Braced Post Insulators Braced Post: Unique insulator design that combines the cantilever properties of a horizontal line post with the tension strength of a suspension insulator to make a high strength insulator assembly. The suspension insulator, or brace, is attached to the line post and to the tower via connection hardware. When loaded, the brace goes into tension, and is the primary support mechanism for the assembly. The line post provides stability for transverse (tension & compression) & longitudinal loads exerted onto the assembly. Connection Hardware: The hardware used to connect the brace to the post and tower can be supplied in a variety of combinations. Typically, the hardware used is greater than or equal to the SML rating of the brace insulator, and the type of connections is determined by the end fittings supplied on the suspension. Options for connection hardware discussed in later sections. Vertical Load: (MDCL) Downward load applied to the assembly, usually determined by the weight of the conductor. Tension Load: Transverse load pulling perpendicularly away from the tower, essentially putting the line post in tension. Compression Load: Transverse load pulling perpendicularly into the tower, compressing the line post towards the tower. Longitudinal Load: Side load applied to the assembly. Ideally, the load on each side of the assembly will be equal / balanced, resulting in no longitudinal load. Longitudinal loading is critical when loads are unbalanced and for broken conductor consideration. Combined Load Curves: Load curve that combines the effects of the various loads and plots working and ultimate strength of the assembly. Load curves are supplied upon request. Working Load Curve: The maximum load that can be applied to the insulator for long periods of time, without damaging or fatiguing the insulator. Ultimate Load Curve: The load at which the assembly approaches its ultimate strength, point of failure. Braced Post Load Application: The maximum load (or worst case load) of a specific application should fit right at or below the working load curve for that respective design. This max load is determined by the customer, and should take into account environmental influences (wind, ice, etc) along with the utilities safety factor practice. Max load applications that surpass the working curve require upgrades in strength for the braced post. Strength Upgrades: Depending on the specific loading requirements, there are many ways to upgrade the strength of a braced post, listed below are a few of the most common upgrades. • Increase the SML of the brace insulator [~ increase Vertical Loading Capability] • Increase the rod diameter of the line post [~ higher Vertical / Transverse Loading Capability] • Change from fixed base to swivel base [~ improves Longitudinal Loading Capability] • Dimensional design changes (Changes to upsweep angle, brace angle, height, etc.) © Copyright 2010 MacLean Power Systems Issued: May 2010 Supercedes: n/a IN-45 11411 Addison Avenue, Franklin Park, IL 60131 T: 847.455.0014 F: 847.455.0029 www.macleanpower.com Braced Post Insulators Insulator Electrical Performance: The electrical values of an insulator are driven by the dry arc distance, and the insulators’ contamination performance is dictated by the leakage distance. Dry Arc Distance: The shortest distance metal to metal up and along the insulator tangent to the sheds. The electrical values for 60Hz & critical impulse flashovers are statistically derived by the dry arc distance of the insulator. Assembly Strike Distance: In a combination assembly, the individual dry arc distances of each insulator are usually not the shortest paths metal to metal. This shorter path or dry arc for the assembly is called the strike distance, which could be the distance from the post base to the brace end fitting or corona ring, or it could be the distance to the conductor hardware, especially on double bundled assemblies with horizontal yoke plates. The strike distance drives the electrical values of the braced post assembly. Leakage Distance: The continuous path across the insulator from metal to metal, measured across the profile of each shed. The leakage distance is controlled by the number of sheds on the insulator. Assembly Leakage Distance: The leakage distance for a braced post assembly is the shortest leakage distance of the 2 insulators that make up the assembly. If the post has 230” of leakage, and the brace has 180” of leakage, the braced post leakage distance is 180”. The strike distance of the braced post assembly is typically shorter than the dry arc distances of either the post or brace insulators. Therefore, the electrical values of the individual insulators are greater than the electrical values of the assembly. The sketch above shows the various strike distances of the assembly, the shortest of which determines the electrical values. Recommended Corona Ring Application for the Braced Post 8” Corona Ring Brace Post 12” Corona Ring 230 kV 345 kV 8” Ring 12” Ring None 6” Ring High voltages can result in unwanted noise (RIV) and corona. To minimize the effects of corona, corona rings are applied to one or both of the insulators of the assembly. Typically, for system voltages 230kV and above a corona ring or combination of rings is necessary. However, some applications may require rings at lower system voltages. The table above shows the recommended corona ring applications for 230kV & 345kV. The ultimate decision of corona ring application is determined by the customer and by the environmental factors where the assembly will be used. © Copyright 2010 MacLean Power Systems Issued: May 2010 Supercedes: n/a IN-46 11411 Addison Avenue, Franklin Park, IL 60131 T: 847.455.0014 F: 847.455.0029 www.macleanpower.com Braced Post Insulators Braced Post Design Options Insulator Options Line Post: Typically, the line post of the braced post assembly will have a tongue line end fitting (F), and a bendable base tower connection (E). The bendable base is available as a gain or flat design type, or it can be replaced with a swivel or pivoting base, depending on the requirements of the application. Brace Insulator: The suspension insulator that makes up the brace can be comprised of many end fitting combinations, per customer preference. The Eye / Eye combination is a commonly used design, it offers a greater degree of articulation when combined with anchor shackles. Bendable Gain Bendable Flat Swivel Base Bendable Base – Formed steel base that mates with an anchor end fitting on the insulator via 2 mounting bolts. These bases provide some vertical articulation of the post, which offers adjustment for the brace and connection hardware to the pole. Bendable bases come in gain and flat designs, with 0° & 12° upsweep angles, as required for by application. Gain Base – Base design used to mate the insulator to a round pole surface. This base is attached to the pole through the center bolt mount holes. Flat Base – Base design used to mate the insulator to a flat surface, using either the 4 bolt holes along the ears of the base, or the 2 center mount bolt holes. Swivel Base or Pivoting Base – This base provides articulation in the vertical and longitudinal directions. This design is typically used in areas where high longitudinal loading is required to compensate for unbalanced loads or broken conductor conditions. Pole Band Assemblies – Another method of attaching a braced post assembly to a tower is by means of a pole band assembly. Pole bands are used on poles when mount holes are not available and cannot be drilled, or for maintenance / emergency response applications. Contact MPS for additional details. Brace Connection Hardware Options The brace of the braced post assembly can be made up of many different insulator and hardware combinations, depending on customer preference and design. • The suspension insulator can make up the entire length of the brace, connected to the post and tower via anchor shackles. This is the simplest and more cost efficient design. • The brace can consist of an electrically proportionate length suspension, combined with shackles for G1. & G2, and some form of steel hardware for item G3 (turnbuckle, straps, links, etc). Options for G1 Options for G2 Options for G3 EF Options for SSL Anchor Shackle (SL = Eye) Socket/Clevis (SL = Y-Clevis) Anchor Shackle (SL = Eye) Turnbuckle Steel Strap Chain Links Eye / Eye Eye / Ball Y-Clevis / Ball © Copyright 2010 MacLean Power Systems Issued: May 2010 Supercedes: n/a IN-47 11411 Addison Avenue, Franklin Park, IL 60131 T: 847.455.0014 F: 847.455.0029 www.macleanpower.com Braced Post Insulators Custom Braced Post Designs The MPS “Braced Post” section of this catalog has many standard designs available for system voltages 69kV through 230kV. If the designs shown in the catalog do not exactly satisfy the requirements of an application, custom braced post designs are available. At the end of the braced post section is a braced post request worksheet, which is designed to communicate the specific details of a custom braced post design to MPS. The information provided on this sheet is used by MPS Design Engineering to develop the best fit design per customer request. In order to properly develop these designs, it is important to know the specific requirements of the application along with clarification about which details are most critical and which have some flexibility within the design. More Information = better designs and faster response time. Braced Post Assembly Details: This section outlines the geometric/dimensional requirements of the assembly, including assembly height, section length, and angles. Ideally, the dimensions required would be expressed as a nominal value, with some +/- tolerances. When a specific dimension is absolutely required, it should be identified as “critical”. Not every dimension can be critical, as some dimensions of the assembly are driven by others, therefore only 2-3 dimensions should be marked as critical. Mechanical Loading Requirements: This section identifies the loading characteristics of the application. These values should be ultimate loads the assembly will be expected to withstand over long periods of time, and should fit within the working load curve of the assembly. Electrical Requirements: This section determines the minimal requirement of the assembly with respect to electrical performance. • Minimum leakage distance (and / or description of contamination level for the application) • Minimum strike distance / dry arc • Minimum requirements for 2 of the 4 electrical values (ex. Dry FO & CIFO+) • Corona ring requirement Assembly Details: The remaining sections identify the various options of the assembly… • Line post base requirement • Suspension end fitting requirements • Hardware attachments • Extension hardware • Conductor information (armor rod) • Conductor attachment hardware Hardware Assemblies & Packaging MPS provides a single catalog number & drawing for each braced post assembly, whether it is a standard catalog item, or a custom design. The catalog number includes all the insulators, connection hardware, and conductor hardware as required, with all the various catalog numbers of the individual components bundled into one catalog number. Packaging: There are several options for packaging insulator assemblies. Typically, the individual components are bulk packed separately and mated in the field by the customer. Custom packs and tower packs are available upon request. These value added options reduce costs in the field, help minimize lost or missing parts, and reduce the time from receipt of goods to installation. Tower Packs: Unique packaging where each component of the assembly is packed into one crate, usually in quantities of 3, 6, or 9. MPS verifies fit and quantity of the components of the assembly. The crate can be marshaled out to the job site and dropped at the tower, where it can then be assembled and installed. Custom Packs: MPS packages components together as required by the customer. For additional information about braced post assemblies, contact your local MPS Sales Representatives © Copyright 2010 MacLean Power Systems Issued: May 2010 Supercedes: n/a IN-48 11411 Addison Avenue, Franklin Park, IL 60131 T: 847.455.0014 F: 847.455.0029 www.macleanpower.com Braced Post - B191-XL Series Identification A = 1.5” [38mm] (not included) H = Assembly Height (Tolerance = +/- 3”) (pole connection offset) SSL = Suspension Length B = Brace Length PSL = Post Section Length C = Brace Angle PSL SSL H C B in (mm) in (mm) in (mm) Deg. in (mm) 1 32.0 (813) 35.4 (899) 35.0 (889) 54.0˚ 40.9 (1039) 2 32.0 (813) 41.7 (42) 44.0 (1118) 63.0˚ 47.2 (1199) 3 35.0 (889) 41.7 (1059) 42.0 (1067) 58.0˚ 47.2 (1199) 4 35.0 (889) 46.4 (1179) 48.0 (1219) 62.0˚ 51.9 (1318) 5 41.0 (1041) 46.4 (1179) 43.5 (1105) 53.0˚ 51.9 (1318) 6 41.0 (1041) 54.3 (1379) 54.5 (1384) 61.0˚ 59.8 (1519) 7 48.0 (1219) 54.3 (1379) 49.0 (1245) 52.0˚ 59.8 (1519) 8 48.0 (1219) 60.6 (1539) 58.0 (1473) 58.0˚ 66.1 (1679) 9 54.0 (1372) 60.6 (1539) 53.0 (1346) 50.0˚ 66.1 (1679) 10 54.0 (1372) 65.3 (1659) 60.0 (1524) 55.0˚ 70.8 (1798) 11 60.0 (1524) 65.3 (1659) 54.0 (1372) 47.0˚ 70.8 (1798) 12 60.0 (1524) 71.7 (1821) 64.0 (1626) 53.0˚ 77.2 (1961) Fig. List Of Materials: Standard Strength Braced Posts 1) 2.0” Line Post Insulator (1 each) 2) 25klb MX Suspension Insulator (1 each) 3) SYC-56 Socket Y-Clevis (1 each) 4) ASH-55 Anchor Shackle (2 each) Fig. Catalog Number Electrical Flashover (kV) Weight Line Voltage MDCL Dry Arc Leakage kV lbs (kN) in (mm) in (mm) Dry Wet Pos Neg lbs. (kg) 234 213 298 490 46.5 (21.1) 60 Hz CIFO 1 B191032XL4AM 1 69 10,387 23.3 51.2 (1300) 2 B191032XL4AM 2 69 11,330 24.5 51.2 (1300) 245 223 416 509 46.4 (21.0) 3 B191035XL4AM 1 69 10,200 29.3 55.9 (1420) 288 264 491 586 47.8 (21.7) 4 B191035XL4AM 2 69 11,200 30.4 37.3 (1709) 298 274 509 604 50.1 (22.7) 5 B191041XL4AM 1 69 10,048 36.3 79.3 (2014) 351 325 603 691 53.5 (24.3) 6 B191041XL4AM 2 115 10,949 37.2 79.5 (2019) 359 332 617 704 53.2 (24.1) 7 B191048XL4AM 1 115 10,023 42.4 85.6 (2174) 405 375 699 775 55.3 (25.1) 8 B191048XL4AM 2 115 10,908 43.3 85.6 (2174) 414 383 714 787 55.0 (24.9) 9 B191054XL4AM 1 138 10,043 48.5 91.5 (2324) 460 426 797 851 56.8 (25.8) 10 B191054XL4AM 2 138 10,762 49.2 96.7 (2456) 466 431 808 860 57.9 (26.3) 11 B191060XL4AM 1 138 10,043 48.5 91.5 (2324) 460 426 797 851 56.8 (25.8) 12 B191060XL4AM 2 138 10,762 49.2 96.7 (2456) 466 431 808 860 57.9 (26.3) Notes: • MDCL = Max. Design Cantilever Load (Load Curves provided upon request) • Electrical Data is derived from the assembly “Strike Distance”, without corona rings for 161kV and below. All 230kV Braced Post assemblies supplied with a corona ring (Electrical Values include the corona ring). • B191 Series supplied with standard G2-0 Bendable Gain Base on line post. • For Flat Base F2-0, change the "9" in B191… to "1" = B111…[See line post base section for details] • For Higher Strength or Custom Designs, please complete the Braced Post Request Worksheet at the end of this section and return the competed worksheet to MPS through your local MPS Sales Representative. • Customized Designs include any dimensional changes, strength changes, hardware changes, end fitting changes, etc. © Copyright 2010 MacLean Power Systems Issued: May 2010 Supercedes: n/a IN-49 11411 Addison Avenue, Franklin Park, IL 60131 T: 847.455.0014 F: 847.455.0029 www.macleanpower.com Braced Post - B191-XT Series H PSL B SSL C Fig. MIN MAX MIN MAX in (mm) in (mm) in (mm) in (mm) Deg. in (mm) in (mm) 1 36.0 (914) 35.4 (899) 50.0 (1270) 57.5 (1461) 63˚ - 68˚ 53.58 (1367) 59.5 (1519) 2 36.0 (914) 35.4 (899) 54.0 (1372) 65.0 (1651) 66˚ - 71˚ 56.9 (1445) 65.9 (1674) 3 41.0 (1041) 41.7 (1059) 55.0 (1397) 63.0 (1600) 62˚ - 66˚ 60.1 (1527) 66.0 (1676) 4 41.0 (1041) 41.7 (1059) 59.0 (1499) 70.0 (1778) 64˚ - 69˚ 63.2 (1605) 72.2 (1834) 5 47.0 (1194) 46.4 (1179) 57.0 (1448) 65.5 (1664) 58˚ - 63˚ 64.8 (1646) 70.8 (1798) 6 47.0 (1194) 46.4 (1179) 61.5 (1562) 73.0 (1854) 61˚ - 66˚ 67.9 (1725) 76.9 (1953) 7 54.0 (1372) 54.3 (1379) 63.0 (1600) 71.5 (1816) 57˚ - 61˚ 72.7 (1847) 78.7 (1999) 8 54.0 (1372) 54.3 (1379) 37.5 (1715) 79.0 (2007) 59˚ - 64˚ 75.8 (1925) 84.8 (2154) 9 60.0 (1524) 60.3 (1532) 67.0 (1702) 75.5 (1918) 55˚ - 59˚ 78.7 (1999) 84.7 (2151) 10 60.0 (1524) 60.3 (1532) 71.5 (1816) 83.5 (2121) 57˚ - 63˚ 81.8 (2078) 90.8 (2306) 11 65.0 (1651) 65.3 (1659) 69.5 (1765) 78.5 (1994) 53˚ - 58˚ 83.7 (2126) 89.7 (2278) 12 65.0 (1651) 65.3 (1659) 74.5 (1892) 86.5 (2197) 56˚ - 61˚ 86.8 (2205) 95.8 (2433) List Of Materials: 1) 2.0” Line Post Insulator (1 each) 2) 25klb MX Suspension Insulator (1 each) 3) SYC-56 Socket Y-Clevis (1 each) 4) Turnbuckle Fig. Catalog Number 1 B191036XT4AM6 2 B191036XT4AM9 3 B191041XT4AM6 4 B191041XT4AM9 5 B191047XT4AM6 6 B191047XT4AM9 7 B191054XT4AM6 8 B191054XT4AM9 9 B191060XT4AM6 10 B191060XT4AM9 11 B191065XT4AM6 12 B191065XT4AM9 Electrical Flashover (kV) Weight Line Voltage MDCL kV lbs (kN) in (mm) in (mm) Dry Wet Pos Neg lbs. (kg) 69 11,369 (50.6) 26.6 (676) 60.8 (1544) 264 242 449 544 62.3 (28.3) 69 11,233 (50.0) 31.6 (803) 76.8 (1951) 309 285 529 622 66.7 (30.3) 115 10,851 (48.3) 37.4 (950) 89.0 (2261) 361 334 620 707 70.8 (32.1) 115 /138 10,652 (47.4) 44.4 (1128) 109.2 (2774) 424 392 732 801 76.0 (34.5) 138 10,448 (46.5) 50.4 (1280) 125.2 (3180) 477 441 827 876 80.5 (36.5) 138 /161 10,250 (45.6) 55.4 (1407) 137.4 (3490) 520 480 905 950 84.4 (38.3) Dry Arc Leakage 60 Hz CIFO Notes: • MDCL = Max. Design Cantilever Load (Load Curves provided upon request) • Electrical Data is derived from the assembly “Strike Distance”, without corona rings for 161kV and below. All 230kV Braced Post assemblies supplied with a corona ring (Electrical Values include the corona ring). • B191 Series supplied with standard G2-0 Bendable Gain Base on line post. • For Flat Base F2-0, change the "9" in B191… to "1" = B111…[See line post base section for details] • For Higher Strength or Custom Designs, please complete the Braced Post Request Worksheet at the end of this section and return the competed worksheet to MPS through your local MPS Sales Representative. • Customized Designs include any dimensional changes, strength changes, hardware changes, end fitting changes, etc. © Copyright 2010 MacLean Power Systems Issued: May 2010 Supercedes: n/a IN-50 11411 Addison Avenue, Franklin Park, IL 60131 T: 847.455.0014 F: 847.455.0029 www.macleanpower.com Braced Post - B291-XL Series Identification A = 1.5” [38mm] (not included) H = Assembly Height (Tolerance = +/- 3”) (pole connection offset) SSL = Suspension Length B = Brace Length PSL = Post Section Length C = Brace Angle PSL SSL H C B in (mm) in (mm) in (mm) Deg. in (mm) 1 35.0 (889) 39.0 (991) 37.9 (963) 54˚ 44.5 (1130) 2 41.0 (1041) 45.0 (1143) 41.5 (1054) 52˚ 50.5 (1283) 3 45.0 (1143) 49.0 (1245) 44.0 (1118) 50˚ 54.5 (1384) 4 52.6 (1336) 58.0 (1473) 51.5 (1308) 50˚ 63.5 (1613) 5 54.0 (1372) 75.0 (1905) 74.0 (1880) 62˚ 80.5 (2045) 6 58.5 (1486) 67.9 (1725) 59.8 (1519) 51˚ 72.5 (1842) 7 59.0 (1499) 84.0 (2134) 83.0 (2108) 63˚ 89.5 (2273) 8 61.5 (1562) 70.0 (1778) 61.5 (1562) 50˚ 75.5 (1918) 9 65.0 (1651) 93.0 (2362) 91.0 (2311) 63˚ 98.5 (2502) 10 67.4 (1712) 78.0 (1981) 68.2 (1732) 51˚ 83.5 (2121) 11 70.4 (1788) 81.0 (2057) 69.9 (1775) 54˚ 86.5 (2197) 12 70.0 (1778) 100.0 (2540) 96.0 (2438) 62˚ 105.5 (2680) 13 75.0 (1905) 88.0 (2235) 75.0 (1904) 51˚ 93.5 (2375) 14 84.0 (2134) 100.0 (2540) 85.0 (2159) 51˚ 105.5 (2680) 15 85.0 (2159) 123.0 (3124) 118.0 (2997) 63˚ 128.5 (3264) 16 90.0 (2286) 107.0 (2718) 90.0 (2287) 51˚ 112.5 (2858) 17 90.0 (2286) 133.0 (3378) 127.0 (3226) 63˚ 138.5 (3518) 18 96.0 (2438) 114.0 (2896) 95.0 (2413) 50˚ 119.5 (3035) Fig. List Of Materials: Standard Strength Braced Posts 5) 2.5” Line Post Insulator (1 each) 6) 25klb (S199) Suspension Insulator (1 each) 7) ASH-55 Anchor Shackle (2 each) Notes: • MDCL = Max. Design Cantilever Load (Load Curves provided upon request) • Electrical Data is derived from the assembly “Strike Distance”, without corona rings for 161kV and below. All 230kV Braced Post assemblies supplied with a corona ring (Electrical Values include the corona ring). • HS = High Strength design. Brace SML = 36k • For Higher Strength or Custom Designs, please complete the Braced Post Request Worksheet at the end of this section and return the competed worksheet to MPS through your local MPS Sales Representative. • B191 Series supplied with standard G2-0 Bendable Gain Base on line post. • For Flat Base F2-0, change the “9” in B191… to “1” = B111…[See line post base section for details] • Customized Designs include any dimensional changes, strength changes, hardware changes, end fitting changes, gain to flat base changes, etc. © Copyright 2010 MacLean Power Systems Issued: May 2010 Supercedes: n/a IN-51 11411 Addison Avenue, Franklin Park, IL 60131 T: 847.455.0014 F: 847.455.0029 www.macleanpower.com Braced Post - B291-XL Series Continued... Fig. Catalog Number Electrical Flashover (kV) Line Voltage MDCL kV lbs (kN) Dry Arc 2 B291035XL99 B in (mm) 69 10,375 (46.2) 23.3 (591) B291041XL99 A 48.5 (1232) 69 10,028 (44.6) 28.8 (731) 5 6 7 8 9 10 11 B291045XL99 B 70.3 (1786) 9,910 (44.1) 33.2 (843) 104.5 (2654) 124.7 (3167) B291052XL99 A 75.6 (1920) 115 9,829 (43.7) 40.6 (1031) 95.0 (2413) B291052XL99 C 125.9 (3198) B291054XL99 A 81.0 (2057) B291054XL99 B 115 11,295 (50.2) 43.8 (1113) 111.6 (2835) B291054XL99 C 138.8 (3526) B291058XL99 A 92.3 (2344) B291058XL99 B 138 10,032 (44.6) 46.8 (1189) 123.3 (3132) B291058XL99 C 145.9 (3706) B291059XL99 D 97.7 (2482) B291059XL99 B 138 11,377 (50.6) 49.1 (1247) 124.8 (3170) B291059XL99 C 155.8 (3957) B291061XL99 A 9135 (2324) B291061XL99 B 138 9,908 (44.1) 49.7 (1262) 122.4 (3109) B291061XL99 C 153.4 (3896) B291065XL99 A 109.2 (2774) B291065XL99 B Wet Pos Neg 161 11,352 (50.5) 55.2 (1402) 136.4 (3465) lbs (kg) 63.6 (28.9) 233 212 396 489 64.5 (29.3) 65.7 (29.8) 68.4 (31.0) 283 260 484 578 70.2 (31.9) 71.7 (32.5) 78.2 (1986) 115 B291045XL99 C B291052XL99 B Dry 90.7 (2304) B291045XL99 A 4 60.4 (1534) 72.4 (1839) B291041XL99 C 3 in (mm) CIFO 48.9 (1242) B291035XL99 C B291041XL99 B Weight 60 Hz B291035XL99 A 1 Leakage 72.2 (32.7) 323 298 553 645 74.3 (33.7) 76.0 (34.5) 77.9 (35.4) 390 361 671 751 79.4 (36.0) 81.8 (37.1) 66.7 (30.3) 418 387 722 793 72.8 (33.0) 78.7 (35.7) 82.8 (37.6) 444 411 769 830 85.2 (38.7) 87.0 (39.5) 70.7 (32.1) 465 430 805 858 76.6 (34.7) 83.4 (37.8) 84.7 (38.4) 470 435 815 865 87.1 (39.5) 89.5 (40.6) 74.1 (33.6) 518 479 902 947 80.0 (36.3) B291065XL99 C 163.6 (4155) 85.9 (39.0) B291067XL99 A 107.2 (2723) 89.6 (40.7) B291067XL99 B 161 9,969 (44.3) 55.8 (1417) 142.0 (3607) B291067XL99 C 173.0 (4394) B291070XL99 A 106.0 (2692) B291070XL99 B 161 9,870 (43.9) B291070XL99 C © Copyright 2010 MacLean Power Systems Issued: May 2010 Supercedes: n/a 58.7 (1491) 141.2 (3586) 182.6 (4638) IN-52 523 483 911 956 92.3 (41.9) 94.7 (43.0) 91.4 (41.5) 549 506 957 1000 94.1 (42.7) 97.4 (44.2) 11411 Addison Avenue, Franklin Park, IL 60131 T: 847.455.0014 F: 847.455.0029 www.macleanpower.com Braced Post - B291-XL Series Continued... Fig. Catalog Number Electrical Flashover (kV) Line Voltage MDCL kV lbs (kN) Dry Arc 13 B291070XL99 J in (mm) 161 11,276 (50.2) 60.0 (1524) B291075XL99 A 113.3 (2878) 161 9,901 (44.0) 63.7 (1618) 16 17 18 B291084AL99 B 140.4 (3566) 9,951 (44.3) 69.7 (1770) 202.7 (5149) 228.0 (5791) B291085AL99 A 156.1 (3965) 230 11,305 (50.3) 72.3 (1836) 193.1 (4905) B291085AL99 C 237.4 (6030) B291090AL99 A 155.6 (3952) B291090AL99 B 230 9,887 (44.0) 75.8 (1925) 202.0 (5131) B291090AL99 C 239.0 (6071) B291090AL99 D 162.0 (4115) B291090AL99 E 230 11,357 (50.5) 77.3 (1963) 207.3 (5265) B291090AL99 F 247.4 (6284) B291096AL99 A 154.8 (3932) B291096AL99 B Wet Pos Neg 230 9,830 (43.7) 81.5 (2070) B291096AL99 C 199.8 (5075) 258.7 (6571) lbs (kg) 78.8 (35.7) 560 516 978 1019 84.0 (38.1) 92.7 (42.0) 94.7 (43.0) 593 545 1036 1074 96.8 (43.9) 101.0 (45.8) 151.3 (3843) 230 B291084AL99 C B291085AL99 B Dry 194.6 (4943) B291084AL99 A 15 150.6 (3825) 191.1 (4854) B291075XL99 C 14 in (mm) CIFO 125.3 (3183) B291070XL99 K B291075XL99 B Weight 60 Hz B291070XL99 I 12 Leakage 9038 (41.2) 644 590 1129 1162 101.7 (46.1) 107.5 (48.8) 91.6 (41.5) 666 609 1168 1200 99.7 (45.2) 109.3 (49.6) 93.0 (42.2) 696 635 1222 1251 102.9 (46.7) 110.9 (50.3) 93.6 (42.5) 709 646 1245 1273 103.5 (46.9) 112.2 (50.9) 93.6 (42.5) 745 676 1308 1333 103.4 (46.9) 116.2 (52.7) Data in this table corresponds with the Sketches on the previous page. Notes: • MDCL = Max. Design Cantilever Load (Load Curves provided upon request) • Electrical Data is derived from the assembly “Strike Distance”, without corona rings for 161kV and below. All 230kV Braced Post assemblies supplied with a corona ring (Electrical Values include the corona ring). • HS = High Strength design. Brace SML = 36k • For Higher Strength or Custom Designs, please complete the Braced Post Request Worksheet at the end of this section and return the competed worksheet to MPS through your local MPS Sales Representative. • Customized Designs include any dimensional changes, strength changes, hardware changes, end fitting changes, gain to flat base changes, etc. © Copyright 2010 MacLean Power Systems Issued: May 2010 Supercedes: n/a IN-53 11411 Addison Avenue, Franklin Park, IL 60131 T: 847.455.0014 F: 847.455.0029 www.macleanpower.com Braced Post - B291-XL High Strength Series Identification A = 1.5” [38mm] (not included) H = Assembly Height (Tolerance = +/- 3”) (pole connection offset) SSL = Suspension Length B = Brace Length PSL = Post Section Length C = Brace Angle PSL SSL H C B in (mm) in (mm) in (mm) Deg. in (mm) 5 54.0 (1372) 75.0 (1905) 74.0 (1880) 62˚ 80.5 (2045) 7 59.0 (1499) 84.0 (2134) 83.0 (2108) 63˚ 89.5 (2273) 9 65.0 (1651) 93.0 (2362) 91.0 (2311) 63˚ 98.5 (2502) 12 70.0 (1778) 100.0 (2540) 96.0 (2438) 62˚ 105.5 (2680) 15 85.0 (2159) 123.0 (3124) 118.0 (2997) 63˚ 128.5 (3264) 17 90.0 (2286) 133.0 (3378) 127.0 (3226) 63˚ 138.5 (3518) Fig. High Strength Braced Posts [marked “HS”] 1) 2.5” Line Post Insulator (1 each) 2) 36klb (S699) Suspension Insulator (1 each) 3) ASH-56 Anchor Shackle (2 each) Fig. Catalog Number Electrical Flashover (kV) Line Voltage MDCL kV lbs (kN) Dry Arc 7 9 12 15 17 B291054XL99 M in (mm) in (mm) 115 14,000 (62.3) 43.8 (1113) 109.8 (2789) 138.8 (3526) B291059XL99 L 99.4 (2525) 138 14,000 (62.3) 49.1 (1247) 122.6 (3114) B291059XL99 N 157.5 (4001) B291065XL99 L 108.4 (2753) B291065XL99 M 161 14,000 (62.3) 55.2 (1402) 135.5 (3442) B291065XL99 N 163.6 (4155) B291070XL99 L 127.0 (3226) B291070XL99 M 161 14,000 (62.3) 60.0 (1524) 150.2 (3815) B291070XL99 N 191.3 (4859) B291085XL99 L 156.9 (3985) B291085XL99 M 230 14,000 (62.3) 72.3 (1836) 192.6 (4892) B291085XL99 N 238.4 (6055) B291090XL99 L 162.0 (4115) B291090XL99 M Dry CIFO Wet Pos Neg 82.7 (2101) B291054XL99 N B291059XL99 M Weight 60 Hz B291054XL99 L 5 Leakage 230 13,577 (60.4) B291090XL99 N 77.3 (1963) 206.5 (5245) 245.2 (6228) lbs (kg) 68.3 (31.0) 418 387 722 793 74.4 (33.7) 80.3 (36.4) 72.3 (32.8) 465 430 805 858 78.2 (35.5) 85.0 (38.6) 75.7 (34.3) 518 479 902 947 81.6 (37.0) 87.5 (39.7) 80.4 (36.5) 560 516 978 1019 85.6 (38.8) 94.3 (42.8) 93.2 (42.3) 666 609 1168 1200 101.3 (45.9) 110.9 (50.3) 95.2 (43.2) 709 646 1245 1273 105.1 (47.7) 113.8 (51.6) Notes: • MDCL = Max. Design Cantilever Load (Load Curves provided upon request) • Electrical Data is derived from the assembly “Strike Distance”, without corona rings for 161kV and below. All 230kV Braced Post assemblies supplied with a corona ring (Electrical Values include the corona ring). • HS = High Strength design. Brace SML = 36k • For Higher Strength or Custom Designs, please complete the Braced Post Request Worksheet at the end of this section and return the competed worksheet to MPS through your local MPS Sales Representative. • Customized Designs include any dimensional changes, strength changes, hardware changes, end fitting changes, gain to flat base changes, etc. © Copyright 2010 MacLean Power Systems Issued: May 2010 Supercedes: n/a IN-54 11411 Addison Avenue, Franklin Park, IL 60131 T: 847.455.0014 F: 847.455.0029 www.macleanpower.com Braced Post - B291-XT Series Identification A = 1.5” [38mm] (not included) (pole connection offset) B = Brace Length C = Brace Angle H = Assembly Height TB = Turnbuckel SSL = Suspension Length PSL = Post Section Length H PSL List Of Materials: 5) 2.5” Line Post Insulator (1 each) 6) 25klb MX Suspension Insulator (1 each) 7) SYC-56 Socket Y-Clevis (1 each) 8) Turnbuckle Fig. Catalog Number 1 B291035XT4M6 2 B291035XT4M9 3 B291041XT4M6 4 B291041XT4M9 5 B291048XT4M6 6 B291048XT4M9 7 B291053XT4M6 8 B291053XT4M9 9 B291062XT4M6 10 B291062XT4M9 11 B291066XT4M6 12 B291066XT4M9 C B SSL Fig. MIN MAX MIN MAX in (mm) in (mm) in (mm) in (mm) Deg. in (mm) in (mm) 1 34.8 (884) 35.4 (899) 51.0 (1295) 58.0 (1473) 65˚ - 69˚ 53.8 (1367) 59.8 (1519) 2 34.8 (884) 35.4 (899) 55.0 (1397) 65.0 (1651) 67˚ - 72˚ 56.9 (1445) 65.9 (1674) 3 40.7 (1034) 41.7 (1059) 55.5 (1410) 62.5 (1588) 62˚ - 66˚ 60.1 (1527) 66.0 (1676) 4 40.7 (1034) 41.7 (1059) 59.5 (1511) 70.0 (1778) 65˚ - 70˚ 63.2 (1605) 72.2 (1834) 5 48.0 (1219) 46.4 (1179) 57.0 (1448) 64.5 (1638) 57˚ - 62˚ 64.8 (1646) 70.8 (1798) 6 48.0 (1219) 46.4 (1179) 61.0 (1549) 72.0 (1829) 60˚ - 65˚ 67.9 (1725) 76.9 (1953) 7 52.6 (1336) 54.3 (1379) 64.5 (1638) 72.0 (1829) 58˚ - 62˚ 72.7 (1847) 78.7 (1999) 8 52.6 (1336) 54.3 (1379) 68.5 (1740) 79.5 (2019) 60˚ - 65˚ 75.8 (1925) 84.8 (2154) 9 61.5 (1562) 603 (1532) 66.0 (1676) 74.0 (1880) 53˚ - 57˚ 78.7 (1999) 84.7 (2151) 10 61.5 (1562) 60.3 (1532) 70.5 (1791) 82.5 (2096) 56˚ - 61˚ 81.8 (2078) 90.8 (2306) 11 66.0 (1676) 65.3 (1659) 69.0 (1753) 77.0 (1956) 52˚ - 56˚ 83.7 (2126) 89.7 (2278) 12 66.0 (1676) 65.3 (1659) 73.5 (1867) 86.0 (2184) 55˚ - 60˚ 86.8 (2205) 95.8 (2433) Electrical Flashover (kV) Line Voltage MDCL kV lbs (kN) in (mm) in (mm) Dry Wet Pos Neg lbs (kg) 69 11,528 (51.3) 25.6 (650) 60.8 (1544) 255 233 433 527 72.0 (32.7) 69 11,265 (50.1) 31.3 (795) 76.8 (1951) 307 282 524 628 77.0 (34.9) 115 10,740 (47.8) 38.3 (973) 89.0 (2261) 370 342 635 720 80.0 (36.3) 155 /138 11,320 (50.4) 43.5 (1105) 109.2 (2774) 415 385 717 789 88.0 (39.9) 138 10,301 (45.8) 51.9 (1318) 125.2 (3180) 489 452 849 897 96.0 (43.5) 138 /161 10,130 (45.1) 56.4 (1433) 137.4 (3490) 529 488 921 965 94.0 (42.6) Dry Arc Leakage Weight 60 Hz CIFO Notes: • MDCL = Max. Design Cantilever Load (Load Curves provided upon request) • Electrical Data is derived from the assembly “Strike Distance”, without corona rings for 161kV and below. All 230kV Braced Post assemblies supplied with a corona ring (Electrical Values include the corona ring). • HS = High Strength design. Brace SML = 36k • For Higher Strength or Custom Designs, please complete the Braced Post Request Worksheet at the end of this section and return the competed worksheet to MPS through your local MPS Sales Representative. • B191 Series supplied with standard G2-0 Bendable Gain Base on line post. • For Flat Base F2-0, change the “9” in B191… to “1” = B111…[See line post base section for details] • Customized Designs include any dimensional changes, strength changes, hardware changes, end fitting changes, gain to flat base changes, etc. © Copyright 2010 MacLean Power Systems Issued: May 2010 Supercedes: n/a IN-55 11411 Addison Avenue, Franklin Park, IL 60131 T: 847.455.0014 F: 847.455.0029 www.macleanpower.com Braced Post - B261 Series w/ Swivel Base Identification A = pole connection offset (not included) B = Brace Length C = Brace Angle H = Assembly Height (Tolerance = +/- 3”) SSL = Suspension Length PSL = Post Section Length PSL SSL H A C B in (mm) in (mm) in (mm) in (mm) Deg. in (mm) 1 54.0 (1372) 52.0 (1321) 51.0 (1295) 18.0 (457) 57˚ 57.5 (1461) 2 60.0 (1524) 58.0 (1473) 56.0 (1422) 20.0 (508) 57˚ 63.5 (1613) 3 66.0 (1676) 64.0 (1626) 61.0 (1549) 22.0 (559) 57˚ 69.5 (1765) 4 72.0 (1829) 70.0 (1778) 66.0 (1676) 24.0 (610) 56˚ 75.5 (1918) 5 87.0 (2210) 87.0 (2210) 80.0 (2032) 28.0 (711) 56˚ 92.5 (2350) 6 93.0 (2362) 93.0 (2362) 85.0 (2159) 30.0 (762) 56˚ 98.5 (2502) Fig. List Of Materials Standard Strength Braced Posts 1) 2.5” Line Post Insulator (1 each) 2) 25klb (S199) Suspension Insulator (1 each) 3) ASH-55 Anchor Shackle (2 each) High Strength Braced Posts [marked “HS”] 1) 2.5” Line Post Insulator (1 each) 2) 36klb (S699) Suspension Insulator (1 each) 3) ASH-56 Anchor Shackle (2 each) © Copyright 2010 MacLean Power Systems Issued: May 2010 Supercedes: n/a Notes: • MDCL = Max. Design Cantilever Load (Load Curves provided upon request) • Electrical Data is derived from the assembly “Strike Distance,” without corona rings for 161kV and below. All 230kV Braced Post assemblies supplied with a corona ring (Electrical Values include the corona ring). • HS = High Strength design. Brace SML = 36k • For Higher Strength or Custom Designs, please complete the Braced Post Request Worksheet at the end of this section and return the competed worksheet to MPS through your local MPS Sales Representative. • Customized Designs include any dimensional changes, strength changes, hardware changes, end fitting changes, gain to flat base changes, etc. IN-56 11411 Addison Avenue, Franklin Park, IL 60131 T: 847.455.0014 F: 847.455.0029 www.macleanpower.com Braced Post - B261 Series w/ Swivel Base Fig. Catalog Number Electrical Flashover (kV) Line Voltage MDCL kV lbs (kN) Dry Arc Weight 60 Hz in (mm) B261054XL99 A B261054XL99 B Leakage in (mm) Dry CIFO Wet Pos Neg 83.7 (2126) 115 10,538 (46.9) 42.6 (1082) B261054XL99 C 106.3 (2700) lbs (kg) 49.2 (22.3) 408 378 704 778 129.0 (3277) 54.0 (24.5) 59.0 (26.8) 1 B261054XL99 L B261054XL99 M 82.9 (2106) HS 14,000 (62.3) 42.6 (1082) 106.0 (2692) B261054XL99 N 129.0 (3277) B261060XL99 A 102.7 (2609) B261060XL99 B 138 10,494 (46.7) 48.6 (1234) 122.0 (3099) B261060XL99 C 149.1 (3787) B261060XL99 L 100.5 (2553) 50.3 (22.8) 408 378 704 778 55.1 (25.0) 60.1 (27.3) 54.4 (24.7) 460 426 798 852 28.9 (26.7) 64.3 (29.2) 2 B261060XL99 M HS 14,000 (62.3) 48.6 (1234) 123.7 (3142) B261060XL99 N 146.9 (3731) B261066XL99 A 112.6 (2860) B261066XL99 B 161 10,458 (46.5) 54.5 (1384) 139.7 (3548) B261066XL99 C 163.7 (4158) B261066XL99 L 110.4 (2804) 55.5 (25.2) 460 426 798 852 60.0 (27.2) 65.4 (29.7) 57.7 (26.2) 513 474 892 937 63.5 (28.8) 68.8 (31.2) 3 B261066XL99 M HS 14,000 (62.3) 54.5 (1384) 137.5 (3493) B261066XL99 N 164.5 (4178) B261072XL99 A 122.4 (3109) B261072XL99 B 161 10,427 (46.4) 60.5 (1537) 153.4 (3896) B261072XL99 C 188.2 (4780) B261072XL99 L 120.2 (3053) 58.8 (26.7) 513 474 892 937 64.6 (29.3) 69.9 (31.7) 61.0 (27.7) 565 520 986 1027 37.2 (30.5) 74.9 (34.0) 4 B261072XL99 M HS 14,000 (62.3) 60.5 (1537) B261072XL99 N 62.1 (28.2) 565 520 986 1027 186.0 (4724) B261087XL99 A B261087XL99 B 151.2 (3840) 76.0 (34.5) 154.9 (3934) 230 10,380 (46.2) 72.2 (1834) 193.6 (4917) B261087XL99 C 228.4 (5801) B261087XL99 L 152.7 (3879) 68.3 (31.0) 74.2 (33.7) 665 608 116 1198 82.7 (37.5) 89.9 (40.8) 5 B261087XL99 M HS 14,000 (62.3) 72.2 (1834) 191.4 (4862) B261087XL99 N 225.5 (5728) B261093XL99 A 163.6 (4155) B261093XL99 B 230 10,361 (46.1) 78.1 (1984) 208.9 (5306) B261093XL99 C 245.1 (6226) B261093XL99 L 162.6 (4130) 75.3 (34.2) 665 608 116 1198 83.8 (38.0) 91.0 (41.3) 77.5 (35.2) 716 652 1258 1285 87.4 (39.6) 95.1 (43.1) 6 B261093XL99 M HS 13,577 (60.4) B261093XL99 N 78.1 (1984) 208.9 (5306) 243.9 (6195) 78.6 (35.7) 716 652 1258 1285 88.5 (40.1) 96.2 (43.6) Data on this table corresponds with the sketches on the previous page. Notes: • MDCL = Max. Design Cantilever Load (Load Curves provided upon request) • Electrical Data is derived from the assembly “Strike Distance”, without corona rings for 161kV and below. All 230kV Braced Post assemblies supplied with a corona ring (Electrical Values include the corona ring). • HS = High Strength design. Brace SML = 36k • For Higher Strength or Custom Designs, please complete the Braced Post Request Worksheet at the end of this section and return the competed worksheet to MPS through your local MPS Sales Representative. • Customized Designs include any dimensional changes, strength changes, hardware changes, end fitting changes, gain to flat base changes, etc. © Copyright 2010 MacLean Power Systems Issued: May 2010 Supercedes: n/a IN-57 11411 Addison Avenue, Franklin Park, IL 60131 T: 847.455.0014 F: 847.455.0029 www.macleanpower.com Custom Braced Post Request Sheet Name: Project Title: Company: Quantity Required: Contact #: Requested Delivery Date: System Voltage (kV): For Standard Design, fill in catalog number below: _______________________________________________ Proceed to Conductor Information... Custom Braced Post Design Brace Post Assembly Details** Item # Description Nominal PSL Post Section Length SSL Suspenstion Section Length H Assembly Height A Vang Length B Brace Length C Brace Angle D Post Upsweep Angle Max. Min. Post Insulator Customization Name Mechanical Load Requirements (Minimum) ID# Post Base Type E. F. Tension lbs. Post Line End Fitting Vertical lbs. Suspension Insulator Customization Longitudinal lbs. Compression lbs Low End Fitting SL. Tower End Fitting ST. Description New # Harware Attachment Cutomization Electrical Requirements (Minimum) Leakage inch Dry Arc Length inch Susp. to Post Connect G1. Susp. to Tower (vang) G2. Extension to Tower (Select 1 Option) 60 Hz Flashover DRY kV 60 Hz Flashover WET kV CIFO Positive (+) kV CIFO Negative (-) kV None / Insulator Only Steel Strap G3. Turnbuckle Other (specify) Corona Rings Required on: (Circle One) Conductor Attachment Hardware None Suspenstion Post Suspension Clamp J. Attachment Hardware J1. Conductor Information Conductor Name: Size (OD): Armor Rod Yes Other No ** Specify which dimensions are critical to the application by adding a tolerance (Max/Min). For the remaining dimensions, provide only the nominal value. MPS will attempt to meet these values, but may change them to meet the critical dimensions. © Copyright 2010 MacLean Power Systems Issued: May 2010 Supercedes: n/a IN-58 11411 Addison Avenue, Franklin Park, IL 60131 T: 847.455.0014 F: 847.455.0029 www.macleanpower.com