Break up of PLCC items for execution

advertisement
Sr.No
.
Particulars of Item
Erection
Total Qty. (Laying/Installation,
to be
testing
supplied
&commissioning)
Qty.
Supply Qty.
Unit
220KV
ATUL S/s
400KV
NAVSARI
(PGCIL) S/s
1
220kV ,4400PF CVT (having two windings with VA
burden 50 & 50 and having accuracy of 0.2 & 3P class for
metering and protection core respectively & simultaneous
burden 100VA. Also with clamp/connectors & supporting
structure. The interconnection from HF terminal of CVT to
PLCC coupling device shall be made using 16 Sq.mm
PVC insulated stranded (non flexible strands) copper
cable.
No.
6
2
8
8
2
220kV, 0.5mH, 1250Amp Wave Trap with Blocking Band
of, Band-(I)-100-160 & Band-(II) 150-500KHz and R min
= 570 Ohm and single point suspension arrangement with
three tie rod assembly including insulator string assembly,
clamp/connectors and require accessories.
No.
6
2
8
8
3
Modular coupling device MCD-80, Make: ABB (Set
comprising of 1 No. of A9BS & 1 No. of A9BT) for Phase
to Phase coupling arrangement for PLCC signal
connectivity.
Set
3
1
4
4
4a. 40 Watt fully programmable carrier terminal of Make:
ABB with dual 19" rack of ETL-41 system.
No.
2
1
3
4b. 40 Watt fully programmable carrier terminal of Make:
ABB with single 19" rack of ETL-41 system .
No.
4
0
4
4
Sr.No
.
Particulars of Item
Erection
Total Qty. (Laying/Installation,
to be
testing
supplied
&commissioning)
Qty.
Supply Qty.
Unit
220KV
ATUL S/s
400KV
NAVSARI
(PGCIL) S/s
5
Protection coupler Make: ABB & Type: NSD-50 with 2
coded & 2 uncoded command arrangement & perfectly
match with above carrier terminal description of which
given at Sr. No. 4a. & 4b. above.
No.
4
2
6
6
6
FSK Data Modem Make: ABB & Type: NSK 5,
Programmable for both Baud Rate (50 to 2400 Baud) and
VFT Channel Centre Frequency and fully compatible with
40W fully programmable Carrier terminal Type :ETL-41,
Make: ABB .
No.
1
0
1
Nil
7
FSK Data Modem with stand alone 19" rack with power
supply module ,Make: ABB & Type: NSK 5,
Programmable for both Baud Rate (50 to 2400 Baud) and
VFT Channel Centre Frequency and fully compatible with
40W fully programmable Carrier terminal Type :ETL-41,
Make: ABB .
No.
1
0
1
1
8
50 Volt, 350AH capacity, storage Low Maintenance ,
High performance Lead acid Battery set with accessories
& FRP stand
set (25
cells/set)
1
0
1
1
9
SCADA Compatible Float & boost charger suitable for
50Volt, 350AH capacity battery with float 0/p volt : 50 to
58 volt, 40 Amp, Boost 0/p : 50 to 72V, 35 Amp with
Variac & Servo Motor mechanism for Auto Operation for
DC O/P Voltage Adjustment of Float Charger as per
technical specification.
No.
1
0
1
1
10
DCDB with 10 Nos. of Feeders (6 Amp each) for DC
supply to PLCC panels & Exchange as per technical
Specification.
No.
1
0
1
1
Sr.No
.
11
Particulars of Item
laying of 75 Ohm, unbalanced armoured co-axial cable for
PLCC signal connectivity and providing UHF gland on
both the ends of each main cable length to be laid for
PLCC carrier room to bay gentry and loop cable for Ph to
Ph coupling arrangement.
Unit
KM
Supply Qty.
220KV
ATUL S/s
400KV
NAVSARI
(PGCIL) S/s
1.65
0.55
Erection
Total Qty. (Laying/Installation,
to be
testing
supplied
&commissioning)
Qty.
2.2
2.2
Sr.No
.
Particulars of Item
Supply Qty.
Unit
220KV
ATUL S/s
400KV
NAVSARI
(PGCIL) S/s
1
0
1
1
Mtr.
100
0
100
100
No.
1
0
1
1
12
PLCC Exchange of Make: MATRIX, Type Eternity 10S
with 8 Nos. of Trunks & 8 Nos. of Subscribers suitable for
both PLCC Dialling and Express Communication
connectivity with Universal slot architecture having Hot
stand by Power supply and CPU and reputed make Push
button type telephone instruments. .
No.
13
DAS Meters network wiring complete up to RS 485 to RS
232 Convertor of DAS PC using
a) 3 core communication cable (as per specification given
hereunder)
Job
b) RS 485 to RS 232 Converter (as per specification
given hereunder)
Erection
Total Qty. (Laying/Installation,
to be
testing
supplied
&commissioning)
Qty.
Download