DIVISION 16 Conduits, Conduit Fastening and Conduit Fittings

advertisement
DIVISION 16
1
Conduits, Conduit Fastening and Conduit Fittings Section 16133
Page 1
GENERAL
1.1
Related Sections
1.1.1
2
Section 16010 – Electrical General Requirements.
PRODUCTS
2.1
2.2
2.3
Conduits
2.1.1
Rigid metal conduit: to CSA C22.2 No. 45, galvanized steel or aluminum threaded.
2.1.2
Epoxy coated conduit: to CSA C22.2 No. 45, with zinc coating and corrosion
resistant epoxy finish inside and outside.
2.1.3
Electrical metallic tubing (EMT): to CSA C22.2 No. 83, with couplings or expanded
ends as indicated.
2.1.4
Rigid pvc conduit: to CSA C22.2 No. 211.2.
2.1.5
Flexible metal conduit: to CSA C22.2 No. 56.
2.1.6
Flexible pvc conduit: to CAN/CSA-C22.2 No. 227.3.
Conduit Fastenings
2.2.1
One hole malleable iron or steel straps to secure surface conduits NPS 2 and smaller.
Two hole steel straps for conduits larger than NPS 2 (50 mm).
2.2.2
Beam clamps to secure conduits to exposed steel work.
2.2.3
Channel type supports for two or more conduits at spacing indicated.
2.2.4
Threaded rods, 6 mm dia., to support suspended channels.
Conduit Fittings
2.3.1
Fittings: manufactured for use with conduit specified. Coating: same as conduit.
2.3.2
Factory "ells" where 90° bends are required for NPS 1 (25 mm) and larger conduits.
2.3.3
Watertight connectors and couplings for EMT. Set-screws are not acceptable.
January 2004
DIVISION 16
2.4
2.5
3
Conduits, Conduit Fastening and Conduit Fittings Section 16133
Page 2
Expansion Fittings for Rigid Conduit
2.4.1
Weatherproof expansion fittings with internal bonding assembly suitable for linear
expansion.
2.4.2
Watertight expansion fittings with integral bonding jumper suitable for linear
expansion and 19 mm deflection in all directions.
2.4.3
Weatherproof expansion fittings for linear expansion at entry to pane.
Fish Cord: Polypropylene.
EXECUTION
3.1
Installation
3.1.1
Install conduits to conserve headroom in exposed locations and cause minimum
interference in spaces through which they pass.
3.1.2
Use EMT (Electrical Mechanical Tubing) conduit except where specified otherwise.
3.1.3
Use epoxy coated or rigid pvc conduit underground or in corrosive areas.
3.1.4
Use electrical metallic tubing (EMT) above 2.4 m not subject to mechanical injury.
3.1.5
Use flexible metal conduit for connection to motors in dry areas, connection to
recessed incandescent fixtures without a prewired outlet box, connection to surface
or recessed fluorescent fixtures and work in movable metal partitions.
3.1.6
Use liquid tight flexible metal conduit for connection to motors or vibrating
equipment in damp, wet or corrosive locations.
3.1.7
Use explosion proof flexible connection for connection to explosion proof motors.
3.1.8
Install conduit sealing fittings in hazardous areas. Fill with compound.
3.1.9
Minimum conduit size for lighting and power circuits: NPS 3/4 (19 mm).
3.1.10 Bend conduit cold. Replace conduit if kinked or flattened more than 1/10th of its
original diameter.
3.1.11 Mechanically bend steel conduit over 19 mm dia.
3.1.12 Field threads on rigid conduit must be of sufficient length to draw conduits up tight.
January 2004
DIVISION 16
Conduits, Conduit Fastening and Conduit Fittings Section 16133
Page 3
3.1.13 Install fish cord in empty conduits.
3.1.14 Run 2-NPS 1 spare conduits up to ceiling space and 2-NPS 1 spare conduits down to
ceiling space from each flush panel. Terminate these conduits in [152 x 152 x 102
mm] junction boxes in ceiling space or in case of an exposed concrete slab,
terminate each conduit in flush concrete or surface type box.
3.1.15 Remove and replace blocked conduit sections. Do not use liquids to clean out
conduits.
3.1.16 Dry conduits out before installing wire
3.2
3.3
3.4
Surface Conduits
3.2.1
Run parallel or perpendicular to building lines.
3.2.2
Locate conduits behind infrared or gas fired heaters with 1.5 m clearance.
3.2.3
Run conduits in flanged portion of structural steel.
3.2.4
Group conduits wherever possible on suspended or surface channels.
3.2.5
Do not pass conduits through structural members except as indicated.
3.2.6
Do not locate conduits less than 75 mm parallel to steam or hot water lines with
minimum of 25 mm at crossovers.
Concealed Conduits
3.3.1
Run parallel or perpendicular to building lines.
3.3.2
Do not install horizontal runs in masonry walls.
3.3.3
Do not install conduits in terrazzo or concrete toppings.
Conduits in Cast-in-place Concrete
3.4.1
Locate to suit reinforcing steel. Install in centre one third of slab.
3.4.2
Protect conduits from damage where they stub out of concrete.
3.4.3
Install sleeves where conduits pass through slab or wall.
3.4.4
Provide oversized sleeve for conduits passing through waterproof membrane, before
membrane is installed. Use cold mastic between sleeve and conduit.
January 2004
DIVISION 16
3.5
Conduits, Conduit Fastening and Conduit Fittings Section 16133
Page 4
3.4.5
Do not place conduits is slabs in which slab thickness is less than 4 times conduit
diameter.
3.4.6
Encase conduits completely in concrete with minimum 25 mm concrete cover.
3.4.7
Organize conduits in slab to minimize cross-overs.
Conduits in Cast-in-place Slabs on Grade
3.5.1
3.6
Run conduits NPS 1 and larger below slab and encased in 75 mm concrete envelope.
Provide 50 mm of sand over concrete envelope below floor slab.
Conduits Underground
3.6.1
Slope conduits to provide drainage.
3.6.2
Waterproof joints (pvc excepted) with heavy coat of bituminous paint.
END OF SECTION 16133