LV 1 N · 04/2008
© Siemens AG 2008
3RW Soft Starters
3RW40
for standard applications
Fused version with 3NE1 SITOR fuses (semiconductor and line protection)
F’1
Q21
M
3~
Soft starters
All-range fuses
Rated current
Q11
Type
A
NSB0_01905
Q11
Line contactors
Rated current Size
F'1
Type
(optional)
Q21
A
Type of coordination 21): Iq = 65 kA at 600 V +5 %
3RW40 24
3RW40 26
3RW40 27
3RW40 28
12.5
25
32
38
3NE1 814-0
3NE1 803-0
3NE1 020-2
3NE1 020-2
20
35
80
80
000
000
00
00
3RT10 24
3RT10 26
3RT10 34
3RT10 35
3RW40 36
3RW40 37
3RW40 38
45
63
72
3NE1 020-2
3NE1 820-0
3NE1 820-0
80
80
80
00
000
000
3RT10 36
3RT10 44
3RT10 45
3RW40 46
3RW40 47
80
106
3NE1 021-0
3NE1 022-0
100
125
00
00
3RT10 45
3RT10 46
3RW40 55
3RW40 56
134
162
3NE1 227-2
3NE1 227-2
250
250
1
1
3RT10 55-6A.36
3RT10 56-6A.36
3RW40 73
3RW40 74
3RW40 75
3RW40 76
230
280
356
432
3NE1 331-2
3NE1 333-2
3NE1 334-2
3NE1 435-2
350
450
500
560
2
2
2
3
3RT10 65-6A.36
3RT10 66-6A.36
3RT10 75-6A.36
3RT10 76-6A.36
The types of coordination are explained in more detail in Catalog LV 1,
"Load Feeders, Motor Starters and Soft Starters"
––> "Fuseless Load Feeders".
The type of coordination "2" refers only to soft starters,
not to any components in the feeder.
6
1)
Siemens LV 1 N · 04/2008
6/47
© Siemens AG 2008
3RW Soft Starters
3RW40
for standard applications
Fused version with 3NE3 SITOR fuses (semiconductor protection by fuse, line and overload protection by motor starter protector;
alternatively, installation with contactor and overload relay possible)
F1
F3
Q21
Q1
F3
Q11
Soft starters
Q11
Type
M
3~
Semiconductor fuses, minimum
Rated
current
A
Rated current
F3
Type
NSB0_01906
M
3~
NSB0_01903
Q11
Semiconductor fuses, maximum
Size
A
Rated current
F3
Type
A
Semiconductor fuses, minimum
Size
Rated current
F3
Type
A
Size
Type of coordination 21): Iq = 65 kA at 600 V +5 %
3RW40 24
3RW40 26
3RW40 27
3RW40 28
12.5
25
32
38
-----
-----
-----
-3NE3 221
3NE3 224
3NE3 224
-100
160
160
-1
1
1
3NE4 101
3NE4 102
3NE4 118
3NE4 118
32
40
63
63
0
0
0
0
3RW40 36
3RW40 37
3RW40 38
45
63
72
--3NE3 221
--100
--1
3NE3 224
3NE3 225
3NE3 227
160
200
250
1
1
1
3NE4 120
3NE4 121
--
80
100
--
0
0
--
3RW40 46
3RW40 47
80
106
3NE3 222
3NE3 224
125
160
1
1
3NE3 225
3NE3 231
200
350
1
1
---
---
---
3RW40 55
3RW40 56
134
162
3NE3 227
3NE3 227
250
250
1
1
3NE3 335
3NE3 335
560
560
2
2
---
---
---
3RW40 73
3RW40 74
3RW40 75
3RW40 76
230
280
356
432
3NE3 232-0B
3NE3 233
3NE3 335
3NE3 337-8
400
450
560
710
1
1
2
2
3NE3 333
3NE3 336
3NE3 336
3NE3 340-8
450
630
630
900
2
2
2
2
-----
-----
-----
Soft starters
Q11
Type
Semiconductor fuses max.
Rated
current
A
Semiconductor fuses min.
Rated current Size
F3
Type
A
Semiconductor fuses max.
Rated current Size
F3
Type
A
25
50
63
80
Cylindrical fuses
Rated current Size
F3
Type
A
00
00
00
00
3NE8 017-1
3NE8 021-1
3NE8 022-1
3NE8 024-1
50
100
125
160
F3
Type
Rated
current
A
00
00
00
00
3NC2 240
3NC2 263
3NC2 280
3NC2 280
40
63
80
80
6
Type of coordination 21): Iq = 65 kA at 600 V +5 %
3RW40 24
3RW40 26
3RW40 27
3RW40 28
12.5
25
32
38
3NE4 117
3NE4 117
3NE4 118
3NE4 118
50
50
63
63
0
0
0
0
3NE8 015-1
3NE8 017-1
3NE8 018-1
3NE8 020-1
3RW40 36
3RW40 37
3RW40 38
45
63
72
3NE4 120
3NE4 121
--
80
100
--
0
0
--
3NE8 020-1 80
3NE8 021-1 100
3NE8 022-1 125
00
00
00
3NE8 024-1 160
3NE8 024-1 160
3NE8 024-1 160
00
00
00
3NC2 280 80
-----
3RW40 46
3RW40 47
80
106
---
---
---
3NE8 022-1 125
3NE8 024-1 160
00
00
3NE8 024-1 160
3NE8 024-1 160
00
00
---
---
3RW40 55
3RW40 56
134
162
---
---
---
---
---
---
---
---
---
---
---
3RW40 73
3RW40 74
3RW40 75
3RW40 76
230
280
356
432
-----
-----
-----
-----
-----
-----
-----
-----
-----
-----
-----
Soft starters
Rated
current
Q11
Type
Line contactors
Motor starter protectors/circuit breakers
(optional)
400 V +10 %
Rated current 575 V +10 %
Q21
Q1
Type
A
Q1
Type
A
F1
Type
A
A
Line protection, maximum
Rated current
Rated current Size
Type of coordination 21): Iq = 65 kA at 600 V +5 %
3RW40 24
3RW40 26
3RW40 27
3RW40 28
12.5
25
32
38
3RT10 24
3RT10 26
3RT10 34
3RT10 35
3RV1 031-4AA10
3RV1 031-4DA10
3RV1 031-4EA10
3RV1 031-4FA10
55
55
55
55
-----
-----
3NA3 820-6
3NA3 822-6
3NA3 824-6
3NA3 824-6
50
63
80
80
00
00
00
00
3RW40 36
3RW40 37
3RW40 38
45
63
72
3RT10 36
3RT10 44
3RT10 45
3RV1 031-4GA10
3RV1 041-4JA10
3RV1 041-4KA10
20
20
20
----
----
3NA3 130-6
3NA3 132-6
3NA3 132-6
100
125
125
1
1
1
3RW40 46
3RW40 47
80
106
3RT10 45
3RT10 46
3RV1 041-4LA10
3RV1 041-4MA10
11
11
---
---
3NA3 136-6
3NA3 136-6
160
160
1
1
3RW40 55
3RW40 56
134
162
3RT10 55-6A.36
3RT10 56-6A.36
3VL3 720-1DC36
3VL3 720-1DC36
200
200
3VL3 720-1DC36
3VL3 720-1DC36
200
200
3NA3 244-6
3NA3 244-6
250
250
2
2
3RW40 73
3RW40 74
3RW40 75
3RW40 76
230
280
356
432
3RT10 65-6A.36
3RT10 66-6A.36
3RT10 75-6A.36
3RT10 76-6A.36
3VL4 731-1DC36
3VL4 731-1DC36
3VL4 740-1DC36
3VL5 750-1DC36
315
315
400
500
3VL5 731-1DC36
3VL5 731-1DC36
3VL5 740-1DC36
3VL5 750-1DC36
315
315
400
500
2 x 3NA3 354-6
2 x 3NA3 354-6
2 x 3NA3 365-6
2 x 3NA3 365-6
2 x 355
2 x 355
2 x 500
2 x 500
3
3
3
3
1)
The types of coordination are explained in more detail in Catalog LV 1,
"Load Feeders, Motor Starters and Soft Starters" ––> "Fuseless Load Feed-
6/48
Siemens LV 1 N · 04/2008
ers". The type of coordination "2" refers only to soft starters, not to any components in the feeder.
© Siemens AG 2008
3RW Soft Starters
3RW40
for standard applications
■ Characteristic curves
Motor protection tripping characteristics for 3RW40
(with asymmetry)
2
6
4
NSB0_01705
103
[s]
4
NSB0_01488a
[s]
6
Tripping time
10
Tripping Time
Motor protection tripping characteristics for 3RW40
(with 3symmetry)
2
10 2
10 2
6
6
4
4
2
2
10 1
101
1
2
4
Class 10
Class 15
6
x e
Class 20
10
0,1
1,0
10
x
Class 10
Class 15
e
Class 20
Permissible installation height
NSB0_01704
105
95
6
Operational rated current I e in %
100
90
85
80
75
70
0
1000
2000
3000
4000
Mounting height in m
5000
At an installation height above 2000 m, the max. permissible operational
voltage is reduced to 460 V.
Siemens LV 1 N · 04/2008
6/49
© Siemens AG 2008
3RW Soft Starters
3RW40
for standard applications
■ More information
Application examples for normal starting (Class 10)
Normal starting Class 10 (up to 20 s with 350 % In motor),
The soft starter rating can be selected to be as high as the rating of the motor used.
Application
Conveyor belt
Roller conveyor
Compressor
Small fan
Pump
Hydraulic pump
%
s
70
10
5 x IM
60
10
5 x IM
50
10
4 x IM
40
10
4 x IM
40
10
4 x IM
40
10
4 x IM
s
5
5
0
0
10
0
Starting parameters
• Voltage ramp and current
limiting
- Starting voltage
- Starting time
- Current limit value
Ramp-down time
Application examples for heavy starting (Class 20)
Heavy starting Class 20 (up to 40 s with 350 % In motor),
The soft starter has to be selected at least one rating class higher than the motor used.
Application
Stirrer
Centrifuge
40
20
4 x IM
40
20
4 x IM
0
0
Starting parameters
• Voltage ramp and current
limiting
- Starting voltage
- Starting time
- Current limit value
Ramp-down time
%
s
6
Note:
These tables present sample set values and device sizes. They
are intended only for the purposes of information and are not
binding. The set values depend on the application in question
and must be optimized during start-up.
The soft starter dimensions should be checked where necessary
with the Win-Soft Starter software or with the help of Technical
Assistance.
6/50
Siemens LV 1 N · 04/2008
© Siemens AG 2008
3RW Soft Starters
3RW40
for standard applications
Configuration
Status graphs
US
tR on
tR off
t
tR on
tR off
t
ON 13/14
RUN 13/14
BYPASSED 23/24
I
xIe
Ie
tR on
t
Win-Soft Starter selection and simulation program
With this software, you can simulate and select all Siemens soft
starters, taking into account various parameters such as mains
properties, motor and load data, and special application
requirements.
The software is a valuable tool, which makes complicated,
lengthy manual calculations for determining the required soft
starters superfluous.
You can order the CD-ROM under the following order number:
Order No. E20001-D1020-P302-V2-7400.
You can find more information on the Internet at:
http://www.siemens.com/softstarter
6
Note:
When induction motors are switched on, voltage drops occur as
a rule on starters of all types (direct starters, wye-delta starters,
soft starters). The infeed transformer must always be dimensioned such that the voltage dip when starting the motor remains
within the permissible tolerance. If the infeed transformer is dimensioned with only a small margin, it is best for the control voltage to be supplied from a separate circuit (independently of the
main voltage) in order to avoid the potential switching off of the
soft starter.
U
UN
NSB0_01486
The 3RW solid-state soft starters are designed for easy starting
conditions. In the event of deviating conditions or increased
switching frequency, it may be necessary to choose a larger
device. For accurate dimensioning, use the Win-Soft Starter selection and simulation program.
Where long starting times are involved, the integrated solid-state
overload relay for heavy starting should not be disconnected.
PTC sensors are recommended. This also applies for the smooth
ramp-down because during the ramp-down time an additional
current loading applies in contrast to free ramp-down.
In the case of high switching frequencies in S4 mode, Siemens
recommends the use of PTC sensors. For corresponding device
versions with integrated thermistor motor protection or separate
thermistor evaluation devices see Catalog LV 1.
In the motor feeder between the SIRIUS 3RW soft starter and the
motor, no capacitive elements are permitted (e.g. no reactivepower compensation equipment). In addition, neither static
systems for reactive-power compensation nor dynamic PFC
(Power Factor Correction) must be operated in parallel during
starting and ramp-down of the soft starter. This is important to
prevent faults arising on the compensation equipment and/or the
soft starter.
All elements of the main circuit (such as fuses and controls)
should be dimensioned for direct starting, following the local
short-circuit conditions. Fuses, controls and overload relays
must be ordered separately. Please observe the maximum
switching frequencies specified in the technical specifications.
Power electronics schematic circuit diagram
L2
L3
T1
T2
T3
NSB0_001485a
L1
A bypass contact system and solid-state overload relay are
already integrated in the 3RW40 soft starter and therefore do not
have to be ordered separately.
Siemens LV 1 N · 04/2008
6/51
© Siemens AG 2008
3RW Soft Starters
Project planning aids
■ Dimensional drawings
3RW30 for standard applications
3RW30 1. ... 3RW30 4.
b
d
e
h
f
c
a
35
m
l
g
NSB0_01945
k
i
d
e
f
g
h
3RW30 1.-1.
3RW30 1.-2.
95
95
45
45
62
62
146
146
126
126
14.4
14.4
63
63
5
5
6.5
6.5
35
35
85
85
3RW30 2.-1.
3RW30 2.-2.
125
125
45
45
92
92
146
146
126
126
14.4
14.4
63
63
5
5
6.5
6.5
35
35
115
115
125
150
3RW30 3.
3RW30 4.
160
170
55
70
110
110
163
181
140
158
18
22.5
63
85
5
5
6.5
10
30
60
150
160
144
160
Distances to grounded parts (mm)
Lateral
Top
Bottom
Fixing screws
Tightening torques (Nm)
3RW30 1.
3RW30 2.
3RW30 3.
3RW30 4.
5
5
30
30
60
60
60
60
40
40
40
40
M4
M4
M4
M4
1
1
1
2
b
c
3RW30 03-1. (screw terminals)
i
k
l
m
95
117.2
3RW30 03-2. (spring-loaded terminals)
3,1
81,6
101,6
ca. 71
ca. 91
8 0
1 0 0
7 3 ,5
6 2
1 1 0
1 2 0
NSC00482
1 0 2
8 2
1)
1 )
5
1 5 2 )
2 2 ,5
5
2 8 ,5
2 6 ,2
1 2 0
N S C 0 _ 0 0 4 3 9 e
6
Type/Dimension (mm) a
1)
For mounting onto standard mounting rail TH 35 according to EN 60715.
2)
Dimension for screw fixing.
Screw fixing with two 3RP1 903 push-in lugs per 3RW30 03 device.
6/52
Siemens LV 1 N · 04/2008
7,2
22,5
5
120
© Siemens AG 2008
3RW Soft Starters
Project planning aids
3RW40 for standard applications
b
d
e
h
f
m
c
a
35
l
g
NSB0_01891a
k
i
Type/Dimension (mm) a
d
e
f
g
h
i
k
l
m
3RW40 2.-1.
3RW40 2.-2.
125
125
b
45
45
c
92
92
149
149
126
126
14.4
14.4
63
63
5
5
6.5
6.5
35
35
115
115
125
150
3RW40 3.
170
55
110
165
140
18
63
5
6.5
30
150
144
3RW40 4.
170
70
110
183
158
22.5
85
5
10
60
160
160
Lateral
Top
Bottom
Fixing screws
Tightening torques (Nm)
3RW40 2.
5
60
40
M4
1
3RW40 3.
30
60
40
M4
1
3RW40 4.
30
60
40
M4
2
6
Distances to grounded parts (mm)
b
h
f
g
n
d
i
e
a
o
k
l
c
N S B 0 _ 0 1 4 8 0
q
m
p
Type/Dimension (mm) a
b
c
d
e
f
g
h
i
k
l
m
n
o
p
q
3RW40 5.
180
120
37
17
167
100
223
250
180
148
6.5
153
7
198
9
M6, 10 Nm
3RW40 7.
210
160
48
25
190
140
240
278
205
166
10
166
9
230
11
M8, 15 Nm
Siemens LV 1 N · 04/2008
6/53
© Siemens AG 2008
3RW Soft Starters
Project planning aids
■ Schematics
3RW30 . . connection examples for control circuit
Control using switches
Automatic mode
N(L-) L1 (L +)
N(L-) L1(L+)
ON/OFF
1
A2
NSB0_01914
A2 A1
1)
Q11
A1
1
NSB0_01895
ON/OFF
1)
Q11
NSB0_01916a
Us
ON
>5 min
OFF
Control by pushbutton
t
Control of a main contactor
N(L-) L(L+)
Q21
OFF
N(L-) L1(L+)
ON
ON/ 1)
OFF
A2 A1 1 13 NO 14
A2 A1
1
13 NO 14
ON
3RW30 connection examples for main circuit2)
3RW30 – 3-phase motor with 3NA/3NE fuse
F1
3NA/3NE
Q21
3RT
Q11
3RW30
3RV
Q11
3RW30
M
3~
NSB0_01944
NSB0_01943
M
3~
3RV motor starter protectors
1)
Note: Risk of starting!
When operating with a switch (ON/OFF) a new, automatic restart will take
place automatically if the start command is still active at terminal 1.
2)
As an alternative, the motor feeder can also be installed as a fuseless or as
a fused version. For fuse and switching device coordination,
see "Technical specifications".
The wiring diagrams are provided only as examples.
6/54
Siemens LV 1 N · 04/2008
NSB0_01997
Q11
NSB0_01942
6
Q11
ON
© Siemens AG 2008
3RW Soft Starters
Project planning aids
Connection examples of 3RW40 2. ... 3RW40 4. for control circuit
Control using switches
Automatic mode
Control by remote reset
N(L-) L1 (L +)
N(L-) L1(L+)
N(L-) L1 (L +)
ON/OFF
ON/OFF
Q11
A1
1
Q11
A2 A1
Q11
1
Us
NSB0_01916a
Us
ON
>5 min
OFF
NSB0_01915
A2
1)
NSB0_01892
1
1)
NSB0_01914
A2 A1
RESET
NSB0_01895
ON/OFF
1)
100 %
>1,5 s
t
Control of 3RW40 2. ... 3RW40 4. by pushbutton
t
Control of a main contactor
N(L-) L(L+)
Q21
OFF
N(L-) L1(L+)
ON
1)
ON/
OFF
1 13 NO 14 24 NO 23
95
96 NC NO 98
A2 A1
1
13 NO 14 24 NO 23 95
ON
96 NC NO 98
RUN
OVERLOAD
FAILURE
6
Q11
NSB0 02007
OVERLOAD
FAILURE
Q11
NSB0_02008
A2 A1
Connection example of 3RW40 2. ... 3RW40 4. for PTC sensors
(thermistor motor protection)
Thermoclick
PTC type A
T12 T22
ϑ
1)
T11/T21
T12 T22
NSB0_01894
T11/T21
Q11
NSB0_01893
Q11
ϑ
Note: Risk of starting!
When operating with a switch (ON/OFF) a new, automatic restart will take
place automatically if the start command is still active at terminal 1.
Siemens LV 1 N · 04/2008
6/55
© Siemens AG 2008
3RW Soft Starters
Project planning aids
Connection examples of 3RW40 5. and 3RW40 7.
for control circuit
3RW40 connection examples for main circuit3)
Control by switch using
internal 24 V DC supply
3RW40 – 3-phase motor with
3NA/3NE fuse
External power supply
3RV/3VL motor starter
protectors/circuit breakers
O N /O F F 1 )
A 2
1
2
3
A 1
A 2
1
2
2 )
1 )
Control by pushbutton
ON
N
OFF
A2
1
2
3 13 NO
14 24
NO 23
95
ON
96 NC NO 98
OVERLOAD
FAILURE
Q11
NSB0_01483b
A1
6
2)
Control of a main contactor
Q21
N
A1
A2
ON/OFF 1)
1
2
3
13 NO
14 24
NO 23
RUN
Q11
95
96 NC NO 98
OVERLOAD
FAILURE
NSB0_01484b
L1
2)
1)
Note: Risk of starting!
When operating with a switch (ON/OFF) a new, automatic restart will take
place automatically if the start command is still active at terminal 3.
2)
Grounding necessary for fan connection to 3RW40 5...
3)
As an alternative, the motor feeder can also be installed as a fuseless or as
a fused version. For fuse and switching device coordination,
see "Technical specifications".
The wiring diagrams are provided only as examples.
6/56
Siemens LV 1 N · 04/2008
3NA/3NE
Q21
3RT
Q11
3RW40
M
3~
2 )
L1
F1
3RV/3VL
3
Q 1 1
N S B 0 _ 0 1 4 8 1 a
Q 1 1
O N /O F F
N
Q11
3RW40
M
3~
NSB0_01487c
L 1
NSB0_01489b
A 1
N
N S B 0 _ 0 1 4 8 2 a
L 1
© Siemens AG 2008
Engineering Software Planning and Configuration with SIRIUS
Introduction
■ Application
12
■ Overview
SIRIUS ES engineering software (E-SW)
The programs of the SIRIUS ES software family enable:
• Clear and easily manageable setting of device functions and
their parameters – online and offline
• Efficient diagnostics functions and display of all key measured
values
• Time saving through shorter start-up times
The SIRIUS ES programs such as Motor Starter ES, Soft Starter
ES and SIMOCODE ES are available in three versions which
differ in user-friendliness, scope of functions and price (for details see the descriptions of the individual products).
SIRIUS ES
Local interface on the device
(system interface)
Basic functions for configuring
the devices
Basic
✔
Standard
✔
Premium
✔
• Parameterizing
✔
✔
✔
✔
✔
✔
✔
✔
✔
✔
✔
✔
• Parameterizing with the
integrated graphics editor1)
--
✔
✔
• Creating typicals
----
✔
✔
--
✔
✔
✔
-----
-----
✔
✔
✔
✔
• Operating
• Diagnostics
• Test
Standard functionality
• Exporting parameters
PROFIBUS interface
Complete functionality
• Group function
• S7 routing
• Teleservice via MPI
• STEP7 Object Manager
1)
Depending on SIRIUS ES program.
12/2
Siemens LV 1 N · 04/2008
In addition to device-specific parameterization, the programs of
the SIRIUS ES software family also provide the following functionality in a uniform look and feel. These functions are available
in many SIRIUS ES programs.
• Standard-conform printouts:
The programs of the SIRIUS ES software family make machine
documentation far easier. Parameterization printouts according to EN ISO 7200 are possible. The elements to be printed
are easy to select and compile as required.
• Easy creating of typicals:
Typicals can be created for devices and applications with parameters which differ only slightly. These typicals contain all
the parameters needed for the parameterization. In addition it
is possible to specify which of these parameters are fixed default values and which can still be adapted by the start-up engineer.
• Group function:
For the user-friendly parameterization of numerous devices or
applications of the same type, the programs of the SIRIUS ES
software family provide a group function which enables the
parameterization of several devices to be read out or written
through PROFIBUS. In conjunction with typicals it is even possible to selectively adapt the parameters in any number of parameterizations.
• Teleservice via MPI:
The premium versions of the SIRIUS ES software family support the use of MPI Teleservice (consisting of the Teleservice
software and various Teleservice adapters) for remote diagnostics of the devices. This facilitates diagnostics and maintenance and shortens the response time for service purposes.
© Siemens AG 2008
Engineering Software Planning and Configuration with SIRIUS
Introduction
The programs of the SIRIUS ES software family are available as
follows:
• Floating license – the license for any one user at any one time
- Authorizes any one user
- Independent of the number of installations (unlike the single
license which is allowed to be installed once only)
- Only the actual use of the program has to be licensed
- Trial license (free use of all program functions for 14 days for
test and evaluation purposes, included on every product
CD, available in the download file of the SIRIUS ES program
in the Service&Support portal).
Following delivery versions are available in addition for the
programs of the SIRIUS ES software family:
• Upgrade
Upgrade from an old to a new version with expanded
functions, e.g. upgrade from Motor Starter ES 2006 to
Motor Starter ES 2007
• Powerpack
Special pack for switching within the same software version to
a more powerful version with more functionality,
e.g. Powerpack Motor Starter ES 2007 for switching from
Standard to Premium
• Software Update Service
To keep you up to date at all times we offer a special service
which supplies you automatically with all service packs and
upgrades
• License download
User-friendly license key download from the A&D Mall
(currently only for customers from Germany) as an easy and
quick way for you to receive additional licenses for your
software
Efficient engineering and commissioning with graphic interfaces and
diagnostics options
Siemens LV 1 N · 04/2008
12/3
12
Types of delivery and license
© Siemens AG 2008
Engineering Software Planning and Configuration with SIRIUS
Soft Starter ES
■ Overview
12
Efficient engineering with new program versions
The Soft Starter ES software program is available in three versions which differ in user-friendliness, scope of functions and
price.
Easy and clearly arranged parameter setting of the 3RW44 soft starter
with Soft Starter ES 2007
Soft Starter ES
Access through local interface
on the device
Parameterizing
Operating
Diagnostics
Creating typicals
Exporting parameters
Comparative functions
Standard-conform printout
according to EN ISO 7200
Service data (slave pointer, statistics data)
Access through PROFIBUS
Group function
Teleservice via MPI
S7 routing
STEP7 Object Manager
1)
Graphic presentation of measured values with the trace function
(oscilloscope function) of Soft Starter ES 2007 Standard and Premium
Soft Starter ES 2007
Soft Starter ES software enables the quick and easy parameterization, monitoring and service-related diagnostics of SIRIUS
3RW44 High Feature soft starters . The device parameters can
be set directly on the PC and transferred through a serial cable
or optional PROFIBUS connection to the soft starter.
The advantages of Soft Starter ES:
• Clear and easily manageable setting of device functions and
their parameters – online and offline
• Effective diagnostics function of the soft starter and display of
all key measured values
• Trace function (oscilloscope function) for recording measured
values and events (in the Soft Starter ES Standard and Premium software versions)
12/4
Siemens LV 1 N · 04/2008
Basic
✔
Standard
✔
Premium
✔
✔
✔
✔
✔
✔
✔
✔
✔
✔
-----
✔1)
✔
✔
✔
✔
✔
✔
✔
--
✔
✔
------
------
✔
✔
✔
✔
✔
Typicals with Service Pack 1 and higher.
More functions
• Standard-conform printouts
The software tool makes machine documentation far easier.
Parameterization printouts according to EN ISO 7200 are possible. The elements to be printed are easy to select and compile as required.
• Easy creating of typicals
Typicals can be created for devices and applications with parameters which differ only slightly. These typicals contain all
the parameters needed for the parameterization. In addition it
is possible to specify which of these parameters are fixed default values and which can still be adapted by the start-up engineer.
• Group function
For the user-friendly parameterization of numerous devices or
applications of the same type, the programs of the SIRIUS ES
software family provide a group function which enables the
parameterization of several devices to be read out or written
through PROFIBUS. In conjunction with typicals it is even possible to selectively adapt the parameters in any number of parameterizations.
• Teleservice via MPI
The Soft Starter ES premium version supports the use of MPI
Teleservice (consisting of the Teleservice software and various
Teleservice adapters) for remote diagnostics of the devices.
This facilitates diagnostics and maintenance and shortens the
response time for service purposes.
© Siemens AG 2008
Engineering Software Planning and Configuration with SIRIUS
Types of delivery and license
• Powerpack
Special pack for switching within the same software version to
a more powerful version with more functionality, e.g.
Powerpack Soft Starter ES 2007 for switching from Standard
to Premium
• Software Update Service
To keep you up to date at all times we offer a special service
which supplies you automatically with all service packs and
upgrades
• License download
User-friendly license key download from the A&D Mall
(currently only for customers from Germany) as an easy
and quick way for you to receive additional licenses for your
software
Soft Starter ES is available as follows:
• Floating license – the license for any one user at any one time
- Authorizes any one user
- Independent of the number of installations (unlike the single
license which is allowed to be installed once only)
- Only the actual use of the program has to be licensed
- Trial license (free use of all program functions for 14 days for
test and evaluation purposes, included on every product
CD, available in the download file of the SIRIUS ES program
in the Service&Support portal).
Following delivery versions are available in addition for
Soft Starter ES 2007:
• Upgrade
Upgrade from an old to a new version with expanded functions, e.g. upgrade from Soft Starter ES 2006 to
Soft Starter ES 2007
New licensing procedure
To make licensing easier, the three versions of Soft Starter ES are
available with immediate effect with the following license:
14 day trial license for Premium functions:
for test and evaluation purposes, included on every product CD,
available also in the download file of the
SIRIUS Soft Starter ES 2007 program in the Service&Support
portal.
System requirements
Soft Starter ES 2007 parameterization, start-up and diagnostics
software for the SIRIUS 3RW44 soft starter
Basic/Standard
Premium
Firmware version ≥ *EO4* 1)
Firmware version ≥ *EO6* 2)
Operating system
Windows 2000 (Service Pack 3 or 4), Windows XP Professional (Service Pack 2)
Processor
≥ Pentium 800 MHz / 1 GHz (Windows VISTA)
Free space on hard disk
≥ 150 MB
CD-ROM/DVD drive
Yes (only when installing from CD)
Serial interface (COM)
Yes
PC cable/parameterizing cable/connection cable
Yes
PROFIBUS communication module (optional)
--
1)
SIRIUS 3RW44 with firmware version ≥ *E04*. Installed in starters
delivered after December 2005.
2)
SIRIUS 3RW44 with firmware version ≥ *E06*. Installed in starters delivered
after May 2006.
Yes
■ Selection and ordering data
Parameterization and service software for SIRIUS 3RW44
soft starters
• Runs on WIN 2000/WIN XP PROF
• Without PC cable
Version
DT
Order No.
Price
per PU
PE
(UNIT,
SET,
M)
PS*
PG
Weight
per PU
approx.
kg
Soft Starter ES 2007 Basic
Floating license for one user
E-SW, software and documentation on CD,
3 languages (German/English/French),
communication through system interface
• License key on USB stick, Class A, including CD
B
3ZS1 313-4CC10-0YA5
1
1 unit
131
0.230
• License key download, Class A, no CD
}
3ZS1 313-4CE10-0YB5
1
1 unit
131
0.230
• License key on USB stick, Class A, including CD
B
3ZS1 313-5CC10-0YA5
1
1 unit
131
0.230
• License key download, Class A, no CD
}
3ZS1 313-5CE10-0YB5
1
1 unit
131
0.230
Soft Starter ES 2007 Standard
Floating license for one user
E-SW, software and documentation on CD,
3 languages (German/English/French),
communication through system interface
You can order this quantity or a multiple thereof.
Siemens LV 1 N · 04/2008
12/5
12
Soft Starter ES
© Siemens AG 2008
Engineering Software Planning and Configuration with SIRIUS
Soft Starter ES
DT
Order No.
Price
per PU
Upgrade for Soft Starter ES 2006
Floating license for one user,
E-SW, software and documentation on CD,
License key on USB stick, Class A,
3 languages (German/English/French),
communication through system interface
B
3ZS1 313-5CC10-0YE5
1
1 unit
131
0.230
Powerpack for Soft Starter ES 2007 Basic
Floating license for one user,
E-SW, software and documentation on CD,
License key on USB stick, Class A,
3 languages (German/English/French),
communication through system interface
B
3ZS1 313-5CC10-0YD5
1
1 unit
131
0.230
Software Update Service
For 1 year with automatic extension,
assuming the current software version is in use,
E-SW, software and documentation on CD,
communication through system interface
}
3ZS1 313-5CC10-0YL5
1
1 unit
131
0.230
12
Version
PE
(UNIT,
SET,
M)
PS*
PG
Weight
per PU
approx.
kg
Soft Starter ES 2007 Premium
Floating license for one user
E-SW, software and documentation on CD,
3 languages (German/English/French),
communication through system interface
• License key on USB stick, Class A, including CD
B
3ZS1 313-6CC10-0YA5
1
1 unit
131
0.230
• License key download, Class A, no CD
}
3ZS1 313-6CE10-0YB5
1
1 unit
131
0.230
Upgrade for Soft Starter ES 2006
Floating license for one user,
E-SW, software and documentation on CD,
License key on USB stick, Class A,
3 languages (German/English/French),
communication through system interface
B
3ZS1 313-6CC10-0YE5
1
1 unit
131
0.230
Powerpack for Soft Starter ES 2007 Standard
Floating license for one user,
E-SW, software and documentation on CD,
License key on USB stick, Class A,
3 languages (German/English/French),
communication through system interface
}
3ZS1 313-6CC10-0YD5
1
1 unit
131
0.230
Software Update Service
For 1 year with automatic extension,
assuming the current software version is in use,
E-SW, software and documentation on CD,
communication through system interface
}
3ZS1 313-6CC10-0YL5
1
1 unit
131
0.230
PC cables for PC/PG communication,
through the system interface on the device,
for connecting to the serial interface on the PC/PG
B
3UF7940-0AA00-0
1
1 unit
131
0.150
Optional PROFIBUS communication modules for
SIRIUS 3RW44
A
3RW4 900-0KC00
1
1 unit
131
0.320
Accessories
You can order this quantity or a multiple thereof.
12/6
Siemens LV 1 N · 04/2008
© Siemens AG 2008
Engineering Software Planning and Configuration with SIRIUS
Motor Starter ES
More functions
• Standard-conform printouts
The software tool makes machine documentation far easier.
Parameterization printouts according to EN ISO 7200 are
possible. The elements to be printed are easy to select and
compile as required
• Easy creating of typicals
Typicals can be created for devices and applications with parameters which differ only slightly. These typicals contain all
the parameters needed for the parameterization. In addition it
is possible to specify which of these parameters are fixed default values and which can still be adapted by the start-up engineer
• Teleservice via MPI
The Motor Starter ES Premium version supports the use of MPI
Teleservice (consisting of the Teleservice software and various
Teleservice adapters) for remote diagnostics of the devices.
This facilitates diagnostics and maintenance and shortens the
response time for service purposes.
Motor Starter ES for parameterization, monitoring, diagnostics and
testing of motor starters
Motor Starter ES is used for start-up, parameterization, diagnostics, documentation and the preventative maintenance of the
High-Feature motor starters of the SIMATIC ET 200S, ET 200pro
and ECOFAST product families.
Interfacing is performed
• either through the local interface on the device (applicable to
ET 200S/ET 200pro/ECOFAST) or
• with PROFIBUS DP V1 capable motor starters from any point
in PROFIBUS (applies for ET 200pro/ECOFAST).
Using Motor Starter ES, the communication-capable motor starters are easily parameterized during start-up, monitored during
normal operation and successfully diagnosed for service purposes. Preventative maintenance is supported by a function for
reading out diverse statistical data (e.g. operating hours, operating cycles, cut-off currents, etc.). The user is supported during
these procedures with comprehensive Help functions and plain
text displays.
Motor Starter ES can either be used as a stand-alone program
or it can be integrated into STEP 7 V5.1 SP3 upwards using an
object manager.
Motor Starter ES
Access through local interface
on the device
Parameterizing
Operating
Diagnostics
Creating typicals
Comparative functions
Standard-conform printout
according to EN ISO 7200
Service data (slave pointer, statistics data)
Access through PROFIBUS
S7 routing
Teleservice via MPI
STEP7 Object Manager
1)
Basic
✔
Standard
✔
Premium
✔
✔
✔
--
✔
✔
✔
✔
✔
✔
----
✔1)
✔
✔
✔
✔
✔
--
✔
✔
-----
-----
✔
✔
✔
✔
Types of delivery and license
Motor Starter ES is available as follows:
• Floating license – the license for any one user at any one time
- Authorizes any one user
- Independent of the number of installations (unlike the single
license which is allowed to be installed once only)
- Only the actual use of the program has to be licensed
- Trial license (free use of all program functions for 14 days for
test and evaluation purposes, included on every product
CD, available in the download file of the SIRIUS ES program
in the Service&Support portal).
Following delivery versions are available in addition for
Motor Starter ES 2007:
• Upgrade
Upgrade from an old to a new version with expanded
functions, e.g. upgrade from Motor Starter ES 2006 to
Motor Starter ES 2007
• Powerpack
Special pack for switching within the same software version to
a more powerful version with more functionality, e.g.
Powerpack Motor Starter ES 2007 for switching from
Standard to Premium
• Software Update Service
To keep you up to date at all times we offer a special service
which supplies you automatically with all service packs and
upgrades
• License download
User-friendly license key download from the A&D Mall
(currently only for customers from Germany) as an easy
and quick way for you to receive additional licenses for your
software
Typicals with Service Pack 1 and higher.
Siemens LV 1 N · 04/2008
12/7
12
■ Overview
© Siemens AG 2008
Engineering Software Planning and Configuration with SIRIUS
Motor Starter ES
12
System requirements
Motor Starter ES 2007 parameterization, start-up and diagnostics
software for ECOFAST motor starters, SIMATIC ET 200S High-Feature
starters and SIMATIC ET 200pro starters
Operating system
Windows 2000 (Service Pack 3 or 4), Windows XP Professional
(Service Pack 2)
Processor
≥ Pentium 800 MHz / 1 GHz (Windows VISTA)
≥ 1024 x 768
Monitor resolution
Free space on hard
≥ 400 MB
disk1)
CD-ROM/DVD drive
Yes (only when installing from CD)
Serial interface (COM)
Yes
PC cable/parameterizing cable/connection cable
Yes
PROFIBUS card/PROFIBUS processor
Optional, with parameterization and diagnostics through PROFIBUS
1)
Allow for additional free space, e.g. for swap-out files.
■ Selection and ordering data
Parameterization and service software for SIRIUS motor starters
ES, ECOFAST motor starters,
SIMATIC ET 200S High Feature starters and
SIMATIC ET 200pro starters
• Runs on WIN 2000/WIN XP PROF
• Without PC cable
Version
DT
Order No.
Price
per PU
PE
(UNIT,
SET,
M)
PS*
PG
Weight
per PU
approx.
kg
Motor Starter ES 2007 Basic
Floating license for one user
E-SW, software and documentation on CD,
3 languages (German/English/French),
communication through system interface
• License key on USB stick, Class A, including CD
B
3ZS1 310-4CC10-0YA5
1
1 unit
121
0.230
• License key download, Class A, no CD
B
3ZS1 310-4CE10-0YB5
1
1 unit
121
0.230
Motor Starter ES 2007 Standard
Floating license for one user
E-SW, software and documentation on CD,
3 languages (German/English/French),
communication through system interface
• License key on USB stick, Class A, including CD
B
3ZS1 310-5CC10-0YA5
1
1 unit
121
0.230
• License key download, Class A, no CD
B
3ZS1 310-5CE10-0YB5
1
1 unit
121
0.230
Upgrade for Motor Starter ES 2006
Floating license for one user,
E-SW, software and documentation on CD,
License key on USB stick, Class A,
3 languages (German/English/French),
communication through system interface
B
3ZS1 310-5CC10-0YE5
1
1 unit
121
0.230
Powerpack for Motor Starter ES 2007 Basic
Floating license for one user,
E-SW, software and documentation on CD,
License key on USB stick, Class A,
3 languages (German/English/French),
communication through system interface
B
3ZS1 310-5CC10-0YD5
1
1 unit
121
0.230
Software Update Service
For 1 year with automatic extension,
assuming the current software version is in use,
E-SW, software and documentation on CD,
communication through system interface
B
3ZS1 310-5CC10-0YL5
1
1 unit
121
0.230
You can order this quantity or a multiple thereof.
12/8
Siemens LV 1 N · 04/2008
© Siemens AG 2008
Engineering Software Planning and Configuration with SIRIUS
Version
DT
Order No.
Price
per PU
PU
(UNIT,
SET,
M)
PS*
PG
Weight
per PU
approx.
kg
Motor Starter ES 2007 Premium
Floating license for one user
E-SW, software and documentation on CD,
3 languages (German/English/French),
communication through system interface
• License key on USB stick, Class A, including CD
B
3ZS1 310-6CC10-0YA5
1
1 unit
121
0.230
• License key download, Class A, no CD
B
3ZS1 310-6CE10-0YB5
1
1 unit
121
0.230
Upgrade for Motor Starter ES 2006
Floating license for one user,
E-SW, software and documentation on CD,
License key on USB stick, Class A,
3 languages (German/English/French),
communication through system interface
B
3ZS1 310-6CC10-0YE5
1
1 unit
121
0.230
Powerpack for Motor Starter ES 2007 Standard
Floating license for one user,
E-SW, software and documentation on CD,
License key on USB stick, Class A,
3 languages (German/English/French),
communication through system interface
B
3ZS1 310-6CC10-0YD5
1
1 unit
121
0.230
Software Update Service
For 1 year with automatic extension,
assuming the current software version is in use,
E-SW, software and documentation on CD,
communication through system interface
B
3ZS1 310-6CC10-0YL5
1
1 unit
121
0.230
• 2DI 24 V DC COM control modules, for
ET 200S High-Feature starters, failsafe starters A
A
3RK1 903-0CH10
1
1 unit
121
0.025
• LOGO! PC cables
A
6ED1 057-1AA00-0BA0
1
1 unit
200
0.176
B
3RK1 922-2BP00
1
1 unit
121
0.330
B
3RK1 911-0BN20
1
1 unit
121
0.162
Siemens LV 1 N · 04/2008
12/9
Accessories
For ET 200S High Feature motor starters
For ET 200pro motor starters
• RS232 interface cables, serial data connection between ET 200pro MS/FC and laptop/PC/PG or MS
For ECOFAST High Feature motor starters
(interface cable)
• PC cables
You can order this quantity or a multiple thereof.
12
Motor Starter ES
© Siemens AG 2008
Appendix
Conditions of sale and delivery
Export regulations
■ Terms and conditions of sale and delivery
By using this catalog you can acquire hardware and software
products described therein from Siemens AG subject to the following terms. Please note! The scope, the quality and the conditions for supplies and services, including software products, by
any Siemens entity having a registered office outside of Germany, shall be subject exclusively to the General Terms and
Conditions of the respective Siemens entity. The following terms
apply exclusively for orders placed with Siemens AG.
For customers with a seat or registered office in Germany
The “General Terms of Payment” as well as the “General Conditions for the Supply of Products and Services of the Electrical
and Electronics Industry” shall apply.
For software products, the “General License Conditions for Software Products for Automation and Drives for Customers with a
Seat or registered Office in Germany” shall apply.
For customers with a seat or registered office outside of
Germany
The “General Terms of Payment” as well as the “General Conditions for Supplies of Siemens, Automation and Drives for Customers with a Seat or registered Office outside of Germany” shall
apply.
For software products, the “General License Conditions for Software Products for Automation and Drives for Customers with a
Seat or registered Office outside of Germany” shall apply.
General
The dimensions are in mm. In Germany, according to the German law on units in measuring technology, data in inches only
apply to devices for export.
Illustrations are not binding.
Insofar as there are no remarks on the corresponding pages,
- especially with regard to data, dimensions and weights given these are subject to change without prior notice.
The prices are in € (Euro) ex works, exclusive packaging.
The sales tax (value added tax) is not included in the prices.
It shall be debited separately at the respective rate according to
the applicable legal regulations.
Prices are subject to change without prior notice. We will debit
the prices valid at the time of delivery.
Surcharges will be added to the prices of products that contain
silver, copper, aluminum, lead and/or gold if the respective basic
official prices for these metals are exceeded. These surcharges
will be determined based on the official price and the metal factor of the respective product.
The surcharge will be calculated on the basis of the official price
on the day prior to receipt of the order or prior to the release
order.
The metal factor determines the official price as of which the
metal surcharges are charged and the calculation method used.
The metal factor, provided it is relevant, is included with the price
information of the respective products.
An exact explanation of the metal factor and the text of the
Comprehensive Terms and Conditions of Sale and Delivery are
available free of charge from your local Siemens business office
under the following Order Nos.:
• 6ZB5310-0KR30-0BA1
(for customers based in Germany)
• 6ZB5310-0KS53-0BA1
(for customers based outside Germany)
or download them from the Internet
http://www.siemens.com/automation/mall
(Germany: A&D Mall Online-Help System)
■ Export regulations
The products listed in this catalog / price list may be subject to
European / German and/or US export regulations.
Therefore, any export requiring a license is subject to approval
by the competent authorities.
According to current provisions, the following export regulations
must be observed with respect to the products featured in this
catalog / price list:
AL
Number of the German Export List
Products marked other than “N” require an export
license.
In the case of software products, the export designations of the relevant data medium must also
be generally adhered to.
Goods labeled with an “AL“ not equal to “N” are
subject to a European or German export authorization when being exported out of the EU.
ECCN
Export Control Classification Number
Products marked other than “N” are subject to a
reexport license to specific countries.
In the case of software products, the export
designations of the relevant data medium must
also be generally adhered to.
Goods labeled with an “ECCN“ not equal to “N”
are subject to a US re-export authorization.
Even without a label or with an “AL: N” or “ECCN: N”, authorization may be required due to the final destination and purpose for
which the goods are to be used.
The deciding factors are the AL or ECCN export authorization
indicated on order confirmations, delivery notes and invoices.
Errors excepted and subject to change without prior notice.
A&D/VuL_ohne MZ/En 05.09.06
© Siemens AG 2008
Get more information
Low-Voltage Controls and Distribution
www.siemens.com/lowvoltage
Siemens AG
Industry Sector
Postfach 48 48
90026 NÜRNBERG
GERMANY
www.siemens.com/automation
Subject to change without prior notice
PDF only: (E86060-K1002-A141-A3-7600)
KG 0408 194 En / 803029
© Siemens AG 2008
The information provided in this catalog contains descriptions or
characteristics of performance which in case of actual use do not
always apply as described or which may change as a result of further
development of the products. An obligation to provide the respective
characteristics shall only exist if expressly agreed in the terms of
contract. Availability and technical specifications are subject to
change without notice.